ATTACHMENT 3 - Drawings 2of2.pdf

PDF 14 MB Posted

Attached to
Y1LZ--762-301 CMOP Building Acquisition Minor Construction - Tucson
Solicitation number
36C77623B0039
Issued by

About this file

This document contains details of a federal solicitation for construction services. The solicitation number 36C77623B0039 was issued by the Department of Veterans Affairs Technology Acquisition Center Austin for the Y1LZ--762-301 CMOP Building Acquisition Minor Construction project located in Tucson, Arizona. The opportunity is for the construction of a new parking lot on the agency's property, as described in the attached drawings. Responses to the solicitation are due based on the deadline provided in the solicitation documents. The award date and other contractual terms are also outlined therein.

View the file

Other files

File Type Posted
36C77623B0039 0004.docx DOCX document
32 31 11 Gate Operator.pdf PDF
ADDENDUM 03_Dwgs.pdf PDF
Technical Questions - FINAL 2 - TUCSON - 06.20.2023.pdf PDF
standard drop arm gate.pdf PDF
ADDENDUM 03 - Front End Doc.pdf PDF
00 01 10 Spec TOC.pdf PDF
36C77623B0039 0003.docx DOCX document
36C77623B0039_Civil Doc 1.pdf PDF
36C77623B0039_Addendum 02.pdf PDF
36C77623B0039_Addendum 02 - Drawings.pdf PDF
Technical Questions - FINAL - Tucson 06-07-2023.pdf PDF
36C77623B0039 0002.docx DOCX document
36C77623B0039_Mech Doc 2.pdf PDF
36C77623B0039_Mech Doc 1.pdf PDF
36C77623B0039_25 10 10 Advanced Utility Metering System.pdf PDF
36C77623B0039_Geo Report.pdf PDF
Site Visit Sign-in Sheet - Tucson 5-11-23.pdf PDF
36C77623B0039 0001.docx DOCX document
ATTACHMENT 2 - Drawings 1of1.pdf PDF
ATTACHMENT 4 - Geotechnical Report.pdf PDF
ATTACHMENT 8 - SIte Visit Instructions.pdf PDF
ATTACHMENT 7 - Contractor Safety - Environmental Form.docx DOCX document
ATTACHMENT 6 - Construction Wage Rates - Pima 2-3-23.pdf PDF
ATTACHMENT 1 - Specifications.pdf PDF
36C77623B0039_1.docx DOCX document
ATTACHMENT 5 - Limitations on Subcontracting - Construction.docx DOCX document
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

4"

1/4 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. 69321 EXP. 09/30/2022

MECH ENGR REG. NO. 69943 EXP. 12/31/2022

ELEC ENGR REG. NO. 70271 EXP. 12/31/2022

CIVIL ENGINEER

H2B, INC.

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FULLY SPRINKLERED

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

6/

:0 0:

P

M

RE XXALL

ISSUED FOR CONSTRUCTION

TUCSON CMOP BUILDING

ACQUISITION MINOR

03/14/2022

762-301

VA CMOP

3675 E. BRITANNIA DR.

TUCSON, ARIZONA, 85706

SPUR #: 22091.02

No. REVISION DESCRIPTION DATE

FENCE DETAILS

CS204

15 36 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. 69321 EXP. 09/30/2022

MECH ENGR REG. NO. 69943 EXP. 12/31/2022

ELEC ENGR REG. NO. 70271 EXP. 12/31/2022

CIVIL ENGINEER

H2B, INC.

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FULLY SPRINKLERED

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

6/

:0 0:

P

M

RE XXALL

ISSUED FOR CONSTRUCTION

TUCSON CMOP BUILDING

ACQUISITION MINOR

03/14/2022

762-301

VA CMOP

3675 E. BRITANNIA DR.

TUCSON, ARIZONA, 85706

SPUR #: 22091.02

No. REVISION DESCRIPTION DATE

GATE DETAILS

CS205

16 36

E BRITANNIA DR

E H

E M

IS

P

H E

R E

L O

O P

VISITOR PARKING

E DESERT WALK LN

CMOP

38'-6" 25'-0" 20'-6" 173'-6" 52'-0"

'-3

'-0

436'-10" FV

1'

-5

F V

2'

-4

F V

2.07

2.22

2.112.12

2.14

2.07

2.13

2.11

2.11

2.12

2.15

2.12

2.07

2.11

2.16

2.17

2.18

2.102.10

2.22

226'-11" FV

248'-6" FV

2.22

LANDSCAPED AREA

PAVED AREA

EXISTING BUILDING

EXTENTS TO BE DEMOLISHED

EXISTING FENCE

LANDSCAPED AREA TO BE DEMOLISHED

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

CERTIFICATE OF AUTHORITY NO. 20013-0

EXP. 09/30/2022

CIVIL ENGINEER

H2B, INC.

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:2 :3

P

M

DEMO ARCHITECTURAL SITE PLAN

ECO 17 36DRH

ISSUED FOR CONSTRUCTION

TUCSON CMOP BUILDING

ACQUISITION MINOR

03/14/2022

762-301

VA CMOP

3675 E. BRITANNIA DR.

TUCSON, ARIZONA, 85706

AS001

SPUR #: 2091.02

1" = 50'-0"

DEMO SITE PLAN1

DEMO SITE PLAN LEGEND

N

KEYNOTE LEGEND

2.07 DEMO EXISTING FENCE TO EXTENTS INDICATED

2.10 DEMO EXISTING LANDSCAPE AND PREPARE AREA FOR NEW CURBS AND PAVEMENT

2.11 EXISTING FIRE HYDRANT TO REMAIN

2.12 EXISTING MAN GATE TO REMAIN

2.13 EXISTING LIGHTING PEDESTAL TO REMAIN

2.14 EXISTING STANDPIPE TO REMAIN

2.15 EXISTING HVAC UNITS TO REMAIN

2.16 EXISTING CONEX / HVAC EQUIP. TO REMAIN

2.17 EXISTING UPS TO REMAIN

2.18 EXISTING GENERATOR TO REMAIN

2.22 DEMO EXISTING CHAIN LINK FENCE IN ITS ENTIRETY

No. REVISION DESCRIPTION DATE

E BRITANNIA DR

E H

E M

IS

P

H E

R E

L O

O P

DELIVERY/

LOGISTIC EXIT

E DESERT WALK LN

CMOP

DELIVERY

EXIT

DELIVERY/

LOGISTIC

ENTRY

EMPLOYEE

ENTRY / EXIT

EMPLOYEE

ENTRY / EXIT

ONE WAY EXIT ONLY

ONE

WAY

TRAFFIC

ONE WAY EXIT ONLY

'-4

'-0

130'-6" 17'-0" 39'-0" 38'-0" 128'-2" 4'-0" 9" 19'-4"

130'-6" FV 256'-11"

'-0

F

V

9' -3

F

V

2.0832.092.082.12

32.02 32.03

32.04

32.03 32.02

32.07 32.05

32.03 32.06

32.02 32.08

2.13

2.19

2.082.08

32.02

32.07

2.12

2.15

32.11

2.12

2.16

2.17

2.18 32.1132.1132.11

32.07

2.202.20

26.01

92'-0" 89'-4"

2'-0" 20'-0"

21 21 21 21

81010

910 10

19 22

7'-0" 20'-0"

6"

'-0

1'-6" 32'-0"

'-0

'-0

'-1

'-4

'-4

'-1

0"

0' -6

'-2

'-9

29'-5" 85'-0" 85'-0"

45'-10" 7'-5" 84'-7" 28'-2" 85'-4"

278'-6" FV

5'

-2

F V

428'-6" FV

24'-0" FV 206'-0" FV 29'-0" FV

'-1

0"

'-5

8"8'-8"8'-0"6'-0"8'-0"6'-0"

E4

E4

E4

E4

E4

E2

E1

E2

E1

E1

32.10

32.10

32.10

32.10 32.10

32.10

8"

2.12

E3

E5

E3 E5

E3E5

E3 E5

E3 E5 32.03

2.11

2.11

2.12

2.11

370'-0" FV

3'-6"

'-8

'-8

36'-0"

'-1

0"

63'-6"

2.19

246'-4" 10'-8"

32.02

32.02

32.05

EXISTING LANDSCAPED AREA

FENCING

PAVED AREA

ANTI-RAM BOLLARDS

EXISTING BUILDING

NEW LANDSCAPED AREA

EXTERIOR SIGNAGE

REF. SIGN TYPES (4/AS002)

E1

EXISTING LIGHT FIXTURE

LIGHT FIXTURE REF. ELECTRICAL

1. ARM EACH EXISTING AND FUTURE PEDESTRIAN GATE WITH AN ELECTRIC STRIKE (WITH

COVER PLATE), DUAL-AUTHENTICATION PIV & PIN CODE PACS, AUTO-CLOSER, AND CONTACT

SENSOR WITH ANTI-PROP ALARM, AND FIXED FACIAL ANALYTICS CAMERA, ALL MONITORED BY

THE SCC AND A LOCALIZED STATION WITHIN THE CMOP (I.E., ADMINISTRATION DESK OR CMOP

MANAGER). ENSURE THE FACIAL ANALYTICS CAMERAS ARE TIED TO THE VA EMPLOYEE

DATABASE FOR CONFIRMATION, AS TO PREVENT UNAUTHORIZED/FORCE CREDENTIAL USAGE

OR TAILGATING. REFER ELECTRICAL.

2. INSTALL PEDESTRIAN GATES AT EACH VEHICLE GATE, ENSURING THE PEDESTRIAN GATES

ARE CONSTRUCTED OF THE SAME MATERIAL AS THE FENCE SYSTEM, AND ARMED AS

DETAILED IN ITEM 1 ABOVE. ARM EACH PEDESTRIAN GATE WITH AN ELECTRIC STRIKE (WITH

COVER PLATE), DUAL-AUTHENTICATION PIV & PIN CODE PACS, AUTO-CLOSER, AND CONTACT

SENSOR WITH ANTI-PROP ALARM, ALL MONITORED BY THE SCC AND A LOCALIZED STATION

WITHIN THE CMOP (I.E., ADMINISTRATION DESK OR CMOP MANAGER). ADDITIONALLY, ENSURE

A FIXED FACIAL ANALYTICS CAMERA IS INSTALLED AT THE GATE ENTRY, TIED TO THE VA

EMPLOYEE DATABASE FOR CONFIRMATION, AS TO PREVENT UNAUTHORIZED/FORCE

CREDENTIAL USAGE OR TAILGATING. REFER ELECTRICAL.

3. BOLLARD SPACING IS 4" O.C. TYP.

GENERAL PLAN NOTES

PARKING

ONLY

2' -6

2'-0"

1' -6

1'-0"

VA SIGN: EN-10.06 VA SIGN: EN-10.06

VA SIGN: PL-12.04

2' -6

2'-0"

SIGN TYPE: E1 SIGN TYPE: E2

SIGN TYPE: E4

1"

1/ 4"

1/

2" 3/

4"

1/ 2"

1"

NO FIREARMS

VA SIGN: IN-02.11

2' -6

2'-0"

SIGN TYPE: E3

OR WEAPONS

ALLOWED ON

THIS PROPERTY

18 USC § 930

NOTICE

2" 1"

2" 2"

2"

1/ 2"

1" 6"

1'-2"

SIGN TYPE: E5

VIDEO

SURVEILLANCE

IN USE ON

THESE PREMISES

NOTICE

VIDEO SURVEILLANCE SIGN

R E

F . S

IG

N

E

LE

V A

T

IO

N S

S

IZ

E V

A R

IE

S

H E

IG

H

T V

A R

IE

S

. R E

F . S

IG

N

E

LE

V A

T

IO

N S

2' -6

1'-6"

3.01

5.29

5.30

1' -6

4'

-6

PARKING

ONLY

2' -6

7'

-0

6' -0

9' -6

EN-10.06

(SINGLE POST)

PL-12.04

(SINGLE POST)

NO FIREARMS

OR WEAPONS

ALLOWED ON

THIS PROPERTY

18 USC § 930

NOTICE

5' -6

IN-02.11

(WALL MOUNTED)

VIDEO

SURVEILLANCE

IN USE ON

THESE PREMISES

NOTICE

VIDEO SURVEILLANCE SIGN

(WALL MOUNTED)

5' -6 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

CERTIFICATE OF AUTHORITY NO. 20013-0

EXP. 09/30/2022

CIVIL ENGINEER

H2B, INC.

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/2

/2

:5 :1

A

M

ARCHITECTURAL SITE PLAN

ECO 18 36DRH

ISSUED FOR CONSTRUCTION

TUCSON CMOP BUILDING

ACQUISITION MINOR

03/14/2022

762-301

VA CMOP

3675 E. BRITANNIA DR.

TUCSON, ARIZONA, 85706

AS002

SPUR #: 2091.02

1" = 50'-0"

SITE PLAN1

SITE PLAN LEGEND

N

KEYNOTE LEGEND

5.30 1/8" ALUMINUM PANEL WITH SURFACE APPLIED REFLECTIVE VINYL. REF. SIGN TYPES

26.01 LIGHT FIXTURE, TYP. REF. ELECTRICAL

32.02 NEW FENCE TO MATCH EXISTING

32.03 GATE CONTROL ISLAND

32.04 ANTI-RAM BARRIERS ASTM F2656 M10

32.05 RETRACTABLE ANTI-RAM SYSTEM ASTM F2656 M30

32.06 NEW PEDESTRIAN GATE

32.07 30' SLIDING GATE AND TRACK

32.08 40' SLIDING GATE AND TRACK

32.09 50' SLIDING GATE AND TRACK

32.10 PAVEMENT MARKINGS

32.11 ANTI-RAM BARRIERS ASTM F2656 M30

KEYNOTE LEGEND

2.08 EXISTING FENCE TO REMAIN

2.11 EXISTING FIRE HYDRANT TO REMAIN

2.12 EXISTING MAN GATE TO REMAIN

2.13 EXISTING LIGHTING PEDESTAL TO REMAIN

2.15 EXISTING HVAC UNITS TO REMAIN

2.16 EXISTING CONEX / HVAC EQUIP. TO REMAIN

2.17 EXISTING UPS TO REMAIN

2.18 EXISTING GENERATOR TO REMAIN

2.19 EXISTING SLIDING GATE TO REMAIN

2.20 EXISTING PARKING AND ISLANDS TO REMAIN

3.01 CONCRETE FOOTING

5.29 3" X 3" STEEL POST

1 1/2" = 1'-0"

SIGN TYPES4

1" = 1'-0"

TYP. SINGLE POST DETAIL21" = 1'-0"

SIGN ELEVATIONS3

No. REVISION DESCRIPTION DATE

1 ADDENDUM 01 05/20/2022

The information on this document is preliminary or incomplete, not for construction, recording urposes, or implementation.

1. ARM EACH EXISTING AND FUTURE PEDESTRIAN GATE WITH AN ELECTRIC STRIKE (WITH

COVER PLATE), DUAL-AUTHENTICATION PIV & PIN CODE PACS, AUTO-CLOSER, AND CONTACT

SENSOR WITH ANTI-PROP ALARM, AND FIXED FACIAL ANALYTICS CAMERA, ALL MONITORED BY

THE SCC AND A LOCALIZED STATION WITHIN THE CMOP (I.E., ADMINISTRATION DESK OR CMOP

MANAGER). ENSURE THE FACIAL ANALYTICS CAMERAS ARE TIED TO THE VA EMPLOYEE

DATABASE FOR CONFIRMATION, AS TO PREVENT UNAUTHORIZED/FORCE CREDENTIAL USAGE

OR TAILGATING. REFER ELECTRICAL.

2. INSTALL PEDESTRIAN GATES AT EACH VEHICLE GATE, ENSURING THE PEDESTRIAN GATES

ARE CONSTRUCTED OF THE SAME MATERIAL AS THE FENCE SYSTEM, AND ARMED AS

DETAILED IN ITEM 1 ABOVE. ARM EACH PEDESTRIAN GATE WITH AN ELECTRIC STRIKE (WITH

COVER PLATE), DUAL-AUTHENTICATION PIV & PIN CODE PACS, AUTO-CLOSER, AND CONTACT

SENSOR WITH ANTI-PROP ALARM, ALL MONITORED BY THE SCC AND A LOCALIZED STATION

WITHIN THE CMOP (I.E., ADMINISTRATION DESK OR CMOP MANAGER). ADDITIONALLY, ENSURE

A FIXED FACIAL ANALYTICS CAMERA IS INSTALLED AT THE GATE ENTRY, TIED TO THE VA

EMPLOYEE DATABASE FOR CONFIRMATION, AS TO PREVENT UNAUTHORIZED/FORCE

CREDENTIAL USAGE OR TAILGATING. REFER ELECTRICAL.

3. BOLLARD SPACING IS 4" O.C. TYP.

GENERAL PLAN NOTES

EXISTING LANDSCAPED AREA

FENCING

PAVED AREA

EXISTING BUILDING

NEW LANDSCAPED AREA

FUTURE BUILDING

LIGHT FIXTURE REF. ELECTRICAL

E BRITANNIA DR

E H

E M

IS

P

H E

R E

L O

O P

DELIVERY/

LOGISTIC EXIT

E DESERT WALK LN

CMOP

DELIVERY

EXIT

DELIVERY/

LOGISTIC

ENTRY

EMPLOYEE

ENTRY / EXIT

EMPLOYEE

ENTRY / EXIT

ONE WAY EXIT ONLY

ONE

WAY

TRAFFIC

ONE WAY EXIT ONLY

'-4

'-0

1'

-6

F V

2.0832.092.082.12

32.03 32.02

32.04

32.03 32.02

32.07

32.05

32.03 32.06

32.02

32.08

2.13

32.12

2.08

32.02

32.07

2.12

2.15

32.11

2.12

2.16

2.17

2.18 32.1132.1132.11

32.07

26.04

FUTURE BLDG

STORAGE / ADMIN

DELIVERY

ENTRY

9'

-2

107'-4"

92'-0" 89'-4"

21 21 21 21

81010

910 10

'-0

7'-0" 20'-0" 1'-6" 32'-0"

'-0

'-1

'-1

1"

'-1 0"

'-8

6' -1

0"

'-0

113'-6"68'-5" 99'-7" 7'-5" 84'-7"

5'

-2

F V

85'-0" 85'-0" 85'-0" 57'-7"

357'-0"

'-1

0"

'-0

'-0

3'

-4

9"4'-0"

32.06

32.03 32.13

4'-0" 4'-6"

'-1

0"

32.12

32.13

370'-0" FV

32.13

26.04

26.04

26.04

26.04

26.04

26.04

32.02

32.02

32.05 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

CERTIFICATE OF AUTHORITY NO. 20013-0

EXP. 09/30/2022

CIVIL ENGINEER

H2B, INC.

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/2

/2

:5 :2

A

M

FUTURE ARCHITECTURAL SITE PLAN

ECO 19 36DRH

ISSUED FOR CONSTRUCTION

TUCSON CMOP BUILDING

ACQUISITION MINOR

03/14/2022

762-301

VA CMOP

3675 E. BRITANNIA DR.

TUCSON, ARIZONA, 85706

AS003

SPUR #: 2091.02

N

SITE PLAN LEGEND

1" = 50'-0"

FUTURE SITE PLAN1

KEYNOTE LEGEND

2.08 EXISTING FENCE TO REMAIN

2.12 EXISTING MAN GATE TO REMAIN

2.13 EXISTING LIGHTING PEDESTAL TO REMAIN

2.15 EXISTING HVAC UNITS TO REMAIN

2.16 EXISTING CONEX / HVAC EQUIP. TO REMAIN

2.17 EXISTING UPS TO REMAIN

2.18 EXISTING GENERATOR TO REMAIN

26.04 FUTURE LIGHT FIXTURE, TYP. REF. ELECTRICAL. OUT OF SCOPE

32.02 NEW FENCE TO MATCH EXISTING

32.03 GATE CONTROL ISLAND

32.04 ANTI-RAM BARRIERS ASTM F2656 M10

32.05 RETRACTABLE ANTI-RAM SYSTEM ASTM F2656 M30

32.06 NEW PEDESTRIAN GATE

32.07 30' SLIDING GATE AND TRACK

32.08 40' SLIDING GATE AND TRACK

32.09 50' SLIDING GATE AND TRACK

32.11 ANTI-RAM BARRIERS ASTM F2656 M30

32.12 FUTURE SLIDING GATE AND TRACK, OUT OF SCOPE

32.13 FUTURE FENCE TO MATCH EXISTING, OUT OF SCOPE

FOR REFERENCE ONLY

No. REVISION DESCRIPTION DATE

1 ADDENDUM 01 05/20/2022

The information on this document is preliminary or incomplete, not for urposes, or implementation.

H AI - Zone Humidity

BI - Filter Status

Elec

BO - Heating Stage 1

HP

BO - Compressor Stage 1

BO - Compressor Stage 2

BO - Reversing Valve

BI - Smoke Detector

T

AI - Discharge Air Temp

BO - Fan Start/Stop

CT

BI - Fan Status

BI - Zone Override

AI - Zone Setpoint Adjust

M

M AO - Return Air Dampers

OA

RA

N.O.

N.O.

SA

T

AI - Zone Temp

M

SEQUENCE OF OPERATIONS

HEAT PUMP (HP - TYP 18)

Run Conditions - Adminstration Areas - Scheduled:

The unit shall run according to a user definable time schedule in the following modes:

• Occupied Mode: The unit shall maintain

• A 75°F (adj.) cooling setpoint

• A 70°F (adj.) heating setpoint.

• Unoccupied Mode (night setback): The unit shall maintain

• A 85°F (adj.) cooling setpoint.

• A 55°F (adj.) heating setpoint.

Run Conditions - Pharmaceutical Areas - Scheduled:

• Occupied Mode: The unit shall maintain

• A 75°F (adj.) cooling setpoint

• A 70°F (adj.) heating setpoint.

• Unoccupied Mode (night setback): The unit shall maintain

• A 75°F (adj.) cooling setpoint.

• A 70°F (adj.) heating setpoint.

Discharge Air Temperature:

The controller shall monitor the discharge air temperature.

Alarms shall be provided as follows:

• High Discharge Air Temp: If the discharge air temperature is greater than 120°F (adj.).

• Low Discharge Air Temp: If the discharge air temperature is less than 40°F (adj.).

Fan Status:

The controller shall monitor the fan status.

Alarms shall be provided as follows:

• Fan Failure: Commanded on, but the status is off.

• Fan in Hand: Commanded off, but the status is on.

• Fan Runtime Exceeded: Fan status runtime exceeds a user definable limit (adj.).

Zone Humidity:

The controller shall monitor the zone humidity.

Alarms shall be provided as follows:

• High Zone Humidity: If the zone humidity is greater than

65% (adj.).

• Low Zone Humidity: If the zone humidity is less than 25% (adj.).

Emergency Shutdown:

The unit shall shut down and generate an alarm upon receiving an emergency shutdown signal.

Smoke Detection:

The unit shall shut down and generate an alarm upon receiving a smoke detector status.

Fan:

The fan shall run anytime the unit is commanded to run, unless shutdown on safeties.

Heating and Cooling - 2 Compressor Stages:

The controller shall measure the zone temperature and stage the compressors to maintain its setpoint. To prevent short cycling, there shall be a user definable (adj.)

delay between stages, and each stage shall have a user definable (adj.) minimum runtime. The compressor shall run subject to its own internal safeties and controls.

The heating shall be enabled whenever:

• Outside air temperature is less than 65°F (adj.).

• AND the fan status is on.

• AND the reversing valve is in heat mode.

The cooling shall be enabled whenever:

• Outside air temperature is greater than 60°F (adj.).

• AND the fan status is on.

• AND the reversing valve is in cool mode.

On mode change, the compressor shall be disabled and remain off until after the reversing valve has changed position.

Alarms shall be provided as follows:

• Compressor 1 Runtime Exceeded: Compressor 1 runtime exceeds a user definable limit (adj.).

• Compressor 2 Runtime Exceeded: Compressor 2 runtime exceeds a user definable limit (adj.).

Demand Limiting - Zone Setpoint Optimization:

To lower power consumption, the zone setpoints shall automatically relax when the facility power consumption exceeds definable thresholds. The amount of relaxation shall be individually configurable for each zone. The zone setpoints shall automatically return to their previous settings when the facility power consumption drops below the thresholds.

Zone Setpoint Adjust:

The occupant shall be able to adjust the zone temperature heating and cooling setpoints at the zone sensor.

Zone Optimal Start:

The unit shall use an optimal start algorithm for morning start-up. This algorithm shall minimize the unoccupied warm-up or cool-down period while still achieving comfort conditions by the start of scheduled occupied period.

Zone Unoccupied Override:

A timed local override control shall allow an occupant to override the schedule and place the unit into an occupied mode for an adjustable period of time. At the expiration of this time, control of the unit shall automatically return to the schedule.

Economizer:

The controller shall measure the zone temperature and modulate the mixed air dampers in sequence to maintain the zone cooling setpoint. The outside air damper shall maintain a minimum adjustable position of 20% (adj.) open whenever occupied.

The economizer shall be enabled whenever:

• Outside air temperature is at least 3°F (adj.) less than the zone temperature.

• AND the outside air temperature is less than 75°F (adj.)

The economizer shall close whenever the freezestat (if present) is on.

The outside air damper shall close and the return air damper shall open when the unit is off. If Optimal Start Up is available the mixed air damper shall operate as described in the occupied mode except that the outside air damper shall modulate to fully closed.

Minimum Outside Air Ventilation - Fixed Percentage:

The outside air dampers shall maintain a minimum position (adj.) during building occupied hours and be closed during unoccupied hours.

Supplemental Electric Heating Stage:

The controller shall measure the zone temperature and stage the heating to maintain its heating setpoint should the compressors not meet the heating demand. To prevent short cycling, the stage shall have a user definable (adj.) minimum runtime.

The heating shall be enabled whenever:

• The heat pump is in heating mode.

• AND the zone temperature is below heating setpoint.

• AND the fan is on.

Filter Status:

The controller shall monitor the filter status.

Alarms shall be provided as follows:

• Filter Change Required: Filter differential pressure exceeds a user definable limit (adj.).

NOTE:

1. FOR HPS-4A, 4B,7,9,10,11,12 THERE ARE NO SMOKE DAMPERS OR SMOKE

DETECTORS.

T

AI - Mixed Air Temp

T

AI - Outside Air Temp

T AI - Return Air Temp

H AI - Return Air Humidity th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. 20013-0 EXP. 10/10/2022

MECH ENGR REG. NO. 20013-0 EXP. 10/10/2022

ELEC ENGR REG. NO. 20013-0 EXP. 10/10/2022

CIVIL ENGINEER

H2B, INC.

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:1 :4

P

M

MECHANICAL CONTROLS

RDC 23 37JRM

ISSUED FOR CONSTRUCTION

TUCSON CMOP BUILDING

ACQUISITION MINOR

03/14/2022

762-301

VA CMOP

3675 E. BRITANNIA DR.

TUCSON, ARIZONA, 85706

M-703

LOW ZONE TEMP IF THE ZONE TEMP IS 5˚F LOWER THAN ITS SETPOINT (ADJ.) X 10 MIN.

LOW ZONE HUMIDITY IF THE ZONE HUMIDITY IS LOWER THAN ITS SETPOINT (ADJ.) X 10 MIN.

HIGH ZONE TEMP IF THE ZONE TEMP IS 5˚F HIGHER THAN ITS SETPOINT (ADJ.) X 10 MIN.

HIGH ZONE HUMIDITY IF THE ZONE HUMIDITY IS HIGHER THAN ITS SETPOINT (ADJ.) X 10 MIN.

FILTER CHANGE REQUIRED FILTER HAS BEEN IN USE FOR MORE THAN 2200 HOURS (ADJ.) OR THE FILTER D.P. EXCEEDED IT LIMIT X 1 HOUR

FAN RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.

FAN IN HAND COMMANDED OFF, BUT THE STATUS IS ON X 10 MIN.

FAN FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.

LOW DISCHARGE AIR TEMPERATURE IF THE DISCHARGE AIR TEMPERATURE IS 5˚F LESS THAN ITS SETPOINT (ADJ.) X 10 MIN.

HIGH DISCHARGE AIR TEMPERATURE IF THE DISCHARGE AIR TEMPERATURE IS 5˚F GREATER THAN ITS SETPOINT (ADJ.) X 10 MIN.

COMPRESSOR 2 RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.

COMPRESSOR 1 RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.

ALARM DESCRIPTION ALARM ALARM...

SCHEDULE X

EMERGENCY SHUTDOWN X X X

COOLING SETPOINT 55°F X X

HEATING SETPOINT N/A X X

SETPOINTS

REVERSING VALVE X X X

HEATING STAGE 1 X X X

FAN START/STOP X X X

COMPRESSOR STAGE 2 X X X

COMPRESSOR STAGE 1 X X X

ZONE OVERRIDE X X X

SMOKE DETECTOR X X X

FILTER STATUS X X X X

FAN STATUS X X X

MIXED AIR DAMPERS X X X

ZONE TEMP X X X

ZONE SETPOINT ADJUST X X

ZONE HUMIDITY X X X

DISCHARGE TEMP X X X

MIXED AIR TEMP X X X

OUTSIDE AIR TEMP X X X

AI AO BI BO SETPOINT AV BV LOOP SCHED TREND ALARM

POINTS NAME

HARDWARE POINTS SOFTWARE POINTS SHOWN ON

GRAPHIC

POINTS LIST SCHEDULE - HEAT PUMP (TYP 18)

No. REVISION DESCRIPTION DATE

NOT TO SCALE

HEAT PUMP CONTROL DIAGRAM (HP-1 THROUGH 17))1

20 36

MECHANICAL CONTROLS LEGEND

ABBREVIATIONS

AI

A

AO ANALOG OUTPUT

AFS AIRFLOW STATION

ANALOG INPUT

CHW

AV

AF

B

BAC BUILDING AUTOMATION CONTROL

BI

BV

BINARY INPUT

BINARY VIRTUAL

BUILDING PRESSURE

HW

IFB

M

ELEC

CURRENT TRANSMITTER

FRZ

ELECTRIC HEATING COIL

DX DIRECT EXPANSION

D

DD DIRECT DRIVE

GAS FURNACE

DP DIFFERENTIAL PRESSURE

EA

E

EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

ECM ELECTRONICALLY COMMUTATED MOTOR

EXHAUST FANEF

ER ENERGY RECOVERY

EWT ENTERING WATER TEMPERATURE

F

FF FINAL FILTER

FSD FIRE SMOKE DAMPER

GF GAS FURNACE

G

HC HEATING COIL

H

HW HOT WATER

HGB HOT GAS BYPASS

IFB INTEGRAL FACE AND BYPASS

I

LAT LEAVING AIR TEMPERATURE

L

LWT LEAVING WATER TEMPERATURE

HGB HOT GAS BYPASS

MAT MIXED AIR TEMPERATURE

M

MOA MINIMUM OUTSIDE AIR

NG NATURAL GAS

N

OA OUTSIDE AIR

O

OCC OCCUPANCY

OX OXYGEN

OXS OXYGEN SENSOR

PCC PRECOOLING COIL

P

PHC PREHEAT COIL

PF PREFILTER

RA RETURN AIR

R

RF

S

SF

RETURN FAN

RHC REHEAT COIL

R/E RETURN/EXHAUST

R/R RETURN/RELIEF

SA SUPPLY AIR

SUPPLY FAN

SD SMOKE DAMPER

CT

TCP TEMPERATURE CONTROL PANEL

T

TA TRANSFER AIR

TMV THERMOSTATIC MIXING VALVE

TCV TEMPERATURE CONTROL VALVE

UV ULTRAVIOLET

U

VFD VARIABLE FREQUENCY DRIVE

V

VOC VOLATILE ORGANIC COMPOUND XX XXXX

POINT NAME

M

M

PLENUM FAN

PUMP

CURRENT TRANSMITTER

H

2-WAY MODULATING

CONTROL VALVE

THERMOSTATIC MIXING VALVE

3-WAY MODULATING

CONTROL VALVE

L

POINT TYPE

H NEGATIVE SPACE DIFFERENTIAL

PRESSURE SENSOR

O

BLOWER FAN

ZONE OCCUPANCY SENSOR

M

2-POSITION PARALLEL BLADE

DAMPER

ZONE TEMPERATURE SENSOR

T

M

2-POSITION OPPOSED BLADE

DAMPER ZONE

M

VAV ATU MODULATING DAMPER

BACKDRAFT DAMPER

P

SD

SMOKE DAMPER

MODULATING PARALLEL BLADE

DAMPER

H

SUPPLY AIR DUCT STATIC PRESSURE

SENSOR

L

PIPING

T

AQUASTAT

FLOW METER

PRESSURE SENSOR

TEMPERATURE SENSOR

H

M

M

MODULATING OPPOSED BLADE

DAMPER

L

RETURN/EXHAUST AIR DUCT STATIC

PRESSURE SENSOR

H L

HUMIDIFIER DISPERSION GRID

H

DIFFERENTIAL PRESSURE SENSOR

DAMPER POSITION INDICATOR

HUMIDITY SENSOR

FREEZESTAT

T

CC COOLING COIL

C

CHW CHILLED WATER

CP CIRCULATING PUMP

CT

HOT WATER INTEGRAL FACE AND

BYPASS COIL TEMPERATURE SENSOR

BO BINARY OUTPUT

BP

BPC BUILDING PRESSURE CONTROL

HW

HOT WATER COIL

SD

SMOKE DETECTOR

ANALOG VIRTUAL

AFTER FILTER

AFCV AIRFLOW CONTROL VALVE

AHU AIR HANDLING UNIT

DX

DIRECT EXPANSION COIL

CHILLED WATER COIL AFS AIRFLOW STATION

AIRFLOW SENSOR

SYMBOLS

EQUIPMENT SENSORS &

DEVICESDUCTWORK

FILTER ZONE HUMIDITY SENSOR

H

L POSITIVE SPACE DIFFERENTIAL

PRESSURE SENSOR

B-ASC

NEW BACNET

PORTABLE

OPERATOR

TERMINAL

NEW BACNET ENGINEERING

CONTROL CENTER (B-AWS)

NEW

BACNET

NETWORK

B-ASC B-ASC

B-ASC

B-ASC

B-ASC

B-ASC

B-ASC

B-ASC

B-AACB-AAC B-AAC

BACNET

BUILDING

CONTROLLER

(B-BC)

ETHERNET COMMUNICATION

NOTES:

1. REPLACE EXISTING ECC WITH NEW BACNET (B-AWS) ENGINEERING

CONTROL CENTER.

2. REPLACE ALL EXISTING CONTROLLERS WITH NEW BACNET CONTROLLERS.

3. INSTALL NEW BACNET COMMUNICATION NETWORK.

4. INSTALL MULTIPLE BUILDING CONTROLLERS (B-BC) AS REQUIRED.

5. INSTALL NEW CONTROLLERS (B-AAC, B-ASC) AS REQUIRED.

6. PROVIDE NEW OPERATORS TERMINAL. COORDINATE LOCATION WITH VA.

7. PROVIDE STORAGE CAPACTY FOR 30 DAYS.

MSTP COMMUNICATION

(TYPICAL)

BACNET

BUILDING

CONTROLLER

(B-BC)

BACNET

BUILDING

CONTROLLER

(B-BC)

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. 20013-0 EXP. 10/10/2022

MECH ENGR REG. NO. 20013-0 EXP. 10/10/2022

ELEC ENGR REG. NO. 20013-0 EXP. 10/10/2022

CIVIL ENGINEER

H2B, INC.

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:1 :4

P

M

MECHANICAL CONTROLS & LEGEND

RDC 21 37JRM

ISSUED FOR CONSTRUCTION

TUCSON CMOP BUILDING

ACQUISITION MINOR

03/14/2022

762-301

VA CMOP

3675 E. BRITANNIA DR.

TUCSON, ARIZONA, 85706

M-701

4. DIVISION 23 CONTRACTOR TO PROVIDE ROOM AIR BALANCE WHERE POSSIBLE. AIR BALANCE SHALL BE NUETRAL FOR NON-CRITICAL SPACES NOT SHOWN IN SCHEDULE.

3. ZONE LEVEL SET POINT CONDITIONS SHALL RESET TO UNOCCUPIED UNTIL PATIENT ROOM SETPOINTS ARE SATISFIED.

2. ZONE LEVEL SET POINT CONDITIONS SHALL BE AS SCHEDULED UNLESS OTHERWISE SCHEDULED OR NOTED FOR ROOM SPECIFIC SPACE CONDITIONS.

1. ZONE LEVEL OCCUPANCY HOUR SCHEDULE SHALL BE PER BUILDING OPERATING HOURS UNLESS OTHERWISE SCHEDULED.

NOTES:

SUNDAY OT

SATURDAY OT

MONDAY - FRIDAY 5:30 a.m. - 12:30 a.m

BUILDING OPERATING HOURS (VERIFY WITH STATION)

COOLING 0.4% (DB / MCWB) 105.8 ˚FDb / 66 ˚FWb

HUMIDIFICATION 99.6% (DP / HR / MCDB) -1 ˚F / 5.7 / 12.3 ˚F

HEATING 99.6% (F DB) 31.8 ˚F

ASHRAE CLIMATE ZONE 2

WEATHER STATION 2017 ASHRAE CLIMATE DATA / TUCSCON INTERNATIONAL AP, AZ

CLIMATE CONDITIONS

PROJECT DESIGN CONDITIONS

1. SEE EQUIPMENT POINT LISTS FOR EQUIPMENT SPECIFIC TRENDING REQUIREMENTS.

NOTES:

CALC 1 HOUR 30 DAYS N/A

BO CHANGE OF VALUE 24 HOURS 3 DAYS

AO 15 MIN. 24 HOURS 3 DAYS

BI CHANGE OF VALUE 24 HOURS 3 DAYS

AI 15 MIN. 24 HOURS 3 DAYS

POINT NAME TREND INTERVAL

OPERATIONAL TREND

DURATION

TESTING TREND

DURATION

POINTS LIST - STANDARD TRENDING INTERVALS

No. REVISION DESCRIPTION DATE

NOT TO SCALE

BACNET CONTROLLER DIAGRAM1

NOTES:

1. ALL EXISTING THERMOSTATS SHALL BE REMOVED AND REPLACED WITH A NEW PROGRAMMABLE THERMOSTAT WITH .

HUMIDIY CONTROL. THERMOSTAT SHALL BE CONNECTED TO NEW BMS. SEE SHEETS M-702 THROUGH M-706.

2. ALL EXISTING MANUAL OUTSIDE AIR DAMPERS SHALL BE REMOVED AND REPLACED WITH MOTORIZED OUTSIDE AIR DAMPERS. MECHANICAL CONTRACTOR SHALL FIELD VERIFY SIZE OF EXISTING DAMPERS BEFORE

BEGINNING CONSTRUCTION.

21 36

Elec

BO - Heating Stage 1

DX

BO - Cooling Stage 1

BO - Cooling Stage 2

T

AI - Return Air Temp

AI - Mixed Air Temp

T

BI - Supply Air Smoke Detector

T

AI - Supply Air Temp

M

CT

Starter BO - Supply Fan Start/Stop

BI - Supply Fan Status

SF

M N.O.

N.O.

BI - Zone Override

AI - Zone Setpoint Adjust

SA

RA

T AI - Zone Temp

OA

SEQUENCE OF OPERATIONS

ROOFTOP UNIT - RTU (TYP OF 2)

Run Conditions - Adminstration Areas - Scheduled:

The unit shall run according to a user definable time schedule in the following modes:

• Occupied Mode: The unit shall maintain

• A 75°F (adj.) cooling setpoint

• A 70°F (adj.) heating setpoint.

• Unoccupied Mode (night setback): The unit shall maintain

• A 85°F (adj.) cooling setpoint.

• A 55°F (adj.) heating setpoint.

Run Conditions - Pharmaceutical Areas - Scheduled:

• Occupied Mode: The unit shall maintain

• A 75°F (adj.) cooling setpoint

• A 70°F (adj.) heating setpoint.

• Unoccupied Mode (night setback): The unit shall maintain

• A 75°F (adj.) cooling setpoint.

• A 70°F (adj.) heating setpoint.

Alarms shall be provided as follows:

• High Zone Temp: If the zone temperature is greater than the cooling setpoint by a user definable amount (adj.).

• Low Zone Temp: If the zone temperature is less than the heating setpoint by a user definable amount (adj.).

Demand Limiting - Zone Setpoint Optimization:

To lower power consumption, the zone setpoints shall automatically relax when the facility power consumption exceeds definable thresholds. The amount of relaxation shall be individually configurable for each zone. The zone setpoints shall automatically return to their previous settings when the facility power consumption drops below the thresholds.

Zone Setpoint Adjust:

The occupant shall be able to adjust the zone temperature heating and cooling setpoints at the zone sensor.

Zone Optimal Start:

The unit shall use an optimal start algorithm for morning start-up. This algorithm shall minimize the unoccupied warm-up or cool-down period while still achieving comfort conditions by the start of scheduled occupied period.

Zone Unoccupied Override:

A timed local override control shall allow an occupant to override the schedule and place the unit into an occupied mode for an adjustable period of time. At the expiration of this time, control of the unit shall automatically return to the schedule.

Minimum Outside Air Ventilation - Fixed Percentage:

The outside air dampers shall maintain a minimum position (adj.) during building occupied hours and be closed during unoccupied hours.

Mixed Air Temperature:

The controller shall monitor the mixed air temperature and use as required for economizer control (if present) or preheating control (if present).

Alarms shall be provided as follows:

• High Mixed Air Temp: If the mixed air temperature is greater than 90°F

(adj.).

• Low Mixed Air Temp: If the mixed air temperature is less than 45°F (adj.).

Freeze Protection:

The unit shall shut down and generate an alarm upon receiving a freezestat status.

Supply Air Smoke Detection:

The unit shall shut down and generate an alarm upon receiving a supply air smoke detector status.

Supply Fan:

The supply fan shall run anytime the unit is commanded to run, unless shutdown on safeties. To prevent short cycling, the supply fan shall have a user definable (adj.)

minimum runtime.

Alarms shall be provided as follows:

• Supply Fan Failure: Commanded on, but the status is off.

• Supply Fan in Hand: Commanded off, but the status is on.

• Supply Fan Runtime Exceeded: Status runtime exceeds a user definable limit (adj.).

Cooling Stages:

The controller shall measure the zone temperature and stage the cooling to maintain its cooling setpoint. To prevent short cycling, there shall be a user definable (adj.)

delay between stages, and each stage shall have a user definable (adj.) minimum runtime.

The cooling shall be enabled whenever:

• Outside air temperature is greater than 60°F (adj.).

• AND the economizer (if present) is disabled or fully open.

• AND the zone temperature is above cooling setpoint.

• AND the supply fan status is on.

• AND the heating is not active.

Electric Heating Stage:

The controller shall measure the zone temperature and stage the heating to maintain its heating setpoint. To prevent short cycling, the stage shall have a user definable (adj.) minimum runtime.

The heating shall be enabled whenever:

• Outside air temperature is less than 65°F (adj.).

• AND the zone temperature is below heating setpoint.

• AND the supply fan status is on.

• AND the cooling is not active.

Return Air Humidity:

The controller shall monitor the return air humidity and use as required for economizer control (if present) or humidity control (if present).

Alarms shall be provided as follows:

• High Return Air Humidity: If the return air humidity is greater than 65% (adj.).

• Low Return Air Humidity: If the return air humidity is less than 25% (adj.).

Return Air Temperature:

The controller shall monitor the return air temperature and use as required for economizer control (if present).

Alarms shall be provided as follows:

• High Return Air Temp: If the return air temperature is greater than 90°

F (adj.).

• Low Return Air Temp: If the return air temperature is less than 45°F (adj.).

Supply Air Temperature:

The controller shall monitor the supply air temperature.

Alarms shall be provided as follows:

• High Supply Air Temp: If the supply air temperature is greater than 120°

F (adj.).

• Low Supply Air Temp: If the supply air temperature is less than 45°F (adj.).

AI - Outside Air Temp

T

H

AI - Return Air Humidity

BI - Filter Status th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. 20013-0 EXP. 10/10/2022

MECH ENGR REG. NO. 20013-0 EXP. 10/10/2022

ELEC ENGR REG. NO. 20013-0 EXP. 10/10/2022

CIVIL ENGINEER

H2B, INC.

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:1 :4

P

M

MECHANICAL CONTROLS

RDC 22 37JRM

ISSUED FOR CONSTRUCTION

TUCSON CMOP BUILDING

ACQUISITION MINOR

03/14/2022

762-301

VA CMOP

3675 E. BRITANNIA DR.

TUCSON, ARIZONA, 85706

M-702

HIGH ZONE TEMP IF THE ZONE TEMPERATURE IS 5˚F GREATER THAN ITS SETPOINT (ADJ.) X 10 MIN.

COMPRESSOR RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.

LOW RETURN AIR HUMIDITY IF THE RETURN AIR HUMIDITY IS LOWER THAN X. X 10 MIN.

HIGH RETURN AIR HUMIDITY IF THE RETURN AIR HUMIDITY IS GREATER THAN X. X 10 MIN.

FILTER CHANGE REQUIRED FILTER HAS BEEN IN USE FOR MORE THAN 2200 HOURS (ADJ.) OR THE FILTER D.P. EXCEEDED IT LIMIT X 1 HOUR

SUPPLY FAN RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.

SUPPLY FAN IN HAND COMMANDED OFF, BUT THE STATUS IS ON X 10 MIN.

SUPPLY FAN FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.

LOW RETURN AIR TEMPERATURE IF THE RETURN AIR TEMPERATURE IS LESS THAN 45˚F (ADJ.) X 10 MIN.

HIGH RETURN AIR TEMPERATURE IF THE RETURN AIR TEMPERATURE IS GREATER THAN 90˚F (ADJ.) X 10 MIN.

LOW SUPPLY AIR TEMPERATURE IF THE SUPPLY AIR TEMPERATURE IS 5˚F LESS THAN ITS SETPOINT (ADJ.) X 10 MIN.

HIGH SUPPLY AIR TEMPERATURE IF THE SUPPLY AIR TEMPERATURE IS 5˚F GREATER THAN ITS SETPOINT (ADJ.) X 10 MIN.

LOW MIXED AIR TEMPERATURE IF THE MIXED AIR TEMPERATURE IS LESS THAN 45˚F (ADJ.) X 10 MIN.

HIGH MIXED AIR TEMPERATURE IF THE MIXED AIR TEMPERATURE IS GREATER THAN 90˚F (ADJ.) X 10 MIN.

ALARM DESCRIPTION ALARM ALARM...

COOLING SETPOINT 55°F X X

HEATING SETPOINT X X

SCHEDULE N/A X X

SETPOINTS

RA TEMP X X X

RETURN AIR

HEATING STAGE 1 X X X

COOLING STAGE 2 X X X

COOLING STAGE 1 X X X X

ZONE SETPOINT ADJUST X X

ZONE OVERRIDE X X X

ZONE TEMP X X X

FREEZESTAT X X X

SA TEMP X X X

SA SMOKE DETECTOR X X X X

SF START/STOP X X X

SF STATUS X X X

SUPPLY AIR

MIXED AIR TEMP X X X

OUTSIDE AIR TEMP X X X

MIXED/OUTSIDE AIR

AI AO BI BO SETPOINT AV BV LOOP SCHED TREND ALARM

POINTS NAME

HARDWARE POINTS SOFTWARE POINTS SHOWN ON

GRAPHIC

POINTS LIST SCHEDULE - PACKAGED ROOFTOP UNIT (RTU)

No. REVISION DESCRIPTION DATE

NOT TO SCALE

ROOFTOP UNIT CONTROLS DIAGRAM (RTU-1,2))1

22 36

SEQUENCE OF OPERATIONS

EXHAUST FAN (EF-X)

GENERAL DESCRIPTION

The exhaust fan provides general exhaust ventilation to the conditioned space(s).

OPERATING MODES

OCCUPIED MODE

The exhaust fan shall be in occupied mode per the project design conditions schedule shown on sheet M-701.

UNOCCUPIED MODE

The exhaust fan shall be in unoccupied mode for all periods not included in the occupied hours of operation.

COMPONENT CONTROL LOOPS

EXHAUST FAN – ON/OFF

• When the HOA switch is in hand position, the supply fan shall operate manually by the operator at the user interface of the drive.

• When the HOA switch is in off position, the fan shall be off.

• When the HOA switch is in auto position, the supply fan shall operate subject to the unit enable signal, and unit operating modes.

OCCUPIED MODE:

• The exhaust fan shall be commanded to run at constant speed.

UNOCCUPIED MODE:

The exhaust fan shall be off.

EA

M

CT

STARTER

BDD

BI

BO

EF STATUS

EF START/STOP

H AI - Zone Humidity

BI - Filter Status

H L

BI - Smoke Detector

DX

BO - Cooling Stage 1

BO - Cooling Stage 2

BO - Cooling Stage 3

BO - Cooling Stage 4

BI - Fan Status

CT

BO - Fan Start/Stop

T

AI - Discharge Air Temp

BI - Zone Override

AI - Zone Setpoint Adjust

RA

T

AI - Zone Temp

DA

M

COMPUTER ROOM AIR CONDITIONING UNIT - (CRAC - TYP 6)

Run Conditions - Scheduled:

The unit shall maintain 70°F 24/7.

Alarms shall be provided as follows:

• High Zone Temp: If the zone temperature is greater than the cooling setpoint by a user definable amount (adj.).

Zone Setpoint Adjust:

The occupant shall be able to adjust the zone temperature heating and cooling setpoints at the zone sensor.

Zone Unoccupied Override:

A timed local override control shall allow an occupant to override the schedule and place the unit into an occupied mode for an adjustable period of time. At the expiration of this time, control of the unit shall automatically return to the schedule.

Emergency Shutdown:

The unit shall shut down and generate an alarm upon receiving an emergency shutdown signal.

Smoke Detection:

The unit shall shut down and generate an alarm upon receiving a smoke detector status.

Fan:

The fan shall run anytime the unit is commanded to run, unless shutdown on safeties.

Cooling Stages:

The controller shall measure the zone temperature and stage the cooling to maintain its cooling setpoint. To prevent short cycling, there shall be a user definable (adj.) delay between stages, and each stage shall have a user definable (adj.) minimum runtime.

The cooling shall be enabled whenever:

• The zone temperature is above cooling setpoint.

• AND the fan is on.

Filter Status:

The controller shall monitor the filter status.

Alarms shall be provided as follows:

• Filter Change Required: Filter differential pressure exceeds a user definable limit (adj.).

Discharge Air Temperature:

The controller shall monitor the discharge air temperature.

Alarms shall be provided as follows:

• High Discharge Air Temp: If the discharge air temperature is greater than 70°F (adj.).

Fan Status:

The controller shall monitor the fan status.

Alarms shall be provided as follows:

• Fan Failure: Commanded on, but the status is off.

• Fan in Hand: Commanded off, but the status is on.

• Fan Runtime Exceeded: Fan status runtime exceeds a user definable limit (adj.).

Zone Humidity:

The controller shall monitor the zone humidity.

Alarms shall be provided as follows:

• High Zone Humidity: If the zone humidity is greater than

60% (adj.).

• Low Zone Humidity: If the zone humidity is less than

35% (adj.).

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. 20013-0 EXP. 10/10/2022

MECH ENGR REG. NO. 20013-0 EXP. 10/10/2022

ELEC ENGR REG. NO. 20013-0 EXP. 10/10/2022

CIVIL ENGINEER

H2B, INC.

1225 NORTH LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:1 :4

P

M

MECHANICAL CONTROLS

RDC 24 37JRM

ISSUED FOR CONSTRUCTION

TUCSON CMOP BUILDING

ACQUISITION MINOR

03/14/2022

762-301

VA CMOP

3675 E. BRITANNIA DR.

TUCSON, ARIZONA, 85706

M-704

NOT TO SCALE

EXHAUST FAN CONTROL DIAGRAM (EF - TYP 2)1

No. REVISION DESCRIPTION DATE

LOW ZONE HUMIDITY IF THE HUMIDITY IS 5% LOWER THAN SETPOINT (ADJ.) X 10 MIN.

HIGH ZONE TEMP IF THE ZONE TEMP IS 5˚F HIGHER THAN THE SETPOINT (ADJ.) X 10 MIN.

HIGH ZONE HUMIDITY IF THE HUMIDITY IS 5% GREATER THAN SETPOINT (ADJ.) X 10 MIN.

FAN RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.

FAN FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.

FAN IN HAND IF THE SMOKE DETECTOR IS ACTIVATED X 5 MIN.

FILTER CHANGE REQUIRED IF THE FILTER HAS BEEN IS USE FOR MORE THAN 2200 HOURS (ADJ.) OR THE FILTER D.P. EXCEEDS ITS LIMIT X 5 MIN.

COMPRESSOR RUNTIME EXCEEDED STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.) X 10 MIN.

ALARM DESCRIPTION ALARM ALARM...

SCHEDULE X

EMERGENCY SHUTDOWN X X X

COOLING SETPOINT X X X

FAN START/STOP X X X

COOLING STAGE 4 X X X

COOLING STAGE 3 X X X

COOLING STAGE 2 X X X

COOLING STAGE 1 X X X

ZONE OVERRIDE X X X

SMOKE DETECTOR X 55 X X X

FILTER STATUS X N/A X X X

FAN STATUS X X X

ZONE TEMP X X X

ZONE SETPOINT ADJUST X X X

ZONE HUMIDITY X X X

DISCHARGE AIR TEMP X X X

AI AO BI BO SETPOINT AV BV LOOP SCHED TREND ALARM

POINTS NAME

HARDWARE POINTS SOFTWARE POINTS SHOWN ON

GRAPHIC

POINTS LIST SCHEDULE - COMPUTER ROOM AIR CONDITIONER (CRAC)

1. SEE STANDARD TRENDING POINTS LIST SCHEDULE ON SHEET M-701 FOR APPLICABLE TREND INTERVALS.

NOTES:

EF RUNTIME EXCEEDED FAN RUNTIME EXCEEDS A USER DEFINABLE LIMIT X 10 MIN.

EF IN HAND COMMANDED OFF, BUT THE STATUS IS ON X 10 MIN.

EF FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.

EXHAUST AIR DAMPER IN HAND COMMANDED CLOSED, BUT THE STATUS IS OPEN X 10 MIN.

EXHAUST AIR DAMPER FAILURE COMMANDED OPEN, BUT THE STATUS IS CLOSED X 10 MIN.

ALARMS DESCRIPTION ALARM ALARM DELAY

EF START/STOP X X X

EF STATUS X X X

EXHAUST FAN

AI AO BI BO AV BV LOOP SCHED TREND ALARM

POINTS NAME

HARDWARE POINTS SOFTWARE POINTS SHOWN ON

GRAPHIC

POINTS LIST SCHEDULE - GENERAL EXHAUST FAN (EF-X)

NOT TO SCALE

COMPUTER ROOM AIR CONDITIONER (SERVER ROOM, UPS ROOM TELEPHONE ROOM)2

23 36

Elec

BO - Heating Stage 1

DX

BO - Cooling Stage 1

BO - Cooling Stage 2

T

AI - Return Air Temp

AI - Mixed Air Temp

T

BI - Supply Air Smoke Detector

H

AI - Return Air Humidity

T

AI - Supply Air Temp

M

CT

Starter BO - Supply Fan Start/Stop

BI - Supply Fan Status

SF

AO - Mixed Air Dampers

M

M N.O.

N.C.

BI - Zone Override

AI - Zone Setpoint Adjust

SA

RA

T AI - Zone Temp

OA

SEQUENCE OF OPERATIONS

AIR HANDLING UNIT (AHU-1)

Run Conditions - Scheduled:

The unit shall run according to a standard room design temperature setting.

Alarms shall be provided as follows:

• High Zone Temp: If the zone temperature is greater than the cooling setpoint by a user definable amount (adj.).

• Low Zone Temp: If the zone temperature is less than the heating setpoint by a user definable amount (adj.).

Demand Limiting - Zone Setpoint Optimization:

To lower power consumption, the zone setpoints shall automatically relax when the facility power consumption exceeds definable thresholds. The amount of relaxation shall be individually configurable for each zone. The zone setpoints shall automatically return to their previous settings when the facility power consumption drops below the thresholds.

Zone Setpoint Adjust:

The occupant shall be able to adjust the zone temperature heating and cooling setpoints at the zone sensor.

Zone Optimal Start:

The unit shall use an optimal start algorithm for morning start-up. This algorithm shall minimize the unoccupied warm-up or cool-down period while still achieving comfort conditions by the start of scheduled occupied period.

Zone Unoccupied Override:

A timed local override control shall allow an occupant to override the schedule and place the unit into an occupied mode for an adjustable period of time. At the expiration of this time, control of the unit shall automatically return to the schedule.

Freeze Protection:

The unit shall shut down and generate an alarm upon receiving a freezestat status.

Supply Air Smoke Detection:

The unit shall shut down and generate an alarm upon receiving a supply air smoke detector status.

Economizer:

The controller shall measure the zone temperature and modulate the economizer dampers in sequence to maintain a setpoint 2°F less than the zone cooling setpoint.

The outside air dampers shall maintain a minimum adjustable position of 20% (adj.)

open whenever occupied.

The economizer shall be enabled whenever:

• Outside air temperature is less than 65°F (adj.).

• AND the outside air temperature is less than the return air temperature.

• AND the supply fan status is on.

The economizer shall close whenever:

• Mixed air temperature drops from 45°F to 40°F (adj.).

• OR on loss of supply fan status.

• OR the freezestat (if present) is on.

The outside air damper shall close and the return air damper shall open when the unit is off. If Optimal Start Up is available, the mixed air damper shall operate as described in the occupied mode except that the outside air damper shall modulate to fully closed.

Minimum Outside Air Ventilation - Fixed Percentage:

The outside air dampers shall maintain a minimum position (adj.) during building occupied hours and be closed during unoccupied hours.

Mixed Air Temperature:

The controller shall monitor the mixed air temperature and use as required for economizer control (if present) or preheating control (if present).

Alarms shall be provided as follows:

• High Mixed Air Temp: If the mixed air temperature is greater than 90°F

(adj.).

• Low Mixed Air Temp: If the mixed air temperature is less than 45°F (adj.).

Supply Fan:

The supply fan shall run anytime the unit is commanded to run, unless shutdown on safeties. To prevent short cycling, the supply fan shall have a user definable (adj.)

minimum runtime.

Alarms shall be provided as follows:

• Supply Fan Failure: Commanded on, but the status is off.

• Supply Fan in Hand: Commanded off, but the status is on.

• Supply Fan Runtime Exceeded: Status runtime exceeds a user definable limit (adj.).

Cooling Stages:

The controller shall measure the zone temperature and stage the cooling to maintain its cooling setpoint. To prevent short cycling, there shall be a user definable (adj.)

delay between stages, and each stage shall have a user definable (adj.) minimum runtime.

The cooling shall be enabled whenever:

• Outside air temperature is greater than 60°F (adj.).

• AND the economizer (if present) is disabled or fully open.

• AND the zone temperature is above cooling setpoint.

• AND the supply fan status is on.

• AND the heating is not active.

Electric Heating Stage:

The controller shall measure the zone temperature and stage the heating to maintain its heating setpoint. To prevent short cycling, the stage shall have a user definable (adj.) minimum runtime.

The heating shall be enabled whenever:

• Outside air temperature is less than 65°F (adj.).

• AND the zone temperature is below heating setpoint.

• AND the supply fan status is on.

• AND the cooling is not active.

Return Air Humidity:

The controller shall monitor the return air humidity and use as required for economizer control (if present) or humidity control (if…