1/2" x 1" DEEP
SAW-CUT JOINT
1/2" x 1" DEEP
SAW-CUT JOINT
2 x 2 KEYWAY 1'-0"
6" CONC DRIVE SLAB
(TO STREET) WITH #3 AT
16" OC, EACH WAY
(3) #4 x CONT.
GRADE SLAB
#4 x 4'-0" @ 12" OC, CENTERED ON JOINT. GREASE
AND WRAP ONE HALF OF THE
BAR (PARKING RAMP SIDE)
1/2" JOINT FILLER
DRIVEWAY PARKING RAMP
1'-0"
6" WIDE x CONT. 12 GA
GALVANIZED SHEET METAL
STRIP, TYP
WATERPROOFING REQUIRED
AT SOIL RETAINING
CONDITION. SEE ARCH SPEC'S
3/4" RAKED
JOINT EACH SIDE
VERT WALL
REINF TYP
BACKER ROD
EACH SIDE
SILICONE SEALANT
EACH SIDE
NOTE:
1. LOCATIONS OF ALL CONTROL JOINTS MUST
BE VERIFIED WITH THE ENGINEER. MAX
SPACING NOT TO EXCEED 24'-0" UNO
NOTE 3
REFER TO FOOTING SCHEDULE ON S-303 FOR
ELEVATOR MAT THICKNESS AND REINFORCING
#4 @ 12" EF
#5 @ 12" EF
GRADE SLAB
CONCRETE WALL
THICKNESS
SAME AS CMU
WALL ABOVE
NOTE 1
EL TOP OF FTG
SEE PLAN /S-101
WATERPROOFING
1" CLR
2" CLR
2'-0"
3" CLR
C L R
C L R
#6 @ 12" EW
TOP AND BOT
HYDRAULIC ELEVATORS: PROVIDE HOLE FOR
JACK. VERIFY OPENING SIZE AND LOCATION
WITH ELEVATOR SHOP DRAWINGS
NOTE:
1.
2.
SEE ARCH
GRADE SLAB
1/2" COMPRESSIBLE
JOINT FILLER
/2
CONC. CURB WITH
#4 @ 18" EACH WAY
AT MID-DEPTH
1'-0"
CONCRETE
COLUMN
CONCRETE
BUMPER WALL
2" SEPARATION TYP
MAIN REINFORCING
CONTINUOUS THROUGH JOINT
IF MAIN REINFORCING IS
DISCONTINUOUS ADD DOWELS
TO MATCH MAIN REINFORCING
ADD DOWELS IF REQUIRED TO
MATCH MAIN REINFORCING
(SIZE, NUMBER AND SPACING)
KEY TO BE
CONTINUOUS
CJ LOCATION TO BE
APPROVED BY SEOR
1 1/2"
D
2'-0" MIN
40 BAR DIAMETERS
2'-0" MIN
40 BAR DIAMETERS
CONDUIT OR PIPE
2'-0" WIDE CONT STRIP
OF SLAB REINFORCING
AT INTERSECTION OF
CONDUIT OR PIPES,
EXCAVATE AS REQUIRED
TO PROVIDE
3" CONCRETE PROTECTION
S E
E P
L A
N S
U B
-G R
A D
E
M
IN
M
IN
TOP OF GRADE BEAM
REINFORCING TO
BE SAME SIZE AND
NUMBER AS GRADE
BEAM BARS
MAX
2'-8"
M A
X T
Y P
S E
E S
C H
E D
D E
P T
H
S E
E S
C H
E D
D E
P T
H
/2
C L R
3" C
LR
M
IND
E P T H
MIN
4'-0"
3" CLR
30 BAR DIA
T Y
P
C
L R
GRADE BEAM FOR
REINFORCING SEE
SCHEDULE
BEGINNING OF
STEPPED GRADE BEAM
30 BAR DIA
WATERPROOFING REQUIRED
AT SOIL RETAINING CONDITION.
SEE ARCH SPEC'S
END OF WALL VERT REINF
TYP EACH SIDE OF JOINT
6" WIDE x CONT 12 GA
GALVANIZED SHEET METAL
STRIP, TYP PROVIDE HILTI X-C
SHOT PINS @ 16"OC ONE SIDE
BACKER ROD
SILICONE SEALANT
NOTE:
DISCONTINUOUS
1/2" EXPANSION JOINT
HORIZ REINF
1. LOCATION OF ALL EXPANSION JOINTS MUST BE
VERIFIED WITH THE ENGINEER. MAX SPACING NOT
TO EXCEED 60'-0" UNO.
V-GROOVE
JOINT SPACING: 10'-0" OR
WALL HEIGHT, WHICHEVER IS
SMALLER, AND NO MORE
THAN 10' -0" FROM CORNER.
CUT EVERY OTHER
HORIZ. BAR AT JOINT
EXCEPT TOP AND
BOTTOM BARS OF WALL
6" WIDE x CONT 12 GA
GALVANIZED SHEET
METAL STRIP. TYP
WATERPROOFING
REQD AT SOIL
RETAINING
CONDITION. SEE
ARCH SPEC'S
EXTEND
TOP AND
BOT BARS
AND EVERY
OTHER
HORIZ BAR
AT JOINT
1 1/2"
1'-0" LAP
1 1/2"
(3) #4 x CONT
PAVING
GRADE SLAB
1'-0"
4"
END OF
WALL OR
JAMB
E Q
E Q
HOOK END
HOOK END
END OF
WALL OR
JAMB
4"
NOTES:
SINGLE ROW OF VERTICAL REINFORCING
VERTICAL REINFORCING EACH FACE
GROUT ALL CELLS FULL, UNLESS OTHERWISE NOTED.
CORNER CONDITIONS SAME AS 1/SE-003.
LAP SPLICE LENGTH, SEE SCHEDULE ON SE-003.
GENERAL NOTES, SEE SE-001.
1.
2.
4.
3.
/4
/4
1'-0"
V A
R
IE
S
ADD (1)#4 T&B
ADD #4 @12" OC
SLAB-ON-GRADE
PREMOLDED
EXPANSION JOINT
ALL AROUND
1'-0" TYP
MECHANICAL OR
ELECTRICAL EQUIPMENT
SEE MECH/ELEC
DRAWINGS
#4 @ 12" EACH
WAY, TOP & BOT
1" CLEAR
MAX
1'-0" COIL LOOP INSERT
C L E
A R
FILL WITH
CONTINUOUS
SEALANT AND
BACKER ROD,
TYP
CONCRETE BEAM
ELEVATIONSECTION
C L E
A R
M
IN
COIL LOOP INSERT WITH
5/8" DIA x 30" THREADED
BAR, SPACING TO MATCH
WALL VERT REINF
SOFFIT OF CONC SLAB
OR BOTTOM OF BEAM
CONCRETE BLOCK WALL
CONTINUOUS SEALANT
AND BACKER ROD EACH
SIDE SEE ARCH FOR
FIRE RATING
3" DIA x 12" RUBATEX
AROUND DOWELS
BEAM
WHERE
OCCURS
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
STRUCTURAL - TYPICAL SLAB
AND WALL DETAILS
A/E DESIGN TO DEVELOP RFP FOR
PARKING STRUCTURE
ET AME
612-165
SE301
VA NORTHERN CALIFORNIA HEALTHCARE SYSTEM
SLAB CONSTRUCTION AND CONTROL
JOINT
3/4" = 1'-0"18
EDGE OF SLAB DETAIL
3/4" = 1'-0"16
MASONRY WALL CONTROL JOINT
3/8" = 1'-0"15
TYPICAL ELEVATOR PIT DETAIL
3/4" = 1'-0"14
CURB/PAD DETAIL
3/4" = 1'-0"13
COLUMN/WALL SEPARATION PLAN
3/4" = 1'-0"12
CONSTRUCTION JOINT AT CONT
FOOTING
3/4" = 1'-0"9
THICKENED SLAB DETAIL
3/8" = 1'-0"7
TYPICAL STEPPED FOOTING DETAIL
3/4" = 1'-0"6
MASONRY WALL EXPANSION JOINT
DETAIL
3/4" = 1'-0"10
CONCRETE WALL VERTICAL
CONSTRUCTION / CONTROL JOINT
3/4" = 1'-0"5
EDGE OF SLAB DETAIL
3/4" = 1'-0"3
TYP CMU WALL REINFORCING DETAILS
3/4" = 1'-0"17
STEPPED SLAB DETAIL
3/4" = 1'-0"2
CONCRETE PAD DETAIL
3/4" = 1'-0"1
WALL PERMANENT RELEASE DETAIL
Revisions: Date:
dmelendez Typewritten text
DESIGN BUILD PROPOSAL PACKAGE
35% SCHEMATIC DESIGN (SD1)
dmelendez Typewritten text 10/11/2019 08/15/2019 crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
crollins Typewritten text 12/18/2019 crollins Typewritten text 12/18/2019 crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
CABLE RAILS
SEE 1/S-523
CONC COLUMN
BEYOND
SLAB ON
GRADE
FOOTING,
SEE PLANS
ALTERNATE HOOKS
SPREAD FOOTING
BEYOND
1/2" ASPHALT
FILLER TYP, ALL
WALLS
D E
P T
H
C L R
WIDTH
EL TOP OF FTG
SEE FOUNDATION PLAN
V A
R
IE
S
-0
T O
F L
O O
R H
E
IG
H T
#5 x 24"
24"
@ 16"
8" CONCRETE
WALL
DOWEL SIZE AND
SPACING SHALL MATCH
WALL VER REINF
WATERPROOFING
AND BACKFILL SEE
NOTE 11.C.5 ON S-001
3 1/2"
NOTE:
HORIZONTAL REINFORCING
BARS DO NOT NEED TO
EXTEND INTO CONC. COLUMNS
CONSTRUCTION SEQUENCE:
1. PLACE WALL - BRACE AS REQUIRED
PLACE LOWER GRADE SLAB
SHORE WALL AS REQUIRED
REMOVE SHORES WHEN CONCRETE
STRENGTH REACH THAT SPECIFIED
2.
3.
4.
5.
6.
PLACE UPPER GRADE SLAB
BACKFILL WALL
CABLE RAILS
SEE 1/S-523
CONC COLUMN
BEYOND
SLAB ON
GRADE
FOOTING, SEE
PLANS
ALTERNATE
HOOKS
SPREAD
FOOTING
BEYOND
8" CMU WALL WITH
#6 @ 16" VERT
AND #5 @ 16"
HORIZ
1/2" ASPHALT
FILLER TYP,
ALL WALLS
D E
P T
H
C L R
WIDTH
EL TOP OF FTG
SEE FOUNDATION PLAN
T O
V A
R
IE
S
EQ EQ
GAP
1"
EL TOP OF FTG
SEE FOUNDATION PLAN
4' - 0" 2' - 0"
/4
WATSON JEENE FW2
EXPANSION JOINT,
SEE 10/S-003
GRADE SLAB
(2) #4 CONT BEHIND
PT TENDON
PT SLAB
1/2" ASPHALT FILLER
GRADE SLAB
#5 x 24"
24"
@ 16"
WATERPROOFING & BACKFILL
SEE SOILS REPORT
12" CMU WALL
WITH #7 @ 16"
VERT AND #5 @ 16"
HORIZ
DOWELS #6 x 36 @ 16"
FOOTING, SEE PLANS
ALTERNATE HOOKS
WIDTH
D E
P T
H
EQ
EQ
2 1/2" MAX
O"
CONSTRUCTION SEQUENCE:
1. PLACE WALL - BRACE AS REQUIRED
PLACE LOWER GRADE SLAB
SHORE WALL AS REQUIRED
REMOVE SHORES WHEN CONCRETE
STRENGTH REACH THAT SPECIFIED
2.
3.
4.
5.
6.
PLACE UPPER GRADE SLAB
BACKFILL WALL
6" 3'-6"
#3@12"OC EW
#3 DOWELS @ 12"OC EW
EL TOP OF FTG
SEE FOUNDATION PLAN
GROUT CORES SOLID
PT SLAB
8" CMU WITH
#5 @ 16" VERT AND
#5 @ 16" HORIZ
3' - 0" WASH
EQ EQ
GRADE SLAB
FOOTING
SEE PLANS
WIDTH ALTERNATE HOOKS
DOWEL SIZE AND
SPACING SHALL MATCH
WALL VERT REINF
D E
P T
H
GRADE SLAB
CONT BACKER ROD
AND SEALANT EACH
SIDE
C L R
M
IN
COIL LOOP INSERT
SEE 3/S-002
RELEASE JOINT,
SEE 3/S-002
M
IN
1'-0"
M
IN
M
A X
(1)#4
#4 @ 12"OCSLAB-ON-GRADE,
SEE PLAN
#4 @ 12"OC
(2)#4
M
IN
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
STRUCTURAL - FOUNDATION
DETAILS
A/E DESIGN TO DEVELOP RFP FOR
PARKING STRUCTURE
Checker Author
612-165
SE302
VA NORTHERN CALIFORNIA HEALTHCARE SYSTEM
Revisions: Date:
3/4" = 1'-0"2
CURB AT RAMP AND WALL DETAIL
3/4" = 1'-0"3
CURB AT RAMP AND WALL DETAIL
3/4" = 1'-0"4
(LOAD BEARING ONLY) WALL/SLAB
DETAIL
3/4" = 1'-0"5
(NON LOAD BEARING) MASONRY WALL
DETAIL
3/4" = 1'-0"1
THICKENDED SLAB EDGE DETAIL
dmelendez Typewritten text
DESIGN BUILD PROPOSAL PACKAGE
35% SCHEMATIC DESIGN (SD1)
dmelendez Typewritten text 10/11/2019 08/15/2019 crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
crollins Typewritten text 12/18/2019 crollins Typewritten text 12/18/2019 crollins
ALTERNATE
HOOKS
GRADE
SLAB
WIDTH
EL TOP OF FTG
SEE FOUNDATION PLAN
CONC
FOOTING
1/2" ASPHALT FILLER
TYP ALL WALLS
GRADE SLAB
DOWEL SIZE AND
SPACING SHALL MATCH
WALL VERT REINF
WHERE OCCURS
3'-0" WASH
T Y
P
C
L R
L A
P D
E P
T H
EQ EQ
NOTE 2
N O
T E
LENGTH
W
ID
T H
PLAN VIEW
SQUARE FOOTING
5'-0"
NOTE 3
N O
T E
= FOOTING
BAND LENGTH
SEE PLAN
WIDTH (LENGTH)
PLAN VIEW
RECTANGULAR FOOTING
SECTION
MIN
D/2
MIN
D/2
DOWELS - SEE COLUMN
FOOTING SCHEDULE
ON SHEET S-610
1/2" ASPHALT FELT
AROUND COLUMN
TYPICAL
CIP CONC FOOTING -
SEE SCHEDULE FOR
SIZE AND REINF
D /2
O R
M
IN
D E
P T
H
EL TOP OF FTG
SEE PLAN
CONTRACTOR
OPTION:
FOOTING MAY BE
FORMED LEVEL
WALL FOOTING AND TIE BEAM SCHEDULE
MARK
WIDTH
(FT)
DEPTH
(FT)
LONGITUDINAL REINFORCING TRANSVERSE REINFORCING
TOP BOT
STIRRUPS
NOTES:
1. CONCRETE STRENGTH F'c = (SEE GENERAL CONCRETE NOTES)
2. LONGITUDINAL REINFORCEMENT TO PASS THRU SPREAD FOOTING/PILE CAPS/FOUNDATIONS
ADDED
REMARKS
TOP BOT ADDED
WF1 2'-0" 1'-6" (2)#4 (3)#4 #4@12"OC
SWF1 8'-0" 3'-6"
LENGTH
(FT)
CONT
60'-0"
SWF1 12'-6" 4'-0"70'-0"
RWF1 4'-0" 1'-6"CONT
RWF2 6'-0" 1'-6"CONT
COLUMN FOOTING SCHEDULE
MARK LENGTH
(FT)
WIDTH
(FT)
TOP REINFORCING
LONGITUDINAL TRANSVERSE
BOTTOM REINFORCING
REMARKS
NOTES:
1. CONCRETE STRENGTH F'c = (SEE GENERAL CONCRETE NOTES)
REINFORCING SHALL BE UNIFORMLY DISTRIBUTED WITHIN THE FOOTING.
AT RECTANGULAR FOOTINGS, A HIGHER PERCENTAGE OF THE REINFORCING SHALL BE DISTRIBUTED IN THE BAND LENGTH. FOR EXAMPLE: IF THE FOOTING IS 10'-0" x 5'-0" WITH (10)#8 AND THE DISTRIBUTION OF 60%. (6)#8 (10 BARS x 60%) SHALL BE PLACED WITHIN A 5'-0" BAND LENGTH AND (2)#8 ON EACH SIDE OF THE BAND LENGTH.
IF AN ODD NUMBER OF REINFORCING BARS OCCUR ON ONE SIDE, THE CONTRACTOR SHALL ROUND-UP TO AN
EVEN NUMBER OF BARS.
2.
3.
REINFORCING
DISTRIBUTION
LONGITUDINAL TRANSVERSE
F1
F2
F4
F5
F3
DEPTH
(FT)
9'-6"
7'-6"
12'-0"
9'-6"
10'-0"
9'-6"
7'-6"
12'-0"
9'-6"
7'-6"
2'-0"
2'-0"
2'-6"
2'-0"
2'-0"
F7
F8
F6 11'-6"
9'-0"
14'-0"
11'-6"
9'-0"
14'-0"
2'-6"
2'-0"
3'-0"
F9 11'-0" 11'-0" 2'-6"
3/4" = 1'-0"3
WALL FOOTING DETAIL
3/4" = 1'-0"2
COLUMN/FOOTING DETAIL
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
STRUCTURAL - FOUNDATION
SCHEDULES AND DETAILS
A/E DESIGN TO DEVELOP RFP FOR
PARKING STRUCTURE
ET AME
612-165
SE303
VA NORTHERN CALIFORNIA HEALTHCARE SYSTEM
Revisions: Date:
dmelendez Typewritten text 10/11/2019 08/15/2019 crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
dmelendez Typewritten text
DESIGN BUILD PROPOSAL PACKAGE
35% SCHEMATIC DESIGN (SD1)
crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
crollins Typewritten text 12/18/2019 crollins
12/18/2019
PA
P1 P2
PA.1
PA.5
P0
PRE-ENGINEERED STAIR
TYP
2'-0"
2'-0" THICK MAT
8" CMU WALL
5" THICK SLAB-
ON-GRADE
PA
P1 P2
PA.1
PA.5
P0
PRE-ENGINEERED STAIR
8" CMU WALL
5" THICK CONCRETE SLAB
PA
P1
PA.1
P0
8" CMU WALL
5" THICK CONCRETE SLAB
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
STRUCTURAL - STAIR TOWER
NO. 1 ENLARGED PLANS
A/E DESIGN TO DEVELOP RFP FOR
PARKING STRUCTURE
Checker Author
612-165
SE410
VA NORTHERN CALIFORNIA HEALTHCARE SYSTEM
SHEET NOTES
LEGEND
Revisions: Date:
1/4" = 1'-0"1
GROUND TIER PLAN
1/4" = 1'-0"2
SECOND TIER PLAN
1/4" = 1'-0"3
STAIR TOWER ROOF
DEDUCT ALTERNATE 1
DELETE ONE (1) ELEVATOR
dmelendez Typewritten text
DESIGN BUILD PROPOSAL PACKAGE
35% SCHEMATIC DESIGN (SD1)
dmelendez Typewritten text 10/11/2019 08/15/2019 crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
crollins Typewritten text 12/18/2019 crollins Typewritten text 12/18/2019 crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
DBibbs Typewritten text
REMOVE ELEVATOR #2 AND SHAFT WITH ALL
ASSOCIATED ELEVATOR EQUIPMENT AND WORK,
ACCENT RAILING TO BE RELOCATED
P23 P24P22.5
PA.1
PA.5
PRE-ENGINEERED STAIR
PA
P23 P24P22.5
PA.1
PA.5
PRE-ENGINEERED STAIR
PA
P23 P24P22.5
PA.1
PA.5
PRE-ENGINEERED STAIR
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
STRUCTURAL - STAIR TOWER
NO. 2 ENLARGED PLANS
A/E DESIGN TO DEVELOP RFP FOR
PARKING STRUCTURE
Checker Author
612-165
SE420
VA NORTHERN CALIFORNIA HEALTHCARE SYSTEM
SHEET NOTES
1/4" = 1'-0"1
FOUNDATION PLAN
1/4" = 1'-0"2
GROUND TIER PLAN
LEGEND
Revisions: Date:
1/4" = 1'-0"3
SECOND TIER PLAN
DEDUCT ALTERNATE 6
REDUCE THE NUMBER OF PARKING SPACES FROM
THE TOP LEVEL
dmelendez Typewritten text
DESIGN BUILD PROPOSAL PACKAGE
35% SCHEMATIC DESIGN (SD1)
dmelendez Typewritten text 10/11/2019 08/15/2019 crollins Typewritten text
FINAL DESIGN BUILD
PROPOSAL PACKAGE
crollins Typewritten text 12/18/2019 crollins Typewritten text 12/18/2019 crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
DBibbs Typewritten text
REMOVE ALL WORK ON THE SECOND TIER FROM
COLUMN LINE P13 TO COLUMN LINE P24, WILL
INCLUDE THE REMOVAL OF PRE-ENGINEERED STAIR
DETAIL 3/SE420
CHAIR,
TYP
CONC
BEAM,
TYP
PT TENDON, SEE
E1/SE-501
SLAB BOLSTERS TYP
TEMPERATURE
TENDONS, SEE PLANS
PT SLAB
TOP BARS,
SEE F6/SE-501
BOT BARS,
SEE F6/SE-501
#4 x CONT
TEMPERATURE AND
SLAB SUPPORT BARS
WITH 2'-0" LAP, TYP
4"
NUMBER OF BARS VARIES
CHORD BARS AT 6" OC
SPACING PER PLAN
MIN COVER SHALL BE
1.5 BAR DIAMETERS
BUT NOT LESS THAN
2" TYP T&B
CONT DRIP
STOP SEE
D1/S-501
PT TENDON
SEE E1/S-501
CHORD
STEEL
E Q
E Q
CONTRACTOR OPTION:
CHORD BARS MAY BE PLACED
BEHIND PT ANCHORS IN LIEU
OF #4 BACKUP BARS
3"
COLUMN
FACE
BEYOND
/2
6" MIN
/4
C
L R
/4
M
IN
DO NOT
ALTERNATE CAP
TIES AT EXTERIOR
BEAM
REINF, SEE PLAN
PT TENDON
ldh MIN
M A
X
W
ID
T H
O F
T E
N D
O N
S
L
IM
IT
O
F M
U L T
IP
L
E A
N C
H O
R S
6"
(2)#4 BACKUP
BARS
SLAB EDGE
ADD (1) HAIRPIN
OUTSIDE LAST ANCHOR
TYP EACH SIDE
MULTIPLE
TENDONS
#3 x t - 2"
HAIRPIN AT EVERY
ANCHOR, TYPICAL
t = SLAB THICKNESS
1'-0"
M
IN
/4
C
L R
M
IN
/4
C
L R
/2
PT SUPPORT BAR
MAY BE CUT TO
ALLOW PLACEMENT
OF CONDUIT
TOP OF SLAB
PT TENDON
ELECTRICAL CONDUIT
ABOVE BEAM TOP
REINFORCING, TYP
EXCEPT AT TOP LEVEL
BEAM TOP
REINFORCING
ELECTRICAL CONDUIT
BELOW BEAM TOP
REINFORCING AT TOP LEVEL
BEAM STIRRUP
CONDUIT CROSS-OVER SINGLE CONDUIT MULTIPLE CONDUIT
NTS
1'-6" MIN
E Q
E Q
SEE
SCHEDU
LEE
Q E
Q
SEE
SCHEDU
LE
4" NTS
OR 3" MIN
3x CONDUIT DIA
2 TOGETHER
MAX
T
B
NOTE:
CONTRACTOR TO PROVIDE 100 "Z
BARS" AT PROJECT SITE PRIOR TO
FIRST POST-TENSIONED DECK
POUR. ENGINEER WILL LOCATE AS
NECESSARY.
CONTRACTOR TO PROVIDE #4 @ 18"
OC NOTE: ADDITIONAL ROWS WILL
BE REQUIRED WHERE THERE IS
MORE THAN 5 CONDUITS
SLAB
THICKNESS
SINGLE CONDUIT
MAX DIAMETER
CONDUIT
CROSS-OVER
MAX DIAMETER
5" TO 5 1/2" 1" (2) 1/2" *
6" TO 7 1/4" 1 1/4" (2) 3/4"
> 7 1/4" 1 1/2" (2) 1"
* 3/4" PERMISSIBLE IF ANGLE OF CROSS-OVER IS GREATER THAN 45 DEGREES
2'-0"
1 1/2" 1"
E Q
E Q
INTERMEDIATE PT
ANCHORS AND POCKETS
2'-0" WIDE STRIP TRAFFIC
BEARING WATERPROOF
MEMBRANE AT ALL LEVELS
EXPOSED TO SUNLIGHT
(2) #4 x CONT AT PT ANCHORS
FIRST SLAB TENSIONED THIS SIDE
3/4" TOOLED JOINT WITH
SEALANT, SEE A3/S-003
PROVIDE #4 x 4'-0" AT
TOP SLAB REBAR SPACING
(4) #4 x CONT AT 4" OC
PT TENDON
PROVIDE CHAIRS FOR
BAR SUPPORT DURING
PLACEMENT OF FIRST SLAB
PT CONC SLAB
(SECOND SLAB)
3/4" V-GROOVE
NOTE:
SHORE FIRST SLAB UNTIL
SECOND SLAB IS STRESSED
S E
E P
L A
N
T Y
P
(1) #4 x TOP AND
BOT, TYP
12 BAR DIA
(1) #4 TOP AND BOT
BACK-UP BARS, TYP
(1) #4 x 3'-0" TOP AND
BOT DIAGONALS
INNER LAYER
C L R
TOP REINFORCING
SEE PLAN
PT TENDON
ROUGHEN JOINT
DRIP STOP
SEE D1/S-501
/4
C L R
/2
KEEP SLAB SHORED
UNTIL BEAM TENDONS
ARE TENSIONED
STAGGER STAGGER
C SPANL
EQ EQ
EQ EQ EQ EQ BOT REBAR
(EXTEND 33% OF
BARS CONT TO
COLUMNS OR
SUPPORTS)
BEAM
SUPPORT
MID-SPAN
SINGLE BAY
BEAM
SUPPORT
BEAM
SUPPORT
BEAM
SUPPORT
BEAM
SUPPORT
MID-SPAN
INTERIOR BAY
MID-SPAN
END BAY
AT TOP LEVEL ONLY
EXTEND 25% OF
BARS CONTINUOUS
TO COLUMNS OR
SUPPORTS
TOP REBAR AT
SUPPORT, TYP
BOT REBAR
(EXTEND 25% OF
BARS CONT TO
COLUMNS OR
SUPPORTS)
BOT REBAR
(EXTEND 25% OF
BARS CONT TO
COLUMNS OR
SUPPORTS)
NOTE:
UNLESS NOTED OTHERWISE, STAGGER ALL
BARS 1'-0" AS SHOWN.
(WHERE (2) BARS
ARE REQUIRED)
MAX EFFECTIVE
OPENING LENGTH
REINFORCING DIAGONALS
(1) #5 EACH SIDE NONE REQUIRED1'-0" TO 1'-6"
(1) #5 TOP AND
BOT EACH SIDE (1) #5 x 3'-0"1'-6" TO 2'-6"
(2) #5 TOP AND
BOT EACH SIDE
(1) #5 x 3'-0"2'-6" TO 6'-0"
4" CLR, TYP
MIN,TYP
2'-0"
1" CLR
NOTES:
1. ALL OPENINGS WITH A DIMENSION OF 1'-0" OR GREATER SHALL BE
TRIMMED AS SHOWN.
2. THIS REINFORCING IS IN ADDITION TO ANY REINFORCING
INDICATED ON THE PLANS.
C L R
/2
MIN
6"
C L R
/2
2" CLR
T Y
P4
SLAB EDGE
STEEL PIPE
INSERT (SCHED
40) IS REQUIRED
WHEN SLAB
PENETRATION IS
WITHIN BEARING
CONE OF TENDON
ANCHOR
PENETRATIONS
FARTHER THAN 1.5
TIMES THE
PENETRATIONS
DIAMETER OR
WIDTH, BUT NOT
LESS THAN 1'-6" MIN
FROM ANCHOR, DO
NOT REQUIRE STEEL
PIPE INSERTS
W
.5
D O
R
.5 W
'-6
M
IN
D
NOTE:
ANY PENETRATION WITH DIMENSIONS GREATER THAN 1'-0"
MUST HAVE TRIM REINFORCEMENT AS DETAIL 8/SE-501
OPENING
POST-TENSIONING
STRANDS
OPENING
REINFORCING PER
DETAIL C5/SE-501
MIN, TYP
1'-0"
STRAIGHT IN THIS AREA
STRANDS SHALL BE
C L R
4'-0"
DOWN DRAIN
SEE PLUMBING
DRAWINGS
FLOOR (ROOF) DRAIN
LOCATE DRAINS AT LOW
ELEVATIONS ON FLOORSOVERFLOW
DRAIN
BUMP UP CONCRETE SURFACE
AROUND OVERFLOW ON UPHILL
AND 2 SIDES AROUND DRAIN
SLOPESLOPE
NOTE:
COORDINATE LOCATION WITH
ARCHITECTURAL/PLUMBING
P/T DECK
6" CONCRETE CURB
W/#4 @ 12"OC EW
SEE PLAN
6" Ø STD PIPE
NOTE: SLAB MAY
SLOPE SET PIPE
PLUMB VERTICALLY
1/4" CAP PLATE
EMBED PLATE
1/2" x 12SQ W/
(4) 1/2"Ø x 3
1/2" HSA
CL
V E
R
IF
Y W
A
R C
H
(6) #4 x 4'-0" EW
1/8
GRIND
SMOOTH
3/16
PT SLAB
PT REINF
WHERE OCCURS
1'-0" TAIL TYP
SQUARE
1'-6"
SLAB-ON-GRADE
6" Ø STD PIPE
NOTE: SLAB MAY SLOPE SET
PIPE PLUMB VERTICALLY
1/4" CAP PLATE
EMBED PLATE 1/2"
x 12SQ W/ (4) 1/2"Ø x 3 1/2" HSA
CL
(6) #4 x 4'-0" EW
1/8
GRIND
SMOOTH
3/16
N T
S
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
STRUCTURAL - TYPICAL SLAB
DETAILS
A/E DESIGN TO DEVELOP RFP FOR
PARKING STRUCTURE
ET AME
612-165
SE501
VA NORTHERN CALIFORNIA HEALTHCARE SYSTEM
3/4" = 1'-0"16
TENDON/REBAR SUPPORT AT SLAB
DETAIL
1 1/2" = 1'-0"15
CHORD STEEL PLACEMENT
3/4" = 1'-0"14
DOWNTURNED BEAM -
EXTERIOR SLAB DETAIL
3/4" = 1'-0"12
MULTIPLE TENDON END ANCHORAGE
DETAIL
3" = 1'-0"13
EMBEDDED CONDUIT IN SLAB AND
BEAM
3/4" = 1'-0"10
SLAB CONSTRUCTION JOINT
PERPENDICULAR TO SLAB SPAN
3/4" = 1'-0"4
SLAB RE-ENTRANT CORNER DETAIL
3/4" = 1'-0"9
EXTERIOR SLAB DETAIL
3/4" = 1'-0"6
REBAR STAGGER DETAIL
ONE-WAY SLAB AND BEAM
1/4" = 1'-0"8
SLAB OPENING DETAIL
3/4" = 1'-0"2
OPENING AT TENDON ANCHORAGE
3/4" = 1'-0"11
TENDON LAYOUT AT OPENING
3/4" = 1'-0"5
FLOOR DRAIN
3/4" = 1'-0"3
CONCRETE CURB DETAIL
1" = 1'-0"7
PIPE BOLLARD AT PT SLAB
1" = 1'-0"1
PIPE BOLLARD AT SLAB-ON-GRADE
Revisions: Date:
dmelendez Typewritten text
DESIGN BUILD PROPOSAL PACKAGE
35% SCHEMATIC DESIGN (SD1)
dmelendez Typewritten text 10/11/2019 08/15/2019 crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
crollins Typewritten text 12/18/2019 crollins Typewritten text 12/18/2019 crollins
6" +/- 1'-6"
9" +/-
#3 x t - 2"
HAIRPIN AT EVERY
ANCHOR, TYPICAL
t = SLAB THICKNESS
1'-0"
TEMPERATURE
TENDONS
(2)#4 BACKUP
BARS
POUR STRIP
T E
N D
O N
S P
A C
IN
G
P
E R
P E
R S
H O
P
D R
A W
IN
G
S
SLAB EDGE
LOCATE 1ST
TENDON ABOUT 6"
FROM SLAB EDGE
/2
EDGE OF SLAB
3/4" CHAMFER
OPTIONAL
SHAPE
SLAB SOFFIT4" +/-
E Q
E Q
(2)#4 x CONT
BACK-UP BARS
GROMMETS AT
STRESSING END
ONLY
TOOLED EDGE
CHAMFER
CAP WITH
WATER TIGHT
CONNECTION
TO ANCHOR
PT CABLE (TYP)
SHEATHING (TYP)
DEAD END ANCHOR
3'-6" OC MAX
ANCHOR PLACEMENT:
SLAB LESS THAN 8" THICK,
POSITION HEAD
HORIZONTALLY. SLAB 8"
AND THICKER, HEADS MAY
BE POSITIONED VERTICALLY
OR HORIZONTALLY.
2 1/2" MIN CONT DRIP
STOP SEE
D1/S-501
SUPPORT/
TEMPERATURE BAR
1" CLR 1" CLR
CAP WITH WATER
TIGHT CONNECTION
TO ANCHOR
LARGE POCKET
FORMER
GROMMET
3/4" CLR
CORROSION
PROTECTION
SLEEVE CPS TYP
WATER-TIGHT
SEAL TYPICAL
STRESSING END ANCHOR
NO DEVIATION
FROM THIS DETAIL
NOTES:
1. SEE SPECIFICATIONS DIVISION 3 FOR ADDITIONAL REQUIREMENTS.
2. MINIMUM CONCRETE COVER AT ANCHOR SHALL BE 1/4" GREATER THAN REQUIRED
AWAY FROM THE ANCHOR OR 1 1/4" WHICHEVER IS GREATER.
3. ANCHORS IN THE SLAB SHALL BE SPACED AT LEAST 8" ON CENTER AND POSITIONED
HORIZONTALLY, WHERE THE SLAB IS LESS THAN 8" THICK. ANCHORS MAY BE
POSITIONED AT 3" ON CENTER WHERE THE SLAB IS 8" THICK AND GREATER.
4. ANCHORING SYSTEM SHALL BE AN INCAPSULATED SYSTEM PER ICC REPORT
NO. ESR-2515 OR APPROVED EQUAL.
1 1/2"
3'-8" (SEE NOTES)
2'-6" LAP UNLESS NOTED
1 1/2"
CHORD STEEL LAP -
SEE SCHEDULE ON
TYPICAL LEVEL
CUT STRAND AND
CAP ANCHORS PER
SPEC 03370
POUR STRIP - PLACE
NOT LESS THAN 28 DAYS
AFTER STRESSING SLAB
PT TENDONS
3/4" TOOLED JOINT WITH
SEALANT BOTH SIDES OF
POUR STRIP SEE A3/S-004
(3)#4 TOP AND BOTTOM
SEE NOTE 4
SEE NOTE 4
SLAB REINFORCING SEE
PLANS EXTEND ADJACENT
TOP BARS INTO POUR STRIP
(2)#4 x CONT 1" CLR
OF PT ANCHOR
TEMPERATURE TENDONS,
SEE F3/SE-501
PT TENDON
1/2" V-GROOVE
BOTH SIDES OF
POUR STRIP
SEE NOTE 3
TO COLUMN LINETO COLUMN LINE
PROVIDE TRAFFIC BEARING
WATERPROOF MEMBRANE AT
ALL LEVELS EXPOSED TO
SUNLIGHT EXTEND 1'-0" EACH
SIDE OF POUR STRIP
NOTES:
1. AT POUR STRIP, USE SAME CONRETE AS USED FOR FLOORS.
2. AT TOP OF POUR STRIP, PROVIDE 3/4" DEEP TOOLED JOINTS, FILLED
WITH SEALANT, IN TRANSVERSE DIRECTION AT 4'-0" ON CENTER.
3. TOP AND BOTTOM LONGITUDINAL BARS IN POUR STRIP TO BE CHAIRED
DURING PLACEMENT OF ADJACENT SLABS.
4. SUPPORT EDGES AND BACKSPAN BAYS TO MAINTAIN ALIGNMENT AT POUR
STRIPS UNTIL 14 DAYS AFTER CLOSURE HAS BEEN PLACED.
5. PROVIDE 3/4" HOLES AT 2'-0" ON CENTER IN PLYWOOD FORMS TO PREVENT
WATER FROM FILLING JOINT PRIOR TO PLACING CONCRETE.
6. INCREASE THE WIDTH OF THE CLOSURE POUR TO PROVIDE THE LAP LENGTH
INDICATED FOR THE CHORD REINFORCING STEEL WITHIN THE CLOSURE POUR,
SHOWN ON THE TYPICAL LEVEL PLAN. LAP SPLICES FOR CHORD STEEL
SHALL NOT EXTEND FROM ONE POUR INTO AN ADJACENT POUR.
DELAY TIME*
LEVEL 2 112 DAYS
LEVEL 3 84 DAYS
LEVEL 4 56 DAYS
LEVEL 5 28 DAYS
* AFTER LAST POUR ON
LEVEL
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
STRUCTURAL - TYPICAL SLAB
DETAILS
A/E DESIGN TO DEVELOP RFP FOR
PARKING STRUCTURE
Checker Author
612-165
SE502
VA NORTHERN CALIFORNIA HEALTHCARE SYSTEM
3/4" = 1'-0"1
TENDON PLACEMENT AT CORNER/SLAB
EDGE
3" = 1'-0"3
DRIP STOP DETAIL
3/4" = 1'-0"4
SLAB EDGE/TENDON ANCHORAGE
DETAIL
3/4" = 1'-0"2
SLAB POUR STRIP DETAIL
Revisions: Date:
dmelendez Typewritten text
DESIGN BUILD PROPOSAL PACKAGE
35% SCHEMATIC DESIGN (SD1)
dmelendez Typewritten text 10/11/2019 08/15/2019 crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
crollins Typewritten text 12/18/2019 crollins Typewritten text 12/18/2019 crollins
GIRDER
PLACE GIRDER
TENDONS IN
BUNDLES OF (5) MAX
ADDED STIRRUPS,
SEE BEAM NOTE 5
ON SE-620
2"
BEAM INTERSECTION
3 @ 2" EACH SIDE OF
3 @ 6"
S E
E S
C H
E D
U L E
E Q
E Q
1'-3" LAP
3'-8" 1'-6"
C L R
GIRDER
COLUMN
GIRDER
TENDONS
#4 @ 16"
(4 SIDES)
2x CONT KEY
AT SLAB
#4 AT 12" OC
EACH WAY
WIDTHWIDTH
O N
S -6
L A
P
S E
E S
C H
E D
U L E
O N
S -6
L A
P
S E
E S
C H
E D
U L E
BEAM WIDTH
COLUMN DIMENSION
LESS THAN
BEAM WIDTH
COLUMN DIMENSION
GREATER THAN
3 TIES WITHIN
BEAM
3 TIES WITHIN
BEAM
C G
S T
B
/2
C L R
(5) BEAM STIRRUPS
AT 3" OC
(2)#4 x (PROVIDE
(4) WHEN ADDED PT
FORCE EXCEEDS 397k)
10"
DEAD END ANCHOR SEE
BEAM NOTE 7 ON SE-620
#4 x EACH FACE
10"
DEAD ENDS
COLUMN ABOVE
WHERE OCCURS
#4x T&B
AND BETWEEN
EACH ROW OF
ANCHORS
W
ID
T H
F
B
A
M
L
S S
14" S
E E
S C
H E
D U
L E
GIRDER
1" MIN CLR
1 1/2" CLR
/2
C L R
SEE BEAM SCHEDULE
BOTTOM BARS SEE
BEAM SCHEDULE
PT TENDON
AT MID-SPAN
T Y
P
/2
C L R
INDICATES PLACEMENT
SEQUENCE OF BOTTOM
REBAR. (TYPICAL AT
MID-SPAN CONDITION)
C L R
/2
TOP BARS SEE
BEAM SCHEDULE
INDICATES PLACEMENT
SEQUENCE OF TOP
REBAR. (TYPICAL AT
SUPPORT CONDITION)
SIDE BARS
SEE SE-620
S E
E B
E A
M S
C H
E D
U L E
AT EXTERIOR BEAMS
PLACE 135° HOOK AT
OUTSIDE FACE
NOTES:
1. FOR REBAR, SEE BEAM SCHEDULE ON SE-620.
ALTERNATE CAP TIE
STIRRUPS SEE
BEAM SCHEDULE FOR
SIZE AND SPACING
SIDE BARS
SEE S-620
INDICATES
PLACEMENT
SEQUENCE OF
BOTTOM REBAR
(TYPICAL AT MID-
SPAN CONDITION)
/2
C L R
1 1/2" CLR
C L R
T Y
P
/2
SEE BEAM SCHEDULE
CLR
1" MIN
TOP BARS, SEE SCHEDULE
INDICATES PLACEMENT
SEQUENCE OF TOP
REBAR. (TYPICAL AT
SUPPORT CONDITION)
BOTTOM BARS, SEE
BEAM SCHEDULE
PT TENDON AT MID-SPAN
1 2
S E
E B
E A
M S
C H
E D
U L E
NOTES:
1. FOR REBAR, SEE BEAM SCHEDULE ON S-620.
/2
C
L R
1 1/2" CLR
SEE BEAM SCHEDULE
S E
E B
E A
M S
C H
E D
U L
EALLOW 3/4" SPACING
BETWEEN ANCHORS TO
INSTALL COLUMN TIES
SIDE BARS SEE S-620
INDICATES PLACEMENT
SEQUENCE OF BOTTOM
REBAR. (TYPICAL AT
MID-SPAN CONDITION)
1 2
5 6
STIRRUPS SEE
BEAM SCHEDULE
FOR SIZE AND
SPACING
INDICATES PLACEMENT
SEQUENCE OF TOP
REBAR. (TYPICAL AT
SUPPORT CONDITION)
NOTES:
1. FOR REBAR, SEE BEAM SCHEDULE ON S-620.
2. THIS DETAIL REPRESENTS REBAR PLACEMENT AT END
OF BEAM AT POST-TENSION ANCHORS.
T Y
P
/2
C
L R
T Y
P
/2
C
L R
STIRRUPS SEE
BEAM SCHEDULE
FOR SIZE AND
SPACING
SEE BEAM SCHEDULE
S E
E B
E A
M S
C H
E D
U L E
C L R
/2
1 1/2" CLR
2" MIN CLR BETWEEN
REBAR AND TENDONS
BOTTOM BAR x
CONT SEE BEAM
SCHEDULE
BOTTOM BAR x
CONT SEE BEAM
SCHEDULE
INDICATES PLACEMENT
SEQUENCE OF BOTTOM
REBAR (TYPICAL AT
MID-SPAN CONDITION)
ALTERNATE CAP
TIE EXCEPT AT
EXTERIOR GIRDER
TOP BARS,
SEE SCHEDULE
INDICATES PLACEMENT
SEQUENCE OF TOP
REBAR (TYPICAL AT
SUPPORT CONDITION)
SIDE BARS,
SEE SE-620
3 4 2
NOTES:
1. FOR REBAR, SEE BEAM SCHEDULE ON S-620.
T Y
P
/2
C
L R
4 3 5
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
STRUCTURAL - DETAILS A/E DESIGN TO DEVELOP RFP FOR
PARKING STRUCTURE
ET AME
612-165
SE520
VA NORTHERN CALIFORNIA HEALTHCARE SYSTEM
3/4" = 1'-0"7
BEAM SECTION
NON-DUCTILE BEAM @ GIRDER
3/4" = 1'-0"9
TEMPORARY SLAB BLOCKOUT DETAIL
(USE WHEN NEEDED)
3/4" = 1'-0"5
DISCONTINUOUS COLUMN DETAIL
3/4" = 1'-0"14
BEAM DETAIL AT INTERMEDIATE
ANCHORS
3/4" = 1'-0"15
BEAM SECTION
NON-DUCTILE BEAM/GIRDER @
COLUMN
1 1/2" = 1'-0"16
EXTERIOR BEAM SECTION
1 1/2" = 1'-0"12
INTERIOR BEAM SECTION
1 1/2" = 1'-0"8
INTERIOR BEAM SECTION AT PT
ANCHORS
1 1/2" = 1'-0"4
GIRDER SECTION
Revisions: Date:
dmelendez Typewritten text
DESIGN BUILD PROPOSAL PACKAGE
35% SCHEMATIC DESIGN (SD1)
dmelendez Typewritten text 10/11/2019 08/15/2019 crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
crollins Typewritten text 12/18/2019 crollins Typewritten text 12/18/2019 crollins
TYP
3" ±
ALLOW 3/4"
SPACING
BETWEEN
ANCHORS TO
INSTALL
COLUMN TIES
BETWEEN
ANCHORS
NON SHRINK
NO STAIN
GROUT AT
STRESSING
END ONLY
CIP COLUMN
CONSTRUCTION JOINT
PT BEAM
TOP LEVEL
2" 2
CIP COLUMN
CONSTRUCTION
JOINT
ALLOW 3/4"
SPACING BETWEEN
ANCHORS TO
INSTALL COLUMN
TIES BETWEEN
ANCHORS
NON SHRINK
NO STAIN GROUT
AT STRESSING
END ONLY
ADD 3 BEAM
STIRRUPS
24" @ 8" OC ±
SEE NOTE 11
SUPPORT
BARS TYP
PT BEAM 6
PT STRAND
PT BEAM
CIP COLUMN
SEE NOTE 11
STD HOOK
PT STRAND
PT BEAM
CIP COLUMN
TOP LEVEL
2"
ADD 3 BEAM
STIRRUPS
24" @ 8" OC ±
TYP
3" ±
CONSTRUCTION JOINT
CONNECT STRAND
THROUGH COLUMN
(MINIMUM (3) STRANDS)
(1)#8 x 10'-0" EF
AT CONSTRUCTION JOINTS
ANCHORS AND (2) 6" x 1 1/2' x 12"
SHEAR KEY AND CJ
ONLY IF UPPER BEAM IS POURED FIRST
CONSTRUCTION JOINT
EXTENDED UPPER
BEAM BOTTOM
REINFORCEMENT AND
LOWER BEAM TOP
REINFORCEMENT 5'-0"
IN ADJACENT BEAM
ANCHORS AND
(2) 6" x 1 1/2" x 12"
SHEAR KEY AND CJ
ONLY IF LOWER
BEAM IS POURED
FIRST
TYP
3" ±
ADD (1)#8 x 7'-0" EF AT
OPTIONAL CONSTRUCTION
JOINT
PT BEAM
OPTIONAL CONSTRUCTION
JOINT, PROVIDE (2) 6" x 1 1/2" x 12" SHEAR KEYS
PVC SLEEVE FOR
TENDONS AT OPTIONAL
CONSTRUCTION JOINT V
A R
IE
S
CIP COLUMN
PT BEAM
CONSTRUCTION
JOINT, TYP
OPTIONAL
CONSTRUCTION
JOINT
D
Z O
N E
B
A D
A A
TOP OF
FOOTING
B E
A M
D E
P T
H
H
F L O
O R
H E
IG
H
T
T H
IS
S
H E
E T
L A
P S
E E
S C
H E
D U
L E
B Z
O N
E Z
O N
E C
Z O
N E
B Z
O N
E C
TYPICAL COLUMN RAMP COLUMN AT SPLIT
F U
L L
H E
IG
H
T
Z O
N E
B
TOP OF
FOOTING
A
A = H/6, 18" OR MAXIMUM COLUMN DIMENSION
D = BEAM DEPTH, SEE SCHEDULE ON S-620
TIE SPACING WITHIN ZONE B SHALL SATISFY ACI 18.7.5.3
TIES SPACING WITH ZONE C SHALL BE AT 6" OC OR 6 TIMES THE
DIAMETER OF THE LONGITUDINAL BARS, WHICHEVER IS SMALLER
PER ACI 18.14.3.2
LEVEL 3
LEVEL 2
RAMP
RAMP
TOP OF COLUMNSEE NOTE 11
MARK
SIZE
CAST IN PLACE COLUMN SCHEDULE
SECOND
GROUND
BASEMENT
TOP OF FOOTING
DOWELS
VERTICAL
ZONE B TIES
ZONE C TIES
VERTICAL
ZONE B TIES
ZONE C TIES
VERTICAL
ZONE B TIES
ZONE C TIES
SEE
NOTE 11
SEE
NOTE 11
C1
24" x 24"
C2
24" x 24"
C3
24" x 36"
C4 C5
SEE
NOTE 11
SEE
NOTE 11
SEE
NOTE 11
24" x 24"
C6
SEE
NOTE 11
C7
SEE
NOTE 11
24" x 24"24" x 24" 24" x 36"
DC1
SEE
NOTE 11
24" x 36"
DC2
SEE
NOTE 11
24" x 36"
BC1
SEE
NOTE 11
24" x 24"
MINIMUM COLUMN REBAR LAP LENGTH
FOR GRAVITY LOAD COLUMNS (inches)
TYPE
DESCRIPTION
BAR SIZE
#3 #4 #5 #6 #7 #8
#10 #11
#14 and #18
#9
VERTICAL LAP SPLICE
4000 5000 6000 7000 8000
MECHANICAL CONNECTION
REQUIRED
BASED ON ACI 318-14
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
STRUCTURAL - COLUMN
SCHEDULE AND DETAILS
A/E DESIGN TO DEVELOP RFP FOR
PARKING STRUCTURE
ET AME
612-165
SE610
VA NORTHERN CALIFORNIA HEALTHCARE SYSTEM
3/4" = 1'-0"7
EXTERIOR BEAM / COLUMN DETAIL
3/4" = 1'-0"8
EXTERIOR BEAM / COLUMN DETAIL
3/4" = 1'-0"5
INTERIOR BEAM / COLUMN DETAIL
3/4" = 1'-0"6
INTERIOR BEAM / COLUMN DETAIL
3/4" = 1'-0"4
INTERIOR BEAM / COLUMN DETAIL
3/4" = 1'-0"1
INTERIOR BEAM / COLUMN DETAIL
3/4" = 1'-0"9
COLUMN TIE SPACING DETAILS
SHEET NOTES:
1. SEE FOUNDATION PLAN FOR COLUMN DESIGNATION.
2. ALL COLUMNS ARE CENTERED ON THE GRID LINES, UNLESS NOTED.
3. OFFSET BEND LONGITUDINAL BARS SHALL CONFORM TO THE
FOLLOWING:
A. SLOPE OF INCLINED PORTION OF AN OFFSET BAR WITH THE AXIS
OF THE COLUMN SHALL NOT EXCEED 1 IN 6.
B. PORTIONS OF THE BAR ABOVE AND BELOW THE OFFSET SHALL
BE PARALLEL WITH THE COLUMN AXIS.
C. OFFSET BARS SHALL BE BENT BEFORE PLACEMENT IN THE FORMS.
D. WHERE A COLUMN FACE IS OFFSET MORE THEN THREE (3) INCHES,
LONGITUDINAL BARS SHALL NOT BE OFFSET BENT. SEPARATE
DOWELS, LAP SPLICED WITH THE LONGITUDINAL BARS ADJACENT
TO THE OFFSET COLUMN FACE, SHALL BE PROVIDED.
4. MINIMUM COMPRESSION LAP IS 30 BAR DIAMETERS OR VALUE
SHOWN IN COLUMN SCHEDULE, WHICHEVER IS LARGER.
5. MINIMUM LAP FOR DUCTILE FRAME COLUMNS ARE AS SHOWN ON
SHEET S-710.
6. NOT USED.
7. CONTRACTOR MAY USE A MECHANICAL REBAR SPLICE IN LIEU OF
THE LAP
SPLICE INDICATED. MECHANICAL SPLICE MUST DEVELOP A MINIMUM
CAPACITY EQUAL TO 125% OF THE BAR YIELD STRENGTH IN NON-
HINGING ZONE (TYPE I COUPLER) MECHANICAL SPLICE MUST
DEVELOP THE ULTIMATE STRENGTH OF THE BAR IF USED IN HINGING
ZONE (TYPE II COUPLER)
8. NOT USED.
9. SEE DETAIL 1/S-610 FOR LAP SPLICE LOCATIONS AT RAMP COLUMNS,
UNLESS NOTED.
10.NOT USED
11.WHERE COLUMNS EXTEND ABOVE THE TOP LEVEL, (TO SUPPORT
EQUIPMENT) EXTEND ALL VERTICAL BARS, AND TIES AT 6" ON
CENTER. ADD (3) TIES AT 2" ON CENTER AT THE TOP OF THE
EXTENDED COLUMN. REFER TO ELECTRICAL AND MECHANICAL
DRAWINGS FOR EMBEDDED ITEMS, PRIOR TO POURING CONCRETE.
Revisions: Date:
dmelendez Typewritten text
DESIGN BUILD PROPOSAL PACKAGE
35% SCHEMATIC DESIGN (SD1)
dmelendez Typewritten text 10/11/2019 08/15/2019 crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
crollins Typewritten text 12/18/2019 crollins Typewritten text 12/18/2019 crollins
MULTIPLE SPAN BEAM
SINGLE SPAN BEAM
D E
P T
H
D
ABOVE TENDONS
8'-0" MIN
BEAM /GIRDER
BEAM /GIRDER2
/3 D
/3
D
POST-TENSION
CABLES TYP
SLEEVE FOR
PIPING, TYP
2'-0" MIN 8'-0" MIN
12'-0" MIN
8'-0" MAX 8'-0" MAX
/5
D
/5 D
BEAM
DEPTH
MAX SLEEVE
SIZE
LESS THAN 24"
25" TO 27"
28" TO 30"
31" TO 36"
NO HOLES*
6" OD
8" OD
10" OD
OD = OUTSIDE DIAMETER
* WITH OUT PERMISSION FROM
STRUCTURAL ENGINEER
ABOVE TENDONS
8'-0" MIN
/3
D
/3 D
NOTE:
COORDINATE EXACT NUMBER, SIZES AND LOCATION OF
SLEEVES WITH STRUCTURAL ENGINEER. PLACE SLEEVES
WHERE REQUIRED TO CLEAR POST-TENSIONED CABLES
AND REINFORCING STEEL.
CONT BAR T&B
SEE BEAM
SCHEDULE
FOR REINF
ADD (1)#6 x 4'-0" T&B
EACH SIDE, HORIZ
ADD (3)#4
STIRRUPS AT 3" OC
EACH SIDE, VERT
NOTE:
NO REQUIREMENTS FOR
HOLES LESS THAN 3" DIA
S E
E
/S E
5" DIA MAX HOLE THROUGH BEAM. SEE
MECHANICAL AND ELECTRICAL
DRAWINGS FOR LOCATIONS AND SIZE
HOLES 3" DIA TO 5" DIA
ADD #4 STIRRUPS
@ 3" OC T&B
SEE BEAM ELEV
FOR REINF
ADD (2)#7 x 5'-0" T&B
EACH SIDE, HORIZ
HOLE PENETRATION 5" DIA TO 10" DIA
MAX. REVIEW EACH LOCATION WITH
ENGINEER. FOR HOLES SMALLER
THAN 5" DIA SEE 3/SE620
S E
E
/S E
CONT BAR T&B
ADD (3)#4
STIRRUPS @ 3" OC
EACH SIDE, VERT
HOLES 5" DIA TO 10" DIA
C
2"
SEE SCHEDULE
STIRRUP SPACING 3"
A
L = SEE PLAN
STANDARD HOOK
T&B, WHERE NO
BACKSPAN OCCURS
ADJACENT BEAM
PT CONCRETE BEAM TYPE V
TRa
BRa
PARABOLIC
PROFILE CENTROID
OF PT TENDON
Fe = SEE SCHEDULE
PT CONCRETE GIRDER TYPE I
A
TYP
2" CLEAR
2" STIRRUP SPACING SEE SCHEDULE 2"
TRa
BRa
TRb TRc
(2'-6" MIN) TYP
SEE SCHEDULE
S T
IR
R
U P
T Y
P
/2
C
L E
A R
T O BRb BRc
NOTE 5 Fe = SEE SCHEDULE
PARABOLIC PROFILE
LOW POINT AT BEAM
INTERSECTION
2'-6" LAP TYP
L/4L/4
SEE PLAN SEE PLAN
L = SEE PLAN
C
9" EXTENSION
PT CONCRETE BEAM TYPE I
A
2" STIRRUP SPACING SEE SCHEDULE 2"
TYP
2" CLEAR TRa WITH
STD HOOK
TRb
PARABOLIC PROFILE
CENTROID
OF PT TENDON
Fe = SEE SCHEDULE
BRa
(2'-6" MIN) TYP
SEE SCHEDULE
S T
IR
R
U P
T Y
P
/2
C L E
A R
T OBRb BRc
TYP
2'-6" LAP
L/4
B C
L/12
L/12
I.P. I.P.
TRc WITH
STD HOOK
L/4
0.5L
BEAM MID-SPAN
L = SEE PLAN
PROVIDE 9"
EXTENSION
AT GIRDERS
TYP
2" CLEAR TRa WITH
STD HOOK
BRa
TRb
PARABOLIC PROFILE
CENTROID
OF PT TENDON
Fe = SEE SCHEDULE TYP
2'-6" LAP
L/4
TRc
C
BRc BRb
PROVIDE 9"
EXTENSION
AT GIRDERS
L/4
BEAM MID-SPAN
L = SEE PLAN
A
I.P. I.P.
L/12
(2'-6" MIN) TYP
SEE SCHEDULE
L/12
B
S T
IR
R
U P
T Y
P
/2
C L E
A R
T O
2" STIRRUP SPACING-SEE SCHEDULE 2"
PT CONCRETE BEAM TYPE II
TRb TRc
BRc BRb
TRa
BRa
I.P. I.P.
L/4
0.5L
BEAM MID-SPAN
L = SEE PLAN
(2'-6" MIN) TYP
SEE SCHEDULE
STIRRUP SPACING-SEE SCHEDULE 2"
PT CONCRETE BEAM TYPE VI
L/4
TYP
2'-6" LAP
L/12
L/12
B
S T
IR
R
U P
T
Y P
/2
C L E
A R
T O
PARABOLIC PROFILE
CENTROID OF PT TENDON
Fe = SEE SCHEDULE
C
TYP
2" CLEAR
A
STD HOOK
TRa WITH
STD HOOK
BRa
L/4
0.5L
BEAM MID-SPAN
L = SEE PLAN
L/12
2" STIRRUP SPACING-SEE SCHEDULE 2"
L/4
(2'-6" MIN) TYP
SEE SCHEDULE
PARABOLIC PROFILE
CENTROID OF PT
TENDON
Fe = SEE SCHEDULE
TRb
BRb BRc
TRc WITH
STD HOOK
PT CONCRETE BEAM TYPE IV
B
S T
IR
R
U P
T Y
P
/2
C L E
A R
T O
C
L/12
L/4
TYP
2'-6" LAP
L/4
I.P. I.P.
I.P.
15'-0".
A
TRb
TRc
BRc BRb
TRa
BRa
I.P. I.P.
L/4
0.5L
BEAM MID-SPAN
L = SEE PLAN
(2'-6" MIN) TYP
SEE SCHEDULE
2" STIRRUP SPACING-SEE SCHEDULE 2"
PT CONCRETE BEAM TYPE III
L/4
TYP
2'-6" LAP
L/12
L/12
B
S T
IR
R
U P
T
Y P
/2
C L E
A R
T O
PARABOLIC PROFILE
CENTROID OF PT
TENDON
Fe = SEE SCHEDULE
A C
SE610
SE610
SE610
SE610
SE610
SE610
BEAM SECTION "A"
BEAM/GIRDER SECTION "C" UPTURN BEAM SECTION "D"
GIRDER SECTION "B"
SLOPE OCCURS
AT RAMP BEAMS
ONLY
" C
L R
TOP BARS, SEE DETAIL
E3/S-520 FOR ADDITIONAL
INFORMATION
SLOPE SIDES
AT INTERIOR
BEAMS ONLY
(2) #4
CONT,
UNO
S C
H E
D
C G
S S
E E
CONT CHAIR
BOLSTERS
BOTTOM BARS
PT TENDONS
#4 SUPPORT BARS
AT 4'-0" OC, MAX
D
3/4" W 3/4"
SLAB
EXTENSION
WHERE SHOWN.
EXTEND SLAB
PT AND REINF
TO EDGE
OF SLAB
D
W
4 1/2" MIN SEE SLAB
PROFILE
(2) #4 CONT.
UNO
STRAIGHT AT
PERIMETER
D
W
EDGE OF SLAB
WHERE OCCURS
HOOK BARS
AT EDGE OF SLAB
(3) #5 CONT
EACH FACE UNO
W
1/2" COLUMN WIDTH
(3) #5
CONT, EF
P T
A N
C H
O R
M
IN
C O
V E
R O
V E
R
KEEP SLAB SHORED
UNTIL BEAM TENDONS
HAVE BEEN TENSIONED
CURB WHERE
OCCURS
WASH WHERE
OCCURS
SEE SLAB
PROFILE
MARK
T Y
P E
S E
C T
IO
N
W D
SIZE
(INCHES)
N U
M B
E R
O F
S T
R A
N D
S
PT
FORCE
Fe
(KIPS)
TENDON
LOCATION
(INCHES)
A B C
CONCRETE BEAM AND GIRDER SCHEDULE
TRa TRb TRc
TOP REINFORCING
BOTTOM
REINFORCING
BRa BRb BRc
#4 STIRRUPS UN
SPACING EACH END, UN
REMARKS
(SEE BEAM AND GIRDER
NOTES ON THIS SHEET.)
D
REINFORCEMENT
BEAM AND GIRDER NOTES:
1. Fe = MINIMUM EFFECTIVE FORCE AFTER LOSSES. Fe IS BASED ON 1/2" DIA., 270 ksi LOW RELAXATION STRANDS. CONCRETE RELEASE
STRENGTH AT THE TIME OF POST-TENSIONING SHALL BE 3000 P.S.I.
THE MINIMUM NUMBER OF STRANDS PER BEAM MUST BE BASED ON
Fe = 26.8 KIPS/STRAND.
2. I.P. = INFLECTION POINT, CG = CENTER GRAVITY OF STRAND
3. SEE MECHANICAL, ELECTRICAL AND FIRE PROTECTION DRAWINGS
FOR LOCATION OF BEAM PENETRATIONS AND EXACT SIZE AND
LOCATION OF CONDUITS.
4. BEAM REINFORCEMENT SHALL NOT BE USED TO SUPPORT SLAB
TENDONS.
5. WHERE A BEAM FRAMES INTO ANOTHER BEAM OR A GIRDER, PROVIDE
STIRRUPS IN THE SUPPORTING MEMBER AT 3 @ 2", 3 @ 6" ON BOTH
SIDES OF THE JOINT.
6. BEAMS SUPPORTED BY OTHER BEAMS (GIRDERS) SHALL BE
STRESSED PRIOR TO STRESSING THE SUPPORTING BEAM.
7. ANCHORAGES FOR ADDED BEAM TENDONS SHALL BE LOCATED AT
THE QUARTER POINT OF THE ADJACENT SPAN AND BE PLACED AT
THE CENTER OF GRAVITY (CG) OF THE BEAM SECTION. PROVIDE
REINFORCEMENT AT ANCHORAGE PER 14/S-520.
8. TO ALLEVIATE CONGESTION AT BEAM/COLUMN INTERSECTIONS,
BOTTOM REINFORCEMENT MAY BE PLACED IN TWO LAYERS. TOP
REINFORCEMENT IS TO BE PLACED IN ONE LAYER, UNLESS NOTED.
TOP BEAM LONGITUDINAL BARS MAY BE SPREAD OUT INTO THE SLAB
OVER A DISTANCE OF 2 TIMES THE THICKNESS OF THE SLAB ON
EITHER SIDE OF THE BEAM.
9. SEE S-620 FOR SLEEVE PLACEMENT GUIDELINES FOR PIPES IN BEAMS.
10. PLACEMENT OF THE TOP BEAM BARS MUST ACCOUNT FOR THE
STANDARD HOOKS FITTING INTO A COLUMN BELOW OR ABOVE THE
BEAM.
11. TOP BEAM BARS AT TOPS OF COLUMNS WHICH DO NOT EXTEND ABOVE
THE TOP OF THE SLAB SHALL HAVE STANDARD HOOKS TURNED DOWN
INTO BEAMS.
12. FOR BEAM CAMBER, SEE CONCRETE BEAM DIAGRAM AND SCHEDULE
ON THIS SHEET.
13. COLUMN BARS AT COLUMNS WHICH DO NOT EXTEND ABOVE THE TOP
OF SLAB SHALL HAVE STANDARD HOOKS TURNED INTO SLAB OR A
BEAM. SEE DETAILS 6 AND 8/S-610 FOR ADDITIONAL INFORMATION.
14. IT IS MORE DESIRABLE TO TENSION THE BEAM TENDONS TOWARDS
THE INTERIOR COLUMNS WHENEVER POSSIBLE TO AVOID PLACINS
STRESSING POCKETS IN THE EXTERIOR COLUMNS.
B11 14 35I A 24 3 1/2 2413 348 (2)#8 (2)#8 (2)#8 (2)#8 (2)#8(2)#5
B13 16 35II A 24 3 1/2 329 240 (2)#8 (2)#8 (2)#8 (2)#8 (2)#8(2)#5
SEE 2/S-620
B21 14 35II A 24 3 1/2 3210 267 (2)#8 (2)#8 (2)#8 (2)#8 (2)#8(2)#5
B22 14 35II A 24 3 1/2 327 187 (2)#8 (2)#8 (2)#8 (2)#8 (2)#8(2)#5
B23 14 35II A 24 3 1/2 325 133 (2)#8 (2)#8 (2)#8 (2)#8 (2)#8(2)#5
B24 14 35II A 24 3 1/2 3212 240 (2)#8 (2)#8 (2)#8 (2)#8 (2)#8(2)#5
UTB1 16 49I D 20 3 1/2 205 133 (3)#8 (3)#8 (3)#8 (3)#8 (3)#8(2)#5
UTB2 16 49I D 20 12 205 133 (3)#8 (3)#8 (3)#8 (3)#8 (3)#8(2)#5
G1 24 36I B 23 3 1/2 2326 696 (3)#9 (3)#9 (3)#9 (3)#9 (3)#9 (3)#9
G2 24 36I B 23 3 1/2 2321 562 (3)#9 (3)#9 (3)#9 (3)#9 (3)#9 (3)#9
G3 24 36I B 23 3 1/2 2318 481 (3)#9 (3)#9 (3)#9 (3)#9 (3)#9 (3)#9
G4 24 36I B 20 3 1/2 206 160 (3)#9 (3)#9 (3)#9 (3)#9 (3)#9 (3)#9
B12 14 35I B - - -- - (3)#8 x CONT #4 @ 8"OC(3)#8 x CONT
SEE 2/S-620
SEE 2/S-620
SEE 2/S-620
SEE 2/S-620
SEE 2/S-620
SEE 2/S-620
SEE 2/S-620
SEE 2/S-620
SEE 2/S-620
SEE 2/S-620
SEE 2/S-620
CAMBER SEE 7/S-620
CAMBER SEE 7/S-620
CAMBER SEE 7/S-620
CAMBER SEE 7/S-620
CAMBER SEE 7/S-620
CAMBER SEE 7/S-620
CAMBER SEE 7/S-620
CAMBER SEE 7/S-620
CAMBER SEE 7/S-620
CAMBER SEE 7/S-620
CAMBER SEE 7/S-620
CAMBER SEE 7/S-620
CAMBER SEE 7/S-620
BG1 24 36I A
L = SEE PLAN
L/4 L/6 REMAINDER L/6 L/4
NOTE:
SEE OTHER DETAILS FOR
BALANCE OF INFORMATION
2"
#4 TIES
3 @ 2", 12 @ 6", REM @ 9"
#4 @ 12"
#4 @ 16"
#4 TIES
3 @ 2", 12 @ 6", REM @ 9"
2"
(FOR SPANS LESS THAN 52'-0" SEE SCHEDULE)
#3
#4
#5
#6
#7
#8
#9
#10
#11
BAR SIZE
DESCRIPTION
TYPE
4000 5000 6000 7000 8000 4000 5000 6000 7000 8000
TOP BARS COMPRESSION
NON-CONFINED HORIZONTAL
BOTTOM BARS TENSION
NON-CONFINED HORIZONTAL
34 34 34 34
BASED ON ACI 318-14
NOTES:
1. WITH LIGHTWEIGHT CONCRETE, INCREASE SPLICE LENGTHS BY 1.33.
EQ
COLUMNCL
COLUMN
C A
M B
E R
COLUMNCL
BEAM CAMBER SCHEDULE
MINIMUM BEAM CAMBER
SPAN
0' TO 20'
20' TO 30'
30' TO 40'
40' TO 50'
50' TO 65'
1/4"
1/2"
3/4"
1"
1 1/4"
BEAM
REINFORCED
1/2"
1"
1 1/2"
2"
2 1/2"
GIRDER
0"
3/8"
1/2"
5/8"
3/4"
BEAM
0"
1/2"
3/4"
1"
1 1/2"
GIRDER
POST-TENSIONED
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
STRUCTURAL - BEAM
SCHEDULE AND DETAILS
A/E DESIGN TO DEVELOP RFP FOR
PARKING STRUCTURE
ET AME
612-165
SE620
VA NORTHERN CALIFORNIA HEALTHCARE SYSTEM
3/4" = 1'-0"5
SLEEVE PLACEMENT THROUGH BEAM
GUIDELINES
3/4" = 1'-0"3
BEAM PENETRATION DETAIL
3/4" = 1'-0"1
BEAM PENETRATION DETAIL
3/4" = 1'-0"4
BEAM & GIRDER TYPES
3/4" = 1'-0"2
STIRRUP SPACING DETAIL FOR
BEAM SPANS GREATER THAN 52'-0"
1" = 1'-0"6
PT BEAM GIRDER LONGITUDIAL
REINFORCEMENT LAP SPLICES
(INCHES)
1" = 1'-0"7
BEAM CAMBER SCHEDULE
Revisions: Date:
dmelendez Typewritten text
DESIGN BUILD PROPOSAL PACKAGE
35% SCHEMATIC DESIGN (SD1)
dmelendez Typewritten text 10/11/2019 08/15/2019 crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
crollins Typewritten text 12/18/2019 crollins Typewritten text 12/18/2019 crollins
P1
SE630
PA.7
PA.5
P0
SE630
24" x 36" BEAM
24" x 36" BEAM8" THICK
CONCRETE SLAB
x
G
IR
D E
R
EL
GROUND TIER
11' - 4"
EL
SECOND TIER
22' - 8"
PA.7
EL
GROUND TIER
11' - 4"
EL
SECOND TIER
22' - 8"
PA.5
SE630
8" 16'-0" 8" 7'-0" 8"
1'-0" 7'-4" 7'-4" 4'-2" 5'-2"
8" THICK
CRASHWALL
8" THICK
CRASHWALL
8" THICK
CONCRETE SLAB
24" x 36"
BEAM TYP
M
IN
25'-0"
EL
GROUND TIER
11' - 4"
EL
SECOND TIER
22' - 8"
P1
SE630
P0
ABUTMENT WALL
SEE CIVIL DRAWINGS
8" THICK
CONCRETE SLAB
24" x 36" BEAM
BEARING PAD 24" x 24" CONCRETE
COLUMN TYP
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
STRUCTURAL - BRIDGE PLAN
AND SECTIONS
A/E DESIGN TO DEVELOP RFP FOR
PARKING STRUCTURE
Checker Author
612-165
SE630
VA NORTHERN CALIFORNIA HEALTHCARE SYSTEM
Revisions: Date:
1/4" = 1'-0"1
SECOND TIER - BRIDGE
1/4" = 1'-0"4
SECTION
1/4" = 1'-0"2
SECTION
dmelendez Typewritten text
DESIGN BUILD PROPOSAL PACKAGE
35% SCHEMATIC DESIGN (SD1)
dmelendez Typewritten text 10/11/2019 08/15/2019 crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
crollins
12/18/2019
EL
GROUND TIER
11' - 4"
EL
SECOND TIER
22' - 8"
P3 P4 P5 P6 P7
18" x 49" UPTURNED
MOMENT FRAME BEAMS
24" x 36" MOMENT
FRAME COLUMNS TYP
EL
BASEMENT
0"
EL
GROUND TIER
11' - 4"
EL
SECOND TIER
22' - 8"
P22P18 P19 P20 P21
18" x 49" UPTURNED
MOMENT FRAME BEAMS
24" x 36" MOMENT
FRAME COLUMNS TYP
EL
BASEMENT
0"
EL
GROUND TIER
11' - 4"
EL
SECOND TIER
22' - 8"
P22 P18P19P20P21
18" x 49" UPTURNED
MOMENT FRAME BEAMS
24" x 36" MOMENT
FRAME COLUMNS TYP
EL
GROUND TIER
11' - 4"
EL
SECOND TIER
22' - 8"
P3P4P5P6P7
18" x 49" UPTURNED
MOMENT FRAME BEAMS
24" x 36" MOMENT
FRAME COLUMNS TYP
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
STRUCTURAL - MOMENT
FRAME ELEVATIONS
A/E DESIGN TO DEVELOP RFP FOR
PARKING STRUCTURE
Checker Author
612-165
SE705
VA NORTHERN CALIFORNIA HEALTHCARE SYSTEM
1/8" = 1'-0"4
MOMENT FRAME ELEVATION @ LINE PC
1/8" = 1'-0"1
MOMENT FRAME ELEVATION @ LINE PC
1/8" = 1'-0"2
MOMENT FRAME ELEVATION @ LINE PA
1/8" = 1'-0"5
MOMENT FRAME ELEVATION @ LINE PA
Revisions: Date:
dmelendez Typewritten text
DESIGN BUILD PROPOSAL PACKAGE
35% SCHEMATIC DESIGN (SD1)
dmelendez Typewritten text 10/11/2019 08/15/2019 crollins Typewritten text 12/18/2019 crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
crollins Typewritten text 12/18/2019 crollins
BASEMENT
0"
EL
GROUND TIER
11' - 4"
EL
SECOND TIER
22' - 8"
PB PA.7
16" THICK CONCRETE SHEAR WALL
EL
GROUND TIER
11' - 4"
EL
SECOND TIER
22' - 8"
PBPA.7
16" THICK CONCRETE SHEAR WALL
SE630
PBPA.7
16" THICK CONCRETE SHEAR WALL
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
STRUCTURAL - SHEAR WALL
ELEVATIONS
A/E DESIGN TO DEVELOP RFP FOR
PARKING STRUCTURE
Checker Author
612-165
SE706
VA NORTHERN CALIFORNIA HEALTHCARE SYSTEM
1/4" = 1'-0"3
SHEAR WALL ELEVATION @ LINE P24
1/4" = 1'-0"1
SHEAR WALL ELEVATION @ LINE P1
1/4" = 1'-0"2
SHEAR WALL ELEVATION @ LINE P13
(SHEAR WALL @ LINE P12 SIMILAR)
Revisions: Date:
dmelendez Typewritten text
DESIGN BUILD PROPOSAL PACKAGE
35% SCHEMATIC DESIGN (SD1)
dmelendez Typewritten text 10/11/2019 08/15/2019 crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
crollins Typewritten text 12/18/2019 crollins Typewritten text 12/18/2019 crollins
PC
P1 P22P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 P14 P15 P16 P17 P18 P19 P20 P21 P23 P24
PB
P2.5 P22.5
16'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 20'-4" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 16'-0" 16'-0" 16'-0" 1'-0"
P13
PA.7
2 S @ 9'-0"= 18'-0"
3'-0"
3'-0"
6'-3" 17 S @ 9'-0"=153'-0" 8'-2" 24'-0" 18'-0"
23 S @ 9'-0"= 207'-0" 5'-1"
5 S @ 9'-0"= 45'-0" 8'-2"
4 S @ 9'-0"= 36'-0" 13'-6" 27'-8" 10"
S
S
PA.1
PA.5
P0
AF03
S T O R A G E
RAMP UP
SLOPE 4.80%
AF09
AF14
AF01
XX SIGN NUMBER
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
BASEMENT TIER STRIPING
PLAN
A/E DESIGN TO DEVELOP RFP FOR
PARKING STRUCTURE
TD RG
612-165
AG101
SCALE: 1/16" = 1'-0"
F2
BASEMENT TIER PLAN
SYMBOL LEGEND
GENERAL NOTES
PARKING SCHEDULE - OVERALL
TIER STANDARD
ACCESSIBLE
CAR
ACCESSIBLE
VAN MOTORCYCLE TOTAL
BASEMENT
TIER
59 0 0 0 59
GROUND
TIER
140 5 3 0 157
SECOND
TIER
119 6 0 0 135
318 11 3 0 351
PARKING EFFICIENCY - OVERALL
TIER AREA
TOTAL
SPACES EFFICIENCY
BASEMENT 22,372 SF 59 379
GROUND TIER 53,886 SF 158 341
SECOND TIER 47,802 SF 141 339
KEYNOTE LEGEND
AF01 4" SINGLE LINE STRIPING (WHITE)
AF03 MOTORCYCLE PARKING. REFER TO
DETAIL C1/AG500
AF09 METAL PIPE BOLLARD ON SLAB
AF14 TRUNCATED DOMES
1. FOR TYPICAL STRIPING DETAILS AND
FLOOR ARROWS SEE SHEET AG500.
2. ALL DIMENSIONS FOR STRIPING ARE
FROM FACE OF COLUMN OR INSIDE
FACE OF WALL UNO.
3. FOR FLOOR ELEVATIONS SEE "S-100"
SERIES DRAWINGS.
Revisions: Date:
8'
SCALE : 1/16" = 1'-0"
0 16' 32'
TRUE
NORTH
N dmelendez Typewritten text
DESIGN BUILD PROPOSAL PACKAGE
35% SCHEMATIC DESIGN (SD1)
dmelendez Typewritten text 10/11/2019 dmelendez Typewritten text 08/15/2019 dmelendez Draft dmelendez Draft crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
crollins Typewritten text 12/18/2019 crollins Typewritten text 12/18/2019 crollins
P1 P22P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 P14 P15 P16 P17 P18 P19 P20 P21 P23 P24
PB
P2.5 P22.5
1'-0" 16'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 20'-4" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 18'-0" 16'-0" 16'-0" 16'-0" 1'-0"
428'-4"
P13
PA.7
5'-6" 18'-0" 1'-2"
5'-0" 8'-0" 5'-0" 40 S @ 9'-0"= 360'-0" 5'-1" 18'-0"
24'-0" 10'-0" 17 S @ 9'-0"= 153'-0" 11'-0" 17 S @ 9'-0"= 153'-0" 9'-5" 24'-0"
10'-0"
9 FUTURE EV
= 81'-0" 8 S @ 9'-0"= 72'-0" 10'-9" 17 S @ 9'-0"= 153'-0" 9'-5"
5'-0" 8'-0" 5'-0"
FUTURE
EV ACCESSIBLE 33 S @ 9'-0"= 297'-0" 6"
S
S
PA.1
PA.5
P0
AF03
AF17
ELEC SEC
RAMP UPRAMP DN
SLOPE 4.80% SLOPE 4.80%
AF15
AF14
AF01
AF16
AE07
XX SIGN NUMBER
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
GROUND TIER STRIPING PLAN A/E DESIGN TO DEVELOP RFP FOR
PARKING STRUCTURE
TD RG
612-165
AG102
SCALE: 1/16" = 1'-0"
F2
GROUND TIER PLAN
SYMBOL LEGEND
GENERAL NOTES
KEYNOTE LEGEND
AE07 BARRIER CABLE
AF01 4" SINGLE LINE STRIPING (WHITE)
AF03 MOTORCYCLE PARKING. REFER TO
DETAIL C1/AG500
AF14 TRUNCATED DOMES
AF15 PIPE BOLLARD
AF16 FLOOR DRAIN
AF17 GUARDRAIL
Revisions: Date:
8'
SCALE : 1/16" = 1'-0"
0 16' 32'
TRUE
NORTH
N dmelendez Typewritten text
DESIGN BUILD PROPOSAL PACKAGE
35% SCHEMATIC DESIGN (SD1)
dmelendez Typewritten text 10/11/2019 dmelendez Typewritten text 08/15/2019 dmelendez Draft dmelendez Draft crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
crollins Typewritten text 12/18/2019 crollins Typewritten text 12/18/2019 crollins
P1 P22P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 P14 P15 P16 P17 P18 P19 P20 P21 P23 P24
PB
P2.5 P22.5P13
PA.7
5'-6" 18'-0" 6'-2" 8'-0" 5'-0" 18 S @ 9'-0"= 162'-0"
10'-0" 15 S @ 9'-0"= 135'-0"
10'-0" 10 FUTURE EV = 90'-0" 7 S @ 9'-0"= 63'-0" 7'-0" 7 S @ 9'-0"= 63'-0" 9'-8" 14'-0" 7'-4" 7 S @ 9'-0"= 63'-0" 8'-6" 24'-0" 18'-0" 8"
8'-10"
8'-0"
5'-0" 40 S @ 9'-0"= 360'-0" 8'-0"
PA.1
PA.5
P0
11 S @ 9'-0"= 99'-0" 8'-10" 18'-0"
S
S
" 1
"2
RAMP DN
SLOPE 4.80%
AF03
AF15
AF14
AF01
AF16
AE07
XX SIGN NUMBER
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANT ARCHITECT/ENGINEER OF RECORD Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Drawing Title
Approved: Project Director
Phase Project Title Project Number
Building Number
Drawing NumberLocation
Issue Date Checked Drawn
VA FORM 08-6231
REVIEW ONLY - NOT FOR CONSTRUCTION
SECOND TIER STRIPING PLAN A/E DESIGN TO DEVELOP RFP FOR
PARKING STRUCTURE
TD RG
612-165
AG103
SCALE: 1/16" = 1'-0"
F2
SECOND TIER PLAN
SYMBOL LEGEND
GENERAL NOTES
KEYNOTE LEGEND
AE0
BARRIER CABLE
AF01 4" SINGLE LINE STRIPING (WHITE)
AF03 MOTORCYCLE PARKING. REFER TO
DETAIL C1/AG500
AF14 TRUNCATED DOMES
AF15 PIPE BOLLARD
AF16 FLOOR DRAIN
Revisions: Date:
8'
SCALE : 1/16" = 1'-0"
0 16' 32'
TRUE
NORTH
N
DEDUCT ALTERNATE 6
REDUCE THE NUMBER OF PARKING SPACES FROM
THE TOP LEVEL
dmelendez Typewritten text 08/15/2019 dmelendez Typewritten text 10/11/2019 dmelendez Typewritten text
DESIGN BUILD PROPOSAL PACKAGE
35% SCHEMATIC DESIGN (SD1)
dmelendez Draft dmelendez Draft crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
crollins Typewritten text 12/18/2019 crollins Typewritten text 12/18/2019 crollins Typewritten text
FINAL DESIGN BUILD PROPOSAL PACKAGE
DBibbs
REFER TO COMMENTS ON SHEET SE103
NOTES:
1. PROVIDE SIGNS AT ALL EXTERIOR
ENTRANCE DOORS, UNO.
/2
10"
THIS FACILITY
ACCESSIBLE BY
PERSONS WITH
DISABILITIES
ISA SYMBOL
/2
M
IN
M A
X
3'-0"
4" PAINTED WHITE
BORDER STRIPE WITH
BLUE (COLOR NO. 15090
IN FEDERAL STANDARDS
595B) BACKGROUND. SEE
STRIPING PLANS FOR
LOCATION AT EACH
ACCESSIBLE STALL.
3"…