Sally Port Control Panel Replacement - Technology Drawings and Specifications
This document is a comprehensive technical specification and drawings package for the Evins State Juvenile Correctional Facility Sally Port Replacement project located in Texas. The project involves the replacement of a control panel system for remote operation of secured doors and gates within the facility's sally port area. The scope of work includes installation of access control systems, security cameras, intercom/PA systems, structured cabling infrastructure, and associated technology equipment across multiple facility areas including the lobby, control room, mechanical rooms, electrical rooms, storage, and toilet facilities. The drawings package consists of a responsibility matrix clearly delineating work scope between Division 27 (Communications Technology) and Division 28 (Security Systems), detailed floor plans showing device locations, site plans, equipment schedules, and control panel layouts. The project specifications require coordination with the facility architect and owner prior to rough-in work, field verification of exact device locations and mounting heights, and adherence to all applicable codes and industry standards including NEC, ANSI/EIA/TIA, and BICSI guidelines.
The installation requirements mandate that all 120-volt power for system functionality be dedicated circuits on emergency power when available, with the electrical contractor responsible for all power connections to main control panels and head-end equipment. Conduit sizing must maintain a 40 percent maximum fill ratio, and all exposed system wiring must be routed in conduit or installed in plenum-rated materials. The contractor must employ certified integrators and installers authorized by specified system manufacturers and provide cable support using Panduit J-MOD systems directly connected to building steel joists. All network data cable runs are limited to a maximum of 295 feet total length without prior architect approval, and cables must maintain minimum 12-inch separation from AC power and other signal cables except at 90-degree crossings. The project requires magnetic door contacts at all roof hatches, proper lightning protection on all communication cables between buildings, and fire blocking to maintain wall ratings, with all installations subject to ADA accessibility compliance standards.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RESPONSIBILITY MATRIX
SCOPE OF WORK RESPONSIBILITY
OFOI
DIV 27 - COMMUNICATIONS
TECHNOLOGY SCOPE
DIV 28 - SECURITY SYSTEMS
ACCESS CONTROL SYSTEM
STRUCTURED CABLING
CABLE TRAY IN ER/TR
CABLE PATHWAY OUTSIDE ER/TR
TELECOM GROUNDING SYSTEM
BACK BOXES, CONDUITS/SLEEVES
EQUIPMENT RACKS/CABINETS
WIRELESS ACCESS POINTS
NETWORK SWITCHES
UPS
TELEPHONES
WORKSTATION PC
CARD READERS
DOOR CONTACTS
ELECTRIFIED LOCKS
REX INSIDE DOOR
PUSH TO EXIT
PIR SENSORS
LOW VOLTAGE POWER SUPPLY
ACCESS CONTROL PANELS
EQUIPMENT RACKS/CABINETS
BACK BOXES, CONDUITS/SLEEVES
COMPOSITE CABLING
NETWORK CABLING REQUIRED
CREDENTIAL CARDS
BADGE PRINTERS
OFCI CFCI
PDU
BACKBONE CABLING
X
X
X
X
X
OFOI OFCI CFCI
X
X
X
DESCRIPTIONTEXT
INDICATES THAT THE DESIGNATED DEVICE IS TO BE WALL MOUNTED AT SPECIFIED HEIGHT OR
IN COMPLIANCE WITH CODE REQUIREMENTS. ALL WALL MOUNTED HEIGHTS ARE TO BE
CONFIRMED WITH THE PROJECT'S ARCHITECT PRIOR TO ROUGH-IN.
INDICATES THAT THE DESIGNATED DEVICE SHALL BE WEATHER PROOF AND RATED FOR
EXTERIOR CONDITIONS INSTALLATION.
INDICATES THAT THE DESIGNATED DEVICE IS TO BE INSTALLED ABOVE THE COUNTERTOP. A
NUMERIC VALUE SHALL REPLACE THE '#' SYMBOL AND SHALL DESIGNATE THE SPECIFIC HEIGHT
ABOVE COUNTER. ALL HEIGHTS ARE TO BE CONFIRMED WITH THE PROJECT'S ARCHITECT
PRIOR TO ROUGH-IN.
INDICATES THAT THE DESIGNATED DEVICE IS TO BE INSTALLED ABOVE THE FINISHED FLOOR. A NUMERIC VALUE SHALL REPLACE THE '#' SYMBOL AND SHALL DESIGNATE THE SPECIFIC HEIGHT ABOVE FINISHED FLOOR. ALL HEIGHTS ARE TO BE CONFIRMED WITH THE PROJECT'S ARCHITECT
PRIOR TO ROUGH-IN.
INDICATES THAT THE DESIGNATED DEVICE IS TO BE INSTALLED ABOVE THE GRADE LEVEL. A
NUMERIC VALUE SHALL REPLACE THE '#' SYMBOL AND SHALL DESIGNATE THE SPECIFIC HEIGHT
ABOVE GRADE. ALL HEIGHTS ARE TO BE CONFIRMED WITH THE PROJECT'S ARCHITECT PRIOR
TO ROUGH-IN.
INDICATES THAT THE DESIGNATED DEVICE IS TO BE SURFACE MOUNTED. CONTRACTOR TO
PROVIDE ALL MATERIALS REQUIRED FOR A COMPLETE, SURFACE MOUNTED SOLUTION. ALL
SURFACE MOUNTED PRODUCTS SHALL BE APPROVED BY THE PROJECT'S ARCHITECT PRIOR TO
PROCUREMENT AND/OR INSTALLATION.
INDICATES THAT THE DESIGNATED DEVICE IS TO BE MOUNTED ON THE UNDERSIDE OF THE
ELEVATED CANOPY.
INDICATES THAT THE DESIGNATED DEVICE IS TO BE INSTALLED UNDER A RAISED FLOOR
SYSTEM.
INDICATES THAT THE DESIGNATED DEVICE IS TO BE CORNER MOUNTED AT SPECIFIED HEIGHT.
ALL WALL MOUNTED HEIGHTS ARE TO BE CONFIRMED WITH THE PROJECT'S ARCHITECT PRIOR
TO ROUGH-IN.
TYPICAL SUBSCRIPTS LEGEND
'WM'
'WP'
'AC'
'AFF'
'AG'
'SM'
'UC'
'UF'
'CM'
GENERAL NOTES
SECURITY GENERAL NOTES
TECHNOLOGY GENERAL NOTES
D E
V
IC
E S
TECHNOLOGY LEGEND
DESCRIPTIONSYMBOLG
R O
U P
'D#'
INDICATES THE LOCATION OF A NEW TECHNOLOGY OUTLET. CONTRACTOR TO
PROVIDE FACEPLATE WITH A MINIMUM OF 4-PORTS AT EACH LOCATION UNLESS
OTHERWISE NOTED. ELECTRICAL CONTRACTOR TO PROVIDE A DOUBLE GANG
BACK BOX WITH A SINGLE GANG REDUCER RING AND A 1" EMT CONDUIT FROM THE
BOX TO THE NEAREST ACCESSIBLE CEILING. SOME EXISTING BUILDINGS MAY
REQUIRE SURFACE MOUNTED RACEWAY. ELECTRICAL CONTRACTOR TO PROVIDE
AND INSTALL RACEWAY AS SPECIFIED AND DESIGNATE IN THE ELECTRICAL
CONTRACT DOCUMENTS. SYSTEM INSTALLER TO PROVIDE AND INSTALL A PLASTIC
PROTECTIVE BUSHING, ON EACH CONDUIT STUB-OUT, TO PREVENT CABLE
DAMAGE.
INDICATES THE LOCATION OF A FLOOR MOUNTED TECHNOLOGY OUTLET.
ELECTRICAL CONTRACTOR TO PROVIDE AND INSTALL A FLOOR BOX WITH (1) 1"
CONDUIT PER EVERY (6) CABLES INSTALLED. ALL CONDUITS SHALL ROUT FROM
THE FLOOR BOX, DIRECTLY TO THE WALL INDICATED AND STUB-UP INTO THE
NEAREST ACCESSIBLE PLENUM CEILING.
INDICATES THE LOCATION OF A CEILING MOUNTED OUTLET. CONTRACTOR SHALL
MOUNT THIS OUTLET AT +12" ABOVE THE CEILING AND COORDINATE ALL FINAL
LOCATIONS WITH OTHER TRADES ON THE PROJECT TO VERIFY THAT THE
LOCATION OF THE OUTLET MAINTAINS 12" OF CLEARANCE FROM THE FRONT OF
THE FACEPLATE FOR OWNER ACCESS. ELECTRICAL CONTRACTOR SHALL ROUTE
(1) 1" CONDUIT FROM THE BUILDING STRUCTURE TO A SINGLE GANG BACK BOX
MOUNTED AT 5' OR LESS ABOVE THE FINISHED CEILING. SECURE CONDUIT AND
BACK BOX TO INSURE MINIMAL SWAY MOVEMENT.
DESIGNATES THAT THE ASSOCIATED TECHNOLOGY OUTLET IS INTENDED FOR THE
USE OF A NETWORK CONNECTION. THE '#' SHALL BE REPLACED WITH NUMERIC
TEXT THAT IDENTIFIES THE TOTAL NUMBER OF CATEGORY 6, NETWORK CABLES
THAT ARE TO BE INSTALLED AT THE TECHNOLOGY OUTLET LOCATION.
CONTRACTOR TO PROVIDE AND INSTALL CATEGORY 6 NETWORK CABLES,
CATEGORY 6 CONNECTORS, STAINLESS STEEL FACEPLATES WITH IDENTIFICATION
WINDOWS, LABELS, BLANK INSERTS, AND ANY OTHER MATERIALS REQUIRED TO
FURNISH A COMPLETE FUNCTIONAL AND TESTED OUTLET LOCATION. ALL
FACEPLATES PROVIDED SHALL CONTAIN A MINIMUM 4-PORTS AND SHALL BE
APPROPRIATELY SIZED TO ACCOMMODATE THE NUMBER OF CIRCUITS BEING
INSTALLED AT THIS TECHNOLOGY OUTLET LOCATION. MAXIMUM OF SIX(6) DATA
CABLES PER OUTLET.
DESIGNATES THAT THE ASSOCIATED TECHNOLOGY OUTLET IS INTENDED FOR THE
USE OF A WALL MOUNTED TELEPHONE CONNECTION. CONTRACTOR TO PROVIDE
AND INSTALL (1) CATEGORY 6 NETWORK CABLE, (1) CATEGORY 6 CONNECTOR,
STAINLESS STEEL WALL TELEPHONE FACEPLATE, LABELS, AND ANY OTHER
MATERIALS REQUIRED TO FURNISH A COMPLETE FUNCTIONAL AND TESTED
CIRCUIT AT EACH LOCATION SHOWN. CONTRACTOR SHALL MOUNT THIS OUTLET
AT +42" AFF AND COORDINATE ALL FINAL LOCATIONS WITH OTHER TRADES ON THE
PROJECT TO VERIFY THAT THE LOCATION OF THE OUTLET MAINTAINS 8" OF
CLEARANCE ON ALL FOUR SIDES OF THE BACK BOX. OUTLETS SHALL REMAIN
CLEAR OF ROOM DOORS, CABINET DOORS, APPLIANCE DOORS, AND SLIDING
DRAWERS.
DESIGNATES THAT THE ASSOCIATED TECHNOLOGY OUTLET IS INTENDED FOR THE
USE OF A WIRELESS ACCESS POINT CONNECTION. CONTRACTOR TO PROVIDE AND
INSTALL (1) CATEGORY 6 NETWORK CABLE, (1) CATEGORY 6 CONNECTOR,
STAINLESS STEEL FACEPLATE WITH IDENTIFICATION WINDOWS, LABELS, AND ANY
OTHER MATERIALS REQUIRED TO FURNISH A COMPLETE FUNCTIONAL AND
TESTED CIRCUIT AT EACH LOCATION SHOWN. REFERENCE SPECIFICATIONS FOR
PATCH CABLE REQUIREMENTS.
INDICATES THE LOCATION OF AN IP VIDEO SURVEILLANCE CAMERA. CONTRACTOR
TO PROVIDE AND INSTALL CATEGORY 6 NETWORK CABLES, CATEGORY 6
CONNECTORS, STAINLESS STEEL FACEPLATES WITH IDENTIFICATION WINDOWS,
LABELS, BLANK INSERTS, AND ANY OTHER MATERIALS REQUIRED TO FURNISH A
COMPLETE FUNCTIONAL AND TESTED OUTLET LOCATION. ALL FACEPLATES
PROVIDED SHALL BE APPROPRIATELY SIZED TO ACCOMMODATE THE NUMBER OF
CIRCUITS BEING INSTALLED AT THIS OUTLET LOCATION. REFERENCE
SPECIFICATIONS FOR PATCH CABLE REQUIREMENTS.
INDICATES THAT THE ASSOCIATED TECHNOLOGY OUTLET IS INTENDED FOR
FUTURE USE. CONTRACTOR TO PROVIDE STAINLESS STEEL, SINGLE-GANG WALL
PLATE AT ALL LOCATIONS.
'W'
'AP'
'B'
NOTES:
1. REFERENCE TECHNOLOGY GENERAL NOTES, PLAN KEYED NOTES, AND ALL OTHER SYSTEM
LEGENDS/NOTES. THE STRUCTURED CABLING SYSTEM CONTRACTOR SHALL PROVIDE AND
INSTALL CATEGORY 6 CABLE TO ALL SYSTEMS' EQUIPMENT REQUIRING NETWORK CONNECTIVITY.
NOTES TO CONTRACTOR
DESCRIPTIONTEXT
INDICATES THAT THE DEVICE IS EXISTING TO REMAIN. CONTRACTOR TO REMOVE DEVICE
AND PLACE IN THE SAME LOCATION AS NEEDED.
INDICATES THAT THE DEVICE IS EXISTING AN IS TO BE REMOVED. CONTRACTOR TO
REMOVE THE DEVICE AND RETURN TO OWNER.
INDICATES THAT THE DEVICE IS EXISTING AND SHALL BE REPLACED. REFERENCE NEW
SYSTEM LAYOUT FOR EXACT LOCATIONS.
INDICATES THAT THE DEVICE IS EXISTING AND SHALL BE REMOVED AND RELOCATED TO A
LOCATION INDICATED ON THE DRAWINGS. REFERENCE NEW SYSTEM LAYOUT FOR EXACT
LOCATIONS.
SUBSCRIPTS LEGEND - EXISTING DEVICES
'E'
'D'
'R'
'RR'
1. ALL 120V POWER REQUIRED FOR THE FUNCTIONALITY OF EACH SYSTEM SHALL BE A DEDICATED CIRCUIT AND ON EMERGENCY POWER WHEN AVAILABLE. PROJECTS ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER TO MAIN CONTROL PANELS, REMOTE POWER SUPPLIES AND ALL HEAD END EQUIPMENT. SYSTEM INSTALLERS SHALL COORDINATE LOCATIONS AND CONNECTIONS WITH
THE PROJECT'S ELECTRICAL CONTRACTOR.
2. THE PROJECT'S ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONDUITS, BACK BOXES, JUNCTION BOXES, RACEWAYS AND SLEEVES REQUIRED TO ESTABLISH CLEAR PATHWAYS FOR ALL SYSTEMS. ALL CONDUITS, SLEEVES, BOXES, AND RACEWAYS SHALL BE PROPERLY SIZED TO MAINTAIN
A 40% MAXIMUM FILL RATIO.
3. ALL EXPOSED SYSTEM'S WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILING SHALL BE ROUTED IN CONDUIT, PROVIDED AND INSTALLED BY THE PROJECT'S ELECTRICAL CONTRACTOR. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE FILL RATIO. MINIMUM CONDUIT SIZE
SHALL BE 3/4".
4. EACH SYSTEM INSTALLER SHALL BE RESPONSIBLE FOR ENSURING ALL EXTERIOR WALL PENETRATIONS
ARE PROPERLY SEALED TO PREVENT ANY MOISTURE FROM ENTERING THE BUILDING.
5. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. IF EXTERIOR CONDUITS ARE REQUIRED FOR A COMPLETE INSTALLATION, EACH SYSTEM CONTRACTOR SHALL COORDINATE WITH
THE PROJECT'S CONSULTANT PRIOR TO ANY ROUGH-IN.
6. EACH SYSTEM INSTALLER SHALL PROVIDE AND INSTALL PROTECTIVE BUSHINGS ON ALL CONDUIT STUB OUTS AND SLEEVES TO PREVENT CABLE DAMAGE. BUSHINGS SHALL BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE
ACCEPTED.
7. ALL CABLE SHALL BE ROUTED DOWN CORRIDORS, PARALLEL AND PERPENDICULAR TO THE BUILDING'S WALLS AND STRUCTURE. CABLE TO EACH DEVICE SHALL BRANCH OUT OF A MAIN CORRIDOR TRUNK.
ROUTING CABLES THROUGH CLASSROOMS, OFFICES, STORAGE ROOMS, RESTROOMS OR ANY TYPE OF ROOM OTHER THAN A CORRIDOR WILL NOT BE ACCEPTED. ENTER ROOMS ABOVE THE ASSOCIATED
ROOM DOORWAY.
1. CONTRACTOR SHALL COORDINATE WITH DBR ENGINEERING PRIOR TO THE INSTALLATION OF RACKS AND RACK EQUIPMENT. NO RACKS SHALL BE PERMANENTLY INSTALLED WITHOUT WRITTEN APPROVAL OF
THE PROPOSED LOCATION.
2. THE SELECTED, INSTALLING CONTRACTOR MUST BE A CERTIFIED INTEGRATOR/INSTALLER AUTHORIZED
BY THE SPECIFIED SYSTEM MANUFACTURER TO INSTALL THE CABLE PLANT AND CONNECTIVITY
PRODUCTS. REFER TO SPECIFICATIONS FOR PRODUCT TYPE AND DESCRIPTION.
3. SYSTEM WIRING AND EQUIPMENT INSTALLATION SHALL BE IN ACCORDANCE WITH GOOD ENGINEERING
PRACTICES AS ESTABLISHED BY ANSI/EIA/TIA, BICSI, AND THE NEC.
4. ALL WIRING SHALL MEET ALL STATE AND LOCAL ELECTRICAL CODES.
5. ALL TELECOMMUNICATIONS SYSTEMS EQUIPMENT AND MOUNTING LOCATIONS SHALL BE IN COMPLIANCE
WITH ADA ACCESSIBILITY STANDARDS.
6. ALL INDUSTRY STANDARD CATEGORY 6 CABLING PRACTICES MUST BE FOLLOWED FOR ALL DATA
CABLING.
7. ALL DATA CABLES ARE TO BE INSTALLED WITH A MINIMUM OF 12 INCHES OF SEPARATION FROM AC POWER CABLES, INTERCOM, FIRE ALARM, SECURITY CABLES IN ANY PARALLEL OPEN WIRE RUN.
8. ALWAYS CROSS OTHER SYSTEM CABLES AT A 90-DEGREE ANGLE.
9. ALL CABLES AND TERMINATION COMPONENTS SHALL BE MACHINE LABELED AT BOTH ENDS. LABEL ALL CABLES PER TS DRAWINGS AND/OR SPECIFICATION. FINAL CABLE/OUTLET IDENTIFICATION LABELS SHALL
BE COORDINATED WITH THE OWNER AND DBR.
10. CONTRACTOR TO PROVIDE LIGHTNING PROTECTION ON ALL COMMUNICATION CABLE BETWEEN
BUILDINGS.
11. ALL EXPOSED CABLING ROUTED IN PLENUM SHALL BE PLENUM-RATED. ALL NON PLENUM-RATED CABLING
INSTALLED IN PLENUM SPACES SHALL BE INSTALLED IN CONDUIT.
12. NO TERMINATION OR SPLICES SHALL BE INSTALLED IN OR ABOVE CEILINGS UNLESS NOTED OTHERWISE.
13. CONTRACTOR SHALL MAINTAIN WALL RATING WITH PROPER FIRE BLOCKING.
14. ALL CABLE INSTALLED SHALL ROUTE TO THE CENTER OF THE ROOM IN WHICH IT SERVES AND THEN TO THE OUTLET LOCATION IT IS INTENDED FOR. EACH CABLE SHALL HAVE A 10' SERVICE LOOP AT THE
CENTER OF EACH ROOM AND A 3' SERVICE LOOP ABOVE EACH OUTLET LOCATION.
15. THE SYSTEM INSTALLER SHALL PROPERLY SUPPORT ALL INSTALLED SYSTEM CABLING FROM A PANDUIT J-MOD CABLE SUPPORT SYSTEMS AS DETAILED IN SPECIFICATIONS. NO CABLING SHALL BE ROUTED AND TIED DIRECTLY TO BUILDING STEEL, CEILING GRID SUPPORT, CONDUIT, PIPING OR DUCTWORK. PANDUIT J-MOD SUPPORT SYSTEM SHALL BE DIRECTLY CONNECTED TO BUILDING'S STEEL JOIST. IN LOCATIONS WHERE THE BOTTOM OF THE JOIST IS MORE THAN 5' ABOVE THE CEILING, THE SYSTEM INSTALLER SHALL PROVIDE AND INSTALL THREADED ROD AND ALL REQUIRED MATERIALS TO CONNECT THE THREADED ROD TO BUILDING STEEL AND THE CABLE SUPPORT SYSTEM TO THE THREADED ROD. CABLE PATHWAYS
SHALL NOT BE HIGHER THAN 5' ABOVE THE CEILING AT ANY LOCATION.
16. CONTRACTOR TO PROVIDE AND INSTALL ALL REQUIRED CABLING AND COMPONENTS TO FURNISH TWO
(2) ANALOG TELEPHONE CABLES TO THE FIRE ALARM SYSTEM. CONTRACTOR TO COORDINATE WITH THE SYSTEM INSTALLER FOR EXACT LOCATIONS AND TERMINATION INSTRUCTIONS PRIOR TO INSTALLATION.
17. CONTRACTOR TO PROVIDE AND INSTALL ONE (1) CATEGORY 6 CABLE TO THE BUILDING'S ACCESS CONTROL HEAD END PANEL. TERMINATION OF THIS CABLE SHALL BE COORDINATED WITH THE SYSTEM
INSTALLER.
18. PROVIDE AND INSTALL ONE (1) CATEGORY 6 CABLE TO EACH LIGHTING CONTROL HUB ON THE ENTIRE PROJECT. COORDINATE EXACT QUANTITY AND LOCATIONS WITH THE LIGHTING CONTROL SYSTEM
INSTALLER. CONTRACTOR TO ASSUME A MINIMUM OF FIVE (5) PER PROJECT.
19. PROVIDE AND INSTALL ONE (1) CATEGORY 6 DATA CIRCUIT TO THE LOCAL AIR UNIT CONTROLLER IN EACH
ER/TR.
1. THE SECURITY SYSTEM INSTALLERS SHALL BE RESPONSIBLE FOR CONNECTING ALL APPLICABLE SYSTEM
EQUIPMENT TO THE OWNER'S NETWORK.
2. THE SYSTEM INSTALLER SHALL PROPERLY SUPPORT ALL INSTALLED SYSTEM CABLING FROM AN APPROVED CABLE SUPPORT SYSTEM AS DETAILED IN SPECIFICATIONS. NO CABLING SHALL BE ROUTED AND TIED DIRECTLY TO BUILDING STEEL, CEILING GRID SUPPORT, CONDUIT, PIPING, OR DUCTWORK. THE CABLE SUPPORT SYSTEM SHALL BE DIRECTLY CONNECTED TO THE BUILDING'S STEEL JOIST. AT LOCATIONS WHERE THE BOTTOM OF THE JOIST IS MORE THAN 5' ABOVE THE CEILING, THE SYSTEM INSTALLER SHALL PROVIDE AND INSTALL THREADED ROD AND ALL REQUIRED MATERIALS TO CONNECT THE THREADED ROD TO THE BUILDING STEEL AND THE CABLE SUPPORT SYSTEM TO THE THREADED ROD. CABLE PATHWAY SHALL NOT BE HIGHER THAN 5' ABOVE THE CEILING AT ANY LOCATIONS.
3. PROVIDE AND INSTALL MAGNETIC DOOR CONTACT AT ALL ROOF HATCHES ON THE ENTIRE PROJECT.
CONTACTS SHALL BE CONNECTED TO THE BUILDING'S INTRUSION DETECTION SYSTEM.
1. EVERY SYMBOL SHOWN ON LEGEND MAY NOT APPEAR ON DRAWINGS. REFER TO GENERAL ELECTRICAL
NOTES FOR WALL MOUNTED DEVICE MOUNTING HEIGHTS.
2. REFERENCE SPECIFICATIONS FOR MATERIALS AND METHODS.
3. COMPLETE INSTALLATION OF ALL PRODUCTS SHALL BE IN COMPLIANCE WITH ALL CODES, INDUSTRY
STANDARDS, COMMON PRACTICES AND MANUFACTURER'S INSTRUCTIONS.
INTERCOM/PA LEGEND
DESCRIPTIONSYMBOLG
R O
U P
D E
V
IC
E
S VOLUME CONTROL - WALL MOUNTED. 42" AFF U.N.O.
INTERCOM/PA SYSTEM CALL-IN OR CALL BACK DEVICE. 42" AFF U.N.O.
VC
CB
S WALL AND CEILING MOUNTED INTERCOM/PA SPEAKER.S
NOTES:
1. REFERENCE VIDEO SURVEILLANCE SCHEDULE AND DIVISION 28 SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS
ACP
PIR
DR
DS
PB
MS
DO
CR
CR
DS
LA
DC
D E
V
IC
E S
ACCESS CONTROL LEGEND
DESCRIPTIONSYMBOLG
R O
U P
WALL OR MULLION MOUNTED ACCESS CONTROL PROXIMITY CARD READER.
DOOR RELEASE BUTTON
MOTION REQUEST TO EXIT DEVICE
DOOR MOUNTED, 2-WAY AUDIO/VIDEO INTERCOM DOOR STATION. PROVIDE ONE (1)
CAT 6 CABLE RUN (BY DIV 27) TO EACH LOCATION.
2-WAY AUDIO/VIDEO INTERCOM MASTER STATION. PROVIDE ONE (1) CAT 6 CABLE RUN
(BY DIV 27) TO EACH LOCATION.
WALL MOUNTED LOCAL ALARM SOUNDER.
ACCESS CONTROL PROXIMITY CARD READER THAT IS INTEGRATED INTO THE DOOR
HARDWARE.
DESIGNATES THE LOCATION OF THE ACCESS CONTROL SYSTEM CONTROL PANEL.
ELECTRICAL CONTRACTOR TO PROVIDE 120V POWER TO PANEL. PROVIDE NETWORK
CABLE TO PANEL AND COORDINATE WITH THE OWNER'S TECHNOLOGY DEPARTMENT
ON ACQUIRING AN IP ADDRESS. PROVIDE ONE (1) CAT 6 CABLE RUN (BY DIV 27) TO
EACH LOCATION.
WALL OR MULLION MOUNTED, 2-WAY AUDIO/VIDEO INTERCOM DOOR STATION.
PROVIDE ONE (1) CAT 6 CABLE RUN (BY DIV 27) TO EACH LOCATION.
ADA AUTO DOOR OPEN BUTTON, SHOWN FOR REFERENCE ONLY. BUTTON AND AUTO
DOOR OPERATOR PROVIDED AND INSTALLED BY THE DOOR SYSTEM INSTALLER.
AUTO DOOR OPERATOR. OPERATOR TO BE PROVIDED AND INSTALLED BY THE DOOR
SYSTEM INSTALLER.
DOUBLE PULL DOUBLE THROW MAGNETIC DOOR CONTACT/DOOR POSITION SENSOR.
FLUSH MOUNTED IN DOOR FRAME, UNLESS NOTED OTHERWISE
NOTES:
1. REFERENCE ACCESS CONTROL SCHEDULE, DETAILS, AND DIVISION 28 SPECIFICATIONS FOR
ADDITIONAL INFORMATION AND REQUIREMENTS
LD INDICATES LOCATION OF EMERGENCY LOCKDOWN BUTTON. MOUNT AT 44" AFF TO
CENTER OF DEVICE.
956.683.1640 p https://www.dbrinc.com
TBPE Firm Registration No. 2234
CHECKED BY:
SHEET TITLE:
SHEET NUMBER:
PROJECT NUMBER
DRAWN BY:
DATE:
REVISION:
SEAL:
TBPE Firm Registration No. 2234
S o u th th S tr e e t, S u it e
M c A lle n T e x a s
.6
.1 p
.6
.1 f
S E
R V
IC
E
Q
U A
L
IT
Y
I N
T E
G R
S
U S
T A
IN
A
B
IL
IT
Y
RT - - -
DBR Project # 258034
GC
E V
IN
S
S T
A T
E J
U V
E N
IL
E
C O
R R
E C
T
IO
N A
L
F
C
IL
IT
Y
C
O N
T R
O L
P A
N E
L
S A
L L
Y P
O R
T
P L A
C E
M E
N T
09/19/2025
258034.000
/3/
/4
/2
:1 :3
P
M
A u to d e s k D o c s /2
.0
E v in s S ta te
J u v e n ile C o rr e c ti o n a l F a c ili ty -H
V A
C R e p la c e m e n ts /2
E V
IN
S
S T
A T
E J
U V
E N
IL
E
M
E P
.r v t
T0.01
TECHNOLOGY SYMBOL
LEGEND
DBR
DBR
No. DATE DESCRIPTION
T2.11
T1.1
T1.1
T1.3
T1.3
A. THE CONTRACTOR SHALL REFERENCE ALL OTHER TRADES’
CONSTRUCTION DOCUMENTS FOR FULL EXTENT OF THE SITE WORK
TO BE PERFORMED, AND FIELD VERIFY THE EXISTING JOB-SITE
CONDITIONS BEFORE BIDDING. NO CHANGE ORDER IS ALLOWED FOR
INCREASED COST ASSOCIATED WITH CONDITIONS WHICH COULD
HAVE BEEN DETERMINED BY EXAMINING THE SITE AND WHOLE
PROJECT DOCUMENTS BEFORE SUBMISSION OF PROPOSALS AND/OR
BEFORE A CONTRACT IS AWARDED.
B. ALL CONDUIT AND CABLE RUNS SHOWN ARE DIAGRAMMATIC AND FOR
DESIGN INTENT ONLY. CONTRACTOR SHALL COORDINATE WITH
INCOMING SERVICE PROVIDERS AND OTHER TRADES (ELECTRICAL,
CIVIL, ETC.) FOR THE EXACT ROUTE AND SHARED TRENCHES, IF
APPLICABLE. CONTRACTOR SHALL MAKE ANY FIELD ADJUSTMENT TO
THE ROUTE AS NECESSARY, AT NO ADDITIONAL COST TO THE
PROJECT OR OWNER, TO AVOID COLLISION AND MEET THE PROJECT
REQUIREMENTS.
C. ONLY SWEEP BENDS ARE ALLOWED FOR ALL OSP COMMUNICATIONS
CONDUITS. ALL UNDERGROUND CONDUITS SHALL ENTER THE
COMMUNICATIONS MANHOLE/HANDHOLE FROM THE SIDE WALLS AND
BE PROPERLY SEALED TO PREVENT WATER INFILTRATION.
D. ALL UNDERGROUND COMMUNICATIONS CONDUITS SHALL BE BURIED
AT MINIMUM 3 FEET FROM FINISHED GRADE, AND SLOPE AWAY FROM
BUILDING, UNLESS OTHERWISE NOTED.
GENERAL SITE PLAN NOTES:
956.683.1640 p https://www.dbrinc.com
TBPE Firm Registration No. 2234
CHECKED BY:
SHEET TITLE:
SHEET NUMBER:
PROJECT NUMBER
DRAWN BY:
DATE:
REVISION:
SEAL:
TBPE Firm Registration No. 2234
S o u th th S tr e e t, S u it e
M c A lle n T e x a s
.6
.1 p
.6
.1 f
S E
R V
U A
L
N
T E
G R
U S
T A
IN
A
B
IL
IT
Y
RT - - -
DBR Project # 258034
GC
E V
IN
S
S T
A T
E J
U V
E N
IL
E
C O
R R
E C
T
IO
N
C
IL
IT
Y
C
O N
T R
O L
P A
N E
L
S A
L L
Y P
O
P L A
C E
M E
N T
09/19/2025
258034.000
/3/
/4
/2
:1 :3
P
M
A u to d e s k D o c s /2
.0
E v in s S ta te
J u v e n ile C o rr e c ti o n a l F a c ili ty -H
V A
C R e p la c e m e n ts /2
E V
IN
S
S T
A T
E J
U V
E N
IL
E
M
E P
.r v t
T0.21
TECHNOLOGY SITE
PLAN
DBR
DBR
▯ TECHNOLOGY KEYED NOTES
T1.1 APPROXIMATE LOCATION OF ACCESS CONTROLLED GATE. PROVIDE POLE
MOUNTED NEMA 4 ENCLOSURE (16"H X 16"W X 10"D) ADJACENT TO GATE
CONTROLLER AND (1) 2-IN CONDUIT FOR SECURITY AND COMMUNICATION
CABLING FROM THIS BOX TO IT ROOM INSIDE CONTROL ROOM BUILDING.
T1.3 APPROXIMATE LOCATION OF INTERCOM BOX IN PEDESTAL TO BE
REPLACED. CONTRACTOR SHALL FIELD VERIFY AND PROVIDE PATHWAY
AND CABLING AS NECESSARY.
TN PN
1" = 60'-0"
TECHNOLOGY SITE PLAN
DC
DC
DC
DC
DC
DC
DC
J
J
CONT RM
V100
LOBBY
V107
MECH
V104
ELECT
V102
TOILET
V101
TOILET
V103
STORAGE
V106
T5.12
T5.13
T5.13
T5.13
T5.13
T5.14 T5.14
T5.14
T .1
T5.15
T5.15
3/ T2.11
2/ T2.11
1. ALL TECHNOLOGY DEVICES, OUTLETS AND CABLE/CONDUIT
PATHWAYS SHOWN ARE DIAGRAMMATIC ONLY AND ARE NOT MEANT
TO SHOW THE EXACT LOCATION OR ROUTE. CONTRACTOR SHALL
VERIFY WITH ARCHITECT AND OWNER FOR EXACT ROUTE, MOUNTING
HEIGHT, AND LOCATION BEFORE INSTALLATION, AND SHALL
COORDINATE WITH OTHER TRADES TO MAKE ANY FIELD
ADJUSTMENTS AS NECESSARY TO AVOID COLLISIONS AND MEET THE
PROJECT REQUIREMENTS.
2. CONDUITS AND BACKBOXES, SIZED PER DIV 27/28 SPECIFICATIONS,
SHALL BE PROVIDED (BY DIV 26) FOR ALL TECHNOLOGY SYSTEM
DEVICES MOUNTED ON WALL, FLOOR, AND OPEN OR SOLID FINISH
CEILING. CONDUITS/SLEEVES SHALL BE PROVIDED FOR ALL CABLES
ROUTED IN WALLS, OR THROUGH FULL HEIGHT PARTITIONS, OR
THROUGH INACCESSIBLE CEILING PLENUM, OR THROUGH SPACES
WITH EXPOSED CEILING DECK.
3. UTP CABLES OF DIFFERENT RATING (CAT 6, CAT 6A, CLASS 4 POWER)
OR JACKETING (SHIELDED OR COLORED SHEATH) OR DIFFERENT
MEDIA TYPE CABLES (UTP, FIBER, COAX, ETC.) SHALL BE ROUTED IN
SEPARATE J-HOOKS, CONDUITS, SLEEVES, CORES, DUCTS, ETC.
THROUGHOUT THE ENTIRE PATHWAY. INSTRUMENTATION, SIGNAL,
AND TELECOMMUNICATIONS CABLING (INCLUDING CLASS 4
POWER), SHALL BE SEPARATED FROM POWER CABLING WITH A
SEPARATE CABLE TRAY OR BY A DIVIDER WITHIN A CABLE TRAY.
4. BUSHINGS SHALL BE INSTALLED AT EACH END OF THE CONDUITS
BEFORE CABLES BEING PULLED THROUGH. PROVIDE PULL STRING IN
EACH CONDUIT INSTALLED AND LEAVE ONE FOR FUTURE PULLING
AFTER CABLE INSTALLATION IS COMPLETE.
5. NO NETWORK DATA CABLE RUN SHALL EXCEED 295 FEET IN TOTAL
LENGTH INCLUDING UP/DOWN AND SERVICE LOOPS WITHOUT PRIOR
APPROVAL FROM THE ARCHITECT AND ENGINEER. CONTRACTOR
SHALL COORDINATE WITH OTHER TRADES FOR PROPER PATHWAY
PLANNING.
6. ALL CONDUITS FOR TECHNOLOGY DEVICES SHALL ROUTE FROM THE
DEVICE LOCATION AND TERMINATE ABOVE LAY IN CEILING IN THE
SAME ROOM (AN OPEN CEILING OR CLOUD TYPE CEILING IS NOT
CONSIDERED AN ACCESSIBLE CEILING) WHERE THE DEVICE IS
LOCATED. IF THE ROOM WHERE THE DEVICE IS LOCATED DOES NOT
HAVE A LAY IN CEILING TO PREVENT THE CABLES FROM BEING
EXPOSED, THE CONDUIT SHALL BE INSTALLED TO THE SHORTEST
ROUTE TO THE MAIN CORRIDOR OR THE NEAREST MDF/IDF TO
REDUCE THE CABLE LENGTH ENSURING THE CABLES DOES NOT
EXCEED THE 250 FEET. ALL CONDUITS AND FITTINGS SHALL BE
PAINTED TO MATCH STRUCTURE UNLESS NOTED OTHERWISE.
7. ALL REMOTELY CONTROLLED DOORS AND GATES SHALL HAVE THE
ABILITY TO BE MANUALLY OVERRIDDEN LOCALLY WITH A KEY.
CONTRACTOR SHALL MATCH EXISTING CYLINDERS AND COORDINATE
WITH OWNER ON REQUIRED MANUFACTURER AND MODEL.
GENERAL FLOOR PLAN NOTES:
T2.11
SALLY PORT GATES
OPEN
STOP
CLOSE
INTERCOM ACTIVATIONCONTROL BUILDING
DOOR RELEASE INTERCOM ACTIVATION
WEST DOOR
LOBBY DOORS
WEST DOOR
DOOR RELEASE
INTERCOM MASTER
PUSH TO TALK
MASTER VOLUME SPEAKER
CONTROL ROOM DOORS
SOUTH DOOR
OPEN
STOP
CLOSE
INTERCOM ACTIVATION
NORTH GATE
SOUTH GATE
INTERCOM ACTIVATION
WALK TROUGH GATE
EAST DOOR
*** LEGEND ***
OPEN
STOP
CLOSE
SYMBOL DESCRIPTION
SALLY PORT SLIDING GATE KNOB. PROVIDE KNOB
AND PROGRAM TO OPEN/CLOSE GATES. SHALL BE
NORMALLY OPEN SWITCH IN THE STOP POSITION
AND CLOSE A CIRCUIT TO EITHER SIDE TO PROVIDE
SIGNAL TO OPEN OR CLOSE GATE. KNOB SHALL
SNAP BACK INTO STOP POSITION UPON RELEASE.
MOMENTARY RELEASE BUTTON. PROVIDE BUTTON
AND PROGRAM TO RELEASE DOOR/GATE
COORDINATE WITH OWNER ON ANY DELAY
REQUIREMENT. SHALL BE NORMALLY OPEN SWITCH
AND CLOSE CIRCUIT WHEN PRESSED.
INTERCOM MASTER VOLUME KNOB. PROVIDE KNOB
AND PROGRAM POTENTIOMETER TO ADJUST
SPEAKER VOLUME.
STATUS LED LIGHT. PROVIDE LIGHT AND PROGRAM
AS FOLLOWS PER APPLICATION:
• FOR BUILDING DOORS, MAN AND SLIDING GATES:
1. RED LIGHT SHALL INDICATE AN OPEN
GATE/DOOR (NOT SECURED) GREEN LIGHT
SHALL INDICATE CLOSED GATE/DOOR
(SECURED)
• FOR INTERCOM, YELLOW LIGHT SHALL INDICATE
ACTIVE INTERCOM LOCATION.
MOMENTARY RELEASE BUTTON. PROVIDE BUTTON
AND PROGRAM TO ACTIVATE INTERCOM
ASSOCIATED TO DOOR AND DEACTIVATE WHEN
PRESSED AGAIN OR ANY OTHER INTERCOM BUTTON
IS PRESSED. SHALL BE NORMALLY OPEN SWITCH
AND CLOSE CIRCUIT WHEN PRESSED.
IC
IC
IC
IC
IC
IC
IC
IC
RED
LED
GREEN
LED
YELLOW
LED
LAMP TEST
PRESS AND HOLD FOR TESTING OF LED LIGHT.
956.683.1640 p https://www.dbrinc.com
TBPE Firm Registration No. 2234
CHECKED BY:
SHEET TITLE:
SHEET NUMBER:
PROJECT NUMBER
DRAWN BY:
DATE:
REVISION:
SEAL:
TBPE Firm Registration No. 2234
S o u th th S tr e e t, S u it e
M c A lle n T e x a s
.6
.1 p
.6
.1 f
S E
R V
U A
L
N
T E
G R
U S
T A
IN
A
B
IL
IT
Y
RT - - -
DBR Project # 258034
GC
E V
IN
S
S T
A T
E J
U V
E N
IL
E
C O
R R
E C
T
IO
N
C
IL
IT
Y
C
O N
T R
O L
P A
N E
L
S A
L L
Y P
O
P L A
C E
M E
N T
09/19/2025
258034.000
/3/
/4
/2
:1 :3
P
M
A u to d e s k D o c s /2
.0
E v in s S ta te
J u v e n ile C o rr e c ti o n a l F a c ili ty -H
V A
C R e p la c e m e n ts /2
E V
IN
S
S T
A T
E J
U V
E N
IL
E
M
E P
.r v t
T2.11
TECHNOLOGY PLAN
LEVEL 1
DBR
DBR
▯ TECHNOLOGY KEYED NOTES
T5.12 APPROXIMATE LOCATION OF EXISTING TO BE REPLACED CONTROL PANEL
FOR REMOTE OPERATION OF SECURED DOORS.
T5.13 LOCATION OF REMOTELY CONTROLLED SECURED DOOR TO BE
RENOVATED.
T5.14 LOCATION OF REMOTELY CONTROLLED SECURED GATE TO BE
RENOVATED.
T5.15 APPROXIMATE LOCATION OF GATE CONTROLLER TO BE REPLACED.
CONTRACTOR SHALL FIELD VERIFY AND PROVIDE NEW MOTORS,
HARDWARE, CONTROL CABINET AND WIRING FOR A COMPLETE
FUNCTIONING SYSTEM.
TN PN
1/8" = 1'-0"
TECHNOLOGY PLAN - GATE
NOT TO SCALE
EXISTING CONTROL PANEL IN EXISTING CONSOLE
NOT TO SCALE
EXISTING CONTROL PANEL LAYOUT
12" = 1'-0"
PROPOSED CONSOLE LAYOUT
1/8" = 1'-0"
EXISTING CONTROL ENCLOSURE NORTH GATE
1/8" = 1'-0"
EXISTING CONTROL ENCLOSURE SOUTH GATE