This is a request for quotation for medical gas inspection and assessment services at two Department of Veterans Affairs medical centers in Nebraska. The solicitation seeks a contractor to perform inspections of medical gas systems at the VA medical centers in Grand Island and Omaha to evaluate compliance with NFPA 99 standards and identify any deficiencies. Services will include inventorying all medical gas outlets, alarms, control valves, and other equipment; assessing compliance of labeling, location of components, and pressure monitoring; and producing a report of findings and recommendations. The quote is due by August 15, 2022 and the period of performance is one year from award. Pricing shall be fixed for the base period and any optional renewal periods. This procurement is set aside for service-disabled veteran-owned small businesses.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Out of Compliance

*All NFPA references are pulled from 2021 edition
#Compliance IssueNFPA 99 ReferenceNFPA 99 CriteriaBuildingRoomLocationApplicable DeficienciesIssue Specific(s)
1Proper Labeling of Shutoff Valves5.1.4.1.3 Labeling (p 99-47)

5.1.11.2 Shutoff Valves (p 99-59)

Table 5.1.11 on p99-60 for standard color designations & pressures5.1.4.1.3: "All valves shall be labeled as to gas supplied and the area(s) controlled, in accordance with 5.1.11.2
5.1.11.2: "…(1) Name or chemical symbol for the specific medical gas or vacuum system, (2) Gas or vacuum system color code in accordance wit Table 5.1.11, (3) Room or areas served, (4) Caution to not close or open the valve except in emergencyMain BLDG 1
2Proper Labeling of Source Valves5.1.4.1.3 Labeling (p 99-47)

5.1.11.2.4 Source Valves (p 99-60)

Table 5.1.11 on p99-60 for standard color designations & pressures 5.1.11.2.4: "…shall be labeled in substance as follows: SOURCE VALVE FOR THE (SOURCE NAME)" ***Unable to personally complete due to time contraints, but this should be evaluated -Kali 8/3/23 3 Proper Labeling of Main Line Valves 5.1.4.1.3 Labeling (p 99-47)

5.1.11.2.5 Main Line Valves (p 99-60)

Table 5.1.11 on p99-60 for standard color designations & pressures 5.1.11.2.5: "…shall be labeled in substance as follows: MAIN LINE VALVE FOR THE (GAS/VACUUM NAME) SERVING (NAME OF THE BUILDING)" ***Unable to personally complete due to time contraints, but this should be evaluated -Kali 8/3/23 4 Proper Labeling of Riser Valves 5.1.4.1.3 Labeling (p 99-47)

5.1.11.2.6 Riser Valves (p 99-60)

Table 5.1.11 on p99-60 for standard color designations & pressures 5.1.11.2.6: "…shall be labeled in substance as follows: RISER FOR THE (GAS/VACUUM NAME) SERVING (NAME OF THE AREA/BUILDING SERVED BY THE PARTICULAR RISER)" ***Unable to personally complete due to time contraints, but this should be evaluated -Kali 8/3/23 5 Proper Labeling of Service Valves 5.1.4.1.3 Labeling (p 99-47)

5.1.11.2.7 Service Valves (p 99-60)

Table 5.1.11 on p99-60 for standard color designations & pressures 5.1.11.2.7: "…shall be labeled in substance as follows: SERVICE VALVE FOR THE (GAS/VACUUM NAME) SERVING (NAME OF THE AREA/BUILDING SERVED BY THE PARTICULAR VALVE)" ALL AREAS Most of the existing Service Valve (SV) boxes are not labeled for areas serviced and/or labels affixed to the removeable metal covers - full audit & correction should be made for all SV boxes; With panels that do not have a non-removable surface to affix label, a separate solution must be executed (EX: SV boxes without trim around the removable cover will require a plaque/wall-mounted, non-removeable label installed above the box to highlight areas serviced)

6 Proper Labeling of Zone Valve Boxes 5.1.4.1.3 Labeling (p 99-47)

5.1.11.2.8 Service Valves (p 99-60)

Table 5.1.11 on p99-60 for standard color designations & pressures5.1.11.2.8: "…shall be labeled in substance as follows: ZONE VALVES FOR THE (GAS/VACUUM NAME) SERVING (NAME OF ROOMS OR SPACES SERVED BY THE PARTICULAR VALVE)… Labeling shall either be visible from outside…through the cover or be replicated on the outside, but not affixed to the removable cover"ALL AREASUNSURE OF INTERPRETATION (if valve names need gas in title or just the ZV box): Most recent audit by external contractor - determined their own nomeclature for all valves, that does NOT indicate gas type… Oldest naming had gas type in title - consider full re-naming of valves to style of oldest (EX: 2SV-MA-130 - where "MA" indicates Medical Air")
ALL AREASMany of the existing ZV boxes have the area(s) serviced labels affixed to the removeable covers - full audit & correction should be made for all ZV boxes; With panels that do not have a non-removable surface to affix label, a separate solution must be executed (EX: valve boxes without trim around the removable cover will require a plaque/wall-mounted, non-removeable label installed above the ZV box)
7Proper Labeling of Alarm Panels5.1.11.4 Alarm Panels (p 99-61)
Table 5.1.11 on p99-60 for standard color designations & pressures5.1.11.4.2: "Area alarm panels shall be identified with the following: (1) Name or chemical symbol for the specific medical gas or vacuum system, (2) Gas or vacuum system color code, in accordance wit Table 5.1.11, of the specific medical gas or vacuum system being monitored , (3) Area(s) monitored by the alarm panel

5.1.11.4.3: "Where medical gas systems operate at pressures other than the standard gauge pressure... the area alarm panel identification shall include the nonstandard operating pressure in addition to the name of the gas."

8Proper Labeling of Source Equipment5.1.11.5 Source Equipment (p 99-61)
5.1.11.5.1: "Source equipment shall be labeled or tagged...: (1) Name of the gas or vacuum system, (2) Gas or vacuum system color code, (3) Rooms, areas, or buildings served, (4) Emergency contact information for the department or individual responsible for maintaining the equipment"
9Proper Labeling of Pipes5.1.11.1 Pipe Labeling (p 99-59)
Table 5.1.11 on p99-60 for standard color designations & pressures5.1.11.1.1: "…labeled by stenciling or adhesive markers… (1) Name of gas or vacuum system or chemical symbol per Table 5.1.11, (2) Gas or vacuum system color code per Table 5.1.11"

5.1.11.1.2: "…operating pressure in addition to the name of the gas shall be labeled" where pressure is not standard 5.1.11.1.3: "...piping in the immediate area of the WAGD systems shall be labeled to indicate both systems."

5.1.11.1.4: "Pipe labels shall be located as follows: (1) At intervals of not more than 6.1m (20ft), (2) At least once in or above every room, (3) On both sides of walls or partitions penetrated by the piping, (4) At least once in every story height traversed by risers" 5.1.11.1.6: "...compressor intakes, vacuum exhausts, and relief valve vent lines shall meet the requirements of 5.1.11.1.1" ***Unable to personally complete due to time contraints, but this should be evaluated -Kali 8/3/23

10Accessibility of Zone Valves5.1.4.1.4 Accessibility (p99-47)
5.1.4.6 Zone Valves (p99-47)5.1.4.1.4: " Zone valves shall be installed in valve boxes with removable covers large enough to allow manual operation of valves"

5.1.4.6.1: "All station outlets/inlets shall be supplied through a zone valve…"

5.1.4.6.2: "A zone valve in each medical gas or vacuum line shall be provided for each Category 1 space and anesthetizing location for moderate sedation, deep sedation, or general anesthesia specific for the occupany, and shall be located as follows: (1) They are installed immediately outside the area controlled. (2) They are installed where they are visible and accessible at all times.BLDG 1Corridor 4215Hallway -across from PACU5.1.4.1.4 & 5.1.4.6.2 - Easily visible & accessible cover with proper labelsNeed verification of area(s) supplied by valve 45V-OX-106; Currently behind metal plate, only accessible via flathead; If this is active & a ZONE valve - zone valve box (easily accessible/removable cover) will need to be installed & properly labeled
BLDG 1RMs 2568 & 2562CT 1 & Fluoro5.1.4.6.2 - zone valve is needed for EACH Category 1 spaceCT 1 is a Category 1 space and requires its own zone valves/box - Fluoro should NOT be tied in with it (i.e. - split existing "ZONE 2567"); Simultaneously investigate need for installing Area Alarm Panels for each (none currently)
BLDG 1RMs 2568 & 2562CT 1 & Fluoro5.1.4.6.1 - all outlets/inlets require a ZONE valve (current service valves are not acceptable)Med Vac zone valve does not seem to exist for tie ins to CT 1 & Fluoro - only service valves; Necessary piping & zone valves need to be installed for each room (see note above for separate ZV to CT)
BLDG 1RMs 2801 & 2803Exam/work RM & Cath Lab A5.1.4.6.2 - zone valve is needed for EACH Category 1 spaceCath Lab A is a Category 1 space and requires its own zone valves/box - exam RM should NOT be tied in with it (i.e. - split existing "ZONE 2803"); Respective area alarm panel must be fixed/re-labeled or new one installed accordingly
BLDG 1RMs 2801 & 2803Exam/work RM & Cath Lab A5.1.4.6.2 (1) - ZV installed IMMEDIATELY outside the area controlledExisting Nitrogen ZV box outside RM 2805 - this is NOT immediately outside Cath Lab A; Box is also not on any current floor plans, does not have a Zone name, or proper labeling for area(s) serviced; This must also be split (see previous note); Respective area alarm panel must be fixed/re-labeled or new one installed accordingly
BLDG 1RM 2572IR Procedure RM5.1.4.6.2 (1) - ZV installed IMMEDIATELY outside the area controlledExisting Nitrogen ZV box outside RM 2773 - this is NOT immediately outside IR RM 2572 - but may be acceptable/open to interpretation; However, box is also not on any current floor plans, does not have a Zone name, or proper labeling for area serviced; Respective area alarm panel must be fixed/re-labeled or new one installed accordingly
BLDG 1RM 2571Cath Lab B5.1.4.6.2 - zone valve is needed for EACH Category 1 space & ZV IMMEDIATELY outside the areaUnable to locate the Nitrogen ZV for Cath Lab B, but shows on area alarm panel for room… Need to create a a separate ZV/box for Nitrogren to Cath Lab B & ensure it does NOT affect Cath Lab A & IR Nitrogen ZVs; Respective area alarm panel must be fixed/re-labeled or new one installed accordingly
BLDG 1RM 2066CT RM in Corridor 21005.1.4.6.2 - zone valve is needed for EACH Category 1 spaceNEED VERIFICATION ON CATEGORY 1 STATUS - check with clinical staff to see if spaces ever utilize mobile anesthesia carts… If so, space requires its own zone valves/box (i.e. - split existing "ZONE 2064"); Respective area alarm panel must be fixed/re-labeled or new one installed accordingly
BLDG 1RMs 2030, 2031, 2033, 2034, & 2037Nuc Med Area5.1.4.6.2 - zone valve is needed for EACH Category 1 spaceNEED VERIFICATION ON CATEGORY 1 STATUS - check with clinical staff to see if imaging spaces ever utilize mobile anesthesia carts… If so, spaces require their own zone valves/boxes (i.e. - split existing zones "ZONE 2031" & "ZONE 2028"); Respective area alarm panel must be fixed/re-labeled or new one installed accordingly
BLDG 1Whole west side of 5th floor5th west5.1.4.6.1 - all outlets/inlets require a ZONE valve (current service valves are not acceptable)Med Vac zone valve does not seem to exist for entire west side - only service valves; Necessary piping & zone valves need to be installed for each branch of west wing (mirror east end of 5th floor); Med air & oxygen are already have appropriate ZVs for west end; Determine if Area Alarm panel is also needed when updated & properly update/label

11 Decommissioning A.5.1.14.3.5 (p99-181) "When spaces are converted, the inlets and outlets should be addressed in one of the following ways: (1) Inlets and outlets removed and tubing capped, (2) Inlets and outlets plugged and provided with a blank-off plate, (3) Inlets and outlets remain accessible for maintenance and testing, (4) Other means deemed appropriate by the AHJ.

Proper decommisioning of systems should include identifying them as not in service. The associated zone valve box and alarm panels should be kept up-to-date with the chages made to rooms no longer served."

12
13
14
15
16
17
18
19
20
21
22

BLDG1 and 25 1st

Inspected=Blue, gray=NOT inspected
#EE #Physical Tag / LabelDeviceMFGDevice DescriptionCommentsLocationRoomPhysical LocationCurrent Status (as of 6/2022)Inspected 2021Inspected 2022Image:
1AIR 1Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1371Exam RM 1Active
2AIR 2Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1371Exam RM 1Active
3VAC 1Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1371Exam RM 1Active
4VAC 2Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1371Exam RM 1Active
5O2 1Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1371Exam RM 1Active
6O2 2Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1371Exam RM 1Active
7AIR 1Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1372Exam RM 2Active
8AIR 2Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1372Exam RM 2Active
9VAC 1Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1372Exam RM 2Active
10VAC 2Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1372Exam RM 2Active
11O2 1Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1372Exam RM 2Active
12O2 2Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1372Exam RM 2Active
13AIR 1Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1373Exam RM 3Active
14AIR 2Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1373Exam RM 3Active
15VAC 1Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1373Exam RM 3Active
16VAC 2Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1373Exam RM 3Active
17O2 1Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1373Exam RM 3Active
18O2 2Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1373Exam RM 3Active
19ED 1ED Alarm PanelTri-Tech MedicalArea Alarm PanelAlarm panel for ED Exam RMs 1-6 & Triage (RM 1362)Emergency DeptHallwayOutside Exam RM 4Active
20AIR 1Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1374Exam RM 4Active
21AIR 2Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1374Exam RM 4Active
22VAC 1Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1374Exam RM 4Active
23VAC 2Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1374Exam RM 4Active
24O2 1Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1374Exam RM 4Active
25O2 2Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1374Exam RM 4Active
26ED 2ED Alarm PanelTri-Tech MedicalArea Alarm PanelServes Exams 7-9, 10a-b, A, B, CEmergency DeptHallwayOutside Exam RM 6Active
27ZONE 1374Zone ValvesTri-Tech MedicalZone ValvesServes Exams 1-6, Triage (RMs 1371-1376, 1362)Emergency DeptHallwayOutside Exam RM 5Active
28AIR 1Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1375Exam RM 5Active
29AIR 2Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1375Exam RM 5Active
30VAC 1Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1375Exam RM 5Active
31VAC 2Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1375Exam RM 5Active
32O2 1Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1375Exam RM 5Active
33O2 2Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1375Exam RM 5Active
34AIR 1Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1376Exam RM 6Active
35AIR 2Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1376Exam RM 6Active
36VAC 1Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1376Exam RM 6Active
37VAC 2Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1376Exam RM 6Active
38O2 1Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1376Exam RM 6Active
39O2 2Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1376Exam RM 6Active
40AIR 1Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1362Triage - LeftActive
41AIR 2Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1362Triage - RightActive
42VAC 1Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1362Triage - LeftActive
43VAC 2Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1362Triage - RightActive
44O2 1Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1362Triage - LeftActive
45O2 2Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1362Triage - RightActive
46AIRMedical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1352Exam RM CActive
47VACMedical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1352Exam RM CActive
48O2Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1352Exam RM CActive
49AIRMedical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1354Exam RM BActive
50VACMedical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1354Exam RM BActive
51O2Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1354Exam RM BActive
52AIRMedical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1356Exam RM AActive
53VACMedical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1356Exam RM AActive
54O2Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1356Exam RM AActive
55AIR 1Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1361Exam RM 7Active
56AIR 2Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1361Exam RM 7Active
57VAC 1Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1361Exam RM 7Active
58VAC 2Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1361Exam RM 7Active
59O2 1Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1361Exam RM 7Active
60O2 2Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1361Exam RM 7Active
61AIRMedical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1363Exam RM 8 - IsolationActive
62VACMedical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1363Exam RM 8 - IsolationActive
63O2Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1363Exam RM 8 - IsolationActive
64AIRMedical Air OutletTri-Tech MedicalOutletGarage door closed in RM - didn't physically see outlets…Emergency DeptRM 1365Exam RM 9Active
65VACMedical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1365Exam RM 9Active
66O2Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1365Exam RM 9Active
67AIR 1Medical Air OutletTri-Tech MedicalOutletAll outlets on the same 1 boom located centrally in the roomEmergency DeptRM 1367Exam RM 10a/bActive
68AIR 2Medical Air OutletTri-Tech MedicalOutletEmergency DeptRM 1367Exam RM 10a/bActive
69VAC 1Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1367Exam RM 10a/bActive
70VAC 2Medical Vacuum OutletTri-Tech MedicalOutletEmergency DeptRM 1367Exam RM 10a/bActive
71O2 1Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1367Exam RM 10a/bActive
72O2 2Oxygen OutletTri-Tech MedicalOutletEmergency DeptRM 1367Exam RM 10a/bActive
73ZONE 1367Zone ValvesTri-Tech MedicalZone ValvesServes ED Exam RMs A, B, C, 7-10a/bEmergency DeptHallwayOutside Exam RM 10a/bActive
74AIRMedical Air OutletOXEQUIPOutlet7/26/23: Eye Clinic / Ophthalmology currently under renovation for new ENT/patient care areas; 7/27/23 per Rob Venner - maintain area as activeEye Clinic / OphthalmologyRM 1230Exam RM 10Active
75O2Oxygen OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1230Exam RM 10Active
76VACMedical Vacuum OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1230Exam RM 10Active
77AIRMedical Air OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1232Exam RM 9Active
78O2Oxygen OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1232Exam RM 9Active
79VACMedical Vacuum OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1232Exam RM 9Active
80AIRMedical Air OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1234Exam RM 8Active
81O2Oxygen OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1234Exam RM 8Active
82VACMedical Vacuum OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1234Exam RM 8Active
83AIRMedical Air OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1236Exam RM 7Active
84O2Oxygen OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1236Exam RM 7Active
85VACMedical Vacuum OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1236Exam RM 7Active
86AIRMedical Air OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1238Exam RM 6Active
87O2Oxygen OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1238Exam RM 6Active
88VACMedical Vacuum OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1238Exam RM 6Active
89AIRMedical Air OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1255Ophthalmology Laser RMActive
90O2Oxygen OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1255Ophthalmology Laser RMActive
91VACMedical Vacuum OutletOXEQUIPOutletEye Clinic / OphthalmologyRM 1255Ophthalmology Laser RMActive
92ZONE 1255Zone ValvesOXEQUIPZone ValvesServes Laser RM - RM 1255Eye Clinic / OphthalmologyHallwayOutside RM 1255Active
93ZONE 1230Zone ValvesOXEQUIPZone ValvesServes Exam RMs #6-10 (1230, 1232, 1234, 1236, & 1238)Eye Clinic / OphthalmologyHallwayOutside RM 1255Active
94ZONE MRI SUITEZone ValvesOhio MedicalZone ValvesServes MRI Suites (1715 & 1716) and MRI Staging (1709-3)MRI SuitesRM 1712MRI Control RMActive
95MRI AREAMRI Alarm PanelOhio MedicalArea Alarm PanelFor MRI Suites and MRI StagingMRI SuitesRM 1712MRI Control RMActive
96AIRMedical Air OutletOhio MedicalOutletMRI SuitesRM 1715MRI - 3.0TActive
97O2Oxygen OutletOhio MedicalOutletMRI SuitesRM 1715MRI - 3.0TActive
98VACMedical Vacuum OutletOhio MedicalOutletMRI SuitesRM 1715MRI - 3.0TActive
99AIRMedical Air OutletOhio MedicalOutletMRI SuitesRM 1716MRI - 1.5TActive
100O2Oxygen OutletOhio MedicalOutletMRI SuitesRM 1716MRI - 1.5TActive
101VACMedical Vacuum OutletOhio MedicalOutletMRI SuitesRM 1716MRI - 1.5TActive
102O2Oxygen OutletOhio MedicalOutletMRI StagingRM 1709Bay 1709-3Active
103AIR 1Medical Air OutletOhio MedicalOutletUltrasoundRM 1951Ultrasound Exam #1Active
104AIR 2Medical Air OutletOhio MedicalOutletUltrasoundRM 1951Ultrasound Exam #1Active
105VAC 1Medical Vacuum OutletOhio MedicalOutletUltrasoundRM 1951Ultrasound Exam #1Active
106VAC 2Medical Vacuum OutletOhio MedicalOutletUltrasoundRM 1951Ultrasound Exam #1Active
107O2 1Oxygen OutletOhio MedicalOutletUltrasoundRM 1951Ultrasound Exam #1Active
108O2 2Oxygen OutletOhio MedicalOutletUltrasoundRM 1951Ultrasound Exam #1Active
109AIRMedical Air OutletOhio MedicalOutletUltrasoundRM 1952Ultrasound Exam #2
110O2Oxygen OutletOhio MedicalOutletUltrasoundRM 1952Ultrasound Exam #2
111VACMedical Vacuum OutletOhio MedicalOutletUltrasoundRM 1952Ultrasound Exam #2
112AIRMedical Air OutletOhio MedicalOutletUltrasoundRM 1953Ultrasound Exam #3
113O2Oxygen OutletOhio MedicalOutletUltrasoundRM 1953Ultrasound Exam #3
114VACMedical Vacuum OutletOhio MedicalOutletUltrasoundRM 1953Ultrasound Exam #3
115AIRMedical Air OutletOhio MedicalOutletUltrasoundRM 1954Ultrasound Exam #4
116O2Oxygen OutletOhio MedicalOutletUltrasoundRM 1954Ultrasound Exam #4
117VACMedical Vacuum OutletOhio MedicalOutletUltrasoundRM 1954Ultrasound Exam #4
118AIRMedical Air OutletOhio MedicalOutletRadiologyRM 1915Cardiac Stress RM
119O2Oxygen OutletOhio MedicalOutletRadiologyRM 1915Cardiac Stress RM
120VACMedical Vacuum OutletOhio MedicalOutletRadiologyRM 1915Cardiac Stress RM
121AIRMedical Air OutletOhio MedicalOutletRadiologyRM 1901Nuc Med PET/SPECT
122O2Oxygen OutletOhio MedicalOutletRadiologyRM 1901Nuc Med PET/SPECT
123VACMedical Vacuum OutletOhio MedicalOutletRadiologyRM 1901Nuc Med PET/SPECT
124O2Oxygen OutletOhio MedicalOutletRadiologyRM 1903Nuc Med Dressing RM
125VACMedical Vacuum OutletOhio MedicalOutletRadiologyRM 1903Nuc Med Dressing RM
126O2Oxygen OutletOhio MedicalOutletRadiologyRM 1905Nuc Med Dressing RM
127VACMedical Vacuum OutletOhio MedicalOutletRadiologyRM 1905Nuc Med Dressing RM
128AIRMedical Air OutletOhio MedicalOutletRadiologyRM 1944SPECT/CT
129O2Oxygen OutletOhio MedicalOutletRadiologyRM 1944SPECT/CT
130VACMedical Vacuum OutletOhio MedicalOutletRadiologyRM 1944SPECT/CT
131AIRMedical Air OutletOhio MedicalOutletRadiologyRM 1909SPECT/CT
132O2Oxygen OutletOhio MedicalOutletRadiologyRM 1909SPECT/CT
133VACMedical Vacuum OutletOhio MedicalOutletRadiologyRM 1909SPECT/CT
134ZONE US/PET/SPECTZone Valve - Vac OnlyOhio MedicalZone ValveServes US & PET/SPECT (RMs 1901, 1903, 1905, 1909, 1915, 1944, 1951-1954)RadiologyHallwayOutside RM 1934 Uptake
135ZONE US/PET/SPECTZone Valve - Med Air & O2Ohio MedicalZone ValvesServes US & PET/SPECT (RMs 1901, 1903, 1905, 1909, 1915, 1944, 1951-1954)RadiologyHallwayOutside RM 1934 Uptake
136US/PET/SPECTUS/PET/SPECT Alarm PanelOhio MedicalLocal Alarm PanelFor US & PET/SPECT (RMs 1901, 1903, 1905, 1909, 1915, 1944, 1951-1954)RadiologyHallwayOutside RM 1934 Uptake
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305

BLDG1 2nd

BLDG 1, FLOOR 2Inspected=Blue, no color=NOT inspected
#EE #Physical Tag / LabelDeviceGas TypeMFGDevice DescriptionCommentsLocationRoomPhysical LocationCurrent Status (as of 6/2022)Inspected 2021Inspected 2022Image:
1ZONE 2423Zone ValvesMedical Air, Medical Vacuum, & OxygenTri-TechZone ValvesServes ICU RMs: 2401-2416; With Zone Valves: ZV-2423-101 (OX), ZV-2423-102 (MED AIR), & ZV-2423-103 (MED VAC)ICUHallwayOutside RM 2424Active
2NO LABELArea Alarm Panel-Tri-TechICU Alarm PanelMonitors ICU RMs: 2401-2416; No real AAP label...ICUNurse StationOutside RM 2438 in nurse station areaActive
3AIR 1Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2401Active
4AIR 2Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2401Active
5VAC 1Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2401Active
6VAC 2Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2401Active
7VAC 3Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2401Active
8VAC 4Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2401Active
9VAC 5Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2401Active
10VAC 6Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2401Active
11O2 1Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2401Active
12O2 2Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2401Active
13O2 3Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2401Active
14O2 4Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2401Active
15AIR 1Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2402Active
16AIR 2Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2402Active
17VAC 1Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2402Active
18VAC 2Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2402Active
19VAC 3Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2402Active
20VAC 4Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2402Active
21VAC 5Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2402Active
22VAC 6Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2402Active
23O2 1Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2402Active
24O2 2Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2402Active
25O2 3Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2402Active
26O2 4Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2402Active
27AIR 1Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2403Active
28AIR 2Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2403Active
29VAC 1Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2403Active
30VAC 2Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2403Active
31VAC 3Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2403Active
32VAC 4Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2403Active
33VAC 5Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2403Active
34VAC 6Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2403Active
35O2 1Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2403Active
36O2 2Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2403Active
37O2 3Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2403Active
38O2 4Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2403Active
39AIR 1Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2404Active
40AIR 2Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2404Active
41VAC 1Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2404Active
42VAC 2Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2404Active
43VAC 3Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2404Active
44VAC 4Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2404Active
45VAC 5Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2404Active
46VAC 6Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2404Active
47O2 1Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2404Active
48O2 2Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2404Active
49O2 3Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2404Active
50O2 4Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2404Active
51AIR 1Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2405Active
52AIR 2Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2405Active
53VAC 1Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2405Active
54VAC 2Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2405Active
55VAC 3Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2405Active
56VAC 4Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2405Active
57VAC 5Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2405Active
58VAC 6Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2405Active
59O2 1Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2405Active
60O2 2Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2405Active
61O2 3Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2405Active
62O2 4Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2405Active
63AIR 1Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2406Active
64AIR 2Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2406Active
65VAC 1Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2406Active
66VAC 2Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2406Active
67VAC 3Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2406Active
68VAC 4Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2406Active
69VAC 5Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2406Active
70VAC 6Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2406Active
71O2 1Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2406Active
72O2 2Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2406Active
73O2 3Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2406Active
74O2 4Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2406Active
75AIR 1Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2407Active
76AIR 2Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2407Active
77VAC 1Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2407Active
78VAC 2Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2407Active
79VAC 3Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2407Active
80VAC 4Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2407Active
81VAC 5Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2407Active
82VAC 6Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2407Active
83O2 1Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2407Active
84O2 2Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2407Active
85O2 3Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2407Active
86O2 4Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2407Active
87AIR 1Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2408Active
88AIR 2Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2408Active
89VAC 1Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2408Active
90VAC 2Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2408Active
91VAC 3Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2408Active
92VAC 4Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2408Active
93VAC 5Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2408Active
94VAC 6Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2408Active
95O2 1Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2408Active
96O2 2Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2408Active
97O2 3Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2408Active
98O2 4Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2408Active
99AIR 1Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2409Active
100AIR 2Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2409Active
101VAC 1Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2409Active
102VAC 2Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2409Active
103VAC 3Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2409Active
104VAC 4Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2409Active
105VAC 5Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2409Active
106VAC 6Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2409Active
107O2 1Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2409Active
108O2 2Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2409Active
109O2 3Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2409Active
110O2 4Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2409Active
111AIR 1Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2410Active
112AIR 2Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2410Active
113VAC 1Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2410Active
114VAC 2Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2410Active
115VAC 3Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2410Active
116VAC 4Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2410Active
117VAC 5Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2410Active
118VAC 6Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2410Active
119O2 1Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2410Active
120O2 2Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2410Active
121O2 3Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2410Active
122O2 4Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2410Active
123AIR 1Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2411Active
124AIR 2Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2411Active
125VAC 1Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2411Active
126VAC 2Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2411Active
127VAC 3Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2411Active
128VAC 4Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2411Active
129VAC 5Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2411Active
130VAC 6Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2411Active
131O2 1Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2411Active
132O2 2Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2411Active
133O2 3Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2411Active
134O2 4Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2411Active
135AIR 1Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2412Active
136AIR 2Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2412Active
137VAC 1Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2412Active
138VAC 2Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2412Active
139VAC 3Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2412Active
140VAC 4Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2412Active
141VAC 5Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2412Active
142VAC 6Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2412Active
143O2 1Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2412Active
144O2 2Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2412Active
145O2 3Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2412Active
146O2 4Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2412Active
147AIR 1Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2413Active
148AIR 2Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2413Active
149VAC 1Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2413Active
150VAC 2Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2413Active
151VAC 3Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2413Active
152VAC 4Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2413Active
153VAC 5Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2413Active
154VAC 6Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2413Active
155O2 1Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2413Active
156O2 2Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2413Active
157O2 3Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2413Active
158O2 4Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2413Active
159AIR 1Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2414Active
160AIR 2Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2414Active
161VAC 1Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2414Active
162VAC 2Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2414Active
163VAC 3Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2414Active
164VAC 4Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2414Active
165VAC 5Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2414Active
166VAC 6Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2414Active
167O2 1Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2414Active
168O2 2Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2414Active
169O2 3Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2414Active
170O2 4Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2414Active
171AIR 1Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2415Active
172AIR 2Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2415Active
173VAC 1Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2415Active
174VAC 2Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2415Active
175VAC 3Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2415Active
176VAC 4Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2415Active
177VAC 5Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2415Active
178VAC 6Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2415Active
179O2 1Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2415Active
180O2 2Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2415Active
181O2 3Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2415Active
182O2 4Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2415Active
183AIR 1Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2416Active
184AIR 2Medical Air OutletMedical AirHillromOutletOn Hillrom headboardICURM 2416Active
185VAC 1Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2416Active
186VAC 2Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2416Active
187VAC 3Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2416Active
188VAC 4Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2416Active
189VAC 5Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2416Active
190VAC 6Medical Vacuum OutletMedical VacuumHillromOutletOn Hillrom headboardICURM 2416Active
191O2 1Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2416Active
192O2 2Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2416Active
193O2 3Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2416Active
194O2 4Oxygen OutletOxygenHillromOutletOn Hillrom headboardICURM 2416Active
195NO LABELZone Valve - Nitrous OxideNitrous OxideAir ProductsZone ValveZone Valve 25V-NO-127; Unsure of areas served & says Out of Svc - requires verificationHallwayHallwayOutside RM 2255 waiting areaActive
196NO LABELZone Valve - OxygenOxygenAir ProductsZone ValveZone Valve 25V-OX-128; Unsure of areas served & says Out of Svc - requires verificationHallwayHallwayOutside RM 2103DActive
197ZONE 2100Zone ValvesMedical Air, Medical Vacuum, & OxygenChemtronZone ValvesServes ECHO Labs 1-3 & Treadmill - RMs: 2102A-B, 2102D, & 2103B; Zone Valves: ZV-2100-101 (O2), ZV-2100-102 (MED AIR), & ZV-2100-103 (MED VAC)EchoHallwayOutside RM 2103AActive
198NO LABELAlarm Panel-ChemtronArea Alarm PanelServes ECHO Labs 1-3 & Treadmill - RMs: 2102A-B, 2102D, & 2103B; No real label/name…EchoHallwayOutside RM 2102AActive
199AIRMedical Air OutletMedical AirOXEQUIPOutletEchoRM 2103BECHO #1Active
200VACMedical Vacuum OutletMedical VacuumOXEQUIPOutletEchoRM 2103BECHO #1Active
201O2Oxygen OutletOxygenOXEQUIPOutletEchoRM 2103BECHO #1Active
202AIRMedical Air OutletMedical AirOXEQUIPOutletEchoRM 2102 DECHO #2Active
203VACMedical Vacuum OutletMedical VacuumOXEQUIPOutletEchoRM 2102 DECHO #2Active
204O2Oxygen OutletOxygenOXEQUIPOutletEchoRM 2102 DECHO #2Active
205AIRMedical Air OutletMedical AirOXEQUIPOutletEchoRM 2102 BECHO #3Active
206VACMedical Vacuum OutletMedical VacuumOXEQUIPOutletEchoRM 2102 BECHO #3Active
207O2Oxygen OutletOxygenOXEQUIPOutletEchoRM 2102 BECHO #3Active
208AIRMedical Air OutletMedical AirOXEQUIPOutletEchoRM 2102 AECHO TreadmillActive
209VACMedical Vacuum OutletMedical VacuumOXEQUIPOutletEchoRM 2102 AECHO TreadmillActive
210O2Oxygen OutletOxygenOXEQUIPOutletEchoRM 2102 AECHO TreadmillActive
211AIRMedical Air OutletMedical AirChemtronOutletUNSURE IF SEPT ZONE VALVE BOX IS NEEDED - WEIGH IN FROM CLINICAL STAFF - ARE MOBILE ANES CARTS EVER USED?RadiologyRM 2066CT ScannerActive
212VACMedical Vacuum OutletMedical VacuumChemtronOutletRadiologyRM 2066CT ScannerActive
213O2Oxygen OutletOxygenChemtronOutletRadiologyRM 2066CT ScannerActive