ATTACHMENT 3 - Drawings 2of2.pdf
PDF 14 MB Posted
- Solicitation number
- 36C77623B0039
About this file
This document contains details of a federal solicitation for construction services. The solicitation number 36C77623B0039 was issued by the Department of Veterans Affairs Technology Acquisition Center Austin for the Y1LZ--762-301 CMOP Building Acquisition Minor Construction project located in Tucson, Arizona. The opportunity is for the construction of a new parking lot on the agency's property, as described in the attached drawings. Responses to the solicitation are due based on the deadline provided in the solicitation documents. The award date and other contractual terms are also outlined therein.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
4"
1/4 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. 69321 EXP. 09/30/2022
MECH ENGR REG. NO. 69943 EXP. 12/31/2022
ELEC ENGR REG. NO. 70271 EXP. 12/31/2022
CIVIL ENGINEER
H2B, INC.
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FULLY SPRINKLERED
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
6/
:0 0:
P
M
RE XXALL
ISSUED FOR CONSTRUCTION
TUCSON CMOP BUILDING
ACQUISITION MINOR
03/14/2022
762-301
VA CMOP
3675 E. BRITANNIA DR.
TUCSON, ARIZONA, 85706
SPUR #: 22091.02
No. REVISION DESCRIPTION DATE
FENCE DETAILS
CS204
15 36 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. 69321 EXP. 09/30/2022
MECH ENGR REG. NO. 69943 EXP. 12/31/2022
ELEC ENGR REG. NO. 70271 EXP. 12/31/2022
CIVIL ENGINEER
H2B, INC.
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FULLY SPRINKLERED
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
6/
:0 0:
P
M
RE XXALL
ISSUED FOR CONSTRUCTION
TUCSON CMOP BUILDING
ACQUISITION MINOR
03/14/2022
762-301
VA CMOP
3675 E. BRITANNIA DR.
TUCSON, ARIZONA, 85706
SPUR #: 22091.02
No. REVISION DESCRIPTION DATE
GATE DETAILS
CS205
16 36
E BRITANNIA DR
E H
E M
IS
P
H E
R E
L O
O P
VISITOR PARKING
E DESERT WALK LN
CMOP
38'-6" 25'-0" 20'-6" 173'-6" 52'-0"
'-3
'-0
436'-10" FV
1'
-5
F V
2'
-4
F V
2.07
2.22
2.112.12
2.14
2.07
2.13
2.11
2.11
2.12
2.15
2.12
2.07
2.11
2.16
2.17
2.18
2.102.10
2.22
226'-11" FV
248'-6" FV
2.22
LANDSCAPED AREA
PAVED AREA
EXISTING BUILDING
EXTENTS TO BE DEMOLISHED
EXISTING FENCE
LANDSCAPED AREA TO BE DEMOLISHED
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
CERTIFICATE OF AUTHORITY NO. 20013-0
EXP. 09/30/2022
CIVIL ENGINEER
H2B, INC.
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:2 :3
P
M
DEMO ARCHITECTURAL SITE PLAN
ECO 17 36DRH
ISSUED FOR CONSTRUCTION
TUCSON CMOP BUILDING
ACQUISITION MINOR
03/14/2022
762-301
VA CMOP
3675 E. BRITANNIA DR.
TUCSON, ARIZONA, 85706
AS001
SPUR #: 2091.02
1" = 50'-0"
DEMO SITE PLAN1
DEMO SITE PLAN LEGEND
N
KEYNOTE LEGEND
2.07 DEMO EXISTING FENCE TO EXTENTS INDICATED
2.10 DEMO EXISTING LANDSCAPE AND PREPARE AREA FOR NEW CURBS AND PAVEMENT
2.11 EXISTING FIRE HYDRANT TO REMAIN
2.12 EXISTING MAN GATE TO REMAIN
2.13 EXISTING LIGHTING PEDESTAL TO REMAIN
2.14 EXISTING STANDPIPE TO REMAIN
2.15 EXISTING HVAC UNITS TO REMAIN
2.16 EXISTING CONEX / HVAC EQUIP. TO REMAIN
2.17 EXISTING UPS TO REMAIN
2.18 EXISTING GENERATOR TO REMAIN
2.22 DEMO EXISTING CHAIN LINK FENCE IN ITS ENTIRETY
No. REVISION DESCRIPTION DATE
E BRITANNIA DR
E H
E M
IS
P
H E
R E
L O
O P
DELIVERY/
LOGISTIC EXIT
E DESERT WALK LN
CMOP
DELIVERY
EXIT
DELIVERY/
LOGISTIC
ENTRY
EMPLOYEE
ENTRY / EXIT
EMPLOYEE
ENTRY / EXIT
ONE WAY EXIT ONLY
ONE
WAY
TRAFFIC
ONE WAY EXIT ONLY
'-4
'-0
130'-6" 17'-0" 39'-0" 38'-0" 128'-2" 4'-0" 9" 19'-4"
130'-6" FV 256'-11"
'-0
F
V
9' -3
F
V
2.0832.092.082.12
32.02 32.03
32.04
32.03 32.02
32.07 32.05
32.03 32.06
32.02 32.08
2.13
2.19
2.082.08
32.02
32.07
2.12
2.15
32.11
2.12
2.16
2.17
2.18 32.1132.1132.11
32.07
2.202.20
26.01
92'-0" 89'-4"
2'-0" 20'-0"
21 21 21 21
81010
910 10
19 22
7'-0" 20'-0"
6"
'-0
1'-6" 32'-0"
'-0
'-0
'-1
'-4
'-4
'-1
0"
0' -6
'-2
'-9
29'-5" 85'-0" 85'-0"
45'-10" 7'-5" 84'-7" 28'-2" 85'-4"
278'-6" FV
5'
-2
F V
428'-6" FV
24'-0" FV 206'-0" FV 29'-0" FV
'-1
0"
'-5
8"8'-8"8'-0"6'-0"8'-0"6'-0"
E4
E4
E4
E4
E4
E2
E1
E2
E1
E1
32.10
32.10
32.10
32.10 32.10
32.10
8"
2.12
E3
E5
E3 E5
E3E5
E3 E5
E3 E5 32.03
2.11
2.11
2.12
2.11
370'-0" FV
3'-6"
'-8
'-8
36'-0"
'-1
0"
63'-6"
2.19
246'-4" 10'-8"
32.02
32.02
32.05
EXISTING LANDSCAPED AREA
FENCING
PAVED AREA
ANTI-RAM BOLLARDS
EXISTING BUILDING
NEW LANDSCAPED AREA
EXTERIOR SIGNAGE
REF. SIGN TYPES (4/AS002)
E1
EXISTING LIGHT FIXTURE
LIGHT FIXTURE REF. ELECTRICAL
1. ARM EACH EXISTING AND FUTURE PEDESTRIAN GATE WITH AN ELECTRIC STRIKE (WITH
COVER PLATE), DUAL-AUTHENTICATION PIV & PIN CODE PACS, AUTO-CLOSER, AND CONTACT
SENSOR WITH ANTI-PROP ALARM, AND FIXED FACIAL ANALYTICS CAMERA, ALL MONITORED BY
THE SCC AND A LOCALIZED STATION WITHIN THE CMOP (I.E., ADMINISTRATION DESK OR CMOP
MANAGER). ENSURE THE FACIAL ANALYTICS CAMERAS ARE TIED TO THE VA EMPLOYEE
DATABASE FOR CONFIRMATION, AS TO PREVENT UNAUTHORIZED/FORCE CREDENTIAL USAGE
OR TAILGATING. REFER ELECTRICAL.
2. INSTALL PEDESTRIAN GATES AT EACH VEHICLE GATE, ENSURING THE PEDESTRIAN GATES
ARE CONSTRUCTED OF THE SAME MATERIAL AS THE FENCE SYSTEM, AND ARMED AS
DETAILED IN ITEM 1 ABOVE. ARM EACH PEDESTRIAN GATE WITH AN ELECTRIC STRIKE (WITH
COVER PLATE), DUAL-AUTHENTICATION PIV & PIN CODE PACS, AUTO-CLOSER, AND CONTACT
SENSOR WITH ANTI-PROP ALARM, ALL MONITORED BY THE SCC AND A LOCALIZED STATION
WITHIN THE CMOP (I.E., ADMINISTRATION DESK OR CMOP MANAGER). ADDITIONALLY, ENSURE
A FIXED FACIAL ANALYTICS CAMERA IS INSTALLED AT THE GATE ENTRY, TIED TO THE VA
EMPLOYEE DATABASE FOR CONFIRMATION, AS TO PREVENT UNAUTHORIZED/FORCE
CREDENTIAL USAGE OR TAILGATING. REFER ELECTRICAL.
3. BOLLARD SPACING IS 4" O.C. TYP.
GENERAL PLAN NOTES
PARKING
ONLY
2' -6
2'-0"
1' -6
1'-0"
VA SIGN: EN-10.06 VA SIGN: EN-10.06
VA SIGN: PL-12.04
2' -6
2'-0"
SIGN TYPE: E1 SIGN TYPE: E2
SIGN TYPE: E4
1"
1/ 4"
1/
2" 3/
4"
1/ 2"
1"
NO FIREARMS
VA SIGN: IN-02.11
2' -6
2'-0"
SIGN TYPE: E3
OR WEAPONS
ALLOWED ON
THIS PROPERTY
18 USC § 930
NOTICE
2" 1"
2" 2"
2"
1/ 2"
1" 6"
1'-2"
SIGN TYPE: E5
VIDEO
SURVEILLANCE
IN USE ON
THESE PREMISES
NOTICE
VIDEO SURVEILLANCE SIGN
R E
F . S
IG
N
E
LE
V A
T
IO
N S
S
IZ
E V
A R
IE
S
H E
IG
H
T V
A R
IE
S
. R E
F . S
IG
N
E
LE
V A
T
IO
N S
2' -6
1'-6"
3.01
5.29
5.30
1' -6
4'
-6
PARKING
ONLY
2' -6
7'
-0
6' -0
9' -6
EN-10.06
(SINGLE POST)
PL-12.04
(SINGLE POST)
NO FIREARMS
OR WEAPONS
ALLOWED ON
THIS PROPERTY
18 USC § 930
NOTICE
5' -6
IN-02.11
(WALL MOUNTED)
VIDEO
SURVEILLANCE
IN USE ON
THESE PREMISES
NOTICE
VIDEO SURVEILLANCE SIGN
(WALL MOUNTED)
5' -6 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
CERTIFICATE OF AUTHORITY NO. 20013-0
EXP. 09/30/2022
CIVIL ENGINEER
H2B, INC.
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:5 :1
A
M
ARCHITECTURAL SITE PLAN
ECO 18 36DRH
ISSUED FOR CONSTRUCTION
TUCSON CMOP BUILDING
ACQUISITION MINOR
03/14/2022
762-301
VA CMOP
3675 E. BRITANNIA DR.
TUCSON, ARIZONA, 85706
AS002
SPUR #: 2091.02
1" = 50'-0"
SITE PLAN1
SITE PLAN LEGEND
N
KEYNOTE LEGEND
5.30 1/8" ALUMINUM PANEL WITH SURFACE APPLIED REFLECTIVE VINYL. REF. SIGN TYPES
26.01 LIGHT FIXTURE, TYP. REF. ELECTRICAL
32.02 NEW FENCE TO MATCH EXISTING
32.03 GATE CONTROL ISLAND
32.04 ANTI-RAM BARRIERS ASTM F2656 M10
32.05 RETRACTABLE ANTI-RAM SYSTEM ASTM F2656 M30
32.06 NEW PEDESTRIAN GATE
32.07 30' SLIDING GATE AND TRACK
32.08 40' SLIDING GATE AND TRACK
32.09 50' SLIDING GATE AND TRACK
32.10 PAVEMENT MARKINGS
32.11 ANTI-RAM BARRIERS ASTM F2656 M30
KEYNOTE LEGEND
2.08 EXISTING FENCE TO REMAIN
2.11 EXISTING FIRE HYDRANT TO REMAIN
2.12 EXISTING MAN GATE TO REMAIN
2.13 EXISTING LIGHTING PEDESTAL TO REMAIN
2.15 EXISTING HVAC UNITS TO REMAIN
2.16 EXISTING CONEX / HVAC EQUIP. TO REMAIN
2.17 EXISTING UPS TO REMAIN
2.18 EXISTING GENERATOR TO REMAIN
2.19 EXISTING SLIDING GATE TO REMAIN
2.20 EXISTING PARKING AND ISLANDS TO REMAIN
3.01 CONCRETE FOOTING
5.29 3" X 3" STEEL POST
1 1/2" = 1'-0"
SIGN TYPES4
1" = 1'-0"
TYP. SINGLE POST DETAIL21" = 1'-0"
SIGN ELEVATIONS3
No. REVISION DESCRIPTION DATE
1 ADDENDUM 01 05/20/2022
The information on this document is preliminary or incomplete, not for construction, recording urposes, or implementation.
1. ARM EACH EXISTING AND FUTURE PEDESTRIAN GATE WITH AN ELECTRIC STRIKE (WITH
COVER PLATE), DUAL-AUTHENTICATION PIV & PIN CODE PACS, AUTO-CLOSER, AND CONTACT
SENSOR WITH ANTI-PROP ALARM, AND FIXED FACIAL ANALYTICS CAMERA, ALL MONITORED BY
THE SCC AND A LOCALIZED STATION WITHIN THE CMOP (I.E., ADMINISTRATION DESK OR CMOP
MANAGER). ENSURE THE FACIAL ANALYTICS CAMERAS ARE TIED TO THE VA EMPLOYEE
DATABASE FOR CONFIRMATION, AS TO PREVENT UNAUTHORIZED/FORCE CREDENTIAL USAGE
OR TAILGATING. REFER ELECTRICAL.
2. INSTALL PEDESTRIAN GATES AT EACH VEHICLE GATE, ENSURING THE PEDESTRIAN GATES
ARE CONSTRUCTED OF THE SAME MATERIAL AS THE FENCE SYSTEM, AND ARMED AS
DETAILED IN ITEM 1 ABOVE. ARM EACH PEDESTRIAN GATE WITH AN ELECTRIC STRIKE (WITH
COVER PLATE), DUAL-AUTHENTICATION PIV & PIN CODE PACS, AUTO-CLOSER, AND CONTACT
SENSOR WITH ANTI-PROP ALARM, ALL MONITORED BY THE SCC AND A LOCALIZED STATION
WITHIN THE CMOP (I.E., ADMINISTRATION DESK OR CMOP MANAGER). ADDITIONALLY, ENSURE
A FIXED FACIAL ANALYTICS CAMERA IS INSTALLED AT THE GATE ENTRY, TIED TO THE VA
EMPLOYEE DATABASE FOR CONFIRMATION, AS TO PREVENT UNAUTHORIZED/FORCE
CREDENTIAL USAGE OR TAILGATING. REFER ELECTRICAL.
3. BOLLARD SPACING IS 4" O.C. TYP.
GENERAL PLAN NOTES
EXISTING LANDSCAPED AREA
FENCING
PAVED AREA
EXISTING BUILDING
NEW LANDSCAPED AREA
FUTURE BUILDING
LIGHT FIXTURE REF. ELECTRICAL
E BRITANNIA DR
E H
E M
IS
P
H E
R E
L O
O P
DELIVERY/
LOGISTIC EXIT
E DESERT WALK LN
CMOP
DELIVERY
EXIT
DELIVERY/
LOGISTIC
ENTRY
EMPLOYEE
ENTRY / EXIT
EMPLOYEE
ENTRY / EXIT
ONE WAY EXIT ONLY
ONE
WAY
TRAFFIC
ONE WAY EXIT ONLY
'-4
'-0
1'
-6
F V
2.0832.092.082.12
32.03 32.02
32.04
32.03 32.02
32.07
32.05
32.03 32.06
32.02
32.08
2.13
32.12
2.08
32.02
32.07
2.12
2.15
32.11
2.12
2.16
2.17
2.18 32.1132.1132.11
32.07
26.04
FUTURE BLDG
STORAGE / ADMIN
DELIVERY
ENTRY
9'
-2
107'-4"
92'-0" 89'-4"
21 21 21 21
81010
910 10
'-0
7'-0" 20'-0" 1'-6" 32'-0"
'-0
'-1
'-1
1"
'-1 0"
'-8
6' -1
0"
'-0
113'-6"68'-5" 99'-7" 7'-5" 84'-7"
5'
-2
F V
85'-0" 85'-0" 85'-0" 57'-7"
357'-0"
'-1
0"
'-0
'-0
3'
-4
9"4'-0"
32.06
32.03 32.13
4'-0" 4'-6"
'-1
0"
32.12
32.13
370'-0" FV
32.13
26.04
26.04
26.04
26.04
26.04
26.04
32.02
32.02
32.05 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
CERTIFICATE OF AUTHORITY NO. 20013-0
EXP. 09/30/2022
CIVIL ENGINEER
H2B, INC.
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/2
/2
:5 :2
A
M
FUTURE ARCHITECTURAL SITE PLAN
ECO 19 36DRH
ISSUED FOR CONSTRUCTION
TUCSON CMOP BUILDING
ACQUISITION MINOR
03/14/2022
762-301
VA CMOP
3675 E. BRITANNIA DR.
TUCSON, ARIZONA, 85706
AS003
SPUR #: 2091.02
N
SITE PLAN LEGEND
1" = 50'-0"
FUTURE SITE PLAN1
KEYNOTE LEGEND
2.08 EXISTING FENCE TO REMAIN
2.12 EXISTING MAN GATE TO REMAIN
2.13 EXISTING LIGHTING PEDESTAL TO REMAIN
2.15 EXISTING HVAC UNITS TO REMAIN
2.16 EXISTING CONEX / HVAC EQUIP. TO REMAIN
2.17 EXISTING UPS TO REMAIN
2.18 EXISTING GENERATOR TO REMAIN
26.04 FUTURE LIGHT FIXTURE, TYP. REF. ELECTRICAL. OUT OF SCOPE
32.02 NEW FENCE TO MATCH EXISTING
32.03 GATE CONTROL ISLAND
32.04 ANTI-RAM BARRIERS ASTM F2656 M10
32.05 RETRACTABLE ANTI-RAM SYSTEM ASTM F2656 M30
32.06 NEW PEDESTRIAN GATE
32.07 30' SLIDING GATE AND TRACK
32.08 40' SLIDING GATE AND TRACK
32.09 50' SLIDING GATE AND TRACK
32.11 ANTI-RAM BARRIERS ASTM F2656 M30
32.12 FUTURE SLIDING GATE AND TRACK, OUT OF SCOPE
32.13 FUTURE FENCE TO MATCH EXISTING, OUT OF SCOPE
FOR REFERENCE ONLY
No. REVISION DESCRIPTION DATE
1 ADDENDUM 01 05/20/2022
The information on this document is preliminary or incomplete, not for urposes, or implementation.
H AI - Zone Humidity
BI - Filter Status
Elec
BO - Heating Stage 1
HP
BO - Compressor Stage 1
BO - Compressor Stage 2
BO - Reversing Valve
BI - Smoke Detector
T
AI - Discharge Air Temp
BO - Fan Start/Stop
CT
BI - Fan Status
BI - Zone Override
AI - Zone Setpoint Adjust
M
M AO - Return Air Dampers
OA
RA
N.O.
N.O.
SA
T
AI - Zone Temp
M
SEQUENCE OF OPERATIONS
HEAT PUMP (HP - TYP 18)
Run Conditions - Adminstration Areas - Scheduled:
The unit shall run according to a user definable time schedule in the following modes:
• Occupied Mode: The unit shall maintain
• A 75°F (adj.) cooling setpoint
• A 70°F (adj.) heating setpoint.
• Unoccupied Mode (night setback): The unit shall maintain
• A 85°F (adj.) cooling setpoint.
• A 55°F (adj.) heating setpoint.
Run Conditions - Pharmaceutical Areas - Scheduled:
• Occupied Mode: The unit shall maintain
• A 75°F (adj.) cooling setpoint
• A 70°F (adj.) heating setpoint.
• Unoccupied Mode (night setback): The unit shall maintain
• A 75°F (adj.) cooling setpoint.
• A 70°F (adj.) heating setpoint.
Discharge Air Temperature:
The controller shall monitor the discharge air temperature.
Alarms shall be provided as follows:
• High Discharge Air Temp: If the discharge air temperature is greater than 120°F (adj.).
• Low Discharge Air Temp: If the discharge air temperature is less than 40°F (adj.).
Fan Status:
The controller shall monitor the fan status.
Alarms shall be provided as follows:
• Fan Failure: Commanded on, but the status is off.
• Fan in Hand: Commanded off, but the status is on.
• Fan Runtime Exceeded: Fan status runtime exceeds a user definable limit (adj.).
Zone Humidity:
The controller shall monitor the zone humidity.
Alarms shall be provided as follows:
• High Zone Humidity: If the zone humidity is greater than
65% (adj.).
• Low Zone Humidity: If the zone humidity is less than 25% (adj.).
Emergency Shutdown:
The unit shall shut down and generate an alarm upon receiving an emergency shutdown signal.
Smoke Detection:
The unit shall shut down and generate an alarm upon receiving a smoke detector status.
Fan:
The fan shall run anytime the unit is commanded to run, unless shutdown on safeties.
Heating and Cooling - 2 Compressor Stages:
The controller shall measure the zone temperature and stage the compressors to maintain its setpoint. To prevent short cycling, there shall be a user definable (adj.)
delay between stages, and each stage shall have a user definable (adj.) minimum runtime. The compressor shall run subject to its own internal safeties and controls.
The heating shall be enabled whenever:
• Outside air temperature is less than 65°F (adj.).
• AND the fan status is on.
• AND the reversing valve is in heat mode.
The cooling shall be enabled whenever:
• Outside air temperature is greater than 60°F (adj.).
• AND the fan status is on.
• AND the reversing valve is in cool mode.
On mode change, the compressor shall be disabled and remain off until after the reversing valve has changed position.
Alarms shall be provided as follows:
• Compressor 1 Runtime Exceeded: Compressor 1 runtime exceeds a user definable limit (adj.).
• Compressor 2 Runtime Exceeded: Compressor 2 runtime exceeds a user definable limit (adj.).
Demand Limiting - Zone Setpoint Optimization:
To lower power consumption, the zone setpoints shall automatically relax when the facility power consumption exceeds definable thresholds. The amount of relaxation shall be individually configurable for each zone. The zone setpoints shall automatically return to their previous settings when the facility power consumption drops below the thresholds.
Zone Setpoint Adjust:
The occupant shall be able to adjust the zone temperature heating and cooling setpoints at the zone sensor.
Zone Optimal Start:
The unit shall use an optimal start algorithm for morning start-up. This algorithm shall minimize the unoccupied warm-up or cool-down period while still achieving comfort conditions by the start of scheduled occupied period.
Zone Unoccupied Override:
A timed local override control shall allow an occupant to override the schedule and place the unit into an occupied mode for an adjustable period of time. At the expiration of this time, control of the unit shall automatically return to the schedule.
Economizer:
The controller shall measure the zone temperature and modulate the mixed air dampers in sequence to maintain the zone cooling setpoint. The outside air damper shall maintain a minimum adjustable position of 20% (adj.) open whenever occupied.
The economizer shall be enabled whenever:
• Outside air temperature is at least 3°F (adj.) less than the zone temperature.
• AND the outside air temperature is less than 75°F (adj.)
The economizer shall close whenever the freezestat (if present) is on.
The outside air damper shall close and the return air damper shall open when the unit is off. If Optimal Start Up is available the mixed air damper shall operate as described in the occupied mode except that the outside air damper shall modulate to fully closed.
Minimum Outside Air Ventilation - Fixed Percentage:
The outside air dampers shall maintain a minimum position (adj.) during building occupied hours and be closed during unoccupied hours.
Supplemental Electric Heating Stage:
The controller shall measure the zone temperature and stage the heating to maintain its heating setpoint should the compressors not meet the heating demand. To prevent short cycling, the stage shall have a user definable (adj.) minimum runtime.
The heating shall be enabled whenever:
• The heat pump is in heating mode.
• AND the zone temperature is below heating setpoint.
• AND the fan is on.
Filter Status:
The controller shall monitor the filter status.
Alarms shall be provided as follows:
• Filter Change Required: Filter differential pressure exceeds a user definable limit (adj.).
NOTE:
1. FOR HPS-4A, 4B,7,9,10,11,12 THERE ARE NO SMOKE DAMPERS OR SMOKE
DETECTORS.
T
AI - Mixed Air Temp
T
AI - Outside Air Temp
T AI - Return Air Temp
H AI - Return Air Humidity th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. 20013-0 EXP. 10/10/2022
MECH ENGR REG. NO. 20013-0 EXP. 10/10/2022
ELEC ENGR REG. NO. 20013-0 EXP. 10/10/2022
CIVIL ENGINEER
H2B, INC.
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:1 :4
P
M
MECHANICAL CONTROLS
RDC 23 37JRM
ISSUED FOR CONSTRUCTION
TUCSON CMOP BUILDING
ACQUISITION MINOR
03/14/2022
762-301
VA CMOP
3675 E. BRITANNIA DR.
TUCSON, ARIZONA, 85706
M-703
LOW ZONE TEMP IF THE ZONE TEMP IS 5˚F LOWER THAN ITS SETPOINT (ADJ.) X 10 MIN.
LOW ZONE HUMIDITY IF THE ZONE HUMIDITY IS LOWER THAN ITS SETPOINT (ADJ.) X 10 MIN.
HIGH ZONE TEMP IF THE ZONE TEMP IS 5˚F HIGHER THAN ITS SETPOINT (ADJ.) X 10 MIN.
HIGH ZONE HUMIDITY IF THE ZONE HUMIDITY IS HIGHER THAN ITS SETPOINT (ADJ.) X 10 MIN.
FILTER CHANGE REQUIRED FILTER HAS BEEN IN USE FOR MORE THAN 2200 HOURS (ADJ.) OR THE FILTER D.P. EXCEEDED IT LIMIT X 1 HOUR
FAN RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.
FAN IN HAND COMMANDED OFF, BUT THE STATUS IS ON X 10 MIN.
FAN FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.
LOW DISCHARGE AIR TEMPERATURE IF THE DISCHARGE AIR TEMPERATURE IS 5˚F LESS THAN ITS SETPOINT (ADJ.) X 10 MIN.
HIGH DISCHARGE AIR TEMPERATURE IF THE DISCHARGE AIR TEMPERATURE IS 5˚F GREATER THAN ITS SETPOINT (ADJ.) X 10 MIN.
COMPRESSOR 2 RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.
COMPRESSOR 1 RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.
ALARM DESCRIPTION ALARM ALARM...
SCHEDULE X
EMERGENCY SHUTDOWN X X X
COOLING SETPOINT 55°F X X
HEATING SETPOINT N/A X X
SETPOINTS
REVERSING VALVE X X X
HEATING STAGE 1 X X X
FAN START/STOP X X X
COMPRESSOR STAGE 2 X X X
COMPRESSOR STAGE 1 X X X
ZONE OVERRIDE X X X
SMOKE DETECTOR X X X
FILTER STATUS X X X X
FAN STATUS X X X
MIXED AIR DAMPERS X X X
ZONE TEMP X X X
ZONE SETPOINT ADJUST X X
ZONE HUMIDITY X X X
DISCHARGE TEMP X X X
MIXED AIR TEMP X X X
OUTSIDE AIR TEMP X X X
AI AO BI BO SETPOINT AV BV LOOP SCHED TREND ALARM
POINTS NAME
HARDWARE POINTS SOFTWARE POINTS SHOWN ON
GRAPHIC
POINTS LIST SCHEDULE - HEAT PUMP (TYP 18)
No. REVISION DESCRIPTION DATE
NOT TO SCALE
HEAT PUMP CONTROL DIAGRAM (HP-1 THROUGH 17))1
20 36
MECHANICAL CONTROLS LEGEND
ABBREVIATIONS
AI
A
AO ANALOG OUTPUT
AFS AIRFLOW STATION
ANALOG INPUT
CHW
AV
AF
B
BAC BUILDING AUTOMATION CONTROL
BI
BV
BINARY INPUT
BINARY VIRTUAL
BUILDING PRESSURE
HW
IFB
M
ELEC
CURRENT TRANSMITTER
FRZ
ELECTRIC HEATING COIL
DX DIRECT EXPANSION
D
DD DIRECT DRIVE
GAS FURNACE
DP DIFFERENTIAL PRESSURE
EA
E
EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
ECM ELECTRONICALLY COMMUTATED MOTOR
EXHAUST FANEF
ER ENERGY RECOVERY
EWT ENTERING WATER TEMPERATURE
F
FF FINAL FILTER
FSD FIRE SMOKE DAMPER
GF GAS FURNACE
G
HC HEATING COIL
H
HW HOT WATER
HGB HOT GAS BYPASS
IFB INTEGRAL FACE AND BYPASS
I
LAT LEAVING AIR TEMPERATURE
L
LWT LEAVING WATER TEMPERATURE
HGB HOT GAS BYPASS
MAT MIXED AIR TEMPERATURE
M
MOA MINIMUM OUTSIDE AIR
NG NATURAL GAS
N
OA OUTSIDE AIR
O
OCC OCCUPANCY
OX OXYGEN
OXS OXYGEN SENSOR
PCC PRECOOLING COIL
P
PHC PREHEAT COIL
PF PREFILTER
RA RETURN AIR
R
RF
S
SF
RETURN FAN
RHC REHEAT COIL
R/E RETURN/EXHAUST
R/R RETURN/RELIEF
SA SUPPLY AIR
SUPPLY FAN
SD SMOKE DAMPER
CT
TCP TEMPERATURE CONTROL PANEL
T
TA TRANSFER AIR
TMV THERMOSTATIC MIXING VALVE
TCV TEMPERATURE CONTROL VALVE
UV ULTRAVIOLET
U
VFD VARIABLE FREQUENCY DRIVE
V
VOC VOLATILE ORGANIC COMPOUND XX XXXX
POINT NAME
M
M
PLENUM FAN
PUMP
CURRENT TRANSMITTER
H
2-WAY MODULATING
CONTROL VALVE
THERMOSTATIC MIXING VALVE
3-WAY MODULATING
CONTROL VALVE
L
POINT TYPE
H NEGATIVE SPACE DIFFERENTIAL
PRESSURE SENSOR
O
BLOWER FAN
ZONE OCCUPANCY SENSOR
M
2-POSITION PARALLEL BLADE
DAMPER
ZONE TEMPERATURE SENSOR
T
M
2-POSITION OPPOSED BLADE
DAMPER ZONE
M
VAV ATU MODULATING DAMPER
BACKDRAFT DAMPER
P
SD
SMOKE DAMPER
MODULATING PARALLEL BLADE
DAMPER
H
SUPPLY AIR DUCT STATIC PRESSURE
SENSOR
L
PIPING
T
AQUASTAT
FLOW METER
PRESSURE SENSOR
TEMPERATURE SENSOR
H
M
M
MODULATING OPPOSED BLADE
DAMPER
L
RETURN/EXHAUST AIR DUCT STATIC
PRESSURE SENSOR
H L
HUMIDIFIER DISPERSION GRID
H
DIFFERENTIAL PRESSURE SENSOR
DAMPER POSITION INDICATOR
HUMIDITY SENSOR
FREEZESTAT
T
CC COOLING COIL
C
CHW CHILLED WATER
CP CIRCULATING PUMP
CT
HOT WATER INTEGRAL FACE AND
BYPASS COIL TEMPERATURE SENSOR
BO BINARY OUTPUT
BP
BPC BUILDING PRESSURE CONTROL
HW
HOT WATER COIL
SD
SMOKE DETECTOR
ANALOG VIRTUAL
AFTER FILTER
AFCV AIRFLOW CONTROL VALVE
AHU AIR HANDLING UNIT
DX
DIRECT EXPANSION COIL
CHILLED WATER COIL AFS AIRFLOW STATION
AIRFLOW SENSOR
SYMBOLS
EQUIPMENT SENSORS &
DEVICESDUCTWORK
FILTER ZONE HUMIDITY SENSOR
H
L POSITIVE SPACE DIFFERENTIAL
PRESSURE SENSOR
B-ASC
NEW BACNET
PORTABLE
OPERATOR
TERMINAL
NEW BACNET ENGINEERING
CONTROL CENTER (B-AWS)
NEW
BACNET
NETWORK
B-ASC B-ASC
B-ASC
B-ASC
B-ASC
B-ASC
B-ASC
B-ASC
B-AACB-AAC B-AAC
BACNET
BUILDING
CONTROLLER
(B-BC)
ETHERNET COMMUNICATION
NOTES:
1. REPLACE EXISTING ECC WITH NEW BACNET (B-AWS) ENGINEERING
CONTROL CENTER.
2. REPLACE ALL EXISTING CONTROLLERS WITH NEW BACNET CONTROLLERS.
3. INSTALL NEW BACNET COMMUNICATION NETWORK.
4. INSTALL MULTIPLE BUILDING CONTROLLERS (B-BC) AS REQUIRED.
5. INSTALL NEW CONTROLLERS (B-AAC, B-ASC) AS REQUIRED.
6. PROVIDE NEW OPERATORS TERMINAL. COORDINATE LOCATION WITH VA.
7. PROVIDE STORAGE CAPACTY FOR 30 DAYS.
MSTP COMMUNICATION
(TYPICAL)
BACNET
BUILDING
CONTROLLER
(B-BC)
BACNET
BUILDING
CONTROLLER
(B-BC)
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. 20013-0 EXP. 10/10/2022
MECH ENGR REG. NO. 20013-0 EXP. 10/10/2022
ELEC ENGR REG. NO. 20013-0 EXP. 10/10/2022
CIVIL ENGINEER
H2B, INC.
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:1 :4
P
M
MECHANICAL CONTROLS & LEGEND
RDC 21 37JRM
ISSUED FOR CONSTRUCTION
TUCSON CMOP BUILDING
ACQUISITION MINOR
03/14/2022
762-301
VA CMOP
3675 E. BRITANNIA DR.
TUCSON, ARIZONA, 85706
M-701
4. DIVISION 23 CONTRACTOR TO PROVIDE ROOM AIR BALANCE WHERE POSSIBLE. AIR BALANCE SHALL BE NUETRAL FOR NON-CRITICAL SPACES NOT SHOWN IN SCHEDULE.
3. ZONE LEVEL SET POINT CONDITIONS SHALL RESET TO UNOCCUPIED UNTIL PATIENT ROOM SETPOINTS ARE SATISFIED.
2. ZONE LEVEL SET POINT CONDITIONS SHALL BE AS SCHEDULED UNLESS OTHERWISE SCHEDULED OR NOTED FOR ROOM SPECIFIC SPACE CONDITIONS.
1. ZONE LEVEL OCCUPANCY HOUR SCHEDULE SHALL BE PER BUILDING OPERATING HOURS UNLESS OTHERWISE SCHEDULED.
NOTES:
SUNDAY OT
SATURDAY OT
MONDAY - FRIDAY 5:30 a.m. - 12:30 a.m
BUILDING OPERATING HOURS (VERIFY WITH STATION)
COOLING 0.4% (DB / MCWB) 105.8 ˚FDb / 66 ˚FWb
HUMIDIFICATION 99.6% (DP / HR / MCDB) -1 ˚F / 5.7 / 12.3 ˚F
HEATING 99.6% (F DB) 31.8 ˚F
ASHRAE CLIMATE ZONE 2
WEATHER STATION 2017 ASHRAE CLIMATE DATA / TUCSCON INTERNATIONAL AP, AZ
CLIMATE CONDITIONS
PROJECT DESIGN CONDITIONS
1. SEE EQUIPMENT POINT LISTS FOR EQUIPMENT SPECIFIC TRENDING REQUIREMENTS.
NOTES:
CALC 1 HOUR 30 DAYS N/A
BO CHANGE OF VALUE 24 HOURS 3 DAYS
AO 15 MIN. 24 HOURS 3 DAYS
BI CHANGE OF VALUE 24 HOURS 3 DAYS
AI 15 MIN. 24 HOURS 3 DAYS
POINT NAME TREND INTERVAL
OPERATIONAL TREND
DURATION
TESTING TREND
DURATION
POINTS LIST - STANDARD TRENDING INTERVALS
No. REVISION DESCRIPTION DATE
NOT TO SCALE
BACNET CONTROLLER DIAGRAM1
NOTES:
1. ALL EXISTING THERMOSTATS SHALL BE REMOVED AND REPLACED WITH A NEW PROGRAMMABLE THERMOSTAT WITH .
HUMIDIY CONTROL. THERMOSTAT SHALL BE CONNECTED TO NEW BMS. SEE SHEETS M-702 THROUGH M-706.
2. ALL EXISTING MANUAL OUTSIDE AIR DAMPERS SHALL BE REMOVED AND REPLACED WITH MOTORIZED OUTSIDE AIR DAMPERS. MECHANICAL CONTRACTOR SHALL FIELD VERIFY SIZE OF EXISTING DAMPERS BEFORE
BEGINNING CONSTRUCTION.
21 36
Elec
BO - Heating Stage 1
DX
BO - Cooling Stage 1
BO - Cooling Stage 2
T
AI - Return Air Temp
AI - Mixed Air Temp
T
BI - Supply Air Smoke Detector
T
AI - Supply Air Temp
M
CT
Starter BO - Supply Fan Start/Stop
BI - Supply Fan Status
SF
M N.O.
N.O.
BI - Zone Override
AI - Zone Setpoint Adjust
SA
RA
T AI - Zone Temp
OA
SEQUENCE OF OPERATIONS
ROOFTOP UNIT - RTU (TYP OF 2)
Run Conditions - Adminstration Areas - Scheduled:
The unit shall run according to a user definable time schedule in the following modes:
• Occupied Mode: The unit shall maintain
• A 75°F (adj.) cooling setpoint
• A 70°F (adj.) heating setpoint.
• Unoccupied Mode (night setback): The unit shall maintain
• A 85°F (adj.) cooling setpoint.
• A 55°F (adj.) heating setpoint.
Run Conditions - Pharmaceutical Areas - Scheduled:
• Occupied Mode: The unit shall maintain
• A 75°F (adj.) cooling setpoint
• A 70°F (adj.) heating setpoint.
• Unoccupied Mode (night setback): The unit shall maintain
• A 75°F (adj.) cooling setpoint.
• A 70°F (adj.) heating setpoint.
Alarms shall be provided as follows:
• High Zone Temp: If the zone temperature is greater than the cooling setpoint by a user definable amount (adj.).
• Low Zone Temp: If the zone temperature is less than the heating setpoint by a user definable amount (adj.).
Demand Limiting - Zone Setpoint Optimization:
To lower power consumption, the zone setpoints shall automatically relax when the facility power consumption exceeds definable thresholds. The amount of relaxation shall be individually configurable for each zone. The zone setpoints shall automatically return to their previous settings when the facility power consumption drops below the thresholds.
Zone Setpoint Adjust:
The occupant shall be able to adjust the zone temperature heating and cooling setpoints at the zone sensor.
Zone Optimal Start:
The unit shall use an optimal start algorithm for morning start-up. This algorithm shall minimize the unoccupied warm-up or cool-down period while still achieving comfort conditions by the start of scheduled occupied period.
Zone Unoccupied Override:
A timed local override control shall allow an occupant to override the schedule and place the unit into an occupied mode for an adjustable period of time. At the expiration of this time, control of the unit shall automatically return to the schedule.
Minimum Outside Air Ventilation - Fixed Percentage:
The outside air dampers shall maintain a minimum position (adj.) during building occupied hours and be closed during unoccupied hours.
Mixed Air Temperature:
The controller shall monitor the mixed air temperature and use as required for economizer control (if present) or preheating control (if present).
Alarms shall be provided as follows:
• High Mixed Air Temp: If the mixed air temperature is greater than 90°F
(adj.).
• Low Mixed Air Temp: If the mixed air temperature is less than 45°F (adj.).
Freeze Protection:
The unit shall shut down and generate an alarm upon receiving a freezestat status.
Supply Air Smoke Detection:
The unit shall shut down and generate an alarm upon receiving a supply air smoke detector status.
Supply Fan:
The supply fan shall run anytime the unit is commanded to run, unless shutdown on safeties. To prevent short cycling, the supply fan shall have a user definable (adj.)
minimum runtime.
Alarms shall be provided as follows:
• Supply Fan Failure: Commanded on, but the status is off.
• Supply Fan in Hand: Commanded off, but the status is on.
• Supply Fan Runtime Exceeded: Status runtime exceeds a user definable limit (adj.).
Cooling Stages:
The controller shall measure the zone temperature and stage the cooling to maintain its cooling setpoint. To prevent short cycling, there shall be a user definable (adj.)
delay between stages, and each stage shall have a user definable (adj.) minimum runtime.
The cooling shall be enabled whenever:
• Outside air temperature is greater than 60°F (adj.).
• AND the economizer (if present) is disabled or fully open.
• AND the zone temperature is above cooling setpoint.
• AND the supply fan status is on.
• AND the heating is not active.
Electric Heating Stage:
The controller shall measure the zone temperature and stage the heating to maintain its heating setpoint. To prevent short cycling, the stage shall have a user definable (adj.) minimum runtime.
The heating shall be enabled whenever:
• Outside air temperature is less than 65°F (adj.).
• AND the zone temperature is below heating setpoint.
• AND the supply fan status is on.
• AND the cooling is not active.
Return Air Humidity:
The controller shall monitor the return air humidity and use as required for economizer control (if present) or humidity control (if present).
Alarms shall be provided as follows:
• High Return Air Humidity: If the return air humidity is greater than 65% (adj.).
• Low Return Air Humidity: If the return air humidity is less than 25% (adj.).
Return Air Temperature:
The controller shall monitor the return air temperature and use as required for economizer control (if present).
Alarms shall be provided as follows:
• High Return Air Temp: If the return air temperature is greater than 90°
F (adj.).
• Low Return Air Temp: If the return air temperature is less than 45°F (adj.).
Supply Air Temperature:
The controller shall monitor the supply air temperature.
Alarms shall be provided as follows:
• High Supply Air Temp: If the supply air temperature is greater than 120°
F (adj.).
• Low Supply Air Temp: If the supply air temperature is less than 45°F (adj.).
AI - Outside Air Temp
T
H
AI - Return Air Humidity
BI - Filter Status th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. 20013-0 EXP. 10/10/2022
MECH ENGR REG. NO. 20013-0 EXP. 10/10/2022
ELEC ENGR REG. NO. 20013-0 EXP. 10/10/2022
CIVIL ENGINEER
H2B, INC.
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:1 :4
P
M
MECHANICAL CONTROLS
RDC 22 37JRM
ISSUED FOR CONSTRUCTION
TUCSON CMOP BUILDING
ACQUISITION MINOR
03/14/2022
762-301
VA CMOP
3675 E. BRITANNIA DR.
TUCSON, ARIZONA, 85706
M-702
HIGH ZONE TEMP IF THE ZONE TEMPERATURE IS 5˚F GREATER THAN ITS SETPOINT (ADJ.) X 10 MIN.
COMPRESSOR RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.
LOW RETURN AIR HUMIDITY IF THE RETURN AIR HUMIDITY IS LOWER THAN X. X 10 MIN.
HIGH RETURN AIR HUMIDITY IF THE RETURN AIR HUMIDITY IS GREATER THAN X. X 10 MIN.
FILTER CHANGE REQUIRED FILTER HAS BEEN IN USE FOR MORE THAN 2200 HOURS (ADJ.) OR THE FILTER D.P. EXCEEDED IT LIMIT X 1 HOUR
SUPPLY FAN RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.
SUPPLY FAN IN HAND COMMANDED OFF, BUT THE STATUS IS ON X 10 MIN.
SUPPLY FAN FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.
LOW RETURN AIR TEMPERATURE IF THE RETURN AIR TEMPERATURE IS LESS THAN 45˚F (ADJ.) X 10 MIN.
HIGH RETURN AIR TEMPERATURE IF THE RETURN AIR TEMPERATURE IS GREATER THAN 90˚F (ADJ.) X 10 MIN.
LOW SUPPLY AIR TEMPERATURE IF THE SUPPLY AIR TEMPERATURE IS 5˚F LESS THAN ITS SETPOINT (ADJ.) X 10 MIN.
HIGH SUPPLY AIR TEMPERATURE IF THE SUPPLY AIR TEMPERATURE IS 5˚F GREATER THAN ITS SETPOINT (ADJ.) X 10 MIN.
LOW MIXED AIR TEMPERATURE IF THE MIXED AIR TEMPERATURE IS LESS THAN 45˚F (ADJ.) X 10 MIN.
HIGH MIXED AIR TEMPERATURE IF THE MIXED AIR TEMPERATURE IS GREATER THAN 90˚F (ADJ.) X 10 MIN.
ALARM DESCRIPTION ALARM ALARM...
COOLING SETPOINT 55°F X X
HEATING SETPOINT X X
SCHEDULE N/A X X
SETPOINTS
RA TEMP X X X
RETURN AIR
HEATING STAGE 1 X X X
COOLING STAGE 2 X X X
COOLING STAGE 1 X X X X
ZONE SETPOINT ADJUST X X
ZONE OVERRIDE X X X
ZONE TEMP X X X
FREEZESTAT X X X
SA TEMP X X X
SA SMOKE DETECTOR X X X X
SF START/STOP X X X
SF STATUS X X X
SUPPLY AIR
MIXED AIR TEMP X X X
OUTSIDE AIR TEMP X X X
MIXED/OUTSIDE AIR
AI AO BI BO SETPOINT AV BV LOOP SCHED TREND ALARM
POINTS NAME
HARDWARE POINTS SOFTWARE POINTS SHOWN ON
GRAPHIC
POINTS LIST SCHEDULE - PACKAGED ROOFTOP UNIT (RTU)
No. REVISION DESCRIPTION DATE
NOT TO SCALE
ROOFTOP UNIT CONTROLS DIAGRAM (RTU-1,2))1
22 36
SEQUENCE OF OPERATIONS
EXHAUST FAN (EF-X)
GENERAL DESCRIPTION
The exhaust fan provides general exhaust ventilation to the conditioned space(s).
OPERATING MODES
OCCUPIED MODE
The exhaust fan shall be in occupied mode per the project design conditions schedule shown on sheet M-701.
UNOCCUPIED MODE
The exhaust fan shall be in unoccupied mode for all periods not included in the occupied hours of operation.
COMPONENT CONTROL LOOPS
EXHAUST FAN – ON/OFF
• When the HOA switch is in hand position, the supply fan shall operate manually by the operator at the user interface of the drive.
• When the HOA switch is in off position, the fan shall be off.
• When the HOA switch is in auto position, the supply fan shall operate subject to the unit enable signal, and unit operating modes.
OCCUPIED MODE:
• The exhaust fan shall be commanded to run at constant speed.
UNOCCUPIED MODE:
The exhaust fan shall be off.
EA
M
CT
STARTER
BDD
BI
BO
EF STATUS
EF START/STOP
H AI - Zone Humidity
BI - Filter Status
H L
BI - Smoke Detector
DX
BO - Cooling Stage 1
BO - Cooling Stage 2
BO - Cooling Stage 3
BO - Cooling Stage 4
BI - Fan Status
CT
BO - Fan Start/Stop
T
AI - Discharge Air Temp
BI - Zone Override
AI - Zone Setpoint Adjust
RA
T
AI - Zone Temp
DA
M
COMPUTER ROOM AIR CONDITIONING UNIT - (CRAC - TYP 6)
Run Conditions - Scheduled:
The unit shall maintain 70°F 24/7.
Alarms shall be provided as follows:
• High Zone Temp: If the zone temperature is greater than the cooling setpoint by a user definable amount (adj.).
Zone Setpoint Adjust:
The occupant shall be able to adjust the zone temperature heating and cooling setpoints at the zone sensor.
Zone Unoccupied Override:
A timed local override control shall allow an occupant to override the schedule and place the unit into an occupied mode for an adjustable period of time. At the expiration of this time, control of the unit shall automatically return to the schedule.
Emergency Shutdown:
The unit shall shut down and generate an alarm upon receiving an emergency shutdown signal.
Smoke Detection:
The unit shall shut down and generate an alarm upon receiving a smoke detector status.
Fan:
The fan shall run anytime the unit is commanded to run, unless shutdown on safeties.
Cooling Stages:
The controller shall measure the zone temperature and stage the cooling to maintain its cooling setpoint. To prevent short cycling, there shall be a user definable (adj.) delay between stages, and each stage shall have a user definable (adj.) minimum runtime.
The cooling shall be enabled whenever:
• The zone temperature is above cooling setpoint.
• AND the fan is on.
Filter Status:
The controller shall monitor the filter status.
Alarms shall be provided as follows:
• Filter Change Required: Filter differential pressure exceeds a user definable limit (adj.).
Discharge Air Temperature:
The controller shall monitor the discharge air temperature.
Alarms shall be provided as follows:
• High Discharge Air Temp: If the discharge air temperature is greater than 70°F (adj.).
Fan Status:
The controller shall monitor the fan status.
Alarms shall be provided as follows:
• Fan Failure: Commanded on, but the status is off.
• Fan in Hand: Commanded off, but the status is on.
• Fan Runtime Exceeded: Fan status runtime exceeds a user definable limit (adj.).
Zone Humidity:
The controller shall monitor the zone humidity.
Alarms shall be provided as follows:
• High Zone Humidity: If the zone humidity is greater than
60% (adj.).
• Low Zone Humidity: If the zone humidity is less than
35% (adj.).
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. 20013-0 EXP. 10/10/2022
MECH ENGR REG. NO. 20013-0 EXP. 10/10/2022
ELEC ENGR REG. NO. 20013-0 EXP. 10/10/2022
CIVIL ENGINEER
H2B, INC.
1225 NORTH LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
/1
/2
:1 :4
P
M
MECHANICAL CONTROLS
RDC 24 37JRM
ISSUED FOR CONSTRUCTION
TUCSON CMOP BUILDING
ACQUISITION MINOR
03/14/2022
762-301
VA CMOP
3675 E. BRITANNIA DR.
TUCSON, ARIZONA, 85706
M-704
NOT TO SCALE
EXHAUST FAN CONTROL DIAGRAM (EF - TYP 2)1
No. REVISION DESCRIPTION DATE
LOW ZONE HUMIDITY IF THE HUMIDITY IS 5% LOWER THAN SETPOINT (ADJ.) X 10 MIN.
HIGH ZONE TEMP IF THE ZONE TEMP IS 5˚F HIGHER THAN THE SETPOINT (ADJ.) X 10 MIN.
HIGH ZONE HUMIDITY IF THE HUMIDITY IS 5% GREATER THAN SETPOINT (ADJ.) X 10 MIN.
FAN RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.
FAN FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.
FAN IN HAND IF THE SMOKE DETECTOR IS ACTIVATED X 5 MIN.
FILTER CHANGE REQUIRED IF THE FILTER HAS BEEN IS USE FOR MORE THAN 2200 HOURS (ADJ.) OR THE FILTER D.P. EXCEEDS ITS LIMIT X 5 MIN.
COMPRESSOR RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.
ALARM DESCRIPTION ALARM ALARM...
SCHEDULE X
EMERGENCY SHUTDOWN X X X
COOLING SETPOINT X X X
FAN START/STOP X X X
COOLING STAGE 4 X X X
COOLING STAGE 3 X X X
COOLING STAGE 2 X X X
COOLING STAGE 1 X X X
ZONE OVERRIDE X X X
SMOKE DETECTOR X 55 X X X
FILTER STATUS X N/A X X X
FAN STATUS X X X
ZONE TEMP X X X
ZONE SETPOINT ADJUST X X X
ZONE HUMIDITY X X X
DISCHARGE AIR TEMP X X X
AI AO BI BO SETPOINT AV BV LOOP SCHED TREND ALARM
POINTS NAME
HARDWARE POINTS SOFTWARE POINTS SHOWN ON
GRAPHIC
POINTS LIST SCHEDULE - COMPUTER ROOM AIR CONDITIONER (CRAC)
1. SEE STANDARD TRENDING POINTS LIST SCHEDULE ON SHEET M-701 FOR APPLICABLE TREND INTERVALS.
NOTES:
EF RUNTIME EXCEEDED FAN RUNTIME EXCEEDS A USER DEFINABLE LIMIT X 10 MIN.
EF IN HAND COMMANDED OFF, BUT THE STATUS IS ON X 10 MIN.
EF FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.
EXHAUST AIR DAMPER IN HAND COMMANDED CLOSED, BUT THE STATUS IS OPEN X 10 MIN.
EXHAUST AIR DAMPER FAILURE COMMANDED OPEN, BUT THE STATUS IS CLOSED X 10 MIN.
ALARMS DESCRIPTION ALARM ALARM DELAY
EF START/STOP X X X
EF STATUS X X X
EXHAUST FAN
AI AO BI BO AV BV LOOP SCHED TREND ALARM
POINTS NAME
HARDWARE POINTS SOFTWARE POINTS SHOWN ON
GRAPHIC
POINTS LIST SCHEDULE - GENERAL EXHAUST FAN (EF-X)
NOT TO SCALE
COMPUTER ROOM AIR CONDITIONER (SERVER ROOM, UPS ROOM TELEPHONE ROOM)2
23 36
Elec
BO - Heating Stage 1
DX
BO - Cooling Stage 1
BO - Cooling Stage 2
T
AI - Return Air Temp
AI - Mixed Air Temp
T
BI - Supply Air Smoke Detector
H
AI - Return Air Humidity
T
AI - Supply Air Temp
M
CT
Starter BO - Supply Fan Start/Stop
BI - Supply Fan Status
SF
AO - Mixed Air Dampers
M
M N.O.
N.C.
BI - Zone Override
AI - Zone Setpoint Adjust
SA
RA
T AI - Zone Temp
OA
SEQUENCE OF OPERATIONS
AIR HANDLING UNIT (AHU-1)
Run Conditions - Scheduled:
The unit shall run according to a standard room design temperature setting.
Alarms shall be provided as follows:
• High Zone Temp: If the zone temperature is greater than the cooling setpoint by a user definable amount (adj.).
• Low Zone Temp: If the zone temperature is less than the heating setpoint by a user definable amount (adj.).
Demand Limiting - Zone Setpoint Optimization:
To lower power consumption, the zone setpoints shall automatically relax when the facility power consumption exceeds definable thresholds. The amount of relaxation shall be individually configurable for each zone. The zone setpoints shall automatically return to their previous settings when the facility power consumption drops below the thresholds.
Zone Setpoint Adjust:
The occupant shall be able to adjust the zone temperature heating and cooling setpoints at the zone sensor.
Zone Optimal Start:
The unit shall use an optimal start algorithm for morning start-up. This algorithm shall minimize the unoccupied warm-up or cool-down period while still achieving comfort conditions by the start of scheduled occupied period.
Zone Unoccupied Override:
A timed local override control shall allow an occupant to override the schedule and place the unit into an occupied mode for an adjustable period of time. At the expiration of this time, control of the unit shall automatically return to the schedule.
Freeze Protection:
The unit shall shut down and generate an alarm upon receiving a freezestat status.
Supply Air Smoke Detection:
The unit shall shut down and generate an alarm upon receiving a supply air smoke detector status.
Economizer:
The controller shall measure the zone temperature and modulate the economizer dampers in sequence to maintain a setpoint 2°F less than the zone cooling setpoint.
The outside air dampers shall maintain a minimum adjustable position of 20% (adj.)
open whenever occupied.
The economizer shall be enabled whenever:
• Outside air temperature is less than 65°F (adj.).
• AND the outside air temperature is less than the return air temperature.
• AND the supply fan status is on.
The economizer shall close whenever:
• Mixed air temperature drops from 45°F to 40°F (adj.).
• OR on loss of supply fan status.
• OR the freezestat (if present) is on.
The outside air damper shall close and the return air damper shall open when the unit is off. If Optimal Start Up is available, the mixed air damper shall operate as described in the occupied mode except that the outside air damper shall modulate to fully closed.
Minimum Outside Air Ventilation - Fixed Percentage:
The outside air dampers shall maintain a minimum position (adj.) during building occupied hours and be closed during unoccupied hours.
Mixed Air Temperature:
The controller shall monitor the mixed air temperature and use as required for economizer control (if present) or preheating control (if present).
Alarms shall be provided as follows:
• High Mixed Air Temp: If the mixed air temperature is greater than 90°F
(adj.).
• Low Mixed Air Temp: If the mixed air temperature is less than 45°F (adj.).
Supply Fan:
The supply fan shall run anytime the unit is commanded to run, unless shutdown on safeties. To prevent short cycling, the supply fan shall have a user definable (adj.)
minimum runtime.
Alarms shall be provided as follows:
• Supply Fan Failure: Commanded on, but the status is off.
• Supply Fan in Hand: Commanded off, but the status is on.
• Supply Fan Runtime Exceeded: Status runtime exceeds a user definable limit (adj.).
Cooling Stages:
The controller shall measure the zone temperature and stage the cooling to maintain its cooling setpoint. To prevent short cycling, there shall be a user definable (adj.)
delay between stages, and each stage shall have a user definable (adj.) minimum runtime.
The cooling shall be enabled whenever:
• Outside air temperature is greater than 60°F (adj.).
• AND the economizer (if present) is disabled or fully open.
• AND the zone temperature is above cooling setpoint.
• AND the supply fan status is on.
• AND the heating is not active.
Electric Heating Stage:
The controller shall measure the zone temperature and stage the heating to maintain its heating setpoint. To prevent short cycling, the stage shall have a user definable (adj.) minimum runtime.
The heating shall be enabled whenever:
• Outside air temperature is less than 65°F (adj.).
• AND the zone temperature is below heating setpoint.
• AND the supply fan status is on.
• AND the cooling is not active.
Return Air Humidity:
The controller shall monitor the return air humidity and use as required for economizer control (if present) or humidity control (if…
This is the start of the file's text. The full file is on GovTribe.