This is an Architect's Supplemental Instructions (ASI) document issued for a HVAC repair project at the USDA ARS facility in Gainesville, Florida.
The ASI Number 001, dated July 10, 2026, directs the contractor to add Building 1 pump P-3 as an additive bid option. The work requires replacement of the existing pump with a Bell & Gossett Series e-1510, Model 2BD pump (WIZE-6F6B286A) operating at 1732 RPM with the following specifications: 206 US gallons per minute flow rate, 60 feet head, 73.7% efficiency, 5 horsepower motor, and 265 pounds weight. The pricing must include modifying the piping as required for pump replacement while reusing the existing pump foundation, valves, and controls. Any damaged or removed insulation must be replaced to match existing conditions. The work shall be performed without change to the contract sum or contract time. The architect, Thomas E. Lovelace, Program Manager of The Johnson-McAdams Firm, issued this instruction on behalf of the owner, USDA ARS. The submittal documentation includes detailed pump performance curves, technical specifications, dimensional drawings, mechanical seal configurations, and materials of construction for the specified Bell & Gossett pump.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Document G710™ – 2017 Architect's Supplemental Instructions
PROJECT:
B1 & B11 HVAC Repair ASI INFORMATION:
Gainesville FL ASI Number: 001
Date: 7/10/2026
OWNER: USDA ARS ARCHITECT: The Johnson-McAdams Firm
The Contractor shall carry out the Work in accordance with the following supplemental instructions without change in Contract Sum or Contract Time. Proceeding with the Work in accordance with these instructions indicates your acknowledgment that there will be no change in the Contract Sum or Contract Time.
(Insert a detailed description of the Architect’s supplemental instructions and, if applicable, attach or reference specific exhibits.)
This ASI addresses the addition of Building 1 pump P-3. Bidders must provide an additive bid option to replace the existing pump with a pump equal to the pump depicted on the attached submittal sheet.
Pricing must include modifying the piping as required to replace the pump. Pricing must be based on reusing existing pump foundation, valves and controls. Damaged or removed insulation must be replaced equal to existing. Refer to original specifications for additional requirements.
ISSUED BY THE ARCHITECT:
The Johnson-McAdams Firm ARCHITECT (Firm name)
SIGNATURE
Thomas E. Lovelace, Prog Mgr
PRINTED NAME AND TITLE
7/10/2026
DATE
AIA Document G710™ – 2017. Copyright © 1979, 1992 and 2017 by The American Institute of Architects. All rights reserved. WARNING: This AIA® Document is protected by U.S. Copyright Law and International Treaties. Unauthorized reproduction or distribution of this AIA® Document, or any portion of it, may result in severe civil and criminal penalties, and will be prosecuted to the maximum extent possible under the law. To report copyright violations of AIA Contract Documents, e-mail The American Institute of Architects’ legal counsel, copyright@aia.org.
mailto:copyright@aia.org mailto:right@aia.org
Pump Schedule / Gainesville B1 Pump 3
P-3
WIZE-6F6B286A 07/10/2026
James M Pleasants Co., Inc
(800) 365-9010 info@jmpco.com
Model: 2BD
206 US gpm
60 ft
18 ft
73.7 %
72.8 %
8.625 in
5 hp
4.1 bhp
1800 rpm
1732 rpm
5.58 ft
78.8 ft
36.9 US gpm
184 US gpm
180 ºF
Water
265 lbs
3.48 ft²
Energy Efficiency Ratings:
Pump & Motor PEIcl: 0.85 ERcl: 15 Pump, Motor & Drive: PEIvl: 0.43 ERvl: 57
2BD
1732 RPM
Performance curve meets 14.6 / ISO 9906 acceptance criteria | Available Phase: , Available Voltage(s) [V]: WIZE-6F6B286A
Constant Speed Curve (1750 rpm)
Operating Point
Flow: 206 US gpm Head: 60 ft Speed: 1732 Efficiency: 73.7% Point BHP: 4.1 End Of Curve: 77%
Maximum Duty Point (at rated motor speed)
Flow: 208 US gpm Head: 61.3 ft Speed: 1750 Efficiency: 73.8% Point BHP: 4.23 NOL Flow: 265 US gpm Runout Flow: 270 US gpm NOL (BHP): 4.96