This document provides details for a Request for Proposal (RFP) for the Z2DZ--590-602 Renovate and Expand Domiciliary project at the Hampton VAMC located in Hampton, Virginia. The RFP seeks proposals for the renovation and expansion of the Domiciliary with a construction magnitude between $5,000,000 to $10,000,000. The NAICS code is 236220 with a size standard of $39.5 million. The solicitation is a 100% SDVOSB set-aside issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6. A pre-proposal site visit will be conducted on August 18, 2020, and requests for information are due by August 21, 2020 with answers provided via amendment by August 28, 2020. Proposals must be submitted by September 21, 2020. The attachment includes proposal and deductive proposal items.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
McPHERSON
DESIGN
GROUP
STRUCTURAL ENGINEERS
6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com
Hampton, Virginia
SEWELLAVENUE
A V
E N
U E
A M
E S S
T R E E T
K N
O X
S T R
E E
T
T H O
M P S O
N S
T R E E T
B L A C K
F R A N K L
IN
B O
U L E V A R D
E M
A N
C
IP
A T
IO
N
D R
A V E N
U E
M cC
LE
LLA
N
H A
R R
IS
A V
E R
IL
L A
V E
N U
E
F R
A N
K L
IN
B O
U L E
V A
R D
MARTIN L. KING JR. BOULEVARD
BOULEVARD
S H
O R
E R
O A
D
A V E N U E
H A
R R
IS
A
V E
N U
E
H A
R R
IS
A V
E R
IL
L A
V E
N U
E
FR
A
N K
LIN
B
O U
LE
V A R
D
MARTIN L. KING JR.
CONTRACTO
R'S STAG
ING AREA
M A
L L O
R Y
S T R
E E
T
J O
N E
S C
R E
E K
S A
L V
A G
E Y
A R
D1
G R A V E L D
R
IV
E W
A Y
G R A V E L D
R
IV
E W
A Y
G R A V E L R
O A D
S T O
R M
W A
T E
R P
O N
D
IM
P
O U
N D
L O
T
A V E N
U E
148T
148B
148S
148A
148D
148C
CONSTRUCTION NOTES
SHEET NOTES
SHEET NOTES
SIDEWALK REPAIR DETAIL
TEMPORARY CONSTRUCTION FENCE DETAIL
SIDE ELEVATION
PLAN VIEW
SECTION A-A
SECTION B-B
STONE CONSTRUCTION ENTRANCE
CEILING AS SCHEDULED
BASE AS SCHEDULED
PROVIDE DIAGONAL BRACING AT
8'-0" OC, AND AT EACH SIDE OF
ALL OPENINGS AND AS REQUIRED
FOR STABILITY
5/8" GWB
METAL STUDS
LINE OF FLOOR
WALL FINISH AS SCHEDULED
ACOUSTICAL SEALANT
CONTINUOUS EACH SIDE
SOUND ATTENUATION INSULATION
PLAN
VIEW
POWDER ACTUATED FASTENER, TYP
BOTTOM OF DECK
PROVIDE TOP TRACK W/ 2" LONG
LEGS, MAINTAIN 3/4" CLEAR BELOW
DECK, TYP
ACOUSTICAL SEALANT CONTINUOUS
AT UNDERSIDE OF STRUCTURE
CEILING AS SCHEDULED
LINE OF FLOOR
ACOUSTICAL SEALANT
CONTINUOUS EACH SIDE
PLAN
VIEW
BASE AS SCHEDULED
5/8" GWB
METAL STUDS
WALL FINISH AS SCHEDULED
SOUND ATTENUATION INSULATION
POWDER ACTUATED FASTENER, TYP
FILL ALL VOIDS AT TOP OF PARTITION
WITH BATT INSULATION
A/C AIR CONDITIONING
ADA AMERICANS WITH DISABILITIES
ACOUS ACOUSTICAL
ACT ACOUSTICAL CEILING TILE
AFF ABOVE FINISHED FLOOR
ALUM ALUMINUM
APPROX APPROXIMATELY
BD BOARD
BLDG BUILDING
BTM BOTTOM
CJ CONTROL JOINT
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
CONC CONCRETE
CONT CONTINUOUS
COORD COORDINATE
D/DIA DIAMETER
DEMO DEMOLISH
DN DOWN
EA EACH
EJ EXPANSION JOINT
EQ EQUAL
EQUIP EQUIPMENT
ETC ETCETERA
EXT EXTERIOR
FD FLOOR DRAIN
FDV FIRE DEPARTMENT VALVE
FEC FIRE EXTINGUISHER CABINET
REV REVERSED
RO ROUGH OPENING
SIM SIMILAR
SQ SQUARE
SS STAINLESS STEEL
STL STEEL
STRUCT STRUCTURAL
TB TACK BOARD
TEMP TEMPORARY
TERM TERMINATE
TGL TEMPERED GLAZING
TV TELEVISION
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
VERT VERTICAL
VCT VINYL COMPOSITION TILE
W WIDTH
WD WOOD
WWF WELDED WIRE FABRIC
@ AT
& AND
CENTER LINE
ø DIAMETER
# NUMBER
CL
FRT FIRE RETARDANT TREATED
FRZR FREEZER
GA GAUGE
GC GENERAL CONTRACTOR
GWB GYPSUM WALL BOARD
GYP GYPSUM
H HEIGHT
HM HOLLOW METAL
HOR HORIZONTAL
HR HOUR
INSUL INSULATION
MANUF MANUFACTURER
MAX MAXIMUM
MB MARKER BOARD
MECH MECHANICAL
MIN MINIMUM
MO MASONRY OPENING
MTL METAL
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OC ON CENTER
OH OPPOSITE HAND
PEMB PRE-ENGINEERED METAL BUILDING
PLAM PLASTIC LAMINATE
PNT PAINT
PREFAB PREFABRICATED
PSI POUNDS PER SQUARE INCH
REF REFRIGERATOR
REINF REINFORCED
ROOM
B-101
A
A
(8'-0")
ROOM NAME AND
NUMBER REFERENCE
DOOR NUMBER
REFERENCE
WINDOW MARKER
SEE SHEET A-XXX
PARTITION TYPE
SEE SHEET A-XXX
CEILING REFERENCE
HEIGHT AFF
NEW WORK NOTES
DEMOLITION WORK NOTES
TOILET ACCESSORY NOTE
SEE SHEET A-XXX
REVISION MARKER
CONTROL OR EXPANSION
JOINT - SEE SHEET A-XXX
AS501
AS501
AS401C A
B
D
A
AS301
DETAIL DRAWN ON THIS SHEET (TYP)
DETAIL NUMBER (TYP)
DETAIL DRAWN ON THIS SHEET (TYP)
DETAIL NUMBER (TYP)
DETAIL INDICATORS
ELEVATIONS DRAWN ON THIS SHEET (TYP)
ELEVATION LETTER (TYP)
INTERIOR ELEVATION REFERENCE
SECTION DRAWN ON THIS SHEET (TYP)
SECTION LETTER (TYP)
BUILDING AND WALL SECTION REFERENCE
ELEVATIONS DRAWN ON THIS SHEET (TYP)
ELEVATION LETTER (TYP)
BUILDING ELEVATION REFERENCE
PLAN
NORTH
AS101
DRAWING OR DETAIL TITLE
SCALE
PLAN OR SITE TITLE
SCALE
SHEETS WHERE DETAIL IS DRAWN
DETAIL NUMBER
TRUE NORTH
PLAN NORTH
AS101
SHEETS WHERE DETAIL IS REFERENCED
A
AS201
SOUND ATTENUATION
INSULATION UON
BRICK
CONCRETE
CONCRETE
MASONRY UNITS
CONTINUOUS
BLOCKING
EARTH
FINISHED WOOD
GRAVEL
GYPSUM BOARD
OR SHEATHING
PLYWOOD
RIGID INSULATION
STEEL
SAFETY - DURING CONSTRUCTION WORK
COMPLETE ALL CRITICAL BARRIERS BEFORE CONSTRUCTION BEGINS.
INSTALL CONSTRUCTION BARRIERS AND CEILING PROTECTION
CAREFULLY, OUTSIDE OF NORMAL WORK HOURS.
SEPARATE ALL OCCUPIED AREAS FROM DEMOLITION, RENOVATION, OR
CONSTRUCTION ACTIVITIES BY TEMPORARY SMOKE-TIGHT
CONSTRUCTION PARTITIONS OF GYPSUM BOARD OR OTHER APPROVED
NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE MATERIAL. PARTITIONS
SHALL BE FULL HEIGHT, EXTENDING THROUGH SUSPENDED CEILINGS
TO THE FLOOR SLAB OR ROOF DECK ABOVE AND SHALL BE ONE-
HOUR FIRE RATED. BARRIER MUST BE PRESENTABLE ON OCCUPIED
SIDE.
DRYWALL BARRIER ERECTED WITH JOINTS COVERED OR SEALED TO
PREVENT DUST AND DEBRIS FROM ESCAPING.
BARRIER DOORS: SELF CLOSING ONE-HOUR SOLID CORE WOOD IN
STEEL FRAME, PAINTED.
ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO
PREVENT CONTAMINATION OF DUCT SYSTEM.
MAINTAIN NEGATIVE AIR PRESSURE, 0.01 INCHES OF WATER GAUGE,
WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS
AND CONTINUOUSLY MONITORED WITH A DIGITAL DISPLAY, RECORDING
AND ALARM INSTRUMENT, WHICH MUST BE CALIBRATED ON
INSTALLATION, MAINTAINED WITH PERIODIC CALIBRATION AND
MONITORED BY THE CONTRACTOR.
EXHAUST HOSES REQUIRED: HEAVY DUTY, FLEXIBLE STEEL
REINFORCED; VENTILATION BLOWER HOSE
ADHESIVE WALK-OFF MATS SHALL BE USED AT ALL INTERIOR
TRANSITIONS FROM THE CONSTRUCTION AREA TO BE OCCUPIED
MEDICAL CENTER AREA. PROVIDE MINIMUM SIZE MATS OF 24 INCHES
X 36 INCHES. THESE MATS SHALL BE CHANGED AS OFTEN AS
REQUIRED TO MAINTAIN CLEAN WORK AREAS DIRECTLY OUTSIDE
CONSTRUCTION AREA AT ALL TIMES.
VACUUM AND WET MOP ALL TRANSITION AREAS FROM CONSTRUCTION
TO THE OCCUPIED MEDICAL CENTER AT THE END OF EACH
WORKDAY. VACUUM SHALL UTILIZE HEPA FILTRATION. MAINTAIN
SURROUNDING AREA FREQUENTLY.
CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY
COVERED CONTAINERS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
SAFETY - COMPLETION OF CONSTRUCTION WORK
DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED
PROJECT IS INSPECTED BY THE CO (OR DESIGNATED REP) AND
THOROUGHLY CLEANED.
REMOVE CONSTRUCTION BARRIERS AND CEILING PROTECTION
CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED
WITH CONSTRUCTION, OUTSIDE OF NORMAL WORK HOURS.
VACUUM WORK AREA WITH HEPA FILTERED VACUUMS.
WET MOP AREA WITH CLEANER/DISINFECTANT.
UPON COMPLETION, RESTORE HVAC SYSTEM WHERE WORK WAS
PERFORMED.
1.
2.
3.
4.
5.
SPECIAL DOCUMENT NOTES
**THE FOLLOWING ARE A LIST OF WORDS/PHRASES WITH
DEFINITIONS THAT ARE USED THROUGHOUT THESE DOCUMENTS
THAT MUST BE USED WHEN EXECUTING THE WORK SHOWN ON
ALL THE DOCUMENTS FOR THIS PROJECT.
1. "PROVIDE" IS DEFINED TO MEAN "FURNISH AND INSTALL
COMPLETE, IN PLACE AND READY FOR OPERATION AND USE."
2. FURNISH" IS DEFINED TO MEAN "SUPPLY AND DELIVER TO
PROJECT SITE, READY FOR INSTALLATION."
3. "INSTALL" IS DEFINED TO MEAN "PLACE IN POSITION FOR
SERVICE OR USE."
Date
Location
Checked Drawn
Drawing Number
Building Number
Project NumberProject TitleDrawingTitle
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
Dwg. of
A
B
C
D
E
F
Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
VA FORM 08-6231
th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
BOWMAN FOSTER
& ASSOCIATES, PC
ALEXANDRIA, VA 22312
6353 CENTER DR. STE 101
NORFOLK, VA 23502
5252 CHEROKEE AVE, STE 101
McPHERSON
DESIGN
GROUP p.c.
STRUCTURAL ENGINEERS
6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com
901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5
Engineers Surveyors Planners
HOGGARD/EURE ASSOCIATES, P.C.
FULLY SPRINKLERED
PARTITION TYPES, LEGENDS,
ABBREVIATIONS AND NOTES
AS001
VA MEDICAL CENTER, HAMPTON, VA
JDB DAS 20 165
590-602
7/26/19
RENOVATE AND EXPAND
DOMICILIARY BUILDING 148
PARTITION TYPE - A
TYPE WIDTH
STUD
SIZE
MAX STUD
SPACING INSUL
FIRE
RATING UL # NOTES
A 4 7/8" 3 5/8" 16" OC 3 1/2" - -
A1 4 7/8" 3 5/8" 16" OC - - -
A2 4 1/4" 3 5/8" 16" OC 3 1/2" - - 1
PARTITION TYPE A
THE CONTRACTOR SHALL VERIFY ALL FIELD CONDITIONS AND
DIMENSIONS PRIOR TO BEGINNING CONSTRUCTION AND SHALL
COORDINATE THE WORK OF ALL TRADES. ALL DISCREPANCIES
SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
ARCHITECT, IN WRITING, BEFORE CONTINUING WORK.
UNLESS OTHERWISE INDICATED, EXTERIOR DIMENSIONS ARE TO
OUTSIDE FACE OF FOUNDATION WALL AND CENTERLINE OF
STRUCTURAL COLUMNS. INTERIOR DIMENSIONS ARE TO FACE OF
STUD AND CENTERLINE OF STRUCTURAL COLUMNS.
SEE CIVIL DRAWINGS FOR FINISH FLOOR AND GRADE ELEVATIONS,
SIDEWALK, CURBS, ETC.
ALL METAL STUDS SHALL BE 20 GAUGE MINIMUM.
THE WORK INCLUDES THE DEMOLITION AND REMOVAL OF ALL
CONSTRUCTION INDICATED, NOTED OR NECESSARY TO
ACCOMPLISH THE WORK AS INDICATED OR SPECIFIED.
THE CONTRACTOR WILL PATCH OR FILL ALL HOLES AND DAMAGED
SURFACES RESULTING FROM THE DEMOLITION OF EXISTING, OR IN
PREPARATION OF NEW WORK WITH FINISH MATERIALS TO MATCH
EXISTING (MINIMUM 2'-0" ALL AROUND WORK AREAS) AND
RESULT IN A THOROUGHLY FINISHED PRODUCT.
IT IS THE GENERAL INTENT OF THE DEMOLITION WORK TO
COMPLETLEY REMOVE ALL ITEMS OF EXISTING CONSTRUCTION,
WHERE NOTED OR INDICATED ON THE DRAWINGS, INCLUDING
ANCHORS, FASTENERS, BRACKETS, CLIPS, RODS, HANGERS, AND
SUPPORTS.
REMOVE AND REPLACE ANY DAMAGED/DISCOLORED CEILING TILES.
RELOCATE EXISTING LIGHT FIXTURES, MECHANICAL DIFFUSERS,
AND SPRINKLER HEADS AS REQUIRED FOR DEMOLITION OF
EXISTING CEILING AS INDICATED.
1.
2.
3.
4.
5.
6.
7.
8.
9.
GENERAL NOTES
ABBREVIATIONS
MATERIAL LEGEND
SYMBOL LEGEND
PARTITION TYPE NOTES
GYP BD ONE SIDE ONLY.
TOPS OF GYP BD ON PARTITIONS SHALL BE CUT TO THE
PROFILE OF THE METAL DECK ABOVE AND ALLOW SPACE FOR
ACOUSTIC SEALANT FOR ALL ACOUSTIC RATED PARTITIONS AND
OTHER PARTITIONS WHERE ACOUSTIC SEALANT IS SHOWN.
PROVIDE "UL" LISTED AND RATED JOINT SYSTEM FOR ALL
PENETRATIONS OF ALL FIRE RATED PARTITIONS.
PROVIDE ACOUSTIC INSULATION AND ACOUSTIC SEALANT AT ALL
PENETRATIONS OF ACOUSTIC RATED PARTITIONS.
FIRE RATED PLYWOOD ONE SIDE ONLY.
1.
2.
3.
4.
5.
PARTITION TYPE B
NOTE: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALE MUST BE USED.
GRAPHIC SCALE:
0 4" 8" 1'-4"
SCALE: 1 1/2" = 1'-0"
PARTITION TYPE - B
TYPE WIDTH
STUD
SIZE
MAX STUD
SPACING INSUL
FIRE
RATING UL # NOTES
B 4 7/8" 3 5/8" 16" OC 3 1/2" - -
B1 7 1/4" 6" 16" OC 3 1/2" - -
B2 4 7/8" 3 5/8" 16" OC 3 1/2" - -
B3 7 1/4" 6" 16" OC 5" - -
R E
F
POD A
POD D
POD C
POD B
MAIN ENTRANCE
SERVICE ENTRANCE
SUPPORT
FACILITY
(POD S)
(REFER TO TYPICAL
DOMICILARY POD
DEMOLITION PLAN AND
FLOOR PLAN ON SHEETS
AD102 & AS102)
(REFER TO TYPICAL DOMICILARY POD
DEMOLITION PLAN AND FLOOR PLAN
ON SHEETS AD102 & AS102, SIMILAR)
(REFER TO TYPICAL
DOMICILARY POD
DEMOLITION PLAN AND
FLOOR PLAN ON SHEETS
AD102 & AS102, SIMILAR,
EXEPT WHERE OTHERWISE
NOTED.)
(REFER TO TYPICAL DOMICILARY POD
DEMOLITION PLAN AND FLOOR PLAN
ON SHEETS AD102 & AS102, SIMILAR)
C3
AS401
C3
AS401
C3
AS401
C3
AS401
B5
AS401
B5
AS401
B5
AS401
B5
AS401
C1
AS401
D5
AS401
Date
Location
Checked Drawn
Drawing Number
Building Number
Project NumberProject TitleDrawingTitle
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
Dwg. of
A
B
C
D
E
F
Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
VA FORM 08-6231
th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
BOWMAN FOSTER
& ASSOCIATES, PC
ALEXANDRIA, VA 22312
6353 CENTER DR. STE 101
NORFOLK, VA 23502
5252 CHEROKEE AVE, STE 101
McPHERSON
DESIGN
GROUP p.c.
STRUCTURAL ENGINEERS
6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com
901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5
Engineers Surveyors Planners
HOGGARD/EURE ASSOCIATES, P.C.
FULLY SPRINKLERED
COMPOSITE FLOOR PLAN
AS002
VA MEDICAL CENTER, HAMPTON, VA
JDB DAS 21 165
590-602
7/26/19
RENOVATE AND EXPAND
DOMICILIARY BUILDING 148
NOTE: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALE MUST BE USED.
GRAPHIC SCALE:
0 48'
SCALE: 3/64" = 1'-0"
12' 24' 3/64" = 1'-0"
COMPOSITE FLOOR PLAN
PLAN
NORTH
UP
ELECTRICAL VAULT
MECHANICAL ROOM
EMERGENCY
GENERATOR
ROOM
STORAGE
STORAGE
EMS STORAGE
STORAGE
MAIN
TELEPHONE
CLOSET
ELECTRICAL
CLOSET
LOUNGE
CONFERENCE ROOM
GENERAL
STORAGE
E L E C
C L O S E T
OFFICE OFFICE
CHIEF
DOMICILLARY OFFICE
OFFICE
MAIN
ENTRANCE
EXISTING RECREATION
ROOM
VENDING
OFFICE
DOMICILLARY
CARE
OFFICE/
RECEPTION
PATIENT SCREENING
PATIENT
SCREENING
STORAGE
OFFICE
OFFICE
OFFICE
OFFICEOFFICE
H.A.C.
EXISTING
LIBRARY
EXISTING
FITNESS CENTER
2 1
TYP
TYP
11'-2"± 17'-4"± 43'-2"± 47'-0"±
161'-10"±
33'-10"± 8'-0"± 1'-4"± 47'-0"± 10'-4"± 32'-10"±
32'-10"±
10'-4"±
EXISTING
GROUP ROOM
13 13 1313
LINE OF
EXISTING VCT
S122
EXISTING MEN'S
S121
EXISTING WOMEN'S
S103
STORAGE
S102
TOILET
817 17
LINE OF
EXISTING VCT
EXISTING WALL AND/OR DOOR TO BE DEMOLISHED
EXISTING WINDOW TO BE DEMOLISHED
EXISTING WALL, WINDOW, AND/OR DOOR TO REMAIN
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
NOTE: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALE MUST BE USED.
DEMOLITION NOTES
REMOVE EXISTING WALLS WHERE INDICATED IN THEIR ENTIRETY.
REMOVE EXISTING DOORS TO INCLUDE FRAMES AND HARDWARE IN
THEIR ENTIRETY.
REMOVE EXISTING WALL WHERE INDICATED FOR NEW DOOR OPENING.
PREPARE WALL WITH NEW STUDS & DRYWALL TO INCLUDE ALL
BLOCKING AND HEADERS TO RECEIVE NEW HM FRAME AND WOOD
DOOR.
REMOVE EXISTING CARPET AND VCT TO INCLUDE ALL ADHESIVE IN
AREAS OF EXISTING LIBRARY AND FITNESS CENTER COMPLETE TO
EXISTING CONCRETE SLAB. PREPARE SLAB TO RECEIVE NEW FLOOR
FINISH.
REMOVE EXISTING CERAMIC TILE SHOWER ENCLOSURE IN ITS
ENTIRETY.
REMOVE EXISTING STOREFRONT AND WINDOW SYSTEM COMPLETE
WHERE INDICATED ON DEMOLITION PLAN TO INCLUDE WINDOW BLINDS
AND TREATMENTS.
REMOVE EXISTING PLUMBING FIXTURES, TOILET PARTITIONS, TOILET
ACCESSORIES IN THEIR ENTIRETY.
REMOVE EXISTING SINK AND ASSOCIATED PIPING. REMOVE ALL
DAMAGED DRYWALL AND REPLACE WITH NEW GYPSUM WALL BOARD TO
MATCH EXISTING WALL FINISH.
REMOVE EXISTING GYPSUM WALL BOARD AND CERAMIC TILE WHERE
INDICATED TO PROVIDE ACCESS TO EXISTING PLUMBING LINES BEHIND
THE EXISTING WALLS. EXISTING WALL FRAMING TO REMAIN. PREPARE
WALLS FOR INSTALLATION OF NEW GYPSUM BOARD AFTER NEW
PLUMBING WORK IS COMPLETE. REFER TO SHEET AS101 FOR NEW
WORK.
DEMOUNTABLE PARTITION SYSTEM FURNITURE ARE SHOWN FOR
GENERAL INFORMATION ONLY. REFER TO SHEET G-003 FOR NOTES ON
OWNER RESPONSIBILITY FOR EXISTING FF&E ITEMS.
REMOVE EXISTING EXTERIOR CANOPY AND SUPPORT FRAMING IN ITS
ENTIRETY.
REMOVE ALL EXISTING EPOXY TERRAZZO FLOORING AND CERAMIC TILE
WAINSCOT IN ITS ENTIRETY.
REMOVE EXISTING RADIANT HEATING BELOW EXISTING WINDOWS. REFER
TO MECHANICAL DRAWINGS FOR LIMITS OF WORK.
REMOVE EXISTING VCT FLOORING TO INCLUDE ALL ADHESIVE AND
EXISTING WALL BASE WHERE INDICATED.
EXISTING VCT FLOORING AND WALL BASE TO REMAIN.
REMOVE EXISTING PLUMBING FIXTURE AND DRYWALL TO PROVIDE
ACCESS TO EXISTING PLUMBING LINES. EXISTING WALL FRAMING MUST
REMAIN. REFER TO PLUMBING DRAWINGS FOR ADDITIONAL NOTES.
REMOVE EXISTING MECHANICAL GRILLES TO ENLARGE WALL OPENINGS
FOR NEW MECHANICAL WORK- REFRAME OPENING FOR NEW DUCT
SIZE. REFER TO MECHANICAL DRAWINGS.
(THIS SHEET ONLY)
GRAPHIC SCALE:
LEGEND
KEY PLAN (NOT TO SCALE)
A
B
C
D
PLAN
NORTH
SERVICE
ENTRANCE
MAIN
ENTRANCE
S
Date
Location
Checked Drawn
Drawing Number
Building Number
Project NumberProject TitleDrawingTitle
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
Dwg. of
A
B
C
D
E
F
Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
VA FORM 08-6231
th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
BOWMAN FOSTER
& ASSOCIATES, PC
ALEXANDRIA, VA 22312
6353 CENTER DR. STE 101
NORFOLK, VA 23502
5252 CHEROKEE AVE, STE 101
McPHERSON
DESIGN
GROUP p.c.
STRUCTURAL ENGINEERS
6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com
901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5
Engineers Surveyors Planners
HOGGARD/EURE ASSOCIATES, P.C.
FULLY SPRINKLERED
FLOOR PLAN 'S' POD - DEMOLITION
AD101
VA MEDICAL CENTER, HAMPTON, VA
JDB DAS 22 165
590-602
7/26/19
RENOVATE AND EXPAND
DOMICILIARY BUILDING 148
1/8" = 1'-0"
FLOOR PLAN 'S' POD - DEMOLITION
DAP OFFICE
LUGGAGE
STORAGE
KITCHENETTE
LAUNDRY
OFFICE
OFFICE
ELECTRICAL
CLOSET
STOR
COMM
CLOSET
HAC
STOR
STOR
BEDROOM
BEDROOM
LOUNGE
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
STORAGE
BEDROOM
H&CC
OFFICE
H&CC
RECEPTION
H&CC
MANAGER
ROOF
ACCESS
BEDROOM
BEDROOMBEDROOM
BEDROOM
NO CURE
BEDROOM
BEDROOM
DAP OFFICE
OFFICE
ELEC
CLOSET
BEDROOM
BEDROOM
BEDROOM
BEDROOM
LOUNGE
BEDROOM
BEDROOM
BEDROOM
BEDROOM BEDROOM
BEDROOM BEDROOM
STOR
COMM
STOR
ROOF
ACCESS
LOUNGE
MED FOS HOME
OFFICE
SOILED LINEN
H&CC NURSE OFFICE
82'-4"± 16'-8"± 66'-9"± 14'-6"±
180'-3"±
17'-7"± 46'-1"± 39'-0"± 17'-0"± 35'-8"± 10'-4"± 14'-7"±
56'-0"±
6 6
6 6 6
6 6 6
6 6
COURTYARD
3 3 3
3 3
3 3
3 3
8 8
8 8
REDO COMPLETELY.
TYP. FOR POD'S
A,B,C,D.
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
NOTE: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALE MUST BE USED.
GRAPHIC SCALE:
KEY PLAN (NOT TO SCALE)
A
B
C
D
PLAN
NORTH
SERVICE
ENTRANCE
MAIN
ENTRANCE
EXISTING WALL AND/OR DOOR TO BE DEMOLISHED
EXISTING WINDOW TO BE DEMOLISHED
EXISTING WALL, WINDOW, AND/OR DOOR TO REMAIN
LEGEND
S
DEMOLITION NOTES
REMOVE EXISTING WALLS WHERE INDICATED IN THEIR ENTIRETY.
REMOVE EXISTING DOORS TO INCLUDE FRAMES AND HARDWARE IN
THEIR ENTIRETY.
REMOVE WALL-MOUNTED HVAC INDUCTION UNIT AND WINDOW STOOL
COMPLETE. REFER TO MECHANICAL DRAWINGS AND DETAIL
REMOVE EXISTING PLUMBING FIXTURE AND DRYWALL TO PROVIDE
ACCESS TO EXISTING PLUMBING LINES. EXISTING WALL FRAMING MUST
REMAIN. REFER TO PLUMBING DRAWINGS FOR ADDITIONAL NOTES.
REMOVE EXISTING CERAMIC TILE SHOWER ENCLOSURE IN ITS
ENTIRETY.
REMOVE EXISTING STOREFRONT AND WINDOW SYSTEM COMPLETE
WHERE INDICATED ON DEMOLITION PLAN TO INCLUDE WINDOW BLINDS
AND TREATMENTS.
REMOVE EXISTING PLUMBING FIXTURES, TOILET PARTITIONS, TOILET
ACCESSORIES IN THEIR ENTIRETY.
REMOVE EXISTING GYPSUM WALL BOARD AND CERAMIC TILE WHERE
INDICATED TO PROVIDE ACCESS TO EXISTING PLUMBING LINES BEHIND
THE EXISTING WALLS. EXISTING WALL FRAMING TO REMAIN. PREPARE
WALLS FOR INSTALLATION OF NEW GYPSUM BOARD AFTER NEW
PLUMBING WORK IS COMPLETE. REFER TO SHEET AS102 FOR NEW
WORK.
REMOVE EXISTING EPOXY TERRAZZO FLOORING AND CERAMIC TILE
WAINSCOT IN ITS ENTIRETY IN THIS SPACE.
(THIS SHEET ONLY)
/A1 AS501
Date
Location
Checked Drawn
Drawing Number
Building Number
Project NumberProject TitleDrawingTitle
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
Dwg. of
A
B
C
D
E
F
Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
VA FORM 08-6231
th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
BOWMAN FOSTER
& ASSOCIATES, PC
ALEXANDRIA, VA 22312
6353 CENTER DR. STE 101
NORFOLK, VA 23502
5252 CHEROKEE AVE, STE 101
McPHERSON
DESIGN
GROUP p.c.
STRUCTURAL ENGINEERS
6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com
901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5
Engineers Surveyors Planners
HOGGARD/EURE ASSOCIATES, P.C.
FULLY SPRINKLERED
FLOOR PLAN TYPICAL POD -
DEMOLITION
AD102
VA MEDICAL CENTER, HAMPTON, VA
JDB DAS 23 165
590-602
7/26/19
RENOVATE AND EXPAND
DOMICILIARY BUILDING 148
1/8" = 1'-0"
FLOOR PLAN TYPICAL POD - DEMOLITION - (POD B SHOWN - POD'S A, C, & D SIM.)
CORRIDOR
TO POD B
CORRIDOR
TO POD A
CORRIDOR
TO POD D
CORRIDOR
TO POD C
1 1
5 5 5
5 5
5 5
5 5
PROJECTION
SCREEN
ENCLOSURE
ELEC. CLOSET
F3
AS301
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
NOTE: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALE MUST BE USED.
GRAPHIC SCALE:
KEY PLAN (NOT TO SCALE)
A
B
C
D
PLAN
NORTH
LEGEND
EXISTING PARTITIONS
GYP BD CEILING
EXISTING 2x2 ACT CEILING TO REMAIN
AIR SUPPLY DIFFUSER
EXISTING 2x4 LIGHT FIXTURE TO REMAIN
DEMOLITION NOTES
REMOVE EXISTING ACOUSTICAL CEILING TILE, GRID, LIGHT FIXTURES
AND ALL OTHER CEILING MOUNTED UTILITIES THAT ARE NOT
INDICATED ON THESE DRAWINGS.
REMOVE EXISTING GYPSUM BOARD CEILING TO INCLUDE FRAMING,
LIGHTS AND ALL OTHER CEILING MOUNTED UTILITIES COMPLETE.
REMOVE EXISTING ACT BULKHEAD IN ITS ENITIRETY.
REMOVE EXISTING EXTERIOR SOFFIT WHERE INDICATED ON DRAWINGS.
REMOVE EXISTING ACT CEILING TO INCLUDE GRID. SALVAGE EXISTING
LIGHTING, FIRE PROTECTION AND OTHER CEILING MOUNTED ITEMS
UNLESS OTHERWISE NOTED FOR REINSTALLATION IN NEW CEILINGS
AFTER MECHANICAL WORK IS COMPLETE. REFER TO SHEET AS103
FOR NEW WORK.
REMOVE EXISTING GYPSUM BOARD CEILING TO INCLUDE GRID.
SALVAGE EXISTING LIGHTING, FIRE PROTECTION AND OTHER CEILING
MOUNTED ITEMS UNLESS OTHERWISE NOTED FOR REINSTALLATION IN
NEW CEILINGS AFTER MECHANICAL WORK IS COMPLETE. REFER TO
SHEET AS103 FOR NEW WORK
REMOVE EXISTING CONCEALED OVERHEAD SECURITY ASSEMBLY.
REFER TO AS103 FOR NEW BULKHED.
AIR RETURN DIFFUSER
RECESSED LIGHT FIXTURE
EXPOSED TO STRUCTURE
EXIT SIGN, CEILING MOUNTED
EXIT SIGN, WALL MOUNTED
EXISTING 1x4 LIGHT FIXTURE TO REMAIN
(THIS SHEET ONLY)
EXISTING 2x2 LIGHT FIXTURE TO REMAIN
EXISTING PARTITIONS TO BE DEMOLISHED
NO DEMOLITION IN THIS AREA (THIS SHEET ONLY). REFER TO
PLUMBING, MECHANICAL, AND ELECTRICAL SHEETS FOR
DEMOLITION NOT SHOWN ON THIS SHEET.
EXISTING 2x2 ACT CEILING TO BE DEMOLISHED
EXISTING 1x4 LIGHT FIXTURE TO BE DEMOLISHED
EXISTING 2x4 LIGHT FIXTURE TO BE DEMOLISHED
SERVICE
ENTRANCE
MAIN
ENTRANCE
EXISTING PARTITIONS TO UNDERSIDE OF CEILING
S
Date
Location
Checked Drawn
Drawing Number
Building Number
Project NumberProject TitleDrawingTitle
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
Dwg. of
A
B
C
D
E
F
Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
VA FORM 08-6231
th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
BOWMAN FOSTER
& ASSOCIATES, PC
ALEXANDRIA, VA 22312
6353 CENTER DR. STE 101
NORFOLK, VA 23502
5252 CHEROKEE AVE, STE 101
McPHERSON
DESIGN
GROUP p.c.
STRUCTURAL ENGINEERS
6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com
901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5
Engineers Surveyors Planners
HOGGARD/EURE ASSOCIATES, P.C.
FULLY SPRINKLERED
REFLECTED CEILING PLAN 'S' POD -
DEMOLITION
AD103
VA MEDICAL CENTER, HAMPTON, VA
JDB DAS 24 165
590-602
7/26/19
RENOVATE AND EXPAND
DOMICILIARY BUILDING 148
PLAN
NORTH
1/8" = 1'-0"
REFLECTED CEILING PLAN 'S' POD - DEMOLITION
CORRIDOR TO
SUPPORT FACILITY
1 1
3 3
ELEC.
CLOSET
TYP.
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
NOTE: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALE MUST BE USED.
GRAPHIC SCALE:
KEY PLAN (NOT TO SCALE)
A
B
C
D
PLAN
NORTH
LEGEND
EXISTING PARTITIONS
GYP BD CEILING
EXISTING 2x2 ACT CEILING TO REMAIN
AIR SUPPLY DIFFUSER
EXISTING 2x4 LIGHT FIXTURE TO REMAIN
DEMOLITION NOTES
REMOVE EXISTING ACT CEILING TO INCLUDE GRID. SALVAGE EXISTING
LIGHTING, FIRE PROTECTION AND OTHER CEILING MOUNTED ITEMS
UNLESS OTHERWISE NOTED FOR REINSTALLATION IN NEW CEILINGS
AFTER MECHANICAL WORK IS COMPLETE.
REMOVE EXISTING EXTERIOR PLASTER CEILING SYSTEM TO INCLUDE
LIGHT FIXTURES COMPLETE. EXISTING WOOD FRAMING SHALL REMAIN.
EXISTING PLASTER SOFFIT TO REMAIN UNLESS OTHERWISE NOTED -
TYPICAL.
AIR RETURN DIFFUSER
RECESSED LIGHT FIXTURE TO BE DEMOLISHED
EXPOSED TO STRUCTURE
EXISTING EXIT SIGN TO REMAIN
EXISTING 1x4 LIGHT FIXTURE TO REMAIN
(THIS SHEET ONLY)
EXISTING 1x2 LIGHT FIXTURE TO REMAIN
EXISTING PARTITIONS TO BE DEMOLISHED
EXISTING 2x2 ACT CEILING TO BE DEMOLISHED
EXISTING 2x4 LIGHT FIXTURE TO BE DEMOLISHED
SERVICE
ENTRANCE
MAIN
ENTRANCE
EXISTING PARTITIONS TO UNDERSIDE OF CEILING
RECESSED LIGHT FIXTURE TO REMAIN
S
GENERAL NOTES
1. REFER TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE
PROTECTION DRAWINGS FOR ITEMS NOT SHOWN ON THESE
DRAWINGS.
Date
Location
Checked Drawn
Drawing Number
Building Number
Project NumberProject TitleDrawingTitle
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
Dwg. of
A
B
C
D
E
F
Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
VA FORM 08-6231
th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
BOWMAN FOSTER
& ASSOCIATES, PC
ALEXANDRIA, VA 22312
6353 CENTER DR. STE 101
NORFOLK, VA 23502
5252 CHEROKEE AVE, STE 101
McPHERSON
DESIGN
GROUP p.c.
STRUCTURAL ENGINEERS
6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com
901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5
Engineers Surveyors Planners
HOGGARD/EURE ASSOCIATES, P.C.
FULLY SPRINKLERED
REFLECTED CEILING PLAN 'A' POD -
DEMOLITION
AD104
VA MEDICAL CENTER, HAMPTON, VA
JDB DAS 25 165
590-602
7/26/19
RENOVATE AND EXPAND
DOMICILIARY BUILDING 148
PLAN
NORTH
REFLECTED CEILING PLAN 'A' POD - DEMOLITION
DAP OFFICE
LUGGAGE
STORAGE
KITCHENETTE
LAUNDRY
OFFICE
OFFICE
ELECTRICAL
CLOSET
STOR
COMM
CLOSET
HAC
STOR
STOR
BEDROOM
BEDROOM
LOUNGE
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
STORAGE
BEDROOM
H&CC
OFFICE
H&CC
RECEPTION
H&CC
MANAGER
ROOF
ACCESS
BEDROOM
BEDROOMBEDROOM
BEDROOM
NO CURE
BEDROOM
BEDROOM
DAP OFFICE OFFICE
ELEC
CLOSET
BEDROOM
BEDROOM
BEDROOM
BEDROOM
LOUNGE
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM BEDROOM
STOR
COMM
STOR
ROOF
ACCESS
LOUNGE
MED FOS HOME
OFFICE
SOILED LINEN
H&CC NURSE OFFICE
COURTYARD
1 1
1 1
TYP.
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
NOTE: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALE MUST BE USED.
GRAPHIC SCALE:
KEY PLAN (NOT TO SCALE)
A
B
C
D
PLAN
NORTH
SERVICE
ENTRANCE
MAIN
ENTRANCE
S
LEGEND
EXISTING PARTITIONS
GYP BD CEILING
EXISTING 2x2 ACT CEILING TO REMAIN
AIR SUPPLY DIFFUSER
EXISTING 2x4 LIGHT FIXTURE TO REMAIN
DEMOLITION NOTES
REMOVE EXISTING ACT CEILING TO INCLUDE GRID. SALVAGE EXISTING
LIGHTING, FIRE PROTECTION AND OTHER CEILING MOUNTED ITEMS
UNLESS OTHERWISE NOTED FOR REINSTALLATION IN NEW CEILINGS
AFTER MECHANICAL WORK IS COMPLETE.
REMOVE EXISTING EXTERIOR PLASTER CEILING SYSTEM TO INCLUDE
LIGHT FIXTURES COMPLETE. EXISTING WOOD FRAMING SHALL REMAIN.
EXISTING PLASTER SOFFIT TO REMAIN UNLESS OTHERWISE NOTED -
TYPICAL.
AIR RETURN DIFFUSER
RECESSED LIGHT FIXTURE TO BE DEMOLISHED
EXPOSED TO STRUCTURE
EXISTING EXIT SIGN TO REMAIN
EXISTING 1x4 LIGHT FIXTURE TO REMAIN
(THIS SHEET ONLY)
EXISTING 1x2 LIGHT FIXTURE TO REMAIN
EXISTING PARTITIONS TO BE DEMOLISHED
EXISTING 2x2 ACT CEILING TO BE DEMOLISHED
EXISTING 2x4 LIGHT FIXTURE TO BE DEMOLISHED
EXISTING PARTITIONS TO UNDERSIDE OF CEILING
RECESSED LIGHT FIXTURE TO REMAIN
GENERAL NOTES
1. REFER TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE
PROTECTION DRAWINGS FOR ITEMS NOT SHOWN ON THESE
DRAWINGS.
Date
Location
Checked Drawn
Drawing Number
Building Number
Project NumberProject TitleDrawingTitle
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
Dwg. of
A
B
C
D
E
F
Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
VA FORM 08-6231
th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
BOWMAN FOSTER
& ASSOCIATES, PC
ALEXANDRIA, VA 22312
6353 CENTER DR. STE 101
NORFOLK, VA 23502
5252 CHEROKEE AVE, STE 101
McPHERSON
DESIGN
GROUP p.c.
STRUCTURAL ENGINEERS
6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com
901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5
Engineers Surveyors Planners
HOGGARD/EURE ASSOCIATES, P.C.
FULLY SPRINKLERED
REFLECTED CEILING PLAN 'B' POD -
DEMOLITION
AD105
VA MEDICAL CENTER, HAMPTON, VA
JDB DAS 26 165
590-602
7/26/19
RENOVATE AND EXPAND
DOMICILIARY BUILDING 148
1/8" = 1'-0"
REFLECTED CEILING PLAN 'B' POD - DEMOLITION
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
NOTE: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALE MUST BE USED.
GRAPHIC SCALE:
KEY PLAN (NOT TO SCALE)
A
B
C
D
PLAN
NORTH
SERVICE
ENTRANCE
MAIN
ENTRANCE
S
LEGEND
EXISTING PARTITIONS
GYP BD CEILING
EXISTING 2x2 ACT CEILING TO REMAIN
AIR SUPPLY DIFFUSER
EXISTING 2x4 LIGHT FIXTURE TO REMAIN
DEMOLITION NOTES
REMOVE EXISTING ACT CEILING TO INCLUDE GRID. SALVAGE EXISTING
LIGHTING, FIRE PROTECTION AND OTHER CEILING MOUNTED ITEMS
UNLESS OTHERWISE NOTED FOR REINSTALLATION IN NEW CEILINGS
AFTER MECHANICAL WORK IS COMPLETE.
REMOVE EXISTING EXTERIOR PLASTER CEILING SYSTEM TO INCLUDE
LIGHT FIXTURES COMPLETE. EXISTING WOOD FRAMING SHALL REMAIN.
EXISTING PLASTER SOFFIT TO REMAIN UNLESS OTHERWISE NOTED -
TYPICAL.
AIR RETURN DIFFUSER
RECESSED LIGHT FIXTURE TO BE DEMOLISHED
EXPOSED TO STRUCTURE
EXISTING EXIT SIGN TO REMAIN
EXISTING 1x4 LIGHT FIXTURE TO REMAIN
(THIS SHEET ONLY)
EXISTING 1x2 LIGHT FIXTURE TO REMAIN
EXISTING PARTITIONS TO BE DEMOLISHED
EXISTING 2x2 ACT CEILING TO BE DEMOLISHED
EXISTING 2x4 LIGHT FIXTURE TO BE DEMOLISHED
EXISTING PARTITIONS TO UNDERSIDE OF CEILING
RECESSED LIGHT FIXTURE TO REMAIN
GENERAL NOTES
1. REFER TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE
PROTECTION DRAWINGS FOR ITEMS NOT SHOWN ON THESE
DRAWINGS.
CORRIDOR TO
SUPPORT FACILITY
1 1 1
1 1
1 1
1 1
1 1
COURTYARD
TYP.
Date
Location
Checked Drawn
Drawing Number
Building Number
Project NumberProject TitleDrawingTitle
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
Dwg. of
A
B
C
D
E
F
Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
VA FORM 08-6231
th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
BOWMAN FOSTER
& ASSOCIATES, PC
ALEXANDRIA, VA 22312
6353 CENTER DR. STE 101
NORFOLK, VA 23502
5252 CHEROKEE AVE, STE 101
McPHERSON
DESIGN
GROUP p.c.
STRUCTURAL ENGINEERS
6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com
901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5
Engineers Surveyors Planners
HOGGARD/EURE ASSOCIATES, P.C.
FULLY SPRINKLERED
REFLECTED CEILING PLAN 'C' POD -
DEMOLITION
AD106
VA MEDICAL CENTER, HAMPTON, VA
JDB DAS 27 165
590-602
7/26/19
RENOVATE AND EXPAND
DOMICILIARY BUILDING 148
REFLECTED CEILING PLAN 'C' POD - DEMOLITION
NOTE: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALE MUST BE USED.
GRAPHIC SCALE:
KEY PLAN (NOT TO SCALE)
A
B
C
D
PLAN
NORTH
SERVICE
ENTRANCE
MAIN
ENTRANCE
S
LEGEND
EXISTING PARTITIONS
GYP BD CEILING
EXISTING 2x2 ACT CEILING TO REMAIN
AIR SUPPLY DIFFUSER
EXISTING 2x4 LIGHT FIXTURE TO REMAIN
DEMOLITION NOTES
REMOVE EXISTING ACT CEILING TO INCLUDE GRID. SALVAGE EXISTING
LIGHTING, FIRE PROTECTION AND OTHER CEILING MOUNTED ITEMS
UNLESS OTHERWISE NOTED FOR REINSTALLATION IN NEW CEILINGS
AFTER MECHANICAL WORK IS COMPLETE.
REMOVE EXISTING EXTERIOR PLASTER CEILING SYSTEM TO INCLUDE
LIGHT FIXTURES COMPLETE. EXISTING WOOD FRAMING SHALL REMAIN.
EXISTING PLASTER SOFFIT TO REMAIN UNLESS OTHERWISE NOTED -
TYPICAL.
AIR RETURN DIFFUSER
RECESSED LIGHT FIXTURE TO BE DEMOLISHED
EXPOSED TO STRUCTURE
EXISTING EXIT SIGN TO REMAIN
EXISTING 1x4 LIGHT FIXTURE TO REMAIN
(THIS SHEET ONLY)
EXISTING 1x2 LIGHT FIXTURE TO REMAIN
EXISTING PARTITIONS TO BE DEMOLISHED
EXISTING 2x2 ACT CEILING TO BE DEMOLISHED
EXISTING 2x4 LIGHT FIXTURE TO BE DEMOLISHED
EXISTING PARTITIONS TO UNDERSIDE OF CEILING
RECESSED LIGHT FIXTURE TO REMAIN
GENERAL NOTES
1. REFER TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE
PROTECTION DRAWINGS FOR ITEMS NOT SHOWN ON THESE
DRAWINGS.
CORRIDOR TO
SUPPORT
FACILITY
1 1
1 1
1 1
1 1
1 1
COURTYARD
TYP.
F4
AS601
Date
Location
Checked Drawn
Drawing Number
Building Number
Project NumberProject TitleDrawingTitle
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
Dwg. of
A
B
C
D
E
F
Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
VA FORM 08-6231
th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
BOWMAN FOSTER
& ASSOCIATES, PC
ALEXANDRIA, VA 22312
6353 CENTER DR. STE 101
NORFOLK, VA 23502
5252 CHEROKEE AVE, STE 101
McPHERSON
DESIGN
GROUP p.c.
STRUCTURAL ENGINEERS
6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com
901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5
Engineers Surveyors Planners
HOGGARD/EURE ASSOCIATES, P.C.
FULLY SPRINKLERED
REFLECTED CEILING PLAN 'D' POD -
DEMOLITION
AD107
VA MEDICAL CENTER, HAMPTON, VA
JDB DAS 28 165
590-602
7/26/19
RENOVATE AND EXPAND
DOMICILIARY BUILDING 148
REFLECTED CEILING PLAN 'D' POD - DEMOLITION
CORRIDOR
TO POD A
CORRIDOR
TO POD D
CORRIDOR
TO POD C
TYP
TYP
TYP
TYP
TYP
TYP
TYP
TYP
TYP
TYP
TYP
TYP
TYP
TYP
TYP
TYP
F3
AS301
B1
AS302
3 3
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
NOTE: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALE MUST BE USED.
DEMOLITION NOTES
EXISTING MEMBRANE ROOF SYSTEM TO REMAIN.
REMOVE EXISTING STANDING SEAM ROOF, SHEATHING, ROOF AND
SOFFIT FRAMING COMPLETE.
EXISTING WOOD STUD WALL FRAMING, METAL PANELS, DOORS AND
LOUVERS SHALL REMAIN. REMOVE EXISTING METAL ROOF FASCIA AND
TRIM TO INCLUDE GUTTERS.
EXISTING STANDING SEAM METAL ROOF AND FASCIA TO REMAIN.
SCRAPE EXISTING STANDING SEAM METAL ROOFING AND FASCIA TO
REMOVE ALL RUST AND CORROSION, AND PREPARE SURFACE FOR
REFINISHING, AS INDICATED ON THE NEW WORK ROOF PLANS.
REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR EXISTING
EQUIPMENT AND ROOF PENETRATIONS WORK NOTES.
REMOVE EXISTING BUILT-UP ROOF SYSTEM AND METAL WALL
PANELS - REFER TO NEW WORK PLANS FOR EXTENT OF NEW ROOF
AND DETAILS.
(THIS SHEET ONLY)
GRAPHIC SCALE:
KEY PLAN (NOT TO SCALE)
A
B
C
D
PLAN
NORTH
SERVICE
ENTRANCE
MAIN
ENTRANCE
S
Date
Location
Checked Drawn
Drawing Number
Building Number
Project NumberProject TitleDrawingTitle
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
Dwg. of
A
B
C
D
E
F
Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
VA FORM 08-6231
th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
BOWMAN FOSTER
& ASSOCIATES, PC
ALEXANDRIA, VA 22312
6353 CENTER DR. STE 101
NORFOLK, VA 23502
5252 CHEROKEE AVE, STE 101
McPHERSON
DESIGN
GROUP p.c.
STRUCTURAL ENGINEERS
6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com
901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5
Engineers Surveyors Planners
HOGGARD/EURE ASSOCIATES, P.C.
FULLY SPRINKLERED
ROOF PLAN 'S' POD - DEMOLITION
AD108
VA MEDICAL CENTER, HAMPTON, VA
JDB DAS 29 165
590-602
7/26/19
RENOVATE AND EXPAND
DOMICILIARY BUILDING 148
PLAN
NORTH
ROOF PLAN 'S' POD - DEMOLITION
COURTYARD
TYP
TYP
4 TYP
4 TYP
4 TYP
4TYP 5
4 TYP
4 TYP
4TYP
4TYP
TYP
TYP
TYP
TYP
TYP
4TYP
TYP
4 TYP
TYP
TYP
TYP
TYP
3TYP
TYP
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
NOTE: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALE MUST BE USED.
DEMOLITION NOTES
EXISTING ROOF SYSTEM TO REMAIN
NOT USED
EXISTING METAL PANEL WALL, FRAMING, AND DOORS TO REMAIN.
EXISTING STANDING SEAM METAL ROOF AND FASCIA TO REMAIN.
SCRAPE EXISTING STANDING SEAM METAL ROOFING AND FASCIA TO
REMOVE ALL RUST AND CORROSION, AND PREPARE SURFACE FOR
REFINISHING, AS INDICATED ON THE NEW WORK ROOF PLANS.
EXISTING STANDING SEAM METAL ROOF AND FASCIA TO REMAIN.
SCRAPE EXISTING STANDING SEAM METAL ROOFING AND FASCIA TO
REMOVE ALL RUST AND CORROSION, AND PREPARE SURFACE FOR
REFINISHING, AS INDICATED ON THE NEW WORK ROOF PLANS.
EXISTING ROOF HATCH TO REMAIN.
(THIS SHEET ONLY)
GRAPHIC SCALE:
KEY PLAN (NOT TO SCALE)
A
B
C
D
PLAN
NORTH
SERVICE
ENTRANCE
MAIN
ENTRANCE
S
Date
Location
Checked Drawn
Drawing Number
Building Number
Project NumberProject TitleDrawingTitle
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
Dwg. of
A
B
C
D
E
F
Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
VA FORM 08-6231
th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
BOWMAN FOSTER
& ASSOCIATES, PC
ALEXANDRIA, VA 22312
6353 CENTER DR. STE 101
NORFOLK, VA 23502
5252 CHEROKEE AVE, STE 101
McPHERSON
DESIGN
GROUP p.c.
STRUCTURAL ENGINEERS
6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com
901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5
Engineers Surveyors Planners
HOGGARD/EURE ASSOCIATES, P.C.
FULLY SPRINKLERED
ROOF PLAN TYPICAL POD -
DEMOLITION
AD109
VA MEDICAL CENTER, HAMPTON, VA
JDB DAS 30 165
590-602
7/26/19
RENOVATE AND EXPAND
DOMICILIARY BUILDING 148
1/8" = 1'-0"
ROOF PLAN TYPICAL POD - DEMOLITION - (POD B SHOWN - POD'S A, C, & D SIM.)
NOTE: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALE MUST BE USED.
GRAPHIC SCALE:
KEY PLAN (NOT TO SCALE)
A
B
C
D
PLAN
NORTH
SERVICE
ENTRANCE
MAIN
ENTRANCE
S
EXISTING WALL AND/OR DOOR TO BE DEMOLISHED
EXISTING WINDOW TO BE DEMOLISHED
EXISTING WALL, WINDOW, AND/OR DOOR TO REMAIN
LEGEND
DEMOLITION NOTES
REMOVE EXISTING WALLS WHERE INDICATED IN THEIR ENTIRETY.
REMOVE EXISTING DOORS TO INCLUDE FRAMES AND HARDWARE IN
THEIR ENTIRETY.
REMOVE WALL-MOUNTED HVAC INDUCTION UNIT AND WINDOW STOOL
COMPLETE. REFER TO MECHANICAL DRAWINGS AND DETAIL
REMOVE EXISTING PLUMBING FIXTURE AND DRYWALL TO PROVIDE
ACCESS TO EXISTING PLUMBING LINES. EXISTING WALL FRAMING MUST
REMAIN. REFER TO PLUMBING DRAWINGS FOR ADDITIONAL NOTES.
REMOVE EXISTING CERAMIC TILE SHOWER ENCLOSURE IN ITS
ENTIRETY.
NOT USED.
REMOVE EXISTING PLUMBING FIXTURES, TOILET PARTITIONS, TOILET
ACCESSORIES IN THEIR ENTIRETY.
REMOVE EXISTING GYPSUM WALL BOARD AND CERAMIC TILE WHERE
INDICATED TO PROVIDE ACCESS TO EXISTING PLUMBING LINES BEHIND
THE EXISTING WALLS. EXISTING WALL FRAMING TO REMAIN. PREPARE
WALLS FOR INSTALLATION OF NEW GYPSUM BOARD AFTER NEW
PLUMBING WORK IS COMPLETE. REFER TO SHEET AS902 FOR NEW
WORK.
REMOVE EXISTING EPOXY TERRAZZO FLOORING AND CERAMIC TILE
WAINSCOT IN ITS ENTIRETY IN THIS SPACE.
(THIS SHEET ONLY)
/A1 AS501
DAP OFFICE
LUGGAGE
STORAGE
KITCHENETTE
LAUNDRY
OFFICE
OFFICE
ELECTRICAL
CLOSET
STOR
COMM
CLOSET
HAC
STOR
STOR
BEDROOM
BEDROOM
LOUNGE
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
STORAGE
BEDROOM
H&CC
OFFICE
H&CC
RECEPTION
H&CC
MANAGER
ROOF
ACCESS
BEDROOM
BEDROOMBEDROOM
BEDROOM
NO CURE
BEDROOM
BEDROOM
DAP OFFICE
OFFICE
ELEC
CLOSET
BEDROOM
BEDROOM
BEDROOM
BEDROOM
LOUNGE
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM BEDROOM
STOR
COMM
STOR
ROOF
ACCESS
LOUNGE
MED FOS HOME
OFFICE
SOILED LINEN
H&CC NURSE OFFICE
82'-4"± 16'-8"± 66'-9"± 14'-6"±
180'-3"±
17'-7"± 46'-1"± 39'-0"± 17'-0"± 35'-8"± 10'-4"± 14'-7"±
56'-0"±
COURTYARD
3 3
3 3 3
3 3 3
3 3
8 8
8 8
REDO COMPLETELY.
TYP. FOR POD'S
A,B,C,D.
Date
Location
Checked Drawn
Drawing Number
Building Number
Project NumberProject TitleDrawingTitle
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
Dwg. of
A
B
C
D
E
F
Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
VA FORM 08-6231
th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
BOWMAN FOSTER
& ASSOCIATES, PC
ALEXANDRIA, VA 22312
6353 CENTER DR. STE 101
NORFOLK, VA 23502
5252 CHEROKEE AVE, STE 101
McPHERSON
DESIGN
GROUP p.c.
STRUCTURAL ENGINEERS
6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com
901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5
Engineers Surveyors Planners
HOGGARD/EURE ASSOCIATES, P.C.
FULLY SPRINKLERED
FLOOR PLAN TYPICAL POD -
DEMOLITION - BID DEDUCT
AD902
VA MEDICAL CENTER, HAMPTON, VA
JDB DAS 31 165
590-602
7/26/19
RENOVATE AND EXPAND
DOMICILIARY BUILDING 148
PLAN
NORTH
1/8" = 1'-0"
FLOOR PLAN TYPICAL POD - DEMOLITION - BID DEDUCT
**NOTE: DEMOLITION INDICATED ON THIS
SHEET APPLIES TO PODS 'A', 'B',
'C', AND 'D'. POD 'B' IS SHOWN.
UPUP
A1
AS201
C1
AS201
xH xH x2 x2 x1 x1 x3 x3 x4 x4 x5 x5 x6 x6 x7 x7 xL xL xK xK xJ xJ xG xG xF xF xE xE xD xD xB xB xC xC xA xA
CORRIDOR
TO POD B
CORRIDOR
TO POD A
CORRIDOR
TO POD D
CORRIDOR
TO POD C
EMERGENCY
GENERATOR
ROOM
STORAGE
MAIN
TELEPHONE
CLOSET
ELECTRICAL
CLOSET
LOUNGE
GENERAL
STORAGE
OFFICE OFFICE
CHIEF
DOMICILLARY OFFICE
OFFICE
MAIN
ENTRANCE
S136B
EXISTING
RECREATION
ROOM
VENDING
DOMICILLARY
CARE
OFFICE/
RECEPTION
STORAGE
OFFICE
OFFICE
OFFICE
OFFICEOFFICE
H.A.C.
ELECTRICAL VAULT
MECHANICAL ROOM
STORAGE
EMS STORAGE
STORAGE
CONFERENCE ROOM
OFFICE
S115
PATIENT SCREENING
C1
AS401
D5
AS401
S134C
S134A S134B
S122
S115
A L
IG
N
ALIGN
A
8'-0"
1'-4"
5'-10"
1'-0"
7'-0"
1'-0"
7'-0"
1'-0"
7'-0"
1'-0"
5'-10"
1'-0"+/-
8'-8 1/4" 3'-0"
EQ
1'-0"
7'-2"
1'-0"
EQ
1'-0"
7'-2"
1'-0"
1'-0"
14'-0"
1'-0"
15'-0"
1'-0"
14'-0"
1'-0"
B
B B B
B
AS401
S121
EXISTING
WOMEN'S
S122
EXISTING
MEN'S
S142
LIBRARY
S134
GROUP ROOM
S
S T O R A G E
S102
TOILET
E1
AS201
E1
AS201
A6
AS201
S136A
FITNESS
ROOM
S135
CORRIDOR
F1
AS302
F3
AS302
F1
AS301
ELEC. CLOSET
A2
ALIGN
D E D
F C C C F
A L
IG
N
A L
IG
N
8'-8 3/8"
C8
AS501
F8
AS501
F3
AS501
A2 TYP.
2"2"
G
F3
AS301
S135
E6
AS301
A1
E8
AS301
E1
6 6
C8
AS501
F8
AS501
F8
AS501
S141
WOMEN'S
S140
MEN'S
C8
AS501
C8
AS501
EXISTING WALL, WINDOW, AND/OR DOOR TO REMAIN
GENERAL NOTES
SEE ENLARGED PLAN FOR PARTITION TYPES NOT INDICATED.
SUPPORT FACILITY EXISTING GROSS SQUARE FOOTAGE IS 19,725 SF.
SUPPORT FACILITY RENOVATED SQUARE FOOTAGE IS 3,210 SF.
SUPPORT FACILITY NEW SQUARE FOOTAGE IS 1,911 SF.
REMOVE WALL NEAR GENERAL STORAGE, ADD FLOORING TO MATCH
EXISTING VCT IN COLOR, SIZE, AND KIND.
ALL NEW WALLS AND EXISTING ADJACENT WALLS MUST BE PAINTED.
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
NOTE: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALE MUST BE USED.
CONSTRUCTION NOTES
PROVIDE 8' HIGH TEMPERED GLASS MIRROR, FULL WIDTH OF WALL
INDICATED WITH J-CHANNEL AT BOTTOM.
PROVIDE NEW GYPSUM WALL BOARD ON ALL EXISTING AND NEW
STUDS, REFER TO FINISH PLANS AND SCHEDULE FOR NEW FINISHES.
REFER TO SHEET AS401 FOR ADDITIONAL WORK.
PROVIDE 5/8” GYPSUM WALL BOARD ON EXISTING WALL FRAMING,
FULL WIDTH AND HEIGHT TO MATCH EXISTING GYPSUM BOARD. AFTER
NEW PLUMBING HAS BEEN COMPLETE. SAND JOINT SMOOTH AND ALL
EXPOSED GYPSUM WALL BOARD IN SPACE MUST BE PAINTED. SEE
FINISH SCHEDULE FOR PAINT FINISHES.
PROVIDE 5/8” GYPSUM WALL BOARD ON EXISTING WALL FRAMING,
FULL WIDTH AND HEIGHT OF WALL INDICATED. PROVIDE 4” X 4”
CERAMIC TILE WAINSCOT WITH BULLNOSE TOP TRIM TO 4’-6” A.F.F.
GYPSUM WALL BOARD SHALL BE ALIGNED WITH THE FACE OF
ADJACENT EXISTING GYPSUM BOARD, SANDED SMOOTH, AND EXPOSED
GYPSUM WALL BOARD ABOVE THE TILE WAINSCOT SHALL BE PAINTED.
SEE FINISH SCHEDULE FOR TILE AND PAINT SELECTIONS.
PROVIDE NEW ALUMINUM STOREFRONT WITH 1/4" TEMPERED CLEAR
GLASS. REFER TO INTERIOR WINDOW ELEVATIONS FOR SIZE AND
DETAILS, SHEET AS601.
PROVIDE 7/8" METAL FURRING AND 5/8" GYPSUM WALL BOARD OVER
EXISTING BRICK AND EXISTING STUD WALLS FULL HEIGHT TO 6"
ABOVE CEILING.
PROVIDE NEW EXTERIOR ALUMINUM STOREFRONT SYSTEM WITH 1"
INSULATION GLASS TO MATCH EXISTING.
PROVIDE NEW VCT FLOOR TILE TO MATCH EXISTING TO PATCH AREA
WHERE EXISTING WALL WAS REMOVED.
INFILL EXISTING WINDOW OPENINGS - REFER TO DETAIL
INFILL EXISTING WINDOW OPENING - REFER TO DETAIL
PAINT EXISTING BRICK PIERS TO MATCH ADJACENT WALLS.
1.
2.
3.
4.
5.
6.
(THIS SHEET ONLY)
GRAPHIC SCALE:
LEGEND
KEY PLAN (NOT TO SCALE)
A
B
C
D
PLAN
NORTH
SERVICE
ENTRANCE
MAIN
ENTRANCE
S
NEW WALL, WINDOW, AND/OR DOOR
10 /E6 AS301
/E8 AS301
Date
Location
Checked Drawn
Drawing Number
Building Number
Project NumberProject TitleDrawingTitle
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
Dwg. of
A
B
C
D
E
F
Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
VA FORM 08-6231
th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
BOWMAN FOSTER
& ASSOCIATES, PC
ALEXANDRIA, VA 22312
6353 CENTER DR. STE 101
NORFOLK, VA 23502
5252 CHEROKEE AVE, STE 101
McPHERSON
DESIGN
GROUP p.c.
STRUCTURAL ENGINEERS
6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com
901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5
Engineers Surveyors Planners
HOGGARD/EURE ASSOCIATES, P.C.
FULLY SPRINKLERED
FLOOR PLAN 'S' POD - NEW WORK
AS101
VA MEDICAL CENTER, HAMPTON, VA
JDB DAS 32 165
590-602
7/26/19
RENOVATE AND EXPAND
DOMICILIARY BUILDING 148
PLAN
NORTH
FLOOR PLAN 'S' POD - NEW WORK
DAP OFFICE
LUGGAGE
STORAGE
KITCHENETTE
LAUNDRY
MED FOS HOME
OFFICE
OFFICE
OFFICE
ELECTRICAL
CLOSET
STOR
COMM
CLOSET
SOILED LINEN
HAC
STOR
STOR
BEDROOM
BEDROOM
LOUNGE
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
STORAGE
BEDROOM
H&CC
OFFICE
H&CC
RECEPTION
H&CC NURSE OFFICE
H&CC
MANAGER
ROOF
ACCESS
BEDROOM
BEDROOMBEDROOM
BEDROOM
NO CURE
BEDROOM
BEDROOM
DAP OFFICE
OFFICE
ELEC
CLOSET
BEDROOM
BEDROOM
BEDROOM
BEDROOM
LOUNGE
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM
BEDROOM BEDROOM
STOR
COMM
STOR
ROOF
ACCESS
LOUNGE
C3
AS401
B5
AS401
COURTYARD
TOILET
TOILET
TOILET
B-102 A
A
A
A
A
A
A
A A A
A
A
A A A
B
A
A
A
A
A
A
A
AAAA
AA
A
A
A
A
A
A
A
A
2 2
2 2
2 2
2 2
2 1 2 2
1 1 1
1 1
1 1
1 2
3 4
4 4
B
5 5
5 5 5
5 5 5
GENERAL NOTES
SEE ENLARGED PLAN FOR PARTITION TYPES NOT INDICATED.
TYPICAL POD GROSS SQUARE FOOTAGE IS 18,193 SF.
TYPICAL POD RENOVATED SQUARE FOOTAGE IS 257 SF.
PATIENT ROOM MECHANICAL SYSTEMS TO BE REMOVED. PAINT
GYPSUM BOARD TO MATCH EXISTING COLOR AND FINISH
NOTE: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALE MUST BE USED.
1.
2.
3.
4.
KEY PLAN (NOT TO SCALE)
A
B
C
D
PLAN
NORTH
SERVICE
ENTRANCE
MAIN
ENTRANCE
S
CONSTRUCTION NOTES
PROVIDE NEW ALUMINUM WINDOW W/ 1" INSULATED GLASS. FIELD
VERIFY ROUGH WINDOW OPENING - REFER TO WINDOW TYPES.
PROVIDE METAL STUDS AND DRYWALL WALL INFILL - REFER TO SHEET
AS501.
PROVIDE 5/8” GYPSUM WALL BOARD ON EXISTING WALL FRAMING,
FULL WIDTH AND HEIGHT TO MATCH EXISTING GYPSUM BOARD. AFTER
NEW PLUMBING HAS BEEN COMPLETE. SAND JOINT SMOOTH AND ALL
EXPOSED GYPSUM WALL BOARD IN SPACE MUST BE PAINTED. SEE
FINISH SCHEDULE FOR PAINT FINISHES.
PROVIDE 5/8” GYPSUM WALL BOARD ON EXISTING WALL FRAMING,
FULL WIDTH AND HEIGHT OF WALL INDICATED. PROVIDE 4” X 4”
CERAMIC TILE WAINSCOT WITH BULLNOSE TOP TRIM TO 4’-6” A.F.F.
GYPSUM WALL BOARD SHALL BE ALIGNED WITH THE FACE OF
ADJACENT EXISTING GYPSUM BOARD, SANDED SMOOTH, AND EXPOSED
GYPSUM WALL BOARD ABOVE THE TILE WAINSCOT SHALL BE PAINTED.
SEE FINISH SCHEDULE FOR TILE AND PAINT SELECTIONS.
PROVIDE NEW SOLID SURFACE WINDOW STOOL.
(THIS SHEET ONLY)
EXISTING WALL, WINDOW, AND/OR DOOR TO REMAIN
LEGEND
NEW WALL, WINDOW, AND/OR DOOR
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
GRAPHIC SCALE:
Date
Location
Checked Drawn
Drawing Number
Building Number
Project NumberProject TitleDrawingTitle
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
Dwg. of
A
B
C
D
E
F
Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
VA FORM 08-6231
th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
BOWMAN FOSTER
& ASSOCIATES, PC
ALEXANDRIA, VA 22312
6353 CENTER DR. STE 101
NORFOLK, VA 23502
5252 CHEROKEE AVE, STE 101
McPHERSON
DESIGN
GROUP p.c.
STRUCTURAL ENGINEERS
6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com
901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5
Engineers Surveyors Planners
HOGGARD/EURE ASSOCIATES, P.C.
FULLY SPRINKLERED
FLOOR PLAN TYPICAL POD - NEW
WORK
AS102
VA MEDICAL CENTER, HAMPTON, VA
JDB DAS 33 165
590-602
7/26/19
RENOVATE AND EXPAND
DOMICILIARY BUILDING 148
PLAN
NORTH
1/8" = 1'-0"
FLOOR PLAN TYPICAL POD - NEW WORK - (POD B SHOWN - POD'S A, C, & D SIM.)
NOTE: NEW WORK INDICATED ON THIS
CORRIDOR
TO POD A
CORRIDOR
TO POD D
CORRIDOR
TO POD C
(8'-0")
(8'-0")
(9'-0")
(8'-0")
(8'-0")
(9'-0")
S134
GROUP
ROOMS135
CORRIDOR
S115
PATIENT
SCREENING
S121
EXISTING
WOMEN'S
S122
EXISTING
MEN'S
S142
LIBRARY
S102
TOILET
S103
STORAGE
(9'-0")
TYP
1 1
NO CEILING WORK THIS AREA
NO CEILING
WORK THIS AREA
NO CEILING
WORK THIS AREA
(9'-0") (9'-0")
(7'-11")
(8'-0")
(8'-11") (8'-11")5
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
NOTE: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALE MUST BE USED.
GRAPHIC SCALE:
KEY PLAN (NOT TO SCALE)
A
B
C
D
PLAN
NORTH
LEGEND
NEW PARTITIONS
GYP BD CEILING
2x2 ACT CEILING
AIR SUPPLY DIFFUSER
2x4 LIGHT FIXTURE
GENERAL CEILING NOTES
UNLESS OTHERWISE NOTED, CEILING TILE SHALL BE CENTERED IN
EACH ROOM, IN ACCORDANCE WITH THE LAYOUTS SHOWN.
THE CEILING CONTRACTOR SHALL MAKE ADJUSTMENTS NECESSARY
TO ELIMINATE ADDITIONAL, SMALL, OR ODD PIECES OF CEILING TILE.
REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR LIGHT
FIXTURES, EXIT LIGHT LOCATIONS, AIR DIFFUSERS, EXHAUST FANS,
ETC.
WHERE TILES ARE CUT, COPE AND FINISH EDGES TO MATCH UNCUT
TILE.
ALL DIMENSIONS ON CEILING PLAN ARE TO FINISHED SURFACES AND
CENTER LINES OF FIXTURES.
CENTER ALL LIGHTS, DIFFUSERS, FIXTURES, SPRINKLER HEADS, ETC.
IN CEILING TILES UNLESS OTHERWISE NOTED.
THE CONTRACTOR SHALL DAMP CLEAN AND HAND DRY ALL FIXTURES
AND LAMPS JUST PRIOR TO FINAL INSPECTION.
SEE INTERIOR ELEVATIONS AND ELECTRICAL DRAWINGS FOR LIGHT
FIXTURE MOUNTING.
ALL NEW CEILING MUST BE INSTALLED AT THE HEIGHT OF THE
ORIGINAL CEILING UNLES OTHERWISE NOTED.
PROVIDE NEW ACOUSTICAL TILE CEILING. ALIGN GRID TO EXISTING
LIGHT FIXTURES.
PROVIDE NEW 5/8" GYP. BOARD CEILING ON EXISTING FRAMING. PAINT
TO MATCH EXISTING.
PROVIDE NEW SUSPENDED TILE CEILING. EXISTING SLOPED ACOUSTICAL
TILE CEILING AT UNDERSIDE OF ROOF JOISTS TO REMAIN.
PROVIDE PLASTER SOFFIT AFTER NEW MECHANICAL WORK IS COMPLETE.
PROVIDE DRYWALL BULKHEAD.
1.
2.
3.
4.
5.
6.
7.
8.
9.
CONSTRUCTION NOTES (THIS SHEET ONLY)
AIR RETURN DIFFUSER
2x4 EMERGENCY LIGHT FIXTURE
PENDANT LIGHT FIXTURE
RECESSED LIGHT FIXTURE
EXPOSED TO STRUCTURE
EXIT SIGN, CEILING MOUNTED
EXIT SIGN, WALL MOUNTED
1x4 LIGHT FIXTURE
1x4 EMERGENCY LIGHT FIXTURE
(THIS SHEET ONLY)
2x2 LIGHT FIXTURE
SERVICE
ENTRANCE
MAIN
ENTRANCE
S
Date
Location
Checked Drawn
Drawing Number
Building Number
Project NumberProject TitleDrawingTitle
Approved: Project Director
ARCHITECT/ENGINEERS:CONSULTANTS:
Dwg. of
A
B
C
D
E
F
Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
VA FORM 08-6231