About this file
This document is a Bill of Materials (BOM) for Panel 2 - HXT1/1B87, part of the Halls Substation Control Panels project for Knoxville Utilities Board (KUB) under Bid #3855. The detailed inventory lists 38 line items, with quantities ranging from 1 to 15 units, covering electrical and communication equipment such as test blocks, test switches, relays, terminal blocks, fuse holders, fiber optic patch panels, and various communication cables and wire terminals. The bill of materials specifies precise manufacturer catalog numbers, device identifications, and technical specifications for each component, indicating a comprehensive technical procurement for a substation control panel.
The document provides extensive technical details on wire specifications, including switchboard wire with XLP insulation rated at 600V, specific conductor types (tinned copper, stranded), and color coding requirements for different circuit types. The procurement appears to focus on precise technical requirements, with specifications for wire gauges, insulation types, and termination methods. While no specific pricing is revealed in this document, the level of detail suggests a professional, technically rigorous procurement process for critical electrical infrastructure components, likely funded through KUB's capital improvement or infrastructure budget.
View the file
Other files
Show 40 more
Latest 50 of 59 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Item Quantity Description
1 9
Test block, 6-pole, complete with cover, shorting hardware and screws, semi-flush mounted. GE Type PK-2, Catalog
No. 6422120G4. Devices: T129A, T129B, T129C, T129D, T129N, 1129E, 1229E, 1329E, 1429E
2 4
Test switch mounting plate, 3 position, 3RU height, low offset, steel, ANSI 61 gray, with individual clear covers.
Suitable for installation of three (3) FT-1 type switches with stud terminals, standard depth. ABB Type FT-19R, Style
No. FRXG000000000C.
3 6
Test switch, 10-pole (8 current, 2 trip), FT-19R style, semi-flush mounted, black current handles, orange trip handles, stud terminals, ABB Type FT-1 Catalog No. RS9682A61G01: O, O, C-C, C-C, C-C, C-C. Devices: T187A29A, T187A29B, T187B29A, T187B29B, 1B8729A, 1B8729B
4 - N/A
5 6
Test switch, 10-pole (10 trip), FT-19R style, semi-flush mounted, orange trip handles, stud terminals, ABB Type FT-1
Catalog No. RS9672A97G01: O, O, O, O, O, O, O, O, O, O. Devices: T187A29C, T187A29D, T187B29C, T187B29D, 1B8729C, 1B8729D
6 - N/A
7 - N/A
8 3
Relay, auxiliary, tripping, multi-contact (16 contacts - 10"a" and 6"b") in addition to 2 contacts in coil circuit, spring trip, hand reset with trip coil for use on 125VDC system, oval handle. GE Type HEA Catalog Number HEA61C240X2.
Devices: T186A, T186B, 1B86
9 - N/A
10 - N/A
11 - N/A
12 3
Light, indicating, 125VDC with blue LED lamp & lens. GE Type ET-16 Catalog Number 116B6708G43B73B4. Device:
Above T186A, T186B, 1B86
13 - N/A
14 - N/A
15 - N/A
16 - N/A
17 - N/A
18 - N/A
19 1
Relay, 7SS85 Busbar Prot. 1 zone, 3 bays incl; Housing type: Flush mounting; BI: 7; BO: 7 (3ST + 4F + 0HS + 0P); CT: 8
(protection); VT: 0 (standard); Measuring-transducer inputs: none; Housing width: 1/3 x 19''; Modules in 19" row 1:
IO203, PS201; Modules in 19" row 2: ; LEDs/Push-buttons: 16 LEDs; Operation Panel: Integrated; Key switch:
Without; Display type: Small display; Front Design: USA; Power Supply: DC 60 V-250 V, AC 100 V-230 V;
Communications encryption: Normal; Integrated Ethernet port J: for DIGSI 5; Plug-in module position E: USART-AD-
1FO: 1 x opt. 2 km 820nm ST connector; Plug-in module position F: No module; Function points class: Base. Siemens
Product Number P1E589611. Devices: 1B87
20 2
Relay, 7UT82 Transformer Prot. (2 winding) with Standard variant; Housing type: Flush mounting; BI: 7; BO: 7 (7ST +
0F + 0HS + 0P); CT: 8 (protection); VT: 0 (standard); Measuring-transducer inputs: none; Housing width: 1/3 x 19'';
Modules in 19" row 1: IO103, PS101; Modules in 19" row 2: ; LEDs/Push-buttons: 16 LEDs; Operation Panel:
Integrated; Key switch: Without; Display type: Large display; Front Design: USA; Power Supply: DC 110 V-250 V, AC
100 V-230 V; Communications encryption: Normal; Integrated Ethernet port J: for DIGSI 5; Plug-in module position E:
USART-AE-2FO: 2 x opt. 2 km; Plug-in module position F: No module; Function points class: Base + 30 function points
Base. Siemens Product Number P1F993210. Devices: T187A, T187B
21 - N/A
22 - N/A
23 1
Power Strip, 1U rack mount, 120V, 20A, 12 outlets (6 front facing, 6 rear facing), 15 ft cord. Eaton Tripp-Lite Model
Number RS-1215-20
24 1
Diode, ABB Type TRB-2 Zener Tripping Unit with two (2) 50 Watt Zener diodes having a maximum +/- 10% tolerance on nominal zener voltage (Motorola Zener Diode 1N2846A or 1N2846B), ABB Style Number 408C003G01. Device:
T1TRB
Attachment B
Engineering Equipment File SB-162
Panel 2 - HXT1/1B87
Bill of Materials
Attachment B
Engineering Equipment File SB-162
Panel 2 - HXT1/1B87
Bill of Materials
25 15
Terminal block, 12-point, 30A, 600V, one piece, Heavy Duty molded phenolic material with washerhead screws and white unmarked terminal identification strip. GE Type EB Catalog No. EB25B12 or Marathon Catalog No. 1512STD
26 6
Fuse holder, 30A, 250V, Class R, 2-pole, phenolic base, screw type, typical for DC circuits. Bussman Catalog No.
RM25030-2SR. Fuses shall be type FRN in quantities and amp ratings as shown on KUB schematic drawings. (FRN-R-6, qty 6; FRN-R-15, qty 6)
27 - N/A
28 1
Terminal Block, 36-point, one pluggable connection per point plus two wire connections per point, for IRIG-B and RS-
485 communication wiring connections, each assembled from Phoenix Contact Clipline products. Catalog Numbers
(36) PIT 2.5-TWIN/1P Order No. 3209633, (6) bridge connectors FBS 10-5 Order No. 3030213, (2) covers D-ST 2.5-
TWIN Order No. 3030488, (2) End brackets Clipfix 35-5 Order No. 3022276, mounting hardware, markers for each terminal, and other parts as appropriate. Ferrule wire termination to be used on each connection as appropriate. See provided wiring diagrams and communication details for bridge connections, plugs, and jumpers. Device: TBPX
29 3
Terminal Plug, 3 pole, with cable housing, for use with communication terminal block (item 28), each assembled from
Phoenix Contact Clipline products Catalog No’s. PP-H 2.5/1-L Order No. 3210062, PP-H 2.1/1-M Order No. 3210091, PP-H 2.5/1-R Order No. 3210127, and PH 2.5/3 Order No. 3209701. Ferrule wire termination to be used on each connection as appropriate. Devices: Connects shielded pair cable to TBPX terminal block (BOM Item #28) from opposite end originating at Port G Siemens relays and opposite of Satec IRIG-B connection.
30 3 Cable Plug, D-sub, 9-pin, male, terminate IRIG-B communication cables to Port G on each of the Siemens relays.
31 - N/A
32 1
Patch panel assembly, Fiber Optic, 6 fibers. Multilink Type FWM-1X-SP-BK black enclosure Part Number 045-187-10 with Multilink Black Adapter Panel having six (6) Simplex ST Multi Mode Fiber Adapters, Part Number 10-5458.
Devices: PP1
33 3
Fiber Jumpers, dual fibers, multimode, 62.5/125um core and cladding with ST connectors at each end, orange color, 5 meter length. MCC Catalog No. FXD6AST-5M or KUB approved equal. Devices: PP1 to Siemens relays.
34 1 lot
Wire terminals - Uninsulated Ring tongue: Except where noted below, control wiring shall be terminated using
Burndy HYLUG type heavy-duty seamless, 1-hole flat, non-insulated ring tongue compression terminals or KUB approved equal. Burndy Catalog Number YAV9C-L36BOX for #10AWG SIS. Burndy Catalog Number YAV12G2BOX FOR
#14AWG SIS.
Wire terminals - Insulated Ring tongue: #10AWG SIS CT wiring that terminates on the Siemens relays CT inputs shall be terminated with insulated ring tongue lugs. Tyco Type PIDG, Part Number 130171.
Wire terminals - #14 SIS Ferrules: #14AWG SIS wiring that terminates on Phoenix type modular blocks on the
Siemens relays and Satec PM180 shall be terminated with wire ferrules. Where two wires terminate on a single point, a twin ferrule shall be used. Do not terminate two single ferrule wires on a point. Tyco Single Wire Ferrule Part
Number 1-966067-6. Tyco Double Wire Ferrule Part Number 966144-8.
Wire terminals - #22AWG SH-PR Ferrules: #22AWG SH-PR conductor wiring (including jumpers) that terminates on
TBL6 (BOM Items #23 and #24) Phoenix modular block shall be terminated with wire ferrules. Where two wires terminate on a single point, a twin ferrule shall be used. Do not terminate two single ferrule wires on a point. Tyco
Single Wire Ferrule Part Number 966067-2. Tyco Double Wire Ferrule Part Number 966144-1.
35 1 lot
Wire labels. All control wiring and communication cable shall be labeled at both ends using High-Visibility labels that indicate opposite end terminations of each wire or cable as shown on the wiring diagrams.
Attachment B
Engineering Equipment File SB-162
Panel 2 - HXT1/1B87
Bill of Materials
36 1 lot
Wire for protection and control shall be switchboard wire, XLP insulated, rated 600V UL Type SIS 90 ºC, flexible stranded, tinned copper conductors, NEMA and IPCEA accepted. Control wiring shall be gray insulated, #14 AWG 41-stranded tinned copper. CT circuit wiring shall be gray insulated, #10 AWG 105-stranded tinned copper. Wiring extending from the ground bus shall be green insulated, #10 AWG 105-stranded tinned copper.
37 1 lot
Cable, shielded pair, 22 AWG copper, for IRIG-B connections from Siemens relays and Satec PQM to TBPX, wire colors to be black and red plus shield, shielded pair between same device and terminal block may be bundled in multi-pair cable but each pair must be separately shielded with no connections between shields.
38 1 lot
Cable, shielded pair cable, 18 AWG copper stranded, wire colors to be black and white plus shield, for SCADA point status communication. Devices: As shown on drawings. Note: For SCADA status points, the white conductor shall be used for the signal and the black conductor shall be used as the common (SP).