Attachment 2- Sally Port Drawings.pdf

PDF 18 MB Posted

Attached to
Control Panel - Sally Port Replacement
Solicitation number
644-26-021326
Issued by
Hidalgo County, Texas

About this file

Sally Port Control Panel Replacement - Technology Drawings and Specifications

This document is a comprehensive technical specification and drawings package for the Evins State Juvenile Correctional Facility Sally Port Replacement project located in Texas. The project involves the replacement of a control panel system for remote operation of secured doors and gates within the facility's sally port area. The scope of work includes installation of access control systems, security cameras, intercom/PA systems, structured cabling infrastructure, and associated technology equipment across multiple facility areas including the lobby, control room, mechanical rooms, electrical rooms, storage, and toilet facilities. The drawings package consists of a responsibility matrix clearly delineating work scope between Division 27 (Communications Technology) and Division 28 (Security Systems), detailed floor plans showing device locations, site plans, equipment schedules, and control panel layouts. The project specifications require coordination with the facility architect and owner prior to rough-in work, field verification of exact device locations and mounting heights, and adherence to all applicable codes and industry standards including NEC, ANSI/EIA/TIA, and BICSI guidelines.

The installation requirements mandate that all 120-volt power for system functionality be dedicated circuits on emergency power when available, with the electrical contractor responsible for all power connections to main control panels and head-end equipment. Conduit sizing must maintain a 40 percent maximum fill ratio, and all exposed system wiring must be routed in conduit or installed in plenum-rated materials. The contractor must employ certified integrators and installers authorized by specified system manufacturers and provide cable support using Panduit J-MOD systems directly connected to building steel joists. All network data cable runs are limited to a maximum of 295 feet total length without prior architect approval, and cables must maintain minimum 12-inch separation from AC power and other signal cables except at 90-degree crossings. The project requires magnetic door contacts at all roof hatches, proper lightning protection on all communication cables between buildings, and fire blocking to maintain wall ratings, with all installations subject to ADA accessibility compliance standards.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RESPONSIBILITY MATRIX

SCOPE OF WORK RESPONSIBILITY

OFOI

DIV 27 - COMMUNICATIONS

TECHNOLOGY SCOPE

DIV 28 - SECURITY SYSTEMS

ACCESS CONTROL SYSTEM

STRUCTURED CABLING

CABLE TRAY IN ER/TR

CABLE PATHWAY OUTSIDE ER/TR

TELECOM GROUNDING SYSTEM

BACK BOXES, CONDUITS/SLEEVES

EQUIPMENT RACKS/CABINETS

WIRELESS ACCESS POINTS

NETWORK SWITCHES

UPS

TELEPHONES

WORKSTATION PC

CARD READERS

DOOR CONTACTS

ELECTRIFIED LOCKS

REX INSIDE DOOR

PUSH TO EXIT

PIR SENSORS

LOW VOLTAGE POWER SUPPLY

ACCESS CONTROL PANELS

EQUIPMENT RACKS/CABINETS

BACK BOXES, CONDUITS/SLEEVES

COMPOSITE CABLING

NETWORK CABLING REQUIRED

CREDENTIAL CARDS

BADGE PRINTERS

OFCI CFCI

PDU

BACKBONE CABLING

X

X

X

X

X

OFOI OFCI CFCI

X

X

X

DESCRIPTIONTEXT

INDICATES THAT THE DESIGNATED DEVICE IS TO BE WALL MOUNTED AT SPECIFIED HEIGHT OR

IN COMPLIANCE WITH CODE REQUIREMENTS. ALL WALL MOUNTED HEIGHTS ARE TO BE

CONFIRMED WITH THE PROJECT'S ARCHITECT PRIOR TO ROUGH-IN.

INDICATES THAT THE DESIGNATED DEVICE SHALL BE WEATHER PROOF AND RATED FOR

EXTERIOR CONDITIONS INSTALLATION.

INDICATES THAT THE DESIGNATED DEVICE IS TO BE INSTALLED ABOVE THE COUNTERTOP. A

NUMERIC VALUE SHALL REPLACE THE '#' SYMBOL AND SHALL DESIGNATE THE SPECIFIC HEIGHT

ABOVE COUNTER. ALL HEIGHTS ARE TO BE CONFIRMED WITH THE PROJECT'S ARCHITECT

PRIOR TO ROUGH-IN.

INDICATES THAT THE DESIGNATED DEVICE IS TO BE INSTALLED ABOVE THE FINISHED FLOOR. A NUMERIC VALUE SHALL REPLACE THE '#' SYMBOL AND SHALL DESIGNATE THE SPECIFIC HEIGHT ABOVE FINISHED FLOOR. ALL HEIGHTS ARE TO BE CONFIRMED WITH THE PROJECT'S ARCHITECT

PRIOR TO ROUGH-IN.

INDICATES THAT THE DESIGNATED DEVICE IS TO BE INSTALLED ABOVE THE GRADE LEVEL. A

NUMERIC VALUE SHALL REPLACE THE '#' SYMBOL AND SHALL DESIGNATE THE SPECIFIC HEIGHT

ABOVE GRADE. ALL HEIGHTS ARE TO BE CONFIRMED WITH THE PROJECT'S ARCHITECT PRIOR

TO ROUGH-IN.

INDICATES THAT THE DESIGNATED DEVICE IS TO BE SURFACE MOUNTED. CONTRACTOR TO

PROVIDE ALL MATERIALS REQUIRED FOR A COMPLETE, SURFACE MOUNTED SOLUTION. ALL

SURFACE MOUNTED PRODUCTS SHALL BE APPROVED BY THE PROJECT'S ARCHITECT PRIOR TO

PROCUREMENT AND/OR INSTALLATION.

INDICATES THAT THE DESIGNATED DEVICE IS TO BE MOUNTED ON THE UNDERSIDE OF THE

ELEVATED CANOPY.

INDICATES THAT THE DESIGNATED DEVICE IS TO BE INSTALLED UNDER A RAISED FLOOR

SYSTEM.

INDICATES THAT THE DESIGNATED DEVICE IS TO BE CORNER MOUNTED AT SPECIFIED HEIGHT.

ALL WALL MOUNTED HEIGHTS ARE TO BE CONFIRMED WITH THE PROJECT'S ARCHITECT PRIOR

TO ROUGH-IN.

TYPICAL SUBSCRIPTS LEGEND

'WM'

'WP'

'AC'

'AFF'

'AG'

'SM'

'UC'

'UF'

'CM'

GENERAL NOTES

SECURITY GENERAL NOTES

TECHNOLOGY GENERAL NOTES

D E

V

IC

E S

TECHNOLOGY LEGEND

DESCRIPTIONSYMBOLG

R O

U P

'D#'

INDICATES THE LOCATION OF A NEW TECHNOLOGY OUTLET. CONTRACTOR TO

PROVIDE FACEPLATE WITH A MINIMUM OF 4-PORTS AT EACH LOCATION UNLESS

OTHERWISE NOTED. ELECTRICAL CONTRACTOR TO PROVIDE A DOUBLE GANG

BACK BOX WITH A SINGLE GANG REDUCER RING AND A 1" EMT CONDUIT FROM THE

BOX TO THE NEAREST ACCESSIBLE CEILING. SOME EXISTING BUILDINGS MAY

REQUIRE SURFACE MOUNTED RACEWAY. ELECTRICAL CONTRACTOR TO PROVIDE

AND INSTALL RACEWAY AS SPECIFIED AND DESIGNATE IN THE ELECTRICAL

CONTRACT DOCUMENTS. SYSTEM INSTALLER TO PROVIDE AND INSTALL A PLASTIC

PROTECTIVE BUSHING, ON EACH CONDUIT STUB-OUT, TO PREVENT CABLE

DAMAGE.

INDICATES THE LOCATION OF A FLOOR MOUNTED TECHNOLOGY OUTLET.

ELECTRICAL CONTRACTOR TO PROVIDE AND INSTALL A FLOOR BOX WITH (1) 1"

CONDUIT PER EVERY (6) CABLES INSTALLED. ALL CONDUITS SHALL ROUT FROM

THE FLOOR BOX, DIRECTLY TO THE WALL INDICATED AND STUB-UP INTO THE

NEAREST ACCESSIBLE PLENUM CEILING.

INDICATES THE LOCATION OF A CEILING MOUNTED OUTLET. CONTRACTOR SHALL

MOUNT THIS OUTLET AT +12" ABOVE THE CEILING AND COORDINATE ALL FINAL

LOCATIONS WITH OTHER TRADES ON THE PROJECT TO VERIFY THAT THE

LOCATION OF THE OUTLET MAINTAINS 12" OF CLEARANCE FROM THE FRONT OF

THE FACEPLATE FOR OWNER ACCESS. ELECTRICAL CONTRACTOR SHALL ROUTE

(1) 1" CONDUIT FROM THE BUILDING STRUCTURE TO A SINGLE GANG BACK BOX

MOUNTED AT 5' OR LESS ABOVE THE FINISHED CEILING. SECURE CONDUIT AND

BACK BOX TO INSURE MINIMAL SWAY MOVEMENT.

DESIGNATES THAT THE ASSOCIATED TECHNOLOGY OUTLET IS INTENDED FOR THE

USE OF A NETWORK CONNECTION. THE '#' SHALL BE REPLACED WITH NUMERIC

TEXT THAT IDENTIFIES THE TOTAL NUMBER OF CATEGORY 6, NETWORK CABLES

THAT ARE TO BE INSTALLED AT THE TECHNOLOGY OUTLET LOCATION.

CONTRACTOR TO PROVIDE AND INSTALL CATEGORY 6 NETWORK CABLES,

CATEGORY 6 CONNECTORS, STAINLESS STEEL FACEPLATES WITH IDENTIFICATION

WINDOWS, LABELS, BLANK INSERTS, AND ANY OTHER MATERIALS REQUIRED TO

FURNISH A COMPLETE FUNCTIONAL AND TESTED OUTLET LOCATION. ALL

FACEPLATES PROVIDED SHALL CONTAIN A MINIMUM 4-PORTS AND SHALL BE

APPROPRIATELY SIZED TO ACCOMMODATE THE NUMBER OF CIRCUITS BEING

INSTALLED AT THIS TECHNOLOGY OUTLET LOCATION. MAXIMUM OF SIX(6) DATA

CABLES PER OUTLET.

DESIGNATES THAT THE ASSOCIATED TECHNOLOGY OUTLET IS INTENDED FOR THE

USE OF A WALL MOUNTED TELEPHONE CONNECTION. CONTRACTOR TO PROVIDE

AND INSTALL (1) CATEGORY 6 NETWORK CABLE, (1) CATEGORY 6 CONNECTOR,

STAINLESS STEEL WALL TELEPHONE FACEPLATE, LABELS, AND ANY OTHER

MATERIALS REQUIRED TO FURNISH A COMPLETE FUNCTIONAL AND TESTED

CIRCUIT AT EACH LOCATION SHOWN. CONTRACTOR SHALL MOUNT THIS OUTLET

AT +42" AFF AND COORDINATE ALL FINAL LOCATIONS WITH OTHER TRADES ON THE

PROJECT TO VERIFY THAT THE LOCATION OF THE OUTLET MAINTAINS 8" OF

CLEARANCE ON ALL FOUR SIDES OF THE BACK BOX. OUTLETS SHALL REMAIN

CLEAR OF ROOM DOORS, CABINET DOORS, APPLIANCE DOORS, AND SLIDING

DRAWERS.

DESIGNATES THAT THE ASSOCIATED TECHNOLOGY OUTLET IS INTENDED FOR THE

USE OF A WIRELESS ACCESS POINT CONNECTION. CONTRACTOR TO PROVIDE AND

INSTALL (1) CATEGORY 6 NETWORK CABLE, (1) CATEGORY 6 CONNECTOR,

STAINLESS STEEL FACEPLATE WITH IDENTIFICATION WINDOWS, LABELS, AND ANY

OTHER MATERIALS REQUIRED TO FURNISH A COMPLETE FUNCTIONAL AND

TESTED CIRCUIT AT EACH LOCATION SHOWN. REFERENCE SPECIFICATIONS FOR

PATCH CABLE REQUIREMENTS.

INDICATES THE LOCATION OF AN IP VIDEO SURVEILLANCE CAMERA. CONTRACTOR

TO PROVIDE AND INSTALL CATEGORY 6 NETWORK CABLES, CATEGORY 6

CONNECTORS, STAINLESS STEEL FACEPLATES WITH IDENTIFICATION WINDOWS,

LABELS, BLANK INSERTS, AND ANY OTHER MATERIALS REQUIRED TO FURNISH A

COMPLETE FUNCTIONAL AND TESTED OUTLET LOCATION. ALL FACEPLATES

PROVIDED SHALL BE APPROPRIATELY SIZED TO ACCOMMODATE THE NUMBER OF

CIRCUITS BEING INSTALLED AT THIS OUTLET LOCATION. REFERENCE

SPECIFICATIONS FOR PATCH CABLE REQUIREMENTS.

INDICATES THAT THE ASSOCIATED TECHNOLOGY OUTLET IS INTENDED FOR

FUTURE USE. CONTRACTOR TO PROVIDE STAINLESS STEEL, SINGLE-GANG WALL

PLATE AT ALL LOCATIONS.

'W'

'AP'

'B'

NOTES:

1. REFERENCE TECHNOLOGY GENERAL NOTES, PLAN KEYED NOTES, AND ALL OTHER SYSTEM

LEGENDS/NOTES. THE STRUCTURED CABLING SYSTEM CONTRACTOR SHALL PROVIDE AND

INSTALL CATEGORY 6 CABLE TO ALL SYSTEMS' EQUIPMENT REQUIRING NETWORK CONNECTIVITY.

NOTES TO CONTRACTOR

DESCRIPTIONTEXT

INDICATES THAT THE DEVICE IS EXISTING TO REMAIN. CONTRACTOR TO REMOVE DEVICE

AND PLACE IN THE SAME LOCATION AS NEEDED.

INDICATES THAT THE DEVICE IS EXISTING AN IS TO BE REMOVED. CONTRACTOR TO

REMOVE THE DEVICE AND RETURN TO OWNER.

INDICATES THAT THE DEVICE IS EXISTING AND SHALL BE REPLACED. REFERENCE NEW

SYSTEM LAYOUT FOR EXACT LOCATIONS.

INDICATES THAT THE DEVICE IS EXISTING AND SHALL BE REMOVED AND RELOCATED TO A

LOCATION INDICATED ON THE DRAWINGS. REFERENCE NEW SYSTEM LAYOUT FOR EXACT

LOCATIONS.

SUBSCRIPTS LEGEND - EXISTING DEVICES

'E'

'D'

'R'

'RR'

1. ALL 120V POWER REQUIRED FOR THE FUNCTIONALITY OF EACH SYSTEM SHALL BE A DEDICATED CIRCUIT AND ON EMERGENCY POWER WHEN AVAILABLE. PROJECTS ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER TO MAIN CONTROL PANELS, REMOTE POWER SUPPLIES AND ALL HEAD END EQUIPMENT. SYSTEM INSTALLERS SHALL COORDINATE LOCATIONS AND CONNECTIONS WITH

THE PROJECT'S ELECTRICAL CONTRACTOR.

2. THE PROJECT'S ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONDUITS, BACK BOXES, JUNCTION BOXES, RACEWAYS AND SLEEVES REQUIRED TO ESTABLISH CLEAR PATHWAYS FOR ALL SYSTEMS. ALL CONDUITS, SLEEVES, BOXES, AND RACEWAYS SHALL BE PROPERLY SIZED TO MAINTAIN

A 40% MAXIMUM FILL RATIO.

3. ALL EXPOSED SYSTEM'S WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILING SHALL BE ROUTED IN CONDUIT, PROVIDED AND INSTALLED BY THE PROJECT'S ELECTRICAL CONTRACTOR. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE FILL RATIO. MINIMUM CONDUIT SIZE

SHALL BE 3/4".

4. EACH SYSTEM INSTALLER SHALL BE RESPONSIBLE FOR ENSURING ALL EXTERIOR WALL PENETRATIONS

ARE PROPERLY SEALED TO PREVENT ANY MOISTURE FROM ENTERING THE BUILDING.

5. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. IF EXTERIOR CONDUITS ARE REQUIRED FOR A COMPLETE INSTALLATION, EACH SYSTEM CONTRACTOR SHALL COORDINATE WITH

THE PROJECT'S CONSULTANT PRIOR TO ANY ROUGH-IN.

6. EACH SYSTEM INSTALLER SHALL PROVIDE AND INSTALL PROTECTIVE BUSHINGS ON ALL CONDUIT STUB OUTS AND SLEEVES TO PREVENT CABLE DAMAGE. BUSHINGS SHALL BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE

ACCEPTED.

7. ALL CABLE SHALL BE ROUTED DOWN CORRIDORS, PARALLEL AND PERPENDICULAR TO THE BUILDING'S WALLS AND STRUCTURE. CABLE TO EACH DEVICE SHALL BRANCH OUT OF A MAIN CORRIDOR TRUNK.

ROUTING CABLES THROUGH CLASSROOMS, OFFICES, STORAGE ROOMS, RESTROOMS OR ANY TYPE OF ROOM OTHER THAN A CORRIDOR WILL NOT BE ACCEPTED. ENTER ROOMS ABOVE THE ASSOCIATED

ROOM DOORWAY.

1. CONTRACTOR SHALL COORDINATE WITH DBR ENGINEERING PRIOR TO THE INSTALLATION OF RACKS AND RACK EQUIPMENT. NO RACKS SHALL BE PERMANENTLY INSTALLED WITHOUT WRITTEN APPROVAL OF

THE PROPOSED LOCATION.

2. THE SELECTED, INSTALLING CONTRACTOR MUST BE A CERTIFIED INTEGRATOR/INSTALLER AUTHORIZED

BY THE SPECIFIED SYSTEM MANUFACTURER TO INSTALL THE CABLE PLANT AND CONNECTIVITY

PRODUCTS. REFER TO SPECIFICATIONS FOR PRODUCT TYPE AND DESCRIPTION.

3. SYSTEM WIRING AND EQUIPMENT INSTALLATION SHALL BE IN ACCORDANCE WITH GOOD ENGINEERING

PRACTICES AS ESTABLISHED BY ANSI/EIA/TIA, BICSI, AND THE NEC.

4. ALL WIRING SHALL MEET ALL STATE AND LOCAL ELECTRICAL CODES.

5. ALL TELECOMMUNICATIONS SYSTEMS EQUIPMENT AND MOUNTING LOCATIONS SHALL BE IN COMPLIANCE

WITH ADA ACCESSIBILITY STANDARDS.

6. ALL INDUSTRY STANDARD CATEGORY 6 CABLING PRACTICES MUST BE FOLLOWED FOR ALL DATA

CABLING.

7. ALL DATA CABLES ARE TO BE INSTALLED WITH A MINIMUM OF 12 INCHES OF SEPARATION FROM AC POWER CABLES, INTERCOM, FIRE ALARM, SECURITY CABLES IN ANY PARALLEL OPEN WIRE RUN.

8. ALWAYS CROSS OTHER SYSTEM CABLES AT A 90-DEGREE ANGLE.

9. ALL CABLES AND TERMINATION COMPONENTS SHALL BE MACHINE LABELED AT BOTH ENDS. LABEL ALL CABLES PER TS DRAWINGS AND/OR SPECIFICATION. FINAL CABLE/OUTLET IDENTIFICATION LABELS SHALL

BE COORDINATED WITH THE OWNER AND DBR.

10. CONTRACTOR TO PROVIDE LIGHTNING PROTECTION ON ALL COMMUNICATION CABLE BETWEEN

BUILDINGS.

11. ALL EXPOSED CABLING ROUTED IN PLENUM SHALL BE PLENUM-RATED. ALL NON PLENUM-RATED CABLING

INSTALLED IN PLENUM SPACES SHALL BE INSTALLED IN CONDUIT.

12. NO TERMINATION OR SPLICES SHALL BE INSTALLED IN OR ABOVE CEILINGS UNLESS NOTED OTHERWISE.

13. CONTRACTOR SHALL MAINTAIN WALL RATING WITH PROPER FIRE BLOCKING.

14. ALL CABLE INSTALLED SHALL ROUTE TO THE CENTER OF THE ROOM IN WHICH IT SERVES AND THEN TO THE OUTLET LOCATION IT IS INTENDED FOR. EACH CABLE SHALL HAVE A 10' SERVICE LOOP AT THE

CENTER OF EACH ROOM AND A 3' SERVICE LOOP ABOVE EACH OUTLET LOCATION.

15. THE SYSTEM INSTALLER SHALL PROPERLY SUPPORT ALL INSTALLED SYSTEM CABLING FROM A PANDUIT J-MOD CABLE SUPPORT SYSTEMS AS DETAILED IN SPECIFICATIONS. NO CABLING SHALL BE ROUTED AND TIED DIRECTLY TO BUILDING STEEL, CEILING GRID SUPPORT, CONDUIT, PIPING OR DUCTWORK. PANDUIT J-MOD SUPPORT SYSTEM SHALL BE DIRECTLY CONNECTED TO BUILDING'S STEEL JOIST. IN LOCATIONS WHERE THE BOTTOM OF THE JOIST IS MORE THAN 5' ABOVE THE CEILING, THE SYSTEM INSTALLER SHALL PROVIDE AND INSTALL THREADED ROD AND ALL REQUIRED MATERIALS TO CONNECT THE THREADED ROD TO BUILDING STEEL AND THE CABLE SUPPORT SYSTEM TO THE THREADED ROD. CABLE PATHWAYS

SHALL NOT BE HIGHER THAN 5' ABOVE THE CEILING AT ANY LOCATION.

16. CONTRACTOR TO PROVIDE AND INSTALL ALL REQUIRED CABLING AND COMPONENTS TO FURNISH TWO

(2) ANALOG TELEPHONE CABLES TO THE FIRE ALARM SYSTEM. CONTRACTOR TO COORDINATE WITH THE SYSTEM INSTALLER FOR EXACT LOCATIONS AND TERMINATION INSTRUCTIONS PRIOR TO INSTALLATION.

17. CONTRACTOR TO PROVIDE AND INSTALL ONE (1) CATEGORY 6 CABLE TO THE BUILDING'S ACCESS CONTROL HEAD END PANEL. TERMINATION OF THIS CABLE SHALL BE COORDINATED WITH THE SYSTEM

INSTALLER.

18. PROVIDE AND INSTALL ONE (1) CATEGORY 6 CABLE TO EACH LIGHTING CONTROL HUB ON THE ENTIRE PROJECT. COORDINATE EXACT QUANTITY AND LOCATIONS WITH THE LIGHTING CONTROL SYSTEM

INSTALLER. CONTRACTOR TO ASSUME A MINIMUM OF FIVE (5) PER PROJECT.

19. PROVIDE AND INSTALL ONE (1) CATEGORY 6 DATA CIRCUIT TO THE LOCAL AIR UNIT CONTROLLER IN EACH

ER/TR.

1. THE SECURITY SYSTEM INSTALLERS SHALL BE RESPONSIBLE FOR CONNECTING ALL APPLICABLE SYSTEM

EQUIPMENT TO THE OWNER'S NETWORK.

2. THE SYSTEM INSTALLER SHALL PROPERLY SUPPORT ALL INSTALLED SYSTEM CABLING FROM AN APPROVED CABLE SUPPORT SYSTEM AS DETAILED IN SPECIFICATIONS. NO CABLING SHALL BE ROUTED AND TIED DIRECTLY TO BUILDING STEEL, CEILING GRID SUPPORT, CONDUIT, PIPING, OR DUCTWORK. THE CABLE SUPPORT SYSTEM SHALL BE DIRECTLY CONNECTED TO THE BUILDING'S STEEL JOIST. AT LOCATIONS WHERE THE BOTTOM OF THE JOIST IS MORE THAN 5' ABOVE THE CEILING, THE SYSTEM INSTALLER SHALL PROVIDE AND INSTALL THREADED ROD AND ALL REQUIRED MATERIALS TO CONNECT THE THREADED ROD TO THE BUILDING STEEL AND THE CABLE SUPPORT SYSTEM TO THE THREADED ROD. CABLE PATHWAY SHALL NOT BE HIGHER THAN 5' ABOVE THE CEILING AT ANY LOCATIONS.

3. PROVIDE AND INSTALL MAGNETIC DOOR CONTACT AT ALL ROOF HATCHES ON THE ENTIRE PROJECT.

CONTACTS SHALL BE CONNECTED TO THE BUILDING'S INTRUSION DETECTION SYSTEM.

1. EVERY SYMBOL SHOWN ON LEGEND MAY NOT APPEAR ON DRAWINGS. REFER TO GENERAL ELECTRICAL

NOTES FOR WALL MOUNTED DEVICE MOUNTING HEIGHTS.

2. REFERENCE SPECIFICATIONS FOR MATERIALS AND METHODS.

3. COMPLETE INSTALLATION OF ALL PRODUCTS SHALL BE IN COMPLIANCE WITH ALL CODES, INDUSTRY

STANDARDS, COMMON PRACTICES AND MANUFACTURER'S INSTRUCTIONS.

INTERCOM/PA LEGEND

DESCRIPTIONSYMBOLG

R O

U P

D E

V

IC

E

S VOLUME CONTROL - WALL MOUNTED. 42" AFF U.N.O.

INTERCOM/PA SYSTEM CALL-IN OR CALL BACK DEVICE. 42" AFF U.N.O.

VC

CB

S WALL AND CEILING MOUNTED INTERCOM/PA SPEAKER.S

NOTES:

1. REFERENCE VIDEO SURVEILLANCE SCHEDULE AND DIVISION 28 SPECIFICATIONS FOR ADDITIONAL

INFORMATION AND REQUIREMENTS

ACP

PIR

DR

DS

PB

MS

DO

CR

CR

DS

LA

DC

D E

V

IC

E S

ACCESS CONTROL LEGEND

DESCRIPTIONSYMBOLG

R O

U P

WALL OR MULLION MOUNTED ACCESS CONTROL PROXIMITY CARD READER.

DOOR RELEASE BUTTON

MOTION REQUEST TO EXIT DEVICE

DOOR MOUNTED, 2-WAY AUDIO/VIDEO INTERCOM DOOR STATION. PROVIDE ONE (1)

CAT 6 CABLE RUN (BY DIV 27) TO EACH LOCATION.

2-WAY AUDIO/VIDEO INTERCOM MASTER STATION. PROVIDE ONE (1) CAT 6 CABLE RUN

(BY DIV 27) TO EACH LOCATION.

WALL MOUNTED LOCAL ALARM SOUNDER.

ACCESS CONTROL PROXIMITY CARD READER THAT IS INTEGRATED INTO THE DOOR

HARDWARE.

DESIGNATES THE LOCATION OF THE ACCESS CONTROL SYSTEM CONTROL PANEL.

ELECTRICAL CONTRACTOR TO PROVIDE 120V POWER TO PANEL. PROVIDE NETWORK

CABLE TO PANEL AND COORDINATE WITH THE OWNER'S TECHNOLOGY DEPARTMENT

ON ACQUIRING AN IP ADDRESS. PROVIDE ONE (1) CAT 6 CABLE RUN (BY DIV 27) TO

EACH LOCATION.

WALL OR MULLION MOUNTED, 2-WAY AUDIO/VIDEO INTERCOM DOOR STATION.

PROVIDE ONE (1) CAT 6 CABLE RUN (BY DIV 27) TO EACH LOCATION.

ADA AUTO DOOR OPEN BUTTON, SHOWN FOR REFERENCE ONLY. BUTTON AND AUTO

DOOR OPERATOR PROVIDED AND INSTALLED BY THE DOOR SYSTEM INSTALLER.

AUTO DOOR OPERATOR. OPERATOR TO BE PROVIDED AND INSTALLED BY THE DOOR

SYSTEM INSTALLER.

DOUBLE PULL DOUBLE THROW MAGNETIC DOOR CONTACT/DOOR POSITION SENSOR.

FLUSH MOUNTED IN DOOR FRAME, UNLESS NOTED OTHERWISE

NOTES:

1. REFERENCE ACCESS CONTROL SCHEDULE, DETAILS, AND DIVISION 28 SPECIFICATIONS FOR

ADDITIONAL INFORMATION AND REQUIREMENTS

LD INDICATES LOCATION OF EMERGENCY LOCKDOWN BUTTON. MOUNT AT 44" AFF TO

CENTER OF DEVICE.

956.683.1640 p https://www.dbrinc.com

TBPE Firm Registration No. 2234

CHECKED BY:

SHEET TITLE:

SHEET NUMBER:

PROJECT NUMBER

DRAWN BY:

DATE:

REVISION:

SEAL:

TBPE Firm Registration No. 2234

S o u th th S tr e e t, S u it e

M c A lle n T e x a s

.6

.1 p

.6

.1 f

S E

R V

IC

E

Q

U A

L

IT

Y

I N

T E

G R

S

U S

T A

IN

A

B

IL

IT

Y

RT - - -

DBR Project # 258034

GC

E V

IN

S

S T

A T

E J

U V

E N

IL

E

C O

R R

E C

T

IO

N A

L

F

C

IL

IT

Y

C

O N

T R

O L

P A

N E

L

S A

L L

Y P

O R

T

P L A

C E

M E

N T

09/19/2025

258034.000

/3/

/4

/2

:1 :3

P

M

A u to d e s k D o c s /2

.0

E v in s S ta te

J u v e n ile C o rr e c ti o n a l F a c ili ty -H

V A

C R e p la c e m e n ts /2

E V

IN

S

S T

A T

E J

U V

E N

IL

E

M

E P

.r v t

T0.01

TECHNOLOGY SYMBOL

LEGEND

DBR

DBR

No. DATE DESCRIPTION

T2.11

T1.1

T1.1

T1.3

T1.3

A. THE CONTRACTOR SHALL REFERENCE ALL OTHER TRADES’

CONSTRUCTION DOCUMENTS FOR FULL EXTENT OF THE SITE WORK

TO BE PERFORMED, AND FIELD VERIFY THE EXISTING JOB-SITE

CONDITIONS BEFORE BIDDING. NO CHANGE ORDER IS ALLOWED FOR

INCREASED COST ASSOCIATED WITH CONDITIONS WHICH COULD

HAVE BEEN DETERMINED BY EXAMINING THE SITE AND WHOLE

PROJECT DOCUMENTS BEFORE SUBMISSION OF PROPOSALS AND/OR

BEFORE A CONTRACT IS AWARDED.

B. ALL CONDUIT AND CABLE RUNS SHOWN ARE DIAGRAMMATIC AND FOR

DESIGN INTENT ONLY. CONTRACTOR SHALL COORDINATE WITH

INCOMING SERVICE PROVIDERS AND OTHER TRADES (ELECTRICAL,

CIVIL, ETC.) FOR THE EXACT ROUTE AND SHARED TRENCHES, IF

APPLICABLE. CONTRACTOR SHALL MAKE ANY FIELD ADJUSTMENT TO

THE ROUTE AS NECESSARY, AT NO ADDITIONAL COST TO THE

PROJECT OR OWNER, TO AVOID COLLISION AND MEET THE PROJECT

REQUIREMENTS.

C. ONLY SWEEP BENDS ARE ALLOWED FOR ALL OSP COMMUNICATIONS

CONDUITS. ALL UNDERGROUND CONDUITS SHALL ENTER THE

COMMUNICATIONS MANHOLE/HANDHOLE FROM THE SIDE WALLS AND

BE PROPERLY SEALED TO PREVENT WATER INFILTRATION.

D. ALL UNDERGROUND COMMUNICATIONS CONDUITS SHALL BE BURIED

AT MINIMUM 3 FEET FROM FINISHED GRADE, AND SLOPE AWAY FROM

BUILDING, UNLESS OTHERWISE NOTED.

GENERAL SITE PLAN NOTES:

956.683.1640 p https://www.dbrinc.com

TBPE Firm Registration No. 2234

CHECKED BY:

SHEET TITLE:

SHEET NUMBER:

PROJECT NUMBER

DRAWN BY:

DATE:

REVISION:

SEAL:

TBPE Firm Registration No. 2234

S o u th th S tr e e t, S u it e

M c A lle n T e x a s

.6

.1 p

.6

.1 f

S E

R V

U A

L

N

T E

G R

U S

T A

IN

A

B

IL

IT

Y

RT - - -

DBR Project # 258034

GC

E V

IN

S

S T

A T

E J

U V

E N

IL

E

C O

R R

E C

T

IO

N

C

IL

IT

Y

C

O N

T R

O L

P A

N E

L

S A

L L

Y P

O

P L A

C E

M E

N T

09/19/2025

258034.000

/3/

/4

/2

:1 :3

P

M

A u to d e s k D o c s /2

.0

E v in s S ta te

J u v e n ile C o rr e c ti o n a l F a c ili ty -H

V A

C R e p la c e m e n ts /2

E V

IN

S

S T

A T

E J

U V

E N

IL

E

M

E P

.r v t

T0.21

TECHNOLOGY SITE

PLAN

DBR

DBR

▯ TECHNOLOGY KEYED NOTES

T1.1 APPROXIMATE LOCATION OF ACCESS CONTROLLED GATE. PROVIDE POLE

MOUNTED NEMA 4 ENCLOSURE (16"H X 16"W X 10"D) ADJACENT TO GATE

CONTROLLER AND (1) 2-IN CONDUIT FOR SECURITY AND COMMUNICATION

CABLING FROM THIS BOX TO IT ROOM INSIDE CONTROL ROOM BUILDING.

T1.3 APPROXIMATE LOCATION OF INTERCOM BOX IN PEDESTAL TO BE

REPLACED. CONTRACTOR SHALL FIELD VERIFY AND PROVIDE PATHWAY

AND CABLING AS NECESSARY.

TN PN

1" = 60'-0"

TECHNOLOGY SITE PLAN

DC

DC

DC

DC

DC

DC

DC

J

J

CONT RM

V100

LOBBY

V107

MECH

V104

ELECT

V102

TOILET

V101

TOILET

V103

STORAGE

V106

T5.12

T5.13

T5.13

T5.13

T5.13

T5.14 T5.14

T5.14

T .1

T5.15

T5.15

3/ T2.11

2/ T2.11

1. ALL TECHNOLOGY DEVICES, OUTLETS AND CABLE/CONDUIT

PATHWAYS SHOWN ARE DIAGRAMMATIC ONLY AND ARE NOT MEANT

TO SHOW THE EXACT LOCATION OR ROUTE. CONTRACTOR SHALL

VERIFY WITH ARCHITECT AND OWNER FOR EXACT ROUTE, MOUNTING

HEIGHT, AND LOCATION BEFORE INSTALLATION, AND SHALL

COORDINATE WITH OTHER TRADES TO MAKE ANY FIELD

ADJUSTMENTS AS NECESSARY TO AVOID COLLISIONS AND MEET THE

PROJECT REQUIREMENTS.

2. CONDUITS AND BACKBOXES, SIZED PER DIV 27/28 SPECIFICATIONS,

SHALL BE PROVIDED (BY DIV 26) FOR ALL TECHNOLOGY SYSTEM

DEVICES MOUNTED ON WALL, FLOOR, AND OPEN OR SOLID FINISH

CEILING. CONDUITS/SLEEVES SHALL BE PROVIDED FOR ALL CABLES

ROUTED IN WALLS, OR THROUGH FULL HEIGHT PARTITIONS, OR

THROUGH INACCESSIBLE CEILING PLENUM, OR THROUGH SPACES

WITH EXPOSED CEILING DECK.

3. UTP CABLES OF DIFFERENT RATING (CAT 6, CAT 6A, CLASS 4 POWER)

OR JACKETING (SHIELDED OR COLORED SHEATH) OR DIFFERENT

MEDIA TYPE CABLES (UTP, FIBER, COAX, ETC.) SHALL BE ROUTED IN

SEPARATE J-HOOKS, CONDUITS, SLEEVES, CORES, DUCTS, ETC.

THROUGHOUT THE ENTIRE PATHWAY. INSTRUMENTATION, SIGNAL,

AND TELECOMMUNICATIONS CABLING (INCLUDING CLASS 4

POWER), SHALL BE SEPARATED FROM POWER CABLING WITH A

SEPARATE CABLE TRAY OR BY A DIVIDER WITHIN A CABLE TRAY.

4. BUSHINGS SHALL BE INSTALLED AT EACH END OF THE CONDUITS

BEFORE CABLES BEING PULLED THROUGH. PROVIDE PULL STRING IN

EACH CONDUIT INSTALLED AND LEAVE ONE FOR FUTURE PULLING

AFTER CABLE INSTALLATION IS COMPLETE.

5. NO NETWORK DATA CABLE RUN SHALL EXCEED 295 FEET IN TOTAL

LENGTH INCLUDING UP/DOWN AND SERVICE LOOPS WITHOUT PRIOR

APPROVAL FROM THE ARCHITECT AND ENGINEER. CONTRACTOR

SHALL COORDINATE WITH OTHER TRADES FOR PROPER PATHWAY

PLANNING.

6. ALL CONDUITS FOR TECHNOLOGY DEVICES SHALL ROUTE FROM THE

DEVICE LOCATION AND TERMINATE ABOVE LAY IN CEILING IN THE

SAME ROOM (AN OPEN CEILING OR CLOUD TYPE CEILING IS NOT

CONSIDERED AN ACCESSIBLE CEILING) WHERE THE DEVICE IS

LOCATED. IF THE ROOM WHERE THE DEVICE IS LOCATED DOES NOT

HAVE A LAY IN CEILING TO PREVENT THE CABLES FROM BEING

EXPOSED, THE CONDUIT SHALL BE INSTALLED TO THE SHORTEST

ROUTE TO THE MAIN CORRIDOR OR THE NEAREST MDF/IDF TO

REDUCE THE CABLE LENGTH ENSURING THE CABLES DOES NOT

EXCEED THE 250 FEET. ALL CONDUITS AND FITTINGS SHALL BE

PAINTED TO MATCH STRUCTURE UNLESS NOTED OTHERWISE.

7. ALL REMOTELY CONTROLLED DOORS AND GATES SHALL HAVE THE

ABILITY TO BE MANUALLY OVERRIDDEN LOCALLY WITH A KEY.

CONTRACTOR SHALL MATCH EXISTING CYLINDERS AND COORDINATE

WITH OWNER ON REQUIRED MANUFACTURER AND MODEL.

GENERAL FLOOR PLAN NOTES:

T2.11

SALLY PORT GATES

OPEN

STOP

CLOSE

INTERCOM ACTIVATIONCONTROL BUILDING

DOOR RELEASE INTERCOM ACTIVATION

WEST DOOR

LOBBY DOORS

WEST DOOR

DOOR RELEASE

INTERCOM MASTER

PUSH TO TALK

MASTER VOLUME SPEAKER

CONTROL ROOM DOORS

SOUTH DOOR

OPEN

STOP

CLOSE

INTERCOM ACTIVATION

NORTH GATE

SOUTH GATE

INTERCOM ACTIVATION

WALK TROUGH GATE

EAST DOOR

*** LEGEND ***

OPEN

STOP

CLOSE

SYMBOL DESCRIPTION

SALLY PORT SLIDING GATE KNOB. PROVIDE KNOB

AND PROGRAM TO OPEN/CLOSE GATES. SHALL BE

NORMALLY OPEN SWITCH IN THE STOP POSITION

AND CLOSE A CIRCUIT TO EITHER SIDE TO PROVIDE

SIGNAL TO OPEN OR CLOSE GATE. KNOB SHALL

SNAP BACK INTO STOP POSITION UPON RELEASE.

MOMENTARY RELEASE BUTTON. PROVIDE BUTTON

AND PROGRAM TO RELEASE DOOR/GATE

COORDINATE WITH OWNER ON ANY DELAY

REQUIREMENT. SHALL BE NORMALLY OPEN SWITCH

AND CLOSE CIRCUIT WHEN PRESSED.

INTERCOM MASTER VOLUME KNOB. PROVIDE KNOB

AND PROGRAM POTENTIOMETER TO ADJUST

SPEAKER VOLUME.

STATUS LED LIGHT. PROVIDE LIGHT AND PROGRAM

AS FOLLOWS PER APPLICATION:

• FOR BUILDING DOORS, MAN AND SLIDING GATES:

1. RED LIGHT SHALL INDICATE AN OPEN

GATE/DOOR (NOT SECURED) GREEN LIGHT

SHALL INDICATE CLOSED GATE/DOOR

(SECURED)

• FOR INTERCOM, YELLOW LIGHT SHALL INDICATE

ACTIVE INTERCOM LOCATION.

MOMENTARY RELEASE BUTTON. PROVIDE BUTTON

AND PROGRAM TO ACTIVATE INTERCOM

ASSOCIATED TO DOOR AND DEACTIVATE WHEN

PRESSED AGAIN OR ANY OTHER INTERCOM BUTTON

IS PRESSED. SHALL BE NORMALLY OPEN SWITCH

AND CLOSE CIRCUIT WHEN PRESSED.

IC

IC

IC

IC

IC

IC

IC

IC

RED

LED

GREEN

LED

YELLOW

LED

LAMP TEST

PRESS AND HOLD FOR TESTING OF LED LIGHT.

956.683.1640 p https://www.dbrinc.com

TBPE Firm Registration No. 2234

CHECKED BY:

SHEET TITLE:

SHEET NUMBER:

PROJECT NUMBER

DRAWN BY:

DATE:

REVISION:

SEAL:

TBPE Firm Registration No. 2234

S o u th th S tr e e t, S u it e

M c A lle n T e x a s

.6

.1 p

.6

.1 f

S E

R V

U A

L

N

T E

G R

U S

T A

IN

A

B

IL

IT

Y

RT - - -

DBR Project # 258034

GC

E V

IN

S

S T

A T

E J

U V

E N

IL

E

C O

R R

E C

T

IO

N

C

IL

IT

Y

C

O N

T R

O L

P A

N E

L

S A

L L

Y P

O

P L A

C E

M E

N T

09/19/2025

258034.000

/3/

/4

/2

:1 :3

P

M

A u to d e s k D o c s /2

.0

E v in s S ta te

J u v e n ile C o rr e c ti o n a l F a c ili ty -H

V A

C R e p la c e m e n ts /2

E V

IN

S

S T

A T

E J

U V

E N

IL

E

M

E P

.r v t

T2.11

TECHNOLOGY PLAN

LEVEL 1

DBR

DBR

▯ TECHNOLOGY KEYED NOTES

T5.12 APPROXIMATE LOCATION OF EXISTING TO BE REPLACED CONTROL PANEL

FOR REMOTE OPERATION OF SECURED DOORS.

T5.13 LOCATION OF REMOTELY CONTROLLED SECURED DOOR TO BE

RENOVATED.

T5.14 LOCATION OF REMOTELY CONTROLLED SECURED GATE TO BE

RENOVATED.

T5.15 APPROXIMATE LOCATION OF GATE CONTROLLER TO BE REPLACED.

CONTRACTOR SHALL FIELD VERIFY AND PROVIDE NEW MOTORS,

HARDWARE, CONTROL CABINET AND WIRING FOR A COMPLETE

FUNCTIONING SYSTEM.

TN PN

1/8" = 1'-0"

TECHNOLOGY PLAN - GATE

NOT TO SCALE

EXISTING CONTROL PANEL IN EXISTING CONSOLE

NOT TO SCALE

EXISTING CONTROL PANEL LAYOUT

12" = 1'-0"

PROPOSED CONSOLE LAYOUT

1/8" = 1'-0"

EXISTING CONTROL ENCLOSURE NORTH GATE

1/8" = 1'-0"

EXISTING CONTROL ENCLOSURE SOUTH GATE

Sheets
T0.01 - TECHNOLOGY SYMBOL LEGEND
T0.21 - TECHNOLOGY SITE PLAN
T2.11 - TECHNOLOGY PLAN LEVEL 1
T6.01 - TECHNOLOGY DETAILS

File details come from the government source that posted it. Updated .