Attachment 21 - RFI 70. B13_WALL_TYPE.pdf
PDF 46 KB Posted
- Solicitation number
- 36C77625R0025
About this file
This file is a technical architectural drawing specifying a B1_ Wall Type for a construction project, detailing fire-rated and sound-tested wall specifications for a VA Medical Center infrastructure upgrade. The drawing provides comprehensive technical details for a 3 5/8" metal stud wall with a 4 7/8" total wall width, featuring a one-hour fire rating (UL U465) and a Sound Transmission Class (STC) rating of 40.
Key technical specifications include full-height metal studs at 16" on-center, 5/8" gypsum board on both sides, sound attenuation insulation (3 1/2" thick), deflection tracks, acoustic/fire sealant, and specific mounting details for metal tracks to concrete floor decks using 1 1/2" powder-activated fasteners. The drawing includes multiple section views (head parallel to metal deck, head perpendicular to metal deck, and plan section) and notes that impact-resistant gypsum board can be used on one or both sides equivalently, with reference to specific Underwriters Laboratories (UL) design systems and test numbers.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RATING
-FIRE- -SOUND-
TEST # STC TEST #
SCALE: 1 1/2"=1'-0"
1 hr UL U465
FIRE RATED - ONE HOUR
WHERE INDICATED ON PLANS
WALL TYPE IDENTIFIERS
B13 3 5/8" METAL STUDS = 4 7/8" WALL
B1_ WALL TYPE
1" DEFLECTION
1" DEFLECTION
FLOOR
PLAN SECTION
HEAD PERPENDICULAR TO MTL DECK
HEAD PARALLEL TO MTL DECK
STUD SIZE &
WALL TYPE
IDENTIFIER -
METAL TRACK ATTACHED TO CONCRETE FLOOR DECK W/
1 1/2" POWDER ACTIVATED FASTENERS @ 24" O.C. - 4"
FROM ENDS - MINIMUM EMBEDMENT: 1 1/4"
ACOUSTIC SEALANT- TYPICAL
(FIRE SEALANT @ FIRE BARRIERS)
CONCRETE FLOOR SLAB
SOUND ATTENUATION INSULATION , THICKNESS PER STC
RATING (3 1/2" IN B13 & B14 AND 6" IN B16)
FULL HEIGHT METAL STUDS @ 16" O.C.
5/8" GYPSUM BOARD, BOTH SIDES
DEFLECTION TRACK PER TESTED UL
DESIGN - FASTEN TO METAL DECK
CONCRETE
INSULATION PER HEAD OF WALL TESTED UL DESIGN
(@ FIRE BARRIERS)
BOTTOM
OF METAL
DECK
DEFLECTION TRACK PER TESTED DESIGN - FASTEN
TO STRAPS PER DESIGN - STRAPS @ 16" O.C.
FIRE SEALANT PER TESTED DESIGN BOTH SIDES
(@FIRE BARRIERS)
CONCRETE
METAL DECK
INSULATION PER TESTED HEAD OF WALL DESIGN
(@ FIRE BARRIERS)
5/8" GYPSUM BOARD BOTH SIDES - TYPICAL
1"
1/ 2"
SEE BELOW
STI SYSTEM No. HW-D-0456
STI SYSTEM No. HW-D-0456
5/8" GYPSUM BOARD BOTH SIDES - TYPICAL
CEILING RUNNER
CEILING RUNNER
& UL V438
NGC 2013004
NGC 25181 hr 40
NOTE: IMPACT RESISTANCE GYPSUM BOARD
ON ONE OR BOTH SIDES ARE EQUIVALENT.