Attachment 3 - 663A4-24-203 -REPLACE HVAC HP3 - DRAWINGS.pdf

PDF 24 MB Posted

Attached to
Y1DA--Construction Project 663A4-24-203 Replace HVAC HP3, Bldg. 19 Federal contract opportunity
Solicitation number
36C26024R0082
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 20

About this file

This document is an attachment for a federal solicitation to replace an HVAC system at Building 19 (Solicitation Number: 36C26024R0082). The acquisition will use best value tradeoff source selection procedures and is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSBs).

The key details are: the project is to Replace HVAC HP3 at Building 19; proposals are due by September 10, 2024 at 11:00 AM PST; the contract will be a Firm-Fixed-Price construction contract; the technical proposal will be evaluated on the Offeror's technical approach, key personnel qualifications, and past performance; and the price proposal will be evaluated for reasonableness. Offerors must provide a minimum of 2 and maximum of 5 relevant past performance projects completed within the last 7 years.

View the file

Other files for this federal contract opportunity

Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DIMENSION TO FACE OF

FRAMING, FACE OF

CONCRETE, GRID

LINE, OR AS NOTED.

CLEAR DIMENSION TO

FINISH FACE OR AS NOTED

SURFACE SLOPE

NORTH ARROW

PROJECT NORTH

(SEE CIVIL FOR TRUE

NORTH)

DRAWING REVISION NEW SPOT ELEV

WINDOW TYPE -

REF WINDOW SCH

DOOR TAG

WINDOW TAG

CALLOUT

DRAWING NUMBER

DRAWING NUMBER

EXTERIOR ELEVATION

DOOR NUMBER -

REF DOOR SCH

SHEET NUMBER

EXISTING SPOT ELEV

ELEVATION TAG

KEYNOTE

BUILDING SECTION

WALL SECTION

SHEET NUMBER

ROOM TAG

(E) 98.75'

INTERIOR ELEVATION

0' - 1 1/4"

0' - 1 1/4"

A101

SIM

A101

SIM

DRAWING NUMBER

SHEET NUMBER

98.75'

ROOM NUMBER

1/4:12

SLOPE

Room name

150 SF

SYMBOLS AND FILL PATTERNS

EARTH

GRAVEL

ASPHALT

METAL - STEEL

MASONRY - CONCRETE BLOCK

WOOD - FINISH

*WOOD - CONTINUOUS

INSULATION - BATT

INSULATION - RIGID

INSULATION - ACOUSTICAL

WOOD - PLYWOOD

GYPSUM BOARD

GLASS

WOOD - PARTICLE BOARD

METAL - ALUMINUM

CONCRETE

MASONRY - BRICK

SAND

*WOOD - BLOCKING

INSULATION - SEMI

RIGID

1t

A101

SIM

A3.00

A3.00

FINISH TAG

A11

AC

GROUP

ASSEMBLY

STUD SIZE

MODIFIER

WALL TAG

Name Elevation

CEILING HEIGHT ABOVE

FINISHED FLOOR- ALL

CEILINGS 9'-0" UNLESS

OTHERWISE NOTED.

CEILING MATERIAL

CEILING TAG

1t 9'-0"

A-1

PROJECT CONTACTS

VA PUGET SOUND HEALTH CARE SYSTEM

AMERICAN LAKE DIVISION

9600 VETERANS DRIVE, TACOMA, WA 98493

Owner:

Architect:

Mechanical/ Electrical Engineers

GENERAL NOTES

CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING WITH

THE WORK.

DIMENSIONS TAKE PRECEDENCE OVER DRAWINGS. DO NOT SCALE DRAWINGS. NOTIFY THE ARCHITECT

OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH THE WORK.

CONTRACTOR IS RESPONSIBLE FOR CONSTRUCTION MEANS AND METHODS.

CONTRACTOR IS RESPONSIBLE FOR VERIFICATION AND COORDINATION OF SUBCONTRACTOR'S WORK, COMPLIANCE WITH THE DRAWINGS AND SPECIFICATIONS, ACCURATE LOCATION OF STRUCTURAL

MEMBERS, AND OPENINGS FOR MECHANICAL, ELECTRICAL, AND MISCELLANEOUS EQUIPMENT.

CONTRACTOR SHALL VERIFY DIMENSIONS AND CLEARANCES FROM MANUFACTURER PRIOR TO THE

CONSTRUCTION AND INSTALLATION OF ALL EQUIPMENT, FURNISHINGS, AND ACCESSORIES.

CONTRACTOR IS RESPONSIBLE FOR THE COMPLETE SECURITY OF THE SITE DURING CONSTRUCTION

AND UNTIL PROJECT COMPLETION.

CONTRACTOR SHALL LOCATE AND PROTECT EXISTING UTILITIES, WHETHER INDICATED IN DRAWINGS OR

NOT.

SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL ELECTRICAL AND EQUIPMENT

INFORMATION.

1.

2.

3.

4.

5.

6.

7.

8.

x x x x x x x x x x x x x xx x xx x x x x x x x x x x x x x x x x xx x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x

N

MAIN PARKING

1662 16

M U S S E R

C T.

VETERANS DR.

T3

T5 T100

92 C

HA

SE

L N.

MU

SS

ER

A

VE

3E N G

LE

W A Y

8 141

CHASE DR.

T98

E N G

LE

W A Y

E N G

LE

C T.

T97

T92

T2

T1

VETERANS DR.

x x x x x x x x x x x x x x x x x x x x x x x x x x x x

--- NONE

& AND

@ AT

± APPROXIMATELY

CENTERLINE

Ø DIAMETER

# NUMBER

" INCH(ES)

' FOOT (FEET)

ANGLE

PERPENDICULAR

PLATE OR PROPERTY LINE

A

ACOUS ACOUSTICAL

A.D. AREA DRAIN

ADJ ADJUSTABLE

AFF ABOVE FINISH FLOOR

AGGR AGGREGATE

AL ALUMINUM

APPROX APPROXIMATE

ARCH ARCHITECTURAL

ASB ASBETOS

ASPH ASPHALT

B

BD BOARD

BITUM BITUMINOUS

BLDG BUILDING

BLK BLOCK

BLKG BLOCKING

BM BEAM

BOT BOTTOM

BR BUMPER RAIL

C

CAB CABINET

C.B. CATCH BASIN

CER CERAMIC

C.I. CAST IRON

CG CORNER GUARD

CGF CORNER GUARD FULL HEIGHT

CHR CHAIR RAIL

CLG CEILING

CLKG CAULKING

CLO CLOSET

CLR CLEAR

C.O. CASED OPENING

COL COLUMN

CONC CONCRETE

CONN CONNECTION

CONSTR CONSTRUCTION

CONT CONTINUOUS

CORR CORRIDOR

CTSK COUNTERSUNK

CNTR COUNTER

D

DBL DOUBLE

DEPT DEPARTMENT

D.F. DRINKING FOUNTAIN

DET DETAIL

DIA DIAMETER

DIM DIMENSION

DISP DISPENSER

DN DOWN

D.O. DOOR OPENING

DR DOOR

DWR DRAWER

DS DOWNSPOUT

D.S.P. DRY STANDPIPE

DWG DRAWING

E

E EAST

(E) EXISTING

EA EACH

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

EMER EMERGENCY

ENCL ENCLOSURE

EP ELECTRICAL PANEL

ABBREVIATIONS

EQ EQUAL

EQUT EQUIPMENT

EWC ELECTRIC WATER COOLER

EXST EXISTING

EXPO EXPOSED

EXT EXTERIOR

F.A. FIRE ALARM

F.B. FLAT BAR

F.D. FLOOR DRAIN

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FHC FIRE HOSE CABINET

FIN FINISH

FL FLOOR

FLOUR FLOURESCENT

F.O.C. FACE OF CONCRETE

F.O.F. FACE OF FINISH

F.O.S. FACE OF STUDS

FPRF FIREPROOF

FT FOOT OR FEET

FTG FOOTING

FURR FURRING

FUT FUTURE

G

GA GAUGE

GALV GALVANIZED

GB GRAB BAR

GL GLASS

GND GROUND

GR GRADE

GYP GYPSUM

H

H.B. HOSE BIB

HC HOLLOW CORE

HDWD HARDWOOD

HDWE HARDWARE

HM HOLLOW METAL

HORIZ HORIZONTAL

HR HOUR

HR-E HANDRAIL, EXISTING

HR-ME HANDRAIL, MATCH EXISTING

HR-1 HANDRAIL, NEW

HGT HEIGHT

I

I.D. INSIDE DIAMETER

INSUL INSULATION

INT INTERIOR

J

JAN JANITOR

JT JOINT

K

KIT KITCHEN

L

LAB LABORATORY

LAM LAMINATE

LAV LAVATORY

LT LIGHT

M

MAX MAXIMUM

M.C. MEDICINE CABINET

MECH MECHANICAL

MEMB MEMBRANE

MET METAL

MFR MANUFACTURER

M.H. MANHOLE

MIN MINIMUM

MIR MIRROR

MISC MISCELLANEOUS

M.O. MASONRY OPENING

MTD MOUNTED

MUL MULLION

N

N NORTH

(N) NEW

N.I.C. NOT IN CONTRACT

NO. NUMBER

NOM NOMINAL

NTS NOT TO SCALE

O

O.A. OVERALL

O.C. ON CENTER

O.D. OUTSIDE DIAMETER

OFCI OWNER FURNISHED, CONTRACTOR INSTALLED

OFOI OWNER FURNISHED, OWNER INSTALLED

OFF OFFICE

OPNG OPENING

OPP OPPOSITE

ORD OVERFLOW ROOF DRAIN

Q

Q.T. QUARRY TILE

R

R RISER

(R) RELOCATE

RAD RADIUS

RD ROOF DRAIN

REF REFERENCE

REFR REFRIGERATOR

RGTR REGISTER

REQ REQUIRED

RESIL RESILIENT

RM ROOM

R.O. ROUGH OPENING

R.W.L. RAIN WATER LEADER

S

S SOUTH

SC SOLID CORE

S.C.D SEAT COVER DISPENSOR

SCHED SCHEDULE

S.D. SOAP DISPENSER

SECT SECTION

SH SHELF

SHC SHOWER CURTAIN

SHR SHOWER

SHT SHEET

SIM SIMILAR

S.N.D. SANITARY NAPKIN DISPENSER

S.N.R. SANITARY NAPKIN RECEPTACLE

S.P.T. SPECIMIN PASS THROUGH

SQ SQUARE

S.T STAINLESS STEEL

S.SK SERVICE SINK

STA STATION

STD STANDARD

STL STEEL

STRUCT STRUCTURAL

SUSP SUSPENDED

SYM SYMMETRICAL

T

T TREAD

T.B. TOWEL BAR

T.C. TOP OF CURB

TEL TELEPHONE

T&G TONGUE AND GROOVE

THK THICK

T.P. TOP OF PAVEMENT

T.P.D. TOILET PAPER DISPENSER

TV TELEVISION

T.W. TOP OF WALL

TYP TYPICAL

U

UL UNDERWRITERS LABORATORY

UNF UNFINISHED

UR URINAL

V

VERT VERTICAL

VEST VESTIBULE

W

W WEST

W/ WITH

W.C. WATER CLOSET

WD WOOD

W/O WITHOUT

WP WATERPROOF

WPR WALL PROTECTION

WSCT WAINSCOT

WT WEIGHT

CL

PL

C

LA

R K

KJ

O

S

AR

C H

IT

EC

TS

, L

LC

C O

PY

R

IG

H

T

8 911 2 3 4 5 6 7

A

BB

C D

E

FF

E D

C B

76543211 9800

A th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e in c h o n e in c h o n e in c h o n e in c h o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

U.S. GOVERNMENT PRINTING OFFICE:1984-440-467

DateDate

Solicitation Number

Project No.

DRAWING NO.

Project Title

Drawn: Building Number

Location

DateName Initials

Safety Office

DIR. FACMGT.

COO

CEO

Submittal

Construction

For:

Approved CADD Information:

Date o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

RevisionsRevisions

VA FORM 08-6231A,JAN 1990

6/ 3/

:1

4:

A M

1/32" = 1'-0"1 VICINITY MAP

U.S. Department of Veterans Affairs

Sheet List Table Sheet Number Sheet Title

G0.00 GENERAL NOTES, SYMBOLS, SHEET INDEX

A1.00 EXISTING FLOOR PLAN

A2.01 WALL AND PARTITION TYPES

A2.02 ROOM FINISH PLAN

A3.00 REFLECTED CEILING PLAN

A4.00 DETAILS

A8.01 WINDOW DETAILS - EXISTING

ES0.0 ELECTRICAL LEGEND

ED1.0 PARTIAL FLOOR PLAN - DEMOLITION

ES2.0 PARTIAL FLOOR PLAN - POWER

ES4.0 PANEL SCHEDULES & DISCONNECT DETAIL

MH0.0 MECH LEGENDS

MH0.1 HVAC SCHEDULES

MD1.0 PARTIAL FLOOR PLAN - DEMO

MH2.1 PARTIAL FLOOR PLAN - HVAC & PIPING

MH2.2 SEQUENCE OF OPERATIONS & POINTS LIST

MH3.0 EXISTING ROOF PLAN - HVAC

MH4.0 ZONING PLAN - HVAC

MH5.0 HVAC DETAILS

AMERICAN LAKE CAMPUS

GENERAL NOTES, SYMBOLS,

ABBREVIATIONS & SHEET INDEX

REPLACE HVAC BLDG 19 - HP3

NCK

6/18/24

663A4-24-203

G0.00 Drawn:Checked:

BB/MW

AutoCAD SHX Text

VAMC AMERICAN LAKE

AutoCAD SHX Text

AMERICAN LAKE

AutoCAD SHX Text

TACOMA, WASHINGTON

AutoCAD SHX Text

PIERCE COUNTY

AutoCAD SHX Text

PROJECT SITE

AutoCAD SHX Text

BUILDING 19

AutoCAD SHX Text

REPLACE HVAC BLDG 19 - HP3

AutoCAD SHX Text

AMERICAN LAKE DIVISION

AutoCAD SHX Text

VA PUGET SOUND HEALTH CARE SYSTEM

AutoCAD SHX Text

PROJECT NO. 663A4-24-203

AutoCAD SHX Text

SOLICITATION NO.

AutoCAD SHX Text

TACOMA, WASHINGTON 98493

AutoCAD SHX Text

VETERANS DRIVE

LOADING

DOCK

OFFICE OFFICEOFFICE OFFICE OFFICE OFFICE OFFICE OFFICE

OPEN OFFICE

OFFICE OFFICE

MAIL

RECORDS

OPEN OFFICE

OPEN OFFICE

BOILER ROOM

RESTROOM

RESTROOM

WAITING

WORK STNS.

STORAGE

TELECOM

DISPATCH

CORRIDOR

LOCKERS

TOILET

OFFICE

CORRIDOR

HAC

OFFICE

BOILER ROOM

611 SF

RECEPTION

CORRIDOR

C

LA

R K

KJ

O

S

AR

C H

IT

EC

TS

PY

R

IG

H

T

8 911 2 3 4 5 6 7

A

BB

C D

E

FF

E D

C B

76543211 9800

A th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e in c h o n e in c h o n e in c h o n e in c h o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

U.S. GOVERNMENT PRINTING OFFICE:1984-440-467

DateDate

Solicitation Number

Project No.

DRAWING NO.

Project Title

Drawn: Building Number

Location

DateName Initials

Safety Office

DIR. FACMGT.

COO

CEO

Submittal

Construction

For:

Approved CADD Information:

Date o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

RevisionsRevisions

VA FORM 08-6231A,JAN 1990

Checked:

AMERICAN LAKE CAMPUS

EXISTING FLOOR PLAN REPLACE HVAC BLDG 19 - HP3

NCK

6/14/24

663A4-24-203

A1.00

AREA OF WORK NO WORK

AREA OF WORK NO WORK

BB/MW

AutoCAD SHX Text

CANOPY ABOVE

AutoCAD SHX Text

CANOPY ABOVE

AutoCAD SHX Text F.E.

AutoCAD SHX Text

DN

AutoCAD SHX Text

DN

AutoCAD SHX Text 1A20

AutoCAD SHX Text

126 SF

AutoCAD SHX Text

89 SF

AutoCAD SHX Text

100 SF

AutoCAD SHX Text 1A18

AutoCAD SHX Text

86 SF

AutoCAD SHX Text

88 SF

AutoCAD SHX Text 1A16A

AutoCAD SHX Text 1A16

AutoCAD SHX Text 1A14

AutoCAD SHX Text

93 SF

AutoCAD SHX Text 1A12A

AutoCAD SHX Text

88 SF

AutoCAD SHX Text 1A12

AutoCAD SHX Text

98 SF

AutoCAD SHX Text 1A10

AutoCAD SHX Text

1165 SF

AutoCAD SHX Text 1A11

AutoCAD SHX Text

154 SF

AutoCAD SHX Text 1A17

AutoCAD SHX Text

99 SF

AutoCAD SHX Text 1A15

AutoCAD SHX Text

MAIN POWER DISC.

AutoCAD SHX Text

MPD

AutoCAD SHX Text

EP

AutoCAD SHX Text

EP

AutoCAD SHX Text 19A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

MAIN POWER DISCONNECT

AutoCAD SHX Text

MPD

AutoCAD SHX Text

SAFETY BOLLARD

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text

SAFETY BOLLARD

AutoCAD SHX Text

435 SF

AutoCAD SHX Text 1A42

AutoCAD SHX Text 1A34

AutoCAD SHX Text

1698 SF

AutoCAD SHX Text

LOW.V

AutoCAD SHX Text

LOW.V

AutoCAD SHX Text

O.H. DOOR

AutoCAD SHX Text 1A03

AutoCAD SHX Text

490 SF

AutoCAD SHX Text 1A03A

AutoCAD SHX Text

145 SF

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text

(TWO LEVEL SPACE BELOW GRADE)

AutoCAD SHX Text

UP

AutoCAD SHX Text

611 SF

AutoCAD SHX Text

OVER-HEAD DOOR

AutoCAD SHX Text

52 SF

AutoCAD SHX Text 1A01A

AutoCAD SHX Text

79 SF

AutoCAD SHX Text 1A01B

AutoCAD SHX Text

180 SF

AutoCAD SHX Text 1A02

AutoCAD SHX Text

95 SF

AutoCAD SHX Text 1A04

AutoCAD SHX Text

363 SF

AutoCAD SHX Text 1A02A

AutoCAD SHX Text

MANHOLE SEWER ACC.

AutoCAD SHX Text

MANHOLE SEWER ACC.

AutoCAD SHX Text

SPRK RISERS

AutoCAD SHX Text

FD

AutoCAD SHX Text

PIT

AutoCAD SHX Text 1A24

AutoCAD SHX Text

114 SF

AutoCAD SHX Text 1A28

AutoCAD SHX Text

603 SF

AutoCAD SHX Text 1A23

AutoCAD SHX Text

90 SF

AutoCAD SHX Text 1A25

AutoCAD SHX Text

123 SF

AutoCAD SHX Text 1A25A

AutoCAD SHX Text

70 SF

AutoCAD SHX Text 1A21

AutoCAD SHX Text

243 SF

AutoCAD SHX Text 1A19

AutoCAD SHX Text

223 SF

AutoCAD SHX Text 1A22

AutoCAD SHX Text

67 SF

AutoCAD SHX Text 1A26

AutoCAD SHX Text

222 SF

AutoCAD SHX Text

FD

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text

SPACE SAVER

AutoCAD SHX Text

MOBIL SHELVING

AutoCAD SHX Text

SPACE SAVER

AutoCAD SHX Text

MOBIL SHELVING

AutoCAD SHX Text

MATCHLINE

AutoCAD SHX Text

BUILDING 0020

AutoCAD SHX Text

MATCHLINE

AutoCAD SHX Text

BUILDING 0020

AutoCAD SHX Text

MECH EQUIP

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text

FD

AutoCAD SHX Text

MECH EQUIP

AutoCAD SHX Text

DOCK LEVELER

AutoCAD SHX Text

DN

AutoCAD SHX Text

(TWO LEVEL SPACE BELOW GRADE)

AutoCAD SHX Text

MANHOLE

AutoCAD SHX Text

SEWER

AutoCAD SHX Text

ACC.

AutoCAD SHX Text

SPRK RISERS

AutoCAD SHX Text

FD

AutoCAD SHX Text

PIT

AutoCAD SHX Text

FD

AutoCAD SHX Text

131 SF

AutoCAD SHX Text 1A01

AutoCAD SHX Text

RELEASE OF INFORMATION (ROI)

AutoCAD SHX Text

VA POLICE

AutoCAD SHX Text 1A01C

AutoCAD SHX Text

188 SF

AutoCAD SHX Text

1-HP3

AutoCAD SHX Text

1-CU2

1-CU2A

A = ACOUSTIC WALL (STC RATING)

F = FURRING WALL

H = SHAFT WALL, RATED (I.B.C. NUMBER)

P = PARTIAL HEIGHT, NON-RATED

R = RATED FIRE BARRIER (I.B.C. NUMBER)

S = SMOKE PARTITION (I.B.C. NUMBER)

0 = NON-RATED, FRAMING FULL HEIGHT,

FINISH FULL ONE SIDE, SEALANT

1 = 1-HOUR RATED, FIRE TAPE AND CAULK

2 = 2-HOUR RATED, FIRE TAPE AND CAULK

3 = 3-HOUR RATED, FIRE TAPE AND CAULK

4 = 45 STC RATING, INSULATION AND SEALANT

5 = 56 STC RATING, RESILIENT CHANNELS,

INSULATION AND SEALANT

6 = 63 STC RATING, RESILIENT CHANNELS,

INSULATION AND SEALANT

7 = FRAMING 6" ABOVE CEILING, FINISH 6"

ABOVE CEILING

8 = FRAMING FULL HEIGHT, FINISH 6"

ABOVE CEILING

1 = 5/8" METAL FURRING CHANNELS

OVER EXISTING SUBSTRATE

2 = 2 1/2" METAL STUDS AT 16"O.C.

3 = 3 1/2" WOOD STUDS AT 16"O.C.

4 = 3 5/8" METAL STUDS AT 16"O.C.

5 = 5 1/2" WOOD STUDS AT 16"O.C.

6 = 6" METAL STUDS AT 16"O.C.

7 = 7 1/4" WOOD STUDS AT 16"O.C.

8 = 8" METAL STUDS AT 16"O.C.

9 = DOUBLE PLUMBING WALL, DIM.

OUT-OUT, 3 5/8" STUDS AT 16"O.C.

A = ACOUSTIC INSULATION & SEALANT

C = 5/8" RESILIENT FURRINGCHANNELS

E = EXISTING CONSTRUCTION

L = LEAD LINED GYPSUM BOARD PER

PHYSICIST REPORT

P = PLYWOOD UNDERLAYMENT, SHEAR

OR WALL REINFORCEMENT

T = TILE FINISH AREA: SUBSTITUTE

CEMENTITIOUS BACKER BOARD

S= SHEAR WALL

GROUP

ASSEMBLY

STUD SIZE

MODIFIER

WALL TYPE LEGEND

A11-AC

GROUP

ASSEMBLY

STUD SIZE

MODIFIER(S)

WALL TAG

IN-WALL TAG

GROUP

ASSEMBLY

STUD SIZE

WHERE PARTITIONS ARE U.L. LISTED

ASSEMBLIES FOR PROPRIETARY

MANUFACTURERS, PROVIDE U.L. LISTED

ASSEMBLIES FOR ANY ALTERNATE

PRODUCTS INSTALLED.

GENERAL NOTE

A11-AC

MODIFIER(S)

01 1000.A0

SPEC SECTION

NOTE NUMBER

KEYNOTE

A11 A

T

C

P

SECTION

PLAN

6"

X = 3 1/8"

X = 4 1/4"

X = 6 5/8"

X

EXISTING WALL

FACE OF EXISTING WALL

F72

F74

F76

CEILING- SEE ROOM FINISH

SCHEDULE AND RCP FOR HEIGHT

AND FINISH

METAL STUD FRAMING

STRUCTURE

BASE AS SCHEDULE

1 LAYER 5/8" GYPSUM

BOARD

PROVIDE R-19 INSULATION AT

EXTERIOR WALLS ONLY

SECTION

PLAN

X = 3 3/4"

X = 4 7/8"

X = 7 1/4"

X

6"

P74

P76

P72

CEILING- SEE ROOM FINISH

SCHEDULE AND RCP FOR HEIGHT

AND FINISH

METAL STUD FRAMING

45 DEGREE METAL STUD BRACING

TO STRUCTURE AT 4'-0"O.C. AS

REQUIRED

BASE AS SCHEDULE

1 LAYER 5/8" GYPSUM

BOARD EACH SIDE

SECTION

PLAN

X = 1 1/4"F71

X 6"

EXISTING WALL

FACE OF EXISTING WALL

5/8" HAT CHANNEL

CEILING- SEE ROOM FINISH

SCHEDULE AND RCP FOR HEIGHT

AND FINISH

STRUCTURE

BASE AS SCHEDULE

1 LAYER 5/8" GYPSUM

BOARD EACH SIDE

5/8" HAT CHANNEL

CP CARPET (WITHOUT CUSHION - BROADLOOM)

CPT CARPET TILE

CT CERAMIC TILE (FLOOR, BASE & WALL)

AT ACOUSTICAL CEILING TILE

EXG EXISTING

GWB GYPSUM WALLBOARD SYSTEMS

FF FACTORY FINISH

RB RESILIENT BASE (RUBBER, VINYL)

VCT RESILIENT TILE FLOORING (VINYL COMPOSITION TILE)

W WALL COVERING (VINYL COATED FABRIC)

SFC SPECIAL FLOOR COVERING

ROOM FINISH ABBREVIATIONS

PT-1 PITTSBURG PAINT, 217-2 COCOA BUTTER EGGSHELL #6-411 PPG

SECTION

PLAN

X = 4 7/8"

X

R14

METAL STUD FRAMING

FIRE SEALANT07 9200.A5

CEILING- SEE ROOM FINISH SCHEDULE

AND RCP FOR HEIGHT AND FINISH

BASE- SEE ROOM FINISH SCHEDULE

1 LAYER 5/8" GYPSUM

BOARD ON EACH SIDE09 2900.D3

FIRE SEALANT07 9200.A5

STRUCTURE

NEW OR EXISTING

PARTITION

NEW OR EXISTING

PARTITION

SECURE CONT.

RETAINER

W/ #8 x 1" SCREWS

@ 8"O.C. MAX

VINYL ACRYLIC

CORNER GUARD

0'

3"

0' - 3"

WRAP AROUND TYPE

CORNER TYPE

0'

2"

0' - 2"

0'

2"

0' - 2"

VERIFY WITH

PLAN SECTION

CABINET MFGR.

VE

R

IF

Y

W

IT

H C

AB

IN

ET

M

FG

R

0' - 10"

GYPSUM WALL

BOARD,

WRAP BACK SIDE OF

CABINET

TO CENTER

OF HANDLE

5'-0" A.F.F

.6 -1

/4

R .O

FIRE EXTINGUISHER

AND CABINET

2' -0

/2

" R .O

3'

-2 " A

FF

CL

1' - 4 1/2"

5/8" GWB OVER

1-5/8" METAL STUDS

EXISTING

STRUCTURAL COLUMN

1'

1/

2"

CORNER GUARD,

TYP. SEE DETAIL

2/ A2.40

BASE BELOW, TYP

CL

VERIFY MIN. CLR.

REQUIREMENTS-

SEE PLAN

0'

3"

0' - 3"

C

LA

R K

KJ

O

S

AR

C H

IT

EC

TS

PY

R

IG

H

T

8 911 2 3 4 5 6 7

A

BB

C D

E

FF

E D

C B

76543211 9800

A th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e in c h o n e in c h o n e in c h o n e in c h o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

U.S. GOVERNMENT PRINTING OFFICE:1984-440-467

DateDate

Solicitation Number

Project No.

DRAWING NO.

Project Title

Building Number

Location

DateName Initials

Safety Office

DIR. FACMGT.

COO

CEO

Submittal

Construction

For:

Approved CADD Information:

Date o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

RevisionsRevisions

VA FORM 08-6231A,JAN 1990

Drawn:Checked:

4/ 8/

:2

2:

A M

1 1/2" = 1'-0"

PARTIAL HEIGHT WALLP1

1 1/2" = 1'-0"

FURRING WALLF1

1 1/2" = 1'-0"

ONE HOUR FIRE RATED WALLR1

3" = 1'-0"2 DETAIL - TYPICAL CORNER GUARD

1 1/2" = 1'-0"3 DETAIL-FIRE EXTINGUISHER - TYPICAL

3" = 1'-0"1 DETAIL - TYPICAL COLUMN FURRING_

AMERICAN LAKE CAMPUS

WALL AND PARTITION TYPES

REFERENCE DETAILS

REPLACE HVAC BLDG 19 - HP3

NCK

6/18/24

663A4-24-203

A2.01

BB/MW

OFFICE OFFICEOFFICE OFFICE

OFFICE OFFICE

TELECOM

DISPATCH

CORRIDOR

LOCKERS

TOILET

OFFICE

CORRIDOR

HAC

OFFICE

CPT-1

VCT-1

CPT-1

CPT-1

VCT-1

VCT-1

CP CARPET (WITHOUT CUSHION - BROADLOOM)

CPT CARPET TILE

CT CERAMIC TILE (FLOOR, BASE & WALL)

AT ACOUSTICAL CEILING TILE

EXG EXISTING

GWB GYPSUM WALLBOARD SYSTEMS

FF FACTORY FINISH

PT-1 PITTSBURG PAINT, 217-2 COCOA BUTTER EGGSHELL #6-411 PPG

RB RESILIENT BASE (RUBBER, VINYL)

VCT RESILIENT TILE FLOORING (VINYL COMPOSITION TILE)

W WALL COVERING (VINYL COATED FABRIC)

SFC SPECIAL FLOOR COVERING

ROOM FINISH ABBREVIATIONS

ROOM FINISH SCHEDULE - REFERENCE

ROOM

NO. ROOM NAME

FLOOR WALL CEILING WAINSCOT

COMMENTSFLOOR BASE MAT. NORTH EAST SOUTH WEST MAT. FINISH HT MAT. HT

1A23 CORRIDOR

VCT-1 PT-1 PT-1 PT-1 PT-1 ----- ----

VCT-1 RB GWB PT-1 PT-1 PT-1 PT-1 AT FF 8'-0" ----- ----

VCT-1 RB GWB PT-1 PT-1 PT-1 PT-1 AT FF 8'-0" ----- ----

GWB PT-1 PT-1 PT-1 PT-1 AT FF 8'-0"

C

LA

R K

KJ

O

S

AR

C H

IT

EC

TS

PY

R

IG

H

T

8 911 2 3 4 5 6 7

A

BB

C D

E

FF

E D

C B

76543211 9800

A th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e in c h o n e in c h o n e in c h o n e in c h o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

U.S. GOVERNMENT PRINTING OFFICE:1984-440-467

DateDate

Solicitation Number

Project No.

DRAWING NO.

Project Title

Building Number

Location

DateName Initials

Safety Office

DIR. FACMGT.

COO

CEO

Submittal

Construction

For:

Approved CADD Information:

Date o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

RevisionsRevisions

VA FORM 08-6231A,JAN 1990

Drawn:Checked:

4/ 8/

:2

5:

A M

AMERICAN LAKE CAMPUS

ROOM FINISH PLAN - AS-BUILT REPLACE HVAC BLDG 19 - HP3

NCK

6/18/24

663A4-24-203

A2.02

1A24 IT CLOSET

1A25 LOCKERS

1A25A TOILET

1A26 EXISTING OFFICE

1A28 CALL CENTER/DISPATCH

CPT-1

CPT-1

CPT-1 RB

RB

RB

RB

GWB

GWB

GWB

PT-1 PT-1 PT-1 PT-1

PT-1 PT-1 PT-1 PT-1 AT

AT

AT

FF

FF

FF

8'-0" 8'-0"

8'-0"

AREA OF WORK NO WORK

AREA OF WORK NO WORK

BB/MW

AutoCAD SHX Text

CANOPY ABOVE

AutoCAD SHX Text 1A20

AutoCAD SHX Text 1A18

AutoCAD SHX Text 1A16A

AutoCAD SHX Text 1A16

AutoCAD SHX Text 1A17

AutoCAD SHX Text 1A15

AutoCAD SHX Text

UP

AutoCAD SHX Text 1A24

AutoCAD SHX Text 1A28

AutoCAD SHX Text 1A23

AutoCAD SHX Text 1A25

AutoCAD SHX Text 1A25A

AutoCAD SHX Text 1A21

AutoCAD SHX Text 1A19

AutoCAD SHX Text 1A22

AutoCAD SHX Text 1A26

AutoCAD SHX Text

MECH EQUIP

AutoCAD SHX Text

VA POLICE

AutoCAD SHX Text

1-HP3

AutoCAD SHX Text

1-CU2

AutoCAD SHX Text

1-CU2A

F.E.C.

EQUIP LAYOUT AND CORE

DRILL EXISTING CONCRETE

EQUIP PAD TO 3" EMBED

INSTALL MECHANICAL EQUIPMENT ANCHORS - 58" DIA HILTI

KWIK BOLT WITH EPOXY ADHESIVE IN ACCORDANCE WITH

MANUFACTURERS INSTALLATION INSTRUCTIONS

C

LA

R K

KJ

O

S

AR

C H

IT

EC

TS

PY

R

IG

H

T

8 911 2 3 4 5 6 7

A

BB

C D

E

FF

E D

C B

76543211 9800

A th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e in c h o n e in c h o n e in c h o n e in c h o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

U.S. GOVERNMENT PRINTING OFFICE:1984-440-467

DateDate

Solicitation Number

Project No.

DRAWING NO.

Project Title

Building Number

Location

DateName Initials

Safety Office

DIR. FACMGT.

COO

CEO

Submittal

Construction

For:

Approved CADD Information:

Date o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

RevisionsRevisions

VA FORM 08-6231A,JAN 1990

Drawn:Checked:

8/ 2/

:0

8:

P M

1" = 1'-0"2 DETAIL - EXISTING CONCRETE SLAB

AMERICAN LAKE CAMPUS

DETAILS REPLACE HVAC BLDG 19 - HP3

NCK

6/18/24

663A4-24-203

A4.00

1" = 1'-0"1 WEST ELEVATION

1HP2B1HP2A

EXISTING HP3

EXISTING CU2

EXISTING CU2A

LA

R K

KJ

O

S

AR

C H

IT

EC

TS

PY

R

IG

H

T

8 911 2 3 4 5 6 7

A

BB

C D

E

FF

E D

C B

76543211 9800

A th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e in c h o n e in c h o n e in c h o n e in c h o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

U.S. GOVERNMENT PRINTING OFFICE:1984-440-467

DateDate

Solicitation Number

Project No.

DRAWING NO.

Project Title

Building Number

Location

DateName Initials

Safety Office

DIR. FACMGT.

COO

CEO

Submittal

Construction

For:

Approved CADD Information:

Date o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

RevisionsRevisions

VA FORM 08-6231A,JAN 1990

Drawn:Checked:

8/ 2/

:0

8:

P M

AMERICAN LAKE CAMPUS

WINDOW DETAILS - EXISTING REPLACE HVAC BLDG 19 - HP3

NCK

6/18/24

663A4-24-203

A8.01BB/MW

MECHANICAL EQUIPMENT EMERGENCY SHUTDOWN SWITCH

MOTOR-RATED SWITCH - SIZE OL PER MOTOR REQUIREMENTS

WP = WEATHERPROOF

OS = OCCUPANCY SENSOR TYPE

OP = OCCUPANCY/PHOTOELECTRIC TYPE

LV = LOW-VOLTAGE

208Y/120V, 3Ø, 4-WIRE PANELBOARD

LOWER CASE LETTER INDICATES SWITCHING GROUP

WALL SWITCH - SUBSCRIPT INDICATES

EQUIPMENT CABINET - TYPE AS NOTED

SINGLE-POLE WALL SWITCH

2 = 2-POLE

3 = 3-WAY

K = KEYED

METER

MOTOR CONNECTION - SEE SCHEDULE FOR MOTOR DATA

EQUIPMENT CONNECTION

MM

COMBINATION STARTER

3-POLE, NEMA SIZE 1 MINIMUM UNLESS NOTED OTHERWISE

HP RATED, 3-POLE, NEMA SIZE 1 MINIMUM, UNLESS NOTED

BY EQUIPMENT MANUFACTURER OR AS NOTED

3-POLE UNLESS NOTED OTHERWISE

DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

OR AS NOTED

PROTECTION AS REQUIRED BY EQUIPMENT MANUFACTURER

3-POLE UNLESS NOTED OTHERWISE - OVERCURRENT

OTHERWISE - OVERCURRENT PROTECTION AS REQUIRED

M STARTER

4 = 4-WAY

SYMBOL

DIAGRAMPLAN

DESCRIPTIONDESCRIPTION

SYMBOLS LEGEND - POWER

SYMBOL

DIAGRAMPLAN

DESCRIPTIONDESCRIPTION

SYMBOLS LEGEND - WIRING DEVICES

ILLUMINATED EXIT SIGN - SINGLE FACE

OCCUPANCY SENSOR WITH POWER PACK CEILING MOUNTED

BATTERY-POWERED EMERGENCY WALLPACK

ILLUMINATION CONTROL STATION

PHOTOELECTRIC CONTROL

ARROW INDICATES DIRECTION OF EGRESS, UNIVERSAL MOUNT

ILLUMINATED EXIT SIGN - DOUBLE FACE

ARROW INDICATES DIRECTION OF EGRESS, UNIVERSAL MOUNT

SYMBOL

DIAGRAMPLAN

DESCRIPTIONDESCRIPTION

SYMBOLS LEGEND - LIGHTING

GROUND ROD

GROUND CONNECTION

SYMBOL

DIAGRAMPLAN

DESCRIPTION

SYMBOLS LEGEND - GROUNDING

SMOKE DETECTOR

HEAT DETECTOR

FIRE ALARM SYSTEM CONTROL PANEL

FIRE ALARM STROBE

FIRE ALARM SMOKE DETECTOR

FIRE ALARM PULL STATION

FIRE ALARM HORN-STROBE

FIRE ALARM PRESSURE SWITCH

FIRE ALARM FLOW SWITCH

SYMBOL

DIAGRAMPLAN

DESCRIPTIONDESCRIPTION

SYMBOLS LEGEND - FIRE ALARM

DUCT-MOUNTED WITH TUBE

BT - BEAM TRANSMITTER

BR - BEAM RECEIVER

I - IONIZATION

P - PHOTOELECTRIC

FIRE ALARM TAMPER SWITCH

POST INDICATOR VALVE

NUMBER INDICATES CANDELLA RATING

CONDUIT - CONCEALED IN OR UNDER FLOOR

LIGHT LINEWEIGHT INDICATES EXISTING INFORMATION

EXISTING TO BE REMOVED

HEAVY LINEWEIGHT INDICATES NEW WORK

CONDUIT OR CABLE VERTICAL DOWN

CONDUIT STUB - TERMINATE WITH BUSHING OR CAP IF UNDERGROUND

CONDUIT OR CABLE VERTICAL UP

CONDUCTORS - CONNECTED

CONDUCTORS - NOT CONNECTED

JUNCTION BOX

PULLBOX - SIZE AS INDICATED OR AS REQUIRED BY CODE

SYMBOL

DIAGRAMPLAN

DESCRIPTION

SYMBOLS LEGEND - GENERAL

MM XX

M

DUPLEX RECEPTACLE NEMA 5-20R, +18" AFF EXCEPT 10"AFF

FOR FURNITURE LOCATIONS

DUPLEX RECEPTACLE NEMA 5-20R, ISOLATED GROUND, +18" AFF UON

RECEPTACLE NEMA 5-20R, CONNECTED TO EMERGENCY CIRCUIT, +18"

AFF UON

RECEPTACLE NEMA 5-20R MOUNTED ABOVE COUNTER. COORDINATE WITH

CASEWORK SHOP DRAWINGS AND ARCHITECTURAL DRAWINGS.

SPECIAL PURPOSE RECEPTACLE TYPE AS SHOWN ON PLANS

COMBINATION FLUSH MOUNTED FLOOR BOX. REFER TO FLOOR PLANS

FOR DEVICE.

CEILING-MOUNTED DUPLEX RECEPTACLE, NEMA 5-20R

DUPLEX RECEPTACLE NEMA 5-20R WITH GROUND FAULT CIRCUIT

INTERRUPTER, +18" AFF UON

POWER/COMM POLE - FLOOR TO CEILING.

STRIP FLUORESCENT

WALL-MOUNTED FLUORESCENT LUMINAIRE

WALL-MOUNTED LUMINAIRE

DOWNLIGHT OR CEILING-MOUNTED LUMINAIRE

DIRECTIONAL LUMINAIRE

WALL WASH LUMINAIRE

WITH BATTERY BACKUP BALLAST

SHADING INDICATES LUMINAIRE

2x4 FLUORESCENT

1x4 FLUORESCENT

2x2 FLUORESCENT

PC

OS

F

TS

PS

FS

PIV

F

TS

PS

FS

PIV

FCP FCP

PB

PANELBOARD

AMPERES SHORT CIRCUIT AVAILABLE (SYMMETRICAL)

XXX

XXXXXX

SYMBOL

DIAGRAM

DESCRIPTIONDESCRIPTION

SYMBOLS LEGEND - POWER

XX

SYMBOL

DIAGRAMPLAN

DESCRIPTION

SYMBOLS LEGEND - COMMUNICATIONS

COMMUNICATIONS - OUTLET @ 18" AFF EXCEPT 10" AFF FOR FURNITURE

(# = REPRESENTS THE NUMBER OF COMMUNICATION PORTS. (IE 1,2,3))

(W = SINGLE COMMUNICATIONS PORT WALL MOUNTED AT +48" AFF.)

(P = PAYPHONE, WALL MOUNTED AT +48" AFF)

COMMUNICATIONS - PAINTED FIRE RESISTANT 3/4" PLYWOOD BACKBOARD

19" COMMUNICATIONS RACK - FLOOR MOUNTED

19" COMMUNICATIONS RACK - WALL MOUNTED

A-1,3,5

POINT OF CONNECTION (POC) BETWEEN NEW AND

EXISTING CIRCUIT

BREAK LINE

CABLE TRAY

MINIMUM 3/4" CONDUIT CONCEALED IN CEILING SPACE OR IN WALL WITH #12

AWG CONDUCTORS, UNLESS OTHERWISE NOTED ON PLAN. PROVIDE

GROUNDING CONDUCTORS SIZED PER NFPA 70.

HOME RUN FROM SOURCE OF SUPPLY

PANEL DESIGNATION

BRANCH CIRCUIT NUMBERS

XXXXX FEEDER TAG - REFER TO FEEDER SCHEDULE

DRAWING CONSTRUCTION ("FLAG") NOTE

EQUIPMENT IDENTIFIER (XX = ABBREVIATION

Y = EQUIPMENT SCHEDULE NUMBER)

MATCHLINE

REVISION CLOUD (ENCIRCLES DRAWING CHANGES MADE SINCE

THE PREVIOUS RELEASE)

DETAIL REFERENCE

SECTION REFERENCE

ELEVATION REFERENCE

REVISION REFERENCE

NORTH REFERENCE

N

XDN

XX

XX.XX

X

XX.XX

X

XX.XX

X

SYMBOL

PLAN

DESCRIPTIONDESCRIPTION

SYMBOLS LEGEND - GENERAL

SECTION IDENTIFICATION NUMBER

SHEET WHERE SECTION IS DRAWN

ELEVATION IDENTIFICATION NUMBER

SHEET WHERE ELEVATION IS DRAWN

DETAIL IDENTIFICATION NUMBER

SHEET WHERE DETAIL IS DRAWN

FLEXIBLE METAL CONDUIT

X-XX

XXXX

EQUIPMENT IDENTIFIER

LIGHT FIXTURE IDENTIFIER - REFER TO LIGHTING FIXTURE SCHEDULE

UNDER-CABINET FLUORESCENT LUMINAIRE

MOUNT SWITCHES AT 48" AFF. TO CL, UON.

ANY COMBINATION OF SWITCH TYPES CAN BE USED. (IE. 3K = 3-WAY

KEYED SWITCH)

J

GENERAL NOTES:

1. CONFORM WITH NATIONAL ELECTRICAL CODE (NEC).

2. ALL MATERIALS TO BE UL LISTED.

3. SCHEDULE ALL POWER OUTAGES WITH VA.

4. MATERIALS SHALL CONFORM TO THE FOLLOWING:

a. CONDUCTORS TO BE COPPER, THWN INSULATION.

b. INTERIOR RACEWAYS TO BE EMT WITH WITH STEEL FITTINGS.

c. EXTERIOR RACEWAYS TO BE RIGID STEEL.

d. EQUIPMENT CONNECTIONS TO BE LIQUIDTITE STEEL FLEX.

5. PROVIDE CORE DRILLING REQUIRED.

6. SEAL ALL CONDUIT PENETRATIONS. PROVIDE UL LISTED FIRE

RATED SEALS MATCHING FIRE RATING OF WALLS AND FLOORS

INSTALLED BY UL QUALIFIED INSTALLERS.

7. COORDINATE ELECTRICAL WORK WITH WORK OF OTHER TRADES.

ELECTRICAL DRAWINGS SHOW ONLY ELECTRICAL WORK AND

SHALL NOT BE USED FOR WORK OF OTHER TRADES.

8. COMPLETION OF WORK SHALL BE EXECUTED IN ACCORDANCE

WITH THE PROJECT SCHEDULE. SCHEDULE INSTALLATION WITH

GENERAL CONTRACTOR AND OTHER TRADES TO ENSURE

PROJECT MILESTONES ARE MET.

9. PROVIDE PULL BOXES AS REQUIRED BY CODE.

10. SEISMIC SUPPORT AND BRACE ELECTRICAL EQUIPMENT AND

RACEWAYS PER CODE, SPECIFICATIONS 13 05 41,

MANUFACTURES RECOMMENDATIONS AND THE FOLLOWING

CRITERIA:

SEISMIC USE GROUP: I

SEISMIC DESIGN CATEGORY D

COMPONENT IMPORTANCE FACTOR: Ip = 1.5 SPECIAL RESPONSE COEFFICIENTS: Sds = 0.814g, Sd1 =0.441g

ICS

FAN SHUTDOWNF F

DOUBLE DUPLEX RECEPTACLE NEMA 5-20R, +18" AFF

EXCEPT 10" AFF FOR FURNITURE LOCATIONS

CARD READER

ELECTRIC DOOR STRIKE

SYMBOL

DIAGRAMPLAN

DESCRIPTION

SYMBOLS LEGEND - SECURITY

WP INDICATES WEATHERPROOFWP

DOOR CONTACT

REQUEST TO EXIT DEVICE

CR

ES

CR

ES

REX REX

CC

PAGING SPEAKER - DUKANE 5A607 WITH WHITE CEILING BAFFLE OR EQUALS

ABBREVIATIONS

@ AT

A (AMP) AMPERE

AC ABOVE COUNTER, ALTERNATING CURRENT

AFF ABOVE FINISHED FLOOR

AIC AMPERES INTERRUPTING

ALT ALTERNATE

ANN ANNUNCIATOR

ARCH ARCHITECT; ARCHITECTURAL

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AWG AMERICAN WIRE GAUGE

BLDG BUILDING

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CLG CEILING

COL COLUMN

COM COMMUNICATION

CT CURRENT TRANSFORMER

CU COPPER

DISC DISCONNECT

DN DOWN

DWG DRAWING

E EXIST, EAST

EC ELECTRICAL CONTACTOR

EDH ELECTRIC DUCT HEATER

EF EXHAUST FAN

EGC EQUIPMENT GROUND CONDUCTOR

EL ELEVATION

ELEC ELECTRIC(AL)

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EQUIP/EQP EQUIPMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXH EXHAUST

EXT EXTERIOR

EXIST EXISTING

FA FIRE ALARM

FAA FIRE ALARM ANNUNCIATOR

FAP FIRE ALARM PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FDR FEEDER

FIXT FIXTURE

FLA FULL LOAD AMPS

FSD FIRE/SMOKE DAMPER

GFCI GROUND FAULT CIRCUIT INTERRUPTER

HID HIGH INTENSITY DISCHARGE

HOA HAND OFF AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

IEEE INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IN INCH

JB JUNCTION BOX

KCMIL THOUSAND CIRCULAR MILLS

KVA KILOVOLT AMPERES

KW KILOWATT

KWH KILOWATT HOUR

LBS POUNDS

LF LINEAR FEET (FEET)

LRA LOCKED ROTOR AMPS

LTG LIGHTING

LV LOW VOLTAGE

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MECH MECHANICAL

MH METAL HALIDE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUG ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

MS MAGNETIC STARTER

MTD MOUNTED

MTG MOUNTING

N NORTH; NEUTRAL

N/A NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRIC MANUFACTURERS ASSOCIATION

NESC NATIONAL ELECTRICAL SAFETY CODE

NEUT NEUTRAL

NFPA NATIONAL FIRE PROTECTION AGENCY

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

OFOI OWNER FURNISHED OWNER INSTALLED

OL OVERLOAD

OS OCCUPANCY SENSOR

P PRIMARY

PA PUBLIC ADDRESS

PC PHOTO CELL

PB PILL BOX

PE PHOTO ELECTRIC

PF POWER FACTOR

PH PHASE

PNL PANEL

POC POINT OF CONNECTION

PWR POWER

QTY QUANTITY

RECPT RECEPTACLE

RLA RUNNING LOAD AMPS

RPM REVOLUTIONS PER MINUTE

S SOUTH

SD SMOKE DETECTOR

SHT SHEET

SPEC SPECIFICATION

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TC TIME CLOCK

TEL TELEPHONE

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION

TYP TYPICAL

UBC UNIFORM BUILDING CODE

UFC UNIFORM FIRE CODE

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITERS LABORATORIES

UON UNLESS OTHERWISE NOTED

UV UNIT VENTILATOR

V VOLT

W WATT, WEST

W/ WITH

W/O WITHOUT

WH WATER HEATER

WP WEATHERPROOF

X REACTANCE

XFMR TRANSFORMER

Z IMPEDANCE

& AND

IE: THAT IS

# NUMBER

ELECTRICAL DRAWING LIST

ES0.0 ELECTRICAL LEGEND

ES2.0 PARTIAL FLOOR PLAN - POWER

ES4.0 PANEL SCHEDULES

ED1.0 PARTIAL FLOOR PLAN - DEMOLITION

C

LA

R K

KJ

O

S

AR

C H

IT

EC

TS

PY

R

IG

H

T

8 911 2 3 4 5 6 7

A

BB

C D

E

FF

E D

C B

76543211 9800

A th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e in c h o n e in c h o n e in c h o n e in c h o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

U.S. GOVERNMENT PRINTING OFFICE:1984-440-467

DateDate

Solicitation Number

Project No.

DRAWING NO.

Project Title

Building Number

Location

DateName Initials

Safety Office

DIR. FACMGT.

COO

CEO

Submittal

Construction

For:

Approved CADD Information:

Date o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

RevisionsRevisions

VA FORM 08-6231A,JAN 1990

S:

\F

MS

\P

RO

JE

CT

S

SE

CT

IO

N\

PR

OJ

EC

TS

\2.

A me ric an La ke \A cti ve

\66 3A

4-

-2

Re pla ce

H

VA

C

HP

3 a t B uil din g 1 9\0

1 P re

-B id

Fo lde rs\

D es ign \C

AD

w ith (N

) D ra wi ng

S he et #s fo r 2

4-

3\E S0

.0.

dw g 6/1

8/2

Be di, G ag an de ep S

PL

OT

TE

D

BY

Drawn:Checked:

AMERICAN LAKE CAMPUS

ELECTRICAL LEGEND REPLACE HVAC BLDG 19 - HP3

NCK

6/18/24

ES0.0BB/MW

UP

ROI

1A09

ROI/RECEPTION

1A01A

OFFICE

1A10

OFFICE

1A12

OFFICE

1A12A

OFFICE

1A14

OFFICE

1A16

OFFICE

1A16A

OFFICE

1A18

OFFICE

1A20

768 SF

HIMS

1A11

WORK ROOM

1A15

OFFICE

1A17

CONFERENCE ROOM

1A21

RECORDS

1A34

HKG

1A22PASSAGE

1A19

CONCRETE SLAB (E)

1-HP3 (E)

1-CU2 (E)

1-CU2A (E) 19M

19A

19MDP

19X

19PB

DOOR POWER

A-41

WPWP

1-FCU1

1-FCU2

1-FCU3

1-FCU12

1-FCU9

1-FCU6

1-HP2A

1-BC2

43/43A, 208V, 3Ø M-32

4.4A, 208V, 3Ø M-26

1.4A, 208V, 1Ø M-22

3.4A, 208V, 1Ø M-22

3.4A, 208V, 1Ø M-18

3.4A, 208V, 1Ø M-18

1.4A, 208V, 1Ø M-14

M-14

0.5A, 208V, 1Ø M-37

M-14

DDC/HVAC CONTROL

POWER U-41

A-2

A-2

A-2

A-2

A-4

A-4

A-19

A-4

A-8 A-8 A-10

A-10 A-14

A-14

A-12 A-16 A-20

A-18

A-18 A-20 A-24

A-22

A-26 A-26

A-24

A-21

A-28

U-39

FCP

A-32 A-34A-32

A-34 A-32A-34A-32

A-34 A-36

A-38A-36 A-36

A-38 A-38

A-40 A-42

A-42

A-40

A-23

A-25

A-27

J

HW

M-2

A-18 J

19U

1 8

1-HP2B

1-FCU11

1-RCC3

2 3 4

ES4.0

C

LA

R K

KJ

O

S

AR

C H

IT

EC

TS

PY

R

IG

H

T

8 911 2 3 4 5 6 7

A

BB

C D

E

FF

E D

C B

76543211 9800

A th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e in c h o n e in c h o n e in c h o n e in c h o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

U.S. GOVERNMENT PRINTING OFFICE:1984-440-467

DateDate

Solicitation Number

Project No.

DRAWING NO.

Project Title

Building Number

Location

DateName Initials

Safety Office

DIR. FACMGT.

COO

CEO

Submittal

Construction

For:

Approved CADD Information:

Date o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

RevisionsRevisions

VA FORM 08-6231A,JAN 1990

S:

\F

MS

\P

RO

JE

CT

S

SE

CT

IO

N\

PR

OJ

EC

TS

\2.

A me ric an La ke \A cti ve

\66 3A

4-

-2

Re pla ce

H

VA

C

HP

3 a t B uil din g 1 9\0

1 P re

-B id

Fo lde rs\

D es ign \C

AD

w ith (N

) D ra wi ng

S he et #s fo r 2

4-

3\E S2

.0.

dw g 6/1

8/2

Be di, G ag an de ep S

PL

OT

TE

D

BY

Drawn:Checked:

AMERICAN LAKE CAMPUS

PARTIAL FLOOR PLAN - POWER REPLACE HVAC BLDG 19 - HP3

NCK

6/18/24

663A4-24-203

ES2.0

HVAC EQUIPMENT WIRING

SCHEDULE

UNIT WIRING

1-FCU11 3/4", 2#10 & #10G.

1-FCU12 3/4", 3#10 & #10G.

AREA OF WORK NO WORK

AREA OF WORK NO WORK

FLAG NOTES:

DEENERGIZE / LOTO CIRCUIT AT PANELBOARD 19M

REMOVE / REPLACE SERVICE DISCONNECT TO AIR-CONDITIONING

SPLIT SYSTEM 1-HP3 AND ASSOCIATED SYSTEM COMPONENTS

REMOVE / REPLACE SERVICE DISCONNECT TO CONDENSING UNIT

1-CU2 AND ASSOCIATED SYSTEM COMPONENTS

REMOVE / REPLACE SERVICE DISCONNECT TO CONDENSING UNIT

1-CU2A AND ASSOCIATED SYSTEM COMPONENTS

REMOVE / REPLACE SERVICE DISCONNECT TO FAN COIL UNIT

1-FCU11 AND ASSOCIATED SYSTEM COMPONENTS

REMOVE / REPLACE SERVICE DISCONNECT TO FAN COIL UNIT

1-FCU12 AND ASSOCIATED SYSTEM COMPONENTS

REMOVE / REPLACE SERVICE DISCONNECT TO REFRIGERANT CIRCUIT

CONTROLLER UNIT 1-RCC3 AND ASSOCIATED SYSTEM COMPONENTS

INSTALL (N) CONDUCTORS FROM EQUIPMENT PAD LOCATION BACK

TO PANELBOARD 19M

COORDINATE DDC CONTROLS AND BACNET NETWORKING TO

GATEWAY WITH MECHANICAL

R K

KJ

O

S

AR

C H

IT

EC

TS

PY

R

IG

H

T

8 911 2 3 4 5 6 7

A

BB

C D

E

FF

E D

C B

76543211 9800

A th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e in c h o n e in c h o n e in c h o n e in c h o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

U.S. GOVERNMENT PRINTING OFFICE:1984-440-467

DateDate

Solicitation Number

Project No.

DRAWING NO.

Project Title

Drawn: Building Number

Location

DateName Initials

Safety Office

DIR. FACMGT.

COO

CEO

Submittal

Construction

For:

Approved

Approved: Medical Center Director

CADD Information:

Date o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

RevisionsRevisions

VA FORM 08-6231A,JAN 1990

Checked:Approved: Chief Engineer

S:

\F

MS

\P

RO

JE

CT

S

SE

CT

IO

N\

PR

OJ

EC

TS

\2.

A me ric an La ke \A cti ve

\66 3A

4-

-2

Re pla ce

H

VA

C

HP

3 a t B uil din g 1 9\0

1 P re

-B id

Fo lde rs\

D es ign \C

AD

w ith (N

) D ra wi ng

S he et #s fo r 2

4-

3\E S4

.0.

dw g 6/1

4/2

Be di, G ag an de ep S

PL

OT

TE

D

BY

SCALE: NOT TO SCALE

DISCONNECT ARRAY AT WEST ELEVATION - DETAIL1

AMERICAN LAKE CAMPUS

PANEL SCHEDULES & DISCONNECT DETAIL REPLACE HVAC BLDG 19 - HP3

NCK

BB

6/14/24

663A4-24-203

ES4.0

Mohammad Waqas

OFFICE OFFICEOFFICE OFFICE

OFFICE OFFICE

TELECOM

DISPATCH

CORRIDOR

LOCKERS

TOILET

OFFICE

CORRIDOR

HAC

OFFICE

C

LA

R K

KJ

O

S

AR

C H

IT

EC

TS

PY

R

IG

H

T

8 911 2 3 4 5 6 7

A

BB

C D

E

FF

E D

C B

76543211 9800

A th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e in c h o n e in c h o n e in c h o n e in c h o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

U.S. GOVERNMENT PRINTING OFFICE:1984-440-467

DateDate

Solicitation Number

Project No.

DRAWING NO.

Project Title

Building Number

Location

DateName Initials

Safety Office

DIR. FACMGT.

COO

CEO

Submittal

Construction

For:

Approved CADD Information:

Date o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

RevisionsRevisions

VA FORM 08-6231A,JAN 1990

S:

\F

MS

\P

RO

JE

CT

S

SE

CT

IO

N\

PR

OJ

EC

TS

\2.

A me ric an La ke \A cti ve

\66 3A

4-

-2

Re pla ce

H

VA

C

HP

3 a t B uil din g 1 9\0

1 P re

-B id

Fo lde rs\

D es ign \C

AD

w ith (N

) D ra wi ng

S he et #s fo r 2

4-

3\E D1

.0.

dw g 6/1

8/2

Be di, G ag an de ep S

PL

OT

TE

D

BY

DEMOLITION NOTES:

1. SCHEDULE ALL ELECTRICAL SYSTEM OUTAGES WITH VA.

2. NOT ALL ELECTRICAL SYSTEMS ARE SHOWN. CONTRACTOR SHALL VISIT

SITE TO DETERMINE THE SCOPE OF ELECTRICAL DEMOLITION REQUIRED

AND INCLUDE ALL COSTS IN BID.

3. ELECTRICAL CIRCUITS SERVING EQUIPMENT BEYOND DEMOLITION

BOUNDARY SHALL REMAIN IN SERVICE. REROUTE CIRCUITS TO PROVIDE

CLEARANCE FOR THE CONSTRUCTION OF THIS PROJECT.

4. CONDUCTORS IN DEMOLITION AREA SHALL BE REMOVED BACK TO THE

SOURCE OR LAST ENERGIZED JUNCTION.

5. REROUTE CIRCUITS IN THE PATHWAY OF NEW DUCTWORK AND PIPING

ROUTES. CONTRACTOR TO VISIT SITE, DETERMINE WORK REQUIRED AND

INCLUDE COSTS IN BID.

6. DE-ENERGIZE/MAKE SAFE BEFORE PERFORMING ELEC. DEMO

7. LOTO CIRCUITS AT PANELBOARD 19M

AMERICAN LAKE CAMPUS

PARTIAL FLOOR PLAN - DEMOLITION REPLACE HVAC BLDG 19 - HP3

NCK

6/18/24

663A4-24-203

ED1.0

AREA OF WORK NO WORK

AREA OF WORK NO WORK

Drawn:Checked:

BB/MW

AutoCAD SHX Text

CANOPY ABOVE

AutoCAD SHX Text 1A20

AutoCAD SHX Text

126 SF

AutoCAD SHX Text

89 SF

AutoCAD SHX Text

100 SF

AutoCAD SHX Text 1A18

AutoCAD SHX Text

86 SF

AutoCAD SHX Text 1A16A

AutoCAD SHX Text 1A16

AutoCAD SHX Text

154 SF

AutoCAD SHX Text 1A17

AutoCAD SHX Text

99 SF

AutoCAD SHX Text 1A15

AutoCAD SHX Text

UP

AutoCAD SHX Text 1A24

AutoCAD SHX Text

114 SF

AutoCAD SHX Text 1A28

AutoCAD SHX Text

603 SF

AutoCAD SHX Text 1A23

AutoCAD SHX Text

90 SF

AutoCAD SHX Text 1A25

AutoCAD SHX Text

123 SF

AutoCAD SHX Text 1A25A

AutoCAD SHX Text

70 SF

AutoCAD SHX Text 1A21

AutoCAD SHX Text

243 SF

AutoCAD SHX Text 1A19

AutoCAD SHX Text

223 SF

AutoCAD SHX Text 1A22

AutoCAD SHX Text

67 SF

AutoCAD SHX Text 1A26

AutoCAD SHX Text

222 SF

AutoCAD SHX Text

FD

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text

MECH EQUIP

AutoCAD SHX Text F.E.C.

AutoCAD SHX Text

VA POLICE

AutoCAD SHX Text

1-HP3

AutoCAD SHX Text

1-CU2

SYMBOL DESCRIPTIONDESCRIPTION

SYMBOLS LEGEND - AIR HANDLING

DRAWING CONSTRUCTION ("FLAG") NOTE

MATCHLINE

REVISION CLOUD (ENCIRCLES DRAWING

CHANGES MADE SINCE THE PREVIOUS RELEASE)

DETAIL REFERENCE

REVISION REFERENCE

NORTH REFERENCE

N

XX.XX

X

SYMBOL

PLAN

DESCRIPTIONDESCRIPTION

SYMBOLS LEGEND - GENERAL

DETAIL IDENTIFICATION NUMBER

SHEET WHERE DETAIL IS DRAWN

X-XX EQUIPMENT IDENTIFIER

10X10

APAD

R

RECTANGULAR TO ROUND TRANSITION

ROUND BRANCH TO ROUND DUCT CONNECTION

ROUND BRANCH TO RECTANGULAR DUCT CONNECTION

RECTANGULAR BRANCH TO RECTANGULAR DUCT

CONNECTION WITH 45° TAPER

ROUND OR RECTANGULAR BRANCH TO ROUND OR

RECTANGULAR DUCT CONNECTION

RECTANGULAR OR ROUND, 90° ELBOW,

R/W OR R/D = 1.5

POSITIVE PRESSURE DUCT - TURNING TOWARD

POSITIVE PRESSURE DUCT - TURNING AWAY

NEGATIVE PRESSURE DUCT - TURNING TOWARD

NEGATIVE PRESSURE DUCT - TURNING AWAY

ROUND DUCT - TURNING TOWARD

ROUND DUCT - TURNING AWAY

FLEXIBLE CONNECTION

ACCESS DOOR (AD) OR ACCESS PANEL (AP)

VOLUME DAMPER

VERTICAL FIRE DAMPER (HORIZONTAL AIRFLOW)

MOTOR OPERATED DAMPER

BACKDRAFT DAMPER

FLEXIBLE DUCT

EQUIPMENT WITH EQUIPMENT IDENTIFICATION

THERMOSTAT

CEILING SUPPLY DIFFUSER

ROUND, 90° ELBOW, R/W OR R/D = 1.5

RECTANGULAR, 90° ELBOW, R/W OR R/D = 1.5

45° BRANCH CONNECTION

TRANSITION OR REDUCER - NOTED FOT (FLAT ON TOP) OR

FOB (FLAT ON BOTTOM) IF REQUIRED

INCLINE RISE (R) OR DROP (D) IN DIRECTION OF ARROW

PLAN

CEILING RETURN DIFFUSER

AIRFLOW, SUPPLY

AIRFLOW, RETURN

T

EQ-ID

DIFFUSER IDENTIFIER

DIFFUSER TYPE MARK

AIR FLOW (CFM)

M

BDD

140° POTABLE HOT WATER

120° POTABLE HOT WATER120°HW

140°HW

COLD WATER

HOT WATER

HOT WATER CIRCULATING

ID INDIRECT DRAIN

VENT

SOIL OR WASTE

THERMOMETER

SYMBOL DESCRIPTIONDESCRIPTION

SYMBOLS LEGEND - PIPING

PLAN & DIAGRAM

CAP

GATE VALVE

RELIEF VALVE

CHECK VALVE

EXISTING TO BE REMOVED (CROSSED)

HEAVY LINEWEIGHT INDICATES NEW WORK

POINT OF CONNECTION (POC) BETWEEN NEW

AND EXISTING

DIAGRAMPLAN

PLAN

PIPE TURNING DOWN / AWAY

PIPE TURNING UP / TOWARDS

PIPING OR DUCTED AIRFLOW

NON-DUCTED AIRFLOW

ELECTRICAL CONNECTION

ELECTRIC MOTOR/STARTER ASSEMBLY

ELECTRIC MOTOR OPERATOR (VALVES AND DAMPERS)

SYMBOL DESCRIPTIONDESCRIPTION

SYMBOLS LEGEND - PIPING & AIRFLOW DIAGRAMS

PLAN & DIAGRAM

M

M

MECHANICAL DRAWING LIST

MH0.0 MECHANICAL LEGEND, GENERAL NOTES, ABBREVIATIONS & DRAWING LIST

MH0.1 HVAC SCHEDULES

MD1.0 PARTIAL FLOOR PLAN - DEMO

MH2.1 PARTIAL FLOOR PLAN - HVAC & PIPING

MH2.2 SEQUENCE OF OPERATIONS & POINTS LIST

MH3.0 PARTIAL ROOF PLAN - HVAC

MH4.0 ZONING PLAN - HVAC

MH5.0 HVAC DETAILS

ENGLISH TO METRIC CONVERSION CHART

AIR FLOW LENGTH POWER

CFM Liters/Sec. Inches Millimeters Horsepower Killowatts 100 47.2 1/2" 13 mm 1/50 HP 0.01 KW 500 236.0 3/4" 19 mm 1/30 HP 0.02 KW

1000 472.0 1" 25 mm 1/6 HP 0.12 KW 15560 7344.3 1 1/4" 32 mm 1/3 HP 0.25 KW

1 1/2" 38 mm 1/8 HP 0.09 KW WATER FLOW 2" 51 mm 1/4 HP 0.19 KW

GPM Liters/Sec. 2 1/2" 64 mm 1/2 HP 0.37 KW 1 0.0631 3" 76 mm 3/4 HP 0.56 KW

100 6.31 3 1/2" 89 mm 1 HP 0.75 KW 4" 102 mm 1 1/2 HP 1.12 KW

TEMPERATURE 5" 127 mm 2 HP 1.49 KW Degrees F Degrees C 6" 152 mm 5 HP 3.73 KW

50° 10° 8" 203 mm 7 1/2 HP 5.59 KW 95° 35° 8 3/4" 222 mm 10 HP 7.45 KW 239° 115° 10" 254 mm 15 HP 11.18 KW

12" 305 mm 30 HP 22.35 KW PRESSURE 14" 356 mm

Feet KPa 24" 610 mm 1 30KPa 36" 914 mm

20 600KPa 38" 965 mm 40" 1016 mm

PRESSURE 48" 1219 mm PSIG KPa 60" 1524 mm

10 69KPa 70" 1778 mm 50 345KPa 96" 2438 mm

100 690KPa

STEAM FLOW - Lbs/Hr.

1000 #/Hr. 0.126 Kg/Sec.

ACTUATOR

AIRFLOW MEASURING UNIT

CURRENT TRANSDUCER

CURRENT SWITCH

DIFFERENTIAL PRESSURE

DIFFERENTIAL PRESSURE SWITCH

FREEZESTAT

SPEED

SMOKE DETECTOR

STATIC PRESSURE SENSOR

START/STOP

TEMPERATURE SENSOR

AVERAGING TEMPERATURE SENSOR

VARIABLE FREQUENCY DRIVE

ALARM

VFD

DUCT TEMPERATURE SENSOR

ELECTRIC ACTUATOR

SYMBOLS LEGEND - CONTROLS

ABBREVIATIONS

A AIR, AMP

AC AIR CONDITIONING UNIT

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

AL ALUMINUM, ACOUSTICAL LINING

ARRGT ARRANGEMENT

ATM ATMOSPHERE

BDD BACKDRAFT DAMPER

BFF BELOW FINISHED FLOOR

BFP BACKFLOW PREVENTER

BLDG BUILDING

BHP BRAKE HORSEPOWER

BOB BOTTOM OF BEAM

BOD BOTTOM OF DUCT

BOS BOTTOM OF STEEL

BTUH BRITISH THERMAL UNITS PER

HOUR

CAP CAPACITY

CC COOLING COIL

CLG CEILLING, COOLING

CD CEILING DIFFUSER

CFM CUBIC FEET PER MINUTE

CI CAST IRON

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CNTFGL CENTRIFUGAL

CO CLEANOUT

CONC CONCRETE

COND CONDENSATE

CONT CONTINUE, CONTROL

CP CIRCULATING PUMP

CRU CONDENSATE RETURN UNIT

CU FT CUBIC FEET

CU CONDENSING UNIT

CV CONSTANT VOLUME

CVTR CONVERTER

CW COLD WATER

dB DECIBLES

DB DRY BULB

DCVA DOUBLE CHECK VALVE ASSEMBLY

DF DRINKING FOUNTAIN

DMPR DAMPER

DN DOWN

DS DOWNSPOUT

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EF EXHAUST FAN

EFF EFFICIENCY

EG EXHAUST GRILLE

EL ELEVATION

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXP EXPANSION

EXT EXTERIOR, EXTERNAL

F FAHRENHEIT, FIRE LINE

FD FIRE DAMPER, FLOOR DRAIN

FDC FIRE DEPARTMENT CONNECTION

FLR FLOOR

FLTR FILTER

FM FLOW METER

FOB FLAT ON BOTTOM

FOT FLAT ON TOP

FPM FEET PER MINUTE

FPS FEET PER SECOND

FSD FIRE SMOKE DAMPER

FT FEET, FAN TERMINAL

FV FACE VELOCITY

GA GAGE

GAL GALLONS

GALV GALVANIZED

GPM GALLONS PER MINUTE

H HUMIDIFIER

HB HOSE BIBB

HC HEATING COIL

HD HEAD

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER, HEAT PUMP

HW HOT WATER

HWC HOT WATER CIRCULATING

ID INSIDE DIAMETER, INDIRECT DRAIN

IE INVERT ELEVATION

INT INTERIOR

KW KILOWATT

LAT LEAVING AIR TEMPERATURE

LB POUND, LINEAR BAR

LD LINEAR DIFFUSER

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH THOUSAND BTU PER HOUR

MD MANUAL DAMPER

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MOD MOTOR OPERATED DAMPER

MTR MOTOR

NC NORMALLY CLOSED

NIC NUMBER, NORMALLY OPEN

NTS NOT TO SCALE

OA OUTDOOR AIR

OC ON CENTER

OD OUTSIDE DIAMETER

OPNG OPENING

ORD OVERFLOW ROOF DRAIN

P PUMP, PLUMBING

PD PRESSURE DROP

POC POINT OF CONNECTION

P/T PRESSURE/TEMPERATURE

PVC POLYVINYL CHLORIDE

PR PUMPED RETURN

RA RETURN AIR

REF REFERENCE

REQD REQUIRED

RG RETURN GRILLE

RH RELIEF HOOD

RPM REVOLUTIONS PER MINUTE

SA SUPPLY AIR

SD STORM DRAIN, SMOKE DAMPER,

SUPPLY DIFFUSER

SG SUPPLY GRILLE

SL SOUNDLINING

SP STATIC PRESSURE

SS STAINLESS STEEL, SANITARY

SEWER

T THERMOSTAT

TG TRANSFER GRILLE

TOD TOP OF DUCT

TP TRAP PRIMER, TOTAL PRESSURE

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

V VENT, VOLT

VA VALVE

VTR VENT THROUGH ROOF

VRF VARIABLE REFRIGERANT FLOW

W WASTE, WATER, WATT

WB WET BULB

WG WATER GAGE

WH WATER HEATER, WALL HYDRANT

GENERAL NOTES

1. THE FULL SCOPE OF THE MECHANICAL WORK IS THE TOTAL OF WORK SHOWN ON THE PLANS AND

CALLED FOR IN THE SPECIFICATIONS. IN CASE OF CONFLICT, THE SPECIFICATIONS SHALL GOVERN.

PROVIDE A COMPLETE & FUNCTIONAL SYSTEM.

2. PERFORM ALL WORK IN ACCORDANCE WITH LOCAL CODES AND ORDINANCES. OBTAIN AND PAY FOR ALL REQUIRED PERMITS AND PAY FOR ALL FEES REQUIRED BY AUTHORITIES HAVING JURISDICTION.

PAY ALL ROYALTIES OR FEES REQUIRED IN CONNECTION WITH THE USE OF PATENTED DEVICES AND

SYSTEMS.

3. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR GENERAL CONSTRUCTION INCLUDING

LOUVERS, CONCRETE EQUIPMENT PADS, FLASHING DETAILS, ETC. REFER TO ARCHITECTURAL

DRAWINGS FOR ROOM ELEVATIONS, LOCATE MECHANICAL DEVICES SUCH AS TEMPERATURE

SENSORS, HUMIDISTATS, PANELS, ETC. SO THAT THEY DO NOT CONFLICT WITH GENERAL

CONSTRUCTION (WAINSCOT, DOOR HARDWARE, ETC.) NOR WITH ELECTRICAL SYSTEM (LIGHT

SWITCHES, SPEAKERS, OUTLETS, ETC.).

4. COORDINATE WITH OTHER TRADES: A) REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL

CHARACTERISTICS OF MECHANICAL EQUIPMENT (VOLTAGE, PHASE, HZ, ETC. B) PROVIDE ADEQUATE

CLEARANCE OF MECHANICAL WORK FROM ELECTRICAL ITEMS. MAINTAIN MINIMUM ACCESS OF

6-INCHES ABOVE ELECTRICAL CABLE TRAYS AND 18-INCHES TO THE SIDE OF CABLE TRAYS.

5. ARRANGE EQUIPMENT SO THAT ACCESS CLEARANCES INDICATED BY DRAWINGS, REQUIRED BY

CODES, OR RECOMMENDED BY MANUFACTURER ARE PROVIDED.

6. INSTALL MATERIALS AND SYSTEMS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ACCEPTED SUBMITTALS. INSTALL MATERIAL IN PROPER RELATION TO ADJACENT CONSTRUCTION

AND WITH UNIFORM APPEARANCE FOR EXPOSED WORK.

7. THOROUGHLY EXAMINE ALL AREAS WHERE EQUIPMENT, DUCTWORK, AND PIPING WILL BE INSTALLED

AND REPORT ANY CONDITION THAT PREVENTS THE PROPER INSTALLATION OF THE MECHANICAL

WORK.

8. COMPLY WITH THE DEPARTMENT OF VETERANS AFFAIRS HVAC DESIGN MANUAL AND

SPECIFICATIONS, WHICH INCLUDE THE DEVELOPMENT OF CONSTRUCTION AND AS-BUILT DRAWINGS, PROJECT MANUALS, AND SYSTEM BALANCING REPORTS.

9. COMPLY WITH THE DEPARTMENT OF VETERANS AFFAIRS HVAC DESIGN MANUAL AND SECTION 1.3 COMMISSIONING. THE HVAC CONTROL SYSTEM SHALL BE TESTED TO ENSURE THAT THE CONTROL DEVICES, EQUIPMENT AND SYSTEMS ARE CALIBRATED, ADJUSTED, AND OPERATE IN ACCORDANCE

WITH THE APPROVED PLANS AND SPECIFICATIONS. SEQUENCES OF OPERATION SHALL BE

FUNCTIONALLY TESTED TO ENSURE THEY OPERATE IN ACCORDANCE WITH THE APPROVED PLANS

AND SPECIFICATIONS.

10. THE COMMISSIONING SPECIFICATION, INCLUDING ALL FUNCTIONAL TEST PROCEDURES, SHALL BE

PROVIDED AND ENFORCED BY THE CONTRACTOR.

11. SUPPORTS AND SEISMIC RESTRAINTS SHALL BE PROVIDED WHERE REQUIRED IN ACCORDANCE WITH

LOCAL CODES, AND SMACNA SEISMIC RESTRAIN MANUAL, SHL(SEISMIC HAZARD LEVEL)-A.

12. PROVIDE A SINGLE SUBMITTAL OF ALL MECHANICAL EQUIPMENT AS SPECIFIED. AS A MINIMUM, SUBMIT PRODUCT DATA FOR ALL EQUIPMENT AND FIXTURES LISTED IN ACCOMPANYING SCHEDULES

FOR APPROVAL.

13. USE EXPERIENCED INSTALLERS. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH

MANUFACTURER'S INSTRUCTIONS.

14. ARRANGEMENT OF SYSTEMS INDICATED ON THE DRAWINGS IS DIAGRAMMATIC, AND INDICATES THE MINIMUM REQUIREMENTS FOR PLUMBING AND MECHANICAL WORK. ADJUST BOX LOCATIONS, BASED

ON FIELD MEASUREMENTS, TO AVOID INSTALLATION ABOVE DESKS. SITE CONDITIONS SHALL

DETERMINE THE ACTUAL ARRANGEMENT OF THE WORK. TAKE FIELD MEASUREMENTS BEFORE

PREPARING SHOP DRAWINGS, OBTAIN APPROVAL OF SHOP DRAWINGS BEFORE BEGINNING

FABRICATION. BE RESPONSIBLE FOR ACCURACY OF DIMENSIONS AND LAYOUT. OVERHEAD PIPING

AND DUCTWORK SHALL BE ARRANGED TO OBTAIN MAXIMUM HEAD ROOM. SHOP DRAWINGS SHALL

BE STAMPED BY A LICENSED ENGINEER.

15. CLEAN AND PROTECT WORK FROM DAMAGE. RESTORE DAMAGED FINISHES. COVER ENDS OF

PIPING AND DUCTWORK NOT ACTIVELY BEING WORKED ON.

16. MODIFY AND EXTEND EXISTING SERVICE TO ACCOMMODATE NEW WORK. RELOCATE EXISTING

COMPONENTS AS REQUIRED FOR NEW SYSTEM. COORDINATE WITH BUILDING MANAGEMENT.

17. PROVIDE PRODUCTS OF MANUFACTURERS, THAT ARE ACCEPTED BY THE VA CONTRACTING

OFFICER. DELIVER, HANDLE, AND STORE MATERIALS IN ACCORDANCE WITH MANUFACTURER'S

INSTRUCTIONS.

18. DO NOT CUT STRUCTURAL ELEMENTS WITHOUT PRIOR WRITTEN APPROVAL.

19. CONCEAL PIPING AND DUCTWORK TO THE GREATEST EXTENT PRACTICAL.

20.…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .