ATTACHMENT 2 - Drawings.pdf

PDF 44 MB Posted

Attached to
Y1DA--675-22-706B EHRM Infrastructure Upgrades Construction Lakemont – Orlando, FL
Solicitation number
36C77625B0002
Issued by

About this file

This file appears to be a set of architectural or engineering drawings ("Attachment 2 - Drawings") related to EHRM (Electronic Health Record Modernization) Infrastructure Upgrades Construction project at the Lakemont facility in Orlando, Florida. However, without access to view the actual PDF file contents, I cannot provide specific details about what the drawings depict, their technical specifications, or other relevant construction details that would be shown in the drawings.

View the file

Other files

File Type Posted
Bid Opening Info..docx DOCX document
36C77625B0002 - 2-18-2025.pdf PDF
36C77625B0002 0007.pdf PDF
36C77625B0002 0006.pdf PDF
675-22-706B Technical Questions Spreadsheet - Lakemont Rev 2-14-25.docx DOCX document
Bid Opening Info.docx DOCX document
36C77625B0002 - 2-13-2025.pdf PDF
36C77625B0002 0005.pdf PDF
Additional Site Docs for QA - 2-3-25.zip ZIP file
ATTACHMENT 10 - OVAHCS Physical Security Systems Technical Specs 10-03-24.pdf PDF
ATTACHMENT 3 - Phasing Instructions Revised - 2-5-25.pdf PDF
36C77625B0002 0004.pdf PDF
675-22-706B Technical Questions Spreadsheet - Lakemont 2-5-25.docx DOCX document
Construction Wage Rates - Orange - 1-24-25.pdf PDF
36C77625B0002 0003.pdf PDF
36C77625B0002 0002.pdf PDF
Construction Wage Rates - Orange - 1-3-25.pdf PDF
Site Visit Sign-in Sheet - Lakemont.pdf PDF
36C77625B0002 0001.pdf PDF
36C77625B0002_1.docx DOCX document
ATTACHMENT 3 - Phasing Instructions.pdf PDF
ATTACHMENT 4 - Asbestos Report - Part 1.pdf PDF
ATTACHMENT 4 - Asbestos Report - Part 2.pdf PDF
ATTACHMENT 8 - Construction Wage Rates - Orange - 11-1-24.pdf PDF
ATTACHMENT 9 - Site Visit Instructions.pdf PDF
ATTACHMENT 4 - Asbestos Report - Part 3.pdf PDF
ATTACHMENT 5 - Brand Name Justification - Lakemont Redacted.pdf PDF
ATTACHMENT 1 - Specifications.pdf PDF
ATTACHMENT 7 - Limitations on Subcontracting - Construction.docx DOCX document
ATTACHMENT 6 - Pre-Construction Risk Assessment.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DX

A3-301

X

XX

X

DETAIL FLAG NUMBER

DOOR NUMBER

AE-501

BUILDING SECTION CUT

OTHER SECTION CUT

SHEET WHERE APPEARS (TYPICAL)

AE-301

AA

SHEET WHERE APPEARS

ELEVATION NUMBER

SHEET WHERE APPEARS

x x x x

EXISTING COLUMN CENTER LINEA

X

WINDOW TAG

AE-301

AA

AE-301

AA

ELEVATION NUMBER

AE-710

4 2

DASHED LINE

AROUND

AREA DETAILED

PLAN OR DETAIL NUMBERX

NOTE: IN ADDITION TO THE FOLLOWING INFECTION CONTROL MEASURES OF ICRA

CLASS & PERMIT LEVEL IV, THE CONTRACTOR SHALL REVIEW THE VA SAFETY-QUALITY

CONTROL-INFECTION CONTROL DOCUMENTS IN THE SPECIFICATIONS. THE AE WILL

PROVIDE A FORM FOR THE CONTRACTOR TO FILL OUT

DURING CONSTRUCTION:

A. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT

CONTAMINATION OF DUCT SYSTEM.

B. COMPLETE ALL CRITICAL BARRIERS I.E. SHEET ROCK, PLYWOOD, PLASTIC,

TO SEAL AREA FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE

METHOD (CART WITH PLASTIC COVERING AND SEALED CONNECTION TO

WORK SITE WITH HEPA VACUUM FOR VACUUMING PRIOR TO EXIT) BEFORE

CONSTRUCTION BEGINS.

C. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA

EQUIPPED AIR FILTRATION UNITS. PROVIDE NEGATIVE AIR PRESSURE

MONITOR.

D. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.

E. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH

THIS ROOM SO THEY CAN BE VACUUMED USING A HEPA VACUUM CLEANER

BEFORE LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER

COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE WORK SITE.

F. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT

IS INSPECTED BY A SAFETY OFFICER AND INFECTION CONTROL

COORDINATOR AND THOROUGHLY CLEANED BY THE ENVIRONMENTAL

MANAGEMENT SERVICES.

UPON COMPLETION OF PROJECT:

A. REMOVE BARRIER MATERIAL CAREFULLY TO MINIMIZE SPREADING OF DIRT

AND DEBRIS ASSOCIATED WITH CONSTRUCTION.

B. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY

COVERED CONTAINERS.

C. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS

SOLID LID.

D. VACUUM WORK AREA WITH HEPA FILTERED VACUUMS.

E. WET MOP AREA WITH DISINFECTANT.

F. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING

PERFORMED.

Approved: Associate Director

Approved: Chief Facilities Management

Approved: Manager / Engineer

Approved: Director

Approved: Union representative

Approved: Safety Officer

EQ-X

CPT1

W-X

E

EA EACH

E EAST

EWC ELECTRIC WATER COOLER

ELEC ELECTRIC (AL)

EL ELEVATION

ELEV ELEVATOR

EMER EMERGENCY

ENGR ENGINEER

EQ EQUAL

EQUIP EQUIPMENT

EXIST EXISTING

ETR EXISTING TO REMAIN

EXP EXPANSION

EXP BT EXPANSION BOLT

EJ EXPANSION JOINT

EXP EXPOSED

EXT EXTERIOR

EIFS EXTERIOR INSULATION AND

FINISH SYSTEM

F

FWC FABRIC WALL COVERING

FT FEET, FOOT

FGL FIBERGLASS

FIN FINISH

FIN GR FINISH GRADE

FDV FIRE DEPARTMENT VALVE

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER

CABINET

FHC FIRE HOSE CABINET

FP FIREPROOF

FIXT FIXTURE

FLASH FLASHING

FLEX FLEXIBLE

FLR FLOOR

FD FLOOR DRAIN

FLUOR FLUORESCENT

FTG FOOTING

FDTN FOUNDATION

FRMG FRAMING

FURN FURNACE, FURNITURE

G

GA GAGE

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GL GLASS

GL BLK GLASS BLOCK

GB GRAB BAR

GR GRADE

GRAN GRANITE

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GUT GUTTER

GYP BD GYPSUM BOARD

H

HNDRL HANDRAIL

HDW HARDWARE

HDWD HARDWOOD

HD HEAD

HVAC HEATING, VENTILATING, AIR CONDITIONING

HT HEIGHT

HPT HIGH POINT

HC HOLLOW CORE

HM HOLLOW METAL

HORIZ HORIZONTAL

HB HOSE BIBB

HOSP HOSPITAL

HR HOUR

I

IN INCH

INFO INFORMATION

ID INSIDE DIAMETER

INSUL INSULATED,INSULATION

INT INTERIOR

J

JAN JANITOR

JT JOINT

K

KPL KICKPLATE

KIT KITCHEN

KB KNEE BRACE

L

LAB LABORATORY

LAM LAMINATE

LC LAUNDRY CHUTE

LV LAVATORY

LT LIGHT

LD LINEAR DIFFUSER

L CL LINEN CLOSET

LL LIVE LOAD

LLV LONG LEG VERTICAL

LPT LOW POINT

M

MACH MACHINE

MH MANHOLE

MFD MANUFACTURED

MFR MANUFACTURER

MRB MARBLE BASE

MRF MARBLE FLOOR

MKR BD MARKER BOARD

MO MASONRY OPENING

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MED MEDICAL

MC MEDICINE CABINET

MEMB MEMBRANE

MTL METAL

MIN MINIMUM, MINUTE

MISC MISCELLANEOUS

MOD MODIFIED

MLDG MOLDING

N

NAT FIN NATURAL FINISH

NOM NOMINAL

N NORTH

NA NOT APPLICABLE

NIC NOT IN CONTRACT

NTS NOT TO SCALE

NO NUMBER

O

OFF OFFICE

OC ON CENTER

OPNG OPENING

OPP OPPOSITE

OPH OPPOSITE HAND

ORCH ORCHESTRA

ORN ORNAMENTAL

OD OUTSIDE DIAMETER

OH OVERHANG, OVERHEAD

OF/CI OWNER FURNISHED/

CONTRACTOR INSTALLED

O OXYGEN

P

P PAINT

PR PAIR

PNL PANEL

PTD PAPER TOWEL DISPENSER

PTN PARTITION

PERF PERFORATED

PC PIECE

PLAM PLASTIC LAMINATE

PLAS PLASTIC, PLASTER

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PCC PRECAST CONCRETE

PREFAB PREFABRICATE

PREFIN PREFINISH

PROD PRODUCTION

Q

QTY QUANTITY

QT QUARRY TILE

A

AFF ABOVE FINISHED FLOOR

ACST ACOUSTIC (AL)

ACT ACOUSTICAL CEILING TILE

APC ACOUSTICAL PANEL CEILING

AWP ACOUSTICAL WALL PANEL

AWT ACOUSTICAL WALL

ADJ ADJUSTABLE

A/C AIR CONDITIONING

AHU AIR HANDLING UNIT

ALT ALTERNATE

ALUM ALUMINUM

AB ANCHOR BOLT

AL ANGLE

APPROX APPROXIMATE

ARCH ARCHITECT (URAL)

ASPH ASPHALT

ASSY ASSEMBLY

AUTO AUTOMATIC

AWN AWNING

B

BALC BALCONY

BSMT BASEMENT

BM BEAM, BENCHMARK

BR BEDROOM

BLKG BLOCKING

BD BOARD

BOT BOTTOM

BRKT BRACKET

BRK BRICK

B CL BROOM CLOSET

BLDG BUILDING

BLT IN BUILT-IN

BUR BUILT-UP ROOFING

C

CAB CABINET

CPT CARPET

CSMT CASEMENT

CI CAST IRON

CB CATCH BASIN

CLG CEILING

CEM CEMENT

CL CENTER LINE

CER CERAMIC

CT CERAMIC TILE

CO CLEANOUT, CASED OPENING

CLR CLEAR, COLOR

CLO CLOSET

COL COLUMN

CMPST COMPOSITE

CONC CONCRETE

CMU CONCRETE MASONRY UNIT

CONSTR CONSTRUCTION

CONT CONTINUOUS

CONTR CONTRACTOR

COTR CONTRACTING OFFICER

CJ CONTROL JOINT

COP COPING

CU COPPER

CG CORNER GUARD

CORR CORRIDOR

CNTR COUNTER

CSK COUNTER SUNK

D

DMPF DAMPPROOFING

DL DEAD LOAD

DEMO DEMOLITION

DET DETAIL

DIA DIAMETER

DIFF DIFFUSER

DIM DIMENSION

DR DOOR, DRAIN

DH DOUBLE HUNG

DN DOWN

DS DOWNSPOUT

DWR DRAWER

DWG DRAWING

DF DRINKING FOUNTAIN

DUPL DUPLICATE

R

R RADIUS, RISER

RWD REDWOOD

REF REFERENCE, REFRIGERATOR

REINF REINFORCE

REQD REQUIRED

RB RESILIENT BASE

RF RESILIENT FLOORING

RA RETURN AIR

REV REVISION

RD ROOF DRAIN

RM ROOM

RO ROUGH OPENING

RS ROUGH SAWN

S

SCHED SCHEDULE

SECT SECTION

SHTHG SHEATHING

SHT SHEET

SHV SHELVING

SIM SIMILAR

S SOUTH

SP FIN SPECIAL FINISH

SPEC SPECIFICATION

SQ SQUARE

SF SQUARE FEET

SST STAINLESS STEEL

STD STANDARD

STL STEEL

STL JST STEEL JOIST

STOR STORAGE

STRUCT STRUCTURAL

S4S SURFACED FOUR SIDES

SUSP SUSPEND

SW SWITCH

SYMM SYMMETRICAL

T

TK BD TACKBOARD

TEL TELEPHONE

TV TELEVISION

TMPD TEMPERED

TEMP TEMPORARY

TER TERRAZZO

THK THICKNESS

TPD TOILET PAPER DISPENSER

T&G TONGUE AND GROOVE

TOS TOP OF SLAB, STEEL

T TREAD

TYP TYPICAL

U

UC UNDERCUT

UNFIN UNFINISH

UNO UNLESS NOTED OTHERWISE

V

VAC VACUUM

VR VAPOR RETARDER

VNR VENEER

VP VENEER PLASTER

VIF VERIFY IN FIELD

VERT VERTICAL

VEST VESTIBULE

VCT VINYL COMPOSITION TILE

VWC VINYL WALL COVERING

W

W CAB WALL CABINETS

WC WALL COVERING, WATER CLOSET

WP WATERPROOFING, WEATHER

WT WEIGHT

WWF WELDED WIRE FABRIC

W WEST

WF WIDE FLANGE

WDW WINDOW

W/ WITH

W/O WITHOUT

WD WOOD

WDP WOOD PANELING

Department of Veterans Affairs

KEYED NOTE

WALL TYPE

X

X WINDOW TREATMENT TYPE

EQUIPMENT

INTERIOR FINISH TYPE

FURNITURE, FIXTURE, EQUIPMENT

CONTRACT LIMIT LINE

COLUMN CENTER LINE

NEW WALL

DEMOLITION

EXISTING WALL

APPROVED FOR CONSTRUCTION

Project No: 675-22-706B

DESIGN TEAM

ABBREVIATIONS OWNER

CODE REFERENCES

PROJECT DESCRIPTIONSYMBOL LEGEND

BUILDING INFORMATION

GENERAL NOTES

INFECTION CONTROL MEASURES

THIS PROJECT IS LOCATED IN ORLANDO, FLORIDA AT THE LAKEMONT VA MEDICAL

CENTER. ALL TELECOMMUNICATION ROOMS ARE EXISTING AND CURRENTLY

OPERATIONAL AT THE FACILITY. THE INTENT OF THIS PROJECT IS TO CORRECT

NOTED DEFICIENCIES AND BRING THE CAMPUS UP TO THE CURRENT STANDARD AS

OUTLINED IN THE VA OI&T INFRASTRUCTURE STANDARDS DESIGN GUIDE.

THE SCOPE OF WORK WILL ALSO BE IN ACCORDANCE WITH THE “ARCHITECT-

ENGINEER DESIGN STATEMENT OF WORK FOR THIS PROJECT, PREPARED BY THE VA.

THIS WORK SHALL INCLUDE BUT NOT BE LIMITED TO ARCHITECTURAL, CIVIL,

LANDSCAPE, STRUCTURAL, MECHANICAL, PLUMBING, & ELECTRICAL.

DESCRIPTIONSYMBOL

EHRM INFRASTRUCTURE UPGRADES

LAKEMONT VA MEDICAL CENTERS

Department of Veterans Affairs

Architect

1050 E. Southern Ave. Suite 5, Tempe, Arizona 85282

AESUS Design Group

David Combs (dcombs@aesusdesign.com)

480-454-2861

A. ANY CHANGES MUST BE APPROVED BY COR BEFORE DOING ANY

ADDITIONAL WORK. WORK SCHEDULE TO BE PERFORMED DURING

REGULAR DAY SHIFT HOURS (8AM-4:30PM) ANY WORK OUTSIDE OF

REGULAR SCHEDULE REQUIRES APPROVAL FROM COR.

B. COORDINATE STAGING AREA WITH COR, AND FIND INTERIOR

COVERED STORAGE ON SITE FOR MATERIALS THAT MUST BE

PROTECTED FROM ELEMENTS - COORDINATE WITH COR.

C. PERFORM WORK IN ACCORDANCE WITH VHA DIRECTIVE 2004-012

SAFETY AND HEALTH DURING CONSTRUCTION ACTIVITIES AND VHA

DIRECTIVE 7701 OCCUPATIONAL SAFETY AND HEALTH (OSH) .

D. WORK PERFORMED FOR THIS PROJECT MAY INTERRUPT SERVICE TO

ADJACENT AREAS AT TIMES BUT WILL NOT INTERRUPT OVERALL

FACILITY OPERATION. SEE ELECTRICAL FOR POWER INTERRUPTION

AND OUTAGE REQUIREMENTS.

E. CONTRACTOR TO VERIFY ALL DETAILS AGAINST EXISTING

CONDITIONS PRIOR TO PURCHASE OF EQUIPMENT AND PRIOR TO

CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR BRINGING ANY

DISCREPANCIES IN PLANS AND EXISTING SITE CONDITIONS TO

IMMEDIATE ATTENTION OF CONTRACTING OFFICER

REPRESENTATIVE.

F. CONTRACTOR SHALL PERFORM ALL WORK AND PROVIDE ALL

MATERIALS IN ACCORDANCE WITH VA MASTER CONSTRUCTION

SPECIFICATIONS, WHICH CAN BE FOUND AT

HTTP://WWW.CFM.VA.GOV/TIL/. WHERE DISCREPANCIES ARE FOUND

THE MORE STRINGENT SHALL APPLY.

G. NOT ALL KEYNOTES ARE ON ALL SHEETS.

NORTH

VICINITY MAP - LAKEMONT

PROJECT AREA

MPE Engineers

550 North Reo Street, Tampa, FL, 33609

MES Group, Inc

David Keith

813-289-4700

BUILDING CODE:

2020 FBC - INTERNATIONAL BUILDING CODE

2020 FBC - EXISTING BUILDING CODE

2020 FBC - INTERNATIONAL ENERGY CONSERVATION CODE

2020 FFPC - NFPA

ACCESSIBILITY CODE & GUIDELINES:

ABAAS & BFDG

MECHANICAL CODE:

2020 FBC - INTERNATIONAL MECHANICAL CODE

PLUMBING CODE:

2020 FBC - INTERNATIONAL PLUMBING CODE

ELECTRICAL CODE:

2020 FBC - INTERNATIONAL ELECTRICAL CODE

NO LIFE SAFETY WILL BE AFFECTED BY THIS PROJECT.

NFPA

NFPA 101 LIFE SAFETY CODE

NFPA NATIONAL FIRE CODES

NFPA 900 (OSHA)

Lakemont, Orlando VA Medical center, 2500 S Lakemont Ave, Orlando FL, 32814

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861 design group

MES GROUP, INC

550 North Reo Street Tampa, FL, 33609 813-289-4700 David Keith

LAKEMONT, ORLANDO VA MEDICAL CENTER,

2500 S LAKEMONT AVE, ORLANDO FL 32814

C U s e rs \a d m in \D o c u m e n ts \6

-2

-7

L A

K E

M O

N T

E

H R

M

R E

V

IT

c c h a n g V

Z R

C

.r v t

/5

/2

:4

:4

P M

GI.00

COVER SHEET 675-22-706B

ALL

JUNE 07, 2024 AESUS AESUS

EHRM INFRASTRUCTURE UPGRADES

VA_LAKEMONT

FINAL SUBMITTAL

FAC FACTORY FINISH

ISSUED SHEETS

Sheet Number Sheet Name

GENERAL

GI.00 COVER SHEET

ARCHITECTURE

AE2-100 LAKEMONT PHASING / TR ZONE

AE2-101 LAKEMONT 1ST FLOOR PLAN

AE2-102 LAKEMONT 2ND FLOOR PLANS

AE2-103 LAKEMONT 3RD FLOOR PLANS

AE2-201 LAKEMONT 1ST FLOOR RCP

AE2-202 LAKEMONT 2ND FLOOR RCP

AE2-203 LAKEMONT 3RD FLOOR RCP

AE-502 DOOR AND FINISH INFORMATION

AE-503 GYP BD DETAILS

AE-504 PARTITION HEAD DETAILS

AE-505 PARTITION TYPES

AE-506 FIRE RATED ASSEMBLIES

AE-950 FIRE RATED ASSEMBLIES - U419, BW-S-0001, BW-S-0023

AE-951 FIRE RATED ASSEMBLIES - HW-D-0538, HW-D-0539

AE-952 FIRE RATED ASSEMBLIES - HW-D-0388, HW-D-0218

AE-953 FIRE RATED ASSEMBLIES - HW-D-0259, HW-D-0634

AE-954 FIRE RATED ASSEMBLIES - HW-D-0639

AE-955 FIRE RATED ASSEMBLIES - W-L-1222, W-L-5073, W-L-8081, C-AJ-3214,

C-AJ-3260, C-AJ-3285

FIRE PROTECTION

FX2-000 FIRE PROTECTION LEGEND, NOTES, AND ABBREVIATIONS

FX2-101 LAKEMONT 1ST FLR DEMO & RENO PLANS - FIRE PROTECTION

FX2-102 LAKEMONT 2ND FLR DEMO & RENO PLANS - FIRE PROTECTION

FX2-103 LAKEMONT 3RD FLR DEMO & RENO PLANS - FIRE PROTECTION

MECHANICAL

MH2-000 LEGENDS, NOTES, AND ABBREVIATIONS - HVAC

MH2-001 SCHEDULES AND DETAILS - HVAC

MH2-101 LAKEMONT 1ST FLOOR DEMOLITION & RENOVATION PLANS - HVAC

MH2-102 LAKEMONT 2ND FLOOR DEMOLITION & RENOVATION PLANS - HVAC

MH2-103 LAKEMONT 3RD FLOOR DEMOLITION & RENOVATION PLANS - HVAC

MH2-401 LAKEMONT 1ST FLOOR ENLARGED PARTIAL PLANS - HVAC

MH2-402 LAKEMONT 2ND FLOOR ENLARGED PARTIAL PLANS - HVAC

MH2-403 LAKEMONT 3RD FLOOR ENLARGED PARTIAL PLANS - HVAC

ELECTRICAL

ET2-001 ELECTRICAL LEGEND, NOTES & ABBREVIATIONS

ET2-100 LAKEMONT - LEVEL 1 OVERALL PLAN & NEXT GEN DEVICES

ET2-101 LAKEMONT - LEVEL 1 OVERALL PLAN - CABLE TRAY

ET2-102 LAKEMONT - LEVEL 1 OVERALL PLAN - FIBER DISTRIBUTION

ET2-103 LAKEMONT - LEVEL 1 - ZONE #1 - TELECOMMUNICATION DROPS

ET2-104 LAKEMONT - LEVEL 1 - ZONE #2 - TELECOMMUNICATION DROPS

ET2-200 LAKEMONT - LEVEL 2 OVERALL PLAN & NEXT GEN DEVICES

ET2-201 LAKEMONT - LEVEL 2 OVERALL PLAN - CABLE TRAY

ET2-202 LAKEMONT - LEVEL 2 OVERALL PLAN - FIBER DISTRIBUTION

ET2-203 LAKEMONT - LEVEL 2 - ZONE #1 - TELECOMMUNICATION DROPS

ET2-204 LAKEMONT - LEVEL 2 - ZONE #2 - TELECOMMUNICATION DROPS

ET2-300 LAKEMONT - LEVEL 3 OVERALL PLAN & NEXT GEN DEVICES

ET2-301 LAKEMONT - LEVEL 3 OVERALL PLAN - CABLE TRAY

ET2-302 LAKEMONT - LEVEL 3 OVERALL PLAN - FIBER DISTRIBUTION

ET2-303 LAKEMONT - LEVEL 3 - ZONE #1 - TELECOMMUNICATION DROPS

ET2-304 LAKEMONT - LEVEL 3 - ZONE #2 - TELECOMMUNICATION DROPS

ET2-401 LAKEMONT - ENLARGED DEMO PLANS - ELECTRICAL

ET2-402 LAKEMONT - ENLARGED DEMO PLANS - ELECTRICAL

ET2-403 LAKEMONT - ENLARGED DEMO PLANS - ELECTRICAL

ET2-404 LAKEMONT - ENLARGED RENO PLANS - ELECTRICAL

ET2-405 LAKEMONT - ENLARGED RENO PLANS - DIMENSIONS

ET2-500 TYPICAL DETAILS FOR TELECOMMUNICATION ROOM

ET2-501 TYPICAL DETAILS FOR TELECOMMUNICATION ROOM

ET2-502 TYPICAL DETAILS FOR TELECOMMUNICATION ROOM

ET2-600 LAKEMONT - ELECTRICAL RISER DIAGRAM

ET2-601 LAKEMONT - FIBER BACKBONE RISER DIAGRAM

ET2-700 LAKEMONT - SCHEDULES - ELECTRICAL

ET2-701 LAKEMONT - SCHEDULES - ELECTRICAL

ET2-702 LAKEMONT - SCHEDULES - ELECTRICAL

ET2-800 OVERALL GROUNDING RISER DETAIL

NOTE: THIS PROJECT NUMBER WAS SEPARATED FROM ANOTHER PROJECT. IF THE

ORIGINAL PROJECT NUMBER 675-22-706 IS REFERENCED IN THIS DOCUMENT, IT

SHOULD BE ASSUMED TO BE 675-22-706B AND PART OF THIS SCOPE.

Revisions: Date:

STAMP

OR

LA

NDO

ER I K GONZALES

PRO F E S S I ONA L ENG

I N

EE

R

MEN

WOMEN

SOCIAL WORK

PAYROLL/TRAVEL

HBPC

SECURITY

SUPPLY

TRAINING/CONFERENCE ROOM

TROA

CAP

VA POLICE CHIEF

DATA CENTER

MAILROOM

MEDICAL

IRMS

BIO-MED

LOGISTICS

LEO & LARRY

SUPPLY IRMS

CHIEF

DEPUTY

IRMS

CONTRACTING

EDUCATION

RESEARCH

CONTRACTING

RECORDS

MEDICAL

RECORDS

LEARNING EXCHANGE

EMPLOYEE AND

LABOR RELATIONS

LOGISTICS

ROOM

EEO

VA

POLICE

TRAVEL

CHIEF

VA POLICE

ADMIN.

TRAINING ROOM

LOUNGE /VENDING

SUPPLY

ROOM

DATA CENTER

COMM

MEN

WOMEN

STOR

STOR

ASST. POLICE

MECH

ELECT

MECH

MECH OFF.

MECH

117C

117B

117A

119A

119B

116B

136 134

116A

125A

XXX

XXX

XXX

XXX

103B 103A 105A

109B

109A

MEN

WOMEN

HUMAN RESOURCES

IRMS

CONTRACTING OFFICE

PEOSTRI

PEOSTRI

MEDICAL

ARMY

HUMAN RESOURCES

SERVICES

CAC

OFFICE SUPPLIES

TRAINING RM.-A

TRAINING RM.-B

IRMS

OFFICE

SECURITY

OFFICE

ACTIVATIONS

CONFERENCE

TELECARE

TELEHEALTH

TELECARE

TELECARE

RECORDS

NURSING

EDUCATION

INTERIOR DESIGN

219C

219B

219A

217A

217B

217C

215C

215B

215A

202B

202A

REHAB

MECH

ADMIN.

HEALTH

HAS

COMM

ELECT

XXX

XXX

OFFICE

OFFICEOFFICE

OFFICE

221A

221B221C221D221E221F

230A

230B

MECH

214A

INFORMATICS

CLINICAL

206C

206B

206A

204C

204B

204A

LEARNING

EXCHANGE

VISN

LEARNING

EXCHANGE

VISN

LEARNING

EXCHANGE

VISN

LEARNING

EXCHANGE

VISN

LEARNING

EXCHANGE

VISN

EXCHANGE

VISN

309308

348 352

304 305

BREAK A

REA

CONF.

RM.

PANEL

CONF.

RM.

TRAINING ROOM

BULK STORAGE

IT STORAGE

OPEN

OFFICE

MAILROOM

CASH

MANAGEMENT

MECHANICAL ROOM

CONFERENCE ROOM

COO

CFO

HR

ISO

WAITING

JANITOR CLOSET

MECHANICAL ROOM

OFFICE

CONFERENCE ROOM UNION

OFFICE

E

LE

V

OFFICE

E

LE

V

CORRIDOR

LOBBY

CORRIDOR

C O

R R

ID

O

R

C O

R R

ID

O

R

CORRIDOR

C O

R R

ID

O

R

EXECUTIVE SUITE

CORRIDOR

TRAINING ROOM

TRAINING ROOM

TELEPHONE RISER

C O

R R

ID

O

R C

O R

R

ID

O R

C O

R R

ID

O

R

OPEN OFFICE

OPEN OFFICE

OPEN OFFICE OPEN OFFICE

OPEN OFFICE

SPRINKLER RISER

OPEN OFFICE

OPEN OFFICE

OPEN OFFICE

OFFICE

CONFERENCE ROOM

FI

R

E E

Q U

IP

. C

LO

S

E T

CONFERENCE ROOM

IT OFFICE

VENDING

MEN'S ROOM

LADIES' ROOM

CORRIDOR

DIRECTOR

OFFICE

IT DEPARTMENT

337A

IT WORK

TR

138A

ELEC

/AE2-101 3

/AE2-101 2

/AE2-101 4

TR

105A

TR

123B

/AE2-101 5

TR ZONE 1

TR ZONE 2

A. ANY CHANGES MUST BE APPROVED BY COR BEFORE DOING ANY

ADDITIONAL WORK. WORK SCHEDULE TO BE PERFORMED DURING

REGULAR DAY SHIFT HOURS (8AM-4:30PM) ANY WORK OUTSIDE OF

REGULAR SCHEDULE REQUIRES APPROVAL FROM COR.

B. COORDINATE STAGING AREA WITH COR, AND FIND INTERIOR

COVERED STORAGE ON SITE FOR MATERIALS THAT MUST BE

PROTECTED FROM ELEMENTS - COORDINATE WITH COR.

C. PERFORM WORK IN ACCORDANCE WITH VHA DIRECTIVE 2004-012

SAFETY AND HEALTH DURING CONSTRUCTION ACTIVITIES AND VHA

DIRECTIVE 7701 OCCUPATIONAL SAFETY AND HEALTH (OSH) .

D. WORK PERFORMED FOR THIS PROJECT MAY INTERRUPT SERVICE

TO ADJACENT AREAS AT TIMES BUT WILL NOT INTERRUPT OVERALL

FACILITY OPERATION. SEE ELECTRICAL FOR POWER INTERRUPTION

AND OUTAGE REQUIREMENTS.

E. CONTRACTOR TO VERIFY ALL DETAILS AGAINST EXISTING

CONDITIONS PRIOR TO PURCHASE OF EQUIPMENT AND PRIOR TO

CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR BRINGING

ANY DISCREPANCIES IN PLANS AND EXISTING SITE CONDITIONS TO

IMMEDIATE ATTENTION OF CONTRACTING OFFICER

REPRESENTATIVE.

F. CONTRACTOR SHALL PERFORM ALL WORK AND PROVIDE ALL

MATERIALS IN ACCORDANCE WITH VA MASTER CONSTRUCTION

SPECIFICATIONS, WHICH CAN BE FOUND AT

HTTP://WWW.CFM.VA.GOV/TIL/. WHERE DISCREPANCIES ARE FOUND

THE MORE STRINGENT SHALL APPLY.

GENERAL NOTES

A. THE CONTRACTORS SHALL COORDINATE EQUIPMENT AND

MATERIAL TRAFFIC AND STORAGE WITH COR.

B. ALL UTILITY WORK SHALL BE COORDINATED WITH MECHANICAL,

PLUMBING ELECTRICAL, AND FIRE PROTECTION.

C. ALL ASPECTS OF CONTRACTOR STAGING AND CONSTRUCTION

PHASING SHALL BE APPROVED BY COR.

D. ALL HOSPITAL ACCESS POINTS, AND ALL BUILDING EXITS, MUST

REMAIN ACCESSIBLE, CLEAR AND UNOBSTRUCTED THROUGHOUT

ALL PHASES OF DEMOLITION AND CONSTRUCTION. SHORT-TERM

CLOSURE MAY BE ACCEPTABLE AS COORDINATED WITH COR.

E. THE CONTRACTOR SHALL COORDINATE ALL ROOF TOP WORK AND

ROOF REPAIRS WITH THE COR.

GENERAL PHASING NOTES

A. THE CONTRACTOR SHALL USE THE FOLLOWING AS A GUIDE FOR ALL

ICRA BARRIERS. TEMPORARY INFECTION CONTROL BARRIERS

SHALL BE CONSTRUCTED AS FOLLOWS DEPENDING UPON LENGTH

OF NEED:

A. 1 DAY MAXIMUM - PLASTIC

B. 1 WEEK MAXIMUM - FLAME-RETARDANT PLASTIC

C. GREATER THAN 1 WEEK - SEE NOTE B AND C.

B. TEMPORARY CONSTRUCTION BARRIERS SHALL BE 3 5/8" METAL

STUDS @ 16" O.C. WITH 5/8" TYPE "X" GYP. BD. EACH SIDE. BARRIERS

ARE TO EXTEND TO THE BOTTOM OF EXISTING CEILINGS. PROVIDE

NON-DAMAGING SEAL AT INTERSECTION WITH CEILING. PROVIDE

PLASTIC SHEET BARRIER SEAL BETWEEN TOP OF WALL AND

STRUCTURE ABOVE. TAPE ALL SEAMS AND PENETRATION

OPENINGS TO PREVENT CONTAMINATION FROM PASSING OVER THE

TOP OR UNDERNEATH THE WALL FROM CONSTRUCTION AREAS.

C. TEMPORARY CONSTRUCTION BARRIERS SHALL BE EITHER TYPE I

OR TYPE II. TYPE I BARRIERS SHALL BE ANCHORED TO THE

FLOORING SURFACE (WHICH IS INTENDED TO BE REPLACED) WITH

POWER ACTUATED FASTENERS. TYPE II BARRIERS SHALL BE

ANCHORED TO THE FLOORING SURFACE (WHICH IS INTENDED TO

REMAIN) BY TAPING BOTTOM STUD TRACK TO FLOOR SURFACE OR

BY OTHER METHODS WHICH WILL NOT HARM FLOOR SURFACE.

D. TEMPORARY PARTITIONS SHALL NOT CONSTRICT WALKWAYS TO

LESS THAN 42" CLEAR. ANY EXITS CHANGED OR BLOCKED SIGNAGE

NEEDS TO BE POSTED FOR THE MODIFICATIONS.

E. PROVIDE TEMPORARY RATED DOOR AND FRAME IN CONSTRUCTION

BARRIER AT ENTRY POINTS TO THE CONSTRUCTION AREAS.

DOORS ARE TO REMAIN LOCKED AT ALL TIMES. CONSTRUCTION

CORES WILL BE PROVIDED BY THE VA.

TEMPORARY CONSTRUCTION

FLOOR PLAN LEGEND

NOT INCLUDED IN SCOPE OF WORK

EXISTING ROOM

NEW ADDITION / RENOVATED SPACE

/AE2-102 5

TR

DATA

/AE2-102 3

/AE2-102 4

/AE2-102 2

TR

214B

TR

202C

TR ZONE 1

TR ZONE 2

/AE2-103 4

TELECOM

/AE2-103 3

TR

339A

TR

/AE2-103 2

TR ZONE 1

TR ZONE 2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861 design group

MES GROUP, INC

550 North Reo Street Tampa, FL, 33609 813-289-4700 David Keith

KEY PLAN NTSKEY PLAN NTS VA_LAKEMONT

LAKEMONT, ORLANDO VA MEDICAL CENTER,

2500 S LAKEMONT AVE, ORLANDO FL 32814

ZONE 1

ZONE 2

C U s e rs \a d m in \D o c u m e n ts \6

-2

-7

L A

K E

M O

N T

E

H R

M

R E

V

IT

c c h a n g V

Z R

C

.r v t

/5

/2

:4

:0

P M

AE2-100

LAKEMONT PHASING / TR ZONE 675-22-706B

ALL

JUNE 07, 2024 AESUS AESUS

EHRM INFRASTRUCTURE UPGRADES

VA_LAKEMONT

FINAL SUBMITTAL

1/32" = 1'-0"1 LAKEMONT - 1ST FLOOR TR ZONE

N

1/16" = 1'-0" GRAPHIC SCALE

8' 16' 48'32'

1/32" = 1'-0"2 LAKEMONT 2ND FLOOR TR ZONE

1/32" = 1'-0"3 LAKEMONT 3RD FLOOR TR ZONE

N

1/16" = 1'-0" GRAPHIC SCALE

8' 16' 48'32' N

1/16" = 1'-0" GRAPHIC SCALE

8' 16' 48'32'

Revisions: Date:

STAMP

OR

LA

NDO

ER I K GONZALES

PRO F E S S I ONA L ENG

I N

SOCIAL WORK

PAYROLL/TRAVEL

HBPC

SECURITY

SUPPLY

TRAINING/CONFERENCE ROOM

TROA

CAP

VA POLICE CHIEF

DATA CENTER

MAILROOM

MEDICAL

IRMS

BIO-MED

LOGISTICS

LEO & LARRY

SUPPLY IRMS

CHIEF

DEPUTY

IRMS

CONTRACTING

EDUCATION

RESEARCH

CONTRACTING

RECORDS

MEDICAL

RECORDS

LEARNING EXCHANGE

EMPLOYEE AND

LABOR RELATIONS

LOGISTICS

ROOM

EEO

VA

POLICE

TRAVEL

CHIEF

VA POLICE

ADMIN.

TRAINING ROOM

LOUNGE /VENDING

SUPPLY

ROOM

DATA CENTER

COMM

MEN

WOMEN

STOR

STOR

ASST. POLICE

MECH

ELECT

MECH

MECH OFF.

MECH

117C

117B

117A

119A

119B

116B

136 134

116A

125A

XXX

XXX

XXX

XXX

103B 103A 105A

109B

109A

CR

CR

A

B

C

D

F

F.3

G

F.6

G.4

J

K

M

N

P

Q

H

L

E

1 2 3 4 5 6 6.3 7 8 9 10 11 12 13 14

TR

138A

ELEC

/AE2-101 3

/AE2-101 2

/AE2-101 4

TR

105A

TR

123B

/AE2-101 5

3 3

3 3

3 3

6.3

ELEC

D

TR

138A

J

H

TR

105A

A

A3

A

TR

123B

B

A

9A3

11 12

123A

FLOOR PLAN SYMBOLS

DEMOLITION

EXISITNG WALL

NEW WALL

CONTRACT LIMIT LINE

COLUMN CENTER LINE

EXISTING DATA DROP

NEW DATA DROP

EXISTING TR, COMM,

DATA, OR ELEC. RM

PROPOSED TR

LOCATION

RM 123

RM 123A

N

1/16" = 1'-0" GRAPHIC SCALE

8' 16' 48'32'

1. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPAL AREAS AND LIMITS OF

CONSTRUCTION WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT.

WORK MUST BE ACCOMPLISHED IN AREAS NOT SHOWN ON ARCHITECTURAL

DRAWINGS DUE TO CHANGES AFFECTING ELECTRICAL, MECHANICAL, PLUMBING AND

TECHNOLOGY ALONG WITH OTHER SYSTEMS. THIS WORK SHALL BE PART OF THIS

CONTRACT, AND ALL TRADES SHALL INSPECT THESE AREAS, ASCERTAIN WORK

REQUIRED AND DO THE WORK IN ACCORDANCE OF CONTRACT REQUIREMENTS AT NO

ADDITIONAL COST. SEE MECHANICAL, ELECTRICAL, PLUMBING AND TECHNOLOGY

PLANS FOR ADDITIONAL WORK. NO EXISTING PLUMBING PIPING SHALL BE LOCATED

ABOVE ANY NEW OR RENOVATED TR SPACE.

2. CONTRACTORS SHALL VISIT THE SITE DURING BIDDING TO BECOME FAMILIAR WITH

THE EXISTING CONDITIONS. THE GENERAL CONTRACTOR SHALL LOCATE, INSPECT

AND FIELD VERIFYALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS PRIOR TO

DEMOLITION AND CONSTRUCTION. NOTIFY ARCHITECT IMMEDIATELY OF ANY

DISCREPANCIES

3. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.

4. WHEREVER OPENINGS ARE CUT THROUGH FIRE RATED PARTITIONS, IT SHALL BE THE

RESPONSIBILITY OF THE CONTRACTOR FOR WHOM THE HOLE IS CUT TO PATCH AND

REPAIR ANY OPENING TO MAINTAIN THE INTEGRITY OF THE FIRE RATING.

5. GENERAL CONTRACTOR TO CHECK MECHANICAL DRAWINGS FOR EXISTING PIPES AND

DUCTSFURRED IN WALLS. VERIFY SIZE AND LOCATION WITH MECHANICAL

CONTRACTOR PRIOR TO PROCEEDING WITH REMODELING.

6. FIREPROOFING SHALL BE UNPIERCED. ANY SUBCONTRACTOR PENETRATING THE

FIREPROOFING SHALL BE REQUIRED TO REPLACE FIREPROOFING TO THE ORIGINAL

CONDITION AND FIRE RATING, AT THE SUBCONTRACTORS EXPENSE.

7. EQUIPMENT UNIT DIMENSIONS ARE FOR PRODUCT DESCRIPTION ONLY, VERIFY SIZE

WITH MANUFACTURER.

8. ALL DIMENSIONS PERTAINING TO MECHANICAL OR ELECTRICAL SERVICES OR

EQUIPMENT SHALL BE VERIFIED WITH THE RESPECTIVE TRADE.

9. ALL CONTRACTORS THAT PENETRATE AND/OR DISTURB ANY AREAS AT EXISTING

CONDITIONS SHALL PATCH AREA TO MATCH EXISTING ADJACENT AREA OR SURFACE

AND PREPARE FOR SCHEDULED FINISH APPLICATION. COORDINATE WORK WITH

GENERAL CONTRACTOR PRIOR TO PROCEEDING.

10. VERIFY HEIGHTS AND LOCATIONS OF ACCESS PANELS (AP) AND COORDINATE TYPES

WITH TRADES WHICH REQUIRE THEM.

11. PROVIDE LINTELS AND FRAMING FOR GRILLES, LOUVERS, AND ROOF VENTS AS

REQUIRED BY MECHANICAL CONTRACTOR, VERIFY SIZE AND LOCATION.

12. STRUCTURAL, MECHANICAL, AND ELECTRICAL ABBREVIATIONS AND SYMBOLS MAY

DIFFER FROM ARCHITECTURAL. SEE RESPECTIVE SECTIONS AND/OR DRAWINGS FOR

DEFINITIONS.

13. AT MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, PROVIDE 3/4" FRT PLYWOOD

BACKING BEHIND ALL SURFACE MOUNTED FIXTURES AND EQUIPMENT, UNLESS NOTED

OTHERWISE.

14. CONTRACTOR SHALL EVALUATE INTEGRITY OF ALL PARTITIONS INDICATED BY

SYMBOLS ON THE LIFE SAFETY PLAN(S) WITHIN THE PROJECT SCOPE AND UPGRADE

AS REQUIRED. ALL FIRE RESISTIVE RATED WALLS SHALL BE CONSTRUCTED OF

MATERIALS / ASSEMBLIES MEETING THE RATING INDICATED, TERMINATE AT THE DECK

ABOVE WITH A TESTED HEAD OF WALL ASSEMBLY AND ALL PENETRATIONS SHALL BE

SEALED WITH A TESTED ASSEMBLY. ALL SMOKE PARTITIONS SHALL BE CONSTRUCTED

OF MATERIALS THAT RESIST THE PASSAGE OF SMOKE, TERMINATE AT THE DECK

ABOVE WITH A JOINT SEALED WITH FIRE CAULK AND ALL PENETRATIONS SHALL BE

SEALED WITH FIRE CAULK.

15. THE GC SHALL MODIFY AND RELOCATE EXISTING AREA DRAINS AS REQUIRED TO

INSTALL BUILDING FOUNDATIONS.

GENERAL NOTES

FLOOR PLAN KEYNOTES

1 EXISTING ELEC. ROOM TO REMAIN. SEE MPE FOR ADDITIONAL INFO.

2 EXISTING TR TO REMAIN FUNCTIONAL UNTIL THE NEW TR IS CONSTRUCTED. SEE

MPE FOR ADDITIONAL INFO.

3 THE GC SHALL REMOVE, PATCH AND REPAIR THE EXISTING WALL AND CEILING AS

REQUIRED TO INSTALL A NEW DATA DROP IN THE VICINITY OF THE EXISTING DATA

DROP, TYPICAL. THE NEW DATA DROP SHALL BE LOCATED AT THE SAME HEIGHT OF

EXISTING. ONCE ALL END USER DEVICES ARE FULLY FUNCTIONAL, THE GENERAL

CONTRACTOR CAN PROCEED TO SCHEDULE THE REMOVAL OF ALL NON USED

DATA PORT WIRING BACK TO THE SOURCE. AT EACH LOCATION WHERE THE

WIRING IS REMOVED, A SOLID FACE PLATE SHALL BE INSTALLED. NOTE, NOT ALL

DEVICES ARE IDENTIFIED BY A KEYNOTE.

4 REMOVE AND REINSTALL EXISTING CEILING AS REQUIRED FOR NEW CAMERA

INSTALLATION. VERIFY EXACT CAMERA LOCATION WITH COR. ALL PENETRATIONS

SHALL BE SEALED TO MATCH EXISTING RATING AND FINISH TYPICAL.

5 NEW KEYPAD / CARD READER, TYPICAL. REMOVE, PATCH AND REPAIR WALL AS

REQUIRED FOR INSTALLATION. SEE ELECTRICAL FOR ADDITIONAL INFO.

6 DEMOLISH EXISTING BASE AND FLOOR FINISH, TYPICAL.

7 RE-INSTALL SALVAGED DOOR.

8 NEW DOOR AND FRAME, SEE SCHEDULE.

9 PATCH AND REPAIR ADJACENT WALL, BASE, AND CEILINGS AS REQUIRED.

10 REMOVE EXISTING WALL FOR NEW DOOR OPENING. PATCH AND REPAIR ADJACENT

WALL AND BASE.

11 DEMOLISH EXISTING CEILING, LIGHTS, DIFFUSERS, LOW VOLTAGE DEVICES AND

ASSOCIATED COMPONENTS, TYPICAL.

12 ALL WALLS IN THIS ROOM SHALL RECEIVE 3/4" FRT PLYWOOD BACKING, UNLESS

NOTED OTHERWISE. PAINT ALL PLYWOOD SURFACES TO MATCH ADJACENT WALL.

13 NEW EQUIPMENT TYPICAL, SEE MPE FOR ADDITIONAL INFO.

14 DEMOLISH EXISTING WALL AND BASE FOR NEW DOOR OPENING.

15 REMOVE AND SALVAGE DOOR, FRAME, AND HARDWARE. RETURN TO OWNER.

16 DEMOLISH EXISTING WALL AND BASE, TYPCIAL.

1/16" = 1'-0"1 LAKEMONT 1ST FLOOR PLAN

1/4" = 1'-0"2 LAKEMONT - 131 (E) ELECT. RM

1/4" = 1'-0"3 LAKEMONT - 138A (E) TR

1/4" = 1'-0"4 LAKEMONT - 105A (N) TR

1/4" = 1'-0"5 LAKEMONT - 123B (N) TR

N

N

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861 design group

MES GROUP, INC

550 North Reo Street Tampa, FL, 33609 813-289-4700 David Keith

KEY PLAN NTSKEY PLAN NTS VA_LAKEMONT

LAKEMONT, ORLANDO VA MEDICAL CENTER,

2500 S LAKEMONT AVE, ORLANDO FL 32814

ZONE 1

ZONE 2

C U s e rs \a d m in \D o c u m e n ts \6

-2

-7

L A

K E

M O

N T

E

H R

M

R E

V

IT

c c h a n g V

Z R

C

.r v t

/5

/2

:4

:0

P M

AE2-101

LAKEMONT 1ST FLOOR PLAN 675-22-706B

ALL

JUNE 07, 2024 AESUS AESUS

EHRM INFRASTRUCTURE UPGRADES

VA_LAKEMONT

FINAL SUBMITTAL

1/4" = 1'-0"6 LAKEMONT - 123 - DEMO

Revisions: Date:

STAMP

OR

LA

NDO

ER I K GONZALES

PRO F E S S I ONA L ENG

I N

HUMAN RESOURCES

IRMS

CONTRACTING OFFICE

PEOSTRI

PEOSTRI

MEDICAL

ARMY

HUMAN RESOURCES

SERVICES

CAC

OFFICE SUPPLIES

TRAINING RM.-A

TRAINING RM.-B

IRMS

OFFICE

SECURITY

OFFICE

ACTIVATIONS

CONFERENCE

TELECARE

TELEHEALTH

TELECARE

TELECARE

RECORDS

NURSING

EDUCATION

INTERIOR DESIGN

219C

219B

219A

217A

217B

217C

215C

215B

215A

202B

202A

DATA

REHAB

MECH

ADMIN.

HEALTH

HAS

COMM

ELECT

XXX

XXX

OFFICE

OFFICEOFFICE

OFFICE

221A

221B221C221D221E221F

230A

230B

MECH

214A

INFORMATICS

CLINICAL

206C

206B

206A

204C

204B

204A

LEARNING

EXCHANGE

VISN

LEARNING

EXCHANGE

VISN

LEARNING

EXCHANGE

VISN

LEARNING

EXCHANGE

VISN

LEARNING

EXCHANGE

VISN

EXCHANGE

VISN

202AC

R

C R

A

B

C

D

F

F.3

G

F.6

G.4

J

K

M

N

P

Q

H

L

E

1 2 3 4 5 6 6.3 7 8 9 10 11 12 13 14

/AE2-102 5

TR

DATA

/AE2-102 3

/AE2-102 4

/AE2-102 2

TR

214B

2 2

2 2 2

2 2

2 2 2

2 2

2 2 2 2

TR

202C

M

L

TR

202C

GYM

202A

202C

A

C

TR

214B

A3

214B 6

C

D

TR

M

L

DATA

FLOOR PLAN SYMBOLS

DEMOLITION

EXISITNG WALL

NEW WALL

CONTRACT LIMIT LINE

COLUMN CENTER LINE

EXISTING DATA DROP

NEW DATA DROP

EXISTING TR, COMM,

DATA, OR ELEC. RM

PROPOSED TR

LOCATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861 design group

MES GROUP, INC

550 North Reo Street Tampa, FL, 33609 813-289-4700 David Keith

KEY PLAN NTSKEY PLAN NTS VA_LAKEMONT

LAKEMONT, ORLANDO VA MEDICAL CENTER,

2500 S LAKEMONT AVE, ORLANDO FL 32814

ZONE 1

ZONE 2

C U s e rs \a d m in \D o c u m e n ts \6

-2

-7

L A

K E

M O

N T

E

H R

M

R E

V

IT

c c h a n g V

Z R

C

.r v t

/5

/2

:4

:0

P M

AE2-102

LAKEMONT 2ND FLOOR PLANS 675-22-706B

ALL

JUNE 07, 2024 AESUS AESUS

EHRM INFRASTRUCTURE UPGRADES

VA_LAKEMONT

FINAL SUBMITTAL

1/16" = 1'-0" GRAPHIC SCALE

8' 16' 48'32'

N

FLOOR PLAN KEYNOTES

1 EXISTING TR TO REMAIN FUNCTIONAL UNTIL THE NEW TR IS CONSTRUCTED. SEE

MPE FOR ADDITIONAL INFO.

2 THE GC SHALL REMOVE, PATCH AND REPAIR THE EXISTING WALL AND CEILING AS

REQUIRED TO INSTALL A NEW DATA DROP IN THE VICINITY OF THE EXISTING DATA

DROP, TYPICAL. THE NEW DATA DROP SHALL BE LOCATED AT THE SAME HEIGHT OF

EXISTING. ONCE ALL END USER DEVICES ARE FULLY FUNCTIONAL, THE GENERAL

CONTRACTOR CAN PROCEED TO SCHEDULE THE REMOVAL OF ALL NON USED

DATA PORT WIRING BACK TO THE SOURCE. AT EACH LOCATION WHERE THE

WIRING IS REMOVED, A SOLID FACE PLATE SHALL BE INSTALLED. NOTE, NOT ALL

DEVICES ARE IDENTIFIED BY A KEYNOTE.

3 NEW KEYPAD / CARD READER, TYPICAL. REMOVE, PATCH AND REPAIR WALL AS

REQUIRED FOR INSTALLATION. SEE ELECTRICAL FOR ADDITIONAL INFO.

4 REMOVE AND REINSTALL EXISTING CEILING AS REQUIRED FOR NEW CAMERA

INSTALLATION. VERIFY EXACT CAMERA LOCATION WITH COR. ALL PENETRATIONS

SHALL BE SEALED TO MATCH EXISTING RATING AND FINISH TYPICAL.

5 DEMOLISH EXISTING BASE AND FLOOR FINISH, TYPICAL.

6 NEW DOOR AND FRAME, SEE SCHEDULE.

7 PATCH AND REPAIR ADJACENT WALL, BASE, AND CEILINGS AS REQUIRED.

8 RE-INSTALL SALVAGED DOOR.

9 REMOVE EXISTING WALL FOR NEW DOOR OPENING. PATCH AND REPAIR ADJACENT

WALL AND BASE.

10 EXISTING DATA ROOM TO REMAIN. SEE MPE FOR ADDITIONAL INFO.

11 ALL WALLS IN THIS ROOM SHALL RECEIVE 3/4" FRT PLYWOOD BACKING, UNLESS

NOTED OTHERWISE. PAINT ALL PLYWOOD SURFACES TO MATCH ADJACENT WALL.

12 NEW EQUIPMENT TYPICAL, SEE MPE FOR ADDITIONAL INFO.

13 DEMOLISH EXISTING CEILING, LIGHTS, DIFFUSERS, LOW VOLTAGE DEVICES AND

ASSOCIATED COMPONENTS, TYPICAL.

14 REMOVE EXISTING DOOR FRAME AND INFILL WALL. MATCH EXISTING ADJACENT

FINISH, TYPICAL.

1/16" = 1'-0"1 LAKEMONT 2ND FLOOR PLAN

1/4" = 1'-0"2 LAKEMONT - 202C (N) TR

1/4" = 1'-0"3 LAKEMONT - 214B (N) TR

1/4" = 1'-0"4 LAKEMONT - 203 (E) TR

1/4" = 1'-0"5 LAKEMONT - 202 (E) DATA RM

N

N

NN

1. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPAL AREAS AND LIMITS OF

CONSTRUCTION WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT.

WORK MUST BE ACCOMPLISHED IN AREAS NOT SHOWN ON ARCHITECTURAL

DRAWINGS DUE TO CHANGES AFFECTING ELECTRICAL, MECHANICAL, PLUMBING AND

TECHNOLOGY ALONG WITH OTHER SYSTEMS. THIS WORK SHALL BE PART OF THIS

CONTRACT, AND ALL TRADES SHALL INSPECT THESE AREAS, ASCERTAIN WORK

REQUIRED AND DO THE WORK IN ACCORDANCE OF CONTRACT REQUIREMENTS AT NO

ADDITIONAL COST. SEE MECHANICAL, ELECTRICAL, PLUMBING AND TECHNOLOGY

PLANS FOR ADDITIONAL WORK. NO EXISTING PLUMBING PIPING SHALL BE LOCATED

ABOVE ANY NEW OR RENOVATED TR SPACE.

2. CONTRACTORS SHALL VISIT THE SITE DURING BIDDING TO BECOME FAMILIAR WITH

THE EXISTING CONDITIONS. THE GENERAL CONTRACTOR SHALL LOCATE, INSPECT

AND FIELD VERIFYALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS PRIOR TO

DEMOLITION AND CONSTRUCTION. NOTIFY ARCHITECT IMMEDIATELY OF ANY

DISCREPANCIES

3. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.

4. WHEREVER OPENINGS ARE CUT THROUGH FIRE RATED PARTITIONS, IT SHALL BE THE

RESPONSIBILITY OF THE CONTRACTOR FOR WHOM THE HOLE IS CUT TO PATCH AND

REPAIR ANY OPENING TO MAINTAIN THE INTEGRITY OF THE FIRE RATING.

5. GENERAL CONTRACTOR TO CHECK MECHANICAL DRAWINGS FOR EXISTING PIPES AND

DUCTSFURRED IN WALLS. VERIFY SIZE AND LOCATION WITH MECHANICAL

CONTRACTOR PRIOR TO PROCEEDING WITH REMODELING.

6. FIREPROOFING SHALL BE UNPIERCED. ANY SUBCONTRACTOR PENETRATING THE

FIREPROOFING SHALL BE REQUIRED TO REPLACE FIREPROOFING TO THE ORIGINAL

CONDITION AND FIRE RATING, AT THE SUBCONTRACTORS EXPENSE.

7. EQUIPMENT UNIT DIMENSIONS ARE FOR PRODUCT DESCRIPTION ONLY, VERIFY SIZE

WITH MANUFACTURER.

8. ALL DIMENSIONS PERTAINING TO MECHANICAL OR ELECTRICAL SERVICES OR

EQUIPMENT SHALL BE VERIFIED WITH THE RESPECTIVE TRADE.

9. ALL CONTRACTORS THAT PENETRATE AND/OR DISTURB ANY AREAS AT EXISTING

CONDITIONS SHALL PATCH AREA TO MATCH EXISTING ADJACENT AREA OR SURFACE

AND PREPARE FOR SCHEDULED FINISH APPLICATION. COORDINATE WORK WITH

GENERAL CONTRACTOR PRIOR TO PROCEEDING.

10. VERIFY HEIGHTS AND LOCATIONS OF ACCESS PANELS (AP) AND COORDINATE TYPES

WITH TRADES WHICH REQUIRE THEM.

11. PROVIDE LINTELS AND FRAMING FOR GRILLES, LOUVERS, AND ROOF VENTS AS

REQUIRED BY MECHANICAL CONTRACTOR, VERIFY SIZE AND LOCATION.

12. STRUCTURAL, MECHANICAL, AND ELECTRICAL ABBREVIATIONS AND SYMBOLS MAY

DIFFER FROM ARCHITECTURAL. SEE RESPECTIVE SECTIONS AND/OR DRAWINGS FOR

DEFINITIONS.

13. AT MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, PROVIDE 3/4" FRT PLYWOOD

BACKING BEHIND ALL SURFACE MOUNTED FIXTURES AND EQUIPMENT, UNLESS NOTED

OTHERWISE.

14. CONTRACTOR SHALL EVALUATE INTEGRITY OF ALL PARTITIONS INDICATED BY

SYMBOLS ON THE LIFE SAFETY PLAN(S) WITHIN THE PROJECT SCOPE AND UPGRADE

AS REQUIRED. ALL FIRE RESISTIVE RATED WALLS SHALL BE CONSTRUCTED OF

MATERIALS / ASSEMBLIES MEETING THE RATING INDICATED, TERMINATE AT THE DECK

ABOVE WITH A TESTED HEAD OF WALL ASSEMBLY AND ALL PENETRATIONS SHALL BE

SEALED WITH A TESTED ASSEMBLY. ALL SMOKE PARTITIONS SHALL BE CONSTRUCTED

OF MATERIALS THAT RESIST THE PASSAGE OF SMOKE, TERMINATE AT THE DECK

ABOVE WITH A JOINT SEALED WITH FIRE CAULK AND ALL PENETRATIONS SHALL BE

SEALED WITH FIRE CAULK.

15. THE GC SHALL MODIFY AND RELOCATE EXISTING AREA DRAINS AS REQUIRED TO

INSTALL BUILDING FOUNDATIONS.

GENERAL NOTES

Revisions: Date:

STAMP

OR

LA

NDO

ER I K GONZALES

PRO F E S S I ONA L ENG

I N

309308

348 352

304 305

BREAK A

REA

CONF.

RM.

PANEL

CONF.

RM.

TRAINING ROOM

BULK STORAGE

IT STORAGE

OPEN

OFFICE

MAILROOM

CASH

MANAGEMENT

MECHANICAL ROOM

CONFERENCE ROOM

COO

CFO

HR

ISO

WAITING

JANITOR CLOSET

MECHANICAL ROOM

OFFICE

CONFERENCE ROOM UNION

OFFICE

E

LE

V

OFFICE

E

LE

V

CORRIDOR

LOBBY

CORRIDOR

C O

R R

ID

O

R

C O

R R

ID

O

R

CORRIDOR

C O

R R

ID

O

R

EXECUTIVE SUITE

CORRIDOR

TRAINING ROOM

TRAINING ROOM

TELEPHONE RISER

C O

R R

ID

O

R C

O R

R

ID

O R

C O

R R

ID

O

R

OPEN OFFICE

OPEN OFFICE

OPEN OFFICE OPEN OFFICE

OPEN OFFICE

SPRINKLER RISER

OPEN OFFICE

OPEN OFFICE

OPEN OFFICE

OFFICE

CONFERENCE ROOM

F

IR

E E

Q U

IP

. C

LO

S

E T

CONFERENCE ROOM

IT OFFICE

VENDING

MEN'S ROOM

LADIES' ROOM

CORRIDOR

DIRECTOR

OFFICE

IT DEPARTMENT

337A

IT WORK

CR CR

C R

A

B

C

D

F

F.3

G

F.6

G.4

J

K

M

N

P

Q

H

L

E

1 2 3 4 5 6 6.3 7 8 9 10 11 12 13 14

/AE2-103 4

TELECOM

315/AE2-103 3

TR

339A

TR

/AE2-103 2

M

L

TR

339A

A

A

IT / Storage

D

TR

D

TELECOM

FLOOR PLAN SYMBOLS

DEMOLITION

EXISITNG WALL

NEW WALL

CONTRACT LIMIT LINE

COLUMN CENTER LINE

EXISTING DATA DROP

NEW DATA DROP

EXISTING TR, COMM,

DATA, OR ELEC. RM

PROPOSED TR

LOCATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861 design group

MES GROUP, INC

550 North Reo Street Tampa, FL, 33609 813-289-4700 David Keith

KEY PLAN NTSKEY PLAN NTS VA_LAKEMONT

LAKEMONT, ORLANDO VA MEDICAL CENTER,

2500 S LAKEMONT AVE, ORLANDO FL 32814

ZONE 1

ZONE 2

C U s e rs \a d m in \D o c u m e n ts \6

-2

-7

L A

K E

M O

N T

E

H R

M

R E

V

IT

c c h a n g V

Z R

C

.r v t

/5

/2

:4

:0

P M

AE2-103

LAKEMONT 3RD FLOOR PLANS 675-22-706B

ALL

JUNE 07, 2024 AESUS AESUS

EHRM INFRASTRUCTURE UPGRADES

VA_LAKEMONT

FINAL SUBMITTAL

1/16" = 1'-0" GRAPHIC SCALE

8' 16' 48'32'

N

FLOOR PLAN KEYNOTES

1 EXISTING DATA ROOM TO REMAIN FUNCTIONAL UNTIL THE NEW TR IS

CONSTRUCTED. SEE MPE FOR ADDITIONAL INFO.

2 NEW KEYPAD / CARD READER, TYPICAL. REMOVE, PATCH AND REPAIR WALL AS

REQUIRED FOR INSTALLATION. SEE ELECTRICAL FOR ADDITIONAL INFO.

3 REMOVE AND REINSTALL EXISTING CEILING AS REQUIRED FOR NEW CAMERA

INSTALLATION. VERIFY EXACT CAMERA LOCATION WITH COR. ALL PENETRATIONS

SHALL BE SEALED TO MATCH EXISTING RATING AND FINISH TYPICAL.

4 NEW DOOR AND FRAME, SEE SCHEDULE.

5 ALL WALLS IN THIS ROOM SHALL RECEIVE 3/4" FRT PLYWOOD BACKING, UNLESS

NOTED OTHERWISE. PAINT ALL PLYWOOD SURFACES TO MATCH ADJACENT WALL.

6 DEMOLISH EXISTING CEILING, LIGHTS, DIFFUSERS, LOW VOLTAGE DEVICES AND

ASSOCIATED COMPONENTS, TYPICAL.

7 REMOVE EXISTING WALL FOR NEW DOOR OPENING. PATCH AND REPAIR ADJACENT

WALL AND BASE.

8 MODIFY EXISTING RAISED FLOOR AT NEW WALL LOCATION, TYPICAL.

9 EXISTING RAISED FLOOR TO REMAIN.

10 DEMOLISH EXISTING BASE AND FLOOR FINISH, TYPICAL.

11 REMOVE AND SALVAGE DOOR, FRAME, AND HARDWARE. RETURN TO OWNER.

12 NEW EQUIPMENT TYPICAL, SEE MPE FOR ADDITIONAL INFO.

13 INFILL OPENING WITH METAL STUDS AND DRYWALL. MATCH EXISTING ADJACENT

FINISH, TYPICAL.

14 NEW WALL AND BASE TO MATCH ADJACENT, TYPICAL.

15 REMOVE EXISTING DOOR, SIDE LITE, AND TRANSOM. RETURN TO OWNER FOR

RE-USE. INFILL WALL TO MATCH EXISTING ADJACENT.

1/16" = 1'-0"1 LAKEMONT 3RD FLOOR PLAN

1/4" = 1'-0"2 LAKEMONT - 339 (N) TR

1/4" = 1'-0"3 LAKEMONT - 353 (N) TR

1/4" = 1'-0"4 LAKEMONT - 315 (E) TELECOM. RM

N

N N

1. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPAL AREAS AND LIMITS OF

CONSTRUCTION WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT.

WORK MUST BE ACCOMPLISHED IN AREAS NOT SHOWN ON ARCHITECTURAL

DRAWINGS DUE TO CHANGES AFFECTING ELECTRICAL, MECHANICAL, PLUMBING AND

TECHNOLOGY ALONG WITH OTHER SYSTEMS. THIS WORK SHALL BE PART OF THIS

CONTRACT, AND ALL TRADES SHALL INSPECT THESE AREAS, ASCERTAIN WORK

REQUIRED AND DO THE WORK IN ACCORDANCE OF CONTRACT REQUIREMENTS AT NO

ADDITIONAL COST. SEE MECHANICAL, ELECTRICAL, PLUMBING AND TECHNOLOGY

PLANS FOR ADDITIONAL WORK. NO EXISTING PLUMBING PIPING SHALL BE LOCATED

ABOVE ANY NEW OR RENOVATED TR SPACE.

2. CONTRACTORS SHALL VISIT THE SITE DURING BIDDING TO BECOME FAMILIAR WITH

THE EXISTING CONDITIONS. THE GENERAL CONTRACTOR SHALL LOCATE, INSPECT

AND FIELD VERIFYALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS PRIOR TO

DEMOLITION AND CONSTRUCTION. NOTIFY ARCHITECT IMMEDIATELY OF ANY

DISCREPANCIES

3. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.

4. WHEREVER OPENINGS ARE CUT THROUGH FIRE RATED PARTITIONS, IT SHALL BE THE

RESPONSIBILITY OF THE CONTRACTOR FOR WHOM THE HOLE IS CUT TO PATCH AND

REPAIR ANY OPENING TO MAINTAIN THE INTEGRITY OF THE FIRE RATING.

5. GENERAL CONTRACTOR TO CHECK MECHANICAL DRAWINGS FOR EXISTING PIPES AND

DUCTSFURRED IN WALLS. VERIFY SIZE AND LOCATION WITH MECHANICAL

CONTRACTOR PRIOR TO PROCEEDING WITH REMODELING.

6. FIREPROOFING SHALL BE UNPIERCED. ANY SUBCONTRACTOR PENETRATING THE

FIREPROOFING SHALL BE REQUIRED TO REPLACE FIREPROOFING TO THE ORIGINAL

CONDITION AND FIRE RATING, AT THE SUBCONTRACTORS EXPENSE.

7. EQUIPMENT UNIT DIMENSIONS ARE FOR PRODUCT DESCRIPTION ONLY, VERIFY SIZE

WITH MANUFACTURER.

8. ALL DIMENSIONS PERTAINING TO MECHANICAL OR ELECTRICAL SERVICES OR

EQUIPMENT SHALL BE VERIFIED WITH THE RESPECTIVE TRADE.

9. ALL CONTRACTORS THAT PENETRATE AND/OR DISTURB ANY AREAS AT EXISTING

CONDITIONS SHALL PATCH AREA TO MATCH EXISTING ADJACENT AREA OR SURFACE

AND PREPARE FOR SCHEDULED FINISH APPLICATION. COORDINATE WORK WITH

GENERAL CONTRACTOR PRIOR TO PROCEEDING.

10. VERIFY HEIGHTS AND LOCATIONS OF ACCESS PANELS (AP) AND COORDINATE TYPES

WITH TRADES WHICH REQUIRE THEM.

11. PROVIDE LINTELS AND FRAMING FOR GRILLES, LOUVERS, AND ROOF VENTS AS

REQUIRED BY MECHANICAL CONTRACTOR, VERIFY SIZE AND LOCATION.

12. STRUCTURAL, MECHANICAL, AND ELECTRICAL ABBREVIATIONS AND SYMBOLS MAY

DIFFER FROM ARCHITECTURAL. SEE RESPECTIVE SECTIONS AND/OR DRAWINGS FOR

DEFINITIONS.

13. AT MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, PROVIDE 3/4" FRT PLYWOOD

BACKING BEHIND ALL SURFACE MOUNTED FIXTURES AND EQUIPMENT, UNLESS NOTED

OTHERWISE.

14. CONTRACTOR SHALL EVALUATE INTEGRITY OF ALL PARTITIONS INDICATED BY

SYMBOLS ON THE LIFE SAFETY PLAN(S) WITHIN THE PROJECT SCOPE AND UPGRADE

AS REQUIRED. ALL FIRE RESISTIVE RATED WALLS SHALL BE CONSTRUCTED OF

MATERIALS / ASSEMBLIES MEETING THE RATING INDICATED, TERMINATE AT THE DECK

ABOVE WITH A TESTED HEAD OF WALL ASSEMBLY AND ALL PENETRATIONS SHALL BE

SEALED WITH A TESTED ASSEMBLY. ALL SMOKE PARTITIONS SHALL BE CONSTRUCTED

OF MATERIALS THAT RESIST THE PASSAGE OF SMOKE, TERMINATE AT THE DECK

ABOVE WITH A JOINT SEALED WITH FIRE CAULK AND ALL PENETRATIONS SHALL BE

SEALED WITH FIRE CAULK.

15. THE GC SHALL MODIFY AND RELOCATE EXISTING AREA DRAINS AS REQUIRED TO

INSTALL BUILDING FOUNDATIONS.

GENERAL NOTES

Revisions: Date:

STAMP

OR

LA

NDO

ER I K GONZALES

PRO F E S S I ONA L ENG

I N

EXP

EXP

/AE2-201 2

/AE2-201 3

REFLECTED CEILING PLAN

GENERAL NOTES

A. THE GC SHALL VISIT THE SITE PRIOR TO BIDDING TO

BETTER UNDERSTAND THE EXISTING CONDITIONS,

TYPICAL.

B. IN THE CASE OF MINOR DISCREPANCIES BETWEEN MEP

AND ARCHITECTURAL DOCUMENTS IN THE LOCATION

OF CEILING MOUNTED COMPONENTS, THE

ARCHITECTURAL REFLECTED CEILING PLAN SHALL

GOVERN. IN THE CASE OF MAJOR DISCREPANCIES, THE

ARCHITECT SHALL BE NOTIFIED AS SOON AS THE

DISCREPANCY IS DISCOVERED PRIOR TO PROCEEDING

WITH THE WORK.

C. REFERENCE MECHANICAL AND ELECTRICAL DRAWINGS

FOR MOUNTING LOCATIONS OF ITEMS WHERE NO

CEILING IS REQUIRED OR INDICATED.

D. LIGHTS, DIFFUSERS, EXIT SIGNS, SMOKE DETECTORS,

SPEAKERS, STROBES, AND MISCELLANEOUS DEVICES

SHALL BE REMOVED AND RE-INSTALLED AS REQUIRED

TO INSTALL THE NEW CABLE TRAY, SEE MPE FOR

ADDITIONAL INFO.

E. ALL CORRIDOR SPRINKLER HEADS SHALL REMAIN

UNDISTURBED IN THE CORRIDOR UNLESS NOTED

OTHERWISE.

F. ACCESS DOOR LOCATIONS IN GYPSUM BOARD

CEILINGS ARE INDICATED ON RCP'S ONLY WHERE

ARCHITECTURALLY SIGNIFICANT. REFERENCE

SPECIFICATIONS AND MEP DRAWINGS FOR OTHER

ACCESS DOOR LOCATIONS.

G. EXIT SIGNS ARE SHOWN ON REFLECTED CEILING PLAN

ONLY WHERE LOCATION IS ARCHITECTURAL

SIGNIFICANT.

H. AT NEW DUCTWORK IN EXISTING CEILING TO REMAIN.

REMOVE AND SALVAGE CEILING GRID, CEILING TILES,

AND CEILING FIXTURES. REINSTALL IN PLACE, PATCH

AND REPAIR AS REQUIRED.

CEILING SYMBOLS

GYP BD CEILING

SUPPLY AIR

RETURN AIR

ACCESS PANEL

FLUORESCENT LIGHT

EXHAUST AIR

ACOUSTIC CEILING TILE

(SEE CEILING TYPE

LEGEND)

EXIT SIGNS - HATCH

INDICATES EXIT TEXT AND

ARROW INDICATES

DIRECTION

WALL MOUNTED LIGHT

FIXTURE

DOWNLIGHT

STRIP LIGHT

SUSPENDED LIGHT

RECESSED ROLLER SHADE

A.F.F.1'-0"

CEILING HEIGHT ABOVE

FINISH FLOOR

NO CEILING, EXPOSED TO

STRUCTURE / DECK ABOVE

EXP

EXP

EXP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861 design group

MES GROUP, INC

550 North Reo Street Tampa, FL, 33609 813-289-4700 David Keith

KEY PLAN NTSKEY PLAN NTS VA_LAKEMONT

LAKEMONT, ORLANDO VA MEDICAL CENTER,

2500 S LAKEMONT AVE, ORLANDO FL 32814

ZONE 1

ZONE 2

C U s e rs \a d m in \D o c u m e n ts \6

-2

-7

L A

K E

M O

N T

E

H R

M

R E

V

IT

c c h a n g V

Z R

C

.r v t

/5

/2

:4

:0

P M

AE2-201

LAKEMONT 1ST FLOOR RCP 675-22-706B

ALL

JUNE 07, 2024 AESUS AESUS

EHRM INFRASTRUCTURE UPGRADES

VA_LAKEMONT

FINAL SUBMITTAL

1/16" = 1'-0"1 LAKEMONT 1ST FLOOR RCP

N

1/16" = 1'-0" GRAPHIC SCALE

8' 16' 48'32'

RCP KEYNOTES

1/4" = 1'-0"2 RM 123 ENLARGED DEMO RCP

1/4" = 1'-0"3 RM 105 ENLARGED DEMO RCP

1/4" = 1'-0"4 TR 105A ENLARGED RCP

1/4" = 1'-0"5 TR 138A ENLARGED RCP

Revisions: Date:

STAMP

OR

LA

NDO

ER I K GONZALES

PRO F E S S I ONA L ENG

I N

112.5 sf

117 sf

427.8 sf

MEN

WOMEN

HUMAN RESOURCES

IRMS

CONTRACTING OFFICE

PEOSTRI

PEOSTRI

MEDICAL

ARMY

HUMAN RESOURCES

SERVICES

CAC

OFFICE SUPPLIES

TRAINING RM.-A

TRAINING RM.-B

IRMS

OFFICE

SECURITY

OFFICE

ACTIVATIONS

CONFERENCE

TELECARE

TELEHEALTH

TELECARE

TELECARE

RECORDS

NURSING

EDUCATION

INTERIOR DESIGN

219C

219B

219A

217A

217B

217C

215C

215B

215A

202B

202A

DATA

REHAB

MECH

ADMIN.

HEALTH

HAS

COMM

ELECT

XXX

XXX

OFFICE

OFFICEOFFICE

OFFICE

221A

221B221C221D221E221F

230A

230B

MECH

214A

INFORMATICS

CLINICAL

206C

206B

206A

204C

204B

204A

LEARNING

EXCHANGE

VISN

LEARNING

EXCHANGE

VISN

LEARNING

EXCHANGE

VISN

LEARNING

EXCHANGE

VISN

LEARNING

EXCHANGE

VISN

EXCHANGE

VISN

REFLECTED CEILING PLAN

GENERAL NOTES

A. THE GC SHALL VISIT THE SITE PRIOR TO BIDDING TO

BETTER UNDERSTAND THE EXISTING CONDITIONS,

TYPICAL.

B. IN THE CASE OF MINOR DISCREPANCIES BETWEEN MEP

AND ARCHITECTURAL DOCUMENTS IN THE LOCATION

OF CEILING MOUNTED COMPONENTS, THE

ARCHITECTURAL REFLECTED CEILING PLAN SHALL

GOVERN. IN THE CASE OF MAJOR DISCREPANCIES, THE

ARCHITECT SHALL BE NOTIFIED AS SOON AS THE

DISCREPANCY IS DISCOVERED PRIOR TO PROCEEDING

WITH THE WORK.

C. REFERENCE MECHANICAL AND ELECTRICAL DRAWINGS

FOR MOUNTING LOCATIONS OF ITEMS WHERE NO

CEILING IS REQUIRED OR INDICATED.

D. LIGHTS, DIFFUSERS, EXIT SIGNS, SMOKE DETECTORS,

SPEAKERS, STROBES, AND MISCELLANEOUS DEVICES

SHALL BE REMOVED AND RE-INSTALLED AS REQUIRED

TO INSTALL THE NEW CABLE TRAY, SEE MPE FOR

ADDITIONAL INFO.

E. ALL CORRIDOR SPRINKLER HEADS SHALL REMAIN

UNDISTURBED IN THE CORRIDOR UNLESS NOTED

OTHERWISE.

F. ACCESS DOOR LOCATIONS IN GYPSUM BOARD

CEILINGS ARE INDICATED ON RCP'S ONLY WHERE

ARCHITECTURALLY SIGNIFICANT. REFERENCE

SPECIFICATIONS AND MEP DRAWINGS FOR OTHER

ACCESS DOOR LOCATIONS.

G. EXIT SIGNS ARE SHOWN ON REFLECTED CEILING PLAN

ONLY WHERE LOCATION IS ARCHITECTURAL

SIGNIFICANT.

H. AT NEW DUCTWORK IN EXISTING CEILING TO REMAIN.

REMOVE AND SALVAGE CEILING GRID, CEILING TILES,

AND CEILING FIXTURES. REINSTALL IN PLACE, PATCH

AND REPAIR AS REQUIRED.

CEILING SYMBOLS

GYP BD CEILING

SUPPLY AIR

RETURN AIR

ACCESS PANEL

FLUORESCENT LIGHT

EXHAUST AIR

ACOUSTIC CEILING TILE

(SEE CEILING TYPE

LEGEND)

EXIT SIGNS - HATCH

INDICATES EXIT TEXT AND

ARROW INDICATES

DIRECTION

WALL MOUNTED LIGHT

FIXTURE

DOWNLIGHT

STRIP LIGHT

SUSPENDED LIGHT

RECESSED ROLLER SHADE

A.F.F.1'-0"

CEILING HEIGHT ABOVE

FINISH FLOOR

NO CEILING, EXPOSED TO

STRUCTURE / DECK ABOVE

EXP

EXP

EXP

/AE2-202 4

/AE2-202 5

EXP

EXP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861 design group

MES GROUP, INC

550 North Reo Street Tampa, FL, 33609 813-289-4700 David Keith

KEY PLAN NTSKEY PLAN NTS VA_LAKEMONT

LAKEMONT, ORLANDO VA MEDICAL CENTER,

2500 S LAKEMONT AVE, ORLANDO FL 32814

ZONE 1

ZONE 2

C U s e rs \a d m in \D o c u m e n ts \6

-2

-7

L A

K E

M O

N T

E

H R

M

R E

V

IT

c c h a n g V

Z R

C

.r v t

/5

/2

:4

:1

P M

AE2-202

LAKEMONT 2ND FLOOR RCP 675-22-706B

ALL

JUNE 07, 2024 AESUS AESUS

EHRM INFRASTRUCTURE UPGRADES

VA_LAKEMONT

FINAL SUBMITTAL

1/16" = 1'-0"1 LAKEMONT 2ND FLOOR RCP

1/16" = 1'-0" GRAPHIC SCALE

8' 16' 48'32'

N

RCP KEYNOTES

1/4" = 1'-0"2 RM 214A ENLARGED DEMO RCP

1/4" = 1'-0"3 RM 202A ENLARGED DEMO RCP

1/4" = 1'-0"4 TR 214B ENLARGED RCP

1/4" = 1'-0"5 TR 202C ENLARGED RCP

Revisions: Date:

STAMP

OR

LA

NDO

ER I K GONZALES

PRO F E S S I ONA L ENG

I N

309308

348 352

304 305

BREAK A

REA

CONF.

RM.

PANEL

CONF.

RM.

TRAINING ROOM

BULK STORAGE

IT STORAGE

OPEN

OFFICE

MAILROOM

CASH

MANAGEMENT

MECHANICAL ROOM

CONFERENCE ROOM

COO

CFO

HR

ISO

WAITING

JANITOR CLOSET

MECHANICAL ROOM

OFFICE

CONFERENCE ROOM UNION

OFFICE

E

LE

V

OFFICE

E

LE

V

CORRIDOR

LOBBY

CORRIDOR

C O

R R

ID

O

R

C O

R R

ID

O

R

CORRIDOR

C O

R R

ID

O

R

EXECUTIVE SUITE

CORRIDOR

TRAINING ROOM

TRAINING ROOM

TELEPHONE RISER

C O

R R

ID

O

R C

O R

R

ID

O R

C O

R R

ID

O

R

OPEN OFFICE

OPEN OFFICE

OPEN OFFICE OPEN OFFICE

OPEN OFFICE

SPRINKLER RISER

OPEN OFFICE

OPEN OFFICE

OPEN OFFICE

OFFICE

CONFERENCE ROOM

F

IR

E E

Q U

IP

. C

LO

S

E T

CONFERENCE ROOM

IT OFFICE

VENDING

MEN'S ROOM

LADIES' ROOM

CORRIDOR

DIRECTOR

IT DEPARTMENT

337A

IT WORK

EXP

EXP

/AE2-203 4

/AE2-203 5

REFLECTED CEILING PLAN

GENERAL NOTES

A. THE GC SHALL VISIT THE SITE PRIOR TO BIDDING TO

BETTER UNDERSTAND THE EXISTING CONDITIONS,

TYPICAL.

B. IN THE CASE OF MINOR DISCREPANCIES BETWEEN MEP

AND ARCHITECTURAL DOCUMENTS IN THE LOCATION

OF CEILING MOUNTED COMPONENTS, THE

ARCHITECTURAL REFLECTED CEILING PLAN SHALL

GOVERN. IN THE CASE OF MAJOR DISCREPANCIES, THE

ARCHITECT SHALL BE NOTIFIED AS SOON AS THE

DISCREPANCY IS DISCOVERED PRIOR TO PROCEEDING

WITH THE WORK.

C. REFERENCE MECHANICAL AND ELECTRICAL DRAWINGS

FOR MOUNTING LOCATIONS OF ITEMS WHERE NO

CEILING IS REQUIRED OR INDICATED.

D. LIGHTS, DIFFUSERS, EXIT SIGNS, SMOKE DETECTORS,

SPEAKERS, STROBES, AND MISCELLANEOUS DEVICES

SHALL BE REMOVED AND RE-INSTALLED AS REQUIRED

TO INSTALL THE NEW CABLE TRAY, SEE MPE FOR

ADDITIONAL INFO.

E. ALL CORRIDOR SPRINKLER HEADS SHALL REMAIN

UNDISTURBED IN THE CORRIDOR UNLESS NOTED

OTHERWISE.

F. ACCESS DOOR LOCATIONS IN GYPSUM BOARD

CEILINGS ARE INDICATED ON RCP'S ONLY WHERE

ARCHITECTURALLY SIGNIFICANT. REFERENCE

SPECIFICATIONS AND MEP DRAWINGS FOR OTHER

ACCESS DOOR LOCATIONS.

G. EXIT SIGNS ARE SHOWN ON REFLECTED CEILING PLAN

ONLY WHERE LOCATION IS ARCHITECTURAL

SIGNIFICANT.

H. AT NEW DUCTWORK IN EXISTING CEILING TO REMAIN.

REMOVE AND SALVAGE CEILING GRID, CEILING TILES,

AND CEILING FIXTURES. REINSTALL IN PLACE, PATCH

AND REPAIR AS REQUIRED.

CEILING SYMBOLS

GYP BD CEILING

SUPPLY AIR

RETURN AIR

ACCESS PANEL

FLUORESCENT LIGHT

EXHAUST AIR

ACOUSTIC CEILING TILE

(SEE CEILING TYPE

LEGEND)

EXIT SIGNS - HATCH

INDICATES EXIT TEXT AND

ARROW INDICATES

DIRECTION

WALL MOUNTED LIGHT

FIXTURE

DOWNLIGHT

STRIP LIGHT

SUSPENDED LIGHT

RECESSED ROLLER SHADE

A.F.F.1'-0"

CEILING HEIGHT ABOVE

FINISH FLOOR

NO CEILING, EXPOSED TO

STRUCTURE / DECK ABOVE

EXP

EXP

EXP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: