This document contains a federal contract opportunity for construction services. The Department of Veterans Affairs Technology Acquisition Center Austin is soliciting bids for a Minor Construction - Medical Specialty Clinic project at the Mather VA Medical Center in California. The contractor will be responsible for site preparation including demolition and removal of existing structures, and construction of a new 6,12-122 Medical Specialties building. The project scope includes foundations, superstructure, mechanical, electrical, plumbing and special systems, landscaping, and other required site improvements. The response deadline and anticipated award date are not specified.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
L L
ELECTRICAL ABBREVIATIONS LIST
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL
CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BYPHENYL
PC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
W2 TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BFG BELOW FINISHED GRADE
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICER
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEC GROUNDING ELECTRODE CONDUCTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MBJ MAIN BONDING JUMPER
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
A1 b
E1 c d
T1
'LPN'
ELECTRICAL SYMBOL NOTES
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
'LPN'-1,3,5
GENERAL ELECTRICAL NOTES
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL
ELECTRICAL CODE AND VA STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING
CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING
HARDWARE TO SUIT THE PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT
DURING CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.
PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST
COMPLY WITH "BUY AMERICAN ACT".
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT
MANUFACTURER'S SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S
SCREW TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED
(MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED
THIRD PARTY TESTING AGENCY.
17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE
GOVERNMENT, SHALL BE PROVIDED.
19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
20. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".
ELECTRICAL SYMBOL LEGEND
120V DUPLEX RECEPTACLE
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
120V DUPLEX RECEPTACLE EMERGENCY OUTLET
AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
SYMBOL HEIGHT DESCRIPTION
18"
18"
18"
18"
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
SPECIAL RECEPTACLE
EQUIPMENT CONNECTION
AS
NOTED
E
208V DUPLEX RECEPTACLE18"
18"
120V DUPLEX RECEPTACLE FLOOR BOX
120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
120V QUADUPLEX RECEPTACLE FLOOR BOX
120V QUADUPLEX RECEPTACLE EMERGENCY
FLOOR BOX OUTLET AND COVER PLATE SHALL BE
RED IN COLOR
CLNG
J
J
J
JUNCTION BOX, CEILING MOUNTED, PURPOSE AS
NOTED
JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS
NOTED
LIGHTING SYMBOL LEGEND
2' X 2' RECESSED DIRECT/INDIRECT TROFFER
2' X 4' RECESSED DIRECT/INDIRECT TROFFER
SYMBOL
HEIGHT
AFF * DESCRIPTION
--- 4' INDUSTRIAL STRIP
POLE MOUNTED LIGHTPOLE MNTD
6" DIAMETER RECESSED DOWNLIGHT---
EXIT SIGN - WALL MOUNTED
EXIT SIGN - CEILING MOUNTED---
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, DUAL TECHNOLOGY
VS: VACANCY SENSOR, DUAL TECHNOLOGY
VSD: VACANCY SENSOR DIMMER, LINE VOLTAGE
DUAL TECHNOLOGY
LV: LOW VOLTAGE
LVD: LOW VOLTAGE DIMMER
D: LINE VOLTAGE DIMMER
T: DIGITAL TIMER
3: 3 WAY
4: 4 WAY
48"
CENTER
OCCUPANCY SENSOR, DUAL
TECHNOLOGY - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
OCCUPANCY SENSOR, DUAL
TECHNOLOGY - WALL/CORNER MOUNTED
2' LINEAR - WALL MOUNTED
7'-0"
CENTER
EMERGENCY LIGHT BATTERY
OPERATED - WALL MOUNTED
7'-6"
CENTER
RC
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE
LISTED HERE.
LIGHT LEVEL SENSOR, SINGLE ZONE
DIMMING CLOSED LOOP - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL
DEVICE WITH 0-10V DIMMING
RCD
4' LINEAR - WALL MOUNTED
7'-0"
CENTER
OS
OS
LS
EXTERIOR WALL MOUNTED LIGHT
10'-0"
CENTER
1. ITEM 01:
A. DELETE ALL WORK AND MATERIAL FOR SUPPORT STEEL FOR ROOF SCREENS. (FROM TOP FLANGE OF ROOF STEEL UP). DELETE ALL WORK AND MATERIAL FOR
INSTALLATION OF ROOF SCREEN. DELETE ALL ROOFING WORK ASSOCIATED WITH FLASHING IN VERTICAL SCREEN SUPPORTS. SEE STRUCTURAL AND ARCHITECTURAL
DRAWINGS.
B. REMOVE ALL WORK AND MATERIAL TO INSTALL BASIS OF DESIGN: HERMAN MILLER COMBO CASEWORK/SINKS AT ALL LOCATIONS AND REPLACE WITH HAND SINK AND
SOLID SURFACE SPLASH PROTECTON. SEE PLUMBING AND INTERIOR DRAWINGS.
C. DELETE ALL WORK AND MATERIAL TO INSTALL GENERATOR, INCLUDING WIRING, AND CONCRETE GENERATOR PAD. SEE CIVIL AND ELECTRICAL DRAWINGS.
2. ITEM 02:
A. INSTALL MANUAL SWING DOORS IN LIEU OF AUTOMATIC SLIDING DOORS AT VESTIBULE 100 (2 PAIRS) SEE ARCHITECTUAL DRAWINGS.
3. ITEM 03:
A. DELETE ALL WORK AND MATERIAL FOR ALL ASPHALT PAVING, ADA STALLS, PROVIDE GRAVEL EMERGENCY ACCESS ONLY. SEE CIVIL DRAWINGS.
4. ITEM 04:
A. DELETE WORK AND MATERIAL IN DESIGNATED AREA AND REPLACE WITH UNOCCUPIED SPACE. SEE SHEET A-101A FOR LIMITED GENERAL TRADES WORK. SPRINKLER
SYSTEM TO STILL BE INSTALLED. SEE SHEET FX101A. INSTALL RECEPTACLES, MECHANICAL POWER, AND TEMPORARY LIGHTING AS PER SHEETS EL101A, EM101A, AND EP101A. SEE SHEET M-101A FOR LIMITED MECHANICAL WORK. SEE SHEET PP101A FOR PLUMBING WORK.
DEDUCT ALTERNATES
SEISMIC DESIGN CRITERIA
LOCATION MATHER, CA
RISK CATEGORY II
MAPPED SHORT PERIOD SPECTRAL RESPONSE (ss) 0.460
MAPPED 1-SECOND SPECTRAL RESPONSE (SI) 0.225
SITE CLASSIFICATION C
SITE COEFFICIENT (Fa) 1.3
SITE COEFFICIENT (Fv) 1.5
MAXIMUM SHORT PERIOD SPECTRAL RESPONSE (SMS)
MAXIMUM 1-SECOND SPECTRAL RESPONSE (SM1)
MAPPED SHORT PERIOD SPECTRAL RESPONSE (SDS)
MAPPED 1-SECOND SPECTRAL RESPONSE (SD1)
SEISMIC DESIGN CATEGORY D
SEISMIC IMPORTANCE FACTOR 1
(FOR FINAL VALUES REFER STRUCTURAL DRAWINGS)
NOTES:
ELECTRICAL GENERATORS, SWITCHGEAR, TRANSFER SWITCHES, UPS, TRANSFORMERS,
MOTOR CONTROL CENTERS, PANELBOARDS, FIRE ALARM CONTROL PANEL, BUSWAYS, IT
SERVERS, AND CONTROL PANELS MUST BE SEISMICALLY RATED PER THE FOLLOWING
CRITERIA AND IN ACCORDANCE WITH ASCE 7.
0.599
0.440
0.399
0.293
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/9
/2
:2
:5
P M
E-001
ELECTRICAL GENERAL NOTES,
SYMBOL LEGENDS, AND
ABBREVIATIONS
1 14EFJ
DESIGN MEDICAL SPECIALTY
CLINIC
10535 HOSPITAL WAY, MATHER CA
95655
SEPTEMBER 10, 2021
100% CONSTRUCTION DOCUMENTS
612-12218-237-Q12
JAV
1 35% SCHEMATIC DESIGN DOCUMENTS 04/10/2020
2 65% DESIGN DEVELOPMENT 06/04/2020
3 65% DESIGN DEVELOPMENT - RE-SUBMISSION 06/26/2020
4 65% DESIGN DEVELOPMENT - RE-SUBMISSION 01/26/2021
5 95% CONSTRUCTION DOCUMENTS 04/06/2021
6 95% CONSTRUCTION DOCUMENTS -
RE-SUBMISSION
04/20/2021
7 95% CONSTRUCTION DOCUMENTS 07/15/2021
8 100% CONSTRCUTION DOCUMENTS 09/10/2021
DocuSign Envelope ID: 9E23B62B-308B-446D-AECD-CF0E77C522A7
9/9/2021 9/10/2021
H
D P
E
H
D P
E
12" HDPE
12" HDPE
H
D P
E
4" PVC
" P
V C
X
X
X
X
X
IT RM
ELEC
ROOM
J4
OHOH
5 TYP.
J 6
GENERATOR
TRANSFORMER
SWITCHGEAR
ATS, CONNECTION
CABINET, MAIN
'PLP'- 1, 3
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/8
/2
:1
:1
P M
ES101
ELECTRICAL SITE PLAN
2 14EFJ
DESIGN MEDICAL SPECIALTY
CLINIC
10535 HOSPITAL WAY, MATHER CA
95655
SEPTEMBER 10, 2021
100% CONSTRUCTION DOCUMENTS
612-12218-237-Q12
JAV
Scale: 1" = 20'-0"
ELECTRICAL SITE PLAN
NORTH
0 2010 40
1 IF BID ALTERNATE ONE (GENERATOR) IS
ACCEPTED AS A DEDUCT THE FOLLOWING
SHALL GOVERN: DELETE GENERATOR,
SWITCHGEAR, AND ASSOCIATE
ACCESSORIES.
2 COORDINATE INSTALLATION OF
TRANSFORMER WITH SMUD. VERIFY PAD
PLACEMENT AND STUBOUTS. SEE
SINGLE-LINE FOR SIZING OF FEEDERS
BETWEEN EQUIPMENT. FIELD ROUTE. SEE
CIVIL AND LANDSCAPE PLANS FOR PAD &
SCREENING.
3 PROPOSED PARKING LOT LIGHTING.
CONNECT NEW WIRING TO ONE OF THE
EXISTING PULL BOXES PROVIDED UNDER
THE PARKING LOT IMPROVEMENT PROJECT.
4 CONNECT NEW PARKING LOT LIGHTING TO
EXISTING JUNCTION BOX, AND TIE INTO
EXISTING CIRCUIT. VERIFY PANEL AND
CIRCUIT TIE IN. COORDINATE TIE WITH COR
SO VA OPERATIONS ARE UNDISTURBED.
5 PROVIDE 2 – 2” PVC SCHEDULE 40
UNDERGROUND CONDUIT AND MATCH
CONDUCTORS FROM PARKING LOT
IMPROVEMENT PROJECT.
6 PROVIDE UNDERGROUND PULL BOX. MATCH
SIZE TO PARKING LOT IMPROVEMENT
PROJECT.
7 COORDINATE WITH ELECTRICAL UTILITY
SMUD FOR THE INSTALLATION
REQUIREMENTS OF UTILITY TRANSFORMER
AND FEED.
8 PROVIDE 3-4” CONDUITS FOR PRIMARY FEED
TO SWITCHGEAR. COORDINATE
INSTALLATION REQUIREMENTS WITH
MANUFACTURER.
9 PROVIDE 3-4” CONDUITS TO MAIN
DISTRIBUTION BOARD. COORDINATE
INSTALLATION REQUIREMENTS WITH
MANUFACTURER.
10 PROVIDE 3-4” CONDUITS TO MAIN
DISTRIBUTION BOARD IN THE CASE THAT BID
ALTERNATE ONE IS ACCEPTED, AND THE
GENERATOR AND SWITCHGEAR IS NOT.
COORDINATE INSTALLATION REQUIREMENTS
WITH MANUFACTURER.
11 PROTECTIVE AND SECURED FENCING
AROUND ELECTRICAL EQUIPMENT. SEE CIVIL
DRAWINGS FOR MORE INFORMATION.
12 PROVIDE NEW GROUND ROD. SEE SHEET
E-502.
13 PROVIDE NEW 250 KCMIL BARE COPPER
GROUND RING AT MINIMUM 3’ BFG.
14 CONNECT #3/0 BARE COPPER GEC FROM
GENERATOR TO GROUND RING.
OH OVERHEAD UTILITY LINES
## KEY NOTES:
1 35% SCHEMATIC DESIGN DOCUMENTS 04/10/2020
2 65% DESIGN DEVELOPMENT 06/04/2020
3 65% DESIGN DEVELOPMENT - RE-SUBMISSION 06/26/2020
4 65% DESIGN DEVELOPMENT - RE-SUBMISSION 01/26/2021
5 95% CONSTRUCTION DOCUMENTS 04/06/2021
6 95% CONSTRUCTION DOCUMENTS -
RE-SUBMISSION
04/20/2021
7 95% CONSTRUCTION DOCUMENTS 07/15/2021
8 100% CONSTRCUTION DOCUMENTS 09/10/2021
9/10/2021
GFI
AC
GFI
AC
GFI
48"
DED
62"
GFI
DED
AC
AC
GFI
48"
AC
GFI
AC
GFI
AC
GFI
AC
AC
DED
GFI
ACAC
AC
GFI
AC
GFI
GFI
DED
48"
GFIDED
J
J
AC
GFI
AC
GFI
48"
GFI
GFI 48"DED
AC
GFI
AC
AC
GFI
DEDAC
AC
GFI
GFI
DED
AC
GFI
AC
GFI
GFI
DED
DED
AC
AC
AC
AC
GFI
AC
GFI
DED
48"
AC
GFI
48"
48" 48"
48"48"48"
48"
48" 48" 48"
48" 48" 48" 48"
AC
GFI
AC
GFI
AC
GFI
AC
GFI
AC
GFI
AC
GFI
AC
GFI
AC
GFI
AC
GFI
GFI
AC
GFI
AC
GFI
48"
GFI
AC
GFI
AC
GFI
AC
GFI
GFI
DED48"
GFI
GFI
12"
62"
J
J
DED
A
EP101
PANEL
'815GZ-ELP01'
PANEL
'815GZ-ELL01'
PULMINARY TESTING LAB
PULMINARY TESTING LAB
SHARED OFFICE
SHARED OFFICE
SHARED OFFICE
SHARED OFFICE
NEPHRO. EXAM 4
NEPHRO. EXAM 3
CORRIDOR
C134
CLEAN / MEDS
PAT UNI TLT
129NEPHROLOGY EXAM 2
NEPHR. EX. 1
PULMONARY EXAM 3
PULMONARY EXAM 2
PULMONARY EXAM 1
CARDIOLOGY EXAM 7
CARDIOLOGY EXAM 8
CARDIOLOGY EXAM 1
CARDIOLOGY EXAM 2
CARDIOLOGY EXAM 3
CARDIOLOGY EXAM 4
CARDIOLOGY EXAM 5
CARDIOLOGY EXAM 6
STF TLT
STF TLT
NURSE ROOM
NURSE ROOM
NURSE ROOM
NURSE ROOM
CORRIDOR
C114
PAT UNI TLT
CHIEF OFFICE
CHIEF OFFICE
CHIEF OFFICE
ALCOVE
EKG TECH WORK AREA
HOLTER EKG
CORRIDOR
C130
CORRIDOR
C114
HEIGHT AND WEIGHT
RECEPTION
100B
TOILET RM
LAB
SOILED
WAITING
100D
LOBBY
100A
MECHANICAL
HAC
135 ELEC
CONFERENCE
KITCHEN
CORRIDOR
C130
CORRIDOR
C118
CORRIDOR
C134
CORRIDOR
C151
CORRIDOR
C154
STAFF WORK AREA
STAFF WORK AREA
STRESS
ECHO
ECHO
ECHO READING
I.T. ROOM
PULMONARY EXAM 4
PANEL
'815GZ-ELM01'
PANEL
'815GZ-ELP02'
PANEL
'815GZ-ELP03'
STOR.
138A
NS MGR OFFICE
'815GZ-ELP01'- 71
'815GZ-ELP01'- 76
'815GZ-ELP01'- 75
'815GZ-ELP01'- 74
'815GZ-ELP01'- 80
'815GZ-ELP01'- 72
'815GZ-ELP01'- 73
'815GZ-ELP01'- 79
'815GZ-ELP01'- 65
'815GZ-ELP01'- 64
'815GZ-ELP01'- 61
'815GZ-ELP01'- 62
'815GZ-ELP01'- 60
'815GZ-ELP01'- 59
EP101
815GZ-ELP03 - 11
815GZ-ELP03 - 9
815GZ-ELP03 - 12
815GZ-ELP03 - 13
815GZ-ELP03 - 14
815GZ-ELP03 - 15
815GZ-ELP03 - 17
815GZ-ELP03 - 16
815GZ-ELP03 - 18
815GZ-ELP03 - 19
815GZ-ELP03 - 21
815GZ-ELP03 - 20
'815GZ-ELP01'- 1
'815GZ-ELP01'- 2
'815GZ-ELP01'- 3
'815GZ-ELP01'- 5
'815GZ-ELP01'- 4
'815GZ-ELP01'- 6
'815GZ-ELP01'- 7
'815GZ-ELP01'- 8 '815GZ-ELP01'- 9
'815GZ-ELP01'- 10
'815GZ-ELP01'- 11
'815GZ-ELP01'- 13
'815GZ-ELP01'- 12
'815GZ-ELP01'- 32
'815GZ-ELP01'- 34
'815GZ-ELP01'- 31
'815GZ-ELP01'- 28
'815GZ-ELP01'- 67
'815GZ-ELP01'- 27
'815GZ-ELP01'- 26
'815GZ-ELP01'- 19 '815GZ-ELP01'- 20
'815GZ-ELP01'- 30
'815GZ-ELP01'- 33
'815GZ-ELP01'- 35
'815GZ-ELP01'- 18'815GZ-ELP01'- 17'815GZ-ELP01'- 16'815GZ-ELP01'- 15
'815GZ-ELP01'- 22
'815GZ-ELP01'- 23 '815GZ-ELP01'- 24 '815GZ-ELP01'- 25
'815GZ-ELP01'- 55
'815GZ-ELP01'- 49 '815GZ-ELP01'- 56
'815GZ-ELP01'- 54 '815GZ-ELP01'- 53 '815GZ-ELP01'- 52 '815GZ-ELP01'- 50 '815GZ-ELP01'- 51
'815GZ-ELP01'- 58
'815GZ-ELP01'- 83
'815GZ-ELP01'- 70
'815GZ-ELP01'- 57
'815GZ-ELP01'- 68'815GZ-ELP01'- 69
'815GZ-ELP01'- 78
'815GZ-ELP01'- 77
2 3 4
5 6
A.1
B
C
D
'815GZ-ELP01'- 41
'815GZ-ELP01'- 14
'815GZ-ELP01'- 14
'815GZ-ELP01'- 82
'815GZ-ELP01'- 81
'815GZ-ELP01'- 48
'815GZ-ELP01'- 66
'815GZ-ELP01'- 63
PANEL 'Panel
ELP02B'
PANEL
'815GZ-ELM01'
PANEL
'815GZ-ELP01'
PANEL
'815GZ-ELL01'
PANEL
'815GZ-ELP03'
'815GZ-ELP03'- 7
'815GZ-ELP03'- 6
'815GZ-ELP03'- 5
'815GZ-ELP03'- 1,3 '815GZ-ELP03'- 2,4
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/8
/2
:1
:0
P M
EP101
FIRST FLOOR POWER PLAN
3 14EFJ
DESIGN MEDICAL SPECIALTY
CLINIC
10535 HOSPITAL WAY, MATHER CA
95655
SEPTEMBER 10, 2021
100% CONSTRUCTION DOCUMENTS
612-12218-237-Q12
JAV
Scale: 1/8" = 1'-0"
FIRST FLOOR POWER PLAN
1 COORDINATE LOCATION WITH FINAL KIOSK
PLACEMENT.
2 DEDICATED CIRCUIT FOR FIRE ALARM
CONTROL PANEL (FACP).
3 PROVIDE CONDUIT UNDER SLAB FOR
OUTLETS SHOWN TO BE INSTALLED ON HALF
WALL.
4 JUNCTION BOX IN WALL COORDINATE EXACT
LOCATION AND CONNECTION WITH
FURNITURE PROVIDE BY VA.
N
KEY PLAN
SCALE: NO SCALE
NORTH
0 4 8 16
Scale: 1/4" = 1'-0"
ELEC ROOM ENLARGEMENT - POWER
A. CONTRACTOR TO PROVIDE AND INSTALL
ALL DEVICES SHOWN ON THIS PLAN.
B. PANEL NAMING CONVENTION CHANGES
WITH DEDUCT ALTERNATES ITEM ONE.
PANELS CHANGE FROM EMERGENCY TO
NORMAL POWER UPDATE EQUIPMENT
NAMING TAGS TO SHOW THAT EQUIPMENT
IS ATTACHED TO NORMAL BRANCH.
C. PRIOR TO INSTALLING BRANCH CIRCUIT
WIRES AND WIRING DEVICES TO LOCATIONS
OF OWNER FURNISHED EQUIPMENT,
CONTRACTOR TO REVIEW ALL OWNER
FURNISHED EQUIPMENT CUT SHEETS.
NOTIFY COR IF DISCREPANCIES EXIST
BETWEEN WIRING DEVICES SHOWN AND
EQUIPMENT FURNISHED.
Scale: 1/4" = 1'-0"
IT ROOM ENLARGEMENT - POWER
NORTH
0 2 4 8
NORTH
0 2 4 8
1 35% SCHEMATIC DESIGN DOCUMENTS 04/10/2020
2 65% DESIGN DEVELOPMENT 06/04/2020
3 65% DESIGN DEVELOPMENT - RE-SUBMISSION 06/26/2020
4 65% DESIGN DEVELOPMENT - RE-SUBMISSION 01/26/2021
5 95% CONSTRUCTION DOCUMENTS 04/06/2021
6 95% CONSTRUCTION DOCUMENTS -
RE-SUBMISSION
04/20/2021
7 95% CONSTRUCTION DOCUMENTS 07/15/2021
8 100% CONSTRCUTION DOCUMENTS 09/10/2021
AC
GFI
AC
GFI
DED
62"
GFI
DED
AC
AC
GFI
48"
AC
GFI
AC
GFI
AC
AC
DED
GFI
ACAC
AC
GFI
AC
GFI
GFI
DED
48"
GFI
J
J
AC
GFI
48"
GFI
GFI 48"DED
AC
GFI
AC
AC
GFI
DEDAC
AC
GFI
DED
AC
AC
AC
48"
AC
GFI
48"
48"
48" 48" 48"
48" 48" 48" 48"
AC
GFI
AC
GFI
AC
GFI
AC
GFI
AC
GFI
AC
GFI
AC
GFI
AC
GFI
AC
GFI
GFI
AC
GFI
DED
48"
GFI
DED48"
GFI
12"
62"
J
J
A
2 3 4
5 6
A.1
B
C
D
VESTIBULE
LOBBY
100A
CORRIDOR
C114
HEIGHT AND WEIGHT
HOLTER EKG
EKG TECH WORK AREA
ALCOVE
108CHIEF OFFICE
CHIEF OFFICE
STAFF WORK AREA
STRESS
105ECHO
ECHO
ECHO READING
STAFF UNI TLT
I.T. ROOM
NS MGR OFFICE
CARDIOLOGY EXAM 1
CARDIOLOGY EXAM 2
CARDIOLOGY EXAM 3
CARDIO. EXAM 4
CARDIO. EXAM 5
CARDIOLOGY EXAM 6
CARDIOLOGY EXAM 7
CARDIOLOGY EXAM 10
CORRIDOR
C151
MECHANICAL
ELEC
WAITING
100D
TOILET RM
NURSE ROOM
NURSE ROOM
NURSE ROOM
NURSE ROOM
SOILED
OFFICE
EP101
CONFERENCE
KITCHEN
PANEL
'815GZ-ELP01'
PANEL
'815GZ-ELL01'
PANEL
'815GZ-ELM01'
PANEL
'815GZ-ELP02'
PANEL
'815GZ-ELP03'
'815GZ-ELP01'- 71
'815GZ-ELP01'- 76 '815GZ-ELP01'- 75
'815GZ-ELP01'- 74
'815GZ-ELP01'- 80
'815GZ-ELP01'- 72
'815GZ-ELP01'- 73
'815GZ-ELP01'- 79
<unnamed>
<unnamed>
'815GZ-ELP01'- 65
'815GZ-ELP01'- 64
'815GZ-ELP01'- 61
'815GZ-ELP01'- 62
'815GZ-ELP01'- 60
'815GZ-ELP01'- 59
EP101
815GZ-ELP03 - 11
815GZ-ELP03 - 9
815GZ-ELP03 - 12
815GZ-ELP03 - 13
815GZ-ELP03 - 14
815GZ-ELP03 - 15
815GZ-ELP03 - 17
815GZ-ELP03 - 16
815GZ-ELP03 - 18
815GZ-ELP03 - 19
815GZ-ELP03 - 21
815GZ-ELP03 - 20
'815GZ-ELP01'- 1
'815GZ-ELP01'- 2
'815GZ-ELP01'- 3
'815GZ-ELP01'- 5
'815GZ-ELP01'- 4
'815GZ-ELP01'- 6
'815GZ-ELP01'- 7
'815GZ-ELP01'- 67
'815GZ-ELP01'- 27
'815GZ-ELP01'- 26
'815GZ-ELP01'- 35
'815GZ-ELP01'- 22
'815GZ-ELP01'- 23 '815GZ-ELP01'- 24 '815GZ-ELP01'- 25
'815GZ-ELP01'- 55
'815GZ-ELP01'- 49 '815GZ-ELP01'- 56
'815GZ-ELP01'- 54 '815GZ-ELP01'- 53 '815GZ-ELP01'- 52 '815GZ-ELP01'- 50 '815GZ-ELP01'- 51
'815GZ-ELP01'- 58
'815GZ-ELP01'- 83
'815GZ-ELP01'- 70
'815GZ-ELP01'- 57
'815GZ-ELP01'- 68'815GZ-ELP01'- 69
'815GZ-ELP01'- 78
'815GZ-ELP01'- 77
'815GZ-ELP01'- 82
'815GZ-ELP01'- 81
UNOCCUPIED SPACE
CARDIOLOGY EXAM 9
CARDIOLOGY EXAM 8
STORAGE
PAT UNI TLT
CLEAN / MEDS
RECEPTION
100B
CORRIDOR
C118
CORRIDOR
C130
HAC
NS MGR OFFICE
'815GZ-ELP01'- 48
'815GZ-ELP01'- 38
'815GZ-ELP01'- 8
'815GZ-ELP01'- 14
'815GZ-ELP01'- 40
'815GZ-ELP01'- 36
'815GZ-ELP01'- 39
'815GZ-ELP01'- 30
'815GZ-ELP01'- 38
'815GZ-ELP03'- 7
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/8
/2
:1
:1
P M
EP101A
FIRST FLOOR POWER PLAN - DEDUCT
ALTERNATE #4
4 14EFJ
DESIGN MEDICAL SPECIALTY
CLINIC
10535 HOSPITAL WAY, MATHER CA
95655
SEPTEMBER 10, 2021
100% CONSTRUCTION DOCUMENTS
612-12218-237-Q12
JAV
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
DEDUCT ALTERNATIVE
NORTH
0 4 8 16
A. CONTRACTOR TO PROVIDE AND INSTALL
ALL DEVICES SHOWN ON THIS PLAN.
B. PANEL NAMING CONVENTION CHANGES
WITH DEDUCT ALTERNATES ITEM ONE.
PANELS CHANGE FROM EMERGENCY TO
NORMAL POWER UPDATE EQUIPMENT
NAMING TAGS TO SHOW THAT EQUIPMENT
IS ATTACHED TO NORMAL BRANCH.
C. PRIOR TO INSTALLING BRANCH CIRCUIT
WIRES AND WIRING DEVICES TO LOCATIONS
OF OWNER FURNISHED EQUIPMENT,
CONTRACTOR TO REVIEW ALL OWNER
FURNISHED EQUIPMENT CUT SHEETS.
NOTIFY COR IF DISCREPANCIES EXIST
BETWEEN WIRING DEVICES SHOWN AND
EQUIPMENT FURNISHED.
1 COORDINATE LOCATION WITH FINAL KIOSK
PLACEMENT.
2 DEDICATED CIRCUIT FOR FIRE ALARM
CONTROL PANEL (FACP).
3 PROVIDE CONDUIT UNDER SLAB FOR
OUTLETS SHOWN TO BE INSTALLED ON HALF
WALL.
4 JUNCTION BOX IN WALL COORDINATE EXACT
LOCATION AND CONNECTION WITH
FURNITURE PROVIDE BY VA.
5 PLAN AND ASSOCIATED NOTES TO BE
ACCEPTED AS MAIN DESIGN IF BID
ALTERNATE ITEM FOUR IS TAKEN.
Scale: 1/8" = 1'-0"
FIRST FLOOR POWER PLAN FIRST FLOOR POWER PLAN - DEDUCT ALTERNATE #4
1 35% SCHEMATIC DESIGN DOCUMENTS 04/10/2020
2 65% DESIGN DEVELOPMENT 06/04/2020
3 65% DESIGN DEVELOPMENT - RE-SUBMISSION 06/26/2020
4 65% DESIGN DEVELOPMENT - RE-SUBMISSION 01/26/2021
5 95% CONSTRUCTION DOCUMENTS 04/06/2021
6 95% CONSTRUCTION DOCUMENTS -
RE-SUBMISSION
04/20/2021
7 95% CONSTRUCTION DOCUMENTS 07/15/2021
8 100% CONSTRCUTION DOCUMENTS 09/10/2021
WP
GFI
WP
GFI
WP
GFI
WP
M
A
815-RTU-5
815-RTU-3 815-RTU-4815-RTU-2815-RTU-1
FDS RHU-1 FDS RHU-2 FDS RHU-5 FDS RHU-3 FDS RHU-4
PANEL
'815PZ-ELP01'
815-CU-1
815-EF-1
815-EF-2
2 3 4
5 6
A.1
B
C
D
'815PZ-ELP01'-
8,10,12
'815PZ-ELP01'- 1,3,5
'815PZ-ELP01'- 2,4,6
'815PZ-ELP01'- 7,9,11'815PZ-ELP01'-
13,15,17
'815GZ-ELP03'- 8,10
'815PZ-ELP01'- 16
'815PZ-ELP01'- 18
'815PZ-ELP01'- 14
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/8
/2
:1
:1
P M
EP102
ROOF POWER PLAN
5 14EFJ
DESIGN MEDICAL SPECIALTY
CLINIC
10535 HOSPITAL WAY, MATHER CA
95655
SEPTEMBER 10, 2021
100% CONSTRUCTION DOCUMENTS
612-12218-237-Q12
JAV
N
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
ROOF MECHANICAL POWER PLAN
A. CONTRACTOR TO PROVIDE AND INSTALL
ALL DEVICES SHOWN ON THIS PLAN.
B. PANEL NAMING CONVENTION CHANGES
WITH DEDUCT ALTERNATES ITEM 1. PANELS
CHANGE FROM EMERGENCY TO NORMAL
POWER UPDATE EQUIPMENT NAMING TAGS
TO SHOW THAT EQUIPMENT IS ATTACHED
TO NORMAL BRANCH.
C. PRIOR TO INSTALLING BRANCH CIRCUIT
WIRES AND WIRING DEVICES TO LOCATIONS
OF OWNER FURNISHED EQUIPMENT,
CONTRACTOR TO REVIEW ALL OWNER
FURNISHED EQUIPMENT CUT SHEETS.
NOTIFY COR IF DISCREPANCIES EXIST
BETWEEN WIRING DEVICES SHOWN AND
EQUIPMENT FURNISHED.
NORTH
0 4 8 16
1 35% SCHEMATIC DESIGN DOCUMENTS 04/10/2020
2 65% DESIGN DEVELOPMENT 06/04/2020
3 65% DESIGN DEVELOPMENT - RE-SUBMISSION 06/26/2020
4 65% DESIGN DEVELOPMENT - RE-SUBMISSION 01/26/2021
5 95% CONSTRUCTION DOCUMENTS 04/06/2021
6 95% CONSTRUCTION DOCUMENTS -
RE-SUBMISSION
04/20/2021
7 95% CONSTRUCTION DOCUMENTS 07/15/2021
8 100% CONSTRCUTION DOCUMENTS 09/10/2021
VAV-1
VAV-2
VAV-3
VAV-5
VAV-4
815-FCU-1
815-DH-1
815-DH-2
815-DH-3 815-DH-4
815-DH-6
815-DH-5
815-DH-7
815-IWH-121 815-IWH-123
815-IWH-125
815-IWH-127
815-IWH-140815-IWH-142815-IWH-144815-IWH-146
815-IWH-119
815-IWH-120 815-IWH-122 815-IWH-124 815-IWH-126 815-IWH-128
815-IWH-104
815-IWH-105815-IWH-107815-IWH-109
815-IWH-131A
815-IWH-102
815-IWH-131B
815-IWH-103
815-IWH-133
815-IWH-135A
815-IWH-135B
815-IWH-138
815-IWH-156
815-IWH-155
815-IWH-113
815-IWH-141 815-IWH-139
'815GZ-ELP02'- 13,15
'815GZ-ELP02'- 18,20
'815GZ-ELP02'- 17,19'815GZ-ELP02'- 22,24
'815GZ-ELP02'- 61,63
'815GZ-ELP02'- 30,32
'815GZ-ELP02'- 25,27 '815GZ-ELP02'- 26,28 '815GZ-ELP02'- 21,23
'815GZ-ELP02'- 29,31
'815GZ-ELP02'- 45,47
'815GZ-ELP02'- 46,48
'815GZ-ELP02'- 41,43
'815GZ-ELP02'- 42,44
'815GZ-ELP02'- 34,36
'815GZ-ELP02'- 33,35'815GZ-ELP02'- 38,40
'815GZ-ELP02'- 37,39
'815GZ-ELP02'- 50,52
'815GZ-ELP02'- 54,56
'815GZ-ELP02'- 49,51
'815GZ-ELP02'- 62,64
'815GZ-ELP02'- 57,59
'815GZ-ELP02'- 58,60
'815GZ-ELP02'- 53,55
'815GZ-ELP02'- 5,7
'815GZ-ELP02'- 6,8
'815GZ-ELP02'- 2,4
'815GZ-ELP02'- 1,3
'815GZ-ELP02'- 10,12
'815GZ-ELP02'- 9,11
'815GZ-ELP02'- 14,16
'815GZ-ELP02'-
65,67,69
'815GZ-ELP02'-
70,72,74
'815GZ-ELP02'-
71,73,75
'815GZ-ELP02'-
77,79,81
'815GZ-ELP01'-
42,44,46
'815GZ-ELP01'-
43,45,47
'815GZ-ELP02'-
76,78,80
'815GZ-ELP03'- 26,28
'815GZ-ELP03'- 22,24
'815GZ-ELP03'- 23,25
'815GZ-ELP03'- 27,29
'815GZ-ELP03'- 30,32
'815GZ-ELP03'-
31,33,35
815-EUH-1
PANEL
'815GZ-ELP02'
PANEL
'815GZ-ELP03'
PANEL
'815GZ-ELP01'
815-IWH-162
'815GZ-ELP02'- 66,68
812-IWH-150
'815GZ-ELP02'- 82,84
815-IWH-129
'815GZ-ELL01'- 11
'815GZ-ELL01'- 11
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/8
/2
:1
:5
P M
EM101
FIRST FLOOR MECHANICAL POWER
PLAN
6 14EFJ
DESIGN MEDICAL SPECIALTY
CLINIC
10535 HOSPITAL WAY, MATHER CA
95655
SEPTEMBER 10, 2021
100% CONSTRUCTION DOCUMENTS
612-12218-237-Q12
JAV
N
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
FIRST FLOOR MECHANICAL POWER PLAN
A. PROVIDE MECHANICAL CONNECTIONS PER
MECHANICAL EQUIPMENT CONDUCTOR
SCHEDULE. SEE SHEET E-603.
NORTH
0 4 8 16
1 FCU POWERED THROUGH MANUFACTURER
SUPPLIED CABLING FROM CONDENSER
COORDINATE WITH MECHANICAL
CONTRACTOR FOR CONNECTION.
2 PROVIDE EMERGENCY CIRCUIT TO
STANDALONE NURSE CALL DEVICES.
1 35% SCHEMATIC DESIGN DOCUMENTS 04/10/2020
2 65% DESIGN DEVELOPMENT 06/04/2020
3 65% DESIGN DEVELOPMENT - RE-SUBMISSION 06/26/2020
4 65% DESIGN DEVELOPMENT - RE-SUBMISSION 01/26/2021
5 95% CONSTRUCTION DOCUMENTS 04/06/2021
6 95% CONSTRUCTION DOCUMENTS -
RE-SUBMISSION
04/20/2021
7 95% CONSTRUCTION DOCUMENTS 07/15/2021
8 100% CONSTRCUTION DOCUMENTS 09/10/2021
VAV-1
VAV-2
VAV-3
VAV-5
VAV-4
815-FCU-1
815-DH-1
815-DH-2
815-DH-3 815-DH-4
815-DH-6
815-DH-5
815-DH-7
815-IWH-121 815-IWH-127815-IWH-119
815-IWH-120 815-IWH-122 815-IWH-124 815-IWH-126 815-IWH-128
815-IWH-104
815-IWH-105815-IWH-107815-IWH-109
815-IWH-102
815-IWH-103
815-IWH-135A
815-IWH-135B
815-IWH-113
'815GZ-ELP02'- 13,15
'815GZ-ELP02'- 18,20
'815GZ-ELP02'- 17,19'815GZ-ELP02'- 22,24
'815GZ-ELP02'- 61,63
'815GZ-ELP02'- 30,32
'815GZ-ELP02'- 25,27 '815GZ-ELP02'- 26,28 '815GZ-ELP02'- 21,23
'815GZ-ELP02'- 29,31
'815GZ-ELP02'- 34,36
'815GZ-ELP02'- 33,35'815GZ-ELP02'- 38,40
'815GZ-ELP02'- 37,39
'815GZ-ELP02'- 50,52
'815GZ-ELP02'- 62,64
'815GZ-ELP02'- 5,7
'815GZ-ELP02'- 2,4
'815GZ-ELP02'- 1,3
'815GZ-ELP02'- 10,12
'815GZ-ELP02'- 9,11
'815GZ-ELP02'- 14,16
'815GZ-ELP02'-
65,67,69
'815GZ-ELP02'-
70,72,74
'815GZ-ELP02'-
71,73,75
'815GZ-ELP02'-
77,79,81
'815GZ-ELP01'-
42,44,46
'815GZ-ELP01'-
43,45,47
'815GZ-ELP02'-
76,78,80
'815GZ-ELP03'- 26,28
'815GZ-ELP03'- 22,24
'815GZ-ELP03'- 23,25
'815GZ-ELP03'- 27,29
'815GZ-ELP03'- 30,32
'815GZ-ELP03'-
31,33,35
815-EUH-1
PANEL
'815GZ-ELP02'
PANEL
'815GZ-ELP03'
PANEL
'815GZ-ELP01'
815-IWH-162
'815GZ-ELP02'- 66,68
812-IWH-150
'815GZ-ELP02'- 82,84
UNOCCUPIED SPACE
'815GZ-ELL01'- 11
'815GZ-ELL01'- 11
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/8
/2
:1
:0
P M
EM101A
FIRST FLOOR MECHANICAL POWER
PLAN - DEDUCT ALTERNATE #4
7 14EFJ
DESIGN MEDICAL SPECIALTY
CLINIC
10535 HOSPITAL WAY, MATHER CA
95655
SEPTEMBER 10, 2021
100% CONSTRUCTION DOCUMENTS
612-12218-237-Q12
JAV
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
DEDUCT ALTERNATIVE
A. PROVIDE MECHANICAL CONNECTIONS PER
MECHANICAL EQUIPMENT CONDUCTOR
SCHEDULE. SEE SHEET E-603.
1 PLAN AND ASSOCIATED NOTES TO BE
ACCEPTED AS MAIN DESIGN IF BID
ALTERNATE ITEM FOUR IS TAKEN.
2 FCU POWERED THROUGH MANUFACTURER
SUPPLIED CABLING FROM CONDENSER
COORDINATE WITH MECHANICAL
CONTRACTOR FOR CONNECTION.
Scale: 1/8" = 1'-0"
FIRST FLOOR MECHANICAL POWER PLAN - DEDUCT ALTERNATE #4
NORTH
0 4 8 16
1 35% SCHEMATIC DESIGN DOCUMENTS 04/10/2020
2 65% DESIGN DEVELOPMENT 06/04/2020
3 65% DESIGN DEVELOPMENT - RE-SUBMISSION 06/26/2020
4 65% DESIGN DEVELOPMENT - RE-SUBMISSION 01/26/2021
5 95% CONSTRUCTION DOCUMENTS 04/06/2021
6 95% CONSTRUCTION DOCUMENTS -
RE-SUBMISSION
04/20/2021
7 95% CONSTRUCTION DOCUMENTS 07/15/2021
8 100% CONSTRCUTION DOCUMENTS 09/10/2021
OS
VSD
VSD
LVD
O S
LVD
VSD
VSD LVD
LVDLVD LVD
LVD
LVD
LVD
OS
OS
OS
OS
LVD
OS
OS
OS
OS
OS
OS
OSOS
OS
OS
OS
OS
LS
LS
LVD
4LV
LVD
OS
LVD
OS
VSD VSD
LVD
OS
OS
LVD
OS
OS OS OS OS
LVD LVD LVD LVD
LVD LVD LVD LVD
OS OS OS OS
VSD
VSD VSD
OS OS OS OS
LVD LVD LVD
OS OS
LVDLVDLVDVSDVSD
LV
OS
OS
OS
OS
LV
D
LV
D
OS
OS
OS
OS OS OS
OS
OS OS OS OS
OS
OS
OS
OS
OS OS OS
VSD
OS
OS
OS
OS
OS
LV
D
LV
D
LV
D
LS
OS
OS
OS
LS
A
A2 A2 A2
A2 A2 A2
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1 A1 A1 A1 A1 A1
A1
A1A1A1A1A1
A1 A1
A1A1A1A1A1
A1
A1 A3
A3
A1
A1
A1A2
A2 A1
A1
A1
A1F A1F
A1 A1
B B
B
B
B
A3
A3
A3 A3
D
D
D
D
E1
E1
E2
E1
E2 E1 E1
E1
E1
A2
A2
B
B
RCD2
RCD
RCD
RCDRCD RCD
RCD2
RCD2
RCD
RCD
E1
E1
RCD
E1
E1
H
D
H
H
A3F
A3F
A3F
A3F
A3F
A2 A2
F F RCD3
RCD3
D D
D
D
D
D
D
D
DCARDIOLOGY EXAM 6
CARDIOLOGY EXAM 7
CARDIOLOGY EXAM 8
NEPHR. EX. 1
NEPHROLOGY EXAM 2
PULMONARY EXAM 3
PULMONARY EXAM 4
PULMONARY EXAM 2
PULMONARY EXAM 1
STF TLT
STF TLT
CORRIDOR
C134
CORRIDOR
C151
NURSE ROOM
NURSE ROOM
NURSE ROOM
NURSE ROOM
KITCHEN
CONFERENCE
SHARED OFFICE
SHARED OFFICE
SHARED OFFICE
SHARED OFFICE
NEPHRO. EXAM 4
NEPHRO. EXAM 3
139 PULMINARY TESTING LAB
MECHANICAL
ELEC
HAC
SOILED
LAB
WAITING
100D
WAITING
100D
LOBBY
100A
LOBBY
100A
CORRIDOR
C130
CORRIDOR
C114
CORRIDOR
C114
CORRIDOR
C118
CORRIDOR
C118
NS MGR OFFICE
I.T. ROOM
PAT UNI TLT
CARDIOLOGY EXAM 1
CARDIOLOGY EXAM 2
CARDIOLOGY EXAM 3
CARDIOLOGY EXAM 4
CARDIOLOGY EXAM 5
CORRIDOR
C130
PAT UNI TLT
CORRIDOR
C134
CORRIDOR
C134
CORRIDOR
C154
STAFF WORK AREA
ECHO READING
ECHO
ECHO
STRESS
TOILET RM
HEIGHT AND WEIGHT
RECEPTION
100B
HOLTER EKG
ALCOVE
CHIEF OFFICE
CHIEF OFFICE
CHIEF OFFICE
EKG TECH WORK AREA
VESTIBULE
PULMINARY TESTING LAB
CLEAN / MEDS
B
B
RCD
RCD
A1 A1
A1A1
A1
A1
A1
A1
A1 A1
A1A1
E1
E1
A2
A2
A2
A2
A2
A2
RCD
A2
A2 A2
D
H
RCD
A1 A1
A1 A1 A1 A1
A1A1
RCD
A1
A1
RCD
A1A1A1A1
A1 A1
RCD
A1A1
A1 A1
RCD
A1
A1
A1
A1
RCD RCD
A1 A1
A1A1 A1
A1 A1
A1 A1
A1
RCDRCD
A1
A1
A1 A1
A1A1
RCD
A1
RCDA1
A1
A1
RCD
A1 A1
A1 A1A1
A1
A1 A1
RCD
RCD
A1
A1
A1 A1
A1 A1A1 A1 A1 A1 A1 A1
A1A1A1A1A1
A2 A2
A2A2
A2 A2
A1
A1 A2
A2 A2
A2
A1
A1
A1
A1
A1
A1
A1 A1
A1
A1 A1
A1
A1
A1
A1
A1
A3
STOR.
138A
A1F
A1F
PANEL
'815GZ-ELL01'
Z
Z
Z
2 3 4
5 6
A.1
B
C
D
'815GZ-ELL01'- 4
'815GZ-ELL01'- 8
A1
C
C
C
C
C C
C C
C C a b c c c c c c c a b c a,b,c c
'815GZ-ELL01'- 5
H
D
'815GZ-ELL01'- 3
RCD
'815GZ-ELL01'- 1
'815GZ-ELL01'- 4
'815GZ-ELL01'- 6
A1
'815GZ-ELL01'- 7
'815GZ-ELL01'- 8
EB1
A3 d,e,f g d d f f f f e d e e e e e f f f f f f f f f f f f f f e e e e g g g d f f f f c a c ca,b a,b a,b a g
RCD
W W
'815GZ-ELL01'- 9
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/8
/2
:1
:4
P M
EL101
FIRST FLOOR LIGHTING PLAN
8 14EFJ
DESIGN MEDICAL SPECIALTY
CLINIC
10535 HOSPITAL WAY, MATHER CA
95655
SEPTEMBER 10, 2021
100% CONSTRUCTION DOCUMENTS
612-12218-237-Q12
JAV
NORTH
0 4 8 16
A. CONTRACTOR TO PROVIDE AND INSTALL
ALL DEVICES SHOWN ON THIS PLAN.
B. EXIT SIGN LIGHTING FIXTURES TO BE
CIRCUITED TO PANEL ‘815GZ-ELL01’-10.
C. EXTERIOR WALL PACK LIGHTING FIXTURES
TO BE CIRCUITED TO PANEL ‘815GZ-ELL01’-2.
N
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
FIRST FLOOR LIGHTING PLAN
1 35% SCHEMATIC DESIGN DOCUMENTS 04/10/2020
2 65% DESIGN DEVELOPMENT 06/04/2020
3 65% DESIGN DEVELOPMENT - RE-SUBMISSION 06/26/2020
4 65% DESIGN DEVELOPMENT - RE-SUBMISSION 01/26/2021
5 95% CONSTRUCTION DOCUMENTS 04/06/2021
6 95% CONSTRUCTION DOCUMENTS -
RE-SUBMISSION
04/20/2021
7 95% CONSTRUCTION DOCUMENTS 07/15/2021
8 100% CONSTRCUTION DOCUMENTS 09/10/2021
OS
VSD
O S
LVD
VSD
VSD LVD
LVDLVD LVD
LVD
OS
OS
LVD
OS
OS
OS
OSOS
OS
OS
OS
OS
LS
LS
LVD
4LV
LVD
OS
LVD
OS
T
T
VSD VSD
LVDOS
LVD
OS
OS OS OS OS
LVD LVD LVD LVD
LVD LVD LVD LVD
OS OS OS OS
VSD
VSD VSD
LV
OS
OS
OS
OS
LV
D
LV
D
OS
OS
OS
OS OS OS
OS
OS
OS
OS
OS OS OS
OS
OS
OS
OS
OS
OS
LV
D
LV
D
LV
D
LS
OS
OS
OS
LS
A
A2
A2 A2
A2
A2 A2
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1 A1 A1 A1 A1 A1
ELEC
MECHANICAL
CONFERENCE
CORRIDOR
C151
NURSE ROOM
NURSE ROOM
NURSE ROOM
NURSE ROOM
CARDIOLOGY EXAM 7
CARDIOLOGY EXAM 10
CARDIO. EXAM 5
CARDIO. EXAM 4
CARDIOLOGY EXAM 3
CARDIOLOGY EXAM 2
CARDIOLOGY EXAM 1
NS MGR OFFICE
I.T. ROOM
STAFF UNI TLT
ECHO READING
ECHO
ECHO
STRESS
LOBBY
100A
VESTIBULE
HOLTER EKG
CORRIDOR
C114
ALCOVE
EKG TECH WORK AREA
OFFICE
CHIEF OFFICE
CHIEF OFFICE
A1
A1A1A1A1A1
A1
A1A2
A2
A1
A1A1
A1F A1F
A1 A1
B B
B
B
B
A3
A3 A3
D
D
D
D
E1
E1
E2
E1
E2 E1 E1
E1
E1
A2
A2
B
B
RCD2
RCD
RCDRCD RCD
RCD2
RCD
CARDIOLOGY EXAM 6
EM
EM
EMEM
EM
EM EM
EM
EM
EM
E1
E1
H
H
CORRIDOR
C118
CORRIDOR
C130
A3F
A3F
A3F
A2 A2
F F RCD3 EM
RCD3
HEIGHT AND WEIGHT
TOILET RM
SOILED
D D
D
D
D
D
D
D
D
HAC
WAITING
100D
CARDIOLOGY EXAM 9
CARDIOLOGY EXAM 8
PAT UNI TLT
STORAGE
CLEAN / MEDS
KITCHEN
STAFF WORK AREA
CORRIDOR
C130
B
B
A1 A1
A1
A1
A1 A1
A1
A1
E1
E1
B B
B
B B B
B
BBB
B
B
B B B
EM EM
EM
E1
RCD
A2
A2 A2
A2
H
D
RCD
A2
A2
RCD
RCD RCD
RCD RCD
RCD
A1
A1
A1 A1A1
A1
A1
A1A1A1
A1
A1A1
A1
A1 A1
RCD
RCD RCD RCD
A1 A1
A1 A1
A1
A1 A1
A1 A1
A1
A1
A1
A1 A1
A1A1
A2
A2
A2
EM
EM
EM
A2 A2
A2 A2
A2A2
A1
A1
A1
A1
A1
A1
A1
A1
A1 A1
A1
A1 A1
A1
A1
A1
A1
A1
B
A1F
A1F
Z
Z
Z
PANEL
'815GZ-ELL01'
RECEPTION
100B
2 3 4
5 6
A.1
B
C
D
UNOCCUPIED
SPACE
B
'815GZ-ELL01'- 12
'815GZ-ELL01'- 8
'815GZ-ELL01'- 6
A1
A1
'815GZ-ELL01'- 3
A3
'815GZ-ELL01'- 4
'815GZ-ELL01'- 1
RCD
C C
A1
C
C C C
C
C a,b,c d,e,f g
EB1
g g g d e f d d d f ff f f f f f f f f f f f f f f f f f f e e e e e e e e e a b a,b a,b a,b a c c a b c c c c c c c c c a c
EM
W W
RCD
'815GZ-ELL01'- 9
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/8
/2
:1
:5
P M
EL101A
FIRST FLOOR LIGHTING PLAN -
DEDUCT ALTERNATE #4
9 14EFJ
DESIGN MEDICAL SPECIALTY
CLINIC
10535 HOSPITAL WAY, MATHER CA
95655
SEPTEMBER 10, 2021
100% CONSTRUCTION DOCUMENTS
612-12218-237-Q12
JAV
Scale: 1/8" = 1'-0"
FIRST FLOOR LIGHTING PLAN - DEDUCT ALTERNATE #4
NORTH
0 4 8 16
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
DEDUCT ALTERNATIVE
1 PLAN AND ASSOCIATED NOTES TO BE
ACCEPTED AS MAIN DESIGN IF BID
ALTERNATE ITEM FOUR IS TAKEN.
A. CONTRACTOR TO PROVIDE AND INSTALL
ALL DEVICES SHOWN ON THIS PLAN.
B. LIGHTING FIXTURES DESIGNATED WITH THE
EM TAG TO HAVE BATTERY BACKUP.
INCLUDING EXIT LIGHTS. THIS IS APPLICABLE
ONLY FOR ALTERNATE DEDUCT 1 ON THE
REMOVAL OF THE GENERATOR FROM THE
PROJECT. CONNECT TO SEPARATE
CIRCUITS.
C. EXIT SIGN LIGHTING FIXTURES TO BE
CIRCUITED TO PANEL ‘815GZ-ELL01’-10. EXIT
SIGNS TO ALSO INCLUDE SELF-TESTING
BATTERY OPERATION. DEVICE MODEL
NUMBER: LEDRBB-ST
D. EXTERIOR WALL PACK LIGHTING FIXTURES
TO BE CIRCUITED TO PANEL ‘815GZ-ELL01’-2.
1 35% SCHEMATIC DESIGN DOCUMENTS 04/10/2020
2 65% DESIGN DEVELOPMENT 06/04/2020
3 65% DESIGN DEVELOPMENT - RE-SUBMISSION 06/26/2020
4 65% DESIGN DEVELOPMENT - RE-SUBMISSION 01/26/2021
5 95% CONSTRUCTION DOCUMENTS 04/06/2021
6 95% CONSTRUCTION DOCUMENTS -
RE-SUBMISSION
04/20/2021
7 95% CONSTRUCTION DOCUMENTS 07/15/2021
8 100% CONSTRCUTION DOCUMENTS 09/10/2021
FINISH GRADE/FLOOR
PVC OR RIGID METAL CONDUIT AS
SPECIFIED-SEE SPECIFICATIONS
AND/OR DRAWINGS
INSYLATING BUSHING-PROVIDE GROUNDING BUSHING AT
PAD MOUNT TRANSFORMER, AND WHEN TERMINATING IN
SERVICE ENTRANCE EQUIPMENT
BEND AND CONDUIT RISE TO
ABOVE GRADE/FLOOR SHALL BE
RIGID METAL CONDUIT-COAT WITH
ASPHALTUM AS SPECIFIED TO 6"
ABOVE GRADE OR FLUSH AT
FLOOR
RISE MIN. 6" ABOVE
GRADE/FLOOR UNO
LUMINAIRE MANUFACTURER'S
EARTHQUAKE CLIP, (4) PER
FIXTURE AT CORNERS. ATTACH
WITH SHEET METAL SCREW
FIXTURE WHIP
FROM JUNCTION
BOX
(6FT. LONG MAX.)
LUMINAIR. REFER TO
SCHEDULE
LUMINAIRE. REFER TO
SCHEDULE
DRYWALL BORDER
CEILING CROSS
BEAM
GYPSUM BOARD
CEILING MAIN BEAM
CEILING CROSS BEAM
GYPSUM BOARD
(TYP)
3 TWIST
MINIMUM (TYP)
LUMINAIRE
SUSPENSION WIRES
(#10 MIN)
ATTACHED TO
STRUCTURE
(TYP EA. CORNER)
LUMINAIRE MANUFACTURER'S
EARTHQUAKE CLIP, (4) PER
FIXTURE AT CORNERES. ATTACH
WITH SHEET METAL SCREW
FIXTURE WHIP
FROM JUNCTION
BOX
(6FT. LONG MAX.)
LUMINAIRE. REFER TO
SCHEDULE
ARCHITECTURAL
CEILING GRID
LUMINAIRE. REFER
TO SCHEDULE
ACOUSTICAL CEILING
TILE (TYP)
3 TWIST
MINIMUM (TYP)
LUMINAIRE
SUSPENSION WIRES
(#10 MIN)
ATTACHED TO
STRUCTURE
(TYP EA. CORNER)
CEILING
MAIN BEAM RECESSED CAN
LUMINAIRE
CEILING BEAM
GYPSUM BOARD (TYP)
LUMINAIRE
BAR HANGERSRECESSED CAN
LUMINAIRE
CEILING
CROSS BEAM
WIRE TIE OR SCREW
BAR HANGER TO
CROSS BEAM TYP.
CEILING HANGER
WIRE, TYP.
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING
INSTRUCTIONS AND USING THE RECOMMENDED MOUNTING
HARDWARE.
FIXTURE WHIP FROM
JUNCTION BOX (6'
[1829MM] LONG MAX
LUMINAIRE SUSPENSION
WIRE REFER TO
SPECIFICATION SECTION 26
51 00
CEILING HANGER
WIRE, TYP.
WIRE TIE OR
SCREW BAR
HANGER TO
ARCHITECTURAL
CEILING GRID TYP.
ARCHITECTURAL
CEILING GRID RECESSED CAN
LUMINAIRE
RECESSED CAN
LUMINAIRE
ARCHITECTURAL CEILING GRID
ACOUSTICAL
CEILING TILE
(TYP)
LUMINAIRE
BAR HANGERS
LUMINAIRE SUSPENSION
WIRE REFER TO
SPECIFICATION SECTION 26
51 00
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING
INSTRUCTIONS AND USING THE RECOMMENDED MOUNTING
HARDWARE.
FIXTURE WHIP FROM
JUNCTION BOX (6'
[1829MM] LONG MAX
CEILING HANGER WIRE
DRYWALL
CEILING CROSS
TEE, TYP.
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
HANGER WIRE AND MOUNTING
CHANNEL ATTACHED TO
STRUCTURE REFER TO
SPECIFICATION SECTION 26 51 00
WIRE TIE THROUGH
MOUNTING CHANNEL
& CROSS BEAM, TYP.
CEILING MAIN
BEAM
GYPSUM
BOARD
DRYWALL
CEILING CROSS
TEE, TYP. 1/4" SCREW
JUNCTION BOX
LOCKING
SQUARE
WASHER & NUT
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING
INSTRUCTIONS AND USING THE RECOMMENDED MOUNTING
HARDWARE.
FIXTURE WHIP FROM JUNCTION
BOX (6' [1829MM] LONG MAX.)
OFF
PROVIDE SWITCH ABOVE
CEILING FOR BATTERY TESTING
CEILING HANGER WIRE
ARCHITECTURAL
CEILING GRID
HANGER WIRE AND MOUNTING
CHANNEL ATTACHED TO
STRUCTURE. REFER TO
SPECIFICATION SECTION 26 51 00
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
WIRE TIE THROUGH
MOUNTING CHANNEL
& CROSS BEAM, TYP.
ARCHITECTURAL
CEILING GRID
ACOUSTICAL CEILING
TILE, TYP.
ARCHITECTURAL
CEILING GRID
1/4" SCREW
JUNCTION BOX
LOCKING SQUARE
WASHER & NUT
FIXTURE WHIP FROM JUNCTION
BOX (6' [1829MM] LONG MAX)
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING
INSTRUCTIONS AND USING THE RECOMMENDED MOUNTING
HARDWARE.
OFF
PROVIDE SWITCH ABOVE
CEILING FOR BATTERY TESTING
1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC WITH NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM)
WIDE BY 1-3/8 IN. (35 MM) DEEP CHANNELS SPACED MAX 24 IN. (610 MM) OC.
B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF
OPENING IS 26 IN. (660 MM).
2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN. (0 MM) (POINT CONTACT) TO MAX 2 IN. (51 MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM 12 IN.
(305 MM) DIAM (OR SMALLER) OR CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE.
C. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL
ELECTRICAL METALLIC TUBING
D. COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING E. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
F. THROUGH PENETRATING PRODUCT* - FLEXIBLE METAL PIPING - THE FOLLOWING TYPES OF STEEL FLEXIBLE METAL GAS
PIPING MAY BE USED:
1. NOM 2 IN. (51 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
OMEGA FLEX INC
2. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
TITEFLEX CORP
A BUNDY CO
3. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY
NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
WARD MFG INC
3. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8. 1-1/4,1-7/8 AND 2-1/2 IN. (16, 32, 48 AND 64 MM) THICKNESS OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES, RESPECTIVELY, APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT CONTACT
LOCATION ON BOTH SIDES OF WALL.
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN
WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE.
THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW:
+WHEN COPPER PIPE IS USED, T RATING IS 0 HR.
3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT,
*BEARING THE UL CLASSIFICATION MARKING
SYSTEM NO.W-L-1001
JUNE 15, 2005
F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2 AND 3)
T RATINGS - 0, 1, 2, 3, AND 4 HR (SEE ITEM 3)
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT
MAX PIPE OR
CONDUIT DIAM
IN. (mm)
1 (25)
1 (25)
4 (102)
6 (152)
12 (305)
F RATING
HR
1 OR 2
3 OR 4
1 OR 2
3 OR 4
1 OR 2
T RATING
HR
0+, 1 OR 2
3 OR 4
SECTION A-A
1B
1A
3A
A
LIGHTING
ZONE (a)
RCD
(AS NEEDED)
SEQUENCE OF OPERATION:
•…