Interim Life Safety Measures (ILSM) VA Northern California Health Care System
Attachment B Policy Statement 138-56 March 1, 2019
INTERIM LIFE SAFETY MEASURES (ILSM) CHECKLIST
Project Name: Planned Project Start Date:
Project Number:
PM / COR P.O.C.: P.O.C extension:
Location of Construction: Estimated Duration:
Yes No
N/A
1. Will any fire alarm, detection or suppression system be out of service more than 8/10 hours respectively in a 24-hour period?
If yes, notify the occupants and fire department and have VA Police initiate a fire watch.
Notification and fire watch times must be documented. Provide temporary but equivalent system fire alarm and detection systems for use. Inspect, test, and document temporary systems monthly. (JC LS.01.02.01 EP 1). A fire watch may not always be needed if construction activity is planned and proper separation with ILSMs in place.
Note: The 2015 edition of the Life Safety Code now refers to the requirements of NFPA 72 where the time requirement is 8 hours. NFPA 101 has referred to the requirements of NFPA 25 since the 2012 Edition of the Life Safety Code, where the time requirement is 10 hours in a 24-hour period.
2. Will any exits/means of egress be obstructed during construction for more than 8 hours such that alternate exits will have to be established?
If yes, then ensure that staff members are notified or trained on alternate routes of exit and that proper signage is installed. Ensure that escape routes for construction workers are maintained at all times, and the means of exiting construction areas are inspected daily. (JC LS.01.02.01
EP 2) 3)
3. Is additional fire-fighting equipment necessary?
If yes, ensure that they are provided and that staff are trained on their use. (JC LS.01.02.01 EP
6) 3
4. Will construction activities or other maintenance/repair activity temporarily impact the normal level of life safety for the building(s) involved?
If yes ILSM checklist will be completed for each construction project (by contractor or in-house. (JC LS.01.02.01 EP 3j)
5. Are exits in affected areas inspected on a daily basis?
If yes, ensure that exits in affected areas are inspected on a daily basis (JC LS 01.02.01 EP 4)
6. Ensure that temporary but equivalent fire alarm and detection systems for use when a fire system is impaired. (JC LS 01.02.01 EP 5)
ILSM Checklist
Yes No
N/A
7.
-Will temporary fire alarm, detection and suppression system be inspected and tested monthly?
If yes, ensure completion date of these test are documented. (JC LS 01.02.01 EP 12) -Will temporary construction partitions be installed?
If yes, ensure that temporary construction partitions are smoke tight and built of noncombustible or limited combustible materials that will not contribute to the development or spread of fire. (JC LS.01.02.01 EP 7)
8. Increase hazard surveillance of buildings, grounds, and equipment, with special attention to excavations, construction areas, construction storage, and field offices. (JC LS.01.02.01 EP 8)3)
9. If implementation of ILSM is required, ensure and enforce practices that reduce the building's flammable and combustible fire load to the lowest feasible level. (Removal of debris, good housekeeping, and minimum storage of construction materials). (JC LS.01.02.01 EP 9)3).
10. -Does the medical center trained those who work in the hospital to compensate for impaired structural or compartmental fire safety features?
If yes, ensure that staff are trained when structural or compartmentalization feature of fire safety are compromised. (JC LS 01.02.01 EP 14)
-If implementation of ILSM is required, provide additional training to those who work in the hospital on the use of fire-fighting equipment. (JC LS.01.02.01 EP 10) 3)
11. Ensure that life safety building deficiencies, construction hazards, and ILSM for construction areas are announced in the Daily Bulletin, Beacon newsletter, and/or the Intranet, when appropriate. (JC LS.01.02.01 EP /3) General - Provide hospital wide safety education programs to promote awareness of life safety building deficiencies, construction hazards, and ILSM through the annual mandatory training.
Train those in the affected areas to compensate for impaired structural or compartmental fire safety features.
COMMENTS:
Submitted by: _____ _____________________ Printed Name & Signature Date
Reviewed by EH&S: ____________________________________________ _____________________ Printed Name & Signature Date
INTERIM LIFE SAFETY MEASURES (ILSM) CHECKLIST
| Project Name: Construct Parking Structure Replacing Expiring Lease | |
| PM COR POC: Hari Kushwaha | |
| POC extension: 925-372-2529 | |
| Location of Construction: MTZ camps -site AB6/AB7/AB5 | |
| Estimated Duration: 400 days | |
| Date1_af_date: 01/21/2021 | |
| Project Number: 612-165 | |
| Text2: | |
| Check Box3: Yes | |
| Check Box4: Off | |
| Check Box5: Off | |
| Check Box6: Off | |
| Check Box7: Yes | |
| Check Box8: Off | |
| Check Box9: Off | |
| Check Box10: Yes | |
| Check Box11: Off | |
| Check Box12: Off | |
| Check Box13: Yes | |
| Check Box14: Off | |
| Check Box15: Yes | |
| Check Box16: Off | |
| Check Box17: Off | |
| Check Box18: Yes | |
| Check Box19: Off | |
| Check Box20: Off | |
| Check Box21: Off | |
| Check Box22: Off | |
| Check Box23: Yes | |
| Check Box24: Yes | |
| Check Box25: Off | |
| Check Box26: Off | |
| Check Box27: Yes | |
| Check Box28: Off | |
| Check Box29: Off | |
| Check Box30: Off | |
| Check Box31: Off | |
| Check Box32: Yes | |
| Check Box33: Off | |
| Check Box34: Off | |
| Check Box35: Yes | |
| 2020-06-25T12:45:33-0700 | |
| Harishankar Kushwaha 1600031 |
| 2020-07-01T13:09:52-0700 | |
| GARRETT S. OLVERA 1014406 |
| Date38_af_date: 6/25/20 | |
| Date39_af_date: 7/1/20 | |
| COMMENTS: | |
| 2020-07-10T09:29:11-0700 | |
| Jonathan L. Bassignani 326635 |