Attachment 24 - RFI 223. Standard Mounting Heights.pdf

PDF 346 KB Posted

Attached to
Y1BG--EHRM Construction Infrastructure Upgrades - 679-20-104 -Tuscaloosa VAMC
Solicitation number
36C77625R0025
Issued by

About this file

This document is a technical drawing detailing standard mounting heights for bathroom fixtures and accessibility features, specifically designed for a Veterans Affairs Medical Center (VAMC) construction project. The detailed architectural diagram provides precise measurements and placement specifications for various bathroom elements including:

Key mounting heights and locations include: robcoat hooks at specific elevations, hand sanitizer and napkin dispensers, water closets (floor mounted) positioned at regulated heights, grab bars with metal strapping requirements, tissue holders, and wall lavatory installations. The drawing includes section views and notes about mounting specifications, emphasizing compliance with accessibility standards such as minimum clearances, grab bar positioning, and carrier framing. The technical drawing is part of the solicitation for the Tuscaloosa VAMC Infrastructure Upgrades project (Solicitation 36C77625R0025) being managed by the Department of Veterans Affairs Technology Acquisition Center in Austin.

View the file

Other files

File Type Posted
36C77625R0025 0005.pdf PDF
36C77625R0025 0004.pdf PDF
Amendment 0004 - Attachment 27 - 36C77625R0025_1.pdf PDF
Attachment 23 - RFI 223. JSN Fixtures_Toilet.pdf PDF
Attachment 18 - Laydown Area Site Map.pdf PDF
Attachment 22 - RFI 77. Special Inpsections.xlsx XLSX spreadsheet
Attachment 27 - 36C77625R0025_1.pdf PDF
Attachment 19 - Lead Based Paint Report.pdf PDF
Attachment 20 - Asbestos Report.pdf PDF
Attachment 26 - RFIs - Tuscaloosa_FINAL.pdf PDF
Attachment 21 - RFI 70. B13_WALL_TYPE.pdf PDF
Attachment 14 - Updated WD_3.13.2025.pdf PDF
36C77625R0025 0003.pdf PDF
Attachment 25 - RFIs 263-265 Partial Electrical.pdf PDF
36C77625R0025 0002.pdf PDF
36C77625R0025 0001.pdf PDF
Amendment 0001 - Att 01 - 679-20-104 Site Visit Sign-In Sheet.pdf PDF
Amendment 0001 - Att 02 - Pre Proposal Conference - Tuscaloosa.pdf PDF
Attachment 8 -EHRM RTA Drawings_Telecommunications General and New Work.pdf PDF
Attachment 2 - EHRM RTA Drawings_Electrical.pdf PDF
36C77625R0025_1.pdf PDF
Attachment 10 - Submittal Register RTA.xlsx XLSX spreadsheet
Attachment 1 - SOW - EHRM Tuscaloosa.pdf PDF
Attachment 14 - WD - AL20240098 - 01.03.2025.pdf PDF
Attachment 5 - EHRM RTA Drawings_Mechanical and Plumbing.pdf PDF
Attachment 6 - EHRM RTA Drawings_Structural and Architecture.pdf PDF
Attachment 12 - Geotechnical Report - EHRM Data Center.pdf PDF
Attachment 16 - Brand Name - Corbin Russwin - Manufacture Document.pdf PDF
Attachment 11 - TVAMC Site Map_PSRDM.pdf PDF
Attachment 17 - Division Cost Breakdown.xlsx XLSX spreadsheet
Attachment 9 - EHRM RTA Specifications.pdf PDF
Attachment 13 - Limitations on Subcontracting - Construction.pdf PDF
Attachment 7 - EHRM RTA Drawings_Telecommunications General and Demolition.pdf PDF
Attachment 4 - EHRM RTA Drawings_General and Civil.pdf PDF
Attachment 15 - Brand Name - EHRM Tuscaloosa.pdf PDF
Attachment 3 - EHRM RTA Drawings_Fire Protection.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

30" X 48" FLOOR SPACE PER

305.3 ANSI A117.1

56" X 60" WC CLR FLOOR SPACE

42" GRAB BARS

WALL HUNG LAVATORY

36" GRAB BARS

NAPKIN DISPOSAL (@ WOMENS TLT)

5'-6" TURNING SPACE TYPICAL

TISSUE HOLDER

MIRROR

TOWEL DISPENSER

7'-0"

1'- 6"

7'- 6"

1'- 3"

M

IN

MAX

1'-0"

MIN

3'-6"

1'- 0"

2'- 0"

(U

SE

" D

OO

R)

1'- 6"

�5'-6" MIN CLEARANCE

18" VERTICAL BAR

3'-4"

4'-6" MIN

DIAGNOSTIC SYSTEM

COORDINATE WITH

ELECTRICAL

4'- 6"

CEILING

THERMOSTAT

OR 6'-8" AFF

WHICHEVER IS

LOWER

NURSE CALL DOME LIGHT

CEILING MOUNTED OR WALL

MOUNTED

MED GAS ALARM PANEL

6"

FIRE ALARM, HORN,

CHIME AND/OR LIGHT

ALIGN WHEN

MOUNTED

ON SAME WALL

NOTE: SWITCHES ARE TO BE GANGED

WHERE SHOWN ADJACENT TO EACH OTHER

ON PLANS

RECEPTACLES &

OUTLETS

(MTD. VERTICALLY)

NURSE CALL,

STAFF / DUTY

STATION

PULL STATION,

LIGHT SWITCH,

KEYPAD, CARD

READER, OR

DIMMER

DUPLEX

RECEPTACLE

BACKSPLASH

CASEWORK CASEWORK

WINDOW

4'- 6"

3'-

1'- 6"

8" 8"

CLOCK

7'- 0"

F I R E

E X T I N G U I S H E R

FIRE DEPT VALVE IN

RECESSED CABINET

FIRE EXTINGUISHER,

FIRE HOSE VALVE & FIRE

DEPT VALVE IN

RECESSED CAB

FIRE

EXTINGUISHER

WALL HUNG

FIRE EXTINGUISHER

& FIRE HOSE VALVE

IN RECESSED

CABINET

NOTE: SEE SPECIFICATIONS FOR MANUFACTURERS AND MODEL NUMBERS (TYP)

TO

F

.E . H

AN

DL

E

OR

V

AL

VE

4'-

0" M

AX

TO

V

AL

VE

H

AN

DL

E

3'-

6"FIRE EXTINGUISHER IN

RECESSED CABINET

(SEE SPEC TYP); IF FE IS

HEAVIER THAN 40LBS,

42" TO HANDLE REQUIRED

3/4" TYP.

3/4

TY

P.

1/4" THK LTWT CEMENT

BACKERBOARD

(BEHIND MIRROR)

METAL-FRAMED MIRROR

2'-0"

3'- 0"

SE

E

TY

P

A

CC

ES

SI

BL

E

MT

G

HE

IG

HT

S

TOP OF TILE

1/4"

3/4

USE 1/4" THK LTWT

CEMENT TO MATCH

PROJECTIONS OF

WAINSCOT

PROVIDE SECURE

WALL ATTACHMENT SCHEDULED MIRROR

SCHEDULED TILE

BACKER ROD &

JOINT SEALANT

MOUNTING STANDARDS NOTES

1.

2.

3.

4.

5.

6.

7.

8.

THE DIMENSIONS SHOWN ON THESE DRAWINGS ARE TYPICAL UNLESS NOTED OTHERWISE AND

DO NOT NECESSARILY SHOW ALL OF THE DEVICES THAT ARE LOCATED ON THE WALLS. REFER

TO DRAWING SET FOR ADDITIONAL INFORMATION IN REGARDS TO EQUIPMENT LOCATIONS.

THE OBJECT OF THIS SHEET IS TO ESTABLISH GUIDELINES FOR THE LOCATION OF DEVICES

GENERALLY THROUGHOUT THE PROJECT. THESE DIMENSIONS SHALL BE TYPICAL UNLESS NOTED

OTHERWISE ON DRAWINGS FOR SPECIFIC CASES.

FOR TYPICAL EQUIPMENT BLOCKING, CONFORM TO MANUFACTURER'S INSTALLATION

REQUIREMENTS UNLESS NOTED OTHERWISE.

REFER TO ALL EQUIPMENT MANUFACTURER'S SPECIFICATIONS REGARDING SUPPORT

REQUIREMENTS AND WEIGHT INFORMATION INCLUDING ITEMS NOT SHOWN HERE.

TYPES AND AMOUNT OF BLOCKING MAY VARY FOR DIFFERENT EQUIPMENT.

THE DIMENSIONS CALLED OUT SHALL BE TO THE TOP, BOTTOM OR CENTERLINE OF THE DEVICE'S

FACE PLATE AS SHOWN, UNLESS NOTED OTHERWISE.

ITEMS SHOWN ARE LOCATED FOR ACCESSIBILITY, SAFETY, AND CONFORMANCE WITH

APPLICABLE CODES AND STANDARDS. IN NO CASE SHALL THIS INFORMATION SUPERSEDE

REQUIREMENTS OF APPLICABLE CODES, STANDARDS OR AUTHORITIES IF A CONFLICT IS FOUND.

NOT ALL ITEMS SHOWN ON THIS SHEET MAY BE IN THE PROJECT.

MIN2'-

3"

M

IN

2'-

" M

AX

1'-3"

3'- 0"

1'- 6"

1'-6"

NOTE: HW & DRAIN PIPES SHALL BE

INSULATED IF SKIRT NOT PROVIDED

WALL LAVATORYWATER CLOSET

(FLOOR MOUNTED)

MIRROR

FACE OF

FINISHED WALL

(1 7"

: 1 9"

2'-0"@

BARIATRIC

6"

LIGHT

3'-

SOAP

(SIDEWALL MTD)

DUPLEX

(3 3"

: 3 6"

TO

P

OF

B

AR

TOP OF

SEAT

3'- 4"

MA

X

TO

R

EF

LE

CT

IN

G

SU

RF

AC

E 3'-

4"

MI

N.

6'-

2" 2'-

TO

P

OF

B

AR

3'-9"

12" MAX

OR 6" MIN

1 1 /2"

1'- 6"

3'-4"

3'- 4"

1'- 6"

NOTE: PROVIDE W/GRAB BARS METAL STRAPPING OR

WOOD BLOCKING PLATE IN WALLS OR FOR ACCESSORIES.

SANITARY NAPKIN

DISPOSAL

TISSUE

HOLDER

WATER CLOSET

(FLOOR MOUNTED)

MI

N

MI

N

GRAB BAR

SEAT

HEIGHT

1'- 6"

3'- 0"

(3 3"

: 3 6"

4'-6" MIN.

CENTER LINE OF 3" _

IN WALL FOR BARIATRIC

GRAB BAR LOCATIONS,

SEE DETAIL

3'-0" BAR

2'-0" 1'-0"

9"MAX

7"MIN

FACE OF

FINISHED WALL

EQ EQ

TI

D

DIAGRAM ONLY

NOT TO SCALE

NOTE: WHERE SINGLE ROBE/COAT H

LOCATED, MOUNT AT ACCESSIBLE H

WHERE MULTIPLE ROBE/COAT HOOK

LOCATED, MOUNT ONE AT ACCES

HEIGHT AND THE REMAINDER AT

STANDARD HEIGHT.

ALL ROBE OR COAT HOOKS SHO

MOUNTED BEHIND A DOOR ARE T

MOUNTED ON THE WALL AND SH

CENTERED WITH RESPECT TO TH

DOOR MOUNTED STOP, COORDINATE

W / MIRRORS WHERE APPLICABLE.

SEE HARDWARE SCHEDULE.

SHARPS GLOVES

5'- 0"

4'- 6"

1'-8"

4'- 0"

X-RAY

ILLUMINATOR

VERIFY JUNCTION BOX

LOCATION W/ MANUFACTURER'S

INSTALLATION INSTRUCTIONS

FILM

ILLUMINATOR

TOILET PAPER

DISPENSER

SANI-WIPES

DISPENSER/ GEL

DISPENSER

FILM/X-RAY

ILLUMINATORS

2'- 4"

METAL STUDS @ 16" OC

FASTEN TO STRUCTURE

ABOVE

SCHEDULED ACT CEILING

NOTE: SEE REFLECTED CEILING

PLAN FOR ALL CEILING HEIGHTS

WALL ANGLE, 7/8" LEG TYP.

5/8" GYPSUM BOARD

METAL STUD BRACES @ 4'-0" OC

TO STRUCTURE ABOVE

MI

N.4"

3" M

IN

8" MAX.8" MAX.

UNO

5 1/4"

SPACER BAR TYP. ALL ENDS

MIN. 12 GA HANGER WIRE TO

STRUCTURE TYP. INSTALL TO

PREVENT VERTICAL MOVEMENT

OR ROTATION OF GRID

MEMBERS PER ASTM E580

TYP.

3"

4" 1 1

/2" 1/2

4"

1'- 8"

A T

2'- 6"

A T

'A ' U

NI

TS

2'- 0"

4"

COUNTERTOP FINISH

AS SCHEDULED

2'-0"

2'- 6"

A T

'A ' U

NI

TS

2'-

BASE AS SCHEDULED

1"

2x FRT WD BLOCKING

AT 24" OC TYP.

1/2" MIN BACK PANEL

CONT 2x FRT WD

BLOCKING

DRAWER

6"

3/4

3/4"

PLAM / WD

VENEER ON SHELF

(ALL SIDES TYP.)

TYP FOR PLAM

G-103

TYP.

3"

4" 1 1

/2" 1/2

4"

8" 8"

8" 4"

1/8

COUNTERTOP FINISH

AS SCHEDULED

2'-0"

2'-

DRAWER

DRAWER

BASE AS SCHEDULED

1"

2x FRT WD BLOCKING

AT 24" OC TYP.

1/4" DUST PANEL

3/4"

1/2" MIN BACK PANEL

CONT 2x FRT WD

BLOCKING

DRAWER

6"

DRAWER

1/8

1/8

3/4

TYP FOR PLAM

NOTE: LETTER FILE CABINETS NEED TO BE MINUMUM 15 1/4" to 16 1/8" WIDE FOR SPECIFIED

BALL BEARING SLIDES ALL CABINET GABLE SIDES FOR LETTER / LEGAL SHALL BE 1/2"

G-103

TOOLED CONTINUOUS

SEALANT

PARTITION WITH

SCHEDULED FINISH

BUILD DOWN:

FOR COUNTERS SUPPORTED BY

CABINETS PROVIDE SPECIFIED BUILD

DOWN IN LADDER CONFIGURATION.

FOR COUNTERS UNSUPPORTED BY

CABINETS PROVIDE CONTINUOUS 1"

PLYWOOD BUILD DOWN FULLY

ADHERED TO DECK.

APPLIED SIDE SPLASH BEYOND.

FIELD FIT TO COVE AND WALL

CONDITIONS. PROVIDE TOOLED

PERIMETER CONTINUOUS

SEALANT

CONTINUOUS 1/2" RADIUS

INTEGRAL COVE BACKSPLASH.

ALL SEAMS SHALL BE

INCONSPICUOUS AND SANDED

SMOOTH.

TYPICAL SSM COUNTER TOP INTEGRAL COVED BACKSPLASH

NORT H CAROL

I N

A

E

DW

A R

D H . HENSO

N

H

I CKORY , N

.C

RE

G

IST

ERED ARCHITECT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FOR OFFICIAL USE ONLY (FOUO)

FOR OFFICIAL USE ONLY (FOUO)

Atriax PLLC 703 Main Ave, SW PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254 www.atriaxgroup.com

3/31/2025

Au to de sk

D oc s:

//E xp an d Fr an kl in C

BO

C

/2 3-

9-

_A

R C

H _A

TR

IA

X_ R

.rv t 3/

/2

:3

2:

A M

G-103

TYPICAL DETAILS & MOUNTING

HEIGHTS

EXPAND FRANKLIN CBOC

647 WAYAH STREET FRANKLIN, NC 28734

637-20-105

3/24/2025 EH BB

100% CONSTRUCTION

DOCUMENTS

1/2" = 1'-0"3

ACCESSIBLE STAFF TOILET

INSWING DOOR (ANSI A117.1)

1/2" = 1'-0"12 DIAGNOSTIC EQUIPMENT MTG HEIGHT

1/2" = 1'-0"8 TYPICAL ELECTRICAL DEVICE MOUNTING HEIGHTS

1/2" = 1'-0"4 FIRE EXTINGUISHER & HOSE CABINET MTG HEIGHTS

1 1/2" = 1'-0"1 METAL FRAMED MIRROR AT WAINSCOT

1 1/2" = 1'-0"2 MIRROR SECTION @ WAINSCOT

1/2" = 1'-0"11 TYPICAL FIXTURE

1/2" = 1'-0"7 TYPICAL MOUNTING HEIGHTS

1 1/2" = 1'-0"5 BULKHEAD DETAIL

1 1/2" = 1'-0"9 222A: BASE CABINET

1 1/2" = 1'-0"10 254: BASE CABINET

3" = 1'-0"6 TYPICAL COVED BACKSPLASH

Revisions: Date:

222 SINK BASE: SIMILAR TO 222A BUT HAS FALSE DRAWER FRONTS

M. Moorer Snapshot

M. Moorer Snapshot