This solicitation is for the rehabilitation of the historic sheriff's house at First State National Historical Park in New Castle, Delaware. The project scope includes rehabilitating the structure located at 211 Delaware Street. This requirement was previously solicited under solicitation 140P2021R0064 but no contract award was made. Offerors are to provide all labor, materials, equipment and supervision required to complete the rehabilitation of the historic property in accordance with the solicitation requirements. The contracting agency is the National Park Service within the Department of the Interior. Products and services must meet preservation standards for historic properties. The period of performance is to be determined.

View the file

Other files

Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COVER

FIRST STATE NATIONAL

HISTORICAL PARK

REHABILITATE HISTORIC SHERIFF’S HOUSE

PMIS No. FRST - 240745

HAZARDOUS MATERIALS SURVEY

July 22, 2019

GWWO Project No. 18053

FIRST STATE NATIONAL

HISTORICAL PARK - REHABILITATE

HISTORIC SHERIFF’S HOUSE

GWWO, Inc.

TABLE OF CONTENTS

HAZARDOUS MATERIALS SURVEY

GWWO Architects First State National Historical Park, Rehabilitate Historic Sheriff’s House New Castle, Delaware December 2018

Table of Contents

1.0 Introduction

2.0 Asbestos-containing Materials Survey

2.1 Methodology

2.2 Findings and Recommendations

3.0 Lead-based Paint Survey

3.1 Methodology

3.2 Findings and Recommendations

4.0 Universal & Regulated Wastes

4.1 Mercury

4.2 Polychlorinated Biphenyls

4.3 Other Potentially Regulated and Hazardous Wastes

Appendix A Asbestos Bulk Sampling Results Appendix B Summary of Materials Tested for Asbestos Appendix C Lead-based Paint Data Sheets Appendix D Photographic Log

Pre-Alteration Hazardous Material Survey First State National Historical Park Rehabilitate Historic Sheriff’s House 211 Delaware Street New Castle, Delaware 19720

800 Wyman Park Drive, Suite 300 Baltimore, Maryland 21211

FIRST STATE NATIONAL HISTORICAL PARK

First State National Historical Park, Rehabilitate Historic Sheriff’s House

EXECUTIVE SUMMARY

Arc Environmental, Inc. performed a pre-alteration hazardous material survey at the Historic Sheriff’s House located within the First State National Historical Park (Site) to evaluate building materials likely to be impacted by planned renovation and/or construction activities. The Site is located at 211 Delaware Street in New Castle, Delaware. The survey was performed to evaluate the Site for the presence and assessment of suspect asbestos-containing materials (ACMs), lead-based paint (LBP), and inventorying of universal/regulated wastes. The survey was performed on November 26 through November 27, 2018.

During the survey, a total of 42 bulk samples were collected from 14 identified homogenous areas suspected of containing asbestos throughout the Site. Based on the findings of the asbestos survey, one

(1) of the sampled homogeneous materials were confirmed by laboratory analysis to be asbestos-containing materials. The confirmed ACM (cementitious ceiling panels) is located within the exterior mechanical room. Additionally, three suspect materials, including the roof matrix, grey roof caulk and white roof caulk, were presumed to be asbestos-containing; the assumed ACMs were not sampled due to inaccessibility and/or based on an effort to maintain the integrity of the material. Section 2.0 of this report discusses in detail the asbestos survey and findings.

The lead-based paint survey was conducted at the Site using a portable X-ray Fluorescence (XRF) device for screening to determine if LBP was present at the site. Testing revealed that lead-based paint was present on interior components including: wood window components, wood baseboard, wood door components, plaster and concrete walls, wood wall trim, wood wall spindle, wood corner table/shelf, wood transom, wood wainscoting, wood shutter door, wood bathroom stall partition, wood riser trim, plaster column, wood closet shelf and walls. Lead-based paint was present on exterior window. Section

3.0 provides detail regarding the LBP survey.

Visual inspection was performed to identify and quantify Universal and regulated wastes associated with the Site. Potentially regulated and/or Universal wastes inventoried include potentially mercury-containing fluorescent tubes and potentially polychlorinated biphenyl (PCB)-containing ballasts. Section 4.0 provides details regarding the universal and regulated waste survey

Prepared by:

Derek Kwon Project Manager, Industrial Hygiene

Pre-alteration Hazardous Material Survey First State National Historical Park, Rehabilitate Historic Sheriff’s House December 28, 2018

1.0 Introduction

Arc Environmental, Inc. of Baltimore, Maryland, was retained by GWWO Architects to conduct a pre-alteration survey for hazardous materials at the Historic Sheriff’s House, located at the First State National Historic Park (Site). The Site is located at 211 Delaware Street in New Castle, Delaware. The inspection included the assessment and sampling of suspect, accessible asbestos-containing materials (ACMs) and testing of painted/coated building components to identify lead-based paint (LBP) along with a visual inspection to identify any universal/regulated waste. The findings of the survey are presented in this report. The survey was conducted by Arc Environmental on November 26 through November 27, 2018.

2.0 Asbestos-containing Materials Survey

2.1 Methodology

The asbestos survey included the identification, assessment, and sampling of suspect asbestos-containing materials. The survey was conducted under protocols established by the Environmental Protection Agency (EPA) 40 Code of Federal Regulations (CFR) 763 Asbestos Hazard Emergency Response Act (AHERA) and 40 CFR 61 Subpart M, National Emission Standards for Hazardous Air Pollutants

(NESHAP).

Every reasonable attempt was made to locate suspect asbestos-containing materials (ACMs) present as thermal system insulation (TSI), surfacing material, or other miscellaneous materials. Specifically, Arc Environmental employed the following protocols while performing the survey: flooring materials were penetrated to the subfloor to determine how many layers of flooring were present; wall systems and ceiling systems were evaluated to identify suspect building materials associated with the systems themselves, as well as any accessible cavities; and mechanical insulation systems were evaluated to identify potential suspect insulation beneath jackets and wraps. The survey was limited to accessible areas throughout the building and did not include roof sampling.

During the survey, a total of 42 bulk samples were collected from 14 suspect homogenous areas identified throughout the accessible portions of the Site. The bulk samples of suspect ACMs were submitted, along with the corresponding chain-of-custody forms to Scientific Analytical Institute, Inc. (SAI) to determine the presence of asbestos in the sampled materials. SAI is accredited for asbestos analysis in bulk materials through the National Voluntary Laboratory Accreditation Program (NVLAP). A copy of the laboratory’s NVLAP accreditation is included in Appendix A of this report.

The bulk samples were analyzed using polarized light microscopy (PLM/Dispersion Staining following the EPA method 600/R-93/116, Method for the Determination of Asbestos in Bulk Building Materials).

Based on the United States Environmental Protection Agency's (USEPA’s) definition, a material which contains greater than one percent (1%) asbestos, as determined using the methods specified in Appendix E, Subpart E, 40 CFR Part 763, Section 1, Polarized Light Microscopy (PLM), is considered an ACM and must be handled according to OSHA, USEPA, and the Delaware Department of Natural Resources and Environmental Control (DNREC).

2.2 Findings and Recommendations

Table 1 summarizes the data for Identified Asbestos-containing Materials at the Site. A copy of the chain of custody forms and Laboratory Analytical Results are included in Appendix A.

First State National Historical Park, A complete list of the building materials sampled during this survey is presented in Appendix B. It is recommended that if additional suspect materials not identified in this report are uncovered/exposed during demolition or construction activities, the materials should be assumed to contain asbestos or sampled and analyzed via PLM for asbestos content to determine if they are ACMs.

Table 1: Identified Asbestos-containing Materials

HA Description Location Total Quantity

TR1 Cementitious Ceiling Panels Exterior Mechanical Room Ceiling 320 SF

RM1* Roof Matrix Roof TBD

CK4* Grey Caulking on Roof Roof TBD

CK5* White Caulking on Roof Roof TBD

*Assumed material that was not sampled due to inaccessibility and/or to maintain the integrity of the material.

The roof matrix is considered a Category I Non-friable material. The EPA regulates Category I non-friable materials (resilient floor coverings, asphalt roof product, gaskets, and packings) when these materials have been rendered friable. Category I non-friable materials may become friable if subjected to sanding, grinding, cutting, or abrading. The Category I non-friable ACMs should be removed prior to disturbance if these materials will be impacted by planned activities at the Site.

The cementitious ceiling panels and various roof caulking are classified by the USEPA as Category II Non-friable materials. Category II non-friable materials are regulated if they have a high probability of becoming or have become crumbled, pulverized, or reduced to powder by the forces expected to impact the materials during the course of demolition or renovation activities. If these materials to remain in place and will not be altered during renovation activities, the materials can be managed in place.

The identified ACM(s) should be removed from the Site prior to renovations which may disturb the identified material(s). All abatement actions should be performed by personnel trained in accordance with USEPA, OSHA, and the DNREC for asbestos-related activities. In addition, a licensed asbestos consultant should be retained to conduct oversight and air-monitoring during any abatement activities.

In addition, if other suspect materials are encountered during demolition that may be impacted, these materials should be sampled and analyzed by PLM to verify asbestos content, or be assumed as ACM, prior to disturbance.

3.0 Lead-based Paint Survey

3.1 Methodology

Painted surfaces within the project area were visually inspected to determine their condition. A lead screening survey was conducted using an X-ray Fluorescence (XRF) Spectrum Analyzer on painted building surfaces and/or components. Surfaces that are intact or deteriorated condition (as defined by the U.S. Department of Housing and Urban Development Guidelines) do not pose an immediate health risk, First State National Historical Park, regardless of the lead content. Leaded paint in poor condition is a priority lead-hazard and should be promptly addressed using approved Lead Safe Work Practices.

The screening included field readings in addition to periodic calibration checks to ensure that the instrument is within acceptable calibration parameters. Lead-based paint, when tested via XRF, is defined by the U.S. Department of Housing and Urban Development (HUD) and the state of Delaware as paint having lead concentrations equal to or in excess of 1.0 milligrams per square centimeter (mg/cm²). The results of the lead-based paint survey are summarized in the XRF Lead-based Paint Inspection Data Sheets included in Appendix C.

3.2 Results

Of the 226 field screening shots, 108 of the XRF readings obtained from surfaces and coatings within the project area were found to contain lead in levels equal to or greater than the 1.0 mg/cm2 guideline for lead-based paint for DNREC. All of the XRF readings are detailed on the “XRF Lead-Based Paint Testing Data Sheets” attached to this report and are given in mg/cm2.

On the XRF data sheets, components described with a wall code of "A" are located on the closest wall with the same orientation as the front of the building. Components within each room are then assigned a letter B, C, or D in a clockwise manner based on the location of wall A.

3.3 ConclusionsandRecommendations

Components identified to be affected with lead-based paint or lead-based coatings include: wooden window casing, wooden window sill, wood window, wood baseboard, wood door casing, wood door trim, wood door, plaster wall, wood wall trim, wood wall spindle, wood corner table/shelf, wood transom, wood wainscoting, concrete wall, wooden shudder door, wooden bathroom stall partition, wooden riser trim, plaster column, wood closet shelf and plaster closet wall.

The OSHA Lead in Construction standard applies to all construction work where an employee may be occupationally exposed to lead. This standard does not indicate a specific percentage or mass per area (mg/cm2) of lead in paint that is permissible during construction/demolition activities. There is no acceptable concentration for lead under the OSHA lead standard that eliminates the requirement for contractors to comply with this regulation. Due to lead-based and lead-containing paint (paint containing detectable levels of lead but having concentrations below the lead-based paint threshold) associated with the Site, OSHA worker protection requirements for lead must be followed during renovation and/or demolition activities. It is recommended that a licensed lead abatement firm be utilized for any historical or non-historical components which may be intended to be stabilized or abated of lead-based paint through stripping, blasting, etc.

Building renovation and/or demolition activities have the potential to produce hazardous waste if lead-based paint is dry scraped, dry sanded, or heated. All renovation activities must incorporate lead Toxicity Characteristic Leaching Procedure (TCLP) testing of the construction debris prior to its disposal in accordance with the Resource Conservation and Recovery Act (RCRA). The hazardous waste criteria for lead waste is established under RCRA, Subtitle C, as 5.0 milligrams per liter (mg/L) measured with the TCLP as listed in CFR 40 Part 261. A representative sample of anticipated or generated waste stream (i.e., demolition debris) should be collected for purposes of TCLP testing to determine disposal options.

The lead-based paint debris generated during demolition should be handled in accordance with all applicable Federal and Delaware regulations.

First State National Historical Park,

4.0 Universal & Regulated Wastes

Arc Environmental conducted a visual inspection for Universal Wastes (UWs) and other potentially regulated and hazardous wastes within the project area. As per 40 Code of Federal Regulations (CFR) 261 Subpart C, UWs include any of the following six wastes that have at least one hazardous characteristic: batteries, pesticides, thermostats, cathode ray tubes, mercury-containing devices, and mercury-containing lamps (e.g., fluorescent tubes and high intensity discharge lamps). These wastes require proper handling and disposal methods when no longer in use or prior to completing any planned renovation/demolition activities. All identified Universal and potentially regulated wastes must be handled, transported, and disposed of in accordance with applicable regulations prior to the renovation of the Site.

4.1 Mercury

Arc Environmental observed 80 fluorescent tubes within the Historic Sheriff’s House. These fluorescent tubes are assumed to contain mercury. Mercury containing fluorescent tubes will require proper removal and disposal in accordance with USEPA regulations listed in 40 CFR Part 273.

4.2 PolychlorinatedBiphenyls

Arc Environmental conducted a visual inspection for PCB-containing light ballasts within fluorescent fixtures along with other potential PCB-containing equipment and material at the Site. If light fixtures containing ballasts were observed in the building, Arc personnel accessed the ballasts and recorded information from the manufacturer’s label. All capacitors and fluorescent light ballasts that are not labeled as “non-PCB” were assumed to contain PCBs. Arc Environmental observed 26 ballasts with the potential to contain PCBs. PCB ballasts will require proper removal and disposal in accordance with USEPA regulations listed in 40 CFR Part 273.

Although some of the ballasts may not contain PCBs, they likely contain other regulated liquids. Arc Environmental recommends collecting and separating all fluorescent light ballasts by type during the demolition process. The ballasts should then be characterized for disposal in accordance with federal, state and local regulations.

4.3 Other PotentiallyRegulatedandHazardousWastes

If other wastes are encountered during any renovation, or demolition activities, they will need to be removed and disposed of prior to any demolition activities due to the potential for releases incidences impacted the environmental. These other wastes will require proper handing, removal and disposal methods much like the UWs prior to any planned alterations or demolition at the Site.

Appendix A:

Asbestos Bulk Sampling Results

REHABILITATE HISTORIC SHERIFF’S HOUSE

GWWO, Inc.

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Bethany Nichols (58)

Analyst Approved Signatory P-F-002 r15 1/16/2021

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888 Page 1 of 8

Customer: ARC Environmental

1311 Haubert Rd Baltimore, MD 21230

Attn: Stacy Kahatapitiya Lab Order ID: 51831597 Analysis ID: 51831597_PLM Date Received: 12/3/2018

Project: First State National Historical Park Rehabilitate Historic Sheriff's House

Date Reported: 12/5/2018

Sample ID Description Asbestos Fibrous

Components Non-Fibrous Components

Attributes Lab Sample ID Lab Notes Treatment

PL1-1

Plaster

None Detected

70% Other 30% Quartz

Gray Non Fibrous Homogeneous single layer plaster Crushed 51831597PLM_1

PL1-2

Gray Non Fibrous single layer plaster Crushed 51831597PLM_2

PL1-3

Gray Non Fibrous single layer plaster Crushed 51831597PLM_3

PL1-4 - A

100% Other

White Non Fibrous finish Crushed 51831597PLM_4

PL1-4 - B

Gray Non Fibrous base Crushed 51831597PLM_43

PL1-5 - A

Non Fibrous finish Crushed 51831597PLM_5

PL1-5 - B

Gray Non Fibrous base Crushed 51831597PLM_44

PL1-6 - A

Non Fibrous finish Crushed 51831597PLM_6

By Polarized Light Microscopy

EPA Method: 600/R-93/116 and 40 CFR, Part 763, Subpart E, App.E

GWWO, Inc.

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Bethany Nichols (58)

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888 Page 2 of 8

Baltimore, MD 21230

Attn: Stacy Kahatapitiya Lab Order ID: 51831597 Analysis ID: 51831597_PLM Date Received: 12/3/2018

Project: First State National Historical Park

Components Non-Fibrous Components

PL1-6 - B

Gray Non Fibrous base Crushed 51831597PLM_45

PL1-7 - A

Non Fibrous finish Crushed 51831597PLM_7

PL1-7 - B

Gray Non Fibrous base Crushed 51831597PLM_46

DW1-8

Drywall

20% Cellulose

80% Other

Gray, Brown Fibrous Heterogeneous

Teased, Crushed 51831597PLM_8

DW1-9

Fibrous

Teased, Crushed 51831597PLM_9

DW1-10

Fibrous

Teased, Crushed 51831597PLM_10

WG1-11

Interior Window Glazing

Non Fibrous

Dissolved 51831597PLM_11

WG1-12

Non Fibrous

Dissolved 51831597PLM_12

REHABILITATE HISTORIC SHERIFF’S HOUSE

GWWO, Inc.

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Bethany Nichols (58)

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888 Page 3 of 8

Baltimore, MD 21230

Attn: Stacy Kahatapitiya Lab Order ID: 51831597 Analysis ID: 51831597_PLM Date Received: 12/3/2018

Project: First State National Historical Park

Components Non-Fibrous Components

WG1-13

Non Fibrous

Dissolved 51831597PLM_13

LN1-14 - A

Black Floor Sheeting

40% Cellulose

60% Other

Green, Black, Tan Fibrous sheet vinyl Dissolved, Ashed 51831597PLM_14

LN1-14 - B

50% Cellulose

50% Other

Fibrous mastic/paper Dissolved, Ashed 51831597PLM_47

LN1-15 - A

Fibrous sheet vinyl Dissolved, Ashed 51831597PLM_15

LN1-15 - B

Fibrous mastic/paper Dissolved, Ashed 51831597PLM_48

LN1-16 - A

Fibrous sheet vinyl Dissolved, Ashed 51831597PLM_16

LN1-16 - B

Fibrous mastic/paper Dissolved, Ashed 51831597PLM_49

LN2-17 - A

White Linoleum Sheeting with Square and Diamond Pattern

15% Cellulose 10% Fiber Glass

75% Other

Fibrous sheet vinyl 1 Dissolved, Teased 51831597PLM_17

GWWO, Inc.

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Bethany Nichols (58)

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888 Page 4 of 8

Baltimore, MD 21230

Attn: Stacy Kahatapitiya Lab Order ID: 51831597 Analysis ID: 51831597_PLM Date Received: 12/3/2018

Project: First State National Historical Park

Components Non-Fibrous Components

LN2-17 - B

Beige Non Fibrous mastic Dissolved 51831597PLM_50

LN2-17 - C

Green, Tan Fibrous sheet vinyl 2 Dissolved, Ashed 51831597PLM_51

LN2-17 - D

Brown, Gray Fibrous mastic/paper Dissolved, Ashed 51831597PLM_52

LN2-18 - A

Fibrous sheet vinyl 1 Dissolved, Teased 51831597PLM_18

LN2-18 - B

Non Fibrous mastic Dissolved 51831597PLM_53

LN2-18 - C

Green, Tan Fibrous sheet vinyl 2 Dissolved, Ashed 51831597PLM_54

LN2-18 - D

Fibrous mastic/paper Dissolved, Ashed 51831597PLM_55

LN2-19 - A

Fibrous sheet vinyl 1 Dissolved, Teased 51831597PLM_19

REHABILITATE HISTORIC SHERIFF’S HOUSE

GWWO, Inc.

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Bethany Nichols (58)

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888 Page 5 of 8

Baltimore, MD 21230

Attn: Stacy Kahatapitiya Lab Order ID: 51831597 Analysis ID: 51831597_PLM Date Received: 12/3/2018

Project: First State National Historical Park

Components Non-Fibrous Components

LN2-19 - B

Fibrous mastic Dissolved, Teased 51831597PLM_56

LN2-19 - C

Non Fibrous sheet vinyl 2 Dissolved 51831597PLM_57

LN2-19 - D

10% Cellulose

90% Other

Fibrous mastic/paper Dissolved, Ashed 51831597PLM_58

RF1-20

Residual Flooring and Mastic

90% Cellulose

10% Other

Gray, White Fibrous paper/mastic Dissolved, Ashed 51831597PLM_20

RF1-21

Residual Flooring and Mastic

90% Cellulose

10% Other

Gray, White Fibrous paper/mastic Dissolved, Ashed 51831597PLM_21

RLN1-22

Residual LN1

Tan, Black Non Fibrous mastic on foam Dissolved 51831597PLM_22

RLNF-23

Non Fibrous mastic on foam Dissolved 51831597PLM_23

RLNF-24

Non Fibrous mastic on foam Dissolved 51831597PLM_24

GWWO, Inc.

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Bethany Nichols (58)

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888 Page 6 of 8

Baltimore, MD 21230

Attn: Stacy Kahatapitiya Lab Order ID: 51831597 Analysis ID: 51831597_PLM Date Received: 12/3/2018

Project: First State National Historical Park

Components Non-Fibrous Components

JC1-25

Joint Compound

Non Fibrous

Crushed 51831597PLM_25

JC1-26

Non Fibrous

Crushed 51831597PLM_26

JC1-27

Non Fibrous

Crushed 51831597PLM_27

CK1-28

Green Exterior Caulk

Brown Non Fibrous

Dissolved, Ashed 51831597PLM_28

CK-29

Green Exterior Caulk

Non Fibrous

Dissolved, Ashed 51831597PLM_29

CK2-30

Grey Exterior Caulk

Non Fibrous

Dissolved, Ashed 51831597PLM_30

CK2-31

Grey Exterior Caulk

Non Fibrous

Dissolved, Ashed 51831597PLM_31

CK3-32

Pink Exterior Caulk

Non Fibrous

Dissolved, Ashed 51831597PLM_32

REHABILITATE HISTORIC SHERIFF’S HOUSE

GWWO, Inc.

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Bethany Nichols (58)

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888 Page 7 of 8

Baltimore, MD 21230

Attn: Stacy Kahatapitiya Lab Order ID: 51831597 Analysis ID: 51831597_PLM Date Received: 12/3/2018

Project: First State National Historical Park

Components Non-Fibrous Components

CK3-33

Pink Exterior Caulk

Non Fibrous

Dissolved, Ashed 51831597PLM_33

TR1-34

Transite Ceiling

20% Chrysotile

Gray Fibrous

Teased 51831597PLM_34

TR1-35

Fibrous

Teased 51831597PLM_35

TR1-36

Fibrous

Teased 51831597PLM_36

PIM1-37

White Pipe Seam Sealant Mastic

White, Tan Fibrous

Dissolved, Teased 51831597PLM_37

PIM1-38

Fibrous

Dissolved, Teased 51831597PLM_38

PIM1-39

Fibrous

Dissolved, Teased 51831597PLM_39

BP1-40

Boiler Pad

Non Fibrous

Crushed 51831597PLM_40

GWWO, Inc.

Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.

Bethany Nichols (58)

Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888 Page 8 of 8

Baltimore, MD 21230

Attn: Stacy Kahatapitiya Lab Order ID: 51831597 Analysis ID: 51831597_PLM Date Received: 12/3/2018

Project: First State National Historical Park

Components Non-Fibrous Components

BP1-41

Non Fibrous

Crushed 51831597PLM_41

BP1-42

Non Fibrous

Crushed 51831597PLM_42

Appendix B:

Summary of Materials Tested for Asbestos

Summary of Sampled Suspect Materials First State National Historical Park, Historic Sheriff’s House

Homogeneous Area Material Description Sample Numbers Results

PL1 Plaster 1, 2, 3, 4, 5, 6, 7 NAD

DW1 Drywall 8, 9, 10 NAD

WG1 Interior White Window Glazing 11, 12, 13 NAD

LN1 Black Floor Sheeting 14, 15, 16 NAD

LN2 White Linoleum Sheeting with Square and Red Diamond Pattern 17, 18, 19 NAD

RF1 Residual Flooring and Mastic 20, 21 NAD

RLN1 Residual of LN1 Potentially 22, 23, 24 NAD

JC1 Joint Compound 25, 26, 27 NAD

CK1 Green Exterior Caulk Around Door 28, 29 NAD

CK2 Grey Exterior Caulk On Steps 30, 31 NAD

CK3 Pink Exterior Caulk 32, 33 NAD

TR1 Cementitious Ceiling Panels 34, 35, 36 20% Chrysotile

PIM1 Pipe Seam Sealant Mastic White 37, 38, 39 NAD

BP1 Boiler Pad 40, 41, 42 NAD

NAD: No Asbestos Detected

Summary of Sampled Suspect Materials First State National Historical Park, Historic Sheriff’s House

Homogeneous Area Material Description Sample Numbers Results

PL1 Plaster 1, 2, 3, 4, 5, 6, 7 NAD

DW1 Drywall 8, 9, 10 NAD

WG1 Interior White Window Glazing 11, 12, 13 NAD

LN1 Black Floor Sheeting 14, 15, 16 NAD

LN2 White Linoleum Sheeting with Square and Red Diamond Pattern 17, 18, 19 NAD

RF1 Residual Flooring and Mastic 20, 21 NAD

RLN1 Residual of LN1 Potentially 22, 23, 24 NAD

JC1 Joint Compound 25, 26, 27 NAD

CK1 Green Exterior Caulk Around Door 28, 29 NAD

CK2 Grey Exterior Caulk On Steps 30, 31 NAD

CK3 Pink Exterior Caulk 32, 33 NAD

TR1 Cementitious Ceiling Panels 34, 35, 36 20% Chrysotile

PIM1 Pipe Seam Sealant Mastic White 37, 38, 39 NAD

BP1 Boiler Pad 40, 41, 42 NAD

NAD: No Asbestos Detected

Appendix C:

Lead-based Paint Data Sheets

XRF Lead-Based Paint Testing Data Sheet

First State National Historical Park Sheriff's House 211 Delaware Street -

Inspection Date: 11/26/2018 Action Level 1.0

Floor

Wall

Room

Component

Substrate

Paint Condition

Lead (mg/cm2)

Classification

Calibration

N/A

0.9

Calibration N/A N/A 1.0 N/A

Calibration N/A N/A 1.0 N/A 1st Floor D Front, Left Wall Plaster Deteriorated -0.1 Negative 1st Floor A Front, Left Window Casing Wood Deteriorated >9.9 Positive 1st Floor A Front, Left Window Sill Wood Deteriorated >9.9 Positive 1st Floor A Front, Left Window Wood Intact 2.3 Positive 1st Floor A Front, Left Radiator Metal Intact -0.1 Negative 1st Floor C Front, Left Wall Plaster Deteriorated 0.0 Negative 1st Floor D Front, Left Baseboard Wood Deteriorated >9.9 Positive 1st Floor D Front, Left Door Casing Wood Deteriorated >9.9 Positive 1st Floor D Front, Left Door Trim Wood Deteriorated >9.9 Positive 1st Floor B Front, Left Wall Plaster Deterioratedd 0.0 Negative 1st Floor A Front, Left Pipe Metal Intact 0.3 Negative 1st Floor - Front, Left Floor Wood Intact -0.3 Negative 1st Floor A Front, Right Window Sill Wood Deteriorated >9.9 Positive 1st Floor A Front, Right Window Casing Wood Deteriorated >9.9 Positive 1st Floor A Front, Right Window Trim Wood Deteriorated >9.9 Positive 1st Floor A Front, Right Window Wood Intact 5.1 Positive 1st Floor B Front, Right Baseboard Wood Intact >9.9 Positive 1st Floor C Front, Right Fireplace Mantel Wood Intact -0.1 Negative 1st Floor D Front, Right Wall Plaster Deteriorated -0.1 Negative 1st Floor C Front, Right Fireplace Façade Wood Intact 0.1 Negative 1st Floor B Front, Right Door Wood Deteriorated >9.9 Positive 1st Floor - Entry Hall Door (Exterior) Wood Intact -0.1 Negative 1st Floor A Entry Hall Door (Interior) Wood Intact -0.1 Negative 1st Floor A Entry Hall Door Casing Wood Intact 0.3 Negative 1st Floor D Entry Hall Wall at Entry Plaster Deteriorated >9.9 Positive 1st Floor D Entry Hall Wall Plaster Deteriorated 0.7 Negative 1st Floor B Entry Hall Trim Wood Deteriorated 3.3 Positive 1st Floor B Entry Hall Wall at Entry Plaster Deteriorated 2.0 Positive 1st Floor B Entry Hall Wall Drywall Intact -0.3 Negative 1st Floor D Entry Hall Radiator Metal Intact -0.1 Negative 1st Floor B Entry Hall Baseboard Wood Deteriorated >9.9 Positive 1st Floor Center Entry Hall Baluster Wood Intact -0.1 Negative 1st Floor Center Entry Hall Spindle Wood Deteriorated 8.5 Positive 1st Floor B Side Entry Corner Table/Shelf Wood Deteriorated >9.9 Positive 1st Floor A Side Entry Door Casing Wood Deteriorated >9.9 Positive 1st Floor A Side Entry Door Wood Intact >9.9 Positive 1st Floor B Side Entry Door Wood Intact 1.7 Positive 1st Floor B Side Entry Transom Wood Intact >9.9 Positive 1st Floor C Side Entry Wall Plaster Intact 5.0 Positive 1st Floor B Side Entry Wall Plaster Intact >9.9 Positive 1st Floor A Side Entry Wall Plaster Intact 0.0 Negative 1st Floor D Side Entry Door Wood Intact -0.7 Negative 1st Floor C Side Entry Door Wood Deteriorated >9.9 Positive 1st Floor A Under Stair Wall Wood Intact >9.9 Positive 1st Floor C Under Stair Wall Plaster Deteriorated >9.9 Positive 1st Floor C Under Stair Baseboard Wood Deteriorated >9.9 Positive 1st Floor C Side Hall Wall Drywall Intact -0.2 Negative 1st Floor D Side Hall Door Trim Wood Intact -0.2 Negative 1st Floor D Side Hall Door Wood Deteriorated >9.9 Positive 1st Floor A Side Hall Wainscotting Wood Intact 5.0 Positive 1st Floor A Side Hall Wall Plaster Deteriorated 1.9 Positive 1st Floor B Rear, Left Wall Plaster Deteriorated 1.4 Positive 1st Floor B Rear, Left Wainscotting Wood Intact 3.6 Positive 1st Floor C Rear, Left Window Casing Wood Deteriorated >9.9 Positive 1st Floor C Rear, Left Window Trim Wood Deteriorated 5.0 Positive 1st Floor C Rear, Left Window Wood Intact 3.2 Positive 1st Floor D Rear, Left Wall Drywall Intact -0.3 Negative 1st Floor D Rear, Left Baseboard Wood Intact -0.2 Negative 1st Floor C Center, Left Door Wood Deteriorated >9.9 Positive 1st Floor D Center, Left Mantel Wood Intact 0.4 Negative 1st Floor D Center, Left Wainscotting Wood Deteriorated 3.5 Positive 1st Floor D Center, Left Wall Plaster Deteriorated 2.0 Positive 1st Floor C Center, Left Wall Drywall Intact -0.2 Negative 1st Floor C To Exit Door Wood Intact -0.1 Negative 1st Floor C To Exit Door Trim Wood Intact -0.2 Negative 1st Floor C To Exit Wall Concrete Deteriorated 0.0 Negative 1st Floor C To Exit Wainscotting Wood Deteriorated 5.1 Positive 1st Floor D To Exit Wall Plaster Deterioratedd 0.3 Negative 1st Floor D Restroom Wall Concrete Deteriorated 1.3 Positive 1st Floor A Restroom Closet Trim Wood Intact -0.1 Negative 1st Floor C Restroom Closet Door Wood Intact -0.1 Negative 1st Floor C Restroom Shudder Door Wood Deteriorated 3.7 Positive 1st Floor C Restroom Wall Drywall Intact -0.3 Negative

1st Floor A Restroom Door Trim Wood Intact 0.0 Negative 1st Floor A Restroom Door Wood Deteriorated >9.9 Positive 1st Floor A Restroom Stall Partition Wood Deteriorated 3.3 Positive 1st Floor Center Restroom Door to Cell Wood Deteriorated >9.9 Positive 1st Floor D Restroom Wall Concrete Deterioratedd 0.1 Negative 1st Floor B Cell Security Bar Metal Deterioratedd 0 Negative 1st Floor D Cell Exterior Wall Concrete Deterioratedd 0.5 Negative 1st Floor D Cell Exterior Door Wood Intact -0.4 Negative 1st Floor D Cell Door Casing Wood Deteriorated >9.9 Positive 1st Floor B Cell at Hallway Wall Concrete Deteriorated 1.3 Positive 1st Floor B Cell at Hallway Door Wood Deteriorated >9.9 Positive 1st Floor A Cell at Hallway Baluster Wood Intact 0.3 Negative 1st Floor Center Stairs Stair Tread Wood Deteriorated -0.1 Negative 1st Floor B Stairs Wall Plaster Deteriorated >9.9 Positive 1st Floor C Stairs Wall Plaster Deterioratedd -0.2 Negative

Calibration N/A N/A 0.8 Negative

Calibration N/A N/A 0.8 Negative

Calibration N/A N/A 0.8 Negative 1st Floor A Wall Plaster Intact 0 Negative 1st Floor D Door Wood Intact -0.9 Negative 1st Floor C Door Wood Deteriorated >9.9 Positive 1st Floor A Under Stair Wall Wood Intact >9.9 Positive 1st Floor C Under Stair Wall Plaster Deteriorated >9.9 Positive 1st Floor C Baseboard Wood Deteriorated >9.9 Positive 1st Floor C Side Hall Wall Drywall Intact -0.2 Negative 1st Floor D Side Hall Door Trim Wood Intact -0.02 Negative 1st Floor D Side Hall Door Wood Deteriorated >9.9 Positive 1st Floor A Side Hall Wainscotting Wood Intact 5 Positive 1st Floor A Side Hall Wall Concrete Deteriorated 1.9 Positive 1st Floor B Rear, Left Wall Plaster Deteriorated 1.4 Positive 1st Floor B Rear, Left Wainscotting Wood Intact 3.6 Positive 1st Floor C Rear, Left Window Casing Wood Deteriorated >9.9 Positive 1st Floor C Rear, Left Window Trim Wood Deteriorated 5 Positive 1st Floor C Rear, Left Window Wood Intact 3.2 Positive 1st Floor D Rear, Left Wall Drywall Intact -0.3 Negative 1st Floor D Rear, Left Baseboard Wood Intact -0.2 Negative 1st Floor C Center, Left Door Wood Deteriorated >9.9 Positive 1st Floor D Center, Left Mantel Wood Intact 0.4 Negative 1st Floor D Center, Left Wainscotting Wood Deteriorated 3.5 Positive 1st Floor D Center, Left Wall Plaster Deteriorated 2 Positive 1st Floor C Center, Left Wall Drywall Intact -0.2 Negative 1st Floor C To Ext Door Wood Intact -0.1 Negative 1st Floor C To Ext Door Trim Wood Intact -0.2 Negative 1st Floor C To Ext Wall Concrete Deteriorated 0 Negative 1st Floor D To Ext Wainscotting Wood Deteriorated 5.9 Positive 1st Floor D To Ext Wall Plaster Deteriorated 0.3 Negative 1st Floor A Restrooms Wall Concrete Deteriorated 1.3 Positive 1st Floor C Restrooms Closet Trim Wood Intact -0.1 Negative 1st Floor C Restrooms Shudder Door Wood Deteriorated 3.07 Positive 1st Floor A Restrooms Wall Drywall Intact -0.3 Negative 1st Floor A Restrooms Door Trim Wood Intact 0 Negative 1st Floor A Restroom Door Wood Deteriorated >9.9 Positive 1st Floor Center Restroom Stall Partiton Wood Deteriorated 3.3 Positive 1st Floor D Restroom Door to Cells Wood Deteriorated >9.9 Positive 1st Floor B Cells Wall Concrete Deteriorated 0.1 Negative 1st Floor D Cells Security Bar Metal Intact 0 Negative 1st Floor D Cells Exterior Wall Concrete Deterioratedd 0.5 Negative 1st Floor D Cells Ext Door Wood Intact -0.4 Negative 1st Floor B Cell @ Hallway Casing - Door Wood Deteriorated >9.9 Positive 1st Floor B Cell @ Hallway Wall Concrete Deteriorated 1.3 Positive 1st Floor B Cell @ Hallway Door Wood Deteriorated >9.9 Positive 1st Floor N/A Stairs Baluster Wood Intact 0.3 Negative 1st Floor B Stairs Stair tread Wood Deteriorated -0.1 Negative 1st Floor B Stairwell Wall Plaster Deteriorated >9.9 Positive 1st Floor B Stairwell Wall Plaster Deteriorated 0.2 Negative 1st Floor B Stairs Baseboard Wood Intact >9.9 Positive 1st Floor Center Stairs Stringer Wood Intact -0.1 Negative 1st Floor Center Stairs Riser Trim Wood Deteriorated >9.9 Positive 2nd Floor C Foyer/Landing Wall Plaster Deteriorated >9.9 Positive 2nd Floor C Foyer/Landing Column Plaster Deteriorated 9.9 Positive 2nd Floor D Foyer/Landing Wall Plaster Deteriorated 0.4 Negative 2nd Floor D Foyer/Landing Window Sill Wood Deteriorated >9.9 Positive 2nd Floor D Foyer/Landing Window Trim Wood Deteriorated >9.9 Positive 2nd Floor B Hallway Wall Plaster Deteriorated 0.5 Negative 2nd Floor D Hallway Wall Plaster Deteriorated 0.5 Negative 2nd Floor B Hallway Baseboard Wood Intact >9.9 Positive 2nd Floor C Hallway Trim Door Wood Intact >9.9 Positive 2nd Floor C Hallway Door Wood Deteriorated >9.9 Positive 2nd Floor A Rear, Left Wall Plaster Deteriorated -0.2 Negative 2nd Floor B Rear, Left Wall Plaster Deteriorated -0.2 Negative 2nd Floor C Rear, Left Window Trim Wood Deteriorated >9.9 Positive 2nd Floor C Rear, Left Window Wood Intact 0 Negative 2nd Floor B Rear, LC Wall Plaster Deteriorated -0.1 Negative

2nd Floor C Rear, LC Wall Plaster Deteriorated -0.1 Negative 2nd Floor A Rear, LC Door Wood Deteriorated >9.9 Positive 2nd Floor A Rear, LC Closet Shelf Wood Deteriorated 0.2 Negative 2nd Floor A Rear, LC Closet Wall Plaster Deteriorated -0.2 Negative 2nd Floor D Rear, LC Transom Wood Deteriorated >9.9 Positive 2nd Floor A Bathroom Door Wood Deteriorated >9.9 Positive 2nd Floor B Bathroom Wall Plaster Deteriorated >9.9 Positive 2nd Floor D Bathroom Wall Plaster Deteriorated >9.9 Positive 2nd Floor B Bathroom Wainscotting Wood Deteriorated >9.9 Positive 2nd Floor D Bathroom Window Sill Wood Deteriorated >9.9 Positive 2nd Floor B Front, Left Chimney Plaster Deteriorated 0 Negative 2nd Floor A Front, Left Baseboard Wood Intact >9.9 Positive 2nd Floor A Front, Left Window Wood Intact 3.2 Positive 2nd Floor C Front, Left Closet Shelf Wood Intact >9.9 Positive 2nd Floor C Front, Left Closet Wall Plaster Intact 2.08 Positive 2nd Floor C Front, Left Door Wood Deteriorated >9.9 Positive 2nd Floor A Front, Left Window Sill Wood Deteriorated >9.9 Positive 2nd Floor D Front, Left Door Trim Wood Intact >9.9 Positive 2nd Floor A Front, Center Window Trim Wood Deteriorated >9.9 Positive 2nd Floor D Front, Center Wall Plaster Deteriorated 0.1 Negative 2nd Floor D Front, Center Radiator Metal Intact -0.1 Negative 2nd Floor B Front, Center Wall Plaster Deteriorated -0.1 Negative 2nd Floor Floor Front, Center Floor Wood Intact 0 Negative 2nd Floor C Front, Center Door Wood Deteriorated >9.9 Positive 2nd Floor A Front, RC Wall Plaster Deteriorated -0.4 Negative 2nd Floor C Rear Front RC Wall Plaster Deteriorated -0.6 Negative 2nd Floor C Rear Front RC Door Casing Wood Intact 79.9 Positive 2nd Floor C Rear Front RC Door Wood Intact 79.9 Positive 2nd Floor B 2nd Fl. Front, Right Wall Plaster Deteriorated -0.5 Negative 2nd Floor C 2nd Fl. Front, Right Wall Plaster Deteriorated 0 Negative 2nd Floor A 2nd Fl. Front, Right Baseboard Wood Intact >9.9 Positive 2nd Floor A Front, Right Window Sill Wood Deteriorated 2.4 Positive 2nd Floor A Front, Right Window Trim Wood Deteriorated 9.9 Positive 2nd Floor D Front, Right Closet Door Wood Deteriorated >9.9 Positive 2nd Floor D Front, Right Closet Wall Plaster Deteriorated -0.2 Negative 2nd Floor Ceiling Front, Right Closet Shelf Wood Deteriorated -0.2 Negative 2nd Floor C Front, Right Ceiling Plaster Deteriorated 0 Negative Basement C Stair Wall Wood Intact 0.2 Negative Basement A Stair Wall Plaster Deteriorated 0.2 Negative Basement N/A Stair Ceiling Plaster Intact -0.2 Negative Basement D Front, Left, MER Wall Drywall Intact -0.4 Negative Basement D Front, Left, MER Door Wood Intact -0.3 Negative Basement D Front, Left, MER Door Casing Metal Intact -0.2 Negative Basement A Front, Left, MER Window Wood Intact -0.2 Negative Basement N/A Front, Left, MER Ceiling Drywall Intact -0.3 Negative Basement B Hallway Arch Plaster Intact 0.3 Negative Basement A Front, Right Window Wood Intact -0.2 Negative Basement Center Front, Right Column/Beam Wood Deteriorated 0.3 Negative Basement C Front, Right Wall Plaster Intact 0.5 Negative Basement N/A Front, Right Pole Metal Deteriorated 0 Negative Basement N/A Front, Right I beam Metal Deteriorated 0.6 Negative Basement N/A Front, Right I beam Metal Deteriorated 0.7 Negative Basement B Rear, Left Door Trim Wood Intact -0.2 Negative Basement C Basement Wall Plaster Intact 0.5 Negative Basement N/A Basement Ceiling Joist Wood Deteriorated 0 Negative Basement D Vault Door Metal Deteriorated >9.9 Positive Basement B Vault Wood Intact 0.2 Negative Basement N/A Vault Ceiling Header Wood Intact 0 Negative

Exterior A Exterior Window Wood Intact 4.3 Positive Exterior A Exterior Gate Wood Deteriorated -0.1 Negative Exterior A Exterior Gate Trim Wood Deteriorated -0.1 Negative Exterior A Exterior Shudder Window Wood Intact -0.1 Negative Exterior A Exterior Shudder Trim Wood Intact -0.2 Negative Exterior A Exterior Door Trim Wood Intact 0.3 Negative Exterior A Exterior Door Wood Intact 0.2 Negative Exterior D Exterior Shudder Window Wood Intact -0.1 Negative Exterior D Exterior Door Casing Wood Intact -0.2 Negative Exterior D Exterior Door Wood Intact -0.3 Negative Exterior D Exterior Fence Wood Intact 0.1 Negative Exterior A Exterior Window Trim Wood Intact 0.2 Negative Exterior A Exterior Handrail Wood Intact 0.2 Negative

Calibration 0.8 Calibration 0.8 Calibration 0.8

Appendix D:

Photographic Log

1311 Haubert Street, Baltimore, Maryland 21230 | P 410. 659.9971 F 410.962.1065

PHOTO 1 Date Site Surveyed:

November 26-27, 2018

First State National Historical Park – Rehabilitate Historic

Sheriff’s House

Non-asbestos-containing flooring and associated mastic.

Non-asbestos-containing interior window glazing.

Non-asbestos-containing pipe seam sealant on fiberglass.

Asbestos-containing cementitious panels in exterior-accessed mechanical room.

REHABILITATE HISTORIC SHERIFF’S HOUSE

PHOTO 2 Date Site Surveyed:

First State National Historical

Assumed asbestos-containing roofing products.

Non-asbestos-containing two-coat plaster.

Non-asbestos-containing resilient sheet goods. Non-asbestos-containing residual flooring mastic.

PHOTO 3 Date Site Surveyed:

First State National Historical

Lead-based paint on wood door and baseboard components.

Lead-based paint on wood components and plaster walls..

Lead-based paint on interior wood window components.

Lead-based paint on vault door.

REHABILITATE HISTORIC SHERIFF’S HOUSE

PHOTO 4 Date Site Surveyed:

First State National Historical

Stored paint cans on Site. Lead-based paint on exterior wood window.

Lead-based paint on interior wood transom and door components.

Lead-based paint on interior waintscotting.