This is a spreadsheet detailing tank inspection requirements for two fuel storage tanks at Fort Riley, Kansas. The document provides technical specifications for API internal inspections of tanks 8314A and 8314B, which are identical 100,000-gallon capacity tanks with dimensions of 28'/24' feet. Both tanks require ultrasonic testing (UT) and roundness surveys, but do not need certified strapping charts or IFR seal replacement. Each tank has one 24-inch shell manway and contains approximately 5,500 gallons of JAA fuel that will need to be stored, transferred, or disposed of, totaling 11,000 gallons for the entire project.

The inspection work falls under Department of the Army Corps of Engineers Engineering District Omaha solicitation W9128F25Q0022, which requires the contractor to perform inspections in compliance with all applicable federal, state, and local regulations and guidelines.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

SITE CODEINSTALLATIONSTATE / COUNTRYINSPECTION TYPEFACILITY NUMBERLOCAL ID #FUEL TYPETANK CAPACITY (GA)TANK DIAMETER (FT)TANK LENGTH / HEIGHT (FT)UT (Yes/No)ROUNDNESS SURVEY Req. (Yes/No)CERTIFIED STRAPPING CHART Req. (Yes/No)REPLACE IFR SEAL (Yes/No)Gallons Remaining will need to be stored/transferred/disposed of# Manways & Sizes
RILFORT RILEYKANSASAPI INTERNAL8314A101AJAA100,00028'/24'YESYESNON/A55001 @ 24" shell
RILFORT RILEYKANSASAPI INTERNAL8314B101BJAA100,00028'/24'YESYESNON/A55001 @ 24" shell

Total gallons per purchase order to be removed: 11000