Attachment 2 - EHRM RTA Drawings_Electrical.pdf
PDF 28 MB Posted
- Solicitation number
- 36C77625R0025
About this file
This file is an electrical drawing set for the EHRM Infrastructure Upgrades project at the Tuscaloosa VA Medical Center (VAMC). The detailed electrical drawings, prepared by Atriax, PLLC and Wiley|Wilson, document comprehensive electrical system modifications across multiple buildings, including new electrical panels, transformers, power distribution systems, and associated infrastructure upgrades.
Key technical details include installing new 208V/120V transformers, electrical panels (emergency and normal branches), automatic transfer switches, and power busways. The project involves electrical work in Buildings 1, 2, 3, 4, 5, 6, 61, 135, 137, 138, 39, 40, 41, 146, 147, 149, and 151, with specific focus on telecommunications rooms, electrical rooms, and infrastructure connections. The electrical design incorporates sophisticated elements like network receptacles, fire alarm systems, lighting controls, and equipment connections, with careful attention to mounting heights, grounding requirements, and compliance with electrical codes and VA specifications.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N
10 12
HAGLER LANE
Fire Station
PL#5
PL#4
PL#3
PL#
PL#9
PL#8
PL#7
PL#6
Hospice
LOOP ROAD
McAbee Center
Property Line
P ro pe rty
L in e
PL#2
TEMP. PL
LIBERTY PARK
33A
Project Locations
D
UN ITED STATES OF AM
ER
IC
A
SR
IA
FF
AS
NARE
TEVFOTNEMTRAPE
679-20-104EHRM INFRASTRUCTURE
UPGRADES
www.atriaxgroup.com
Atriax, pllc 703 Main Avenue SW PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 NC Architectural License No.: 51254 03/08/2024
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Chief Engineer
Revisions: Date:
Specialized Engineering Solutions 1300 Baxter Street, Suite 355 Charlotte, NC 28204
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
TUSCALOOSA VAMC, TUSCALOOSA, AL.
COVER SHEET
GI001
MM/TRTG
REVIEWER'S SIGNATURES
TUSCALOOSA VA MEDICAL CENTER
TUSCALOOSA, AL 35404
PROJECT # 679-20-104
EHRM INFRASTRUCTURE UPGRADESELECTRICAL
INDEX OF DRAWINGS
ELECTRICAL
GI002
MM/TRTG
679-20-104EHRM INFRASTRUCTURE
UPGRADES
www.atriaxgroup.com
Atriax, pllc 703 Main Avenue SW PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 NC Architectural License No.: 51254 03/08/2024
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Chief Engineer
Revisions: Date:
Specialized Engineering Solutions 1300 Baxter Street, Suite 355 Charlotte, NC 28204
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
TUSCALOOSA VAMC, TUSCALOOSA, AL.
INDEX OF DRAWINGS
ELECTRICAL ABBREVIATIONS
ABBREVIATION DESCRIPTION
REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.
MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)
AMPERE
AMPERE FRAME
ABOVE FINISHED FLOOR
ALUMINUM
AMPERE TRIP
CEILING
CIRCUIT BREAKER
COLOR TEMP CONTROL
COPPER
DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)
DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)
EXISTING
ELECTRICALLY OPERATED
ENERGY REDUCING MAINTENANCE SWITCH
FUSE
FULL LOAD AMPS
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT ALARM
GROUND FAULT PROTECTION
HORSEPOWER
KILOAMPERE INTERRUPTING CAPACITY
KILOVOLT AMPERE
KILOWATT
MAXIMUM
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MINIMUM
MAIN LUGS ONLY
MANUALLY OPERATED
NORMALLY CLOSED
NON-FUSED
NOT IN CONTRACT
NORMALLY OPEN
POLES
PARTIAL
RELOCATE
SHORT CIRCUIT CURRENT RATING
SURGE PROTECTIVE DEVICE
SHUNT TRIP
TYPICAL
UNLESS NOTED OTHERWISE
VOICE
WALL PHONE
WIRE
WEATHER RESISTANT
TRANSFORMER
ZONE SELECTIVE INTERLOCKING
A
AF
AFF
AL
AT
C
CB
CCT
CU
D
D
E
EO
ERMS
F
FLA
G, GFCI
GFA
GFP
HP
KAIC
KVA
KW
MAX
MCA
MCB
MIN
MLO
MO
NC
NF
NIC
NO
P
PART
R
SCCR
SPD
ST
TYP
UNO
V
W
W
WR
XFMR
ZSI
A. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75' SHALL UTILIZE #10 AWG CONDUCTORS.
RECEPTACLE BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 150' SHALL UTILIZE #8 AWG
CONDUCTORS.
B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE
SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.
C. NEW ROOF MOUNTED EQUIPMENT SHALL BE BONDED TO EXISTING BUILDING LIGHTNING PROTECTION SYSTEM IF ONE EXISTS. PROVIDE AIR TERMINALS ON TOP OF EQUIPMENT AND BOND TO EXISTING SYSTEM PER NFPA 780 AND UL 96A REQUIREMENTS. PROVIDE UL INSPECTION AND/OR LPI SYSTEM INSPECTION AS REQUIRED TO OBTAIN UL MASTER LABEL RECERTIFICATION, UL MASTER LABEL AND/OR LPI SYSTEM
CERTIFICATE.
D. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL
COST TO THE OWNER.
E. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR
INSTALLED DEVICES.
F. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS
ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND
PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.
G. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND ALL
NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE SAME
INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.
H. ALL CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, INCLUDING LIGHTING AND WALL RECEPTACLES, SHALL BE MECHANICALLY PROTECTED PER NEC 517.31(C)(3). NON-FLEXIBLE RACEWAY SHALL BE USED FOR CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, EXCEPT THAT THE FINAL CONNECTION TO VIBRATING EQUIPMENT OR LIGHT FIXTURES IF THE TOTAL LENGTH OF FLEXIBLE RACEWAY IS 6' OR LESS ACROSS THE
ENTIRE CIRCUIT LENGTH.
I. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN
CABLING.
(GENERAL NOTES SHALL APPLY TO ALL SHEETS)
ELECTRICAL GENERAL NOTES:
A. LIGHTING CONTROL DEVICES ARE INDICATED WITHOUT CONNECTION TO FIXTURE(S) BEING CONTROLLED.
WITHIN EACH AREA, CONNECT CONTROL DEVICE TO SERVE LIGHT FIXTURE(S) LOCATED WITHIN SAME AREA. WHERE LIGHT FIXTURES ARE INDICATED WITH A SUBSCRIPT LETTER IDENTIFYING INDIVIDUAL LIGHTING CONTROL ZONES, CONTROL DEVICE SERVING AREA WITH MATCHING SUBSCRIPT SHALL
CONTROL CORRESPONDING LIGHT FIXTURES.
B. SWITCHES SERVING UNDERCABINET TASK LIGHTING SHALL MATCH RECEPTACLE HEIGHT ABOVE COUNTER.
C. LIGHTING CONTROL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS.
CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH
ARCHITECTURAL INTERIOR ELEVATIONS. WHERE DEVICE MOUNTING HEIGHTS ARE NOT INDICATED PER ARCHITECT, MOUNT DEVICES AT HEIGHT INDICATED IN ELECTRICAL PROJECT SPECIFICATIONS.
D. CONTRACTOR SHALL COORDINATE ALL LIGHTING CONTROL DEVICE ROUGH-IN LOCATIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS TO ASSURE COMPATIBILITY WITH FINISHES SPECIFIED ON THE ARCHITECTURAL DRAWINGS. COORDINATE ROUTING OF ALL ELECTRICAL BRANCH CIRCUITS AND CONDUIT WITH OTHER TRADES TO ALLOW FOR SERVICE AND MAINTENANCE AND TO MINIMIZE THE USE OF ACCESS PANELS. WHERE ACCESS PANELS CANNOT BE AVOIDED, WORK TO INSTALL PANELS IN LOCATIONS
ACCEPTABLE TO ARCHITECT.
E. FIXTURES DESIGNATED ['24'][,] ['LS'][,] AND EXIT LIGHTS SHALL BE SERVED FROM A [COMMON] 20A [120V] [277V] [LIFE SAFETY BRANCH CIRCUIT (WITHIN PANEL ___)][CENTRAL BATTERY INVERTER BRANCH CIRCUIT].
[FIXTURES DESIGNATED '24' AND] EXIT LIGHTS SHALL BE ILLUMINATED 24 HOURS. [FIXTURES DESIGNATED 'LS' SHALL BE SWITCHED BY CONTROLS INDICATED. PROVIDE EMERGENCY LIGHTING CONTROL RELAYS PER SPECIFICATIONS FOR EMERGENCY LIGHTING OVERRIDE. REFER TO MANUFACTURER'S WIRING DIAGRAMS FOR INSTALLATION INSTRUCTIONS.] [BRANCH CIRCUITS SHALL BE DISTRIBUTED AS FOLLOWS:
• FLOOR A, AREA A (- LIFE SAFETY PANEL-CIRCUIT NUMBER)
• REPEAT AS NEEDED]
F. REFER TO DETAILS, SCHEDULES, AND SYMBOL LEGENDS FOR ADDITIONAL REQUIREMENTS.
(LIGHTING GENERAL NOTES SHALL APPLY TO ALL SHEETS)
LIGHTING GENERAL NOTES:
A. ELECTRICAL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS.
CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH
ARCHITECTURAL INTERIOR ELEVATIONS. WHERE DEVICE MOUNTING HEIGHTS ARE NOT INDICATED PER ARCHITECT, MOUNT DEVICES AT HEIGHT INDICATED IN ELECTRICAL PROJECT SPECIFICATIONS.
B. CONTRACTOR SHALL COORDINATE ALL ELECTRICAL DEVICE ROUGH-IN LOCATIONS AND ELEVATIONS WITH
ARCHITECTURAL DRAWINGS TO ASSURE COMPATIBILITY WITH FINISHES SPECIFIED ON THE
ARCHITECTURAL DRAWINGS. ROUTE ALL ELECTRICAL BRANCH CIRCUITS AND CONDUITS SPECIFIED, TO COORDINATE WITH OTHER TRADES AND TO ALLOW FOR SERVICE AND MAINTENANCE AND TO MINIMIZE THE USE OF ACCESS PANELS. WHERE ACCESS PANELS CANNOT BE AVOIDED, ARRANGE WORK TO INSTALL
PANELS IN LOCATIONS ACCEPTABLE TO ARCHITECT.
C. REFER TO DETAILS, SCHEDULES, AND SYMBOL LEGENDS FOR ADDITIONAL REQUIREMENTS.
D. REDUNDANT GROUNDING METHODS REQUIRED FOR PATIENT CARE AREAS. REFER TO NEC FOR
REQUIREMENTS AND TO PROJECT SPECIFICATIONS FOR ACCEPTABLE METHODS/APPLICATIONS.
E. GFCI TYPE RECEPTACLES ARE NOTED AS SUCH ON THE PLANS FOR PRICING PURPOSES. HOWEVER, CONTRACTOR SHALL BE RESPONSIBLE TO ENSURE ALL RECEPTACLES INSTALLED WHERE A 6' CORD
LENGTH COULD REACH THE EDGE OF A SINK HAVE GFCI PROTECTION.
(POWER GENERAL NOTES SHALL APPLY TO ALL SHEETS)
POWER GENERAL NOTES:
A. THE INTENT OF THE DEMOLITION DRAWINGS IS TO DEFINE THE SCOPE OF ELECTRICAL DEMOLITION WORK.
EXISTING ELECTRICAL SYSTEMS (DEVICES, FIXTURES, EQUIPMENT, WIRING, AND RACEWAYS INCLUDING DATA/COMMUNICATION SYSTEMS) WITHIN LIMITS OF DEMOLITION AND NOT SERVING ADJACENT AREAS, SHALL BE REMOVED UNLESS OTHERWISE INDICATED. RE-SUPPORT EXISTING CONDUITS AND CABLES THAT
MUST REMAIN.
OR
THE INTENT OF THE DEMOLITION
DRAWINGS IS TO DEFINE THE SCOPE OF ELECTRICAL DEMOLITION WORK. PROVIDE DEMOLITION FOR
ITEMS AS SHOWN.
B. ITEMS INDICATED WITH A SUBSCRIPT 'E' SHALL BE EXISTING TO REMAIN (E-EXISTING). ITEMS INDICATED WITH A SUBSCRIPT 'D' OR SHOWN DASHED SHALL BE REMOVED (D-DEMOLITION). ITEMS INDICATED WITH A SUBSCRIPT 'R' SHALL BE REMOVED, STORED, AND REINSTALLED PER NEW WORK (R-RELOCATION).
C. THESE DRAWINGS DO NOT IDENTIFY EACH INDIVIDUAL ITEM TO BE REMOVED. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ITEMS WHICH MUST BE REMOVED TO FACILITATE NEW CONSTRUCTION.
SEE ARCHITECTURAL PLANS FOR EXACT LIMITS OF DEMOLITION AND CONSTRUCTION. THESE PLANS ARE BASED ON PAST PROJECT DRAWINGS AND SITE OBSERVATIONS. THE DRAWINGS ARE PROVIDED TO THE CONTRACTOR AS AN AID IN DETERMINING THE EXTENT OF WORK REQUIRED FOR DEMOLITION AND TO PROVIDE GENERAL INFORMATION ABOUT EXISTING SYSTEMS. THESE DRAWINGS MAY NOT BE ACCURATE IN ALL AREAS. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING
CONDITIONS AND IS ENCOURAGED TO REVIEW FACILITY DRAWINGS PRIOR TO THE BID DATE.
D. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL ITEMS REMOVED. IF OWNER REFUSES SALVAGE, CONTRACTOR IS RESPONSIBLE FOR DISPOSAL.
E. WHERE EXISTING WALLS ARE TO BE REMOVED, ALL ASSOCIATED ELECTRICAL EQUIPMENT SHALL BE REMOVED. DISCONNECT POWER SO THAT DEVICES AND EQUIPMENT MAY BE REMOVED WITH WALLS. SEE
ARCHITECTURAL DRAWINGS FOR WALLS TO BE REMOVED. ABANDON CONCEALED CONDUITS WHERE
WALLS ARE NOT REMOVED. CONCEALED CONDUITS MAY BE REUSED WHERE AVAILABLE. WHERE EXISTING CIRCUITING/CABLING IS TO BE DEMOLISHED AND NOT REUSED, REMOVE CONDUCTORS AND ASSOCIATED ACCESSIBLE RACEWAYS/CONDUIT BACK TO THE SOURCE. WHERE EXISTING ELECTRICAL CONDUITS SERVING CIRCUITS TO BE DEMOLISHED ARE EMBEDDED IN CONCRETE FLOORS OR WALLS, CONDUITS MAY BE ABANDONED IN PLACE. EXISTING CONDUCTORS SHALL BE REMOVED BACK TO SOURCE AND CONDUITS SHALL BE CUT AT SURFACE OF CONCRETE AND FILLED. EXISTING BACK BOXES AND CONDUITS REMAINING FROM DEVICES BEING REMOVED MAY BE UTILIZED FOR NEW DEVICES WHERE LOCATIONS PERMIT.
REMOVE AND PATCH WHERE BOXES ARE NOT REUSED.
F. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL ELECTRICAL DEMOLITION ITEMS. DISCONNECT AND REMOVE ELECTRICAL DEVICES, EQUIPMENT AND ASSOCIATED WIRING AS REQUIRED TO ACCOMMODATE NEW WORK. IF THE CONTRACTOR IS UNCLEAR REGARDING A SPECIFIC ITEM TO REMAIN OR BE REMOVED, THE CONTRACTOR SHALL SEEK CLARIFICATION FROM THE ARCHITECT.
G. SYSTEMS SERVING ADJACENT AREAS AND ITEMS THAT REMAIN SHALL BE MAINTAINED AT ALL TIMES.
MODIFY SYSTEMS AS REQUIRED THROUGHOUT CONSTRUCTION TO MAINTAIN CONTINUITY OF SERVICE. DO
NOT INTERRUPT SERVICE WITHOUT OWNER'S PRIOR WRITTEN APPROVAL. LIMIT DURATION OF
INTERRUPTION ONLY TO THE TIME NECESSARY FOR DISCONNECTION AND IMMEDIATE RECONNECTION.
INTERRUPTION TO SERVICE DEEMED BY OWNER AS ESSENTIAL MAY REQUIRE PREMIUM TIME AND SHALL BE INCLUDED WITH THE BID. EXTREME CARE SHALL BE TAKEN BY THE CONTRACTOR TO IDENTIFY EXISTING SYSTEM COMPONENTS ASSOCIATED WITH THESE SERVICES. APPROPRIATE METHODS OF MARKING THESE SHALL OCCUR TO ELIMINATE THE POSSIBILITY OF ACCIDENTAL INTERRUPTION. FOR CONDUIT AND CABLING THAT CAN REMAIN, PROVIDE SUPPORT AS REQUIRED. RELOCATE EXISTING JUNCTION BOXES THAT
BECOME INACCESSIBLE DUE TO NEW WORK.
H. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY POWER AND
LIGHTING AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED.
I. PROTECT EXISTING ELECTRICAL EQUIPMENT THAT REMAINS. IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY, QUALITY, AND FUNCTIONALITY.
J. PATCH AND REPAIR OPENINGS IN EXISTING WALLS AND FLOORS RESULTANT FROM SPECIFIED ELECTRICAL DEMOLITION. PATCH SHALL MATCH EXISTING CONSTRUCTION, FIRE RATING, AND FINISH. SEE
ARCHITECTURAL SPECIFICATIONS FOR MEANS AND METHODS.
K. THIS PROJECT WILL BE PHASED. SEE PROJECT MANUAL AND ARCHITECTURAL PLANS FOR DETAILS.
SYSTEM SERVICES TO AREAS NOT IN THE CURRENT PHASE OF CONSTRUCTION SHALL BE MAINTAINED AT
ALL TIMES.
L. WHERE DEMOLITION OF EQUIPMENT INVOLVES REMOVAL OF EQUIPMENT LOCATED ON CONCRETE HOUSEKEEPING PADS, PADS SHALL ALSO BE REMOVED AND FLOOR/GRADE SHALL BE FINISHED TO MATCH
ADJACENT SURFACE.
M. ALL UNLABELED ELECTRICAL DEVICES [WITH CIRCUITRY OR DEVICES MODIFIED DURING CONSTRUCTION] [THAT EXIST IN ALL ROOMS WHERE THERE IS WORK WITHIN SCOPE] SHALL BE CIRCUIT TRACED AS NEEDED
WITH A LABEL PROVIDED.
(ELECTRICAL DEMOLITION NOTES APPLY TO ALL ELECTRICAL DEMOLITION PLANS AND
ALL ELECTRICAL DEMOLITION WORK)
ELECTRICAL DEMOLITION GENERAL NOTES:
(BLANKET DEMO)
(SELECTIVE DEMO)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Specialized Engineering Solutions 1300 Baxter Street, Suite 355 Charlotte, NC 28204
Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 NC Architectural License No.: 51254 www.atriaxgroup.com
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
03/08/2024
A u to d e s k D o c s /2
.0
V A
T u s c a lo o s a E
H R
M I n fr a s tr u c tu re U p g ra d e s /2
.0
V A
T u s c a lo o s a
E H
R M
I n fr U p g ra d e s
B X
X X
S
E S
.r v t
/0
/2
:1
:1
E-000
ELECTRICAL SYMBOLS AND
ABBREVIATIONS
EHRM INFRASTRUCTURE UPGRADES
TUSCALOOSA VAMC, TUSCALOOSA, AL.
679-20-104
03/08/2024 CGH MJJ
ELECTRICAL FIXTURE
SYMBOLS
PLAN SYMBOL NAME
RECEPTACLE - DOUBLE DUPLEX
- CONV
RECEPTACLE - DUPLEX - CONV
RECEPTACLE - DUPLEX - CONV -
GFCI
RECEPTACLE - DUPLEX -
EMERGENCY (RED) - CONV
ELECTRICAL FIXTURE SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
ELECTRICAL GROUND BAR PROVIDE LENGTH AS REQUIRED TO ACCOMMODATE TERMINATIONS, MINIMUM 20" IN LENGTH. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
JUNCTION BOX - CEILING GENERAL:
PROVIDE JUNCTION BOX AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH JUNCTION BOX TYPE. REFER TO FLOOR PLANS FOR JUNCTION BOX DESIGNATION. PROVIDE ONE (1) 4" SQUARE, 2-1/8" DEEP JUNCTION BOX WITH SINGLE GANG TRIM RING AND BLANK WALL PLATE WITH ONE (1) 1” CONDUIT TO ABOVE ACCESSIBLE CEILING WHERE NOT INSTALLED IN ACCESSIBLE CEILING. WHERE SHOWN ADJACENT TO CEILING RECEPTACLES ON FLOOR PLANS, PROVIDE MAXIMUM 8” BETWEEN BACK BOXES. WHERE SHOWN AS PART OF BRANCH CIRCUIT, PROVIDE CONDUCTORS WITHIN CONDUIT TO SOURCE. REFER TO FLOOR PLANS FOR BRANCH
CIRCUIT DESIGNATION.
TYPE 'LIGHT', CEILING PROCEDURE LIGHT:
PROVIDE 20A 120V BRANCH CIRCUIT TO OWNER FURNISHED CEILING PROCEDURE LIGHT AT APPROXIMATE
LOCATION INDICATED. COORDINATE FINAL CONNECTION WITH FINAL EQUIPMENT SELECTION.
TYPE 'SHADE', MOTORIZED SHADE:
PROVIDE 20A 120V BRANCH CIRCUIT TO JUNCTION BOX, MOUNTED IN ACCESSIBLE LOCATION ABOVE CEILING WITHIN 5'0" OF MOTORIZED SHADE MOTOR LOCATION. PROVIDE CONNECTION TO MANUFACTURER FURNISHED JUNCTION BOX LEADS AND MOTOR LEADS. PROVIDE ONE (1) 1" CONDUIT FROM MOTOR LOCATION TO ACCESSIBLE CEILING LOCATION FOR LOW VOLTAGE CONNECTION TO MOTORIZED SHADE CONTROLLER AND ANY APPLICABLE SPLITTERS. MOUNT SPLITTERS IN LOCATION PER MANUFACTURER REQUIREMENTS. COORDINATE WITH FINAL
EQUIPMENT SELECTION.
TYPE 'EWC-1', ELECTRIC WATER COOLER, REMOTE CHILLER:
PROVIDE 20A 120V BRANCH CIRCUIT TO REMOTE CHILLER, MOUNTED ABOVE FINISHED CEILING. PROVIDE WITH
TOGGLE SWITCH DISCONNECTING MEANS. COORDINATE WITH FINAL EQUIPMENT SELECTION.
JUNCTION BOX - WALL PROVIDE JUNCTION BOX AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH JUNCTION BOX TYPE. REFER TO PLANS FOR JUNCTION BOX DESIGNATION. PROVIDE ONE (1) 4" SQUARE, 2-1/8" DEEP JUNCTION BOX WITH SINGLE GANG TRIM RING AND BLANK WALL PLATE WITH ONE (1) 1” CONDUIT TO ABOVE FINISHED CEILING WHERE NOT INDICATED OTHERWISE. WHERE SHOWN ADJACENT TO RECEPTACLES ON FLOOR PLANS, PROVIDE MAXIMUM 12” BETWEEN BACK BOXES. WHERE SHOWN AS PART OF BRANCH CIRCUIT, PROVIDE CONDUCTORS
WITHIN CONDUIT TO SOURCE INDICATED ON FLOOR PLANS.
RECEPTACLE - NEMA PROVIDE ONE (1) 4" SQUARE, 2 1/8" DEEP JUNCTION BOX WITH 1 GANG TRIM RING. PROVIDE CONDUIT TO ELECTRICAL SOURCE SIZED AS INDICATED BELOW. REFER TO FLOOR PLANS FOR ELECTRICAL SOURCE AND NEMA
DESIGNATION. PROVIDE DEVICE, FEEDER, AND CIRCUIT BREAKER AS LISTED BELOW:
•NEMA 5-30 & L5-30: 2-#10, #10 GND IN 3/4" CONDUIT; 30A, 1 POLE CIRCUIT BREAKER
•NEMA 21-20 & L21-20: 4-#12, #12 GND IN 3/4" CONDUIT; 20A, 3 POLE CIRCUIT BREAKER
RECEPTACLE - NEMA OUTLET -
CEILING MOUNTED
PROVIDE ONE (1) 4" SQUARE, 2 1/8" DEEP JUNCTION BOX WITH 1 GANG TRIM RING. PROVIDE CONDUIT TO ELECTRICAL SOURCE SIZED AS INDICATED BELOW. REFER TO FLOOR PLANS FOR ELECTRICAL SOURCE AND NEMA
DESIGNATION. PROVIDE DEVICE, FEEDER, AND CIRCUIT BREAKER AS LISTED BELOW:
•NEMA 5-30 & L5-30: 2-#10, #10 GND IN 3/4" CONDUIT; 30A, 1 POLE CIRCUIT BREAKER
•NEMA 21-20 & L21-20: 4-#12, #12 GND IN 3/4" CONDUIT; 20A, 3 POLE CIRCUIT BREAKER
FIRE ALARM SYMBOLS
PLAN SYMBOL NAME
DETECTOR - SYSTEM HEAT -
CEILING
DETECTOR - SYSTEM SMOKE -
CEILING
FIRE ALARM REMOTE
ANNUNCIATOR
HORN AND STROBE
COMBINATION - WALL
MANUAL PULL STATION
STROBE - WALL
FIRE ALARM SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
FIRE ALARM CONTROL PANEL -
SURFACE MOUNT
CIRCUIT CONTROL PANEL TO 20A 120V BRANCH CIRCUIT IN ASSOCIATED [LIFE SAFETY] [EMERGENCY] [NORMAL] BRANCH PANEL (INSTALL CIRCUIT BREAKER LOCK ON BRANCH BREAKER). REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATION. PROVIDE SYSTEM SMOKE DETECTOR AT CEILING WITHIN 5 FEET OF PANEL (UNLESS SHOWN WITH ROOM DETECTION COVERAGE ON PLAN). PROVIDE TWO (2) VOICE CONNECTIONS TO FACP.
FIRE SUPPRESSION CONTROL
PANEL
CIRCUIT FIRE SUPPRESSION CONTROL PANEL TO 20A 120V BRANCH CIRCUIT IN ASSOCIATED [LIFE SAFETY] [EMERGENCY] [NORMAL] BRANCH PANEL (INSTALL CIRCUIT BREAKER LOCK ON BRANCH BREAKER). REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATION. PROVIDE FIRE ALARM CONTROL MODULE, VALVE TAMPER SWITCH, AND FIRE ALARM MONITORING MODULE FOR FIRE ALARM SYSTEM MONITORING. PROVIDE TWO (2) VOICE
CONNECTIONS TO FSCP.
SMOKE DAMPER OR FIRE/SMOKE
DAMPER
CIRCUIT FIRE AND FIRE/SMOKE DAMPERS PROVIDED BY MECHANICAL CONTRACTOR TO 20A 120V BRANCH CIRCUITS IN ASSOCIATED [LIFE SAFETY] [EMERGENCY] [NORMAL] BRANCH PANEL (INSTALL CIRCUIT BREAKER LOCK ON BRANCH BREAKERS). EACH BRANCH CIRCUIT SHALL SERVE A MAXIMUM OF 20 DAMPERS. PROVIDE INDIVIDUAL CIRCUITS FOR EACH AIR HANDLING UNIT ZONE. REFER TO MECHANICAL PLANS FOR ASSOCIATED ZONES. CONTROL EACH DAMPER INDIVIDUALLY WITH ADDRESSABLE CONTROL MODULES FROM FIRE ALARM SYSTEM. LABEL EACH RELAY WITH THE NAME OF THE AIR HANDLING UNIT SERVING THE SMOKE ZONE AND WITH THE WORDS "SMOKE DAMPER CONTROL". [PROVIDE SYSTEM DUCT SMOKE DETECTOR IN ACCESSIBLE LOCATION WITHIN 5 FEET OF THE DAMPER TO CONTROL DAMPER. DUCT DETECTOR MAY BE OMITTED WHERE THE DAMPER IS INSTALLED IN A CORRIDOR WALL OR CEILING AND IS CONTROLLED BY AN AREA SMOKE DETECTION SYSTEM INSTALLED IN THE CORRIDOR.][CONTROL DAMPER BY ACTIVATION OF ANY SMOKE DETECTOR WITHIN AIR HANDLING UNIT ZONE.] PROVIDE REMOTE STATUS INDICATOR AND TEST STATION FOR DETECTOR AND COORDINATE ASSOCIATED MOUNTING LOCATION WITH OWNER. REFER TO [LIGHTING] [LOW VOLTAGE] FLOOR PLANS FOR DAMPER
LOCATIONS.
LIGHTING DEVICE SYMBOLS
PLAN SYMBOL NAME
LIGHT SWITCH
OCCUPANCY SENSOR - CEILING
OCCUPANCY SENSOR - WALL
SWITCH - 3 WAY
SWITCH - VACANCY SENSOR
LIGHTING DEVICE SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
PUSH BUTTON DEVICE SHALL PROVIDE ON/OFF CONTROL OF ZONES INDICATED. SUBSCRIPT LETTER(S) CORRESPOND TO LIGHTING ZONE(S) IN AREA. PROVIDE DEVICE CAPABLE OF SWITCHING QUANTITY OF ZONES INDICATED. WHERE NO ZONES ARE INDICATED, PROVIDE CONTROL OF SINGLE ZONE. MUST BE CAPABLE OF 3 AND 4 WAY SWITCHING FROM
ADDITIONAL DEVICES.
TYPE ‘D’ – DEVICE SHALL PROVIDE ON/OFF AND MIN/MAX DIMMING CONTROL OF ZONES INDICATED. SUBSCRIPT LETTER(S) CORRESPOND TO LIGHTING ZONE(S) IN AREA, PROVIDE DEVICE CAPABLE OF SWITCHING QUANTITY OF ZONES INDICATED. MUST BE CAPABLE OF 3 AND 4 WAY SWITCHING FROM ADDITIONAL DEVICES.
TYPE ‘SC#’ – DEVICE SHALL PROVIDE SCENE CONTROL CAPABLE OF CONTROLLING ALL ZONES IN ROOM BY PRESET SCENES. NUMBER INDICATES QUANTITY OF SCENES TO BE SELECTED AT THIS LOCATION. SEE LIGHTING SCENE
SCHEDULE FOR DESCRIPTION OF DESIRED SCENES.
TYPE ‘GFX’ – DEVICE SHALL INCLUDE GRAPHICAL TOUCH SCREEN TO PROVIDE SCENE CONTROL AS WELL AS
ON/OFF AND MIN/MAX DIMMING CONTROL OF ALL ZONES IN ROOM.
ELECTRICAL MISC SYMBOLS
PLAN SYMBOL NAME
BRANCH CIRCUIT CONCEALED IN
CEILING OR WALL
BRANCH CIRCUIT CONCEALED IN
FLOOR OR BELOW GRADE
CLEARANCE SPACE
CONDUIT BREAK
CONDUIT DOWN
CONDUIT STUB-OUT
CONDUIT UP
HOMERUN TO PANEL
G = GFCI CIRCUIT
(PART) = PARTIAL CIRCUIT
SWITCHED RECEPTACLE
ELECTRICAL MISC SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
CABLE TRAY PROVIDE CABLE TRAY AT LOCATIONS INDICATED ON PLANS. REFER TO FLOOR PLANS FOR TYPE DESIGNATION.
COORDINATE MOUNTING WITH OTHER TRADES AND REQUIREMENTS IN SPECIFICATION.
TYPE 'WIDTH x DEPTH", WIRE BASKET CABLE TRAY:
PROVIDE CABLE TRAY IN DIMENSION INDICATED ON FLOOR PLANS.
TYPE 'WIDTH LADDER', LADDER CABLE TRAY:
PROVIDE CABLE TRAY IN DIMENSION INDICATED ON FLOOR PLANS.
LIGHTING CONTROL TAG REFER TO LIGHTING CONTROL SCHEDULE FOR ADDITIONAL INFORMATION.
ELECTRICAL EQUIPMENT
SYMBOLS
PLAN SYMBOL NAME
AUTOMATIC TRANSFER SWITCH
BUS DUCT
DISTRIBUTION PANEL
ENCLOSED CIRCUIT BREAKER -
SURFACE
ENCLOSED DISCONNECT
SWITCH - FUSED
PANELBOARD - SURFACE
SWITCHBOARD
TRANSFORMER - DRY TYPE
UPS CABINET
UPS TRANSFORMER
UTILITY PAD MOUNT SWITCH
ONE LINE SYMBOL
PLAN SYMBOL NAME
AUTOMATIC TRANSFER SWITCH
CONTINUATION
DIGITAL METER
ENCLOSED CIRCUIT BREAKER
GENERATOR
GENERATOR CONNECTION BOX
GROUND BAR
GROUNDING ELECTRODE
KEY INTERLOCK
PANEL BOARD
SURGE PROTECTIVE DEVICE
SWITCHBOARD/SWITCHGEAR
TRANSFORMER
UPS PANEL
UTILITY METER
ELECTRICAL EQUIPMENT SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
DIRECT DIGITAL CONTROL
SYSTEM CONTROL PANEL
CIRCUIT CONTROL PANEL TO 20A 120V BRANCH CIRCUIT IN LOCAL [EQUIPMENT] [NORMAL] BRANCH PANEL OF THE ASSOCIATED CONSTRUCTION PHASE. REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATIONS. COORDINATE CONNECTION REQUIREMENTS WITH FINAL EQUIPMENT SELECTION AND PROVIDED NEMA 5-20 RECEPTACLE OR HARD-WIRED CONNECTION TO CABINET AS REQUIRED. PROVIDE ONE (1) NETWORK DATA
CABLE FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM.
Revisions: Date:
UP
TR
IT/
ELECTRICAL
RM
IT RM
STORAGE
1A
TREATMENT RM
TR
E-001.G
E-001.G
SSCU-132
SSCU-236
1-ATS-TR-GWA
1-MSB-GWA
1-CR-TR-DP
1-TR-DP
1-FP-GEN-GWA
E
NEW 112.5KVA TRANSFORMER
E-001.G
1-TR-GA
1-CR-TR-GA
I4E I4E
I4E
L21-20 (TYP.)
1-TR-GA-1,3,5
1-CR-TR-GA-1,3,5
1-TR-GA-2
1-CR-TR-GA-2 1-CR-TR-GA-4
4 3
I4E1-TR-GA-7,9,11
1-CR-TR-GA-7,9,11
1-TR-GA-13,15,17
1-CR-TR-GA-13,15,17
1-TR-GA-4,6,8
1-CR-TR-GA-6,8,10
1-TR-GA-10,12,14
1-CR-TR-GA-12,14,16
3 3 3 34 4 4 4
1-MSB-GWA
(E)
INSTALL TWO NEW 400/3 CIRCUIT
BREAKERS TO SERVE NEW
PANELS.
1-TR-DP
1-ATS-TR-GWA
400A
112.5KVA
480/3 TO
120/208/3
1-FP-GEN
-GWA
(E)
INSTALL A NEW 175/3 CIRCUIT
BREAKER IN EXISTING PANEL TO
SERVE NEW TRANSFORMER.
1-CR-TR-GA
1-CR-TR-DP
1-CR-TR-2A 1-CR-TR-3A 1-CR-TR-4A1-CR-TR-1A
1-CR-TR-DP
INSTALL TWO NEW 400/3 CIRCUIT
BREAKER PANEL WITH 5-100/3
CIRCUIT BREAKERS.
1-TR-GA 1-TR-2A 1-TR-3A 1-TR-4A1-TR-1A
INSTALL A NEW 400/3 MAIN
BREAKER PANEL WITH 5-100/3
CIRCUIT BREAKERS.
10N 10N
10N
10N 10N
40N
40N
112T
40N
10N 10N 10N
10N
10N
400A FSD
40N
1-FP-GEN-GWA
1-TR-DP
1-CR-TR-DP
1-MSB-GWA
1-ATS-TR-GWA
NEW 112.5KVA
TRANSFORMER
E
E
REMARKS: (AUTOMATIC TRANSFER SWITCH SCHEDULE)
1. NOT USED.
GENERAL NOTES: (AUTOMATIC TRANSFER SWITCH SCHEDULE)
A. REFER TO DEFINITIONS BELOW FOR CLARIFICATIONS OF REQUIREMENTS.
B. "MIN 3 CYCLE WCR" AND "MIN 30 CYCLE WCR" - VALUE INDICATED IS AVAILABLE SHORT CIRCUIT CURRENT (SCC) IN KILOAMPS AT THE EQUIPMENT BASED ON PRELIMINARY
DESIGN PHASE CALCULATIONS. EQUIPMENT SCCR SHALL BE MINIMUM 120% OF THE AVAILABLE SCC AT THE DURATION INDICATED. RATING SHALL BE ADJUSTED IF REQUIRED
BASED ON FINAL SCC CALCULATION.
C. "PRIORITY" - GENERATOR LOADING AND ATS LOAD SHEDDING SHALL BE SETUP BASED ON THE FOLLOWING PRIORITY LEVELS WITH THE LOWEST NUMBER BEING THE FIRST LOAD STEP AND THE HIGHEST NUMBER BEING THE LAST LOAD STEP. QUANTITY OF LOAD STEPS SHALL BE MINIMUM REQUIRED FOR SYSTEM CONFIGURATION. ADDITIONAL LOAD
STEPS MAY BE ADDED TO ASSIST WITH GENERATOR STABILITY.
a. "1" - POWER MUST BE TRANSFERRED TO LOAD FROM GENERATOR WITHIN 10 SECONDS. LOAD CANNOT BE SHED.
b. "2,3,4, ETC." - LOAD CAN BE SHED. HIGHEST VALUES SHALL BE SHED FIRST.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Specialized Engineering Solutions 1300 Baxter Street, Suite 355 Charlotte, NC 28204
Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 NC Architectural License No.: 51254 www.atriaxgroup.com
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
03/08/2024
A u to d e s k D o c s /2
.0
V A
T u s c a lo o s a
E H
R M
I n fr a s tr u c tu re U p g ra d e s /2
.0
V
A E
H R
M T u s c a lo o s a
R
B
.r v t
-0
-2
:0
:1
E-001.G
BUILDING 1 GROUND LEVEL -
ELECTRICAL
EHRM INFRASTRUCTURE UPGRADES
TUSCALOOSA VAMC, TUSCALOOSA, AL.
679-20-104
03/08/2024 CGH MJJ
SHEET NOTES:
1. REMOVE ALL EXISTING DEVICES AND WIRING BACK TO SOURCE. VISIT SITE TO DETERMINE
FULL EXTENT OF DEMOLITION.
2. NOT USED.
3. PROVIDE RECEPTACLE FOR BUS B. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.
4. PROVIDE RECEPTACLE FOR BUS A. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.
5. PROVIDE UNISTRUT SUPPORTS FOR NEW PANEL IN CENTER OF ROOM.
NTS1
OVERALL FLOOR PLAN
GROUND LEVEL -
ELECTRICAL
1/4" = 1'-0"3
DEMOLITION FLOOR
PLAN GROUND FLOOR -
ELECTRICAL
1/4" = 1'-0"4
NEW FLOOR PLAN
GROUND FLOOR -
ELECTRICAL
PLAN TRUENO SCALE5
BUILDING 1 -
ELECTRICAL ONE-LINE
B. BUS A PANEL.
C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
10 A
SPARE CAPACITY:
10 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 40394 A
DEMAND CURRENT: 90 A
REC 900 VA 100.00% 900 VA DEMAND LOAD: 32315 VA
PWR-C 25000 VA 125.00% 31250 VA CONNECTED CURRENT: 72 A
LTG 132 VA 125.00% 165 VA CONNECTED LOAD: 26032 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 77 A 71 A 69 A
TOTAL LOAD: 9233 VA 8465 VA 8333 VA
23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24
21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22
19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20
17 1667 VA -- 1 -- -- SPACE 18
15 1667 VA 1667 VA 16
REC - IT RACK TR-1 20 A 3
1667 VA 1667 VA 14
11 1667 VA 1667 VA
3 20 A REC - IT RACK TR-1
9 1667 VA 1667 VA 10
REC - IT RACK TR-1 20 A 3
1667 VA 1667 VA 8
5 1667 VA 1667 VA
3 20 A REC - IT RACK TR-1
3 1667 VA 132 VA 1 20 A LTG - TR-1 4
REC - IT RACK TR-1 20 A 3
1667 VA 900 VA 1 20 A REC - TR-1 2
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: NEMA 1
MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24
SERVICE RATED: No INTEGRAL SPD: Yes SECTIONS: 1
BRANCH: EMERGENCY WIRES: 4 MCB OPTIONS:
SUPPLY FROM: 1-CR-TR-DP PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: TR 1 VOLTS: 208/120 WYE MAINS TYPE: MLO
PANEL: 1-CR-TR-GA
B. BUS B PANEL.
C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
11 A
SPARE CAPACITY:
10 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 40188 A
DEMAND CURRENT: 89 A
DEMAND LOAD: 32150 VA
REC 900 VA 100.00% 900 VA CONNECTED CURRENT: 72 A
PWR-C 25000 VA 125.00% 31250 VA CONNECTED LOAD: 25900 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 77 A 69 A 69 A
TOTAL LOAD: 9233 VA 8333 VA 8333 VA
23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24
21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22
19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20
17 1667 VA -- 1 -- -- SPACE 18
15 1667 VA 0 VA 1 20 A -- SPARE 16
REC - IT RACK TR-1 20 A 3
1667 VA 1667 VA 14
11 1667 VA 1667 VA 12
9 1667 VA 1667 VA
3 20 A REC - IT RACK TR-1
REC - IT RACK TR-1 20 A 3
1667 VA 1667 VA 8
5 1667 VA 1667 VA 6
3 1667 VA 1667 VA
3 20 A REC - IT RACK TR-1
REC - IT RACK TR-1 20 A 3
1667 VA 900 VA 1 20 A REC - TR-1 2
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: NEMA 1
MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24
SERVICE RATED: No INTEGRAL SPD: Yes SECTIONS: 1
BRANCH: NORMAL WIRES: 4 MCB OPTIONS:
SUPPLY FROM: 1-TR-DP PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: TR 1 VOLTS: 208/120 WYE MAINS TYPE: MLO
PANEL: 1-TR-GA
GENERAL NOTES:
A. REFER TO TELECOM, HVAC, AND FIRE PROTECTION DRAWINGS. COORDINATE LOCATION
ON NEW LIGHTING FIXTURES, NEW ELECTRICAL PANELS, AND NEW CABLE TRAY MOUNTED
RECEPTACLES WITH OTHER DISCIPLINES.
EQUIPMENT CONNECTION SCHEDULE
MARK DESCRIPTION FLA MCA MOCP VOLTS PHASE POLES
LOAD
[VA]
CONTROL
TYPE
DISCONNECT
BY
DISCONNECT
TYPE FEEDER PANEL
CIRCUIT
NUMBER SCCR GEN REMARKS
SSAH-132 SPLIT SYSTEM CONDENSING UNIT 0 0 0 208 1 2 0 INT - - (3X) (30A) 2-#10 CU, #10 CU GND - 3/4"C. 1-CR-TR-1A 7,9 5 Yes 2
SSAH-236 SPLIT SYSTEM CONDENSING UNIT 0 0 0 208 1 2 0 INT - - (3X) (30A) 2-#10 CU, #10 CU GND - 3/4"C. 1-CR-TR-2A 7,9 5 Yes 2
SSAH-301 SPLIT SYSTEM CONDENSING UNIT 0 0 0 208 1 2 0 INT - - (3X) (30A) 2-#10 CU, #10 CU GND - 3/4"C. 1-CR-TR-3A 7,9 5 Yes 2
SSAH-TBD SPLIT SYSTEM CONDENSING UNIT 0 0 0 208 1 2 0 1-CR-TR-4A 7,9 0 Yes
SSCU-132 SPLIT SYSTEM CONDENSING UNIT 20 25 30 208 1 2 3330 INT ELECTRICAL 30A/2P/208V
FUSED
DISCONNECT
SWITCH
(3X) (30A) 2-#10 CU, #10 CU GND - 3/4"C. 1-CR-TR-1A 7,9 5 Yes 1
SSCU-236 SPLIT SYSTEM CONDENSING UNIT 20 25 30 208 1 2 3330 INT ELECTRICAL 30A/2P/208V
FUSED
DISCONNECT
SWITCH
(3X) (30A) 2-#10 CU, #10 CU GND - 3/4"C. 1-CR-TR-2A 7,9 5 Yes 1
SSCU-301 SPLIT SYSTEM CONDENSING UNIT 20 25 30 208 1 2 3330 INT ELECTRICAL 30A/2P/208V
FUSED
DISCONNECT
SWITCH
(3X) (30A) 2-#10 CU, #10 CU GND - 3/4"C. 1-CR-TR-3A 7,9 5 Yes 1
SSCU-TBD SPLIT SYSTEM CONDENSING UNIT 0.4 1 0 208 1 2 1960 1-CR-TR-4A 7,9 0 Yes
UH-TBD UNIT HEATER 12.5 0 0 120 1 1 1500 INT MANUFACTURER - (2X) (20A) 2-#12 CU, #12 CU GND - 3/4"C. 1-TR-4A 4 0 No
REMARKS: (EQUIPMENT CONNECTION SCHEDULE)
1. CONTROLS BETWEEN INDOOR AND OUTDOOR UNITS - INCLUDE CONTROL WIRING IN CONDUIT BETWEEN INDOOR AND OUTDOOR UNIT PER MANUFACTURERS REQUIREMENTS.
2. "CONTROL TYPE" - PROVIDE CONTROL AND CONNECTIONS "INT" - CONTROLS ARE MANUFACTURED INTEGRAL TO THE EQUIPMENT (SELF-CONTAINED).
FEEDER SCHEDULE - COPPER
FEEDER NOMINAL SIZE WIRE AND CONDUIT
10N 100 A 4-#1 CU, #8 CU GND - 2" C.
17 175 A 3-#2/0 CU, #6 CU GND - 2" C.
40N 400 A 4-#4/0 CU, #3 CU GND - 2-1/2" C. (2 SETS)
112T 350 A 4-600 KCMIL CU, #1/0 CU GND - 4"C.
AUTOMATIC TRANSFER SWITCH SCHEDULE
NAME AMPS VOLTAGE PHASE
NUMBER
OF POLES
BYPASS
ISOLATION
TRANSITION
TYPE
MIN. 3 CYCLE
WCR
MIN. 30 CYCLE
WCR PRIORITY REMARKS
1-ATS-TR-GWA 400 A 208 V 3 3 Yes CLOSED 1
1/4" = 1'-0"2
ENLARGED PLAN
GROUND LEVEL
ELECTRICAL ROOM
TR
STAIRWELL
OFFICE
OFFICE
CORRIDOR
TR
E-001.1
E-001.1
I4E I4E
L21-20 (TYP.)
1-TR-1A
SSAH-132
1-CR-TR-1A
1-CR-TR-1A-2
1-TR-1A-2
1-CR-TR-1A-4
3 4
1-TR-1A-1,3,5
1-CR-TR-1A-1,3,5
3 4
1-TR-1A-4,6,8
1-CR-TR-1A-6,8,10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Specialized Engineering Solutions 1300 Baxter Street, Suite 355 Charlotte, NC 28204
Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 NC Architectural License No.: 51254 www.atriaxgroup.com
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
03/08/2024
A u to d e s k D o c s /2
.0
V A
T u s c a lo o s a
E H
R M
I n fr a s tr u c tu re U p g ra d e s /2
.0
V
A E
H R
M T u s c a lo o s a
R
B
.r v t
-0
-2
:0
:1
E-001.1
BUILDING 1 LEVEL 01 -
ELECTRICAL
EHRM INFRASTRUCTURE UPGRADES
TUSCALOOSA VAMC, TUSCALOOSA, AL.
679-20-104
03/08/2024 CGH MJJ
NTS1
OVERALL FLOOR PLAN
LEVEL 01 - ELECTRICAL
1/4" = 1'-0"2
DEMOLITION FLOOR
PLAN LEVEL 01 -
ELECTRICAL
1/4" = 1'-0"3
NEW FLOOR PLAN LEVEL
01 - ELECTRICAL
B. BUS B PANEL.
C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
63 A
SPARE CAPACITY:
63 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 16525 A
DEMAND CURRENT: 37 A
DEMAND LOAD: 13220 VA
REC 720 VA 100.00% 720 VA CONNECTED CURRENT: 30 A
PWR-C 10000 VA 125.00% 12500 VA CONNECTED LOAD: 10720 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 34 A 28 A 28 A
TOTAL LOAD: 4053 VA 3333 VA 3333 VA
23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24
21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22
19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20
17 SPACE -- -- 1 -- -- 1 -- -- SPACE 18
15 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 16
13 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 14
11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12
9 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 10
7 SPARE -- 20 A 1 0 VA 1667 VA 8
5 1667 VA 1667 VA 6
3 1667 VA 1667 VA
3 20 A REC - IT RACK TR-132
REC - IT RACK TR-132 20 A 3
1667 VA 720 VA 1 20 A REC - TR-132 2
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: NEMA 1
MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24
SERVICE RATED: No INTEGRAL SPD: Yes SECTIONS: 1
BRANCH: NORMAL WIRES: 4 MCB OPTIONS:
SUPPLY FROM: 1-TR-DP PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: TR 132 VOLTS: 208/120 WYE MAINS TYPE: MLO
PANEL: 1-TR-1A
B. BUS A PANEL.
C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
52 A
SPARE CAPACITY:
51 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 21831 A
MEQ-C 3330 VA 125.00% 4163 VA DEMAND CURRENT: 48 A
REC 720 VA 100.00% 720 VA DEMAND LOAD: 17465 VA
PWR-C 10000 VA 125.00% 12500 VA CONNECTED CURRENT: 39 A
LTG 66 VA 125.00% 83 VA CONNECTED LOAD: 14116 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 50 A 44 A 28 A
TOTAL LOAD: 5718 VA 5064 VA 3333 VA
23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24
21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22
19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20
17 SPACE -- -- 1 -- -- 1 -- -- SPACE 18
15 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 16
13 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 14
11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12
9 1665 VA 1667 VA 10
SSCU-132/SSAH-132 30 A 2
1665 VA 1667 VA 8
5 1667 VA 1667 VA
3 20 A REC - IT RACK TR-132
3 1667 VA 66 VA 1 20 A LTG - TR-132 4
REC - IT RACK TR-132 20 A 3
1667 VA 720 VA 1 20 A REC - TR-132 2
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: NEMA 1
MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24
SERVICE RATED: No INTEGRAL SPD: Yes SECTIONS: 1
BRANCH: EMERGENCY WIRES: 4 MCB OPTIONS:
SUPPLY FROM: 1-CR-TR-DP PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: TR 132 VOLTS: 208/120 WYE MAINS TYPE: MLO
PANEL: 1-CR-TR-1A
SHEET NOTES:
1. REMOVE ALL EXISTING DEVICES AND WIRING BACK TO SOURCE. VISIT SITE TO DETERMINE
FULL EXTENT OF DEMOLITION.
2. REFER TO EQUIPMENT CONNECTION SCHEDULE.
3. PROVIDE RECEPTACLE FOR BUS B. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.
4. PROVIDE RECEPTACLE FOR BUS A. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.
GENERAL NOTES:
A. REFER TO TELECOM, HVAC, AND FIRE PROTECTION DRAWINGS. COORDINATE LOCATION
ON NEW LIGHTING FIXTURES, NEW ELECTRICAL PANELS, AND NEW CABLE TRAY MOUNTED
RECEPTACLES WITH OTHER DISCIPLINES.
PLAN TRUE
LIMITS OF DEMOLITION
UP DN
TR
PROJECTION RM
235A
STAIRWELL
OFFICE
CONFERENCE
TR
E-001.2
E-001.2
1-CR-TR-2A
1-TR-2A
I4EI4E
L21-20 (TYP.)
SSAH-236
1-CR-TR-2A-2
1-TR-2A-2
1-CR-TR-2A-4
1-CR-TR-2A-1,3,5
1-TR-2A-1,3,5
1-CR-TR-2A-6,8,10
1-TR-2A-4,6,8
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Specialized Engineering Solutions 1300 Baxter Street, Suite 355 Charlotte, NC 28204
Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 NC Architectural License No.: 51254 www.atriaxgroup.com
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
03/08/2024
A u to d e s k D o c s /2
.0
V A
T u s c a lo o s a
E H
R M
I n fr a s tr u c tu re U p g ra d e s /2
.0
V
A E
H R
M T u s c a lo o s a
R
B
.r v t
-0
-2
:0
:1
E-001.2
BUILDING 1 LEVEL 02 -
ELECTRICAL
EHRM INFRASTRUCTURE UPGRADES
TUSCALOOSA VAMC, TUSCALOOSA, AL.
679-20-104
03/08/2024 CGH MJJ
NTS1
OVERALL FLOOR PLAN
LEVEL 02 - ELECTRICAL
1/4" = 1'-0"2
DEMOLITION FLOOR
PLAN LEVEL 02 -
ELECTRICAL
1/4" = 1'-0"3
NEW FLOOR PLAN LEVEL
02 - ELECTRICAL
B. BUS B PANEL.
C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
63 A
SPARE CAPACITY:
63 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 16525 A
DEMAND CURRENT: 37 A
DEMAND LOAD: 13220 VA
REC 720 VA 100.00% 720 VA CONNECTED CURRENT: 30 A
PWR-C 10000 VA 125.00% 12500 VA CONNECTED LOAD: 10720 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 34 A 28 A 28 A
TOTAL LOAD: 4053 VA 3333 VA 3333 VA
23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24
21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22
19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20
17 SPACE -- -- 1 -- -- 1 -- -- SPACE 18
15 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 16
13 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 14
11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12
9 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 10
7 SPARE -- 20 A 1 0 VA 1667 VA 8
5 1667 VA 1667 VA 6
3 1667 VA 1667 VA
3 20 A REC - IT RACK TR-236
REC - IT RACK TR-236 20 A 3
1667 VA 720 VA 1 20 A REC - TR-236 2
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: NEMA 1
MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24
SERVICE RATED: No INTEGRAL SPD: Yes SECTIONS: 1
BRANCH: NORMAL WIRES: 4 MCB OPTIONS:
SUPPLY FROM: 1-TR-DP PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: TR 236 VOLTS: 208/120 WYE MAINS TYPE: MLO
PANEL: 1-TR-2A
B. BUS A PANEL.
C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
52 A
SPARE CAPACITY:
51 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 21831 A
MEQ-C 3330 VA 125.00% 4163 VA DEMAND CURRENT: 48 A
REC 720 VA 100.00% 720 VA DEMAND LOAD: 17465 VA
PWR-C 10000 VA 125.00% 12500 VA CONNECTED CURRENT: 39 A
LTG 66 VA 125.00% 83 VA CONNECTED LOAD: 14116 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 50 A 44 A 28 A
TOTAL LOAD: 5718 VA 5064 VA 3333 VA
23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24
21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22
19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20
17 SPACE -- -- 1 -- -- 1 -- -- SPACE 18
15 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 16
13 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 14
11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12
9 1665 VA 1667 VA 10
SSCU-236/SSAH-236 30 A 2
1665 VA 1667 VA 8
5 1667 VA 1667 VA
3 20 A REC - IT RACK TR-236
3 1667 VA 66 VA 1 20 A LTG - TR-236 4
REC - IT RACK TR-236 20 A 3
1667 VA 720 VA 1 20 A REC - TR-236 2
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: NEMA 1
MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24
SERVICE RATED: No INTEGRAL SPD: Yes SECTIONS: 1
BRANCH: EMERGENCY WIRES: 4 MCB OPTIONS:
SUPPLY FROM: 1-CR-TR-DP PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: TR 236 VOLTS: 208/120 WYE MAINS TYPE: MLO
PANEL: 1-CR-TR-2A
SHEET NOTES:
1. REMOVE ALL EXISTING DEVICES AND WIRING BACK TO SOURCE. VISIT SITE TO DETERMINE
FULL EXTENT OF DEMOLITION.
2. REFER TO EQUIPMENT CONNECTION SCHEDULE.
3. PROVIDE RECEPTACLE FOR BUS B. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.
4. PROVIDE RECEPTACLE FOR BUS A. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.
GENERAL NOTES:
A. REFER TO TELECOM, HVAC, AND FIRE PROTECTION DRAWINGS. COORDINATE LOCATION
ON NEW LIGHTING FIXTURES, NEW ELECTRICAL PANELS, AND NEW CABLE TRAY MOUNTED
RECEPTACLES WITH OTHER DISCIPLINES.
PLAN TRUE
PAY PHONE
UP
DN
301D
TR
HOUSE KEEPING
HOUSE KEEPING
PIPE CHASE
MALE
TOILET
307B
FP
TELEPHONE CLOSET
VESTIBULE
307A
FP
PIPE
CHASE
PIPE
CHASE
FP
TOILET
301A
FP
TELEPHONE CLOSET
OFFICE
COPY RM
OFFICE
PIPE CHASE
352A
OFFICE
OFFICE
FILE RM
MEDIA
COUNTER
OFFICE
301C
301B
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
EXAM RM
FILE RM
OFFICE
RECEPTION AREA
OFFICE
314A
OFFICE
OFFICE
STORAGE
OFFICE
ELECTRICAL CLOSET
OFFICE
OFFICE
BREAK RM
OFFICE
COPY RM
IT
CLOSET
OFFICE
OFFICE
COPY RM
OFFICE
OFFICE
OFFICE
IT
CLOSET
ELECTRICAL
OFFICE
STAIR WELL
ELEVATOR
P3
STORAGE
STORAGE
RESOURCE
LIBRARY
OFFICE
OFFICE
ELEVATOR
P-2
ELEVATOR
P-1
OFFICE
OFFICE
365A
STAIR WELL
FILE RM
OFFICE
OFFICE
OFFICE
STAIR WELL
CORRIDOR
CORRIDOR
FEMALE
TOILET
CORRIDOR
FEMALE
TOILET
MALE
TOILET
CORRIDOR
CORRIDOR
FEMALE TOILET
CORRIDOR
STAIRWELL
CORRIDOR
MEDICAL RM
QUIET RM
OFFICE
MEN
TOILET
OFFICE
365B
OFFICE
OFFICE
CLOSET
OFFICE
301D
TOILET
301A
MEDIA
COUNTER
OFFICE
301C
301B
301D
TR
TOILET
301A
MEDIA
COUNTER
OFFICE
301C
301B
E-001.3
E-001.3
LIMITS OF DEMOLITION
I4EI4E
1-CR-TR-3A
1-TR-3A
SSAH-301
L21-20 (TYP.)
1-CR-TR-3A-2
1-TR-3A-2
1-CR-TR-3A-4
1-CR-TR-3A-1,3,5
1-TR-3A-1,3,5
1-CR-TR-3A-6,8,10
1-TR-3A-4,6,8
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Specialized Engineering Solutions 1300 Baxter Street, Suite 355 Charlotte, NC 28204
Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 NC Architectural License No.: 51254 www.atriaxgroup.com
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
03/08/2024
A u to d e s k D o c s /2
.0
V A
T u s c a lo o s a
E H
R M
I n fr a s tr u c tu re U p g ra d e s /2
.0
V
A E
H R
M T u s c a lo o s a
R
B
.r v t
-0
-2
:0
:1
E-001.3
BUILDING 1 LEVEL 03 -
ELECTRICAL
EHRM INFRASTRUCTURE UPGRADES
TUSCALOOSA VAMC, TUSCALOOSA, AL.
679-20-104
03/08/2024 CGH MJJ
NTS1
OVERALL FLOOR PLAN
LEVEL 03 - ELECTRICAL
1/4" = 1'-0"2
DEMOLITION FLOOR
PLAN LEVEL 03 -
ELECTRICAL
1/4" = 1'-0"3
NEW FLOOR PLAN LEVEL
03 - ELECTRICAL
B. BUS B PANEL.
C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
63 A
SPARE CAPACITY:
63 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 16525 A
DEMAND CURRENT: 37 A
DEMAND LOAD: 13220 VA
REC 720 VA 100.00% 720 VA CONNECTED CURRENT: 30 A
PWR-C 10000 VA 125.00% 12500 VA CONNECTED LOAD: 10720 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 34 A 28 A 28 A
TOTAL LOAD: 4053 VA 3333 VA 3333 VA
23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24
21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22
19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20
17 SPACE -- -- 1 -- -- 1 -- -- SPACE 18
15 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 16
13 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 14
11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12
9 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 10
7 SPARE -- 20 A 1 0 VA 1667 VA 8
5 1667 VA 1667 VA 6
3 1667 VA 1667 VA
3 20 A REC - IT RACK TR-301D
REC - IT RACK TR-301D 20 A 3
1667 VA 720 VA 1 20 A REC - TR-301D 2
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: NEMA 1
MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24
SERVICE RATED: No INTEGRAL SPD: Yes SECTIONS: 1
BRANCH: NORMAL WIRES: 4 MCB OPTIONS:
SUPPLY FROM: 1-TR-DP PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: TR VOLTS: 208/120 WYE MAINS TYPE: MLO
PANEL: 1-TR-3A
B. BUS A PANEL.
C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
52 A
SPARE CAPACITY:
52 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 21606 A
MEQ-C 3330 VA 125.00% 4163 VA DEMAND CURRENT: 48 A
REC 540 VA 100.00% 540 VA DEMAND LOAD: 17285 VA
PWR-C 10000 VA 125.00% 12500 VA CONNECTED CURRENT: 39 A
LTG 66 VA 125.00% 83 VA CONNECTED LOAD: 13936 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 48 A 44 A 28 A
TOTAL LOAD: 5538 VA 5064 VA 3333 VA
23 SPACE -- -- 1 -- -- 1 -- -- SPACE 24
21 SPACE -- -- 1 -- -- 1 -- -- SPACE 22
19 SPACE -- -- 1 -- -- 1 -- -- SPACE 20
17 SPACE -- -- 1 -- -- 1 -- -- SPACE 18
15 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 16
13 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 14
11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12
9 1665 VA 1667 VA 10
SSCU-301/SSAH-301 30 A 2
1665 VA 1667 VA 8
5 1667 VA 1667 VA
3 20 A REC - IT RACK TR-301D
3 1667 VA 66 VA 1 20 A LTG - TR-301D 4
REC - IT RACK TR-301D 20 A 3
1667 VA 540 VA 1 20 A REC - TR-301D 2
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: NEMA 1
MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24
SERVICE RATED: No INTEGRAL…