Attachment F - FP PH1 Surge Tank Roof STEP 1 Drawings.pdf
PDF 11 MB Posted
- Attached to
- Fort Peck PH 1 Surge Tank Roof Replacement
- Solicitation number
- W9128F25BA002
About this file
These engineering drawings detail the roof replacement project for Powerhouse #1 at Fort Peck Dam in Montana. The comprehensive set of architectural and structural plans, prepared by the US Army Corps of Engineers Omaha District, covers the complete removal and restoration of the existing clay tile roof, which was originally constructed in the 1940s. Key technical specifications include:
The drawings outline a meticulous restoration process involving removal of existing 15-pound asphalt-impregnated felt, coal-tar pitch, and original clay tiles, with replacement using new Ludowici tiles matching the historical design. The roof, situated 272.48 feet above grade, has an 8:12 slope and spans 40 feet in diameter, covering approximately 2,500 square feet. The project aims to preserve the structural integrity of the precast concrete roof panels while maintaining the historical character of the Fort Peck Dam, with careful documentation to ensure compliance with Montana State Historical Preservation Office (SHPO) regulations.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
S T
E P
S O
L
IC
IT
A
T
IO
N
A N
S I
D
P O
W E
R H
O U
S E
R O
O F
R E
P A
IR
S
F O
R T
P E
C K
D A
M
M O
N T
A N
A
W
F
B A
/0
/2
M
A H
A
N E
C A
P
IT
O L
A V
E
O M
A H
A D
IS
T
R
IC
T
F
IL
E
N U
M B
E R
F
IL
E N
A M
E
C F
O S
M E
R
C
V E
R
I N
D E
X
G-001
M H
O F
F M
A N
C F
O S
M
G
-0
.d g n
H
O F
F M
N
SOLICITATION NO.:
CONTRACT NO.:
ISSUE DATE:
POWERHOUSE #1 ROOF REPAIRS
FORT PECK DAM, MONTANA
W9128F25BA002
04/04/2025
OMAHA DISTRICT
of Engineers
US Army Corps
Omaha District of Engineers
US Army Corps
SUBMITTED BY:
CHIEF:
SUBMITTED BY:
CHIEF:
SUBMITTED BY:
CHIEF:
SUBMITTED BY:
CHIEF:
SUBMITTED BY:
CHIEF:
SUBMITTED BY:
CHIEF:
SUBMITTED BY:
CHIEF:
SUBMITTED BY:
SECTION
PE
SECTION
PE
SECTION
PE
SECTION
PE
SECTION
PE
SECTION
SECTION
RA
CADD
PROJECT COORD.
DATE
DATE
DATE
DATE
CHIEF, DESIGN BRANCH
SIGNATURES AFFIXED BELOW INDICATE OFFICIAL RECOMMENDATION AND APPROVAL OF DRAWINGS IN THIS SET.
ENGINEERING DIVISION, P.E.
CHIEF,
EMPLOYMENT AS REQUIRED BY ER 1110-1-8152
AND REGISTRATION DESIGNATIONS OF INDIVIDUALS APPEAR ON THESE PROJECT DOCUMENTS WITHIN THE SCOPE OF THEIR
THIS PROJECT WAS DESIGNED BY THE OMAHA DISTRICT OF THE US ARMY CORPS OF ENGINEERS. THE INITIALS OR SIGNATURES
ENGINEERING & SCIENCES BRANCH
CHIEF, GEOTECHNICAL
ENGINEERING BRANCH
CHIEF, HYDROLOGIC
FUELS
ARCH. / INTER.
ELEC.
MECH.
PE
CIVIL / ENVIR.
STRUCT.
DATECHIEF, DAM SAFETY PROD.
CENTER
GEOT./ DAM SAFETY
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
S T
E P
S O
L
IC
IT
A
T
IO
N
A N
S I
D
W E
R H
O U
S E
R O
O F
R E
P A
IR
S
F O
R T
P E
C K
D A
M
M O
N T
A N
A
W
F
B A
/0
/2
A H
A
N E
C A
P
IT
O L
A V
E
O M
A H
A D
IS
T
R
IC
IL
E
N U
M B
E R
F
IL
E N
A M
E
C F
O S
M
B
B R
E V
IA
T
IO
N
S
G-002
M H
O F
F M
A N
C F
O S
M
G
-0
.d g
H
O F
F M
CONTRACTORCONTR
CONTINUE CONT
CONSTRUCTIONCONSTR
CONNECTCONN
CONCRETECONC
COMPARTMENTCOMPT
COMBUSTIONCOMB
COMMONCOM
COLUMNCOL
CARBON DIOXIDECO2
CLEANOUTCO
COUNTERCNTR
CORNERCNR
CONDUCTIVE NEOPRENE LATEXCNL
CONDUITCND
CONCRETE MASONRY UNITCMU
COMPOSITECMPST
CORRUGATED METAL PIPECMP
CENTIMETER(S)cm
CLEAR WIRED GLASSCLWG
CLEAR(ANCE)CLR
CLOSURECLOS
CLOSETCLO
CONTRACT LIMIT LINECLL
CLEAR GLASSCLGL
CEILING HEIGHTCLG HT
CEILINGCLG
CENTER LINECL
CIRCUIT BREAKERCKT BRKR
CIRCUITCKT
CONSTRUCTION JOINTCJ
CONTROL JOINTCJ
CIRCULARCIRC
CAST-IN-PLACECIP
CURB INLETCI
CAST IRONCI
CHROME PLATEDCHR PL
CHECKCHK
CHIMNEYCHIM
CHAMFERCHFR
CHALKBOARDCH BD
CORNER GUARDCG
CUBIC FEET PER MINUTECFM
COUNTERFLASHINGCFLG
CONDUCTIVE FLOORINGCFI
CERAMICCER
CEMENT PLASTERCEM PLAS
CEMENTCEM
COVER ELEVATIONCE
CLOSED CIRCUIT TELEVISIONCCTV
CUBICLE CURTAIN TRACKCCT
CATCH BASINCB
CAPACITYCAP
CABINETCAB
BOTH WAYSBW
BUILT-UP ROOFINGBUR
BETWEENBTWN
BTU PER HOURBtuH
BRITISH THERMAL UNITBtu
BASEMENTBSMT
BOTH SIDESBS
BRONZEBRZ
BRACKETBRKT
BRICKBRK
BEARING PLATEBRG PL
BEARINGBRG
BRIDGINGBRDG
BRACINGBRCG
BACK PLASTER(ED)BP
BOTTOMBOT
BOTTOM OFBO
BENCHMARKBM
BELOWBLW
BUILDINGBLDG
BUILDING LINEBL
BED JOINTBJT
BITUMINOUSBITUM
BEVELBEV
BRICK EXPANSION JOINTBEJ
BOUNDARYBDRY
BOARDBD
BOOKCASEBC
BULLETIN BOARDBB
ACOUSTICAL WALL TREATMENTAWT
AMERICAN WIRE GAUGEAWG
AVERAGEAVG
AUTOMATICAUTO
ACOUSTICAL TILE CEILINGATC
ASPHALTASPH
ABOVE SUSPENDED CEILINGASC
ASBESTOSASB
AMERICAN REFRIGERATION INSTITUTEARI
ARCHITECTARCH
APPROXIMATEAPPROX
APPROVEDAPPD
AMERICAN NATIONAL STANDARDS INSTITUTEANSI
ANODIZEANOD
AMPEREAMP
AMBIENTAMB
ALUMINUMALUM
ALTERNATEALT
ACTIVE LEAFA.L.
AMERICAN INSTITUTE OF STEEL CONSTRUCTIONAISC
AMPERE INTERRUPTING CAPACITYAIC
AREA INLETAI
AIR HANDLING UNITAHU
ANCHOR AHR
AGGREGATEAGGR
ABOVE FINISHED FLOORAFF
AUTOMATIC DOOR OPERATORADO
ADJACENT, ADJOINING, ADJUSTABLEADJ
ADHESIVEADH
ADDENDUMADDM
ACOUSTICAL CEILING TILEACT
ACOUSTICACST
ALUMINUM CABLE STEEL REINFORCEDACSR
ACCESS PANELACS PNL
ACCESS DOORACS DR
ACRYLIC PLASTICACR
AMERICAN CONCRETE INSTITUTEACI
ACCESSIBLEACC
ALTERNATING CURRENTAC
ABOVEABV
ANCHOR BOLTAB
AIR CONDITIONING UNITA/C UNIT
AIR CONDITIONINGA/C
ANGLEL
FLOORFLR
FLASHINGFLASH
FLUSH JOINTFJT
FIXTUREFIXT
FINISH FLOORFIN FLR
FINISHFIN
FIGUREFIG
FLAT HEAD WOOD SCREWFHWS
FIRE HOSE STATIONFHS
FIRE HOSE RACKFHR
FLAT HEAD MACHINE SCREWFHMS
FIRE HOSE CABINETFHC
FLAT HEADFH
FIRE HYDRANTFH
FIBERGLASSFGL
FACTORY FINISHFF
FIRE EXTINGUISHER CABINETFEC
FIRE EXTINGUISHER BRACKETFEB
FIRE EXTINGUISHERFE
FOUNDATIONFDTN
FIRE DAMPERFDMPR
FLOOR DRAINFD
FAN COIL UNITFCU
FLOOR CLEANOUTFCO
FLOOR CONSTRUCTION JOINTFCJ
FACINGFCG
FACE BRICKFC BRK
FOOT CANDLEFC
FIRE BRICKF BRK
FRESH AIR INTAKEFAI
FIRE APPARATUS CLOSETFAC
FRESH AIRFA
FIRE ALARMFA
FAHRENHEITF
EXTERIOREXT
EXPANSION BOLTEXP BT
EXPOSEDEXP
EXPANSIONEXP
EXISTINGEXST
EXHAUST AIREXH A
EXHAUSTEXH
EXCAVATEEXC
ENTERING WATER TEMPERATUREEWT
ELECTRIC WATER COOLEREWC
ESTIMATE(D)EST
ESCALATORESCAL
EQUIPMENTEQUIP
EQUALEQ
EPOXY COATINGEPY
EXPLOSION PROOFEPRF
ELECTRICAL PANELBOARDEP
ENTRANCE, ENTERINGENTR
ENCLOSE(URE)ENCL
EMERGENCYEMER
ESTIMATED MAXIMUM DEMANDEMD
EXPANDED METAL EM
ELECTRICELEC
ELEVATION - GRADE OR BUILDINGEL
EXPANSION JOINTEJ
EACH FACEEF
ENTERING AIR TEMPERATUREEAT
EACHEA
EASTE
DIRECT EXPANSIONDX
DUMBWAITERDWTR
DRAWERDWR
DOWELSDWLS
DRAWINGDWG
DOVETAIL DVTL
DRAIN TILEDT
DOWNSPOUTDS
DOUBLE STRENGTH (GLASS)DS
DOOR CLOSERDR CL
DRAINBOARDDRB
DRAINDR
DOORDR
DOWNDN
DEMOUNTABLEDMT
DAMPERDMPR
DAMPPROOFINGDMPF
DEAD LOADDL
DIVISIONDIV
DISTRIBUTION PANELDISTR PNL
DISPENSERDISP
DISCONNECTDISC
DIMENSIONDIM
DIAGONALDIAG
DIAMETERDIA
DUCT HEATERDH
DOUBLE HUNGDH
DRINKING FOUNTAINDF
DETAILDET
DEPARTMENTDEPT
DEPRESSIONDEPR
DEMOLITIONDEMO
DEGREEDEG
DUMMY CONTROL JOINTDCJT
DOWELED CONTROL JOINTDCJ
DOUBLE ACTING DOORDBL ACT DR
DOUBLEDBL
DRY BULBDB
DATUMDAT
PENNY (AS IN NAIL - 10D)d
CYLINDERCYL
COLD WATERCW
CONDUCTIVE VINYL HOMOGENEOUS (SHEET TYPE)CVH
CEILING VENTCV
CUBIC YARDSCU YD
CABINET UNIT HEATERCUH
CUBIC FEETCU FT
COPPERCu
CONDENSING UNITCU
CENTERCTR
CENTER TO CENTERC TO C
CURRENT TRANSFORMERCT
CERAMIC TILECT
CASEMENTCSMT
COUNTERSUNKCSK
CAST STONECS
COURSE(S)CRS
CROSS GRAINCRG
CORROSIVE RESISTANT STEELCRES
CIRCUMFERENCECRCMF
CARPETCPT
COMPRESSIBLECPRS
COVERCOV
CORRIDORCORR
LAG BOLTLB
LAVATORYLAV
LAUNDRYLAU
LEAVING AIR TEMPERATURELAT
LAMINATELAM
LADDERLAD
LABORATORYLAB
KEYWAYKWY
KILOWATTkW
KILOVOLT AMPERES REACTIVEkVAR
KILOVOLT AMPERESkVA
KILOVOLTSkV
KILOMETERkm
KICKPLATEKPL
KNOCKOUT PANELKOP
KITCHENKIT
KILOPOUND (1000 POUNDS)KIP
JOINTJT
JOISTJST
JUNCTIONJCT
JUNCTION BOXJ-BOX
JANITOR’S CLOSETJAN CLO
INSIDE PIPE SIZEI.P.S.
IRON PIPE SIZEIPS
IRON PIPEIP
INVERTINV
INTERMEDIATEINTM
INTERIORINT
INSULATIONINSUL
INSULATING FILLINSF
INCLUDEDINCL
INCINERATORINCIN
INCHIN
INTERLOCKILK
ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICAIESNA
INSIDE DIAMETERID
INTERCOMIC
HERTZHz
HYDRAULICHYDR
HEATING, VENTILATING AND AIR CONDITIONINGHVAC
HEATERHTR
HEATINGHTG
HEIGHTHT
HOUSEKEEPINGHSKPG
HIGH-STRENGTH GYPSUM PLASTERHSGYP
HIGH STRENGTHHS
HOURHR
HIGH POINTHPT
HORSEPOWERHP
HIGH PRESSUREHP
HORIZONTALHORIZ
HANDRAILHNDRL
HOLLOW METALHM
HOOK(S)HK
HANDHOLEHH
HEXAGONHEX
HIGH EARLY-STRENGTH CEMENTHES
HARDWOODHDWD
HARDWAREHDW
HEADERHDR
HEAD JOINTHD JT
HARDBOARDHDBD
HEAVY DUTYHD
HEADHD
HANDICAPPEDHCP
HALON CONTAINMENT DAMPERHCD
HOLLOW COREHC
HOSE BIBBHB
GYPSUM PLASTERGYP PLAS
GYPSUM BOARDGYP BD
GYPSUMGYP
GLAZED WALL TILEGWT
GROUTGT
GLAZED STRUCTURAL UNITSGSU
GLAZED STRUCTURAL TILEGST
GRATINGGRTG
GRADE LINEGR LN
GRANITEGRAN
GYPSUM TILEGPT
GALLONS PER MINUTEGPM
GOVERNMENTGOVT
GROUNDG
GLAZED CONCRETE MASONRY UNITSGLZ CMU
GLAZINGGLZ
GLASS FIBERGLF
GLASS BLOCKGL BLK
GLASSGL
GASKET(ED)GKT
GALVANIZED IRON PIPEGIP
GALVANIZED IRONGI
GOVERNMENT-FURNISHED EQUIPMENT CONTRACTOR INSTALLEDGFE/CI
GOVERNMENT-FURNISHED EQUIPMENTGFE
GROUND FAULT CIRCUIT INTERRUPTERGFCI
GROUND FACEGF
GENERALGEN
GENERAL CONTRACTORGC
GRAB BARGB
GALVANIZED STEELGALV STL
GALVANIZEDGALV
GALLON(S)GAL
GAGEGA
NATURAL GASG
FABRIC WALL COVERINGFWC
FIRE WATERFW
FUTUREFUT
FURRINGFURG
FOOTINGFTG
FEETFT
FASTEN(ER)FSTNR
FULL SIZEFS
FIRE-RETARDANTFRT
FRAMINGFRMG
FORGEDFRG
FRAMEFR
FIRE RESISTANT FR
FEET PER MINUTEFPM
FIREPROOFFP
FIRE PARTITIONFP
FACE OF STUDFOS
FACE OF MASONRYFOM
FACE OF FINISHFOF
FACE OF CONCRETEFOC
FENCEFN
FLUORESCENTFLUOR
FLOOR PLATEFLR PL
FLOORINGFLG
FLEXIBLEFLEX
PERFORATE(D)PERF
PEDESTALPED
PAVEMENT DRAINPD
CEMENT PLASTER (PORTLAND)PCP
POUNDS PER CUBIC FOOTPCF
PRECAST CONCRETEPCC
PIECEPC
PUSH BUTTON STATIONPBS
PARTICLE BOARDPBD
PANIC BARPB
PARALLELPAR
PUBLIC ADDRESSPA
POLEP
OBSCURE WIRED GLASSOWGL
OUTSIDE SCREW AND YOKEOS & Y
OPERATIONSOPS
OPAQUEOPQ
OPPOSITEOPP
OPENINGOPNG
OPPOSITE HANDOPH
OVALHEAD WOOD SCREWOHWS
OVALHEAD MACHINE SCREWOHMS
OVERHEADOH
OBSCURE GLASSOGL
OFFICEOFC
OUTSIDE DIAMETEROD
ON CENTER EACH WAYOCEW
ON CENTEROC
OBSERVATION WINDOWOBW
OBSCUREOBSC
OUTSIDE AIROA
NOT TO SCALENTS
NOT REQUIREDN’’REQD
NOISE REDUCTION COEFFICIENTNRC
NOISE REDUCTIONNR
NOMINALNOM
NUMBERNO
NORMALLY OPENNO
NONMETALLICNM
NEOPRENE LATEXN.L.
NAILABLENL
NOT IN CONTRACTNIC
NICKELNi
NATIONAL FIRE PROTECTION ASSOCIATIONNFPA
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATIONNEMA
NATIONAL ELECTRICAL CODENEC
NORMALLY CLOSEDNC
NATURALNAT
NORTHN
MULLIONMULL
MOVABLEMVBL
METALMTL
METAL FURRINGMTFR
MOUNTEDMTD
MOUNTMT
METAL THRESHOLDMT
MACHINE SCREWSMS
METAL ROOF DECKINGMRD
MARBLE BASEMRB
MOP RECEPTORMR
MOVABLE PARTITIONMP
MOTORMOT
MODIFIEDMOD.
MODULARMOD
MASONRY OPENINGMO
MATERIAL NOT IN CONTRACT (INSTALLATION BY CONTRACTOR)MNIC
MILLIMETER(S)mm
MILLWORKMLWK
MOULDINGMLDG
MONOLITHICML
METAL LATHML
MISCELLANEOUSMISC
MIRRORMIRR
MINIMUMMIN
MALLEABLE IRONMI
MANHOLEMH
MATTE-GLAZED TILEMGT
MOTOR GENERATORMG
MANUFACTURERMFR
MANUFACTURINGMFG
METAL FLOOR DECKINGMFD
METAL EDGE STRIPMES
MEMBRANEMEMB
MEDIUMMED
MECHANICAL ROOMMECH RM
MECHANICALMECH
METAL DIVIDER STRIPMDS
METAL-CASED OPENINGMCO
MASONRY CONTROL JOINTMCJ
MEDICINE CABINETMC
MEMBERMBR
MACHINE BOLTSMB
MAXIMUMMAX
MATERIAL(S)MATL
MASONRYMAS
MACHINEMACH
MATCHED AND BEADEDM&B
METER(S)m
LEAVING WATER TEMPERATURELWT
LIGHTWEIGHT CONCRETELWC
LOUVERLVR
LIGHTNINGLTNG
LIGHTINGLTG
LIGHTWEIGHTLT WT
LIGHTLT
LAWN SPRINKLERLS
LIVING ROOMLR
LOW POINTLPT
LIGHTPROOF LOUVERLPL
LIGHTPROOF DOORLPD
LIGHTPROOFLP
LONGITUDINALLONG
LINTELLNTL
LIMESTONELMST
LUMENLM
LEAD-LINED DOORLLD
LIVE LOADLL
LOCKERLKR
LINEARLIN
LEFT HAND(ED)LH
LENGTHLG
LOADINGLDG
LOADLD
LIGHT CONTROLLC
LUMBERLBR
LABELLBL
POUNDLB
SOUNDPROOF DOORSPD
SPECIALSPCL
SPACERSPC
SHUT OFF VALVESOV
SHEET METAL SCREWSSMS
SHEET METALSM
SLEEVESLV
SEALANTSLNT
SKYLIGHTSKLT
STEEL JOIST INSTITUTESJI
SIMILARSIM
SHELVINGSHV
SHEATHINGSHTHG
SHEETSHT
SHOULDERSHLDR
SHEET GLASSSG
STRUCTURAL FACING UNITSFU
STRUCTURAL FACING TILE UNITSFTU
SAFETY GLASSSFGL
SEQUENCESEQ
SECTIONSECT
STEEL DOOR INSTITUTESDI
STORM DRAINSD
STRUCTURAL CLAY TILESCT
SCREENSCRN
SCHEDULESCHED
SOLID CORESC
SECURITY BARSS.B.
SPLASH BLOCKSB
SUPPLY AIRSA
SOUTHS
RAINWATER CONDUCTORRWC
RIVETRVT
REVERSERVS
RUBBER TILE FLOORRTF
RAISED PATTERN RUBBER TILERPRT
REVOLUTIONS PER MINUTERPM
RETRACTABLE PARTITIONRP
RIGHT OF WAYROW
ROUGH OPENINGRO
ROUNDRND
ROOMRM
RAILINGRLG
RACKRK
ROOF HATCHRH
RIGHT HANDRH
RELATIVE HUMIDITYRH
ROOFINGRFG
REVISIONREV
RETURNRET
RESILIENTRESIL
REQUIREDREQD
REMOVE(ABLE)REM
REINFORCEREINF
REGLETREG
REGISTERREG
REFRIGERATIONREFR
REFLECTREFL
REFERENCEREF
RECTIFIERRECT
RECREATION ROOMREC ROOM
RECEPTACLERECPT
RIGID INSULATIONRDG INS
ROOF DRAINRD
RECEIVERRCVR
REINFORCED CONCRETE PIPERCP
REMOTE CONTROLRC
RUBBERRBR
RUBBLE STONERBL
RUBBER BASE, RESILIENT BASERB
RETURN AIR REGISTERRAR
RETURN AIR GRILLERA GR
RABBETEDRAB
RETURN AIRRA
RISERR
RANGER
RADIUSR
QUANTITYQTY
QUARTER ROUND1/4 RND
QUARTERQTR
QUARTQT.
QUARRY TILEQT
PASS WINDOWPW
PAVINGPVG
POLYVINYL CHLORIDEPVC
PAVEDPV
PAPER TOWEL RECEPTACLEPTR
PARTITIONPTN
PAPER TOWEL DISPENSERPTD
POST-TENSIONED CONCRETEPT CONC
POINTPT.
PNEUMATIC TUBEPT
POUNDS PER SQUARE INCHPSI
POUNDS PER SQUARE FOOTPSF
PRESTRESSED CONCRETEPS CONC
PRESSED STEELP.S.
PIPE SPACEPS
PRESSURE-REGULATING VALVEPRV
PROJECTPROJ
PARKINGPRKG
PREFORMEDPREFMD
PREFINISHEDPREFIN
PREFABRICATE(D)PREFAB
PAIRPR
PARTS PER MILLIONPPM
POLISHED PLATE GLASSPPGL
PORTABLEPORT
PORCELAINPORC
POLISHEDPOL
PAINT(ED)PT
PANELPNL
PLYWOODPLYWD
PLATE GLASSPL GL
PILINGPLG
POUNDS PER LINEAR FOOTPLF
PLUMBINGPLBG
PLATFORMPLAT
PLASTERPLAS
PLASTIC LAMINATEPLAM
PROPERTY LINEPL
PLATEPL
POST INDICATING VALVEPIV
PREFAB ISOLATION POWER UNITPIPU
POINT OF INTERSECTIONPI
PHARMACYPHAR
PHASEPH
PERIMETERPERIM
YARD DRAINYD
YARDYD
TRANSFORMERXFMR
WELDED WIRE REINFORCEMENTWWR
WELDED WIRE MESHWWM
WELDED WIRE FABRICWWF
WALL TO WALLW/W
WIDTHWTH
WEIGHTWT
WAINSCOTWSCT
WASTE STACKW.S.
WATERSTOPWS
WARDROBEWRB
WASTE RECEPTACLEWR
WORKING POINTWP
WEATHERPROOFWP
WATERPROOF(ING)WP
WITHOUTW/O
WIRE MESHWM
WORK SHOPWKSH
WROUGHT IRONWI
WATT-HOUR METERWHM
WHEEL BUMPERWHB
WATER HEATERWH
WALL HUNGWH
WIRED GLASSWGL
WIDE FLANGEWF
WINDOWWDW
WASTE DISPOSERWDSP
WOOD DOORWD
WOODWD
WOOD-CASED OPENINGWCO
WHEELCHAIRW/C
WATER CLOSETWC
WOOD BLOCKINGWBL
WET BULBWB
WITHW/
WESTW
VINYL WALL COVERINGVWC
VENT THRU ROOFVTR
VOLTAGE TRANSFORMERV.T.
VENT STACKVS
VERMICULITEVRM
VAPOR RETARDERVR
VOLUMEVOL
VENEERVNR
V-JOINT(ED)VJ
VINYL HOMOGENEOUSVH
VERTICAL GRAINVG
VINYL FABRICVF
VESTIBULEVEST
VERTICALVERT
VENTILATOR(TION)VENT
VAULT DOORVD
VITRIFIED CLAY TILEVCT
VINYL COMPOSITION TILEVCT
VINYL BASEVB
VARNISHVAR
VOLTV
UNIT VENTILATORUV
UTILITYUTIL
URINALUR
UNINTERRUPTABLE POWER SUPPLYUPS
UNFINISHEDUNFIN
UNEXCAVATEDUNEX
UNDERWRITERS LABORATORIESUL
UNIT HEATERUH
UNDERGROUNDUGND
UNIT COOLERUC
TYPICALTYP
TELEVISIONTV
THERMOSTATTSTAT
TRANSVERSETRANS
TRANSOMTRANS
TOILET PARTITIONTPTN
TOILET PAPER DISPENSERTPD
TOP OF WALLTOW
TOP OF STEELTOS
TOP OF SLABTOS
TOPOGRAPHYTOPO
TOLERANCETOL
TOP OFTO
TACKSTRIPTKS
TACKBOARDTK BD
THRESHOLDTHRES
THICK(NESS)THK
TRUSS HEADTH
TOGGLETGL
TONGUE AND GROOVET&G
TERMINALTERM
TERRAZZOTER
TEMPORARYTEMP
TEMPERATURETEMP
TELEPHONETEL
TERRA COTTATC
TOWEL BARTB
TANGENTTAN
TREADT
SYSTEMSYS
SYNTHETICSYNTH
SYMMETRICALSYMM
SWITCHBOARDSWBD
SWITCHSW
SHEET VINYL SV
SUSPENDEDSUSP
SUBFLOORSUB FL
STAIRWAYSTWY
STRUCTURALSTRUCT
STRINGERSTR
STATIC PRESSUREST PR
STORAGESTOR
STEELSTL
SEATINGSTG
STANDARDSTD
STATIONSTA
STAINLESS STEELSST
STANDING SEAM (ROOF)SS
SERVICE SINKSS
SHELF AND RODS&R
SQUARE HEADSQHD
SQUARESQ
SPEAKERSPKR
SPACE HEATERSPH
SPECIAL FINISHSP FIN
SOUNDPROOFSPF
SPECIFICATIONSPEC
ABBREVIATIONS
US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N
AM
E:
ST
EP
SO
LI
C
IT
AT
IO
N
S-001
G
EN
ER
AL
S
TR
U C
TU
R
AL
N
O
TE
S, D
ES
IG
N L
O
AD
S
AB
BR
EV
IA
TI
O
N S
FO
R
T
PE
C K
D
AM
, M O
N
TA
N A
O M
AH
A
D
IS
TR
IC
T
C
AP
IT
O L
AV
E, O M
AH
A, N E
T.
H
AH
N
T.
H
AH
N
S.
D
EN
N
IN
G
W . B
O
EC
K
/0
4/
W
F2
5B A0
PO
W
ER
H
O U
SE
R
O O
F R
EP
AI
R S
FP
3_
PP
1R
_S tu c.
rv t
STRUCTURAL ABBREVIATIONS
ABBREVI
ATION ABBREVIATION NAME
# NUMBER
& AND
= EQUAL, EQUALS
@ AT
A/C AIR CONDITIONING
AB ANCHOR BOLT
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADJ ADJACENT
AFF ABOVE FINISEHD FLOOR
AH, AHU AIR HANDLING UNIT
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALT ALTERNATE
APA AMERICAN PLYWOOD ASSOCIATION
APPROX APPROXIMATELY
ARCH ARCHITECTURAL
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AT/FP ANTI-TERRORISM/ FORCE PROTECTION
AWS AMERICAN WELDING SOCIETY
BET BETWEEN
BLW BELOW
BM BEAM
BN BOUNDARY NAIL
BOF BOTTOM OF FOOTING
BOT BOTTOM
BRG BEARING
C CHANNEL
CE CARBON EQUIVALENT
CENT CENTERED
CFMF COLD-FORMED METAL FRAMING
CFS COLD-FORMED STEEL
CIP CAST IN PLACE
CJ CONTROL JOINT/CEILING JOIST
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
COND CONDITION
CONN CONNECT, CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CORNER
CWB CAPILLARY WATERBARRIER
D DEEP, DEPTH
DEG DEGREE
DEM DEMOLISH, DEMOLITION
DEP DEPRESSED
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DL DEADLOAD
DO DITTO
DT DRAG TRUSS
DWG(S) DRAWINGS
DWL DOWEL
EA EACH
EF EACHFACE
ELEC ELECTRICAL
ELEV ELEVATION
EN EDGE NAIL
EQN EQUATION
EQUIP EQUIPMENT
ES EACH SIDE
EW EACH WAY
EXIST EXISTING
EXT EXTERNAL, EXTERIOR
FF FAR FACE
FFE FINISH FLOOR ELEVATION
FG FINISH GRADE
FJ FLOOR JOIST
FMG FRAMING
FN FIELD NAIL
FND FOUNDATION
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FOS FACE OF STUD
FS FAR SIDE
FT, ' FOOT
FTG FOOTING
Fy YIELD STRESS
GA GAUGE
GLB GLUED LAMINATED BEAM
GT GIRDER TRUSS
GUSS GUSSET
GYP BD GYPSUM BOARD
HD HOLD DOWN
HDR HEADER
HGR HANGER
HK HOOK
HORIZ HORIZONTAL
HP HIGH POINT
HSS HOLLOW STRUCTURAL SECTION
HT HEIGHT
HVAC HEATNG/ VENTILATING/ AIR CONDITIONING
I MOMENT OF INERTIA
IBC INTERNATIONAL BUILDING CODE
ICF INSULATED CONCRETE FORM
ID INSIDE DIAMETER
IN, " INCH
STRUCTURAL ABBREVIATIONS
ABBREVI
ATION ABBREVIATION NAME
INCL INCLUDE
INFO INFORMATION
INS INSULATED, INSULATION
JST JOIST
K, KIPS THOUSAND POUNDS
L LENGTH, ANGLE
LB POUND
LG LONG
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC LOCATE, LOCATION
LONG LONGITUDINAL
LP LOW POINT
LW LIGHT WEIGHT
MAS MASONRY
MB MACHINE BOLT
MBR MEMBER
MECH MECHANICAL
MED MEDIUM
MEZZ MEZZANINE
MF MOMENT FRAM
MFG MANUFACTURING
MIN MINIMUM
MO MASONRY OPENING
MOD MODIFY, MODIFIED
MRF MANUFACTURER
NF NEAR FACE
NOM NOMINAL
NS NEAR SIDE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OPPOSITE HAND, OVERHEAD
OWSJ OPEN WEB STEEL JOIST
P/C PIN CONNECTED
PAR PARALLEL
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PEN PENETRATION
PFJ PERIMETER FELT JOINT
PL PLATE
PLYWD PLYWOOD
PNL PANEL
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED, POINT, PRETENSIONED
REINF REINFORCING, REINFORCED
REQ REQUIRED
RET RETURN, RETAINING
REV REVISION, REVISED
RF ROOF
RFT RAFTERS
RPM REVOLUTIONS PR MINUTE
RS ROUGH SAWN
RT ROOF TRUSS
S SECTION MODULUS
SC SLIP CRITICAL
SCBRW SEGMENTAL CONCRETE BLOCK RETAINING WALL
SCHED SCHEDULE
SDI STEEL DECK INSTITUTE
SECT SECTION
SEIS SEISMIC
SEP SEPARATION
SHT SHEET
SIM SIMILAR
SJI STEEL JOIST INSTITUTE
SMS SHEET METAL SCREW
SPEC(S) SPECIFICATION(S)
SPRT SUPPORT
SQ SQUARE
SS STAINLESS STEEL
ST SNUG TIGHT
STD STANDARD
STIF/STIFF STIFFENER
STL STEEL
STRUCT STRUCTURAL, STRUCTURE
SUSP SUSPENDED
SYM SYMMETRICAL
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TGB TOP OF GRADE BEAM
THK THICK, THICKNESS
TL TOTAL LOAD
TN TOE NAIL
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOS TOP OF STEEL
TOW TOP OF WALL
TYP TYPICAL
UFC UNITED FACILITES CRITERIA
UNO UNLESS NOTED OTHERWISE
UON UNLESS OTHERWISE NOTED
VB VAPOR BARRIER
VERT VERTICAL
W WIDTH, WEST, WIDE FLANGE
w/ WITH
WF WIDE FLANGE
WPT WORKING POINT
WWF WELDED WIRE FABRIC
WWM WELDED WIRE MESH
x BY, TIMES
1. GENERAL:
A. THESE NOTES AND OTHER DRAWINGS NOTES CONTAINED WITHIN, ARE PROVIDED TO
MEET SPECIFIC REQUIREMENTS AND TO SUPPLEMENT CONTRACT SPECIFICATIONS. THESE
NOTES NEITHER REPLACE NOR OVERRIDE PROVISIONS AND REQUIREMENTS OF
CONTRACT SPECIFICATIONS.
B. SEE ARCHITECTURAL SHEETS FOR BUILDING ELEVATIONS.
C. COORDINATE STRUCTURAL DRAWINGS WITH DRAWINGS FROM OTHER DISCIPLINES.
D. REPORT DISCREPANCIES IN DIMENSIONS ON THE DRAWINGS VIA THE "EXISTING
CONDITIONS" SUBMITTAL REFERENCED IN SPECIFICATION SECTION 024100 PRIOR TO
BEGINNING WORK IN AREA THAT WILL AFFECTED. IF CERTAIN FEATURES ARE NOT FULLY
SHOWN OR CALLED FOR ON THE DRAWINGS OR SPECIFICATIONS, PROVIDE
CONSTRUCTION OF THE SAME CHARACTER AS FOR SIMILAR CONDITIONS THAT ARE
SHOWN OR CALLED FOR WITH APPROVAL OF CONTRACTING OFFICER'S REPRESENTATIVE.
E. "TYPICAL" APPLIES NOT ONLY WHERE SPECIFICALLY INDICTED OR REFERENCED, BUT
ALSO IN ALL OTHER CASES WHERE THE NATURE OF THE CONSTRUCTION REQUIRES THEIR
USE. DETERMINE APPLICABILITY OF TYPICAL DETAILS FROM DESCRIPTIVE TITLES OR FROM
THE SIMILARITY OF A CONSTRUCTION CONDITION TO ANOTHER CONDITION WHERE THE
DETAIL IS SPECIFICALLY INDICATED OF REFERENCED.
F. DRAWINGS AND SPECIFICATIONS REPRESENT FINISHED STRUCTURE. CONTRACTOR IS
RESPONSIBLE FOR MEANS AND METHODS OF CONSTRUCTION INCLUDED, BUT NOT
LIMITED TO SHORING AND TEMPORARY BRACING. UNDERTAKE ALL NECESSARY
MEASURES TO ENSURE SAFETY OF ALL PERSONS AND STRUCTURES AT SITE AND
ADJACENT TO SITE.
G. REPRODUCTION OF CONTRACT DRAWINGS SHALL NOT BE USED AS SHOP DRAWINGS.
H. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON STRUCTURAL FRAME
SUCH THAT THE LOADING DOES NOT EXCEED THE DESIGN LIVE LOADS. PROVIDE SHORING
AND BRACING WHERE DESIGN STRENGTH HAS NOT BEEN ATTAINED OR STRUCTURE IS
NOT COMPLETE. MATERIALS SHALL BE STAGED ON MAIN ROOF BEAMS.
I. SHOULD EXISTING NAILABLE CONCRETE NOT BE USED AS FASTENING SURFACE. A
MAXIMUM OF 3 PSF MAY BE ADDED AS A FASTENING SURFACE.
J. CONCRETE PANEL UPLIFT CLIPS MUST BE PROTECTED DURING ROOF REMOVAL. CLIPS
MUST BE IMMEDIATELY REPAIRED IF DAMAGED.
K. EXISTING NAILS SHALL BE REMOVED IN A MATTER TO LIMIT DAMAGE TO THE CONCRETE
ROOF PANELS.
L. CLAY TILE FASTENERS ARE TO RESIST A MINIMUM AVERAGE SERVICE LOAD PULLOUT
RESISTANCE VALUES OF 180 LBS/FASTENER WITH NO INDIVIDUAL FASTENER LESS THAN
170LBS/FASTENER OR AS PER MANUFACTURER INSTALLATION INSTRUCTIONS, WHICHEVER
IS GREATER. FASTENER PULLOUT RESISTANCE VALUES MUST BE IN COMPLIANCE WITH
AMERICAN NATIONAL STANDARDS INSTITUTE(ANSI) ANSI/SPRI FX-1 - STANDARD FIELD TEST
PROCEDURE FOR DETERMINING THE WITHDRAWAL RESISTANCE OF ROOFING FASTENERS.
2. DESIGN CRITERIA:
STRUCTURAL DESIGN IS IN ACCORDANCE WITH THE FOLLOWING CODES, GUIDE AND
SPECIFICATIONS:
A. INTERNATIONAL BUILDING CODE, 2021.
B. ASCE 7-16, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES, 2016.
C. ACI 318-19, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE, 2019.
3. DESIGN LOADS:
A. RISK CATEGORY: III
B. DEAD LOADS (IN ADDITION TO SELF WEIGHT):
1. CLAY TILE ROOFING 10 PSF
2. CONCRETE PANEL 30 PSF (VERIFY IF REPLACING)
3. PLYWOOD UNDERLAYMENT AND FURRING 3 PSF (MAXIMUM)
C. ROOF LIVE LOAD (NON-REDUCIBLE): 20 PSF (300 LB CONCENTRATED)
D. SNOW LOAD CRITERIA:
1. GROUND SNOW LOAD, Pg 24 PSF
2. FLAT-ROOF SNOW LOAD, Pf 17.7 PSF
3. SLOPED ROOF SNOW LOA, Ps 17.7 PSF
4. SNOW IMPORTANCE FACTOR 1.1
5. SNOW EXPOSURE FACTOR, Ce 0.8
6. SNOW THERMAL FACTOR, Ct 1.2
7. ROOF SLOPE FACTOR, Cs 1.0
E. WIND LOAD CRITERIA:
1. BASIC DESIGN WIND SPEED,3-SECOND GUST, V 118 MPH
2. ALLOWABLE STRESS DESIGN WIND SPEED, V 91 MPH
3. WIND EXPOSURE CATEGORY D
4. INTERNAL PRESSURE COEFFICIENTS, GCpi +/- 0.18
5. DESIGN PRESSURES FOR EXTERIOR COMPONENTS AND CLADDINGS ARE
INDICATED ON DRAWINGS S-002
GENERAL STRUCTURAL NOTES
COMPONENT AND CLADDING PRESSURES (psf)
EFFECTIVE
AREA (SQ FEET)
ROOF ZONES
1 2r 2e 3
+34.3 -62.9
+34.3 -120
+34.3 -124.8
+34.3 -162.9
+17.6 -84.3 +16.0 -58.1 +16.0 -39.1
+16.0 -41.4
+17.6 -53.3
+17.6 -58.1 +16.0 -29.5 +16.0 -29.5 +16.0 -29.5
+17.6 -77.1 +16.0 -39.1 +16.0 -39.1 +16.0 -39.1 +16.0 -39.1 +16.0 -39.1
+16.0 -31.9 +16.0 -24.8 +16.0 -24.8 +16.0 -24.8
+16.0 -39.1 +16.0 -39.1 +16.0 -39.1
+16.0 -29.5 +16.0 -29.5
NOTES:
1. h = MEAN ROOF HEIGHT = 264 FT
2. a = END ZONE WIDTH = 4.5 FT
3. POSITIVE PRESSURES ACT TOWARDS SURFACE
4. NEGATIVE PRESSURES ACT AWAY FROM SURFACE
5. VALUES SHOWN IN TABLE ARE ULTIMATE PER ASCE 7-16
COMPONENTS AND CLADDING NOTES
1. WIND PRESSURES SHOWN IN THE TABLE CORRESPOND TO WIND PRESSURE DIAGRAMS.
INTERPOLATING BETWEEN TRIBUTARY AREA IS PERMITTED.
2. WIND PRESSURES SHOWN SHALL BE USED IN CONJUNCTION WITH LOAD COMBINATIONS SPECIFIED
IN SECTIONS 2.3 AND 2.4 OF ASCE 7-16
3. ALL WIND LOADS WERE CALCULATED FROM ASCE 7-16 USING THE DESIGN WIND SPEED (SEE
SHEET S-001)
4. POSITIVE NUMBERS ARE TOWARDS THE SURFACE AND NEGATIVE NUMBERS ARE AWAY FROM THE
SURFACE.
5. TRIBUTARY AREA GREATER THAN 700 SF MAY BE DESIGNED USING THE MAIN WIND FORCE
RESISTING SYSTEM (MWFRS) PROVISIONS FROM ASCE 7-16, SECTION 30.2.3
1 1
2r 2r
2r
2r 2r
2r
2r
2r 2r
2e 2e
2e a a a
US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N
AM
E:
ST
EP
SO
LI
C
IT
AT
IO
N
S-002
W
IN
D L
O
AD
S
FO
R
T
PE
C K
D
AM
, M O
N
TA
N A
O M
AH
A
D
IS
TR
IC
T
C
AP
IT
O L
AV
E, O M
AH
A, N E
T.
H
AH
N
T.
H
AH
N
S.
D
EN
N
IN
G
W . B
O
EC
K
/0
4/
W
F2
5B A0
PO
W
ER
H
O U
SE
R
O O
F R
EP
AI
R S
FP
3_
PP
1R
_S tu c.
rv t
NTSA1
COMPONENTS AND CLADDING
PRESSURES
MAXIMUM 24"
24 INCHES O.C.
MINIMUM 3 INCHES
FROM ANY CONCRETE
EDGE.
1/4" DIAMETER HOT DIP
GALVANIZED ASTM A 307
THROUGH BOLTS. USE WASHER
ON EACH FACE. WASHERS TO
HAVE A MINIMUM OUTSIDE
DIAMETER OF 1". COUNTERSINK
THE BOLT TO MAINTAIN A FLAT
SURFACE TO ATTACH THE
PLYWOOD OVERLAY.
2"X3" WOOD
FURRING STRIPS
3/4" PLYWOOD PANEL
#8 STAINLESS STEEL SCREWS. EMBED IN
2X3 FURRING STRIP 1.25" MINIMUM.
FASTEN 6 INCHES O.C. AT SUPPORTED
PANEL ENDS AND 6 INCHES O.C. AT
INTERMEDIATE SUPPORTS.
EXISTING
CONCRETE
ROOF PANEL
EXISTING STEEL ROOF BEAM
NOTES:
1. THROUGH BOLTS ARE NOT ALLOWED IN THICKENED
PORTIONS OF THE CONCRETE ROOF PANELS.
2. CONTRACTOR IS TO TAKE PRECAUTIONS TO AVOID ANY
DAMAGE TO EXISTING UPLIFT CLIPS AT ANY POINT DURING
CONSTRUCTION.
3. DO NOT PENETRATE STEEL ROOF BEAMS.
4. THE 3/4" PLYWOOD OVERLAY IS THE MAXIMUM THICKNESS
ALLOWED. THE ROOF TILES AND FASTENERS SHALL BE
VERIFIED TO MEET MINIMUM UPLIFT REQUIREMENTS. SEE
S-001 FOR FASTENER PULLOUT REQUIREMENTS.
5. MINIMUM BENDING STRENGTH OF PLYWOOD IS fb=575 psi
SPAN PLYWOOD TO ENSURE
STRONG BENDING AXIS IS
PERPENDICULAR TO FURRING
STRIPS
BORDER BLOCKING TO BE ADDED FOR FASCIA
ATTACHMENT. SEE ARCHITECTURAL DETAILS FOR
BLOCKING LOCATION AND FASCIA DETAIL. BLOCKING TO BE
FASTENED TO CONCRETE ROOF DECK PANELS WITH
CONSTRUCTION ADHESIVE. ADHESIVE TO HAVE A MINIMUM
TENSILE STRENGTH OF 100 PSI.
INSTALL H-CLIPS AT ALL UNSUPPORTED FREE
EDGES GREATER THAN 16". SEE DETAIL M2 ON S-501
H-CLIP
PLYWOOD SHEATHING
US Army Corps of Engineers ®
SHEET ID
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N
AM
E:
ST
EP
SO
LI
C
IT
AT
IO
N
S-501
PL
YW
O O
D O
VE
R
LA
Y
BI
D
O
PT
IO
N
FO
R
T
PE
C K
D
AM
, M O
N
TA
N A
O M
AH
A
D
IS
TR
IC
T
C
AP
IT
O L
AV
E, O M
AH
A, N E
T.
H
AH
N
T.
S
AU
N
D
ER
S
S.
D
EN
N
IN
G
W . B
O
EC
K
/0
4/
W
F2
5B A0
PO
W
ER
H
O U
SE
R
O O
F R
EP
AI
R S
FP
3_
PP
1R
_S tu c.
rv t
NTSA1 3/4" PLYWOOD SHEATING (BID OPTION)
NTSM2 H-CLIP
C2 A-301
7/
2"
8"
REMOVE AND
SCRAP EXISTING 16
OZ. COPPER
FLASHING 15" WIDE
ON ALL HIPS
(DEMO)
REMOVE AND SCRAP
EXISTING SHINGLE TILE
ROOF ON PRECAST
NAILING CONCRETE ROOF
DECK PANELS
EXISTING LANTERN
TO REMAIN
REMOVE AND SCRAP
EXISTING BOSTON
TILE RIDGE (DEMO)
EXISTING MOPPED
ASPHALT ON CONCRETE
SURFACES BELOW NOT
IN CONTRACT
57' - 8"
14' - 9 1/8"
1/1 6"
17' - 4 7/8"
41' - 1/16"
/8
CROSS HATCHING REPRESENTS
THE TEST AREA DEMOLITION -
SEE DEMOLITION NOTE 7
EXISTING STEEL
PURLIN TO REMAIN
REMOVE AND
SCRAP EXISTING
SHINGLE TILE ROOF
(DEMO)
EXISTING PRECAST
CONC. NAILABLE
ROOF PANELS TO
REMAIN
REMOVE AND SCRAP
EXISTING ROOF FELT
UNDERLAYMENT (DEMO)
FLASHING MEMBRANE
(DEMO)
REMOVE AND SCRAP
EXISTING CONC.
NAILS (DEMO)
EXISTING STEEL BEAM
TO REMAIN
REMOVE AND
SCRAP EXISTING
WOOD NAILERS
(DEMO)
T.O. ROOF (EL. 2340.48)
COPPER
WIRE GLASS EXISTING (TO REMAIN)
EXISTING CLAY TILE
SHINGLE
ROOF(DEMO)
STRUCTURAL STEEL
CURB EXISTING (TO
REMAIN)
TOP LINE OF
ROOF TRUSS
COPPER FLASHING (DEMO)
CAULKING
COPPER EXISTING (TO REMAIN)
3"
1/ 2"
2" 3"
1'
0"
1/ 2"
VA
R
IE
S
2 1/2" PRECAST
CONCRETE ROOF
DECK TO REMAIN
REMOVE AND SCRAP EXISTING
ROOF FELT UNDERLAYMENT
(DEMO)
VARIES
3'
/2
2" 4" 2"
REMOVE AND SCRAP
EXISTING CLAY TILE
SHINGLE ROOF (DEMO)
EXISTING PRECAST
CONCRETE ROOF DECK
PANELS TO REMAIN
EXISTING ROOF DECK
PANEL RETENTION CLIPS
TO REMAIN - TYP.
EXISTING STEEL TRUSS
TO REMAIN
EXISTING PRECAST
CONCRETE FASCIA
PANELS TO REMAIN
EXISTING GRATING AND
SCREEN TO REMAIN
EXISTING CONCRETE
SLAB TO REMAIN
7"
EL 2320.0
2'
0"
1/ 2"
1'
4"
EL 2321.96
12" 8"
EXISTING STEEL ROOF
PURLIN TO REMAIN
DEMOLITION AREA
EXISTING ROOF
DECK RETENTION
CLIPS TO REMAIN
EXISTING
STEEL ROOF
PURLIN TO
REMAIN
EXISTING 2 1/2"
PRECAST NAILING
CONCRETE ROOF DECK
PANELS TO REMAIN
REMOVE AND
SCRAP EXISTING
CLAY TILE
SHINGLE ROOF
(DEMO)
TOP LINE OF
EXISTING STEEL
TRUSS
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N
AM
E:
C :\U se rs
\g 6e dx br g\ D oc um en ts
\F P0
_P P1
R _D
M M
_g 6e dx br g.
rv t 4/
4/
:4 4:
P
M
AD101
D
EM
O
LI
TI
O
N R
O O
F
PL
AN
A
N D
D
ET
AI
LS
FO
R
T
PE
C K
D
AM
, M O
N
TA
N A
O M
AH
A
D
IS
TR
IC
T
C
AP
IT
O L
AV
E, O M
AH
A, N E
B.
G
O R
U P
A.
W
ES
TB
R O
O K
B.
G
O R
U P
B.
G
O R
U P
/0
4/
W
F2
5B A0
PO
W
ER
H
O U
SE
R
O O
F R
EP
AI
R S
FP
3_
PP
IR
_D M
M .rv t
ST
EP
SO
LI
C
IT
AI
TO
N
1/8" = 1'-0"J1 DEMO ROOF PLAN
3" = 1'-0"J9 ROOF RIDGE DEMO
1 1/2" = 1'-0"D1 ROOF AT LANTERN DETAIL DEMO
3/4" = 1'-0"D9 ROOF EAVE DEMO
GENERAL DEMOLITION NOTES:.
1. REMOVE AND SCRAP ALL EXISTING CLAY ROOFING TILES, FLASHING, FELT UNDERLAYMENT, CONCRETE NAILS, AND ANY OTHER ROOFING PRODUCTS REMAINING OVER THE PRECAST CONCRETE ROOF PANELS.
2. REMOVE AND SCRAP EXISTING FLASHING ASSEMBLIES.
3. EXISTING CONCRETE ROOF PANELS AND PURLINS TO REMAIN. EXISTING CONCRETE ROOF PANELS SHALL BE PROTECTED AND REPAIRED IF NECESSARY DURING THE DEMOLITION PROCESS. EVERY CAUTION SHALL BE TAKEN TO NOT DISTURB THE CONCRETE PANELS, PURLINS, AND METAL RETENTION
CLIPS.
4. REMOVE AND SCRAP EXISTING WOOD MEMBERS AND NAILERS AT HIPS, PERIMETER, AND OTHER
LOCATIONS WHERE EXISTING.
5. ALL DIMENSIONS SHALL BE FIELD VERIFIED.
6. CONTRACTOR SHALL DESIGN AND SUBMIT A SITE-SPECIFIC FALL PROTECTION PLAN FOR GOVERNMENT REVIEW AND APPROVAL PRIOR TO ON SITE ACTIVITIES AS REQUIRED PER RELEVANT SPECIFICATION
SECTIONS.
7. SEE SPECIFICATION SECTION 02 41 00, PARAGRAPH 1.2.2.1. FOR THE TEST AREA DEMOLITION
REQUIREMENTS.
8. THE EXISTING CLAY TILE ROOFING SHINGLES HAS AN ASBESTOS BITUMINOUS MATERIAL PRESENT ON
PORTIONS OF THE UNDERSIDE. THE CLAY TILES AND ASSOCIATED MATERIAL WITH ASBESTOS
CONTAINING MATERIAL WILL REQUIRE REMOVAL AND PROPER HANDLING AND DISPOSAL AS PART OF THE
TILE ROOFING REMOVAL PROCESS IN ACCORDANCE WITH SPECIFICATION SECTION 02 82 00.
PLAN NORTH
1/32" = 1'-0"
DEMOLITION LEGEND
3" = 1'-0"F16 TYP. CLIP DETAIL
C2 A-301
NEW 16 OZ.
COPPER FLASHING
15" WIDE AT ALL
HIPS TO MATCH
EXISTING AND AS
REQUIRED IF HIP
TILES MULTIPLE
PIECES- TYP.
NEW CLAY TILE ROOF
SHINGLES ON EXISTING
PRECAST CONCRETE
DECK PANELS - TYP.
EXISTING LANTERN TO
REMAIN AND BE
PROTECTED DURING
CONSTRUCTION
NEW ONE PIECE CLAY
HIP TILES AT ALL HIPS - TYP.
EXISTING MOPPED
ASPHALT ON CONCRETE
SURFACES BELOW IS
NOT IN THE CONTRACT -
TYP.
7/
2"
8"
57' - 8"
14' - 9 1/8"
1/1 6"
17' - 4 7/8"
41' - 1/16"
/8
T.O. ROOF (EL. 2340.48)
NEW COPPER
FLASHING TO MATCH
EXISTING. DETAIL MAY NOT
ACCURATELY REPRESENT
EXISTING CONDITIONS
EXISTING WIRE GLASS TO REMAIN
NEW CLAY TILE
ROOF SHINGLES ON
EXISTING PRECAST
CONCRETE DECK
PANELS
EXISTING
STRUCTURAL STL
CURB
TOP LINE OF
EXISTING
ROOF TRUSS
NEW COPPER
FLASHING
NEW CONT. SEALANT
BENEATH FLASHING AND
TOP OF UPPERMOST
TILE- TYP.
EXISTING COPPER TRIM
TO REMAIN
3"
1/ 2"
2" 3"
1'
0"
1/ 2"
VA
R
IE
S
NEW CONTINUOUS COMBINATION
ROOF FELT UNDERLAYMENT
NEW SEALANT AT TILE LAPS AND
LAPS AND JOINTS OF HIP TILES AS
RECOMMENDED BY THE
MANUFACTURER - TYP. VARIES
3"
3'
/2
2" 4" 2"
NEW CLAY TILE
SHINGLE ROOF
ASSEMBLY - TYP.
EXISTING PRECAST
CONCRETE DECK PANELS
TO REMAIN
UNDISTURBED
EXISTING PANEL
RETENTION CLIPS TO
REMAIN - TYP.
EXISTING STEEL TRUSS
EXISTING PRECAST
CONC.
EXISTING GRATING AND
SCREEN
EXISTING CONC. SLAB
7"
EL 2320.0
2'
0"
1/ 2"
1'
4"
EL 2321.96
12" 8"
EXISTING STEEL
PURLIN
EXISTING PRECAST
CONCRETE DECK
PANELS TO REMAIN
UNDISTURBED
CONTINUOUS ROOF
UNDERLAYMENT EXTEND OVER
WOOD BLOCKING - TYP.
NEW CLAY ROOF SHINGLES/HIP
CAP ON EXISTING PRECAST
CONCRETE DECK PANELS
NEW 18" STRIP OF HIGH TEMP
SELF-ADHERING FLASHING
MEMBRANE AS STD W/ MFR
ROOFING NAILS OR
FASTENERS
CONNECTION BETWEEN
TILE AND CONCRETE
PANEL TO BE AS INDICATED
IN THE SPECIFICATION.
ALTERNATIVE PROPOSED
METHODS OF
SECUREMENT ARE
ACCEPTABLE SUBJECT TO
GOVERNMENT APPROVAL
NEW WOOD NAILERS
SECURED TO EXISTING
DECK AT HIPS AND ALL
LOCATIONS WHERE
EXISTING WERE
REMOVED.
EXISTING STEEL BEAMS
AND PURLINS TO REMAIN
UNDISTURBED
NEW SEALANT AT TILE LAPS AND
LAPS AND JOINTS OF HIP TILES AS
RECOMMENDED BY THE
MANUFACTURER - TYP..
STANDARD CLIPS
TO REMAIN
PURLIN
EXISTING 2 1/2"
PRECAST NAILING
CONCRETE ROOF
PANELS
NEW CLAY TILE
SHINGLE ROOF
TOP LINE OF
TRUSS
NEW SEALANT AT TILE LAPS AND
LAPS AND JOINTS OF HIP TILES AS
RECOMMENDED BY THE
MANUFACTURER - TYP.
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N
AM
E:
C :\U se rs
\g 6e dx br g\ D oc um en ts
\F P0
_P P1
R _D
M M
_g 6e dx br g.
rv t 4/
4/
:3 8:
P
M
A-101
R O
O F
PL
AN
A N
D D
ET
AI
LS
FO
R
T
PE
C K
D
AM
, M O
N
TA
N A
O M
AH
A
D
IS
TR
IC
T
C
AP
IT
O L
AV
E, O M
AH
A, N E
B.
G
O R
U P
A.
W
ES
TB
R O
O K
B.
G
O R
U P
B.
G
O R
U P
/0
4/
W
F2
5B A0
PO
W
ER
H
O U
SE
R
O O
F R
EP
AI
R S
FP
3_
PP
IR
_D M
M .rv t
ST
EP
SO
LI
C
IT
AI
TO
N
1/8" = 1'-0"G1 ROOF PLAN
PLAN NORTH
NEW ROOF GENERAL NOTES:
1. ALL DIMENSIONS TAKEN FROM "AS BUILTS". CONTRACTOR IS TO FIELD VERIFY ALL EXISTING
CONDITIONS AND DIMENSIONS.
2. THE CONTRACTOR IS RESPONSIBLE FOR PROTECTING THE ROOF, THE BUILDING, AND ALL CONTENTS
DURING INCLEMENT WEATHER.
3. EXISTING CONCRETE ROOF PANELS AND PURLINS TO REMAIN.
4. PROVIDE NEW WOOD MEMBERS AND NAILERS AT HIPS, PERIMETER, AND OTHER LOCATIONS WHERE
EXISTING AND AS PER EXISTING CONDITIONS AND SECURE AS PER EXISTING.
5. PROVIDE ELASTOMERIC SEALANT AT ROOF TILE LAPS, LAP JOINTS OF HIP TILES, TO COVER ANY
EXPOSED FASTENERS, BETWEEN HEADER TILES, AS REQUIRED TO SET FLASHINGS, AND WHERE
RECOMMENDED BY THE ROOF TILE MANUFACTURER FOR THE STEEP SLOPE AND THE HIGH WIND
CONDITIONS THAT EXIST.
1 1/2" = 1'-0"A1 ROOF AT LANTERN DETAIL
3/4" = 1'-0"A9 ROOF EAVE .
3" = 1'-0"H9 ROOF HIP/RIDGE
3" = 1'-0"H18 TYP CLIP DETAIL
EL. 2299
EL. 2309
T.O. ROOF (EL. 2340.48)
EL 2321.96
EL. 2289
EL. 2112.50
EL. 2120.0
EL. 2129.0
EL. 2135.0
EL. 2267.0
EL 2061.50
EL 2050.0
RETAINING WALL
NORMAL TAIL
WATER @ EL. 2032.0
RECESSED PANELS
NEW CLAY TILE ROOF SHINGLES
ON EXISTING PRECAST CONCRETE
DECK PANELS
LANTERN
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N
AM
E:
C :\U se rs
\g 6e dx br g\ D oc um en ts
\F P0
_P P1
R _D
M M
_g 6e dx br g.
rv t 4/
4/
:4 5:
P
M
A-200
BU
IL
D
IN
G E
LE
VA
TI
O
N
FO
R
T
PE
C K
D
AM
, M O
N
TA
N A
O M
AH
A
D
IS
TR
IC
T
C
AP
IT
O L
AV
E, O M
AH
A, N E
B.
G
O R
U P
A.
W
ES
TB
R O
O K
B.
G
O R
U P
B.
G
O R
U P
/0
4/
W
F2
5B A0
PO
W
ER
H
O U
SE
R
O O
F R
EP
AI
R S
FP
3_
PP
IR
_D M
M .rv t
ST
EP
SO
LI
C
IT
AI
TO
N
1/16" = 1'-0"A1 EXISTING NORTH ELEVATION
ELEVATION GENERAL NOTES:
1. ALL DIMENSIONS TAKEN FROM "AS BUILTS" AND SHALL BE FIELD VERIFIED.
2. DURING CONSTRUCTION PROTECT THE EXPOSED AREAS OF THE ROOF FROM RAIN, PRECIPITATION, AND WATER DAMAGE. PROTECTED AREAS SHALL REMAIN COVERED UNTIL CONSTRUCTION RESUMES.
3. EXISTING CONCRETE ROOF PANELS AND PURLINS TO REMAIN.
4. ONSITE ACCESS TO ROOF IS BY STAIRS ONLY INSIDE OF THE BUILDING. NO ELEVATOR IS AVAILABLE
TO ACCESS THE WORK AREA.
EL. 2299
EL. 2309
T.O. ROOF (EL. 2340.48)
EL 2321.96
SECOND 'ROOF'
0"
2'
8" 7'
1/ 2"
1'
/2
8"
A-101 A9
EL. 2289
A-101 A1
7"
EXISTING LANTERN TO REMAIN
SHINGLE TILE ROOF ON
PRECAST CONC. ROOF
PANELS
EXISTING MOPPED
ASPHALT ON CONCRETE
FINISH TO REMAIN
EXISTING PVC MEMBRANE
ROOF TO REMAIN
8" 12"
7-7/16" 12"
EXISTING 1 1/2" PIPE HANDRAIL
TO REMAIN
EXISTING ASBESTOS
CEMENT BOARD
PARTITIONS TO
REMAIN
EXISTING SURGE
TANK VENT TO
REMAIN
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N
AM
E:
C :\U se rs
\g 6e dx br g\ D oc um en ts
\F P0
_P P1
R _D
M M
_g 6e dx br g.
rv t 4/
4/
:4 6:
P
M
A-301
BU
IL
D
IN
G S
EC
TI
O N
FO
R
T
PE
C K
D
AM
, M O
N
TA
N A
O M
AH
A
D
IS
TR
IC
T
C
AP
IT
O L
AV
E, O M
AH
A, N E
B.
G
O R
U P
A.
W
ES
TB
R O
O K
B.
G
O R
U P
B.
G
O R
U P
/0
4/
W
F2
5B A0
PO
W
ER
H
O U
SE
R
O O
F R
EP
AI
R S
FP
3_
PP
IR
_D M
M .rv t
ST
EP
SO
LI
C
IT
AI
TO
N
3/16" = 1'-0"C2 Section 1
0 2' 4' 8' 12'
NEW ROOF GENERAL NOTES:
1. ALL DIMENSIONS TAKEN FROM "AS BUILTS" AND SHALL BE FIELD VERIFIED.
2. DURING CONSTRUCTION PROTECT THE EXPOSED AREAS OF THE ROOF FROM RAIN, PRECIPITATION, AND WATER DAMAGE. PROTECTED AREAS SHALL REMAIN COVERED UNTIL CONSTRUCTION RESUMES.
3. EXISTING CONCRETE ROOF PANELS AND PURLINS TO REMAIN.
VARIES
3'
/2
2" 4" 2"
NEW CLAY TILE
SHINGLE ROOF
EXISTING 2 1/2" PRECAST
NAILING CONC. ROOF
PANELS
EXISTING RETENTION
CLIPS - TYP.
EXISTING STL TRUSS
EXISTING PRECAST
CONC. FASCIA
EXISTING GRATING AND
SCREEN
EXISTING CONC. SLAB
7"
EL 2320.0
2'
0"
1/ 2"
1'
4"
EL 2321.96
EXISTING STEEL
ROOF PURLIN
NEW 3/4" THICK (MAX) PLYWOOD ROOF SHEATHING
SECURED TO WOOD FURRING STRIPS
SECURED TO EXISTING CONCRETE
DECK (SEE STRUCTURAL) - TYP.
12" 8"
NEW WOOD FURRING -
BEYOND - SEE STR.
NEW UNDERLAYMENT -
LAP WOOD FURRING
NEW PERIMETER WOOD
FURRING - SEE STR.
NEW COPPER FLASHING CLEAT
SECURED TO WOOD BLOCKING
NEW COPPER DRIP EDGE
FLASHING - DEPTH +/-
5" AND AS REQD TO
COVER CONCRETE
PURLIN
NEW CLAY TILE
SHINGLE ROOF
EXISTING 2 1/2"
PRECAST NAILING
CONC. ROOF PANELS
NEW CONTINUOUS
ROOF UNDERLAYMENT
EXTEND OVER WOOD
NAILER - TYP
NEW 3/4" THICK (MAX)
PLYWOOD ROOF SHEATHING
SECURED TO NEW WOOD
NAILERS AND EXISTING
CONCRETE DECK AS INDICATED
ON DRAWING S-501 - TYP. -
ALTERNATIVE
SECUREMENT METHODS
PROPOSED WILL REQUIRE
SUBMISSION AND APPROVAL BY
THE GOVT.
NEW HIP WOOD
NAILERS/FURRING -
SEE STR.
NEW 18" STRIP OF HIGH
TEMP SELF-ADHERING
FLASHING MEMBRANE AS
STD W/ MFR
CONTINUOUS SEALANT - TYP.
NEW SEALANT AT TILE LAPS AND
LAPS AND JOINTS OF HIP TILES AS
RECOMMENDED BY THE
MANUFACTURER - TYP..
T.O. ROOF (EL. 2340.48)
NEW COPPER FLASHING TO
MATCH EXISTING. DETAIL MAY
NOT ACCURATELY REPRESENT
EXISTING CONDITIONS
EXISTING WIRE GLASS
EXISTING PRECAST
NAILING CONCRETE
ROOF PANELS
EXISTING STRUCTURAL
STEEL CURB
TOP LINE OF ROOF TRUSS
NEW COPPER FLASHING
NEW CONT. SEALANT
BENEATH FLASHING AND
TOP OF UPPERMOST
TILE- TYP.
EXISTING COPPER TRIM
3"
1/ 2"
2" 3"
1'
0"
1/ 2"
VA
R
IE
S
NEW 3/4" THICK (MAX)
PLYWOOD ROOF SHEATHING
SECURED TO NEW WOOD
NAILERS AND EXISTING
CONCRETE DECK AS INDICATED
ON DRAWING S-501- TYP.
7"
NEW CLAY
SHINGLE TILE
CONTINUOUS ROOF
UNDERLAYMENT
NEW PERIMETER WOOD
FURRING - SEE STR.
NEW SEALANT AT TILE LAPS AND
LAPS AND JOINTS OF HIP TILES AS
RECOMMENDED BY THE
MANUFACTURER - TYP.
STANDARD CLIPS
TO REMAIN
PURLIN
EXISTING 2 1/2" PRECAST
NAILING CONCRETE ROOF
PANELS TO REMAIN
NEW CLAY TILE SHINGLE ROOF
TOP LINE OF
TRUSS
NEW 3/4" THICK (MAX) PLYWOOD ROOF
SHEATHING SECURED TO NEW WOOD
NAILERS AND EXISTING CONCRETE
DECK AS INDICATED ON DRAWING
S-501- TYP.
CONTINUOUS ROOF
UNDERLAYMENT
NEW SEALANT AT TILE LAPS AND LAPS
AND JOINTS OF HIP TILES AS
RECOMMENDED BY THE
MANUFACTURER - TYP.
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N
AM
E:
C :\U se rs
\g 6e dx br g\ D oc um en ts
\F P0
_P P1
R _D
M M
_g 6e dx br g.
rv t 4/
4/
:4 7:
P
M
A-511
R O
O F
D
ET
AI
LS
(B
ID
O
PT
IO
N
FO
R
T
PE
C K
D
AM
, M O
N
TA
N A
O M
AH
A
D
IS
TR
IC
T
C
AP
IT
O L
AV
E, O M
AH
A, N E
B.
G
O R
U P
A.
W
ES
TB
R O
O K
B.
G
O R
U P
B.
G
O R
U P
/0
4/
W
F2
5B A0
PO
W
ER
H
O U
SE
R
O O
F R
EP
AI
R S
FP
3_
PP
IR
_D M
M .rv t
ST
EP
SO
LI
C
IT
AI
TO
N
3/4" = 1'-0"H1 ROOF EAVE (BID OPTION)
3" = 1'-0"C1 ROOF HIP/RIDGE (BID OPTION)
1 1/2" = 1'-0"H8 ROOF AT LANTERN DETAIL (BID OPTION)
NEW ROOF GENERAL NOTES:
1. ALL DIMENSIONS TAKEN FROM THE "RECORD DRAWINGS" ("AS BUILTS"). THE CONTRACTOR SHALL
FIELD VERIFY ALL EXISTING CONDITIONS.
2. DURING CONSTRUCTION PROTECT THE EXPOSED AREAS OF THE ROOF FROM RAIN, PRECIPITATION, AND WATER DAMAGE. PROTECTED AREAS SHALL REMAIN COVERED UNTIL CONSTRUCTION RESUMES.
3. EXISTING CONCRETE ROOF PANELS AND PURLINS TO REMAIN.
4. BID OPTION MAY BE AWARDED BASED ON CONDITIONS OF CONCRETE PANELS AND GOVERNMENT
REVIEW OF CONTRACTOR'S INSPECTION REPORT.
5. PROVIDE ELASTOMERIC SEALANT AT ROOF TILE LAPS, LAP JOINTS OF HIP TILES, TO COVER ANY
EXPOSED FASTENERS, BETWEEN HEADER TILES, AS REQUIRED TO SET FLASHINGS, AND WHERE
RECOMMENDED BY THE ROOF TILE MANUFACTURER FOR THE STEEP SLOPE AND THE HIGH WIND
CONDITIONS THAT EXIST.
3" = 1'-0"C8 TYP. CLIP DETAIL (BID OPTION)
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N
AM
E:
C :\U se rs
\g 6e dx br g\ D oc um en ts
\F P0
_P P1
R _D
M M
_g 6e dx br g.
rv t 4/
4/
:4 8:
P
M
A-520
PH
O
TO
S
FO
R
T
PE
C K
D
AM
, M O
N
TA
N A
O M
AH
A
D
IS
TR
IC
T
C
AP
IT
O L
AV
E, O M
AH
A, N E
M
AR
Y
BI
EG
ER
T
M
AR
Y
BI
EG
ER
T
BR
O
O
KE
S
PA
R R
O W
BE
R
N
AR
D G
O R
U P
/0
4/
W
F2
5B A0
PO
W
ER
H
O U
SE
R
O O
F R
EP
AI
R S
FP
3_
PP
IR
_D M
M .rv t
ST
EP
SO
LI
C
IT
AI
TO
N
NTS1 PHOTO 1
12" = 1'-0"2 PHOTO 2
12" = 1'-0"3 PHOTO 3
12" = 1'-0"4 PHOTO 4
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N
AM
E:
C :\U se rs
\g 6e dx br g\ D oc um en ts
\F P0
_P P1
R _D
M M
_g 6e dx br g.
rv t 4/
4/
:4 9:
P
M
A-521
PH
O
TO
S
FO
R
T
PE
C K
D
AM
, M O
N
TA
N A
O M
AH
A
D
IS
TR
IC
T
C
AP
IT
O L
AV
E, O M
AH
A, N E
D es ig ne r
Au th or
C he ck er
/0
4/
W
F2
5B A0
PO
W
ER
H
O U
SE
R
O O
F R
EP
AI
R S
FP
3_
PP
IR
_D M
M .rv t
ST
EP
SO
LI
C
IT
AI
TO
N
12" = 1'-0"5 PHOTO 5
12" = 1'-0"6 PHOTO 6
12" = 1'-0"7 PHOTO 7
12" = 1'-0"8 PHOTO 8
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N
AM
E:
C :\U se rs
\g 6e dx br g\ D oc um en ts
\F P0
_P P1
R _D
M M
_g 6e dx br g.
rv t 4/
4/
:5 0:
P
M
A-522
PH
O
TO
S
FO
R
T
PE
C K
D
AM
, M O
N
TA
N A
O M
AH
A
D
IS
TR
IC
T
C
AP
IT
O L
AV
E, O M
AH
A, N E
D es ig ne r
Au th or
C he ck er
/0
4/
W
F2
5B A0
PO
W
ER
H
O U
SE
R
O O
F R
EP
AI
R S
FP
3_
PP
IR
_D M
M .rv t
ST
EP
SO
LI
C
IT
AI
TO
N
12" = 1'-0"9 PHOTO 9
12" = 1'-0"10 PHOTO 10
12" = 1'-0"11 PHOTO 11
12" = 1'-0"12 PHOTO 12
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
FI
LE
N
AM
E:
C :\U se rs
\g 6e dx br g\ D oc um en ts
\F P0
_P P1
R _D
M M
_g 6e dx br g.
rv t 4/
4/
:5 1:
P
M
A-523
PH
O
TO
S
FO
R
T
PE
C K
D
AM
, M O
N
TA
N A
O M
AH
A
D
IS
TR
IC
T
C
AP
IT
O L
AV
E, O M
AH
A, N E
D es ig ne r
Au th or
C he ck er
/0
4/
W
F2
5B A0
PO
W
ER
H
O U
SE
R
O O
F R
EP
AI
R S
FP
3_
PP
IR
_D M
M .rv t
ST
EP
SO
LI
C
IT
AI
TO
N
12" = 1'-0"13 PHOTO 13
12" = 1'-0"14 PHOTO 14
12" = 1'-0"15 PHOTO 15
12" = 1'-0"16 PHOTO 16
RELAY TEST BENCH
RECORDER BOARD
AUX. RELAY BOARD
EF-8
BATTERY ROOM
EH3-2
CAC
ROOM
LIGHTING PANELS V
E
S T
IB
U
L E
CABLE PASSAGE
WORK TABLE
CONTROL ROOM
FILE CAB
S T
A T
IO
N
B O
A R
D
LOCKER ROOM
EF-10
KITCHEN
PANEL LP5
CORRIDOR
PUBLIC ROOM
EL. 2071.0
PUBLIC RECEPTION ROOM
WATER COOLERS
FLOOR DRAIN
VESTIBULE
SINK
PANEL PP2
UP
AIR COND. UNIT
RISER NO.1
L P
L P
L P
E M
U P
D N
UP
RISER NO.3
LIGHTING DISTR. PANEL LDP
POWER PANEL DP
13.8KV SWITCHGEAR CUBICLES
CUBICLE ROOM
RETAINING WALL
WIRE FENCE
ERECTION BAY
TRAINING WALL
> GENERATOR ROOM
> UNITS & REFERENCE LINE
> UNIT NO.1> UNIT NO.2 & REFERENCE LINE> BUILDING> UNIT NO.3
D O
W N
BALCONY
GENERATOR FLOOR
REMOVABLE SLAB
UP
U P
REMOVABLE SLABS
UP
CLOSER
REGISTERS
FLOOR H & V
RACKS
BATTERY
(ABANDON)
HEATER FLUE
TRANSF. SW.
EMER. LTG.
EH3-1
HEATER
WALL
FIRST AID
ROOM
OPER.
TOILET
COOLER
WATER
TABLE/CAB.
FILE
MONITOR
CONTROL
PPCS
DESK
OPERATORS
IN
S
T R
U M
E N
T
R E
L A
Y B
O A
R D
2'-3"X1'-7" (EA.)
DATA & ALARM LOGGERS
STATION
PC WORK
LINK
COMM
REHAC
PASSENGER
ELEVATOR
MENS
TOILET
WOMENS
TOILET
DRAIN
FLOOR
REMOVABLE
SLABS
TRANSFORMER
SERVICE
ROOM
PLYWOOD
WALL
RISER
NO.2
SWITCHGEAR
480V
STATION
SERVICE
ROOM
RETAINING WALL
TOP OF PRESENT
CABINET
GOV. ACT. 1
CABINET
GOV. ACT. 2
CABINET
GOV. ACT. 3
20'-9"
47'-0"
22'-0"
31'-6"
19'-9"
39'-6"
67'-0" 1"
185'-6"
38'-10 1/2 "
D N
U P
U P
17'-5"
D O
W N
1'-9"
EL. 2065.50
DUCT
SHAFT
15'-6" 34'-6" 44'-0" 34'-6" 15'-6"
20'-3"
22'-4 1/2 " 20'-3" 20'-3" 10'-1 1/2 " 10'-1 1/2 " 20'-3" 20'-3" 22'-4 1/2 " 19'-9"
53'-3" 20'-3" 33'-0" 39'-6"
46'-0" 46'-0" 26'-6"
CONSTRUCTION
REP
T
A L
L T
A L
L
CAP, 12000 LBS
ELEVATOR
FREIGHT
7'-7"
DOOR
HEIGHT
7'-6"
CEILING
8'-2"
4'
EL. 2071
EL. 2069
WIDTH
DOOR
6'-5"
S
L
IC
IT
A
T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S I Z
E
S U
B M
IT
T
E D
B Y
D A
T E
C H
E C
K E
D B
Y
D R
A W
N B
Y
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
A N
S I
D
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R
AS-BUILT RECORD SET
E R
A T
IO
N
A L
D R
A W
IN
G
S E
T x x
/x x
/x x x
U
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
F O
R T
P E
C K
D A
M
M O
N T
A N
A
F O
R T
P E
C K
P R
O J E
C T
P O
B O
X
F O
R T
P E
C K
M
T
O M
A H
A D
IS
T
R
IC
T
C
A P
IT
A
L A
V E
O M
A H
A
N E
V
IS
U
E D
A T
PWHSE X
xT H
L A
D
M F
P -O
P N
X X
E X
X X
X
X X
M F
P -O
P N
X
X E
L X x x x x /x x /x x
G
N E
R A
L R
E V
IS
IO
EL-6xx
P
G
E N
C
O N
T R
O L
R O
O M
F L
O O
R P
L A
N C
U B
IC
L
E R
O O
M A
C C
E
C
N T
R A
C T
N O
F
IL
E N
U M
B E
R
F
IL
E N
A M
E
PASSENGER ELEVATOR 1800 LBS CAPACITY
FREIGHT ELEVATOR 12000 LBS CAPACITY
NOTES
FP17-70-127 PP1 GENERATOR FLOOR SECTIONS ROUGH CONCRETE
MFP-OPN84E105 PP1 GEN & CONTROL ROOM FLOOR PLAN
REF.
FOR INFORMATION ONLY
a u t o s c a le a u t o s h o r t d e s ig n a u t o s y t im e a u t o u s e r n a m e a u t o d e s ig
A-100
.L .P
R .L .P
D .V .M
D .V .M
SCALE: 1/8" = 1’- 0"
S U
R G
E T
A N
K R
O O
F E
L .0
S P
IL
L W
A Y C
O N
T R
O L B
U
IL
D
IN
G O
P T
O N
R O
O F P
L A
N S S
E C
T
IO
-1
-1
A
M
R
E V
IS
E D R
E D
R A
W N
POWER PLANT #1 SURGE TANK
ROOF PLAN AT ELEV 2299.0 - BASE BID
SCALE: 1/8" = 1’-0"
0 8’8’ 4’ a u t o s c a le a u t o s h o r t d e s ig n a u t o s y t im e a u t o u s e r n a m e a u t o d e s ig
L
IC
IT
A T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
NUMBER
IDENTIFICATION
SHEET
OF ENGINEERS
US ARMY CORPS
D A
T E
F
IL
E N
U M
B E
R
S
IZ
E
S U
B M
IT
T E
D B
Y
P L
O T S
C A
L E
P L
O T D
A T
E
D A
T E
C O
R P
S O
F E
N G
IN
E E
R S
U S
A R
M Y E
N G
IN
E E
R D
IS
T R
IC
T
M A
R K
D E
S C
R
IP
T
IO
N A
P P
R
D A
T E
C O
N T
R A
C T N
.1
X
W
F
C
W
F
B
O M
A H
A
N E
B R
A S
K A
OMAHA DISTRICT
M F
P
F O
R T P
E C
K
M O
N T
A N
A
R E
H A
B R
O O
F M
E M
B R
A N
E P
O W
E R P
L A
N T
A N
D S
P
IL
L W
A Y C
O N
T R
O L B
U
IL
D
IN
G
A U
G U
A -1
A -2
A
1 2 3
TYPICAL
B
TYPICAL
CLEANED, WITH ALL DEBRIS & TEMPORARY PROTECTIVE MATERIALS REMOVED.
6 AFTER INSTALLATION IS COMPLETE ALL AREAS OF THE JOB SITE SHALL BE COMPLETELY
ELASTOMERIC MANUFACTURER’S REQUIREMENTS.
PRIOR TO THE START OF ROOFING INSTALLATION. ROOF DECKS SHALL MEET ROOFING
5 CONTRACTING OFFICER’S REPRESENTATIVE SHALL INSPECT CLEANED ROOF DECKS
FEATURES NOT SLATED TO BE REMOVED.
4 CONTRACTOR SHALL PROTECT ALL EXISTING ELECTRICAL DEVICES & OTHER BUILDING
PERFORMANCE OF THE WORK, PRIOR TO THE COMMENCEMENT OF ANY WORK.
OFFICER’S REPRESENTATIVE OF ANY CONDITIONS THAT MAY NEGATIVELY AFFECT THE
3 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS & NOTIFY CONTRACTING
& FEATURES THAT ARE EXPOSED TO THE UNDERSIDE OF THE ROOF DECK.
2 BEFORE REMOVAL OF ROOFING PROTECT ALL INTERIOR EQUIPMENT
APPROVED BY CONTRACTING OFFICER REPRESENTATIVE.
PER SQUARE FOOT. MATERIALS LOADING ON THE ROOF SHALL BE
1 MAXIMUM LIVE LOAD PERMITTED ON THE ROOF DECK IS 20 POUNDS
GENERAL NOTES:
5 REMOVE EXISTING METAL FLASHING.
4 REMOVE & SCRAP EXISTING ASPHALT ROOFING.
REQUIRED FOR THE REMOVAL OF THE ROOFING.
AND RELATED DRAIN ACCESSORIES AS
DRAIN STRAINERS, CLAMPING RINGS,
3 REMOVE & SALVAGE FOR RE -INSTALLATION ROOF
2 REMOVE EXISTING SLIP SHEET.
1 REMOVE EXISTING ELASTOMERIC ROOFING.
REMOVAL NOTES:
ROOF DRAIN
ROOF DRAIN
ROOF DRAIN
ROOF DRAIN
SHEETS FOR CONSTRUCTION IN THIS AREA
SEE INFORMATION ONLY DRAWING
SURGE TANK AT POWER PLANT 1
44’-0 5/8 " 44’-0 5/8 "
121’-7 3/4 "
/8
/4
’-0
13’-0"
C
TYPICAL
C
TYPICAL
C
TYPICAL
C
TYPICAL
ROOF DRAIN
SEE DETAIL C ON SHEET A-200 - OPTION 1.
C INSTALL NEW COPPER FLASHING IN EXISTING REGLETS AT ELEVATION 2089.0 +/-
& WATER TIGHT INSTALLATION.
MANUFACTURER’S RECOMMENDATIONS. PROVIDE A SECURE
DRAIN ACCESSORIES IN ACCORDANCE WITH ELASTOMERIC ROOF
B RE-INSTALL EXISTING CLAMPING RINGS, STRAINERS AND RELATED
WITH THE ROOFING MANUFACTURER’S RECOMMENDATIONS.
FLASHING AND RELATED ACCESSORIES IN ACCORDANCE
A INSTALL NEW ELASTOMERIC ROOFING, SLIP SHEET,
NEW CONSTRUCTION NOTES:
TO ELEVATION 2299.0.
WATER WILL BE REQUIRED TO BE PUMPED OR HAULED
THAT CAN BE UTILIZED (CURRENT WATER LEVEL IS 2251).
THERE ARE ALSO TAPS TO SURGE TANKS @ ELEVATION 2128
OR 2299.0. WATER IS AVAILABLE @ ELEVATION 2096.
2. THERE IS NO POTABLE WATER AT EITHER LEVEL 2289.38
1. 2 - 60 AMP, 480V CANNON PLUGS, 1 @ 2289.38 & 1 @ 2299.0.
SERVICES PROVIDED AT ELEVATIONS 2289.38 & 2299.0
SERVICE BAY DEPENDENT ON APPROVAL OF THE CONTRACTING OFFICER.
3 POSSIBLE STORAGE CAN BE PROVIDED IN THE ERECTION BAY OR TRANSFORMER
ON FLOOR LOAD LIMITS AND APPROVAL OF THE CONTRACTING OFFICER.
2. SOME STORAGE SPACE MAY BE AVAILABLE @ ELEVATION 2288.83 DEPENDENT
1. GROUND LEVEL STORAGE AREA IS AVAILABLE IN THE PARKING LOT.
MATERIAL STORAGE
PROVIDES ROOF ACCESS.
3 A 3’-0" BY 7’-0" HOLLOW METAL DOOR AT LEVEL 2299.0
2299.0. SIZE OF HATCH 41" X 83".
USING THE STAIRWAY BETWEEN ELEVATION 2289.0 &
LOWER LEVELS TO THIS LEVEL & THEN CARRIED BY HAND TO 2299.0
(T.O. STEEL DECK) SO THAT MATERIALS CAN BE LIFTED FROM
2. A 3,000 POUND CAPACITY AIR TUG IS LOCATED AT LEVEL 2289.38
2289.0 TO ELEVATION 2299.0.
2288.0) W/ AN ANOTHER STAIRWAY RUNNING FROM ELEVATION
ELEVATION 2128 TO ELEVATION 2288.38 (TOP OF TANK @
TO ELEVATION 2096. THERE IS ALSO STAIRWAY ACCESS FROM
1. A FRIEGHT ELEVATOR PROVIDES ACCESS FROM GROUND LEVEL
ROOF ACCESS INFORMATION
| GENERAL | |
| G-001 | COVER & INDEX (1) |
| G-002 | ABBREVIATIONS (1) |
| STRUCTURAL | |
| S-001 | GENERAL STRUCTURAL NOTES, DESIGN LOADS & ABBREVIATIONS (1) |
| S-002 | WIND LOADS (1) |
| S-501 | PLYWOOD OVERLAY BID OPTION (1) |
| ARCHITECTURAL | |
| AD101 | DEMOLITION ROOF PLAN AND DETAILS (1) |
| A-101 | ROOF PLAN AND DETAILS (1) |
| A-200 | BUILDING ELEVATION (1) |
| A-301 | BUILDING SECTION (1) |
| A-511 | ROOF DETAILS (BID OPTION) (1) |
| A-520 | PHOTOS (1) |
| A-521 | PHOTOS (1) |
| A-522 | PHOTOS (1) |
| A-523 | PHOTOS (1) |
| FOR INFORMATION ONLY |
| POWER PLANT #1 - FREIGHT ELEVATOR INFORMATION |
| POWER PLANT #1 - SURGE TANK - ROOF ACCESS INFORMATION |
| POWER PLANT #1 - SURGE TANK - STAIR INFORMATION |