This is an asbestos survey report conducted by Atlas Technical Consultants LLC for the Gloria Ford Site in Garden Valley, Idaho, prior to building demolition. The survey was performed on July 19, 2021, and reported on July 26, 2021.

The survey identified asbestos-containing materials (ACM) in four categories: joint compound in drywall throughout the building (2% asbestos, Regulated ACM); surfacing layer on greenboard wall backing in the living room northeast corner (~200 ft², 2% asbestos, Category II non-friable); smooth texture on drywall ceilings in side room, bedroom, hallway, bathroom, and kitchen (~2,200 ft², 2% asbestos, Category II non-friable); and orange peel texture on drywall in the dining room (~800 ft², 2% asbestos, Category II non-friable). All identified asbestos materials contain chrysotile fiber at or near the regulatory limit. The survey notes that wiring was not sampled due to building vacancy and disrepair, and flooring materials could not be assessed due to heavy dirt accumulation. The report emphasizes that asbestos abatement using special removal methods will be required for all identified ACM prior to demolition. A National Emission Standard for Hazardous Air Pollutants (NESHAP) Competent Person should be on-site during demolition to address any previously unidentified suspect materials in accordance with EPA regulations 40 CFR Part 61. Detailed bulk sample analysis results and an ACM location map are included as supporting documentation.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PAGE #1 OF 2

PRINT DATE 7/26/2021

B211968e – ACM TCLP 2791 S Victory View Way, Boise, ID 83709

208.376.4748 | oneatlas.com

LESLIE ELDRIDGE, CHMM, P.E.

WATER, CIVIL AND ENVIRONMENTAL INC.

514 North 16th Street Boise, Idaho 83702

Project: Gloria Ford Site, Garden Valley, Idaho – Asbestos Survey

Ladies and Gentlemen:

Atlas Technical Consultants LLC (ATLAS) has conducted an asbestos survey of the former Gloria Ford Residence, a house near Garden Valley, Idaho, prior to demolition. The analysis results are attached.

At the time of the survey, the buildings were vacant and in a state of disrepair. As a result, wiring was not sampled as part of the survey. Furthermore, much of the flooring materials in the building were covered in a 2 to 4-foot thick layer of dirt, and removing it to assess the flooring was not practical. Our survey identified the following Asbestos Containing Materials (ACM):

Sample Number

Material Location

Asbestos Category1 Friable1 Quantity2

2-03, 04, 05, 06, 07

Joint compound Drywall throughout building

2%3 RACM

3-09, 10 Surfacing Layer on Greenboard Wall Backing

Living Room (Northeast corner)

2%3 II No ~200 ft2

7-19, 20, 21, 22

Smooth Texture on Drywall

Ceilings in side room, bedroom;

throughout hallway, bathroom, and kitchen.

2%3 II No ~2200 ft2

8-24, 25 Orange Peel Texture on

Drywall Dining Room 2%3 II No ~800 ft2

1Category of building material as it exists in the building, as installed, and as observed during the inspection. Condition may change depending upon demolition or renovation techniques.

2 Quantities are estimations only and must be verified by the Abatement Contactor.

3 Based on the results being at or near the regulatory limit for abatement, ATLAS recommends point count analysis to aid in quantification.

The United States Environmental Protection Agency’s National Emission Standard for Hazardous Air Pollutants (NESHAP), Asbestos Final Rule currently classifies asbestos under three separate categories; they are as follows:

Category I Non-friable ACM: This category includes all asphalt roofing products and resilient flooring products (floor tile and sheet flooring). In theory, these materials consist mostly of cohesive elements which rarely release significant numbers of asbestos fibers into the air, even when they are damaged. In practice, however, roofing and flooring can become brittle or crumbly with age and be damaged enough by construction equipment to release fibers into the air during removal. At this point, the EPA requires special methods during removal and handling of the materials to protect people against fiber release. If, on a specific renovation or demolition project, there is a chance of fiber release associated with roofing or flooring, we assume that special methods (abatement by

Appendix C.

PAGE #2 OF 2

PRINT DATE 7/26/2021

B211968e – ACM TCLP 2791 S Victory View Way, Boise, ID 83709

208.376.4748 | oneatlas.com removal) will be required. In the case of intentional burning, all ACM, friable or non-friable, must be removed prior to any such activities.

Category II Non-friable ACM: This category includes all other non-friable asbestos containing materials. These materials must always be removed using special abatement methods if they are expected to be disturbed or damaged in any way during renovation or removal activities.

Regulated Asbestos Containing Materials (RACM): All friable asbestos containing materials, including Category I and II materials that have become or will become friable due to renovation or demolition activities. Friable asbestos is defined as any material containing more than one percent asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure.

These materials must always be removed using special abatement methods prior to any renovation or demolition activity.

ATLAS was able to perform some limited destructive sampling, which included exposing walls, ceilings, removing floor coverings, etc. However, ATLAS cannot guarantee that hidden ACM is not still present in the building without complete deconstruction of the structure. Additional sampling may be necessary if demolition or renovation activities expose previously unidentified suspect materials. During demolition or renovation activities, a National Emission Standard for Hazardous Air Pollutants (NESHAP) Competent Person should be on site in the event additional ACM is discovered and/or disturbed as outlined in Environmental Protection Agency (EPA) regulations 40 CFR Part 61.

ATLAS is pleased to have this opportunity to serve you and looks forward to a continuing relationship as your environmental consultant. If you have any questions regarding this letter or the attached analysis result please feel free to contact ATLAS at (208) 376-4748.

Respectfully Submitted, David Decker Reviewed by: Jennifer Babione Project Manager Environmental Services Asst. Manager

PAGE #1 OF 2

REVISION DATE 7/26/2021

rpt001b

2791 S Victory View Way, Boise, ID 83709

208.376.4748 | oneatlas.com

LESLIE ELDRIDGE ATLAS FILE #: B211968e

WATER, CIVIL, AND ENVIRONMENTAL INC.

514 N. 16TH ST.

BOISE, ID 83702

Project: Gloria Ford Site Date Received: 7/19/2021 P.O. Number: Date Reported: 7/26/2021

Atlas Technical Consultants, LLC has conducted the following survey of the above-mentioned project per the client’s request. Please reference the Cover Letter for location, quantity, and condition of each of the materials sampled below.

ASBESTOS BULK SAMPLE ANALYSIS REPORT

Sample Number

Lab Number Sample Type, Location, and Description Asbestos

Fibers Non-Asbestos

Fibers Non-Fibrous

Materials Comments

1-1 B180608

Layer 1 – sheet vinyl flooring-kitchen-stone mosaic pattern compact resilient NAD 100% other

Layer 2 – backing-green fibrous NAD 85% cellulose 10% synthetic fiber 5% other

Layer 3 – mastic-cream pliable NAD 100% mastic

1-2 B180609

Layer 1 – sheet vinyl flooring-dining room-stone mosaic pattern compact resilient NAD 100% other

Layer 2 – backing-green fibrous NAD 85% cellulose 10% synthetic fiber 5% other

Layer 3 – mastic-cream pliable NAD 100% mastic

2-3 B180610 Joint compound-side room ceiling-grey semi compact powdery with fibers 2% Chrysotile 98% other

2-4 B180611 Joint compound-kitchen ceiling

PS 2-5 B180612 Joint compound-hallway 2-6 B180613 Joint compound-bathroom 2-7 B180614 Joint compound-bathroom

3-8 B180615 Paint on green board-living room north east corner-white semi compact powdery with fibers

NAD 10% cellulose 90% other No surfacing or felt present

3-9 B180616

Layer 1 – surfacing-living room north east corner-white semi compact powdery with fibers 2% Chrysotile 98% other

Layer 2 – green board-white semi compact powdery with fibers NAD 10% cellulose 90% other

Layer 3 – felt-black bituminous fibrous NAD 80% cellulose 20% other

3-10 B180617 Green board-living room north east corner PS

4-11 B180618 Asphalt shingle-roof outside north east corner kitchen-black bituminous fibrous NAD 40% cellulose 60% other

4-12 B180619 Asphalt shingle-roof north east corner near bedroom-black bituminous fibrous NAD 40% cellulose 60% other

5-13 B180620 Felt-under cedar shake south east corner of roof- black bituminous fibrous NAD 70% cellulose 30% other

5-14 B180621 Felt-under cedar shake south west corner of roof- black bituminous fibrous NAD 70% cellulose 30% other

6-15 B180622 Paint on drywall-living room ceiling north west corner-white semi compact powdery with fibers

NAD 10% cellulose 90% other No surfacing present

6-16 B180623 Paint on drywall-living room ceiling north west corner-white semi compact powdery with fibers

NAD 10% cellulose 90% other No surfacing present

PAGE #2 OF 2

REVISION DATE 7/26/2021

rpt001b

2791 S Victory View Way, Boise, ID 83709

208.376.4748 | oneatlas.com

Sample Number

Lab Number Sample Type, Location, and Description Asbestos

Fibers Non-Asbestos

Fibers Non-Fibrous

Materials Comments

6-17 B180624 Paint on drywall-living room ceiling north west corner-white semi compact powdery with fibers

NAD 10% cellulose 90% other No surfacing present

7-18 B180625 Paint on drywall-side room ceiling-white semi compact powdery with fibers NAD 10% cellulose 90% other No texture present

7-19 B180626

Layer 1 – smooth texture-kitchen south east corner-tan semi compact powdery with fibers 2% Chrysotile 98% other

Layer 2 – drywall-white semi compact powdery with fibers NAD 10% cellulose 90% other

7-20 B180627 Smooth texture on drywall-hall ceiling north side

PS 7-21 B180628 Smooth texture on drywall-bedroom ceiling east wall

7-22 B180629 Smooth texture on drywall-bathroom north west corner

8-23 B180630 Paint on drywall-dining room ceiling south side-white semi compact powdery with fibers NAD 10% cellulose 90% other No texture present

8-24 B180631

Layer 1 – orange peel texture-dining room north west corner-tan semi compact powdery with fibers 2% Chrysotile 98% other

Layer 2 – drywall-white semi compact powdery with fibers NAD 10% cellulose 90% other

8-25 B180632 Orange peel texture on drywall-dining room south west corner PS

9-26 B180633 Unfinished drywall-shed north east corner-white semi compact powdery with fibers NAD 10% cellulose 90% other

9-27 B180634 Unfinished drywall-shed south east corner-white semi compact powdery with fibers NAD 10% cellulose 90% other

9-28 B180635 Unfinished drywall-shed south west corner-white semi compact powdery with fibers NAD 10% cellulose 90% other

Sample component percentages may not total 100% for multi-layered samples

Glossary of Acronyms

NAD - No Asbestos Detected TRACE - Detectable but not quantifiable PS – Positive Stop – Not Analyzed IS - Insufficient Sample -percentages may be inaccurate AFC - Asbestos Found As Contaminant

Sampled by: Client

Analyzed by: David Kesner Chief Microscopist

Sample components are identified using polarized light microscopy (PLM) coupled with dispersion staining methods as determined by visual estimation. Small asbestos fibers may not be detected by PLM due to the resolution limitations of the optical microscope. Detecting asbestos in non-friable organically bound materials is not consistently reliable using PLM analysis. This test report relates only to the items tested in the sample as submitted to the laboratory.

Analysis method: Polarized Light Microscopy (PLM) by EPA/600/R-93/116 with Central Stop Dispersion by NIOSH 9002 American Industrial Hygiene Association (AIHA) Performance Analytical Testing (PAT) Laboratory Number 101571

rpt001b (4).pdf
Glossary of Acronyms

File details come from the government source that posted it. Updated .