33 72 33.16 Substation Control Panels (002).pdf

PDF 197 KB Posted

Attached to
Halls Substation Control Panels, Bid #3855
Solicitation number
3855
Issued by
Knox County, Tennessee

About this file

This document is a technical specification section for substation control panels prepared by Knoxville Utilities Board (KUB) for a project involving the fabrication and installation of indoor relay control panels. The specification details comprehensive requirements for manufacturing relay control panels, including fabrication standards, submittal processes, delivery instructions, and warranty terms. The panels are designed for installation in an electric substation control building and will be constructed using 11-gauge steel, with specific requirements for wiring, labeling, mounting, and finish.

The specification outlines strict technical requirements for the control panels, including a two-year warranty from shipment date or eighteen months from energization. The panels must be designed for 125VDC power supply, with draw-out type relays and precise wiring and labeling protocols. Manufacturer responsibilities include providing detailed construction drawings, bill of materials, instruction books, and factory testing. The specification emphasizes precise manufacturing standards, including chemical cleaning, priming, and finishing with ANSI No. 61 light gray paint. Shipping terms are FOB Destination, with the manufacturer assuming transit risk and required to provide 48-hour advance notification of equipment arrival.

View the file

Other files

File Type Posted
D-18920 SH03 R00 - HX 125VDC SCH - PNL 1 - AB87 BUS DIFF.pdf PDF
D-18922 SH10 R00 - HX SCADA-COMM - TB WIRING DIAGRAM (13).pdf PDF
Attachment A - Panel 1.pdf PDF
D-18920 SH10 R00 - HX 125VDC SCH - PNL 4 - BB87 BUS DIFF.pdf PDF
D-18920 SH06 R00 - HX 125VDC SCH - PNL 3 - HX82.pdf PDF
D-18922 SH09 R00 - HX SCADA-COMM - TB WIRING DIAGRAM (12).pdf PDF
D-18920 SH02 R00 - HX 125VDC SCH - PNL 1 - HX81.pdf PDF
Invitation Letter.pdf PDF
D-18933 SH06 R00 - HX WIRING DIAGRAM - PNL 3 - HX82 TERM BLOCKS.pdf PDF
D-18922 SH02 R00 - HX SCADA-COMM - CONSTRUCTION DETAILS.pdf PDF
D-18922 SH04 R00 - HX SCADA-COMM - AC-DC POWER SCHEMATIC.pdf PDF
D-18922 SH09 R00 - HX SCADA-COMM - TB WIRING DIAGRAM.pdf PDF
D-18922 SH10 R00 - HX SCADA-COMM - TB WIRING DIAGRAM.pdf PDF
D-18920 SH09 R00 - HX 125VDC SCH - PNL 4 - HX83.pdf PDF
D-18933 SH01 R00 - HX WIRING DIAGRAM - PNL 1 - HX81-AB87 POINT-TO-POINT.pdf PDF
D-18933 SH02 R00 - HX WIRING DIAGRAM - PNL 1 - HX81-AB87 TERM BLOCKS.pdf PDF
D-18919 SH01 R00 - HX FRONT VIEWS - RELAY PANELS 1-2.pdf PDF
D-18933 SH05 R00 - HX WIRING DIAGRAM - PNL 3 - HX82 POINT-TO-POINT.pdf PDF
D-18921 SH01 R00 - HX SCADA _ COMM SCHEMATIC.pdf PDF
D-18918 SH02 R00 - HX THREE LINE.pdf PDF
D-18924 SH01 R00 - HX AC PANELS _ STA SERV.pdf PDF
D-18933 SH08 R00 - HX WIRING DIAGRAM - PNL 4 - HX83-BB87 TERM BLOCKS.pdf PDF
Bid Terms and Conditions.pdf PDF
D-18921 SH02 R00 - HX SCADA _ COMM SCHEMATIC (2).pdf PDF
D-18922 SH02 R00 - HX SCADA-COMM - CONSTRUCTION DETAILS (5).pdf PDF
D-18922 SH04 R00 - HX SCADA-COMM - AC-DC POWER SCHEMATIC (7).pdf PDF
D-18922 SH05 R00 - HX SCADA-COMM - WIRING DIAGRAM.pdf PDF
D-18919 SH02 R00 - HX FRONT VIEWS - RELAY PANELS 3-4.pdf PDF
D-18922 SH06 R00 - HX SCADA-COMM - WIRING DIAGRAM.pdf PDF
D-18933 SH07 R00 - HX WIRING DIAGRAM - PNL 4 - HX83-BB87 POINT-TO-POINT.pdf PDF
D-18922 SH01 R00 - HX SCADA-COMM FRONT VIEW (4).pdf PDF
D-18922 SH06 R00 - HX SCADA-COMM - WIRING DIAGRAM (9).pdf PDF
Attachment B - Panel 2.pdf PDF
D-18920 SH05 R00 - HX 125VDC SCH - PNL 2 - 1B87 BUS DIFF.pdf PDF
D-18922 SH07 R00 - HX SCADA-COMM - WIRING DIAGRAM (10).pdf PDF
Attachment D - Panel 4.pdf PDF
Attachment E - SCADA-Comm.pdf PDF
D-18933 SH03 R00 - HX WIRING DIAGRAM - PNL 2 - HXT1-1B87 POINT-TO-POINT.pdf PDF
D-18922 SH08 R00 - HX SCADA-COMM - TB WIRING DIAGRAM (11).pdf PDF
D-18922 SH01 R00 - HX SCADA-COMM FRONT VIEW.pdf PDF
Attachment C - Panel 3.pdf PDF
D-18922 SH05 R00 - HX SCADA-COMM - WIRING DIAGRAM (8).pdf PDF
D-18921 SH03 R00 - HX COMM DETAILS.pdf PDF
D-18921 SH02 R00 - HX SCADA _ COMM SCHEMATIC.pdf PDF
D-18917 SH01 R00 - HX SINGLE LINE.pdf PDF
D-18933 SH04 R00 - HX WIRING DIAGRAM - PNL 2 - HXT1-1B87 TERM BLOCKS.pdf PDF
D-18922 SH03 R00 - HX SCADA-COMM - CONSTRUCTION DETAILS.pdf PDF
D-18920 SH04 R00 - HX 125VDC SCH - PNL 2 - HXT1 DIFF.pdf PDF
D-18920 SH01 R00 - HX 125VDC SCH - PNL 1 - HX81.pdf PDF
D-18921 SH01 R00 - HX SCADA _ COMM SCHEMATIC (1).pdf PDF
Show 40 more

Latest 50 of 59 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

[PROJECT NAME]

[PROJECT ID] SUBSTATION CONTROL PANELS

REVISED 08/28/24 33 72 33.16 - 1

SECTION 33 72 33.16

SUBSTATION CONTROL PANELS

PART 1 – GENERAL

1.01 SUMMARY

A. Section Includes: Requirements for the fabrication, construction, and furnishing of indoor relay control panels. Panels described in this specification shall be fabricated and furnished as shown on the referenced drawings and as described in this specification.

B. Related Requirements: Contract Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 specification sections, apply to this Section.

1.02 REFERENCES

A. Abbreviations and Acronyms:

1. ANSI – American National Standards Institute

2. IEEE – Institute of Electrical and Electronics Engineers

3. NEC – National Electrical Code

B. Reference Standards: The following specifications and standards of the organizations and documents listed in this paragraph form a part of the specification to the extent required by the references thereto.

In the event the requirements of the following referenced standards and specifications conflict with the specification section, the requirement of this specification shall prevail. In the event the requirements of any of the following referenced standards and specifications conflict with each other, the more stringent requirement shall prevail.

1.03 SUBMITTALS

A. Manufacturer shall provide an electronic set of all construction drawings and bill of materials for approval as soon as possible after placement of Owner’s purchase order.

B. Manufacturer shall furnish all final drawings in AutoCAD .DWG format. Do not provide .DXF format. The electronic files shall be delivered via e-mail, FTP site, or standard USB 2.0 or 3.0 flash drive media. Either NTFS or FAT32 file formatting is acceptable.

C. Manufacturer shall provide three (3) copies of 3-ring bound composite instruction books, including pamphlets, leaflets, relay instructions, and software CDs furnish complete instructions for installation, operation and maintenance of all devices furnished. One (1) copy of the composite instruction book, including pamphlets, leaflets, and relay instructions shall also be provide on USB 2.0 or 3.0 flash drive media.

SUBSTATION CONTROL PANELS [PROJECT ID]

33 72 33.16 - 2 REVISED 08/28/24

D. All submittals shall be sent to:

Knoxville Utilities Board Attn: Rody Blevins 4505 Middlebrook Pike, Knoxville TN 37921 Phone #: 865-558-2135 Email: Rody.Blevins@kub.org

1.04 DELIVERY AND HANDLING

A. The relay control panels shall be loaded and braced carefully to prevent any damage to the panels or contents. Packaging shall be such that the relay control panels will not be exposed to rain, dirt, debris, or contamination.

B. Manufacturer shall assume all risk due to loss or damage while shipment is in transit to Owner from Manufacturer’s facility.

C. The relay control panels shall be shipped FOB Destination.

D. Owner shall receive prompt notification that each shipment has been released to carrier and expected time of arrival of shipment at the point of destination. Manufacturer shall provide Owner with at least 48 hours notice of equipment arrival at the Site.

1.05 WARRANTY

A. The relay control panel and all accessories and equipment furnished shall be warranted free from defects in design, materials, and workmanship and is the kind and quality specified herein. Warranty shall be for two (2) years from date of shipment to Owner or eighteen (18) months from date of energization.

B. If for some reason any equipment shall need replacement or repair during the warranty period, the Manufacturer shall replace or repair the defective equipment at no cost to Owner. Manufacturer shall also be responsible for transportation costs if the defective equipment is to be transported to the Manufacturer’s repair facility or an Owner-approved repair facility.

PART 2 – PRODUCTS

2.01 CONTROL PANEL

A. Description:

1. The relay control panel shall consist of the metal frame, channel, relays, wire-way, copper ground bus, switches, meters, terminal blocks, fuse holders, fuses, diodes, control wiring, and other required accessories all assembled into a one-piece unit for installation in an electric substation control building. The relay panels and all auxiliary equipment shall be wired by the Manufacturer and factory tested.

REVISED 08/28/24 33 72 33.16 - 3

2. All relays are to be in draw out type case for semi-flush mounting except as otherwise noted, and for use on a 125VDC supply only.

B. Materials:

1. See Attachments for Bill of Materials. No substitutes will be allowed except as approved by Owner.

2. Mounting hardware, DIN Rail, or other items necessary to build a finished panel as described in this specification and shown on the drawings shall be provided in sufficient quantities as required at no additional cost to Owner.

C. Assembly or Fabrication:

1. The panel, rack, and base of each shall be as shown on the Contract Drawings. Panels and rack shall be formed of steel sheet of 11-guage thickness and shall be mounted on a structural steel, 6-inches,

8.2 pound channel section to serve as a vertical wiring gutter. The front channel sections will not be used as wiring gutters. The rear channel sections shall be joined to the front channel sections by bolts. Both of the front channel sections shall be provided with holes for fastening to adjoining racks of similar design. The panels rack shall be attached to the structural steel channel by welding and the base section shall be furnished with mounting and grouting holes.

2. Labeling: Panel wiring shall be labeled on both ends of the conductor. Consistent with the point-to-point wiring diagrams, each end of each conductor shall be labeled to indicate the destination of the opposite end. Each label shall also include, in parenthesis or braces, the wire node name whenever it is shown on supplied drawings.

3. Nameplates: Front nameplates shall be attached to the panels using screws and rear nameplates shall use adhesive. The name plates shall be black phenolic with white core letters. Nameplates shall be furnished on both the front and back of the panels. Front nameplates shall be as noted on the Front View drawings, while the rear nameplate shall carry the short name designation (i.e. AA, AB, AC, BA, BB, BC, etc.) as used on the wiring/connection diagrams. Permanently label all devices on the back of the panels to correlate with wiring diagram nomenclature.

4. Wiring Practices: Panel wiring shall be logically grouped at terminal blocks for termination of external cables. All terminal blocks shall be clearly identified for proper external connections.

Indicating lights shall be wired at the end pf daisy-chained circuits. Use cable ties on multiple wire runs and panduit on multiple cable runs. Size the panduit for maximum fill of 60%, taking into account external cables. No more than two wires shall terminate on any same terminal. Where more than one terminal block on the same panel is part of a daisy-chained circuit, such terminal blocks shall be daisy-chained directly to each other and then to the other devices on the panel.

This shall be done such as to permit future disconnecting of devices on a panel without interrupting continuity that passes through the panel.

5. Assembly Drawings: See list of drawings found in Appendix B of this Section.

D. Finishes:

1. After fabrication, and before assembly, the panels, rack, and all associated parts shall be chemically cleaned, neutralized, prime-coated, and finished-coated with ANSI No. 61 light gray paint. One (1) quart of touch-up paint (ANSI No. 61 light gray) shall be included with the shipment.

33 72 33.16 - 4 REVISED 08/28/24

2.02 SOURCE QUALITY CONTROL

A. All equipment shall be tested in accordance with the latest applicable standards of ANSI, IEEE, and NEC.

If any test performed fails, corrections shall be made, and the test shall be performed again at the Manufacturer’s expense.

B. Complete relay wiring shall be tested prior to shipment. Problems shall be brought to Owner’s attention and resolved prior to shipment.

C. All wiring shall be performed by skilled electricians to guarantee good, tight connections at terminal points, and they do not touch adjacent bare wires. An excessive number of loose wiring connections will disqualify the Manufacturer from future opportunities to bid. Owner shall be the sole judge as to how many loose connections shall be deemed excessive.

D. Manufacturer shall furnish a factory certified test report for each relay control panel.

2.03 ATTACHMENTS

A. Bill of Materials

B. List of Assembly Drawings

PART 3 – EXECUTION (NOT USED)

END OF SECTION

REVISED 08/28/24 33 72 33.16 ATTACHMENT A - 1

Engineering Equipment File XXXX Panel XX – LABEL Bill of Materials

Item Quantity Description

SEE ATTACHED

REVISED 08/28/24 33 72 33.16 ATTACHMENT B - 1

The following drawings shall be used in the fabrication and assembly of the control panels

LIST OF ASSEMBLY DRAWINGS

DRAWING NO. DRAWING DESCRIPTION REVISION

D-XXXX

Sheet XX of XX Sheet Title R# or Date

D-18917 SH01 HX SINGLE LINE R0

D-18918 SH01 HX THREE LINE R0

D-18918SH02

D-18919 SH01

HX THREE LINE

HX FRONT VIEWS-RELAY PANELS 1-2

R0 R0

D-18919 SH02 HX FRONT VIEWS-RELAY PANELS 3-4 R0

D-18920 SH01 HX 125VDC SCH-PNL 1- HX81 R0

D-18920 SH02 HX 125VDC SCH-PNL 1- HX81 R0

D-18920 SH03 HX 125VDC SCH-PNL 1- AB87 BUS DIFF R0

D-18920 SH04 HX 125VDC SCH-PNL 2- HXT1 DIFF R0

D-18920 SH05 HX 125VDC SCH-PNL 2- 1B87 BUS DIFF R0

D-18920 SH06 HX 125VDC SCH-PNL 3- HX82 R0

D-18920 SH07 HX 125VDC SCH-PNL 3- HX82I R0

D-18920 SH08 HX 125VDC SCH-PNL 4-HX83 R0

D-18920 SH09 HX 125VDC SCH-PNL 4- HX83I R0

D-18920 SH10 HX 125VDC SCH-PNL 4- BB87 BUS DIFF R0

D-18933 SH01 HX WIRING DIAGRAM-PNL 1- HX81-AB87 POINT-TO-POINT R0

D-18933 SH02 HX WIRING DIAGRAM-PNL 1- HX81-AB87 TERM BLOCKS R0

D-18933 SH03 HX WIRING DIAGRAM-PNL 2- HXT1- 1B87 POINT-TO-POINT RO

D-18933 SH04 HX WIRING DIAGRAM-PNL 2- HXT1- 1B87 TERM BLOCKS R0

D-18933 SH05 HX WIRING DIAGRAM-PNL 3- HX82- POINT-TO-POINT R0

D-18933 SH06 HX WIRING DIAGRAM-PNL 3- HX82 TERM BLOCKS R0

D-18933 SH07 HX WIRING DIAGRAM-PNL 4- HX83-BB87 POINT-TO-POINT R0

D-18933 SH08 HX WIRING DIAGRAM-PNL 4- HX83-BB87 TERM BLOCKS R0

D-18921 SH01 HX SCADA & COMM SCHEMATIC R0

D-18921 SH02 HX SCADA & COMM SCHEMATIC R0

D-18921 SH03 HX COMM DETAILS R0

D-18922 SH01 HX SCADA-COMM FRONT VIEW R0

D-18922 SH02 HX SCADA-COMM- CONSTRUCTION DETAILS R0

D-18922 SH03 HX SCADA-COMM- CONSTRUCTION DETAILS R0

D-18922 SH04 HX SCADA-COMM- AC-DC POWER SCHEMATIC R0

D-18922 SH05 HX SCADA-COMM- WIRING DIAGRAM R0

D-18922 SH06 HX SCADA-COMM- WIRING DIAGRAM R0

D-18922 SH07 HX SCADA-COMM- WIRING DIAGRAM R0

D-18922 SH08 HX SCADA-COMM- TB WIRING DIAGRAM R0

33 72 33.16 REVISON PAGE - 2 REVISED 08/28/24

D-18922 SH09 HX SCADA-COMM- TB WIRING DIAGRAM R0

D-18922 SH10 HX SCADA-COMM- TB WIRING DIAGRAM R0

REVISED 08/28/24 33 72 33.16 ATTACHMENT B - 3

Master Specification Section Owner: Electric Systems Engineering Discipline Reviewer: Electric Systems Engineering Manager Cross-Discipline Reviewer:

Summary of Changes:

Rev. No. Revision Date Description / Justification Author

1. 08/28/24 Original Issuance Les Beaver

2.

3.

4.

5.

6.

7.

8.

9.

10.

1 PART 1 – GENERAL
1.01 SUMMARY
A. Section Includes: Requirements for the fabrication, construction, and furnishing of indoor relay control panels. Panels described in this specification shall be fabricated and furnished as shown on the referenced drawings and as described in this ...
B. Related Requirements: Contract Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 specification sections, apply to this Section.
1.02 REFERENCES
A. Abbreviations and Acronyms:
1. ANSI – American National Standards Institute
2. IEEE – Institute of Electrical and Electronics Engineers
3. NEC – National Electrical Code

B. Reference Standards: The following specifications and standards of the organizations and documents listed in this paragraph form a part of the specification to the extent required by the references thereto. In the event the requirements of the fol...

1.03 SUBMITTALS
A. Manufacturer shall provide an electronic set of all construction drawings and bill of materials for approval as soon as possible after placement of Owner’s purchase order.
B. Manufacturer shall furnish all final drawings in AutoCAD .DWG format. Do not provide .DXF format. The electronic files shall be delivered via e-mail, FTP site, or standard USB 2.0 or 3.0 flash drive media. Either NTFS or FAT32 file formatting is...
C. Manufacturer shall provide three (3) copies of 3-ring bound composite instruction books, including pamphlets, leaflets, relay instructions, and software CDs furnish complete instructions for installation, operation and maintenance of all devices fu...
D. All submittals shall be sent to:
Knoxville Utilities Board
Attn: Rody Blevins
4505 Middlebrook Pike, Knoxville TN 37921
Phone #: 865-558-2135
Email: Rody.Blevins@kub.org
1.04 DELIVERY AND HANDLING
A. The relay control panels shall be loaded and braced carefully to prevent any damage to the panels or contents. Packaging shall be such that the relay control panels will not be exposed to rain, dirt, debris, or contamination.
B. Manufacturer shall assume all risk due to loss or damage while shipment is in transit to Owner from Manufacturer’s facility.
C. The relay control panels shall be shipped FOB Destination.
D. Owner shall receive prompt notification that each shipment has been released to carrier and expected time of arrival of shipment at the point of destination. Manufacturer shall provide Owner with at least 48 hours notice of equipment arrival at th...
1.05 Warranty
A. The relay control panel and all accessories and equipment furnished shall be warranted free from defects in design, materials, and workmanship and is the kind and quality specified herein. Warranty shall be for two (2) years from date of shipment ...
B. If for some reason any equipment shall need replacement or repair during the warranty period, the Manufacturer shall replace or repair the defective equipment at no cost to Owner. Manufacturer shall also be responsible for transportation costs if ...
2 part 2 – PRODUCTS
2.01 CONTROL PANEL
A. Description:
1. The relay control panel shall consist of the metal frame, channel, relays, wire-way, copper ground bus, switches, meters, terminal blocks, fuse holders, fuses, diodes, control wiring, and other required accessories all assembled into a one-piece un...
2. All relays are to be in draw out type case for semi-flush mounting except as otherwise noted, and for use on a 125VDC supply only.
B. Materials:
1. See Attachments for Bill of Materials. No substitutes will be allowed except as approved by Owner.
2. Mounting hardware, DIN Rail, or other items necessary to build a finished panel as described in this specification and shown on the drawings shall be provided in sufficient quantities as required at no additional cost to Owner.
C. Assembly or Fabrication:
1. The panel, rack, and base of each shall be as shown on the Contract Drawings. Panels and rack shall be formed of steel sheet of 11-guage thickness and shall be mounted on a structural steel, 6-inches, 8.2 pound channel section to serve as a vertic...
2. Labeling: Panel wiring shall be labeled on both ends of the conductor. Consistent with the point-to-point wiring diagrams, each end of each conductor shall be labeled to indicate the destination of the opposite end. Each label shall also include...
3. Nameplates: Front nameplates shall be attached to the panels using screws and rear nameplates shall use adhesive. The name plates shall be black phenolic with white core letters. Nameplates shall be furnished on both the front and back of the pa...
4. Wiring Practices: Panel wiring shall be logically grouped at terminal blocks for termination of external cables. All terminal blocks shall be clearly identified for proper external connections. Indicating lights shall be wired at the end pf dais...
5. Assembly Drawings: See list of drawings found in Appendix B of this Section.
D. Finishes:
1. After fabrication, and before assembly, the panels, rack, and all associated parts shall be chemically cleaned, neutralized, prime-coated, and finished-coated with ANSI No. 61 light gray paint. One (1) quart of touch-up paint (ANSI No. 61 light gr...
2.02 SOURCE QUALITY CONTROL
A. All equipment shall be tested in accordance with the latest applicable standards of ANSI, IEEE, and NEC. If any test performed fails, corrections shall be made, and the test shall be performed again at the Manufacturer’s expense.
B. Complete relay wiring shall be tested prior to shipment. Problems shall be brought to Owner’s attention and resolved prior to shipment.
C. All wiring shall be performed by skilled electricians to guarantee good, tight connections at terminal points, and they do not touch adjacent bare wires. An excessive number of loose wiring connections will disqualify the Manufacturer from future ...
D. Manufacturer shall furnish a factory certified test report for each relay control panel.
2.03 attachments
A. Bill of Materials
B. List of Assembly Drawings

3 part 3 – EXECUTION (not USed)