This document appears to be Attachment 2 - MAHG201158 - Appendix A - Drawings related to a federal contract opportunity to Replace AHU FCU Weather Bldg. The contract opportunity is a Historically Underutilized Business Zone (HUBZone) certified small business set-aside issued by the Department of the Air Force Air Education and Training Command, with an estimated construction value between $500,000 and $1,000,000. A site visit is scheduled for August 14, 2024. The solicitation number is FA301024R0015, and funds are not yet available, so no award will be made until funding is secured. The document includes drawings and layouts for the Weather Training facility at Keesler AFB in Mississippi.
View the file
Other files for this federal contract opportunity
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MAHG20-1158
KEESLER AFB, MISSISSIPPI
7 MAY 2024
84332 Weather Trainin
1/ a 901 824 0
904 000
CJ CJ CJ
oD
l. 4330 = 1704
2 =
1E2)
N
1 6
C.
C.
C
:g_ ·5 m
'<:I" N N w z z �
=> .!1 m
"O ii: ii'! "' ...J " s� ·� 0
/ll ..... 0 (.)
, N • � ·e , V
."I • • � ·e I}_ V
" ."I • 0 • 0:
Iii " e •• 0 • •
I}_ " " it � ;; " "' al � V V "'
I � • i·" • � � • �
0 0 0: <
Cl) z a:
:: 0 0 uj 0:: LL
Cl) <( U)
� :::) I- z 0 z w
LU
Cl)
(.) 0:: 0:: =i w u w 0 LL z (.) 0:: Cl
(!) Cl ...J z LU 0 0:: w
6 en w ...J ...J
> a:
Cl) c..
w c..
w � <( � co
N C"') co => C"') LO
U""" u.. llJ '
N
=>0' (!)
Io I <( <( ...J ::!!:
w llJ ci Uo::'. z <( w I- ...J I w a.. I- -, w <( o::'. w a.
Facility 4332 LO.
Drawing No.
M1.0
Sheet 1 of 8
Attachment 2
FA301024R0015
HVAC LEGEND GENERAL HVAC NOTES
--CHS CHILLED WATER SUPPLY 1. MINIMUM PIPE SIZE SHALL BE¾", UNLESS SPECIFICALLY
SHOWN OTHERWISE.
---CHR CHILLED WATER RETURN 2. CONDENSATE DRAINS FROM AIR HANDLING UNITS TO BE FULL SIZE
OF CONNECTION. RUN DRAIN LINE TO NEAREST FLOOR DRAIN.
HOT WATER SUPPLY 3. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS
IIWS PRIOR TO COMMENCEMENT OF THE WORK.
4. EXISTING CONTROL SEQUENCES SHALL REMAIN. SEE APPENDIX D,
IIWR HOT WATER RETURN M5.2 FOR HVAC SEQUENCE OF OPERATIONS.
5. ALL AHUS AND EQUIPMENT MUST BE MAINTAINABLE AND VIEWABLE
---MBD MANUAL BALANCING DAMPER (MBD) FROM THE USER FRONT-END EMCS LOACTATED AT BUILDING 4705.
6. ALL PADS TO BE 4" THICK, EXTEND 6" BEYOND EQUIPMENT IN ALL
--MOD MOTOR OPERATED DAMPER (MOD) DIRECTIONS, WITH¾" CHAMFER ON ALL EDGES.
-+FD FIRE DAMPER (FD), SMOKE DAMPER (SD), COMBINATION FIRE/SMOKE DAMPER (FD/SD)
---OA -- OUTSIDE AIR
--+RA RETURN AIR
--OTC-- DATA TERMINATION CABINET
C.
C.
·5 m
N N w z
=> .Si m ii:
...J " □ s� ·� □
/ll ..... □ (.)
, N • � ·e , V
."I • • � ·e I}_ V " ."I • 0 • 0:
Iii " e • • 0 •
I}_ " " i � ;; " "' al � V V "'
I � • i ·"
0 0 0: <
Cl) z 0:: :: 0 0 uj 0:: LL
Cl) <( :::, I-z:z w
0 w 0 Cl)
(.) 0::0:: ::::> w (_) w
0 LL z 0 (..)
(!) 0 ...Jz 0 0:: w w w ...J > en ...J
Cl) 0::
w (.) a..
w � a..
)<:'. CX) <(
N co => (") LO
U-.::1" � �
LL CC
N
=> (9 (!)
IO
<( _J :::
w cc 0 u a:: z
<( w I-
_J I a.. I- -, w <( 0 a:: w c..
Facility 4332
LD.
Drawing No.
M1 .1 Sheet 2 of 8
2.
I. 2
3J5TRS
AWMC CLASSROOM
(IJ)
ELECTRICAL
25'-6"
I
El.ECll<CAL
COMIIIUNICATION
CLASSRO<JM
(17) n ---r.
�3 II
I H,;1-. Jfts
A.WC CL.ASSR00W
(13) AWC a..ASSROOM
(13)
JJ5TRS -,,.,., INSTRUCTOR
SU'EIMSOR
(1/1)
Q.ASSROOM
(17) o.ASSROOM
(17) a.ASSROOM
(17)
HERITACE ROOM
3351RS 3351RS
a.A""""' CLASSR<IOM
(17) {17)
Jfts a.ASSROOM/ LAS
(13) tlSTRU� BAY ,,.,., (8)
OIATIU (3)
MElElil (2)
3351RS
CLASSROOM
(17)
�s a..ASSROOM/ LAB
(IJ)
mz
335TRS
._,RTIJAL. REALITY
COJRSE ROOM
3351'5
CLASSRO<JM
(17)
""'2
LACTATION ROCM
3� '''"
BROADCASTINQ
ROOM
(6)
JJ51RS'""
BROADCASTING
ROOM
(8)
TEAM MEETING ROOlil
(8)
SNACK SHA
CURRICUWM
DEl.£LOPMENT W,)
I FIRST FLOOR PLAN
I. 2
L
� I I
I I I
I I I
I
NTS
FD/SD - -
L ____ t--__J �L - 6" c
46X24 IL 36X24
11 I JI: • tR G) I I : L _____ ....J 16X14
I I _L'--/ ___ ....L
I I I I
I
I I 24X18 I -----�
-□ I E)
RA r---
-5"
":"''" � ;-� X , l � -r-
_j1_ 3� . , 1 V �
I I • 1,3" I --
7--� w ____
I I I i I
O.A. ! 22X24
LOUVER -
(3 [> �1-� lJ CX)
,;;f" N
I
F D/SD
AHU
E128.
CNATl\l
CLASSROOM
(11) w,, ,,.,., CONFERENCE ROOM
(00)
CLASSROOM
(12)
Elllll
J35TRS
CLASSROOM
(17)
WO.
CNATTU/METEM """''"""
E1J2. '""'
FLT CHIEF
OFFlCE (1/1)
W2. """ 3351RS !lilRS
SECRETARY S
OFFlCE (1/1)
W2. ,.,,,., "-' cc OFFlCE (1/1)
3351R5
CLASSROOM/I.AB
(17)
CONTROL PANEL
SMOKE DAMPER
OTC
AHU-1 (1ST FLOOR, WEST) PLAN
NTS
CNATl\l a.A�/ I.AB (11)
NSTRUCTOR BAY
3JSTRS (5)
OIIATIU (5)
MElEM (5)
FLT CHIEF
OfflCE (1/1)
CLASSROCll/l.AB
(17)
CNATl\l
CLASSROOM/ LAS
(11)
WI!. "'"'
STORAGE
Em ,.,,,., CLASSROOM
(17)
E1Ll ,.,,,., CLASSROOM
(17)
CNATl\l
CLASSROOM
(10)
33�
CLA""""'
(17)
I. 2
CLASSRO<JM
{11) m
CLASSRO<JM
(11)
'111. ""'"' '"'"'"
El.ECll<CAL
Ell2.
El.ECll<CAL
CUSTOOl�TORAGE
CLASSROOM
(17)
21'-6"
GENERAL NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO COMMENCEMENT OF WORK.
2. CONTRACTOR TO VERIFY FLUE SIZING WITH MANUFACTURER'S
RECOMMENDATIONS.
3. 20X16 DUCT ROM ABOVE TERMINATED 6' BELOW 2ND FLOOR SLAB
WITH MANUAL BALANCING DAMPER.
4. ALL PADS TO BE 4" THICK, EXTEND 6" BEYOND EQUIPMENT IN ALL
DIRECTIONS, WITH¾" CHAMFER ON ALL EDGES.
KEY NOTES
(!) DEMO AREAS ARE SHADED FOR THE FIRST FLOOR.
(2) AHU-1 IS LOCATED IN ROOM W145. AHU-1 IS TO BE REMOVED
REPLACED WITH NEW. AHU-1 SF VHD CONTROLLER TO BE
REMOVED AND REPLACED WITH NEW. SEE 2,3/M1.2.
(2,'> AHU-2 IS LOCATED IN ROOM E114. AHU-2 IS TO BE REMOVED
REPLACED WITH NEW. AHU-2 SF VHD CONTROLLER TO BE
REMOVED AND REPLACED WITH NEW. SEE 1,2/M1 .3.
(4) FAN COIL UNIT-5 (FC-5) IS LOCATED IN ROOM E131. FC-5 IS TO BE
REMOVED, REPLACED WITH NEW. SEE FAN COIL SCHEDULE M1 .6.
.--- 24X 18 SMOKE
DAMPER
2 4 X 3 6 -----rt-..___,,, 14X16
SMOKE
DAMPER
4" PAD-.../
24x46
FLEX -+-
CONN
) I r
(FAN J
'-- _,,, I I j
COIL SECTION ____,
24X22 TO O.A. LOUVER
T"""
'--- PLENUM SECTION
AHU-1 (1ST FLOOR, WEST) SECTION
NTS
,;;f" N N w z s� /ll ..-
·e ,• ."I ·e" ."I• • Iii •• i " al � "' • i ·" • • 0 0 en u.j en w 0::
0LL
0::
0::
w ....I en w w z 0::
::::i en
0::
w w z z w ....I a, N
U-.::f" u.. llJ - - => (.9 Io <( ....J w llJ Uo::'.
<( w
....J I a... 1-w <( o::'. w
Facility
LO_
E" z .Si
V • 1§. • e 0 •" V
I � 0:
C.
C.
C :g_ ·5
0::
LL
en I- :z w w
0::
a..
a..
coLO��' N I z
1-w a.
�m i,'!
...J
N � � � V
0: •• 1§.
V z
__J
Cl)
Drawing No.
M1 .2
Sheet 3 of 8 v FD/SD T"""
SMOKE
DAMPER
FLEX
-- CONN.
I
I 17
\FAN I I I
I I
_./ I I L
4" PAD _____,,
COIL SECTION�
1--++-- R.A. DAMPER
20X72
�----- PLENUM
SECTION
�FILTER SECTION
I AHU-2 (1ST FLOOR, EAST) SECTION
MI. 3 NTS
72X20 DOWN TO,
PLENUM SECTION
W/RA DAMPER
\ I I� L
22X22 I
DTC
AHU-2
CONTROL PANEL
¾" HWS & HWR UP TO SECOND �
FLOOR MECH ROOM '-')
3" CHS & CHR UP TO -
SECOND FLOOR
MECH ROOM
FD/SD
_1.
i
38X24
X -
� f- - -c----
I MOD
i �
77---b .L --- :::::: :;...J. =4
FILTER�
/ COIL SECTION I -<--CHS:
SECTION
I � Cl�- L/
L FAN SECTIONFLEX.-
CONN.
t -SMOKE I 'n] I DAMPER
LJ r3",-
- _ vHR
- - HS
44X24
I k - I ;
38X24
., • � .. HWS&HWR ---- FD/SD /-
2 AHU-2 (1ST FLOOR, EAST) PLAN
MI. 3 NTS
I� I
_J
2\ 1.
j
22X22 UP W/FD
p LENUM SECTION
GENERAL NOTE
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO
COMMENCEMENT OF WORK.
2. ALL PADS TO BE 4" THICK, EXTEND 6" BEYOND EQUIPMENT IN ALL
DIRECTIONS, WITH¾" CHAMFER ON ALL EDGES.
N
N w z s� /ll
, • ·e ,•."I ·e" ."I• Iii " • i " al � "' • i·" •• 0 0
Cl) z
0:: u.j □
Cl) <( w Cl) (.) 0::0:: w0 w LL z 0:: (!)
<( z
0:: w w ....I ....I > Cl) w (.)
w � co
C")
=> C")
U""" LL llJ
=> (9 Io <( ...J w llJ Uo::'.
<( w ...J I a.. I-w <( o::'. w
Facility I.D.
C.
C.
·5
.!1 ii:
N � V • I}_ V
• 0
0: e • 0 • •
I}_ " ot ;; "' V V
I � 0: < c:::
LL
en I- zz:
0 w ::a:
(..) 0 0 ...J w 0
6 CJ)
c:::
a...
a...
co
LO ��
N ci z I-a.
Drawing No.
M1 .3 Sheet 4 of 8
== "'' (11) .......""
<D
- lltSlllUCRII BAY
»!!'IRS - 10
CW.TIU - B --•
IYl • ...,_ '-,-- c--" .... -~ ' � ,,.
OCIIIIIMICAOON
2ND FLOOR PLAN
NTS
18X34--
FD/SD ____,,
18X30 ____J
RISE UP TIGHT
TO STRUCTURE
-14X30
20X52
SMOKE
DAMPER
FAN
COIL SECTION ___,
I r7 : I I I I I I
LJ
a &
Ill
-u
FLEX
-20X52
18X28
R.A.
DAMPER
'--- PLENUM
FILTER SECTION
llilll'RUCltlll om ...
21'
�TRS - 14
ca.1&110N
T"""
121 H X 119W ACCESS DOOR/ LOUVER
46H X 58W OA DUCT w/ 3"INSUL
�22x22
'---30X60
AHU-3 (2ND FLOOR, WEST) SECTION
NTS
II
(1) 0 ('I)
<I>
GENERAL NOTES
1 . CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO COMMENCEMENT OF WORK.
2. ALL PADS TO BE 4" THICK, EXTEND 6" BEYOND EQUIPMENT IN ALL
DIRECTIONS, WITH i" CHAMFER ON ALL EDGES .
KEY NOTES
(_0 DEMO AREAS ARE SHADED FOR THE SECOND FLOOR .
<i) AHU-3 IS LOCATED IN ROOM W244. AHU-3 IS TO BE
REMOVED, REPLACED WITH NEW. AHU-3 SF VFD
CONTROLLER TO BE REMOVED, REPLACED WITH NEW. SEE
2,3/M1 .4 .
@ AHU-4 IS LOCATED IN ROOM E214. AHU-4 IS TO BE REMOVED,
REPLACED WITH NEW. AHU-4 SF VFD CONTROLLER TO BE
REMOVED, REPLACED WITH NEW. SEE 1/M1 .5.
FD/SD
HW
34X 18 24X2
16"<!) TYPE B VENT UP THRU ROOF _ ___._.,...,___,,
FD/SD
HWR
36X20 2"
24X24
I 24 X 14 I
SMOKE
DAMPER
o rI
PLENUM
SECTION
48X 18
30X 14
FD
CONTROL PANEL
AHU-3 (2ND FLOOR, WEST) PLAN
NTS
C.
C.
·5
N
N w z
=> .Si ii:
s� ·� □ ill..- □ (.)
, N • �·e , V
."I • • � ·e I}_ V " ."I • I}_ • " eIii • • 0 • � •
I}_ " " i ot ;; " "' al � V V "'
I � • i·" • � � • �
0 0 � <
Cl) z c::: :: 0 uj 0:: 0
LL
Cl) <( en
� :::, I- z 0 z:
0 w Cl) w (.) 0::
::a:
� 0:: w ::::, 0 w (.)
LL z 0 0::
0 (..)
<( z 0 _J
0:: w w 0 w ...J 6 CJ) ...J > Cl) c:::
w (.) a..
w � a.. � co <( co => C"') LO
U""" � � u.. llJ N
=>0' (!)
Io <( ...J ::!!:
w llJ ci Uo::'. z <( w I-
...J I a.. I- ., w <( o::'. w a.
Facility 4332
LD.
Drawing No.
M1.4
Sheet 5 of 8
AHU-4 CONTROL PANEL
HVAC CONTROL PANEL
121H X 119W ACCESS DOOR/ LOUVER
46H X 58W OA DUCT w/ 3"INSUL
RA DUCT
OADUCT
O>---�O
@ (D
<D�
121W X 12 L CONCRETE MT SLAB
SA DUCT
(D
RA DUCT
19 X 19 OA DUCTw/ 3"INSUL
DN TO 1ST FLOOR, AHU-2
AHU-4 SF VFD CONTROLLER
AHU-4 (2ND FLOOR, EAST) DETAIL
NTS
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS PRIOR TO COMMENCEMENT OF
WORK.
2. ALL PADS TO BE 4" THICK, EXTEND 6" BEYOND
EQUIPMENT IN ALL DIRECTIONS, WITH¾"
CHAMFER ON ALL EDGES.
KEY NOTES (INTERFERENCE WORK):
(D AT MIN. (4) SPRINKLER HEADS AND PIPING MUST
BE REMOVED, REINSTALLED; TO REMOVE
DUCTWORK AND MOVE AHU IN/ OUT.
(1) L TG FIXTURE MUST BE REMOVED,
REINSTALLED; TO REMOVE DUCTWORK AND
MOVE AHU IN/ OUT.
@ APPROX 15LF OF PLUMBING VENT PIPE MUST BE
REMOVED, REINSTALLED AT ACCESS OPENING.
3" RISER, 2" OFFSET.
@ AHU-4 TO BE REMOVED, REPLACED WITH NEW.
AHU-4 SF VFD CONTROLLER TO BE REMOVED,
REPLACED WITH NEW.
C.
C.
·5
N
N ;;
w " z z �
.!1 m
=> ii'!
□ s� ·� □
/ll ..... (.)
, N • � ·e , u
."I • •·e I}_ u " ."I • 0 • 0:
Iii " e • • 0 •
I}_ " " i � ;; " "' al � u u "'
I � • i·"
0 0 0: <
Cl) z c::: ::
0:: 0 uj □ LL
Cl) <( en
� :::) I- z 0 z:
0w Cl) w
(.) 0::
::a:
0::
w
0 w (.)
LL z 0
(..) 0::
<( z 0 ...J
0:: w w 0 > enw ...J 0 ...J
> c::: Cl) w (.) a.
w a.
<( )<:'. CX)
co => (") LO
U-.::1" � � u.. cc N
=> (9 (!)
IO
<( _J :::
w cc 0 u a:: z
<( w I-
....J I a.. I- -, w <( 0 a:: w c..
Facility 4332
LD.
Drawing No.
M1.5 Sheet 6 of 8
� FC-1 � -
U-LA_ l_ <D@
NN
OBSERVATION AREA
(D@ n_lY _J FC-3 � - -
� FC-2
(D@
<D@ c-
� FC-4
FAN-COIL UNIT SCHEDULE
TYPE NOMINA MIN. COOLING COIL (NOTE 3)
NO. AREA SERVED
(NOTE 1) L CFM SENSIBLE LATENT RUNOUT
(NOTE 2)
O.A. CFM GPM
MBH MBH SIZES, IN.
FC-1 THIRD FLOOR V 900 50 18.3 1.5 3.7 3/4"
FC-2 THIRD FLOOR V 900 50 18.3 1.5 3.7 3/4"
FC-3 THIRD FLOOR V 900 50 18.3 1.5 3.7 3/4"
FC-4 THIRD FLOOR V 900 50 18.3 1.5 3.7 3/4"
FC-5 ELEV. EQUIP. RM. HC 900 - 4.8 4.7 1 3/4"
NOTES:
1. TYPES: HC HORIZONTAL CONCEALED
VC VERTICLE CONCEALED
V VERTICLE WITH CABINET
VH VERTICAL HIGH RISE
2. CFM BASED ON MEDI UM FAN SPEED.
3. CHILLED WATER BASED ON : 76 °F DB AND 63°F
WB EAT, 46 °F EWT, 10 ° 8T, AND MAXIMUM 12'
WPD.
4. HOT WATER BASED ON: 70°F DB EAT, 180°F EWT,
GENERAL NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO COMMENCEMENT OF WORK ..
KEY NOTES
(D DEMO FC-1 THROUGH FC-4 AS INDICATED ON THE THRID FLOOR.
SEE FAN COIL SCHEDULE.
@ PROVIDE AND INSTALL NEW FC-1 THRU FC-4. SEE FAN COIL
SCHEDULE.
HEATING COIL (NOTE 4)
RUNOUT
MBH GPM
SIZES, IN
28.6 1.5 3/4"
28.6 1.5 3/4"
28.6 1.5 3/4"
28.6 1.5 3/4"
N N w z s� /ll
·e ,• ."I ·e Iii • " it al • ·"• C en uj en w 0::
LL
0::
0::
w ...I en w w
."I i• C z 0::
en
0::
w w z z w ...I a, N
U""' u.. llJ - - => (9 Io <( ...J w llJ Uo::'.
<( w ...J I a.. 1-w <( o::'. w
E " z .!1
V • I}_ • e 0 •" V
I � 0:
c:::
LL
en I-z
LU
:a; => c., Cl
D
LU
6 c:::
Cl..
Cl..
co
LO��'
N I z 1-w a.
ii'!
...J
N � � � V
0: •• I}_
V z
_J en
Facility 4332
LO.
Drawing No.
M1.6
Sheet 7 of 8
NO. AREA SERVED {NOTE 1)
AHU-1
1ST FLOOR WEST
AHU-2
1ST FLOOR EAST
AHU-3
2ND FLOOR WEST
AHU-4 2ND FLOOR EAST
TYPE
{NOTE 2)
CFM
HZ-DT 15720
HZ-DT 16280
HZ-DT 21190
HZ-DT 15500
I
FAN
ESP. IN.
TYPE
RPM WG
(NOTE 3)
(NOTE 4)
1330 AF,W 1.5
1150 AF,W 1.75
1390 AF,W 1.5
1110 AF,W 1.75
- NOTES:
1. DESIGN CONDITIONS:
2. TYPES:
OUTSIDE
GENERAL COND. SPACES
COMP. RM (YR-ROUND)
DT DRAW-THROUGH
BT BLOW-THROUGH
HZ HORIZONTAL
VT VERTICLE
3. FAN TYPES:
FC FORWARD CURVED
AF AIRFOIL
SUMMER
92°F DB, 81 °F
77°F DB
74° DB
WINTER
WB, 31°F DB
68°F DB
&50% RH
CV CONSTANT VOLUME
VV VARIABLE VOLUME
4. EXTERNAL STATIC PRESSURE DOES NOT INCLUDE UNIT CASING,
DIFFUSER SECTION, OR UNIT MOUNTED HEATING AND COOLING COILS,
BUT DOES INCLUDE FILTERS. FAN STATIC PRESSURE IS FOR ESTIMATING
PURPOSES ONLY. CONTRACTOR SHALL CALULATE AND PROVIDE FOR
EQUIPMENT ACTUALLY INSTALLED.
5. MAX. FOR VARIABLE VOLUME UNITS: 550 FPM COIL FACE VELOCITY,
. 85" WG APO. MAX. FOR CONSTANT VOLUME UNITS: 500 FPM COIL FACE
VELOCITY, .75" WG APO. EXTENDED WIDTH COILS ARE NOT
ACCEPTABLE.
6. CHILLED WATER BASED ON 46°F EWT, 14° L1T, AND MAX. 18' WPD, MIN.
6 ROW 12 FINS PER INCH FOR COILS.
7. MAX. 0.2" WG APO.
8. PROVIED INLET VANES.
I
I I I
AIR HANDLING UNIT SCHEDULE
MIN. OA
MOTOR CFM
HP.
15 4000
15 4000
20 4000
10 4000
TOTAL
CFM
COOLING
(NOTE 5)
MBH
15720 765
16820 763
21190 920
15500 782
COOLING COIL VIBRATION ISOLATION
SEN CHILLED
EAT °F LAT °F
MIN STATIC NOTES
COOLING WATER GPM TYPE DEFLECTION
MBH
(NOTE 6)
DB WB DB WB
82.2
82.3
84.2
COOLING
COIL
DRAIN PAN
69.4
68.9
67.8
69.7
54.8 53.9 s
54.9 53.9 s
54.8 53.7 s
54.8 53.7 s r HARDWARE CLOTH
SCREEN COVER
�2"MINIMUM
J i.---FAN TOTAL
STATIC PRESSURE
i-1" GREATER THAN
HALF OF FAN
TOTAL STATIC
PRESSURE
MINUMUM - � FLOOR
1" CLEARANCE -�--�/ __ _
IN.
1 1/2
1 1/2
CONDENSATE DRAIN FOR DRAW-THROUGH COOLING COILS
NOTES:
1. ALL PIPING SHALL BE FULL SIZE OF DRAIN CONNECTION.
2. EXTEND DRAIN TO NEAREST FLOOR DRAIN.
3. WHERE SUPPORTED, ISOLATE PIPING FROM CLAMPS WITH 2 LAYERS
OF t" THICK 30 DUROMETER NEOPRENE WAFFLE PADS .
GENERAL NOTE
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO
COMMENCEMENT OF WORK.
2. ALL PADS TO BE 4" THICK, EXTEND 6" BEYOND EQUIPMENT IN ALL
DIRECTIONS, WITH l" CHAMFER ON ALL EDGES.
I I
I
I I
�'!av,�
C.
C. <
N N w z s� /ll
·e , •."I ·e" ."I• "• i "� al "'• i·"
C C
Cl) z :: 0
- 0::
LJJ □
Cl) <( LJJ g
(.) 0::0:: LJJ 0 LJJ
LL z 0:: - <( z
0:: LJJ
LJJ ...J
...J - Cl) >
LJJ (.)
LJJ �
)<:'. CX)
U""
LL CC
=> (9
IO
<( _J w cc u a::
<( w _J I a.. I-w <( a:: w
.!1 ii:
V • I}_ • e 0 •" ot V
I � 0:
c:::
LL
N � V
0:•• I}_
V
I- z iTI 0 ::a: - ::::, !;: u l o- 0 (..)
0 ...J wo
� Cl) a.
a.
co
LO� �
N
I-c..
Facility 4332
LD.
Drawing No.
M1.7 Sheet 8 of 8
| MAGH201158M1 |
| MAGH201158M2 |
| MAGH201158M3 |
| MAGH201158M4 |
| MAGH201158M5 |
| MAGH201158M6 |
| MAGH201158M7 |
| MAGH201158M8 |