Attachment 1_Design Drawings_Repair HVAC Systems.pdf

PDF 11 MB Posted

Attached to
Repair HVAC Systems, Gainesville, FL
Solicitation number
1232SA26Q0704
Issued by

About this file

This is a design document set (Title Sheet, Drawing List, and associated construction drawings) for an HVAC system repair project at the Center for Medical Agricultural and Veterinary Entomology (CMAVE) facility in Gainesville, Florida, under the U.S. Department of Agriculture Agricultural Research Service.

The project scope includes replacement of roof-mounted exhaust fans, replacement of the roof-mounted Air Handling Unit (AHU-1) with in-kind equipment, modification of ductwork as required for the replacement fans and AHU, disconnection and reconnection of HVAC equipment, and modification of the existing lightning protection system. The work is phased construction requiring separate stand-alone bids for each phase; this document set pertains to Building 1 Base Bid. Design Contract No. 12405B21D0003 and Design Order No. 1232SA25F0354 are identified. The drawings include mechanical demolition plans, HVAC floor and roof plans, mechanical schedules detailing exhaust fan specifications (including manufacturers such as Greenheck and ACME), AHU-1 specifications (York model XTO-057X084), controls diagrams, electrical demolition plans, electrical floor and roof plans, electrical equipment schedules, panel schedules, lightning protection plans, and detailed mechanical and electrical specifications. Key requirements include field verification of all existing dimensions prior to work, hazardous materials compliance, protection of existing finishes and facilities, coordination between trades, and compliance with the Buy American Act for equipment procurement.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EPM

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

C :\U se rs

\T O

M

LO

V~ 1\

Ap pD at a\

Lo ca l\T em p\ Ac

Pu bl is h_

\T

-1

.d w g M ay

3,

- 1 2:

pm

COR

TEL

E. WILSON

E. WILSON

TBD

TBD 5/04/2026

Agricultural

Service Research

USDA ARS

5601 SUNNYSIDE AVENUE

RM 3-2102

BELTVILLE MD 20705

REPAIR HVAC SYSTEM, BULDINGS 1 AND 11 CENTER FOR MEDICAL

AGRICULTURAL AND VETENARY ENTOMOLOGY (CMAVE) -

GAINESVILLE, FLORIDA

BTD

JND

BUILDING 1

TITLE SHEET

LOCATION MAPVICINITY MAP NO SCALE

N

NO SCALE

U.S. DEPARTMENT OF AGRICULTURE

AGRICULTURAL RESEARCH SERVICE

REPAIR HVAC SYSTEMS, BUILDING 1 BASE BID

DESIGN CONTRACT NO: 12405B21D0003

DESIGN ORDER NO: 1232SA25F0354

CENTER FOR MEDICAL AGRICULTURAL AND VETERINARY ENTOMOLOGY (CMAVE)

1600 SW 23RD DRIVE

GAINESVILLE, FL 32608

CENTER FOR MEDICAL AGRICULTURAL AND VETERINARY ENTOMOLOGY (CMAVE)

1600 SW 23RD DRIVE

GAINESVILLE, FL 32608

SW

RD

D

RI

VE

PROJECT LOCATION

PROJECT INFORMATION

GENERAL NOTES:

1. THE CONTRACTOR MUST FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO PERFORMING WORK, FABRICATION OR PURCHASE OF ANY EQUIPMENT, MATERIALS, AND ASSEMBLIES. ANY DISCREPANCIES MUST BE BROUGHT TO THE CONTRACTING OFFICER'S ATTENTION FOR RESOLUTION BEFORE PROCEEDING WITH ANY CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.

2. CONTRACTOR MUST PERFORM A THOROUGH SURVEY OF THE BUILDING AND DOCUMENT ANY DEFICIENCIES IN BUILDING FINISHES, BUILDING EQUIPMENT AND BUILDING SYSTEMS PRIOR TO BEGINNING WORK. SUBMIT DOCUMENT WITH

PHOTOGRAPHS TO THE CONTRACTING OFFICER.

3. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROTECT EXISTING FURNISHINGS TO ACCOMMODATE THE WORK.

PROTECT FINISHES AND FURNISHINGS DURING THE WORK.

HAZARDOUS MATERIALS INFORMATION:

1. REFER TO THE HAZARDOUS MATERIALS SURVEY REPORT IN THE SPECIFICATIONS. CONTRACTOR MUST ABIDE BY ALL GOVERNING REGULATIONS IN REGARDS TO DISTURBANCE, REMOVAL AND DISPOSAL OF HAZARDOUS MATERIALS

(REFERENCE SAID REPORT).

2. CONTRACTOR MUST ASSUME THAT ALL EXISTING PAINT COATINGS ON BUILDING MATERIALS AND SYSTEMS CONTAINS SOME LEVEL OF LEAD. ANY MATERIALS TO BE DISPOSED OF WITH PAINT COATINGS INTACT, MAY BE DISPOSED OF AS NORMAL CONSTRUCTION WASTE. THE CONTRACTOR MUST PROVIDE WORKER PROTECTION IN ACCORDANCE WITH OSHA

FOR ANY DISTURBANCE OF EXISTING PAINT COATINGS.

3. THE HAZARDOUS MATERIALS SURVEY TOOK SAMPLES OF SUSPECT ASBESTOS-CONTAINING MATERIALS. LABORATORY ANALYSIS OF THE SAMPLES DID NOT TEST POSITIVE FOR ASBESTOS. SHOULD THE CONTRACTOR DISCOVER MATERIALS THEY REASONABLY BELIEVE TO CONTAIN ASBESTOS, THE WORK MUST STOP AND THE CONTRACTING OFFICER MUST BE

NOTIFIED IMMEDIATELY.

PROTECTION OF EXISTING FACILITIES:

1. CONTRACTOR MUST PROTECT ALL EXISTING CONSTRUCTION DURING WORK INCLUDING, BUT NOT LIMITED TO, FINISHES, EQUIPMENT, DOORS, WINDOWS, FURNISHINGS AND SEATING. ANY DAMAGE TO EXISTING CONSTRUCTION MUST BE

REPAIRED OR REPLACED NEW, LIKE-IN-KIND.

MIAMI

TALLAHASSEE JACKSONVILLE

GAINESVILLE

ORLANDO

TAMPA

PENSACOLA

ST. PETERSBURG

KEY WEST

CANAL

POINT

SW

RD

D

RI

VE

HULL ROAD

IF

AS

R

ES

EA

RC

H

DR

IV

E

IF

AS

R

ES

EA

RC

H

DR

IV

E

PROJECT LOCATION

BUILDING 1

BUILDING 11

N

T-101

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

C :\U se rs

\J

AC

KI

E~

1\ Ap pD at a\ Lo ca l\T em p\

Ac Pu bl is h_

8\

T-

2.

dw g M ay

4,

- 1 :5

5p m

COR

TEL

E. WILSON

E. WILSON

TBD

TBD 5/04/2026

Agricultural

Service Research

USDA ARS

5601 SUNNYSIDE AVENUE

RM 3-2102

BELTVILLE MD 20705

REPAIR HVAC SYSTEM, BULDINGS 1 AND 11 CENTER FOR MEDICAL

AGRICULTURAL AND VETENARY ENTOMOLOGY (CMAVE) -

GAINESVILLE, FLORIDA

BTD

T-102

BUILDING 1

DRAWING LIST

JND

INDEX OF DRAWINGS

DRAWING NO. SHEET NO. TITLE

GENERAL

T-101 1 OF 20 BUILDING 1 TITLE SHEET

T-102 2 OF 20 BUILDING 1 DRAWING LIST

CIVIL

C-101 3 OF 20 BUILDING 1 MECHANICAL SITE PLAN SITE PLAN

HVAC

M-001 4 OF 20 BUILDING 1 GENERAL HVAC NOTES

M-002 5 OF 20 BUILDING 1 HVAC SYMBOL LEGEND

MD101 6 OF 20 BUILDING 1 1ST FLOOR HVAC DEMOLITION

MD102 7 OF 20 BUILDING 1 ROOF HVAC DEMOLITION

M-101 8 OF 20 BUILDING 1 FIRST FLOOR HVAC

M-102 9 OF 20 BUILDING 1 ROOF HVAC PLAN

M-501 10 OF 20 BUILDING 1 MECHANICAL DETAILS

M-601 11 OF 20 BUILDING 1 MECHANICAL SCHEDULES

M-701 12 OF 20 BUILDING 1 DEDICATED OUTDOOR UNIT AHU-1 CONTROLS DIAGRAM

ELECTRICAL

E-001 13 OF 20 BUILDING 1 ELECTRICAL LEGEND

ED101 14 OF 20 BUILDING 1 1ST FLOOR ELECTRICAL DEMO

ED102 15 OF 20 BUILDING 1 ROOF ELECTRICAL DEMOLITION PLAN

E-101 16 OF 20 BUILDING 1 1ST FLOOR ELECTRICAL

E-102 17 OF 20 BUILDING 1 ELECTRICAL ROOF PLAN

E-501 18 OF 20 BUILDING 1 EQUIPMENT SCHEDULE AND DETAILS

E-701 19 OF 20 BUILDING 1 PANEL SCHEDULES

EG101 20 OF 20 BUILDING 1 LIGHTNING PROTECTION PLAN

WORK PHASING INFORMATION

THIS IS PROJECT CONSISTS OF PHASED CONSTRUCTION. SUBMIT A SEPARATE, STAND ALONE BID FOR EACH WORK PHASE. THE WORK IN THIS SET OF PLANS PERTAINS TO BUILDING 1. REFER TO THE SPECIFICATIONS FOR MORE INFORMATION. THE SCOPE

OF THIS PROJECT INCLUDES BUT IS NOT LIMITED TO:

1. REPLACE THE EXISTING ROOF MOUNTED FANS. THE DESIGN INTENT IS TO REPLACE THE EXISTING FANS IN KIND. THE REPLACEMENT FANS WILL CONNECT TO THE EXISTING DUCTWORK. MODIFY DUCTWORK AS REQUIRED TO ACCOMMODATE

THE REPLACEMENT FANS.

2. REPLACE ROOF MOUNTED AHU-1. THE INTENT IS TO REPLACE THE AHU IN KIND. THE REPLACEMENT AHU WILL CONNECT TO THE EXISTING DUCTWORK. MODIFY DUCTWORK AS REQUIRED TO ACCOMMODATE THE REPLACEMENT AHU.

3. AHU-2 AND AHU-3 ARE EXISTING TO REMAIN.

4. ELECTRICAL WORK IS PRIMARILY IN SUPPORT OF THE MECHANICAL WORK. DISCONNECT AND RECONNECT HVAC

EQUIPMENT AS SHOWN.

5. MODIFY THE EXISTING LIGHTNING PROTECTION SYSTEM (LPS) AS REQUIRED TO ACCOMMODATE NEW ROOF-MOUNTED

EQUIPMENT.

GREENHOUSE

SW

RD

D

RI

VE

BUILDING 1

BUILDING 11

EXIST. ACCH-1

EPM

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

C :\U se rs

\J

AC

KI

E~

1\ Ap pD at a\ Lo ca l\T em p\

Ac Pu bl is h_

8\

C -1

.d w g

M ay

4,

- 1

:5 6p m

COR

TEL

E. WILSON

E. WILSON

TBD

TBD 5/04/2026

Agricultural

Service Research

USDA ARS

5601 SUNNYSIDE AVENUE

RM 3-2102

BELTVILLE MD 20705

REPAIR HVAC SYSTEM, BULDINGS 1 AND 11 CENTER FOR MEDICAL

AGRICULTURAL AND VETENARY ENTOMOLOGY (CMAVE) -

GAINESVILLE, FLORIDA

BTD

SCALE:

BUILDING 1

MECHANICAL SITE PLAN

NOT TO SCALE

C-101

GENERAL NOTES

JND

BUILDING 1

MECHANICAL SITE PLAN

C-101

1. THIS SHEET PROVIDED TO SHOW GENERAL SITE

CONDITIONS AND CONTRACTOR LAY DOWN AREAS. NO

CIVIL WORK IS REQUIRED FOR THIS PROJECT.

2. THE LAY DOWN AREAS SHOWN ARE FOR REFERENCE

ONLY AND ARE SUBJECT TO CHANGE. COORDINATE LAY

DOWN AREAS FOE EACH PHASE OF CONSTRUCTION WITH

SITE PERSONNEL AT TIME OF CONSTRUCTION.

LAY DOWN AREA FOR

BUILDING 1 WORK

LAY DOWN AREA FOR

BUILDING 1 WORK

LAY DOWN AREA FOR

BUILDING 11 WORK

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

C :\U se rs

\J

AC

KI

E~

1\ Ap pD at a\ Lo ca l\T em p\

Ac Pu bl is h_

8\

M -0

.d w g

M ay

4,

- 2

:0 0p m

COR

TEL

E. WILSON

E. WILSON

TBD

TBD 5/04/2026

Agricultural

Service Research

USDA ARS

5601 SUNNYSIDE AVENUE

RM 3-2102

BELTVILLE MD 20705

REPAIR HVAC SYSTEM, BULDINGS 1 AND 11 CENTER FOR MEDICAL

AGRICULTURAL AND VETENARY ENTOMOLOGY (CMAVE) -

GAINESVILLE, FLORIDA

BTD

JND

BUILDING 1

GENERAL HVAC NOTES

M-001

1. THIS PROJECT IS A RENOVATION OF AN EXISTING FACILITY. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION OR PROCUREMENT OF EQUIPMENT, MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS MUST BE BROUGHT TO THE CONTRACTING OFFICER'S ATTENTION FOR RESOLUTION BEFORE PROCEEDING

WITH ANY CONSTRUCTION, FABRICATION, OR EQUIPMENT PROCUREMENT.

2. INSTALLATION OF HVAC WORK MUST BE COORDINATED WITH OTHER TRADES BEFORE ANY WORK IS STARTED. DUCTWORK AND PIPING SHOWN ON PLANS IS SCHEMATIC. PROVIDE ALL TRANSITIONS, ELBOWS, REDUCERS, ETC. REQUIRED TO AVOID CONFLICTS & MAXIMIZE CEILING HEIGHTS. EQUIPMENT, PIPING OR DUCTWORK INTERFERING WITH OTHER TRADES MUST

BE RELOCATED AS REQUIRED AT NO ADDITIONAL COST TO THE OWNER.

3. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT MECHANICAL PIPING, DUCTWORK AND EQUIPMENT IS NOT

LOCATED OVER OR ABOVE ANY ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT.

4. AT START OF CONSTRUCTION, PREPARE TYPED LISTS OF EQUIPMENT THAT ARE SUPPLIED REQUIRING ELECTRICAL WORK, AND SEND LISTS TO THE ELECTRICAL CONTRACTOR FOR REVIEW AND COORDINATION.

5. WRITTEN DIMENSIONS ON DRAWINGS HAVE PRECEDENCE OVER SCALED DIMENSIONS. VERIFY DIMENSIONS ON SITE.

6. EQUIPMENT MUST BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED CLEARANCE, UNIFIED FACILITIES

CRITERIA, AND INTERNATIONAL BUILDING CODE / INTERNATIONAL MECHANICAL CODE.

7. INSTALLATION OF EQUIPMENT MUST PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT WITHOUT

NECESSITATING REMOVAL OR MODIFICATION TO OTHER PIPING, WIRING, OR EQUIPMENT.

8. CEILING-MOUNTED EQUIPMENT MUST BE INSTALLED IN SUCH A MANNER THAT LIGHTS, PIPING, DUCTWORK, ETC. , DO NOT

BLOCK ACCESS TO EQUIPMENT AND RELATED ACCESSORIES.

9. SEAL WITH SILICONE ALL GAPS BETWEEN WALL, CEILING, AND FLOOR OPENINGS AND HVAC EQUIPMENT PENETRATIONS.

PATCH LARGE GAPS BEFORE SEALANT IS APPLIED.

10. DUCTWORK AIR DISTRIBUTION SYSTEMS MUST BE INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS AND THE

PRESSURE CLASSIFICATION OF EACH INDIVIDUAL DUCTWORK SYSTEM.

11. VOLUME DAMPERS MUST BE PROVIDED AT EACH MAIN BRANCH TAKE-OFF, EACH TAKEOFF TO DIFFUSERS/GRILLS/REGISTERS, AND OTHER LOCATIONS WHERE REQUIRED TO PROPERLY BALANCE THE SYSTEM. ALL

REQUIRED VOLUME DAMPERS MAY NOT BE SHOWN ON PLANS.

12. INSTRUMENT TEST HOLES MUST BE PROVIDED IN AIR DISTRIBUTION SYSTEMS WHEREVER VOLUME DAMPERS ARE

INSTALLED. TEST HOLES MUST BE SEALED WITH RUBBER OR PLASTIC TEST HOLE PLUGS.

13. SQUARE ELBOWS MUST ONLY BE USED WHERE SPACE LIMITATIONS PREVENT USE OF 1-1/2 RADIUS ELBOW AND ONLY UPON APPROVAL OF CONTRACTING OFFICER. PROVIDE TURNING VANES IN ALL SQUARE ELBOWS GREATER THAN OR EQUAL TO 45°. TURNING VANES MUST BE SINGLE THICKNESS TYPE WITHOUT RAILING EDGE. TURNING VANES LONGER THAN 36

INCHES MUST BE DOUBLE THICKNESS TYPE.

14. DUCTWORK RUNOUTS TO AIR DISTRIBUTION DEVICES MUST BE SAME DIAMETER AS AIR DISTRIBUTION DEVICE INLET

CONNECTION UNLESS OTHERWISE NOTED ON THE DRAWINGS.

15. FLEXIBLE DUCTWORK RUNOUTS FROM BRANCH DUCTS TO AIR DISTRIBUTION DEVICES MUST NOT EXCEED 5 FEET IN LENGTH. BENDS IN FLEXIBLE DUCTWORK MUST NOT EXCEED A MAXIMUM OF 45 DEGREE CHANGE OF DIRECTION AND MUST BE SUPPORTED SUCH THAT THE BEND RADIUS IS NOT RESTRICTIVE TO AIR FLOW THROUGH THE DUCT. FLEXIBLE

DUCTWORK MUST NOT BE CRUSHED OR DISTORTED IN ITS FINAL CONFIGURATION.

16. PROVIDE SHEETMETAL TRANSITIONS AT AIR HANDLING UNITS, HEAT PUMP UNITS, FANS, AND OTHER SIMILAR HVAC EQUIPMENT. TRANSITION TO FULL SIZE OF CONNECTION ON UNIT. FLEXIBLE DUCT CONNECTORS MUST BE USED ON FINAL

CONNECTION TO AIR HANDLING EQUIPMENT.

17. TRANSFER DUCTS MUST BE SIZED FOR MAX VELOCITY ALLOWED OF 500 FPM. OPEN-ENDED TRANSFER DUCTS MUST HAVE

90° ELBOW FOR SOUND ATTENUATION.

18. LOUVERED SUPPLY AIR DIFFUSERS MUST BE 4-WAY FLOW UNLESS OTHERWISE SHOWN BY FLOW ARROWS ON THE DRAWINGS. LINEAR DIFFUSERS MUST BE ADJUSTABLE 2-WAY FLOW. PROVIDE BATT INSULATION ON DIFFUSER AND

GRILLES THAT ARE EXPOSED TO CEILING PLENUM.

19. EXACT LOCATIONS OF THERMOSTATS, CO2 SENSORS, AND EMCS SENSORS MUST BE COORDINATED WITH FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL AND ELECTRICAL EQUIPMENT. MOUNT THERMOSTATS AND CO2 SENSORS

MINIMUM 48" AFF.

20. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE OVER SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.

21. ALL EQUIPMENT MUST BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED PUBLISHED LITERATURE.

22. DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.

23. EXPOSED DUCTWORK, WITH THE EXCEPTION OF DUCTWORK IN MECHANICAL ROOMS MUST BE DOUBLE-WALL, DUCTWORK WITH COATING.

24. ALL THERMOSTATS MUST BE WALL MOUNTED AND WIRED.

25. ALL EQUIPMENT INSTALLED IN THIS PROJECT MUST COMPLY WITH THE "BUY AMERICAN ACT" (BAA). BASIS OF DESIGN

SHOWN ON SCHEDULES IS TO ESTABLISH A STANDARD OF QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT FROM ANOTHER MANUFACTURER IS ACCEPTABLE. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN FOR INFORMATION ONLY AND MAY OR MAY NOT COMPLY WITH BAA. REFER TO

SPECIFICATIONS FOR COMPLETE REQUIREMENTS.

26. CONTROLS CONTRACTOR MUST PROVIDE ALL LOW VOLTAGE DEVICES, CONDUCTORS, AND PATHWAYS IN ACCORDANCE WITH THE REQUIREMENTS OF 26 20 00. INSTALL CONTROL WIRING IN CONDUIT. SEE DIVISION 26 SPECIFICATIONS FOR

REQUIREMENTS.

HVAC GENERAL NOTES:

1. THE DEMOLITION PLANS AND EXISTING CONDITIONS SHOWN ARE APPROXIMATE AND ARE TO BE FIELD VERIFIED. ITEMS TO

BE REMOVED ARE DENOTED BY HATCHING. ADDITIONAL ITEMS ARE LIKEY TO REQUIRE REMOVAL, RELOCATION AND/OR REINSTALLATION TO PERFORM THE WORK BUT REQUIRE VERIFICATION THRU C.O. BEFORE PERFORMING THE WORK.

2. DEMOLITION MUST INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS IDENTIFIED. THE CONTRACTOR MUST COORDINATE ALL REQUIRED RENOVATION AND NEW CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE TOTAL EXTENT OF THE

DEMOLITION WORK REQUIRED.

3. THE CONTRACTOR IS RESPONSIBLE FOR THE DEMOLITION AND REMOVAL OF ALL EXISTING BUILDING COMPONENTS, MATERIALS, EQUIPMENT, AND APPURTENANCES AS REQUIRED TO PROVIDE ALL NEW CONSTRUCTION.

4. IN THE EVENT THE CONTRACTOR ENCOUNTERS MATERIAL REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED HARMLESS, THE CONTRACTOR MUST

IMMEDIATELY REPORT THE CONDITION TO THE CONTRACTING OFFICER IN WRITING.

5. THE CONTRACTOR IS RESPONSIBLE FOR THE ERECTION, MAINTENANCE, AND REMOVAL OF ALL CONSTRUCTION

ASSISTANCE DEVICES SUCH AS SCAFFOLDING AND BARRIERS.

6. THE BUILDING ENVELOPE MUST REMAIN WATERTIGHT THROUGHOUT THE CONSTRUCTION PROCESS.

7. IF IT BECOMES NECESSARY DURING DEMOLITION TO TEMPORARILY REMOVE ANY EXISTING WORK NOT SPECIFICALLY NOTED TO BE REMOVED OR RELOCATED (THEREBY IMPLYING THAT THEY ARE TO BE LEFT FOR FUTURE USE), THE CONTRACTOR MUST REINSTALL SAID WORK TO FULLY OPERABLE CONDITION IN THEIR ORIGINAL LOCATIONS

8. CONTRACTOR MUST DEMOLISH ALL EQUIPMENT, PIPING, DUCTWORK, INSULATION, SUPPORTS, CONTROLS

THERMOSTATS, WIRING AND ALL APPURTENANCES WITH THE HVAC SYSTEM TO BE DEMOLISHED.

9. PROTECT EXISTING INTERIOR WALLS DURING REMOVAL AND CONSTRUCTION. PROVIDE TEMPORARY PROTECTION FROM DUST, NOISE, DAMAGE, ETC. AND CONSTRUCTION BARRIERS AND OTHER SITE PROTECTION REQUIREMENTS CONSISTENT

WITH THE SPECIFICATIONS SECTION, AND DIVISION 1, GENERAL REQUIREMENTS.

10. IN AREAS OF WORK, AT EXISTING FINISHES TO REMAIN, PATCH AND REPAIR ANY DAMAGE TO MATCH EXISTING FINISH.

PREPARE SURFACE TO RECEIVE NEW FINISHES.

11. FIXED ITEMS ON WALLS AND CEILINGS WILL REMAIN IN PLACE DURING CONSTRUCTION. CONTRACTOR MUST PROVIDE

PROTECTION OF EXISTING FIXED ITEMS.

HVAC GENERAL DEMOLITION NOTES:

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

C :\U se rs

\J

AC

KI

E~

1\ Ap pD at a\ Lo ca l\T em p\

Ac Pu bl is h_

8\

M -0

.d w g

M ay

4,

- 2

:0 0p m

COR

TEL

E. WILSON

E. WILSON

TBD

TBD 5/04/2026

Agricultural

Service Research

USDA ARS

5601 SUNNYSIDE AVENUE

RM 3-2102

BELTVILLE MD 20705

REPAIR HVAC SYSTEM, BULDINGS 1 AND 11 CENTER FOR MEDICAL

AGRICULTURAL AND VETENARY ENTOMOLOGY (CMAVE) -

GAINESVILLE, FLORIDA

BTD

JND

BUILDING 1

HVAC SYMBOL LEGEND

M-002

-10"

S1

ABBREVIATIONS:

@ AT

& AND

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

ARCH ARCHITECTURAL

AS AIR SEPARATOR

ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING,

AND AIR CONDITIONING ENGINEERS

ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS

APD AIR PRESSURE DROP

BLDG BUILDING

BTU, BTUH BRITISH THERMAL UNITS, BTUs PER HOUR

C CONDENSATE RECEIVER

CD CONDENSATE DRAIN

CFM CUBIC FEET PER MINUTE

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CLG COOLING

CMU CONCRETE MASONRY UNIT

CO CLEANOUT

CO2 CARBON DIOXIDE

CONC CONCRETE

COND STEAM CONDENSATE

CONN CONNECT, CONNECTING, CONNECTION

CONT CONTINUED

CONV STEAM CONVERTER

COP COEFFICIENT OF PERFORMANCE

COR CONTRACTING OFFICER'S (OWNER'S)

REPRESENTATIVE

CU CONDENSING UNIT

D DEPTH

D DIFFUSER

DISC DISCONNECT

DB, Tdb DRY BULB (TEMPERATURE) dBA DECIBELS

DCW DOMESTIC COLD WATER

DDC DIRECT DIGITAL CONTROLS

DEG F (°F) DEGREES FAHRENHEIT

DFCU DUCTLESS FAN COIL UNIT

DIA, Ø DIAMETER

DIV DIVISION

DN DOWN

DP DIFFERENTIAL PRESSURE

DWG DRAWING

DWH DOMESTIC WATER HEATER

DX DIRECT EXPANSION

(E) EXISTING

EA EXHAUST AIR

EAG EXHAUST AIR GRILLE

EAT ENTERING AIR TEMPERATURE

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EFF EFFICIENCY

ELEC ELECTRICAL

EMCS ENERGY MONITORING AND CONTROLS SYSTEM

ER EXHAUST REGISTER

ERV ENERGY RECOVERY VENTILATOR

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

EUH ELECTRIC UNIT HEATER

EWT ENTERING WATER TEMPERATURE

EXIST. EXISTING

EXT EXTERIOR

EXH EXHAUST

DEG EXISTING

FCU FAN COIL UNIT

FD FIRE DAMPER

FFE FINISHED FLOOR ELEVATION

FLA FULL LOAD AMPS

FPD FLUID PRESSURE DROP

FPM FEET PER MINUTE

FSD FIRE SMOKE DAMPER

FT FOOT, FEET

GA GAUGE

GALV GALVANIZED

GC GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

GRD GRILLES, REGISTERS AND DIFFUSERS

HP HORSE POWER

HR HOUR

HTG HEATING

HTR HEATER

HTW HEATING WATER

HTWR HEATING WATER RETURN

HTWS HEATING WATER SUPPLY

HVAC HEATING, VENTILATING, AND AIR CONDITIONING

HWP HOT WATER PIPE

HWR HOT WATER RETURN

HWS HOT WATER SUPPLY

HZ HERTZ

IMC INTERNATIONAL MECHANICAL CODE

IN INCH, INCHES

IN WC INCHES WATER COLUMN

IN WG INCHES WATER GAUGE

IPLV INTEGRATED PART LOAD VALUE

KW KILOWATTS

L LENGTH, LOUVER (WALL)

LAT LEAVING AIR TEMPERATURE

LBD LINEAR BAR DIFFUSER

LB POUNDS

LD LINEAR DIFFUSER

LPR LOW PRESSURE RETURN

LPS LOW PRESSURE SUPPLY

LWT LEAVING WATER TEMPERATURE

M MOTORIZED

MA MIXED AIR

MAX MAXIMUM

MBH 1000 BRITISH THERMAL UNITS

MCA MINIMUM CIRCUIT AMPACITY

MECH MECHANICAL

MER MECHANICAL EQUIPMENT ROOM

MERV MINIMUM EFFICIENCY REPORTING VALUE

MIN MINIMUM

MOCP MAXIMUM OVER CURRENT PROTECTION

MSS SP MANUFACTURERS STANDARD SOCIETY STANDARD

PRACTICE

MTL METAL

N.C. NORMALLY CLOSED

NC NOISE CRITERIA

NG NATURAL GAS

NO. NUMBER

N.O. NORMALLY OPEN

NTS NOT TO SCALE

OA OUTSIDE AIR

PD PRESSURE DROP

PH PHASE

PLBG PLUMBING

PPM PARTS PER MILLION

PRV PRESSURE RELIEF VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

QTY QUANTITY

R/A RETURN AIR

RAG RETURN AIR GRILLE

REF REFER TO, REFERENCE

RF RADIO FREQUENCY

REQD REQUIRED

RH RELATIVE HUMIDITY, ROOF HOOD

RLD RECTANGULAR LINEAR DIFFUSER

RM ROOM

RPM REVOLUTIONS PER MINUTE

RR RETURN REGISTER

SA SUPPLY AIR

SAD SUPPLY AIR DIFFUSER

SAG SUPPLY AIR GRILLE

SD SMOKE DAMPER, SMOKE DETECTOR

SEER SEASONAL ENERGY EFFICIENCY RATIO

SF SUPPLY FAN

SHT SHEET

SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTOR'S

NATIONAL ASSOCIATION

SP STATIC PRESSURE

SS STAINLESS STEEL

SWR SIDEWALL REGISTER

T&P TEMPERATURE AND PRESSURE

TEMP TEMPERATURE

TSTAT THERMOSTAT

TYP TYPICAL

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UMCS UTILITY MONITORING AND CONTROL SYSTEM

V VOLTAGE, VOLTS

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VFD VARIABLE FREQUENCY DRIVE

WG WATER GAUGE

WB WET BULB (TEMPERATURE)

WPD WATER PRESSURE DROP

W/O WITHOUT

MISCELLANEOUS LEGEND:

AIR DISTRIBUTION DEVICE TAGS

AIRFLOW (CFM)

NORTH ARROW

SD

SP

F

CO

DUCT SMOKE DETECTOR

CARBON MONOXIDE SENSOR

STATIC PRESSURE SENSOR

FIRESTAT

TEMPERATURE SENSORT

VARIABLE FREQUENCY DRIVEVFD

FLOW ARROW

RETURN AIR GRILLE

SUPPLY AIR DIFFUSER

FLOW ARROWS INDICATE AIR PATTERN.

NO FLOW ARROWS SHOWN INDICATES

4-WAY PATTERN.

EXHAUST AIR GRILLE

T THERMOSTAT

H HUMIDISTAT

TH THERMOSTAT/ HUMIDISTAT

HUMIDITY SENSORH

NECK SIZE

DP DIFFERENTIAL PRESSURE SENSOR

POINT OF RECONNECTION OR

EXTENT OF DEMOLITION

PIPING LEGEND:

EXISTING PIPING (EXIST.)

ITEMS TO BE DEMOLISHED

FLEXIBLE CONNECTION

THERMOMETER

PRESSURE REDUCING VALVE

MANUAL AIR VENT

PRESSURE/TEMPERATURE TAP WITH

BALL VALVE

PRESSURE SWITCH

PLUG VALVE

FLOW SWITCH

T&P RELIEF VALVE

AUTOMATIC AIR VENT

PRESSURE GAUGE WITH GAUGE COCK

PS

FS

BUTTERFLY VALVE

STRAINER WITH BLOWDOWN VALVE,

CAP, AND CHAIN

FLOW MEASURING/BALANCING/SHUT-

OFF VALVE

GATE VALVE

CHECK VALVE

BALL VALVE

CONCENTRIC REDUCER

DIRECTION OF FLOW

ECCENTRIC REDUCER

PIPE FLANGE

PIPE CAP

UNION

TEE OUTLET UP

BRANCH BOTTOM CONNECTION

BRANCH TOP CONNECTION

ELBOW UP

ELBOW DOWN

RISE OR DROP

TEE OUTLET DOWN

DUCTWORK LEGEND:

M

FIRE DAMPER

EXHAUST AIR DUCT DOWN

EXHAUST AIR DUCT UP

RETURN AIR DUCT DOWN

30"x14"

SQUARE TO ROUND DUCT BRANCH TAKE-OFF

WITH 45 DEGREE BRANCH INLET

ROUND DUCT BRANCH TAKE-OFF FROM

RECTANGULAR MAIN WITH CONICAL TAP

FLEXIBLE DUCT CONNECTION

DUCT SIZE TRANSITION

RECTANGULAR DUCT BRANCH TAKE-OFF

WITH 45 DEGREE BRANCH INLET

90 DEGREE DUCT ELBOW WITH TURNING VANES

24"Ø ROUND DUCT. DIAMETER INDICATED IN INCHES.

IN-LINE 90 DEGREE RISE/DROP IN

SUPPLY DUCT

FD

SD

DAMPER TYPE:

M - MOTORIZED DAMPER (ELECTRIC)

VD

SMOKE DAMPER

VOLUME/BALANCING DAMPER

(LABEL MAY BE OMITTED)

BD

BACKDRAFT DAMPER

(COUNTER-BALANCED UNLESS

OTHERWISE NOTED)

RADIUS DUCT ELBOW - ROUND OR

RECTANGULAR (MIN. 1.5 RADIUS UNLESS

OTHERWISE NOTED)

RECTANGULAR DUCT. SIZE INDICATED IN

INCHES, FIRST NUMBER IS SIDE SHOWN.

DASHED LINES INDICATE ACOUSTICAL LINER

FSD

COMBINATION

FIRE/SMOKE DAMPER

IN-LINE 90 DEGREE RISE/DROP IN

RETURN DUCT

DUCT SIZE TRANSITION RECTANGULAR TO

ROUND

RETURN AIR DUCT UP

SUPPLY OR OUTSIDE AIR DUCT DOWN

SUPPLY OR OUTSIDE AIR DUCT UP

IN-LINE 90 DEGREE RISE/DROP IN

EXHAUST DUCT

SD

DUCT MOUNTED SMOKE DETECTORGLOBE VALVEPLAN

NORTH

HATCHING INDICATES ITEMS TO

BE DISMANTLED AND REMOVED.

DEMOLITION LEGEND:

EXISTING EQUIPMENT

CH-1 (E) (E) AFTER AN EQUIPMENT

MARK INDICATES EXISTING

TRUE NORTH

DIFFUSER MARK (REFER

TO GRD SCHEDULE)

HEATING WATER RETURN (HTWR)

HEATING WATER SUPPLY (HTWS)

CHILLED WATER RETURN (CHWR)

CHILLED WATER SUPPLY (CHWS)

ABBREVIATION NOTES:

1. SOME ABBREVIATIONS SHOWN MAY NOT BE USED FOR THIS PROJECT.

2. SCHEDULED EQUIPMENT IS NOTED USING UNDERLINED TEXT SUCH AS AHU-1. THIS IS NOT AN

ABBREVIATION. IT IS AN EQUIPMENT MARK. REFER TO SCHEDULE SHEETS M-601 THRU M-699

FOR INFORMATION REGARDING SCHEDULED EQUIPMENT.

EXIST.

VAV-6

EXIST.

MAV-5

EXIST.

MAV-6

EXIST.

VAV-7

EXIST.

VAV-8

EXIST.

MAV-7 EXIST.

MAV-8

EXIST.

VAV-9

EXIST.

CAV-2

EXIST.

MAV-11

EXIST.

VAV-11

EXIST.

CAV-1

EXIST.

MAV-2

EXIST.

MAV-1

EXIST.

VAV-1

EXIST.

MAV-3 EXIST.

VAV-4

EXIST.

VAV-3

EXIST.

VAV-28

EXIST.

CAV-3

EXIST.

VAV-27

EXIST.

VAV-26

EXIST.

VAV-25

EXIST.

VAV-24

EXIST.

VAV-23

EXIST.

VAV-22

EXIST.

VAV-12

EXIST.

MAV-12

EXIST.

VAV-19

EXIST.

VAV-20

EXIST.

VAV-21

EXIST.

MAV-9

EXIST.

MAV-10

EXIST.

VAV-2

EXIST.

VAV-10

EXIST.

VAV-17

EXIST.

VAV-18

EXIST.

HC-14EXIST.

HC-13

EXIST.

HC-15

EXIST.

HC-16

EXIST.

MAV-4

EXIST.

UH-1

EXIST.

VAV-5

EXIST.

VAV-13

EXIST.

VAV-14

EXIST.

VAV-16

EXIST.

VAV-15

LAB

153/154 LAB

150-152

C O

R R

ID

O

R

OFFICE

148/149

BOILER RM

MECH RM

OFFICE

OFFICE

LAB

141-143

VESTIBULE

LAB

137-140

CORRIDOR

CORRIDOR

OFFICE

OFFICE

LAB

133/134 MICROSCOPE RM

OFFICE

OFFICE

OFFICE

OFFICE

CORRIDOR

CONFERENCE RM

CONF. RM

125A

OFFICE

COPY RM

127 OFFICE

VESTIBULE

OFFICE

OFFICE

WOMENS TLT

MENS TLT

JAN

DARK RM

MSCOPE RM

LAB

LAB

LAB

LAB

LAB

LAB

189/190

MECH RM

OFFICE

C O

R R

ID

O

R

FIRST AID

LAB

175/176

OFFICE

OFFICE

118B

LAB

174B

LAB

174A

BREAK RM

LAB

LAB

170/171

LAB

LAB

167/168

INSECT REARING

INSECT REARING

CORRIDOR

INSECT REARING

INSECT REARING

CORRIDOR

LAB

ELEC RM

LAB

193/194

OFFICE

DARK RM

LAB

LAB

196A

LAB

196B

CHEM STORAGE

OFFICE

OFFICE

LAB

C O

R R

ID

O

R

4 LAB

LAB

ENV RM

STORAGE

WOMENS TLT

MENS TLT

LAB

LAB

OFFICE

STORAGE

STORAGE

STORAGE

STORAGE

OFFICE

OFFICE

STORAGE

LAB

OFFICE

OFFICE

OFFICE

OFFICE

118A

WOMENS VESTIBULE

101A

SCALE:

BUILDING 1

1ST FLOOR HVAC DEMOLITION

3/32" = 1'-0"

MD101

GENERAL NOTES

GRAPHIC SCALE

A. NO INTERIOR DEMOLITION. SHEET PROVIDED FOR

INFORMATION ONLY.

1'-0'

EPM

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

C :\U se rs

\J

AC

KI

E~

1\ Ap pD at a\ Lo ca l\T em p\

Ac Pu bl is h_

8\

M D

1.

dw g

M ay

4,

- 2

:0 0p m

COR

TEL

E. WILSON

E. WILSON

TBD

TBD 5/04/2026

Agricultural

Service Research

USDA ARS

5601 SUNNYSIDE AVENUE

RM 3-2102

BELTVILLE MD 20705

REPAIR HVAC SYSTEM, BULDINGS 1 AND 11 CENTER FOR MEDICAL

AGRICULTURAL AND VETENARY ENTOMOLOGY (CMAVE) -

GAINESVILLE, FLORIDA

BTD

JND

BUILDING 1

1ST FLOOR HVAC DEMOLITION

MD101

LEGEND

MAV LABORATORY MAKEUP AIR VALVE

VAV VARIABLE AIR VOLUME TERMINAL UNIT

CAV CONSTANT AIR VOLUME TERMINAL UNIT

HOOD

H O

O D

HOOD

HOOD

H O

O D

HOOD

H O

O D

H O

O D

HOOD

H O

O D

HOOD

HOOD

SCALE:

BUILDING B1

ROOF HVAC DEMOLITION

3/32" = 1'-0"

MD102

GENERAL NOTES

GRAPHIC SCALE

A. EXISTING ROOF IS A LOW-SLOPED MEMBRANE SYSTEM.

EXISTING ROOF WARRANTY MUST BE MAINTAINED

DURING THE WORK.

1'-0'

KEYED NOTESX

1. DISMANTLE AND REMOVE EXISTING ROOF FAN.

PREPARE EXISTING DUCTWORK FOR CONNECTION TO

NEW FAN. EXISTING ROOF RAILS TO REMAIN.

2. EXISTING BACKDRAFT DAMPERS TO REMAIN.

3. DISMANTLE AND REMOVE EXISTING AIR HANDLER.

4. EXISTING AIR HANDLER TO REMAIN.

5. DISMANTLE AND REMOVE EXISTING EXHAUST FAN.

EXISTING CURB TO REMAIN FOR INSTALLATION OF NEW

FAN.

6. DISMANTLE AND REMOVE EXISTING SUPPLY FAN.

EXISTING CURB TO REMAIN FOR INSTALLATION OF NEW

FAN

1 2

1 2

1 2

EF-6

EF-12

EF-5

EF-9

EF-10

EF-13

EF-14 SF-1

EF-7

EF-11

AHU-2 AHU-3

AHU-1

EF-2A/2B

1 2

EF-3A/3B

EF-1A/1B

EF-4A/4B

EF-8

4 4

EPM

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

C :\U se rs

\J

AC

KI

E~

1\ Ap pD at a\ Lo ca l\T em p\

Ac Pu bl is h_

8\

M D

2.

dw g

M ay

4,

- 2

:0 0p m

COR

TEL

E. WILSON

E. WILSON

TBD

TBD 5/04/2026

Agricultural

Service Research

USDA ARS

5601 SUNNYSIDE AVENUE

RM 3-2102

BELTVILLE MD 20705

REPAIR HVAC SYSTEM, BULDINGS 1 AND 11 CENTER FOR MEDICAL

AGRICULTURAL AND VETENARY ENTOMOLOGY (CMAVE) -

GAINESVILLE, FLORIDA

BTD

JND

BUILDING 1

ROOF HVAC DEMOLITION

MD102

EXISTING FUME HOOD

BELOW ROOF (TYP)

EXIST.

VAV-6

EXIST.

MAV-5

EXIST.

MAV-6

EXIST.

VAV-7

EXIST.

VAV-8

EXIST.

MAV-7 EXIST.

MAV-8

EXIST.

VAV-9

EXIST.

CAV-2

EXIST.

MAV-11

EXIST.

VAV-11

EXIST.

CAV-1

EXIST.

MAV-2

EXIST.

MAV-1

EXIST.

VAV-1

EXIST.

MAV-3 EXIST.

VAV-4

EXIST.

VAV-3

EXIST.

VAV-28

EXIST.

CAV-3

EXIST.

VAV-27

EXIST.

VAV-26

EXIST.

VAV-25

EXIST.

VAV-24

EXIST.

VAV-23

EXIST.

VAV-22

EXIST.

VAV-12

EXIST.

MAV-12

EXIST.

VAV-19

EXIST.

VAV-20

EXIST.

VAV-21

EXIST.

MAV-9

EXIST.

MAV-10

EXIST.

VAV-2

EXIST.

VAV-10

EXIST.

VAV-17

EXIST.

VAV-18

EXIST.

HC-14EXIST.

HC-13

EXIST.

HC-15

EXIST.

HC-16

EXIST.

MAV-4

EXIST.

UH-1

EXIST.

VAV-5

EXIST.

VAV-13

EXIST.

VAV-14

EXIST.

VAV-16

EXIST.

VAV-15

LAB

153/154 LAB

150-152

C O

R R

ID

O

R

OFFICE

148/149

BOILER RM

MECH RM

OFFICE

OFFICE

LAB

141-143

VESTIBULE

LAB

137-140

CORRIDOR

CORRIDOR

OFFICE

OFFICE

LAB

133/134 MICROSCOPE RM

OFFICE

OFFICE

OFFICE

OFFICE

CORRIDOR

CONFERENCE RM

CONF. RM

125A

OFFICE

COPY RM

127 OFFICE

VESTIBULE

OFFICE

OFFICE

WOMENS TLT

MENS TLT

JAN

DARK RM

MSCOPE RM

LAB

LAB

LAB

LAB

LAB

LAB

189/190

MECH RM

OFFICE

C O

R R

ID

O

R

FIRST AID

LAB

175/176

OFFICE

OFFICE

118B

LAB

174B

LAB

174A

BREAK RM

LAB

LAB

170/171

LAB

LAB

167/168

INSECT REARING

INSECT REARING

CORRIDOR

INSECT REARING

INSECT REARING

CORRIDOR

LAB

ELEC RM

LAB

193/194

OFFICE

DARK RM

LAB

LAB

196A

LAB

196B

CHEM STORAGE

OFFICE

OFFICE

LAB

C O

R R

ID

O

R

4 LAB

LAB

ENV RM

STORAGE

WOMENS TLT

MENS TLT

LAB

LAB

OFFICE

STORAGE

STORAGE

STORAGE

STORAGE

OFFICE

OFFICE

STORAGE

LAB

OFFICE

OFFICE

OFFICE

OFFICE

118A

WOMENS VESTIBULE

101A

B-1 (E)

CHW EXP

TANK (E)

P-2 (E)

P-3 (E)P-1 (E)

AC (E)

B-1A (E)

GWH (E)

FLUE (E)

P-6 (E)

SCALE:

BUILDING 1

1ST FLOOR HVAC

3/32" = 1'-0"

M-101

GRAPHIC SCALE

1'-0'

EPM

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

C :\U se rs

\J

AC

KI

E~

1\ Ap pD at a\ Lo ca l\T em p\

Ac Pu bl is h_

8\

M -1

.d w g

M ay

4,

- 2

:0 0p m

COR

TEL

E. WILSON

E. WILSON

TBD

TBD 5/04/2026

Agricultural

Service Research

USDA ARS

5601 SUNNYSIDE AVENUE

RM 3-2102

BELTVILLE MD 20705

REPAIR HVAC SYSTEM, BULDINGS 1 AND 11 CENTER FOR MEDICAL

AGRICULTURAL AND VETENARY ENTOMOLOGY (CMAVE) -

GAINESVILLE, FLORIDA

BTD

JND

BUILDING 1

1ST FLOOR HVAC

M-101

LEGEND

MAV LABORATORY MAKEUP AIR VALVE

VAV VARIABLE AIR VOLUME TERMINAL UNIT

CAV CONSTANT AIR VOLUME TERMINAL UNIT

(E) EXISTING EQUIPMENT

GENERAL NOTES

A. NO INTERIOR WORK. SHEET PROVIDED FOR INFORMATION

ONLY.

HOODH

O

O D

HOOD

SCALE:

BUILDING B1

ROOF HVAC PLAN

3/32" = 1'-0"

M-102

GRAPHIC SCALE

1'-0'

KEYED NOTESX

1. PROVIDE UTILITY SET TYPE EXHAUST FAN. INSTALL ON

EXISTING ROOF RAILS. (2) FANS ARE REQUIRED AT

EACH LOCATION.

2. PROVIDE GRAVITY BACKDRAFT DAMPER TO BE

INSTALLED IN EXISTING DUCTWORK.

3. PROVIDE CURB MOUNTED EXHAUST FAN. INSTALL ON

EXISTING CURB.

4. PROVIDE CURB MOUNTED SUPPLY FAN. INSTALL ON

EXISTING CURB.

5. PROVIDE CENTRAL STATION AHU. AHU TO BE

DIMENSIONALLY EQUAL TO EXISTING AHU OR FURNISH

CURB ADAPTOR.

EF-2A/2B

EF-3A/3B

EF-1A/1B

EF-4A/4B

AHU-1

EXISTING AHU-3EXISTING AHU-2

EF-11

EF-7

SF-1EF-14

EF-13

EF-10

EF-9

EF-5

EF-12

EF-6

EF-8

3 4

EPM

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

C :\U se rs

\J

AC

KI

E~

1\ Ap pD at a\ Lo ca l\T em p\

Ac Pu bl is h_

8\

M -1

.d w g

M ay

4,

- 2

:0 0p m

COR

TEL

E. WILSON

E. WILSON

TBD

TBD 5/04/2026

Agricultural

Service Research

USDA ARS

5601 SUNNYSIDE AVENUE

RM 3-2102

BELTVILLE MD 20705

REPAIR HVAC SYSTEM, BULDINGS 1 AND 11 CENTER FOR MEDICAL

AGRICULTURAL AND VETENARY ENTOMOLOGY (CMAVE) -

GAINESVILLE, FLORIDA

BTD

JND

BUILDING 1

ROOF HVAC PLAN

M-102

EXISTING FUME HOOD

BELOW ROOF (TYP)

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

C :\U se rs

\J

AC

KI

E~

1\ Ap pD at a\ Lo ca l\T em p\

Ac Pu bl is h_

8\

M -5

.d w g

M ay

4,

- 2

:0 0p m

COR

TEL

E. WILSON

E. WILSON

TBD

TBD 5/04/2026

Agricultural

Service Research

USDA ARS

5601 SUNNYSIDE AVENUE

RM 3-2102

BELTVILLE MD 20705

REPAIR HVAC SYSTEM, BULDINGS 1 AND 11 CENTER FOR MEDICAL

AGRICULTURAL AND VETENARY ENTOMOLOGY (CMAVE) -

GAINESVILLE, FLORIDA

BTD

JND

BUILDING 1

MECHANICAL DETAILS

M-501

BIRD SCREEN

MOTOR

STAINLESS STEEL BACKDRAFT DAMPER

EXISTING EXHAUST DUCT

SECURE FAN TO CURB AND SEAL TIGHT

EXISTING ROOF

VIBRATION ABSORBING

MOUNT

DUCT

FASTENING

FLANGE

EXISTING ROOF CURB

OUTSIDE

AIR INTAKE

PIPING

ENCLOSURE

RE-USE EXISTING

SA DUCT

7/

8"

NORTH ELEVATION

NOTE:

DIMENSIONS ARE BASED ON SHOP

DRAWINGS OF THE EXISTING AIR HANDLER.

THEY ARE SHOWN FOR REFERENCE.

VERIFY ACTUAL DIMENSIONS IN THE FIELD

PRIOR TO ORDERING EQUIPMENT.

PLAN

OUTSIDE

AIR INTAKE

RE-USE EXISTING

ROOF CURB

PROVIDE HEAVY

DUTY BASE RAIL

RE-USE EXISTING

PIPING (FAR SIDE)

TO THE EXTENT

POSSIBLE

REMOVE EXISTING LIGHTNING PROTECTION SYSTEM, INCLUDING

AIR TERMINALS AND REINSTALL ON NEW CONSTRUCTION

EXISTING EXHAUST DUCT

EXISTING ROOF DECK

EXISTING GRAVITY BACKDRAFT DAMPERS

EXISTING MOUNTING RAIL

REMOVE EXISTING GUY

WIRES AND PROVIDE NEW

STAINLESS STEEL WIRES PROVIDE EXHAUST FAN AS SCHEDULED

PROVIDE EXHAUST FAN AS SCHEDULED

SA

OA

OA

FILTER HYDRONIC

COILS ACCESS FAN SECTION DISCHARGE

PLENUM

MIXING

BOX

FILTER HYDRONIC

COILS ACCESS FAN SECTION DISCHARGE

PLENUM

MIXING

BOX 82

1/

2"

39" 13" 49" 27" 45" 29"

202"

SCALE:

DOWNBLAST ROOF EXHAUST FAN DETAIL

NOT TO SCALE

M-501

SCALE:

UPBLAST UTILITY FAN DETAIL

NOT TO SCALE

M-501

SCALE:

AHU-1 DETAIL

NOT TO SCALE

M-501

REMOVE EXISTING GUY WIRES AND

PROVIDE NEW STAINLESS STEEL WIRES

EXISTING GUY WIRE ANCHORS (TYP)

NOTES

1. PROVIDE WITH GRAVITY BACKDRAFT DAMPER

2. PROVIDE SPEED CONTROLLER MOUNTED IN ACCESSIBLE SPACE (SHIPPED LOOSE)

3. PROVIDE DUCT TO OUTDOORS. TERMINATE WITH WALL CAP. COORDINATE COLOR WITH ARCH.

4. DIRECT DRIVE

5. BELT DRIVE

6. VARIABLE SPEED DRIVE

7. HANGING SPRING ISOLATOR

8. THE EXISTING STARTING DEVICE (CONTACTOR OR VFD) IS TO BE REUSED FOR ALL FANS.

9. PROVIDE FACTORY INSTALLED DISCONNECT SWITCHES FOR 115 VOLT, SINGLE PHASE FANS. DISCONNECT SWITCHES FOR 3 PHASE FANS TO BE PROVIDED

BY THE ELECTRICAL CONTRACTOR. REFER TO ELECTRICAL DRAWINGS.

CENTRAL STATION AIR HANDLING UNIT SCHEDULE

MARK

BASIS OF DESIGN AIRFLOW DATA HOT WATER PRE-HEAT COIL DATA CHILLED WATER COOLING COIL DATA ELECTRICAL DATA

NOTES

MANUFACTURER MODEL NO.

SUPPLY

AIR FLOW

(CFM)

MINIMUM

OUTSIDE

AIR

(CFM)

ESP

(IN. WG)

TSP

(IN. WG)

FAN

QTY

FAN

MOTOR

POWER

(HP)

TOTAL

HEAT

(BTUH)

ENTERING

WATER

TEMP

(°F)

LEAVING

WATER

TEMP

(°F)

WATER

FLOW

(GPM)

WATER

PRESSURE

DROP

(FT HD)

ENTERING

AIR

TEMP

(°F)

LEAVING

AIR

TEMP

(°F)

AIR

PRESSURE

DROP

(IN. WG)

TOTAL

COOLING

(BTUH)

SENSIBLE

COOLING

(BTUH)

ENTERING

WATER

TEMP

(°F)

LEAVING

WATER

TEMP

(°F)

WATER

FLOW

(GPM)

WATER

PRESSURE

DROP

(FT HD)

ENTERING

AIR

DRY BULB

(°F)

ENTERING

AIR

WET BULB

(°F)

LEAVING

AIR

DRY BULB

(°F)

LEAVING

AIR

WET BULB

(°F)

AIR

PRESSURE

DROP

(IN. WG)

VOLTAGE

(V/PH/Hz)

FLA

(AMPS)

FLA

(AMPS)

AHU-1 YORK XTO-057X084 11,500 11,500 2.25 6.6 1 20 497,000 160 140 62 2.2 15 55 0.09 1,006,000 514,600 45 57 168 5.4 95 79 54.5 54.5 2.78 460/3/60 24 30 ALL

NOTES:

1. INTENT IS REPLACEMENT IN KIND. MANUFACTURER DATA PROVIDED FOR THAT PURPOSE.

2. PROVIDE SUPPLY AIR SMOKE DETECTORS COMPATIBLE WITH EXISTING FIRE ALARM SYSTEM.

3. PROVIDE MIXING BOX SECTION WITH DAMPERS AND ACTUATORS COMPATIBLE WITH EXISTING BUILDING AUTOMATION SYSTEM, FILTER SECTION WITH MERV 8 PRE-FILTERS AND

MERV 13 SECONDARY FILTERS, PRE-HEAT SECTION, COOLING SECTION, HINGED AND LATCHED ACCESS SECTION, FAN SECTION AND DISCHARGE PLENUM. REFER TO ELEVATIONS

FOR CONFIGURATION DETAILS.

4. PROVIDE UNIT WITH HEAVY DUTY BASE RAIL. INSTALL ON 4" HIGH CONCRETE HOUSEKEEPING PAD.

5. UNIT SHALL BE SHIPPED IN MULTIPLE SECTIONS FOR FIELD ASSEMBLY TO ACCOMMODATE INSTALLATION IN BUILDING.

6. DOUBLE WALL CONSTRUCTION WITH FOAM INJECTED INSULATION.

7. PROVIDE STAINLESS STEEL SLOPED DRAIN PANS IN ALL COIL SECTIONS.

EXHAUST FAN SCHEDULE

MARK

EXISTING FAN INFO BASIS OF DESIGN (NEW)

TYPE

FAN DATA ELECTRICAL DATA

NOTES

MANUFACTURER MODEL NO. MFR MODEL NO. VOLUME ESP MOTOR

POWER

FLA

(AMPS) VOLTAGE

EF-1A ACME 7122R A/10 CL/1 GREENHECK SP-B70 UTILITY SET 4,765 2.500 3 - 460/3 ALL EF-1B ACME 7122R A/10 CL/1 GREENHECK SP-B70 UTILITY SET 4,765 2.500 3 - 460/3 ALL

EF-2A ACME 7122R A/10 GREENHECK SP-B70 UTILITY SET 5,020 2.500 5 - 460/3 ALL

EF-2B ACME 7122R A/10 GREENHECK CUBE-180-7 UTILITY SET 5,020 2.500 5 - 460/3 ALL

EF-3A ACME 7122R A/10 GREENHECK CUBE-180-7 UTILITY SET 5,060 2.500 5 - 460/3 ALL

EF-3B ACME 7122R A/10 GREENHECK CUBE-180-7 UTILITY SET 5,060 2.500 5 - 460/3 ALL

EF-4A ACME 7122R A/10 CL/1 GREENHECK USF-18 UTILITY SET 4,650 2.500 3 - 460/3 ALL EF-4B ACME 7122R A/10 CL/1 GREENHECK USF-18 UTILITY SET 4,650 2.500 3 - 460/3 ALL

EF-5 GREENHECK CUE-140-C GREENHECK CUE-140-C ALUMINUM UPBLAST 790 0.250 1

8 - 120/1 ALL

EF-6 GREENHECK CUE-140-C GREENHECK CUE-140-C ALUMINUM UPBLAST 800 0.375 1

8 - 120/1 ALL

EF-7 GREENHECK CUE-140-C GREENHECK CUE-140-C ALUMINUM UPBLAST 885 0.375 1

8 - 120/1 ALL

EF-8 GREENHECK CUE-100-C GREENHECK CUE-100-C ALUMINUM DOWNBLAST 750 0.125 - - 120/1 ALL

EF-9 GREENHECK CUE-140-C GREENHECK CUE-140-C ALUMINUM UPBLAST 1,870 0.500 1

8 - 120/1 ALL

EF-10 GREENHECK CUBE-160-3 GREENHECK CUBE-160-3 ALUMINUM UPBLAST 2,480 0.500 1

3 - 120/1 ALL

EF-11 GREENHECK CUBE-180-5 GREENHECK CUBE-180-5 ALUMINUM UPBLAST 265 0.250 1

2 - 120/1 ALL

EF-12 GREENHECK CUE-95-B GREENHECK CUE-95-B ALUMINUM UPBLAST 350 1.000 1

6 - 120/1 ALL

EF-13 GREENHECK 7-0RB GREENHECK 7-0RB ALUMINUM UPBLAST 450 0.125 3

4 - 460/3 ALL

EF-14 GREENHECK G-100-C GREENHECK G-100-C ALUMINUM UPBLAST 0.125 1

8 - 120/1 ALL

SF-1 GREENHECK AIS-18-C GREENHECK AIS-18-C ALUMINUM SUPPLY FAN 1481 0.125 1

8 - 120/1 ALL

EPM

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

C :\U se rs

\J

AC

KI

E~

1\ Ap pD at a\ Lo ca l\T em p\

Ac Pu bl is h_

8\

M -6

.d w g

M ay

4,

- 2

:0 0p m

COR

TEL

E. WILSON

E. WILSON

TBD

TBD 5/04/2026

Agricultural

Service Research

USDA ARS

5601 SUNNYSIDE AVENUE

RM 3-2102

BELTVILLE MD 20705

REPAIR HVAC SYSTEM, BULDINGS 1 AND 11 CENTER FOR MEDICAL

AGRICULTURAL AND VETENARY ENTOMOLOGY (CMAVE) -

GAINESVILLE, FLORIDA

BTD

JND

BUILDING 1

MECHANICAL SCHEDULES

M-601

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

C :\U se rs

\J

AC

KI

E~

1\ Ap pD at a\ Lo ca l\T em p\

Ac Pu bl is h_

8\

M -7

.d w g

M ay

4,

- 2

:0 0p m

COR

TEL

E. WILSON

E. WILSON

TBD

TBD 5/04/2026

Agricultural

Service Research

USDA ARS

5601 SUNNYSIDE AVENUE

RM 3-2102

BELTVILLE MD 20705

REPAIR HVAC SYSTEM, BULDINGS 1 AND 11 CENTER FOR MEDICAL

AGRICULTURAL AND VETENARY ENTOMOLOGY (CMAVE) -

GAINESVILLE, FLORIDA

BTD

JND

BUILDING 1 DEDICATED OUTDOOR UNIT

AHU-1 CONTROLS DIAGRAM

M-701

SEQUENCE OF OPERATION

M

AI - SPACE TEMP

BI - FREEZESTAT

VFDAI- OUTSIDE AIR TEMP

T

100% OA

CW

T

SF

T

AO - SUPPLY FAN VFD SPEED

S/A DUCT TO SPACE

LH

T

BI - SUPPLY AIR SMOKE

DETECTOR

AI - SUPPLY AIR TEMP

LH

BI - HIGH STATIC SHUTDOWN

AI - SUPPLY AIR STATIC

PRESSURE

LOCATE 3/4 DISTANCE DOWN

LONGEST DUCT

LH

AI - BUILDING STATIC PRESSURE

INSIDE OUTSIDE

VARIABLE AIR VOLUME 100% OA ROOFTOP UNIT SYSTEM OPERATION

ROOFTOP UNIT (AHU-1) RUN CONDITIONS - REQUESTED:

THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES:

· OCCUPIED MODE: THE UNIT SHALL MAINTAIN

§ A 72°F (ADJ.) COOLING SETPOINT

§ A 70°F (ADJ.) HEATING SETPOINT.

· UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN

§ A 80°F (ADJ.) COOLING SETPOINT.

§ A 55°F (ADJ.) HEATING SETPOINT.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

· HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS GREATER THAN THE

COOLING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).

· LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS LESS THAN THE

HEATING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).

DISCHARGE AIR SETPOINT ADJUST:

THE OCCUPANT SHALL BE ABLE TO ADJUST THE DISCHARGE AIR TEMPERATURE HEATING AND

COOLING SETPOINTS.

OPTIMAL START:

THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START-UP. THIS ALGORITHM

SHALL MINIMIZE THE UNOCCUPIED WARM-UP OR COOL-DOWN PERIOD WHILE STILL ACHIEVING

COMFORT CONDITIONS BY THE START OF SCHEDULED OCCUPIED PERIOD.

ZONE UNOCCUPIED OVERRIDE:

A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE AND PLACE THE UNIT INTO AN OCCUPIED MODE FOR AN ADJUSTABLE PERIOD OF TIME. AT THE EXPIRATION

OF THIS TIME, CONTROL OF THE UNIT SHALL AUTOMATICALLY RETURN TO THE SCHEDULE.

SUPPLY FAN:

THE SUPPLY FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN, UNLESS SHUTDOWN ON SAFETIES. TO PREVENT SHORT CYCLING, THE SUPPLY FAN SHALL HAVE A USER DEFINABLE (ADJ.)

MINIMUM RUNTIME. THE SUPPLY FAN VFD SHALL MODULATE TO MAINTAIN A USER ADJUSTABLE DUCT STATIC PRESSURE SETPOINT. FAN MODULATION SHALL ALSO BE CONTROLLED TO MAINTAIN POSITIVE BUILDING PRESSURE WITH RESPECT TO OUTDOORS AND SHALL MAINTAIN THE LAB SPACES NEGATIVE WITH RESPECT TO THE OTHER AREAS OF THE BUILDING. ALARMS SHALL BE PROVIDED AS FOLLOWS:

· SUPPLY FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

· SUPPLY FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

· SUPPLY FAN RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT

(ADJ.).

SUPPLY AIR TEMPERATURE SETPOINT - OPTIMIZED:

THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE AND SHALL MAINTAIN A SUPPLY AIR

TEMPERATURE SETPOINT RESET BASED ON ZONE COOLING AND HEATING REQUIREMENTS AS

DETERMINED BY AVERAGE ZONE TEMPERATURE. THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE

RESET FOR COOLING BASED ON ZONE COOLING REQUIREMENTS AS FOLLOWS:

· THE INITIAL SUPPLY AIR TEMPERATURE SETPOINT SHALL BE 55°F (ADJ.).

· AS COOLING DEMAND INCREASES, THE SETPOINT SHALL INCREMENTALLY RESET DOWN TO A

MINIMUM OF 53°F (ADJ.).

· AS COOLING DEMAND DECREASES, THE SETPOINT SHALL INCREMENTALLY RESET UP TO A

MAXIMUM OF 58°F (ADJ.).

IF MORE ZONES NEED HEATING THAN COOLING, THEN THE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE

RESET AS FOLLOWS:

· THE INITIAL SUPPLY AIR TEMPERATURE SETPOINT SHALL BE 60°F (ADJ.).

· AS HEATING DEMAND INCREASES, THE SETPOINT SHALL INCREMENTALLY RESET UP TO A

MAXIMUM OF 65°F (ADJ.).

· AS HEATING DEMAND DECREASES, THE SETPOINT SHALL INCREMENTALLY RESET DOWN TO A

MINIMUM OF 58°F (ADJ.).

CILLED WATER COOLING:

THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND CONTROL THE COOLING SYSTEM TO MAINTAIN DISCHARGE AIR SETPOINT. THE CHILLED WATER MODULATE BASED ON COOLING LOAD.

COOLING SHALL BE ENABLED WHENEVER:

· THE TEMPERATURE CONTROLS IS ACTIVATED.

· AND THE SUPPLY FAN STATUS IS ON.

· AND THE ZONE TEMPERATURE IS ABOVE COOLING SETPOINT.

· AND THE HEATING IS NOT ACTIVE.

FREEZESTAT:

THE FREEZESTAT SHALL PROTECT THE UNIT FROM FREEZING.

HEATING COIL CONTROL:

HEAT SHALL BE ENABLED WHENEVER:

· OUTSIDE AIR TEMPERATURE IS LESS THAN 65°F (ADJ.).

· AND THE DISCHARGE AIR TEMPERATURE IS BELOW HEATING SETPOINT.

· AND THE SUPPLY FAN STATUS IS ON.

· AND THE COOLING IS NOT ACTIVE.

SUPPLY AIR TEMPERATURE:

THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE. ALARMS SHALL BE PROVIDED AS

FOLLOWS:

· HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.).

· LOW SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).

HW

SPACE TEMPERATURE SENSOR

BI - SUPPLY FAN VFD FAULT

BO - SUPPLY FAN START/STOP

UNIT

CONTROLLER

CONNECT TO EXISTING CONTROL SYSTEM

HEATING COIL

EXISTING

S

COOLING COIL

NOTE:

ALL CONTROLS FOR AHU-1 SHALL BE

COMPATABLE WITH AND CONNECT

TO THE EXISTING CONTROL SYSTEM

SERVING THE BUILDING.

SCALE:

DEDICATED OUTDOOR UNIT AHU-1 CONTROLS DIAGRAM

NOT TO SCALE

M-701

1. DEVICES NOTED AS 'GFI' SHALL BE GROUND FAULT CIRCUIT INTERRUPTING DEVICES.

2. DEVICES NOTED AS 'WP' SHALL BE WEATHERPROOF WHILE-IN-USE.

3. PROVIDE UNSWITCHED POWER TO THE EMERGENCY BATTERY PACKS.

4. 'W/E' DENOTES PROVIDED WITH EQUIPMENT.

5. MINIMUM RACEWAY SIZE SHALL BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT RACEWAY FILL RATIO TO LESS THAN 40% FULL.

6. THE ELECTRICAL CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH THE GENERAL CONTRACTOR AND SHALL

BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT AND CORRECT ROUGH-IN LOCATIONS OF ELECTRICAL

CONNECTIONS.

7. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED GROUND CONDUCTOR, SIZED PER THE NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE BRANCH CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR.

8. "PROVIDE" IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.

9. ALL CONDUCTORS SHALL BE COPPER

10. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS BEFORE PROCUREMENT OF ANY MATERIALS AND

DEVELOPMENT OF ANY SHOP DRAWINGS OR SUBMITTALS.

11. PROVIDE LABELS ON ALL RECEPTACLES AND JUNCTION BOXES INDICATING THE SOURCE PANEL & CIRCUIT(S). TEXT SHALL BE BLACK, 1/4". LABELS

ABOVE FINISHED CEILING CAN BE HANDWRITTEN WITH AN INDELIBLE MARKER.

12. CIRCUIT SIZES INDICATED ON THE DRAWINGS ARE MINIMUM REQUIREMENTS.

13. DO NOT CONNECT CONDUCTORS LARGER THAN #10 DIRECTLY TO A RECEPTACLE OR A SWITCH. PROVIDE A JUNCTION BOX TO DOWNSIZE THE

CONDUCTOR TO #12 AT THE DEVICE.

GENERAL NOTES:

1.

MASTER NOTES - ELECTRICAL:

THE CONTRACTOR SHALL ABIDE BY ALL FEDERAL, STATE, AND/OR

LOCAL CODES. IF A DISCREPANCY BETWEEN CODES OCCURS, THE

MOST STRINGENT SHALL PREVAIL.

2. THE CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS PRIOR

TO THE COMMENCEMENT OF ANY WORK. SHOULD DISCREPANCIES BE

DISCOVERED, THE CONTRACTOR SHALL VERIFY INTENT WITH THE

ENGINEER/CONTRACTING OFFICER BEFORE PROCEEDING.

3. COORDINATE LOCATIONS OF ALL CEILING MOUNTED DEVICES WITH

OTHER TRADES PRIOR TO INSTALLATION.

4. ALL EQUIPMENT INSTALLED IN THIS PROJECT MUST COMPLY

WITH THE "BUY AMERICAN ACT" (BAA). BASIS OF DESIGN SHOWN

ON SCHEDULES IS TO ESTABLISH A STANDARD OF QUALITY, NOT

TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT FROM

ANOTHER MANUFACTURER IS ACCEPTABLE. MANUFACTURER

NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE

SHOWN FOR INFORMATION ONLY AND MAY OR MAY NOT COMPLY

WITH BAA. REFER TO SPECIFICATIONS FOR COMPLETE

REQUIREMENTS.

5. CONTRACTOR SHALL COORDINATE ALL ELECTRICAL WORK WITH

MECHANICAL CONTRACTOR TO ENSURE PROPER INSTALLATION OF

HVAC EQUIPMENT, CONTROLS, AND ASSOCIATED SYSTEMS.

PROVIDE ALL NECESSARY POWER, CONTROL WIRING, AND

CONNECTIONS WHETHER OR NOT SPECIFICALLY SHOWN.

SYMBOL / KEY DESCRIPTION

(NOT ALL SYMBOLS MAY APPLY, TYP.)

GENERAL SYMBOLS LEGEND

LA-1

LA-1

CONDUCTORS IN CONDUIT CONCEALED WITHIN WALL OR CEILING. TIC MARKS INDICATE NUMBER OF CONDUCTORS.

THE EQUIPMENT GROUNDING CONDUCTOR IS NOT SHOWN, BUT SHALL BE PROVIDED. SIZE THE EQUIPMENT GROUNDING CONDUCTOR AND THE CONDUIT PER THE NEC. THE ABSENCE OF TIC MARKS SIGNIFIES THAT TWO CONDUCTORS PLUS AN EQUIPMENT GROUNDING CONDUCTOR SHOULD BE PROVIDED. FOR EXAMPLE, THE MARKINGS TO THE LEFT SIGNIFY

THAT THREE CONDUCTORS PLUS AN EQUIPMENT GROUNDING CONDUCTOR SHOULD BE PROVIDED.

THE TEXT INSIDE THE ARC INDICATES THE AWG SIZE OF THE CONDUCTORS THAT SHALL BE RUN IN THE CONDUIT.

THE ABSENCE OF TEXT SIGNIFIES THAT THE CONDUCTORS SHOULD BE #12 AWG.

CIRCUITRY RUN IN STRAIGHT LINE SEGMENTS SIGNIFIES EXPOSED SURFACE-MOUNTED RACEWAY (SEE SPECIFICATIONS).

CONDUCTORS IN CONDUIT CONCEALED BELOW GRADE OR FLOOR. TIC MARKS INDICATE NUMBER OF CONFUCTORS.

THE EQUIPMENT GROUNDING CONDUCTOR IS NOT SHOWN, BUT SHALL BE PROVIDED. SIZE THE EQUIPMENT GROUNDING CONDUCTOR AND THE CONDUIT PER THE NEC. THE ABSENCE OF TIC MARKS SIGNIFIES THAT TWO CONDUCTORS PLUS AN EQUIPMENT GROUNDING CONDUCTOR SHOULD BE PROVIDED. THE MARKINGS TO THE LEFT SIGNIFY THAT THREE CONDUCTORS PLUS AN EQUIPMENT GROUNDING CONDUCTOR SHOULD BE PROVIDED.

HOMERUN TO PANELBOARD. ARC DENOTES CONCEALED CIRCUITRY. TEXT DENOTES PANELBOARD NAME WITH CIRCUIT NUMBER. DEVICES HAVING CIRCUIT NUMBERS LOCATED BESIDE THEM MAY NOT SHOW THE CIRCUIT

NUMBERS AT THE HOMERUN ARROWS.

PARTIAL HOMERUN TO PANELBOARD. COMBINE ALL PARTIAL HOMERUNS THAT ARE ON THE SAME CIRCUIT IN A

JUNCTION BOX PRIOR TO ENTERING THE PANELBOARD.

PANELBOARD AND CIRCUIT DESIGNATIONLA1-13

? DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED 18" A.F.F. TO CENTERLINE OF BOX UNLESS NOTED OTHERWISE.

SYMBOL / KEY

POWER OUTLET AND COMMUNICATIONS LEGEND

J

J

CEILING MOUNTED JUNCTION BOX.

WALL MOUNTED JUNCTION BOX.

FLEX. CONNECTION TO EQUIPMENT.

F-?

NON-FUSED DISCONNECT SWITCH.

TEXT INDICATES AMPACITY/NUMBER

OF POLES/ENCLOSURE TYPE.

MAGNETIC MOTOR STARTER/

VARIABLE FREQUENCY DRIVE.

PANELBOARD.

VOLTAGE DROP CHART FOR 20A, 1Ø CIRCUITS

VOLTAGE CIRCUIT LENGTH CONDUCTOR SIZE (AWG)

120 >140'

>90'

>50'

<50' #12

#10

#8

#6

277 >330'

>200'

>130'

<130' #12

#10

#8

#6

VOLTAGE DROP CHART NOTES:

1) CIRCUIT SIZES INDICATED ON THE DRAWINGS ARE MINIMUM REQUIREMENTS.

REFER TO THIS CHART FOR UPSIZING CONDUCTORS AS NEEDED.

2) DO NOT CONNECT CONDUCTORS LARGER THAN #10 DIRECTLY TO A RECEPTACLE OR A SWITCH.

PROVIDE A JUNCTION BOX TO DOWNSIZE THE CONDUCTOR TO #12 AT THE DEVICE.

3) FOR CIRCUITS LONGER THAN THOSE LISTED ABOVE, CONSULT WITH THE ENGINEER FOR CONDUCTOR

SIZES.

DESCRIPTION

(42) ELECTRICAL OR COMMUNICATION DEVICE, MH = AT ELEVATION AFF INDICATED (42" AFF SHOWN)

LIGHTING AND SWITCHING LEGEND

SYMBOL / KEY DESCRIPTION SYMBOL / KEY DESCRIPTION

FACP EXISTING FIRE ALARM CONTROL PANEL

SYMBOL / KEY SYMBOL / KEYDESCRIPTION DESCRIPTION

ONE-LINE DIAGRAM, SCHEDULE, AND DISTRIBUTION LEGEND

FUSED DISCONNECT SWITCH.

TEXT INDICATES AMPACITY/NUMBER

OF POLES/ENCLOSURE TYPE;

F-(RATING OF FUSES).

MOTOR

RECEPTACLE DETAIL NOTES:

B. RECEPTACLES SHOWN AS GFI MAY BE NON GFI TYPE RECEPTACLES IF FED FROM A 20/1 GFI BREAKER OR THE LOAD SIDE OF A GFI RECEPTACLE IN THE SAME ROOM, ON THE SAME CIRCUIT

AND RATED 20 AMP FEED-THRU CAPACITY. COVER PLATES SHALL BE CLEARLY MARKED GFI.

C. NON GFI RECEPTACLES SHALL NOT BE CONNECTED IN A FEED-THRU MANNER. WIRE

CONNECTIONS IN RECEPTACLE BOXES SHALL BE MADE IN A PIGTAIL MANNER AS SHOWN IN

RECEPTACLE DETAIL.

BOND EQUIPMENT GROUND

TO METAL BOX.

SCALE:

RECEPTACLE DETAIL

NONE

E-001

DUCT SMOKE DETECTOR IN RETURN DUCT.

DUCT SMOKE DETECTOR IN SUPPLY DUCT.

S

D

D R

EXISTING WALL MOUNTED EXIT SIGN?

EMERGENCY LIGHTING.

ST HORSEPOWER RATED SWITCH WITH THERMAL

OVERLOADS (MANUAL MOTOR STARTER).

2'X4' RECESSED FIXTURE.

A. RECEPTACLES SHALL NOT BE CONNECTED IN A FEED-THRU MANNER. WIRE CONNECTIONS IN

RECEPTACLE BOXES SHALL BE MADE IN A PIGTAIL MANNER.

BUILDING 1

ELECTRICAL LEGEND

E-001

EPM

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

C :\U se rs

\B R

AD

EN

~1 \A pp D at a\

Lo ca l\T em p\ Ac

Pu bl is h_

8\ E-

1.

dw g

M ay

4,

- 1

2:

pm

COR

TEL

E. WILSON

E. WILSON

TBD

TBD 5/04/2026

Agricultural

Service Research

USDA ARS

5601 SUNNYSIDE AVENUE

RM 3-2102

BELTVILLE MD 20705

REPAIR HVAC SYSTEM, BULDINGS 1 AND 11 CENTER FOR MEDICAL

AGRICULTURAL AND VETENARY ENTOMOLOGY (CMAVE) -

GAINESVILLE, FLORIDA

BTD

EJH

35781

T-2

G-1

M B-

M D

P

D1 D2

H

BLB

1 H A

M B-

2LA

L-12-B L-12-A

EP

ATS

SCALE:

BUILDING 1

1ST FLOOR ELECTRICAL DEMO

3/32" = 1'-0"

ED101

EPM

REVISIONS

DESCRIPTION

SHEET

DATEP.A.

FIRM

U

NO.

D

REAL PROPERTY

SAFETY & HEALTH

A

DATE

PROJECT NO.

SUSDA

BY

OF

THE

DESIGNER

PROJECT MGR

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson-McAdams

ARCHITECTS/ENGINEERS · PLANNING · SURVEYING · MANAGEMENT

J:

\g re en w oo d\

J ob s\

U

SD

A B1

B

H

VA

C

R ep ai r G ai ne sv ille

F L\

W or ki ng F ol de r\E le c\ B1

\E D

1.

dw g

M ay

4,

- 1

2:

pm

COR

TEL

E. WILSON

E. WILSON

TBD

TBD 5/04/2026

Agricultural

Service Research

USDA ARS

5601 SUNNYSIDE AVENUE

RM 3-2102

BELTVILLE MD 20705

REPAIR HVAC SYSTEM, BULDINGS 1 AND 11 CENTER FOR MEDICAL

AGRICULTURAL AND VETENARY ENTOMOLOGY (CMAVE) -

GAINESVILLE, FLORIDA

BTD

EJH

BUILDING 1

1ST FLOOR ELECTRICAL DEMO

ED101

GENERAL DEMOLITION NOTES

GRAPHIC SCALE

1'-0'

KEYED NOTESX

A. THE DEMOLITION PLAN AND EXISTING CONDITIONS ARE

APPROXIMATE. ITEMS TO BE REMOVED ARE

DESIGNATED BY HATCHING AND DASHED LINES. OTHER

ITEMS ARE INTENDED TO REMAIN IN PLACE UNLESS

NOTED OTHERWISE.

B. PRIOR TO BEGINNING WORK, SURVEY EXISTING

ELECTRICAL SYSTEMS. DOCUMENT, IN WRITING,

SIGNED BY THE…