This document provides details for a Request for Proposal (RFP) for the Z2DZ--590-602 Renovate and Expand Domiciliary project at the Hampton VAMC located in Hampton, Virginia. The RFP seeks proposals for the renovation and expansion of the Domiciliary with a construction magnitude between $5,000,000 to $10,000,000. The NAICS code is 236220 with a size standard of $39.5 million. The solicitation is a 100% SDVOSB set-aside issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6. A pre-proposal site visit will be conducted on August 18, 2020, and requests for information are due by August 21, 2020 with answers provided via amendment by August 28, 2020. Proposals must be submitted by September 21, 2020. The attachment includes proposal and deductive proposal items.

View the file

Other files

Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

McPHERSON

DESIGN

GROUP

STRUCTURAL ENGINEERS

6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com

Hampton, Virginia

SEWELLAVENUE

A V

E N

U E

A M

E S S

T R E E T

K N

O X

S T R

E E

T

T H O

M P S O

N S

T R E E T

B L A C K

F R A N K L

IN

B O

U L E V A R D

E M

A N

C

IP

A T

IO

N

D R

A V E N

U E

M cC

LE

LLA

N

H A

R R

IS

A V

E R

IL

L A

V E

N U

E

F R

A N

K L

IN

B O

U L E

V A

R D

MARTIN L. KING JR. BOULEVARD

BOULEVARD

S H

O R

E R

O A

D

A V E N U E

H A

R R

IS

A

V E

N U

E

H A

R R

IS

A V

E R

IL

L A

V E

N U

E

FR

A

N K

LIN

B

O U

LE

V A R

D

MARTIN L. KING JR.

CONTRACTO

R'S STAG

ING AREA

M A

L L O

R Y

S T R

E E

T

J O

N E

S C

R E

E K

S A

L V

A G

E Y

A R

D1

G R A V E L D

R

IV

E W

A Y

G R A V E L D

R

IV

E W

A Y

G R A V E L R

O A D

S T O

R M

W A

T E

R P

O N

D

IM

P

O U

N D

L O

T

A V E N

U E

148T

148B

148S

148A

148D

148C

CONSTRUCTION NOTES

SHEET NOTES

SHEET NOTES

SIDEWALK REPAIR DETAIL

TEMPORARY CONSTRUCTION FENCE DETAIL

SIDE ELEVATION

PLAN VIEW

SECTION A-A

SECTION B-B

STONE CONSTRUCTION ENTRANCE

CEILING AS SCHEDULED

BASE AS SCHEDULED

PROVIDE DIAGONAL BRACING AT

8'-0" OC, AND AT EACH SIDE OF

ALL OPENINGS AND AS REQUIRED

FOR STABILITY

5/8" GWB

METAL STUDS

LINE OF FLOOR

WALL FINISH AS SCHEDULED

ACOUSTICAL SEALANT

CONTINUOUS EACH SIDE

SOUND ATTENUATION INSULATION

PLAN

VIEW

POWDER ACTUATED FASTENER, TYP

BOTTOM OF DECK

PROVIDE TOP TRACK W/ 2" LONG

LEGS, MAINTAIN 3/4" CLEAR BELOW

DECK, TYP

ACOUSTICAL SEALANT CONTINUOUS

AT UNDERSIDE OF STRUCTURE

CEILING AS SCHEDULED

LINE OF FLOOR

ACOUSTICAL SEALANT

CONTINUOUS EACH SIDE

PLAN

VIEW

BASE AS SCHEDULED

5/8" GWB

METAL STUDS

WALL FINISH AS SCHEDULED

SOUND ATTENUATION INSULATION

POWDER ACTUATED FASTENER, TYP

FILL ALL VOIDS AT TOP OF PARTITION

WITH BATT INSULATION

A/C AIR CONDITIONING

ADA AMERICANS WITH DISABILITIES

ACOUS ACOUSTICAL

ACT ACOUSTICAL CEILING TILE

AFF ABOVE FINISHED FLOOR

ALUM ALUMINUM

APPROX APPROXIMATELY

BD BOARD

BLDG BUILDING

BTM BOTTOM

CJ CONTROL JOINT

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CO CLEAN OUT

CONC CONCRETE

CONT CONTINUOUS

COORD COORDINATE

D/DIA DIAMETER

DEMO DEMOLISH

DN DOWN

EA EACH

EJ EXPANSION JOINT

EQ EQUAL

EQUIP EQUIPMENT

ETC ETCETERA

EXT EXTERIOR

FD FLOOR DRAIN

FDV FIRE DEPARTMENT VALVE

FEC FIRE EXTINGUISHER CABINET

REV REVERSED

RO ROUGH OPENING

SIM SIMILAR

SQ SQUARE

SS STAINLESS STEEL

STL STEEL

STRUCT STRUCTURAL

TB TACK BOARD

TEMP TEMPORARY

TERM TERMINATE

TGL TEMPERED GLAZING

TV TELEVISION

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

VERT VERTICAL

VCT VINYL COMPOSITION TILE

W WIDTH

WD WOOD

WWF WELDED WIRE FABRIC

@ AT

& AND

CENTER LINE

ø DIAMETER

# NUMBER

CL

FRT FIRE RETARDANT TREATED

FRZR FREEZER

GA GAUGE

GC GENERAL CONTRACTOR

GWB GYPSUM WALL BOARD

GYP GYPSUM

H HEIGHT

HM HOLLOW METAL

HOR HORIZONTAL

HR HOUR

INSUL INSULATION

MANUF MANUFACTURER

MAX MAXIMUM

MB MARKER BOARD

MECH MECHANICAL

MIN MINIMUM

MO MASONRY OPENING

MTL METAL

NIC NOT IN CONTRACT

NTS NOT TO SCALE

OC ON CENTER

OH OPPOSITE HAND

PEMB PRE-ENGINEERED METAL BUILDING

PLAM PLASTIC LAMINATE

PNT PAINT

PREFAB PREFABRICATED

PSI POUNDS PER SQUARE INCH

REF REFRIGERATOR

REINF REINFORCED

ROOM

B-101

A

A

(8'-0")

ROOM NAME AND

NUMBER REFERENCE

DOOR NUMBER

REFERENCE

WINDOW MARKER

SEE SHEET A-XXX

PARTITION TYPE

SEE SHEET A-XXX

CEILING REFERENCE

HEIGHT AFF

NEW WORK NOTES

DEMOLITION WORK NOTES

TOILET ACCESSORY NOTE

SEE SHEET A-XXX

REVISION MARKER

CONTROL OR EXPANSION

JOINT - SEE SHEET A-XXX

AS501

AS501

AS401C A

B

D

A

AS301

DETAIL DRAWN ON THIS SHEET (TYP)

DETAIL NUMBER (TYP)

DETAIL DRAWN ON THIS SHEET (TYP)

DETAIL NUMBER (TYP)

DETAIL INDICATORS

ELEVATIONS DRAWN ON THIS SHEET (TYP)

ELEVATION LETTER (TYP)

INTERIOR ELEVATION REFERENCE

SECTION DRAWN ON THIS SHEET (TYP)

SECTION LETTER (TYP)

BUILDING AND WALL SECTION REFERENCE

ELEVATIONS DRAWN ON THIS SHEET (TYP)

ELEVATION LETTER (TYP)

BUILDING ELEVATION REFERENCE

PLAN

NORTH

AS101

DRAWING OR DETAIL TITLE

SCALE

PLAN OR SITE TITLE

SCALE

SHEETS WHERE DETAIL IS DRAWN

DETAIL NUMBER

TRUE NORTH

PLAN NORTH

AS101

SHEETS WHERE DETAIL IS REFERENCED

A

AS201

SOUND ATTENUATION

INSULATION UON

BRICK

CONCRETE

CONCRETE

MASONRY UNITS

CONTINUOUS

BLOCKING

EARTH

FINISHED WOOD

GRAVEL

GYPSUM BOARD

OR SHEATHING

PLYWOOD

RIGID INSULATION

STEEL

SAFETY - DURING CONSTRUCTION WORK

COMPLETE ALL CRITICAL BARRIERS BEFORE CONSTRUCTION BEGINS.

INSTALL CONSTRUCTION BARRIERS AND CEILING PROTECTION

CAREFULLY, OUTSIDE OF NORMAL WORK HOURS.

SEPARATE ALL OCCUPIED AREAS FROM DEMOLITION, RENOVATION, OR

CONSTRUCTION ACTIVITIES BY TEMPORARY SMOKE-TIGHT

CONSTRUCTION PARTITIONS OF GYPSUM BOARD OR OTHER APPROVED

NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE MATERIAL. PARTITIONS

SHALL BE FULL HEIGHT, EXTENDING THROUGH SUSPENDED CEILINGS

TO THE FLOOR SLAB OR ROOF DECK ABOVE AND SHALL BE ONE-

HOUR FIRE RATED. BARRIER MUST BE PRESENTABLE ON OCCUPIED

SIDE.

DRYWALL BARRIER ERECTED WITH JOINTS COVERED OR SEALED TO

PREVENT DUST AND DEBRIS FROM ESCAPING.

BARRIER DOORS: SELF CLOSING ONE-HOUR SOLID CORE WOOD IN

STEEL FRAME, PAINTED.

ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO

PREVENT CONTAMINATION OF DUCT SYSTEM.

MAINTAIN NEGATIVE AIR PRESSURE, 0.01 INCHES OF WATER GAUGE,

WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS

AND CONTINUOUSLY MONITORED WITH A DIGITAL DISPLAY, RECORDING

AND ALARM INSTRUMENT, WHICH MUST BE CALIBRATED ON

INSTALLATION, MAINTAINED WITH PERIODIC CALIBRATION AND

MONITORED BY THE CONTRACTOR.

EXHAUST HOSES REQUIRED: HEAVY DUTY, FLEXIBLE STEEL

REINFORCED; VENTILATION BLOWER HOSE

ADHESIVE WALK-OFF MATS SHALL BE USED AT ALL INTERIOR

TRANSITIONS FROM THE CONSTRUCTION AREA TO BE OCCUPIED

MEDICAL CENTER AREA. PROVIDE MINIMUM SIZE MATS OF 24 INCHES

X 36 INCHES. THESE MATS SHALL BE CHANGED AS OFTEN AS

REQUIRED TO MAINTAIN CLEAN WORK AREAS DIRECTLY OUTSIDE

CONSTRUCTION AREA AT ALL TIMES.

VACUUM AND WET MOP ALL TRANSITION AREAS FROM CONSTRUCTION

TO THE OCCUPIED MEDICAL CENTER AT THE END OF EACH

WORKDAY. VACUUM SHALL UTILIZE HEPA FILTRATION. MAINTAIN

SURROUNDING AREA FREQUENTLY.

CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY

COVERED CONTAINERS.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

SAFETY - COMPLETION OF CONSTRUCTION WORK

DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED

PROJECT IS INSPECTED BY THE CO (OR DESIGNATED REP) AND

THOROUGHLY CLEANED.

REMOVE CONSTRUCTION BARRIERS AND CEILING PROTECTION

CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED

WITH CONSTRUCTION, OUTSIDE OF NORMAL WORK HOURS.

VACUUM WORK AREA WITH HEPA FILTERED VACUUMS.

WET MOP AREA WITH CLEANER/DISINFECTANT.

UPON COMPLETION, RESTORE HVAC SYSTEM WHERE WORK WAS

PERFORMED.

1.

2.

3.

4.

5.

SPECIAL DOCUMENT NOTES

**THE FOLLOWING ARE A LIST OF WORDS/PHRASES WITH

DEFINITIONS THAT ARE USED THROUGHOUT THESE DOCUMENTS

THAT MUST BE USED WHEN EXECUTING THE WORK SHOWN ON

ALL THE DOCUMENTS FOR THIS PROJECT.

1. "PROVIDE" IS DEFINED TO MEAN "FURNISH AND INSTALL

COMPLETE, IN PLACE AND READY FOR OPERATION AND USE."

2. FURNISH" IS DEFINED TO MEAN "SUPPLY AND DELIVER TO

PROJECT SITE, READY FOR INSTALLATION."

3. "INSTALL" IS DEFINED TO MEAN "PLACE IN POSITION FOR

SERVICE OR USE."

Date

Location

Checked Drawn

Drawing Number

Building Number

Project NumberProject TitleDrawingTitle

Approved: Project Director

ARCHITECT/ENGINEERS:CONSULTANTS:

Dwg. of

A

B

C

D

E

F

Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

VA FORM 08-6231

th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

BOWMAN FOSTER

& ASSOCIATES, PC

ALEXANDRIA, VA 22312

6353 CENTER DR. STE 101

NORFOLK, VA 23502

5252 CHEROKEE AVE, STE 101

McPHERSON

DESIGN

GROUP p.c.

STRUCTURAL ENGINEERS

6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com

901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5

Engineers Surveyors Planners

HOGGARD/EURE ASSOCIATES, P.C.

FULLY SPRINKLERED

PARTITION TYPES, LEGENDS,

ABBREVIATIONS AND NOTES

AS001

VA MEDICAL CENTER, HAMPTON, VA

JDB DAS 20 165

590-602

7/26/19

RENOVATE AND EXPAND

DOMICILIARY BUILDING 148

PARTITION TYPE - A

TYPE WIDTH

STUD

SIZE

MAX STUD

SPACING INSUL

FIRE

RATING UL # NOTES

A 4 7/8" 3 5/8" 16" OC 3 1/2" - -

A1 4 7/8" 3 5/8" 16" OC - - -

A2 4 1/4" 3 5/8" 16" OC 3 1/2" - - 1

PARTITION TYPE A

THE CONTRACTOR SHALL VERIFY ALL FIELD CONDITIONS AND

DIMENSIONS PRIOR TO BEGINNING CONSTRUCTION AND SHALL

COORDINATE THE WORK OF ALL TRADES. ALL DISCREPANCIES

SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE

ARCHITECT, IN WRITING, BEFORE CONTINUING WORK.

UNLESS OTHERWISE INDICATED, EXTERIOR DIMENSIONS ARE TO

OUTSIDE FACE OF FOUNDATION WALL AND CENTERLINE OF

STRUCTURAL COLUMNS. INTERIOR DIMENSIONS ARE TO FACE OF

STUD AND CENTERLINE OF STRUCTURAL COLUMNS.

SEE CIVIL DRAWINGS FOR FINISH FLOOR AND GRADE ELEVATIONS,

SIDEWALK, CURBS, ETC.

ALL METAL STUDS SHALL BE 20 GAUGE MINIMUM.

THE WORK INCLUDES THE DEMOLITION AND REMOVAL OF ALL

CONSTRUCTION INDICATED, NOTED OR NECESSARY TO

ACCOMPLISH THE WORK AS INDICATED OR SPECIFIED.

THE CONTRACTOR WILL PATCH OR FILL ALL HOLES AND DAMAGED

SURFACES RESULTING FROM THE DEMOLITION OF EXISTING, OR IN

PREPARATION OF NEW WORK WITH FINISH MATERIALS TO MATCH

EXISTING (MINIMUM 2'-0" ALL AROUND WORK AREAS) AND

RESULT IN A THOROUGHLY FINISHED PRODUCT.

IT IS THE GENERAL INTENT OF THE DEMOLITION WORK TO

COMPLETLEY REMOVE ALL ITEMS OF EXISTING CONSTRUCTION,

WHERE NOTED OR INDICATED ON THE DRAWINGS, INCLUDING

ANCHORS, FASTENERS, BRACKETS, CLIPS, RODS, HANGERS, AND

SUPPORTS.

REMOVE AND REPLACE ANY DAMAGED/DISCOLORED CEILING TILES.

RELOCATE EXISTING LIGHT FIXTURES, MECHANICAL DIFFUSERS,

AND SPRINKLER HEADS AS REQUIRED FOR DEMOLITION OF

EXISTING CEILING AS INDICATED.

1.

2.

3.

4.

5.

6.

7.

8.

9.

GENERAL NOTES

ABBREVIATIONS

MATERIAL LEGEND

SYMBOL LEGEND

PARTITION TYPE NOTES

GYP BD ONE SIDE ONLY.

TOPS OF GYP BD ON PARTITIONS SHALL BE CUT TO THE

PROFILE OF THE METAL DECK ABOVE AND ALLOW SPACE FOR

ACOUSTIC SEALANT FOR ALL ACOUSTIC RATED PARTITIONS AND

OTHER PARTITIONS WHERE ACOUSTIC SEALANT IS SHOWN.

PROVIDE "UL" LISTED AND RATED JOINT SYSTEM FOR ALL

PENETRATIONS OF ALL FIRE RATED PARTITIONS.

PROVIDE ACOUSTIC INSULATION AND ACOUSTIC SEALANT AT ALL

PENETRATIONS OF ACOUSTIC RATED PARTITIONS.

FIRE RATED PLYWOOD ONE SIDE ONLY.

1.

2.

3.

4.

5.

PARTITION TYPE B

NOTE: IF THIS DRAWING IS A REDUCTION,

GRAPHIC SCALE MUST BE USED.

GRAPHIC SCALE:

0 4" 8" 1'-4"

SCALE: 1 1/2" = 1'-0"

PARTITION TYPE - B

TYPE WIDTH

STUD

SIZE

MAX STUD

SPACING INSUL

FIRE

RATING UL # NOTES

B 4 7/8" 3 5/8" 16" OC 3 1/2" - -

B1 7 1/4" 6" 16" OC 3 1/2" - -

B2 4 7/8" 3 5/8" 16" OC 3 1/2" - -

B3 7 1/4" 6" 16" OC 5" - -

R E

F

POD A

POD D

POD C

POD B

MAIN ENTRANCE

SERVICE ENTRANCE

SUPPORT

FACILITY

(POD S)

(REFER TO TYPICAL

DOMICILARY POD

DEMOLITION PLAN AND

FLOOR PLAN ON SHEETS

AD102 & AS102)

(REFER TO TYPICAL DOMICILARY POD

DEMOLITION PLAN AND FLOOR PLAN

ON SHEETS AD102 & AS102, SIMILAR)

(REFER TO TYPICAL

DOMICILARY POD

DEMOLITION PLAN AND

FLOOR PLAN ON SHEETS

AD102 & AS102, SIMILAR,

EXEPT WHERE OTHERWISE

NOTED.)

(REFER TO TYPICAL DOMICILARY POD

DEMOLITION PLAN AND FLOOR PLAN

ON SHEETS AD102 & AS102, SIMILAR)

C3

AS401

C3

AS401

C3

AS401

C3

AS401

B5

AS401

B5

AS401

B5

AS401

B5

AS401

C1

AS401

D5

AS401

Date

Location

Checked Drawn

Drawing Number

Building Number

Project NumberProject TitleDrawingTitle

Approved: Project Director

ARCHITECT/ENGINEERS:CONSULTANTS:

Dwg. of

A

B

C

D

E

F

Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

VA FORM 08-6231

th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

BOWMAN FOSTER

& ASSOCIATES, PC

ALEXANDRIA, VA 22312

6353 CENTER DR. STE 101

NORFOLK, VA 23502

5252 CHEROKEE AVE, STE 101

McPHERSON

DESIGN

GROUP p.c.

STRUCTURAL ENGINEERS

6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com

901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5

Engineers Surveyors Planners

HOGGARD/EURE ASSOCIATES, P.C.

FULLY SPRINKLERED

COMPOSITE FLOOR PLAN

AS002

VA MEDICAL CENTER, HAMPTON, VA

JDB DAS 21 165

590-602

7/26/19

RENOVATE AND EXPAND

DOMICILIARY BUILDING 148

NOTE: IF THIS DRAWING IS A REDUCTION,

GRAPHIC SCALE MUST BE USED.

GRAPHIC SCALE:

0 48'

SCALE: 3/64" = 1'-0"

12' 24' 3/64" = 1'-0"

COMPOSITE FLOOR PLAN

PLAN

NORTH

UP

ELECTRICAL VAULT

MECHANICAL ROOM

EMERGENCY

GENERATOR

ROOM

STORAGE

STORAGE

EMS STORAGE

STORAGE

MAIN

TELEPHONE

CLOSET

ELECTRICAL

CLOSET

LOUNGE

CONFERENCE ROOM

GENERAL

STORAGE

E L E C

C L O S E T

OFFICE OFFICE

CHIEF

DOMICILLARY OFFICE

OFFICE

MAIN

ENTRANCE

EXISTING RECREATION

ROOM

VENDING

OFFICE

DOMICILLARY

CARE

OFFICE/

RECEPTION

PATIENT SCREENING

PATIENT

SCREENING

STORAGE

OFFICE

OFFICE

OFFICE

OFFICEOFFICE

H.A.C.

EXISTING

LIBRARY

EXISTING

FITNESS CENTER

2 1

TYP

TYP

11'-2"± 17'-4"± 43'-2"± 47'-0"±

161'-10"±

33'-10"± 8'-0"± 1'-4"± 47'-0"± 10'-4"± 32'-10"±

32'-10"±

10'-4"±

EXISTING

GROUP ROOM

13 13 1313

LINE OF

EXISTING VCT

S122

EXISTING MEN'S

S121

EXISTING WOMEN'S

S103

STORAGE

S102

TOILET

817 17

LINE OF

EXISTING VCT

EXISTING WALL AND/OR DOOR TO BE DEMOLISHED

EXISTING WINDOW TO BE DEMOLISHED

EXISTING WALL, WINDOW, AND/OR DOOR TO REMAIN

0 4' 8' 16'

SCALE: 1/8" = 1'-0"

NOTE: IF THIS DRAWING IS A REDUCTION,

GRAPHIC SCALE MUST BE USED.

DEMOLITION NOTES

REMOVE EXISTING WALLS WHERE INDICATED IN THEIR ENTIRETY.

REMOVE EXISTING DOORS TO INCLUDE FRAMES AND HARDWARE IN

THEIR ENTIRETY.

REMOVE EXISTING WALL WHERE INDICATED FOR NEW DOOR OPENING.

PREPARE WALL WITH NEW STUDS & DRYWALL TO INCLUDE ALL

BLOCKING AND HEADERS TO RECEIVE NEW HM FRAME AND WOOD

DOOR.

REMOVE EXISTING CARPET AND VCT TO INCLUDE ALL ADHESIVE IN

AREAS OF EXISTING LIBRARY AND FITNESS CENTER COMPLETE TO

EXISTING CONCRETE SLAB. PREPARE SLAB TO RECEIVE NEW FLOOR

FINISH.

REMOVE EXISTING CERAMIC TILE SHOWER ENCLOSURE IN ITS

ENTIRETY.

REMOVE EXISTING STOREFRONT AND WINDOW SYSTEM COMPLETE

WHERE INDICATED ON DEMOLITION PLAN TO INCLUDE WINDOW BLINDS

AND TREATMENTS.

REMOVE EXISTING PLUMBING FIXTURES, TOILET PARTITIONS, TOILET

ACCESSORIES IN THEIR ENTIRETY.

REMOVE EXISTING SINK AND ASSOCIATED PIPING. REMOVE ALL

DAMAGED DRYWALL AND REPLACE WITH NEW GYPSUM WALL BOARD TO

MATCH EXISTING WALL FINISH.

REMOVE EXISTING GYPSUM WALL BOARD AND CERAMIC TILE WHERE

INDICATED TO PROVIDE ACCESS TO EXISTING PLUMBING LINES BEHIND

THE EXISTING WALLS. EXISTING WALL FRAMING TO REMAIN. PREPARE

WALLS FOR INSTALLATION OF NEW GYPSUM BOARD AFTER NEW

PLUMBING WORK IS COMPLETE. REFER TO SHEET AS101 FOR NEW

WORK.

DEMOUNTABLE PARTITION SYSTEM FURNITURE ARE SHOWN FOR

GENERAL INFORMATION ONLY. REFER TO SHEET G-003 FOR NOTES ON

OWNER RESPONSIBILITY FOR EXISTING FF&E ITEMS.

REMOVE EXISTING EXTERIOR CANOPY AND SUPPORT FRAMING IN ITS

ENTIRETY.

REMOVE ALL EXISTING EPOXY TERRAZZO FLOORING AND CERAMIC TILE

WAINSCOT IN ITS ENTIRETY.

REMOVE EXISTING RADIANT HEATING BELOW EXISTING WINDOWS. REFER

TO MECHANICAL DRAWINGS FOR LIMITS OF WORK.

REMOVE EXISTING VCT FLOORING TO INCLUDE ALL ADHESIVE AND

EXISTING WALL BASE WHERE INDICATED.

EXISTING VCT FLOORING AND WALL BASE TO REMAIN.

REMOVE EXISTING PLUMBING FIXTURE AND DRYWALL TO PROVIDE

ACCESS TO EXISTING PLUMBING LINES. EXISTING WALL FRAMING MUST

REMAIN. REFER TO PLUMBING DRAWINGS FOR ADDITIONAL NOTES.

REMOVE EXISTING MECHANICAL GRILLES TO ENLARGE WALL OPENINGS

FOR NEW MECHANICAL WORK- REFRAME OPENING FOR NEW DUCT

SIZE. REFER TO MECHANICAL DRAWINGS.

(THIS SHEET ONLY)

GRAPHIC SCALE:

LEGEND

KEY PLAN (NOT TO SCALE)

A

B

C

D

PLAN

NORTH

SERVICE

ENTRANCE

MAIN

ENTRANCE

S

Date

Location

Checked Drawn

Drawing Number

Building Number

Project NumberProject TitleDrawingTitle

Approved: Project Director

ARCHITECT/ENGINEERS:CONSULTANTS:

Dwg. of

A

B

C

D

E

F

Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

VA FORM 08-6231

th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

BOWMAN FOSTER

& ASSOCIATES, PC

ALEXANDRIA, VA 22312

6353 CENTER DR. STE 101

NORFOLK, VA 23502

5252 CHEROKEE AVE, STE 101

McPHERSON

DESIGN

GROUP p.c.

STRUCTURAL ENGINEERS

6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com

901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5

Engineers Surveyors Planners

HOGGARD/EURE ASSOCIATES, P.C.

FULLY SPRINKLERED

FLOOR PLAN 'S' POD - DEMOLITION

AD101

VA MEDICAL CENTER, HAMPTON, VA

JDB DAS 22 165

590-602

7/26/19

RENOVATE AND EXPAND

DOMICILIARY BUILDING 148

1/8" = 1'-0"

FLOOR PLAN 'S' POD - DEMOLITION

DAP OFFICE

LUGGAGE

STORAGE

KITCHENETTE

LAUNDRY

OFFICE

OFFICE

ELECTRICAL

CLOSET

STOR

COMM

CLOSET

HAC

STOR

STOR

BEDROOM

BEDROOM

LOUNGE

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

STORAGE

BEDROOM

H&CC

OFFICE

H&CC

RECEPTION

H&CC

MANAGER

ROOF

ACCESS

BEDROOM

BEDROOMBEDROOM

BEDROOM

NO CURE

BEDROOM

BEDROOM

DAP OFFICE

OFFICE

ELEC

CLOSET

BEDROOM

BEDROOM

BEDROOM

BEDROOM

LOUNGE

BEDROOM

BEDROOM

BEDROOM

BEDROOM BEDROOM

BEDROOM BEDROOM

STOR

COMM

STOR

ROOF

ACCESS

LOUNGE

MED FOS HOME

OFFICE

SOILED LINEN

H&CC NURSE OFFICE

82'-4"± 16'-8"± 66'-9"± 14'-6"±

180'-3"±

17'-7"± 46'-1"± 39'-0"± 17'-0"± 35'-8"± 10'-4"± 14'-7"±

56'-0"±

6 6

6 6 6

6 6 6

6 6

COURTYARD

3 3 3

3 3

3 3

3 3

8 8

8 8

REDO COMPLETELY.

TYP. FOR POD'S

A,B,C,D.

0 4' 8' 16'

SCALE: 1/8" = 1'-0"

NOTE: IF THIS DRAWING IS A REDUCTION,

GRAPHIC SCALE MUST BE USED.

GRAPHIC SCALE:

KEY PLAN (NOT TO SCALE)

A

B

C

D

PLAN

NORTH

SERVICE

ENTRANCE

MAIN

ENTRANCE

EXISTING WALL AND/OR DOOR TO BE DEMOLISHED

EXISTING WINDOW TO BE DEMOLISHED

EXISTING WALL, WINDOW, AND/OR DOOR TO REMAIN

LEGEND

S

DEMOLITION NOTES

REMOVE EXISTING WALLS WHERE INDICATED IN THEIR ENTIRETY.

REMOVE EXISTING DOORS TO INCLUDE FRAMES AND HARDWARE IN

THEIR ENTIRETY.

REMOVE WALL-MOUNTED HVAC INDUCTION UNIT AND WINDOW STOOL

COMPLETE. REFER TO MECHANICAL DRAWINGS AND DETAIL

REMOVE EXISTING PLUMBING FIXTURE AND DRYWALL TO PROVIDE

ACCESS TO EXISTING PLUMBING LINES. EXISTING WALL FRAMING MUST

REMAIN. REFER TO PLUMBING DRAWINGS FOR ADDITIONAL NOTES.

REMOVE EXISTING CERAMIC TILE SHOWER ENCLOSURE IN ITS

ENTIRETY.

REMOVE EXISTING STOREFRONT AND WINDOW SYSTEM COMPLETE

WHERE INDICATED ON DEMOLITION PLAN TO INCLUDE WINDOW BLINDS

AND TREATMENTS.

REMOVE EXISTING PLUMBING FIXTURES, TOILET PARTITIONS, TOILET

ACCESSORIES IN THEIR ENTIRETY.

REMOVE EXISTING GYPSUM WALL BOARD AND CERAMIC TILE WHERE

INDICATED TO PROVIDE ACCESS TO EXISTING PLUMBING LINES BEHIND

THE EXISTING WALLS. EXISTING WALL FRAMING TO REMAIN. PREPARE

WALLS FOR INSTALLATION OF NEW GYPSUM BOARD AFTER NEW

PLUMBING WORK IS COMPLETE. REFER TO SHEET AS102 FOR NEW

WORK.

REMOVE EXISTING EPOXY TERRAZZO FLOORING AND CERAMIC TILE

WAINSCOT IN ITS ENTIRETY IN THIS SPACE.

(THIS SHEET ONLY)

/A1 AS501

Date

Location

Checked Drawn

Drawing Number

Building Number

Project NumberProject TitleDrawingTitle

Approved: Project Director

ARCHITECT/ENGINEERS:CONSULTANTS:

Dwg. of

A

B

C

D

E

F

Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

VA FORM 08-6231

th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

BOWMAN FOSTER

& ASSOCIATES, PC

ALEXANDRIA, VA 22312

6353 CENTER DR. STE 101

NORFOLK, VA 23502

5252 CHEROKEE AVE, STE 101

McPHERSON

DESIGN

GROUP p.c.

STRUCTURAL ENGINEERS

6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com

901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5

Engineers Surveyors Planners

HOGGARD/EURE ASSOCIATES, P.C.

FULLY SPRINKLERED

FLOOR PLAN TYPICAL POD -

DEMOLITION

AD102

VA MEDICAL CENTER, HAMPTON, VA

JDB DAS 23 165

590-602

7/26/19

RENOVATE AND EXPAND

DOMICILIARY BUILDING 148

1/8" = 1'-0"

FLOOR PLAN TYPICAL POD - DEMOLITION - (POD B SHOWN - POD'S A, C, & D SIM.)

CORRIDOR

TO POD B

CORRIDOR

TO POD A

CORRIDOR

TO POD D

CORRIDOR

TO POD C

1 1

5 5 5

5 5

5 5

5 5

PROJECTION

SCREEN

ENCLOSURE

ELEC. CLOSET

F3

AS301

0 4' 8' 16'

SCALE: 1/8" = 1'-0"

NOTE: IF THIS DRAWING IS A REDUCTION,

GRAPHIC SCALE MUST BE USED.

GRAPHIC SCALE:

KEY PLAN (NOT TO SCALE)

A

B

C

D

PLAN

NORTH

LEGEND

EXISTING PARTITIONS

GYP BD CEILING

EXISTING 2x2 ACT CEILING TO REMAIN

AIR SUPPLY DIFFUSER

EXISTING 2x4 LIGHT FIXTURE TO REMAIN

DEMOLITION NOTES

REMOVE EXISTING ACOUSTICAL CEILING TILE, GRID, LIGHT FIXTURES

AND ALL OTHER CEILING MOUNTED UTILITIES THAT ARE NOT

INDICATED ON THESE DRAWINGS.

REMOVE EXISTING GYPSUM BOARD CEILING TO INCLUDE FRAMING,

LIGHTS AND ALL OTHER CEILING MOUNTED UTILITIES COMPLETE.

REMOVE EXISTING ACT BULKHEAD IN ITS ENITIRETY.

REMOVE EXISTING EXTERIOR SOFFIT WHERE INDICATED ON DRAWINGS.

REMOVE EXISTING ACT CEILING TO INCLUDE GRID. SALVAGE EXISTING

LIGHTING, FIRE PROTECTION AND OTHER CEILING MOUNTED ITEMS

UNLESS OTHERWISE NOTED FOR REINSTALLATION IN NEW CEILINGS

AFTER MECHANICAL WORK IS COMPLETE. REFER TO SHEET AS103

FOR NEW WORK.

REMOVE EXISTING GYPSUM BOARD CEILING TO INCLUDE GRID.

SALVAGE EXISTING LIGHTING, FIRE PROTECTION AND OTHER CEILING

MOUNTED ITEMS UNLESS OTHERWISE NOTED FOR REINSTALLATION IN

NEW CEILINGS AFTER MECHANICAL WORK IS COMPLETE. REFER TO

SHEET AS103 FOR NEW WORK

REMOVE EXISTING CONCEALED OVERHEAD SECURITY ASSEMBLY.

REFER TO AS103 FOR NEW BULKHED.

AIR RETURN DIFFUSER

RECESSED LIGHT FIXTURE

EXPOSED TO STRUCTURE

EXIT SIGN, CEILING MOUNTED

EXIT SIGN, WALL MOUNTED

EXISTING 1x4 LIGHT FIXTURE TO REMAIN

(THIS SHEET ONLY)

EXISTING 2x2 LIGHT FIXTURE TO REMAIN

EXISTING PARTITIONS TO BE DEMOLISHED

NO DEMOLITION IN THIS AREA (THIS SHEET ONLY). REFER TO

PLUMBING, MECHANICAL, AND ELECTRICAL SHEETS FOR

DEMOLITION NOT SHOWN ON THIS SHEET.

EXISTING 2x2 ACT CEILING TO BE DEMOLISHED

EXISTING 1x4 LIGHT FIXTURE TO BE DEMOLISHED

EXISTING 2x4 LIGHT FIXTURE TO BE DEMOLISHED

SERVICE

ENTRANCE

MAIN

ENTRANCE

EXISTING PARTITIONS TO UNDERSIDE OF CEILING

S

Date

Location

Checked Drawn

Drawing Number

Building Number

Project NumberProject TitleDrawingTitle

Approved: Project Director

ARCHITECT/ENGINEERS:CONSULTANTS:

Dwg. of

A

B

C

D

E

F

Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

VA FORM 08-6231

th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

BOWMAN FOSTER

& ASSOCIATES, PC

ALEXANDRIA, VA 22312

6353 CENTER DR. STE 101

NORFOLK, VA 23502

5252 CHEROKEE AVE, STE 101

McPHERSON

DESIGN

GROUP p.c.

STRUCTURAL ENGINEERS

6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com

901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5

Engineers Surveyors Planners

HOGGARD/EURE ASSOCIATES, P.C.

FULLY SPRINKLERED

REFLECTED CEILING PLAN 'S' POD -

DEMOLITION

AD103

VA MEDICAL CENTER, HAMPTON, VA

JDB DAS 24 165

590-602

7/26/19

RENOVATE AND EXPAND

DOMICILIARY BUILDING 148

PLAN

NORTH

1/8" = 1'-0"

REFLECTED CEILING PLAN 'S' POD - DEMOLITION

CORRIDOR TO

SUPPORT FACILITY

1 1

3 3

ELEC.

CLOSET

TYP.

0 4' 8' 16'

SCALE: 1/8" = 1'-0"

NOTE: IF THIS DRAWING IS A REDUCTION,

GRAPHIC SCALE MUST BE USED.

GRAPHIC SCALE:

KEY PLAN (NOT TO SCALE)

A

B

C

D

PLAN

NORTH

LEGEND

EXISTING PARTITIONS

GYP BD CEILING

EXISTING 2x2 ACT CEILING TO REMAIN

AIR SUPPLY DIFFUSER

EXISTING 2x4 LIGHT FIXTURE TO REMAIN

DEMOLITION NOTES

REMOVE EXISTING ACT CEILING TO INCLUDE GRID. SALVAGE EXISTING

LIGHTING, FIRE PROTECTION AND OTHER CEILING MOUNTED ITEMS

UNLESS OTHERWISE NOTED FOR REINSTALLATION IN NEW CEILINGS

AFTER MECHANICAL WORK IS COMPLETE.

REMOVE EXISTING EXTERIOR PLASTER CEILING SYSTEM TO INCLUDE

LIGHT FIXTURES COMPLETE. EXISTING WOOD FRAMING SHALL REMAIN.

EXISTING PLASTER SOFFIT TO REMAIN UNLESS OTHERWISE NOTED -

TYPICAL.

AIR RETURN DIFFUSER

RECESSED LIGHT FIXTURE TO BE DEMOLISHED

EXPOSED TO STRUCTURE

EXISTING EXIT SIGN TO REMAIN

EXISTING 1x4 LIGHT FIXTURE TO REMAIN

(THIS SHEET ONLY)

EXISTING 1x2 LIGHT FIXTURE TO REMAIN

EXISTING PARTITIONS TO BE DEMOLISHED

EXISTING 2x2 ACT CEILING TO BE DEMOLISHED

EXISTING 2x4 LIGHT FIXTURE TO BE DEMOLISHED

SERVICE

ENTRANCE

MAIN

ENTRANCE

EXISTING PARTITIONS TO UNDERSIDE OF CEILING

RECESSED LIGHT FIXTURE TO REMAIN

S

GENERAL NOTES

1. REFER TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE

PROTECTION DRAWINGS FOR ITEMS NOT SHOWN ON THESE

DRAWINGS.

Date

Location

Checked Drawn

Drawing Number

Building Number

Project NumberProject TitleDrawingTitle

Approved: Project Director

ARCHITECT/ENGINEERS:CONSULTANTS:

Dwg. of

A

B

C

D

E

F

Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

VA FORM 08-6231

th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

BOWMAN FOSTER

& ASSOCIATES, PC

ALEXANDRIA, VA 22312

6353 CENTER DR. STE 101

NORFOLK, VA 23502

5252 CHEROKEE AVE, STE 101

McPHERSON

DESIGN

GROUP p.c.

STRUCTURAL ENGINEERS

6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com

901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5

Engineers Surveyors Planners

HOGGARD/EURE ASSOCIATES, P.C.

FULLY SPRINKLERED

REFLECTED CEILING PLAN 'A' POD -

DEMOLITION

AD104

VA MEDICAL CENTER, HAMPTON, VA

JDB DAS 25 165

590-602

7/26/19

RENOVATE AND EXPAND

DOMICILIARY BUILDING 148

PLAN

NORTH

REFLECTED CEILING PLAN 'A' POD - DEMOLITION

DAP OFFICE

LUGGAGE

STORAGE

KITCHENETTE

LAUNDRY

OFFICE

OFFICE

ELECTRICAL

CLOSET

STOR

COMM

CLOSET

HAC

STOR

STOR

BEDROOM

BEDROOM

LOUNGE

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

STORAGE

BEDROOM

H&CC

OFFICE

H&CC

RECEPTION

H&CC

MANAGER

ROOF

ACCESS

BEDROOM

BEDROOMBEDROOM

BEDROOM

NO CURE

BEDROOM

BEDROOM

DAP OFFICE OFFICE

ELEC

CLOSET

BEDROOM

BEDROOM

BEDROOM

BEDROOM

LOUNGE

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM BEDROOM

STOR

COMM

STOR

ROOF

ACCESS

LOUNGE

MED FOS HOME

OFFICE

SOILED LINEN

H&CC NURSE OFFICE

COURTYARD

1 1

1 1

TYP.

0 4' 8' 16'

SCALE: 1/8" = 1'-0"

NOTE: IF THIS DRAWING IS A REDUCTION,

GRAPHIC SCALE MUST BE USED.

GRAPHIC SCALE:

KEY PLAN (NOT TO SCALE)

A

B

C

D

PLAN

NORTH

SERVICE

ENTRANCE

MAIN

ENTRANCE

S

LEGEND

EXISTING PARTITIONS

GYP BD CEILING

EXISTING 2x2 ACT CEILING TO REMAIN

AIR SUPPLY DIFFUSER

EXISTING 2x4 LIGHT FIXTURE TO REMAIN

DEMOLITION NOTES

REMOVE EXISTING ACT CEILING TO INCLUDE GRID. SALVAGE EXISTING

LIGHTING, FIRE PROTECTION AND OTHER CEILING MOUNTED ITEMS

UNLESS OTHERWISE NOTED FOR REINSTALLATION IN NEW CEILINGS

AFTER MECHANICAL WORK IS COMPLETE.

REMOVE EXISTING EXTERIOR PLASTER CEILING SYSTEM TO INCLUDE

LIGHT FIXTURES COMPLETE. EXISTING WOOD FRAMING SHALL REMAIN.

EXISTING PLASTER SOFFIT TO REMAIN UNLESS OTHERWISE NOTED -

TYPICAL.

AIR RETURN DIFFUSER

RECESSED LIGHT FIXTURE TO BE DEMOLISHED

EXPOSED TO STRUCTURE

EXISTING EXIT SIGN TO REMAIN

EXISTING 1x4 LIGHT FIXTURE TO REMAIN

(THIS SHEET ONLY)

EXISTING 1x2 LIGHT FIXTURE TO REMAIN

EXISTING PARTITIONS TO BE DEMOLISHED

EXISTING 2x2 ACT CEILING TO BE DEMOLISHED

EXISTING 2x4 LIGHT FIXTURE TO BE DEMOLISHED

EXISTING PARTITIONS TO UNDERSIDE OF CEILING

RECESSED LIGHT FIXTURE TO REMAIN

GENERAL NOTES

1. REFER TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE

PROTECTION DRAWINGS FOR ITEMS NOT SHOWN ON THESE

DRAWINGS.

Date

Location

Checked Drawn

Drawing Number

Building Number

Project NumberProject TitleDrawingTitle

Approved: Project Director

ARCHITECT/ENGINEERS:CONSULTANTS:

Dwg. of

A

B

C

D

E

F

Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

VA FORM 08-6231

th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

BOWMAN FOSTER

& ASSOCIATES, PC

ALEXANDRIA, VA 22312

6353 CENTER DR. STE 101

NORFOLK, VA 23502

5252 CHEROKEE AVE, STE 101

McPHERSON

DESIGN

GROUP p.c.

STRUCTURAL ENGINEERS

6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com

901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5

Engineers Surveyors Planners

HOGGARD/EURE ASSOCIATES, P.C.

FULLY SPRINKLERED

REFLECTED CEILING PLAN 'B' POD -

DEMOLITION

AD105

VA MEDICAL CENTER, HAMPTON, VA

JDB DAS 26 165

590-602

7/26/19

RENOVATE AND EXPAND

DOMICILIARY BUILDING 148

1/8" = 1'-0"

REFLECTED CEILING PLAN 'B' POD - DEMOLITION

0 4' 8' 16'

SCALE: 1/8" = 1'-0"

NOTE: IF THIS DRAWING IS A REDUCTION,

GRAPHIC SCALE MUST BE USED.

GRAPHIC SCALE:

KEY PLAN (NOT TO SCALE)

A

B

C

D

PLAN

NORTH

SERVICE

ENTRANCE

MAIN

ENTRANCE

S

LEGEND

EXISTING PARTITIONS

GYP BD CEILING

EXISTING 2x2 ACT CEILING TO REMAIN

AIR SUPPLY DIFFUSER

EXISTING 2x4 LIGHT FIXTURE TO REMAIN

DEMOLITION NOTES

REMOVE EXISTING ACT CEILING TO INCLUDE GRID. SALVAGE EXISTING

LIGHTING, FIRE PROTECTION AND OTHER CEILING MOUNTED ITEMS

UNLESS OTHERWISE NOTED FOR REINSTALLATION IN NEW CEILINGS

AFTER MECHANICAL WORK IS COMPLETE.

REMOVE EXISTING EXTERIOR PLASTER CEILING SYSTEM TO INCLUDE

LIGHT FIXTURES COMPLETE. EXISTING WOOD FRAMING SHALL REMAIN.

EXISTING PLASTER SOFFIT TO REMAIN UNLESS OTHERWISE NOTED -

TYPICAL.

AIR RETURN DIFFUSER

RECESSED LIGHT FIXTURE TO BE DEMOLISHED

EXPOSED TO STRUCTURE

EXISTING EXIT SIGN TO REMAIN

EXISTING 1x4 LIGHT FIXTURE TO REMAIN

(THIS SHEET ONLY)

EXISTING 1x2 LIGHT FIXTURE TO REMAIN

EXISTING PARTITIONS TO BE DEMOLISHED

EXISTING 2x2 ACT CEILING TO BE DEMOLISHED

EXISTING 2x4 LIGHT FIXTURE TO BE DEMOLISHED

EXISTING PARTITIONS TO UNDERSIDE OF CEILING

RECESSED LIGHT FIXTURE TO REMAIN

GENERAL NOTES

1. REFER TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE

PROTECTION DRAWINGS FOR ITEMS NOT SHOWN ON THESE

DRAWINGS.

CORRIDOR TO

SUPPORT FACILITY

1 1 1

1 1

1 1

1 1

1 1

COURTYARD

TYP.

Date

Location

Checked Drawn

Drawing Number

Building Number

Project NumberProject TitleDrawingTitle

Approved: Project Director

ARCHITECT/ENGINEERS:CONSULTANTS:

Dwg. of

A

B

C

D

E

F

Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

VA FORM 08-6231

th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

BOWMAN FOSTER

& ASSOCIATES, PC

ALEXANDRIA, VA 22312

6353 CENTER DR. STE 101

NORFOLK, VA 23502

5252 CHEROKEE AVE, STE 101

McPHERSON

DESIGN

GROUP p.c.

STRUCTURAL ENGINEERS

6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com

901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5

Engineers Surveyors Planners

HOGGARD/EURE ASSOCIATES, P.C.

FULLY SPRINKLERED

REFLECTED CEILING PLAN 'C' POD -

DEMOLITION

AD106

VA MEDICAL CENTER, HAMPTON, VA

JDB DAS 27 165

590-602

7/26/19

RENOVATE AND EXPAND

DOMICILIARY BUILDING 148

REFLECTED CEILING PLAN 'C' POD - DEMOLITION

NOTE: IF THIS DRAWING IS A REDUCTION,

GRAPHIC SCALE MUST BE USED.

GRAPHIC SCALE:

KEY PLAN (NOT TO SCALE)

A

B

C

D

PLAN

NORTH

SERVICE

ENTRANCE

MAIN

ENTRANCE

S

LEGEND

EXISTING PARTITIONS

GYP BD CEILING

EXISTING 2x2 ACT CEILING TO REMAIN

AIR SUPPLY DIFFUSER

EXISTING 2x4 LIGHT FIXTURE TO REMAIN

DEMOLITION NOTES

REMOVE EXISTING ACT CEILING TO INCLUDE GRID. SALVAGE EXISTING

LIGHTING, FIRE PROTECTION AND OTHER CEILING MOUNTED ITEMS

UNLESS OTHERWISE NOTED FOR REINSTALLATION IN NEW CEILINGS

AFTER MECHANICAL WORK IS COMPLETE.

REMOVE EXISTING EXTERIOR PLASTER CEILING SYSTEM TO INCLUDE

LIGHT FIXTURES COMPLETE. EXISTING WOOD FRAMING SHALL REMAIN.

EXISTING PLASTER SOFFIT TO REMAIN UNLESS OTHERWISE NOTED -

TYPICAL.

AIR RETURN DIFFUSER

RECESSED LIGHT FIXTURE TO BE DEMOLISHED

EXPOSED TO STRUCTURE

EXISTING EXIT SIGN TO REMAIN

EXISTING 1x4 LIGHT FIXTURE TO REMAIN

(THIS SHEET ONLY)

EXISTING 1x2 LIGHT FIXTURE TO REMAIN

EXISTING PARTITIONS TO BE DEMOLISHED

EXISTING 2x2 ACT CEILING TO BE DEMOLISHED

EXISTING 2x4 LIGHT FIXTURE TO BE DEMOLISHED

EXISTING PARTITIONS TO UNDERSIDE OF CEILING

RECESSED LIGHT FIXTURE TO REMAIN

GENERAL NOTES

1. REFER TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE

PROTECTION DRAWINGS FOR ITEMS NOT SHOWN ON THESE

DRAWINGS.

CORRIDOR TO

SUPPORT

FACILITY

1 1

1 1

1 1

1 1

1 1

COURTYARD

TYP.

F4

AS601

Date

Location

Checked Drawn

Drawing Number

Building Number

Project NumberProject TitleDrawingTitle

Approved: Project Director

ARCHITECT/ENGINEERS:CONSULTANTS:

Dwg. of

A

B

C

D

E

F

Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

VA FORM 08-6231

th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

BOWMAN FOSTER

& ASSOCIATES, PC

ALEXANDRIA, VA 22312

6353 CENTER DR. STE 101

NORFOLK, VA 23502

5252 CHEROKEE AVE, STE 101

McPHERSON

DESIGN

GROUP p.c.

STRUCTURAL ENGINEERS

6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com

901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5

Engineers Surveyors Planners

HOGGARD/EURE ASSOCIATES, P.C.

FULLY SPRINKLERED

REFLECTED CEILING PLAN 'D' POD -

DEMOLITION

AD107

VA MEDICAL CENTER, HAMPTON, VA

JDB DAS 28 165

590-602

7/26/19

RENOVATE AND EXPAND

DOMICILIARY BUILDING 148

REFLECTED CEILING PLAN 'D' POD - DEMOLITION

CORRIDOR

TO POD A

CORRIDOR

TO POD D

CORRIDOR

TO POD C

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

TYP

F3

AS301

B1

AS302

3 3

0 4' 8' 16'

SCALE: 1/8" = 1'-0"

NOTE: IF THIS DRAWING IS A REDUCTION,

GRAPHIC SCALE MUST BE USED.

DEMOLITION NOTES

EXISTING MEMBRANE ROOF SYSTEM TO REMAIN.

REMOVE EXISTING STANDING SEAM ROOF, SHEATHING, ROOF AND

SOFFIT FRAMING COMPLETE.

EXISTING WOOD STUD WALL FRAMING, METAL PANELS, DOORS AND

LOUVERS SHALL REMAIN. REMOVE EXISTING METAL ROOF FASCIA AND

TRIM TO INCLUDE GUTTERS.

EXISTING STANDING SEAM METAL ROOF AND FASCIA TO REMAIN.

SCRAPE EXISTING STANDING SEAM METAL ROOFING AND FASCIA TO

REMOVE ALL RUST AND CORROSION, AND PREPARE SURFACE FOR

REFINISHING, AS INDICATED ON THE NEW WORK ROOF PLANS.

REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR EXISTING

EQUIPMENT AND ROOF PENETRATIONS WORK NOTES.

REMOVE EXISTING BUILT-UP ROOF SYSTEM AND METAL WALL

PANELS - REFER TO NEW WORK PLANS FOR EXTENT OF NEW ROOF

AND DETAILS.

(THIS SHEET ONLY)

GRAPHIC SCALE:

KEY PLAN (NOT TO SCALE)

A

B

C

D

PLAN

NORTH

SERVICE

ENTRANCE

MAIN

ENTRANCE

S

Date

Location

Checked Drawn

Drawing Number

Building Number

Project NumberProject TitleDrawingTitle

Approved: Project Director

ARCHITECT/ENGINEERS:CONSULTANTS:

Dwg. of

A

B

C

D

E

F

Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

VA FORM 08-6231

th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

BOWMAN FOSTER

& ASSOCIATES, PC

ALEXANDRIA, VA 22312

6353 CENTER DR. STE 101

NORFOLK, VA 23502

5252 CHEROKEE AVE, STE 101

McPHERSON

DESIGN

GROUP p.c.

STRUCTURAL ENGINEERS

6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com

901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5

Engineers Surveyors Planners

HOGGARD/EURE ASSOCIATES, P.C.

FULLY SPRINKLERED

ROOF PLAN 'S' POD - DEMOLITION

AD108

VA MEDICAL CENTER, HAMPTON, VA

JDB DAS 29 165

590-602

7/26/19

RENOVATE AND EXPAND

DOMICILIARY BUILDING 148

PLAN

NORTH

ROOF PLAN 'S' POD - DEMOLITION

COURTYARD

TYP

TYP

4 TYP

4 TYP

4 TYP

4TYP 5

4 TYP

4 TYP

4TYP

4TYP

TYP

TYP

TYP

TYP

TYP

4TYP

TYP

4 TYP

TYP

TYP

TYP

TYP

3TYP

TYP

0 4' 8' 16'

SCALE: 1/8" = 1'-0"

NOTE: IF THIS DRAWING IS A REDUCTION,

GRAPHIC SCALE MUST BE USED.

DEMOLITION NOTES

EXISTING ROOF SYSTEM TO REMAIN

NOT USED

EXISTING METAL PANEL WALL, FRAMING, AND DOORS TO REMAIN.

EXISTING STANDING SEAM METAL ROOF AND FASCIA TO REMAIN.

SCRAPE EXISTING STANDING SEAM METAL ROOFING AND FASCIA TO

REMOVE ALL RUST AND CORROSION, AND PREPARE SURFACE FOR

REFINISHING, AS INDICATED ON THE NEW WORK ROOF PLANS.

EXISTING STANDING SEAM METAL ROOF AND FASCIA TO REMAIN.

SCRAPE EXISTING STANDING SEAM METAL ROOFING AND FASCIA TO

REMOVE ALL RUST AND CORROSION, AND PREPARE SURFACE FOR

REFINISHING, AS INDICATED ON THE NEW WORK ROOF PLANS.

EXISTING ROOF HATCH TO REMAIN.

(THIS SHEET ONLY)

GRAPHIC SCALE:

KEY PLAN (NOT TO SCALE)

A

B

C

D

PLAN

NORTH

SERVICE

ENTRANCE

MAIN

ENTRANCE

S

Date

Location

Checked Drawn

Drawing Number

Building Number

Project NumberProject TitleDrawingTitle

Approved: Project Director

ARCHITECT/ENGINEERS:CONSULTANTS:

Dwg. of

A

B

C

D

E

F

Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

VA FORM 08-6231

th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

BOWMAN FOSTER

& ASSOCIATES, PC

ALEXANDRIA, VA 22312

6353 CENTER DR. STE 101

NORFOLK, VA 23502

5252 CHEROKEE AVE, STE 101

McPHERSON

DESIGN

GROUP p.c.

STRUCTURAL ENGINEERS

6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com

901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5

Engineers Surveyors Planners

HOGGARD/EURE ASSOCIATES, P.C.

FULLY SPRINKLERED

ROOF PLAN TYPICAL POD -

DEMOLITION

AD109

VA MEDICAL CENTER, HAMPTON, VA

JDB DAS 30 165

590-602

7/26/19

RENOVATE AND EXPAND

DOMICILIARY BUILDING 148

1/8" = 1'-0"

ROOF PLAN TYPICAL POD - DEMOLITION - (POD B SHOWN - POD'S A, C, & D SIM.)

NOTE: IF THIS DRAWING IS A REDUCTION,

GRAPHIC SCALE MUST BE USED.

GRAPHIC SCALE:

KEY PLAN (NOT TO SCALE)

A

B

C

D

PLAN

NORTH

SERVICE

ENTRANCE

MAIN

ENTRANCE

S

EXISTING WALL AND/OR DOOR TO BE DEMOLISHED

EXISTING WINDOW TO BE DEMOLISHED

EXISTING WALL, WINDOW, AND/OR DOOR TO REMAIN

LEGEND

DEMOLITION NOTES

REMOVE EXISTING WALLS WHERE INDICATED IN THEIR ENTIRETY.

REMOVE EXISTING DOORS TO INCLUDE FRAMES AND HARDWARE IN

THEIR ENTIRETY.

REMOVE WALL-MOUNTED HVAC INDUCTION UNIT AND WINDOW STOOL

COMPLETE. REFER TO MECHANICAL DRAWINGS AND DETAIL

REMOVE EXISTING PLUMBING FIXTURE AND DRYWALL TO PROVIDE

ACCESS TO EXISTING PLUMBING LINES. EXISTING WALL FRAMING MUST

REMAIN. REFER TO PLUMBING DRAWINGS FOR ADDITIONAL NOTES.

REMOVE EXISTING CERAMIC TILE SHOWER ENCLOSURE IN ITS

ENTIRETY.

NOT USED.

REMOVE EXISTING PLUMBING FIXTURES, TOILET PARTITIONS, TOILET

ACCESSORIES IN THEIR ENTIRETY.

REMOVE EXISTING GYPSUM WALL BOARD AND CERAMIC TILE WHERE

INDICATED TO PROVIDE ACCESS TO EXISTING PLUMBING LINES BEHIND

THE EXISTING WALLS. EXISTING WALL FRAMING TO REMAIN. PREPARE

WALLS FOR INSTALLATION OF NEW GYPSUM BOARD AFTER NEW

PLUMBING WORK IS COMPLETE. REFER TO SHEET AS902 FOR NEW

WORK.

REMOVE EXISTING EPOXY TERRAZZO FLOORING AND CERAMIC TILE

WAINSCOT IN ITS ENTIRETY IN THIS SPACE.

(THIS SHEET ONLY)

/A1 AS501

DAP OFFICE

LUGGAGE

STORAGE

KITCHENETTE

LAUNDRY

OFFICE

OFFICE

ELECTRICAL

CLOSET

STOR

COMM

CLOSET

HAC

STOR

STOR

BEDROOM

BEDROOM

LOUNGE

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

STORAGE

BEDROOM

H&CC

OFFICE

H&CC

RECEPTION

H&CC

MANAGER

ROOF

ACCESS

BEDROOM

BEDROOMBEDROOM

BEDROOM

NO CURE

BEDROOM

BEDROOM

DAP OFFICE

OFFICE

ELEC

CLOSET

BEDROOM

BEDROOM

BEDROOM

BEDROOM

LOUNGE

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM BEDROOM

STOR

COMM

STOR

ROOF

ACCESS

LOUNGE

MED FOS HOME

OFFICE

SOILED LINEN

H&CC NURSE OFFICE

82'-4"± 16'-8"± 66'-9"± 14'-6"±

180'-3"±

17'-7"± 46'-1"± 39'-0"± 17'-0"± 35'-8"± 10'-4"± 14'-7"±

56'-0"±

COURTYARD

3 3

3 3 3

3 3 3

3 3

8 8

8 8

REDO COMPLETELY.

TYP. FOR POD'S

A,B,C,D.

Date

Location

Checked Drawn

Drawing Number

Building Number

Project NumberProject TitleDrawingTitle

Approved: Project Director

ARCHITECT/ENGINEERS:CONSULTANTS:

Dwg. of

A

B

C

D

E

F

Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

VA FORM 08-6231

th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

BOWMAN FOSTER

& ASSOCIATES, PC

ALEXANDRIA, VA 22312

6353 CENTER DR. STE 101

NORFOLK, VA 23502

5252 CHEROKEE AVE, STE 101

McPHERSON

DESIGN

GROUP p.c.

STRUCTURAL ENGINEERS

6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com

901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5

Engineers Surveyors Planners

HOGGARD/EURE ASSOCIATES, P.C.

FULLY SPRINKLERED

FLOOR PLAN TYPICAL POD -

DEMOLITION - BID DEDUCT

AD902

VA MEDICAL CENTER, HAMPTON, VA

JDB DAS 31 165

590-602

7/26/19

RENOVATE AND EXPAND

DOMICILIARY BUILDING 148

PLAN

NORTH

1/8" = 1'-0"

FLOOR PLAN TYPICAL POD - DEMOLITION - BID DEDUCT

**NOTE: DEMOLITION INDICATED ON THIS

SHEET APPLIES TO PODS 'A', 'B',

'C', AND 'D'. POD 'B' IS SHOWN.

UPUP

A1

AS201

C1

AS201

xH xH x2 x2 x1 x1 x3 x3 x4 x4 x5 x5 x6 x6 x7 x7 xL xL xK xK xJ xJ xG xG xF xF xE xE xD xD xB xB xC xC xA xA

CORRIDOR

TO POD B

CORRIDOR

TO POD A

CORRIDOR

TO POD D

CORRIDOR

TO POD C

EMERGENCY

GENERATOR

ROOM

STORAGE

MAIN

TELEPHONE

CLOSET

ELECTRICAL

CLOSET

LOUNGE

GENERAL

STORAGE

OFFICE OFFICE

CHIEF

DOMICILLARY OFFICE

OFFICE

MAIN

ENTRANCE

S136B

EXISTING

RECREATION

ROOM

VENDING

DOMICILLARY

CARE

OFFICE/

RECEPTION

STORAGE

OFFICE

OFFICE

OFFICE

OFFICEOFFICE

H.A.C.

ELECTRICAL VAULT

MECHANICAL ROOM

STORAGE

EMS STORAGE

STORAGE

CONFERENCE ROOM

OFFICE

S115

PATIENT SCREENING

C1

AS401

D5

AS401

S134C

S134A S134B

S122

S115

A L

IG

N

ALIGN

A

8'-0"

1'-4"

5'-10"

1'-0"

7'-0"

1'-0"

7'-0"

1'-0"

7'-0"

1'-0"

5'-10"

1'-0"+/-

8'-8 1/4" 3'-0"

EQ

1'-0"

7'-2"

1'-0"

EQ

1'-0"

7'-2"

1'-0"

1'-0"

14'-0"

1'-0"

15'-0"

1'-0"

14'-0"

1'-0"

B

B B B

B

AS401

S121

EXISTING

WOMEN'S

S122

EXISTING

MEN'S

S142

LIBRARY

S134

GROUP ROOM

S

S T O R A G E

S102

TOILET

E1

AS201

E1

AS201

A6

AS201

S136A

FITNESS

ROOM

S135

CORRIDOR

F1

AS302

F3

AS302

F1

AS301

ELEC. CLOSET

A2

ALIGN

D E D

F C C C F

A L

IG

N

A L

IG

N

8'-8 3/8"

C8

AS501

F8

AS501

F3

AS501

A2 TYP.

2"2"

G

F3

AS301

S135

E6

AS301

A1

E8

AS301

E1

6 6

C8

AS501

F8

AS501

F8

AS501

S141

WOMEN'S

S140

MEN'S

C8

AS501

C8

AS501

EXISTING WALL, WINDOW, AND/OR DOOR TO REMAIN

GENERAL NOTES

SEE ENLARGED PLAN FOR PARTITION TYPES NOT INDICATED.

SUPPORT FACILITY EXISTING GROSS SQUARE FOOTAGE IS 19,725 SF.

SUPPORT FACILITY RENOVATED SQUARE FOOTAGE IS 3,210 SF.

SUPPORT FACILITY NEW SQUARE FOOTAGE IS 1,911 SF.

REMOVE WALL NEAR GENERAL STORAGE, ADD FLOORING TO MATCH

EXISTING VCT IN COLOR, SIZE, AND KIND.

ALL NEW WALLS AND EXISTING ADJACENT WALLS MUST BE PAINTED.

0 4' 8' 16'

SCALE: 1/8" = 1'-0"

NOTE: IF THIS DRAWING IS A REDUCTION,

GRAPHIC SCALE MUST BE USED.

CONSTRUCTION NOTES

PROVIDE 8' HIGH TEMPERED GLASS MIRROR, FULL WIDTH OF WALL

INDICATED WITH J-CHANNEL AT BOTTOM.

PROVIDE NEW GYPSUM WALL BOARD ON ALL EXISTING AND NEW

STUDS, REFER TO FINISH PLANS AND SCHEDULE FOR NEW FINISHES.

REFER TO SHEET AS401 FOR ADDITIONAL WORK.

PROVIDE 5/8” GYPSUM WALL BOARD ON EXISTING WALL FRAMING,

FULL WIDTH AND HEIGHT TO MATCH EXISTING GYPSUM BOARD. AFTER

NEW PLUMBING HAS BEEN COMPLETE. SAND JOINT SMOOTH AND ALL

EXPOSED GYPSUM WALL BOARD IN SPACE MUST BE PAINTED. SEE

FINISH SCHEDULE FOR PAINT FINISHES.

PROVIDE 5/8” GYPSUM WALL BOARD ON EXISTING WALL FRAMING,

FULL WIDTH AND HEIGHT OF WALL INDICATED. PROVIDE 4” X 4”

CERAMIC TILE WAINSCOT WITH BULLNOSE TOP TRIM TO 4’-6” A.F.F.

GYPSUM WALL BOARD SHALL BE ALIGNED WITH THE FACE OF

ADJACENT EXISTING GYPSUM BOARD, SANDED SMOOTH, AND EXPOSED

GYPSUM WALL BOARD ABOVE THE TILE WAINSCOT SHALL BE PAINTED.

SEE FINISH SCHEDULE FOR TILE AND PAINT SELECTIONS.

PROVIDE NEW ALUMINUM STOREFRONT WITH 1/4" TEMPERED CLEAR

GLASS. REFER TO INTERIOR WINDOW ELEVATIONS FOR SIZE AND

DETAILS, SHEET AS601.

PROVIDE 7/8" METAL FURRING AND 5/8" GYPSUM WALL BOARD OVER

EXISTING BRICK AND EXISTING STUD WALLS FULL HEIGHT TO 6"

ABOVE CEILING.

PROVIDE NEW EXTERIOR ALUMINUM STOREFRONT SYSTEM WITH 1"

INSULATION GLASS TO MATCH EXISTING.

PROVIDE NEW VCT FLOOR TILE TO MATCH EXISTING TO PATCH AREA

WHERE EXISTING WALL WAS REMOVED.

INFILL EXISTING WINDOW OPENINGS - REFER TO DETAIL

INFILL EXISTING WINDOW OPENING - REFER TO DETAIL

PAINT EXISTING BRICK PIERS TO MATCH ADJACENT WALLS.

1.

2.

3.

4.

5.

6.

(THIS SHEET ONLY)

GRAPHIC SCALE:

LEGEND

KEY PLAN (NOT TO SCALE)

A

B

C

D

PLAN

NORTH

SERVICE

ENTRANCE

MAIN

ENTRANCE

S

NEW WALL, WINDOW, AND/OR DOOR

10 /E6 AS301

/E8 AS301

Date

Location

Checked Drawn

Drawing Number

Building Number

Project NumberProject TitleDrawingTitle

Approved: Project Director

ARCHITECT/ENGINEERS:CONSULTANTS:

Dwg. of

A

B

C

D

E

F

Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

VA FORM 08-6231

th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

BOWMAN FOSTER

& ASSOCIATES, PC

ALEXANDRIA, VA 22312

6353 CENTER DR. STE 101

NORFOLK, VA 23502

5252 CHEROKEE AVE, STE 101

McPHERSON

DESIGN

GROUP p.c.

STRUCTURAL ENGINEERS

6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com

901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5

Engineers Surveyors Planners

HOGGARD/EURE ASSOCIATES, P.C.

FULLY SPRINKLERED

FLOOR PLAN 'S' POD - NEW WORK

AS101

VA MEDICAL CENTER, HAMPTON, VA

JDB DAS 32 165

590-602

7/26/19

RENOVATE AND EXPAND

DOMICILIARY BUILDING 148

PLAN

NORTH

FLOOR PLAN 'S' POD - NEW WORK

DAP OFFICE

LUGGAGE

STORAGE

KITCHENETTE

LAUNDRY

MED FOS HOME

OFFICE

OFFICE

OFFICE

ELECTRICAL

CLOSET

STOR

COMM

CLOSET

SOILED LINEN

HAC

STOR

STOR

BEDROOM

BEDROOM

LOUNGE

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

STORAGE

BEDROOM

H&CC

OFFICE

H&CC

RECEPTION

H&CC NURSE OFFICE

H&CC

MANAGER

ROOF

ACCESS

BEDROOM

BEDROOMBEDROOM

BEDROOM

NO CURE

BEDROOM

BEDROOM

DAP OFFICE

OFFICE

ELEC

CLOSET

BEDROOM

BEDROOM

BEDROOM

BEDROOM

LOUNGE

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM BEDROOM

STOR

COMM

STOR

ROOF

ACCESS

LOUNGE

C3

AS401

B5

AS401

COURTYARD

TOILET

TOILET

TOILET

B-102 A

A

A

A

A

A

A

A A A

A

A

A A A

B

A

A

A

A

A

A

A

AAAA

AA

A

A

A

A

A

A

A

A

2 2

2 2

2 2

2 2

2 1 2 2

1 1 1

1 1

1 1

1 2

3 4

4 4

B

5 5

5 5 5

5 5 5

GENERAL NOTES

SEE ENLARGED PLAN FOR PARTITION TYPES NOT INDICATED.

TYPICAL POD GROSS SQUARE FOOTAGE IS 18,193 SF.

TYPICAL POD RENOVATED SQUARE FOOTAGE IS 257 SF.

PATIENT ROOM MECHANICAL SYSTEMS TO BE REMOVED. PAINT

GYPSUM BOARD TO MATCH EXISTING COLOR AND FINISH

NOTE: IF THIS DRAWING IS A REDUCTION,

GRAPHIC SCALE MUST BE USED.

1.

2.

3.

4.

KEY PLAN (NOT TO SCALE)

A

B

C

D

PLAN

NORTH

SERVICE

ENTRANCE

MAIN

ENTRANCE

S

CONSTRUCTION NOTES

PROVIDE NEW ALUMINUM WINDOW W/ 1" INSULATED GLASS. FIELD

VERIFY ROUGH WINDOW OPENING - REFER TO WINDOW TYPES.

PROVIDE METAL STUDS AND DRYWALL WALL INFILL - REFER TO SHEET

AS501.

PROVIDE 5/8” GYPSUM WALL BOARD ON EXISTING WALL FRAMING,

FULL WIDTH AND HEIGHT TO MATCH EXISTING GYPSUM BOARD. AFTER

NEW PLUMBING HAS BEEN COMPLETE. SAND JOINT SMOOTH AND ALL

EXPOSED GYPSUM WALL BOARD IN SPACE MUST BE PAINTED. SEE

FINISH SCHEDULE FOR PAINT FINISHES.

PROVIDE 5/8” GYPSUM WALL BOARD ON EXISTING WALL FRAMING,

FULL WIDTH AND HEIGHT OF WALL INDICATED. PROVIDE 4” X 4”

CERAMIC TILE WAINSCOT WITH BULLNOSE TOP TRIM TO 4’-6” A.F.F.

GYPSUM WALL BOARD SHALL BE ALIGNED WITH THE FACE OF

ADJACENT EXISTING GYPSUM BOARD, SANDED SMOOTH, AND EXPOSED

GYPSUM WALL BOARD ABOVE THE TILE WAINSCOT SHALL BE PAINTED.

SEE FINISH SCHEDULE FOR TILE AND PAINT SELECTIONS.

PROVIDE NEW SOLID SURFACE WINDOW STOOL.

(THIS SHEET ONLY)

EXISTING WALL, WINDOW, AND/OR DOOR TO REMAIN

LEGEND

NEW WALL, WINDOW, AND/OR DOOR

0 4' 8' 16'

SCALE: 1/8" = 1'-0"

GRAPHIC SCALE:

Date

Location

Checked Drawn

Drawing Number

Building Number

Project NumberProject TitleDrawingTitle

Approved: Project Director

ARCHITECT/ENGINEERS:CONSULTANTS:

Dwg. of

A

B

C

D

E

F

Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

VA FORM 08-6231

th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

BOWMAN FOSTER

& ASSOCIATES, PC

ALEXANDRIA, VA 22312

6353 CENTER DR. STE 101

NORFOLK, VA 23502

5252 CHEROKEE AVE, STE 101

McPHERSON

DESIGN

GROUP p.c.

STRUCTURAL ENGINEERS

6371 Center Drive, Suite 100 Norfolk, Virginia 23502-4102 Phone (757) 965-2000 Facsimile (757) 965-2001 www.McPhersonDesignGroup.com

901 PortCentre Parkway, Portsmouth, Virginia 23704 Suite 5

Engineers Surveyors Planners

HOGGARD/EURE ASSOCIATES, P.C.

FULLY SPRINKLERED

FLOOR PLAN TYPICAL POD - NEW

WORK

AS102

VA MEDICAL CENTER, HAMPTON, VA

JDB DAS 33 165

590-602

7/26/19

RENOVATE AND EXPAND

DOMICILIARY BUILDING 148

PLAN

NORTH

1/8" = 1'-0"

FLOOR PLAN TYPICAL POD - NEW WORK - (POD B SHOWN - POD'S A, C, & D SIM.)

NOTE: NEW WORK INDICATED ON THIS

CORRIDOR

TO POD A

CORRIDOR

TO POD D

CORRIDOR

TO POD C

(8'-0")

(8'-0")

(9'-0")

(8'-0")

(8'-0")

(9'-0")

S134

GROUP

ROOMS135

CORRIDOR

S115

PATIENT

SCREENING

S121

EXISTING

WOMEN'S

S122

EXISTING

MEN'S

S142

LIBRARY

S102

TOILET

S103

STORAGE

(9'-0")

TYP

1 1

NO CEILING WORK THIS AREA

NO CEILING

WORK THIS AREA

NO CEILING

WORK THIS AREA

(9'-0") (9'-0")

(7'-11")

(8'-0")

(8'-11") (8'-11")5

0 4' 8' 16'

SCALE: 1/8" = 1'-0"

NOTE: IF THIS DRAWING IS A REDUCTION,

GRAPHIC SCALE MUST BE USED.

GRAPHIC SCALE:

KEY PLAN (NOT TO SCALE)

A

B

C

D

PLAN

NORTH

LEGEND

NEW PARTITIONS

GYP BD CEILING

2x2 ACT CEILING

AIR SUPPLY DIFFUSER

2x4 LIGHT FIXTURE

GENERAL CEILING NOTES

UNLESS OTHERWISE NOTED, CEILING TILE SHALL BE CENTERED IN

EACH ROOM, IN ACCORDANCE WITH THE LAYOUTS SHOWN.

THE CEILING CONTRACTOR SHALL MAKE ADJUSTMENTS NECESSARY

TO ELIMINATE ADDITIONAL, SMALL, OR ODD PIECES OF CEILING TILE.

REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR LIGHT

FIXTURES, EXIT LIGHT LOCATIONS, AIR DIFFUSERS, EXHAUST FANS,

ETC.

WHERE TILES ARE CUT, COPE AND FINISH EDGES TO MATCH UNCUT

TILE.

ALL DIMENSIONS ON CEILING PLAN ARE TO FINISHED SURFACES AND

CENTER LINES OF FIXTURES.

CENTER ALL LIGHTS, DIFFUSERS, FIXTURES, SPRINKLER HEADS, ETC.

IN CEILING TILES UNLESS OTHERWISE NOTED.

THE CONTRACTOR SHALL DAMP CLEAN AND HAND DRY ALL FIXTURES

AND LAMPS JUST PRIOR TO FINAL INSPECTION.

SEE INTERIOR ELEVATIONS AND ELECTRICAL DRAWINGS FOR LIGHT

FIXTURE MOUNTING.

ALL NEW CEILING MUST BE INSTALLED AT THE HEIGHT OF THE

ORIGINAL CEILING UNLES OTHERWISE NOTED.

PROVIDE NEW ACOUSTICAL TILE CEILING. ALIGN GRID TO EXISTING

LIGHT FIXTURES.

PROVIDE NEW 5/8" GYP. BOARD CEILING ON EXISTING FRAMING. PAINT

TO MATCH EXISTING.

PROVIDE NEW SUSPENDED TILE CEILING. EXISTING SLOPED ACOUSTICAL

TILE CEILING AT UNDERSIDE OF ROOF JOISTS TO REMAIN.

PROVIDE PLASTER SOFFIT AFTER NEW MECHANICAL WORK IS COMPLETE.

PROVIDE DRYWALL BULKHEAD.

1.

2.

3.

4.

5.

6.

7.

8.

9.

CONSTRUCTION NOTES (THIS SHEET ONLY)

AIR RETURN DIFFUSER

2x4 EMERGENCY LIGHT FIXTURE

PENDANT LIGHT FIXTURE

RECESSED LIGHT FIXTURE

EXPOSED TO STRUCTURE

EXIT SIGN, CEILING MOUNTED

EXIT SIGN, WALL MOUNTED

1x4 LIGHT FIXTURE

1x4 EMERGENCY LIGHT FIXTURE

(THIS SHEET ONLY)

2x2 LIGHT FIXTURE

SERVICE

ENTRANCE

MAIN

ENTRANCE

S

Date

Location

Checked Drawn

Drawing Number

Building Number

Project NumberProject TitleDrawingTitle

Approved: Project Director

ARCHITECT/ENGINEERS:CONSULTANTS:

Dwg. of

A

B

C

D

E

F

Revisions: Date th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

VA FORM 08-6231

th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

BOWMAN FOSTER

& ASSOCIATES, PC

ALEXANDRIA,…