Attachment 24 - RFI 223. Standard Mounting Heights.pdf
PDF 346 KB Posted
- Solicitation number
- 36C77625R0025
About this file
This document is a technical drawing detailing standard mounting heights for bathroom fixtures and accessibility features, specifically designed for a Veterans Affairs Medical Center (VAMC) construction project. The detailed architectural diagram provides precise measurements and placement specifications for various bathroom elements including:
Key mounting heights and locations include: robcoat hooks at specific elevations, hand sanitizer and napkin dispensers, water closets (floor mounted) positioned at regulated heights, grab bars with metal strapping requirements, tissue holders, and wall lavatory installations. The drawing includes section views and notes about mounting specifications, emphasizing compliance with accessibility standards such as minimum clearances, grab bar positioning, and carrier framing. The technical drawing is part of the solicitation for the Tuscaloosa VAMC Infrastructure Upgrades project (Solicitation 36C77625R0025) being managed by the Department of Veterans Affairs Technology Acquisition Center in Austin.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
30" X 48" FLOOR SPACE PER
305.3 ANSI A117.1
56" X 60" WC CLR FLOOR SPACE
42" GRAB BARS
WALL HUNG LAVATORY
36" GRAB BARS
NAPKIN DISPOSAL (@ WOMENS TLT)
5'-6" TURNING SPACE TYPICAL
TISSUE HOLDER
MIRROR
TOWEL DISPENSER
7'-0"
1'- 6"
7'- 6"
1'- 3"
M
IN
MAX
1'-0"
MIN
3'-6"
1'- 0"
2'- 0"
(U
SE
" D
OO
R)
1'- 6"
�5'-6" MIN CLEARANCE
18" VERTICAL BAR
3'-4"
4'-6" MIN
DIAGNOSTIC SYSTEM
COORDINATE WITH
ELECTRICAL
4'- 6"
CEILING
THERMOSTAT
OR 6'-8" AFF
WHICHEVER IS
LOWER
NURSE CALL DOME LIGHT
CEILING MOUNTED OR WALL
MOUNTED
MED GAS ALARM PANEL
6"
FIRE ALARM, HORN,
CHIME AND/OR LIGHT
ALIGN WHEN
MOUNTED
ON SAME WALL
NOTE: SWITCHES ARE TO BE GANGED
WHERE SHOWN ADJACENT TO EACH OTHER
ON PLANS
RECEPTACLES &
OUTLETS
(MTD. VERTICALLY)
NURSE CALL,
STAFF / DUTY
STATION
PULL STATION,
LIGHT SWITCH,
KEYPAD, CARD
READER, OR
DIMMER
DUPLEX
RECEPTACLE
BACKSPLASH
CASEWORK CASEWORK
WINDOW
4'- 6"
3'-
1'- 6"
8" 8"
CLOCK
7'- 0"
F I R E
E X T I N G U I S H E R
FIRE DEPT VALVE IN
RECESSED CABINET
FIRE EXTINGUISHER,
FIRE HOSE VALVE & FIRE
DEPT VALVE IN
RECESSED CAB
FIRE
EXTINGUISHER
WALL HUNG
FIRE EXTINGUISHER
& FIRE HOSE VALVE
IN RECESSED
CABINET
NOTE: SEE SPECIFICATIONS FOR MANUFACTURERS AND MODEL NUMBERS (TYP)
TO
F
.E . H
AN
DL
E
OR
V
AL
VE
4'-
0" M
AX
TO
V
AL
VE
H
AN
DL
E
3'-
6"FIRE EXTINGUISHER IN
RECESSED CABINET
(SEE SPEC TYP); IF FE IS
HEAVIER THAN 40LBS,
42" TO HANDLE REQUIRED
3/4" TYP.
3/4
TY
P.
1/4" THK LTWT CEMENT
BACKERBOARD
(BEHIND MIRROR)
METAL-FRAMED MIRROR
2'-0"
3'- 0"
SE
E
TY
P
A
CC
ES
SI
BL
E
MT
G
HE
IG
HT
S
TOP OF TILE
1/4"
3/4
USE 1/4" THK LTWT
CEMENT TO MATCH
PROJECTIONS OF
WAINSCOT
PROVIDE SECURE
WALL ATTACHMENT SCHEDULED MIRROR
SCHEDULED TILE
BACKER ROD &
JOINT SEALANT
MOUNTING STANDARDS NOTES
1.
2.
3.
4.
5.
6.
7.
8.
THE DIMENSIONS SHOWN ON THESE DRAWINGS ARE TYPICAL UNLESS NOTED OTHERWISE AND
DO NOT NECESSARILY SHOW ALL OF THE DEVICES THAT ARE LOCATED ON THE WALLS. REFER
TO DRAWING SET FOR ADDITIONAL INFORMATION IN REGARDS TO EQUIPMENT LOCATIONS.
THE OBJECT OF THIS SHEET IS TO ESTABLISH GUIDELINES FOR THE LOCATION OF DEVICES
GENERALLY THROUGHOUT THE PROJECT. THESE DIMENSIONS SHALL BE TYPICAL UNLESS NOTED
OTHERWISE ON DRAWINGS FOR SPECIFIC CASES.
FOR TYPICAL EQUIPMENT BLOCKING, CONFORM TO MANUFACTURER'S INSTALLATION
REQUIREMENTS UNLESS NOTED OTHERWISE.
REFER TO ALL EQUIPMENT MANUFACTURER'S SPECIFICATIONS REGARDING SUPPORT
REQUIREMENTS AND WEIGHT INFORMATION INCLUDING ITEMS NOT SHOWN HERE.
TYPES AND AMOUNT OF BLOCKING MAY VARY FOR DIFFERENT EQUIPMENT.
THE DIMENSIONS CALLED OUT SHALL BE TO THE TOP, BOTTOM OR CENTERLINE OF THE DEVICE'S
FACE PLATE AS SHOWN, UNLESS NOTED OTHERWISE.
ITEMS SHOWN ARE LOCATED FOR ACCESSIBILITY, SAFETY, AND CONFORMANCE WITH
APPLICABLE CODES AND STANDARDS. IN NO CASE SHALL THIS INFORMATION SUPERSEDE
REQUIREMENTS OF APPLICABLE CODES, STANDARDS OR AUTHORITIES IF A CONFLICT IS FOUND.
NOT ALL ITEMS SHOWN ON THIS SHEET MAY BE IN THE PROJECT.
MIN2'-
3"
M
IN
2'-
" M
AX
1'-3"
3'- 0"
1'- 6"
1'-6"
NOTE: HW & DRAIN PIPES SHALL BE
INSULATED IF SKIRT NOT PROVIDED
WALL LAVATORYWATER CLOSET
(FLOOR MOUNTED)
MIRROR
FACE OF
FINISHED WALL
(1 7"
: 1 9"
2'-0"@
BARIATRIC
6"
LIGHT
3'-
SOAP
(SIDEWALL MTD)
DUPLEX
(3 3"
: 3 6"
TO
P
OF
B
AR
TOP OF
SEAT
3'- 4"
MA
X
TO
R
EF
LE
CT
IN
G
SU
RF
AC
E 3'-
4"
MI
N.
6'-
2" 2'-
TO
P
OF
B
AR
3'-9"
12" MAX
OR 6" MIN
1 1 /2"
1'- 6"
3'-4"
3'- 4"
1'- 6"
NOTE: PROVIDE W/GRAB BARS METAL STRAPPING OR
WOOD BLOCKING PLATE IN WALLS OR FOR ACCESSORIES.
SANITARY NAPKIN
DISPOSAL
TISSUE
HOLDER
WATER CLOSET
(FLOOR MOUNTED)
MI
N
MI
N
GRAB BAR
SEAT
HEIGHT
1'- 6"
3'- 0"
(3 3"
: 3 6"
4'-6" MIN.
CENTER LINE OF 3" _
IN WALL FOR BARIATRIC
GRAB BAR LOCATIONS,
SEE DETAIL
3'-0" BAR
2'-0" 1'-0"
9"MAX
7"MIN
FACE OF
FINISHED WALL
EQ EQ
TI
D
DIAGRAM ONLY
NOT TO SCALE
NOTE: WHERE SINGLE ROBE/COAT H
LOCATED, MOUNT AT ACCESSIBLE H
WHERE MULTIPLE ROBE/COAT HOOK
LOCATED, MOUNT ONE AT ACCES
HEIGHT AND THE REMAINDER AT
STANDARD HEIGHT.
ALL ROBE OR COAT HOOKS SHO
MOUNTED BEHIND A DOOR ARE T
MOUNTED ON THE WALL AND SH
CENTERED WITH RESPECT TO TH
DOOR MOUNTED STOP, COORDINATE
W / MIRRORS WHERE APPLICABLE.
SEE HARDWARE SCHEDULE.
SHARPS GLOVES
5'- 0"
4'- 6"
1'-8"
4'- 0"
X-RAY
ILLUMINATOR
VERIFY JUNCTION BOX
LOCATION W/ MANUFACTURER'S
INSTALLATION INSTRUCTIONS
FILM
ILLUMINATOR
TOILET PAPER
DISPENSER
SANI-WIPES
DISPENSER/ GEL
DISPENSER
FILM/X-RAY
ILLUMINATORS
2'- 4"
METAL STUDS @ 16" OC
FASTEN TO STRUCTURE
ABOVE
SCHEDULED ACT CEILING
NOTE: SEE REFLECTED CEILING
PLAN FOR ALL CEILING HEIGHTS
WALL ANGLE, 7/8" LEG TYP.
5/8" GYPSUM BOARD
METAL STUD BRACES @ 4'-0" OC
TO STRUCTURE ABOVE
MI
N.4"
3" M
IN
8" MAX.8" MAX.
UNO
5 1/4"
SPACER BAR TYP. ALL ENDS
MIN. 12 GA HANGER WIRE TO
STRUCTURE TYP. INSTALL TO
PREVENT VERTICAL MOVEMENT
OR ROTATION OF GRID
MEMBERS PER ASTM E580
TYP.
3"
4" 1 1
/2" 1/2
4"
1'- 8"
A T
2'- 6"
A T
'A ' U
NI
TS
2'- 0"
4"
COUNTERTOP FINISH
AS SCHEDULED
2'-0"
2'- 6"
A T
'A ' U
NI
TS
2'-
BASE AS SCHEDULED
1"
2x FRT WD BLOCKING
AT 24" OC TYP.
1/2" MIN BACK PANEL
CONT 2x FRT WD
BLOCKING
DRAWER
6"
3/4
3/4"
PLAM / WD
VENEER ON SHELF
(ALL SIDES TYP.)
TYP FOR PLAM
G-103
TYP.
3"
4" 1 1
/2" 1/2
4"
8" 8"
8" 4"
1/8
COUNTERTOP FINISH
AS SCHEDULED
2'-0"
2'-
DRAWER
DRAWER
BASE AS SCHEDULED
1"
2x FRT WD BLOCKING
AT 24" OC TYP.
1/4" DUST PANEL
3/4"
1/2" MIN BACK PANEL
CONT 2x FRT WD
BLOCKING
DRAWER
6"
DRAWER
1/8
1/8
3/4
TYP FOR PLAM
NOTE: LETTER FILE CABINETS NEED TO BE MINUMUM 15 1/4" to 16 1/8" WIDE FOR SPECIFIED
BALL BEARING SLIDES ALL CABINET GABLE SIDES FOR LETTER / LEGAL SHALL BE 1/2"
G-103
TOOLED CONTINUOUS
SEALANT
PARTITION WITH
SCHEDULED FINISH
BUILD DOWN:
FOR COUNTERS SUPPORTED BY
CABINETS PROVIDE SPECIFIED BUILD
DOWN IN LADDER CONFIGURATION.
FOR COUNTERS UNSUPPORTED BY
CABINETS PROVIDE CONTINUOUS 1"
PLYWOOD BUILD DOWN FULLY
ADHERED TO DECK.
APPLIED SIDE SPLASH BEYOND.
FIELD FIT TO COVE AND WALL
CONDITIONS. PROVIDE TOOLED
PERIMETER CONTINUOUS
SEALANT
CONTINUOUS 1/2" RADIUS
INTEGRAL COVE BACKSPLASH.
ALL SEAMS SHALL BE
INCONSPICUOUS AND SANDED
SMOOTH.
TYPICAL SSM COUNTER TOP INTEGRAL COVED BACKSPLASH
NORT H CAROL
I N
A
E
DW
A R
D H . HENSO
N
H
I CKORY , N
.C
RE
G
IST
ERED ARCHITECT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
Atriax PLLC 703 Main Ave, SW PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 NC Architectural License No.: 51254 www.atriaxgroup.com
3/31/2025
Au to de sk
D oc s:
//E xp an d Fr an kl in C
BO
C
/2 3-
9-
_A
R C
H _A
TR
IA
X_ R
.rv t 3/
/2
:3
2:
A M
G-103
TYPICAL DETAILS & MOUNTING
HEIGHTS
EXPAND FRANKLIN CBOC
647 WAYAH STREET FRANKLIN, NC 28734
637-20-105
3/24/2025 EH BB
100% CONSTRUCTION
DOCUMENTS
1/2" = 1'-0"3
ACCESSIBLE STAFF TOILET
INSWING DOOR (ANSI A117.1)
1/2" = 1'-0"12 DIAGNOSTIC EQUIPMENT MTG HEIGHT
1/2" = 1'-0"8 TYPICAL ELECTRICAL DEVICE MOUNTING HEIGHTS
1/2" = 1'-0"4 FIRE EXTINGUISHER & HOSE CABINET MTG HEIGHTS
1 1/2" = 1'-0"1 METAL FRAMED MIRROR AT WAINSCOT
1 1/2" = 1'-0"2 MIRROR SECTION @ WAINSCOT
1/2" = 1'-0"11 TYPICAL FIXTURE
1/2" = 1'-0"7 TYPICAL MOUNTING HEIGHTS
1 1/2" = 1'-0"5 BULKHEAD DETAIL
1 1/2" = 1'-0"9 222A: BASE CABINET
1 1/2" = 1'-0"10 254: BASE CABINET
3" = 1'-0"6 TYPICAL COVED BACKSPLASH
Revisions: Date:
222 SINK BASE: SIMILAR TO 222A BUT HAS FALSE DRAWER FRONTS
M. Moorer Snapshot
M. Moorer Snapshot
File details come from the government source that posted it. Updated .