Amendment 0002 Attachment_Ethernet Jacket Color Table 3-2_Feb2016.pdf

PDF 100 KB Posted

Attached to
EHRM Birmingham Infrastructure Upgrades Federal contract opportunity
Solicitation number
36C77623B0026
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document outlines technical requirements for horizontal cabling and work area outlets for a Veterans Affairs Medical Center infrastructure upgrade project. It specifies that horizontal cabling must be category 5e or higher, installed in raceways, and have jackets colored according to the standards in Table 3-2. Wireless equipment must be coordinated with the VA's Spectrum Management and COMSEC Service to avoid interference. The related federal contract opportunity is for infrastructure upgrades to the Birmingham VAMC, including furnishing labor, materials, and services to complete the Electronic Health Records Modernization project.

View the file

Other files for this federal contract opportunity

Other files attached to EHRM Birmingham Infrastructure Upgrades, newest first.
File Type Posted
Attachment to Amendment 0008_Specification 01 33 00 Submittal Procedures 7-28-2023.pdf PDF
Amendment 0008_36C77623B0026_QAs and Revised Specs_28JUL2023.pdf PDF
Attachment to Amendment 0008_Specification Section 27 10 00 - Control and Signal Wiring_27JUL2023.pdf PDF
Amendment 0007_36C77623B0026_Spec 096519 Flooring_26JUL2023.pdf PDF
Attachment to Amendment 0007_Specification Section 096519 Resilient Tile Flooring_26JUL2023.pdf PDF
Site Visit Attendance Sheet_21JULY2023.pdf PDF
Amendment 0006_36C77623B0026_25JUL2023.pdf PDF
Amendment 0005_36C77623B0026_24JUL2023.pdf PDF
Amendment 0004_36C77623B0026_20JUL2023.pdf PDF
Amendment 0003_36C77623B0026_18JUL2023.pdf PDF
36C77623B0026_Amendment 0002_11JUL2023.pdf PDF
Amendment 0001_36C77623B0026 0001_1_30JUN2023.pdf PDF
Site Visit Attendance Sheet_21JUNE2023.pdf PDF
Signed Site Visit Attendance Sheet_21JUNE2023.pdf PDF
36C77623B0026_09JUN2023.docx DOCX document
Attachment 9 - VA Notice Limitations on Subcontracting - Construction (JAN 2023) (DEV).docx DOCX document
Attachment 5 Design Narrative Birmingham EHRM 08-18-2022.pdf PDF
Attachment 3(a) HazMaterials Survey Birmingham EHRM Part_1_of_2.pdf PDF
Attachment 1(b) Specifications Birmingham EHRM 08-31-2022_Part_2_of_2.pdf PDF
Attachment 7(c) OIT-InfrastrucStdTelecomSpaces_Part 3 of 3.pdf PDF
Attachment 8 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 4 Scope of Work Birmingham EHRM 05-19-2023.pdf PDF
Attachment 2(c) Drawings Part_3_of_5 Birmingham EHRM 09-01-2022.pdf PDF
Attachment 10(b) Wage Determination AL20230096_ShelbyCounty_27JAN2023.pdf PDF
Attachment 10(a) Wage Determination AL20230087_JeffersonCounty_27JAN2023.pdf PDF
Attachment 7(b) OIT-InfrastrucStdTelecomSpaces_Part 2 of 3.pdf PDF
Attachment 7(a) OIT-InfrastrucStdTelecomSpaces_Part 1 of 3.pdf PDF
Attachment 2(d) Drawings Part_4_of_5 Birmingham EHRM 09-01-2022.pdf PDF
Attachment 2(b) Drawings Part_2_of_5 Birmingham EHRM_09-01-2022.pdf PDF
Attachment 3(b) HazMaterial Survey Birmingham EHRM 09-01-2022_Part_2_of_2.pdf PDF
Attachment 6 Submittal Register Birmingham EHRM 08-18-2022.xlsx XLSX spreadsheet
Attachment 2(a) Drawings Part_1_of_5 521-20-901 Birmingham EHRM 09-01-2022 Rev.pdf PDF
Attachment 2(e) Drawings Part_5_of_5 Birmingham EHRM 09-01-2022.pdf PDF
Attachment 1(a) Specifications Part_1_of_2 Birmingham EHRM 08-31-2022.pdf PDF
Show all 34

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CHAPTER 3: WORK AREA OUTLETS AND HORIZONTAL CABLING

REQUIRMENTS

(g) All horizontal TIP wire and cabling shall be installed in a raceway system, which may consist of a mixture of conduits, enclosed cable trays, open wireways, covered cable ducts, Nationally Recognized Testing Laboratory (NRTL)-approved partitioned communications wireways, and/or cable ladders, except as specifically disallowed by SMCS 005OP2H3 .

(h) TIP wires or cables may only be installed inside gypsum-board walls using flexible conduit, where specifically approved in writing by the Facility’s OI&T Chief or Chief Engineer and SMCS for each particular location.

TIP HORIZONTAL MEDIA SELECTION

Design professional must specify horizontal cable based on the project specific needs (See Table 3-1) and according to the information contained herein.

BALANCED TWISTED PAIR CABLING

Copper conductor balanced twisted pair cable is required in the horizontal TIP (See Table 3-1). Aluminum, copper clad aluminum, or copper clad steel conductors and like wires and cables are not permitted.

TABLE 3-1 Balanced Twisted Pair CENTER HERE

Category Max.

Frequency

Minimum Field Tester Level

Category 3 (included ONLY for Reference)

16 MHz NOT TO BE

USED IN VA

PROJECTS

Category 5e 100 MHz Level IIe Category 6* 250 MHz Level III Category 6A* 500 MHz Level IIIe

* WLAN may require cable with data rate in excess of 1 Gb/s confirm required cable category and quantity of cables to WAPs with active electronic manufacturer before designing horizontal cable and pathway.

(Note: Category 5e is recommended. Use higher category (6 or 6A) for specialized powered systems technically approved by SMCS 005OP2H3H2, and the Contracting Officer Representative

(COR)).

Jacket color shall be per Table 3-2. Colors for cable jackets refer to horizontal cable not patch cords. OSP cable color shall be black, regardless of category, to accommodate environmental requirements.

3‐1

CHAPTER 3: WORK AREA OUTLETS AND HORIZONTAL CABLING

REQUIRMENTS

TABLE 3-2 Jacket Color

System Cable Jacket Voice White Data Yellow

Data Green

Data Grey Wireless Orange Video Surveillance Violet

Nurse Call Blue

Fire Alarm Red

BAS & DAS Black

When selecting cable, consider PoE effects on the cable installation.

Bundling PoE cables can cause an increased temperature inside the bundle and require larger conduit. Derating of cable is required to compensate for heat buildup.

Shielded cable may be required. F/UTP, shielded or screened cable, has advantages over UTP including improved heat dissipation, higher immunity from EMI in exterior locations, protection from alien crosstalk due to mixing of cables in pathways and spaces.

Power on balanced twisted pair shall not exceed 60 volts.

When using consolidation points and MUTOAS derate cable per standards; See Paragraph 3.4.1.1

WIRELESS AND FREQUENCY COORDINATION

Contact VACO’s AHJ for FMS Special Communications, Low Voltage and other Communication Systems, Spectrum Management and COMSEC Service (SMCS 005OP2H3) for each wireless item and equipment/system for Spectrum and Frequency Coordination.

(a) Existing Building

Coordinate with VA to obtain results of a series of VA biomed engineering baseline RF measurements using a spectrum analyzer to identify the existing RF environment and areas of potential interference.

(b) New Construction

Obtain operating frequency band of equipment from the OEM and co ordinate with SMCS 005OP2H3 to determine whether the new equipment will cause, or be a victim of, interference.

(c) Interference Resolution