Attachment 2 - EHRM RTA Drawings_Electrical.pdf

PDF 28 MB Posted

Attached to
Y1BG--EHRM Construction Infrastructure Upgrades - 679-20-104 -Tuscaloosa VAMC
Solicitation number
36C77625R0025
Issued by

About this file

This file is an electrical drawing set for the EHRM Infrastructure Upgrades project at the Tuscaloosa VA Medical Center (VAMC). The detailed electrical drawings, prepared by Atriax, PLLC and Wiley|Wilson, document comprehensive electrical system modifications across multiple buildings, including new electrical panels, transformers, power distribution systems, and associated infrastructure upgrades.

Key technical details include installing new 208V/120V transformers, electrical panels (emergency and normal branches), automatic transfer switches, and power busways. The project involves electrical work in Buildings 1, 2, 3, 4, 5, 6, 61, 135, 137, 138, 39, 40, 41, 146, 147, 149, and 151, with specific focus on telecommunications rooms, electrical rooms, and infrastructure connections. The electrical design incorporates sophisticated elements like network receptacles, fire alarm systems, lighting controls, and equipment connections, with careful attention to mounting heights, grounding requirements, and compliance with electrical codes and VA specifications.

View the file

Other files

File Type Posted
36C77625R0025 0005.pdf PDF
36C77625R0025 0004.pdf PDF
Amendment 0004 - Attachment 27 - 36C77625R0025_1.pdf PDF
Attachment 23 - RFI 223. JSN Fixtures_Toilet.pdf PDF
Attachment 18 - Laydown Area Site Map.pdf PDF
Attachment 22 - RFI 77. Special Inpsections.xlsx XLSX spreadsheet
Attachment 27 - 36C77625R0025_1.pdf PDF
Attachment 19 - Lead Based Paint Report.pdf PDF
Attachment 20 - Asbestos Report.pdf PDF
Attachment 26 - RFIs - Tuscaloosa_FINAL.pdf PDF
Attachment 21 - RFI 70. B13_WALL_TYPE.pdf PDF
Attachment 14 - Updated WD_3.13.2025.pdf PDF
Attachment 24 - RFI 223. Standard Mounting Heights.pdf PDF
36C77625R0025 0003.pdf PDF
Attachment 25 - RFIs 263-265 Partial Electrical.pdf PDF
36C77625R0025 0002.pdf PDF
36C77625R0025 0001.pdf PDF
Amendment 0001 - Att 01 - 679-20-104 Site Visit Sign-In Sheet.pdf PDF
Amendment 0001 - Att 02 - Pre Proposal Conference - Tuscaloosa.pdf PDF
Attachment 8 -EHRM RTA Drawings_Telecommunications General and New Work.pdf PDF
36C77625R0025_1.pdf PDF
Attachment 10 - Submittal Register RTA.xlsx XLSX spreadsheet
Attachment 1 - SOW - EHRM Tuscaloosa.pdf PDF
Attachment 14 - WD - AL20240098 - 01.03.2025.pdf PDF
Attachment 5 - EHRM RTA Drawings_Mechanical and Plumbing.pdf PDF
Attachment 6 - EHRM RTA Drawings_Structural and Architecture.pdf PDF
Attachment 12 - Geotechnical Report - EHRM Data Center.pdf PDF
Attachment 16 - Brand Name - Corbin Russwin - Manufacture Document.pdf PDF
Attachment 11 - TVAMC Site Map_PSRDM.pdf PDF
Attachment 17 - Division Cost Breakdown.xlsx XLSX spreadsheet
Attachment 9 - EHRM RTA Specifications.pdf PDF
Attachment 13 - Limitations on Subcontracting - Construction.pdf PDF
Attachment 7 - EHRM RTA Drawings_Telecommunications General and Demolition.pdf PDF
Attachment 4 - EHRM RTA Drawings_General and Civil.pdf PDF
Attachment 15 - Brand Name - EHRM Tuscaloosa.pdf PDF
Attachment 3 - EHRM RTA Drawings_Fire Protection.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N

10 12

HAGLER LANE

Fire Station

PL#5

PL#4

PL#3

PL#

PL#9

PL#8

PL#7

PL#6

Hospice

LOOP ROAD

McAbee Center

Property Line

P ro pe rty

L in e

PL#2

TEMP. PL

LIBERTY PARK

33A

Project Locations

D

UN ITED STATES OF AM

ER

IC

A

SR

IA

FF

AS

NARE

TEVFOTNEMTRAPE

679-20-104EHRM INFRASTRUCTURE

UPGRADES

www.atriaxgroup.com

Atriax, pllc 703 Main Avenue SW PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254 03/08/2024

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Chief Engineer

Revisions: Date:

Specialized Engineering Solutions 1300 Baxter Street, Suite 355 Charlotte, NC 28204

Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com

FOR OFFICIAL USE ONLY (FOUO)

FOR OFFICIAL USE ONLY (FOUO)

TUSCALOOSA VAMC, TUSCALOOSA, AL.

COVER SHEET

GI001

MM/TRTG

REVIEWER'S SIGNATURES

TUSCALOOSA VA MEDICAL CENTER

TUSCALOOSA, AL 35404

PROJECT # 679-20-104

EHRM INFRASTRUCTURE UPGRADESELECTRICAL

INDEX OF DRAWINGS

ELECTRICAL

GI002

MM/TRTG

679-20-104EHRM INFRASTRUCTURE

UPGRADES

www.atriaxgroup.com

Atriax, pllc 703 Main Avenue SW PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254 03/08/2024

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Chief Engineer

Revisions: Date:

Specialized Engineering Solutions 1300 Baxter Street, Suite 355 Charlotte, NC 28204

Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com

FOR OFFICIAL USE ONLY (FOUO)

FOR OFFICIAL USE ONLY (FOUO)

TUSCALOOSA VAMC, TUSCALOOSA, AL.

INDEX OF DRAWINGS

ELECTRICAL ABBREVIATIONS

ABBREVIATION DESCRIPTION

REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.

MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)

AMPERE

AMPERE FRAME

ABOVE FINISHED FLOOR

ALUMINUM

AMPERE TRIP

CEILING

CIRCUIT BREAKER

COLOR TEMP CONTROL

COPPER

DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)

DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)

EXISTING

ELECTRICALLY OPERATED

ENERGY REDUCING MAINTENANCE SWITCH

FUSE

FULL LOAD AMPS

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT ALARM

GROUND FAULT PROTECTION

HORSEPOWER

KILOAMPERE INTERRUPTING CAPACITY

KILOVOLT AMPERE

KILOWATT

MAXIMUM

MINIMUM CIRCUIT AMPS

MAIN CIRCUIT BREAKER

MINIMUM

MAIN LUGS ONLY

MANUALLY OPERATED

NORMALLY CLOSED

NON-FUSED

NOT IN CONTRACT

NORMALLY OPEN

POLES

PARTIAL

RELOCATE

SHORT CIRCUIT CURRENT RATING

SURGE PROTECTIVE DEVICE

SHUNT TRIP

TYPICAL

UNLESS NOTED OTHERWISE

VOICE

WALL PHONE

WIRE

WEATHER RESISTANT

TRANSFORMER

ZONE SELECTIVE INTERLOCKING

A

AF

AFF

AL

AT

C

CB

CCT

CU

D

D

E

EO

ERMS

F

FLA

G, GFCI

GFA

GFP

HP

KAIC

KVA

KW

MAX

MCA

MCB

MIN

MLO

MO

NC

NF

NIC

NO

P

PART

R

SCCR

SPD

ST

TYP

UNO

V

W

W

WR

XFMR

ZSI

A. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75' SHALL UTILIZE #10 AWG CONDUCTORS.

RECEPTACLE BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 150' SHALL UTILIZE #8 AWG

CONDUCTORS.

B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE

SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.

C. NEW ROOF MOUNTED EQUIPMENT SHALL BE BONDED TO EXISTING BUILDING LIGHTNING PROTECTION SYSTEM IF ONE EXISTS. PROVIDE AIR TERMINALS ON TOP OF EQUIPMENT AND BOND TO EXISTING SYSTEM PER NFPA 780 AND UL 96A REQUIREMENTS. PROVIDE UL INSPECTION AND/OR LPI SYSTEM INSPECTION AS REQUIRED TO OBTAIN UL MASTER LABEL RECERTIFICATION, UL MASTER LABEL AND/OR LPI SYSTEM

CERTIFICATE.

D. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL

COST TO THE OWNER.

E. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR

INSTALLED DEVICES.

F. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS

ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING

ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND

PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.

G. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND ALL

NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE SAME

INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.

H. ALL CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, INCLUDING LIGHTING AND WALL RECEPTACLES, SHALL BE MECHANICALLY PROTECTED PER NEC 517.31(C)(3). NON-FLEXIBLE RACEWAY SHALL BE USED FOR CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, EXCEPT THAT THE FINAL CONNECTION TO VIBRATING EQUIPMENT OR LIGHT FIXTURES IF THE TOTAL LENGTH OF FLEXIBLE RACEWAY IS 6' OR LESS ACROSS THE

ENTIRE CIRCUIT LENGTH.

I. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN

CABLING.

(GENERAL NOTES SHALL APPLY TO ALL SHEETS)

ELECTRICAL GENERAL NOTES:

A. LIGHTING CONTROL DEVICES ARE INDICATED WITHOUT CONNECTION TO FIXTURE(S) BEING CONTROLLED.

WITHIN EACH AREA, CONNECT CONTROL DEVICE TO SERVE LIGHT FIXTURE(S) LOCATED WITHIN SAME AREA. WHERE LIGHT FIXTURES ARE INDICATED WITH A SUBSCRIPT LETTER IDENTIFYING INDIVIDUAL LIGHTING CONTROL ZONES, CONTROL DEVICE SERVING AREA WITH MATCHING SUBSCRIPT SHALL

CONTROL CORRESPONDING LIGHT FIXTURES.

B. SWITCHES SERVING UNDERCABINET TASK LIGHTING SHALL MATCH RECEPTACLE HEIGHT ABOVE COUNTER.

C. LIGHTING CONTROL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS.

CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH

ARCHITECTURAL INTERIOR ELEVATIONS. WHERE DEVICE MOUNTING HEIGHTS ARE NOT INDICATED PER ARCHITECT, MOUNT DEVICES AT HEIGHT INDICATED IN ELECTRICAL PROJECT SPECIFICATIONS.

D. CONTRACTOR SHALL COORDINATE ALL LIGHTING CONTROL DEVICE ROUGH-IN LOCATIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS TO ASSURE COMPATIBILITY WITH FINISHES SPECIFIED ON THE ARCHITECTURAL DRAWINGS. COORDINATE ROUTING OF ALL ELECTRICAL BRANCH CIRCUITS AND CONDUIT WITH OTHER TRADES TO ALLOW FOR SERVICE AND MAINTENANCE AND TO MINIMIZE THE USE OF ACCESS PANELS. WHERE ACCESS PANELS CANNOT BE AVOIDED, WORK TO INSTALL PANELS IN LOCATIONS

ACCEPTABLE TO ARCHITECT.

E. FIXTURES DESIGNATED ['24'][,] ['LS'][,] AND EXIT LIGHTS SHALL BE SERVED FROM A [COMMON] 20A [120V] [277V] [LIFE SAFETY BRANCH CIRCUIT (WITHIN PANEL ___)][CENTRAL BATTERY INVERTER BRANCH CIRCUIT].

[FIXTURES DESIGNATED '24' AND] EXIT LIGHTS SHALL BE ILLUMINATED 24 HOURS. [FIXTURES DESIGNATED 'LS' SHALL BE SWITCHED BY CONTROLS INDICATED. PROVIDE EMERGENCY LIGHTING CONTROL RELAYS PER SPECIFICATIONS FOR EMERGENCY LIGHTING OVERRIDE. REFER TO MANUFACTURER'S WIRING DIAGRAMS FOR INSTALLATION INSTRUCTIONS.] [BRANCH CIRCUITS SHALL BE DISTRIBUTED AS FOLLOWS:

• FLOOR A, AREA A (- LIFE SAFETY PANEL-CIRCUIT NUMBER)

• REPEAT AS NEEDED]

F. REFER TO DETAILS, SCHEDULES, AND SYMBOL LEGENDS FOR ADDITIONAL REQUIREMENTS.

(LIGHTING GENERAL NOTES SHALL APPLY TO ALL SHEETS)

LIGHTING GENERAL NOTES:

A. ELECTRICAL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS.

CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH

ARCHITECTURAL INTERIOR ELEVATIONS. WHERE DEVICE MOUNTING HEIGHTS ARE NOT INDICATED PER ARCHITECT, MOUNT DEVICES AT HEIGHT INDICATED IN ELECTRICAL PROJECT SPECIFICATIONS.

B. CONTRACTOR SHALL COORDINATE ALL ELECTRICAL DEVICE ROUGH-IN LOCATIONS AND ELEVATIONS WITH

ARCHITECTURAL DRAWINGS TO ASSURE COMPATIBILITY WITH FINISHES SPECIFIED ON THE

ARCHITECTURAL DRAWINGS. ROUTE ALL ELECTRICAL BRANCH CIRCUITS AND CONDUITS SPECIFIED, TO COORDINATE WITH OTHER TRADES AND TO ALLOW FOR SERVICE AND MAINTENANCE AND TO MINIMIZE THE USE OF ACCESS PANELS. WHERE ACCESS PANELS CANNOT BE AVOIDED, ARRANGE WORK TO INSTALL

PANELS IN LOCATIONS ACCEPTABLE TO ARCHITECT.

C. REFER TO DETAILS, SCHEDULES, AND SYMBOL LEGENDS FOR ADDITIONAL REQUIREMENTS.

D. REDUNDANT GROUNDING METHODS REQUIRED FOR PATIENT CARE AREAS. REFER TO NEC FOR

REQUIREMENTS AND TO PROJECT SPECIFICATIONS FOR ACCEPTABLE METHODS/APPLICATIONS.

E. GFCI TYPE RECEPTACLES ARE NOTED AS SUCH ON THE PLANS FOR PRICING PURPOSES. HOWEVER, CONTRACTOR SHALL BE RESPONSIBLE TO ENSURE ALL RECEPTACLES INSTALLED WHERE A 6' CORD

LENGTH COULD REACH THE EDGE OF A SINK HAVE GFCI PROTECTION.

(POWER GENERAL NOTES SHALL APPLY TO ALL SHEETS)

POWER GENERAL NOTES:

A. THE INTENT OF THE DEMOLITION DRAWINGS IS TO DEFINE THE SCOPE OF ELECTRICAL DEMOLITION WORK.

EXISTING ELECTRICAL SYSTEMS (DEVICES, FIXTURES, EQUIPMENT, WIRING, AND RACEWAYS INCLUDING DATA/COMMUNICATION SYSTEMS) WITHIN LIMITS OF DEMOLITION AND NOT SERVING ADJACENT AREAS, SHALL BE REMOVED UNLESS OTHERWISE INDICATED. RE-SUPPORT EXISTING CONDUITS AND CABLES THAT

MUST REMAIN.

OR

THE INTENT OF THE DEMOLITION

DRAWINGS IS TO DEFINE THE SCOPE OF ELECTRICAL DEMOLITION WORK. PROVIDE DEMOLITION FOR

ITEMS AS SHOWN.

B. ITEMS INDICATED WITH A SUBSCRIPT 'E' SHALL BE EXISTING TO REMAIN (E-EXISTING). ITEMS INDICATED WITH A SUBSCRIPT 'D' OR SHOWN DASHED SHALL BE REMOVED (D-DEMOLITION). ITEMS INDICATED WITH A SUBSCRIPT 'R' SHALL BE REMOVED, STORED, AND REINSTALLED PER NEW WORK (R-RELOCATION).

C. THESE DRAWINGS DO NOT IDENTIFY EACH INDIVIDUAL ITEM TO BE REMOVED. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ITEMS WHICH MUST BE REMOVED TO FACILITATE NEW CONSTRUCTION.

SEE ARCHITECTURAL PLANS FOR EXACT LIMITS OF DEMOLITION AND CONSTRUCTION. THESE PLANS ARE BASED ON PAST PROJECT DRAWINGS AND SITE OBSERVATIONS. THE DRAWINGS ARE PROVIDED TO THE CONTRACTOR AS AN AID IN DETERMINING THE EXTENT OF WORK REQUIRED FOR DEMOLITION AND TO PROVIDE GENERAL INFORMATION ABOUT EXISTING SYSTEMS. THESE DRAWINGS MAY NOT BE ACCURATE IN ALL AREAS. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING

CONDITIONS AND IS ENCOURAGED TO REVIEW FACILITY DRAWINGS PRIOR TO THE BID DATE.

D. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL ITEMS REMOVED. IF OWNER REFUSES SALVAGE, CONTRACTOR IS RESPONSIBLE FOR DISPOSAL.

E. WHERE EXISTING WALLS ARE TO BE REMOVED, ALL ASSOCIATED ELECTRICAL EQUIPMENT SHALL BE REMOVED. DISCONNECT POWER SO THAT DEVICES AND EQUIPMENT MAY BE REMOVED WITH WALLS. SEE

ARCHITECTURAL DRAWINGS FOR WALLS TO BE REMOVED. ABANDON CONCEALED CONDUITS WHERE

WALLS ARE NOT REMOVED. CONCEALED CONDUITS MAY BE REUSED WHERE AVAILABLE. WHERE EXISTING CIRCUITING/CABLING IS TO BE DEMOLISHED AND NOT REUSED, REMOVE CONDUCTORS AND ASSOCIATED ACCESSIBLE RACEWAYS/CONDUIT BACK TO THE SOURCE. WHERE EXISTING ELECTRICAL CONDUITS SERVING CIRCUITS TO BE DEMOLISHED ARE EMBEDDED IN CONCRETE FLOORS OR WALLS, CONDUITS MAY BE ABANDONED IN PLACE. EXISTING CONDUCTORS SHALL BE REMOVED BACK TO SOURCE AND CONDUITS SHALL BE CUT AT SURFACE OF CONCRETE AND FILLED. EXISTING BACK BOXES AND CONDUITS REMAINING FROM DEVICES BEING REMOVED MAY BE UTILIZED FOR NEW DEVICES WHERE LOCATIONS PERMIT.

REMOVE AND PATCH WHERE BOXES ARE NOT REUSED.

F. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL ELECTRICAL DEMOLITION ITEMS. DISCONNECT AND REMOVE ELECTRICAL DEVICES, EQUIPMENT AND ASSOCIATED WIRING AS REQUIRED TO ACCOMMODATE NEW WORK. IF THE CONTRACTOR IS UNCLEAR REGARDING A SPECIFIC ITEM TO REMAIN OR BE REMOVED, THE CONTRACTOR SHALL SEEK CLARIFICATION FROM THE ARCHITECT.

G. SYSTEMS SERVING ADJACENT AREAS AND ITEMS THAT REMAIN SHALL BE MAINTAINED AT ALL TIMES.

MODIFY SYSTEMS AS REQUIRED THROUGHOUT CONSTRUCTION TO MAINTAIN CONTINUITY OF SERVICE. DO

NOT INTERRUPT SERVICE WITHOUT OWNER'S PRIOR WRITTEN APPROVAL. LIMIT DURATION OF

INTERRUPTION ONLY TO THE TIME NECESSARY FOR DISCONNECTION AND IMMEDIATE RECONNECTION.

INTERRUPTION TO SERVICE DEEMED BY OWNER AS ESSENTIAL MAY REQUIRE PREMIUM TIME AND SHALL BE INCLUDED WITH THE BID. EXTREME CARE SHALL BE TAKEN BY THE CONTRACTOR TO IDENTIFY EXISTING SYSTEM COMPONENTS ASSOCIATED WITH THESE SERVICES. APPROPRIATE METHODS OF MARKING THESE SHALL OCCUR TO ELIMINATE THE POSSIBILITY OF ACCIDENTAL INTERRUPTION. FOR CONDUIT AND CABLING THAT CAN REMAIN, PROVIDE SUPPORT AS REQUIRED. RELOCATE EXISTING JUNCTION BOXES THAT

BECOME INACCESSIBLE DUE TO NEW WORK.

H. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY POWER AND

LIGHTING AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED.

I. PROTECT EXISTING ELECTRICAL EQUIPMENT THAT REMAINS. IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY, QUALITY, AND FUNCTIONALITY.

J. PATCH AND REPAIR OPENINGS IN EXISTING WALLS AND FLOORS RESULTANT FROM SPECIFIED ELECTRICAL DEMOLITION. PATCH SHALL MATCH EXISTING CONSTRUCTION, FIRE RATING, AND FINISH. SEE

ARCHITECTURAL SPECIFICATIONS FOR MEANS AND METHODS.

K. THIS PROJECT WILL BE PHASED. SEE PROJECT MANUAL AND ARCHITECTURAL PLANS FOR DETAILS.

SYSTEM SERVICES TO AREAS NOT IN THE CURRENT PHASE OF CONSTRUCTION SHALL BE MAINTAINED AT

ALL TIMES.

L. WHERE DEMOLITION OF EQUIPMENT INVOLVES REMOVAL OF EQUIPMENT LOCATED ON CONCRETE HOUSEKEEPING PADS, PADS SHALL ALSO BE REMOVED AND FLOOR/GRADE SHALL BE FINISHED TO MATCH

ADJACENT SURFACE.

M. ALL UNLABELED ELECTRICAL DEVICES [WITH CIRCUITRY OR DEVICES MODIFIED DURING CONSTRUCTION] [THAT EXIST IN ALL ROOMS WHERE THERE IS WORK WITHIN SCOPE] SHALL BE CIRCUIT TRACED AS NEEDED

WITH A LABEL PROVIDED.

(ELECTRICAL DEMOLITION NOTES APPLY TO ALL ELECTRICAL DEMOLITION PLANS AND

ALL ELECTRICAL DEMOLITION WORK)

ELECTRICAL DEMOLITION GENERAL NOTES:

(BLANKET DEMO)

(SELECTIVE DEMO)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Specialized Engineering Solutions 1300 Baxter Street, Suite 355 Charlotte, NC 28204

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254 www.atriaxgroup.com

Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com

03/08/2024

A u to d e s k D o c s /2

.0

V A

T u s c a lo o s a E

H R

M I n fr a s tr u c tu re U p g ra d e s /2

.0

V A

T u s c a lo o s a

E H

R M

I n fr U p g ra d e s

B X

X X

S

E S

.r v t

/0

/2

:1

:1

E-000

ELECTRICAL SYMBOLS AND

ABBREVIATIONS

EHRM INFRASTRUCTURE UPGRADES

TUSCALOOSA VAMC, TUSCALOOSA, AL.

679-20-104

03/08/2024 CGH MJJ

ELECTRICAL FIXTURE

SYMBOLS

PLAN SYMBOL NAME

RECEPTACLE - DOUBLE DUPLEX

- CONV

RECEPTACLE - DUPLEX - CONV

RECEPTACLE - DUPLEX - CONV -

GFCI

RECEPTACLE - DUPLEX -

EMERGENCY (RED) - CONV

ELECTRICAL FIXTURE SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

ELECTRICAL GROUND BAR PROVIDE LENGTH AS REQUIRED TO ACCOMMODATE TERMINATIONS, MINIMUM 20" IN LENGTH. REFER TO

SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

JUNCTION BOX - CEILING GENERAL:

PROVIDE JUNCTION BOX AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH JUNCTION BOX TYPE. REFER TO FLOOR PLANS FOR JUNCTION BOX DESIGNATION. PROVIDE ONE (1) 4" SQUARE, 2-1/8" DEEP JUNCTION BOX WITH SINGLE GANG TRIM RING AND BLANK WALL PLATE WITH ONE (1) 1” CONDUIT TO ABOVE ACCESSIBLE CEILING WHERE NOT INSTALLED IN ACCESSIBLE CEILING. WHERE SHOWN ADJACENT TO CEILING RECEPTACLES ON FLOOR PLANS, PROVIDE MAXIMUM 8” BETWEEN BACK BOXES. WHERE SHOWN AS PART OF BRANCH CIRCUIT, PROVIDE CONDUCTORS WITHIN CONDUIT TO SOURCE. REFER TO FLOOR PLANS FOR BRANCH

CIRCUIT DESIGNATION.

TYPE 'LIGHT', CEILING PROCEDURE LIGHT:

PROVIDE 20A 120V BRANCH CIRCUIT TO OWNER FURNISHED CEILING PROCEDURE LIGHT AT APPROXIMATE

LOCATION INDICATED. COORDINATE FINAL CONNECTION WITH FINAL EQUIPMENT SELECTION.

TYPE 'SHADE', MOTORIZED SHADE:

PROVIDE 20A 120V BRANCH CIRCUIT TO JUNCTION BOX, MOUNTED IN ACCESSIBLE LOCATION ABOVE CEILING WITHIN 5'0" OF MOTORIZED SHADE MOTOR LOCATION. PROVIDE CONNECTION TO MANUFACTURER FURNISHED JUNCTION BOX LEADS AND MOTOR LEADS. PROVIDE ONE (1) 1" CONDUIT FROM MOTOR LOCATION TO ACCESSIBLE CEILING LOCATION FOR LOW VOLTAGE CONNECTION TO MOTORIZED SHADE CONTROLLER AND ANY APPLICABLE SPLITTERS. MOUNT SPLITTERS IN LOCATION PER MANUFACTURER REQUIREMENTS. COORDINATE WITH FINAL

EQUIPMENT SELECTION.

TYPE 'EWC-1', ELECTRIC WATER COOLER, REMOTE CHILLER:

PROVIDE 20A 120V BRANCH CIRCUIT TO REMOTE CHILLER, MOUNTED ABOVE FINISHED CEILING. PROVIDE WITH

TOGGLE SWITCH DISCONNECTING MEANS. COORDINATE WITH FINAL EQUIPMENT SELECTION.

JUNCTION BOX - WALL PROVIDE JUNCTION BOX AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH JUNCTION BOX TYPE. REFER TO PLANS FOR JUNCTION BOX DESIGNATION. PROVIDE ONE (1) 4" SQUARE, 2-1/8" DEEP JUNCTION BOX WITH SINGLE GANG TRIM RING AND BLANK WALL PLATE WITH ONE (1) 1” CONDUIT TO ABOVE FINISHED CEILING WHERE NOT INDICATED OTHERWISE. WHERE SHOWN ADJACENT TO RECEPTACLES ON FLOOR PLANS, PROVIDE MAXIMUM 12” BETWEEN BACK BOXES. WHERE SHOWN AS PART OF BRANCH CIRCUIT, PROVIDE CONDUCTORS

WITHIN CONDUIT TO SOURCE INDICATED ON FLOOR PLANS.

RECEPTACLE - NEMA PROVIDE ONE (1) 4" SQUARE, 2 1/8" DEEP JUNCTION BOX WITH 1 GANG TRIM RING. PROVIDE CONDUIT TO ELECTRICAL SOURCE SIZED AS INDICATED BELOW. REFER TO FLOOR PLANS FOR ELECTRICAL SOURCE AND NEMA

DESIGNATION. PROVIDE DEVICE, FEEDER, AND CIRCUIT BREAKER AS LISTED BELOW:

•NEMA 5-30 & L5-30: 2-#10, #10 GND IN 3/4" CONDUIT; 30A, 1 POLE CIRCUIT BREAKER

•NEMA 21-20 & L21-20: 4-#12, #12 GND IN 3/4" CONDUIT; 20A, 3 POLE CIRCUIT BREAKER

RECEPTACLE - NEMA OUTLET -

CEILING MOUNTED

PROVIDE ONE (1) 4" SQUARE, 2 1/8" DEEP JUNCTION BOX WITH 1 GANG TRIM RING. PROVIDE CONDUIT TO ELECTRICAL SOURCE SIZED AS INDICATED BELOW. REFER TO FLOOR PLANS FOR ELECTRICAL SOURCE AND NEMA

DESIGNATION. PROVIDE DEVICE, FEEDER, AND CIRCUIT BREAKER AS LISTED BELOW:

•NEMA 5-30 & L5-30: 2-#10, #10 GND IN 3/4" CONDUIT; 30A, 1 POLE CIRCUIT BREAKER

•NEMA 21-20 & L21-20: 4-#12, #12 GND IN 3/4" CONDUIT; 20A, 3 POLE CIRCUIT BREAKER

FIRE ALARM SYMBOLS

PLAN SYMBOL NAME

DETECTOR - SYSTEM HEAT -

CEILING

DETECTOR - SYSTEM SMOKE -

CEILING

FIRE ALARM REMOTE

ANNUNCIATOR

HORN AND STROBE

COMBINATION - WALL

MANUAL PULL STATION

STROBE - WALL

FIRE ALARM SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

FIRE ALARM CONTROL PANEL -

SURFACE MOUNT

CIRCUIT CONTROL PANEL TO 20A 120V BRANCH CIRCUIT IN ASSOCIATED [LIFE SAFETY] [EMERGENCY] [NORMAL] BRANCH PANEL (INSTALL CIRCUIT BREAKER LOCK ON BRANCH BREAKER). REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATION. PROVIDE SYSTEM SMOKE DETECTOR AT CEILING WITHIN 5 FEET OF PANEL (UNLESS SHOWN WITH ROOM DETECTION COVERAGE ON PLAN). PROVIDE TWO (2) VOICE CONNECTIONS TO FACP.

FIRE SUPPRESSION CONTROL

PANEL

CIRCUIT FIRE SUPPRESSION CONTROL PANEL TO 20A 120V BRANCH CIRCUIT IN ASSOCIATED [LIFE SAFETY] [EMERGENCY] [NORMAL] BRANCH PANEL (INSTALL CIRCUIT BREAKER LOCK ON BRANCH BREAKER). REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATION. PROVIDE FIRE ALARM CONTROL MODULE, VALVE TAMPER SWITCH, AND FIRE ALARM MONITORING MODULE FOR FIRE ALARM SYSTEM MONITORING. PROVIDE TWO (2) VOICE

CONNECTIONS TO FSCP.

SMOKE DAMPER OR FIRE/SMOKE

DAMPER

CIRCUIT FIRE AND FIRE/SMOKE DAMPERS PROVIDED BY MECHANICAL CONTRACTOR TO 20A 120V BRANCH CIRCUITS IN ASSOCIATED [LIFE SAFETY] [EMERGENCY] [NORMAL] BRANCH PANEL (INSTALL CIRCUIT BREAKER LOCK ON BRANCH BREAKERS). EACH BRANCH CIRCUIT SHALL SERVE A MAXIMUM OF 20 DAMPERS. PROVIDE INDIVIDUAL CIRCUITS FOR EACH AIR HANDLING UNIT ZONE. REFER TO MECHANICAL PLANS FOR ASSOCIATED ZONES. CONTROL EACH DAMPER INDIVIDUALLY WITH ADDRESSABLE CONTROL MODULES FROM FIRE ALARM SYSTEM. LABEL EACH RELAY WITH THE NAME OF THE AIR HANDLING UNIT SERVING THE SMOKE ZONE AND WITH THE WORDS "SMOKE DAMPER CONTROL". [PROVIDE SYSTEM DUCT SMOKE DETECTOR IN ACCESSIBLE LOCATION WITHIN 5 FEET OF THE DAMPER TO CONTROL DAMPER. DUCT DETECTOR MAY BE OMITTED WHERE THE DAMPER IS INSTALLED IN A CORRIDOR WALL OR CEILING AND IS CONTROLLED BY AN AREA SMOKE DETECTION SYSTEM INSTALLED IN THE CORRIDOR.][CONTROL DAMPER BY ACTIVATION OF ANY SMOKE DETECTOR WITHIN AIR HANDLING UNIT ZONE.] PROVIDE REMOTE STATUS INDICATOR AND TEST STATION FOR DETECTOR AND COORDINATE ASSOCIATED MOUNTING LOCATION WITH OWNER. REFER TO [LIGHTING] [LOW VOLTAGE] FLOOR PLANS FOR DAMPER

LOCATIONS.

LIGHTING DEVICE SYMBOLS

PLAN SYMBOL NAME

LIGHT SWITCH

OCCUPANCY SENSOR - CEILING

OCCUPANCY SENSOR - WALL

SWITCH - 3 WAY

SWITCH - VACANCY SENSOR

LIGHTING DEVICE SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

PUSH BUTTON DEVICE SHALL PROVIDE ON/OFF CONTROL OF ZONES INDICATED. SUBSCRIPT LETTER(S) CORRESPOND TO LIGHTING ZONE(S) IN AREA. PROVIDE DEVICE CAPABLE OF SWITCHING QUANTITY OF ZONES INDICATED. WHERE NO ZONES ARE INDICATED, PROVIDE CONTROL OF SINGLE ZONE. MUST BE CAPABLE OF 3 AND 4 WAY SWITCHING FROM

ADDITIONAL DEVICES.

TYPE ‘D’ – DEVICE SHALL PROVIDE ON/OFF AND MIN/MAX DIMMING CONTROL OF ZONES INDICATED. SUBSCRIPT LETTER(S) CORRESPOND TO LIGHTING ZONE(S) IN AREA, PROVIDE DEVICE CAPABLE OF SWITCHING QUANTITY OF ZONES INDICATED. MUST BE CAPABLE OF 3 AND 4 WAY SWITCHING FROM ADDITIONAL DEVICES.

TYPE ‘SC#’ – DEVICE SHALL PROVIDE SCENE CONTROL CAPABLE OF CONTROLLING ALL ZONES IN ROOM BY PRESET SCENES. NUMBER INDICATES QUANTITY OF SCENES TO BE SELECTED AT THIS LOCATION. SEE LIGHTING SCENE

SCHEDULE FOR DESCRIPTION OF DESIRED SCENES.

TYPE ‘GFX’ – DEVICE SHALL INCLUDE GRAPHICAL TOUCH SCREEN TO PROVIDE SCENE CONTROL AS WELL AS

ON/OFF AND MIN/MAX DIMMING CONTROL OF ALL ZONES IN ROOM.

ELECTRICAL MISC SYMBOLS

PLAN SYMBOL NAME

BRANCH CIRCUIT CONCEALED IN

CEILING OR WALL

BRANCH CIRCUIT CONCEALED IN

FLOOR OR BELOW GRADE

CLEARANCE SPACE

CONDUIT BREAK

CONDUIT DOWN

CONDUIT STUB-OUT

CONDUIT UP

HOMERUN TO PANEL

G = GFCI CIRCUIT

(PART) = PARTIAL CIRCUIT

SWITCHED RECEPTACLE

ELECTRICAL MISC SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

CABLE TRAY PROVIDE CABLE TRAY AT LOCATIONS INDICATED ON PLANS. REFER TO FLOOR PLANS FOR TYPE DESIGNATION.

COORDINATE MOUNTING WITH OTHER TRADES AND REQUIREMENTS IN SPECIFICATION.

TYPE 'WIDTH x DEPTH", WIRE BASKET CABLE TRAY:

PROVIDE CABLE TRAY IN DIMENSION INDICATED ON FLOOR PLANS.

TYPE 'WIDTH LADDER', LADDER CABLE TRAY:

PROVIDE CABLE TRAY IN DIMENSION INDICATED ON FLOOR PLANS.

LIGHTING CONTROL TAG REFER TO LIGHTING CONTROL SCHEDULE FOR ADDITIONAL INFORMATION.

ELECTRICAL EQUIPMENT

SYMBOLS

PLAN SYMBOL NAME

AUTOMATIC TRANSFER SWITCH

BUS DUCT

DISTRIBUTION PANEL

ENCLOSED CIRCUIT BREAKER -

SURFACE

ENCLOSED DISCONNECT

SWITCH - FUSED

PANELBOARD - SURFACE

SWITCHBOARD

TRANSFORMER - DRY TYPE

UPS CABINET

UPS TRANSFORMER

UTILITY PAD MOUNT SWITCH

ONE LINE SYMBOL

PLAN SYMBOL NAME

AUTOMATIC TRANSFER SWITCH

CONTINUATION

DIGITAL METER

ENCLOSED CIRCUIT BREAKER

GENERATOR

GENERATOR CONNECTION BOX

GROUND BAR

GROUNDING ELECTRODE

KEY INTERLOCK

PANEL BOARD

SURGE PROTECTIVE DEVICE

SWITCHBOARD/SWITCHGEAR

TRANSFORMER

UPS PANEL

UTILITY METER

ELECTRICAL EQUIPMENT SYMBOL LEGEND

PLAN SYMBOL NAME DESCRIPTION

DIRECT DIGITAL CONTROL

SYSTEM CONTROL PANEL

CIRCUIT CONTROL PANEL TO 20A 120V BRANCH CIRCUIT IN LOCAL [EQUIPMENT] [NORMAL] BRANCH PANEL OF THE ASSOCIATED CONSTRUCTION PHASE. REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATIONS. COORDINATE CONNECTION REQUIREMENTS WITH FINAL EQUIPMENT SELECTION AND PROVIDED NEMA 5-20 RECEPTACLE OR HARD-WIRED CONNECTION TO CABINET AS REQUIRED. PROVIDE ONE (1) NETWORK DATA

CABLE FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM.

Revisions: Date:

UP

TR

IT/

ELECTRICAL

RM

IT RM

STORAGE

1A

TREATMENT RM

TR

E-001.G

E-001.G

SSCU-132

SSCU-236

1-ATS-TR-GWA

1-MSB-GWA

1-CR-TR-DP

1-TR-DP

1-FP-GEN-GWA

E

NEW 112.5KVA TRANSFORMER

E-001.G

1-TR-GA

1-CR-TR-GA

I4E I4E

I4E

L21-20 (TYP.)

1-TR-GA-1,3,5

1-CR-TR-GA-1,3,5

1-TR-GA-2

1-CR-TR-GA-2 1-CR-TR-GA-4

4 3

I4E1-TR-GA-7,9,11

1-CR-TR-GA-7,9,11

1-TR-GA-13,15,17

1-CR-TR-GA-13,15,17

1-TR-GA-4,6,8

1-CR-TR-GA-6,8,10

1-TR-GA-10,12,14

1-CR-TR-GA-12,14,16

3 3 3 34 4 4 4

1-MSB-GWA

(E)

INSTALL TWO NEW 400/3 CIRCUIT

BREAKERS TO SERVE NEW

PANELS.

1-TR-DP

1-ATS-TR-GWA

400A

112.5KVA

480/3 TO

120/208/3

1-FP-GEN

-GWA

(E)

INSTALL A NEW 175/3 CIRCUIT

BREAKER IN EXISTING PANEL TO

SERVE NEW TRANSFORMER.

1-CR-TR-GA

1-CR-TR-DP

1-CR-TR-2A 1-CR-TR-3A 1-CR-TR-4A1-CR-TR-1A

1-CR-TR-DP

INSTALL TWO NEW 400/3 CIRCUIT

BREAKER PANEL WITH 5-100/3

CIRCUIT BREAKERS.

1-TR-GA 1-TR-2A 1-TR-3A 1-TR-4A1-TR-1A

INSTALL A NEW 400/3 MAIN

BREAKER PANEL WITH 5-100/3

CIRCUIT BREAKERS.

10N 10N

10N

10N 10N

40N

40N

112T

40N

10N 10N 10N

10N

10N

400A FSD

40N

1-FP-GEN-GWA

1-TR-DP

1-CR-TR-DP

1-MSB-GWA

1-ATS-TR-GWA

NEW 112.5KVA

TRANSFORMER

E

E

REMARKS: (AUTOMATIC TRANSFER SWITCH SCHEDULE)

1. NOT USED.

GENERAL NOTES: (AUTOMATIC TRANSFER SWITCH SCHEDULE)

A. REFER TO DEFINITIONS BELOW FOR CLARIFICATIONS OF REQUIREMENTS.

B. "MIN 3 CYCLE WCR" AND "MIN 30 CYCLE WCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT BASED ON PRELIMINARY

DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC AT THE DURATION INDICATED. RATING SHALL BE ADJUSTED IF REQUIRED

BASED ON FINAL SCC CALCULATION.

C. "PRIORITY" - GENERATOR LOADING AND ATS LOAD SHEDDING SHALL BE SETUP BASED ON THE FOLLOWING PRIORITY LEVELS WITH THE LOWEST NUMBER BEING THE FIRST LOAD STEP AND THE HIGHEST NUMBER BEING THE LAST LOAD STEP. QUANTITY OF LOAD STEPS SHALL BE MINIMUM REQUIRED FOR SYSTEM CONFIGURATION. ADDITIONAL LOAD

STEPS MAY BE ADDED TO ASSIST WITH GENERATOR STABILITY.

a. "1" - POWER MUST BE TRANSFERRED TO LOAD FROM GENERATOR WITHIN 10 SECONDS. LOAD CANNOT BE SHED.

b. "2,3,4, ETC." - LOAD CAN BE SHED. HIGHEST VALUES SHALL BE SHED FIRST.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Specialized Engineering Solutions 1300 Baxter Street, Suite 355 Charlotte, NC 28204

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254 www.atriaxgroup.com

Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com

03/08/2024

A u to d e s k D o c s /2

.0

V A

T u s c a lo o s a

E H

R M

I n fr a s tr u c tu re U p g ra d e s /2

.0

V

A E

H R

M T u s c a lo o s a

R

B

.r v t

-0

-2

:0

:1

E-001.G

BUILDING 1 GROUND LEVEL -

ELECTRICAL

EHRM INFRASTRUCTURE UPGRADES

TUSCALOOSA VAMC, TUSCALOOSA, AL.

679-20-104

03/08/2024 CGH MJJ

SHEET NOTES:

1. REMOVE ALL EXISTING DEVICES AND WIRING BACK TO SOURCE. VISIT SITE TO DETERMINE

FULL EXTENT OF DEMOLITION.

2. NOT USED.

3. PROVIDE RECEPTACLE FOR BUS B. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.

4. PROVIDE RECEPTACLE FOR BUS A. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.

5. PROVIDE UNISTRUT SUPPORTS FOR NEW PANEL IN CENTER OF ROOM.

NTS1

OVERALL FLOOR PLAN

GROUND LEVEL -

ELECTRICAL

1/4" = 1'-0"3

DEMOLITION FLOOR

PLAN GROUND FLOOR -

ELECTRICAL

1/4" = 1'-0"4

NEW FLOOR PLAN

GROUND FLOOR -

ELECTRICAL

PLAN TRUENO SCALE5

BUILDING 1 -

ELECTRICAL ONE-LINE

B. BUS A PANEL.

C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.

A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).

GENERAL REMARKS:

CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'

- PROVIDE CIRCUIT BREAKER WITH RED MARKING

OPTIONS:

10 A

SPARE CAPACITY:

10 %

FEEDER AVAILABLE:

EQUIPMENT AMPS: 100 A

CONSIDER 125% DEMAND: 40394 A

DEMAND CURRENT: 90 A

REC 900 VA 100.00% 900 VA DEMAND LOAD: 32315 VA

PWR-C 25000 VA 125.00% 31250 VA CONNECTED CURRENT: 72 A

LTG 132 VA 125.00% 165 VA CONNECTED LOAD: 26032 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 77 A 71 A 69 A

TOTAL LOAD: 9233 VA 8465 VA 8333 VA

23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24

21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22

19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20

17 1667 VA -- 1 -- -- SPACE 18

15 1667 VA 1667 VA 16

REC - IT RACK TR-1 20 A 3

1667 VA 1667 VA 14

11 1667 VA 1667 VA

3 20 A REC - IT RACK TR-1

9 1667 VA 1667 VA 10

REC - IT RACK TR-1 20 A 3

1667 VA 1667 VA 8

5 1667 VA 1667 VA

3 20 A REC - IT RACK TR-1

3 1667 VA 132 VA 1 20 A LTG - TR-1 4

REC - IT RACK TR-1 20 A 3

1667 VA 900 VA 1 20 A REC - TR-1 2

CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT

NEMA ENCLOSURE: NEMA 1

MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24

SERVICE RATED: No INTEGRAL SPD: Yes SECTIONS: 1

BRANCH: EMERGENCY WIRES: 4 MCB OPTIONS:

SUPPLY FROM: 1-CR-TR-DP PHASES: 3 MCB/MLO RATING: 100 A

LOCATION: TR 1 VOLTS: 208/120 WYE MAINS TYPE: MLO

PANEL: 1-CR-TR-GA

B. BUS B PANEL.

C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.

A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).

GENERAL REMARKS:

CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'

- PROVIDE CIRCUIT BREAKER WITH RED MARKING

OPTIONS:

11 A

SPARE CAPACITY:

10 %

FEEDER AVAILABLE:

EQUIPMENT AMPS: 100 A

CONSIDER 125% DEMAND: 40188 A

DEMAND CURRENT: 89 A

DEMAND LOAD: 32150 VA

REC 900 VA 100.00% 900 VA CONNECTED CURRENT: 72 A

PWR-C 25000 VA 125.00% 31250 VA CONNECTED LOAD: 25900 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 77 A 69 A 69 A

TOTAL LOAD: 9233 VA 8333 VA 8333 VA

23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24

21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22

19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20

17 1667 VA -- 1 -- -- SPACE 18

15 1667 VA 0 VA 1 20 A -- SPARE 16

REC - IT RACK TR-1 20 A 3

1667 VA 1667 VA 14

11 1667 VA 1667 VA 12

9 1667 VA 1667 VA

3 20 A REC - IT RACK TR-1

REC - IT RACK TR-1 20 A 3

1667 VA 1667 VA 8

5 1667 VA 1667 VA 6

3 1667 VA 1667 VA

3 20 A REC - IT RACK TR-1

REC - IT RACK TR-1 20 A 3

1667 VA 900 VA 1 20 A REC - TR-1 2

CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT

NEMA ENCLOSURE: NEMA 1

MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24

SERVICE RATED: No INTEGRAL SPD: Yes SECTIONS: 1

BRANCH: NORMAL WIRES: 4 MCB OPTIONS:

SUPPLY FROM: 1-TR-DP PHASES: 3 MCB/MLO RATING: 100 A

LOCATION: TR 1 VOLTS: 208/120 WYE MAINS TYPE: MLO

PANEL: 1-TR-GA

GENERAL NOTES:

A. REFER TO TELECOM, HVAC, AND FIRE PROTECTION DRAWINGS. COORDINATE LOCATION

ON NEW LIGHTING FIXTURES, NEW ELECTRICAL PANELS, AND NEW CABLE TRAY MOUNTED

RECEPTACLES WITH OTHER DISCIPLINES.

EQUIPMENT CONNECTION SCHEDULE

MARK DESCRIPTION FLA MCA MOCP VOLTS PHASE POLES

LOAD

[VA]

CONTROL

TYPE

DISCONNECT

BY

DISCONNECT

TYPE FEEDER PANEL

CIRCUIT

NUMBER SCCR GEN REMARKS

SSAH-132 SPLIT SYSTEM CONDENSING UNIT 0 0 0 208 1 2 0 INT - - (3X) (30A) 2-#10 CU, #10 CU GND - 3/4"C. 1-CR-TR-1A 7,9 5 Yes 2

SSAH-236 SPLIT SYSTEM CONDENSING UNIT 0 0 0 208 1 2 0 INT - - (3X) (30A) 2-#10 CU, #10 CU GND - 3/4"C. 1-CR-TR-2A 7,9 5 Yes 2

SSAH-301 SPLIT SYSTEM CONDENSING UNIT 0 0 0 208 1 2 0 INT - - (3X) (30A) 2-#10 CU, #10 CU GND - 3/4"C. 1-CR-TR-3A 7,9 5 Yes 2

SSAH-TBD SPLIT SYSTEM CONDENSING UNIT 0 0 0 208 1 2 0 1-CR-TR-4A 7,9 0 Yes

SSCU-132 SPLIT SYSTEM CONDENSING UNIT 20 25 30 208 1 2 3330 INT ELECTRICAL 30A/2P/208V

FUSED

DISCONNECT

SWITCH

(3X) (30A) 2-#10 CU, #10 CU GND - 3/4"C. 1-CR-TR-1A 7,9 5 Yes 1

SSCU-236 SPLIT SYSTEM CONDENSING UNIT 20 25 30 208 1 2 3330 INT ELECTRICAL 30A/2P/208V

FUSED

DISCONNECT

SWITCH

(3X) (30A) 2-#10 CU, #10 CU GND - 3/4"C. 1-CR-TR-2A 7,9 5 Yes 1

SSCU-301 SPLIT SYSTEM CONDENSING UNIT 20 25 30 208 1 2 3330 INT ELECTRICAL 30A/2P/208V

FUSED

DISCONNECT

SWITCH

(3X) (30A) 2-#10 CU, #10 CU GND - 3/4"C. 1-CR-TR-3A 7,9 5 Yes 1

SSCU-TBD SPLIT SYSTEM CONDENSING UNIT 0.4 1 0 208 1 2 1960 1-CR-TR-4A 7,9 0 Yes

UH-TBD UNIT HEATER 12.5 0 0 120 1 1 1500 INT MANUFACTURER - (2X) (20A) 2-#12 CU, #12 CU GND - 3/4"C. 1-TR-4A 4 0 No

REMARKS: (EQUIPMENT CONNECTION SCHEDULE)

1. CONTROLS BETWEEN INDOOR AND OUTDOOR UNITS - INCLUDE CONTROL WIRING IN CONDUIT BETWEEN INDOOR AND OUTDOOR UNIT PER MANUFACTURERS REQUIREMENTS.

2. "CONTROL TYPE" - PROVIDE CONTROL AND CONNECTIONS "INT" - CONTROLS ARE MANUFACTURED INTEGRAL TO THE EQUIPMENT (SELF-CONTAINED).

FEEDER SCHEDULE - COPPER

FEEDER NOMINAL SIZE WIRE AND CONDUIT

10N 100 A 4-#1 CU, #8 CU GND - 2" C.

17 175 A 3-#2/0 CU, #6 CU GND - 2" C.

40N 400 A 4-#4/0 CU, #3 CU GND - 2-1/2" C. (2 SETS)

112T 350 A 4-600 KCMIL CU, #1/0 CU GND - 4"C.

AUTOMATIC TRANSFER SWITCH SCHEDULE

NAME AMPS VOLTAGE PHASE

NUMBER

OF POLES

BYPASS

ISOLATION

TRANSITION

TYPE

MIN. 3 CYCLE

WCR

MIN. 30 CYCLE

WCR PRIORITY REMARKS

1-ATS-TR-GWA 400 A 208 V 3 3 Yes CLOSED 1

1/4" = 1'-0"2

ENLARGED PLAN

GROUND LEVEL

ELECTRICAL ROOM

TR

STAIRWELL

OFFICE

OFFICE

CORRIDOR

TR

E-001.1

E-001.1

I4E I4E

L21-20 (TYP.)

1-TR-1A

SSAH-132

1-CR-TR-1A

1-CR-TR-1A-2

1-TR-1A-2

1-CR-TR-1A-4

3 4

1-TR-1A-1,3,5

1-CR-TR-1A-1,3,5

3 4

1-TR-1A-4,6,8

1-CR-TR-1A-6,8,10

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Specialized Engineering Solutions 1300 Baxter Street, Suite 355 Charlotte, NC 28204

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254 www.atriaxgroup.com

Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com

03/08/2024

A u to d e s k D o c s /2

.0

V A

T u s c a lo o s a

E H

R M

I n fr a s tr u c tu re U p g ra d e s /2

.0

V

A E

H R

M T u s c a lo o s a

R

B

.r v t

-0

-2

:0

:1

E-001.1

BUILDING 1 LEVEL 01 -

ELECTRICAL

EHRM INFRASTRUCTURE UPGRADES

TUSCALOOSA VAMC, TUSCALOOSA, AL.

679-20-104

03/08/2024 CGH MJJ

NTS1

OVERALL FLOOR PLAN

LEVEL 01 - ELECTRICAL

1/4" = 1'-0"2

DEMOLITION FLOOR

PLAN LEVEL 01 -

ELECTRICAL

1/4" = 1'-0"3

NEW FLOOR PLAN LEVEL

01 - ELECTRICAL

B. BUS B PANEL.

C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.

A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).

GENERAL REMARKS:

CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'

- PROVIDE CIRCUIT BREAKER WITH RED MARKING

OPTIONS:

63 A

SPARE CAPACITY:

63 %

FEEDER AVAILABLE:

EQUIPMENT AMPS: 100 A

CONSIDER 125% DEMAND: 16525 A

DEMAND CURRENT: 37 A

DEMAND LOAD: 13220 VA

REC 720 VA 100.00% 720 VA CONNECTED CURRENT: 30 A

PWR-C 10000 VA 125.00% 12500 VA CONNECTED LOAD: 10720 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 34 A 28 A 28 A

TOTAL LOAD: 4053 VA 3333 VA 3333 VA

23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24

21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22

19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20

17 SPACE -- -- 1 -- -- 1 -- -- SPACE 18

15 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 16

13 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 14

11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12

9 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 10

7 SPARE -- 20 A 1 0 VA 1667 VA 8

5 1667 VA 1667 VA 6

3 1667 VA 1667 VA

3 20 A REC - IT RACK TR-132

REC - IT RACK TR-132 20 A 3

1667 VA 720 VA 1 20 A REC - TR-132 2

CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT

NEMA ENCLOSURE: NEMA 1

MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24

SERVICE RATED: No INTEGRAL SPD: Yes SECTIONS: 1

BRANCH: NORMAL WIRES: 4 MCB OPTIONS:

SUPPLY FROM: 1-TR-DP PHASES: 3 MCB/MLO RATING: 100 A

LOCATION: TR 132 VOLTS: 208/120 WYE MAINS TYPE: MLO

PANEL: 1-TR-1A

B. BUS A PANEL.

C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.

A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).

GENERAL REMARKS:

CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'

- PROVIDE CIRCUIT BREAKER WITH RED MARKING

OPTIONS:

52 A

SPARE CAPACITY:

51 %

FEEDER AVAILABLE:

EQUIPMENT AMPS: 100 A

CONSIDER 125% DEMAND: 21831 A

MEQ-C 3330 VA 125.00% 4163 VA DEMAND CURRENT: 48 A

REC 720 VA 100.00% 720 VA DEMAND LOAD: 17465 VA

PWR-C 10000 VA 125.00% 12500 VA CONNECTED CURRENT: 39 A

LTG 66 VA 125.00% 83 VA CONNECTED LOAD: 14116 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 50 A 44 A 28 A

TOTAL LOAD: 5718 VA 5064 VA 3333 VA

23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24

21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22

19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20

17 SPACE -- -- 1 -- -- 1 -- -- SPACE 18

15 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 16

13 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 14

11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12

9 1665 VA 1667 VA 10

SSCU-132/SSAH-132 30 A 2

1665 VA 1667 VA 8

5 1667 VA 1667 VA

3 20 A REC - IT RACK TR-132

3 1667 VA 66 VA 1 20 A LTG - TR-132 4

REC - IT RACK TR-132 20 A 3

1667 VA 720 VA 1 20 A REC - TR-132 2

CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT

NEMA ENCLOSURE: NEMA 1

MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24

SERVICE RATED: No INTEGRAL SPD: Yes SECTIONS: 1

BRANCH: EMERGENCY WIRES: 4 MCB OPTIONS:

SUPPLY FROM: 1-CR-TR-DP PHASES: 3 MCB/MLO RATING: 100 A

LOCATION: TR 132 VOLTS: 208/120 WYE MAINS TYPE: MLO

PANEL: 1-CR-TR-1A

SHEET NOTES:

1. REMOVE ALL EXISTING DEVICES AND WIRING BACK TO SOURCE. VISIT SITE TO DETERMINE

FULL EXTENT OF DEMOLITION.

2. REFER TO EQUIPMENT CONNECTION SCHEDULE.

3. PROVIDE RECEPTACLE FOR BUS B. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.

4. PROVIDE RECEPTACLE FOR BUS A. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.

GENERAL NOTES:

A. REFER TO TELECOM, HVAC, AND FIRE PROTECTION DRAWINGS. COORDINATE LOCATION

ON NEW LIGHTING FIXTURES, NEW ELECTRICAL PANELS, AND NEW CABLE TRAY MOUNTED

RECEPTACLES WITH OTHER DISCIPLINES.

PLAN TRUE

LIMITS OF DEMOLITION

UP DN

TR

PROJECTION RM

235A

STAIRWELL

OFFICE

CONFERENCE

TR

E-001.2

E-001.2

1-CR-TR-2A

1-TR-2A

I4EI4E

L21-20 (TYP.)

SSAH-236

1-CR-TR-2A-2

1-TR-2A-2

1-CR-TR-2A-4

1-CR-TR-2A-1,3,5

1-TR-2A-1,3,5

1-CR-TR-2A-6,8,10

1-TR-2A-4,6,8

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Specialized Engineering Solutions 1300 Baxter Street, Suite 355 Charlotte, NC 28204

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254 www.atriaxgroup.com

Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com

03/08/2024

A u to d e s k D o c s /2

.0

V A

T u s c a lo o s a

E H

R M

I n fr a s tr u c tu re U p g ra d e s /2

.0

V

A E

H R

M T u s c a lo o s a

R

B

.r v t

-0

-2

:0

:1

E-001.2

BUILDING 1 LEVEL 02 -

ELECTRICAL

EHRM INFRASTRUCTURE UPGRADES

TUSCALOOSA VAMC, TUSCALOOSA, AL.

679-20-104

03/08/2024 CGH MJJ

NTS1

OVERALL FLOOR PLAN

LEVEL 02 - ELECTRICAL

1/4" = 1'-0"2

DEMOLITION FLOOR

PLAN LEVEL 02 -

ELECTRICAL

1/4" = 1'-0"3

NEW FLOOR PLAN LEVEL

02 - ELECTRICAL

B. BUS B PANEL.

C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.

A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).

GENERAL REMARKS:

CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'

- PROVIDE CIRCUIT BREAKER WITH RED MARKING

OPTIONS:

63 A

SPARE CAPACITY:

63 %

FEEDER AVAILABLE:

EQUIPMENT AMPS: 100 A

CONSIDER 125% DEMAND: 16525 A

DEMAND CURRENT: 37 A

DEMAND LOAD: 13220 VA

REC 720 VA 100.00% 720 VA CONNECTED CURRENT: 30 A

PWR-C 10000 VA 125.00% 12500 VA CONNECTED LOAD: 10720 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 34 A 28 A 28 A

TOTAL LOAD: 4053 VA 3333 VA 3333 VA

23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24

21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22

19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20

17 SPACE -- -- 1 -- -- 1 -- -- SPACE 18

15 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 16

13 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 14

11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12

9 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 10

7 SPARE -- 20 A 1 0 VA 1667 VA 8

5 1667 VA 1667 VA 6

3 1667 VA 1667 VA

3 20 A REC - IT RACK TR-236

REC - IT RACK TR-236 20 A 3

1667 VA 720 VA 1 20 A REC - TR-236 2

CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT

NEMA ENCLOSURE: NEMA 1

MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24

SERVICE RATED: No INTEGRAL SPD: Yes SECTIONS: 1

BRANCH: NORMAL WIRES: 4 MCB OPTIONS:

SUPPLY FROM: 1-TR-DP PHASES: 3 MCB/MLO RATING: 100 A

LOCATION: TR 236 VOLTS: 208/120 WYE MAINS TYPE: MLO

PANEL: 1-TR-2A

B. BUS A PANEL.

C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.

A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).

GENERAL REMARKS:

CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'

- PROVIDE CIRCUIT BREAKER WITH RED MARKING

OPTIONS:

52 A

SPARE CAPACITY:

51 %

FEEDER AVAILABLE:

EQUIPMENT AMPS: 100 A

CONSIDER 125% DEMAND: 21831 A

MEQ-C 3330 VA 125.00% 4163 VA DEMAND CURRENT: 48 A

REC 720 VA 100.00% 720 VA DEMAND LOAD: 17465 VA

PWR-C 10000 VA 125.00% 12500 VA CONNECTED CURRENT: 39 A

LTG 66 VA 125.00% 83 VA CONNECTED LOAD: 14116 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 50 A 44 A 28 A

TOTAL LOAD: 5718 VA 5064 VA 3333 VA

23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24

21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22

19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20

17 SPACE -- -- 1 -- -- 1 -- -- SPACE 18

15 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 16

13 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 14

11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12

9 1665 VA 1667 VA 10

SSCU-236/SSAH-236 30 A 2

1665 VA 1667 VA 8

5 1667 VA 1667 VA

3 20 A REC - IT RACK TR-236

3 1667 VA 66 VA 1 20 A LTG - TR-236 4

REC - IT RACK TR-236 20 A 3

1667 VA 720 VA 1 20 A REC - TR-236 2

CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT

NEMA ENCLOSURE: NEMA 1

MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24

SERVICE RATED: No INTEGRAL SPD: Yes SECTIONS: 1

BRANCH: EMERGENCY WIRES: 4 MCB OPTIONS:

SUPPLY FROM: 1-CR-TR-DP PHASES: 3 MCB/MLO RATING: 100 A

LOCATION: TR 236 VOLTS: 208/120 WYE MAINS TYPE: MLO

PANEL: 1-CR-TR-2A

SHEET NOTES:

1. REMOVE ALL EXISTING DEVICES AND WIRING BACK TO SOURCE. VISIT SITE TO DETERMINE

FULL EXTENT OF DEMOLITION.

2. REFER TO EQUIPMENT CONNECTION SCHEDULE.

3. PROVIDE RECEPTACLE FOR BUS B. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.

4. PROVIDE RECEPTACLE FOR BUS A. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.

GENERAL NOTES:

A. REFER TO TELECOM, HVAC, AND FIRE PROTECTION DRAWINGS. COORDINATE LOCATION

ON NEW LIGHTING FIXTURES, NEW ELECTRICAL PANELS, AND NEW CABLE TRAY MOUNTED

RECEPTACLES WITH OTHER DISCIPLINES.

PLAN TRUE

PAY PHONE

UP

DN

301D

TR

HOUSE KEEPING

HOUSE KEEPING

PIPE CHASE

MALE

TOILET

307B

FP

TELEPHONE CLOSET

VESTIBULE

307A

FP

PIPE

CHASE

PIPE

CHASE

FP

TOILET

301A

FP

TELEPHONE CLOSET

OFFICE

COPY RM

OFFICE

PIPE CHASE

352A

OFFICE

OFFICE

FILE RM

MEDIA

COUNTER

OFFICE

301C

301B

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

EXAM RM

FILE RM

OFFICE

RECEPTION AREA

OFFICE

314A

OFFICE

OFFICE

STORAGE

OFFICE

ELECTRICAL CLOSET

OFFICE

OFFICE

BREAK RM

OFFICE

COPY RM

IT

CLOSET

OFFICE

OFFICE

COPY RM

OFFICE

OFFICE

OFFICE

IT

CLOSET

ELECTRICAL

OFFICE

STAIR WELL

ELEVATOR

P3

STORAGE

STORAGE

RESOURCE

LIBRARY

OFFICE

OFFICE

ELEVATOR

P-2

ELEVATOR

P-1

OFFICE

OFFICE

365A

STAIR WELL

FILE RM

OFFICE

OFFICE

OFFICE

STAIR WELL

CORRIDOR

CORRIDOR

FEMALE

TOILET

CORRIDOR

FEMALE

TOILET

MALE

TOILET

CORRIDOR

CORRIDOR

FEMALE TOILET

CORRIDOR

STAIRWELL

CORRIDOR

MEDICAL RM

QUIET RM

OFFICE

MEN

TOILET

OFFICE

365B

OFFICE

OFFICE

CLOSET

OFFICE

301D

TOILET

301A

MEDIA

COUNTER

OFFICE

301C

301B

301D

TR

TOILET

301A

MEDIA

COUNTER

OFFICE

301C

301B

E-001.3

E-001.3

LIMITS OF DEMOLITION

I4EI4E

1-CR-TR-3A

1-TR-3A

SSAH-301

L21-20 (TYP.)

1-CR-TR-3A-2

1-TR-3A-2

1-CR-TR-3A-4

1-CR-TR-3A-1,3,5

1-TR-3A-1,3,5

1-CR-TR-3A-6,8,10

1-TR-3A-4,6,8

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Specialized Engineering Solutions 1300 Baxter Street, Suite 355 Charlotte, NC 28204

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254 www.atriaxgroup.com

Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com

03/08/2024

A u to d e s k D o c s /2

.0

V A

T u s c a lo o s a

E H

R M

I n fr a s tr u c tu re U p g ra d e s /2

.0

V

A E

H R

M T u s c a lo o s a

R

B

.r v t

-0

-2

:0

:1

E-001.3

BUILDING 1 LEVEL 03 -

ELECTRICAL

EHRM INFRASTRUCTURE UPGRADES

TUSCALOOSA VAMC, TUSCALOOSA, AL.

679-20-104

03/08/2024 CGH MJJ

NTS1

OVERALL FLOOR PLAN

LEVEL 03 - ELECTRICAL

1/4" = 1'-0"2

DEMOLITION FLOOR

PLAN LEVEL 03 -

ELECTRICAL

1/4" = 1'-0"3

NEW FLOOR PLAN LEVEL

03 - ELECTRICAL

B. BUS B PANEL.

C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.

A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).

GENERAL REMARKS:

CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'

- PROVIDE CIRCUIT BREAKER WITH RED MARKING

OPTIONS:

63 A

SPARE CAPACITY:

63 %

FEEDER AVAILABLE:

EQUIPMENT AMPS: 100 A

CONSIDER 125% DEMAND: 16525 A

DEMAND CURRENT: 37 A

DEMAND LOAD: 13220 VA

REC 720 VA 100.00% 720 VA CONNECTED CURRENT: 30 A

PWR-C 10000 VA 125.00% 12500 VA CONNECTED LOAD: 10720 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 34 A 28 A 28 A

TOTAL LOAD: 4053 VA 3333 VA 3333 VA

23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24

21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22

19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20

17 SPACE -- -- 1 -- -- 1 -- -- SPACE 18

15 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 16

13 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 14

11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12

9 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 10

7 SPARE -- 20 A 1 0 VA 1667 VA 8

5 1667 VA 1667 VA 6

3 1667 VA 1667 VA

3 20 A REC - IT RACK TR-301D

REC - IT RACK TR-301D 20 A 3

1667 VA 720 VA 1 20 A REC - TR-301D 2

CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT

NEMA ENCLOSURE: NEMA 1

MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24

SERVICE RATED: No INTEGRAL SPD: Yes SECTIONS: 1

BRANCH: NORMAL WIRES: 4 MCB OPTIONS:

SUPPLY FROM: 1-TR-DP PHASES: 3 MCB/MLO RATING: 100 A

LOCATION: TR VOLTS: 208/120 WYE MAINS TYPE: MLO

PANEL: 1-TR-3A

B. BUS A PANEL.

C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.

A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).

GENERAL REMARKS:

CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'

- PROVIDE CIRCUIT BREAKER WITH RED MARKING

OPTIONS:

52 A

SPARE CAPACITY:

52 %

FEEDER AVAILABLE:

EQUIPMENT AMPS: 100 A

CONSIDER 125% DEMAND: 21606 A

MEQ-C 3330 VA 125.00% 4163 VA DEMAND CURRENT: 48 A

REC 540 VA 100.00% 540 VA DEMAND LOAD: 17285 VA

PWR-C 10000 VA 125.00% 12500 VA CONNECTED CURRENT: 39 A

LTG 66 VA 125.00% 83 VA CONNECTED LOAD: 13936 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 48 A 44 A 28 A

TOTAL LOAD: 5538 VA 5064 VA 3333 VA

23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24

21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22

19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20

17 SPACE -- -- 1 -- -- 1 -- -- SPACE 18

15 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 16

13 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 14

11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12

9 1665 VA 1667 VA 10

SSCU-301/SSAH-301 30 A 2

1665 VA 1667 VA 8

5 1667 VA 1667 VA

3 20 A REC - IT RACK TR-301D

3 1667 VA 66 VA 1 20 A LTG - TR-301D 4

REC - IT RACK TR-301D 20 A 3

1667 VA 540 VA 1 20 A REC - TR-301D 2

CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT

NEMA ENCLOSURE: NEMA 1

MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24

SERVICE RATED: No INTEGRAL…