ATTACHMENT 3 - Specifications - Volume 3 - Reference Only.pdf

PDF 15 MB Posted

Attached to
Y1DA--Specialty Treatment Expansion (Minor) Construction - Tampa
Solicitation number
36C77623B0016
Issued by

About this file

This file is an attachment to a federal solicitation for construction services. The Department of Veterans Affairs Technology Acquisition Center Austin is seeking proposals to expand specialty treatment facilities at the Tampa VA Medical Center. Offerors must submit proposals by the date listed in the solicitation to be considered for award of a firm-fixed price construction contract. The selected contractor will be responsible for completing the specified construction work within 18 months of receiving the Notice to Proceed. This attachment provides reference specifications but does not include pricing, response date, or other solicitation details.

View the file

Other files

File Type Posted
Technical Questions - FINAL - Tampa 9-22-23.pdf PDF
2226 - ASI 1- Technical Clarifications - 08-31-23 - Part 1.pdf PDF
2226 - ASI 1- Technical Clarifications - 08-31-23 - Part 2.pdf PDF
0941.2300130.0000- AA-1 - 100% SUBMITTAL JAMES HALEY VETERANS HOSPITAL AA-1.pdf PDF
GEO_James_Haley_Veterans_Hospital_Heliport_-_AES.PDF PDF
Building 1- Life Safety Plans- 4-11-13 FOR REFERENCE ONLY - Part 1.pdf PDF
Building 1- Life Safety Plans- 4-11-13 FOR REFERENCE ONLY - Part 2.pdf PDF
36C77623B0016 0004.pdf PDF
James Haley Veterans Hospital - Record Drawings 2.pdf PDF
James Haley Veterans Hospital - Record Drawings 1.pdf PDF
ATTACHMENT 13 - Wage Rates - Hillsborough 9-15-23.pdf PDF
36C77623B0016 0003.pdf PDF
36C77623B0016 0002.pdf PDF
ATTACHMENT 13 - Wage Rates - Hillsborough 8-25-23.pdf PDF
Site Visit Sign-in Sheet - Tampa 8-15-23.pdf PDF
36C77623B0016 0001.pdf PDF
ATTACHMENT 14 - Contractor Safety - Environmental Form.docx DOCX document
ATTACHMENT 15 - Site Visit Instructions.pdf PDF
ATTACHMENT 13 - Wage Rates - Hillsborough 1-13-23.pdf PDF
ATTACHMENT 10 - Drawings - Part 7.pdf PDF
ATTACHMENT 1 - Specifications - Volume 1.pdf PDF
ATTACHMENT 5 - Drawings - Part 2.pdf PDF
36C77623B0016 - 8-7-23.pdf PDF
ATTACHMENT 8 - Drawings - Part 5.pdf PDF
ATTACHMENT 12 - Limitations on Subcontracting - Construction.docx DOCX document
ATTACHMENT 6 - Drawings - Part 3.pdf PDF
ATTACHMENT 11 - Drawings - Part 8.pdf PDF
ATTACHMENT 7 - Drawings - Part 4.pdf PDF
ATTACHMENT 4 - Drawings - Part 1.pdf PDF
ATTACHMENT 9 - Drawings - Part 6.pdf PDF
ATTACHMENT 2 - Specifications - Volume 2.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SPECIALTY TREATMENT EXPANSION PROJECT

JAMES A. HALEY VETERAN’S HOSPITAL

TAMPA, FLORIDA

VOLUME 3

FOR REFERENCE ONLY

OWNER PROVIDED MANUFACTURER'S

EQUIPMENT DRAWINGS & INFORMATION FOR

THE EQUIPMENT WITHIN THE SPECIALTY

TREATMENT EXPANSION

for

DEPARTMENT OF VETERANS AFFAIRS

VA Project Number 673-CSI-100

PHYSICAL AND ELECTRIC SECURITY UPDATE

August 19, 2022

115 East Forsyth St. • Jacksonville, Florida 32202 USA • (904)798-8333 • Fax (904)798-8335 www.ttvarch.com • Lic.#AA0002609 • info@ttvarch.com

VHACLECouncT Highlight

VOLUME 3

FOR REFERENCE ONLY

OWNER PROVIDED MANUFACTURER'S EQUIPMENT DRAWINGS & INFORMATION FOR THE

EQUIPMENT WITH SPECIALTY TREATMENT EXPANSION

-G.C. TO COORDINATE MANUFACTURER'S EQUIPMENT REQUIREMENTS & RECOMMENDATIONS W/

ALL DISCIPLINES.

-WHERE THERE IS A CONFLICT BETWEEN THE REFERENCED MANUFACTURER'S DOCUMENTS AND

ANY OTHER DISCIPLINES- CONSULT ARCHITECT FOR DIRECTION.

-THE GC IS RESPONSIBLE FOR THE SCOPE OF THE WORK LISTED IN THE CONTRACT

DOCUMENTS AND IN REFERENCED MANUFACTURER'S EQUIPMENT DOCUMENTS (EVEN IF THEY

ARE IN CONFLICT.)

TABLE OF CONTENTS

II. TRAVERSE PATIENT LIFTS- LIKORALL (HILL-ROM)

Contact- Erica Shukrie Direct: 305.333.3257

Customer Support: 800.445.2114 Email: Erica.Shukrie@hill-rom.com

III. EXAM LIGHTS- BURTON

www.burtonmedical.com

IV. ANGIO EQUIPMENT- GE HEALTHCARE (ATTACHED DRAWINGS)

Contact- Delgado, Jack (GE Healthcare)

Jack.Delgado@med.ge.com mailto:Erica.Shukrie@hill-rom.com http://www.burtonmedical.com/ VHACLECouncT Highlight

EXAM LIGHTS

BURTON

- i -

Installation, Operation, & Maintenance Instructions

VISIONARY® SURGERY LIGHT

This product was designed and manufactured in the U.S.A. by:

Burton Medical Products 21100 Lassen Street Chatsworth, CA 91311 U.S.A.

Questions?

Tel: (800) 444-9909

(818) 701-8700 Fax: (800) 765-1770

(818) 701-8725 www.burtonmedical.com

1019200 A04

JAMES A HALEY VETERAN'S HOSPITAL

SPECIALTY TREATMENT EXPANSION 673-CSI-100

BASIS OF DESIGN

tom Text Box

JAMES A HALEY VETERAN'S HOSPITAL

SPECIALTY TREATMENT EXPANSION

673-CSI-100

BASIS OF DESIGN

Burton Medical Products ii

The following Models are described in this Manual:

Model 0212040 (115v) Visionary®- Single Ceiling

Surgery Light

Model 0212050 (115v) Visionary®- Double Ceiling

Surgery Light

Models 0212040 and 0212050 incorporate slider dimmer controls mounted at the wall switch location to adjust lamp intensity.

This Manual contains detailed information on the above, but responsibility for effective installation ultimately rests with skilled and qualified contractors. Products should at all times be handled by qualified staff; it is the responsibility of the user to ensure this is the case.

JAMES A HALEY VETERAN'S HOSPITAL

SPECIALTY TREATMENT EXPANSION 673-CSI-100

Burton Medical Products iii

TABLE OF CONTENTS

Section Page

Specifications....................................................................................................................v

Technical Description .................................................................................................... vii

Terminology.................................................................................................................... ix

Symbols and Warnings ................................................................................................... xi

Installation Check List……………………………………………………………...….xiv

1.0 UNPACKING

2.0 INSTALLATION NOTES

3.0 MOUNTING AND CHECKOUT

3.1 Head and Arm Movement

3.2 Ceiling Mount Installation

3.3 Fitting & Adjustment of the Articulating Arm

3.4 Maximum Height Adjustment……………………………………23

3.5 Spot Focus……………………………………………………..…23

3.6 Electrical Checks ……………………………………………….23

4.0 OPERATION

4.1 Sterilization Protocol – Handle

4.2 Applying Power – the Dimmer and On-Off Switches

4.3 Maneuvering the Lighthead

5.0 SERVICE AND MAINTENANCE

5.1 Schedule

5.2 Changing Bulbs

5.3 General Cleaning, Hygiene and Disinfection

5.4 Adjusting Horizontal Friction

5.5 Adjusting Upper Limit of Spring Arm

5.6 Keeping the Optics Clean

5.7 Inspection and Replacement – Optical Filters

5.8 Adjusting the Reflectors

5.9 Adjusting Lighthead Rotating Friction

5.10 Adjusting Arm Tension

6.0 TROUBLESHOOTING GUIDE………………………………………………40

7.0 REPLACEMENT PARTS & ACCESSORIES

JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products iv

LIST OF FIGURES

No. Title Page

1 Range of Motion, Sgl. Ceiling Mt., Short Downtube

2 Range of Motion, Sgl. Ceiling Mt., Long Downtube

3 Range of Motion, Dbl. Ceiling Mt., Short Downtube

4 Range of Motion, Dbl. Ceiling Mt., Long Downtube

5 Seismic Engineering Drawing – Elevation

6 Seismic Engineering Drawing – Plan @ Ceiling

7 Ceiling Mount………………………………………………………… ...…13

8 Drilling Template for Ceiling Mount.. ………………………………….…14

9 Ceiling Mount Electrical Connections…………………………………… 15

10 Double Casing Installation…………………………………………………17

11 Horizontal Arm Friction Adjustments

12 Articulating Arm – Upper Limit Adjustments

13 Wall Plate Assembly

14 Schematic Diagram – Sgl. Ceiling Mount

15 Schematic Diagram – Dbl. Ceiling Mount

16 Access to Wiring – Bulb Voltage Measurements

17 Bulb Voltage vs. Input (Mains) Voltage

18 Spot Focus Adjustments

19 Articulating Arm Load Adjustments

JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products v

SPECIFICATIONS - VISIONARY® SURGICAL LUMINAIRES

General

The Visionary® is intended for use as a surgical light in hospital operating rooms, emergency rooms, trauma rooms, or outpatient clinics. It is available in single or double ceiling models and in two different downtube lengths for each model as designated below.

Model 0212040 Visionary® Single Ceiling Surgery light.

1019101 Single Ceiling Mount – Short Downtube, 15.5”.

1019102 Single Ceiling Mount – Long Downtube, 34.0”.

Model 0212050 Visionary® Double Ceiling Surgery light.

1019103 Double Ceiling Mount – Short Downtube, 15.5”.

1019104 Double Ceiling Mount – Long Downtube, 34.5”.

Power to the fixture is controlled from a wall switch panel, which contains a master power switch, dimmer, and fuses. Effective working distance between patient and lighthead is from 0.6 to 1.5 meters. A removable and autoclavable handle (which also serves as bulb-focus control) accepts pre-sterilized covers. Burton will make available to the purchaser or his representative, technical material, including circuit diagrams, parts lists, component descriptions, which will assist the user’s qualified personnel in repairing those parts of this equipment designated by Burton as repairable.

Classification

Type of protection against electric shock ......................................................Class 1 Allowable leakage current ...................................................does not exceed 200 µa Reliability of earth protection ............................................does not exceed 0.1 ohm Mode of operation................................................................................... Continuous Protection against explosion hazards ......................... not to be used in presence of flammable anesthetics Protection against hazardous parts and ingress of liquids ................................ IPX0 Degree of mobility ...................................Ceiling mounts are permanently installed Safety tests………………UL2601-1(60601-1), CAN/CSA C22.2 601.1 (60601-1)

Electrical

Supply connections (to transformer primary) ........................................115V/60 Hz Power consumption (Single all bulbs on)……………….…………….….175 watts Power consumption (Double all bulbs on)……………….…………….…350 watts Bulb types Description......................35 watts each, 24 volt, BA15d base, CC-8, halogen Life………………………………………………………...1000 hrs (35 watt) Fusing.…………………………………………….(2) @ 3 amps, wall switch plate

JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products vi

Environmental Conditions

Transport and Storage Ambient temperature ....................................................................0°C to 70°C Relative humidity............................................10% to 95% (no condensation) Atmospheric pressure........................................................ 500hPa to 1060hPa Operation Ambient temperature ..................................................................10°C to 30°C Relative humidity..........................................................................30% to 75% Atmospheric pressure....................................................... 700hPa to 1060 hPa

Weights and Dimensions

Single ceiling mount (short droptube) ................................................ 61 lbs (28 kg) Double ceiling mount (short droptube)............................................. 105 lbs (48 kg) Visionary® Lighthead with yoke........................................................ 20 lbs (9.1 kg) Lighthead diameter ..............................................................................19 in (48 cm) Effective swing radius from center mount.........................................65 in (165 cm) Lighthead vertical movement (depends on ceiling height)................47 in (118 cm) Lighthead rotation about yoke attachment.........................................................±95°

Optical Performance/Operating Characteristics

The optical data are nominal values based on measurements done according to the IEC 60601-2-41 standard based on bulb voltage of 26.4V. Please be aware that lights are very sensitive to voltage variations, and that this can affect the light performance and bulb life significantly. Also the performance of the individual bulbs has a natural variance due to their manufacturing process.

Central Illumination at 1-meter, Ec ......................................... 8300 fc (90,000 Lux) Light Field Diameter, d10 .................................................................8.1 in (206 mm) Light Field Diameter, d50 ...................................................................3.7 in (94 mm) Total Irradiance, Ee below IES recommendation................................... 36 mW/cm2 Illumination adjustment (dimmer) ............................................................ 0 to 100% Depth of field when focused at 1-meter......................greater than 39.4 in (1 meter) Color temperature (CCT).............................................................................. 4200°K CRI (Color Rendering Index) Focus range ………………………………………..30 in (76 cm) to 40 in (102 cm) Maximum housing temperature .........................................................143° F (61° C) Can be installed in ceilings ...............................from 8’6” (2.6 m) to 10’0” (3.1 m)∗ Rotation about the central ceiling axis (single mounts).................................Infinite Rotation about the extension arm outboard axis............................................Infinite Rotation about the central ceiling axis (dbl. mounts)………............Limited by mutual arm interference

Warranty Standard 5 years warranty on parts and labor.

∗ Consult factory for installations in ceilings lower than 8’6” (259cm) and higher then 10’ (305cm). JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products vii

TECHNICAL DESCRIPTION

A Single Ceiling Mount consists of one Visionary® lighthead (surgical luminaire) suspended from the end of a horizontal arm (extension arm) and vertically articulating arm. The arms are connected to a vertical tube (downtube) secured to the structural ceiling. All this is illustrated in the following figures. The lighthead can be positioned anywhere within the great circle defined by the combined length of the extension arm and articulating arm. Up and down movement is limited by the vertical range of the articulating arm. A Single Ceiling Mounted Visionary® does not have redundant wiring, and, therefore, a single fault in the primary or secondary circuits will cause the lamp to go out. Terminology used herein is the same as contained in the International Standard, IEC 60601-2-41, First Edition 2000-02. The common American term, Surgery Light, is synonymous with the European, Surgical Luminaire.

In similar fashion, the configuration of two lightheads mounted off a single downtube from a fixed point on the ceiling is called a Double Ceiling Mount. The horizontal motion of the lightheads on the Double is restricted because of mutual interference of the extension arms (with the downtube, and each other); however, the output from both lightheads can be focused on the same object within the great circle defined above.

When the two lightheads are mounted and the combined light energy directed at a single work area (surgical field), light intensity is essentially twice that of a single lighthead.

Because a “double” Ceiling Mounted Visionary® has two lightheads and redundant wiring, if one of the circuits opens, only one light goes out; the other remains on, and the total fixture can be classified as a fail safe Surgical Luminaire System (provided the illuminance from a single lighthead is more than 40,000 Lux at one meter). The IEC

60601-2-41 terms the Double Ceiling Mount models as a Surgical Luminaire System, or Major Surgical Luminaire, and has defined it as ‘failsafe’ in that one half the total intensity is remaining under single fault conditions.

Each lighthead contains four special bulb/reflector/filter assemblies. When the lighthead is located about 1-meter above the patient field, slight focus adjustments of the

JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products viii synchronized bulb pattern can be made by twisting the handle located asymmetrically off the bottom of the housing. This handle, which can be steam autoclaved, also is used to reposition the lighthead anywhere within its full Range of Motion. To remove the handle for sterilization, the operator must push a release rod, located above the handle flange, with a finger or thumb. To reinsert, all that is necessary is to push the handle over the guide rod until it ‘clicks’ into position. The handle also accepts commercial pre-sterilized covers, so it will not have to be removed for sterilization after each procedure.

Bulb changes are made from the front of the lighthead by removing the front window assembly. A small tool (Phillips screwdriver) is required for this. If the light was in use approximately 40 minutes are required for the light to cool down sufficiently for the windows and bulbs to be touched safely. The non-working bulb is then released from its socket by gently pushing, twisting and pulling it out. Disposal of the light bulb must be in accordance with local regulations.

JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products ix

TERMINOLOGY

(This terminology is quoted from

Standard IEC 60601-2-41, 2000-02)

SURGICAL LUMINAIRE SYSTEM

Combination of several SURGICAL LUMINAIRES to illuminate the body of the

PATIENT locally. It is FAIL SAFE and provides an adequate CENTRAL

ILLUMINANCE. It is intended to support the treatment and diagnosis, and to be used in operating rooms.

(Example: A proved fail-safe combination of two or more minor surgical luminaires is a

SURGICAL LUMINAIRE SYSTEM, or MAJOR SURGICAL LUMINAIRE.)

CENTRAL ILLUMINANCE

Illuminance at 1-meter distance from the light emitting area of the EQUIPMENT in the

LIGHT FIELD CENTER without any obstruction of the light beam.

LIGHT FIELD DIAMETER

Diameter of a circle around the LIGHT FIELD CENTER where the illuminance reaches

10% of the CENTRAL ILLUMINANCE.

LIGHT FIELD CENTRE (LFC)

Point of maximum illuminance in the light field (lighted area). It is the reference point for light field size and distribution measurements.

DEPTH OF ILLUMINATION

Working distance around 1 meter below the emitting surface of the EQUIPMENT, in which the illuminance reaches at least 20% of CENTRAL ILLUMINANCE.

SHADOW DILUTION (REDUCTION)

Ability of the EQUIPMENT to minimize the impact of shadows in the working area due to the partial obstruction by the OPERATOR of the emitted light.

Burton Medical Products x

FAIL SAFE

Capability of an EQUIPMENT to provide a minimum illuminance and to be directed on the operation area even in SINGLE FAULT CONDITION.

JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products xi

SYMBOLS & WARNINGS

SYMBOLS

Indicates that the applicable paragraphs of the Manual should be read.

Indicates a ‘ground’, or ‘earth’ connection, unprotected.

Indicates a protective ‘ground’ or ‘earth’ connection.

Indicates ‘alternating current’, i.e., ‘ac’.

WARNINGS

1. Safety precautions when working with the single or double ceiling mount.

• It is the responsibility of the customer to be in compliance with all applicable building codes and load requirements for this product above the ceiling.

• CAUTION: Before undertaking any work on the ceiling mount, ensure that the main power is off and secured from accidentally being switched on again.

• The ceiling mounts must only be installed by a technical expert (electrical engineer, technician) or a comparably qualified person.

• The 120-volt connection must only be made by an electrical engineer.

2. Safety precautions when working with the articulating arm.

• CAUTION: Before undertaking any work on the articulating arm, ensure that it has been disconnected from the main electrical supply!

Burton Medical Products xii

• Electrical connections, installation, removal and repairs should only be carried out by a qualified electrician.

• Do not remove safety caps (3) Figure 11 and (1) Figure 10 until the equipment is ready to assemble, and always ensure that the electrical supply is switched “OFF” until final assembly is completed.

• The articulating arm is tensioned by a spring. Always raise the arm (6) Figure 11 slowly to its upper limit before assembling or dismantling.

• It is recommend that installation of equipment on the articulating arm be carried out by two people.

3. Safety precautions when working with the lighthead.

• Both models are intended for installation on a 15-ampere branch circuit. All tests were performed on a circuit with that rating.

• When relamping the light, make sure that power to the bulb is off.

• Do not open the top for relamping. Change the bulbs by opening the windows at the bottom of the light.

• Avoid relamping when the fixture is hot. Wait approximately 40-minutes for it to cool.

• Replace bulbs with same type and rating. Do not exceed 35 watts per bulb.

Purchase bulbs from a Burton-authorized distributor.

• Do not touch the bulb’s glass envelope with bare hands, as oil from skin will cause premature failure. Use a tissue or Kimwipe®.

• Do not operate fixture with missing or damaged heat filters (coated glass filters are assembled to inside of windows).

• During normal operation do not touch any optical surfaces (glass filter, bulb, reflector). These surfaces are extremely hot and will burn tissue on contact.

• If a bulb burns out just prior to, or during a procedure, continue to use the fixture until a replacement can be made. But be aware that the added voltage, caused by the non-operating failed bulb, will eventually lead to premature burnout of the remaining bulbs.

• Disconnect power to the lamp circuit at the main breaker before replacing fuses.

Replace only with F3A/250V.

• Do not look directly at the light bulb when it is on.

Burton Medical Products xiii

• Do not operate the equipment if the front window assemblies are not retained securely in their respective openings, or if the wire tethers are defective or missing.

• Under normal conditions of use it is not necessary to open the housing from the top.

Normal maintenance items such as bulb replacements are made from the bottom after removing the front windows.

• Do not use the fixture if, for any reason, it does not appear to work properly.

Reasons can include inadequate light output, poor or loose movement, odd noises while moving the lighthead, apparent separation of mating components, etc. Instead, alert your Maintenance Department, or Burton, of observed deficiencies and have them corrected before returning the light to service.

4. Electromagnetic Compliance (EMC).

• It is important to install and use the equipment in accordance with the instructions, to prevent harmful interference to other devices in the vicinity. If this equipment does cause harmful interference to other devices, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

o Re-orient or relocate the other device(s).

o Increase the separation between the equipment.

o Use different electrical circuits for the conflicting devices.

o Consult with Burton or your field service technician for help.

Burton Medical Products xiv

INSTALLATION CHECK LIST

(2 pages)

SUPPORT STRUCTURE

� Support structure completed according to good structural engineering practices, and meets conditions of seismic drawings in manual.

� Adapter plate installed (or not).

� Ceiling Plate mounted with (4) 1/2-inch bolts, and plumbed (leveled). Note mounting recommendations for proper ceiling in the Manual.

� Junction box mounted on top of Ceiling Plate and 3/4-inch electrical conduit run to

Control Panel. Installation meets requirements for Class I, Div. I of the N.E.C.

� A total of (3) 12-18 AWG conductors run from Ceiling Plate to Control Panel. One of the conductors to be green or green/yellow, and shall be grounded to the Ceiling Plate. The other two can be black.

� Electrical connections completed in the above-ceiling junction box.

� Shroud (ceiling cover) installed.

EXTENSION ARM ASSEMBLY

� Retainer clip securely mounted.

� Slip ring is properly seated and connected.

� Elbow-cover in place and secured.

� Proper friction applied to both joints.

ARTICULATING ARM/LIGHTHEAD ASSEMBLY

� Retainer clip ring in place.

� Sleeve properly located and securing retainer clip � Sleeve is secured with screw.

CONTROL PANEL

� Box installed per user request and instructions in Manual.

� Mains wiring complete. Ground connections secure.

� Proper conductor AWG gages and secure connections throughout.

Burton Medical Products xv

INSTALLATION CHECK LIST (CONTINUED)

LIGHTHEAD/YOKE ASSEMBLY

� Lighthead mounted to articulating arm.

� Secondary voltage check.

� Power on, bulb voltage is 26.4v when dimmer control at maximum.

� Center focus handle installed.

� Bulbs remain illuminated and do not flicker when Lighthead/Yoke is moved throughout its range of motion. This includes swinging the lamp more than 360° in both directions about the vertical ceiling axis and the vertical articulating arm axis, moving the lamp up and down over its full range of travel, and twisting the lamp within the gimbled and caged suspension -- roll and pitch.

� Bulbs can be dimmed by moving the Control Panel Dimmer slider.

� When the Lighthead is placed at different distances above the work plane, the bulbs can be refocused by the Center Handle.

� Lamp movement is smooth throughout its total range of motion. The Lighthead remains where put without drifting.

MISCELLANEOUS

� Surfaces are clean.

� Current leakage and grounding tests ok.

(END)

Burton Medical Products xvi

Burton Medical Products

21100 LASSEN STREET, CHATSWORTH, CA. 91311

Telephone: (818) 701-8700 Fax: (818) 701-8725

January 9, 2004

IMPORTANT INSTALLATION ADVISORY

To: Installers and End Users of all domestic models of Visionary Surgery Lights

Re: Premature bulb burnout in Visionary

Premature bulb burnout may be the result of incorrect installation of your Visionary Surgery Light due to the applied bulb voltage being higher than 26.5 volts. The following are the steps to have your electrician take to verify that your Visionary Surgery Light was installed properly:

1) Verify your MAINS (Input) voltage.

2) If your MAINS (Input) voltage is in the range of 104V – 116V, then the Red and

Gray transformer secondary wiring (taps) should have been hooked up.

3) If your MAINS (Input) voltage is in the range of 117V – 124V, then the Red and

Yellow transformer secondary wiring (taps) should have been hooked up.

4) If your MAINS (Input) voltage is in the range of 125V – 134V, then the Red and

Orange wiring (taps) should have been hooked up.

This information can be found in the Visionary Installation, Operations and Maintenance Instructions on page 24 and 30 (Figure 17) that were provided with your light. For optimal performance of your light, please consult Figure 17 on page 30 of your Visionary Installation, Operations and Maintenance Instructions.

Sincerely, Wayne Okazaki Quality Assurance Manger

Burton Medical Products Corp. 1

1. UNPACKING

1.1 Unpacking and Inspection

The Visionary® Lighthead, arms, and ceiling mount(s) have been packaged to survive normal rigors of shipment. When unpacking the merchandise be sure to note loss or damage. If there is apparent loss or damage, but minimal damage to the shipping container itself, stop unpacking until you have contacted the carrier. In all cases of loss or damage, follow the instructions printed on the following page and do not throw away any cartons until told by Burton

Medical.

1.2 Special Instructions

Save the original shipping cartons until the fixtures are mounted and operational, and the customer is satisfied with the installation.

Burton Medical Products Corp. 2

Burton Medical Products Corp. 3

2. INSTALLATION NOTES

2.1 Range of Motion

Look at the diagrams showing RANGE OF MOTION (Figures 1 through 4) for the Visionary mounts (Single and Double Ceiling Mounts). It is the responsibility of the purchaser to inform Burton and the end user of installation details, including ceiling height, desired height of lighthead above the floor, location of mains power, etc., prior to purchase so there will be no misunderstandings regarding performance of the installed product. Before commencing work, the contractor/installer should review the RANGE OF MOTION diagrams with the customer and confirm the limits of travel.

2.2 Structural Requirements

The ceiling to which the lights are to be attached must be structurally sound, and suitably reinforced in order to support the light according to applicable codes

(esp. IBC 2000). Check the strength and stability of the mounting structure. It should provide for bracing which will prevent twisting or lateral motion of the light fixture. EQUIPMENT ANCHORAGE DIAGRAMS are supplied with these instructions to help with the installation (Figure 5 & 6). They were prepared by a

California-licensed Structural Engineer, and if the lights are installed accordingly, the systems will meet requirements of the State Seismic Codes.

2.3 Condition of Product

Each BURTON Visionary Light is shipped in two or more cartons. If there is obvious damage, or you suspect hidden damage incurred during shipment, follow the printed instructions in this manual under “UNPACKING”. Otherwise, remove all components for identification and check for completeness of the inventory. Report any missing items to your dealer or the factory at once.

2.4 Location of Components

Burton Medical Products Corp. 4

Included with the installation kit is a junction box containing the transformer, and a doublewide wall switch plate with dimmer control and fuses. The junction box should be mounted above the ceiling, preferably adjacent to the mount because the transformer must be accessed. The wiring run between transformer and lighthead should be kept as short as possible to minimize line losses. The wall plate should be substituted for an existing wall plate at a convenient location, and the wiring dedicated to the Visionary Surgery Light. Each lighthead must have its own dimmer wall plate assembly.

2.5 Installation

Follow the installation instructions in this manual and utilize the Checklist (page

xiv) while assembling the light to make certain that all steps are completed correctly.

2.6 Main Power Connection

In the special case of a Double Ceiling Mounted fixture, the mains power to both wall plates must originate from a single, switched power source so that one breaker switch at the central panel can disconnect power to the entire fixture.

2.7 Transformer Location

The junction box containing the transformer should be located conveniently so the transformer and wiring can be accessed or changed. To minimize line losses between the transformer and fixture, it is recommended that the transformer box be located above a ceiling panel near the fixture mount. Connecting wiring

(contractor-supplied) must be minimum AWG 16 from the transformer to the fixture. Wiring to the transformer must be minimum AWG 18. Wiring and conduit must meet local and national fire protection codes.

WARNING: Both models are intended for installation on a 15-ampere branch circuit.

Burton Medical Products Corp. 5

Burton Medical Products Corp. 9

Fig. 5

Burton Medical Products Corp. 10

Fig. 6

Burton Medical Products Corp. 11

3.0 MOUNTING AND CHECKOUT

3.1 Head and Arm Movement

The Ceiling Mount and Downtube must be securely mounted to the structural ceiling. Reference the Seismic and plan view drawings (Figures 5 and 6) showing bolt circle dimensions and swing radius of the lighthead(s). Make sure the downtube is located at a point on the ceiling that allows the lighthead to be positioned conveniently above the work area where there will not be interference between any of the moving parts and fixed objects, such as walls, cabinets, other fixtures, etc. The connection from the downtube to the structural ceiling support must be stiff so that there is no ‘sway’ to the loaded downtube, otherwise the lighthead will be difficult to position, and will drift. Also, the downtube itself must be ‘plumb’, i.e., perpendicular to the floor/ceiling. If it is not plumb, the horizontal extension arm always will drift so the lighthead swings lower to the floor.

3.2 Ceiling Mount installation (Single or Double)

3.2.1 Packing list, single ceiling mount: Ceiling plate with spacer tube, extension arm bearing and fixture flange.

3.2.2 Accessories required for installation:

3.2.2.1 Wrench (attached to the ceiling plate)

3.2.2.2 Sleeve with fastening component (pre-mounted on the extension arm bearing)

3.2.3 Packing list, double ceiling mount: Ceiling plate with spacer tube, extension arm bearing and fixture flange.

3.2.4 Accessories required for installation:

3.2.4.1 Wrench (attached to the ceiling plate)

3.2.4.2 Sleeve with fastening component (pre-mounted on the extension arm bearing)

Burton Medical Products Corp. 12

3.2.5 Installation of the single and double ceiling mounts as shown in Figure 7

(see the Symbols & Warning section for safety precautions).

3.2.5.1 It is recommended that a mounting plate meeting all structural and load requirements be provided at the ceiling level by the customer.

3.2.5.2 The template in Figure 8 can be used to drill the mounting hole pattern and electrical wiring access holes (1) in the ceiling plate as shown in Figure 7. Make sure that the connecting cable is positioned in the cut-out (1) for both plates. The four holes drilled must meet or exceed structural force specifications and meet the dimensional requirements for the fastening bolts.

3.2.5.3 Remove rubber bands at the fixture flange and slide it somewhat downwards.

3.2.5.4 Remove the wrench (3).

3.2.5.5 Insert the fastening bolts with the joint between the plates flush with the ceiling and if required, use washers for vertical alignment. If the down tube is not plumb and stable the arm will drift side-ways and the position of the lighthead will not be attainable.

3.2.5.6 Check the ceiling anchorage (2) for safe fit.

3.2.5.7 The downtube was sized at the factory for the ceiling specifications provided by the customer.

3.2.6 Electrical connection as shown in Figure 9.

3.2.6.1 WARNING – Turn the power off to the work area and secure it from accidentally being switched on.

3.2.6.2 Take the on-site connecting cable (1) through the cable fitting (2) and connect it to the terminal block in accordance with the terminal diagram as shown in Figure 9.

3.2.6.3 WARNING - Electrical surges: A ceiling anchorage that was not correctly grounded might cause electrical surges in the case of failure. Check the pre-mounted ground connection and connect on-site ground conductors.

Burton Medical Products Corp. 13

Figure 7

1- Cut-out for the on-site connecting cable

2- Ceiling plate (Anchorage)

3- Allen wrench 4- Shroud

JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products Corp. 14

NOT TO SCALE

Burton Medical Products Corp. 15

Figure 9

1- On-site connecting cable:

Single, 1 cable/AWG 16 for

UL

Double, 2 cables/AWG 16 for UL

2- Cable fitting 3- Terminal block 4- Connecting point for the pre-mounted internal ground conductor

5- Shroud 6- Screws (3)

JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products Corp. 16

3.2.6.4 Connect the on-site green ground conductor to the connecting point of the pre-mounted internal ground conductor (4).

3.2.6.5 The double ceiling mount has to be connected with two connecting cables (1).

3.2.6.6 Shift the Shroud (5) up-wards and tighten the three screws (6).

3.2.7 Installing the cover plates for the double ceiling mount per Figure 10.

3.2.7.1 The sleeves (1) containing the fastening components as shown in

Figure 10 for the further installation need to be stored.

3.2.7.2 Loosen the screws (2) and removed sleeves (1) from the double part extension arm bearing (3).

3.2.7.3 Unscrew the two recessed head screws (4) in the cover plates of the extension arm bearing (6).

3.2.7.4 Move the pre-mounted disks 1.890 in. (48mm) (5) diameter on the double part extension arm bearing (3) a little bit upwards.

3.2.7.5 Place the two halves of the cover plates (6) around the double part extension arm bearing (3) and stick them together at the lower end.

3.2.7.6 Lock the two halves of the cover plates (6) by carefully pressing them together at one of the sides at a time.

3.2.7.7 Screw the two halves of the cover plates (6) together with the two recessed head screws (4).

3.2.7.8 Check the cover plates of the extender arm bearing for safe fit.

3.2.7.9 Reattach the sleeves (1) to the extender arm bearings for protection only if the articulating arm installation will be delayed.

3.3 Fitting and adjustment of the articulating arm (see the Symbols &

Warning section for safety precautions)

Burton Medical Products Corp. 17

Figure 10

1- Sleeves (2) 2- Screws (2) 3- Double part extender arm bearing 4- Recessed head screws (2) 5- Pre-mounted disk (2) 6- Cover plates of extender arm bearing

JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products Corp. 18

3.3.1 Placing the articulating arm on the Single Ceiling Mount

3.3.1.1 Loosen the screws (2) shown in Figure 10 and removed sleeve (1) from the down tube. Keep the washer in place on the down tube.

3.3.1.2 Using a pair of retainer ring pliers remove the retainer ring and copper washer from the sleeve. Store the sleeve and chrome washer in a save place for future disassembly operations.

3.3.1.3 Remove the plastic joint cover over the slip ring connection on the extension arm and put aside for reuse when directed.

3.3.1.4 Remove the slip ring electrical connection from the extension arm and let it dangle on the cord.

3.3.1.5 With another person helping slip the extension arm on the shaft of the tube making sure that the washer is between the down tube and extension arm.

3.3.1.6 Place the copper washer over the shaft of the down tube.

3.3.1.7 Place the retainer ring with the help of the retainer ring pliers over the shaft of the down tube and make sure the ring snaps into and sits securely in the groove of the down tube shaft.

3.3.1.8 Reinsert the slip ring electrical connection into the articulating arm.

3.3.1.9 Separate the two halves of the plastic joint cover and place the cover over the down tube and extension arm joint by snapping them together.

3.3.1.10 Adjust the rotational friction with the adjustment screw. See

Figure 11.

3.3.1.11 Once the rotational friction is acceptable snap the plastic screw cover in place by pushing it into the screw head.

3.3.2 Placing the arm on the Double Ceiling Mount

WARNING - This is a very critical connection since the entire weight of the light and articulating arm are supported by this connection.

JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products Corp. 19

3.3.2.1 Loosen the screws (2) shown in Figure 10 and removed sleeve (1) from the down tube. Keep the washer in place on the down tube.

3.3.2.2 Using a pair of retainer ring pliers remove the retainer ring and copper washer from the sleeve. Store the sleeve and chrome washer in a save place for future disassembly operations.

3.3.2.3 Place the copper washer over the shaft of the down tube below the extension arm.

3.3.2.4 Remove the plastic cover plates over the slip ring connection on the extension arm and put aside for reuse when directed.

3.3.2.5 Remove the slip ring electrical connection from the extension arm and let it dangle on the cord.

3.3.2.6 With another person helping slip the extension arm on the shaft of the down tube making sure that the washers are between the down tube and extension arm.

3.3.2.7 Place the retainer ring with the help of the retainer ring pliers over the shaft of the down tube and make sure the ring snaps into and sits securely in the groove of the down tube shaft.

3.3.2.8 Reinsert the slip ring electrical connection into the extension arm.

3.3.2.9 Separate the two halves of the cover plates and place the cover over the down tube and extension arm joint by snapping them together.

3.3.2.10 Adjust the rotational friction with the adjustment screw. See

Figure 11.

3.3.2.11 Once the rotational friction is acceptable snap the plastic screw cover in place by pushing it into the screw head.

3.3.3 Installation of light head on the articulating arm (Figure 11).

3.3.3.1 CAUTION: Maximum height of the lower arm (6) should be in position B shown on diagram (= horizontal): check carefully. If necessary, adjust by placing Allen Key firmly home to Opening (5) (see diagram) and

WARNING - This is a very critical connection since the entire weight of the light and extension arm are supported by this connection.

JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products Corp. 20 turn fully to the right. This operation can only be done with the lighthead connected to the articulating arm.

3.3.3.2 Remove screw (2).

3.3.3.3 Lift the safety sleeve (1) slightly, twist to the right, and then pull right up.

3.3.3.4 Remove retainer clip (4).

3.3.3.5 Place spigot (12) of light head into socket (11) and replace the retainer clip (4).

3.3.3.6 Pull the safety sleeve (1) downward and re-fit screw (2).

3.3.4 Movement Adjustment (Figure 11)

3.3.4.1 The lower arm (6) of the articulating arm can be moved upwards and downwards.

3.3.4.2 The downward movement is restricted to a fixed limit Position C.

3.3.4.3 Upward movement can be adjusted as follows between Position A and B (Position B = Transit setting) shown on the diagram:

a. Push Allen key fully home into Opening (5) as illustrated.

b. To make upper limit higher: Turn Allen key to the left.

c. To make upper limit lower: Turn Allen key to the right.

3.3.4.4. Remove Allen key from the opening (5) and store safely in a suitable place for future use if required.

3.3.5 Adjustment of Load Counterbalance (Figure 11)

3.3.5.1 The carrying capacity should be adjusted for the light head.

If this is not done, the light head can either swing downwards

(weight capacity too low) or swing upwards (weight capacity too high).

3.3.5.2 To adjust the weight capacity counterbalance:

a. Push the Allen key fully into the Opening (7). As you turn, push the lower arm (6) to adjust above horizontal (Position B on the

Diagram). If necessary, adjust lower arm higher (see Movement

Adjustment 3.3.4.3 above). JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products Corp. 21

b. To increase weight capacity (light head (6) swings downwards too easily): Turn Allen key towards the left.

c. To decrease weight capacity (light head (6) swings upwards too easily): Turn Allen key towards the right.

CAUTION: Lighthead will sink downwards as the key is turned.

3.3.5.3 Remove Allen key from the opening (7) and store safely in a suitable place for future use if required.

3.3.6 Removing Equipment from the articulating arm (Figure 11).

3.3.6.1 CAUTION: The lower arm (6) must not rise higher than

Position B (= horizontal) shown on the diagram – check carefully.

If adjustment is necessary, follow the instructions for Movement

Adjustment above.

3.3.6.2 Remove screw (2).

3.3.6.3 Lift the safety sleeve (1) slightly, turn to the right, and then push right up.

3.3.6.4 Separating the equipment from the arm (6):

a. CAUTION: If the arm (6) is not positioned in Position B, when the equipment is removed, the arm will rise upwards very quickly. Make sure that there are no obstructions above the arm, and keep clear.

b. Hold firmly on to the light head.

c. Removed the retainer clip (4) and separate the light head from the arm. If necessary, turn the light head slightly to make this easier.

3.3.6.5 Replace safety cap (3).

3.3.6.6 Replace the retainer clip (4) lower the safety cover (1) and secure with screw (2).

JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products Corp. 22

Burton Medical Products Corp. 23

3.4 Maximum Height Adjustment

If the fixture is mounted to a ‘low’ ceiling, e.g., one where the articulating arm can’t be raised to its upper stop, the height of the lighthead above the floor will be limited by the vertical movement of the arm (it hits the ceiling). This situation is illustrated in the Range of Motion Diagrams for the 8’6” (259cm) ceiling example. However, movement of the arm can be adjusted so that it will be prevented from hitting the ceiling (see Figure 12). In the other example, 10’0”

(305cm) ceiling height, the articulating arm can be exercised to its full unrestricted height without hitting the ceiling, and vertical travel doesn’t have to be limited.

The lighthead can be positioned to any convenient height and angle by grasping the handle. It should be easy to do this using one hand. If there seems to be too little or too much resistance to movement, consult Section 5.0 and check the

Friction Adjustments instructions for both the lighthead and the arms.

3.5 Spot Focus

By twisting the handle slightly, the individual spots from each of the three outer high-intensity bulbs can be merged into a single spot in the center of the examination field. During initial setup (power not applied) the handle should be twisted gently to make sure the reflector pods respond properly. This can be verified by looking through the front windows at the reflectors and noting if they rock slightly as the handle is twisted.

3.6 Electrical Checks

Main power to each fixture is controlled by a dimmer mounted to a special doublewide wall switch plate (Fig. 13). This switch plate assembly, manufactured by Burton, contains the on-off switch, dimmer, and two fuses, and should be mounted at a convenient location (e.g., next to the door inside the operating room) where the dimmer can be adjusted by the operator. For a Double Ceiling mounted fixture, two complete switch plate assemblies are required and should be mounted adjacent to each other. They should share a common mains supply, i.e., a single breaker switch will shut off power to both switch plate assemblies at the same

JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products Corp. 24 time. Note that wiring to the wall box must contain hot, neutral, and ground leads. Wiring from the switch plate assembly is run (inside conduit) to the transformer junction box, where the appropriate connections are made (see schematic diagrams, Figures 14 and 15). Wiring from the transformer junction box (16AWG or larger) is run to the mount. To test the system after power is connected, make sure the main switch at the wall plate is turned OFF; load both fuses (3-amp) into the holders on the wall plate, and turn the dimmer to its

LOWEST power setting. Now, turn the main switch ON, and check the dimmer

LED indicators. Press the dimmer until the green LED line illuminates, showing that power is applied. The bulbs in the lighthead should be ON, although they might be dim. With full power applied (dimmer at full on), measured voltage at the secondary wires inside the Yoke cover (Figure 16) should not exceed 26.5v

ac. If it does, a different secondary tap from the transformer should be selected.

For inputs between 110 and 134 volts ac, secondary tap combinations of red/gray, red/yellow, or red/orange, should be selected so as to keep the applied bulb voltage between 25 and 26.5 volts at all times (reference Figure 17). For inputs less than 110 v ac, there will be corresponding loss of bulb voltage, and light intensity.

Burton Medical Products Corp. 25

Fig. 12

Small access hole with plastic cover

Insert Allen wrench through small access hole with cover, push on plastic cover and engage adjustment screw, turn it clockwise to lower the upper limit.

(Also see paragraph 5.5)

JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products Corp. 26

Fi g.

JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products Corp. 27

Burton Medical Products Corp. 28

Burton Medical Products Corp. 29

Fig. 16

Burton Medical Products Corp. 30

Fig. 17

Burton Medical Products Corp. 31

4.0 OPERATION

4.1 Sterilization Protocol – Handle

The Visionary® Handle assembly is extremely rugged and will withstand many, steam autoclave sterilization cycles without deterioration.

Wrap the handle assembly(s) per standard autoclave procedure.

Place the handle assembly(s) in the autoclave.

Set the autoclave cycle for 270°F (132°C), pre-vacuumed cycle.

Set the autoclave cycle time for 3-minutes, turn the sterilizer on, and wait for the process to be completed.

Remove the handle assembly(s) and place it (them) in use, or transport and store it (them) in a sterile environment pending use.

4.2 Applying Power – the Dimmer and On-Off Switches

The main power on-off switch is located on the wall plate. When it is turned on, a green pilot light in the rocker illuminates. The dimmer is next to the power switch. Push the large dimmer switch in and out and see if a line of green LED’s shows that output power from the dimmer to the lighthead is available. If not, there is a very small slider at the bottom of the dimmer used for disconnecting power (the ‘hot’ line only) so minor maintenance, such as bulb changes, can be performed safely. Moving the slider to the left disconnects the dimmer.

Slide it to the right (see Fig. 13). If the LED’s weren’t illuminated before, they should be on now, and all the bulbs in the lighthead should be on. A line of (7)

LED’s to the left of the dimmer lets the user know dimmer status at a glance.

When the dimmer is OFF, a single LED glows dimly to indicate the prior voltage level. When the dimmer is ON, the entire line of LED’s illuminates brightly to show that voltage is applied to the fixture. If some, but not all LED’s are brightly illuminated, this means that output voltage is limited. The setting can be changed by pressing and holding the top or bottom part of the rocker at the right of the switch. Press and hold it at the top end to increase intensity; press and hold it at the bottom end to decrease intensity. The line of green LED’s will provide visual

Burton Medical Products Corp. 32 cues for intensity. When they all are on, light intensity at the work surface should be at maximum. A bulb-saving feature of this dimmer can be observed when first turning the lighthead on. Note that the bulbs gradually, not instantaneously, turn on (‘soft start’). The reverse happens when the fixture is turned off. This single feature may increase bulb life dramatically – on the order of 2x.

Burton recommends that light intensity at the working surface be only as high as necessary to perform the procedure. Extremely high intensities present uncomfortable eye glare, as well as result in reduced bulb life and in thermal stresses on the equipment. When adjusting the dimmer for optimal intensity

(white – high color temperature – non-glare – easy viewing), gradually increase dimmer setting. The dimmer features a memory function, and if the fixture is turned off then restarted, power will automatically ramp up to the previous setting.

4.3 Maneuvering the Lighthead

If a procedure is to be performed which requires a sterile field, the Handle must be sterilized, and at no time during the procedure may any other part of the fixture be touched. The Visionary® arm system and Lighthead attachment were designed so the Lighthead could be positioned at any location within its Range of Motion using only the Handle. To verify this, grasp the Handle with one hand and, gently but firmly, maneuver the Lighthead so that the projected light will illuminate the subject from various angles.

Also, note that a slight twist of the Handle will adjust the beam pattern so that the individual light beams from the three high-power bulbs can be merged at the work surface.

Forces required to manipulate the Lighthead are modest; there should not be

‘hang-ups’ when moving the fixture. Also, once the Lighthead is positioned, it should not move, or ‘drift’ when released. Proper functioning is contingent upon proper installation; if the fixture is not ‘plumb’, it is not secured properly to the ceiling, the set-up adjustments have not been tested, or periodic maintenance has not been performed according to the schedule, maneuverability will be adversely

JAMES A HALEY VETERAN'S HOSPITAL

Burton Medical Products Corp. 33 affected.

After the procedure is completed, the Handle can be removed for cleaning and sterilization by pushing the plunger located between the Handle flange and housing with your thumb. The Handle will slide off its retaining shaft.

Burton Medical Products Corp. 34

5.0 SERVICE AND MAINTENANCE

5.1 Schedule

Task Table

After Each Procedure Every 1300 hrs Every 1800 hrs Clean/sterilize Handle Change all (4) bulbs, or change them as they fail

Clean optics

Clean/disinfect Lighthead Check & adj. horiz. friction Check & tighten ceiling bolts

Clean windows and front optics

Remove top lid, clean external parts

Reset switches and controls Check & adj. friction between lighthead and

Check & adjust vertical balance

Yoke shaft.

5.2 Changing Bulbs

All the bulbs are the same type (quartz-halogen 24v, 35w, with BA15D bases) and can only be purchased from Burton-authorized distributors (Part #0002000 pk.).

They are replaced from the front (bottom) of the Lighthead. Before changing bulbs, allow the fixture to cool (approximately 40-minutes). Under no circumstances should bulbs with different ratings or bases be substituted.

This is the start of the file's text. The full file is on GovTribe.