Attachment 8_B704 Lighting Requirements.pdf
PDF 270 KB Posted
- Attached to
- Lighting installation for B704 Federal contract opportunity
- Solicitation number
- FA449726Q0020
About this file
This is an architectural floor plan and lighting design specification for Building 704, specifically the first floor layout. The document provides detailed room dimensions, square footage, and comprehensive illumination target criteria for various space types within the facility.
The floor plan depicts a linear building layout measuring 208 feet in length with multiple instructional and administrative spaces. Key rooms include eight QTP (Qualification Training Program) classrooms ranging from 263 to 437 square feet, three CUT (Continuing Upgrade Training) classrooms between 204 and 449 square feet, administrative offices (Chief AGT Office, Shift Chief Office), support spaces (Men's and Women's latrines, break room, boiler room, utility locker room), and specialized areas (AFETs classroom, AFETs office, computer room, conference room, and instructor development space). Ceiling heights are specified at 7'8" for lobbies, foyers, and corridors, with all other spaces at 8'8". The lighting specifications establish daytime and nighttime illuminance targets measured in foot-candles (fc) and lux, with uniformity requirements varying by space type. Classrooms require 40 fc average horizontal illuminance at 2'6" above finished floor with 2:1 uniformity; offices require 30 fc with 2:1 uniformity; conference rooms require 30 fc horizontal with 15 fc vertical illuminance; restrooms require 5-15 fc depending on area with 3:1 uniformity; mechanical/boiler rooms require 20 fc; locker rooms require 5 fc with 3:1 uniformity; corridors require 3 fc with 5:1 uniformity; and storage areas require 10 fc with 3:1 uniformity.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| QnA - Lighting Installation for B704 - FA449726Q0020.pdf | ||
| Combined Synopsis_Solicitation Updated.pdf | ||
| Combined Synopsis_Solicitation.pdf | ||
| Attachment 4_52.212-1, Instructions to Offerors Addendum.pdf | ||
| Attachment 7_B704 Lighting Layout.pdf | ||
| Attachment 9_B704 Photometric Study.pdf | ||
| Combined Synopsis - Solicitation.pdf | ||
| Attachment 1_SOW.pdf | ||
| Attachment 2 _ Quote Schedule.xlsx | XLSX spreadsheet | |
| Attachment 3_Provisions and Clauses.pdf | ||
| Attachment 5_52.212-2, Evaluation Addendum.pdf | ||
| Attachment 6 _Wage Determination.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2 4 4 2 4 4 8 8 4 16
208'
QTP
Classroom
16'-41"
263 Sq Ft
QTP Classroom
21'-23"
341 Sq Ft
20'-5"
327 Sq Ft
CUT Classroom
11'-93"
188 Sq Ft
Boiler
RM
8'-01"
Utility
Locker RM
9'-93"
156 Sq Ft
Mens
Latrine
15'
Women
Latrine
14'-93"
Chief AGT
Office
11'-07"
182 Sq Ft
Shift Chief
Office
11'-07"
189 Sq Ft
Break RM
15'-33"
261 Sq Ft
12'-0 1 "
204 Sq Ft
17'
290 Sq Ft
290 Sq Ft
127'-11"
78'-5 7 "
Computer
AFETs Classroom
AFETs Office
Conference RM
Instructor Development
1 3 7 1 1 3 Area 7 1
16'-82"
375 Sq Ft
19'-58"
437 Sq Ft
5'-48" 20'
449 Sq Ft
15'-62"
349 Sq Ft
31'-88"
711 Sq Ft
15'-44" 17'-1116"
263 Sq Ft
17'
382 Sq Ft
8'-02"
181 Sq Ft
17'
382 Sq Ft
382 Sq Ft
A-101
" 8
B L
D G s t
F L O
O R
F
JX
T -A
S -0
P
\P ro je c ts
_C o m p le te d \F
L O
O R
P
L A
N S \A u to
C A
D
F lo o r p la n s\
B ld g _7
.d w g
Classrooms: Target Criteria Daytime/Nighttime Average Horizontal Illuminance 40 fc (400 lux) at 2’-6” (762 mm) AFF Average Vertical Illuminance 15 fc (150 lux) at 4’ (1,219 mm) AFF on presentation wall Horizontal Illuminance Uniformity 2:1 average to minimum
Locker Room: Target Criteria Daytime/Nighttime Average Horizontal Illuminance 5 fc (50 lux) at floor Average Vertical Illuminance 10 fc (100 lux) at locker faces Horizontal Illuminance Uniformity 3:1 average to minimum
Restrooms: Target Criteria Daytime/Nighttime Average Horizontal Illuminance, General 5 fc (50 lux) at floor Average Horizontal Illuminance, Fixtures and vanities 15 fc (150 lux) at vanity surface Average Horizontal Illuminance, Showers 10 fc (100 lux) at floor Horizontal Illuminance Uniformity 3:1 average to minimum
Mechanical/Boiler Rooms: Target Criteria Daytime/Nighttime Average Horizontal Illuminance 20 fc (200 lux) at 3’-6” (1067 mm) AFF Horizontal Illuminance Uniformity 3:1 average to minimum
Office Rooms: Target Criteria Daytime/Nighttime Average Horizontal Illuminance 30 fc (300 lux) at 2’-6” (762 mm) AFF Horizontal Illuminance Uniformity 2:1 average to minimum
Conference Room: Target Criteria Daytime/Nighttime Average Horizontal Illuminance 30 fc (300 lux) at 2’-6” (762 mm) AFF Average Vertical Illuminance 15 fc (150 lux) at 4’-0” (1524 mm) AFF
Hallways/Corridors: Target Criteria Daytime/Nighttime Average Horizontal Illuminance 3 fc (30 lux) at floor Horizontal Illuminance Uniformity 5:1 average to minimum
Storage: Target Criteria Daytime/Nighttime Average Horizontal Illuminance 10 fc (100 lux) at floor Average Vertical Illuminance 7.5 fc (75 lux) at 4’-0” (1219 mm) AFF
Ceiling heights: Based on existing as-built drawings; lobbies, foyers and corridors height are 7’ 8” All other spaces are 8’ 8”
File details come from the government source that posted it. Updated .