WORK TASK/CAPITAL PROJECT #:

FACILITY:

REQUESTER:

08 March 2021

(This inspection is valid for three years from the inspection date regardless of Exp. Date of inspector cert. If past this date, a visual or additional assessment will then be required)

LEAD BASED PAINT

ASBESTOS

LIMITED INSPECTION REPORT

Utah Certified State Inspector: Kyle Daly

(ASB#-7321: Expires-17 Sept. 2022, PB#-2753: Expires-17 March 2024)

INSPECTION DATE: 19 November 2021

Reference UDAQ R307-807-6

DEPARTMENT OF THE AIR FORCE

75TH CIVIL ENGINEERING (CEOHA)

HILL AIR FORCE BASE, UTAH

SIGNATURE:

PREPARED BY: Kyle Daly (ASB#-7321, PB#-2753)

BREEZEWAY ROOF REPLACEMENT

ORGANIZATION:

REQUESTED:

9505087

NICK CHILD

THE QUANTITIES WITHIN THIS REPORT ARE ESTIMATES AND SHOULD

NOT BE USED FOR BIDDING PURPOSES

309 CMXG

FACILITY CONSTRUCTION DATE:

ASBESTOS

N/A

This inspection was performed in accordance with the Utah Division of Air Quality (DAQ) requirements as found in the Utah Air Quality Rule R307-801-10. This inspection report is required to be on site during all abatement, renovation, and demolition activities. Samples referenced in this report were analyzed by polarized light microscopy (PLM) utilizing method 600R-93-116 by The Science and Engineering Laboratory (AIHA Acc.#-

101572) at Hill Air Force Base, Utah (R307-801-10.8.a-b).

N/A

*LOCATIONS FOUND

N/AN/A

Civil Engineering personnel also reviewed previous asbestos inspection reports of suspect asbestos containing materials (ACM) that could potentially be encountered in the proposed area/areas. The information gathered from all current and previous inspections is shown below by homogenous area (R307-801-9-4).

*Per UDAQ definition.

LIMITED ASBESTOS INSPECTION REPORT INFORMATION

RACM: Regulated Asbestos-Containing Material (RACM)" means friable ACM, Category I non-friable ACM that has become friable, Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading, or Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation project operations.

Locations found: Locations of building materials as described in this report indicate where they were found, but do not necessarily mean that these are the only locations where these materials may be encountered during the project.

Category II Non-Friable ACM: Any material, excluding Category I non- friable ACM, containing more than 1% asbestos as determined by using the methods specified in 40 CFR Part 763, Subpart E, Appendix E, Section 1, Polarized Light Microscopy (PLM) that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.

Breezeway Roof Replacement.Statement of Work:

Category I Non-Friable ACM: Asbestos-containing packings, gaskets, resilient floor coverings, or asphalt roofing products containing more than 1% asbestos as determined by using the method specified in 40 CFR Part

763, Subpart E, Appendix E, Section 1, Polarized Light Microscopy (PLM).

DEPARTMENT OF THE AIR FORCE

75 CIVIL ENGINEERING (CEOHA)

HILL AIR FORCE BASE, UTAH

The quantities within this report are estimates and are not to be used for bidding purposes.

Table 1

SUMMARY OF ASBESTOS CONTAINING MATERIALS FOUND

MATERIAL TYPE

N/A

*RACM

*Category I

*Category II

FRIABILITY QUANTITY

N/A

A total of 10 3

GM220277 Northwest None-Detected

GM220278 Southwest None-Detected

Roof Decking, Gravel Over Black Roof Flashing, Black

Per EPA requirements, all materials analyzed as containing ≤10% asbestos are point counted utilizing EPA method 600/R-93/116 this information is summarized in Table 2.

Table 2.

ASBESTOS

CONTACT INFORMATION

suspect materials assessed as part of the inspection.

Sample # samples reference the

Table 4.

POTENTIAL FOR ADDITIONAL MATERIALS:

This inspection report only encompasses the areas/materials designated within the scope of work that was provided at the date of inspection (see title page for inspection date). Should the scope of the project be altered in any way or any materials found that are not identified in this report shall require additional assessment. This report cannot be used for any other projects within the building.

Any questions or concerns regarding this inspection report or if any new suspect asbestos containing material

(ACM) is encountered, stop work and contact the personnel listed below for further assistance/assessment.

*LOCATIONS FOUND

N/A N/A

Table 3.

The following table summarizes the sampling data.

Homogenous Building Material, Description, Location, Quantity.

GM220282 West Center, West Roof None-Detected

GM220279

Results

MATERIAL TYPE

Per Hill AFB requirements, all materials containing any detectable amount of asbestos shall be handled as Asbestos Containing Material (ACM). Table 2 shows the summary of materials containing ≤1% that were identified via "Point Counting". Per EPA/UDAQ

≤1% is not considered to be an asbestos containing material, but special handling/packaging requirements are necessary per OSHA 29CFR 1926.1101 and 29CFR

1910.1001

Sample Location

QUANTITY

N/A

The following is a list of the "Suspect Materials" that were sampled as part of this inspection:

N/A

Southwest, Center Roof None-Detected

Northwest, Center Roof None-Detected

GM220281 West Center, Center Roof None-Detected

GM220276 West Center None-Detected

None-Detected

GM220285 South Center None-Detected

Cell: (801)940-2970

Supervisor: Taylor Brimberry: DSN: (801)586-7094

Asbestos/LBP Shop 75 CES(CEOHA)

Asbestos/LBP Shop Personnel

DSN:(801)777-8006

Roof Decking, Gravel Over Black, Center

Breezeway Roof, 925 Square Feet

Roof Flashing, Black, Multiple Locations, 120

Linear Feet

Heavy Paint Tan Over Block, 505 South

Exterior Wall, 250 Square Feet

Heavy Paint, Tan Over Block

GM220280

GM220283 South Center None-Detected

GM220284 South Center

5-This inspection report only encompasses the areas/materials designated within the scope of work provided at the date of inspection (see title page for inspection date). This report must be modified should the scope of the project be altered in any way or additional materials not previously identified within this report are encountered. This report may not be used for any other projects within the building.

2-It is possible that lead based paint could be encountered during any renovation project. Additional identification for lead based paint on other building components may be required. The facility manager/Project Manager should ensure that these components are surveyed for lead as well, to meet OSHA Standard 29 CFR 1926.62 construction requirements for lead.

3-The U.S. Department of Housing and Urban Development defines Lead-based paint as any paint, varnish, stain, or other applied coating that has 1 mg/cm² as measured by an X-ray Fluorescence (XRF) Analyzer or by laboratory analysis of 0.5 percent by weight (5,000 µg/g dry weight) or more of lead. All other components tested were less than 1 mg/cm².

4-Any effort to disturb lead paint can create lead dust. Ensure that appropriate abatement, cleanup, and disposal will be accomplished and that appropriate safety measures are taken IAW 29 CFR 1926.62. If you have any questions please feel free to call Taylor Brimberry at 586-7094.

SCOPE OF WORK: Breezeway Roof Replacement.

1-Positive Lead based paint readings were not-detected. Please refer to the final page of section of this inspection for all readings.

XRF Analyzer XL3t 300 (Serial #30660)XRF Analyzer Used :

DEPARTMENT OF THE AIR FORCE

75TH CIVIL ENGINEERING (CEOHA)

HILL AIR FORCE BASE, UTAH

LIMITED NEGATIVE LEAD-BASED PAINT INSPECTION REPORT INFORMATION

3895 0.98 3925 1.13

3896 0.84 3926 1.05

3897 1.15 POS 3927 0.94

Range: .8 to 1.2 Paint Range: .8 to 1.2

Side Condition Color PbL(mg/cm2) NEG/POS

South Good Tan 0.01 NEG

West Good Tan 0.01 NEG

West Good Grey 0.01 NEG

Center Good Brown 0.01 NEG

East Good Brown 0.10 NEG

3903 Breezeway Roof Roof Siding Metal

Pre

Calibration PbL (mg/cm²)

Calibration

Range

Model# Serial #

Per 20

Second

Reading

3902 Breezeway Roof West Breezeway Roof Metal

3901 Breezeway Roof 505 Wall Block

XL Number Room/Area Structure

Per 20

Second

Reading

Calibration

Range

Substrate

Post

Calibration

PbL

(mg/cm²)XRF Analyzer XL3t 300 (Serial #30660)

MetalEast Breezeway Roof Breezeway Roof 3905

Metal507 SidingBreezeway Roof 3904

2021-12-09T08:05:43-0700
DALY.JOHN.KYLE.1590487178
Roof Flashing BlackHeavy Paint Tan Over Block:
Range 8 to 12: