This document is a technical specification section (Section 22 35 00) for Domestic Water Heat Exchangers for a construction project at the VA Medical Center (VAMC) in Miami, Florida. The specification details requirements for indirect water heating systems using steam or hot water, with comprehensive guidelines for heat exchangers, including materials, construction, testing, and installation requirements. Key technical specifications include a packaged hot water storage tank with a heat exchanger coil, constructed of phase-balanced stainless steel with specific chromium content, a circulating pump, and advanced control systems featuring temperature controls, safety valves, and BACnet communication capabilities.
The document outlines rigorous quality assurance standards, requiring ETL listing, ASME certification, compliance with NSF standards for potable water components, and adherence to ASHRAE energy efficiency guidelines. Installation requirements include specific testing protocols such as hydrostatic pressure testing, performance testing to ensure water temperature consistency, and commissioning procedures. The specification also mandates a comprehensive warranty covering the storage tank (25 years), heat exchanger (1-3 years), and other components (1 year), with additional requirements for manufacturer's technical representative training and documentation. The project is part of a larger effort to construct a new boiler building and controls in the old incinerator area at the VAMC Miami facility.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM NO. 1
May 31, 2024
CONSTRUCT A NEW BOILER BUILDING AND
CONTROLS IN THE OLD INCENERATOR AREA
EXPAND/MOVE GRAPHIC CONTROL
VAMC MIAMI, FLORIDA
546-22-110 22 35 00-1
SECTION 22 35 00
DOMESTIC WATER HEAT EXCHANGERS
PART 1 GENERAL
1.1 DESCRIPTION
A. This section describes the requirements for domestic hot water heat exchangers including thermometers and all necessary accessories, connections and equipment.
B. Application is for indirect water heating utilizing steam or hot water as a medium and can be used for heat recovery or solar systems for pre-heating water prior to primary water heating equipment.
C. A complete listing of common acronyms and abbreviations are included in Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING.
1.2 RELATED WORK
A. Section 01 00 00, GENERAL REQUIREMENTS.
B. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
C. Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS.
D. Section 01 91 00, GENERAL COMMISSIONING REQUIREMENTS./
E. Section 03 30 00, CAST-IN-PLACE CONCRETE: Concrete and Grout.
F. Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING.
G. Section 22 05 19, METERS AND GAGES FOR PLUMBING PIPING.
H. Section 22 05 23, GENERAL-DUTY VALVES FOR PLUMBING PIPING.
I. Section 22 08 00, COMMISSIONING OF PLUMBING SYSTEMS.
J. Section 22 11 23, DOMESTIC WATER PUMPS: Circulating Pump.
1.3 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. Where conflicts occur these specifications and the VHA standards will govern.
B. American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE):
90.1-2019 Energy Standard for Buildings Except Low-Rise
Residential Buildings
C. American National Standard Institute (ANSI):
Z21.22-2015 Relief Valves for Hot Water Supply Systems
D. American Society of Mechanical Engineers (ASME):
ASME Boiler and Pressure Vessel Code -
BPVC Section IV-2021 Rules for Construction of Heating Boilers
BPVC Section VIII-1-2032 Rules for Construction of Pressure Vessels, Division 1
Form U-1 Manufacturer’s Data Report for Pressure
Vessels
B1.20.1-2013(R2018) Pipe Threads, General Purpose (Inch)
B16.5-2020 Pipe Flanges and Flanged Fittings: NPS 1/2 through NPS 24 Metric/Inch Standard
CONSTRUCT A NEW BOILER BUILDING AND
546-22-110 22 35 00-2
B16.24-2016
Cast Copper Alloy Pipe Flanges, Flanged
Fittings, and Valves: Classes 150, 300, 600, 900, 1500, and 2500
PTC 25-2018 Pressure Relief Devices
E. National Fire Protection Association (NFPA):
70-2020 National Electrical Code (NEC)
F. NSF International (NSF):
61-2020 Drinking Water System Components – Health
Effects
372-2020 Drinking Water System Components – Lead
Content
G. Underwriter Laboratories (UL):
207-2009(R2020) Standard for Refrigerant-Containing
Components and Accessories, Nonelectrical
778-2016(R2019) Standard for Motor-Operated Water Pumps
1.4 SUBMITTALS
A. Submittals, including number of required copies, shall be submitted in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES.
B. Information and material submitted under this section shall be marked “SUBMITTED UNDER SECTION 22 35 00, DOMESTIC WATER HEAT EXCHANGERS”, with applicable paragraph identification.
C. Manufacturer's Literature and Data Including: Full item description and optional features and accessories. Include dimensions, weights, materials, applications, standard compliance, model numbers, size, and capacity.
1. Heat Exchangers.
2. Heat Reclaimers.
3. Pressure and Temperature Relief Valves.
4. Steam Control Valves.
5. Thermometers.
6. Pressure Gauges.
7. Vacuum Breakers.
8. Safety Valves.
9. Expansion Tanks.
10. Circulating Pumps.
11. Steam Traps.
12. Heat Traps.
D. A Form U-1 or other documentation stating compliance with the ASME Boiler and Pressure Vessel Code.
E. Shop drawings shall include wiring diagrams for power, signal and control functions.
F. Submit documentation indicating compliance with applicable requirements of ASHRAE 90.1, Unfired Storage Tanks, for Service Water Heating.
G. Complete operating and maintenance manuals including wiring diagrams, technical data sheets, information for ordering replaceable parts, and troubleshooting guide:
1. Include complete list indicating all components of the systems.
2. Include complete diagrams of the internal wiring for each item of equipment.
CONSTRUCT A NEW BOILER BUILDING AND
546-22-110 22 35 00-3
3. Diagrams shall have their terminals identified to facilitate installation, operation and maintenance.
H. Completed System Readiness Checklist provided by the CxA and completed by the contractor, signed by a qualified technician and dated on the date of completion, in accordance with the requirements of Section 22 08 00, COMMISSIONING OF PLUMBING SYSTEMS.
I. Submit training plans and instructor qualifications in accordance with the requirements of Section 22 08 00, COMMISSIONING OF PLUMBING SYSTEMS.
1.5 QUALITY ASSURANCE
A. ETL listed and labeld, entire water heater.
B. Water heater shall bear the ASME HLW Stamp and be registered with the National Board of Boiler and Pressure Vessel Inspectors (NBBI).
C. Equipment components in contact with potable water shall meet compliance requirements in documents NSF 61 and NSF 372.
D. Comply with American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) 90.1 for efficiency performance.
E. The heat exchanger shall be certified and labeled by an independent testing agency.
F. Circulating pump power shall be installed per NFPA 70.
G. Bio-Based Materials: For products designated by the USDA’s Bio-Preferred Program, provide products that meet or exceed USDA recommendations for bio-based content, so long as products meet all performance requirements in this specifications section. For more information regarding the product categories covered by the Bio-Preferred Program, visit https://www.biopreferred.gov.
H. Refer to Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for additional sustainable design requirements.
1.6 AS-BUILT DOCUMENTATION
A. Comply with requirements in Paragraph AS-BUILT DOCUMENTATION of Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING.
1.7 WARRANTY
A. Storage Tank: 25-Years, including 15-Year full coverage and 10-Year prorated coverage, for manufacturing and material defects, leaks, production of rusty water, and chloride stress corrosion cracking.
B. Heat Exchanger: One-Year coverage for manufacturing and material defects, leaks, and production of rusty water.
C. Heat Exchanger: 3-Year coverage for manufacturing and material defects, leaks, and production of rusty water.
D. All Other Components: One-Year coverage for manufacturing and material defects, leaks, and production of rusty water.
E. The heater shall have a first year service policy, which shall cover labor and freight for warranty covered services.
PART 2 PRODUCTS
2.1 CIRCULATING DOMESTIC WATER HEAT EXCHANGERS
A. A packaged hot water storage tank with heat exchanger coil; circulator, controls, sacrificial anode, and specialties for heating domestic water. The domestic water heat exchanger with circulator shall be based upon a standard flow arrangement with water from bottom of storage tank circulated across the heat exchanger coil and returned to tank. The vessel shall be ASME
CONSTRUCT A NEW BOILER BUILDING AND
546-22-110 22 35 00-4
BPVC Section VIII-1, fabricated with a pressure rating of 1034 kPa (150 psig). Tank shall comply with NSF 61 and NSF 372 for barrier materials for potable-water tank linings. Provide with access for cleaning and disinfection.
B. The vessel shall be unlined and constructed of phase-balanced, austenitic and ferritic, duplex, stainless-steel. The chemical structure of the stainless-steel shall contain a minimum of 21 percent chromium and be certified per ASTM A 923 Methos A. Materials of construction shall also be certified as passing chloride stress cracking test protocols as defined in ISO 3651-2 and ASTM G 123-00 (2005) " Standard Test Method for Evaluating Stress-Sorrosion Cracking of Stainless Alloys with Different Nickel Content in Boiling Acidified Sodium Chloride Solution."
C. A hot water outlet shall be included at the top of the tank.
D. A temperature sensor shall be located inside the storage tank.
E. A water pressure gauge located on the storage tank.
F. A circulating pump complying with UL 778, all bronze construction, overhung impeller, and separately coupled inline pump shall be included. The pump shall have mechanical seals. The working pressure shall be rated at 861 kPa (125 psig). Refer to Section 22 11 23, DOMESTIC WATER PUMPS for additional requirements.
G. The stand shall be factory-fabricated for floor mounting.
H. The tappings (openings) shall be factory-fabricated of materials compatible with the tank and in accordance with appropriate ASME standards for piping connections, pressure and temperature relief valve, pressure gauge, thermometer, drain valve, anode rods and controls.
The openings shall be in accordance with ASME standards listed below:
1. 50 mm or DN50 (NPS 2 inch) and smaller: Threaded ends according to ASME B1.20.1.
2. 65 mm or DN65 (NPS 2-1/2 inch) and larger: Flanged ends according to ASME B16.5 for steel and stainless-steel flanges, and according to ASME B16.24.
I. Shell fiberglass insulation shall comply with ASHRAE 90.1 and suitable for operating temperature, with jacket. The entire shell and nozzles shall be completely surrounded except connections and controls.
J. The heat exchanger coils shall be constructed from cupro-nickel and fabricated in a u-tube configuration for steam heating medium. The pressure rating shall be equal to or greater than the steam or water supply pressure plus 50 percent, but not less than 1034 kPa (150 psig).
K. The relief valves shall be ASME rated and stamped for combination temperature and pressure relief valves.
L. On the steam and condensate systems, provide an inlet y-strainer and a float and thermostatic type steam trap for both upstream of the steam valve and at the outlet of the heat exchanger.
M. On the steam system, provide a 0-60 PSIG pressure gauge.
N. Packaged Controls
1. The temperature controls shall be based upon an adjustable temperature transmitter that operates a control valve and is capable of maintaining outlet water temperature within 2 degrees C (4 degrees F) of setting of 60 degrees C (140 degrees F). Heaters shall be capable of raising the discharge temperature to 77 to 82 degrees C (170 to 180 degrees F) for thermal eradication.
2. Pilot-operated, solenoid inlet steam valve with built-in double-solenoid safety system.
3. Safety control shall be automatic, high temperature limit shutoff device with manual reset.
4. Electronic, low-water cut-off with a test and reset function.
5. Protocol gateway for BACnet communication. Coordinate with existing BAS controls system for specific protocol.
6. Alarm with switched contacts for remote notification.
7. 95dB local, audible alarm with silencing switch.
CONSTRUCT A NEW BOILER BUILDING AND
546-22-110 22 35 00-5
2.2 THERMOMETERS
A. Thermometers shall be rigid stem or remote sensing, scale or dial type with an aluminum, black metal, stainless-steel, or chromium plated brass case. The thermometer shall be back connected, red liquid (alcohol or organic-based) fill, vapor, bi-metal or gas actuated, with 228 mm (9 inches) high scale dial or circular dial 50 to 127 mm (2 to 5 inches) in diameter graduated from 4 to 100 degrees C (40 to 212 degrees F), with two-degree graduations guaranteed accurate within one scale division. The socket shall be separable, double-seat, micrometer-fittings, with extension neck not less than 63 mm (2 1/2 inches) to clear tank or pipe covering. The thermometer shall be suitable for 19 mm (3/4 inch) pipe threads. Thermometers may be console-mounted with sensor installed in separate thermometer well.
2.3 SAFETY VALVES FOR SHELL AND COIL HEATERS
A. Separate combination pressure/temperature relief valves shall be provided on each water heater.
B. A double solenoid safety system shall be provided for each shell and coil heater to function as a safety over temperature prevention system. System shall consist of aquastat, pilot light, solenoid safety valve and solenoid water safety valve located in the control circuit. The aquastat shall be set at 60 degrees C (140 degrees F). Shutoff valves shall comply with Section 22 05
23, GENERAL-DUTY VALVES FOR PLUMBING PIPING.
2.4 DOMESTIC HOT WATER EXPANSION TANKS
A. A steel pressure rated tank constructed with welded joints and factory installed butyl rubber diaphragm shall be installed as scheduled. The air precharge shall be set to minimum system operating pressure at tank.
B. The tappings shall be factory-fabricated steel, welded to the tank and include ASME B1.20.1 pipe thread.
C. The interior finish shall comply with NSF 61 and NSF 372 for barrier materials for potable water tank linings and the liner shall extend into and through the tank fittings and outlets.
D. The air charging valve shall be factory installed.
2.5 HEAT TRAPS
A. Heat traps shall be installed in accordance with ASHRAE 90.1 unless provided integrally with the heaters.
2.6 COMBINATION TEMPERATURE AND PRESSURE RELIEF VALVES
A. The combination pressure and temperature relief Valve shall be ANSI Z21.22 and ASME rated and constructed of all brass or bronze with a self-closing reseating valve. The relief valves shall include a relieving capacity greater than the heat input and include a pressure setting less than the water heater’s working pressure rating. Sensing element shall extend into storage tank.
PART 3 EXECUTION
3.1 INSTALLATION
A. If an installation is unsatisfactory to the COR, the contractor shall correct the installation at no additional cost or time to the Government.
B. The water heaters shall be installed on concrete bases. Refer to Specification Section 03 30 00, CAST-IN-PLACE CONCRETE and Section 22 05 11, COMMON WORK RESULTS FOR
PLUMBING.
C. The water heaters shall be installed level and plumb and securely anchored.
D. Water heaters shall be installed and connected in accordance with manufacturer’s written instructions with manufacturer’s recommended clearances.
CONSTRUCT A NEW BOILER BUILDING AND
546-22-110 22 35 00-6
E. All pressure and temperature relief valves discharge shall be piped to nearby floor drains with air gap or break.
F. Thermometers and isolation valves shall be installed on water heater inlet and outlet piping and shall be positioned such that they can be read by an operator or staff standing on floor or walkway.
G. The thermostatic control shall be set for a minimum setting of 60 degrees C (140 degrees F) for storage heaters.
H. Shutoff valves shall be installed on the domestic water supply piping to the water heater and on the domestic hot water outlet piping.
I. All manufacturer’s required clearances shall be maintained.
J. A combination temperature and pressure relief valve shall be installed at the top portion of the storage tank. The sensing element shall extend into the tank. The relief valve outlet drain piping shall discharge by air gap into a floor drain.
K. Piping type heat traps shall be installed on the inlet and outlet piping of the domestic water heater storage tanks, unless provided integrally with the tanks.
L. Water heater drain piping shall be installed as indirect waste to spill by air gap into open drains or over floor drains. Hose end drain valves shall be installed at low points in water piping for gas fueled domestic hot water heaters without integral drains.
M. Dielectric unions shall be provided if there are dissimilar metals between the water heater connections and the attached piping.
N. Provide vacuum breakers per ANSI Z21.22 on the inlet pipe if the water heater is bottom fed.
3.2 LEAKAGE TEST
A. Before piping connections are made, the water heaters shall be tested at a hydrostatic pressure of 1380 kPa (200 psig) for water heaters rated at less than 1104 kPa (160 psig) and 1654 kPa (240 psig) for units with an maximum working pressure of 1104 kPa (160 psig) or over. Any failed test shall be corrected and the water heater shall be replaced with a new unit at no additional cost or time to the Government.
3.3 PERFORMANCE TEST
A. Ensure that all the remote water outlets are always tested to a minimum of 43 degrees C (110 degrees F) and a maximum of 49 degrees C (120 degrees F) water flow. If necessary, make all correction to balance the return water system or reset the thermostat to make the system comply with design requirements.
3.4 STARTUP AND TESTING
A. Perform tests ss recommended by product manufacturer and listed standards and under actual or simulated operating conditions and prove full compliance with design and specified requirements. Tests of the various items of equipment shall be performed simultaneously with the system of which each item is an integral part.
B. The tests shall include system capacity, control function, and alarm functions.
C. When any defects are detected, correct defects and repeat test at no additional cost or time to the Government.
D. The CxA will observe startup and contractor testing of selected equipment. Coordinate the startup and contractor testing schedules with the COR and CxA. Provide a minimum notice of 10 working days prior to startup and testing.
3.5 COMMISSIONING
A. Provide commissioning documentation in accordance with the requirements of Section 22 08
00, COMMISSIONING OF PLUMBING SYSTEMS.
CONSTRUCT A NEW BOILER BUILDING AND
546-22-110 22 35 00-7
B. Components provided under this section of the specification will be tested as part of a larger system.
3.6 DEMONSTRATION AND TRAINING
A. Provide services of manufacturer’s technical representative for 4 hours to instruct each VA Personnel responsible in operation and maintenance of the system.
B. Submit training plans and instructor qualifications in accordance with the requirements of Section 22 08 00, COMMISSIONING OF PLUMBING SYSTEMS.
END OF SECTION