This document provides details for a federal contract opportunity to upgrade a 3D printer room at Rickenbacker Air Base in Columbus, Ohio. The project involves modifications to Facility Room 112 such as installing a new 50-amp power supply, additional overhead lighting, and a double-door access point. The project magnitude is between $25,000 to $100,000 and will be solicited as a competitive small business set-aside. The solicitation number is W50S8P24B0001 and the project title is NLZG242002 Building 885 3D Printer Install. The period of performance is 120 days but power and door work must be completed within approximately 35 days of contract award. The Department of the Army National Guard is the contracting agency.
View the file
Other files for this federal contract opportunity
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USACE / NAVFAC / AFCEC UFGS-26 51 00 (May 2020)
Change 2 - 11/21
Preparing Activity: NAVFAC Superseding UFGS-26 51 00 (May 2016)
UNIFIED FACILITIES GUIDE SPECIFICATIONS
References are in agreement with UMRL dated October 2023
SECTION TABLE OF CONTENTS
DIVISION 26 - ELECTRICAL
SECTION 26 51 00
INTERIOR LIGHTING
05/20, CHG 2: 11/21
PART 1 GENERAL
1.1 REFERENCES
1.2 RELATED REQUIREMENTS
1.3 DEFINITIONS
1.4 SUBMITTALS
1.5 QUALITY ASSURANCE
1.5.1 Luminaire Drawings
1.5.2 Luminaire Design Data
1.5.3 ANSI/IES LM-79 Test Report
1.5.4 ANSI/IES LM-80 Test Report
1.5.5 ANSI/IES TM-21 Test Report
1.5.6 ANSI/IES TM-30 Test Report
1.5.7 LED Driver and Dimming Switch Compatibility Certificate
1.5.8 Photometric Plan
1.5.8.1 Computer-generated Photometric Plans
1.5.8.2 Schematic Photometric Plan Calculations
1.5.8.3 Final Photometric Plan Calculations
1.5.9 Occupancy/Vacancy Sensor Coverage Layout
1.5.10 Test Laboratories
1.5.11 Regulatory Requirements
1.5.12 Standard Products
1.5.12.1 Alternative Qualifications
1.5.12.2 Material and Equipment Manufacturing Date
1.6 WARRANTY
1.6.1 Luminaire Warranty
1.6.2 Lighting Controls Warranty
1.7 OPERATION AND MAINTENANCE MANUALS
1.7.1 Lighting System
1.7.2 Lighting Control System
PART 2 PRODUCTS
2.1 PRODUCT COORDINATION
SECTION 26 51 00 Page 1
2.2 LUMINAIRES
2.2.1 Luminaire Samples
2.2.2 Luminaires
2.2.2.1 Luminaire Conversion Kits
2.2.3 Luminaires for Hazardous Locations
2.3 LIGHT SOURCES
2.3.1 LED Light Sources
2.3.1.1 Linear LED Lamps
2.4 LED DRIVERS
2.4.1 Remote LED Drivers
2.5 LIGHTING CONTROLS
2.5.1 System
2.5.1.1 Localized Control Systems
2.5.1.1.1 Local Area Controller
2.5.1.2 Centralized Control Systems
2.5.1.2.1 Lighting Relay Panel
2.5.1.2.2 Lighting Control Panel
2.5.1.2.3 Gateway
2.5.1.2.4 Lighting Contactor
2.5.2 Devices
2.5.2.1 Switches
2.5.2.2 Digital Switch Timers
2.5.2.3 Wall Box Dimmers
2.5.2.4 Scene Wallstations
2.5.2.5 Occupancy/Vacancy Sensors
2.5.2.5.1 Passive Infrared Sensors
2.5.2.5.2 Ultrasonic Sensors
2.5.2.5.3 Dual Technology Sensors
2.5.2.5.4 High Bay Sensors
2.5.2.5.5 Integrated Sensors
2.5.2.5.6 Power Packs
2.5.2.6 Photosensors
2.5.2.7 Time Clocks
2.6 EXIT AND EMERGENCY LIGHTING EQUIPMENT
2.6.1 Exit Signs
2.6.1.1 Exit Signs with Battery Backup
2.6.1.2 Remote-Powered Exit Signs
2.6.2 Emergency Lighting Unit (ELU)
2.6.3 LED Emergency Drivers
2.6.4 Self-Diagnostic Circuitry for LED Drivers
2.6.5 Mini Inverters
2.6.6 Central Emergency Lighting System
2.6.6.1 Operation
2.6.6.2 Charger
2.6.6.3 Batteries
2.6.6.4 Accessories
2.6.6.5 Enclosure
2.7 LUMINAIRE MOUNTING ACCESSORIES
2.7.1 Suspended Luminaires
2.7.2 Recess and Surface Mounted Luminaires
2.7.3 Luminaire Support Hardware
2.7.3.1 Wire
2.7.3.2 Wire for Humid Spaces
2.7.3.3 Threaded Rods
2.7.3.4 Straps
2.7.4 Power Hook Luminaire Hangers
2.8 EQUIPMENT IDENTIFICATION
2.8.1 Manufacturer's Nameplate
2.8.2 Labels
SECTION 26 51 00 Page 2
2.9 FACTORY APPLIED FINISH
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Light Sources
3.1.2 Luminaires
3.1.2.1 Suspended Luminaires
3.1.2.2 Recessed and Semi-Recessed Luminaires
3.1.2.3 Field Applied Painting
3.1.3 LED Drivers
3.1.3.1 Remote LED Drivers
3.1.4 Exit Signs
3.1.5 Lighting Controls
3.1.5.1 Scene Wallstations
3.1.5.2 Occupancy/Vacancy Sensors
3.1.5.3 Photosensors
3.2 FIELD QUALITY CONTROL
3.2.1 Tests
3.2.1.1 Lighting Control Verification Tests
3.2.1.2 Emergency Lighting Test
3.3 CLOSEOUT ACTIVITIES
3.3.1 Commissioning
3.3.2 Training
3.3.2.1 Maintenance Staff Training
3.3.2.2 End-User Training
-- End of Section Table of Contents --
SECTION 26 51 00 Page 3
USACE / NAVFAC / AFCEC UFGS-26 51 00 (May 2020)
Change 2 - 11/21
Preparing Activity: NAVFAC Superseding UFGS-26 51 00 (May 2016)
UNIFIED FACILITIES GUIDE SPECIFICATIONS
References are in agreement with UMRL dated October 2023
SECTION 26 51 00
INTERIOR LIGHTING
05/20, CHG 2: 11/21
NOTE: This guide specification covers lighting and lighting control system requirements for interior installations.
This specification does not cover all possible methods or requirements for interior lighting;
therefore, designer should add special information required to suit a specific project. Industry publications and websites exist to aid the designer in choosing the best lighting system for the project. These include, but are not limited to, the Illuminating Engineering Society (IES) 'Lighting Handbook, 10th Edition' and 'RP-1-12 - American National Standard Practice for Office Lighting';
National Fire Protection Association (NFPA) 101 - 'Life Safety Code'; the DesignLights Consortium (DLC); US Department of Energy's Federal Energy Management Program (FEMP) and ENERGY STAR program.
Adhere to UFC 1-300-02 Unified Facilities Guide Specifications (UFGS) Format Standard when editing this guide specification or preparing new project specification sections. Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable item(s) or insert appropriate information.
Remove information and requirements not required in respective project, whether or not brackets are present.
Comments, suggestions and recommended changes for this guide specification are welcome and should be submitted as a Criteria Change Request (CCR).
NOTE: For supplemental information regarding
SECTION 26 51 00 Page 4
Section 26 51 00, including PDF and CAD downloads of luminaire plates, go to:
http://www.wbdg.org/ffc/dod/unified-facilities-guide-specifications-ufgs/ufg
NOTE: This section contains the following luminaire plates (also referred to as 'sketches' or 'details'.) These are available in metric (SI) and U.S. Customary (IP) system dimensions. Plate titles and style numbers are unchanged for both units.
Do not include list of plates, or plates themselves, in project specifications. Use luminaire plates as details on drawings whenever possible. If special features are required for a project, do not modify plates, but indicate these changes on notes in luminaire schedule. The "NL" style numbers and dates must remain on the drawing details. If additional luminaire types are needed that are not covered in plates, provide additional sketches or details on drawings, but do not label as NL plate type.
Luminaire list is now divided into 2004 sketches and 2016 sketches. Use the 2016 sketches instead of the 2004 unless use of legacy technology is strictly necessary. Indicate on luminaire schedule if the luminaire is from the 2016 or 2004 list if the same sketch number is used.
2016 PLATE
NUMBER
TITLE
NL-1 DIRECT/INDIRECT LED LUMINAIRE
NL-2 FLAT LENS LED LUMINAIRE
NL-3 SURFACE LED WRAPAROUND
NL-4 LINEAR LED SLOT
NL-5 ROUND LED LUMINAIRE
NL-6 DIRECT/INDIRECT LED PENDANT
NL-7 DIRECT WAL-MOUNTED LINEAR
NL-8 INDIRECT WALL MOUNT
NL-9 RECESSED LINEAR WALL WASH
NL-10 INDIRECT COVE LIGHT
NL-11 ADJUSTABLE RECESSED DOWNLIGHT
NL-12 FIXED RECESSED DOWNLIGHT
NL-13 WALLWASH RECESSED DOWNLIGHT
NL-14 LED TRACK LIGHTING
NL-15 LED UNDERCABINET LIGHT
NL-16 LED ROUND CEILING SURFACE MOUNT
SECTION 26 51 00 Page 5
2016 PLATE
NUMBER
TITLE
NL-17 LED DECORATIVE ACCENT PENDANT
NL-18 LED DECORATIVE WALL SCONCE
NL-19 LED UP/DOWN WALL SCONCE
NL-20 LED FOOD SERVICE LIGHT
NL-21 LED HIGH ABUSE LIGHT
NL-22 LED HAZARDOUS LOCATION LIGHT
NL-23 LED INDUSTRIAL LIGHT
NL-24 LED INDUSTRIAL HIGH-BAY
NL-25 LED INDUSTRIAL LOW-BAY
NL-26 LED EMERGENCY LIGHTING UNIT (ELU)
NL-27 EDGE-LIT EXIT SIGN
NL-28 EXIT SIGN
NL-29 LED NICHE POOL LUMINAIRE
NOTE: Do not include this index in project specification.
NOTE: Include the following information on the project drawings:
1. Luminaire schedule indicating luminaire symbol;
luminaire type; NL plate number and type designation; light source; voltage; input watts;
delivered lumen output; efficacy; CCT; CRI; LED driver; dimming; mounting; BUG rating if applicable;
and any other applicable options or notes.
2. Location and mounting height of all luminaires (including normal and emergency) for each given area or room.
3. Referenced NL plate number or detail (if no NL plate is available) for each luminaire type provided.
4. All accessories required, such as mounting hardware, emergency battery back-up inverters, remote LED drivers, sensors and control equipment, and central emergency system components.
5. Occupancy, vacancy, and photosensor locations, mounting, and technology type. For occupancy and vacancy control, note if the sensor is Passive Infrared, Ultrasonic, or Dual-Tech. For photosensor, note if the sensor is open-loop or closed-loop.
SECTION 26 51 00 Page 6
6. Control strategy description for each given area or room. If the lighting controls manufacturer will not be providing shop drawings showing sensor locations and mounting heights, provide this information on the project plans.
7. Manual control wall stations, switches, and dimmers.
8. EMI filters, surge suppression, or shielding required.
NOTE: Demolition work that involves disposal of fluorescent and HID lamps and ballasts will require the use of Section 02 84 16 HANDLING OF LIGHTING BALLASTS AND LAMPS CONTAINING PCBs AND MERCURY.
PART 1 GENERAL
1.1 REFERENCES
NOTE: This paragraph is used to list the publications cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.
Use the Reference Wizard's Check Reference feature when you add a Reference Identifier (RID) outside of the Section's Reference Article to automatically place the reference in the Reference Article. Also use the Reference Wizard's Check Reference feature to update the issue dates.
References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print process.
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A580/A580M (2023) Standard Specification for Stainless Steel Wire
ASTM A641/A641M (2019) Standard Specification for Zinc-Coated (Galvanized) Carbon Steel Wire
ASTM A653/A653M (2023) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or
SECTION 26 51 00 Page 7
Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A1008/A1008M (2021a) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable
ASTM B164 (2003; R 2014) Standard Specification for Nickel-Copper Alloy Rod, Bar, and Wire
ASTM B633 (2023) Standard Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM D4674 REV A (2002; R 2010) Standard Practice for Accelerated Testing for Color Stability of Plastics Exposed to Indoor Office Environments
CALIFORNIA ENERGY COMMISSION (CEC)
CEC Title 20 (2019) Appliance Efficiency Regulations / Public Utilities and Energy Division 2.
State Energy Resources Conservation and Development Commission
CEC Title 24 (2016) Building Energy Efficiency Standards For Residential and Nonresidential Buildings
EUROPEAN UNION (EU)
Directive 2011/65/EU (2011) Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment
ILLUMINATING ENGINEERING SOCIETY (IES)
ANSI/IES LM-79 (2019) Approved Method: Electrical and Photometric Measurements of Solid State Lighting Products
ANSI/IES LM-80 (2020) Approved Method: Measuring Luminous Flux and Color Maintenance of LED Packages, Arrays and Modules
ANSI/IES LS-1 (2020) Lighting Science: Nomenclature and Definitions for Illuminating Engineering
ANSI/IES TM-15 (2020) Technical Memorandum: Luminaire Classification System for Outdoor Luminaires
ANSI/IES TM-21 (2021) Technical Memorandum: Projecting Long-TermLuminous, Photon, and Radiant Flux Maintenance of LED Light Sources
SECTION 26 51 00 Page 8
ANSI/IES TM-30 (2020) Technical Memorandum: IES Method for Evaluating Light Source Color Rendition
IES Lighting Library IES Lighting Library
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms
IEEE C2 (2023) National Electrical Safety Code
IEEE C62.41 (1991; R 1995) Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ANSI C78.54 (2019) Specification Sheet for Tubular Fluorescent Replacement and Retrofit LED Lamps
NEMA 77 (2017) Temporal Light Artifacts: Test Methods and Guidance for Acceptance Criteria
NEMA 250 (2020) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA ANSLG C78.377 (2017) Electric Lamps— Specifications for the Chromaticity of Solid State Lighting Products
NEMA C82.77-10 (2020) Harmonic Emission Limits - Related Power Quality Requirements
NEMA ICS 2 (2000; R 2020) Industrial Control and Systems Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures
NEMA SSL 1 (2016) Electronic Drivers for LED Devices, Arrays, or Systems
NEMA SSL 3 (2011) High-Power White LED Binning for General Illumination
NEMA SSL 7A (2015) Phase-Cut Dimming for Solid State Lighting: Basic Compatibility
NEMA WD 1 (1999; R 2020) Standard for General Color Requirements for Wiring Devices
NEMA WD 7 (2011; R 2016; R 2021) Occupancy Motion Sensors Standard
SECTION 26 51 00 Page 9
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023; ERTA 4 2023) National Electrical Code
NFPA 101 (2021; TIA 21-1) Life Safety Code
NFPA 110 (2022) Standard for Emergency and Standby Power Systems
U.S. DEPARTMENT OF ENERGY (DOE)
Energy Star (1992; R 2006) Energy Star Energy Efficiency Labeling System (FEMP)
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
47 CFR 15 Radio Frequency Devices
UNDERWRITERS LABORATORIES (UL)
UL 20 (2018; Reprint May 2023) UL Standard for Safety General-Use Snap Switches
UL 94 (2023; Reprint May 2023) UL Standard for Safety Tests for Flammability of Plastic Materials for Parts in Devices and Appliances
UL 508 (2018; Reprint Jul 2021) UL Standard for Safety Industrial Control Equipment
UL 844 (2012; Reprint Oct 2021) UL Standard for Safety Luminaires for Use in Hazardous (Classified) Locations
UL 916 (2015; Reprint Oct 2021) UL Standard for Safety Energy Management Equipment
UL 917 (2006; Reprint Aug 2013) UL Standard for Safety Clock-Operated Switches
UL 924 (2016; Reprint Dec 2022) UL Standard for Safety Emergency Lighting and Power Equipment
UL 1472 (2015) UL Standard for Safety Solid-State Dimming Controls
UL 1598 (2021; Reprint Jun 2021) Luminaires
UL 1598C (2014) Standard for Light-Emitting Diode (LED) Retrofit Luminaire Conversion Kits
UL 1993 (2017) Self-Ballasted Lamps and Lamp Adapters
UL 2043 (2023) Fire Test for Heat and Visible Smoke Release for Discrete Products and
SECTION 26 51 00 Page 10
Their Accessories Installed in Air-Handling Spaces
UL 8750 (2015; Reprint Sep 2021) UL Standard for Safety Light Emitting Diode (LED) Equipment for Use in Lighting Products
1.2 RELATED REQUIREMENTS
NOTE: For the purpose of this document, interior luminaires include those in the interior portion of buildings or facilities, luminaires attached to the exterior of a building, and luminaires mounted in parking garages. Luminaires that are not attached to the exterior of a building and that are intended to illuminate exterior areas are specified in Section 26 56 00 EXTERIOR LIGHTING.
Materials not considered to be luminaires, luminaire accessories, or lighting equipment are specified in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM. Luminaires and accessories that are mounted in exterior environments and not attached to the exterior of the building are specified in Section 26 56 00 EXTERIOR LIGHTING. Cybersecurity requirements are specified in Section 25 05 11.[_____] CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS. Commissioning requirements are specified in Section 01 91 00.15 BUILDING COMMISSIONING. Emergency lighting requirements are specified in Section 26 52 00.00 40 EMERGENCY
LIGHTING.
1.3 DEFINITIONS
a. Unless otherwise specified or indicated, electrical and electronics terms used in these specifications and on the drawings, must be as defined in IEEE 100 and ANSI/IES LS-1.
b. For LED luminaire light sources, "Useful Life" is the operating hours before reaching 70 percent of the initial rated lumen output (L70) with no catastrophic failures under normal operating conditions. This is also known as 70 percent "Rated Lumen Maintenance Life" as defined in ANSI/IES LM-80.
c. For LED luminaires, "Luminaire Efficacy" (LE) is the appropriate measure of energy efficiency, measured in lumens/watt. This is gathered from LM-79 data for the luminaire, in which absolute photometry is used to measure the lumen output of the luminaire as one entity, not the source separately and then the source and housing together.
d. Total harmonic distortion (THD) is the root mean square (RMS) of all the harmonic components divided by the total fundamental current.
1.4 SUBMITTALS
NOTE: Review Submittal Description (SD) definitions in Section 01 33 00 SUBMITTAL PROCEDURES and edit the following list, and corresponding submittal
SECTION 26 51 00 Page 11 items in the text, to reflect only the submittals required for the project. The Guide Specification technical editors have classified those items that require Government approval, due to their complexity or criticality, with a "G." Generally, other submittal items can be reviewed by the Contractor's Quality Control System. Only add a "G" to an item if the submittal is sufficiently important or complex in context of the project.
For Army projects, fill in the empty brackets following the "G" classification, with a code of up to three characters to indicate the approving authority. Codes for Army projects using the Resident Management System (RMS) are: "AE" for Architect-Engineer; "DO" for District Office (Engineering Division or other organization in the District Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project Office. Codes following the "G" typically are not used for Navy and Air Force projects.
The "S" classification indicates submittals required as proof of compliance for sustainability Guiding Principles Validation or Third Party Certification and as described in Section 01 33 00 SUBMITTAL
PROCEDURES.
Choose the first bracketed item for Navy and Air Force projects, or choose the second bracketed item for Army projects.
Luminaire shop drawings are required for custom luminaires, luminaires specified to a specific custom length, or linear luminaires with lengths greater than 2.5 meters 8 feet.
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are [for Contractor Quality Control approval.][for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.] Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Luminaire Drawings; G[, [_____]]
Occupancy/Vacancy Sensor Coverage Layout; G[, [_____]]; S
Lighting Control System One-Line Diagram; G[, [_____]]
Sequence of Operation for Lighting Control System; G[, [_____]]
SD-03 Product Data
SECTION 26 51 00 Page 12
Luminaires; G[, [_____]]
Light Sources; G[, [_____]]
LED Drivers; G[, [_____]]
Luminaire Warranty; G[, [_____]]
Lighting Controls Warranty; G[, [_____]]
Local Area Controller; G[, [_____]]
Lighting Relay Panel; G[, [_____]]
Lighting Control Panel; G[, [_____]]
Gateway; G[, [_____]]
Lighting Contactor; G[, [_____]]
Switches; G[, [_____]]
Digital Switch Timers; G[, [_____]]
Wall Box Dimmers; G[, [_____]]
Scene Wallstations; G[, [_____]]
Occupancy/Vacancy Sensors; G[, [_____]]
Photosensors; G[, [_____]]
Time Clocks; G[, [_____]]
Power Packs; G[, [_____]]
Power Hook Luminaire Hangers; G[, [_____]]
Mini Inverters; G[, [_____]]
Exit Signs; G[, [_____]]
Emergency Drivers; G[, [_____]]
Energy Star Label For Residential Luminaires; S
Linear LED Lamps; G[, [_____]]
[ SD-04 Samples
Luminaire Samples; G[, [_____]]
] SD-05 Design Data
Luminaire Design Data; G[, [_____]]
Photometric Plan; G[, [_____]]
SD-06 Test Reports
SECTION 26 51 00 Page 13
ANSI/IES LM-79 Test Report; G[, [_____]]
ANSI/IES LM-80 Test Report; G[, [_____]]
ANSI/IES TM-21 Test Report; G[, [_____]]
ANSI/IES TM-30 Test Report; G[, [_____]]
Occupancy/Vacancy Sensor Verification Test; G[, [_____]]
Photosensor Verification Test; G[, [_____]]
SD-07 Certificates
LED Driver and Dimming Switch Compatibility Certificate; G[, SD-10 Operation and Maintenance Data
Lighting System, Data Package 5; G[, [_____]]
Lighting Control System, Data Package 5; G[, [_____]]
Maintenance Staff Training Plan; G[, [_____]]
End-User Training Plan; G[, [_____]]
1.5 QUALITY ASSURANCE
Data, drawings, and reports must employ the terminology, classifications and methods prescribed by the IES Lighting Library as applicable, for the lighting system specified.
1.5.1 Luminaire Drawings
NOTE: Aiming diagrams are required for applications with directional luminaires, such as art lighting, track lighting, and wallwash applications.
Include dimensions, accessories installation details, and construction details. Photometric data, including CRI, CCT, LED driver type,[ aiming diagram,] zonal lumen data, and candlepower distribution data must accompany shop drawings.
1.5.2 Luminaire Design Data
a. Provide safety certification and file number for the luminaire family that must be listed, labeled, or identified in accordance with the NFPA 70. Applicable testing bodies are determined by the US Occupational Safety Health Administration (OSHA) as Nationally Recognized Testing Laboratories (NRTL) and include: CSA (Canadian Standards Association), ETL (Edison Testing Laboratory), and UL (Underwriters Laboratories).
b. Provide long term lumen maintenance projections for each LED luminaire in accordance with ANSI/IES TM-21. Data used for projections must be
SECTION 26 51 00 Page 14 obtained from testing in accordance with ANSI/IES LM-80.
1.5.3 ANSI/IES LM-79 Test Report
Submit test report on manufacturer's standard production model of specified luminaire. Testing must be performed at the same operating drive current as specified luminaire. Include all applicable and required data in IES format as outlined under "14.0 Test Report" in ANSI/IES LM-79.
1.5.4 ANSI/IES LM-80 Test Report
Submit report on manufacturer's standard production LED light source (package, array, or module) of specified luminaire. Testing must be performed at the same operating drive current as specified luminaire.
Include all applicable and required data as outlined under "8.0 Test Report" in ANSI/IES LM-80.
1.5.5 ANSI/IES TM-21 Test Report
Submit test report on manufacturer's standard production LED light source (package, array, or module) of specified luminaire. Testing must be performed at the same operating drive current as specified luminaire.
Include all applicable and required data, as well as required interpolation information as outlined under "7.0 Report" in ANSI/IES TM-21.
1.5.6 ANSI/IES TM-30 Test Report
Submit color vector graphic in accordance with ANSI/IES TM-30 on manufacturer's standard production LED light source (package, array, or module) of specified luminaire. Include spectral distribution of test LED light source.
1.5.7 LED Driver and Dimming Switch Compatibility Certificate
Submit certification from the luminaire, driver, or dimmer switch manufacturer that ensures compatibility and operability between devices without flickering and to specified dimming levels.
1.5.8 Photometric Plan
NOTE: Require photometric plans and design criteria to be submitted if the project is a Design-Build project and will not have a engineer or designer producing photometrics during design.
1.5.8.1 Computer-generated Photometric Plans
Computer-generated photometric plans for each space are required to verify proposed luminaires and locations meet the required performance criteria of the design using the applicable light loss factor (LLF).
Target illumination levels are provided for each Interior Application.
Depending on the application and the recommendations provided by the IES, values are given as one of the following:
a. Minimum: No values anywhere on the calculation grid may be less than this value, within a 10 percent margin of error.
SECTION 26 51 00 Page 15
b. Minimum Average: An average, taken over the entire task area for the application, may not be less than this value, within a 10 percent margin of error.
c. Maximum: No values anywhere on the calculation grid may be greater than this value, within a 10 percent margin of error.
d. Maximum Average: An average, taken over the entire task area for the application, may not be greater than this value, within a 10 percent margin of error.
e. Uniformity: Unless otherwise noted, uniformity is calculated as a ratio of the average calculated illuminance over the minimum calculated illuminance of the calculation grid.
1.5.8.2 Schematic Photometric Plan Calculations
Schematic photometric plan calculations must include:
a. Horizontal illuminance measurements at workplane or other designated height above finished floor, taken at a maximum of every 305 mm one foot across the task area.
b. Average maintained illuminance level.
c. Minimum and maximum maintained illuminance levels.
d. Lighting power density (Watts per square meter) (Watts per square foot).
e. LLF. Recommended LLF is 0.81 for LED luminaires but LLF varies based on environment and application.
1.5.8.3 Final Photometric Plan Calculations
Final photometric plan calculations must include:
a. Horizontal illuminance measurements at workplane or other designated height above finished floor, taken at a maximum of every 305 mm one foot across the task area.
b. Where applicable, vertical illuminance measurements at designated surface, taken at a maximum of every 305 mm one foot across task area.
c. Minimum and maximum maintained illuminance levels.
d. Average maintained illuminance level.
e. Average to minimum and maximum to minimum ratios for horizontal illuminance.
f. Lighting power density (Watts per square meter) (Watts per square foot).
g. LLF. Recommended LLF is 0.81 for LED luminaires but LLF varies based on environment and application.
1.5.9 Occupancy/Vacancy Sensor Coverage Layout
Provide floor plans showing coverage layouts of all devices using
SECTION 26 51 00 Page 16 manufacturer's product information.
1.5.10 Test Laboratories
Test laboratories for the ANSI/IES LM-79 and ANSI/IES LM-80 test reports must be one of the following:
a. National Voluntary Laboratory Accreditation Program (NVLAP) accredited for solid-state lighting testing as part of the Energy-Efficient Lighting Products laboratory accreditation program for both LM-79 and LM-80 testing.
b. One of the qualified labs listed on the Department of Energy - LED Lighting Facts Approved Testing Laboratories List for LM-79 testing.
c. One of the EPA-Recognized Laboratories listed for LM-80 testing.
1.5.11 Regulatory Requirements
Equipment, materials, installation, and workmanship must be in accordance with the mandatory and advisory provisions of NFPA 70, unless more stringent requirements are specified or indicated. Provide luminaires and assembled components that are approved by and bear the label of UL for the applicable location and conditions unless otherwise specified.
1.5.12 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design, and workmanship. Products must have been in satisfactory commercial or industrial use for six months prior to bid opening. The six-month period must include applications of equipment and materials under similar circumstances and of similar size. The product must have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the six-month period. Where two or more items of the same class of equipment are required, these items must be products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
1.5.12.1 Alternative Qualifications
Products having less than a six-month field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.5.12.2 Material and Equipment Manufacturing Date
Do not use products manufactured more than six months prior to date of delivery to site, unless specified otherwise.
1.6 WARRANTY
Support all equipment items by service organizations which are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.
SECTION 26 51 00 Page 17
1.6.1 Luminaire Warranty
NOTE: In applications where color rendition and color detection are a high priority, require warranty for color maintenance.
Provide and transfer to the government the original LED luminaire manufacturers standard commercial warranty for each different luminaire manufacturer used in the project.
a. Provide a written five year minimum replacement warranty for material, luminaire finish, and workmanship. Provide written warranty document that contains all warranty processing information needed, including customer service point of contact, whether or not a return authorization number is required, return shipping information, and closest return location to the luminaire location.
(1) Finish warranty must include failure and substantial deterioration such as blistering, cracking, peeling, chalking, or fading.
(2) Material warranty must include:
(a) All LED drivers and integral control equipment.
(b) Replacement when more than 15 percent of LED sources in any lightbar or subassembly(s) are defective, non-starting, or operating below 70 percent of specified lumen output.
[ (c) Replacement when more than 15 percent of LED sources in any lightbar or subassembly(s) show a color shift greater than 0.003 delta u'v' from the zero hour measurement stated in the ANSI/IES LM-79 Test Report.
] b. Warranty period must begin in accordance with the manufacturer's standard warranty starting date.
c. Provide replacements that are promptly shipped, without charge, to the using Government facility point of contact and that are identical to or an improvement upon the original equipment. All replacements must include testing of new components and assembly.
1.6.2 Lighting Controls Warranty
Provide and transfer to the government the original lighting controls manufacturers standard commercial warranty for each different lighting controls manufacturer used in the project. Warranty coverage must begin from date of final system commissioning or three months from date of delivery, whichever is the earliest. Warranty service must be performed by a factory-trained engineer or technician.
a. Unless otherwise noted, provide a written five year minimum warranty on the complete system for all systems with factory commissioning.
Provide warranty that covers 100 percent of the cost of any replacement parts and services required over the five years which are directly attributable to the product failure. Failures include, but are not limited to, the following:
SECTION 26 51 00 Page 18
(1) Software: Failure of input/output to execute switching or dimming commands.
(2) Damage of electronic components due to transient voltage surges.
(3) Failure of control devices, including but not limited to occupancy sensors, photosensors, and manual wall station control devices.
b. Provide a written five year minimum warranty on all input devices against defect in workmanship or materials provided by device manufacturer.
c. Provide a written five year minimum warranty on all control components attached to luminaires against defect in workmanship or materials.
1.7 OPERATION AND MAINTENANCE MANUALS
1.7.1 Lighting System
Provide operation and maintenance manuals for the lighting system in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA that provide basic data relating to the design, operation, and maintenance of the lighting system for the building. Additional O&M Manual requirements for the Army are provided in Section 01 78 24.00 10 FACILITY DATA REQUIREMENTS. Additional requirements for the Navy are provided in Section 01 78 24.00 20 FACILITY DATA WORKBOOK (FDW). Include the following:
a. Manufacturers' operating and maintenance manuals.
b. Luminaire shop drawings for modified and custom luminaires.
c. Luminaire Manufacturers' standard commercial warranty information as specified in paragraph LUMINAIRE WARRANTY.
1.7.2 Lighting Control System
NOTE: Lighting control panel schedules are not required for localized control systems.
Provide operation and maintenance manuals for the lighting control system in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA that provide basic data relating to the design, operation, and maintenance of the lighting control system for the building. Include the following:
a. Lighting control system layout and wiring plan.
b. Lighting control system one-line diagram.
c. Product data for all devices, including installation and programming instructions.
d. Occupancy/vacancy sensor coverage layout.
e. Training materials, such as videos or in-depth manuals, that cover basic operation of the lighting control system and instructions on modifying the lighting control system. Training materials must
SECTION 26 51 00 Page 19 include calibration, adjustment, troubleshooting, maintenance, repair, and replacement.
f. Sequence of operation descriptions for each typical room type, including final programming, schedules, and calibration settings.
[ g. "As-built" lighting control panel schedules.
]PART 2 PRODUCTS
2.1 PRODUCT COORDINATION
2.2 LUMINAIRES
NOTE: For luminaires used in residential applications, include requirements for Energy Star Label. If building-mounted exterior luminaires are specified on this project, require compliance with BUG rating as indicated in the luminaire schedule.
UL 1598, NEMA C82.77-10. Provide luminaires as indicated in the luminaire schedule and NL plates or details on project plans, complete with light source, wattage, and lumen output indicated. All luminaires of the same type must be provided by the same manufacturer. Luminaires must be specifically designed for use with the driver and light source provided.
[ Provide luminaire with Energy Star Label For Residential Luminaires in accordance with Energy Star.
][2.2.1 Luminaire Samples
NOTE: Only require the acquisition of samples for luminaire installations that warrant mock-ups, such as wall grazing unique materials, for custom luminaires, or for applications where aesthetics are of high priority.
Submit one sample of each luminaire type [_____], complete with light source, LED driver rated for 120 V operation, and 2 meters 6 feet pigtail with 3-prong Edison plug. Sample will be returned to the Contractor for installation in the project work.
]2.2.2 Luminaires
NOTE: Provide design information including delivered lumen output, L70 lumen maintenance data, and luminaire efficacy in the luminaire schedule on project plans.
Luminaires attached to the exterior of the building are included in this interior lighting specification. For any interior project with exterior building-mounted luminaires, select the requirements for exterior luminaires, including BUG
SECTION 26 51 00 Page 20 rating.
If there are any recessed luminaires that are in contact with insulation, require those luminaires to be IC-rated. If the project is located in the City of Chicago or a jurisdiction that has adopted Chicago amendments to the NEC, select Chicago Plenum requirements.
UL 8750, ANSI/IES LM-79, ANSI/IES LM-80. For all luminaires, provide:
a. Complete system with LED drivers and light sources.
b. Housings constructed of non-corrosive materials. All new aluminum housings must be anodized or powder-coated. All new steel housings must be treated to be corrosion resistant.
c. ANSI/IES TM-21, ANSI/IES LM-80. Minimum L70 lumen maintenance value of 50,000 hours unless otherwise indicated in the luminaire schedule.
Luminaire drive current value must be identical to that provided by test data for luminaire in question.
d. Minimum efficacy as specified in the luminaire schedule. Theoretical models of initial lamp lumens per watt are not acceptable. If efficacy values are not listed in the luminaire schedule, provide luminaires that meet the following minimum values:
Luminaire Style Minimum Luminaire Efficacy
Recessed 1 by 4, 2 by 4, and 2 by 2 100 LPW
Recessed Downlight (fixed, adjustable, wallwash) 80 LPW
Linear, Accent (undercabinet, cove) 45 LPW
Linear, Ambient (indirect wall mount, linear pendent)
100 LPW
High Bay, Low Bay, and Industrial Locations 100 LPW
Food Service and Hazardous Locations 60 LPW
Other (track, residential diffusers) 50 LPW
Exterior Wall Sconce 50 LPW
Steplight 30 LPW
Parking Garage Luminaire 100 LPW
e. UL listed for dry or damp location typical of interior installations.[ Any luminaire mounted on the exterior of the building must be UL listed for wet location typical of exterior installations.]
f. LED driver and light source package, array, or module are accessible for service or replacement without removal or destruction of luminaire.
SECTION 26 51 00 Page 21
g. Lenses constructed of heat tempered borosilicate glass, UV-resistant acrylic, or silicone.[ Provide polycarbonate vandal-resistant lenses as indicated.] Sandblasting, etching and polishing must be performed as indicated in the luminaire description.
[ h. ANSI/IES TM-15. Provide exterior building-mounted luminaires that do not exceed the BUG ratings as listed in the luminaire schedule. If BUG ratings are not listed in the luminaire schedule, provide luminaires that meet the following minimum values for each application and mounting conditions:
Lighting Application Mounting Conditions BUG Rating
Exterior Wall Sconce Above 1.2 meters 4 feet AFF B1-U0-G2
Exterior Wall Sconce Below or at 1.2 meters 4 feet
AFF
B4-U0-G4
Steplight Above 1.2 meters 4 feet AFF B1-U1-G2
Steplight Below or at 1.2 meters 4 feet
AFF
B4-U1-G4
Parking Garage Luminaire Ceiling mounted B4-U4-G3
][i. For all recessed luminaires that are identified to be in contact with insulation, provide luminaires that are IC-rated.
][j. For all recessed luminaires that are to be installed in air plenums, require housings that are Chicago Plenum rated.
]2.2.2.1 Luminaire Conversion Kits
NOTE: Provide LED luminaire conversion kits to replace non-LED light sources in renovation or energy conservation projects, only where entire luminaires are not replaced.
Provide luminaire conversion kits that meet UL 1598C Standard for Light-Emitting Diode (LED) Retrofit Luminaire Conversion Kits.
2.2.3 Luminaires for Hazardous Locations
In addition to requirements stated herein, provide LED luminaires for hazardous locations which conform to UL 844 or which have Factory Mutual certification for the class and division indicated.
2.3 LIGHT SOURCES
NEMA ANSLG C78.377, NEMA SSL 3. Provide type, delivered lumen output, and wattage as indicated in the luminaire schedule on project plans.
2.3.1 LED Light Sources
NOTE: A color temperature of 3500 K is standard for
SECTION 26 51 00 Page 22 most applications. When specifically desired by the designer, a nominal color temperature of 2700 K, 3000 K, or 4000 K may be selected. The highest allowable CCT is 4100 K.
In applications where color rendition and color detection are a high priority, require that LED light sources meet the recommended fidelity and gamut indices as determined by ANSI/IES TM-30.
Additionally, select color maintenance requirements.
For projects in the state of California, require compliance with CEC Title 20.
Refer to UFC 3-530-01 for CRI allowances in maintenance and recreational spaces.
[CEC Title 20. ]Provide LED light sources that meet the following requirements:
a. NEMA ANSLG C78.377. Emit white light and have a nominal CCT of [3000][2700][3500][4000] Kelvin.
b. Minimum Color Rendering Index (CRI) of [80][90][95 with an R9 value of 95].[ Fidelity index greater than or equal to 80, gamut index between 97 and 110, determined in accordance with ANSI/IES TM-30.]
c. Directive 2011/65/EU. Restriction of Hazardous Substances (RoHS) compliant.
d. Light source color consistency by utilizing a binning tolerance within a 3-step McAdam ellipse.
[ e. Color maintenance value of no greater than 0.003 (delta u'v') at 6000 hours as listed in ANSI/IES LM-79 Test Report.
][2.3.1.1 Linear LED Lamps
NOTE: Minimum beam angle of 270-degrees is preferred over 180-degrees, but is less common. If target light levels and optical performance of linear LED lamp is critical for the specified application, select 270-degree beam angle.
Provide linear LED Lamps to replace fluorescent light sources in renovation or energy conservation projects, only where entire luminaires are not replaced or LED conversion kits are not available.
Do not use UL 1993 Type B, UL 1993 Type C, or any hybrid Linear LED Lamps.
Provide linear LED Lamps that are compatible with existing instant-start or programmed-start ballasts, and meet the following additional requirements:
a. UL 1993 UL Type A linear LED lamp.
SECTION 26 51 00 Page 23
b. Power Factor greater than or equal to 0.90 at full input power and across specified dimming range.
c. Maximum Total Harmonic Distortion (THD) less than or equal to 20 percent at full input power and across specified dimming range.
d. Lumen per watt efficacy no less than 120.
e. Minimum beam angle of [270][180] degrees.
f. Lamp datasheet complies with ANSI C78.54. Manufacturer must provide list of all ballasts that are compatible for use with lamp.
]2.4 LED DRIVERS
NOTE: Dimmable LED drivers should be specified with dimming down to at least 10 percent. Dimmable drivers with a dimming range down to 1 percent should be specified for applications where audio/visual presentations are common such as conference and meetings rooms, and hospitality.
NEMA SSL 1, UL 8750. Provide LED drivers that are electronic, UL Class 1 or Class 2, constant-current type and that comply with the following requirements:
a. The combined driver and LED light source system does not exceed the minimum luminaire efficacy values as listed in the luminaire schedule provided.
b. Operates at a voltage of [120-277][120][277] volts at 50/60 hertz, with input voltage fluctuations of plus/minus 10 percent.
c. Power Factor (PF) greater than or equal to 0.90 at full input power and across specified dimming range.
d. Maximum Total Harmonic Distortion (THD) less than 20 percent at full input power and across specified dimming range.
e. Operates for at least 50,000 hours at maximum case temperature and 90 percent non-condensing relative humidity.
f. Withstands Category A surges of 2 kV without impairment of performance. Provide surge protection that is integral to the driver.
g. Integral thermal protection that reduces the output power to protect the driver and light source from damage if the case temperature approaches or exceeds the driver's maximum operating temperature.
h. 47 CFR 15. Complies with the requirements of the Federal Communications Commission (FCC) rules and regulations, Non-Consumer (Class A) for EMI/RFI (conducted and radiated).
i. Class A sound rating.
j. Directive 2011/65/EU. Restriction of Hazardous Substances (RoHS)
SECTION 26 51 00 Page 24 compliant.
k. Provide dimming capability as indicated in the luminaire schedule on project plans.[ Dimmable drivers must dim down to [10][5][1] percent. Dimmable drivers must be controlled by a [Class 2 low voltage 0-10VDC controller] [Digital Addressable Lighting Interface (DALI)] dimming signal protocol unless otherwise specified. LED drivers of the same family/series must track evenly across multiple luminaires at all light levels.]
[2.4.1 Remote LED Drivers
NOTE: Do not allow use of remote drivers unless specifically noted on the lighting plate and luminaire schedule.
Provide remote LED Drivers that are UL listed for dry locations typical of interior installations. Provide LED driver in junction box or housing with mounting plate. Housing must allow for field connections to occur inside the housing or must contain mechanical connections.
]2.5 LIGHTING CONTROLS
NOTE: Include a version of Section 25 05 11
CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS
edited specifically for the lighting control system where a control system is specified.
Provide network certification for all networked lighting control systems and devices in accordance with the requirements of Section 25 05 11.[_____] CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS. Provide lighting control systems that do not switch off battery-operated or emergency backup luminaires or exit signs in path of egress. Provide system with override of lighting control devices controlling luminaires in path of egress with activation of fire alarm system.
2.5.1 System
Provide lighting control system that operates the lighting system as described in the lighting control strategies in the project plans. Submit Sequence of Operation for Lighting Control System describing the operation of the proposed lighting control system and devices. Sequence of Operation must provide the strategies identified in the lighting control strategies.
2.5.1.1 Localized Control Systems
Provide room or area-wide lighting control system capable of manual control, time-based control, and receiving input from photosensors and occupancy/vacancy sensors.
2.5.1.1.1 Local Area Controller
NOTE: Select requirement for daylight harvesting
SECTION 26 51 00 Page 25 capabilities for all regularly-occupied spaces with access to daylight. Task oriented areas such as offices, conference rooms, and classrooms require continuous dimming of electric lighting per UFC 3 530 01.
When using receptacle load control in private offices, allow capability for receptacle load control via the localized control system. Only use receptacle load control for areas with non-critical loads such as computer monitors, task lights, or personal convenience devices.
Select Item g. if Local Area Controller is connected to luminaires in the path of egress.
Provide controller designed for single area or room with the following requirements:
a. Operates at a voltage of [120-277][120][277] volts at 50/60 hertz.
b. [2][_____] zone, with [1][2][_____] relay[s] rated 20 amps[ each] with one manual [switch][dimmer] per zone.
c. Provide inputs for occupancy/vacancy sensors, photosensors, and low-voltage wall switches.
[ d. Provide daylight harvesting capability with full-range dimming control with input from photosensor.
][e. Provide capability for receptacle load control from occupancy sensors.
][f. Provide full 'OFF' function with input from external time clock input.
][g. Capable of 0-10V dimming.
][h. AV interface via [RS-232][RS-485][ethernet and CAT5].
][i. Provide override 'ON' function with input from Fire Alarm Control Panel for all emergency lighting. Controller must not turn off power to emergency batteries or exit signs.
]2.5.1.2 Centralized Control Systems
Provide a centralized lighting control system capable of manual control, time-based control, receiving input from photosensors and occupancy/vacancy sensors, with the capabilities of controlling, monitoring, and programming changes from one centralized on-site location, and integration with other building systems.
2.5.1.2.1 Lighting Relay Panel
NOTE: Select NEMA 1 enclosure for indoor use with normal conditions, NEMA 3R for indoor or outdoor use when weather resistance is necessary, and NEMA 4 if a watertight enclosure is necessary.
SECTION 26 51 00 Page 26
UL 924. Enclose panel hardware in a [surface][flush]-mounted, NEMA [1][3R][4], painted, steel enclosure with lockable access door and ventilation openings. Internal low-voltage compartment must be separated from line-voltage compartment of enclosure with only low-voltage compartment accessible upon opening of door. Provide additional remote cabinets that communicate back to main control panel as required. Provide Lighting Control Panels that meet the following criteria:
a. Input voltage of [120][277][120-277] at 50/60 Hz, with internal low voltage power supply as required.
b. [8][16][32][_____] single-pole latching relays rated at [20][30] amps, [120-277][120][277] volts. Provide provision for relays to close upon power failure. Provide relays designed for 10 years of use at full rated load.
c. Relay control module operates at 24 VDC and is rated to control a minimum of [8][16][32][_____] relays.
[ d. Capable of 0-10V dimming.
]2.5.1.2.2 Lighting Control Panel
NOTE: Select NEMA 1 enclosure for indoor use with normal conditions, NEMA 3R for indoor or outdoor use when weather resistance is necessary, and NEMA 4 if a watertight enclosure is necessary.
When providing a control panel that interfaces with the building automated control system, reference IES Technical Memorandum IES TM-23-11 for technical information on various protocols, architectures and topologies for such systems. Include Section
25 10 10 UTILITY MONITORING AND CONTROL SYSTEM
(UMCS) FRONT END AND INTEGRATION for UMCS and integration requirements.
For projects in the state of California, require compliance with CEC Title 24.
UL 916, 47 CFR 15[, CEC Title 24]. Provide an electronic, programmable lighting control panel complete with microprocessor, capable of providing lighting control with input from internal programming, digital switches,[ time clocks,] and other control devices.
Enclose panel hardware in a [surface][flush]-mounted, NEMA [1][3R][4], painted, steel enclosure with lockable access door and ventilation openings. Internal low-voltage compartment must be separated from line-voltage compartment of enclosure with only low-voltage compartment accessible upon opening of door. Provide additional remote cabinets that communicate back to main control panel as required. Provide Lighting Control Panels that meet the following criteria:
a. Input voltage of [120][277][120-277] at 50/60 Hz, with internal low-voltage VDC power supply as required.
SECTION…