This document is an Attachment A describing the fire protection systems and fire alarm details for the Senate Office Buildings. The attachment provides a detailed inventory of the fire protection equipment, including quantities and locations, for the Hart Senate Office Building, Dirksen Senate Office Building, Russell Senate Office Building, Senate Underground Garage, Senate Employees Child Care Center, Daniel Webster Page Dorm, and Blue Plains Furniture Warehouse. The information covers the fire alarm systems, fire pump systems, dry pipe sprinkler systems, and kitchen hood suppression systems in these facilities. This attachment appears to support a Request for Quote (RFQ) solicitation #AOCSSB24Q0024 issued by the Architect of the Capitol for inspection and testing services of the Senate Office Buildings' fire protection systems.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment A Senate Fire Testing SOW
ATTACHMENT A
Senate Office Building
Fire Protection Systems
Hart Senate Office Building
Built in 1980 1,094,805 sf
The Hart Senate Office Building (HSOB) is a nine story building. The building is open to the public and provides office space for U.S. Senators, their staff, and Hearing and Meeting rooms.
Service areas, storage areas, electrical rooms and mechanical rooms are located in the ground floor and attic. The building also has a parking garage on three below grade floors. The building is considered business occupancy.
Fire Alarm System:
Notifier system with 77 control panels installed in 2008-2010.
Item Description Quantity Node 10 Node 20 Node 30 1 Phone 62 24 24 21 2 Speaker 893 3 Manual pull station 147 4 Smoke detector 388
5 Heat detector 72 6 Duct detector 425 7 strobe/horn/bell 128 8 Tamper switch 118 9 Pressure switch (H/L air switch)
10 Flow switch/meter 83 32 24 29 11 Dry pipe sprinkler system 1 12 Fire pump system 1 13 Kitchen Hood System 0*
*3 DSOB Kitchen hoods are monitored using one ANSUL R-102 suppression system tied to a HSOB Notifier Fire Alarm Zone
Dirksen Senate Office Building
Built in 1956 706,603 sf
The Dirksen Senate Office Building (DSOB) is a seven story building. The building is open to the public and provides office space for U.S. Senators, their staff, and Hearing and Meeting rooms. Service areas, storage areas, electrical rooms and mechanical rooms are located in the ground sub-basement and attic. The building also has a parking garage on grade and two floors below grade. The building is considered business occupancy.
Fire Alarm Systems (x2):
AutoCall system with 55 control and I/O panels installed in 1990s.
Item Description Quantity Notes 1 Phone 51 2 Speaker 204 3 Manual pull station 52 4 Smoke detector 1466 5 Heat detector 3 6 Duct detector 43 7 strobe/horn/bell 284 8 Tamper switch 90 9 Pressure switch (H/L air swicth) 2 10 Flow switch/meter 60 11 Fire pump system 2 12 Dry pipe sprinkler system 0 13 Kitchen hood suppression 5*
*3 DSOB Kitchen hoods are monitored using one ANSUL R-102 suppression system tied to a HSOB Notifier Fire Alarm Zone
Notifier 320 system installed in 2017
1 Phone 0 2 Speaker 0 3 Manual pull station 0 4 Smoke detector 17 5 Heat detector 0 6 Duct detector 0 7 strobe/horn/bell 0 8 Tamper switch 1 9 Pressure switch (H/L air swicth) 0 10 Flow switch/meter 1 11 Fire pump system 0 12 Dry pipe sprinkler system 13 Kitchen hood suppression 0
Russell Senate Office Building
Built in 1909 661,009 sf
The Russell Senate Office Building (RSOB) is a five story building. The building is open to the public and provides office space for U.S. Senators, their staff, and Hearing and Meeting rooms.
Service areas, storage areas, electrical rooms and mechanical rooms are located in the basement floor and attic. The building also has one floor below grade. The building is considered business occupancy. The RSOB has (x1) dry sprinkler system.
Fire Alarm Systems (x9):
AutoCall system with 75 control and I/O panels installed in 1990s.
1 Phone 38 2 Speaker 47 3 Manual pull station 49 4 Smoke detector 1539 18 of these devices are within
HVAC return grills located throughout public hallways
5 Heat detector 7 6 Duct detector 30 7 strobe/horn/bell 104 8 Tamper switch 123 9 Pressure switch (H/L air switch) 1 10 Flow switch/meter 73 11 Dry pipe sprinkler system 1 12 Fire pump system 1 13 Kitchen hood suppression 2 1 Fire Alarm Zone
Notifier 3030 system installed in 2016-2017 (Attic Smoke Detection)
2 Speaker 0 3 Manual pull station 0 4 Smoke detector 401 -5 loops
-60 of these devices are within HVAC return grills located throughout public hallway on lower-level floors
5 Heat detector 0 6 Duct detector 0 7 strobe/horn/bell 0 8 Tamper switch 3 9 Pressure switch (H/L air switch) 0 10 Flow switch/meter 3 11 Dry pipe sprinkler system 0 12 Fire pump system 0
Notifier 320 system installed in 2016 (Elev 1 & 2 Recall/Shunt Panel)
2 Speaker 0 3 Manual pull station 0 4 Smoke detector 7 Initiates Recall 5 Heat detector 7 Initiates Shunt Trip 6 Duct detector 0 7 strobe/horn/bell 0
8 Tamper switch 0 9 Pressure switch (H/L air switch) 0 10 Flow switch/meter 0 11 Dry pipe sprinkler system 0
Notifier 320 system installed in 2016 (Elev 3 & 4 Recall/Shunt Panel)
2 Speaker 0 3 Manual pull station 0 4 Smoke detector 6 Initiates Recall 5 Heat detector 9 Initiates Shunt Trip 6 Duct detector 0 7 strobe/horn/bell 0 8 Tamper switch 0 9 Pressure switch (H/L air switch) 0 10 Flow switch/meter 0 11 Dry pipe sprinkler system 0
Notifier 320 system installed in 2016 (Elev 7, 8 & 9 Recall/Shunt Panel)
2 Speaker 0 3 Manual pull station 0 4 Smoke detector 17 Initiates Recall 5 Heat detector 17 Initiates Shunt Trip 6 Duct detector 0 7 strobe/horn/bell 0 8 Tamper switch 0 9 Pressure switch (H/L air switch) 0 10 Flow switch/meter 0 11 Dry pipe sprinkler system 0
Notifier 320 system installed in 2016 (Elev 10 & 11 Recall/Shunt Panel)
2 Speaker 0 3 Manual pull station 0 4 Smoke detector 9 Initiates Recall
5 Heat detector 11 Initiates Shunt Trip 6 Duct detector 0 7 strobe/horn/bell 0 8 Tamper switch 0 9 Pressure switch (H/L air switch) 0 10 Flow switch/meter 0 11 Dry pipe sprinkler system 0
Notifier 320 system installed in 2016 (Elev 12 & 13 Recall/Shunt Panel)
2 Speaker 0 3 Manual pull station 0 4 Smoke detector 14 Initiates Recall 5 Heat detector 12 Initiates Shunt Trip 6 Duct detector 0 7 strobe/horn/bell 0 8 Tamper switch 0 9 Pressure switch (H/L air switch) 0 10 Flow switch/meter 0 11 Dry pipe sprinkler system 0
Notifier 320 system installed in 2016 (Elev 14 Recall/Shunt Panel)
2 Speaker 0 3 Manual pull station 0 4 Smoke detector 8 Initiates Recall 5 Heat detector 4 Initiates Shunt Trip 6 Duct detector 0 7 strobe/horn/bell 0 8 Tamper switch 0 9 Pressure switch (H/L air switch) 0 10 Flow switch/meter 0 11 Dry pipe sprinkler system 0
Notifier 320 system installed in 2016 (Elev 15 Recall/Shunt Panel)
2 Speaker 0 3 Manual pull station 0 4 Smoke detector 9 Initiates Recall 5 Heat detector 4 Initiates Shunt Trip 6 Duct detector 0 7 strobe/horn/bell 0 8 Tamper switch 0 9 Pressure switch (H/L air switch) 0 10 Flow switch/meter 0 11 Dry pipe sprinkler system 0
Senate Underground Garage
Built in 1909 84,324 sf
The Senate Underground Garage (SUG) is a one-story building. The SUG provides office space and parking for staff. Service areas, storage areas, electrical rooms and mechanical rooms are also located in the SUG. The building has one floor below grade. The building is considered business occupancy. The SUG has (x2) dry sprinkler systems.
Fire Alarm System:
Simplex system with 4 control panels installed in 2004-2005. Annunciator was installed in 2021 during SUG Renovation project.
Item Description Quantity Notes 1 Phone 0 2 Speaker 0 3 Manual pull station 14 4 Smoke detector 80 -Some smoke detectors shut down associated air handling units.
5 Heat detector 118 -Parking area heat detectors shut down associated air handling units.
-Some other heat detectors shut down associated air handling units
6 Duct detector 1 -Duct detector shuts down associated air handling unit.
7 Strobes, horns and strobe/horns 90 8 Tamper switch 11 9 Pressure switch 2 10 Flow switch/meter 8 11 Dry Pipe Sprinkler System 2 1. Tyco DPV-1 6” DN150 w/
TFP Model ACC-1 Accelerator
2. Tyco DPV-1 4” DN1000 w/
TFP Model ACC-1 Accelerator 12 Fire Pump System 0
13 Kitchen Hood System 0 14 Door Release Relays 7 15 Annunciator 1 Annunciator is in main panel room
Senate Employees Child Care Center
Built in 1984 9,344 sf
The Senate Employees Child Care Center (SECCC) is a two story building. The building is open to the public and provides office space and classrooms. Service areas, storage areas, electrical rooms and mechanical rooms are located in the basement floor. The building is considered school occupancy. The classrooms are occupied from 8am to 7pm workdays.
Notifier system with 5 control panels installed in 2006-2008.
1 Speaker 2 Manual pull station 10 3 Smoke detector 55 4 Heat detector 5 5 Duct detector 2 6 strobe/horn/bell 40 7 Tamper switch 6 8 Pressure switch 1 9 Flow switch/meter 3 10 CO detector 1 11 Natural Gas Detector 1
Daniel Webster Page Dorm
Built in 1984 20,870 sf
The Daniel Webster Page Dorm (DWPD) is a two story building. The building provides office space, classrooms and dormitory space. Service areas, storage areas, electrical rooms and mechanical rooms are located in the basement floor. The Paige’s occupy the building 24 hours a day and 7 days a week. There are 6 weeks a year when the Paige’s are not in residency.
Notifier system with 7 control panels installed in 2006-2008.
1 Speaker 2 2 Manual pull station 8 3 Smoke detector 108 4 Heat detector 18 5 Duct detector 14 6 strobe/horn/ 81 7 Tamper switch 5
8 Pressure switch 1 9 Flow switch/meter 4 10 CO detector 2 11 Natural Gas Detector 2
Blue Plains Furniture Warehouse *Offsite: 4700 Shepherd Parkway SW, Washington, DC 20032
Built in UNKNOWN 20,921 sf
The Blue Plains Furniture Warehouse is a two story building. Service areas, storage areas, electrical rooms and mechanical rooms are located in the building. The building is considered warehouse occupancy.
Thorn M-200 control panel system
1 Speaker 8 2 Manual pull station 4 3 Smoke detector 2 4 Heat detector 2 5 Duct detector 0 6 strobe/horn 8 7 Tamper switch 2 8 Pressure switch 0 9 Flow switch/meter 2 10 CO detector 0 11 Natural Gas Detector 0
File details come from the government source that posted it. Updated .