Attachment 01 - Drawings Mechanical 672-CSI-124 - Part IV of VI - 4 Pages.pdf
PDF 9 MB Posted
- Attached to
- Z2DA--Construct New Hybrid Operating Room
- Solicitation number
- 36C24825R0026
About this file
This document is a set of mechanical engineering drawings for a new hybrid operating room project at the VA Caribbean Healthcare System. The drawings, prepared by strollo & strollo architects and MES Group, Inc., detail comprehensive mechanical system renovations including ductwork, piping, air handling, and HVAC equipment specifications.
Key technical details include a 4,880 CFM air handling unit for the hybrid operating room with dual air handlers in a duty/standby configuration, multiple variable air volume (VAV) terminal units, exhaust fans, airflow control valves, and specific requirements for air filtration (MERV 8-16 filters), outside air dampers, and pressure differential controls. The drawings cover demolition plans, renovation plans, penthouse mechanical systems, detailed equipment schedules for louvers, terminal units, fans, grilles/diffusers, and air handling units, with extensive notes on installation, seismic restraints, code compliance, and coordination requirements for the mechanical systems.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
MECHANICAL NOTES AND
LEGENDS
NS TH
SMOKE DETECTOR
NEW THERMOSTAT
POINT OF NEW CONNECTION
X DRAWING NOTE
U 1" DOOR UNDERCUT
CARBON DIOXIDE SENSOR
PIPE DOWN
PIPE UP
CD CONDENSATE DRAIN
BACKDRAFT DAMPER
DESIGNATES OUTSIDE AIR CFM-
FLOW SWITCHF
DIFFERENTIAL PRESSURE SWITCHDP
PIPE PENETRATION
END CAP
INDICATES SUPPLY AIRFLOW
INDICATES RETURN AIRFLOW
UP DUCT UP
DN DUCT DOWN
- EQUIPMENT MARK
FIRE/SMOKE DAMPERFS
SMOKE DAMPERSD
FIRE DAMPER
MANUAL BALANCING DAMPER
EXHAUST
RETURN OR TRANSFER
MOTORIZED DAMPERM
RECTANGULAR DUCT
(INSIDE DIMENSIONS: WIDTH x DEPTH)AxB
EXISTING DUCT
(INSIDE DIMENSIONS: WIDTH x DEPTH)AxB
EXISTING FLEX-DUCT
EXISTING DUCT TO BE REMOVED
EXISTING RETURN
EXISTING EXHAUST
SUPPLY
EXISTING SUPPLY
(E) EXISTING
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AFM AIRFLOW MEASURING DEVICE
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
ATU AIR TERMINAL UNIT
BHP BRAKE HORSEPOWER
BOD BOTTOM OF DUCT
BOS BOTTOM OF STRUCTURE
BTUH BRITISH THERMAL UNIT PER HOUR
CCV COOLING CONTROL VALVE
CD CEILING SUPPLY AIR DIFFUSER
CF CUBIC FEET
CFM CUBIC FEET PER MINUTE
CG CEILING GRILLE
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
COR CONTRACTING OFFICER'S REPRESENTATIVE
CTE CONNECT TO EXISTING
CU CONDENSING UNIT
CV CONSTANT AIR VOLUME
DD DUCT MOUNTED SMOKE DETECTOR
DIA DIAMETER
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EDH ELECTRIC DUCT HEATER
EF EXHAUST FAN
EWT ENTERING WATER TEMPERATURE
FBC FLORIDA BUILDING CODE 2017
FCU FAN COIL UNIT
FD FIRE DAMPER
FMC FLORIDA MECHANICAL CODE 2017
FO FLAT OVAL
FPM FEET PER MINUTE
FSD COMBINATION FIRE SMOKE DAMPER
FT FEET
G GAS / GRILLE
GPM GALLONS PER MINUTE
HCV HEATING CONTROL VALVE
HHWR HEATING HOT WATER RETURN
HHWS HEATING HOT WATER SUPPLY
HP HORSEPOWER
IBC INTERNATIONAL BUILDING CODE
IN INCH
LAT LEAVING AIR TEMPERATURE
LWT LEAVING WATER TEMPERATURE
MBTUH 1,000 BTUH
MCA MINIMUM CIRCUIT AMPACITY
MOCP MAXIMUM OVERCURRENT PROTECTION
MUA MAKE UP AIR
NC NEW CONNECTION / NOISE CRITERIA
NG NATURAL GAS
OA OUTSIDE AIR
OAL OUTSIDE AIR LOUVER
OBD OPPOSED BLADE DAMPER
PTAC PACKAGED TERMINAL AIR CONDITIONING
RA RETURN AIR
RG RETURN AIR GRILLE
RPM REVOLUTIONS PER MINUTE
RTU ROOFTOP UNIT
SA SUPPLY AIR
SD SMOKE DAMPER
SF SQUARE FEET
SR SUPPLY AIR REGISTER
TAB TEST AND BALANCE
TOD TOP OF DUCT
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
WG WATER GAUGE
ABBREVIATIONS
LIMIT OF DEMOLITION
MOTORIZED CONTROL VALVE
M
BUTTERFLY VALVE
BALL VALVE
FLEX-DUCT
ROUND DUCT
(INSIDE DIMENSIONS: DIAMETER)AØ
45° BRANCH TAKE-OFF FITTING
AIRFLOW MEASURING DEVICEAFM
GATE VALVE
STRAINER
MECHANICAL LEGEND
1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATIVE OF WORK TO BE
PROVIDED (FURNISHED AND INSTALLED) UNDER THIS CONTRACT. DRAWINGS
SHOULD NOT BE SCALED.
2. THE CONTRACTOR IS RESPONSIBLE TO EXAMINE THE EXISTING CONDITIONS UNDER
WHICH THEY SHALL OPERATE AND VERIFY THE EXTENT OF WORK REQUIRED TO
COMPLETE THE WORK UNDER THIS CONTRACT.
3. PRIOR TO ORDERING AND FABRICATING ANY EQUIPMENT, IT IS THE RESPONSIBILITY
OF THE CONTRACTOR TO EXAMINE THE PHYSICAL CONDITIONS AT THE PROJECT
SITE AND VERIFY SPACE AND SUFFICIENT CLEARANCES ARE AVAILABLE FOR
INSTALLING EQUIPMENT, DUCTWORK, PIPING, AND APPURTENANCES, AND TO
DETERMINE ANY NECESSARY MODIFICATIONS.
4. PERFORM ALL WORK IN COMPLIANCE WITH ALL APPLICABLE FEDERAL, STATE, AND
LOCAL CODES, REGULATIONS, AND STANDARDS ADOPTED BY THE AUTHORITY
HAVING JURISDICTION. IF CONFLICTS EXIST BETWEEN THESE ENGINEERING
DOCUMENTS AND CODES, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN.
5. ALL CONSTRUCTION WORK SHALL ALSO MEET THE FOLLOWING CODE
REQUIREMENTS:
· INTERNATIONAL BUILDING CODE (IBC) 2020
· INTERNATIONAL EXISTING BUILDING CODE 2020
· IBC MECHANICAL 2020
· IBC PLUMBING 2020
· IBC ENERGY CONSERVATION 2020
· NFPA 1-2018, THE UNIFORM FIRE CODE
· NFPA 101-2018, THE LIFE SAFETY CODE
· NFPA 51B-2014, STANDARD FOR FIRE PREVENTION DURING WELDING, CUTTING
AND OTHER HOT WORK
· NFPA 13-2016, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS
· NFPA 70-2017, NATIONAL ELECTRICAL CODE
· NFPA 90A-2018, STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND
VENTING SYSTEMS.
· NFPA 99-2018, STANDARD FOR HEALTH CARE FACILITIES
· NFPA 241-2013, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION
AND DEMOLITION OPERATIONS.
· VA HVAC DESIGN MANUAL, LATEST EDITION
· VA ELECTRICAL DESIGN MANUAL, LATEST EDITION
· VA FIRE PROTECTION DESIGN MANUAL, LATEST EDITION
· VA SURGICAL AND ENDOVASCULAR SERVICES DESIGN GUIDE
· ALL OTHER APPLICABLE VA DESIGN MANUALS
6. CONTRACTOR SHALL COORDINATE AND SEQUENCE DEMOLITION, CLEANING, AND
CONSTRUCTION WORK.
7. CONTRACTOR SHALL NOTE ANY SPECIAL REQUIREMENTS FOR INSTALLATION OF
WORK UNDER THIS CONTRACT. DISMANTLE AND REASSEMBLE EQUIPMENT AS
NECESSARY FOR ENTRY INTO THE BUILDING AND THE LOCATION OF INSTALLATION.
8. THE CONTRACTOR SHALL MAINTAIN A COMPLETE PROJECT SCHEDULE AND SHALL
UPDATE THIS SCHEDULE WEEKLY. ANY CHANGES SHALL BE NOTED AND AN
UPDATED SCHEDULE SHALL BE PROVIDED TO THE OWNER.
9. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS, PARTITIONS,
CEILINGS, AND FLOORS. SEAL ALL PENETRATIONS THROUGH RATED ASSEMBLIES
WITH FIRESTOP MATERIAL IN ACCORDANCE WITH U.L. REQUIREMENTS TO MAINTAIN
THE ASSEMBLY RATING.
10. CONTRACTOR SHALL FURNISH U.L. APPROVED DRAWINGS FOR EACH TYPE OF FIRE
AND SMOKE RATED ASSEMBLY PENETRATION BY DUCTS, PIPES, OR CONDUITS, AND
SHALL DISPLAY THESE DRAWINGS ON THE JOB SITE AT ALL TIMES DURING
CONSTRUCTION.
11. CONTRACTOR SHALL REFER TO ALL DETAILS FOR PROPER GUIDANCE.
12. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIPMENT SUBMITTALS
FOR ALL PRODUCTS USED ON PROJECT.
13. THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE
CONTRACTOR OF RESPONSIBILITY FOR DEVIATIONS FROM THE REQUIREMENTS OF
CONTRACT DOCUMENTS UNLESS THE CONTRACTOR HAS RECEIVED WRITTEN
APPROVAL FROM THE ENGINEER TO THE SPECIFIC DEVIATION. THE ENGINEER'S
APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE CONTRACTOR OF
RESPONSIBILITY FOR ERRORS OR OMISSIONS IN HIS OR HER SUBMITTAL DATA.
14. THE CONTRACTOR IS REQUIRED TO SUBMIT THREE COMPLETE O&M MANUALS IN
THREE RING BINDERS AT SUBSTANTIAL COMPLETION. MANUALS SHALL INCLUDE
INSTALLATION AND MAINTENANCE DATA ON ALL NEW EQUIPMENT AND MATERIALS,
CERTIFIED TECHNICAL PRODUCT DATA, EQUIPMENT SHOP DRAWINGS, SPARE PARTS
DATA, ETC. PROVIDE AN INDEX AND ASSOCIATED DIVIDERS.
15. CLOSE OUT DOCUMENTS: THE CONTRACTOR IS TO MAINTAIN ONE SET OF
CONSTRUCTION DRAWINGS ON SITE AND KEEP CURRENT WITH MARK UP AS-BUILT
CONDITIONS DURING CONSTRUCTION OF THE PROJECT. THIS SET IS TO INCLUDE
ALL CONTRACT CHANGES, MODIFICATIONS, AND CLARIFICATIONS. THIS SET ALONG
WITH ALL SHOP DRAWINGS SHALL BE TURNED OVER TO THE ARCHITECT/ENGINEER
AFTER CONSTRUCTION COMPLETION.
16. IT IS THE RESPONSIBILITY OF ALL BIDDERS TO THOROUGHLY REVIEW AND
UNDERSTAND ALL CONSTRUCTION DOCUMENTS. THIS INCLUDES BUT IS NOT LIMITED
TO ALL DRAWINGS, SPECIFICATION SECTIONS, ETC. THE DRAWINGS ARE SCHEMATIC
IN NATURE. THEREFORE BEFORE STARTING ANY WORK, THE CONTRACTOR SHALL
REVIEW ALL OTHER CONSTRUCTION DOCUMENTS, VERIFY FIELD CONDITIONS AND
SHALL MAKE ANY REQUIRED MINOR ADJUSTMENTS WITHOUT EXTRA COST TO THE
OWNER. ANY MAJOR DISCREPANCIES FOUND SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT/ENGINEER. THE BASE BID SHALL REFLECT THE
TOTAL COST OF NEW EQUIPMENT INSTALLATION. THIS INCLUDES LABOR, EQUIPMENT
AND MATERIALS. NO CHANGE ORDERS SHALL BE ISSUED WITHOUT WRITTEN
CONSENT AND APPROVAL FROM ENGINEER AND ARCHITECT.
GENERAL NOTESMECHANICAL NOTES
1. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF FIELD CONDITIONS PRIOR TO BEGINNING WORK AND ORDERING EQUIPMENT, AND FOR COORDINATING NEW EQUIPMENT DIMENSIONS AND MEANS AND METHODS FOR
INSTALLATION WITH FIELD CONDITIONS.
2. CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH SUBMITTED EQUIPMENT TO ENSURE ALL INLET/OUTLET CONNECTIONS COORDINATE WITH FIELD INSTALLED DUCTWORK AND MAKE ANY NECESSARY DUCT MODIFICATIONS
TO ENSURE PROPER OPERATION OF MECHANICAL EQUIPMENT.
3. SUBMITTALS SHALL MEET SCHEDULED DESIGN CHARACTERISTICS, INCLUDING BUT NOT LIMITED TO CFMS, EAT(DB/WB), ESP, CAPACITIES, VOLTAGES/PHASES, MCA/MOCP, SONES, ETC.
4. ALL DUCT CONSTRUCTION, INSTALLATION, AND SUPPORTS ARE TO COMPLY WITH LATEST EDITION OF SMACNA'S HVAC DUCT CONSTRUCTION STANDARDS METAL DUCT. ALL DUCTWORK SHALL BE GALVANIZED STEEL OR STAINLESS STEEL, CLASS 304 (REFER TO PLANS). DUCTS SHALL BE 3" PRESSURE CLASS UPSTREAM OF THE AIR
TERMINAL UNITS AND 2" DOWNSTREAM OF THE ATU'S UNLESS OTHERWISE NOTED.
5. INSULATE ALL DUCTWORK ACCORDING TO SPECIFICATIONS.
6. ALL WALL-MOUNTED THERMOSTATS AND/OR TEMPERATURE SENSORS SHALL BE INSTALLED AT AN ELEVATION OF 48" ABOVE FINISHED FLOOR TO THE TOP UNLESS OTHERWISE NOTED ON DRAWINGS. LOCATION OF WALL-MOUNTED THERMOSTATS SHALL BE COORDINATED WITH OTHER TRADES FOR A NEAT APPEARANCE. FINAL LOCATION OF THERMOSTATS SHALL BE SUBJECT TO THE APPROVAL OF THE ENGINEER OR REPRESENTATIVE IN
THE FIELD.
7. ALL SUPPLY AIR DIFFUSERS SHALL BE 4-WAY THROW UNLESS NOTED OTHERWISE. CONTRACTOR SHALL PAINT INSIDE EACH RETURN GRILLE'S PLENUM AND DUCT CONNECTION FLAT BLACK TO CONCEAL CONNECTION.
COORDINATE AIR DEVICE LOCATIONS WITH LIGHTING FIXTURES AND FIRE SPRINKLER HEADS. PRIOR TO INSTALLATION, THE CONTRACTOR IS TO REFER TO THE ARCHITECTURAL REFLECTED CEILING PLAN FOR ACTUAL
FINAL LOCATIONS OF AIR DEVICES.
8. DIFFUSERS/GRILLES SHALL NEVER BE INSTALLED ON SURFACE OF ACOUSTICAL LAY-IN TILE. ALL DIFFUSERS/GRILLES IN LAY-IN CEILINGS SHALL BE LAY-IN PANEL MOUNT. REFER TO SCHEDULE. GYPSUM BOARD
SURFACE MOUNT DIFFUSERS SHALL NOT BE BEVEL MOUNT.
9. CONTRACTOR SHALL COORDINATE DIFFUSER/GRILLE LOCATIONS WITH STRUCTURE IN EXPOSED SITUATIONS IN ORDER TO ENSURE AIR IS NOT DIRECTLY SUPPLIED OR RETURNED OVER STRUCTURE OR OTHER TRADE COMPONENTS SUCH AS FIRE SPRINKLER PIPING, PLUMBING PIPING, ETC., CAUSING DUST ACCUMULATION.
DUCTWORK ALONG WITH DIFFUSER/GRILLE LOCATIONS SHALL BE INSTALLED SYMMETRICALLY WITH ANY ADJACENT DUCTWORK/GRILLES. CENTER DIFFUSERS/GRILLES BETWEEN STRUCTURAL MEMBERS WHERE DUCTWORK AND STRUCTURAL MEMBERS ARE EXPOSED. CONTRACTOR SHALL BE RESPONSIBLE FOR FINAL
INSTALLATION APPEARANCE AND SHALL MAKE APPROPRIATE CHANGES WHERE DIRECTED BY
ARCHITECT/ENGINEER AT THEIR OWN EXPENSE WHERE ITEMS ARE NOT INSTALLED PER ABOVE STANDARDS.
10. CONTRACTOR SHALL PROVIDE A COPY OF THE TEST AND BALANCE REPORT BY AN AABC OR NEBB CERTIFIED AGENCY. THIS REPORT MUST BE REVIEWED AND APPROVED BY THE ENGINEER PRIOR TO THE FINAL INSPECTION.
THE CONTRACTOR MUST ALSO PROVIDE ALL REPORTS REQUIRED BY THE SPECIFICATION. OUTDOOR TEMPERATURE (DB); OUTSIDE AIR (DB/WB & CFM); SUPPLY AIR AT UNIT DISCHARGE (DB/WB & CFM); RETURN AIR {MIXED} (DB/WB & CFM); LEAVING COIL (DB/WB); DIFFUSER/GRILLE (DB/WB); EQUIPMENT (EWT/LWT); EQUIPMENT (EAT/LAT); EQUIPMENT (GPM); EQUIPMENT (PRESSURES). OUTSIDE AIR CFM SHALL BE MEASURED DIRECTLY AND
NOT CALCULATED FROM THE DIFFERENCE BETWEEN SUPPLY AIR CFM AND RETURN AIR CFM.
11. CONTRACTOR SHALL MAKE NECESSARY ADJUSTMENTS DURING TEST AND BALANCE AS REQUIRED TO ENSURE EQUIPMENT IS OPERATING WITHIN VA TIL HVAC REQUIREMENTS. THIS INCLUDES, BUT IS NOT LIMITED TO, ADJUSTING BELTS, SHEAVES, PULLEYS, AND IMPELLERS.
12. ALL AIR HANDLING UNITS SHALL BE MECHANICALLY ATTACHED TO OTHER AIR DISTRIBUTION SYSTEM COMPONENTS. AIR HANDLING UNITS LOCATED OUTSIDE THE CONDITIONED SPACE SHALL BE SEALED USING APPROVED CLOSURE SYSTEMS CONFORMING TO THE APPROVED CLOSURE AND MECHANICAL APPLICATION
REQUIREMENTS OF FLORIDA BUILDING CODE.
13. ALL DUCTWORK MUST BE INSTALLED 6" AWAY FROM ANY FIRE RATED WALL TO FACILITATE INSPECTION.
14. WHEN DUCTWORK IS INSTALLED 12 FT. OR MORE ABOVE THE FINISHED FLOOR, WRITE DUCT SIZES IN LARGE FONT ON THE BOTTOM OF DUCTWORK, SUCH THAT DUCT SIZES CAN BE OBSERVED AT FLOOR LEVEL WITHOUT THE NEED
OF A LADDER OR MEASUREMENTS.
15. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL TRADES INSTALLATION SCHEDULES. FIXED WORK SUCH AS DUCTWORK AND PLUMBING SHALL BE INSTALLED PRIOR TO ANY TRADE WORK THAT CAN BE EASILY RELOCATED OR OFFSET SUCH AS ELECTRICAL CONDUITS, SMALL WATER LINES, ETC. IDEALLY DUCTWORK SHALL BE INSTALLED
FIRST.
16. PROVIDE A FIRE DAMPER AT EVERY DUCT PENETRATION OF A FIRE-RATED WALL OR CEILING, WHETHER SHOWN ON DRAWINGS OR NOT. ALL FIRE DAMPERS SHALL BE DYNAMIC TYPE WITH BLADES OUTSIDE AIRSTREAM, UNLESS
NOTED OTHERWISE.
17. PROVIDE FIRE, SMOKE, AND COMBINATION FIRE/SMOKE DAMPERS AT EVERY LOCATION WHERE REQUIRED BY SECTION 607.5 OF THE IBC-MECHANICAL, WHETHER SHOWN ON DRAWINGS OR NOT. PROVIDE PROPER DAMPER ACTUATION IN ACCORDANCE WITH SECTION 607.3.3 OF THE IBC-MECHANICAL. PROVIDE ACCESS AND
IDENTIFICATION IN ACCORDANCE WITH SECTION 607.4 OF THE IBC-MECHANICAL.
18. WHERE SMOKE OR COMBINATION FIRE/SMOKE DAMPERS ARE REQUIRED, THE ELECTRICAL OR FIRE ALARM CONTRACTOR (MECHANICAL CONTRACTOR TO COORDINATE) SHALL PROVIDE 120V POWER AND ENSURE PROPER OPERATION UPON ACTIVATION. PROVIDE PROPER DAMPER ACTUATION IN ACCORDANCE WITH SECTION 607.3.3.2
OF THE FBC-MECHANICAL.
19. PROVIDE SMOKE DAMPERS FOR ALL SYSTEMS WITH DESIGN CAPACITY GREATER THAN 15,000 CFM TO ISOLATE AIR HANDLING UNIT FROM THE REMAINDER OF THE SYSTEM ON BOTH THE SUPPLY AND RETURN SIDE, UNLESS THE AIR HANDLING UNIT IS LOCATED ON THE FLOOR IT SERVES AND SERVES ONLY THAT FLOOR, OR UNLESS THE AIR HANDLING UNIT IS LOCATED ON THE ROOF AND SERVES ONLY THE FLOOR IMMEDIATELY BELOW THE ROOF.
20. PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY AIR DUCT, DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY BRANCH CONNECTIONS, FOR ALL SYSTEMS HAVING A DESIGN CAPACITY GREATER THAN 2,000 CFM.
21. PROVIDE DUCT SMOKE DETECTORS WHERE REQUIRED BY SECTION 606.2 AND 607.3.3.2 OF THE IBC-MECHANICAL.
LOCATIONS OF DUCT MOUNTED SMOKE DETECTORS SHOWN ON DRAWINGS ARE DIAGRAMMATIC IN LOCATION ONLY. FINAL PLACEMENT OF DETECTORS IN DUCTWORK SHALL MEET THE REQUIREMENTS OF THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. PROVIDE A PRESSURE DIFFERENTIAL TEST AND MANUFACTURER'S TEST KIT. A COPY OF ALL TEST DATA SHALL BE MADE AVAILABLE AT FINAL INSPECTION.
PROVIDE A READILY ACCESSIBLE DUCT ACCESS DOOR FOR INSPECTING AND SERVICING EACH DETECTOR.
PROVIDE CEILING/WALL ACCESS PANELS WHERE INSTALLED IN INACCESSIBLE LOCATIONS; ACCESS PANELS IN RATED CONSTRUCTION SHALL BEAR A U.L. LABEL. MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL DETECTOR WITHIN THE DUCTWORK. ELECTRICAL OR FIRE ALARM CONTRACTOR (MECHANICAL CONTRACTOR TO COORDINATE) SHALL PROVIDE 120V POWER AND ENSURE PROPER OPERATION FOR EACH DETECTOR. OTHER THAN IN MECHANICAL SMOKE CONTROL SYSTEMS, UPON ACTIVATION, THE ASSOCIATED AIR DISTRIBUTION SYSTEM SHALL SHUT DOWN AND A SUPERVISORY SIGNAL SHALL BE GENERATED PER SECTION 606.4 OF THE
FBC-MECHANICAL.
22. PENETRATIONS FOR PIPES, CONDUITS OR OTHER PURPOSES THROUGH ASSEMBLIES (FLOORS, ROOF, WALLS, PARTITIONS, ETC.) WITH A REQUIRED FIRE RESISTANCE RATING SHALL BE SEALED TO THE PENETRATING MEMBER IN AN APPROVED MANNER WHICH MAINTAINS THE REQUIRED FIRE RESISTANCE RATING OF THE ASSEMBLY.
23. INTENT OF MECHANICAL NOTES ON DRAWINGS IS TO CLARIFY THE SCOPE OF WORK AND ALERT CONTRACTOR OF EXISTING CONDITIONS. CONTRACTOR IS TO VISIT THE SITE AND VERIFY ALL CLEARANCES BEFORE FABRICATION OF DUCTWORK, AND PROVIDE ADDITIONAL OFFSET AND/OR CHANGES IN DUCT SIZES TO MEET FIELD CONDITIONS, AND TO COORDINATE WITH ELECTRICAL, PLUMBING, AND FIRE PROTECTION SUBCONTRACTORS, BEFORE ANY
CONSTRUCTION WORK.
24. INSTALL DUCTWORK AS HIGH AS POSSIBLE, TIGHT TO BOTTOM OF STRUCTURE, UNLESS NOTED OTHERWISE.
COORDINATE DUCT ELEVATIONS WITH RAIN LEADERS, WATER PIPING, SANITARY DRAINS, AND MAJOR ELECTRICAL
CONDUITS.
25. CONTRACTOR SHALL PROVIDE ALL SUPPLEMENTARY STEEL, STRUCTURES, INSERTS, SLEEVES, AND HANGING DEVICES REQUIRED TO INSTALL AND ADEQUATELY SUPPORT MECHANICAL EQUIPMENT AND COMPONENTS IN A MANNER WHICH WILL NOT OVERLOAD BUILDING STRUCTURE. CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND ALL BUILDING TRADES TO AVOID CONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS AND
SERVICEABILITY.
26. CONTRACTOR SHALL INSTALL MOTORIZED OUTSIDE AIR DAMPERS FOR ALL AIR HANDLING EQUIPMENT. AIR HANDLING UNITS SHALL HAVE AN EQUIVALENT OR BETTER OF RUSKIN "CD50" DAMPER, WHICH SHALL MODULATE
PER 24V ACTUATOR MECHANICALLY WIRED. ALL DAMPERS SHALL CLOSE UPON UNIT SHUTDOWN.
27. PROVIDE A TRAP IN ALL CONDENSATE PIPING LOCATED AT THE AIR HANDLING EQUIPMENT. INSULATE ALL CONDENSATE LINES WITH 1/2" CLOSED CELL FOAM INSULATION. ALL PIPING EXPOSED TO EXTERNAL ELEMENTS
SHALL BE JACKETED WITH UV STABILIZED PVC OR ALUMINUM SHEETING.
28. PROVIDE A 4" HIGH CONCRETE HOUSEKEEPING PAD UNDER ALL MECHANICAL EQUIPMENT, UNLESS NOTED
OTHERWISE. PADS SHALL BE 4" LARGER THAN EQUIPMENT ON ALL SIDES.
29. ALL UNDERGROUND PIPING SHALL HAVE A MINIMUM 3'-0" OF COVER, UNLESS NOTED OTHERWISE.
30. IT IS THE RESPONSIBILITY OF THE MECHANICAL INSTALLER TO PATCH AND REPAIR ANY DUCT OPENINGS WHICH RESULT FROM THE RELOCATION OR ELIMINATION OF ANY EXISTING AIR DEVICES. THE PATCH IS TO BE OF A SIMILAR MATERIAL TO THE REPAIRED DUCT AND TO BE SEALED IN ACCORDANCE WITH SMACNA STANDARDS.
31. AIR HANDLING EQUIPMENT WARRANTIES SHALL BE EQUAL TO OR EXCEED WARRANTY OF SCHEDULED EQUIPMENT, UNLESS NOTED OTHERWISE.
32. PROVIDE SEISMIC RESTRAINTS FOR DUCTWORK AND PIPING CONFORMING TO THE LATEST EDITION OF THE "SMACNA GUIDELINES FOR SEISMIC RESTRAINTS OF MECHANICAL SYSTEMS AND PLUMBING SYSTEMS."
33. PROVIDE ADDITIONAL DUCTWORK AND PIPING SUPPORTS ON BOTH SIDES AND WITHIN 18" OF EACH FIRE RATED
WALL. DUCTWORK OR PIPING SHALL NOT BE SUPPORTED FROM ANY FIRE RATED WALL.
34. PROVIDE SINGLE WALL TURNING VANES IN ALL RECTANGULAR DUCT ELBOWS WITH ANGLES FROM 45 DEGREES TO 90 DEGREES, EXCEPT FOR TRANSFER AIR ELBOWS. TURNING VANES SHALL BE PROVIDED ACCORDING TO SMACNA
HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE.
35. DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS (FREE AREA).
36. CONTRACTOR SHALL COORDINATE ALL INTAKE/EXHAUST LOCATIONS TO ENSURE MINIMUM 10'-0" DISTANCE
BETWEEN ANY INTAKES AND EXHAUSTS, PLUMBING VENTS, RELIEF, ETC.
37. ALL HVAC EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER'S RECOMMENDATIONS UNLESS INDICATED
OTHERWISE.
38. CONTRACTOR SHALL THOROUGHLY CLEAN AND ENSURE PROPER OPERATION OF ANY EXISTING HVAC EQUIPMENT.
ANY CHANGE TO THE SYSTEM SHALL RESULT IN EQUIPMENT MODIFICATIONS (AS REQUIRED) INCLUDING BUT NOT
LIMITED TO REPLACING MOTORS, VFDS, PULLEYS, SHEAVES, BELTS, ETC.
39. MECHANICAL CONTRACTOR SHALL SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATIONS. REFRIGERANT PIPING SHALL BE TYPE "L" COPPER WITH SOLDERED OR BRAZED JOINTS AND 1" CLOSED CELL INSULATION. ALL PIPING EXPOSED TO EXTERNAL ELEMENTS SHALL BE JACKETED WITH UV STABILIZED PVC OR ALUMINUM SHEETING. PRE-CHARGED LINES AND SOLDER ON SHORT 90'S ARE NOT ACCEPTABLE. CONTRACTOR SHALL USE SWEEPING 90'S AT EVERY BEND WITH EXCEPTION OF EQUIPMENT
CONNECTIONS.
40. CONTRACTOR SHALL PROVIDE A PERMANENT/PROFESSIONAL LABEL FOR EACH PIECE OF EQUIPMENT, ASSOCIATED THERMOSTAT(S) AND/OR SENSOR(S).
41. EQUIPMENT LOCATION IDENTIFICATIONS AT CEILINGS: WHERE VALVES, EQUIPMENT SUCH AS VAV BOXES, FANS, ETC., CIRCUIT BREAKERS, OR OTHER ITEMS SUBJECT TO ROUTINE SERVICE, ARE MOUNTED IN A CONCEALED AREA ABOVE A CEILING, THE CEILING MUST BE MARKED WITH A LABEL UNDER THE SERVICED DEVICE. THE LABEL SHALL
CARRY APPROPRIATE IDENTIFICATION TAG.
42. DUCTWORK, DIFFUSERS, REGISTERS, GRILLES, AND OTHER MECHANICAL SYSTEM COMPONENTS SHALL NOT BE
SUPPORTED BY THE CEILING OR CEILING SUSPENSION SYSTEM.
43. ALL EXHAUST DUCT WORK SHALL BE NON-INSULATED SHEET METAL, UNLESS NOTED OTHERWISE.
44. CONTRACTOR SHALL SUPPLY PIPE SUPPORTS 4'-0" ON CENTERS FOR REFRIGERANT LINES AND CONDENSATE
LINES. SUPPORTS SHALL BE PER DETAILS.
45. ALL DOOR UNDERCUTS FOR THE PURPOSE OF BALANCING RETURN AIR SHALL BE 5/8".
46. ALL CONTROL WIRING SHALL BE INCLUDED AS PART OF MECHANICAL WORK; REFER TO ELECTRICAL SPECIFICATIONS FOR CONDUIT AND WIRING REQUIREMENTS. COORDINATE WITH ELECTRICAL CONTRACTOR TO ENSURE THAT REQUIRED INTERFACE DEVICES ARE PROVIDED WITH ELECTRICAL COMPONENTS (I.E. FAN SPEED
RHEOSTATS, AUXILIARY CONTACTS, INTERLOCKS, ETC.).
47. ALL EQUIPMENT DISCONNECTS, WHETHER INTERNALLY MOUNTED OR EXTERNALLY MOUNTED, SHALL BE FURNISHED, INSTALLED AND WIRED BY ELECTRICAL CONTRACTOR. IF EXTERNALLY MOUNTED, PROVIDE DISCONNECTING MEANS AT SAME ELEVATION AS EQUIPMENT. REFER TO ELECTRICAL SPECIFICATIONS FOR
REQUIREMENTS.
48. MECHANICAL CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL MECHANICAL EQUIPMENT WITH ELECTRICAL CONTRACTOR BEFORE BIDDING/ORDERING AND INSTALLATION.
49. WHERE MOTOR SPEED CONTROL IS REQUIRED, THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING THE APPROPRIATE METHOD OF SPEED CONTROL. TYPICALLY, SINGLE PHASE MOTORS REQUIRE SPEED CONTROLLERS, AND THREE PHASE MOTORS REQUIRE VFD'S.
MH000
Sheet List Table Sheet Number Sheet Title
MH000 MECHANICAL NOTES AND LEGENDS
MD100 MECHANICAL DEMOLITION PLAN - DUCTWORK
MD101 MECHANICAL DEMOLITION PLANS - PIPING
MH100 MECHANICAL RENOVATION PLAN -
DUCTWORK
MH101 MECHANICAL AIR BALANCE PLAN
MH200 MECHANICAL PENTHOUSE PLAN - DUCTWORK
MP100 MECHANICAL RENOVATION PLAN - PIPING
MP200 MECHANICAL PENTHOUSE PLAN - PIPING
MH500 MECHANICAL DETAILS
MH501 MECHANICAL DETAILS
MH600 MECHANICAL SCHEDULES
23 JAN 2504/03/2024 23 JAN 2504/03/2024
WAITING AREA
CONTROL
ROOM CLOSET
FILES
CONTROL
CYSTOSCOPY ROOM
ROOM
A-164
STORAGE
TOILET
RADIOGRAPHIC
PROCEDURES
TECHNICAL
CLERICAL
AREA
STORAGE
A-168
TOILET
EXAM
ROOM
A-173
C O R R I D O R
OFFICE
BUDGET
A-160
CARDIAC.
ROOM
A-158
OFFICE
A-159
PHYSICS
MEDICAL
A-158
ROOM
CONTROL
CYSTOSCOPY
A-167
ROOM
A-168
SUPERVISOR
OFFICE
A-169 A-170
A-171
EXAM
ROOM
A-172
EXAM
ROOM
A-158a
STO.
ROOMROOM
EXAM EXAM
H.A.C.
A-171
A-172b
TOILET
LOUNGE STAFF RM.
A-
2a
LO
C
K R
M
A-172 ECOCARDIO-
GRAPHY RM.
B-117 B-115
B-114
C O
R R
I D
O R
ELEC.
CLOS.
MALE LOCKERS
SIGNAL
CLOS. FEMALE LOCKERS
PHYSICIAN'S
LOCKERS
C O R R I D O R C1-8
(E)FCU
(E)FCU
(E)CD
(E)CD
(E)CD
(E)EG
(E)CD (E)RG
(E)CD
(E)CD
(E)CD (E)CD
(E)EG
(E)CD
(E)CD
(E)CD
(E)CD
(E)CD
(E)CD(E)CD
(E)CD
(E)EG
(E)EG
(E)CD
(E)CD
(E)EG
(E)EG
(E)10"Ø
(E)24X14
(E )2
4X
(E)8X6(E)8X8
(E)9X9
(E)8X8
(E)8"Ø
(E)22x14
(E )1
2x
(E)14X10
(E)22X16
(E)22X14
(E)30X10
(E )1
4X
(E)8X8 (E)44X14
(E )3
2X
(E)8"Ø (E)8"Ø
(E)8"Ø
(E )8
"Ø
(E )8
"Ø
(E)6"Ø
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
MECHANICAL DEMOLITION
PLAN - DUCTWORK
CB TH
KEYNOTES
1. REMOVE EXISTING AIR DEVICES AND AIR TERMINAL UNITS. DEMO
DUCTWORK BACK TO MAIN AND CAP. REMOVE ASSOCIATED HOT WATER
PIPING.
2. REMOVE EXISTING FAN COIL UNITS AND ASSOCIATED CHILLED WATER
(CHW) AND HEATING HOT WATER PIPING. CAP CHW PIPING BACK AT
MAIN.
3. EXISTING EXHAUST DUCTWORK TO BE REMOVED. PROVIDE TEMPORARY
CAP ON EXISTING DUCT TO REMAIN.
4. EXISTING HEATING HOT WATER PIPING FROM 2ND FLOOR PER AS BUILT
MH1-103 CHW.
5. REMOVE EXISTING HEATING HOT WATER PIPING IN AREA OF WORK BACK
TO THIS LOCATION. CAP FOR CONNECTION OF NEW VAV BOXES PIPING.
REFER TO RENOVATION PLAN MP100.
X
MD100
GENERAL NOTES
A. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A
MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE
REQUIREMENTS WITH THE COR.
B. ANY DEMOLITION OR RENOVATION WORK WITH THE EXISTING DUCT OR
PIPING SYSTEM NEEDS TO BE PERFORMED AFTER HOURS AND
COORDINATED WITH THE FACILITY FOR DOWN TIME.
C. EXISTING EQUIPMENT, PIPE ROUTING, AND ASSOCIATED COMPONENTS
SHOWN ON DRAWINGS ARE APPROXIMATE LOCATIONS BASED ON
RECORD DRAWINGS AND ARE PROVIDED FOR REFERENCE USE ONLY.
FIELD VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,
SIZES AND CONDITIONS OF EXISTING COMPONENTS.
D. ALL OPENINGS CREATED BY DEMOLITION OF EXISTING DUCTWORK OR
PIPING SHALL BE PATCHED WITH LIKE MATERIALS AND TO MAINTAIN
EXISTING FIRE RESISTIVE BARRIERS.
CYSTOSCOPY ROOM
ROOM
A-164
STORAGE
TOILET
PROCEDURES
TECHNICAL
CLERICAL
AREA
STORAGE
A-168
TOILET
EXAM
ROOM
A-173
CYSTOSCOPY
A-167
ROOM
A-168
SUPERVISOR
OFFICE
A-169 A-170
A-171
EXAM
ROOM
A-172
EXAM
ROOM
A-158a
STO.
ROOMROOM
EXAM EXAM
H.A.C.
A-171
A-172b
TOILET
A-
2a
LO
C
K R
M
C O R R I D O R C1-8
(E)FCU
(E)30X10
(E )8
"Ø
(E)1-1/2"
HHWS & R
FROM 2ND
FLOOR AND
MAINS ON
(E)HHWS
& R
(E)HHWS
& R
(E)HHWS
& R
(E)HHWS & R
1-1/2" HHWS & R
1-1/2" HHWS & R
(E)FCU
A
A
B
B
C
C
CONTROL
CYSTOSCOPY ROOM
ROOM
A-164
STORAGE
TOILET
PROCEDURES
TECHNICAL
CLERICAL
AREA
STORAGE
A-168
TOILET
EXAM
ROOM
A-173
CYSTOSCOPY
A-167
ROOM
A-168
SUPERVISOR
OFFICE
A-169 A-170
A-171
EXAM
ROOM
A-172
EXAM
ROOM
A-158a
STO.
ROOMROOM
EXAM EXAM
H.A.C.
A-171
A-172b
TOILET
A-
2a
LO
C
K R
M
CLOS.
C O R R I D O R C1-8
(E)FCU
(E)30X10
(E)1-1/2"
HHWS & R
FROM 2ND
FLOOR AND
MAINS ON
ROOF (AS
(E)HHWS
& R
(E)HHWS
& R
(E)HHWS
& R
(E)HHWS & R
(E)HHWS
& R
(E)HHWS
& R
(E)HHWS
& R
(E)FCU
6(E)HHWS
& R
(E)HHWS
& R
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
MECHANICAL DEMOLITION
PLANS - PIPING
CB TH
KEYNOTES
1. CONNECT NEW PIPING PROVIDED IN PRE-DEMO PHASE TO EXISTING AT
THIS END DURING COORDINATED SHUTDOWN TIME.
2. REMOVE EXISTING AIR TERMINAL UNITS AND ASSOCIATED HEATING HOT
WATER PIPING.
3. REMOVE EXISTING FAN COIL UNITS AND ASSOCIATED CHILLED WATER
(CHW) AND HEATING HOT WATER PIPING. CAP CHW PIPING BACK AT
MAIN.
4. EXISTING HEATING HOT WATER PIPING FROM 2ND FLOOR PER AS BUILT
MH1-103 CHW.
5. EXISTING HEATING HOT WATER PIPING MAINS IN CONFLICT WITH NEW
DUCTWORK (SEE MH100). REMOVE EXISTING HHWS & R PIPING IN AREA
OF WORK. REFER TO RENOVATION PLAN MP100.
6. PIPING CONTINUE TO SERVE AREA BEYOND AREA IN SCOPE OF WORK.
X
MD101
GENERAL NOTES
A. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A
MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE
REQUIREMENTS WITH THE COR.
B. ANY DEMOLITION OR RENOVATION WORK WITH THE EXISTING DUCT OR
PIPING SYSTEM NEEDS TO BE PERFORMED AFTER HOURS AND
COORDINATED WITH THE FACILITY FOR DOWN TIME.
C. EXISTING EQUIPMENT, PIPE ROUTING, AND ASSOCIATED COMPONENTS
SHOWN ON DRAWINGS ARE APPROXIMATE LOCATIONS BASED ON
RECORD DRAWINGS AND ARE PROVIDED FOR REFERENCE USE ONLY.
FIELD VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,
SIZES AND CONDITIONS OF EXISTING COMPONENTS.
D. ALL OPENINGS CREATED BY DEMOLITION OF EXISTING DUCTWORK OR
PIPING SHALL BE PATCHED WITH LIKE MATERIALS AND TO MAINTAIN
EXISTING FIRE RESISTIVE BARRIERS.
PRE-DEMOLITION NOTES
A. TO KEEP HEATING HOT WATER SERVICE AT MINIMUM INTERRUPTION,
PRIOR TO REMOVING THE EXISTING HHWS AND HHWR, PROVIDE NEW
PIPING READY TO BE CONNECTED TO EXISTING PIPING SERVING AREA
BEYOND THE AREA IN SCOPE OF WORK.
B. EXISTING PIPING NOT TO BE DISTURBED. COORDINATE TO TEMPORARILY
SHUT DOWN THE EXISTING PIPING TO PROVIDE NEW ISOLATION VALVES
ON EXISTING MAINS.
C. CONNECT NEW PIPING TO EXISTING PIPING THAT ARE TO REMAIN. SEE
DEMOLITION PLAN AND NOTE 1 ON THIS SHEET AND PIPING RENOVATION
PLAN MP-100.
X
ROOM
CLOSET
FILES
RADIOGRAPHIC
C O R R I D O R
OFFICE
BUDGET
A-160
CARDIAC.
ROOM
A-158
OFFICE
A-159
PHYSICS
MEDICAL
A-158
ROOM
CONTROL
A-
8a
ST
O
H.A.C.
A-171
A-172b
TOILET
A-172 ECOCARDIO-
GRAPHY RM.
B-117 B-115
B-114
LOUNGE STAFF RM.
A-172a
LOCK RM.
ELEC.
CLOS.
MALE LOCKERS
SIGNAL
CLOS. FEMALE LOCKERS
PHYSICIAN'S
LOCKERS
C O
R R
I D
DN.DN.
C O R R I D O R C1-8
HYBRID
OPERATING
ROOM
CONTROL
ROOM
SCRUB STN.
IMAGING
COMPONENT
ROOM
STERILE
SUPPLY
GURNEY
8.8
9.8
CBA
NO WORK IN THIS ROOM
NO WORK IN
THIS ROOM
NO WORK
IN THIS
ROOM
CD-1
8"Ø
185 CFM
T
T
T
T
ATU-1-2
ATU-1-3
ATU-1-4
EG-1
8"Ø
370 CFM
EG-1
8X6
170 CFM
X1
8"Ø8X8
CD-1
8"Ø
185 CFM
CD-1
8"Ø
135 CFM
CD-1
8"Ø
135 CFM
6"Ø8X6
CD-1
8"Ø
140 CFM
CD-1
12"Ø
515 CFM
CD-1
12"Ø
515 CFM16X12
X1
EG-1
8X6
140 CFM
EG-1
18X12
505 CFM
EG-1
20X20
1030 CFM
14X14
X1
12X8
16X14 20X20
20X20
EG-1
18X12
505 CFM
EG-1
18X12
505 CFM
12X8
20X16
X1
X1
12X8
2.3
2.3
2.3
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.3
2.3
3.0
3.0
3.0
3.0
3.03.0
3.0
3.0
3.0 3.0
3.0
3.0
2.3
2.3
2.3
2.3
2.3
3.0
3.0
3.0
3.0
2.3
2.3
2.3
2.3
2.3
ATU-1-1
ATU-1-3
ATU-1-4
ATU-1-2
2EG-1
18X12
505 CFM
ATU-1-1
X2
14"Ø
6 TYP
20X20
H
H
1445 CFM
1445 CFM
ATU-1-5
ATU-1-6
AFCV
AFCV
AFCV
AFCV
E
E
12X8
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
MECHANICAL RENOVATION
PLAN - DUCTWORK
NS TH
MH100
KEYNOTES
1. 2890 CFM TOTAL SUPPLY AIR DUCTS CONNECT TO MODULAR LAMINAR
CEILING DIFFUSER SYSTEM BY SLD AIRFRAME. COORDINATE DUCT
CONNECTIONS WITH SYSTEM MANUFACTURER. PROVIDE ALL
NECESSARY OFFSETS AND TRANSITIONS FOR CONNECTION TO THE
SYSTEM. SEE ARCHITECTURAL PLANS FOR EXACT LOCATION, DETAILS
AND ADDITIONAL REQUIREMENTS. TEST AND BALANCE AGENCY TO SET
AIR FLOW TO 1445 CFM AT EACH CONNECTION AND SPREAD EQUALLY
THOUGH HEPA FILTERS. HEPA FILTERS TO BE PROVIDED WITH AIR
FRAME UNIT BY G.C. ALL HEPA FILTERS SHALL BE ACCESSIBLE FOR
SERVICE.
2. MOUNT EXHAUST GRILLES LOW IN WALL. BOTTOM OF GRILLE TO BE 7"
AFF. ROUTE DUCTWORK UP THROUGH CHASE TO DUCT ABOVE CEILING.
3. ROUTE 20X20 SUPPLY DUCT UP TO ROOF LEVEL AND ROUTE ACROSS
LOW ROOF TO MECHANICAL PENTHOUSE.
4. ROUTE 20X20 EXHAUST/RETURN DUCTWORK UP TO ROOF LEVEL AND
ROUTE ACROSS LOW ROOF TO MECHANICAL PENTHOUSE.
5. CONNECT 14X14 SUPPLY DUCTWORK TO SLD AIRFRAME CEILING SYSTEM
BY OTHERS. COORDINATE FINAL CONNECTION SIZE AND LOCATION IN
FIELD.
6. COORDINATE LOCATION OF DUCTWORK AND TERMINAL UNITS WITH
OTHER CEILING COMPONENTS.
7. CONNECT TO EXISTING DUCT ABOVE CEILING. VERIFY SIZE AND
LOCATION IN FIELD.
8. AFCV LOCATED IN VERTICAL RETURN DUCT IN CHASE. PROVIDE ACCESS
PANEL FOR ACCESS TO CONTROL PANEL. COORDINATE ACCESS PANEL
LOCATION WITH OTHER TRADES.
X
GENERAL NOTES
A. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A MINIMUM.
COORDINATE ALL DISRUPTIVE WORK AND OUTAGE REQUIREMENTS WITH
THE COR.
B. ANY DEMOLITION OR RENOVATION WORK WITH THE EXISTING DUCT OR
PIPING SYSTEM NEEDS TO BE PERFORMED AFTER HOURS AND
COORDINATED WITH THE FACILITY FOR DOWN TIME.
C. EXISTING EQUIPMENT, PIPE ROUTING, AND ASSOCIATED COMPONENTS
SHOWN ON DRAWINGS ARE APPROXIMATE LOCATIONS BASED ON RECORD
DRAWINGS AND ARE PROVIDED FOR REFERENCE USE ONLY. FIELD VERIFY
AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS, SIZES AND
CONDITIONS OF EXISTING COMPONENTS.
D. ALL OPENINGS CREATED BY DEMOLITION OF EXISTING DUCTWORK OR
PIPING SHALL BE PATCHED WITH LIKE MATERIALS AND TO MAINTAIN
EXISTING FIRE RESISTIVE BARRIERS.
X
ROOM
CLOSET
FILES
RADIOGRAPHIC
C O R R I D O R
OFFICE
BUDGET
A-160
CARDIAC.
ROOM
A-158
OFFICE
A-159
PHYSICS
MEDICAL
A-158
ROOM
CONTROL
A-
8a
ST
O
H.A.C.
A-171
A-172b
TOILET
A-172 ECOCARDIO-
GRAPHY RM.
B-117 B-115
B-114
LOUNGE STAFF RM.
A-172a
LOCK RM.
ELEC.
CLOS.
MALE LOCKERS
SIGNAL
CLOS. FEMALE LOCKERS
PHYSICIAN'S
LOCKERS
C O
R R
I D
HYBRID
OPERATING
ROOM
CONTROL
ROOM
SCRUB STN.
IMAGING
COMPONENT
ROOM
STERILE
SUPPLY
GURNEY
8.8
9.8
CBA
NO WORK IN THIS ROOM
NO WORK IN
THIS ROOM
NO WORK
IN THIS
ROOM
(o)
(o)
DP
DP
DP DP
DP DP
2 DP
DP
2 DP
DP
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
MECHANICAL AIR BALANCE
PLAN
NS TH
MH101
KEYNOTES
1. REFER TO ROOM AIRFLOW CALCULATION SCHEDULE.
2. DIFFERENTIAL PRESSURE MONITOR. COORDINATE FINAL LOCATION IN
FIELD.
X
GENERAL NOTES
A. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A
MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE
REQUIREMENTS WITH THE COR.
B. EXISTING EQUIPMENT, PIPE ROUTING, AND ASSOCIATED COMPONENTS
SHOWN ON DRAWINGS ARE APPROXIMATE LOCATIONS BASED ON
RECORD DRAWINGS AND ARE PROVIDED FOR REFERENCE USE ONLY.
FIELD VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,
SIZES AND CONDITIONS OF EXISTING COMPONENTS.
C. ALL OPENINGS CREATED BY DEMOLITION OF EXISTING DUCTWORK OR
PIPING SHALL BE PATCHED WITH LIKE MATERIALS AND TO MAINTAIN
EXISTING FIRE RESISTIVE BARRIERS.
ROOM AIRFLOW CALCULATIONS
ATU
NUMBER
ROOM
NUMBER
ROOM NAME
ON PLAN
ROOM TYPE per VA Design Guidelines
ROOM
AREA
(SF)
ROOM
HEIGHT
(FT)
ROOM AIR
BALANCE
MIN. OA
AC/H
MIN
TOTAL
AC/H
ALL AIR
EXHAUSTED
DIRECTLY
TO
OUTDOORS
ROOM
AIR FLOW
OUTDOOR AIR TOTAL AIR FLOW EXHAUST AIR FLOW TRANSFER RETURN AIR FLOW RELATIVE
SPACE
PRESSURE/
AIR
MOVEMENT
REQD
CFM
DESIGN
CFM
REQD MIN
TOTAL
CFM
ROUNDED
REQD MIN
TOTAL
CFM
ACTUAL
SA
DESIGN
CFM
REQD
EXHAUST
CFM
DESIGN
EXHAUST
CFM
REQD
TRANSFER
CFM (IN)
DESIGN
TRANSFER
CFM (IN)
REQD
RETURN
CFM
DESIGN
RETURN
CFM
1-3 100 SCRUB STN Semi-Restricted Corridor 107 9.50 (o) 2 8 NO VAV 34 40 136 140 140 0 0 0 0 140 140 Neutral
1-3 101
IMAGING
COMPONENT
ROOM
Radiographic Film Processing Room 141 9.50 (-) 2 8 YES CV 45 50 179 180 1,030 1,190 1,190 160 160 0 0 Negative/IN
1-1 102 HYBRID
OPERATING ROOM
ORGS1: General Operating Room 910 9.50 (++) 4 20 NO VAV 576 580 2,882 2,890 2,890 0 0 -870 -870 2,020 2,020 Positive/OUT
1-4 103 CONTROL ROOM ORHC1: Hybrid OR Control Room 285 9.50 (o) 2 8 NO VAV 90 100 361 370 370 0 0 0 0 370 370 Neutral
1-2 104 STERILE SUPPLY
SRSP1: Sterile Processing Supplies Storage 421 9.50 (+) 4 4 YES CV 267 270 267 270 270 220 170 -50 -100 0 0 Positive/OUT
LV-1
EF-1BEF-1A
AHU-1BAHU-1A
P-2
P-1
STAIR # 1
UP. DN.
ROOM
A-309-X
F G H JFEDC
20X20
20X20
AHU-3-01
(E)
FC-P4-01
(E)
EF-3-01-01
(E)
EF-3-01-02
(E)
LV-2
20X20
20X20
X2
20X20
X2
M
M
M
X2
X2
DD DD
M
M M
M
ROOF (2ND FLOOR)
ROOF (2ND FLOOR)
PENTHOUSE (4TH
FLOOR)
20X20
20X20 22"Ø
22"Ø
22"Ø
22"Ø
22"Ø
22"Ø
22"Ø
22"Ø
X2
X2
VFDVFD VFD VFDVFD VFD
M12
TYP.
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
MECHANICAL PENTHOUSE
PLAN - DUCTWORK
NS TH
MH200
KEYNOTES
1. AIR HANDLERS LOCATED IN EXISTING PENTHOUSE. COORDINATE
LOCATION WITH OTHER EQUIPMENT. ROUTE INTAKE DUCT HIGH FROM
LOUVER TO AIR HANDLER.
2. EXHAUST FANS LOCATED IN PENTHOUSE. ROUTE DISCHARGE DUCT TO
EXHAUST LOUVER. VERIFY FINAL LOCATION IN FIELD.
3. ROUTE 20X20 SUPPLY DUCTWORK DOWN THROUGH ROOF TO FIRST
FLOOR CEILING SPACE ADJACENT TO HYBRID OR. SEE MH-100 FOR
CONTINUATION.
4. ROUTE 20X20 EXHAUST/RETURN DUCTWORK DOWN THROUGH ROOF TO
FIRST FLOOR CEILING SPACE ADJACENT TO HYBRID OR. SEE MH-100 FOR
CONTINUATION.
5. INTAKE LOUVER IN PENTHOUSE WALL. VERIFY FINAL LOCATION IN FIELD.
6. EXHAUST LOUVER IN PENTHOUSE WALL. VERIFY FINAL LOCATION IN
FIELD.
7. ROUTE DUCT DOWN TO FIRST FLOOR ROOF LEVEL AND ACROSS ROOF
TO ABOVE NEW HYBRID OR LOCATION. PROVIDE WALL AND ROOF
SUPPORTS AS REQUIRED. REFER TO DETAILS 1, 3, AND 6 ON MH501.
8. DUCT DOWN TO PENETRATE PENTHOUSE FLOOR. SEAL PENETRATION
WATERTIGHT. SECURE DUCT TO 3RD FLOOR EXTERIOR WALL.
9. PROVIDE ROOF SUPPORTS FOR ALL DUCTWORK ROUTED ON ROOF.
10. TYPICAL LOW LEAKAGE MOTORIZED MODULATING DAMPER CONTROLLED
BY BMS.
11. PROVIDE SUPPORTS AT BOTTOM OF VERTICAL DUCT (DUCT CHANGE IN
DIRECTION).
12. COORDINATE VFD LOCATION WITH ELECTRICAL. TYPICAL.
13. DUCTWORK HIGH, OVERHEAD, SUPPORTED FROM ROOF STRUCTURE.
14. ULTRA-LOW LEAKAGE AMCA 511 - CLASS 1A RATING AUTOMATIC
DAMPER.
GENERAL NOTES
A. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A
MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE
REQUIREMENTS WITH THE COR.
B. ANY DEMOLITION OR RENOVATION WORK WITH THE EXISTING DUCT OR
PIPING SYSTEM NEEDS TO BE PERFORMED AFTER HOURS AND
COORDINATED WITH THE FACILITY FOR DOWN TIME.
C. EXISTING EQUIPMENT, PIPE ROUTING, AND ASSOCIATED COMPONENTS
SHOWN ON DRAWINGS ARE APPROXIMATE LOCATIONS BASED ON
RECORD DRAWINGS AND ARE PROVIDED FOR REFERENCE USE ONLY.
FIELD VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,
SIZES AND CONDITIONS OF EXISTING COMPONENTS.
D. ALL OPENINGS CREATED BY DEMOLITION OF EXISTING DUCTWORK OR
PIPING SHALL BE PATCHED WITH LIKE MATERIALS AND TO MAINTAIN
ROOM
CLOSET
FILES
RADIOGRAPHIC
C O R R I D O R
OFFICE
BUDGET
A-160
CARDIAC.
ROOM
A-158
OFFICE
A-159
PHYSICS
MEDICAL
A-158
ROOM
CONTROL
A-
8a
ST
O
H.A.C.
A-171
A-172b
TOILET
A-172 ECOCARDIO-
GRAPHY RM.
B-117 B-115
B-114
LOUNGE STAFF RM.
A-172a
LOCK RM.
ELEC.
CLOS.
MALE LOCKERS
SIGNAL
CLOS. FEMALE LOCKERS
PHYSICIAN'S
LOCKERS
C O
R R
I D
HYBRID
OPERATING
ROOM
CONTROL
ROOM
SCRUB STN.
IMAGING
COMPONENT
ROOM
STERILE
SUPPLY
GURNEY
8.8
9.8
CBA
NO WORK IN THIS ROOM
NO WORK IN
THIS ROOM
NO WORK
IN THIS
ROOM
T
T
T
T
ATU-1-2
ATU-1-3
ATU-1-4
ATU-1-1
ATU-1-3
ATU-1-4
ATU-1-2
ATU-1-1
1-1/2"
3/4"
3/4"
3/4"
(E)1-1/2" FROM 2ND
FLOOR AND MAINS ON
ROOF (AS BUILT MH1-103
CHW)
3/4"
(E)1-1/2"
1-1/2"
1-1/2"
3/4"
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
MECHANICAL RENOVATION
PLAN - PIPING
NS TH
MP100
KEYNOTES
1. HHWS & HHWR MAINS PROVIDED IN PRE-DEMOLITION PHASE. REFER TO
DEMOLITION PLAN MD100.
2. PROVIDE HHWS & HHWR PIPING AT NEW AIR TERMINAL. TYPICAL.
X
GENERAL NOTES
A. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A
MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE
REQUIREMENTS WITH THE COR.
B. ANY DEMOLITION OR RENOVATION WORK WITH THE EXISTING DUCT OR
PIPING SYSTEM NEEDS TO BE PERFORMED AFTER HOURS AND
COORDINATED WITH THE FACILITY FOR DOWN TIME.
C. EXISTING EQUIPMENT, PIPE ROUTING, AND ASSOCIATED COMPONENTS
SHOWN ON DRAWINGS ARE APPROXIMATE LOCATIONS BASED ON
RECORD DRAWINGS AND ARE PROVIDED FOR REFERENCE USE ONLY.
FIELD VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,
SIZES AND CONDITIONS OF EXISTING COMPONENTS.
D. ALL OPENINGS CREATED BY DEMOLITION OF EXISTING DUCTWORK OR
PIPING SHALL BE PATCHED WITH LIKE MATERIALS AND TO MAINTAIN
EF-1BEF-1A
AHU-1BAHU-1A
P-2
P-1
STAIR # 1
UP. DN.
ROOM
A-309-X
F G H JFED
1-1/4" HWS
1-1/4" HWR
2" CHWS
2" CHWR
1-1/4" HWS
1-1/4" HWR
2" CHWS
2" CHWR
1-1/4" HWS
1-1/4" HWR2" CHWS
2" CHWR
AHU-3-01
(E)
FC-P4-01
(E)
EF-3-01-01
(E)
EF-3-01-02
(E)
(E)3" CHWS
(E)3" CHWR
(E)8" CHWS (E)8" CHWR
(E)8" CHWS
(E)8" CHWR
1-1/4" HWS 1-1/4" HWR
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
MECHANICAL PENTHOUSE
PLAN - PIPING
NS TH
MP200
KEYNOTES
1. ROUTE DRAIN FROM AHU TO APPROVED LOCATION.
2. HHWS AND HHWR PIPING CONNECTED TO EXISTING HHWS AND HHWR
PIPING LOCATED ON ROOF BELOW. VERIFY SIZE AND LOCATION IN FIELD.
PROVIDE ISOLATION VALVE AT CONNECTION.
3. CHWS AND CHWR PIPING CONNECTED TO EXISTING 8" MAIN. VERIFY
SIZE AND LOCATION IN FIELD.
4. PIPING TO BE SUPPORTED FROM STRUCTURE ABOVE. COORDINATE IN
FIELD.
X
GENERAL NOTES
A. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A
MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE
REQUIREMENTS WITH THE COR.
B. ANY DEMOLITION OR RENOVATION WORK WITH THE EXISTING DUCT OR
PIPING SYSTEM NEEDS TO BE PERFORMED AFTER HOURS AND
COORDINATED WITH THE FACILITY FOR DOWN TIME.
C. EXISTING EQUIPMENT, PIPE ROUTING, AND ASSOCIATED COMPONENTS
SHOWN ON DRAWINGS ARE APPROXIMATE LOCATIONS BASED ON
RECORD DRAWINGS AND ARE PROVIDED FOR REFERENCE USE ONLY.
FIELD VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,
SIZES AND CONDITIONS OF EXISTING COMPONENTS.
D. ALL OPENINGS CREATED BY DEMOLITION OF EXISTING DUCTWORK OR
PIPING SHALL BE PATCHED WITH LIKE MATERIALS AND TO MAINTAIN
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
MECHANICAL DETAILS
NS TH
MH500
20° TRANSITION (MAX)
0.25 D (4" MIN. PER SMACNA)
RECTANGULAR DUCT
D
VOLUME DAMPER
CONICAL FITTING WITH LOCKING
TYPE VOLUME DAMPER.
FLEX DUCT OR ROUND SHEET METAL DUCT. FLEX DUCT
MAX. 8'-0" LONG, USE CLAMP TO ATTACH FLEX DUCTS AND
SEAL. SUPPORT DUCT EVERY FOUR FEET FROM
STRUCTURE
1.
D
DUCT DETAILS NTS
SUPPORT AS PER
SMACNA STANDARDS
SPIN-IN FITTING WITH BUTTERFLY
DAMPER
ROUND "SNAPLOCK" SHEET METAL OR SPIRAL
LOCKSEAM WITH WRAP INSULATION
(SAME AS DIFFUSER NECK)
RIGID DUCT: PROVIDE RADIUS
ELBOW (SAME SIZE AS
DIFFUSER NECK)
THREE SHEET METAL
SCREWS THROUGH DUCT,
MASTIC OR TAPE
2" WRAP INSULATION:
CUT, FIT & GLUED OVER
CEILING DIFFUSER
CEILING DIFFUSERCEILING
SUPPLY DUCT
SUPPORT STRAP (PER
SMACNA)
CEILING DIFFUSER RUNOUT DETAIL NTS
PROVIDE VOLUME
DAMPER WHEN SHOWN
ON PLANS
PROVIDE VOLUME
DAMPER
MAIN SUPPLY DUCT
ADJUSTABLE METAL
ROD OR LINKAGE
TOP REGISTER
MAIN SUPPLY DUCT
BRANCH DUCT
1/4W 4" MIN.
SEE PLAN FOR SPLIT DIMENSION
MAIN SUPPLY
DUCT
TURNING VANES
SQUARE ELBOW SHOWN.
PROVIDE ROUND ELBOW
WHEN SHOWN ON PLANS
SUPPLY REGISTER
OR BRANCH DUCT
PLAN VIEW
AIR SPLIT TYPE DUCT TAKE-OFF
PLAN VIEW
BRANCH DUCT TAKE-OFF
PLAN VIEW
SUPPLY REGISTER TAKE-OFF
SUPPLY DUCT TAKE-OFFS NTS
R.F. CEILING PANEL W/
COPPER SHIELD
NOTES:
1. ALL UNDERLINED ITEMS ARE PROVIDED BY THE R.F. SHIELD
MANUFACTURER OR INSTALLER.
2. DURING FABRICATION OF THE R.F. SHIELD, HVAC CONTRACTOR SHALL
MAKE DUCKWORK CONNECTION TO THE WAVEGUIDE.
R.F. WALL PANEL W/
COPPER SHIELD
WOOD FURRING
CANVAS COLLAR
DUCT (SEE DRAWINGS
FOR TYPE AND SIZE)
FINISHED
CEILING
AIR DEVICE (SEE
SCHEDULE)
FINISHED WALL
1-3/4" WOOD
COLLAR
FINISHED
CEILING
WAVE GUIDE : DIMENSIONS TO
MATCH DUCT SIZE, COORDINATE
WITH R.F SHIELD MANUFACTURER
SIDEWALL WAVE GRILLE DETAIL NTS3
4 2
REFER TO SPECIFICATION SECTION 13 05 41 FOR
SEISMIC RESTRAINTS AND BRACING.
AIR HANDLING UNIT DRAIN TRAP DETAIL NTS5
VARIABLE VOLUME AIR TERMINAL CONTROL DIAGRAM8 WATER COILS PIPING CONNECTIONS6
DUCT CONNECTIONS - AIR TERMINAL UNITS7AIR HANDLER9
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
MECHANICAL DETAILS
NS TH
MH501
1 ROOF DUCT SUPPORT NTS
SEISMIC SWAY BRACING DETAILS NTS7
SEISMIC PIPE SUPPORT DETAIL NTS5 SEISMIC BRACING FOR MECHANICAL EQUIPMENT NTS2
ROOF CURB ATTACHMENT
SEE NOTE 3
NTS
M
IN
. 1 2"
NOTES:
PT BLOCKING
SEE NOTE 1
REFER TO ARCHITECTURAL
DRAWINGS FOR PROPER WEATHER
PROOFING DETAILS
1. SECURE CURB CAP TO WOOD NAILING STRIP WITH 2" LONG 3/8"
CADMIUM PLATED LAG BOLTS NOT OVER 12" ON CENTER.
2. SECURE ROOF CURB TO STRUCTURAL STEEL BELOW ROOF DECK
WITH 4" LONG HOT-DIPPED GALVANIZED #10 TEK SCREWS 6" O.C.
3. ROOF CURB ATTACHMENT
SEE NOTE 2
GALVANIZED, (AND INSULATED, FOR
OUTSIDE AIR DUCT ONLY) THYBAR
MANUFACTURED CURB WITH BUILT-IN CANT,
PROVIDE CRICKETS ON LOW SIDE OF CURB.
6" O.C.
TYP.
2" FROM
EDGE.
CRICKET LOCATION
CONTRACTOR SHALL BE
RESPONSIBLE FOR WATER TIGHT
SEAL (PER SMACNA)
CURB
DUCT
NTS
12" X 12" X 1/4" PLATE
1"
9"
5/8" DRILLED HOLES
FOR 1/2" BOLTS
1/4"
DUCT DEPTH
10" MIN
SUPPORT BOTH
SIDES OF DUCT AT
12 FT DUCT
INTERVAL
1-1/4" X 1-1/4" X 1/8"
WELDED
6" MIN
TIE DOWN
AS
R
EQ
UI
RE
D
4 3 SIDES
GALVANIZED STEEL ANGLE - L2" x 2" x 1/4" (TYP)
WELDED CONNECTIONS, REPAIR DAMAGED
GALVANIZING WITH COLD GALVANIZING
COMPOUND (TYP.)
5/16"Ø GALVANIZED BOLT, NUT AND LOCKWASHER
(TYP)
24" x 48" CONCRETE PAD
GALVANIZED STEEL BASE PLATE, 8" x 8" x 1/4", BOLT TO
CONCRETE PAD WITH 1/4" X 3" EXPANSION BOLTS
1/2" THICK NEOPRENE ROOF
PROTECTIVE PAD, 2" LARGER THAN
CONCRETE ALL 4 SIDES
1/4" CONN. PLATE (TYP)
AT ROOF DUCT SUPPORT-INSULATE OVER ANGLE
IRON SUPPORTS AND SEAL ALL CORNERS OF
ANGLES IN A WEATHER TIGHT MANNER.
1/8 1/8
1/8
R-8 INSULATION
DOUBLE WALL DUCT
2" WIDE X 18 GAGE DUCT STRAP
EXIST. ROOF
12X8 RETURN
12X8 RETURN
AIRFLOW CONTROL
VALVE
AFCV CONTROL PANEL*
CHASE WALL
ACCESS PANEL*
FROM MAIN
RETURN DUCT
CEILING
7" AFF
RETURN AIR GRILLE
(* LOCATIONS TO BE
FIELD COORDINATED)
NTS
PRESSURE DIFFERENTIAL CONTROL9
RF SF
RELIEF AIR OUTSIDE AIR
AHU
PR
EFILTER
H C
C C
FILTER
VAVRAV
HYBRID OR
SP
SP
RAV - RETURN AIR VALVE
VAV - VARIABLE AIR VALVE
RAVRAVRAV
23 JAN 2504/03/2024
strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
MECHANICAL SCHEDULES
NS TH
MH600
LOUVER SCHEDULE
MARK MANUFACTURER MODEL # TYPE CFM MAX Δ P
IN W.G. LxW %FA DRAINABLE REMARKS
LV-1 RUSKIN ELF375DXD INTAKE 4,880 0.5 12'X4' 49 YES 1, 2
LV-2 RUSKIN ELF375DXD EXHAUST 4,880 0.5 6'X4' 49 YES 1, 2
NOTES:
1. COORDINATE LOUVER INSTALLATION AND COLOR WITH ARCHITECTURAL.
2. PROVIDE INSECT SCREEN.
VAV TERMINAL UNIT SCHEDULE
MARK AREA SERVING MANUFACTURER MODEL # MAX CFM MIN CFM HTG COIL
GPM HTG MBH INLET
SIZE
MAX PRESS.
DROP REMARKS
ATU-1-1 OPERATING ROOM PRICE INDUSTRIES SDV14 2890 2,890 1.0 27.1 14 0.25 1-4
ATU-1-2 STERILE SUPPLY PRICE INDUSTRIES SDV06 270 65 0.5 7.5 6 0.25 1-4
ATU-1-3 IMAGING COMPONENT ROOM PRICE INDUSTRIES SDV10 1170 300 1.0 11.9 10 0.25 1-4
ATU-1-4 CONTROL ROOM PRICE INDUSTRIES SDV08 370 120 0.5 8.8 8 0.25 1-4
ATU-1-5 CONTROL ROOM (RA) PRICE INDUSTRIES SDV08 370 120 NA NA 8 0.25 1-2
ATU-1-6 STERILE SUPPLY (RA) PRICE INDUSTRIES SDV08 170 50 NA NA 6 0.25 1-2
NOTES:
1. ALL AIR TERMINAL UNITS SHALL BE PRESSURE INDEPENDENT TYPE WITH VELOCITY RESET CONTROLLERS.
2. INSTALL UNIT WITH CLEARANCE FOR ELECTRICAL AND MAINTENANCE ACCESS. PROVIDE CEILING ACCESS PANEL WHERE NEED TO ACCESS UNIT.
3. PROVIDE DOUBLE WALL CASING
3. PROVIDE COPPER FINS FOR HOT WATER COILS.
FAN SCHEDULE
MARK MANUFACTURER MODEL # TYPE CFM ESP HP VOLTS/Ø DRIVE REMARKS
EF-1A GREENHECK QEID-16 MIXED FLOW 4,880 2 3 460/3 DIRECT 1-4
EF-1B GREENHECK QEID-16 MIXED FLOW 4,880 2 3 460/3 DIRECT 1-4
NOTES:
1. PROVIDE VFD WITH DISCONNECT.
2. PROVIDE GRAVITY BACKDRAFT DAMPER.
3. INTERLOCK WITH AIR HANDLERS
4. FANS TO OPERATE IN A LEAD LAG CONFIGURATION.
GRILLE, REGISTER, AND DIFFUSER SCHEDULE
MARK MANUFACTURER MODEL # DESCRIPTION MATERIAL DAMPER REMARKS
CD-1 TITUS TMS-AA SQUARE THREE CONE CEILING DIFFUSER ALUMINUM YES 1-6
EG-1 TITUS 350FL LOUVER FACE, 3/4" BLADE SPACING ALUMINUM YES 1-6
* TRM MOUNTING FRAME SHALL BE USED FOR GRILLES/DIFFUSERS MOUNTED IN GYP. BOARD CEILINGS, UNLESS NOTED OTHERWISE.
NOTES:
1. PAINT PER ARCHITECT.
2. NECK SIZE AS LISTED. FLEX SIZE SHALL MATCH NECK SIZE. PROVIDE FULL FACE LAY-IN MATCHING GRID DIMENSIONS.
3. GRILLE NECK SIZE AS LISTED. DUCTWORK SHALL BE FULL FACE.
4. DAMPERS SHALL BE INSTALLED IN DUCTWORK FOR ALL DIFFUSERS/GRILLES UNLESS OTHERWISE INDICATED.
5. PROVIDE WITH SERVICE ACCESS BOARDER TYPE.
6. SIZE GRILLE AS PER FLOOR PLAN.
AIR HANDLING UNIT SCHEDULE
EQUIPMENT
MARK
LOCATION /
SERVICE
UNIT AIRFLOW CHILLED WATER COOLING COIL* HOT WATER HEATING COIL SUPPLY FAN RETURN FAN
MANUFACTURER MODEL NOTESSUPPLY
AIR
(CFM)
OUTSIDE
AIR
(CFM)
TOTAL
COOLING
CAPACITY
(MBH)
SENSIBLE
COOLING
CAPACITY
(MBH)
ENTERING AIR
TEMPERATURE
(°Fdb - °Fwb)
LEAVING AIR
TEMPERATURE
(°Fdb - °Fwb)
COIL # ROWS / FINS
SPACING (# / FT) /
FACE VELOCITY
(FPM)
MINIMUM
FACE
AREA
(SQ. FT.)
CHILLED
WATER FLOW
(GPM)
ENTERING /
LEAVING WATER
TEMP
(°Fdb /°Fdb )
WATER
PRESSURE DROP
(FT FLUID)
MAXIMUM AIR
PRESSURE
DROP
(IN. WG)
HEATING
CAPACITY
(MBTUH)
ENTERING /
LEAVING AIR
TEMPERATURE
(°Fdb /°Fdb )
FLUID ENTERING /
LEAVING TEMP
(°Fdb /°Fdb )
COIL ROW / FACE
AREA (SQFT)/gpm
MAXIMUM AIR
PRESSURE
DROP
(FT. H2O)
EXTERNAL
STATIC
PRESSURE
(IN. WG)
TOTAL
STATIC
PRESSURE
(IN. WG)
FAN MOTOR
POWER, TOTAL
(HP)
EXTERNAL
STATIC
PRESSURE
(IN. WG)
TOTAL
STATIC
PRESSURE
(IN. WG)
FAN MOTOR
POWER,
TOTAL
(HP)
ELECTRICAL
V/PH/HZ
AHU-1A/AHU-1B HYBRID OR 4,880 4,880 401.42 195.96 91 / 78 55 / 54.9 6 / 123 / 397 11.81 66.7 44 / 55 4.9 0.68 126.0 39 /62.8 140 1 / 11.25 / 12.62 0.53 2 6.46 2 FANS X 5 2 2.77 5 460/3/60 TRANE CSAA012 1-11
* SELECT COOLING COILS WITH A MAXIMUM OF 12 FINS PER INCH AND MAXIMUM WATER PRESSURE DROP OF 10 FT.
NOTES: - SEE DRAWING M-500 FOR UNIT CONFIGURATION
1 PROVIDE MOTORIZED OUTSIDE AIR DAMPER INTEGRAL TO UNIT - THE TWO AIR HANDLERS ARE IN DUTY/ STAND-BY CONFIGURATION.
2 PROVIDE UNIT WITH HINGED ACCESS DOORS ON EACH SECTION AND BOTH SIDES OF UNIT (SCREWED ON PANELS NOT ACCEPTED). - AIR HANDLERS SHALL ONLY OPERATE AS 100% OA UNITS ON COMMAND (AS IN PANDEMIC MODE) AND SHALL RUN AS RECIRCULATING UNITS IN NORMAL MODE.
3 PROVIDE WITH SINGLE POINT POWER CONNECTION - PRE-FILTER 2" MERV 8, FILTERS 4" MERV 11, FINAL FILTERS (NORMAL MODE) MERV 14, (PANDEMIC MODE) MERV 16A - HEPA.
4 PROVIDE WITH 2 SETS OF FILTERS. AT PROJECT COMPLETION, INSTALL NEW FILTERS IN UNIT AND PROVIDE ONE EXTRA SET OF FILTERS FOR OWNER. UNITS SHALL NOT BE RUN WITHOUT SCHEDULED FILTERS IN PLACE. - PRESSURE DROP OF FILTERS AT MID LIFE ARE INCLUDED IN TOTAL S.P.
5 PROVIDE FACTORY MOUNTED MAGNAHELIC FILTER GAUGE ACROSS FILTER SECTION. - PROVIDE COPPER FINS FOR ALL COILS.
6 ALL MOTORS SHALL BE PREMIUM EFFICIENCY COMPATIBLE WITH VARIABLE FREQUENCY DRIVE OPERATION.
7 PROVIDE MODULATING 2-WAY ELECTRONIC CONTROL VALVE ON RETURN LINE FOR EACH HYDRONIC COIL.
8 COORDINATE INSTALLATION OF EQUIPMENT TO PROVIDE ACCESS FOR MAINTENANCE AND FILTER REPLACEMENT.
9 PROVIDE FIELD INSTALLED REMOTE VFD FOR SUPPLY AND RETURN FANS, WITH SOFT START, MANUAL BYPASS SWITCH, SURGE PROTECTION, AND FUSED DISCONNECT.
10 FOR ALL SYSTEMS WITH DESIGN SUPPLY AIR GREATER THAN 2000 CFM, INSTALL DUCT SMOKE DETECTOR IN SUPPLY AIR DUCT.
11 COORDINATE ALL COOLING WATER AND HOT WATER CONNECTIONS, COMPONENTS, REQUIREMENTS, AND EQUIPMENT INSTALLATION WITH PLANT UTILITY UPGRADES UNDER SEPARATE CONTRACT.
AIRFLOW CONTROL VALVE SCHEDULE
MARK AREA SERVING MANUFACTURER MODEL # MAX CFM MIN CFM INLET
SIZE
MAX PRESS.
DROP REMARKS
AFCV-1-1 OPERATING ROOM ACCUTROL AVC6000 505 450 8 0.2 1-3
AFCV-1-2 OPERATING ROOM ACCUTROL AVC6000 505 450 8 0.2 1-3
AFCV-1-3 OPERATING ROOM ACCUTROL AVC6000 505 450 8 0.2 1-3
AFCV-1-4 OPERATING ROOM ACCUTROL AVC6000 505 450 8 0.2 1-3
NOTES:
1. ALL AIRFLOW CONTROL VALVES SHALL BE PRESSURE INDEPENDENT.
2. INSTALL UNIT WITH CLEARANCE FOR ELECTRICAL AND MAINTENANCE ACCESS. PROVIDE ACCESS PANEL TO ACCESS CONTROL PANEL.
3. PROVIDE 24V INTEGRAL CONTROL PANEL.
23 JAN 2504/03/2024
| 672-CSI-124 Mechanical |
| MH000 MECHANICAL NOTES AND LEGENDS |
| MD100 MECHANICAL DEMOLITION PLAN - DUCTWORK |
| MD101 MECHANICAL DEMOLITION PLANS - PIPING |
| MH100 MECHANICAL RENOVATION PLAN - DUCTWORK |
| MH101 MECHANICAL AIR BALANCE PLAN |
| MH200 MECHANICAL PENTHOUSE PLAN - DUCTWORK |
| MP100 MECHANICAL RENOVATION PLAN - PIPING |
| MP200 MECHANICAL PENTHOUSE PLAN - PIPING |
| MH500 MECHANICAL DETAILS |
| MH501 MECHANICAL DETAILS |
| MH600 MECHANICAL SCHEDULES |
MH600 MECHANICAL SCHEDULES