ATTACHMENT J Drawings~26.pdf

PDF 11 MB Posted

Attached to
ITB 25-0022 Stage Improvements
Solicitation number
S-P34048-00016221
Issued by
Washington County, Barlow City, Oregon

About this file

This is a Bid/Permit document package for theatrical stage upgrades at two Beaverton School District middle schools (Meadow Park MS and Mountain View MS) in Beaverton, Oregon. The project encompasses replacement of theatrical controls, audio-visual devices, and production lighting systems to make teaching and production spaces equivalent to other recently remodeled BSD high schools. The scope includes providing power to replacement lighting, controls, and AV devices, with all new lighting specified as LED fixtures. The project involves comprehensive electrical, theatrical lighting, audio-visual, and rigging system upgrades, with detailed drawings and specifications provided for all systems including production relay panels, equipment racks, control systems, and related infrastructure. The document package includes architectural floor plans, electrical single-line diagrams, luminaire schedules, AV panel schedules, assistive listening system specifications, and production rigging plans dated February 21, 2025 for bid purposes.

The project requires coordination among multiple consulting firms including Opsis Architecture (architect), Interface Engineering (theatrical electrical and theatrical systems), DCI Structural, DCW Cost Management, and The Shalleck Collaborative for production systems design. All new electrical work must comply with 2021 Oregon Energy Efficiency Specialty Code, 2021 Oregon Electrical Specialty Code, 2022 Oregon Structural Specialty Code, 2021 International Fire Code, and local City of Beaverton requirements. An allowance of $50,000 is included to cover potential costs for upgrading the electrical distribution system pending 30-day metering efforts per NEC 220.87. Existing electrical loads will be metered over 30 days with a 25-percent safety factor applied to confirm acceptable loads at panels. The project includes assistive listening system requirements with calculations based on seating capacity (10 receivers minimum, 3 hearing-aid compatible units for Meadow Park's 240-seat cafetorium).

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BSD Meadow Park MS Stage Upgrades

BID / PERMIT

Beaverton School District 14100 SW Downing St, Beaverton OR 97006

02/21/2025

GENERAL

C COVER SHEET

GENERAL

A1.11 FLOOR PLAN LEVEL 01

ELECTRICAL

E0.01 SYMBOL LIST AND GENERAL NOTES – ELECTRICAL

E0.02 LUMINAIRE SCHEDULE – ELECTRICAL

E3.01 FLOOR PLAN LEVEL 01 – ELECTRICAL

E4.01 ENLARGED PLANS – ELECTRICAL

E4.02 ENLARGED PLANS – ELECTRICAL

E5.01 SINGLE LINE DIAGRAMS – ELECTRICAL

E6.01 SCHEDULES – ELECTRICAL

E7.01 DETAILS – ELECTRICAL

ED4.01 ENLARGED DEMO PLANS – ELECTRICAL

THEATRICAL PRODUCTION LIGHTING

PL0.01 PRODUCTION LIGHTING DEMOLITION PLAN

PL1.01 PRODUCTION LIGHTING DEVISE PLAN

PL3.01 PRODUCTION LIGHTING SINGLE-LINE AND SCHEDULE

PL4.01 PRODUCTION LIGHTING DETAILS

PL4.02 PRODUCTION LIGHTING MOUNTING DETAILS

THEATRICAL AUDIO-VISUAL

AV0.10 AV PANEL SCHEDULE, ALS, SCOPE INFO

AV0.20 AV WIRETYPE SCHEDILE & CABLE CONDUIT GUIDE

AV0.30 AV STANDARD DETAILS

AV0.50 AV DEMO PLAN

AV1.10 AV DEVICE PLAN & RCP LEVEL 01

AV2.10 AV PANEL EQPT PLAN, RCP, SECTIONS, ELEVATION

AV6.10 AV BLOCK DIAGRAMS

AV7.10 AV PANEL ELEVATIONS & CONDUIT DIAGRAM

AV8.10 AV MOUNTING DETAILS

AV8.20 AV MOUNTING DETAILS

THEATRICAL RIGGING

PR1.01 PRODUCTION RIGGING PLANS

AUDIENCE AND PROCINIUM STAGE

SHEET INDEX

VICINITY MAP Contact: Michael Lamberty Contact: Randall Heeb Contact: Eric Stoeser Contact: Jill Collins Contact: Chris Roybal Contact: Shirley Chalupa

503.356.4587 503.943.6226 206.489.2643 503.305.3240 503.382.2722 503.242.2448 Beaverton, OR, 97006 Portland, Oregon 97214 Portland, OR 97209 Portland, OR Portland, Oregon 97204 Portland, Oregon 97205 1260 NW Waterhouse Avenue 975 SE Main Street 220 NW 8th Ave. Disperse 100 SW Main St., 1600 921 SW Washington St., 560 Beaverton School District Opsis Architecture DCW Cost Management The Shalleck Collaborative, Inc. Interface Engineering, Inc. DCI Structural

OWNER ARCHITECT COST ESTIMATE THEATRICAL ELECTRICAL STRUCTURAL

THEATRICAL

REPLACE THEATRICAL CONTROLS, AUDIO-VISUAL DEVICES AND PRODUCTIONS LIGHTING. MAKE

TEACHING AND PRODUCTIONS SPACES EQUIVALENT TO OTHER BSD HIGH SCHOOLS THAT WERE

RECENTLY REMODELED.

ELECTRICAL

PROVIDE POWER TO REPLACEMENT LIGHTING, CONTROLS AND AV DEVICES. ALL NEW LIGHTING TO

BE LED FIXTURES.

OBSERVE METERING TO CONFIRM ACCEPTABLE LOADS AT PANELS.

THEATER UPGRADES

PROJECT SCOPE:

SECTION 303.1.3:

ASSEMBLY SPACES IN A GROUP E BUILDING ARE NOT INTENDED TO BE

REGULATED AS SEPARATE GROUP A OCCUPANCIES, REGARDLESS OF

THEIR FLOOR AREA, BUT RATHER AN EXTENSION OF THE GROUP E

CLASSIFICATION.

GROUP E EDUCATIONAL OCCUPANCY FOR STUDENTS

OCCUPANCY CLASSIFICATION (Section 303 & 304)

CHAPTER 3: USE AND OCCUPANCY CLASSIFICATION

ACCOUNT R27116

TAX LOT: 1S104BC00100

OSSC CHAPTER 11: NOT APPLICABLE TO PROPOSED SCOPE

NFPA 101 (NOTE: LOCAL CODE WILL TAKE PRECEDENCE. DEVIATIONS

FROM NFPA IN INDIVIDUAL SECTIONS.)

2021 OREGON ENERGY EFFICIENCY SPECIALTY CODE

2021 OREGON PLUMBING SPECIALTY CODE

2021 OREGON ELECTRICAL SPECIALTY CODE

2022 MECHANICAL SPECIALTY CODE

2021 INTERNATIONAL FIRE CODE

APPLICABLE CODE: 2022 OREGON STRUCTURAL SPECIALTY CODE

JURISDICTION: CITY OF BEAVERTON

BEAVERTON, OR 97006

14100 SW DOWNING STREET

PROJECT ADDRESS: MEADOW PARK MIDDLE SCHOOL

CHAPTER 1: ADMINISTRATION

CODE ANALYSIS

GRAPHIC SCALE

(IN FEET)

STOR12

B O Y S

LO

C K E R

G

IR

LS

LO

C K E R

STOR16

STOR18

BOYS1GIRLS1

CORRIDOR2

A

H A

LL

C E N T R A L

MAIN ENTRANCE

CAFETERIA

STAFF

KITCHEN

A

H A

LL

S O U T H

A-17

BOILER

MAIN GYM

WEST GYM

C-13B

OFF5OFF4

STOR8 STOR9

OFF3

STOR10

STOR15

S T O R

CUST OFF

CORRIDOR1

PRIN

HEALTH

RR1

FILE

WORK

ROOM

A-10

VP1

VP2

OFF1

MAIN

OFFICE

RR3

RR4

CONF

OFF2

STOR1 STOR9 M

E C H

UPPER

GYM

STOR2 STOR3

STOR7

STOR8

A-19

A-2

A-4

A-6

S

TO

R

S

TO

R

A-8

A

H A

LL

N O R

TH

A-1

A-3

A-5

A-7

A-9

B-1

B-3

B-5

B-7

B-9

B-2

B-4

B-6

B-8

S

TO

R

4 STOR3

C-1

C-3

C-5

C-7A

C

R E S O U R C E

C

H A

LL

N O R

TH

C-2

C-4

C-6

C-8

S

TO

R

S

TO

R

B

H A

LL

N O R

TH

A-15

A-13

A-11

COUNS1COUNS2

B-14

B-12

B-10

B

H A

LL

C E N

TR

A L

LIBRARY

LIB

OFF

STU

STORE

AV

PRODTVSTAFF

LIB

CUST2

MEN1

C-10

C-12

C

H A

LL

C E N

TR

A L

C-9

C-11

MECH3

GIRLS2BOYS2

WOMEN1

GIRLS3BOYS3

MECH2

BOYS4GILRS4

C-13

C-13A

STOR14

STOR11

CUST3

MECH1

ISS

RR5

QUIET

ROOMS

STOR4 STOR5 STOR6

STOR13

CUST1

STOR7

R O O M

SCI

STOR

PROD

STOR

ELEC

RR

QUIET

RM

STOR

STOR19

FLOOR PLANS SHEET NOTES

1.

2.

3.

4.

5.

6.

7.

REFERENCE SHEET AX.XX FOR MOUNTING HEIGHTS AND GENERAL

INFORMATION

REFERENCE LIGHTING / ELECTRICAL FOR LIGHTING TYPES. NOT ALL

LIGHTING IS SHOWN ON THE ARCHITECTURAL PLAN

REFERENCE EXTERIOR ELEVATIONS FOR EXTERIOR MATERIALS

ALL OUTSIDE INTERIOR CORNERS WITHOUT FRL WALL COVERING TO HAVE

4' HIGH S.S. CORNER GUARDS

ALL FURNITURE SHOWN FOR REFERENCE ONLY - OFOI.

PROVIDE BLOCKING AS REQUIRED FOR ALL LOCATIONS TO RECEIVE FRP

PANEL FINISH

PROVIDE BLOCKING AT LOCATIONS TO RECEIVE NEW TOILET

ACCESSORIES

A

B

SCOPE OF WORK

Sheet Title

Project Name:

Project Adress:

Project Owner:

Opsis Architecture LLP 920 NW Avenue, Portland, OR 97209

503.525.9511 | info@opsisarch.com opsisarch.com

Sheet No.

Job No.

Key Plan

Status:

Date:

Revisions to Sheet

No. Date plo tte d:

THESE DRAWINGS ARE THE PROPERTY OF OPSIS ARCHITECTURE

LLP AND ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER,

WITHOUT PRIOR WRITTEN PERMISSION.

sh ee t s ize

" x

Revision

2/

/2

5:

:4

PM

FLOOR PLAN

LEVEL 01

BSD Meadow Park MS Stage Upgrades

14100 SW Downing St, Beaverton OR 97006

A1.11 4921-01

02/21/2025

BID / PERMIT

Beaverton School District copyright 2025

N

1/16" = 1'-0"A1.11 1 Level 01

Sheet Title

Project Name:

Project Adress:

Project Owner:

Opsis Architecture LLP 920 NW Avenue, Portland, OR 97209

503.525.9511 | info@opsisarch.com opsisarch.com

Sheet No.

Job No.

Key Plan

Status:

Date:

Revisions to Sheet

No. Date pl ot te d:

THESE DRAWINGS ARE THE PROPERTY OF OPSIS ARCHITECTURE

LLP AND ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER,

WITHOUT PRIOR WRITTEN PERMISSION.

sh ee t s iz e:

x

Revision

EXPIRES: 06/30/26

/2

/2

:0 :1

A

M

SYMBOL LIST

AND GENERAL

NOTES -

ELECTRICAL

BSD Meadow Park MS Stage Upgrades

14100 SW Downing St, Beaverton OR 97006

E0.01

4921-01

2025-02-21

100% CONSTRUCTION

DOCUMENTS

BSD

E0.01 SYMBOL LIST AND GENERAL NOTES - ELECTRICAL

E0.02 LUMINAIRE SCHEDULE - ELECTRICAL

ED4.01 ENLARGED DEMO PLANS - ELECTRICAL

E3.01 FLOOR PLAN LEVEL 01 - ELECTRICAL

E4.01 ENLARGED PLANS - ELECTRICAL

E4.02 ENLARGED PLANS - ELECTRICAL

E5.01 SINGLE LINE DIAGRAMS - ELECTRICAL

E6.01 SCHEDULES - ELECTRICAL

E7.01 DETAILS - ELECTRICAL

SHEET INDEX

Abbreviations

AFC ABOVE FINISHED CEILING

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

ARF ABOVE RAISED FLOOR

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

AWG AMERICAN WIRE GAUGE

A AMPERES, AMBER

AV AUDIO VISUAL

AHJ AUTHORITY HAVING JURISDICTION

AIC AVAILABLE INTERRUPTING CAPACITY

BAS BUILDING AUTOMATION SYSTEM

CA CABLE

CAT CATEGORY

CLG CEILING

CB CIRCUIT BREAKER

C CONDUIT, CLOSE, CONTROL

CFCI CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CFOI CONTRACTOR FURNISHED OWNER INSTALLED

COORD COORDINATE

CU COPPER

dB DECIBEL

(X) DEMOLISH

DTL DETAIL

DIA DIAMETER

DIM DIMENSION

DIV DIVISION

DN DOWN

DWG DRAWING

EA EACH

EMT ELECTRICAL METALLIC TUBING

ENT ELECTRICAL NON-METALLIC TUBING

ESD ELECTROSTATIC DISCHARGE

EL ELEVATION

E EMERGENCY

EF EXHAUST FAN

(E) EXISTING

FMS FACILITY MANAGEMENT SYSTEMS

FF FINISH FLOOR

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FMC FLEXIBLE METAL CONDUIT

FT FOOT, FEET

FBO FURNISHED BY OTHERS

G, GND GROUND

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GFI GROUND FAULT INTERRUPTER

GFP GROUND FAULT PROTECTION

GE GROUNDING EQUALIZER

HH HANDHOLE

HT HEIGHT

HC HORIZONTAL CROSS CONNECT

ID IDENTIFICATION

IN INCH, INCHES

IEEE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS

IMC INTERMEDIATE METAL CONDUIT

IG ISOLATED GROUND

KV KILOVOLT

KVA KILOVOLT AMPERES

KW KILOWATT

LED LIGHT EMITTING DIODE

LNC LIQUID TIGHT FLEXIBLE NONMETALLIC CONDUIT

LFMC LIQUIDTIGHT FLEXIBLE METAL CONDUIT

LV LOW VOLTAGE

MOCP MAXIMUM OVERCURRENT PROTECTION

MHz MEGAHERTZ mA MILLIAMPERES

MIN MINIMUM

MCA MINIMUM CIRCUIT AMPS

MISC MISCELLANEOUS

M MOTOR

MCC MOTOR CONTROL CENTER

MT, MTD MOUNT, MOUNTED

MDU MULTI-DWELLING UNIT

NEC NATIONAL ELECTRIC CODE

NESC NATIONAL ELECTRIC SAFETY CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

N NEUTRAL

(N) NEW

NC NORMALLY CLOSED

NO NORMALLY OPEN

N/A NOT APPLICABLE

N.I.C. NOT IN CONTRACT

NTS NOT TO SCALE

OC ON CENTER

OSP OUTSIDE PLANT

OFCI OWNER FURNISHED, CONTRACTOR INSTALLED

OFOI OWNER FURNISHED, OWNER INSTALLED

PNL PANEL

PH PHASE

PVC POLY-VINYL-CHLORIDE

PWR POWER

QTY QUANTITY

REF REFERENCE

(R) RELOCATE

RFI REQUEST FOR INFORMATION

REQD REQUIRED

RMC RIGID METAL CONDUIT

RM ROOM

SHT SHEET

SIM SIMILAR

SPKR SPEAKER

STD STANDARD

SPD SURGE PROTECTION DEVICE

SWBD SWITCHBOARD

TBB TELECOMMUNICATIONS BONDING BACKBONE

TGB TELECOMMUNICATIONS GROUNDING BUS BAR

TTB TELEPHONE TERMINAL BOARD

TBD TO BE DETERMINED

XFMR TRANSFORMER

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR

TP TRANSITION POINT

TYP TYPICAL

UG UNDERGROUND

UL UNDERWRITERS LABORATORIES

UPS UNINTERRUPTIBLE POWER SUPPLY

UON UNLESS OTHERWISE NOTED

VFD VARIABLE FREQUENCY DRIVE

VRFY VERIFY

V VOLTS, VOLTAGE

WP WEATHERPROOF

WG WIRE GUARD

W WIRE, WHITE

W/ WITH

W/O WITHOUT

WAO WORK AREA OUTLET

Connections / Equipment

COMBINATION ADJUSTABLE FREQUENCY DRIVE WITH SAFETY

DISCONNECT SWITCH. FURNISHED BY DIVISION 23 AND INSTALLED

BY DIVISION 26.

COMBINATION MOTOR STARTER/FUSED DISCONNECT SWITCH

CONTACTOR COIL

HEAVY DUTY FUSED DISCONNECT SWITCH

MOTOR CONNECTION

NON-FUSED DISCONNECT SWITCH

RELAY

REMOTE DRIVER FOR LED LUMINAIRES

TRANSFORMER

FIRE SMOKE DAMPER

SMOKE DAMPER

CEILING MOUNTED JUNCTION BOX

FLOOR MOUNTED JUNCTION BOX

WALL-MOUNTED JUNCTION BOX

MAGNETIC DOOR HOLDER

Fire Alarm

FIRE ALARM CONTROL PANEL

NOTIFICATION APPLIANCE CIRCUIT PANEL

FIRE ALARM ANNUNCIATOR PANEL

General

DETAIL NUMBER AND SHEET LOCATION

EQUIPMENT IDENTIFICATION

FOOD SERVICE EQUIPMENT / CALCULATION TAG

KEYED NOTE

POINT OF CONNECTION

SECTION NUMBER AND SHEET LOCATION

DEMOLISH

EXISTING WORK

NEW WORK

Lighting

LUMINAIRE RECESSED IN WALL

LUMINAIRE RECESSED IN WALL CONNECTED TO EMERGENCY/LIFE

SAFETY CIRCUIT

SURFACE MOUNTED LUMINAIRE CONNECTED TO EMERGENCY/LIFE

SAFETY CIRCUIT

SURFACE OR PENDANT MOUNTED STRIPLIGHT

WALL MOUNTED 6" WIDE LUMINAIRE

WALL MOUNTED 6" WIDE LUMINAIRE CONNECTED TO

EMERGENCY/LIFE SAFETY CIRCUIT

WALL MOUNTED LUMINAIRE

WALL MOUNTED LUMINAIRE CONNECTED TO EMERGENCY/LIFE

SAFETY CIRCUIT

Miscellaneous

BRANCH CIRCUIT WIRING. ARROW INDICATES HOME RUN TO

PANEL WITH CIRCUITS AS NOTED. WIRE SIZE IS #12 AWG MINIMUM

UNLESS NOTED OTHERWISE. SHORT TICK MARKS INDICATE PHASE

CONDUCTORS. LONG TICK MARKS INDICATE NEUTRAL

CONDUCTORS. A SINGLE CURVED TICK MARK INDICATES

INSULATED GREEN GROUND CONDUCTOR. SECOND CURVED TICK

MARK INDICATES "ISOLATED GROUND" (GREEN INSULATION WITH

YELLOW STRIPE) CONDUCTOR.

BRANCH PANEL

CIRCUIT BREAKER

DRY TYPE TRANSFORMER

FLUSH MOUNT EQUIPMENT ENCLOSURE AS NOTED

FLUSH WALL MOUNTED BRANCH PANEL

GROUND BAR

GROUNDING POINT

MAIN DISTRIBUTION PANEL / SUB DISTRIBUTION PANEL

POWER UTILITY POLE

SUBGRADE VAULT CATV

SUBGRADE VAULT POWER

SUBGRADE VAULT TELEPHONE

SURFACE MOUNT EQUIPMENT ENCLOSURE AS NOTED

TELEPHONE UTILITY POLE

UTILITY TRANSFORMER PAD/VAULT

Raceways

EXISTING CONDUIT CONCEALED IN WALL OR CEILING SPACE

ELECTRICAL SYMBOL LIST

NOTE: This is a standard symbol list and not all items listed may be used.

EXISTING CONDUIT ROUTED BELOW FLOOR / GRADE

OVERHEAD PRIMARY SERVICE

OVERHEAD TELEPHONE SERVICE

UNDERGROUND CABLE TELEVISION SERVICE

UNDERGROUND PRIMARY SERVICE

UNDERGROUND SECONDARY SERVICE

UNDERGROUND TELEPHONE SERVICE

CONDUIT CONCEALED IN WALL OR CEILING SPACE

CONDUIT ROUTED BELOW FLOOR / GRADE

CONDUIT ELLED DOWN

CONDUIT ELLED UP

CONDUIT/WIRING CONTINUATION

CONDUIT/WIRING STUBBED OUT WITH END CAP OR INSULATED

PLASTIC BUSHING

FLEXIBLE CONDUIT

Switches and Receptacles

COMBINATION COMMUNICATIONS OUTLET AND DOUBLE DUPLEX

RECEPTACLE, FLUSH FLOOR

COMBINATION COMMUNICATIONS OUTLET AND DUPLEX

RECEPTACLE, FLUSH FLOOR

DUPLEX RECEPTACLE (MULTIPLE LETTERS INDICATE MULTIPLE

OPTIONS)

A = ABOVE COUNTER

B = CLOCK HANGER

C = FLUSH CEILING MOUNTED

E = EMERGENCY

F = ARC FAULT PROTECTED BY BREAKER IN PANEL

G = GROUND FAULT CIRCUIT INTERRUPTER

H = HOSPITAL GRADE

K = CHILD RESISTANT COVER

L = ISOLATED GROUND

P = PENDANT MOUNTED WITH CORD GRIPS. VERIFY PENDANT

LENGTH

R1 = HALF SWITCHED BY OCCUPANCY SENSOR RELAY

R2 = FULLY SWITCHED BY OCCUPANCY SENSOR RELAY

S = SPLIT WIRED

T = TAMPER RESISTANT SHUTTERED RECEPTACLE

U = USB PORT(S)

W = WEATHERPROOF CONTINUOUS USE COVER, GFCI PROTECTED,

WITH WEATHER-RESISTANT RECEPTACLE

DUPLEX RECEPTACLE, FLUSH FLOOR

DOUBLE DUPLEX RECEPTACLE, FLUSH FLOOR

DOUBLE DUPLEX RECEPTACLE. SEE LETTER CODE LIST AT DUPLEX

RECEPTACLE FOR OPTIONS

SINGLE RECEPTACLE, FLUSH FLOOR

SINGLE RECEPTACLE. SEE LETTER CODE LIST AT DUPLEX

RECEPTACLE FOR OPTIONS

EQUIPMENT ELECTRICAL CONNECTION

SPECIAL PURPOSE RECEPTACLE. LETTER CODE DENOTES

RECEPTACLE CONFIGURATION

LX-XXR = NEMA CONFIGURATION TWIST-LOCK RECEPTACLE

X-XXR = NEMA CONFIGURATION STRAIGHT BLADE RECEPTACLE

P = PENDANT MOUNT WITH CORD GRIPS. VERIFY PENDANT LENGTH

X = COORDINATE RECEPTACLE CONFIGURATION WITH EQUIPMENT

BEING SUPPLIED

PENDANT RECEPTACLE WITH CORD GRIPS. VERIFY PENDANT

LENGTH. SEE LETTER CODE LIST AT DUPLEX RECEPTACLE FOR

OPTIONS

CEILING MOUNTED OCCUPANCY SENSOR

P = PASSIVE INFRARED

D = DUAL TECHNOLOGY

U = ULTRASONIC, 360 DEG RANGE

H = ULTRASONIC, HALLWAY PATTERN

v (LOWERCASE) = VACANCY CONTROL DESIGNATION

WALL MOUNTED OCCUPANCY SENSOR

P = PASSIVE INFRARED

D = DUAL TECHNOLOGY

v (LOWERCASE) = VACANCY CONTROL DESIGNATION

WALL MOUNTED OCCUPANCY SENSOR/SWITCH

S = PASSIVE INFRARED WITH INTEGRAL "OFF" SWITCH

T = DUAL RELAY PASSIVE INFRARED WITH TWO INTEGRAL "OFF"

SWITCHES

D = PASSIVE INFRARED WITH INTEGRAL DIMMER TO OFF.

v (LOWERCASE) = VACANCY CONTROL DESIGNATION

MULTIPLE CHANNEL SURFACE METAL RECEPTACLE RACEWAY

WITH LOW VOLTAGE DIVIDERS, LENGTH AND RECEPTACLES AS

INDICATED

SURFACE METAL RECEPTACLE RACEWAY

PHOTO ELECTRIC SWITCH

D = CONTINUOUS DIMMING PHOTOCELL

S = SWITCHED PHOTOCELL

SINGLE POLE SWITCH

2 = DOUBLE POLE SWITCH

3 = THREE-WAY SWITCH

4 = FOUR-WAY SWITCH

a THRU z (LOWERCASE) = LUMINAIRE CONTROL DESIGNATION

D = DIMMER

F = FAN SPEED CONTROL

K = KEY OPERATED SWITCH

L = LIGHTED HANDLE

M = MANUAL MOTOR STARTER WITH THERMAL OVERLOAD

P = SWITCH WITH PILOT LIGHT

S = SENTRY SWITCH

T = INTERVAL TIMER

W = WEATHERPROOF SWITCH

V = LOW VOLTAGE SWITCH

PROJECT

CONTACT

www.interfaceengineering.com

Chris Roybal 2024-0306

100 SW Main Street, Suite 1600 Portland, OR 97204

TEL 503.382.2266

GENERAL ELECTRICAL

DEMOLITION NOTES

A. THE CONTRACTOR SHALL SEAL ALL UNUSED OPENINGS DUE TO ELECTRICAL DEMOLITION TO ENSURE

THAT FIRE-RESISTANCE IS MAINTAINED.

B. REFER TO SPECIFICATION SECTION 260000 FOR ADDITIONAL DEMOLITION AND EXISTING CONDITIONS

REQUIREMENTS.

C. ALLOW FOR TEMPORARY BASE BUILDING LIGHTS AS REQUIRED FOR PHASING AND/OR MEETING THE

CONSTRUCTION SCHEDULE.

D. DEVICES, CONDUIT, AND CONDUCTORS WITHIN WALLS SHOWN AS DEMOLISHED SHOULD BE REMOVED

BACK TO SOURCE UNLESS NOTED OTHERWISE.

GENERAL ELECTRICAL NOTES

A. IN FINISHED INTERIOR AREAS, ALL CONDUITS TO BE CONCEALED, UNLESS OTHERWISE NOTED.

SURFACE CONDUIT OR RACEWAY IS NOT PERMISSIBLE.

B. CONSULT ALL DRAWINGS AND SPECIFICATIONS IN THIS PROJECT AND BECOME FAMILIAR WITH ALL

EQUIPMENT TO BE INSTALLED. COORDINATE ALL ASPECTS OF THE CONSTRUCTION WITH OTHER

TRADES ON THE JOB TO ENSURE THAT ALL WORK AND MATERIALS REQUIRED TO PROVIDE A

COMPLETE AND OPERATIONAL FACILITY ARE INCLUDED IN BID.

C. EXISTING CONDITIONS ARE BASED ON AVAILABLE RECORD DRAWINGS AND FIELD OBSERVATIONS.

VERIFY LOCATIONS/CONDITIONS PRIOR TO CONSTRUCTION.

GENERAL LIGHTING NOTES

A. NO WIRE SMALLER THAN NO. 12 AWG SHALL BE USED FOR BRANCH CIRCUIT WIRING.

B. ALL LIGHTING SWITCHES, DIMMERS, AND MOTION SENSORS TO CONTROL LIGHTING IN THE ROOM THEY

ARE LOCATED IN UNLESS OTHERWISE NOTED.

C. ALL MOTION SENSORS TO BE MOUNTED AT LEAST 4' AWAY FROM ANY MECHANICAL DIFFUSERS.

D. IN FINISHED INTERIOR AREAS, ALL CONDUITS TO BE CONCEALED, UNLESS OTHERWISE NOTED.

SURFACE CONDUIT OR RACEWAY IS NOT PERMISSIBLE.

2/21/25

UL/IP DRIVER/

RATING POWER SUPPLY LIGHT SOURCE MFG/CATALOG # NOTES

A1 SURFACE MOUNTED LED

STRIPLIGHT; GENERAL

DISTRIBUTION; NOMINAL 3.5IN

WIDE x 3.5IN TALL x 48IN LONG

COLD ROLLED STEEL ROUND FROSTED

ACRYLIC

SURFACE MOUNTED WHITE UL DAMP INTEGRAL DRIVER;

0-10V DIMMING TO 1%

NOMINAL 10000 LUMENS; 3000K

LED; 80CRI

70.7 LITHONIA CLX SERIES;

OR APPROVED

A2 WALL MOUNTED LED

STRIPLIGHT; GENERAL

DISTRIBUTION; NOMINAL 3.5IN

WIDE x 3.5IN TALL x 48IN LONG

COLD ROLLED STEEL ROUND FROSTED

ACRYLIC

WALL MOUNTED WHITE UL DAMP INTEGRAL DRIVER;

0-10V DIMMING TO 1%

NOMINAL 10000 LUMENS; 3000K

LED; 80CRI

70.7 LITHONIA CLX SERIES;

OR APPROVED

B1 WALL MOUNTED LED SCONCE;

DIRECT AND INDIRECT

DISTRIBUTION; NOMINAL 5IN

WIDE x 5IN TALL x 4IN DEEP

FORMED ALUMINUM FROSTED ACRYLIC WALL MOUNTED AS SELECTED BY

ARCHITECT

UL DAMP INTEGRAL DRIVER;

0-10V DIMMING TO 1%

NOMINAL 1550 LUMENS; 3000K

LED; 80CRI

19 VISA NAYA SERIES;

OR APPROVED

C1 RECESSED IN-WALL LED

STEPLIGHT; NOMINAL 15IN

WIDE x 5.5IN TALL x 2.125IN

DEEP

DIE CAST ALUMINUM FROSTED ACRYLIC LENS WALL MOUNTED AS SELECTED BY

ARCHITECT

UL WET INTEGRAL DRIVER;

0-10V DIMMING TO 5%

NOMINAL 386 LUMENS; 3000K

LED; 80CRI

11 HYDREL HSL13 SERIES;

OR APPROVED

LUMINAIRE SCHEDULE

TYPE DESCRIPTION HOUSING SHIELDING MOUNTING FINISH

INPUT

WATTS

NOTES:

THIS LUMINAIRE SCHEDULE IS NOT COMPLETE WITHOUT A COPY OF THE PROJECT MANUAL CONTAINING THE ELECTRICAL SPECIFICATIONS.

DIMMING CONTROL PROTOCOL (0-10VDC, LINE VOLTAGE, DALI, ETC.) COMPATIBLE WITH LIGHTING CONTROL SYSTEM AS SPECIFIED AND SHOWN ON DRAWINGS.

PROVIDE +/- 12 INCH ADJUSTABILITY IN AIRCRAFT CABLE LENGTH WHERE USED.

COORDINATE ALL CEILING TYPES WITH LUMINAIRE LOCATIONS PRIOR TO ORDERING LUMINAIRES. COORDINATE INSTALLATION WITH REFLECTED CEILING PLAN.

SPECIFIED MANUFACTURERS ARE APPROVED TO SUBMIT BID. INCLUSION DOES NOT RELIEVE MANUFACTURER FROM SUPPLYING PRODUCT AS DESCRIBED.

PROVIDE SUBMITTALS THAT INCLUDE THE LUMINAIRE, LAMP AND DIMMABLE LED DRIVER INFORMATION OF EACH LUMINAIRE, WITH APPLICABLE OPTIONS CLEARLY CHECKED OR HIGHLIGHTED. SUBMITTALS NOT INCLUDING THIS INFORMATION WILL BE RETURNED AS REJECTED BY THE ENGINEER OF

RECORD.

PROVIDE FUNCTIONAL TESTING OF LIGHTING AND LIGHTING CONTROLS IN ACCORDANCE WITH THE 2021 OREGON ENERGY EFFICIENCY SPECIALY CODE (OEESC) FUNCTIONAL TESTING REQUIREMENTS

Sheet Title

Project Name:

Project Adress:

Project Owner:

Opsis Architecture LLP 920 NW Avenue, Portland, OR 97209

503.525.9511 | info@opsisarch.com opsisarch.com

Sheet No.

Job No.

Key Plan

Status:

Date:

Revisions to Sheet

No. Date pl ot te d:

THESE DRAWINGS ARE THE PROPERTY OF OPSIS ARCHITECTURE

LLP AND ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER,

WITHOUT PRIOR WRITTEN PERMISSION.

sh ee t s iz e:

x

Revision

EXPIRES: 06/30/26

/2

/2

:0 :1

A

M

LUMINAIRE

SCHEDULE -

ELECTRICAL

BSD Meadow Park MS Stage Upgrades

14100 SW Downing St, Beaverton OR 97006

E0.02

4921-01

2025-02-21

100% CONSTRUCTION

DOCUMENTS

BSD

PROJECT

CONTACT

www.interfaceengineering.com

Chris Roybal 2024-0306

100 SW Main Street, Suite 1600 Portland, OR 97204

TEL 503.382.2266

J

J

J

B

B

(X) PANEL '2E'

(X) PANEL '2CS'

(X) PANEL '2CC'

(X) PANEL 'D'

(E)

(E) (E)

(E)

CAFETERIASTAFF

KITCHEN

STAGE

B

(E) (E) (E) (E)

(E) (E) (E) (E)

(E) (E) (E) (E)

(E) (E) (E) (E)

(E) (E) (E) (E)

(X)

(X)

(X) (X)

(X)

(X) (X)

(X)

(X) (X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)(X)

(E) (E)

(E)

(E)

CAFETERIASTAFF

KITCHEN

STAGE

(X)

(X)

(X)

(X)

(X) (X)

(X)

Sheet Title

Project Name:

Project Adress:

Project Owner:

Opsis Architecture LLP 920 NW Avenue, Portland, OR 97209

503.525.9511 | info@opsisarch.com opsisarch.com

Sheet No.

Job No.

Key Plan

Status:

Date:

Revisions to Sheet

No. Date pl ot te d:

THESE DRAWINGS ARE THE PROPERTY OF OPSIS ARCHITECTURE

LLP AND ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER,

WITHOUT PRIOR WRITTEN PERMISSION.

sh ee t s iz e:

x

Revision

EXPIRES: 06/30/26

/2

/2

:0 :1

A

M

ENLARGED

DEMO PLANS -

ELECTRICAL

BSD Meadow Park MS Stage Upgrades

14100 SW Downing St, Beaverton OR 97006

ED4.01

4921-01

2025-02-21

100% CONSTRUCTION

DOCUMENTS

BSD

PROJECT

CONTACT

www.interfaceengineering.com

Chris Roybal 2024-0306

100 SW Main Street, Suite 1600 Portland, OR 97204

TEL 503.382.2266

0' 4' 8' 16'

1/8" = 1'-0"

1 ENLARGED LEVEL 01 STAGE DEMO PLAN - POWER

0' 4' 8' 16'

1/8" = 1'-0"

2 ENLARGED LEVEL 01 STAGE DEMO PLAN - LIGHTING

GENERAL SHEET NOTES

A. DEVICES NOTED WITH (X) ARE TO BE REMOVED ALONG WITH CONDUCTORS BACK

TO SOURCE, UNLESS NOTED OTHERWISE. EXISTING CONDUIT TO REMAIN.

SHEET KEYNOTES

1. REMOVE ALL EXISTING PRODUCTION LIGHTING RECEPTACLES AND HARDWIRED

LIGHT FIXTURES. REMOVE (E) CONDUCTORS BACK TO SOURCE AND KEEP EXISTING

CONDUIT AS MUCH AS PRACTICAL FOR RE-USE. REFER TO 'PL' & 'AV' SERIES

DRAWINGS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

STOR12

B O Y S

L O C K E R

G

IR

L S

L O C K E R

STOR16

STOR18

BOYS1GIRLS1

CORRIDOR2

A

H A L L

C E N T R A L

MAIN ENTRANCE

CAFETERIA

STAFF

KITCHEN

A

H A L L

S O U T H

A-17

BOILER

MAIN GYM

WEST GYM

C-13B

OFF5OFF4

STOR8 STOR9

OFF3

STOR10

STOR15

S T O R

CUST OFF

CORRIDOR1

PRIN

HEALTH

RR1

FILE

WORK

ROOM

A-10

VP1

VP2

OFF1

MAIN

OFFICE

RR3

RR4

CONF

OFF2

STOR1 STOR9

M E C H

A-2

A-4

A-6

S T O R

S T O R

A-8

A

H A L L

N O R T H

A-1

A-3

A-5

A-7

A-9

B-1

B-3

B-5

B-7

B-9

B-2

B-4

B-6

B-8

S T O R

4 STOR3

C-1

C-3

C-5

C-7A

C

R E S O U R C E

C

H A L L

N O R T H

C-2

C-4

C-6

C-8

S T O R

S T O R

B

H A L L

N O R T H

A-15

A-13

A-11

COUNS1COUNS2

B-14

B-12

B-10

B

H A L L

C E N T R A L

LIBRARY

LIB

OFF

STU

STORE

AV

PRODTVSTAFF

LIB

CUST2

MEN1

C-10

C-12

C

H A L L

C E N T R A L

C-9

C-11

MECH3

GIRLS2BOYS2

WOMEN1

GIRLS3BOYS3

MECH2

BOYS4GILRS4

C-13

C-13A

STOR14

STOR11

CUST3

MECH1

ISS

RR5

QUIET

ROOMS

STOR13

CUST1

STOR7

R O O M

SCI

STOR

PROD

STOR

ELEC

RR

QUIET

RM

STOR

STOR19

A

B

B

E4.01

E4.02

PANEL '4E' 1

E4.02

Sheet Title

Project Name:

Project Adress:

Project Owner:

Opsis Architecture LLP 920 NW Avenue, Portland, OR 97209

503.525.9511 | info@opsisarch.com opsisarch.com

Sheet No.

Job No.

Key Plan

Status:

Date:

Revisions to Sheet

No. Date pl ot te d:

THESE DRAWINGS ARE THE PROPERTY OF OPSIS ARCHITECTURE

LLP AND ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER,

WITHOUT PRIOR WRITTEN PERMISSION.

sh ee t s iz e:

x

Revision

EXPIRES: 06/30/26

/2

/2

:0 :1

A

M

FLOOR PLAN

LEVEL 01 -

ELECTRICAL

BSD Meadow Park MS Stage Upgrades

14100 SW Downing St, Beaverton OR 97006

E3.01

4921-01

2025-02-21

100% CONSTRUCTION

DOCUMENTS

BSD

PROJECT

CONTACT

www.interfaceengineering.com

Chris Roybal 2024-0306

100 SW Main Street, Suite 1600 Portland, OR 97204

TEL 503.382.2266

0' 4' 8' 16'

1/16" = 1'-0"

1 LEVEL 01 OVERALL PLAN - ELECTRICAL

SHEET KEYNOTES

1. EXISTING PANEL TO BE REPLACED, SEE SINGLE-LINE

DIAGRAM FOR MORE INFORMATION.

J

J

J

J P

J P

J P

J C

J C

J C

J J

B

B

(E) PANEL '2E'

PANEL '2CS'

PANEL 'PRP' 2

(E)

(E) (E)

(E)

MOTORIZED SCREEN

C

C

C

+50"

CAFETERIASTAFF

KITCHEN

STAGE

2CS-21.

2CS-23.

2CS-22.

2CS-22.

2CS-24.

2CS-26.

2CS-25. 2CS-26. 2CS-26.

2CS-26. 2CS-26.

2CS-26.

2CS-26.

2CS-30.

2CS-28.

2CS-25.

B

'A1'

'A1'

'A1' 'A1'

'A1'

'A1' 'A1'

'A1'

'A1' 'A1'

'A1'

'A1'

'B1'

'B1'

'B1'

'B1'

'B1'

'B1'

'B1'

'B1'

'C1'

'C1'

'C1'

(E) (E) (E) (E)

(E) (E) (E) (E)

(E) (E) (E) (E)

(E) (E) (E) (E)

(E) (E) (E) (E)

'A2''A2'

(E)

(E)

(E)(E)

CAFETERIASTAFF

KITCHEN

STAGE

3D

3D

3D

3D 3D

DDD

4 4

4 4

4 4

Sheet Title

Project Name:

Project Adress:

Project Owner:

Opsis Architecture LLP 920 NW Avenue, Portland, OR 97209

503.525.9511 | info@opsisarch.com opsisarch.com

Sheet No.

Job No.

Key Plan

Status:

Date:

Revisions to Sheet

No. Date pl ot te d:

THESE DRAWINGS ARE THE PROPERTY OF OPSIS ARCHITECTURE

LLP AND ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER,

WITHOUT PRIOR WRITTEN PERMISSION.

sh ee t s iz e:

x

Revision

EXPIRES: 06/30/26

/2

/2

:0 :2

A

M

ENLARGED

PLANS -

ELECTRICAL

BSD Meadow Park MS Stage Upgrades

14100 SW Downing St, Beaverton OR 97006

E4.01

4921-01

2025-02-21

100% CONSTRUCTION

DOCUMENTS

BSD

PROJECT

CONTACT

www.interfaceengineering.com

Chris Roybal 2024-0306

100 SW Main Street, Suite 1600 Portland, OR 97204

TEL 503.382.2266

0' 4' 8' 16'

1/8" = 1'-0"

1 ENLARGED LEVEL 01 STAGE PLAN - POWER

0' 4' 8' 16'

1/8" = 1'-0"

2 ENLARGED LEVEL 01 STAGE PLAN - LIGHTING

GENERAL SHEET NOTES

A. REFER TO 'PL' AND 'AV' SERIES DRAWINGS FOR CONDUIT AND CONDUCTOR SIZES

OF LV AND CONTROL WIRING.

B. FOR EACH 20A, 120V CIRCUIT, PROVIDE 2#10 CU, 1#10 CU GND., IN 3/4" CONDUIT

UNLESS NOTED OTHERWISE.

SHEET KEYNOTES

1. PROVIDE CONNECTION TO PRODUCTION LIGHTING FROM PRODUCTION RELAY

PANELS 'PRP'. REFER TO 'PL' SERIES DRAWINGS FOR CIRCUIT QUANTITY AND

CONTROLS INFORMATION.

2. PROVIDE 200A, 208V, 3PH CONNECTION FOR PRODUCTION LIGHTING RELAY PANEL

'PRP'. REFER TO 'PL' SERIES DRAWINGS FOR MORE INFORMATION.

3. PROVIDE (2) 20A, 120V, CIRCUITS FOR AV EQUIPMENT RACK 'RK-1' . REFER TO 'AV'

SERIES DRAWINGS FOR MORE INFORMATION.

4. CONNECT NEW LUMINAIRES TO CIRCUITS MADE AVAILABLE FROM DEMOLITION AND

TIE INTO EXISTING LIGHTING CONTROLS UNLESS NOTED OTHERWISE.

T

ATST

T

ATST

A

(X) TRANSFORMER 'TR-1'

(X) PANEL 'EM DIST'

(E) TRANSFORMER 'TR-3'

(E) SWITCHBOARD '4MDP'

(E) PANEL '2SDP'

(E) ATS

BOILER

CUST

STORAGE

A

TRANSFORMER 'TR-1'

PANEL 'EM DIST'

(E) PANEL '2SDP'

(E) SWITCHBOARD '4MDP'

(E) TRANSFORMER 'TR-3'

(E) ATS

BOILER

CUST

STORAGE

'TR-1' DISCONNECT

Sheet Title

Project Name:

Project Adress:

Project Owner:

Opsis Architecture LLP 920 NW Avenue, Portland, OR 97209

503.525.9511 | info@opsisarch.com opsisarch.com

Sheet No.

Job No.

Key Plan

Status:

Date:

Revisions to Sheet

No. Date pl ot te d:

THESE DRAWINGS ARE THE PROPERTY OF OPSIS ARCHITECTURE

LLP AND ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER,

WITHOUT PRIOR WRITTEN PERMISSION.

sh ee t s iz e:

x

Revision

EXPIRES: 06/30/26

/2

/2

:0 :2

A

M

ENLARGED

PLANS -

ELECTRICAL

BSD Meadow Park MS Stage Upgrades

14100 SW Downing St, Beaverton OR 97006

E4.02

4921-01

2025-02-21

100% CONSTRUCTION

DOCUMENTS

BSD

PROJECT

CONTACT

www.interfaceengineering.com

Chris Roybal 2024-0306

100 SW Main Street, Suite 1600 Portland, OR 97204

TEL 503.382.2266

0' 4' 8' 12'

3/16" = 1'-0"

1 DEMO ENLARGED LEVEL 01 BOILER ROOM - POWER

0' 4' 8' 12'

3/16" = 1'-0"

2 NEW ENLARGED LEVEL 01 BOILER ROOM - POWER

G

NEUT. BUS

(E) UTILITY

PRIMARY

FULL LENGTH

GROUND BUS

FIRST FLOOR

(E)MAIN DISTRIBUTION SWITCHBOARD (4MDP)

480Y/277 VOLT, 3 PHASE, 4 WIRE AVAILABLE

FAULT CURRENT: -----A

1000 AMP BUS

200A 3P

(E)GENERATOR

480V, 50 KW

(E) METER BASE

(E)CURRENT

TRANSF.

CABINET

M

(E)

(E) (E) (E) (E)

UTILITY

TRANSFORMER

T

(E)

200A 3P

200A 3P

200A 3P

60A 3P

60A 3P

(E)

400A 3P

(E) (E) (E) (E)

600A 3P

100A 3P

400A 3P

(E) ATS

(E) GEN DISCO

(X)PANEL

'EM DIST'

60A

MCB

(E)

(X)

(X)PANEL

'4E'

100A

MLO

(X)PANEL

'2E'

100A

MLO

(X)

(X)

(X)TRANSFORMER: TR-1

10kVA, 480-120/240V

3PH, 4W

(E)PANEL

'2SDP'

400A

MCB

(E)

(E)TRANSFORMER: TR-3

150kVA, 480-120/208V

3PH, 4W

(X)

(X)PANEL

'2CS'

100A

MLO

(X)PANEL

'2CC'

200A

MLO

(X)

(E) (E)

200A 3P

200A 3P

(E) (E)

(X)

(X)PANEL

'D'

200A

MLO

AREA OF WORK

G

NEUT. BUS

(E) UTILITY

PRIMARY

FULL LENGTH

GROUND BUS

FIRST FLOOR

(E)MAIN DISTRIBUTION SWITCHBOARD (4MDP)

480Y/277 VOLT, 3 PHASE, 4 WIRE AVAILABLE

FAULT CURRENT: -----A

1000 AMP BUS

200A 3P

(E)GENERATOR

480V, 50 KW

(E) METER BASE

(E)CURRENT

TRANSF.

CABINET

M

(E)

(E) (E) (E) (E)

UTILITY

TRANSFORMER

T

(E)

200A 3P

200A 3P

200A 3P

60A 3P

60A 3P

(E)

400A 3P

(E) (E) (E) (E)

600A 3P

100A 3P

400A 3P

(E) ATS

(E) GEN DISCO

(N)PANEL

'EM DIST'

60A

MCB

(E)

(N)PANEL

'4E'

100A

MLO

(N)PANEL

'2E'

100A

MLO

304X

(N)TRANSFORMER: TR-1

10kVA, 480-120/208V

3PH, 4W

(E)PANEL

'2SDP'

400A

MCB

(E)

(E)TRANSFORMER: TR-3

150kVA, 480-120/208V

3PH, 4W

(N)PANEL

'2CS'

100A

MLO

(E) (E)

200A 3P

200A 3P

(E) (E)

(N)PANEL

'PRP'

200A

MLO

AREA OF WORK

PRODUCTION

RELAY PANEL

1 1

4 3 3 3

5 7 8

#8 CU

F

30AS

30AF

Sheet Title

Project Name:

Project Adress:

Project Owner:

Opsis Architecture LLP 920 NW Avenue, Portland, OR 97209

503.525.9511 | info@opsisarch.com opsisarch.com

Sheet No.

Job No.

Key Plan

Status:

Date:

Revisions to Sheet

No. Date pl ot te d:

THESE DRAWINGS ARE THE PROPERTY OF OPSIS ARCHITECTURE

LLP AND ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER,

WITHOUT PRIOR WRITTEN PERMISSION.

sh ee t s iz e:

x

Revision

EXPIRES: 06/30/26

/2

/2

:0 :2

A

M

SINGLE LINE

DIAGRAMS -

ELECTRICAL

BSD Meadow Park MS Stage Upgrades

14100 SW Downing St, Beaverton OR 97006

E5.01

4921-01

2025-02-21

100% CONSTRUCTION

DOCUMENTS

BSD

A,C,S,X A=Aluminum C=Conduit only S=Service secondary X=Seperately derived system

FEEDER SCHEDULE

203 3 #12 CU, 1 #12 CU GND., IN 3/4" C

304 4 #10 CU, 1 #10 CU GND., IN 3/4" C.

304X 4 #10 CU, 1 #8 CU GND., IN 3/4" C.

404 4 #8 CU, 1 #10 CU GND., IN 3/4" C.

1004 4 #2 CU, 1 #8 CU GND., IN 1 1/4" C.

2004 4 #3/0 CU, 1 #6 CU GND., IN 2" C.

NO SCALE

1 DEMO ONE-LINE POWER DISTRIBUTION DIAGRAM

PROJECT

CONTACT

www.interfaceengineering.com

Chris Roybal 2024-0306

100 SW Main Street, Suite 1600 Portland, OR 97204

TEL 503.382.2266

A. CALCULATED VALUES FOR AVAILABLE FAULT CURRENT ARE

SUITABLE FOR PLAN REVIEW PURPOSES BUT ARE NOT

CONSIDERED ACCURATE FOR ACTUAL INSTALLED FEEDER

ROUTING. UPDATE THE AS-BUILT DRAWING SET AT THE

CONSTRUCTION SITE WITH RESULTS OF CALCULATIONS FOR FAULT

CURRENT BASED ON ACTUAL FEEDER LENGTHS AND ROUTING

USING RESULTS OF LICENSED SOFTWARE PER APPROVED

ELECTRICAL DISTRIBUTION SYSTEM STUDY (SECTION 26 05 73).

B. PROVIDE ALLOWANCE OF $50,000 TO COVER ANY POTENTIAL

COSTS FOR UPGRADING THE ELECTRICAL DISTRIBUTION SYSTEM

PENDING THE 30-DAY METERING EFFORTS PER NEC 220.87.

NO SCALE

2 NEW ONE-LINE POWER DISTRIBUTION DIAGRAM

SHEET KEYNOTES

1. PROVIDE NEW CONDUCTORS IN EXISTING CONDUIT.

2. PROVIDE NEW 200A, 3P BREAKER TO FEED PANEL FROM '2SDP'.

3. DISCONNECT AND RECONNECT ALL EXISTING CIRCUITS, CONDUIT, AND

CONDUCTORS TO NEW ELECTRICAL DISTRIBTUION SYSTEM, UNLESS NOTED

OTHERWISE.

4. PANEL PROVIDED BY DIV. 11 AND INSTALLED BY DIV. 26.

5. MATCH EXISTING SCCR RATING.

6. DISCONNECT TO BE LOCATED WITHIN 25' OF SECONDARY SIDE OF THE

TRANSFORMER.

7. 42 KAIC.

8. 22 KAIC.

GENERAL SHEET NOTES

Sheet Title

Project Name:

Project Adress:

Project Owner:

Opsis Architecture LLP 920 NW Avenue, Portland, OR 97209

503.525.9511 | info@opsisarch.com opsisarch.com

Sheet No.

Job No.

Key Plan

Status:

Date:

Revisions to Sheet

No. Date pl ot te d:

THESE DRAWINGS ARE THE PROPERTY OF OPSIS ARCHITECTURE

LLP AND ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER,

WITHOUT PRIOR WRITTEN PERMISSION.

sh ee t s iz e:

x

Revision

EXPIRES: 06/30/26

/2

/2

:0 :2

A

M

SCHEDULES -

ELECTRICAL

BSD Meadow Park MS Stage Upgrades

14100 SW Downing St, Beaverton OR 97006

E6.01

4921-01

2025-02-21

100% CONSTRUCTION

DOCUMENTS

BSD

TOTAL AMPS (480V, 3 PHASE): 381.3 AMPS

TOTAL NEW DEMAND LOAD: 317 KVA

+ADDED (NEW) DEMAND: LOAD: 3.1 KVA

+25% SAFETY FACTOR: 313.9 KVA

POWER FACTOR (0.9): 251.1 KVA

(E) MAXIMUM DEMAND: 226.00 KW

AT EXISTING MAIN DISTRIBUTION SWITCHBOARD.MAXIMUM

12-MONTH PEAK DEMAND ON MAY, 2023 WAS 226 KW, AS PER

SERVING UTILITY

LOAD SUMMARY

PROJECT

CONTACT

www.interfaceengineering.com

Chris Roybal 2024-0306

100 SW Main Street, Suite 1600 Portland, OR 97204

TEL 503.382.2266

Total NEC Demand Current: 0.0 A

Total Connected Current: 0.0 A

Total NEC Demand: 0.0 VA

Total Connected Load: 0.0 VA

Load Type Connected Load NEC Demand Factor NEC Demand Load Panel Totals

E = Existing Load 30-day metered (125%) EL = Elevator (Demand as per NEC Table... W = Water Heater (125%) EV = Electric Vehicle Changer

R = Receptacles (to 10kVA100%, over 10 kVA... G = General Load (Non-continuous) (100%) L = Lighting (125%) H = Heating (100%)

Motor (125% largest Motor + 100% remaining... K = Kitchen (Demand as per NEC Table 220.56) C = Continuous Load (125%) X = X-Rays (Demand per NEC...

Load Type Definitions:

1. EXISTING LOAD ON NEW BREAKER.

Notes:

Total Connected load Ph. C 0 A

Total Connected load Ph. B 0 A Total Demand Load: 0.0 kVA 0.0 A

Total Connected load Ph. A 0 A Panel Connected Load: 0.0 kVA 0.0 A

23 BUSSED SPACE -- -- 1 -- -- 1 -- -- BUSSED SPACE 24

21 BUSSED SPACE -- -- 1 -- -- 1 -- -- BUSSED SPACE 22

19 BUSSED SPACE -- -- 1 -- -- 1 -- -- BUSSED SPACE 20

17 SPARE BREAKER -- 20 A 1 0 0 1 20 A -- SPARE BREAKER 18

15 SPARE BREAKER -- 20 A 1 0 0 1 20 A -- SPARE BREAKER 16

13 SPARE BREAKER -- 20 A 1 0 0 1 20 A -- SPARE BREAKER 14

11 A-HALL CEILING LIGHTS, OFFICE -- 20 A 1 1 0 0 1 1 20 A -- EXISTING LOAD 12

9 2-HALL EXIT LIGHTS -- 20 A 1 1 0 0 1 1 20 A -- LIBRARY PERIMETER LIGHTS 10

7 2-HALL, LIBRARY CEILING LIGHTS -- 20 A 1 1 0 0 1 1 20 A -- LIBRARY EXIT LIGHTS 8

5 A,B,C HALL CEIL LIGHTS -- 20 A 1 1 0 0 1 1 20 A -- I-HALL EXIT LIGHTS 6

3 A,B,C HALL EXIT LIGHTS -- 20 A 1 1 0 0 1 1 20 A -- A-HALL CEILING, KITCHEN, I... 4

1 BUSSED SPACE -- -- 1 -- -- 1 -- -- BUSSED SPACE 2

CKT Description/Location Type C.B. Pole Note

A B C A B C

Note Pole C.B. Type Description/Location CKT

Load (VA)

FOR AIC RATING SEE ONE-LINE DIAGRAM SUPPLIED FROM: EM DIST

EQUIPMENT RATING: 480/277 V, 3PH, 4 WIRE LOCATION:

BUS AMPACITY: 100 A ENCLOSURE: TYPE 1

MAIN LUG ONLY MOUNTING: RECESSED Accessories:

PANELBOARD: 4E

Total NEC Demand Current: 0.0 A

Total Connected Current: 0.0 A

Total NEC Demand: 0.0 VA

Total Connected Load: 0.0 VA

Load Type Connected Load NEC Demand Factor NEC Demand Load Panel Totals

E = Existing Load 30-day metered (125%) EL = Elevator (Demand as per NEC Table... W = Water Heater (125%) EV = Electric Vehicle Changer

R = Receptacles (to 10kVA100%, over 10 kVA 50%) G = General Load (Non-continuous) (100%) L = Lighting (125%) H = Heating (100%)

Motor (125% largest Motor + 100% remaining motors) K = Kitchen (Demand as per NEC Table... C = Continuous Load (125%) X = X-Rays (Demand per NEC 660.6)

Load Type Definitions:

1. EXISTING LOAD ON NEW BREAKER.

Notes:

Total Connected load Ph. C 0 A

Total Connected load Ph. B 0 A Total Demand... 0.0 kVA 0.0 A

Total Connected load Ph. A 0 A Panel... 0.0 kVA 0.0 A

23 BUSSED SPACE -- -- 1 -- -- 1 -- -- BUSSED SPACE 24

21 BUSSED SPACE -- -- 1 -- -- 1 -- -- BUSSED SPACE 22

19 BUSSED SPACE -- -- 1 -- -- 1 -- -- BUSSED SPACE 20

17 BUSSED SPACE -- -- 1 -- -- 1 -- -- BUSSED SPACE 18

15 SPARE BREAKER -- 20 A 1 0 0 1 20 A -- SPARE BREAKER 16

13 SPARE BREAKER -- 20 A 1 0 0 1 20 A -- SPARE BREAKER 14

11 SPARE BREAKER -- 20 A 1 0 0 1 20 A -- SPARE BREAKER 12

9 GIRLS GYM CEIL & EXIT LTS -- 20 A 1 1 0 0 1 1 20 A -- FIRE ALARM 10

7 BOYS GYM CEIL LTS, EXIT LT GY... -- 20 A 1 1 0 0 1 1 20 A -- KITCHEN, MUSIC AREA EXIT LTS 8

5 GIRLS LOCKER RM CEIL LTS -- 20 A 1 1 0 0 1 1 20 A -- MAIN OFFICE RECEPTACLE 6

3 B'S GYM, B'S&G'S LOCKER EXIT... -- 20 A 1 1 0 0 1 1 20 A -- MAIN OFFICE COPIER 4

1 BOYS LOCKER RM CEIL LTS -- 20 A 1 1 0 0 1 1 20 A -- CAFETORIUM EM LIGHTS 2

CKT Description/Location Type C.B. Pole Note

A B A B

Note Pole C.B. Type Description/Location CKT

Load (VA)

FOR AIC RATING SEE ONE-LINE DIAGRAM SUPPLIED FROM: TR-1

EQUIPMENT RATING: 120/208 V, 3PH, 4 WIRE LOCATION:

BUS AMPACITY: 100 A ENCLOSURE: TYPE 1

MAIN LUG ONLY MOUNTING: RECESSED Accessories:

PANELBOARD: 2E

Total NEC Demand Current: 8.7 A

Total Connected Current: 8.5 A

Total NEC Demand: 3130.0 VA

R 2880.0 100.00% 2880.0 Total Connected Load: 3080.0 VA

Motor 200.0 125.00% 250.0

Load Type Connected Load NEC Demand Factor NEC Demand Load Panel Totals

E = Existing Load 30-day metered (125%) EL = Elevator (Demand as per NEC Table... W = Water Heater (125%) EV = Electric Vehicle Changer

R = Receptacles (to 10kVA100%, over 10 kVA... G = General Load (Non-continuous) (100%) L = Lighting (125%) H = Heating (100%)

Motor (125% largest Motor + 100% remaining... K = Kitchen (Demand as per NEC Table 220.56) C = Continuous Load (125%) X = X-Rays (Demand per NEC...

Load Type Definitions:

1. EXISTING LOAD ON NEW BREAKER.

2. NEW LOAD ON NEW BREAKER.

Notes:

Total Connected load Ph. C 5 A

Total Connected load Ph. B 8 A Total Demand Load: 3.1 kVA 8.7 A

Total Connected load Ph. A 14 A Panel Connected Load: 3.1 kVA 8.5 A

41 BUSSED SPACE -- -- 1 -- 0 1 20 A -- SPARE BREAKER 42

39 BUSSED SPACE -- -- 1 -- 0 1 20 A -- SPARE BREAKER 40

37 BUSSED SPACE -- -- 1 -- 0 1 20 A -- SPARE BREAKER 38

35 SPARE BREAKER -- 20 A 1 0 0 1 20 A -- SPARE BREAKER 36

33 SPARE BREAKER -- 20 A 1 0 0 1 20 A -- SPARE BREAKER 34

31 SPARE BREAKER -- 20 A 1 0 0 1 20 A -- SPARE BREAKER 32

29 SPARE BREAKER -- 20 A 1 0 180 2 1 20 A R RK-1 EQUIPMENT RACK 30

27 SPARE BREAKER -- 20 A 1 0 180 2 1 20 A R RK-1 EQUIPMENT RACK 28

25 R CAFETORIUM, STAGE R 20 A 1 2 360 1,260 2 1 20 A R R STAGE 26

23 CAFETORIUM PROJECTOR R 20 A 1 2 180 200 2 1 20 A Motor STAGE PROJECTOR SCREEN 24

21 R CAFETORIUM R 20 A 1 2 360 360 2 1 20 A R R STAGE CEILING 22

19 CAFETORIUM RECEP. NORTH -- 20 A 1 1 0 0 -- -- -- -- -- 20

17 CAFETORIUM RECEP. NORTH -- 20 A 1 1 0 0 1 2 30 A -- EXISTING LOAD 18

15 STAGE LEFT RECEPTACLE -- 20 A 1 1 0 0 -- -- -- -- -- 16

13 CAFETORIUM WALL RE. S -- 20 A 1 1 0 0 1 2 30 A -- EXISTING LOAD 14

11 CAFETORIUM WALL RE. S -- 20 A 1 1 0 0 1 1 20 A -- EXISTING LOAD 12

9 STAGE CEILING LIGHTS -- 20 A 1 1 0 0 1 1 20 A -- EXISTING LOAD 10

7 STAGE CEILING LIGHTS -- 20 A 1 1 0 0 1 1 20 A -- STAGE PLATFORM LIGHTS 8

5 STAGE CEILING LIGHTS -- 20 A 1 1 0 0 1 1 20 A -- PANEL & STAIR LIGHTS 6

3 STAGE CEILING LIGHTS -- 20 A 1 1 0 0 1 1 20 A -- STAGE REAR RECEPTACLE 4

1 CAFETORIUM BRACKET LTS -- 20 A 1 1 0 0 1 1 20 A -- STAGE REAR RECEPTACLE 2

CKT Description/Location Type C.B. Pole Note

A B C A B C

Note Pole C.B. Type Description/Location CKT

Load (VA)

FOR AIC RATING SEE ONE-LINE DIAGRAM SUPPLIED FROM:

EQUIPMENT RATING: 120/208 V, 3PH, 4 WIRE LOCATION:

BUS AMPACITY: 100 A ENCLOSURE: TYPE 1

MAIN LUG ONLY MOUNTING: SURFACE Accessories:

PANELBOARD: 2CS

Total NEC Demand Current: 0.0 A

Total Connected Current: 0.0 A

Total NEC Demand: 0.0 VA

Total Connected Load: 0.0 VA

Load Type Connected Load NEC Demand Factor NEC Demand Load Panel Totals

E = Existing Load 30-day metered (125%) EL = Elevator (Demand as per NEC Table... W = Water Heater (125%) EV = Electric Vehicle Changer

R = Receptacles (to 10kVA100%, over 10 kVA... G = General Load (Non-continuous) (100%) L = Lighting (125%) H = Heating (100%)

Motor (125% largest Motor + 100% remaining... K = Kitchen (Demand as per NEC Table 220.56) C = Continuous Load (125%) X = X-Rays (Demand per NEC...

Load Type Definitions:

Notes:

Total Connected load Ph. C 0 A

Total Connected load Ph. B 0 A Total Demand Load: 0.0 kVA 0.0 A

Total Connected load Ph. A 0 A Panel Connected Load: 0.0 kVA 0.0 A

19 BUSSED SPACE -- -- 1 -- -- 1 -- -- BUSSED SPACE 20

17 BUSSED SPACE -- -- 1 -- -- 1 -- -- BUSSED SPACE 18

15 BUSSED SPACE -- -- 1 -- -- 1 -- -- BUSSED SPACE 16

13 BUSSED SPACE -- -- 1 -- -- 1 -- -- BUSSED SPACE 14

11 BUSSED SPACE -- -- 1 -- -- 1 -- -- BUSSED SPACE 12

9 BUSSED SPACE -- -- 1 -- -- 1 -- -- BUSSED SPACE 10

7 BUSSED SPACE -- -- 1 -- -- 1 -- -- BUSSED SPACE 8

5 -- -- -- -- -- 0 0 -- -- -- -- -- 6

3 -- -- -- -- -- 0 0 -- -- -- -- -- 4

1 TR-1 Spare 30 A 3 0 0 3 40 A Spare PANEL 4E 2

CKT Description/Location Type C.B. Pole Note

A B C A B C

Note Pole C.B. Type Description/Location CKT

Load (VA)

FOR AIC RATING SEE ONE-LINE DIAGRAM SUPPLIED FROM:

EQUIPMENT RATING: 480/277 V, 3PH, 4 WIRE LOCATION:

BUS AMPACITY: 100 A ENCLOSURE: TYPE 1

MAIN CIRCUIT BREAKER 60 A MOUNTING: SURFACE Accessories:

PANELBOARD: EM DIST

T E

L E

P H

O N

E /D

A T

A

D O

U B

L E

D U

P L E

X

W A

L L M

O U

N T

T E

L E

P H

O N

E

R E

C E

P T

A C

L E

D U

P L E

X R

E C

E P

T A

C L E

S W

IT

C

H E

S

O C

C U

P A

N C

Y S

E N

S O

R S

BRANCH

PANELBOARD

D U

P L E

X R

E C

E P

T A

C L E

BACKSPLASH COUNTERTOP

OUTLETS AT

CABINETS

PLUGMOLD

FINISHED FLOOR

Sheet Title

Project Name:

Project Adress:

Project Owner:

Opsis Architecture LLP 920 NW Avenue, Portland, OR 97209

503.525.9511 | info@opsisarch.com opsisarch.com

Sheet No.

Job No.

Key Plan

Status:

Date:

Revisions to Sheet

No. Date pl ot te d:

THESE DRAWINGS ARE THE PROPERTY OF OPSIS ARCHITECTURE

LLP AND ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER,

WITHOUT PRIOR WRITTEN PERMISSION.

sh ee t s iz e:

x

Revision

EXPIRES: 06/30/26

/2

/2

:0 :2

A

M

DETAILS -

ELECTRICAL

BSD Meadow Park MS Stage Upgrades

14100 SW Downing St, Beaverton OR 97006

E7.01

4921-01

2025-02-21

100% CONSTRUCTION

DOCUMENTS

BSD

PROJECT

CONTACT

www.interfaceengineering.com

Chris Roybal 2024-0306

100 SW Main Street, Suite 1600 Portland, OR 97204

TEL 503.382.2266

NO SCALE

1 TYPICAL MOUNTING HEIGHTS

DISCONNECT AND REMOVE

DIMMER CONTROL PANEL

BOARD "D"

PL0.01

PL0.01

B

ABBREVIATIONS

# = POUNDS

AFF = ABOVE FINISHED FLOOR

CLR = CLEAR

DIV = SPECIFICATIONS DIVISION

EC = ELECTRICAL CONTRACTOR

EE = ELECTRICAL ENGINEER

FM = FLUSH MOUNT

HL = HOUSE LEFT

HR = HOUSE RIGHT

HT = HEIGHT

LF = LINEAR FEET

MAX = MAXIMUM

MIN = MINIMUM

NIC = NOT IN CONTRACT

NTS = NOT TO SCALE

OPP = OPPOSITE

PL = PRODUCTION LIGHTING

PR = PRODUCTION RIGGING

PS = PRODUCTION SEATING

RWL = RECOMMENDED WORKING LOAD

SAD = SEE ARCHITECTURAL DRAWINGS

SED = SEE ELECTRICAL DRAWINGS

SF = SQUARE FEET

SIM = SIMILAR

SL = STAGE LEFT

SM = SURFACE MOUNT

SMD = SEE MECHANICAL DRAWINGS

SR = STAGE RIGHT

SSD = SEE STRUCTURAL DRAWINGS

TYP = TYPICAL

UON = UNLESS OTHERWISE NOTED

VIF = VERIFY IN FIELD

LIGHTING GENERAL NOTES

1. THIS SHEET IS INTENDED TO PROVIDE PRODUCTION LIGHTING

SYSTEM INFORMATION ONLY. REFERENCE OTHER PRODUCTION

SYSTEMS, ARCHITECTURAL, AND ENGINEERING DOCUMENTS

FOR RELATED AREAS.

2. REFERENCE SPECIFICATIONS AND ELECTRICAL DRAWINGS FOR

DIVISION 26 INSTALLATION REQUIREMENTS.

3. ALL CIRCUITS SHALL HAVE A DEDICATED HOMERUN UNLESS

OTHERWISE INDICATED.

4. ALL CIRCUIT LOAD WIRING SHALL BE CONTINUOUS. NO SPLICES

WILL BE ACCEPTED BETWEEN RELAY PANEL LUGS AND DEVICE

TERMINAL STRIP.

5. ALL CIRCUITS SHALL HAVE A DEDICATED NEUTRAL. ALL

POWER DEVICE BOXES SHALL HAVE AT LEAST ONE DEDICATED

GROUND [PER (6) CIRCUITS] HOMERUN TO RELAY PANEL.

6. EXISTING CIRCUIT WIRING MAY BE RETAINED AND REUSED AS

DEEMED APPROPRIATE BY THE EEOR.

PROD. LIGHTING SCOPE MATRIX

POWER SYSTEMS (COMPLETE)

SCOPE

RESPONSIBILITY

EC PL

X

COMPANY SWITCHES X

CONDUIT & STANDARD BACK BOXES X

WIRE & PULL FOR PL SYSTEMS X

LOW-VOLT WIRE TERMINATION FOR PL SYSTEMS X

SUPPLY PL DEVICES & EQUIPMENT X

INSTALL PL EQUIPMENT X

ADDRESSING OF PERMANENT DMX FIXTURES X

PL PROGRAM & CONFIGURATION X

COORDINATE ALL CLEAR ZONES ON DRAWINGS/SPECS X

NTS4

EXISTING FLOOR BOXES

NTS3

EXISTING DISTRIBUTION PLAN

NTS5

EXISTING DIMMER CONTROL BOARD

Planning and Design of Theatres Production Systems | AV

The

Inc.

415-956-4100

1553 Martin Luther King Jr Way Berkeley CA 94709

Collaborative Shalleck www.shalleck.com

Sheet Title

Project Name:

Project Adress:

Project Owner:

Opsis Architecture LLP 920 NW Avenue, Portland, OR 97209

503.525.9511 | info@opsisarch.com opsisarch.com

Sheet No.

Job No.

Key Plan

Status:

Date:

Revisions to Sheet

No. Date pl ot te d:

THESE DRAWINGS ARE THE PROPERTY OF OPSIS ARCHITECTURE

LLP AND ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER,

WITHOUT PRIOR WRITTEN PERMISSION.

sh ee t s iz e:

x

NOT FOR

CONSTRUCTION

Revision

/7

/2

:2 :0

P

M

PRODUCTION

LIGHTING DEMO

PLAN

BSD Meadow Park MS Stage Upgrades

14100 SW Downing St, Beaverton OR 97006

PL0.01

4921-01

02/07/2025

100% CD

BSD

copyright 2021

1/8" = 1'-0"2

MEADOW PARK STAGE PLAN - DEMOLITION

1/8" = 1'-0"1

MEADOW PARK REFLECTED CEILING PLAN - DEMOLITION

REMOVE ALL EXISTING PRODUCTION

LIGHTING RECEPTACLE DEVICES, AND

HARDWIRED LIGHTING FIXTURES. POWER

RECEPTACLE WIRING TO REMAIN FOR REUSE

AS DEEMED APPROPRIATE PER THE EEOR

FLOORBOXES TO BE REMOVED KEEP CONDUIT STUB

IN FLOOR AND REPLACE WITH NEW FSR FLOORBOX

VERIFY SIZE OF OPENING IN FEILD

REMOVE THREE (3) OLD STYLE WELDED

BATTEN AND RACEWAY ASSEMBLIES;

STANDARD BATTENS FROM WHICH THOSE

HANG ARE TO REMAIN IN PLACE.

Jill Callout remove CS and lower pipe from assembly. retain upper pipe as rigging pipe

PRODUCTION LIGHTING SYMBOL KEY

NEMA 5-20R DUPLEX POWER RECEPTACLE

INTEGRAL TO DEVICE, 120V, 20A, CONSTANT

NEMA 5-20R QUAD POWER RECEPTACLE

INTEGRAL TO DEVICE, 120V, 20A, CONSTANT

2B

PLB-1

DEVICE LOCATION

T - TOUCH SCREEN CONTROL STATION

DEVICE TYPE

PRODUCTION LIGHTING DEVICE

DEVICE NUMBER

PRODUCTION RELAY CIRCUIT

PLD-1

GR

3 @ 20A-P

CIRCUITS AMPERAGE

NUMBER OF CIRCUITS

DEVICE LOCATION

DEVICE TYPE

IC - CONTROL BOX WITH (1) DMX IN

RECEPTACLE

IOC - CONTROL BOX WITH (1) DMX IN

AND (1) DMX OUT RECEPTACLE

OR - COMBO CONTROL AND POWER BOX

WITH (1) DMX RECEPTACLES AND

POWER RECEPTACLES PER SCHEDULE

OOR - COMBO CONTROL AND POWER

BOX WITH (2) DMX RECEPTACLES AND

POWER RECEPTACLES PER SCHEDULE

PRODUCTION LIGHTING DEVICE

DEVICE NUMBER

B

__________PLD- 4

OR

2@20A-P2@20A-P

__________PLD- 6

OR

2@20A-P2@20A-P

__________PLD- 5

OR

2@20A-P2@20A-P

__________PLD- 7

OR

2@20A-P2@20A-P

__________PLD- 2

IOC

_______PLB- 3

T

__________PLD- 1

IC

NEW ETC - SENSOR IQ 24 CIRCUIT

PANEL, IN LOCATION OF EXISTING

DIMMER CONTROL PANEL BOARD

"DP"

STAGE EQUIPMENT RACK "RK-1" WITH

120V CONVENIENCE OUTLET

(RACK BY AV)

(OUTLET BY ELECTRICAL)

B

__________PLD- 11

OOR

6@20A-P6@20A-P

__________PLD- 12

OOR

5@20A-P5@20A-P

__________PLD- 13

OOR

2@20A-P2@20A-P

__________PLD- 10

OR

1@20A-P1@20A-P

__________PLD- 9

OR

1@20A-P1@20A-P

__________PLD- 8

OR

1@20A-P1@20A-P

ABBREVIATIONS

# = POUNDS

AFF = ABOVE FINISHED FLOOR

CLR = CLEAR

DIV = SPECIFICATIONS DIVISION

EC = ELECTRICAL CONTRACTOR

EE = ELECTRICAL ENGINEER

FM = FLUSH MOUNT

HL = HOUSE LEFT

HR = HOUSE RIGHT

HT = HEIGHT

LF = LINEAR FEET

MAX = MAXIMUM

MIN = MINIMUM

NIC = NOT IN CONTRACT

NTS = NOT TO SCALE

OPP = OPPOSITE

PL = PRODUCTION LIGHTING

PR = PRODUCTION RIGGING

PS = PRODUCTION SEATING

RWL = RECOMMENDED WORKING LOAD

SAD = SEE ARCHITECTURAL DRAWINGS

SED = SEE ELECTRICAL DRAWINGS

SF = SQUARE FEET

SIM = SIMILAR

SL = STAGE LEFT

SM = SURFACE MOUNT

SMD = SEE MECHANICAL DRAWINGS

SR = STAGE RIGHT

SSD = SEE STRUCTURAL DRAWINGS

TYP = TYPICAL

UON = UNLESS OTHERWISE NOTED

VIF = VERIFY IN FIELD

LIGHTING GENERAL NOTES

1. THIS SHEET IS INTENDED TO PROVIDE PRODUCTION LIGHTING

SYSTEM INFORMATION ONLY. REFERENCE OTHER PRODUCTION

SYSTEMS, ARCHITECTURAL, AND ENGINEERING DOCUMENTS

FOR RELATED AREAS.

2. REFERENCE SPECIFICATIONS AND ELECTRICAL DRAWINGS FOR

DIVISION 26 INSTALLATION REQUIREMENTS.

3. ALL CIRCUITS SHALL HAVE A DEDICATED HOMERUN UNLESS

OTHERWISE INDICATED.

4. ALL CIRCUIT LOAD WIRING SHALL BE CONTINUOUS. NO SPLICES

WILL BE ACCEPTED BETWEEN RELAY PANEL LUGS AND DEVICE

TERMINAL STRIP.

5. ALL CIRCUITS SHALL HAVE A DEDICATED NEUTRAL. ALL

POWER DEVICE BOXES SHALL HAVE AT LEAST ONE DEDICATED

GROUND [PER (6) CIRCUITS] HOMERUN TO RELAY PANEL.

6. EXISTING CIRCUIT WIRING MAY BE RETAINED AND REUSED AS

DEEMED APPROPRIATE BY THE EEOR.

PROD. LIGHTING SCOPE MATRIX

POWER SYSTEMS (COMPLETE)

SCOPE

RESPONSIBILITY

EC PL

X

COMPANY SWITCHES X

CONDUIT & STANDARD BACK BOXES X

WIRE & PULL FOR PL SYSTEMS X

LOW-VOLT WIRE TERMINATION FOR PL SYSTEMS X

SUPPLY PL DEVICES & EQUIPMENT X

INSTALL PL EQUIPMENT X

ADDRESSING OF PERMANENT DMX FIXTURES X

PL PROGRAM & CONFIGURATION X

COORDINATE ALL CLEAR ZONES ON DRAWINGS/SPECS X

Planning and Design of Theatres Production Systems | AV

The

Inc.

415-956-4100

1553 Martin Luther King Jr Way Berkeley CA 94709

Collaborative Shalleck www.shalleck.com

Sheet Title

Project Name:

Project Adress:

Project Owner:

Opsis Architecture LLP 920 NW Avenue, Portland, OR 97209

503.525.9511 | info@opsisarch.com opsisarch.com

Sheet No.

Job No.

Key Plan

Status:

Date:

Revisions to Sheet

No. Date pl ot te d:

THESE DRAWINGS ARE THE PROPERTY OF OPSIS ARCHITECTURE

LLP AND ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER,

WITHOUT PRIOR WRITTEN PERMISSION.

sh ee t s iz e:

x

NOT FOR

CONSTRUCTION

Revision

/7

/2

:2 :0

P

M

PRODUCTION

LIGHTING

DEVICE PLAN

BSD Meadow Park MS Stage Upgrades

14100 SW Downing St, Beaverton OR 97006

PL1.01

4921-01

02/07/2025

100% CD

BSD

copyright 2021

1/8" = 1'-0"2 MEADOW PARK STAGE PLAN

1/8" = 1'-0"1 MEADOW PARK REFLECTED CEILING PLAN

D D

OVERSTAGE

STAGE

HOUSE

ND

PRP

PRODUCTION

RELAY PANEL

1-24 24@20A

PRODUCTION

LIGHTING

CIRCUITS

SEE SCHEDULE

BELOW

WIREWAY, S.E.D.D

20A, 120/208VAC, CONSTANT POWER (UNDER ELECT)

200A, 120/208V, 3Ø BREAKER OR DISCONNECT (UNDER ELECT)

INTERCONNECT WITH AV CONTROLLER

STAGE RIGHT WING

STAGE AND HOUSE

PRODUCTION LIGHTING

WIRING DEVICES

PLD - ##

OR

D D D

ALL LOW VOLTAGE WIRE PROVIDED AND INSTALLED BY DIVISION 26.

ALL LOW VOLTAGE WIRE TERMINATED BY DIVISION 11 PRODUCTION LIGHTING.

STANDARD BACKBOXES PROVIDED BY DIVISION 26,

UNLESS SURFACE MOUNTED OR A CUSTOM SPECIALTY BOX.

ALL CONDUIT FOR LOW VOLTAGE PLB/PLD

DEVICES SHALL BE 1" MIN DIAMETER

UNLESS OTHERWISE NOTED

HOUSE

D D D

D

D

2 4 6

1 2 3

N

D D 1 2

L

OVERSTAGE

STAGE

RK-1

SHARED RACK

PROVIDED BY AV -

SEE AV DRAWINGS

NETWORK SWITCH

PARADIGM TOUCHSCREEN

4 PORT DMX GATEWAY

4 PORT DMX GATEWAY

4 PORT DMX GATEWAY

4 PORT DMX GATEWAY

4 PORT DMX GATEWAY

ETC RESPONSE SNAPBACK

PARADIGM LIGHTING

PROCESSOR

UPS

__________PLD- 4

OR

__________PLD- 6

OR

__________PLD- 5

OR

__________PLD- 7

OR

__________PLD- 2

IOC

_______PLB- 3

T

__________PLD- 1

IC

__________PLD- 11

OOR

__________PLD- 12

OOR

__________PLD- 13

OOR

__________PLD- 10

OR

__________PLD- 9

OR

__________PLD- 8

OR

WIRING KEY

X

WIRE AND CONDUIT (BY DIV. 26) -

1" CONDUIT UON

WIRE & CONDUIT TYPE

N ETHERNET - CAT5e:

DRY: (1) BELDEN 1583A

A ARCH LTG CONTROL:

DRY: (1) BELDEN 8471 & (1) 14 AWG THHN

D DMX CONTROL:

DRY: (1) BELDEN 9729

WET: (1) WEST PENN AQ225 & (1) 14 AWG THWN

WET: (1) BELDEN 1594A

WET: (1) BELDEN 3107DB

L LINE VOLTAGE NORMAL CIRCUIT WIRING

(SHOWN FOR REFERENCE ONLY, SEE ELECTRICAL DRAWINGS)

ABBREVIATIONS

# = POUNDS

AFF = ABOVE FINISHED FLOOR

CLR = CLEAR

DIV = SPECIFICATIONS DIVISION

EC = ELECTRICAL CONTRACTOR

EE = ELECTRICAL ENGINEER

FM = FLUSH MOUNT

HL = HOUSE LEFT

HR = HOUSE RIGHT

HT = HEIGHT

LF = LINEAR FEET

MAX = MAXIMUM

MIN = MINIMUM

NIC = NOT IN CONTRACT

NTS = NOT TO SCALE

OPP = OPPOSITE

PL = PRODUCTION LIGHTING

PR = PRODUCTION RIGGING

PS = PRODUCTION SEATING

RWL = RECOMMENDED WORKING LOAD

SAD = SEE ARCHITECTURAL DRAWINGS

SED = SEE ELECTRICAL DRAWINGS

SF = SQUARE FEET

SIM = SIMILAR

SL = STAGE LEFT

SM = SURFACE MOUNT

SMD = SEE MECHANICAL DRAWINGS

SR = STAGE RIGHT

SSD = SEE STRUCTURAL DRAWINGS

TYP = TYPICAL

UON = UNLESS OTHERWISE NOTED

VIF = VERIFY IN FIELD

LIGHTING GENERAL NOTES

1. THIS SHEET IS INTENDED TO PROVIDE PRODUCTION LIGHTING

SYSTEM INFORMATION ONLY. REFERENCE OTHER PRODUCTION

SYSTEMS, ARCHITECTURAL, AND ENGINEERING DOCUMENTS

FOR RELATED AREAS.

2. REFERENCE SPECIFICATIONS AND ELECTRICAL DRAWINGS FOR

DIVISION 26 INSTALLATION REQUIREMENTS.

3. ALL CIRCUITS SHALL HAVE A DEDICATED HOMERUN UNLESS

OTHERWISE INDICATED.

4. ALL CIRCUIT LOAD WIRING SHALL BE CONTINUOUS. NO SPLICES

WILL BE ACCEPTED BETWEEN RELAY PANEL LUGS AND DEVICE

TERMINAL STRIP.

5. ALL CIRCUITS SHALL HAVE A DEDICATED NEUTRAL. ALL

POWER DEVICE BOXES SHALL HAVE AT LEAST ONE DEDICATED

GROUND [PER (6) CIRCUITS] HOMERUN TO RELAY PANEL.

6. EXISTING CIRCUIT WIRING MAY BE RETAINED AND REUSED AS

DEEMED APPROPRIATE BY THE EEOR.

PROD. LIGHTING SCOPE MATRIX

POWER SYSTEMS (COMPLETE)

SCOPE

RESPONSIBILITY

EC PL

X

COMPANY SWITCHES X

CONDUIT & STANDARD BACK BOXES X

WIRE & PULL FOR PL SYSTEMS X

LOW-VOLT WIRE TERMINATION FOR PL SYSTEMS X

SUPPLY PL DEVICES & EQUIPMENT X

INSTALL PL EQUIPMENT X

ADDRESSING OF PERMANENT DMX FIXTURES X

PL PROGRAM & CONFIGURATION X

COORDINATE ALL CLEAR ZONES ON DRAWINGS/SPECS X

Planning and Design of Theatres Production Systems | AV

The

Inc.

415-956-4100

1553 Martin Luther King Jr Way Berkeley CA 94709

Collaborative Shalleck www.shalleck.com

Sheet Title

Project Name:

Project Adress:

Project Owner:

Opsis Architecture LLP 920 NW Avenue, Portland, OR 97209

503.525.9511 | info@opsisarch.com opsisarch.com

Sheet No.

Job No.

Key Plan

Status:

Date:

Revisions to Sheet

No. Date pl ot te d:

THESE DRAWINGS ARE THE PROPERTY OF OPSIS ARCHITECTURE

LLP AND ARE NOT TO BE USED OR REPRODUCED IN ANY MANNER,

WITHOUT PRIOR WRITTEN PERMISSION.

sh ee t s iz e:

x

NOT FOR

CONSTRUCTION

Revision

/7

/2

:2 :0

P

M

PRODUCTION

LIGHTING

SINGLE LINE

AND SCHEDULE

BSD Meadow Park MS Stage Upgrades

14100 SW Downing St, Beaverton OR 97006

PL3.01

4921-01

02/07/2025

100% CD

BSD

copyright 2021

PRODUCTION LIGHTING DEVICE SCHEDULE - MEADOW PARK

D E

V

IC

E N

U M

B E

R

D E

V

IC

E T

Y P

E

HARDWIRE DMX LIGHTING DATA NETWORK

PRODUCTION RELAY

CIRCUITS

F

IN

IS

H

D E

V

IC

E D

E T

A

IL

MOUNTING REFERENCE

B A

C K

B O

X T

Y P

E

N O

T E

S

D M

X I

N

D M

X O

U T

P O

R T

C O

U N

T

P A

T C

H P

A N

E L

I D

P A

T C

H P

A N

E L

L O

C A

T

IO

N L

A B

E L

C

IR

C U

IT

Q

T Y

C

IR

C U

IT

B A

C K

B O

X M

O U

N T

IN

G

M O

U N

T

IN

G L

O C

A T

IO

N

1 IC 1 REAR OF HOUSE BLACK 3/PL401 SURFACE

MOUNT

@ OUTLET HT PER MFR

2 IOC 1 1 FRONT OF STAGE BLACK 4/PL401 FLUSH

MOUNT

@ OUTLET HT PER MFR COORDINATE FLUSH MOUNT

WITH DIV 26 AND FIELD

CONDITIONS

3 T 1 AV RACKMOUNT TOUCHSCREEN BLACK 5/PL401 RACKMOUNT IN

EQUIPMENT

RACK

N/A CUSTOM MOUNTED WITH

TOUCHSCREEN

4 OR 1 DOWNSTAGE LEFT FLOORBOX 2 1-2 BLACK 1/PL401 FLUSH

MOUNT

IN FLOORBOX FLOOR SIZE FLOORBOX TO FIT EXISTING

CUTOUT IN STAGE FLOOR

5 OR 1 DOWNSTAGE RIGHT FLOORBOX 2 3-4 BLACK 1/PL401 FLUSH

MOUNT

IN FLOORBOX FLOOR SIZE FLOORBOX TO FIT EXISTING

CUTOUT IN STAGE FLOOR

6…

This is the start of the file's text. The full file is on GovTribe.