This solicitation requests proposals for Electronic Health Records Modernization infrastructure upgrades at the Veterans Affairs Medical Center in Birmingham, Alabama. The selected contractor shall provide all labor, materials, project management and quality control services necessary to complete upgrades to support the EHRM initiative. Specific requirements include furnishing and installing new cabling, servers, networking equipment and related infrastructure at the medical center. The period of performance is one year from the award date. The soliciting agency is the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.
View the file
Other files for this federal contract opportunity
Show all 34
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Infrastructure Standard for Telecommunications Spaces Version 3.1
July 1, 2021 | Solution Delivery-Data Center and Infrastructure Engineering
OFFICE OF INFORMATION AND TECHNOLOGY
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| i
Version Changes Table 1: Version Changes
Date Reason for Changes Version Author 2007 Original 0.1 Michael Julian, RCDD 2009 Revision 0.2 Michael Julian, RCDD 2012 Revision 1.0 Michael Julian, RCDD 12/07/2016 Enterprise Data Center Infrastructure Collaboration
Team (EDICT) Revision
1.1 EDICT
2/05/2018 -Expanded revision including the addition of Administrative and Operations Standards.
-Name changed to include IT Support Infrastructure to reflect broader scope.
1.2 EDICT
6/11/2018 -Minor update to allow for deeper network racks in cooperation with IO’s request.
-Expanded allowance for fiber cabinets, cassettes, patch panels, and racks.
-Changed National Data Center Operations & Logistics (NDCOL) facility ID numbers to VA Record ID numbers.
-Clarified reference to OIT responsibility for the enterprise-wide technical framework and IT architecture services.
2.1 EDICT
4/10/2019 -Name updated from “VA Enterprise Facility IT Support Infrastructure Standard” to “Infrastructure Standard for Telecommunications Spaces.”
-Minor editorial changes resulting from initial review by the Office of Construction and Facilities Management (CFM) Facilities Standards Service (FSS) for publication in Technical Information Library (TIL).
-Removed operational information not required for building planning and design for publishing of the Standard on the TIL. Information redacted will be published as part of the Operations and Maintenance Standards for Telecommunications Spaces. In the interim, refer to the June 11th, 2018 version 2.1 of The Standard on the Baseline Configuration Management (BCM) Standards site.
-508 compliance updates.
2.2 EDICT
CFM
8/21/2020 -Editorial changes resulting from full review by CFM FSS for publication in CFM’s TIL.
-Updated Telecommunications Room (TR), entrance room, and electrical power standards -Added grounding and bonding, transformers, intra-building/inter-building cabling, lighting, and lightning protection system sections and Request for Variance process instructions.
3.0 EDICT
CFM
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| ii
Date Reason for Changes Version Author -Created VA-modified Data Center Facility Environment Conditioning Standards figure to replace ASHRAE’s less stringent requirements -Reorganized sequence of chapters for a more logical flow of data center design. Refer to the Table of Contents and the associated links to quickly find any subject of interest.
-Relocated Figures, Tables, Definitions, References, and Acronyms sections to front matter for consistency with Telecommunication Industry Association (TIA) formats.
-Added appendices to include Request for Variance form and OIT Design Guide Template Design Package
7/1/2021 -4.2.8 Bonding and Grounding: changed “supplementary” ground path to “dedicated” -4.4.4 Fiber Optic Cable: relaxed authorization for Universal Cassettes to be used when breaking out to LC connectors -Appendix B Sheet 2: corrected split package air conditioner heat rejection requirement to be 17,000 BTU/h (5 kW) per rack -Appendix B Sheet 3: corrected layer issue masking attributes and specifications in the table -Appendix B Sheet 21: corrected layer issue masking a PDU on left side of Plate 1
3.1 EDICT
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| iii
Table of Contents Version Changes .............................................................................................................................. i Table of Contents ........................................................................................................................... iii Definitions ..................................................................................................................................... ix References .................................................................................................................................... xv Acronyms and Initialisms ............................................................................................................. xxi Contributors .............................................................................................................................. xxvi 1 Introduction
1.1 Purpose
1.2 Scope
1.3 Administration
1.3.1 Request for Variance from Infrastructure Standards
1.3.2 Request for Change to Infrastructure Standards for Telecommunications Spaces
1.3.3 Contact Information
1.4 Standards Overview
1.5 Background
1.6 Objectives
1.7 Authority
2 IT Support Space Classification
2.1 Core Data Centers
2.2 Mission Support Centers
2.3 Campus Support Centers
2.4 Network Support Centers
3 Information Technology Support Space Planned Redundancy Levels
3.1 Core Data Center and Campus Support Center Planned Redundancy Levels
3.2 Mission Support Center Planned Redundancy Levels
3.3 Network Support Center, Telecommunications Room, and Entrance Room Planned Redundancy Levels
4 Infrastructure Standards
4.1 Architectural Standards and Space Design
4.1.1 Building Specifications for Common Telecommunications Spaces
4.1.2 Data Center Layout Standards
4.1.3 Telecommunications Room
4.1.4 Entrance Room
4.2 Electrical Power and Grounding Standards
4.2.1 Topology for Power Distribution Standards
4.2.2 Uninterruptible Power Supply Specifications
4.2.3 Transformers
4.2.4 Branch Power Circuit to Rack/Cabinet
4.2.5 Zone Power Distribution Units
4.2.6 Rack Mounted Uninterruptible Power Supplies
4.2.7 Vertical Rack Power Distribution Units
4.2.8 Bonding and Grounding
4.2.9 Lighting
4.2.10 Metering
4.3 Mechanical and Environmental Conditioning Standards and Monitoring
4.3.1 Introduction
4.3.2 Environmental Operating Envelope Conditions
4.3.3 Data Center Facility Environment Conditioning Standards
4.3.4 Data Center Facility Environment Conditioning Standards (Amendments and Exceptions) ... 54
4.3.5 Environmental Control Equipment Requirements
4.3.6 Airflow Control
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| iv
4.3.7 Monitoring
4.4 Telecommunications Standards
4.4.1 Unshielded Twisted Pair
4.4.2 Unshielded Twisted Pair Patch Panel Standards
4.4.3 Unshielded Twisted Pair Patch Cord
4.4.4 Fiber Optic Cable
4.4.5 Fiber Distribution Cassettes
4.4.6 Fiber Patch Cords
4.4.7 Fiber Distribution Panel/Cabinet
4.4.8 Cable Support Infrastructure
4.4.9 Work Area Outlets
4.4.10 Horizontal Distribution
4.4.11 Backbone Distribution
4.4.12 Server Cabinets
4.4.13 Network Equipment Racks
4.4.14 Network Equipment Cabinets
5 Administration Standards
5.1 Data Center Position Identification
5.1.1 Cross-Reference to Other Identification Systems
5.1.2 Standardized Data Center Facility Type Identification
5.1.3 Standardized Data Center Naming Convention
5.1.4 Color Coded Identification
5.1.5 Information Transport Systems Equipment and Component Labeling
5.2 Management Standards
5.2.1 Management of Telecommunications Cabling
5.2.2 Management of Airflow
Appendix A: Request for Variance ............................................................................................... A-1 Appendix B: OIT Design Guide Templates .....................................................................................B-1
B.1 Design Narrative ............................................................................................................ B-1 B.2 Main Computer Rooms ..................................................................................................B-1 B.3 Entrance Rooms .............................................................................................................B-2 B.4 Telecommunications Rooms ..........................................................................................B-2 B.5 IT Design Guide Templates for Critical Infrastructure in Telecommunications Spaces.. B-3
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| v
Figures Figure 1: Generic Redundancy Level Standards for Physical Plants, Facilities, and Infrastructure Systems
Figure 2: Hot Aisle/Cold Aisle Approach
Figure 3: Power Distribution Options Simplified Visualization (CDC, CSC, MSC)
Figure 4: Standard Density Underfloor/Whip Distribution Topology (CDC, CSC, MSC) – 60 A Zone PDU
Figure 5: Standard Density Underfloor/Whip Distribution Topology (CDC, CSC, MSC) – 30 A Zone PDU
Figure 6: High Density Underfloor/Whip Distribution Topology (CDC, CSC, MSC) – 60 A Zone PDU
Figure 7: High Density Underfloor/Whip Distribution Topology (CDC, CSC, MSC) – 30 A Zone PDU
Figure 8: Whip Distribution Topology with In-Rack UPS (NSC, TR, Entrance Room) – 60 A Zone PDU . 27
Figure 9: Whip Distribution Topology with In-Rack UPS (NSC, TR, Entrance Room) – 30 A Zone PDU . 27
Figure 10: Single Rack Whip Distribution Topology with In-Rack UPS (NSC, TR, Entrance Room) –20 A Circuits
Figure 11: International Electrotechnical Commission (IEC) Standard C13/14 cord set
Figure 12: Typical Bonding Connection
Figure 13: Typical Rack Bonding Layout
Figure 14: Typical Bonding Requirements for IT Equipment Enclosures
Figure 15: OEM Equipment Ground Lug Connection
Figure 16: OEM Equipment Ground Connection
Figure 17: Primary Bonding Busbar
Figure 18: Power Usage Effectiveness
Figure 19: VA-Modified ASHRAE Environmental Classes for Data Center Applications
Figure 20: Brushed Floor Grommet
Figure 21: Air Dam Foam
Figure 22: Blanking Panel Application
Figure 23: Method A Polarity of Horizontal Pre-terminated MPO-based Fiber Optic Cabling
Figure 24: Method A Polarity End to End Connectivity (A-B and A-A Patch Cords Required)
Figure 25: Polarity of Fiber Optic Patch Cable
Figure 26: Typical Position Identification Examples
Figure 27: Example of Best-Practice Differentiated Power Cord Coloration Implementation
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| vi
Figure 28: Rack Unit Identification Example
Figure 29: Example of Communications Cable Labeling
Figure 30: Detailed Example of Communications Cable Labeling
Figure 31: Power Whip Label Example
Figure 32: Equipment-Specific Cable Management Requirements
Figure 33: Acceptable Cable Management Results
Figure 34: Unacceptable Cable Management Results
Figure 35: Cable Labels in Bundles
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| vii
Tables Table 1: Version Changes ......................................................................................................................... i
Table 2: Contributors .......................................................................................................................... xxvi
Table 3: Data Center Classification Standards
Table 4: Data Center Planned Redundancy Levels
Table 5: Core Data Center and Campus Support Center Planned Redundancy Levels
Table 6: Mission Support Center Planned Redundancy Levels
Table 7: Network Support Center, Telecommunications Room, and Entrance Room Planned Redundancy Levels
Table 8: Building Specifications
Table 9: Data Center Floor Layout Standards
Table 10: Data Center Uninterruptible Power Supply Specifications
Table 11: Branch Power Circuit to Rack/Cabinet Standards (Underfloor/Whip Distribution)
Table 12: Branch Power Circuit to Rack/Cabinet Standards (Busbar Distribution)
Table 13: Zone Power Distribution Unit Standards
Table 14: Rack Mounted Uninterruptible Power Supply Standards
Table 15: Vertical Rack Power Distribution Unit Standards
Table 16: Busbar Standards
Table 17: Building Earth Ground System Standards
Table 18: Lightning Protection System
Table 19: Metered Energy Consumption Data
Table 20: Energy Consumption Performance Metrics
Table 21: Data Center Facility Environment Conditioning Standards
Table 22: Facility Environmental Requirements (CDC Amendments and Exceptions)
Table 23: Facility Environmental Requirements (MSC Amendments and Exceptions)
Table 24: Facility Environmental Requirements (NSC Amendments and Exceptions)
Table 25: Environmental Control Equipment
Table 26: Monitored Conditions
Table 27: Unshielded Twisted Pair Standards
Table 28: Unshielded Twisted Pair Patch Panel Standards
Table 29: Unshielded Twisted Pair Patch Cord Standards
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| viii
Table 30: Fiber Optic Cable Standards
Table 31: Fiber Distribution Cassettes
Table 32: Fiber Patch Cord Standards
Table 33: Fiber Distribution Panel/Cabinet Standards
Table 34: Cable Support Infrastructure Standards
Table 35: Cable Distribution Standards
Table 36: Server Cabinet Standards
Table 37: Network Equipment Racks
Table 38: Network Equipment Cabinet Standards
Table 39: Data center Position Identification Conventions
Table 40: Standard FACILITYTYPE Naming Conventions
Table 41: Color Identification Conventions
Table 42: Information Technology Systems Equipment and Component Labeling Conventions
Table 43: Support Infrastructure Identification Conventions
Table 44: Transport Media and Interface Identification Conventions
Table 45: Power Distribution Identification Conventions
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| ix
Definitions Access Provider: The operator of any facility that is used to convey telecommunications signals to and from a customer premises.
Administration: The method for labeling, identification, documentation and usage needed for installation, moves, additions and changes of the telecommunications infrastructure.
Alarming: Communicating when an absolute limit has been exceeded.
Alerting: Communicating when a condition threshold has been reached or exceeded.
American Society of Heating and Air-Conditioning Engineers (ASHRAE) Recommended Monitoring Locations (Modified):
· Front Top (FT): Centered horizontally, inside the front door, no more than 1 ft from the top of the cabinet
· Front Middle (FM): Centered horizontally, inside the front door, 4 ft +/- 6 in. from the finished floor surface
· Front Bottom (FB): Centered horizontally, inside the front door, no more than 1 ft from the finished floor surface
· Rear Top (RT): Centered horizontally, inside the rear door, no more than 1 ft from the top of the cabinet
· Rear Middle (RM): Centered horizontally, inside the rear door, 4 ft +/- 6 in. from the finished floor surface (not required by VA but recommended)
· Rear Bottom (RB): Centered horizontally, inside the rear door, no more than 1 ft from the finished floor surface (not required by VA but recommended)
Backbone:
· A facility (e.g., pathway, cable, conductors, optical fibers) between any of the following spaces: telecommunications rooms (TRs), telecommunications enclosures (TE), common TRs, floor-serving terminals, entrance facilities (EF), equipment rooms, and common equipment rooms.
· In a data center, a facility (e.g., pathway, cable, conductors, optical fibers) between any of the following spaces: entrance rooms or spaces, Main Distribution Areas (MDA), Horizontal Distribution Areas (HDA), Zone Distribution Areas (ZDA), and TRs.
Backbone Bonding Conductor: A telecommunication bonding connection which interconnects telecommunications bonding.
Busway: A pre-fabricated electrical distribution system used as an effective alternative to cable and conduit consisting of bus bars in a protective enclosure.
Bonding: The permanent joining of metallic parts to form an electrically conducive path that ensures electrical continuity and the capacity to conduct safely any current likely to be imposed.
Cabinet: A container that may enclose connection devices, terminations, apparatus, wiring, and equipment.
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| x
Channel: All telecommunications cable elements, permanent cable (link) and patching elements, that connect two pieces of IT equipment.
Channel Rack: A network four-post rack with sides having a cable management pattern of staggered shapes (circles, hexagons, etc.) to allow for connection points for cable management accessories used for housing networking equipment.
Compression Connection: A means of permanently bonding a conductor to a connector by permanently deforming the connector using a compression tool.
Computer Room: An architectural space whose primary function is to accommodate data processing equipment.
Concurrently Maintainable: The ability to have planned maintenance performed at any time on any path, equipment or component of the system without interrupting the operation of the system.
Cross-connect: A facility enabling the termination of cable elements and their interconnection or cross connection.
Conduit: (1) A raceway of circular cross-section. (2) A structure containing one or more ducts.
Data Center: A building or portion of a building whose primary function is to house a computer room and its support areas.
Demarcation Point: A point where the operational control or ownership changes.
Dew Point: The temperature to which air must be cooled (assuming constant air pressure and moisture content) to reach a relative humidity of 100 % (i.e. saturation).
Electromagnetic Interference (EMI): Radiated or conducted electromagnetic energy (noise) of any frequency that has an undesirable effect on electronic equipment or signal transmissions.
Entrance Room: A space in which the joining of inter or intra building telecommunications cabling takes place.
Equipment Distributor (ED): Reservation of the top 5 Rack Units (RU) of space in a server cabinet for copper and fiber patch panel equipment.
Exothermic Weld: A method of permanently bonding two metals together by a controlled heat reaction resulting in a molecular bond.
Facility Total Electrical Consumption (FEC): Total of all energy used from all sourced by the building housing the data center. This metric requires totaling the amount of electrical
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xi energy going into the building through the building’s main step-down transformer(s) and the amount of electrical energy generated through running any facility or data center generator equipment.
Ground: A conducting connection, whether intentional or accidental, between an electrical circuit (e.g., telecommunications) or equipment and the earth, or to some conducting body that serves in place of earth.
Grounding: The act of creating a ground.
Grounding Electrode: A conductor, usually a rod, pipe or plate (or group of conductors) in direct contact with the earth for the purpose of providing a low-impedance connection to the earth.
Grounding Electrode System: One or more grounding electrodes that are connected.
Horizontal Cabling (HC): (1) The cabling (media) between and including the telecommunications outlet and connector and the horizontal cross connect, usually in a telecommunications room. (2) Within a data center, the media between the Equipment Distributor (ED) and the Horizontal Distributor (HD).
Horizontal Distribution Area (HDA): Distribution used to serve equipment areas when the horizontal cabling is not located in the main distribution area. When used, the horizontal distribution area may include the horizontal cabling, which is the distribution point for cabling to the equipment distribution areas.
Information Transport Systems (ITS): The physical connectivity elements required to deliver a high-performance, reliable network system infrastructure for all requirements including data, voice, and video.
Infrastructure (telecommunications): A collection of those telecommunications components, excluding equipment, that together provide the basic support for the distribution of information within a building or campus.
Link: A single permanently-installed telecommunications cable element. See also permanent link.
Listed: Equipment included in a list published by an organization, acceptable to the authority having jurisdiction, that maintains periodic inspection of production of listed equipment, and whose listing states either that the equipment or material meets appropriate standards or has been tested and found suitable for use in a specified manner.
Main Distribution Area (MDA): The central point of distribution for the data center structured cabling system which includes the main cross-connect (MC) and may include horizontal cross-connect (HC) when equipment areas are served directly from the main distribution area.
Mechanical Connection: A reversible means of connecting a conductor to a connector through the use of a set screw or other bolt and nut device.
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xii
Mechanical Room: An enclosed space serving the needs of mechanical building systems.
Media: Wire, cable, or conductors used for telecommunications (transmission of signal).
Mesh Bonding Network: The set of metallic components that are interconnected to form the principle means for effectively bonding equipment inside a building to the grounding electrode system.
Metering: Measurement of a condition or set of conditions over a period of time. Metering is primarily a data collection function, intended to support analysis of operational characteristics of a data center.
Monitoring: Continual real-time observation of a condition or set of conditions affecting a data center.
Multimode Optical Fiber: An optical fiber that carries many paths of light.
Patch Cord: A cord used to establish connections on a patch panel.
Patch Panel: A connecting hardware system that facilitates cable termination and cabling administration using patch cords.
Pathway: A facility for the placement of telecommunications cable.
Permanent Link: The permanent, or fixed part of the network comprised of components that will permanently stay in place, such as patch panels, horizontal or backbone cable, and an outlet.
Plenum: A compartment or chamber to which one or more air ducts are connected and forms part of the air distribution system.
Pod: A modular subset of the data center.
Power Usage Effectiveness (PUE): A dimensionless metric which describes how efficiently a data center is designed and operated to conserve power. PUE is defined as the ratio: Total Data Center Energy Consumption (TEC)/Total IT Equipment Energy Consumption (TITEC) or
TEC/TITEC.
Primary Bonding Busbar (PBB): The dedicated extension of the building grounding electrode system for the telecommunications infrastructure. The PBB also serves as the central attachment point for the TBB(s) and equipment.
Rack: Supporting frame equipped with side mounting rails to which equipment and hardware are mounted.
Rack Bonding Busbar (RBB): A busbar within a cabinet, frame or rack.
Rack Bonding Conductor (RBC): The bonding conductor from the rack or rack bonding busbar to the telecommunications equipment bonding conductor.
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xiii
Rack Unit (RU): Vertical mounting space of 1.75 in. for cabinets or racks compliant with IEC 60297 or EIA/ECA-310-E.
Radio Frequency Interference (RFI): Radiated or conducted electromagnetic energy (noise) of a specific frequency that has an undesirable effect on electronic equipment or signal transmissions.
Raised Floor aka Access Floor: A platform with removable panels where equipment is installed, with the intervening space between it and the main building floor used to house the interconnecting cables and at times is used as a means for supplying conditioned air to the IT equipment and the room.
Secondary Bonding Busbar (SBB): A common point of connection for telecommunications system and equipment bonding to ground located in the distributor room.
Service Provider: The operator of any service that furnishes telecommunications content (transmissions) delivered over access provider facilities.
Single-Mode Optical Fiber: An optical fiber that carries only one path of light.
Site Infrastructure Energy Efficiency Rating (SIEER): A dimensionless metric which describes how efficiently a data center is designed and operated to conserve power. SIEER is defined as the ratio: Total Data Center Energy Consumption (TEC)/Total Uninterruptible Power Supply (UPS) Load Energy Consumption (TUPEC) or TEC/TUPSC.
Telecommunications: Any transmission, emission, and receptions of information by cable, radio, optical, or other electromagnetic systems including signaling commonly referred to as “data.”
Telecommunications Room (TR): A telecommunications space that differs from equipment rooms and entrance rooms in that this space is a floor-serving space that provides a connection point between backbone and horizontal cabling. The terms “closet,” “telecom closet,” “phone closet,” “Intermediate Distribution Frame (IDF),” etc. are no longer used.
Blueprints are to use the abbreviation “TR.”
Telecommunications Space: An area used for housing the installation and termination of telecommunications equipment and cable. Telecommunications spaces include telecommunications rooms, entrance rooms, data centers, computer rooms, horizontal pathways, vertical pathways, etc. The term “telecommunications spaces” is used interoperably with the term “IT support space.”
Total Data Center Energy Consumption (TEC): Total of all energy used from all sources required to power all infrastructure and equipment within the confines of a data center.
Total Data Center Physical Infrastructure Energy Consumption: Summation of all energy used by facilities physical infrastructure equipment that supports the computer space. This is the total amount of electricity necessary to run all mechanical and electrical equipment
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xiv providing support to the computer space but does not include the IT Equipment Load Electrical Consumption.
Total IT Equipment Energy Consumption (TITEC): Summation of all energy directly consumed by IT equipment in the data center. IT equipment includes, but is not limited to, computers, storage systems, and networking gear.
Total Renewable Energy Usage by Data Center (RENEW): All electricity consumed by the facility housing the VA computer facility generated from renewable resources (solar, wind, hydro, wave, and similar) locally or through the supplying utility. Hydrocarbon and nuclear utility sources are not considered renewable for the purposes of this value.
Total UPS Load Energy Consumption (TUPEC): Summation of all energy used on the load (not source) side(s) of all UPS system(s) supporting the critical load in the computer space.
Uninterruptible Power Supply (UPS): A buffer between utility power or other power source and a load that requires continuous precise power.
Work Area: A building space where the occupants interact with telecommunications terminal equipment.
Work Area Outlet (WAO): A fixed connector in an equipment outlet assembly consisting of faceplate, body, housing, and one or more telecommunications cabling interface in the building space where the occupants interact with telecommunications terminal equipment.
The term “jack” is no longer used.
Zone Distribution Areas (ZDA): A space in a data center where an equipment outlet or a consolidation point is located.
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xv
References References are effective from their date of publication unless otherwise stated and are inclusive of supplements or addenda published by the standards body, amendments adopted by Authority Having Jurisdiction (AHJ), and superseding standards. The list is not comprehensive; compliance with all applicable standards is required. References consist primarily of nationally recognized “model” building codes, and technical standards developed or adopted by voluntary consensus standards bodies, use of which is required by P.L. 100-678, P.L. 104-113, and OMB Circular A119.
ANSI/ASHRAE Addendum15c, Safety Code for Mechanical Refrigeration
ANSI/ASHRAE Addendum15d, Safety Code for Mechanical Refrigeration
ANSI/ASHRAE Standard 90.4, Energy Standard for Data Centers
ANSI/ASHRAE Standard 188, Legionellosis: Risk Management for Building Water Systems
ANSI/BICSI 004-2018, Information Communication Technology Systems Design and Implementation Best Practices for Healthcare Institutions and Facilities
ANSI/TIA -455-C, General requirements for standard test procedures for optical fibers, cables, transducers, sensors, connecting and terminating devices, and other fiber optic components
ANSI/TIA-455-78B, FOTP-78 IEC 60793-1-40 Optical Fibres - Part 1-40: Measurement Methods and Test Procedures Attenuation
ANSI/TIA-470.110-D, Telecommunications Telephone Terminal Equipment - Transmission Requirements for Analog Telephones with Handsets
ANSI/TIA-492AAAA-B, Detail Specification for 62.5-μm.Core Diameter/125-μm�Cladding� Diameter�Class�Ia�Graded-Index�Multimode�Optical� Fibers
ANSI/TIA-492AAAB-A,� Detail� Specification� for�50-μm�Core�Di ameter/125-μm�Cladding� Diameter�Class�Ia� Graded-Index�Multimode�Optical� Fibers
ANSI/TIA-492AAAC-B,� Detail� Specification� for�850-nm�Laser-�Optimized,� 50-μm�Core� Diameter/125-μm�Cladding� Diameter�Class�Ia� Graded-Index�Multimode�Optical� Fibers
ANSI/TIA-526-7-A,� Measurement� of� Optical� Power�Loss�of� Installed� Single-Mode�Fiber�Cable� Plant,�A doption�o f�IE C�61280 -4-2�e dition� 2:�Fibre-Optic�Communications�Subsystem�Test� Procedures;�Part� 4-2:�Installed� Cable�Plant� Single-Mode�Attenuation� and� Optical� Return� Loss� Measurement
ANSI/TIA-526-14-C,� Optical� Power�Loss�Measurement� of� Installed� Multimode�Fiber�Cable� Plant;�Modification� of�IE C�6128 0-4-1�edition� 2,� Fiber-Optic�Communications�Subsystem�Test� Procedures-�Part�4 -1:�Installed� Cable�Plant-Multimode�Attenuation� Measurement
ANSI/TIA-568.0-D,� Generic�Telecommunications�Cabling� for�Customer�Premises
ANSI/TIA-568.1-D,� Commercial�Building� Telecommunications�Infrastructure�Standard
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xvi
ANSI/TIA-568.2-D, Balanced Twisted-Pair Telecommunications Cabling and Components Standard
ANSI/TIA-568.3-D, Optical Fiber Cabling and Components Standard
ANSI/TIA-568-C.2, Balanced Twisted-Pair Telecommunications Cabling and Components Standards
ANSI/TIA-568-C.2 ERTA, Balanced Twisted-Pair Telecommunications Cabling and Components Standards
ANSI/TIA-568-C.2-1, Balanced Twisted-Pair Telecommunications Cabling and Components Standard, Addendum 1: Specifications�for�100�Ω�Category�8�Cabling
ANSI/TIA-568-C.2-2, Balanced Twisted-Pair Telecommunications Cabling and Components Standard, Addendum 2: Alternative Test Methodology for Category 6A Patch Cords - Addendum to TIA-568-C
ANSI/TIA-568-C.4, Broadband Coaxial Cabling and Components Standard
ANSI/TIA-569-D, Telecommunications Pathways and Spaces
ANSI/TIA-569-D-1, Telecommunications Pathways and Spaces: Addendum 1- Revised Temperature and Humidity Requirements for Telecommunications Spaces - Addendum to
TIA-569-D
ANSI/TIA-598-D, Optical Fiber Cable Color Coding
ANSI/TIA-606-C, Administration Standard for Telecommunications Infrastructure
ANSI/TIA-607-D, Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises
ANSI/TIA-607-C-1, Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises - Addendum to ANSI/TIA-607-C (Superseded by 607-D)
ANSI/TIA-758-B, Customer-Owned Outside Plant Telecommunications Infrastructure Standard
ANSI/TIA-810-B, Telecommunications Telephone Terminal Equipment Transmission Requirements for Narrowband Digital Telephones
ANSI/TIA-862-B, Structured Cabling Infrastructure Standard for Intelligent Building Systems
ANSI/TIA-942-B, Telecommunications Infrastructure Standard for Data Centers
ANSI/TIA-968-B, Telecommunications Telephone Terminal Equipment Technical Requirements for Connection of Terminal Equipment to the Telephone Network
ANSI/TIA-968-B-1, Telecommunications Telephone Terminal Equipment Technical Requirements for Connection of Terminal Equipment to the Telephone Network-Addendum 1 - Addendum to TIA-968-B
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xvii
ANSI/TIA-968-B-2, Telecommunications Telephone Terminal Equipment Technical Requirements for Connection of Terminal Equipment to the Telephone Network- Addendum 2 - Addendum to TIA-968-B
ANSI/TIA-968-B-3, Telecommunications Telephone Terminal Equipment Technical Requirements for Connection of Terminal Equipment to the Telephone Network- Addendum 3 - Addendum to TIA-968-B
ANSI/TIA-1005-A, Telecommunications Infrastructure Standard for Industrial Premises
ANSI/TIA-1005-A-1, Telecommunications Infrastructure Standard for Industrial Premises
Addendum 1- M12-8 X-Coding Connector (Addendum to TIA-1005-A)
ANSI/TIA-1152-A, Requirements for Field Test Instruments and Measurements for Balanced Twisted-Pair Cabling
ANSI/TIA-1179, Healthcare Facility Telecommunications Infrastructure
ANSI/TIA/EIA-455-1-B, Cable Flexing for Fiber Optic Interconnecting Devices
ANSI/TIA/EIA -455-2C, Impact Test Measurements for Fiber Optic Devices
ANSI/TIA/EIA-455-5C, FOTP-5 Humidity Test Procedure for Fiber Optic Components
ANSI/TIA/EIA-455-8, FOTP-8 Measurement of Splice or Connector Loss and Reflectance Using an OTDR
ANSI/TIA/EIA-455-34A, FOTP-34 Interconnection Device Insertion Loss Test
ANSI/TIA/EIA-455-171A, FOTP-171 Attenuation by Substitution Measurement for Short- Length Multimode Graded-Index and Single-Mode Optical Fiber Cable Assemblies
ANSI/TIA/EIA-455-185, FOTP-185 Strength of Coupling Mechanism for Fiber Optic Interconnecting Devices
ANSI/TIA/EIA-455-188, FOTP-188 Low Temperature Testing of Fiber Optic Components
ANSI/TIA/EIA-492CAAB, Detail Specification for Class IVa Dispersion-Unshifted Single-Mode Optical Fibers with Low Water Peak
ANSI/TIA/EIA-568-Set, Commercial Building Telecommunications Cabling Standard
American Society of Heating and Air-Conditioning Engineers (ASHRAE) Standard 52.2, Method of Testing General Ventilation Air-Cleaning Devices Removal by Particle Size (ANSI approved)
ASHRAE 62.1, Ventilation for Acceptable Indoor Air Quality
ASHRAE 135, BACnet - A Data Communication Protocol for Building Automation and Control Networks
ASHRAE 135 ERTA, BACnet - A Data Communication Protocol for Building Automation and Control Network
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xviii
ASHRAE 135 INT 1, BACnet - A Data Communication Protocol for Building Automation and Control Network
ASHRAE 135 INT 2, BACnet - A Data Communication Protocol for Building Automation and Control Network
ASTM B258, Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors
ASTM B539, Standard Test Methods for Measuring Resistance of Electrical Connections (Static Contacts)
ASTM D4565, Standard Test Methods for Physical and Environmental Performance Properties of Insulations and Jackets for Telecommunications Wire and Cable
ASTM D4566, Standard Test Methods for Electrical Performance Properties of Insulations and Jackets for Telecommunications Wire and Cable
ATIS 0600311, DC Power Systems Telecommunications Environment Protection
ATIS 0600336, Design Requirements for Universal Cabinets and Framework
BICSI 002, Data Center Design and Implementation Best Practices
BICSI ITSIMM, Information Technology Systems Installation Methods Manual (ITSIMM) - 7th Edition
BICSI OSPDRM, Outside Plant Design Reference Manual (OSPDRM) - 5th Edition
BICSI TDMM, Telecommunications Distribution Methods Manual - 13th Edition; Volumes I &
II
BICSI/NECA 568, Standard for Installing Commercial Building Telecommunications Cabling
BICSI/NECA 607 Standard for Telecommunications Bonding and Grounding Planning and Installation Methods for Commercial Buildings 2011
CSI MASTERFORMAT ™ 2004 EDITION NUMBERS & TITLES Construction Specifications Institute (CSI)
ECIA EIA/ECA-310-E, Cabinets, Racks, Panels, and Associated Equipment
Executive Order No. 13693 “Federal Leadership on Climate Change and Environmental Sustainability” 2015
Executive Order No. 13834 “Efficient Federal Operations” 2018
Federal Information Processing Standard (FIPS) 200, Minimum Security Requirements for Federal Information and Information Systems
IEEE STD 81, Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Grounding System.
IEEE STD 446, Emergency and Standby Power Systems for Industrial and Commercial Applications (Orange Book)
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xix
MIL-STD-188-124B, Grounding, Shielding, and Bonding
National Energy Policy Act of 2005-SEC. 203. FEDERAL PURCHASE REQUIREMENT
NEMA FG 1, Fiberglass Cable Tray Systems - Revision No.1
NEMA VE 1, METAL CABLE TRAY SYSTEMS
NEMA VE 2, Cable Tray Installation Guidelines - Incorporates Errata 2016
NFPA 70, National Electrical Code®
NFPA 70E, Standard for Electrical Safety in the Workplace
NFPA 72, National Fire Alarm and Signaling Code
NFPA 75, Standard for the Fire Protection of Information Technology Equipment
NFPA 99, Healthcare Facilities Code
NFPA 101, Life Safety Code
NFPA 780, Standard for the Installation of Lightning Protection Systems
NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems
PG 18-12 OIT Design Guide, Office of Construction and Facilities Management Design Guide
Physical Security and Resiliency Design Manual
Presidential Memorandum 131205, “Federal Leadership on Energy Management”
TIA-232-F, Interface Between Data Terminal Equipment and Data Circuit-Terminating Equipment Employing Serial Binary Data Interchange
TIA-455-6-B, FOTP-6 Cable Retention Test Procedure for Fiber Optic Cable Interconnecting Devices
TIA-455-13-A, FOTP-13 Visual and Mechanical Inspection of Fiber Optic Components, Devices, and Assemblies
TIA-455-21-A, FOTP-21 Mating Durability of Fiber Optic Interconnecting Devices
TIA-455-36-A, FOTP-36 Twist Test for Fiber Optic Connecting Devices
TIA-455-107-A, FOTP-107 Determination of Component Reflectance or Link/System Return Loss Using a Loss Test Set
TIA-470.000-E, Telecommunications Telephone Terminal Equipment Overview of Performance Standards for Analog Telephones
TIA-485-A, Electrical Characteristics of Generators and Receivers for Use in Balanced Digital Multipoint Systems
TIA-492CAAA, Detail Specification for Class IVa Dispersion-Unshifted Single-Mode Optical Fibers
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xx
TIA-561, Simple 8-Position Non-Synchronous Interface Between Data Terminal Equipment and Data Circuit-Terminating Equipment Employing Serial Binary Data Interchange
TIA-568.2-D, Balanced Twisted-Pair Telecommunications Cabling and Components Standard
TIA-604-3-B, FOCIS 3 Fiber Optic Connector Intermateability Standard- Type SC and SC-APC
TIA-968-B ERTA, Telecommunications Telephone Terminal Equipment Technical Requirements for Connection of Terminal Equipment to the Telephone Network
TIA/EIA-455-4C, FOTP-4 Fiber Optic Component Temperature Life Test
TIA TSB-153, Static Discharge Between LAN and Data Terminal Equipment
TIA TSB-155-A, Guidelines for the Assessment and Mitigation of Installed Category 6 Cabling to Support 10GBASE-T
TIA TSB-184-A, Guidelines for Supporting Power Delivery Over Balanced Twisted-Pair Cabling
TIA TSB-184-A-1 (Addendum to TSB-184-A), Guidelines for Supporting Power Delivery Over Balanced Twisted-Pair Cabling-Addendum 1- use of 28 AWG cords
UL 444, UL Standard for Safety Communications Cables - 5th Edition
UL 444 BULLETIN, UL Standard for Safety Communications Cables
VA DIRECTIVE 6500, INFORMATION SECURITY PROGRAM
VA Electrical Design Manual
VA Fire Protection Design Manual
VA HVAC Design Manual
VA Lighting Design Manual
VA OIT Design Guide
VA Operations and Maintenance Standard for Telecommunications Spaces (Pending publication)
VA Physical Security and Resiliency Design Manual
VA Sustainable Design Manual
VA Telecommunications and Special Telecommunications Systems Design Manual
VHA Directive 1061, Prevention of Healthcare-Associated Legionella Disease and Scald Injury from Potable Water Distribution Systems
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xxi
Acronyms and Initialisms For other acronyms and initialisms, VA employees and contractors with VA intranet access may refer to the full VA Acronym List or VA Acronym Lookup. All others may inquire with Enterprise Data Center and Infrastructure Engineering (DCIE) via e-mail at VAITESEDatacenterEngineering2@va.gov.
Acronym Definition
AC Alternating Current
ACEG Alternating Current Equipment Ground
AES Advanced Encryption Standard
AHJ Authority Having Jurisdiction
ANSI American National Standards Institute
APC Angled Physical Contact
ARU Air Removal Units
ASD Aspirated Smoke Detection
ASHRAE American Society of Heating and Air-Conditioning Engineers
ATS Automatic Transfer Switch
AWG American Wire Gauge
BACnet Building Automation and Control Networking Protocol
BAS Building Automation System
BCM Branch Circuit Monitoring
BCP Branch Circuit Panelboard
BICSI Building Industry Consulting Service International
BMS Battery Monitoring System
CAB Change Advisory Board
CANbus Controller Area Network Bus
CDC Core Data Center
CE Clinical Engineering
CFD Computational Fluid Dynamics
CFM Cubic Feet Per Minute
CFM VA Office of Construction and Facilities Management
CM Communications
CMMS Computerized Maintenance Management System https://vaww.va.gov/acronyms/fulllist.cfm https://vaww.va.gov/acronyms/ mailto:VAITESEDatacenterEngineering2@va.gov
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xxii
Acronym Definition
CMOP Consolidated Mail Outpatient Pharmacy
CMP Communications Plenum
CMR Communications Riser
CPAC Consolidated Patient Account Center
CRAC Computer Room Air Conditioner
CRAH Computer Room Air Handler
CSC Campus Support Center
DC Direct Current
DCIE Data Center and Infrastructure Engineering
DCIM Data Center Infrastructure Management
DR Disaster Recovery
DX Direct Expansion
EBSR Enterprise Baseline and Standard Review
EC Electronically Commutated
ED Equipment Distributor
EDICT Enterprise Data Center Infrastructure Collaboration Team
EGS Earth Ground System
EIA Electronic Industries Alliance
EMCS Energy Management Control System
EPO Emergency Power Off
ESD Electrostatic Discharge
DX Direct Expansion
FB Front Bottom
FCU Fan Coil Units
FEC Facility Total Electrical Consumption
FM Front Middle
FMS Facilities Management Service
FSC Financial Services Center
FSS Facilities Standards Service
FT Front Top
GbE Gigabit Ethernet
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xxiii
Acronym Definition
Gb/s Gigabit per second
HA High Availability
HAC Health Administration Center
HC Horizontal Cross Connect
HCC Health Care Centers
HEC Health Eligibility Center
HD High Density
HD Horizontal Distribution
HDA Horizontal Distribution Area
HVAC Heating, Ventilation, and Air Conditioning
IAW In Accordance With
ICC Intermediate Cross Connect
IEC International Electrotechnical Commission
IEEE Institute of Electrical and Electronics Engineers
IO Infrastructure Operations
ISP Inside Plant
IT Information Technology
ITOPS IT Operations and Services
ITS Information Transport Systems
LAN Local Area Network
LED Light Emitting Diode
LFMC Liquid-tight Flexible Metal Conduit
LP Limited Power
LPS Lightning Protection System
MCC Main Cross Connect
MM Multimode
MPDU Master Power Distribution Unit
MPO Multi-Fiber Push On
MSC Mission Support Center
NCA National Cemetery Administration
NDCOL National Data Center Operations and Logistics
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xxiv
Acronym Definition
NEC® National Electrical Code®
NEMA National Electrical Manufacturers Association
NFPA National Fire Protection Association
NIC Network Interface Card
NSC Network Support Center
O&M Operations and Maintenance
OIFO Office of Information Field Office
OIT Office of Information and Technology
OM Optical Multimode
OMB Office of Management & Budget
OPC Outpatient Clinic
PBB Primary Bonding Busbar
PDU Power Distribution Unit
PoE Power-over-Ethernet
PVC Polyvinyl Chloride
PS Power Supply
PUE Power Usage Effectiveness
R&D Research & Development
RB Rear Bottom
RBB Rack Bonding Busbar
RBC Rack Bonding Conductor
RCDD Registered Communications Distribution Designer
RDC Regional Data Center
RDC Remote Distribution Cabinet
RH Relative Humidity
RM Rear Middle rPDU Rack Power Distribution Unit
RT Rear Top
RT Refrigeration Ton
RU Rack Unit
SBB Secondary Bonding Busbar
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xxv
Acronym Definition
SAN Storage Area Network
SD Solution Delivery
SD Standard Density
SIEER Site Infrastructure Energy Efficiency Rating
SM Single-mode
SSL Secure Sockets Layer
SWDM Short Wavelength Division Multiplexing
TBB Telecommunication Bonding Backbone
TEBC Telecommunications Equipment Bonding Conductor
TEC Total Data Center Energy Consumption
TIA Telecommunications Industry Association
TIL Technical Information Library
TITEC Total IT Equipment Energy Consumption
TPIEC Total Data Center Physical Infrastructure Energy Consumption
TR Telecommunications Room
TUPSC Total UPS Load Energy Consumption
UL Underwriters Laboratories Inc
UPS Uninterruptible Power Supply
UTP Unshielded Twisted Pair
VA Department of Veterans Affairs
VAMC Veterans Affairs Medical Center
VACO VA Central Office
VBA Veterans Benefits Administration
VED Vertical Exhaust Duct
VESDA Very Early Smoke Detection Apparatus
VHA Veterans Health Administration
VLA Vented Lead Acid
VRLA Valve Regulated Lead Acid
VSD Variable Speed Drive
WC Water Column zPDU Zone Power Distribution Unit
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xxvi
Contributors This Standard is maintained by the Enterprise Data Center Infrastructure Collaboration Team.
The following subject matter experts have contributed to the development of this document as indicated:
Table 2: Contributors
Name Solution Delivery Role
Michael Julian
Office of Information and Technology (OIT), IT Operations and Services (ITOPS), Solution Delivery (SD)-Data Center and Infrastructure Engineering (DCIE) (OIT ITOPS SD DCIE)
SME,
Telecommunications Distribution Design, Original Standard Author
Kelly Bates OIT ITOPS SD DCIE SME, Electrical and Mechanical Design
Kevin Grzelka OIT ITOPS SD DCIE
SME,
Telecommunications Space Design, Template Author and Custodian
John Wernau OIT ITOPS SD DCIE SME, Energy Efficiency and Airflow Design, Standard Custodian
Curtis Derbigny OIT ITOPS SD DCIE SME, Systems Integration
Name Infrastructure Operations Role
William Pittman OIT ITOPS Infrastructure Operations (IO) National Data Center Operations & Logistics (NDCOL) SME, Director, NDCOL
Jack McLain OIT ITOPS IO NDCOL
SME, Director, Data Center Facilities, Connectivity and Physical Security
Mitch Cobb OIT ITOPS IO NDCOL SME
Lawrence Manzanera OIT ITOPS IO NDCOL SME
Robert Burke OIT ITOPS IO NDCOL SME
Clay Whitney OIT ITOPS IO NDCOL SME
Wesley Patton OIT ITOPS IO NDCOL SME
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| xxvii
Name Infrastructure Operations (cont.) Role
Ken Girardi OIT ITOPS IO NDCOL SME
Robert Hoag OIT ITOPS IO NDCOL SME
Robert Skipper OIT ITOPS IO NDCOL SME
Name Construction and Facilities Management Role
Bryan Unger Office of Construction and Facilities Management (CFM) Facilities Standards Service (FSS)
SME, Coordinator – CFM Technical Information Library (TIL)
Dave Tashakkori CFM FSS SME
Gary Krupa CFM FSS SME
Name 508 Office Role
Myra Coffield Section 508 Office Technical Writing, CommonLook Office
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| 1
1 Introduction
1.1 Purpose
The Infrastructure Standard for Telecommunications Spaces (The Standard) serves as the master reference document of criteria for Department of Veterans Affairs (VA) facility Information Technology (IT) support infrastructure. It defines the technical requirements necessary to maintain optimum reliability and efficiency within VA facilities and computing centers.
1.2 Scope
The Standard shall be applied to all aspects of IT support infrastructure at all VA owned, operated, and leased spaces. “All aspects” includes, but is not limited to planning, design, construction, sustainment (operations, maintenance, repair), restoration, modernization, and administration. “All VA spaces” includes but is not limited to VA Central Office (VACO) facilities and all field facilities managed by Veterans Health Administration (VHA), Veterans Benefits Administration (VBA), and the National Cemetery Administration (NCA).
IT Support Infrastructure is defined as all passive telecommunications and IT equipment, and supporting physical space and equipment, supporting:
· Copper and fiber cabling Information Transport Systems (ITS)
· IT equipment and systems (servers, storage, network switching and distribution, etc.)
· Telecommunications spaces, Telecommunications Rooms (TR), entrance rooms, data centers, horizontal distribution pathways, vertical distribution pathways, etc.
· Telecommunications equipment and systems (local and wide area network, telephone, cable television, physical security IT system, etc.)
· Physical infrastructure equipment and systems necessary to support active equipment operations at the required availability and sustainability levels (power distribution, environmental conditioning, monitoring and metering equipment, grounding, etc.)
1.3 Administration
The Standard shall be implemented without modification, except when required by an Authority Having Jurisdiction (AHJ), Federal, state, or local laws and codes. Additional requirements of AHJs shall be provided to Enterprise Data Center and Infrastructure Engineering (DCIE) for evaluation of project application and possible amendment of The Standard.
Projects in the planning, design, or implementation phases shall contact DCIE for assistance in telecommunications space design and standards compliance.
Existing IT support infrastructure that does not conform to The Standard shall be brought into compliance during routine tech refresh, lifecycle replacement, upgrades, new installations, or renovations of existing space.
INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES| 2
Facility managers should take every opportunity to bring telecommunications spaces into compliance with The Standard through incremental changes between scheduled sustainment activities.
Area Managers shall ensure that all contracting officers, IT personnel, and engineering staff are aware and make use of The Standard.
1.3.1 Request for Variance from Infrastructure Standards