ATTACHMENT 17 - SEED 3_PROJECT 619A4-25-102_PIC BOOK 100 FINAL.pdf

PDF 13 MB Posted

Attached to
VISN 7 CONSTRUCTION MATOC 36C24726R0026 - SOLICITATION
Solicitation number
36C24726R0026
Issued by

About this file

This is a Picture Book (survey documentation) that catalogues egress door deficiencies identified at the Tuskegee Veterans Affairs Medical Center in Tuskegee, Alabama, as part of Project No. 619A4-25-102 under Contract No. 36C24724C0050. The document, prepared by Beaufort Engineering Services Inc. and submitted in September 2024, contains photographs and detailed inspection data for doors across twelve buildings (Buildings 2, 3, 3A, 4, 4A, 5, 13, 14, 15, 65, 68, 83, 88, 93, and 129).

The inspection tabulates deficiencies across multiple categories including missing or improperly painted door/frame labels, damaged doors or frames, clearance violations, malfunctioning closing devices, missing coordinators, broken hardware, unlabeled glazing and fire exit hardware, and improper smoke detector placement. Doors are categorized by required fire rating (90-minute, 45-minute, 20-minute, and non-rated), with a total inventory spanning mechanical room doors, stairwell doors, and perimeter doors. Each door entry documents dimensions, location, current condition, deficiency type, wall material (CMU, brick, concrete, etc.), and specific comments noting issues such as automatic doors, double doors, glass doors, missing smoke ratings, and structural concerns. The picture book provides photographic evidence for all documented deficiencies, serving as a comprehensive baseline assessment for the correction of egress door code violations at this VA medical facility.

View the file

Other files

File Type Posted
36C24726R0026 0013.pdf PDF
Seed 2_Project 557-20-101_27 10 00_Update Structured Cabling.pdf PDF
RFI LOG AMENDMENT 0012_ SEED 3.pdf PDF
36C24726R0026 0010.pdf PDF
SEED 1_PROJECT 534-23-910 INFECTION CONTROL DETAILS.pdf PDF
SEED 1_PROJECT 534-23-910 INFECTION CONTROL RISK ASSESSMENT.pdf PDF
36C24726R0026 0009.pdf PDF
ATTACHMENT 18 - SEED 3 WAGE DETERMINATION TUSKEGEE AL20260078 5 18 2026.pdf PDF
36C24726R0026 0007.pdf PDF
RFI LOG AMENDMENT 0007_Seed 3 - 619A4-25-102.pdf PDF
Seed 3_ 619A4-25-102 - Correct Egress Door Deficiencies Final Drawings.pdf PDF
Seed 2_557-20-101 - Project Bldg 5 As-Builts.pdf PDF
36C24726R0026 0006.pdf PDF
RFI LOG AMENDMENT 0006_SEED 2-557-20-101.pdf PDF
Seed 2_557-20-101 -GEHC-SP_REVAPEX_6-120F.pdf PDF
Seed 2_557-20-101 - Persona RF PREMIUM Brochure Fuji.pdf PDF
Seed 2_557-20-101 -Cardiac_D-Spect Specs.pdf PDF
Seed 2_557.20-101 - REVIT and CAD Screenshot.docx DOCX document
Seed 2_557-20-101 -5418654-1EN Rev 22.pdf PDF
Seed 2_557-20-101 -GEHC-SP_SIGNA-VOYAGER_8-278F.pdf PDF
Seed 2_557-20-101 - 2024-06-19_SD Rpt_ GC85A_Physicist Rp.pdf PDF
Seed 2_557-20-101 -HME_DR_GM85_Datasheet_v42_230209_FDA.pdf PDF
Seed 2_557-20-101 -Typical - Symbia Intevo Bold.pdf PDF
078400-Rev 2.pdf PDF
36C24726R0026 0005.pdf PDF
RFI 182 PICS.docx DOCX document
534-23-910 VA Charleston Stairwells Restrooms and Doors - Revision 1- A101-A601.pdf PDF
534-23-910 VA Charleston Stairwells Restrooms and Doors - Revision 1-Demolition pages.pdf PDF
36C24726R0026 0003.pdf PDF
534-23-910 VA Charleston Stairwells Restrooms and Doors - Revision 1- General pages.pdf PDF
534-23-910 - Environmental Survey Report.pdf PDF
Seed 1 - 534-23-910 Site Visit Attendance Roster_4 21 26.pdf PDF
Seed 2 - 557-20-101 Site Visit Attendance Roster_4 22 26.pdf PDF
NCS-VISN 7-MATOC-SEED 2-RFI 1 - 2 A600.pdf PDF
Seed 3 - 619A4-25-102 Site Visit Attendance Roster_4 23 26.pdf PDF
36C24726R0026 0002.pdf PDF
ATTACHMENT 8R - SEED 1_PROJECT 534-23-910_SPECIFICATIONS REV 4.pdf PDF
ATTACHMENT 10 - SEED 1_ PROJECT 534-23-910_ FINAL CONSTRUCTION DOCUMENTS VOL II.pdf PDF
ATTACHMENT 13 - SEED 2_PROJECT 557-20-101 DRAWINGS.pdf PDF
ATTACHMENT 14 - SEED 2_WAGE DETERMINATION GA20260095 01 23 26.pdf PDF
ATTACHMENT 18 - SEED 3_ WAGE DETERMINATION AL20260098 01 02 26.pdf PDF
36C24726R0026_VISN 7 CONSTRUCTION MATOC.pdf PDF
ATTACHMENT 4 - SUBCONTRACTOR CONSENT FOR PAST PERFORMANCE.docx DOCX document
ATTACHMENT 5 - EXPERIENCE MODIFICATION RATE FORM.docx DOCX document
ATTACHMENT 11 - SEED 1_WAGE DETERMINATION SC20260023 01 02 26.pdf PDF
ATTACHMENT 15 - SEED 3_PROJECT 619A4-25-102_SPECS 100 FINAL rev1.pdf PDF
ATTACHMENT 1 - CONTRACTOR EXPERIENCE FORM.docx DOCX document
ATTACHMENT 2 - CONTRACTOR SURETY LIMITATION.docx DOCX document
ATTACHMENT 7 - ITEMIZED COST BREAKDOWN.xlsx XLSX spreadsheet
ATTACHMENT 19 - VAAR 852.219-75 VA Notice of Limitations on Subcontracting Jan 2023 Deviation.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Beaufort Engineering Services Inc | 766 MIDDLE STREET, FAIRHOPE, AL 36532 | PHONE: 251.990.5778

Survey Pictures Prepared For

521-24-135

Correct Egress Door Deficiencies

Tuskegee Veterans Affairs Medical Center Tuskegee, AL

CONTRACT # 36C24724C0050

Project No. 619A4-25-102

Submittal Date: September 2024

FINAL SUBMISSION

Door Location Door Width Door Height Required Rating

Provided Rating No Door Label

Door Label Painted

Door Damaged

Bottom Clearance

Exceeds 3/4"

Top and/or Vertical

Clearances Exceeds 3/16"

Missing Closing Device

Closing Device Not

Working Properly

Door is Provided with Chock

Door Does Not Latch Properly

Coordinator Not Installed

Broken Coordinator

No Frame Label

Painted Frame Label

Damaged Frame

Fire Exit Hardware

Not Labeled

Glazing Not

Labeled

Missing Screw on

Hinge

Edge Protection

Added

Smoke Detector Exceeds Allowable Distance from Door

Wall Material

Comments

02-B-01 STAIRS SB-7 3'-8'' 7' 90 90 X X X X X CMU

02-B-02 STAIRS SB-6 3'-8'' 7' 90 90 X X X CMU

02-B-03 CORR. C-2 WEST 3'-8'' 7' 90 90 X X

02-B-04 MECH. RM. 8 4'-0'' 6'-8'' 180 180 X X CMU

02-B-05 MECH. RM. 5 5'-0'' D 7' 45 X X X X X X X X X

02-1-01 STAIRS S1-6 3'-8'' 7' 90 90 X X X CMU

02-1-02 CORR. WEST-S 3'-6'' 7' --- X X X CMU GLASS DOOR

02-1-03 CORR. C-1 WEST 5'-0'' D 6'-8'' 20 X X CMU

02-1-04 CORR. C-1 WEST 3'-8'' 7' 90 90 DINGED X X

02-1-05 MUSEUM 104 CORR 5'-4'' D 7' 20 20 X X LOC X X GLASS/WOOD DOOR

02-1-06 MUSEUM 104 EXT 3'-6'' 7' --- X X X X CMU

02-1-07 STAIRS S1-7 3'-8'' 7' 90 90 X X CMU

02-1-08 CORR. EAST-S 3'-6'' 7' --- X X X X CMU GLASS DOOR

02-1-09 CORR. EAST-N 3'-8'' 7' 20 X X X

02-1-10 CORR. EAST-N 3'-4'' 7' 20 X X X

02-2-01 STAIRS S2-7 3'-8'' 7' 90 90 X X CMU

02-2-02 CORR. C-5 4'-6'' D 7' 20 X X X

02-2-03 STAIRS S2-6 3'-8'' 7' 90 90 X X CMU

02-2-04 CORR. C-4 WEST 3'-8'' 7' 90 90 X X X CMU

02-3-01 CORR. C-8 WEST 3'-8'' 7' 20 X X X X X

02-3-02 STAIRS S3-6 3'-8'' 7' 90 90 X X X CMU

02-3-03 CORR. C-9 4'-6'' D 7' 20 X X X

02-3-04 STAIRS S3-7 3'-8'' 7' 90 90 CMU BOT. OF DOOR DRAGS

02-3-05 CORR. C-10 3'-0'' 7' 20 20 X X X

02-3-06 CORR. RCC301R 3'-0'' 7' 20 X X X X X

02-3-07 CORR. RCC301R 3'-0'' 7' 20 20 X X X

LEGEND Door Counts Mechanical Room Doors 90 minute 11

Stairwell Doors 45 minute 1 Perimeter Doors 20 minute 10

No Work Not Rated 3 Special Frame 180 minute 1

Final Submission September 2024

BUILDING 2

DOOR 02-B-01 DOOR 02-B-02

DOOR 02-B-03 DOOR 02-B-04

DOOR 02-B-05

DOOR 02-1-01 DOOR 02-1-02

DOOR 02-1-03 DOOR 02-1-04

DOOR 02-1-05 DOOR 02-1-06

DOOR 02-1-07 DOOR 02-1-08

DOOR 02-1-09 DOOR 02-1-10

Sheet 9 of 11

DOOR 02-2-01 DOOR 02-2-02

Sheet 10 of 11

DOOR 02-2-03 DOOR 02-2-04

Sheet 11 of 11

DOOR 02-3-01 DOOR 02-3-02

Sheet 12 of 11

DOOR 02-3-03 DOOR 02-3-04

Sheet 13 of 11

DOOR 02-3-05 DOOR 02-3-06

Sheet 14 of 11

DOOR 02-3-07

Provided Rating No Door Label

Door Label Painted

Door Damaged

Bottom Clearance

Exceeds 3/4"

Top and/or Vertical

Clearances Exceeds 3/16"

Missing Closing Device

Closing Device Not

Working Properly

Door is Provided with Chock

Door Does Not Latch Properly

Coordinator Not Installed

Broken Coordinator

No Frame Label

Painted Frame Label

Damaged Frame

Fire Exit Hardware

Not Labeled

Glazing Not

Labeled

Missing Screw on

Hinge

Edge Protection

Added

Smoke Detector Exceeds Allowable Distance from Door

Wall Material

Comments

03-B-01 CORR. @ BLDG. 2 3'-8'' 6'-8'' 90 90 X X X X X CMU

03-B-02 PUMP ROOM 3'-0'' 6'-8'' 20 X X X X CMU

03-B-03 CORR. @ BLDG. 4A 3'-8'' 7' 90 90 X X CMU

03-1-01 CORR. RCC109R 7'-4'' D 7' 90 90 X CMU

03-1-02 CORR. RCC110R 6'-8'' D 7' 20 X X X X X

03-1-03 STAIR RCC111R 3'-10'' 7' 90 90 X X X CMU

03-1-04 STAIR RCC111R 3'-10'' 7' 90 90 X X CMU

03-1-05 CORR. RCC112R 3'-8'' 7' 20 X X X X

03-1-06 STAIR RCC111R 3'-6'' 6'-8'' 90 X X X X X X CMU

03-1-07 CORR. RCC108R 3'-8'' 7' 90 90 X X X X CMU

03-1-08 CORR. RCC107R 3'-6'' 7' 20 X X X X X X X

03-1-09 STAIR RCC106R 3'-10'' 7' 90 90 X X X CMU

03-1-10 STAIR RCC106R 3'-10'' 7' 90 90 X CMU

03-1-11 STAIR RCC106R 3'-6'' 6'-4'' --- X X X CMU

03-2-01 STAIR RCC208R 3'-10'' 7' 90 90 X X X X CMU

03-2-02 STAIR RCC208R 3'-10'' 7' 90 90 X CMU HOLD OPEN BROKEN

03-2-03 CORR. RCC209R 3'-8'' 7' 20 X X X X X

03-2-04 CORR. RCC201R 6'-8'' D 7' 20 X X X

03-2-05 CORR. RCC211R 3'-6'' 7' 20 X X X X

03-2-06 STAIR RCC212R 3'-10'' 7' 90 90 X CMU

03-2-07 STAIR RCC212R 3'-10'' 7' 90 90 X X CMU

03-2-08 CORR. RCC210R 3'-8'' 7' 90 90 X X X CMU

03-3-01 CORR. RCC311R 3'-8'' 7' 90 90 X X X X X CMU

03-3-02 CORR. RCC310R 6'-0'' D 7' 20 20 X X X COORD. WORKS

03-3-03 CORR. 312 6'-0'' D 7' 20 X X X X

03-3-04 CORR. 312 3'-10'' 7' 20 X X X X X CMU

03-3-05 STAIR RCC309R 3'-10'' 7' 90 90 X X X CMU

03-3-06 STAIR RCC309R 3'-10'' 7' 90 90 X X CMU

03-3-07 CORR. RCC312R 6'-8'' D 7' 20 X X X X X X

03-3-08 CORR. RCC304R 6'-0'' D 7' 20 90 X X X X

03-3-09 STAIR RCC313R 3'-10'' 7' 90 90 X X X X CMU

03-3-10 STAIR RCC313R 3'-10'' 7' 90 90 X X X X CMU

03-3-11 CORR. RCC314R 3'-6'' 7' 20 90 X X X X NO SMOKE

LEGEND Door Counts Mechanical Room Doors 90 minute 19

Stairwell Doors 45 minute 0 Perimeter Doors 20 minute 13

No Work Not Rated 1 Special Frame

Sheet 1 of 11

BUILDING 3

DOOR 03-B-01 DOOR 03-B-02

Sheet 2 of 11

DOOR 03-B-03

Sheet 3 of 11

DOOR 03-1-01 DOOR 03-1-02

Sheet 4 of 11

DOOR 03-1-03 DOOR 03-1-04

Sheet 5 of 11

DOOR 03-1-05 DOOR 03-1-06

Sheet 6 of 11

DOOR 03-1-07 DOOR 03-1-08

Sheet 7 of 11

DOOR 03-1-09 DOOR 03-1-10

Sheet 8 of 11

DOOR 03-1-11

DOOR 03-2-01 DOOR 03-2-02

DOOR 03-2-03 DOOR 03-2-04

DOOR 03-2-05 DOOR 03-2-06

DOOR 03-2-07 DOOR 03-2-08

DOOR 03-3-01 DOOR 03-3-02

DOOR 03-3-03 DOOR 03-3-04

Sheet 15 of 11

DOOR 03-3-05 DOOR 03-3-06

Sheet 16 of 11

DOOR 03-3-07 DOOR 03-3-08

Sheet 17 of 11

DOOR 03-3-09 DOOR 03-3-10

Sheet 18 of 11

DOOR 03-3-11

Provided Rating No Door Label

Door Label Painted

Door Damaged

Bottom Clearance

Exceeds 3/4"

Top and/or Vertical

Clearances Exceeds 3/16"

Missing Closing Device

Closing Device Not

Working Properly

Door is Provided with Chock

Door Does Not Latch Properly

Coordinator Not Installed

Broken Coordinator

No Frame Label

Painted Frame Label

Damaged Frame

Fire Exit Hardware

Not Labeled

Glazing Not

Labeled

Missing Screw on

Hinge

Edge Protection

Added

Smoke Detector Exceeds Allowable Distance from Door

Wall Material

Comments

3A-B-01 CORR. BC-1 TO 120 7'-4'' D 7' 90 90 X X X CMU

3A-B-02 CORR. BC-2A 6'-0'' D 7' 90 90 X X X X CMU

3A-B-03 CORR. BC-2 EXT. 3'-0'' 7' 90 90 X X X CMU

3A-B-04 HOSP. REC. COMM 5'-0'' D 7' 90 180 X X NO LATCH X LOC X X CMU AUTOMATIC DOOR 3A-B-05 HOSP. REC. COMM 5'-0'' D 7' 20 X X X X NO LATCH X X X X X X CMU AUTOMATIC DOOR

3A-B-06 STAIR RCCB10R 3'-8'' 7' 90 X X X X CMU

3A-B-07 STAIR RCCB12R 3'-8'' 7' 90 X X X X CMU

3A-B-08 STAIR RCCB12R 3'-0'' 7' 90 X X X X X X CMU

3A-B-09 REC./CLEANUP 13 4'-0'' 7' 90 CMU ASK LES

3A-B-10 AUTOPSY 7A 5'-0'' D 7' 20 X X X X X CMU DBL. DOOR

3A-B-11 AUTOPSY 7D 3'-0'' 7' 20 X X X X X

3A-B-12 MECH RM. 9 3'-0'' 7' 45 X X X X X X NO SMOKE

3A-1-01 VEST. RCC104R 7'-4'' D 7' 90 90 X X X CMU

3A-1-02 CORR. COMM. C-1 7'-4'' D 7' 90 90 X X CMU

3A-1-03 CORR. COMM. C-2 W. 3'-10'' 7' 90 90 X CMU

3A-1-04 STAIR RCC114R 3'-8'' 7' 90 90 X CMU

3A-1-05 CORR. COMM. 119 3'-8'' 7' 90 90 X CMU

3A-1-06 CORR. COMM. C-2 E. 3'-8'' 7' 20 X X X X

3A-1-07 CORR. COMM. C-2 N. 7'-4'' D 7' 20 20 X X X

3A-1-08 STAIR RCC112R 3'-8'' 7' 90 X X X CMU

3A-1-09 STAIR S1-4 3'-8'' 7' 90 90 X CMU MAGNETIC LOCK, REPLACE DOOR/FRAME

3A-1-10 STAIR S1-4 EXT. 3'-8'' 7' 90 X X CMU REPLACE DOOR

3A-1-11 CORR. PHARMACY 3'-8'' 7' 20 X X X X X X NO SMOKE

3A-2-01 STAIR S2-10 3'-8'' 7' 90 90 X X X CMU

3A-2-02 STAIR S2-10 3'-8'' 7' 90 X X X CMU

3A-2-03 CORR. RCC213R 6'-0'' D 7' 90 90 X X X CMU LEFT DOOR STICKS

3A-2-04 CORR. RCC201R 3'-8'' 7' 20 X X X X X X X

3A-2-05 STAIR S2-4 3'-8'' 7' 90 X X X X CMU

3A-2-06 CORR. RCC210R S. 6'-8'' D 6'-8'' 90 90 X X X X CMU

3A-2-07 STAIR RCC208R 3'-8'' 7' 90 90 X X X CMU

3A-2-08 MECH. RM. 242 3'-0'' 7' 45 20 X X NEEDS DOOR STOP (LOUD)

3A-3-01 STAIR S3-10 3'-8'' 7' 90 90 X X X CMU

3A-3-02 CORR. RCC305R 3'-8'' 7' 20 X X X X

3A-3-03 STAIR RCC303R 3'-8'' 7' 90 90 X X X X CMU

3A-3-04 CORR. RCC304R N. 7'-4'' D 7' 90 90 X CMU

3A-3-05 STAIR S3-10 3'-8'' 7' 90 90 X X X CMU

3A-3-06 CORR. RCC307R E. 6'-8'' D 6'-8'' 20 X X X X X

3A-3-07 CORR. RCC308R E. 3'-8'' 7' 90 90 X X X CMU

3A-3-08 ENT. COMM. RCC302R 7'-4'' D 7' 90 90 X X X X X CMU

3A-3-09 STAIR S3-4 3'-8'' 7' 90 90 X X X X CMU

3A-4-01 CORR. W402/P460 7'-0'' D 7' 20 20 X X

3A-4-02 STAIR D463 3'-8'' 7' 90 90 X X X X CMU

3A-4-03 CORR. COMM. P462 7'-4'' D 7' 90 90 X X CMU

3A-4-04 STAIR S159 3'-8'' 7' 90 90 X X X CMU

3A-4-05 CORR. COMM. D434 7'-0'' D 7' 20 20 X X

3A-4-06 CORR. COMM. D436 3'-8'' 7' 20 X X X X

3A-4-07 STAIR S160 3'-8'' 7' 90 X X X X CMU

3A-4-08 CORR. COMM. D437 7'-4'' D 7' 90 90 X X X X X CMU

LEGEND Door Counts Mechanical Room Doors 90 minute 34

Stairwell Doors 45 minute 2 Perimeter Doors 20 minute 12

No Work Not Rated 0

BUILDING 3A

DOOR 3A-B-01 DOOR 3A-B-02

DOOR 3A-B-03 DOOR 3A-B-04

DOOR 3A-B-05 DOOR 3A-B-06

DOOR 3A-B-07 DOOR 3A-B-08

DOOR 3A-B-09 DOOR 3A-B-10

DOOR 3A-B-11 DOOR 3A-B-12

DOOR 3A-1-01 DOOR 3A-1-02

DOOR 3A-1-03 DOOR 3A-1-04

DOOR 3A-1-05 DOOR 3A-1-06

DOOR 3A-1-07 DOOR 3A-1-08

DOOR 3A-1-09 DOOR 3A-1-10

DOOR 3A-1-11

DOOR 3A-2-01 DOOR 3A-2-02

DOOR 3A-2-03 DOOR 3A-2-04

DOOR 3A-2-05 DOOR 3A-2-06

DOOR 3A-2-07 DOOR 3A-2-08

DOOR 3A-3-01 DOOR 3A-3-02

DOOR 3A-3-03 DOOR 3A-3-04

Sheet 19 of 11

DOOR 3A-3-05 DOOR 3A-3-06

Sheet 20 of 11

DOOR 3A-3-07 DOOR 3A-3-08

Sheet 21 of 11

DOOR 3A-3-09

Sheet 22 of 11

DOOR 3A-4-01 DOOR 3A-4-02

Sheet 23 of 11

DOOR 3A-4-03 DOOR 3A-4-04

Sheet 24 of 11

DOOR 3A-4-05 DOOR 3A-4-06

Sheet 25 of 11

DOOR 3A-4-07 DOOR 3A-4-08

Provided Rating No Door Label

Door Label Painted

Door Damaged

Bottom Clearance

Exceeds 3/4"

Top and/or Vertical

Clearances Exceeds 3/16"

Missing Closing Device

Closing Device Not

Working Properly

Door is Provided with Chock

Door Does Not Latch Properly

Coordinator Not Installed

Broken Coordinator

No Frame Label

Painted Frame Label

Damaged Frame

Fire Exit Hardware

Not Labeled

Glazing Not

Labeled

Missing Screw on

Hinge

Edge Protection

Added

Smoke Detector Exceeds Allowable Distance from Door

Wall Material

Comments

04-B-01 CORR. G27/G41 6'-0'' D 7' 20 20 X X X X

04-B-02 STAIR SB-4 3'-8'' 7' 90 90 COVERED X X CMU

04-B-03 MEDIA G39 3'-6'' 7' 20 X X X LOC X X

04-B-04 CORR. G41 EXT. 3'-4'' 7' 20 HIDDEN COVERED X

MOVED NOW 04-1-12 CMU REPLACE

04-B-06 CORR. COMM. G20 6'-0'' D 7' 45 45 X

04-B-07 MECH. RM. G40 3'-0'' 7' 45 45 X X

04-1-01 STAIR S1-4 3'-0'' 6'-7'' 90 90 X X X CMU

04-1-02 STAIR S1-4 EXT. 3'-6'' 6'-4'' 90 90 X LOC X X CMU

04-1-03 CORR. RCC121R 3'-10'' 7' 90 90 X X X CMU

04-1-04 CORR. RCC120R E. 3'-10'' 7' 90 90 X X X CMU

04-1-05 CORR. RCC120R W. 3'-8'' 7' 20 20 X X X X X X

04-1-06 CORR. RCC119R EXT. 3'-8'' 7' 90 90 X CMU

04-1-07 CORR. COMM. 126 3'-8'' 7' 20 X X ? LOC

04-1-08 CORR. RCC118R 3'-0'' 7' --- X X X

04-1-09 STAIR S1-5 3'-10'' 7' 90 X COV X CMU

04-1-10 STAIR S1-5 EXT. 3'-6'' 7' --- X LOC X CMU GLASS DOOR

04-1-11 STAIR S1-5 3'-10'' 7' 90 X X X X X CMU

04-1-12 STAIR S1-5 3'-0'' 7' 90

04-2-01 CORR. RCC203C/208R 3'-8'' 7' 90 90 X X CMU

04-2-02 STAIR S2-4 3'-10'' 7' 90 90 X X X CMU

04-2-03 STAIR S2-4 3'-10'' 7' 90 90 X X X CMU

04-2-04 IMAGING WAITING 201 4'-0'' 7' 90 90 X X CMU

04-2-05 IMAGING WAITING 201 4'-0'' 7' 20 20 X

04-2-06 STAIR S2-5 3'-8'' 7' 90 X X X X X X CMU

04-3-01 STAIR S3-5 3'-10'' 7' 90 90 X X X CMU

04-3-02 STAIR S3-5 3'-10'' 7' 90 90 X X X CMU

04-3-03 CORR. RCC301R 6'-8'' D 7' 90 90 X CMU

04-3-04 CORR. RCC301R 3'-8'' 7' 90 90 X X X CMU

04-3-05 CORR. COMM. C-7 6'-0'' D 7' 20 X X X

04-3-06 CORR. COMM. C-9 6'-0'' D 7' 20 X X X

04-3-07 STAIR S3-4 3'-0'' 7' 90 90 X X CMU

04-3-08 CORR. COMM. C-7 W. 3'-8'' 7' 90 90 X X X CMU

04-3-09 CORR. COMM. C-7 E. 3'-8'' 7' 90 90 X X X X CMU

LEGEND Door Counts Mechanical Room Doors 90 minute 21

Stairwell Doors 45 minute 2 Perimeter Doors 20 minute 8

No Work Not Rated 2

BUILDING 4

DOOR 04-B-01 DOOR 04-B-02

DOOR 04-B-03 DOOR 04-B-04

DOOR 04-B-05 DOOR 04-B-06

Relabeled as door 04-1-12

DOOR 04-B-07

DOOR 04-1-01 DOOR 04-1-02

DOOR 04-1-03 DOOR 04-1-04

DOOR 04-1-05 DOOR 04-1-06

DOOR 04-1-07 DOOR 04-1-08

DOOR 04-1-09 DOOR 04-1-10

DOOR 04-1-11 DOOR 04-1-12

DOOR 04-2-01 DOOR 04-2-02

DOOR 04-2-03 DOOR 04-2-04

DOOR 04-2-05 DOOR 04-2-06

DOOR 04-3-01 DOOR 04-3-02

DOOR 04-3-03 DOOR 04-3-04

DOOR 04-3-05 DOOR 04-3-06

DOOR 04-3-07 DOOR 04-3-08

DOOR 04-3-09

Provided Rating No Door Label

Door Label Painted

Door Damaged

Bottom Clearance

Exceeds 3/4"

Top and/or Vertical

Clearances Exceeds 3/16"

Missing Closing Device

Closing Device Not

Working Properly

Door is Provided with Chock

Door Does Not Latch Properly

Coordinator Not Installed

Broken Coordinator

No Frame Label

Painted Frame Label

Damaged Frame

Fire Exit Hardware

Not Labeled

Glazing Not

Labeled

Missing Screw on

Hinge

Edge Protection

Added

Smoke Detector Exceeds Allowable Distance from Door

Wall Material

Comments

4A-B-01 CORR. RCCB03R EXT. 3'-6'' 7' 90 90 X X X X X CMU AUTOMATIC DOOR

4A-B-02 STAIR SB-2 3'-6'' 7' 90 X X X X X CMU

4A-B-03 STAIR SB-2 EXT. 3'-6'' 7' 90 X X X X X X X X X X CMU

4A-B-04 POLICE 14 EXT. 3'-6'' 7' 20 X X X X X X CMU

4A-B-05 POLICE 14 3'-0'' 7' 20 X X X X LOC X X

4A-B-06 CORR. MH8 6'-0'' D 7' 20 ? X X X NA X

4A-B-07 STAFF TRAINING ED. 4 3'-6'' 7' 20 X X X X X

4A-B-08 STAFF TRAIN. ED. 4 EXT. 3'-10'' 7' 20 X X X X LOC X X X CMU

4A-B-09 CORR. RCCB03R EXT. 3'-6'' 7' 20 X X X X X X CMU

4A-B-10 CORR. RCCB05R 6'-0'' D 7' 20 X X X

4A-B-11 CORR. RCCB05R 3'-8'' 7' 90 90 X X CMU

4A-B-12 STAIR SB-3 3'-6'' 7' 90 90 X X X CMU

4A-B-13 STAIR SB-3 EXT. 3'-8'' 7'-2'' 90 X X X X X X X X CMU

4A-B-14 MECH. RCCB04R 6'-0'' D 7'-2'' 45 X X X X X X X X X CMU SURF. RUST ON FRAME

4A-B-15 STAIR SB-1 EXT. 3'-10'' 7' 90 X X X X X X CMU

4A-B-16 GROUP RM. 9D EXT. 4'-0'' 7' 20 X X X NA CMU CANNOT ACCESS

4A-B-17 STAIR SB-1 4'-0'' 7' 90 X X NA CMU REPLACE

4A-B-18 MECH. RM. 9A 3'-0'' 7' 45 NONE X X X X NA X NA MECH.

4A-B-19 MECH. RM. 15 3'-6'' 7' 45 X X X X NA CMU MECH.

4A-1-01 STAIR S1-3 3'-6'' 7' 90 X X X X CMU

4A-1-02 CORR. RCC113R 6'-0'' D 7' 90 90 X X X X CMU DBL. DOORS OVERLAP

4A-1-03 CORR. RCC112R 6'-0'' D 7' 90 90 X X CMU DBL. DOORS OVERLAP

4A-1-04 CORR. RCC102R 3'-6'' 7' --- X X X X CMU GLASS FRONT DOOR

4A-1-05 WAITING RM MH 141 3'-6'' 7' 90 90 ARM MISS. LOC X CMU

4A-1-06 STAIR S1-2 3'-6'' 7' 90 90 X X CMU

4A-1-07 STAIR S1-1 4'-0'' 7' 90 X X CMU

4A-2-01 CORR. RCC209R 3'-6'' 7' 90 90 X X X CMU

4A-2-02 STAIR S2-2 3'-6'' 7' 90 90 X X X CMU

4A-2-03 CORR. RCC210R 3'-6'' 7' 90 90 X X X X CMU

4A-2-04 STAIR S2-1 4'-0'' 7' 90 90 X X X CMU

4A-2-05 CORR. RCC212R 6'-0'' D 7' 90 90 X X CMU

4A-2-06 CORR. RCC204R 6'-0'' D 7' 90 90 X X CMU

4A-2-07 STAIR S2-3 3'-6'' 7' 90 X X X X X CMU

4A-3-01 STAIR S3-2 3'-6'' 7' 90 90 X X X X X CMU

4A-3-02 CORR. RCC325R 3'-6'' 7' 20 X X X DOOR LOCKED

4A-3-03 CORR. RCC323R 3'-6'' 7' 90 90 X X X X CMU

4A-3-04 STAIR S3-2 3'-0'' 7' 90 90 X X X CMU

4A-3-05 STAIR S3-1 4'-0'' 7' 90 90 X X X X CMU

4A-3-06 CORR. RCC324R 6'-0'' D 7' 90 90 X X X CMU

4A-3-07 CORR. RCC326R 3'-0'' 7' 90 90 X X CMU

4A-3-08 STAIR S3-3 3'-6'' 7' 90 90 X X X X CMU

LEGEND Door Counts Mechanical Room Doors 90 minute 28

Stairwell Doors 45 minute 3 Perimeter Doors 20 minute 9

BUILDING 4A

DOOR 4A-B-01 DOOR 4A-B-02

DOOR 4A-B-03 DOOR 4A-B-04

DOOR 4A-B-05 DOOR 4A-B-06

DOOR 4A-B-07 DOOR 4A-B-08

DOOR 4A-B-09

DOOR 4A-B-10 DOOR 4A-B-11

DOOR 4A-B-12 DOOR 4A-B-13

DOOR 4A-B-14 DOOR 4A-B-15

DOOR 4A-B-16 DOOR 4A-B-17

DOOR 4A-B-18 DOOR 4A-B-19

DOOR 4A-1-01

DOOR 4A-1-02 DOOR 4A-1-03

DOOR 4A-1-04 DOOR 4A-1-05

DOOR 4A-1-06

DOOR 4A-1-07 DOOR 4A-2-01

DOOR 4A-2-02 DOOR 4A-2-03

DOOR 4A-2-04 DOOR 4A-2-05

DOOR 4A-2-06 DOOR 4A-2-07

DOOR 4A-3-01

DOOR 4A-3-02 DOOR 4A-3-03

DOOR 4A-3-04 DOOR 4A-3-05

DOOR 4A-3-06 DOOR 4A-3-07

DOOR 4A-3-08

Provided Rating No Door Label

Door Label Painted

Door Damaged

Bottom Clearance

Exceeds 3/4"

Top and/or Vertical

Clearances Exceeds 3/16"

Missing Closing Device

Closing Device Not

Working Properly

Door is Provided with Chock

Door Does Not Latch Properly

Coordinator Not Installed

Broken Coordinator

No Frame Label

Painted Frame Label

Damaged Frame

Fire Exit Hardware

Not Labeled

Glazing Not

Labeled

Missing Screw on

Hinge

Edge Protection

Added

Smoke Detector Exceeds Allowable Distance from Door

Wall Material

Comments

05-B-01 AC SHOP ENG. 26 5'-0'' D 7' 45 None BRICK 05-B-02 AC SHOP ENG. 27A 6'-0'' D 7' --- None X X X X X X BRICK 05-B-03 STORAGE COMM. 29 6'-0'' D 7' 20 None BRICK 05-B-04 VESTIBLE COMM. 30 5'-0'' D 7' 20 None X X X X N/A X X BRICK

05-B-05 STAIR RCCB11R 3'-8'' 7' 90 X X X X X CMU

05-B-06 VESTIBLE COMM. 30 3'-8'' 7' 20 X X X X X BRICK

05-B-07 CORR. RCCB01R 5'-2'' D 7' 20 None X BRICK

05-B-08 MECH. RM. ENG. 23 3'-0'' 7' 45 X X X X X CMU

05-B-09 MECH. RM. ENG. 23 3'-0'' 7' 45 X X X X X X X CMU

05-B-10 MECH. RM. ENG. 23 6'-0'' D 7' 45 X X X X CMU

05-B-11 STAIR RCCB09R 3'-8'' 7' 90 X X X X X CMU

05-B-12 MECH. RM. ENG. 5 6'-0'' D 7' 45 X X X X X CMU

05-B-13 MECH. RM. ENG. 2 5'-0'' D 7' 45 X X X X X CMU

05-B-14 MECH. RM. ENG. 1 3'-8'' 7' 45 X X X X X CMU

05-B-15 STOR. ENG. 8 5'-0'' D 7' 45 X X X X CMU

05-B-16 STOR. ENG. 8 6'-0'' D 7' --- None X X X X BRICK

05-B-17 CORR. RCCB03R 6'-0'' D 7' 20 X X CMU

05-B-18 CORR. RCCB03R 5'-0'' D 7' 20 None BRICK

05-B-19 STAIR RCCB08R 3'-8'' 7' 90 X X X CMU

05-B-20 MECH. RM. ENG. 46 2'-6'' 7' 45 X X X CMU

05-B-21 MECH. RM. ENG. 32 3'-0'' 7' 45 X BRICK

05-B-22 MECH. RM. ENG. 21 6'-0'' D 7' --- None BRICK

05-B-23 STAIR RCCB09R 3'-8'' 7' 90 90 X X X X X CMU NO SMOKE

05-B-24 ELEV. LOB. RCCB05R 6'-0'' D 7' 20 X X X X X X CMU

05-B-25 STAIR RCCB06R 4'-0'' 7' 90 X X X X X X BRICK NO SMOKE

05-B-26 STORAGE COMM. 19 3'-8'' 7' 20 X X X X X X CMU WEDGED SHUT

05-B-27 STORAGE COMM. 19 6'-0'' D 7' 20 X X X X X X X X X CMU NO SMOKE

05-01-01 STAIR RCC119R 3'-8'' 7' 90 X X X X X CMU

05-01-02 STOR. FOOD 104A 3'-0'' 7' 20 X X X X X CMU

05-01-03 ELEV LOB. RCC110R 3'-8'' 7' 90 90 X X CMU

05-01-04 STAIR RCC116R 3'-8'' 7' 90 X X CMU

05-01-05 CART WARMING 6'-0'' D 7' 20 X X CMU

05-01-06 DINING RM 101 3'-6'' 7' 20 None X X X BRICK

05-01-07 DINING RM 101 3'-4'' 7' 90 90 X X X BRICK

05-01-08 DINING RM 101 3'-6'' 7' 90 90 X X X CMU

05-01-09 KITCHEN 103 5'-0'' D 7' 20 X CMU

05-01-10 KITCHEN 104 3'-0'' 7' 20 X X X CMU

05-01-11 CORR. COMM. C-2 3'-8'' 7' 20 X X X CMU

05-01-12 STAIR RCC115R 3'-8'' 7' 90 90 X CMU

05-01-13 STAIR RCC118R 3'-8'' 7' 90 X X X CMU

05-01-14 CORR. RCC106R 3'-8'' 7' 20 X X CMU

05-01-15 STOR. FOOD 104A 3'-0'' 7' 20 X X

05-01-16 CORR. RCC106R 3'-8'' 7' --- None X X CMU

05-01-17 PASTORAL 127 3'-6'' 7' 20 X X X X X X CMU

05-01-18 PASTORAL 127 3'-6'' 7' 20 X X X X X CMU

LEGEND Door Counts Mechanical Room Doors 90 minute 12

Stairwell Doors 45 minute 10 Perimeter Doors 20 minute 19

No Work Not Rated 4

BUILDING 5

DOOR 05-B-01 DOOR 05-B-02

DOOR 05-B-03 DOOR 05-B-04

DOOR 05-B-05 DOOR 05-B-06

DOOR 05-B-07 DOOR 05-B-08

DOOR 05-B-09 DOOR 05-B-10

DOOR 05-B-11 DOOR 05-B-12

DOOR 05-B-13 DOOR 05-B-14

DOOR 05-B-15 DOOR 05-B-16

DOOR 05-B-17 DOOR 05-B-18

DOOR 05-B-19 DOOR 05-B-20

DOOR 05-B-21 DOOR 05-B-22

DOOR 05-B-23 DOOR 05-B-24

DOOR 05-B-25 DOOR 05-B-26

DOOR 05-B-27

DOOR 05-01-01 DOOR 05-01-02

DOOR 05-01-03 DOOR 05-01-04

DOOR 05-01-05 DOOR 05-01-06

DOOR 05-01-07 DOOR 05-01-08

DOOR 05-01-09 DOOR 05-01-10

DOOR 05-01-11 DOOR 05-01-12

DOOR 05-01-13 DOOR 05-01-14

DOOR 5-01-15 DOOR 05-01-16

DOOR 05-01-17 DOOR 05-01-18

Provided Rating No Door Label

Door Label Painted

Door Damaged

Bottom Clearance

Exceeds 3/4"

Top and/or Vertical

Clearances Exceeds 3/16"

Missing Closing Device

Closing Device Not

Working Properly

Door is Provided with Chock

Door Does Not Latch Properly

Coordinator Not Installed

Broken Coordinator

No Frame Label

Painted Frame Label

Damaged Frame

Fire Exit Hardware

Not Labeled

Glazing Not

Labeled

Missing Screw on

Hinge

Edge Protection

Added

Smoke Detector Exceeds Allowable Distance from Door

Wall Material

Comments

13-1-01 FOYER RCC104R 6'-0'' D 7' --- None X X X X X X X X X BRICK

13-1-02 FOYER RCC104R 5'-0'' D 7' 20 X X X X X CMU

13-1-03 METAL SHOP 101 3'-4'' 7' --- None X X X X X X CMU 13-1-04 CORR. RCC103R 3'-4'' 7' --- None X X X X X X CMU 13-1-05 SHOP ENG. 104 3'-8'' 7' --- None X X X X CMU 13-1-06 SHOP ENG. 104 6'-0'' D 7' --- None X X X X X X X BRICK 13-1-07 OFFICE ENG. 105A 3'-4'' 7' --- None X X X X X X CMU

LEGEND Door Counts Mechanical Room Doors 90 minute 0

Stairwell Doors 45 minute 0 Perimeter Doors 20 minute 1

No Work Not Rated 6

BUILDING 13

DOOR 13-01-01 DOOR 13-01-02

DOOR 13-01-03 DOOR 13-01-04

DOOR 13-01-05 DOOR 13-01-06

DOOR 13-01-07 DOOR 13-01-08

Provided Rating No Door Label

Door Label Painted

Door Damaged

Bottom Clearance

Exceeds 3/4"

Top and/or Vertical

Clearances Exceeds 3/16"

Missing Closing Device

Closing Device Not

Working Properly

Door is Provided with Chock

Door Does Not Latch Properly

Coordinator Not Installed

Broken Coordinator

No Frame Label

Painted Frame Label

Damaged Frame

Fire Exit Hardware

Not Labeled

Glazing Not

Labeled

Missing Screw on

Hinge

Edge Protection

Added

Smoke Detector Exceeds Allowable Distance from Door

Wall Material

Comments

14-1-01 FOYER RCC104R 6'-0'' 7' --- None X X X X X X BRICK 14-1-02 FOYER RCC104R 2'-8'' 7' --- None X X BRICK 14-1-03 OFFICE RCC105R 3'-6'' 7' --- None X BRICK

14-1-04 BREAK RM RCC106R 6'-0'' D 7' 20 CMU

14-1-05 SHOP ENG. 100 5'-0'' D 7' 20 None X X X X X CMU

LEGEND Door Counts Mechanical Room Doors 90 minute 0

Stairwell Doors 45 minute 0 Perimeter Doors 20 minute 2

No Work Not Rated 3

BUILDING 14

DOOR 14-01-01 DOOR 14-01-02

DOOR 14-01-03 DOOR 14-01-04

DOOR 14-01-05

Provided Rating No Door Label

Door Label Painted

Door Damaged

Bottom Clearance

Exceeds 3/4"

Top and/or Vertical

Clearances Exceeds 3/16"

Missing Closing Device

Closing Device Not

Working Properly

Door is Provided with Chock

Door Does Not Latch Properly

Coordinator Not Installed

Broken Coordinator

No Frame Label

Painted Frame Label

Damaged Frame

Fire Exit Hardware

Not Labeled

Glazing Not

Labeled

Missing Screw on

Hinge

Edge Protection

Added

Smoke Detector Exceeds Allowable Distance from Door

Wall Material

Comments

15-1-01 GARAGE FIRE DEPT 3'-0'' 7' 90 None X CMU

15-1-02 GARAGE FIRE DEPT 3'-0'' 7' 90 90 X X X CMU

15-1-03 WORKOUT RM 114 7'-6'' 7' 120 BRICK

15-1-04 CORR. RCC107R 3'-0'' 7' --- None CMU 15-1-05 CORR. RCC103R 3'-0'' 7' --- None CMU

15-1-06 GARAGE 105 3'-0'' 6'-8'' 90 CONC

15-1-07 GARAGE 105 3'-0'' 6'-8'' 90 CONC

15-1-08 GARAGE 105 3'-0'' 6'-8'' 90 CONC

15-1-09 GARAGE 104 3'-0'' 6'-8'' 90 X X X X CMU

15-1-10 STAIR RCC102R 3'-0'' 6'-8'' --- None X X X CMU 15-1-11 LOUNGE ENG. 121B 3'-6'' 7' --- None X CMU 15-1-12 STOR. ENG. 118 3'-0'' 7' --- None X CMU 15-1-13 GARAGE ENG. 117 3'-6'' 7' --- None X CMU

LEGEND Door Counts Mechanical Room Doors 90 minute 6

Stairwell Doors 45 minute 0 Perimeter Doors 20 minute 0

No Work Not Rated 6 Special Frame 120 minute 1

BUILDING 15

DOOR 15-01-01 DOOR 15-01-02

DOOR 15-01-03 DOOR 15-01-04

DOOR 15-01-05 DOOR 15-01-06

DOOR 15-01-07 DOOR 15-01-08

DOOR 15-01-09 DOOR 15-01-10

DOOR 15-01-11 DOOR 15-01-12

DOOR 15-01-13

Provided Rating No Door Label

Door Label Painted

Door Damaged

Bottom Clearance

Exceeds 3/4"

Top and/or Vertical

Clearances Exceeds 3/16"

Missing Closing Device

Closing Device Not

Working Properly

Door is Provided with Chock

Door Does Not Latch Properly

Coordinator Not Installed

Broken Coordinator

No Frame Label

Painted Frame Label

Damaged Frame

Fire Exit Hardware

Not Labeled

Glazing Not

Labeled

Missing Screw on

Hinge

Edge Protection

Added

Smoke Detector Exceeds Allowable Distance from Door

Wall Material

Comments

65-B-01 STORAGE RCCB05R 3'-0'' 7' 20 X CONC LOCKED

65-B-02 SVC RM RCCB01R 6'-0'' D 7' 20 X X X CONC LOCKED

65-1-01 CLEAN LINEN EMS 101 7'-0'' D 7' 20 ILLEGIBLE X X X X X X X BRICK

65-1-02 CORR. EMS RCC102R 6'-0'' D 7' 90 90 X X X X CMU

65-1-03 STORAGE EMS 110 3'-0'' 7' 20 X X X X BRICK

65-1-04 CONF. RM EMS 102 EXT. 3'-8'' 7' 20 X X X X CMU

65-1-05 CONF. RM EMS 102 3'-0'' 7' 20 X X X X CMU HALF-DOOR

LEGEND Door Counts Mechanical Room Doors 90 minute 1

Stairwell Doors 45 minute 0 Perimeter Doors 20 minute 6

No Work Not Rated 0

BUILDING 65

DOOR 65-B-01 DOOR 65-B-02

DOOR 65-1-01 DOOR 65-1-02

DOOR 65-1-03 DOOR 65-1-04

DOOR 65-1-05

Provided Rating No Door Label

Door Label Painted

Door Damaged

Bottom Clearance

Exceeds 3/4"

Top and/or Vertical

Clearances Exceeds 3/16"

Missing Closing Device

Closing Device Not

Working Properly

Door is Provided with Chock

Door Does Not Latch Properly

Coordinator Not Installed

Broken Coordinator

No Frame Label

Painted Frame Label

Damaged Frame

Fire Exit Hardware

Not Labeled

Glazing Not

Labeled

Missing Screw on

Hinge

Edge Protection

Added

Smoke Detector Exceeds Allowable Distance from Door

Wall Material

Comments

68-B-01 STAIR RCCB08R 3'-6'' 7' 90 X HDN X X X CMU

68-B-02 STAIR RCCB08R 3'-8'' 7' 90 X X X X X X X NA X CMU

68-B-03 COR 67/04F 3'-6'' 7' 20 X X X X X CMU

68-B-04 CORR 67 TO B69 3'-6'' 7' 20 DOOR LOCKED

68-B-05 CORR 04G 3'-0'' 7' 20 X X X X NA X X

68-B-06 STAIR RCCB12R 3'-6'' 7' 90 X X X X X X CMU WOOD DR. FIRE EXIT

68-B-07 STAIR RCCB12R 3'-8'' 7' 90 90 X X X X X CMU

68-B-08 CORR 67 3'-8'' 7' 20 X X X X X

68-B-09 STAIR RCCB07R 3'-6'' 7' 90 90 X X X CMU DOOR HANDLE ISSUE

68-B-10 STAIR RCCB07R 3'-8'' 7' 90 90 X X X X X X CMU

68-B-11 STAIR RCCB07R 3'-0'' 7' 90 90 X X X X X X X CMU

68-B-12 CORR RCCB02R EXT. 3'-8'' 7' 20 X X X X X X X CMU

68-B-13 CORR RCCB02R 3'-0'' 7' 20 X X NA X X

68-B-14 STAIR RCCB06R 3'-6'' 7' 90 X X X X X X CMU

68-B-15 STAIR RCCB06R 3'-8'' 7' 90 X X X X X X X CMU

68-B-16 STAIR RCCB04R 3'-6'' 7' 90 X X X X X CMU

68-B-17 STAIR RCCB04R 3'-8'' 7' 90 X X X X X CMU

68-B-18 CORR 03 3'-8'' 7' 20 X X X X

68-B-19 CORR 20/03 3'-0'' 7' 20 X X X X

68-B-20 STAIR RCCB05R 3'-6'' 7' 90 X X X X CMU

68-B-21 STAIR RCCB05R 3'-6'' 7' 90 90 X X X X CMU

68-B-22 CORR 03/04I 3'-6'' 7' 20 X NA X X

68-B-23 STAIR RCCB11R 3'-6'' 7' 90 X X X X X X CMU

68-B-24 STAIR RCCB11R 3'-8'' 7' 90 90 X X X X X CMU

68-B-25 AIR LOCK 02 3'-6'' 7' 20 X X X X X X AUTOMATIC DOOR

68-B-26 AIR LOCK 02 3'-6'' 7' 90 90 X X X X X CMU AUTOMATIC DOOR

68-B-27 MECH. RM. 36A 3'-0'' 7' 45 X X X X X X WOOD/HANDLE/NO GLASS

68-1-01 STAIR RCC101R 3'-6'' 7' 90 X X X X X X CMU

68-1-02 CORR RCC106R 3'-10'' 7' 90 90 X X X CMU DR DOES NOT CLOSE

68-1-03 VESTIBULE 111 3'-8'' 7' 20 X X X X

68-1-04 VESTIBULE 111 EXT 3'-6'' 7' --- X X X X X CMU DR DOES NOT LOCK OR LATCH

68-1-05 STAIR RCC116R 3'-6'' 7' 90 X X X X X CMU

68-1-06 STAIR RCC118R 3'-6'' 7' 90 90 X BROKEN X X X X CMU

68-1-07 CORR RCC110R 3'-10'' 7' 20 X X X X X

68-1-08 STAIR RCC114R 3'-6'' 7' 90 X X X X CMU

68-1-09 CORR RCC107R 3'-6'' 7' 90 90 X X X X X

68-1-10 CORR RCC107R EXT 3'-6'' 7' --- X X X CMU

68-1-11 CORR RCC102R 6'-4'' D 7' 20 X X

68-1-12 CORR RCC102R 3'-10'' 7' 90 90 X X X X X

68-1-13 STAIR RCC119R 3'-6'' 7' 90 90 X X X X X CMU

68-1-14 CORR RCC105R 3'-10'' 7' 90 90 X X X

68-1-15 CONF ROOM 149 3'-8'' 7' 20 X X X X X

68-1-16 STAIR RCC117R 3'-6'' 7' 90 90 X X X X CMU

68-1-17 STAIR RCC115R 3'-6'' 7' 90 90 X X X X CMU

68-2-01 STAIR RCC219R 3'-6'' 7' 90 X X X X X CMU

68-2-02 CORR NEAR OFC 247 3'-6'' 7' 20 X X X X X X

68-2-03 CORR NEAR RR 241A 3'-10'' 7' 90 90 X X X X X X X

68-2-04 STAIR RCC209R 3'-6'' 7' 90 90 X X X X X CMU

68-2-05 CORR NEAR RCC210R 3'-10'' 7' 90 90 X X X X

68-2-06 CORR NEAR ELEV RCC221R 6'-4'' D 7' 20 20 X X X DOUBLE DOOR

68-2-07 LOBBY RCC215R 3'-10'' 7' 20 20 X X X X

68-2-08 STAIR RCC216R 3'-6'' 7' 90 90 X X CMU

68-2-09 CORR NEAR 204 3'-10'' 7' 20 X X X X X

68-2-10 STAIR RCC211R 3'-6'' 7' 90 X X X X CMU

68-2-11 CORR 207R 3'-10'' 7' 20 X X X X X X X

68-2-12 STAIR RCC208R 3'-6'' 7' 90 X X X X X CMU

68-2-13 STAIR RCC210R 3'-6'' 7' 90 90 X X CMU

68-2-14 STAIR RCC222R 3'-6'' 7' 90 X X X X X X X CMU NO SMOKE

LEGEND Door Counts Mechanical Room Doors 90 minute 36

Stairwell Doors 45 minute 1 Perimeter Doors 20 minute 19

No Work Not Rated 2

BUILDING 68

DOOR 68-B-01 DOOR 68-B-02

DOOR 68-B-03 DOOR 68-B-04

DOOR 68-B-05 DOOR 68-B-06

DOOR 68-B-07 DOOR 68-B-08

DOOR 68-B-09 DOOR 68-B-10

DOOR 68-B-11 DOOR 68-B-12

DOOR 68-B-13 DOOR 68-B-14

DOOR 68-B-15 DOOR 68-B-16

DOOR 68-B-17 DOOR 68-B-18

DOOR 68-B-19 DOOR 68-B-20

DOOR 68-B-21 DOOR 68-B-22

DOOR 68-B-23 DOOR 68-B-24

DOOR 68-B-25 DOOR 68-B-26

DOOR 68-B-27

DOOR 68-1-01

DOOR 68-1-02 DOOR 68-1-03

DOOR 68-1-04 DOOR 68-1-05

DOOR 68-1-06 DOOR 68-1-07

DOOR 68-1-08 DOOR 68-1-09

DOOR 68-1-10 DOOR 68-1-11

DOOR 68-1-12 DOOR 68-1-13

DOOR 68-1-14 DOOR 68-1-15

DOOR 68-1-16

DOOR 68-1-17 DOOR 68-2-01

DOOR 68-2-02 DOOR 68-2-03

DOOR 68-2-04 DOOR 68-2-05

DOOR 68-2-06 DOOR 68-2-07

DOOR 68-2-08

DOOR 68-2-09 DOOR 68-2-10

DOOR 68-2-11 DOOR 68-2-12

DOOR 68-2-13 DOOR 68-2-14

Provided Rating No Door Label

Door Label Painted

Door Damaged

Bottom Clearance

Exceeds 3/4"

Top and/or Vertical

Clearances Exceeds 3/16"

Missing Closing Device

Closing Device Not

Working Properly

Door is Provided with Chock

Door Does Not Latch Properly

Coordinator Not Installed

Broken Coordinator

No Frame Label

Painted Frame Label

Damaged Frame

Fire Exit Hardware

Not Labeled

Glazing Not

Labeled

Missing Screw on

Hinge

Edge Protection

Added

Smoke Detector Exceeds Allowable Distance from Door

Wall Material

Comments

83-B-01 MECH. RM. B2 6'-0'' D 7' 45 X X X X X X CMU NO SMOKE

83-B-02 MECH. RM. B5 6'-0'' D 7' 45 X X X X X X CMU NO SMOKE

83-B-03 MECH. RM. 7 6'-0'' D 7' 45 X X X X X X CMU NO SMOKE

83-1-01 VEST. RCC102R EXT. 5'-8'' D 6'-10'' --- X X BRICK SLIDING GLASS DR.

83-1-02 VEST. RCC102R 5'-8'' D 6'-10'' --- X X BRICK SLIDING GLASS DR.

83-1-03 CORR. RCC112R 7'-4'' D 7' 20 X X X X DOUBLE WOOD DR.

83-1-04 NURSES STATION GECR115 7'-4'' D 7' 20 X X X X X

83-1-05 VEST RCC101R 5'-8'' D 7' --- X X CMU SLIDING GLASS DR.

83-1-06 VEST. RCC101R EXT. 5'-8'' D 7' --- X X CMU SLIDING GLASS DR.

83-1-07PRIMARY CARE CLINIC GECR123 4'-0'' 7' 20 X X X HALF DR., BOT. DRAGS

83-1-08 CORR. RCC110R 7'-4'' D 7' 20 X X X X X DOUBLE WOOD DR.

83-1-09 CORR. RCC121R 3'-10'' 7' 20 X X X X X

83-1-10 CORR. RCC111R 7'-4'' D 7' 20 X X X DOUBLE WOOD DR.

83-1-11 CORR. RCC114R 7'-4'' D 7' 20 X BROKE X X X X DOUBLE WOOD DR.

83-1-12 CORR. RCC111R EXT. 3'-8'' 7' --- X X X X X BRICK GLASS

83-1-13 CORR. RCC115R 7'-4'' D 7' 90 90 X X X DBL. DOOR

83-1-14 CORR. 7'-4'' D 7' 90 90 X X X

83-1-15 CORR. RCC117R 3'-10'' 7' 20 X X X X X X

83-1-16 EXIT 3'-8'' 7' --- X X X X X X X BRICK NO SMOKE

83-1-17 PHARMACY 3'-10'' 7' --- BRICK SEE PICTURE

LEGEND Door Counts Mechanical Room Doors 90 minute 2

Stairwell Doors 45 minute 3 Perimeter Doors 20 minute 8

No Work Not Rated 7

BUILDING 83

DOOR 83-B-01 DOOR 83-B-02

DOOR 83-B-03

DOOR 83-1-01 DOOR 83-1-02

DOOR 83-1-03 DOOR 83-1-04

DOOR 83-1-05

DOOR 83-1-06 DOOR 83-1-07

DOOR 83-1-08

DOOR 83-1-09 DOOR 83-1-10

DOOR 83-1-11

DOOR 83-1-12 DOOR 83-1-13

DOOR 83-1-14 DOOR 83-1-15

DOOR 83-1-16 DOOR 83-1-17

Provided Rating No Door Label

Door Label Painted

Door Damaged

Bottom Clearance

Exceeds 3/4"

Top and/or Vertical

Clearances Exceeds 3/16"

Missing Closing Device

Closing Device Not

Working Properly

Door is Provided with Chock

Door Does Not Latch Properly

Coordinator Not Installed

Broken Coordinator

No Frame Label

Painted Frame Label

Damaged Frame

Fire Exit Hardware

Not Labeled

Glazing Not

Labeled

Missing Screw on

Hinge

Edge Protection

Added

Smoke Detector Exceeds Allowable Distance from Door

Wall Material

Comments

88-1-01 MAIN WAREHOUSE 101 3'-0'' 7' 90 90 X X X X X BRICK

88-1-02 MAIL OFFICE 104 4'-0'' 7' 20 X X X X X CMU HALF DOOR

88-1-03 STORAGE 104B 3'-0'' 7' --- X X X X BRICK METAL/GLASS DOOR

LEGEND Door Counts Mechanical Room Doors 90 minute 1

Stairwell Doors 45 minute 0 Perimeter Doors 20 minute 1

BUILDING 88

DOOR 88-1-01 DOOR 88-1-02

DOOR 88-1-03

Provided Rating No Door Label

Door Label Painted

Door Damaged

Bottom Clearance

Exceeds 3/4"

Top and/or Vertical

Clearances Exceeds 3/16"

Missing Closing Device

Closing Device Not

Working Properly

Door is Provided with Chock

Door Does Not Latch Properly

Coordinator Not Installed

Broken Coordinator

No Frame Label

Painted Frame Label

Damaged Frame

Fire Exit Hardware

Not Labeled

Glazing Not

Labeled

Missing Screw on

Hinge

Edge Protection

Added

Smoke Detector Exceeds Allowable Distance from Door

Wall Material

Comments

93-1-01CHAPEL PASTORAL CARE 110 ENTRY 5'-0'' D 8' --- X X X X BRICK AUTOMATIC DOOR, WOOD

93-1-02 CORR C1 3'-0'' 7' 20 X X X X

93-1-03 CORR C1 EXT 3'-0'' 7' 90 90 X X X X BRICK

93-1-04 CHAPEL PAST. CARE 110 EXT 3'-4'' 7' --- X X X BRICK

93-1-05 CHAPEL PAST. CARE 110 EXT 3'-4'' 7' --- X X X X BRICK

93-1-06 CHAPEL PAST. CARE 110 EXT 3'-4'' 7' --- X X BRICK

93-1-07 MECH. RM. 109 3'-0'' 7' 45 X X X X X X X BRICK NO SMOKE

LEGEND Door Counts Mechanical Room Doors 90 minute 1

Stairwell Doors 45 minute 1 Perimeter Doors 20 minute 1

No Work Not Rated 4

BUILDING 93

DOOR 93-1-01 DOOR 93-1-02

DOOR 93-1-03 DOOR 93-1-04

DOOR 93-1-05 DOOR 93-1-06

DOOR 93-1-07

Provided Rating No Door Label

Door Label Painted

Door Damaged

Bottom Clearance

Exceeds 3/4"

Top and/or Vertical

Clearances Exceeds 3/16"

Missing Closing Device

Closing Device Not

Working Properly

Door is Provided with Chock

Door Does Not Latch Properly

Coordinator Not Installed

Broken Coordinator

No Frame Label

Painted Frame Label

Damaged Frame

Fire Exit Hardware

Not Labeled

Glazing Not

Labeled

Missing Screw on

Hinge

Edge Protection

Added

Smoke Detector Exceeds Allowable Distance from Door

Wall Material Comments

129-G-01 CORR. COMM. CG-2 7'-4'' D 6'-8'' 20 X X X X X X DBL. DOORS

129-G-02 CORR. COMMON CG-1 7'-4'' D 6'-8'' 90 90 X X X X X DBL. DOORS

129-G-03 SERV. AREA GA-111 3'-8'' 6'-8'' 20 X X X X X CMU

129-G-04 CORR. COMM. CG-6 7'-4'' D 6'-8'' 90 90 X X X CMU DBL. DOORS

129-G-05 HAC EMS GA-117 3'-0'' 6'-8'' 90 60 X X CMU

129-G-06 CORR. COMMON CG-9 7'-4'' D 6'-8'' 20 X X X X DBL. DOORS

129-G-07 CORR. COMM. CG-16 7'-4'' D 6'-8'' 20 X X X X DBL. DOORS

129-G-08 CORR. COMM. CG-14 7'-4'' D 6'-8'' 20 X X X X X DBL. DOORS

129-G-09 CORR. COMM. CG-8 7'-4'' D 6'-8'' 90 90 X X DBL. DOORS

129-G-10 CORR. COMM. CG-8 7'-4'' D 6'-8'' 20 X X X X DBL. DOORS

129-G-11 LOADING DOCK 7'-4'' D 6'-8'' --- X X X X X X X BRICK

129-G-12 MECH. RM. ENG. 3'-8'' 6'-8'' 45 X X X X X

129-G-13 STAIRS WEST 3'-0'' 6'-8'' --- X OK X OK X BRICK GLASS DOOR

129-G-14 STAIRS EAST 3'-0'' 6'-8'' --- X OK X OK X BRICK GLASS DOOR

129-G-15 STAIRS NORTH 3'-0'' 6'-8'' --- X OK X OK X BRICK GLASS DOOR

129-G-16 CORR. COMM. CG-6 7'-8'' D 6'-8'' --- X X X X BRICK

129-G-17 UTILITIES ENG. 6'-0'' D 6'-8'' --- X X X X BRICK MECHANICAL

129-G-18 UTILITIES ENG. 6'-0'' D 6'-8'' --- X X X X BRICK MECHANICAL

129-G-19 ELECT. UTIL. ENG. 3'-0'' 6'-8'' --- X X X NO? X X BRICK MECHANICAL

129-1-01 VESTIBULE C1-5 5'-5'' D 6'-10'' --- X STOREFRONT DBL. GLASS SLIDING DR.

129-1-02 CORR. COMM. C1-4 5'-5'' D 6'-10'' --- X BRICK DBL. GLASS SLIDING DR.

129-1-03 PHYS. THERAPY 3'-10'' 6'-8'' 20 X X X X X

129-1-04 CORR. COMM. C1-9 7'-4'' D 6'-8'' 20 20 X X X X

129-1-05 CORR. COMM. C1-16 7'-4'' D 6'-8'' 20 X X X X

129-1-06 CORR. COMM. C1-14 7'-4'' D 6'-8'' 20 X X X X

129-1-07 STAIRS NORTH 3'-0'' 6'-8'' 90 X X X X CMU

129-1-08 STAIRS OFF C1-1 3'-0'' 6'-8'' 90 60 X CMU

129-1-09 STAIRS WEST 3'-0'' 6'-8'' 90 X X X X X CMU

129-1-10 STAIRS EAST 3'-0'' 6'-8'' 90 X X X X X CMU

129-1-11 MECH. RM. 1A-100 7'-4'' D 6'-8'' 45 45 X X X X X X

LEGEND Door Counts Mechanical Room Doors 90 minute 8

Stairwell Doors 45 minute 2 Perimeter Doors 20 minute 10

No Work Not Rated 10

BUILDING 129

DOOR 129-G-01 DOOR 129-G-02

DOOR 129-G-03 DOOR 129-G-04

DOOR 129-G-05 DOOR 129-G-06

DOOR 129-G-07 DOOR 129-G-08

DOOR 129-G-09 DOOR 129-G-10

DOOR 129-G-11 DOOR 129-G-12

DOOR 129-G-13 DOOR 129-G-14

DOOR 129-G-15 DOOR 129-G-16

DOOR 129-G-17 DOOR 129-G-18

DOOR 129-G-19 DOOR 129-1-01

DOOR 129-1-02 DOOR 129-1-03

DOOR129-1-04 DOOR 129-1-05

DOOR 129-1-06 DOOR 129-1-07

DOOR 129-1-08 DOOR 129-1-09

DOOR 129-1-10 DOOR 129-1-11

aPicture Book Cover
2
Door Pictures BLDG 2
3
Door Pictures BLDG 3
3A
Door Pictures BLDG 3A
4
Door Pictures BLDG 4
4A
Door Pictures BLDG 4A
5
Door Pictures BLDG 5
13
Door Pictures BLDG 13