This federal solicitation seeks a general contractor to renovate approximately 7,700 square feet of existing space at the Oklahoma City VA Health Care System. The renovation project aims to convert the space for use as administration and training areas to support the deployment of new Cerner electronic health record management equipment and software at the Oklahoma City VA facility and its associated community based outpatient clinics and other leased locations. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. Key requirements specified include furnishing all necessary labor, tools, materials, equipment and supervision to complete the construction work.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ALL WORK SHALL BE IN ACCORDANCE WITH THE 2018 INTERNATIONAL MECHANICAL
CODE (IMC), THE VHA HVAC AND MECHANICAL DESIGN MANUAL 2018 SPECIFICATIONS
AND GUIDELINES, AND THE AUTHORITIES HAVING JURISDICTION (AHJ).
CONTRACTOR IS TO VERIFY ALL DRAWING INFORMATION PRIOR TO STARTING WORK.
MINOR CHANGES IN ROUTING IS EXPECTED. WHERE WORK VARIES GREATLY FROM
THE PLANS CONTRACTOR SHALL CONTACT THE AE IMMEDIATELY BEFORE STARTING
WORK.
EXCEPT WHERE INDICATED, ALL EQUIPMENT, MATERIALS, AND ARTICLES
INCORPORATED IN THE WORK SHALL BE NEW AND OF COMPARABLE QUALITY AS
SPECIFIED. ALL WORKMANSHIP SHALL BE FIRST-CLASS AND SHALL BE PERFORMED
BY PERSONNEL SKILLED AND REGULARLY EMPLOYED IN THEIR RESPECTIVE TRADES.
ITEMS REUSED AND/OR RELOCATED SHALL BE BROUGHT TO LIKE NEW CONDITION
PRIOR TO BEING PLACED INTO SERVICE.
ALL WORK SHALL BE COORDINATED WITH ALL AFFECTED TRADES PRIOR TO
STARTING WORK. REWORK REQUIRED DUE TO COORDINATION ISSUES SHALL BE
DONE BY THE INSTALLATION CONTRACTOR WITHOUT INCREASED COST TO THE
OWNER.
SYSTEMS DESIGNATED TO BE PROVIDED AND INSTALLED WITHIN THESE CONTRACT
DOCUMENTS ARE INTENDED TO BE COMPLETE AND OPERATIONAL. PROVIDE
EVERYTHING ESSENTIAL FOR THE COMPLETION OF THE WORK TO MAKE THE SYSTEM
READY FOR NORMAL AND PROPER OPERATION. THIS INCLUDES ALL WORK OR
MATERIALS NOT DIRECTLY SHOWN ON THE DRAWINGS OR IN THE SPECIFICATIONS,
BUT NECESSARY FOR THE PROPER OPERATION OF THE SYSTEM.
IN GENERAL IT IS THE INTENT OF THESE DRAWINGS:
ITEMS INSTALLED WHERE THE STRUCTURE IS EXPOSED - INSTALLED AS HIGH AS
POSSIBLE. ALL VALVES AND CONTROL DEVICES SHOULD BE INSTALLED AS LOW AS
POSSIBLE OR WHERE IT WILL BE MAINTAINABLE FROM A LADDER OR LIFT. CLOSE
COORDINATION WILL BE REQUIRED IN ORDER TO AVOID ALL CONFLICTS.
ALL DUCT TO BE GALVANIZED STEEL. EXPOSED DUCT SHALL BE OF SPIRAL
CONSTRUCTION.
ALL SQUARE THROAT DUCT ELBOWS WITH ANY DIMENSIONS LARGER THAN 6" SHALL
HAVE TURNING VANES, WHETHER SHOWN ON THE PLANS OR NOT.
MANUFACTURERS/MODEL NUMBERS INDICATED ON DRAWINGS ARE BASIS OF DESIGN.
OTHER MANUFACTURERS/MODEL NUMBERS WILL BE ACCEPTED PROVIDING THEY
MEET SPECIFICATIONS AND PERFORMANCE REQUIREMENTS OF THE BASIS OF
DESIGN.
GENERAL MECHANICAL NOTES:
ABBREVIATIONS:
AC ALTERNATING CURRENT
ADJ. ADJUSTABLE
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
BHP BRAKE HORSEPOWER
BMS BUILDING MANAGEMENT SYSTEM
CALC CALCULATED
CC CHILLED WATER COOLING COIL - AHU
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
C/L CENTERLINE
CO CLEANOUT
COEF COEFFICIENT
COMLINK COMMUNICATION LINK
COND CONDENSATION
CONFIG CONFIGURED
COR CONTRACTING OFFICER'S REPRESENTATIVE
CNTRL. CONTROL
CP CONDENSATE PUMP
CPVC CHLORINATED POLYVINYL CHLORIDE
CR CONDENSATE RETURN
CV CONTROL VALVE
CV FLOW COEFFICIENT
DAMP. DAMPER
DAT DISCHARGE AIR TEMPERATURE
DB DRY BULB
DC DIRECT CURRENT
DCW DOMESTIC COLD WATER
DEG DEGREES
DHR DOMESTIC HOT WATER RETURN
DHW DOMESTIC HOT WATER
DIFF. DIFFERENTIAL
DIST DISTRUBUTION
DS DOWNSPOUT
DSP DEHUMIDIFICATION SET POINT
DWV DRAIN, WASTE AND VENT
(E) EXISTING
EA EXHAUST AIR
ECC ENERGY CONTROL CENTER
ELECT. ELECTRICAL
ELEV ELEVATION
ENT ENTERING
ERC ENERGY RECOVERY COIL - AHU
ES END SWITCH
EWC ELECTRIC WATER COOLER
F FAHRENHEIT
FD FLOOR DRAIN
FILT. FILTER
FPM FEET PER MINUTE
FT FEET
GAL GALLONS
GALV GALVANIZED
G.C. GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GT GLYCOL TANK
H HEIGHT
H HUMIDIFIER - AHU
HP HORSEPOWER
HPS HIGH PRESSURE STEAM
HR HOUR
HRCR HEAT RECOVERY RETURN
HRCS HEAT RECOVERY SUPPLY
HRP HEAT RECOVERY PUMP
HSP HUMIDIFICATION SET POINT
HVAC HEATING, VENTILATION, AND AIR CONDITIONING
HX HEAT EXCHANGER
Hz HERTZ
IBC INTERNATIONAL BUILDING CODE
ICVAMC IOWA CITY VETERANS AFFAIRS MEDICAL CENTER
IECC INTERNAIONAL ENERGY CONSERVATION CODE
IFB INTEGRAL FACE AND BYPASS
IMC INTERNATIONAL MECHANICAL CODE
I/O INPUT/OUTPUT
IPC INTERNATIONAL PLUMBING CODE
K.O. COMMANDING OFFICER
L LENGTH
LBS POUNDS
LPS LOW PRESSURE STEAM
LWA SOUND POWER LEVEL
MAX MAXIMUM
MBH THOUSAND BRITISH THERMAL UNITS PER HOUR
MC MECHANICAL CONTRACTOR
MD MOTORIZED DAMPER
MECH MECHANICAL
MFG MANUFACTURER
MIN MINIMUM
MIN MINUTE
mm MILLIMETER
MPS MEDIUM PRESSURE STEAM
MT MOISTURE (HUMIDITY) TRANSMITTER
MV MANUAL VENT
N.C. NORMALLY CLOSED
NC NOISE CRITERIA LEVEL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NG NATURAL GAS
N.O. NORMALLY OPEN
NPT NATIONAL PIPE THREAD
OA OUTSIDE AIR
OAT OUTSIDE AIR TEMPERATURE
ORD OVERFLOW ROOF DRAIN
OSA OUTSIDE AIR
OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
Pa PASCAL
PC PUMPED CONDENSATE
PC PREHEAT STEAM COIL - AHU
PD PRESSURE DROP
PDS PRESSURE DIFFERENTIAL SENSOR
PH PHASE
PI PROPORTIONAL INTEGRAL
PID PROPORTIONAL INTEGRAL DERIVATIVE
PRESS. PRESSURE
PSH HIGH PRESSURE SWITCH
PSIG POUNDS PER SQUARE INCH - GAUGE
PSL LOW PRESSURE SWITCH
QUANT. QUANTITY
R RADIUS
R RETURN
RA RETURN AIR
RC REHEAT STEAM COIL - AHU
RD ROOF DRAIN
RE RESIDENT ENGINEER
RFR REFRIGERANT RETURN
RFS REFRIGERANT SUPPLY
REQ'D REQUIRED
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
S SUPPLY
SA SUPPLY AIR
SAN SANITARY
SD SMOKE DAMPER
SF FAN SECTION - AHU
SF SQUARE FEET
SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS ASSOCIATION
SP STATIC PRESSURE
SPEC SPECIFICATION
SS STAINLESS STEEL
SST START/STOP
SUH STEAM UNIT HEATER
SV STEAM VALVE
SV STEAM VENT
T THERMOSTAT
TEMP. TEMPERATURE
TSP TOTAL STATIC PRESSURE
TT TEMPERATURE SENSOR/TRANSMITTER
TYP TYPICAL
UH UNIT HEATER
V VENT
V VOLTS
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
VSMC VARIABLE SPEED MOTOR CONTROLLER
VTR VENT THROUGH ROOF
W WIDTH
W/ WITH
WB WET BULB
WG INCHES OF WATER
ZAT ZONE AIR TEMPERATURE
ZC VALVE OR DAMPER CONTROLLER
T
P
AHU-6 2
H
HVAC / MECHANICAL SYMBOLS
MECHANICAL EQUIPMENT TAG WITH
NUMBER DESIGNATION
THERMOSTAT
MECHANICAL PLAN NOTE
POINT OF CONNECTION
POINT OF DISCONNECTION
TO BE DEMOLISHED
CHILLED WATER SUPPLY
CHILLED WATER RETURN
PRESSURE SENSOR
PIPE DOWN
PIPE UP
PIPE TEE DOWN
LOW PRESSURE STEAM
MEDIUM PRESSURE STEAM
CONDENSATE RETURN
HIGH PRESSSURE STEAM
CONDENSATE RETURN
PUMPED STEAM CONDENSATE RETURN
PIPE ELBOW
STRAINER
STEAM BUCKET TRAP
GATE VALVE
UNION
CHECK VALVE
CONCENTRIC PIPE REDUCER
PIE TEE
HUMIDITY SENSOR
HOT WATER SUPPLY
HOT WATER RETURN
REHEAT HOT WATER SUPPLY
REHEAT HOT WATER RETURN
BALL VALVE
HEAT EXCHANGER
PRESSURE GAUGE
STEAM CONDENSATE PUMP
STEAM FLASH TANK
TEMPERATURE GAUGE
FLOAT & THERMOSTATIC TRAP
STEAM THERMOSTATIC TRAP
GLOBE VALVE
ECCENTRIC PIPE REDUCER
MODULATING CONTROL VALVE
PRESSURE REDUCING VALVE
LIQUID FLOW DIRECTION
MANUAL BALANCING / SHUT-OFF VALVE
HWS
HWR
RHWS
RHWR
CHS
CHR
MEDIUM PRESSURE STEAM
HIGH PRESSURE STEAM
LOW PRESSURE STEAM
CONDENSATE RETURN
STM-LP
STM-MP
STM-HP
CDR-L
CDR-M
CDR-H
PC
SA SUPPLY AIR DUCT FROM AHU
REFRIGERANT - LIQUID
REFRIGERANT - SUCTION
RL
RS
N.O. N.C.
S DIFFERENTIAL PRESSURE SENSORP
TS TEMPERATURE SENSOR
EXPANSION TANK
PERIMETER HEATING WATER SUPPLY
PERIMETER HEATING WATER RETURN
PHWS
PHWR
TWO HOUR FIRE BARRIER
ONE HOUR FIRE BARRIER
DIRECTION OF AIR FLOW
S/A SUPPLY AIR DUCT FROM VAV
F/A FRESH AIR DUCT FROM ERV
O/A OUTSIDE AIR DUCT TO AHU OR ERV
EA EXHAUST AIR DUCT TO AHU
E/A EXHAUST AIR DUCT TO EXTERIOR
VANED ELBOW (PROVIDE ALL SQUARE
OR RECTANGULAR ELBOWS WITH
VANES EVEN IF SYMBOL IS MISSING)
VANED RADIUS ELBOW (SHORT RADIUS)
RADIUS ELBOW (SHORT RADIUS)
10X8
RECTANGULAR DUCT (INSIDE
DIMENSIONS: WIDTH / DEPTH)
10/8
OVAL DUCT (INSIDE DIMENSIONS:
WIDTH / DEPTH)
10"⌀
ROUND DUCT (INSIDE DIMENSIONS:
WIDTH / DEPTH)
10X8 SUPPLY DUCT UP
10X8 SUPPLY DUCT DOWN
10X8 RETURN DUCT UP
10X8 RETURN DUCT DOWN
10X8 EXHAUST DUCT UP
10X8 EXHAUST DUCT DOWN
M
MOTORIZED DAMPER
W/ ACCESS DOOR
FD
FIRE DAMPER
W/ ACCESS DOOR
FSD
FIRE AND SMOKE DAMPER
W/ ACCESS DOOR
BD
BACKDRAFT DAMPER
W/ ACCESS DOOR
MANUAL VOLUME DAMPER
SUPPLY DIFFUSER
RETURN GRILLE
EXHAUST GRILLE
SD
SMOKE DAMPER
W/ ACCESS DOOR
575 CFM
S-1 GRILLE / REGISTER / DIFFUSER
TAG W/ CFM
FLEX DUCT
DUCT FLEX CONNECTOR
VARIABLE AIR VOLUME BOX (VAV) /
TERMINAL UNIT (TU)
WALL MOUNTED EXHAUST FAN
DUCT HOT WATER REHEAT COIL
PIPE TEE UP
OR
SMOKE BARRIERS S
E E
N
No. 20031
AOM
TN AN
SC
L I EN
DE
S S
R O
F E
P
LI O AN
NG
E
I
R
ALEX R.
ZIMMERMAN
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of
Veterans Affairsof
/1
/2
:2
:1
P
M
CONSTRUCTION DOCUMENTS
05/12/2022
MECHANICAL ABBREVIATIONS,
SYMBOLS, LEGENDS, AND GENERAL
NOTES
M0.00
EHRM TRAINING AND ADMIN
SPACE
AZRD
921 NE 13TH ST
OKLAHOMA CITY, OK 73104Owner
VA259-16-D-0217
28 59
MECHANICAL SHEET INDEX
M0.00 MECHANICAL ABBREVIATIONS, SYMBOLS, LEGENDS, AND GENERAL NOTES
M0.01 MECHANICAL SCHEDULES
M0.02 MECHANICAL DETAILS
M0.03 MECHANICAL DETAILS
MD1.00 LOWER LEVEL HVAC DEMOLITION PLAN
MD1.10 UPPER LEVEL HVAC DEMOLITION PLAN
MH1.00 LOWER LEVEL HVAC NEW PLAN
MH1.10 UPPER LEVEL HVAC NEW PLAN
MP1.00 LOWER LEVEL HYDRONIC NEW PLAN
MP1.10 UPPER LEVEL HYDRONIC NEW PLAN
MH2.01 ENLARGED MECHANICAL ROOM PLAN AND ELEVATIONS
M2.10 HVAC CONTROL DETAILS
MH3.00 MECHANICAL SECTIONS
MH3.01 ENLARGED MECHANICAL SECTIONS
M3.10 HVAC DUCT ISOMETRIC VIEW
M3.20 HYDRONIC PIPING ISOMETRIC VIEW
OVERHEAD RADIANT PANEL SCHEDULE
MANUFACTURER & MODEL
OPTIONS-ACCESSORIES
HEATING CAPACITY
GPM
RAD-1
1852 180 ZEHNDER RITTLING 24" LINEAR RADIANT PANEL
1,2,3,4
1. TO BE MOUNTED IN LAY-IN CEILING FRAME, MODIFY CEILING PANEL TO ACCOMODATE.
2. PROVIDE WITH SOV'S AND CONTROL VALVE.
3. SUPPORT PANEL AS PER MANUFACTURERS WRITTEN INSTRUCTIONS.
4. SHOWN AS BASIS OF DESIGN, APPROVED EQUAL ALLOWED
PANEL SIZE
24"x48" 0.74
RAD-2
RAD
2778 180 ZEHNDER RITTLING 24" LINEAR RADIANT PANEL
1,2,3,4
24"x72" 1.11
PUMP SCHEDULE
NOTES:
LOCATION GPM SIZE
MOTOR
HP RPM VOLT.-PH.-CY.
MANUFACTURER & MODELSERVICE NOTES
FLA
P
P-4,5 PERIMETER RADIANT HEAT
17 MECHANICAL
GRUNDFOS MAGNA1 40-80 F 1,2,3,4
1. PROVIDE WITH FLANGES SELECTED BY INSTALLING CONTRACTOR.
2. INSTALL PER MANUFACTURERS INSTRUCTIONS.
3. CONTRACTOR SHALL SET PUMP TO ENABLE ON ANY ZONE DEMAND CALL FOR HEAT.
4. SHOWN AS BASIS OF DESIGN, APPROVED EQUAL ALLOWED.
5. PROVIDE WITH FACTORY CONTROL PANEL.
P-2,3 VAV REHEAT
17 MECHANICAL
GRUNDFOS MAGNA1 32-60 F
STEAM TO HOT WATER HEAT EXCHANGER SCHEDULE
NOTES:
LOCATION GPM MANUFACTURER & MODELSERVICE OPTIONS-ACCESSORIES
HEX
1. PROVIDE VACUUM BREAKER.
2. PROVIDE WITH MANUFACTURERS STAND AND RACK.
3. SET RELIEF VALVE AT 15PSI.
4. PROVIDE WITH ALL EQUIPMENT SHOWN ON M-0.03.
5. SHOWN AS BASIS OF DESIGN, APPROVED EQUAL ALLOWED
EWT
°F
LWT
°F
MBH LBS/HR
STEAM
AREA
FT
1,2,3,4
NOTES:
GRILLE/REGISTER/DIFFUSER SCHEDULE
TAG NO. NECK SIZE TYPE MANUFACTURER & MODEL MATL/FINISH OPTIONS & ACCESSORIES
RG=RETURN GRILLE SD=SUPPLY DIFFUSER EG=EXHAUST GRILLE
NOTES:
RG-1 CEILING LOUVERED RETURN GRILLE LAY-IN NAILOR 5145H-24x24-L-O WHITE
SD-1 VARIES CEILING SUPPLY DIFFUSER LAY-IN NAILOR ARNS-L-O WHITE
EG-1 WHITE
XX
CFM
1. REFER TO PLANS FOR NECK SIZE, TO MATCH DUCT SIZE SERVING DIFFUSER.
2. -O IN MODEL REFERS TO OPPOSED BLADE DAMPER.
3. SHOWN AS BASIS OF DESIGN, APPROVED EQUAL ALLOWED.
4. CONTRACTOR TO PROVIDE ALL NECESSARY HARDWARE FOR MOUNTING TYPE LISTED ABOVE.
CEILING LOUVERED RETURN GRILLE LAY-IN
1,2,3
2,3
2,3NAILOR 5145H-24x24-L-O
VARIES
VARIES
LOCATION
CFM
MOTOR
HP-W SONES VOLT.-PH.-CY.
MANUFACTURER & MODEL
SERVICE
NOTES
EF-1 EXHAUST
EF
1. PROVIDE WITH DISCONNECT, BACKDRAFT DAMPER, SPEED CONTROL, AND PRE-RAB ROOF CURB.
2. ANY ONE OF 6 OCCUPANCY SENSORS IN THE FOLLOWING SPACES TO ENABLE FAN:
2.· 3 TOILET
2.· 4 TOILET
2.· 7 TOILET
2.· 8 TOILET
2.· 9 HAC
2.· OA1 BREAK ROOM
3. SHOWN AS BASIS OF DESIGN, APPROVED EQUAL ALLOWED
FAN SCHEDULE
561 0.18 5.4
120-1-60 1,2,3
1/25
ROOF GREENHECK CUE-090-G
NOTES:
EQUIPMENT
NO.
TOTAL
BTU/HR.
WATER
ENT.( F)
ITEM
NO.
GLYCOL
FT
HEAD
ITEM
NO.
EQUIP.
NO.
STATIC
PRESS.
(IN. W.G.)
P-103
WALL HUNG TOILET. ELONGATED BOWL W/ HARDWIRED1.6 GAL/FLUSH SIPHON JET FLUSH VALVE
ELONGATED OPEN FRONT-ADA SEAT
2"3"
1"
VENT C.W.
PLUMBING FIXTURE SCHEDULE
FIXTURE TAG
DESCRIPTION
PIPING CONNECTIONS
TRAP S/W
H.W.
REMARKS
1. PROVIDE ADA OFFSET TRAP ASSEMBLY WITH INSULATION KIT.
2. COORDINATE COLOR OF FIXTURE DURING SUBMITTAL PROCESS. ARCHITECT TO SELECT COLORS.
P-420
2"
REFER TO SPECIFICATION SECTION 22 40 00 FOR TRAP, STOPS, AND MIXING VALVE REQUIREMENTS.
APPROX. 19" DIAMETER SELF RIMMING COUNTERTOP LAVATORY. VITREOUS CHINA
HARDWIRED SENSOR FAUCET. CHROME PLATE GOOSENECK 4"-5" ABOVE RIM LEVEL
P-609
ELECTRIC WATER COOLER. DUAL HEIGHT STAINLESS STEEL FOUNTAIN WITH BOTTLE FILLER.
2"
P-502
3"
REFER TO SPECIFICATION SECTION 22 40 00 FOR TRAP, STOPS, AND MIXING VALVE REQUIREMENTS.
FLOOR MOUNTED CORNER TERRAZZO SERVICE SINK. APPROX 28"x28"x12" W/ 6" DROP FRONT
WALL MOUNTED COMBINATION FAUCET WITH INTEGRAL CHECKS/STOPS, HOSE THREADS, VACUUM
BREAKER, AND PAIL HOOK.
2"
REFER TO SPECIFICATION SECTION 22 40 00 FOR SEAT, FLUSH VALVE, CARRIER REQUIREMENTS.
2" 2"
REFER TO SPECIFICATION SECTION 22 40 00 FOR ADDITIONAL REQUIREMENTS.
NOTES:
VENT C.W.
PLUMBING SPECIALTY SCHEDULE
FIXTURE TAG
DESCRIPTION
PIPING CONNECTIONS
TRAP S/W
H.W.
REMARKS
1. SIZE LISTED ON SCHEDULES APPLY TO ALL FIXTURES ON PROJECT UNLESS OTHERWISE NOTED.
2. SEE PLUMBING SPECIFICATIONS FOR ADDITIONAL INFORMATION.
3" 1,2
3" FLOOR CLEANOUT. ZURN ZN1400-SZ.
NOTES:
FCO-1
HVAC SPECIALTY SCHEDULE
TAG NO.
SIZE TYPE MANUFACTURER & MODEL
NOTES
ADDITIONAL NOTES
BALANCING DAMPER RECTANGULAR (<10" SINGLE / GREATER OPP BLD)
HIGH EFFICIENCY DUCT TAKEOFF
NOTE: ALL ITEMS LISTED ON THIS SCHEDULE ARE CONSIDERED BASIS OF DESIGN, AND PRODUCTS CONSIDERED EQUAL SHALL BE ELIGIBLE TO BE
SUPPLIED AND INSTALLED ON THIS PROJECT, UPON APPROVAL OF ENGINEER.
* INDICATES ITEMS THAT MAY NOT BE SPECIFICALLY TAGGED ON PLAN SHEETS, BUT ARE NOTED IN FLOOR PLANS, DETAILS, SECTIONS, OR CALLOUTS
SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR BASED ON REQUIREMENTS ASSOCIATED WITH THIS PROJECT.
HETO*
BD* VARIES
WITH LOCKING QUAD
WITH LOCKING QUAD
BALANCING DAMPER ROUNDBD* VARIES WITH LOCKING QUAD
VARIES HERCULES HTO
NAILOR 1870 / 1020
NAILOR 1890
SD-2 WHITE 2,3VARIES
CEILING SUPPLY DIFFUSER LAY-IN
NAILOR 5875 PLENUM SLOT DIFFUSER WITH ICE-TONG PATTERN CONTROLLER
RAD-3
1356 180 ZEHNDER RITTLING 18" LINEAR RADIANT PANEL
1,2,3,4
18"x48" 0.54
HEX-1,2 PERIMETER RADIANT HEAT AND VAV REHEAT
17 MECHANICAL
1,2,3,4,5ARMSTRONG SHELL AND TUBE WS-0602-400-1
35 159 180 350 365 8.9
P-1 HEAT EXCHANGER
17 MECHANICAL
GRUNDFOS MAGNA3 32-100 F 1,2,3,430
1-1/2"7.729 1/6 - 120-1-60 1.0
2-1/2"3.035 178 W - 120-1-60 1.6
42 2-1/2"20.8 280 W 120-1-60 2.5-
AIR HANDLING UNIT SCHEDULE
NOTES:
RETURN FAN
CFM
MANUFACTURER & MODEL
SERVICE
OPTIONS-ACCESSORIES
AHU
HP
LOCATION
SUPPLY FAN ELECTRICAL
V.-PH.-CY. FLA
MOCP
AHU-1 H/C/V 17 MECHANICAL 1950 7100 1.48 2 208-3-60 44.0 70 TRANE CSAA017 1,2,3,4,5,6,7
1. PROVIDE WITH FULL ECONOMIZER MIXING SECTION WITH DAMPERS, AND STEAM HUMIDIFIER SECTION.
2. PROVIDE WITH WITH VFD AND FUSED DISCONNECT.
3. PROVIDE WITH INTERIOR ENCLOSURE, TOP SUPPLY AND MIXING SECTION, AND FLOOR MOUNT OPTION.
4. PROVIDE WITH 4" CONCRETE HOUSEKEEPING PAD.
5. PROVIDE WITH SUPPLY AND RETURN AIR STREAM SMOKE DETECTORS.
6. PROVIDE WITH MERV 7 PRE-FILTER AND MERV 11 SECOND PRE-FILTER.
7. SHOWN AS BASIS OF DESIGN, APPROVED EQUAL ALLOWED.
MCA
49.5236
CHILLED WATER COOLING COIL
STEAM PREHEAT COIL
MBH
EAT °F
LAT °F
PSI
LBS/HR
STEAM HUMIDIFIER
PSI
CFM
LBS/HR
MBH
EAT °F
LAT °F
EWT °F
LWT °F
GPM
MIN
OUTSIDE
AIR
(CFM)
EQUIP.
NO.
E.S.P.
(IN. W.G.)
SUPPLY FAN
CFM HP
7100 4.65 5
E.S.P.
(IN. W.G.)
QTY
QTY
RETURN FAN ELECTRICAL
V.-PH.-CY. FLA MOCP
208-3-60 13.6 20
MCA
15.3
EXPANSION TANK SCHEDULE
EQUIP TAG MFGR MODEL TYPE
TANK VOLUME (GAL) TANK ACCEPT (GAL) HEIGHT (IN) DIAMETER (IN) WEIGHT (LBS)
NOTES
ET-1 TACO CBX15-125 BLADDER 4 2.5 15 14 45 1
AIR SEPARATOR SCHEDULE
EQUIP TAG MFGR MODEL SYSTEM
CONNECTION SIZE (IN) FLOW (GPM) HEIGHT (IN) DIAMETER (IN)
NOTES
1. MANUFACTURER IS BASIS OF DESIGN. OTHER MANUFACTURERS ALLOWED.
AS
ET
AS-1 TACO 49025ADT-125 HOT WATER 2.5 35 17 10
NOTES:
1. MANUFACTURER IS BASIS OF DESIGN. OTHER MANUFACTURERS ALLOWED.
NOTES:
VARIABLE AIR VOLUME BOX SCHEDULE
MANUFACTURER & MODEL
OPTIONS-ACCESSORIES
HEATING CAPACITY
GPM
VAV-01 800 0.40
55 83 23.8K 180 149 TITUS DESV SINGLE DUCT 08
1,2,3,4
1. PROVIDE WITH FACTORY DISCONNECT AND ELECTRIC ACTUATOR.
2. DDC CONTROL (CONTROLLER BY TC CONTRACTOR).
3. PROVIDE WITH SPRING VIBRATION ISOLATION AND ALL-THREAD HANGING RODS.
4. SHOWN AS BASIS OF DESIGN, APPROVED EQUAL ALLOWED
1.55
VAV-02
VAV-03
VAV-04
VAV-05
VAV-06
VAV-07
VAV-08
VAV-11
VAV-12
VAV-13
VAV-14
VAV-17
VAV-18
160 0.04 55 83 180 159 0.45
100 0.02 55 92 180 162 0.45
400 0.32 55 84 180 153 0.90
190 0.06 55 83 180 161 0.58
320 0.15 55 83 180 173 2.91
360 0.27 55 86 180 154 0.90
510 0.19 55 83 180 146 0.90
440 0.39 55 83 180 153 0.97
430 0.37 55 83 180 153 0.94
4.8K
4.0K
12.3K
5.7K
9.6K
11.9K
15.4K
13.2K
12.9K
500 0.18 55 83 180 146 0.9115.4K
VAV
1,2,3,4
1,2,3,4
1,2,3,4
1,2,3,4
1,2,3,4
1,2,3,4
1,2,3,4
1,2,3,4
1,2,3,4
1,2,3,4
1,2,3,4
1,2,3,4
1,2,3,4
NOTES:
EQUIPMENT
NO.
INLET SIZE
"Ø
ESP
(IN)
DESIGN
CFM
AIR ENTERS
(°F)
AIR LEAVES
MAX (°F)
TOTAL
BTU/HR.
WATER
ENT.(°F)
WATER
LVG.(°F)
VAV-09 8 570 0.23
55 83 180 146 1.0117.1K
1,2,3,4
VAV-15 6 180 0.06
55 83 180 160 0.575.6K
1,2,3,4
VAV-10 8 600 0.25
55 83 180 146 1.0718.0K
1,2,3,4
VAV-16 6 125 0.03
55 87 180 161 0.464.4K
1,2,3,4
TITUS DESV SINGLE DUCT 08
TITUS DESV SINGLE DUCT 08
TITUS DESV SINGLE DUCT 08
TITUS DESV SINGLE DUCT 08
TITUS DESV SINGLE DUCT 08
TITUS DESV SINGLE DUCT 06
TITUS DESV SINGLE DUCT 06
TITUS DESV SINGLE DUCT 06
TITUS DESV SINGLE DUCT 06
TITUS DESV SINGLE DUCT 06
TITUS DESV SINGLE DUCT 06
TITUS DESV SINGLE DUCT 06
TITUS DESV SINGLE DUCT 06
TITUS DESV SINGLE DUCT 06
TITUS DESV SINGLE DUCT 06
TITUS DESV SINGLE DUCT 06
6 360 0.27 55 86 180 154 0.9011.9K
8 500 0.18 55 83 180 146 0.9115.4K
8 555 0.23
55 83 180 146 1.4217.5K TITUS DESV SINGLE DUCT 08
CONSTRUCTION DOCUMENTS
05/12/2022
EHRM TRAINING AND ADMIN
SPACE
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of
Construction and Facilities
Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e i g h t h i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t t h r e e i n c h e s o n e f o o t
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
921 NE 13TH ST.
OKLAHOMA CITY, OK 73104
of
VA259-16-D-0217
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
AZ
Owner
RD
Department of
Veterans Affairs
MECHANICAL SCHEDULES
M0.01
29 59
STEAM TRAP ASSEMBLY
M I N
M I N
M I N
DRIP LEG (TYP.)
20mm [3/4"] DRAIN
(ALTERNATE LOCATIONS)
(TYPICAL)
STEAM LINE
(TYPICAL)
CAP (TYPICAL)
PIPE T0 STEAM
TRAP (TYPICAL)
NOTE:
DRIP POCKET PIPE SIZE SAME AS
STEAM MAIN UNLESS OTHERWISE
NOTED.
STEAM LINE DRIP POCKET
20mm [3/4"] MIN.
FROM DRIP
CONNECTION
DRIP
RETURN
10mm [3/8"] TEST
CONNECTION
FROM STRUCTURE
SAME AS DIFFUSER
INLET: 5'-0" MAX
FLEXIBLE DUCT SIZE
LENGTH.
12"
CEILING
SUPPORT SADDLE
VOLUME DAMPER W/
LOCKING QUAD
SADDLE
SHEET METAL
CONICAL OUTLET
BRANCH DUCT
FOR CHANGE OF
DIRECTION GREATER
USE RIGID ELBOWS
THAN 45°
[300mm]
SEE SPECIFICATIONS FOR CLAMPS
AND SEALANT (TYP.)
TYPICAL
DIFFUSER OR
REGISTER IN
LAY-IN CLG.
THERMAL INSULATION
SEE SPECIFICATIONS
BRANCH DUCT TAKE-OFF PLAN VIEW
SUPPLY REGISTER TAKE-OFF PLAN VIEW
PROVIDE VOLUME
DAMPER
ADJUSTABLE
METAL ROD
OR LINKAGE
TOP REGISTER
MAIN SUPPLY
DUCT
VOLUME EXTRACTOR; ADJUSTABLE
FROM FULLY CLOSED POSITION TO
CFM NOTED ON FLOOR PLANS
AIR
FLOW
AIR
FLOW
1/4 W OR 4"
[100mm] MIN.
AIR
FLOW
MAIN SUPPLY
DUCT
W
A I R
F L
O W
NOTE:
1.
2.
3.
4.
5.
RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A
MINIMUM OF 3 TIMES THE DIAMETER OF INLET
A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS BOX, BUT ALLOWED
TO ACCOMMODATE MINOR OFFSETS. MAXIMUM LENGTH 3'-0" [900mm].
A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE BOX INLET,
PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10
FEET (3 METERS). FOR LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A DUCT
TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE DROP AT OR BELOW 0.2"/100' [1.64Pa/m].
FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY AIR DUCT TO
DIFFUSER, SHALL NOT EXCEED 5'-0" [1500mm]. USE RIGID ELBOWS FOR CHANGE OF DIRECTION
GREATER THAN 45°.
COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE
INSULATION W/VAPOR BARRIER FOR CONNECTING DUCT SECTIONS.
AIR TERMINAL UNIT
(VAV)
REHEAT COIL
SOUND ATTENUATOR SEE
EQUIPMENT SCHEDULE
FLEXIBLE AIR DUCT
CONNECTOR. SEE DETAIL
DIFFUSER (TYP.)
SEE SPECIFICATIONS FOR
CLAMPS AND SEALANT (TYP.)
SEE NOTE 5
S
E
N
O T
E
SEE NOTE 3
SEE NOTE 2
SEE NOTE 1
VOLUME
DAMPER (TYP)
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
M
A
X
M
A
X
E Q
U I P
M E
N T
AIR
FLOW
AIR
FLOW
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEW
TYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
M
A
X
M
A
X
M A
X
M
A
X
D U
C T
H
I G
STEAM
CONDENSATE
RETURN TO
BASEMENT
TEMPERATURE
SWITCH
SCALE POCKET
HUMIDIFIER
CONTROL VALVE
TO HUMIDISTAT
MANIFOLD PIPE ADAPTERS
STEAM SUPPLY
ON-OFF CONTROL VALVE DUCT CROSS SECTION
M
I N m m
INVERTED BUCKET
TRAP ASSEMBLY
NOTE:
SEE MANUFACTURER'S PIPING RECOMMENDATIONS FOR
FINAL LAYOUT
NOTE:
1.
2.
3.
4.
ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE
REGARDLESS OF W DIMENSION.
ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM
SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE VANE
TYPE.
W
W1
VANE
VANE
NOTE:
1.
2.
THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL
SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED, SUPPORTED
AND FASTENED AS RECOMMENDED BY SMACNA.
R SHALL
EQUAL OR
BE
GREATER
THAN W.
R SHALL
EQUAL OR
BE
GREATER
THAN
1/3W.
R
W
R SHALL
EQUAL OR
BE
GREATER
THAN
1/6W.
STANDARD RADIUS OR
LONG RADIUS ELBOW
SHORT RADIUS ELBOW
WITH ONE VANE
SHORT RADIUS ELBOW
WITH TWO VANES
W W
W
1/6W
R
STANDARD RADIUS OR
LONG RADIUS ELBOW
SIDE VIEW TRAPEZE HANGER FOR UP TO
453KG [1000 LB.] UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE
43 - SEE SPECIFICATIONS
PROVIDE INSULATION
SHIELD
& INSERT FOR ALL PIPING
(200mm [8"] MIN.)
43mm [1-5/8"] 12 GAUGE
CHANNEL OR 50x50x6.4mm
[2"X2"X1/4"] ANGLE
15mm [1/2"] DIA.
HANGER RODS WITH
900mm [36"] MAX.
SPACING ON EACH
CHANNEL
INSULATION SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9 PSF
MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
NOTE:
SEE SPECIFER FOR DETAILED HANGER
REQUIREMENTS
mm
[IN]
mm
[FT]
mm
[FT]
THRU 20
[THRU
[7]
[5]
[1]
[7]
[6]
[1
[7]
[7]
[1
[9]
[8]
[2]
[10]
[8]
[2
[11]
[9]
[3]
[12]
[10]
[4]
[14]
[12]
[5]
[16]
[13]
[6]
[17]
[14]
[8]
[19]
[16]
[10]
[22]
[12]
[23]
[14]
[25]
[16]
[27]
[18]
[28]
[20]
[30]
[24]
[32]
WATER COIL
AIR VENT
WHEN COIL
IS NOT
SELF-VENTING
DRAIN WHEN COIL IS
NOT SELF-DRAINING
TEST PLUG
(TYP.)
PIPE HANGER SHALL
SUPPORT PIPING
INDEPENDENT OF COIL
REDUCER, IF REQUIRED
DRAIN
NOTES:
1. WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST
2 HANGERS FOR EACH PIPE SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" FOR
100mm [4"]Ø PIPE & SMALLER. TYPE "H-P" FOR 125mm [5"]Ø PIPE & LARGER.
2. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE SWING
OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE SERVICING
OF FILTERS, VALES, OR EQUIPMENT.
3. THE FLOW ELEMENT MAY BE INSTALLED IN THE SUPPLY PIPING IF THE REQUIRED
MINIMUM UPSTREAM AND DOWNSTREAM DIMENSIONS CANNOT BE OBTAINED IN
THE RETURN PIPING.
FE
MV
MV
MV
TI
TEMPERATURE
INDICATION TO ECC
SEE CONTROL DIAGRAM
COND/CWR
STM/CWS
1/4 TURN BOILER DRAIN
VALVE WITH BRASS CAP, TYP.
1/4 TURN BOILER DRAIN
VALVE WITH BRASS CAP, TYP.
STEAM TRAP ASSEMBLY DETAIL
M0.02
SCALE: NTS
CONSTRUCTION DOCUMENTS
05/12/2022
EHRM TRAINING AND ADMIN
SPACE
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of
Construction and Facilities
Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e i g h t h i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t t h r e e i n c h e s o n e f o o t
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
921 NE 13TH ST.
OKLAHOMA CITY, OK 73104
of
VA259-16-D-0217
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
AZ
Owner
RD
Department of
Veterans Affairs
MECHANICAL DETAILS
M0.02
FLEXIBLE AIR DUCT CONNECTOR DETAIL
M0.02
SCALE: NTS
SUPPLY DUCT TAKEOFF DETAILS
M0.02
SCALE: NTS
AIR TERMINAL UNIT DUCT CONNECTION DETAIL
M0.02
SCALE: NTS
DUCTWORK TRANSITIONS W/EQUIPMENT IN DUCT DETAILS
M0.02
SCALE: NTS
STEAM HUMIDIFIER PIPING DETAIL
M0.02
SCALE: NTS
DUCTWORK ELBOW DETAILS
M0.02
SCALE: NTS
PIPE HANGER DETAIL
M0.02
SCALE: NTS
AHU WATER COIL PIPING CONNECTION DETAIL
M0.02
SCALE: NTS
30 59
D
R
I
V
Q
U
I
P
M
E
N
T
M
O
T
O
R
TYPICAL STRUCTURAL
STEEL MEMBER FOR
EQUIPMENT
TYPE"B"
WELDED STEEL BASE
TYPE "1"
CONCRETE INERTIA BASE
NUMBER OF ISOLATION
UNITS AS REQUIRED
NUMBER OF ISOLATION
UNITS AS REQUIRED
TYPICAL STRUCTURAL
STEEL MEMBER FOR
EQUIPMENT
ALL WELDED STEEL
FRAMEWORK
SECTION A-A
STRUCTURAL
STEEL FRAME
SPRING
ISOLATOR
ANCHOR
BOLT
REINFORCING BARSSLEEVE
A
S
H
A
F
T
M
O
T
O
R
S
H
A
F
I
V
Q
U
I
P
M
E
N
T
A
REHEAT COIL
TEST PLUG (TYP.)
REDUCER, IF REQUIRED
HWR
MANUAL AIR VENT
UNION CONNECTIONS
(TYP.)
HWS
SHUT OFF VALVE
DRAIN WITH
CAPPED HOSE
CONNECTION
MV
3-WAY MODULATION CONTROL
VALVE
VAV
1/4 TURN BOILER DRAIN
VALVE WITH BRASS CAP, TYP.
PIPE HANGERS - PROVIDE DOUBLE
DEFLECTION NEOPRENE (TYPE HN) FOR
FIRST TWO ON EACH SIDE OF PUMP (SEE
NOTE NO. 1)
PRESSURE GAGE
1/2" [15mm]
STRAINER
FLEXIBLE
CONNECTION
BALL VALVE TYP.
NOTES:
1. SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM MOTOR.
BALANCING
DEVICE
HEATING ONLY PANEL
HWS
HWR
RUNOUT PIPING. PROVIDE DIELECTRIC
FITTINGS AS REQUIRED. CIRCUIT TO COMPLY
WITH SPECIFIED CAPACITY & PRESSURE
DROP. (TYP.)
NOTE:
1. MINIMUM FLOW SHALL BE NO
LESS THAN 0.5 GPM [1.9 LPM]
TEST PLUG
(TYP.)
CAPPED 1/4 TURN
DRAIN FOR AIR
VENT (TYP.)
1/4 TURN BOILER DRAIN
VALVE WITH BRASS CAP, TYP.
WELD SLEEVE PIPE
TO RACK PIPE
FLOOR
2" OD PIPE
6" TALL 2-1/2" OD PIPE
MOUNTING SLEEVE
2"x4"x3/16" THICK
SQUARE TUBE
WELD SQUARE TUBE
TO SLEEVE PIPE
2"x4"x3/16" THICK
SQUARE TUBE
HORIZONTAL SUPPORT
NOTES:
ELEVATE HEAT EXCHANGERS TO
ALLOW GRAVITY FEED OF
CONDENSATE TO BASEMENT.
PROVIDE SUPPORT AT EACH END
OF HEAT EXCHANGER STACK.
REFER TO DETAIL
6 THIS SHEET
HEX
HEX
FILLET WELD PIPE TO
BLACK STEEL PLATE
1" DRYPACK
(TYP)
5"x
" ALLTHREAD (TYP)
FLOOR
2" OD PIPE
" BY 3" WEDGE ANCHOR OR
EQUAL TO SECURE BLACK
STEEL ANGLE CONNECTIONS.
4"x4"x1/4" BLACK STEEL PLATE
FOR 2" OD PIPE. 6"x6"1/4" BLACK
STEEL PLATE FOR 3-1/2" OD PIPE
NOTES:
1. SEE EXPANSION TANK SYSTEM
SCHEDULE FOR COMPONENT SIZES.
2. FOR HOT WATER SYSTEMS 50mm [2"]
AND SMALLER AND CHILLED WATER
SYSTEMS USE IN-LINE AIR PURGER
IN LIEU OF AIR SEPARATOR.
3. SET PRESSURE REDUCING VALVE SO
PRESSURE AT HIGHEST POINT IN
SYSTEM HAS A MINIMUM OF 28kPa [4
PSIG].
4. PROVIDE STRAINER IN AIR
SEPARATOR.
DRAIN
DRAIN
TO PUMP
SUCTION
NC
D
MV
PT
REDUCED PRESSURE ZONE
BACKFLOW PREVENTER
BLADDER
EXPANSION
TANK
150mm [6"]
HOUSE-
KEEPING PAD
FLOOR MOUNTING BASE RING
WITH DRAIN ACCESS OPENING
SHOWN. ANGLE IRON LEGS
MAY BE USED AS AN OPTION.
HANGER
RODS (TYP)
AIR SEPARATOR
SEE NOTES 1 & 2
BALL ISOLATION
VALVE
AUTO. AIR VENT TO DRAIN
CONNECTOR PIPE
RUN DRAIN LINE
TO NEAREST FS
3/4" COLD WATER FILL LINE.
AIR CHARGING
SHRAEDER VALVE
FROM SYSTEM
9"
MIN
CENTER MIRROR
ON LAV U.N.O.
HOT WATER SUPPLY & DRAIN
SHALL BE INSULATED OR
COVERED WITH A REMOVABLE
NON METALLIC BAFFLE WHEN
HOT WATER EXCEEDS 120°F.
6"
MAX
8"
MIN
17"
MIN
27"
MIN
29"
MIN
34"
MAX
40"
MAX
36" MIN
T O
P
O
F
S
E A
T
18"
TOILET
PAPER
DISPENSER
19"
36" MAX
12" MAX
42" MIN
33"-36"
18" MIN
39"-41"
39"-41"
DUAL HEIGHT ELECTRIC
WATER COOLER
36"
MAX
15" CLR
MIN
39"
MIN
BOTTLE FILLER
TEST PLUG
(TYP.)
THERMOMETER
(TYP.)
LPS STEAM
SUPPLY
HEAT
EXCHANGER
(TYP.)
RUN DRAIN LINE FROM RELIEF
VALVE TO NEAREST FLOOR
SINK. (TYP.)
N
D
E
N
S
A
Y
P
15mm [1/2"] CHECK
VALVE VACUUM
BREAKER (TYP.)
DDC TEMPERATURE
SENSORS (TYP.)
RELIEF VALVE
T
H
E
R
M
O
S
T
A
T
I
A
R
V
E
Y
P
IF INSTALLED
LOWER THAN
MAIN LPS LINE,
PROVIDE
ANOTHER
SCALE
POCKET/TRAP
HERE.
CONTROL VALVE
(TYP)
NOTES:
1. THE ABOVE DETAIL SHOWS REQUIRED PIPING FOR TWO 100% REDUNDANT HEAT EXCHANGERS IN PARALLEL.
2. PROVIDE SADDLE SUPPORTS AND LEGS OR HANGERS FOR HEAT EXCHANGER. MOUNTING HEIGHT SHALL BE ADJUSTED TO
FACILITATE GRAVITY RETURN OF STEAM CONDENSATE.
3. MAKE THE BYPASS THE SAME SIZE AS THE CONNECTIONS TO THE CONTROL VALVES.
4. CONTROL VALVES SHALL BE IN A 1/3 AND 2/3 SIZE ARRANGEMENT.
5. STACK HEAT EXCHANGERS VERTICALLY TO REDUCE FOOTPRINT IN MECHANICAL ROOM.
D
D m m
M
I N
T
Y P
H
W
R
L
P
L
A
S
H
S
C
A
C
K
E
T
T
Y
P
T
T
P
I
P
I
B
Y
P
A
S
S
R
E
F
T
T
N
C
DDC PRESSURE
SENSORS (TYP.)
REFER TO DETAILS ON THIS
SHEET FOR PUMP AND AIR
SEPARATOR DETAILS
CIRCULATION
PUMP
AIR SEPARATOR
LOW-POINT
1/4 TURN
DRAIN (TYP.)
1/4 TURN
BOILER DRAIN
VALVE WITH
BRASS CAP,
TYP.
H
W
S
PERIMETER
RADIANT PUMPS
UPPER LEVEL
RADIANT LOOP
LOWER LEVEL
RADIANT LOOP
LOWER LEVEL
REHEAT LOOP
UPPER LEVEL
REHEAT LOOP
VAV REHEAT
PUMPS
REHEAT
HWR
RADIANT
HWR
HEX
HEX
P
P
P
P
P
VIBRATION ISOLATION BASES
M0.03
SCALE: NTS
CONSTRUCTION DOCUMENTS
05/12/2022
EHRM TRAINING AND ADMIN
SPACE
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOURFRONT
D E S I G N I N C.
Office of
Construction and Facilities
Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e i g h t h i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t t h r e e i n c h e s o n e f o o t
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
921 NE 13TH ST.
OKLAHOMA CITY, OK 73104
of
VA259-16-D-0217
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
AZ
Owner
RD
Department of
Veterans Affairs
MECHANICAL DETAILS
M0.03
TERMINAL UNIT WATER COIL DETAIL
M0.03
SCALE: NTS
IN-LINE PUMP CONNECTIONS DETAIL
M0.03
SCALE: NTS
CEILING RADIANT PANEL PIPING DETAIL
M0.03
SCALE: NTS
DRY PACK AT WELDED PIPE STAND BASE DETAIL
M0.03
SCALE: NTS
DRY PACK AT WELDED PIPE STAND BASE DETAIL
M0.03
SCALE: NTS
AIR SEPARATOR/EXPANSION TANK DETAIL
M0.03
SCALE: NTS
ADA COUNTER LAVATORY MOUNTING DETAIL
M0.03
SCALE: NTS
ADA WATER CLOSET MOUNTING DETAIL
M0.03
SCALE: NTS
ADA DUAL HEIGHT DRINKING FOUNTAIN MOUNTING DETAIL
M0.03
SCALE: NTS
STEAM TO HOT WATER HEAT EXCHANGER DETAIL
M0.03
31 59
B
D
E F G
H
REMOVE EXISTING
SUPPLY DIFFUSERS
AND DUCTING
REMOVE EXISTING
EXHAUST GRILLES
AND DUCTING
REMOVE EXISTING
12"x12" EXHAUST
TO ROOF
REMOVE EXISTING EXHAUST
GRILLES AND DUCTING
REMOVE EXISTING EXHAUST
GRILLES AND DUCTING
REMOVE EXISTING
SUPPLY DIFFUSERS
AND DUCTING
REMOVE EXISTING SUPPLY
DIFFUSERS AND DUCTING
REMOVE EXISTING SUPPLY
DIFFUSERS AND DUCTING
REMOVE EXISTING
RETURN/TRANSFER GRILLES
(TYP OF 8)
REMOVE EXISTING
RETURN GRILLES
AND DUCTING
REMOVE EXISTING
SUPPLY DIFFUSERS
AND DUCTING
EXISTING SUPPLY
DIFFUERS AND
DUCTING TO REMAIN
MH3.00
EXISTING WALL RATING:
SMOKE RESISTIVE HAZARDOUS
ROOM ENCLOSURE
2 HOUR FIRE BARRIER
PROJECT LOCATION
TRUE
NORTH
N
E E
N
No. 20031
AOM
TN AN
SC
L I EN
DE
S S
R O
F E
P
LI O AN
NG
E
I
R
ALEX R.
ZIMMERMAN
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of
Veterans Affairsof
/1
/2
:2
:2
P
M
CONSTRUCTION DOCUMENTS
05/12/2022
LOWER LEVEL HVAC DEMOLITION
PLAN
MD1.00
EHRM TRAINING AND ADMIN
SPACE
AZRD
921 NE 13TH ST
OKLAHOMA CITY, OK 73104Owner
VA259-16-D-0217
32 59
1/4" = 1'-0"
LOWER LEVEL HVAC PLAN - DEMOLITION
• EQUIPMENT, DUCT, AND GRILLES, REGISTERS, AND
DIFFUSERS SHOWN IN GRAY ARE EXISTING AND TO
REMAIN.
GENERAL NOTES
KEY PLAN
B
D
E F G
H
REMOVE EXISTING SUPPLY
DIFFUSERS AND DUCTING
REMOVE EXISTING RETURN
DIFFUSERS AND DUCTING
REMOVE EXISTING
RETURN DUCT
REMOVE EXISTING SUPPLY
DIFFUSERS AND DUCTING
REMOVE EXISTING RETURN
DIFFUERS AND DUCTING
REMOVE EXISTING SUPPLY
DIFFUSERS AND DUCTING
REMOVE EXISTING AIR
HANDLING UNIT AND
HOUSEKEEPING PAD
REMOVE EXISTING
12"x12" EXHAUST TO
ROOF; REMOVE
EXISTING ROOFTOP
EXHAUST FAN
REMOVE EXISTING
RETURN GRILLE
REMOVE EXISTING
SUPPLY DUCT
AHU
(E)
MH3.00
EXISTING 60"X36" RELIEF
AIR LOUVER AND DUCT
FOR AHU TO REMAIN
EXISTING 48"X48" OUTSIDE
AIR LOUVER AND DUCT
FOR AHU TO REMAIN
EXISTING WALL RATING:
SMOKE RESISTIVE HAZARDOUS
ROOM ENCLOSURE
2 HOUR FIRE BARRIER
PROJECT LOCATION
TRUE
NORTH
N
E E
N
No. 20031
AOM
TN AN
SC
L I EN
DE
S S
R O
F E
P
LI O AN
NG
E
I
R
ALEX R.
ZIMMERMAN
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of
Veterans Affairsof
/1
/2
:2
:2
P
M
CONSTRUCTION DOCUMENTS
05/12/2022
UPPER LEVEL HVAC DEMOLITION PLAN
MD1.10
EHRM TRAINING AND ADMIN
SPACE
AZRD
921 NE 13TH ST
OKLAHOMA CITY, OK 73104Owner
VA259-16-D-0217
33 59
1/4" = 1'-0"
UPPER LEVEL HVAC PLAN - DEMOLITION
• EQUIPMENT, DUCT, AND GRILLES, REGISTERS, AND
DIFFUSERS SHOWN IN GRAY ARE EXISTING AND TO
REMAIN.
S
S
B
D
E F G
H
NEW 10"x10" RISER
TO EXHAUST FAN
ON ROOF
SD-1
100 CFM
SD-1
100 CFM
SD-1
100 CFM
"x
S /A
"ø
S /A
6"x6" S/A
"x
R /A
6"ø S/A
6"x6" R/A
RG-1
100 CFM
SD-1
100 CFM
"x
S /A
12"x8" R/A
RG-1
360 CFM
SD-1
100 CFM
SD-1
100 CFM
SD-1
100 CFM
SD-1
100 CFM
10"X10" S/A FROM
MECH. ROOM
12"x8" R/A
SD-1
80 CFM
SD-1
80 CFM
RG-1
360 CFM
RG-1
140 CFM
SD-1
140 CFM
SD-1
145 CFM
VAV
16"x10 R/A TO
MECH. ROOM
16"x10" R/A
18"x10" S/A
8" x8
R
/A
4" x6
S
/A
10"x8" E/A
12"x10" S/A
14"x10" R/A
6"x6" E/A 8"x6" E/A
6" x8
S
/A
8" x8
S
/A
6"x6" S/A
"x
8" S
/A
"x
8" S
/A
8" x8
R
/A
8" x8
8" x8
RG-1
270 CFM
SD-1
80 CFM
SD-1
80 CFM
SD-1
95 CFM
SD-1
95 CFM
5"ø S/A
SD-1
80 CFM
RG-1
360 CFM
SD-1
80 CFM
12"x8" R/A
SD-1
80 CFM
5"ø S/A
5"ø S/A
8"x6" R/A
SD-1
140 CFM
SD-1
145 CFM
SD-1
150 CFM
SD-1
150 CFM
RG-1
255 CFM
SD-1
150 CFM
SD-1
150 CFM
SD-1
90 CFM
RG-1
270 CFM
SD-1
90 CFM
SD-1
70 CFM
SD-1
160 CFM
EG-1
80 CFM
RG-1
145 CFM
EG-1
60 CFM
EG-1
60 CFM
RG-1
160 CFMEG-1
60 CFM
EG-1
60 CFM
SD-1
120 CFM
SD-1
120 CFM
SD-1
90 CFMRG-1
90 CFM
7"ø S/A
8"x10" S/A
6"ø S/A
8"x8" S/A
9" ø
S /A
9" ø
S /A
8" x8
R
/A
VAV
RG-1
145 CFM
SD-1
90 CFM
RG-1
145 CFMSD-1
90 CFM
SD-1
120 CFM
RG-1
145 CFM
RG-1
255 CFM
7"ø S/A
7"ø S/A
7"ø S/A
7"ø S/A
7"ø S/A
7"ø S/A
7"ø S/A
7"ø S/A
6"x4" E/A
DN
6"x4" E/A
U P
DN
UP
6"ø S/A
U P
6"ø S/A
6"ø S/A
MEETING ROOM
2MEETING ROOM
TOILET
TOILET
HAC
TOILET
TOILET
OFFICE
OA2
OPEN OFFICE
OA3
OPEN OFFICE
OA3
OFFICE
OA5
OPEN OFFICE
OA3
BREAK ROOM
OA1
STORAGE
STORAGE
8"x6" R/A
6"ø S/A
7"ø S/A
5"ø S/A 6"x6" R/A
6"x6" R/A
6"ø S/A
6"ø S/A
5"ø S/A
5"ø S/A
5"ø S/A
5"ø S/A
5"ø S/A
RG-1
170 CFM
6"ø S/A
6"ø S/A
DN
DN
D N
SD-1
100 CFM
6"ø S/A
6"ø S/A
8"x6" R/A
6"ø S/A
6"ø S/A
6"ø S/A
6"ø S/A
6"ø S/A
6"ø S/A
MH3.00
MH3.00
MH3.00
MH3.00
VAV
MH3.01 2
MH3.01
MH3.01
10"x8" R/A
"x
R /A
6"ø S/A
7"ø S/A
6"x8" S/A
10"x6" S/A
18"x10 S/A FROM
MECH. ROOM
8"x8" R/A
10"X10" R/A TO
MECH. ROOM
6"x4" E/A6"x4" E/A 6"x4" E/A 6"x4" E/A
8"x6" E/A 10"x10" E/A
6"x6" E/A
6"x4 E/A FROM
UPPER LEVEL
VAV
VAV
VAV
VAV
VAV
VAV
VAV
D N
"x
S /A
UP
6"ø S/A
D N
DN
D N
7"ø S/A
6"ø S/A
6"x6"
6"x6" R/A
6"x6" R/A
MH3.00
SMOKE
DAMPERS
STORAGE
OA4
SMOKE
DAMPER
6"ø S/A
EXISTING WALL RATING:
SMOKE RESISTIVE HAZARDOUS
ROOM ENCLOSURE
2 HOUR FIRE BARRIER
PROJECT LOCATION
TRUE
NORTH
N
E E
N
No. 20031
AOM
TN AN
SC
L I EN
DE
S S
R O
F E
P
LI O AN
NG
E
I
R
ALEX R.
ZIMMERMAN
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of
Veterans Affairsof
/1
/2
:2
:2
P
M
CONSTRUCTION DOCUMENTS
05/12/2022
LOWER LEVEL HVAC NEW PLAN
MH1.00
EHRM TRAINING AND ADMIN
SPACE
AZRD
921 NE 13TH ST
OKLAHOMA CITY, OK 73104Owner
VA259-16-D-0217
34 59
1/4" = 1'-0"
LOWER LEVEL HVAC PLAN - NEW
• INSTALL ALL NEW DUCTWORK AS HIGH AS POSSIBLE
TO STRUCTURE ABOVE. COORDINATE WITH ALL OTHER
TRADES PRIOR TO INSTALLATION.
• TAGS AND LABELS SHOWN ARE SPECIFIC TO THESE
PLANS. CONTRACTOR TO COORDINATE FINAL TAGS
AND LABELING REQUIREMENTS WITH THE OKLAHOMA
CITY VA COR.
• FIRECAULK ALL NEW DUCT AND PIPE PENETRATIONS
THROUGH NEW AND EXISTING WALLS.
GENERAL HVAC NOTES
• EQUIPMENT, DUCT, AND GRILLES, REGISTERS, AND
DIFFUSERS SHOWN IN GRAY ARE EXISTING AND TO
REMAIN.
S S
S S
B
D
E F G
H
NEW 10"x10" EXHAUST
RISER TO NEW ROOFTOP
EXHAUST FAN EF-1
SD-1
125 CFM
SD-1
125 CFM
SD-1
125 CFM
SD-1
125 CFM
SD-1
125 CFM
SD-1
125 CFM
SD-1
125 CFM
SD-1
125 CFM
RG-1
225 CFM
RG-1
225 CFM
SD-1
60 CFM
SD-1
105 CFM
SD-1
105 CFM
SD-1
110 CFM
SD-1
110 CFM
RG-1
195 CFM
SD-1
145 CFM
SD-1
145 CFM
SD-1
145 CFM
RG-1
490 CFM
SD-1
110 CFM
SD-1
110 CFM
SD-1
110 CFMRG-1
200 CFM
SD-1
110 CFM
RG-1
225 CFM
RG-1
225 CFM
RG-1
200 CFM
RG-1
195 CFM
10"x10" S/A
10"x10" R/A
10"x6" R/A
"x
S /A
"x
S /A
9" ø
S /A
6"x6" S/A
5"ø S/A
10"x6" R/A
"x
8" S
/A
8"ø S/A
8"x8" R/A 8"x8" R/A
10"x6" R/A
"x
6" R
/A
8"x8" R/A
"x
8" S
/A
8"ø S/A
8"x8"
5"ø
6"x6" S/A
9"ø S/A12"x8" S/A
VAV
CONNECT NEW
32"x12" RETURN
DUCT TO NEW AHU-1
RG-1
470 CFM
EG-1
100 CFM
8" ø
S /A
7"ø S/A
7"ø S/A
"x
8" S
/A
"x
R /A
12"x10" R/A
8"ø S/A
7"ø S/A 7"ø S/A
7"ø S/A
7"ø S/A
7"ø S/A
7"ø S/A
7"ø S/A
7"ø S/A
SD-1
65 CFM
SD-1
90 CFM
6" ø
S /A
6"x4" E/A
RG-1
210 CFM
16"x10" S/A
5"ø S/A
5"ø S/A
6"ø S/A
6"ø S/A
6"ø S/A6"ø S/A
RG-1
140 CFM
6"ø S/A
6"ø S/A
6"ø S/A
6"ø S/A
MEETING ROOM
MEETING ROOM
MEETING ROOM
MEETING ROOM
MECHANICAL
CORRIDOR
CO2
STAIRS
MH3.00
MH3.00
MH3.00
MH3.00
VAV
VAV
MH3.01 2
MH3.01
SD-1
120 CFM
6"ø S/A
RG-1
120 CFM
6"x6" R/A
7"ø S/A
SD-1
90 CFM
9" ø
S /A
16"x10" R/A
20"x10" R/A
22"x10" S/A
NEW AIR HANDLING
UNIT WITH NEW 4"
HOUSEKEEPING PAD
SD-2
170 CFM
SD-2
170 CFM
SD-2
170 CFM
6"ø S/A
12"x10" R/A
6"ø S/A
CONNECT NEW
32"x14" SUPPLY
DUCT TO NEW AHU-1
16"x10 R/A FROM
LOWER LEVEL
18"x10 S/A TO
LOWER LEVEL
30"x12" S/A
24"x10" R/A
"x
S /A
32"x14" S/A
6"x4 E/A TO
LOWER LEVEL
32"x12" R/A
10"X10" S/A TO
LOWER LEVEL
10"X10" R/A FROM
LOWER LEVEL
10"x10" R/A10"x10" S/A
VAV
VAV
VAV
17 VAV
VAV
AHU
6"ø6"ø
DN
UP
DN
10"x10" E/A TO
LOWER LEVEL
10"x10" E/A
MH3.00
CONNECT EXISTING
48"X48" OUTSIDE AIR
DUCT TO NEW AHU-1
CONNECT EXISTING
60"X36" RELIEF AIR
DUCT TO NEW AHU-1
SMOKE
DAMPERS
SMOKE
DAMPERS
SMOKE
DAMPERS
20"x10" R/A
"x
R
/A
ELECTRICAL ROOM
BREAK ROOM
OA1
EXISTING WALL RATING:
SMOKE RESISTIVE HAZARDOUS
ROOM ENCLOSURE
2 HOUR FIRE BARRIER
PROJECT LOCATION
TRUE
NORTH
N
E E
N
No. 20031
AOM
TN AN
SC
L I EN
DE
S S
R O
F E
P
LI O AN
NG
E
I
R
ALEX R.
ZIMMERMAN
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of
Veterans Affairsof
/1
/2
:2
:2
P
M
CONSTRUCTION DOCUMENTS
05/12/2022
UPPER LEVEL HVAC NEW PLAN
MH1.10
EHRM TRAINING AND ADMIN
SPACE
AZRD
921 NE 13TH ST
OKLAHOMA CITY, OK 73104Owner
VA259-16-D-0217
35 59
1/4" = 1'-0"
UPPER LEVEL HVAC PLAN - NEW
• INSTALL ALL NEW DUCTWORK AS HIGH AS POSSIBLE
TO STRUCTURE ABOVE. COORDINATE WITH ALL OTHER
TRADES PRIOR TO INSTALLATION.
• TAGS AND LABELS SHOWN ARE SPECIFIC TO THESE
PLANS. CONTRACTOR TO COORDINATE FINAL TAGS
AND LABELING REQUIREMENTS WITH THE OKLAHOMA
CITY VA COR.
• FIRECAULK ALL NEW DUCT AND PIPE PENETRATIONS
THROUGH NEW AND EXISTING WALLS.
GENERAL HVAC NOTES
• EQUIPMENT, DUCT, AND GRILLES, REGISTERS, AND
DIFFUSERS SHOWN IN GRAY ARE EXISTING AND TO
REMAIN.
B
D
E F G
H
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
VAV
VAV
2"⌀ PHWS FROM
UPPER LEVEL
3/4"⌀ HWS/HWR
TYP OF VAV
1 1/4"ø PHWS
1 1/4"ø PHWR
1/
4" ø
P H
W R
1/
4" ø
P H
W S
1 1/4"ø PHWR
1 1/4"ø PHWS
1 1/4"ø PHWR
1 1/4"ø PHWS
1/
4" ø
P H
W R
1/
4" ø
P H
W S
3/4"ø 3/4"ø
3/ 4" ø
3/ 4" ø
1" ø
1" ø
1 1/2"ø RHWR
1 1/2"ø RHWS1 1/2"ø RHWS
1 1/2"ø RHWR
1/
2" ø
R H
W R1
1/ 2" ø R
H W
S
1 1/2"ø RHWR
1 1/2"ø RHWS
1 1/2"ø RHWR
1 1/2"ø RHWS
3/ 4" ø3/ 4" ø
3/4"ø 3/4"ø
3/4"ø 3/4"ø
1/
4" ø
P H
W S
1/
4" ø
P H
W R
1 1/2"ø
3/4"ø
1/
2" ø
P H
W R
1/
2" ø
P H
W S
3/ 4" ø
1/ 2" ø P
H W
S
1/
2" ø
P H
W R
1/
2" ø
1/
2" ø
P H
W R
3/4"ø
3/4"ø
3/4"ø
1 1/2"ø
1 1/2"ø PHWR
3/4"ø
3/ 4" ø
1 1/2"ø PHWR
1 1/2"ø PHWS
1/
2" ø
P H
W S
1/
2" ø
P H
W R
3/ 4" ø
1/
2" ø
P H
W S
3/ 4" ø
1" ø
R H
W S
1" ø
R H
W R
1" ø
R H
W S
1" ø
R H
W R
3/ 4" ø
3/ 4" ø
3/4"⌀ HWS/HWR FLEX PIPE
TYP OF RAD
1 1/4"ø
1 1/4"ø PHWS
1 1/4"ø PHWR
1 1/2"ø RHWR
1 1/2"ø RHWS
T T
T
T
T
T
T
T
T
T
T
SEE UPPER LEVEL PLAN
FOR CONNECTIONS TO
VAV AND RADIANT PANELS
MEETING ROOM
MEETING ROOM
BREAK ROOM
OA1
OFFICE
OA2
CORRIDOR
CO1
TOILET
TOILET
TOILET
TOILET
HAC
OPEN OFFICE
OA3
OFFICE
OA5
OPEN OFFICE
OA3
STORAGE
STORAGE
MH3.00
MH3.00
MH3.00
MH3.00
VAV
MH3.01
MH3.01
MH3.01
1/
4" ø
P H
W R
1/
4" ø
P H
W S
2"⌀ PHWR TO
UPPER LEVEL
1-1/2"⌀ RHWR TO
UPPER LEVEL
1-1/2"⌀ RHWS FROM
UPPER LEVEL
VAV
VAV
VAV
VAV
VAV
VAV
VAV
1/
2" ø
R H
W S
1/
2" ø
R H
W R
3/4"ø
3/4"ø
3/4"ø3/4"ø
3/4"ø
3/4"ø
3/4"ø
3/4"ø3/4"ø
3/4"ø
3/4"ø
3/4"ø
3/4"ø
3/4"ø
MH3.00
STORAGE
OA4
COORDINATE
INSTALLATION WITH
DIV 27 CONTRACTOR
EXISTING WALL RATING:
SMOKE RESISTIVE HAZARDOUS
ROOM ENCLOSURE
2 HOUR FIRE BARRIER
PROJECT LOCATION
TRUE
NORTH
N
E E
N
No. 20031
AOM
TN AN
SC
L I EN
DE
S S
R O
F E
P
LI O AN
NG
E
I
R
ALEX R.
ZIMMERMAN
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of
Veterans Affairsof
/1
/2
:2
:4
P
M
CONSTRUCTION DOCUMENTS
05/12/2022
LOWER LEVEL HYDRONIC NEW PLAN
MP1.00
EHRM TRAINING AND ADMIN
SPACE
AZRD
921 NE 13TH ST
OKLAHOMA CITY, OK 73104Owner
VA259-16-D-0217
36 59
1/4" = 1'-0"
LOWER LEVEL HYDRONIC PLAN - NEW
• INSTALL ALL NEW STEAM, CONDENSATE, CHILLED
WATER, AND HYDRONIC HOT WATER PIPING AS HIGH
AS POSSIBLE TO STRUCTURE ABOVE. INSTALL BELOW
DUCT WHERE NEEDED FOR ACCESS TO THE PIPE.
COORDINATE WITH ALL OTHER TRADES PRIOR TO
INSTALLATION.
• TAGS AND LABELS SHOWN ARE SPECIFIC TO THESE
PLANS. CONTRACTOR TO COORDINATE FINAL TAGS
AND LABELING REQUIREMENTS WITH THE OKLAHOMA
CITY VA COR.
• PROVIDE DOUBLE ISOLATION VALVES ON ALL STEAM
SERVED EQUIPMENT.
• DOUBLE ISOLATION VALVES ON ALL END EQUIPMENT
REQUIRED.
• FIRECAULK ALL NEW DUCT AND PIPE PENETRATIONS
THROUGH NEW AND EXISTING WALLS.
GENERAL PIPING NOTES
• EQUIPMENT, DUCT, PIPING, AND GRILLES, REGISTERS,
AND DIFFUSERS SHOWN IN GRAY ARE EXISTING AND
TO REMAIN.
B
D
E F G
H
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
RAD
VAV
EXISTING
2-1/2"⌀ STM-LP
EXISTING 3/4"⌀
CDR-L
3/4"⌀ HWS/HWR
TYP OF VAV
1 1/2"ø PHWR 1 1/2"ø PHWS
1 1/4"ø RHWR
1 1/4"ø RHWS
3/4"ø
3/4"ø
1 1/2"ø PHWR
3/4"ø
3/4"ø
1 1/2"ø PHWS
1 1/2"ø PHWR
1/
2" ø
P H
W R
1/
2" ø
P H
W S
1 1/2"ø PHWS1 1/2"ø PHWS 1 1/2"ø PHWR
3/4"ø
3/4"ø3/4"ø
1 1/2"ø PHWR
3/4"ø
3/4"ø
3/4"ø
3/4"ø
1/
2" ø
P H
W S
3/ 4" ø
3/ 4" ø
3/4"ø
3/ 4" ø
1 1/4"ø RHWS 1 1/4"ø RHWR
3/4"ø
1 1/4"ø RHWR
1 1/4"ø RHWS
3/ 4" ø
3/ 4" ø
1 1/4"ø RHWR
1 1/4"ø RHWS
1/
4" ø
R H
W R
1/
4" ø
R H
W S
1 1/2"ø PHWS
3/ 4" ø
1 1/2"ø PHWR
1 1/2"ø PHWS
T
T T
TT
T T
RAD
RAD
RAD
1 1/2"ø PHWS
1 1/2"ø PHWR
1 1/2"ø PHWS
1 1/2"ø PHWR
3/4"ø
T
MH3.00
MH3.00
MH3.00
MH3.00
MEETING ROOM
MEETING ROOM
MEETING ROOM
MEETING ROOM
CORRIDOR
CO2
STAIRS
MECHANICAL
STORAGE
VAV
VAV
MH3.01 2
MH3.01
MH3.01
RAD
3/4"ø 3/4"ø
RAD
1-1/2"⌀ PHWS TO LOWER LEVEL
2-1/2"⌀ PHWS FROM PUMPS
1-1/2"⌀ PHWR FROM LOWER LEVEL
2-1/2" PHWR TO PUMPS
1-1/2"⌀ RHWR FROM LOWER
LEVEL AND PUMPS
1-1/2"⌀ RHWS TO LOWER
LEVEL AND PUMPS
1 1/2"ø
VAV
VAV
VAV
VAV
3/4"ø 1 1/4"ø RHWR
1 1/4"ø RHWS
3/ 4" ø
3/4"ø
3/ 4" ø
3/4"ø
VAV
3/ 4" ø
3/4"ø
1" ø
R H
W R
1" ø
R H
W S
3/4"ø3/4"ø
1" ø
R H
W S
1" ø
R H
W R 1
1/ 2" ø
1 1/4"ø1 1/4"ø
P
P
P
HEX
P
P
AHU
3/ 4" ø
3/4"ø
MH3.00
2 1/2"ø STM-LP
3/4"ø CDR-L
(E )2
/2
"ø C
H R
(E )2
/2
"ø C
H S
(E )3
/4 "ø
C D
R -L
(E )2
/2
"ø S
T M
-L P
COORDINATE
INSTALLATION WITH
DIV 27 CONTRACTOR
ELECTRICAL ROOM
EXISTING WALL RATING:
SMOKE RESISTIVE HAZARDOUS
ROOM ENCLOSURE
2 HOUR FIRE BARRIER
PROJECT LOCATION
TRUE
NORTH
N
E E
N
No. 20031
AOM
TN AN
SC
L I EN
DE
S S
R O
F E
P
LI O AN
NG
E
I
R
ALEX R.
ZIMMERMAN
SUMMIT FIRE CONSULTING
575 MINNEHAHA AVE WEST
ST. PAUL, MINNESOTA 55103
(612) 387-7050
ALBERTSON ENGINEERING, INC.
315 NORTH MAIN AVENUE, SUITE 200
SIOUX FALLS, SOUTH DAKOTA 57104
PH: (605) 274-0880
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA 57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COM
FOURFRONT
D E S I G N I N C.
Office of Construction and Facilities Management
Project Number
Building Number
Drawing Number
Dwg.
DrawnCheckedDate
Location
Project TitleDrawing Title
Approved: Project Director
ARCHITECTCONSULTANTS:
DateRevisions:
VA FORM 08-6231
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
Department of
Veterans Affairsof
/1
/2
:2
:4
P
M
CONSTRUCTION DOCUMENTS
05/12/2022
UPPER LEVEL HYDRONIC NEW PLAN
MP1.10
EHRM TRAINING AND ADMIN
SPACE
AZRD
921 NE 13TH ST
OKLAHOMA CITY, OK 73104Owner
VA259-16-D-0217
37 59
1/4" = 1'-0"
UPPER LEVEL HYDRONIC PLAN - NEW
• INSTALL ALL NEW STEAM, CONDENSATE, CHILLED
WATER, AND HYDRONIC HOT WATER PIPING AS HIGH
AS POSSIBLE TO STRUCTURE ABOVE. INSTALL BELOW
DUCT WHERE NEEDED FOR ACCESS TO THE PIPE.
COORDINATE WITH ALL OTHER TRADES PRIOR TO
INSTALLATION.
• TAGS AND LABELS SHOWN ARE SPECIFIC TO THESE
PLANS. CONTRACTOR TO COORDINATE FINAL TAGS
AND LABELING REQUIREMENTS WITH THE OKLAHOMA
CITY VA COR.
• PROVIDE DOUBLE ISOLATION VALVES ON ALL STEAM
SERVED EQUIPMENT.
• DOUBLE ISOLATION VALVES ON ALL END EQUIPMENT
REQUIRED.
• FIRECAULK ALL NEW DUCT AND PIPE PENETRATIONS
THROUGH NEW AND EXISTING WALLS.
• REFER TO 5/M0.03 FOR MECHANICAL ROOM HYDRONIC
PIPING DETAILS.
GENERAL PIPING NOTES
• EQUIPMENT, DUCT, PIPING, AND GRILLES, REGISTERS,
AND DIFFUSERS SHOWN IN GRAY ARE EXISTING AND
TO REMAIN.
F
F F
F
B
MH2.01
MH3.00
HEX
P
P
P
P
P
MH3.00
3/4"ø CDR-L
3/4"ø RHWR
3/4"ø RHWS
24"x10" R/A
9"ø S/A
24"x10" R/A
30"x12" S/A
32"x14" S/A
2 1/2"ø STM-LP
32"x12" R/A
6"ø S/A
AHU
12"x8" S/A
"ø
S /A
6"x6" R/A
8"ø S/A
"x
R /A
1" ø
R H
W R
1" ø
R H
W S
1 1/2"ø PHWS
1 1/2"ø PHWR
RG-1
SD-1
SD-1
6"ø S/A
1 1/4"ø RHWS
1 1/4"ø RHWR
1 1/4"ø RHWS
1 1/4"ø RHWR
1 1/2"ø PHWS
1 1/2"ø PHWR
10"x10" S/A DOWN
10"x10" RS/A DOWN
VAV
(E )2
/2
"ø C
H S
(E )2
/2
"ø C
H R
(E )2
/2
"ø S
T M
-L P
(E )3
/4 "ø
C D
R -L
SD-1 20"x10" S/A
RG-1
SD-1 10"x20" S/A DOWN
10"x20" R/A DOWN
12"x10" R/A
20"x10" R/A
22"x10" S/A
6"ø S/A
EXISTING RELIEF
AIR LOUVER
EXISTING OUTSIDE
AIR LOUVER
ELECTRICAL ROOM
ROOF LEVEL
121' - 0"
CEILING LEVEL
119' - 0"
BOTTOM OF TRUSS
119' - 8"
TOP OF ROOF
125' - 4 1/2"
B.O.S AT ADMIN
123' - 8"
TOS AT ADMIN
125' - 1"
MECH RM LEVEL
114' - 7"
RG-1
AHU
SD-1
6"x6" R/A
6"ø S/A
14"x32" S/A
"x
S /A
12"x30" S/A
12"x10" R/A
12"x12" R/A
8"ø S/A
ROOF LEVEL
121' - 0"
5 87
CEILING LEVEL
119' - 0"
BOTTOM OF TRUSS
119' - 8"
TOP OF ROOF
125' - 4 1/2"
B.O.S AT ADMIN
123' - 8"
TOS AT ADMIN
125' - 1"
MECH RM LEVEL
114' - 7"
SD-1
RG-1
SD-1
SD-1
AHU
VAV
6"ø S/A
"x
S /A
32"x14…