Attachment 01 - Drawings Electrical 672-CSI-124 - Part V of VI - 15 Pages.pdf
PDF 13 MB Posted
- Attached to
- Z2DA--Construct New Hybrid Operating Room
- Solicitation number
- 36C24825R0026
About this file
This is an electrical drawings file for a construction project to build a new hybrid operating room at the VA Caribbean Healthcare System in San Juan, Puerto Rico. The 15-page set of electrical drawings, prepared by strollo & strollo architects and MES Group, Inc., provides comprehensive electrical design details including:
The drawings cover electrical demolition, lighting, power, telecommunications, auxiliary systems, conduit and raceway plans, and electrical schedules for various panels. Key electrical components include new electrical panels (1LXR, 1LX-OR-C, Hybrid-OR, IPP-1-C, IPP-2), transformer specifications, emergency power systems, and detailed wiring and circuit breaker configurations. The design focuses on supporting the hybrid operating room's complex electrical infrastructure, with specific attention to medical equipment power requirements, emergency lighting, isolated power systems, and compliance with electrical codes and VA healthcare facility standards.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
ELECTRICAL SYMBOLS AND
LEGENDS
E000
GENERAL PROJECT NOTES
1. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED
FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.
2. LIGHTING FIXTURES WITH MORE THAN TWO LAMPS SHALL HAVE TWO OUTER LAMPS
CONTROLLED WITH ONE SWITCH AND INNER LAMP(S) CONTROLLED BY A SECOND SWITCH.
3. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH
BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT
GROUNDING CONDUCTOR.
4. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND
NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.
5. ALL WORK SHALL CONFORM TO FEDERAL, STATE AND LOCAL LAWS, CODES AND
ORDINANCES.
6. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY.
7. THE CONTRACTOR SHALL SEISMICALLY BRACE ALL EXISTING AND NEW NON STRUCTURAL
ELEMENTS FALLING WITHIN RENOVATION “LIMITS OF CONSTRUCTION” AS REQUIRED BY
CODE. REFER TO SPECIFICATION SECTION 130541 (SEISMIC RESTRAINT REQUIREMENTS
FOR NON-STRUCTURAL COMPONENTS) FOR ADDITIONAL INSTRUCTIONS.
8. THE ELECTRICAL DRAWINGS ARE SCHEMATIC IN NATURE. BEFORE STARTING THE WORK
THE CONTRACTOR SHALL REVIEW ALL OTHER DISCIPLINE DRAWINGS AND VERIFY FIELD
CONDITIONS AND SHALL MAKE ANY REQUIRED MINOR ADJUSTMENTS WITHOUT EXTRA
COST TO THE VA. ANY MAJOR DISCREPANCIES FOUND SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT/ENGINEER.
RECEPTACLE, DUPLEX (18" AFF)
RECEPTACLE, QUADRAPLEX (18" AFF)
ELECTRICAL POWER SYMBOLS LEGEND
(MOUNTING HEIGHT TO CENTER LINE OF BOX UNLESS NOTED OTHERWISE)
PANELBOARD, SURFACE MOUNTED
TRANSFORMER
MOTOR, SINGLE - PHASE, HORSE POWER AS NOTED
DISCONNECT SWITCH - FUSED - FRAME/FUSE/POLES/NEMA
AS NOTED ON PLANS, ALL DISCONNECTS SHALL BE HEAVY
DUTY AND NEMA TYPE 1 U.O.N.
DISCONNECT SWITCH - MOTOR/STARTER COMBINATION
NEMA SIZE TO MATCH HP SHOWN ON PLANS AT THE
SPECIFIED VOLTAGE, HEAVY DUTY
JUNCTION BOX OR PULL BOX - SINGLE GANG U.O.N.
SM
30/15/2/3R
DISCONNECT SWITCH - NON-FUSED -
FRAME/FUSE/POLES/NEMA AS NOTED ON PLANS, ALL
DISCONNECTS SHALL BE HEAVY DUTY AND NEMA TYPE 1
U.O.N.
30/2/3R
MANUAL MOTOR STARTING SWITCH
J
COMMUNICATION SYMBOLS LEGEND
OUTLET, COMBINATION TELEPHONE/DATA COMMUNICATION
(18" AFF)
COMMUNICATION CABLE TRAY MOUNTED ABOVE
SUSPENDED CEILING - SIZE AS NOTED ON PLANS
8" CEILING MOUNTED PAGING SPEAKER; PROVIDED WITH
BAFFLE, GRILL AND MATCHING TRANSFORMER
(MOUNTING HEIGHT TO CENTER LINE OF BOX UNLESS NOTED OTHERWISE)
S
CONDUIT AND WIRING
2A-1,3,5
BRANCH CIRCUIT RUN CONCEALED
BRANCH CIRCUIT RUN UNDER FLOOR
BRANCH CIRCUIT DOWN
BRANCH CIRCUIT UP
HOME RUN TO PANEL 2A SPACES 1, 3, & 5, REFER TO PANEL
SCHEDULES
LINE TYPES
NEW WORK SCOPE OF WORK
EXISTING SCOPE OF WORK
DEMOLITION SCOPE OF WORK
FUTURE SCOPE OF WORK
GENERAL SYMBOLS
KEY NOTE INDICATOR
DRAWING REVISION INDICATORX
X X X X
NURSE CALL STATION.
D = DUTY STATION. MTD 5'-0" AFF UON
U = UTILITY CALL STATION, MTD 5'-0" AFF UON
C = CODE BLUE
T = TOILET
NURSE CALL SYMBOLS LEGEND
N
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED
CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR AVAILABLE
FAULT CURRENT
AFCI ARC-FAULT CURRENT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
Ah AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BD BOARD
BFF BELOW FINISH FLOOR
BLDG BUILDING
BRKR BREAKER
BYP BY PASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR
INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
OR C/B
CLF CURRENT LIMITING FUSE
CLG CEILING
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CUR CURRENT
dB DECIBEL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR PNL DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST OR EXISTING
(E)
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FIXT FIXTURE
FLA FULL LOAD AMPS
FLUOR FLUORESCENT
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G ELECTRICAL GROUND
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IESNA ILLUMINATION ENGINEERING SOCIETY OF
NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAh KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWh KILOWATT HOUR kWhM KILOWATT HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NEUT OR N NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PB PULL BOX
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
RM ROOM
RMS ROOT MEAN SQUARE
REQD REQUIRED
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TEL TELEPHONE
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
ELECTRICAL ABBREVIATIONS
ECB ENCLOSED CIRCUIT BREAKER
ST SHUNT TRIP
RSAP REMOTE STATUS ALARM PANEL
ERB EQUI-POTENTIAL REFERENCE BAR
GBB GROUND BUS BAR
LIGHT FIXTURE, RECESSED (2'X4') - LETTER INDICATES TYPE.
LIGHT FIXTURE, RECESSED, EMERGENCY - LETTER
INDICATES TYPE.
2X2 FIXTURE - RECESSED, SURFACE, OR PENDANT
MOUNTED - LETTER INDICATES TYPE.
2X2 CRITICAL BRANCH FIXTURE - RECESSED, SURFACE, OR
PENDANT MOUNTED - LETTER INDICATES TYPE.
1X4 FIXTURE - RECESSED, SURFACE, OR PENDANT
MOUNTED - LETTER INDICATES TYPE.
1X4 CRITICAL BRANCH FIXTURE - RECESSED, SURFACE, OR
PENDANT MOUNTED - LETTER INDICATES TYPE.
EXIT SIGN-CEILING MOUNTED - TYPE AS SPECIFIED,
ARROWS AS SHOWN ON PLANS
CEILING MOUNTED VACANCY SENSOR;
DUAL TECHNOLOGY
(PASSIVE INFRARED/ULTRASONIC)
S
VS
A
A
B
B
C
C
SWITCH (# SUBSCRIPT AS INDICATED BELOW):
BLANK = SINGLE POLE 2 = DOUBLE POLE
3 = THREE-WAY 4 = FOUR-WAY
D = DIMMER K = KEY OPERATED
LV= LOW VOLTAGE P = WITH PILOT LIGHT
LM= LOW VOLTAGE MASTER RC= REMOTE CONTROL
PB= PUSH BUTTON STATION WP= WEATHER PROOF
T = TIMER OPERATED Mo= OCCUPANCY SENSOR
ELECTRICAL LIGHTING SYMBOLS LEGEND
(REFER TO LIGHTING FIXTURE SCHEDULE FOR MORE INFORMATION)
6" RECESSED DOWNLIGHT FIXTURE - LETTER INDICATES
TYPE.
6" RECESSED DOWNLIGHT FIXTURE - CRITICAL BRANCH
FIXTURE - LETTER INDICATES TYPE.
D
D
CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:
M = MOUNT
W - WALL
T = TECHNOLOGY / TYPE
M - MAG STRIP
M
T
RECEPTACLE, DUPLEX ON EMERGENCY POWER (18" AFF)
HP
D
N
D NURSE CALL STATION.
D = CORRIDOR DOME LIGHT
SAFETY AND SECURITY SYMBOLS LEGEND
(MOUNTING HEIGHT TO CENTER LINE OF BOX UNLESS NOTED OTHERWISE)
T
M T
ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:
M = MOUNT
W - WALL
T = TECHNOLOGY / TYPE
H - HYBRID L- LATCH SET M - MAGNETIC S - STRIKE
T
EXIT DEVICE; LETTER INDICATES AS FOLLOWS:
T = TECHNOLOGY / TYPE
D - DELAYED EGRESS E - ELECTRIFIED M - MECHANICAL
X - HIGH SECURITY
M T
INTERCOM ; LETTER INDICATES AS FOLLOWS:
M = MOUNT
W - WALL
T = TECHNOLOGY / TYPE
M - MASTER S - SUBSTATION
M T
PUSH BUTTON ; LETTER INDICATES AS FOLLOWS:
M = MOUNT
W - WALL
T = TECHNOLOGY / TYPE
B - BELL PUSH D - DURESS P - PANIC
R - DOOR RELEASE X - REQUEST TO EXIT
PTZ
SECURITY ACCESS, VIDEO CAMERA WITH LENS
M = MOTION DETECTOR
PZ = MOTION DETECTOR WITH PAN AND ZOOM
PTZ = MOTION DETECTOR WITH PAN, TILT, AND ZOOM
CEILING RECEPTACLE, DUPLEX
RECEPTACLE, QUADRAPLEX ON EMERGENCY POWER (18"
AFF)
RELAY LIGHTING RELAY - 110V OR 24V
RC# ELCU#
ROOM CONTROLLER
EMERGENCY ROOM CONTROLLER
EXIT SIGN-WALL MOUNTED - TYPE AS SPECIFIED, ARROWS
AS SHOWN ON PLANS
LIGHT FIXTURE - WALL MOUNT - LETTER INDICATES TYPE.
RECEPTACLE, SIMPLEX
RECEPTACLE, SPECIALTY
CEILING MOUNTED PASSIVE INFRARED SENSOR;
PROVIDED BY CONTRACTOR
(PASSIVE INFRARED/ULTRASONIC)
PIR
Sheet List Table Sheet Number Sheet Title
E000 ELECTRICAL SYMBOLS AND LEGENDS
ED100 ELECTRICAL DEMOLITION PLAN
EL100 ELECTRICAL LIGHTING PLAN
EP100 ELECTRICAL POWER PLAN
EP101 ELECTRICAL CONDUIT AND RACEWAY PLAN
EP200 ELECTRICAL PENTHOUSE PLAN
ET100 ELECTRICAL TELECOMMUNICATIONS PLAN
EY100 ELECTRICAL AUXILIARY SYSTEMS PLAN
E500 BASIS OF DESIGN DETAILS
E501 BASIS OF DESIGN DETAILS
E502 BASIS OF DESIGN DETAILS
E503 BASIS OF DESIGN DETAILS
E504 ELECTRICAL DETAILS
E600 ELECTRICAL ONE-LINE DIAGRAM
E700 ELECTRICAL SCHEDULES
04/03/2024
WAITING AREA
CONTROL
ROOM CLOSET
FILES
RADIOGRAPHIC
RAD. SUPERVISOR
C O R R I D O R
OFFICE
BUDGET
A-160
CARDIAC.
ROOM
A-158
OFFICE
A-159
PHYSICS
MEDICAL
A-158
ROOM
CONTROL
A-172b
TOILET
LOUNGE STAFF RM.
A-
2a
LO
C
K R
M
A-172
A-173
ECOCARDIO-
GRAPHY RM.
B-117 B-115
B-114
B-109
C O
R R
I D
O R
MALE LOCKERS
SIGNAL
CLOS. FEMALE LOCKERS
PHYSICIAN'S
LOCKERS
C O R R I D O R C1-8
S
S
CONTROLS
S C
C
WAP
WAP
S S
S
S
CONTROL
CYSTOSCOPY ROOM
ROOM
A-164
STORAGE
CLERICAL
AREA
STORAGE
TOILET
EXAM
ROOM
A-173
CYSTOSCOPY ROOM
A-167
A-171
EXAM
ROOM
A-172
EXAM
ROOM
S C
S S
WAP
S
S C
S
J
CONTROLS
S
S
N
J
S C
J
X-RAY RCPT
WAP
J
S
CONTROLS
S
J
CONTROLS
J
J
J
MINI SPLIT
J
MINI SPLIT
PANEL
1LA1C
(E)
ELECTRICAL CLOSET
B-117a
1HX(1)(E) 1HX(2)(E)
1LX-OR-A (E)
1LX-OR-B (E)
1LX-OR-C
(DEMO)
SUPERVISOR OFFICE
A-168
S
S
TECHNICAL PROCEDURES
A-168
S
J
J
S
CONTROLS
J
WAP
EXAM ROOM
A-170
EXAM ROOM
A-169
J
J
CONTROLS
J J
J J J
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
(TYP)
S
T
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
ELECTRICAL DEMOLITION PLAN - FIRST FLOOR
1/4" = 1'-0"
ED100
ELECTRICAL DEMOLITION
PLAN
ED100
GENERAL NOTES - DEMOLITION
KEYNOTES
1. ELECTRICAL PANEL '1LA1C' IS EXISTING TO REMAIN. DISCONNECT ALL
ASSOCIATED CIRCUITS CURRENTLY FEEDING DEVICES AND EQUIPMENT
FROM AREA IN SCOPE OF WORK AND LABEL AS "SPARE".
2. EXISTING PANEL '1LX-OR-C' IS OUTDATED AND SHALL BE REPLACED
WITH NEW ELECTRICAL PANEL TO COMPLY WITH CURRENT CODES.
3. TYPICAL FOR ALL ROOMS - DEMOLISH ALL ELECTRICAL EQUIPMENT,
FIRE ALARM DEVICES, RECEPTACLES, DATA DEVICES, JUNCTION
BOXES, ETC. AND ASSOCIATED WIRING AND CONDUIT BACK TO THE
SOURCE, UNLESS OTHERWISE NOTED. ALL DEMOLISHED EQUIPMENT
AND DEVICES SHALL BE RETURNED TO THE VA.
4. TYPICAL FOR ALL ROOMS - LIGHTING FIXTURES AND EXIT SIGNS SHALL
BE DEMOLISHED AND RETURNED TO THE VA. ELECTRICAL CIRCUITS
FROM PANEL '1HA1' (ELECTRICAL CLOSET A-133-X) CURRENTLY
FEEDING NORMAL LIGHTING SHALL REMAIN FOR CONNECTION OF NEW
LIGHTING FIXTURES. EMERGENCY FIXTURES' CONDUIT AND WIRING
SHALL BE DEMOLISHED BACK TO THE SOURCE AND LABELED AS
"SPARE" IN PANEL (IF APPLICABLE). NEW EMERGENCY FIXTURES SHALL
BE CONNECTED TO EMERGENCY PANEL '1HX(2)' IN ELECTRICAL CLOSET
B-117a.
5. FOR ALL WAP DEVICES IN SCOPE OF PROJECT, THE CONTRACTOR
SHALL CAREFULLY REMOVE, INVENTORY, STORE AND PRESENT TO THE
VA FOR FIRST RIGHT OF REFUSAL.
A. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING
DEVICES, CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED,
COMPLETELY CUT/CAP CONDUITS AT THE AREA OF WORK PERIMETER
AND REMOVE CONDUIT AND REMOVE CONDUIT WITHIN THE WORK AREA,
DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND
REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS FROM
THE SOURCE POINT CONNECTION.
B. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE
OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL
ABANDONED WIRING..
C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND
CONDUCTORS PASSING THRU RENOVATED AREAS AND SERVICING
UNDISTURBED AREAS.
D. PRIOR TO REMOVAL OF EXISTING FIRE ALARM DEVICES, THE FIRE ALARM
CONTRACTOR SHALL VERIFY AND PERFORM TESTING OF THE EXISTING
FIRE ALARM SYSTEM TO ENSURE IT IS COMPLETELY OPERATIONAL AND
FUNCTIONAL OF ALL FIRE ALARM COMPONENTS/DEVICES WITHIN THE
AREA BEFORE MAKING CHANGES OR CONNECTIONS. THIS IS NOT
REQUIRED IF THE SYSTEM IS BEING MAINTAINED BY A CONTRACTOR BY
THE VA.
E. CONTRACTOR SHALL IDENTIFY ALL EXISTING FIRE ALARM DEVICES IN
AREA OF WORK. ALL FIRE ALARM DEVICES UNDER THE SCOPE OF THIS
PROJECT SHALL BE CAREFULLY REMOVED, INVENTORIED, STORED, AND
HANDED OVER TO THE VA AS SPARE PARTS.
F. CONTRACTOR SHALL IDENTIFY ALL EXISTING WAP DEVICES IN AREA OF
WORK. ALL WAP DEVICES UNDER THE SCOPE OF THIS PROJECT SHALL
BE CAREFULLY REMOVED, INVENTORIED, STORED AND PRESENTED TO
THE VA FOR FIRST RIGHT OF REFUSAL.
F. CONTRACTOR SHALL IDENTIFY NURSE CALL IN AREA OF WORK. ALL
NURSE CALL DEVICES UNDER THE SCOPE OF THIS PROJECT SHALL BE
CAREFULLY REMOVED, INVENTORIED, STORED AND PRESENTED TO THE
VA FOR FIRST RIGHT OF REFUSAL.
8.8
9.8
CBA
2.3
2.3
2.3
3.0 3.0
3.0 3.0
3.0 3.0
3.0 3.0
3.0 3.0
3.0 3.0
2.3
2.3
3.0 3.0
3.0 3.0
3.03.0 3.0
3.0
3.0 3.0
3.0 3.0
2.3
2.3
2.3
2.3
2.3
3.0 3.0
3.0 3.0
2.3
2.3
2.3
2.3
2.3
PIR
PIR PIR
PIR
VS
VS
VS
VS
VS
VS
TREATMENT
PLANNING
COMPUTER
WAITING AREA
CONTROL
ROOM
CLOSET
FILES
264.96n.s.f.
RADIOGRAPHIC
ROOM 1
A-140 104.56n.s.f.
A-
8a
ST
O
31.41n.s.f.
H.A.C.
A-171
B-117 B-115
ELEC.
CLOS.
MALE LOCKERS CLOS. FEMALE LOCKERS
25.58n.s.f.
25.75n.s.f.
152.44n.s.f.122.11n.s.f.
DN.DN.
C O R R I D O R C1-8
FX
C CE
BE B B
A1
HYBRID
OPERATING
ROOM
CONTROL
ROOM
SCRUB STN.
IMAGING
COMPONENT
ROOM
STERILE
SUPPLY
GURNEY
X
SD SD
RC1
RC2
ELCU
VS
SD
S S b
RC1
RC2
ELCU
S D S D c c b bbc d e f g f g
RC1
RC2
ELCUVS
VS
VS
SDSD
hk h k k h,k h,k d,e b,c
VS
b,c
1HX(2) - 08
J
S D
J
(TYPICAL)
(TYPICAL)
X
J
SD
A1E c
A1 b
A1 b d e e c b
VS
h,k
AE
e
A d
S 3 S 3 k h
AE
e
AE
e
AE
h
AE
h
AE
h
A k
A k
A k
J
RELAY
IPP-1-C-14
J
1HX(2)-20
1HX(2)-18
(TYPICAL)
J J
A d
SD
b,c
SD
HYBRID OR-3
J
'MA'
RELAY
(TYPICAL)
(TYPICAL)
(TYPICAL)
(TYPICAL)
(TYPICAL)
NO WORK IN THIS ROOM
NO WORK IN THIS
ROOM
NO WORK IN THIS
ROOM
(TYPICAL)
FIRST FLOOR PLAN - RENO. - LIGHTING
1/4" = 1'-0"
EL100
ELECTRICAL LIGHTING PLAN
EL100
GENERAL NOTES
A. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC/SCHEMATIC IN NATURE AND
REPRESENT THE GENERAL SCOPE OF WORK. IT IS NOT WITHIN THE
SCOPE OF THE ELECTRICAL DRAWINGS TO SHOW ALL NECESSARY
RACEWAY ROUTING, BENDS, OFFSET, PULL BOXES AND OBSTRUCTIONS.
CONTRACTOR SHALL COORDINATE THE FINAL LOCATION OF EQUIPMENT
FOR PROPER OPERATION IN ACCORDANCE WITH CODE, OWNER, AND
MANUFACTURER RECOMMENDATIONS.
B. CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFICATION OF ALL
RATED WALLS, CEILINGS AND SLABS AND THEIR SPECIFIED RATING ON
THE ARCHITECTURAL DRAWINGS. ALL DEVICES AND MATERIALS SHALL
MEET THE UL RATING OF THE RATED WALLS, CEILINGS AND SLABS
ASSEMBLY. CONTRACTOR SHALL PROVIDE AN ASSEMBLY INSTALLED IN
ACCORDANCE WITH THE RATED APPLICATION.
C. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD
OBSERVATION. ELECTRICAL CONTRACTOR SHALL REPORT
DISCREPANCIES TO ENGINEER PRIOR TO DISTURBING EXISTING
INSTALLATION.
D. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH OTHER TRADES AS
REQUIRED TO KEEP THE PROJECT PROGRESSING.
E. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND
CONDUCTORS PASSING THROUGH AREAS AND SERVICING UNDISTURBED
AREAS.
F. LIGHTING FIXTURES CONNECTED TO THE EMERGENCY CIRCUITS AND
EXIT SIGNS SHALL HAVE A 24/7 OPERATION.
G. DO NOT INSTALL CEILING SENSORS WITHIN 48" OF AIR DIFFUSERS OR
SIMILAR OBSTRUCTION THAT MAY ADVERSELY AFFECT THE SENSOR'S
PERFORMANCE. COORDINATE FINAL LOCATION OF SENSORS WITH
OTHER TRADES AND INSTALL IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS.
H. ALL JUNCTION BOXES SHALL BE RIGIDLY ATTACHED TO STRUCTURE OR
MILLWORK.
I. ALL LIGHTING CONTROLS SHALL BE IN ACCORDANCE WITH THE VA
LIGHTING DESIGN MANUAL.
J. PROVIDE DUAL TECHNOLOGY OCCUPANCY/VACANCY SENSORS FOR
AUTOMATIC LIGHTING CONTROL IN EQUIPMENT ROOM AND
MAINTENANCE SPACES.
K. LIGHTING CONTROLS CONTRACTOR SHALL PROVIDE CONTROLS AND
SENSORS WITH APPROPRIATE COVERAGE PATTERNS, AND
ADJUSTMENTS OF SENSITIVITY LEVELS TO PREVENT NUANCE
SWITCHING ON AND OFF OF LIGHTS.
L. THE CONTROL SYSTEMS SHALL BE A STAND ALONE, NON NETWORKED
SYSTEM FOLLOWING THE BASIS OF DESIGN, OR O/A/E APPROVED EQUAL.
M. PROVIDE TEMPORARY AND/OR MODIFY EXISTING LIGHTING AND POWER,
AND RELATED SERVICES AS REQUIRED FOR CONSTRUCTION-PERIOD’S
INTERIM LIFE SAFETY MEASURES.
KEYNOTES
1. PROVIDE JUNCTION BOX/ES AS REQUIRED PER MANUFACTURER'S
SPECIFICATIONS.
2. EACH LUMINAIRE ABOVE THE SURGERY TABLE SHALL BE POWERED
THROUGH THE BATTERY INVERTER SYSTEM.
3. MODULAR CEILING DIFFUSER SYSTEM INTEGRATED LIGHTING SYSTEM.
COORDINATE ELECTRICAL CONNECTIONS WITH SYSTEM MANUFACTURER.
INSTALL PER MANUFACTURER'S REQUIREMENTS. SEE ARCHITECTURAL
SHEETS FOR ADDITIONAL INFORMATION.
4. CONTRACTOR SHALL COORDINATE WITH EQUIPMENT MANUFACTURER FOR
CONNECTION OF X-RAY IN-USE LIGHT, EXAM ROOM LIGHTS AND DOOR
SWITCH.
5. CONTRACTOR SHALL SUPPLY AND LOCATE 110V RELAY BOX IN CEILING
SPACE AWAY FROM IMAGING HYBRID OR EQUIPMENT AND CONNECT TO
LOCAL LIGHTING CONTROL. CONTRACTOR SHALL PROVIDE SWITCH LEGS
TO EQUIPMENT AS SPECIFIED BY MANUFACTURER.
6. 20A SPARE NORMAL BRANCH LIGHTING CIRCUIT FROM PANEL '1HA1'
(ELECTRICAL CLOSET A-133-X) CREATED FROM DEMOLITION TO BE REUSED
AND LISTED ON EXISTING PANEL SCHEDULE.
7. VERIFY LOCATION OF POINT OF CONNECTION TO INTEGRATED LIGHTING
SYSTEM. DRIVER BOX REQUIRES A SINGLE POWER CONNECTION AND
SINGLE DIMMING CONTROL CONNECTION.
8. EMERGENCY BATTERY INVERTER. REFER TO EP100 FOR ADDITIONAL
POWER INFORMATION.
9. JUNCTION BOX WITH BLANK COVER FOR SURGICAL LIGHT MOUNTING
PLATE. COORDINATE EXACT LOCATION WITH CEILING MODULAR SYSTEM
AND HYBRID OR EQUIPMENT PRIOR TO ROUGH-IN.
10. MOUNT LIGHTING CONTROLLER AT 60" AFF. VERIFY LOCATION WITH VA
AND CEILING MODULAR SYSTEM VENDOR PRIOR TO ROUGH-IN.
11. REFER TO THE SUPPLEMENTARY PHOTOMETRIC DESIGN DRAWINGS
REFLECTING PROPOSED ILLUMINATION LEVELS AND DISTRIBUTION
ATTRIBUTES.
12. REFER TO THE OR MODULAR CEILING DIFFUSER INTEGRATED LIGHTING
SYSTEM FOR PROPOSED PHOTOMETRIC PLAN FOR FIXTURE TYPE AND
DESCRIPTION.
13. PASSIVE INFRARED DEVICES SUPPLIED AND LOCATED BY MANUFACTURER.
14. BOOM LOCATIONS AND QUANTITIES ARE SUBJECT TO CHANGE PER VA
FINAL SELECTION. REFER TO SHEET EP100 FOR ADDITIONAL INFORMATION.
MODULAR CEILING DIFFUSER INTEGRATED
BASIS OF DESIGN OF THE PROPOSED OR LAYOUT PROVIDED BY SLD. CONTRACTOR SHALL PROVIDE REVISED PHOTOMETRIC PLAN AS A PART OF THE OR ROOM LIGHTING SUBMITTAL. FIXTURES SHOWN TO SCALE FOR CLARITY PURPOSES.
8.8
9.8
CBA
LIGHTING CONTROL NOTES
A. CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFICATION OF ALL
RATED WALLS, CEILINGS, SLABS, AND THEIR SPECIFIED RATING ON THE
ARCHITECTURAL DRAWINGS. ALL DEVICES AND MATERIALS SHALL MEET
THE UL RATING OF THE RATED WALLS, CEILINGS AND SLABS ASSEMBLY.
CONTRACTOR SHALL PROVIDE AN ASSEMBLY, INSTALLED IN
ACCORDANCE WITH UL WHERE NECESSARY.
B. CONTRACTOR SHALL COORDINATE ANY WALL MOUNTED LIGHT FIXTURE
WITH ARCHITECT AND OWNER PRIOR TO INSTALLATION.
C. ALL OCCUPANCY SENSOR CONTROLLED LOADS SHALL TURN OFF WITHIN
20 MINUTES OF THE OCCUPANT LEAVING THE ROOM.
D. WHERE MULTIPLE SWITCHES ARE SHOWN AT THE SAME LOCATION, THEY
SHALL BE GANGED TOGETHER WITH A COMMON GANG PLATE.
E. ALL EXIT LIGHTS AND EMERGENCY BATTERY PACKS SHALL BE
CONNECTED TO UNSWITCHED LEG OF THE LOCAL LIGHTING BRANCH
CIRCUIT.
F. ALL LIGHTING CONTROLS SHALL BE IN ACCORDANCE WITH 2018 PUERTO
RICO BUILDING CODE, ENERGY CONSERVATION.
G. PROVIDE DUAL TECH OCCUPANCY/VACANCY SENSORS IN ALL OFFICES,
CORRIDORS, OPEN OFFICES, LOUNGES/BREAKROOMS, RESTROOMS,
STORAGE ROOMS, AND ALL OTHER SPACES 300 SQUARE FEET OR LESS
ENCLOSED BY FLOOR TO CEILING HEIGHT PARTITIONS. THIS EXCLUDES
MECHANICAL ROOMS, ELECTRICAL ROOMS, TELECOMMUNICATION
SPACES, AND OTHER AREA WHERE THE AUTOMATIC SHUT OFF OF
LIGHTS WILL CAUSE A DANGER TO LIFE SAFETY.
H. WHERE VACANCY SENSORS ARE REQUIRED, LIGHTS SHALL BE MANUAL
ON, AUTOMATIC OFF. LIGHTS SHALL TURN OFF AUTOMATICALLY WITHIN
20 MINUTES OF THE SPACE BECOMING VACANT.
I. WHERE OCCUPANCY SENSORS ARE REQUIRED, LIGHTS SHALL TURN ON
TO FULL AUTOMATICALLY, TURN OFF AUTOMATICALLY WITHIN 20
MINUTES OF THE SPACE BECOMING UNOCCUPIED, AND SHALL HAVE A
SWITCH FOR MANUAL OVERRIDE.
J. CONTRACTOR SHALL PROVIDE QUANTITY OF SENSORS REQUIRED WITH
PROPER COVERAGE PATTERN TO ACHIEVE REQUIRED LIGHTING
CONTROL WITHIN THE SPACE.
K. CONTRACTOR SHALL PROVIDE SHOP DRAWINGS FROM THE CONTROLS
MANUFACTURER'S REPRESENTATIVE SHOWING LAYOUT, QUANTITY,
COVERAGE PATTERNS, AND WIRING DIAGRAM OF COMPLETE SYSTEM.
L. FOR CLARITY, ONLY VACANCY (VS) OR OCCUPANCY (OC) ARE SHOWN IN
SPACES REQUIRING THAT MODE OF CONTROL.
M. PROVIDE LOW VOLTAGE OVERRIDE DIMMING SWITCHES IN ALL SPACES
REQUIRING VACANCY/OCCUPANCY SENSORS WITH CONTROL FUNCTION
AS OUTLINED.
N. PROVIDE ROOM CONTROLLERS AS REQUIRED TO INTERFACE ALL
LIGHTS, SWITCHES, SENSORS, ETC. IN ALL SPACES SHOWN TO RECEIVE
AUTOMATIC LIGHTING CONTROLS.
O. EXTERIOR LIGHTING SHALL BE CONTROLLED BY PHOTOCELL ON/TIME
CLOCK OFF. PROVIDE TIME CLOCK FOR CONTROLS. COORDINATE TIME
OF DAY SCHEDULING WITH STATION REPRESENTATIVE.
P. LIGHTING CONTROL SYSTEM SHALL BE A STAND ALONE
NON-NETWORKED SYSTEM AS MANUFACTURED BY ACUITY. ALTERNATE
APPROVED MANUFACTURERS ARE GREENGATE, WATTSTOPPER, AND
HUBBELL.
D
E
F
G
LIGHTING SYSTEM
D
D
D
D D
D
D
D
DD
E
E
E
E
G
G
F
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304 04/03/2024
ROOM
CLOSET
FILES
RADIOGRAPHIC
C O R R I D O R
OFFICE
BUDGET
A-160
CARDIAC.
ROOM
A-158
OFFICE
A-159
PHYSICS
MEDICAL
A-158
ROOM
CONTROL
A-
8a
ST
O
H.A.C.
A-171
A-172b
TOILET
A-172 ECOCARDIO-
GRAPHY RM.
B-117 B-115
B-114
LOUNGE STAFF RM.
A-172a
LOCK RM.
ELEC.
CLOS.
MALE LOCKERS
SIGNAL
CLOS. FEMALE LOCKERS
PHYSICIAN'S
LOCKERS
DN.DN.
C O R R I D O R C1-8
NO WORK IN THIS ROOM
NO WORK IN
THIS ROOM
NO WORK
IN THIS
ROOM
PANEL
1LA1C
(E)
ELECTRICAL CLOSET
B-117a
1HX(1)(E) 1HX(2)(E)
1LX-OR-A (E)
1LX-OR-B (E)
1LX-OR-C
(NEW)
CONTROL
ROOM
SCRUB STN.
IMAGING
COMPONENT
ROOM
STERILE
SUPPLY
GURNEY
GFCI
EPO
EPO
2 (TYP)
J
J
J
PANEL
1PP-1
IPP-1-1
IPP-1-3
IPP-1-5
IPP-1-7
1LXR-1
1LXR-3
1LXR-5
1LXR-C-24
1LXR-2
1LXR-4
IPP-2-6
IPP-2-5
IPP-2-4IPP-2-3
IPP-2-2
IPP-2-1
(TYPICAL)
PANEL
1PP-2
J
J
IPP-1-C-12
J
1LXR-7
1LXR-6
1LXR-8
IPP-1-4
IPP-1-2
IPP-1-6IPP-1-8
HYBRID
OPERATING
ROOM
GURNEY
PANEL
HYBRID-OR
(NEW)
PANEL
1LXR
(NEW)
XFMR
1LXR
(NEW)
XFMR
PAD
J
1LXR-OR
-C-25
1LXR-OR-C-26
1LXR-OR-C-27
1LXR-OR-C-29
J
1LXR-OR-C-22
+44"
1LXR-9
+44"
J
J
J
J
J
1LX-OR-C-28
J
1LX-OR-C-28
J
1LX-OR-C-28
J
UPS
150A
ECB/ST
80A
ECB
RASP
GBB
ERB
J
SM
IPP-1-C-9
IPP-1-C-10
IPP-1-C-11
J
IPP-2-7
IPP-2-8
15IPP-2-10 SM
15IPP-2-12 SM
HYBRID-OR-1
J
XFC
IPP-1-C-14
J
1LX-OR-C-28
J J
1HX(2)-20
1HX(2)-18
1 9
1 9
RIC
HYBRID-OR-2
HYBRID-OR-4
HYBRID-OR-3
J
J 1 9
ATU-1-2
ATU-1-3
ATU-1-4
ATU-1-1
ATU-1-5
ATU-1-6
J
J
1-LX-OR-C-6
SM
SM
J
SM
J
SM
J
SM
J
SM
JSM
AFCV
AFCV
AFCV
AFCV
J SM
JSM
J
SM
J J J
J J
1LXR-OR-C-30
1LXR-OR-C-31
(TYP)
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
ELECTRICAL POWER PLAN - FIRST FLOOR
1/4" = 1'-0"
EP100
ELECTRICAL POWER PLAN
EP100
GENERAL NOTES
A. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD
OBSERVATION. NOTIFY ENGINEER OF ANY DISCREPANCIES BETWEEN
THESE DRAWINGS AND EXISTING CONDITIONS PRIOR TO DISTURBING
EXISTING INSTALLATION.
B. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A
MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE
REQUIREMENTS WITH THE VA/COR.
C. ELECTRICAL POWER SERVICES PASSING THROUGH CONSTRUCTION
AREA SHALL BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD.
D. ALL CIRCUITS SERVING AREAS ADJACENT TO THE CONSTRUCTION AREA
THAT ARE MODIFIED, AS PART OF THE CONSTRUCTION PROJECT, SHALL
BE RE-CIRCUITED AS PART OF THE CONSTRUCTION PROJECT.
E. REFER TO SHEEP EP101 FOR MINIMUM RECOMMENDED CONDUIT SIZE
AND ADDITIONAL INFORMATION.
KEYNOTES
1. FOR THE PROPOSED BOOMS (PROVIDED BY OTHERS), PROVIDE
JUNCTION BOX AS REQUIRED PER MANUFACTURER'S SPECIFICATIONS
AND AS REQUIRED BY THE NEC. RUN POWER FROM THE PANEL TO
JUNCTION BOX AND LEAVE ELECTRICAL PROVISION PROTECTED WITH
WIRE NOTES. PROVIDE BLANK PLATE TO JUNCTION BOX. REFER TO
MODULAR CEILING DIFFUSER SYSTEM SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
2. REFER TO SHEETS E500 - E504 FOR DETAILS AND LEGEND OF
EQUIPMENT. INFORMATION PROVIDED AS A BASIS OF DESIGN ONLY.
FINAL MANUFACTURER HAS NET BEING FINALIZED YET, ADDITIONAL ITEM
MIGHT BE REQUIRED AND SHALL BE PROVIDED AS A DESIGN ADDENDUM,
AND SHALL BE INCLUDED IN PROJECT BID.
3. RECEPTACLES SHALL BE HOSPITAL GRADE. TYPICAL FOR ALL
RECEPTACLES IN THE HYBRID OPERATION ROOM AREA.
4. NEW RECESSED ISOLATED PANEL SOURSE PANEL. PANEL SHALL
INCLUDE AN INTEGRATED 7.5 KVA, 208V PRIMARY, 120V SECONDARY
TRANSFORMER. PANEL SHALL INCLUDE LINE ISOLATION MONITORING
AND AN INTEGRATED POWER MODULE WITH 4 DUPLEX RECEPTACLES
AND 4 GROUND RECEPTACLES. BREAKERS 2 AND 4 SHALL BE USED TO
POWER THE RECEPTACLES OF THE POWER MODULE. COORDINATE
INSTALLATION WITH EXISTING UTILITIES IN THE AREA.
5. ALL WIRING WITHIN THE ISOLATED POWER SYSTEM SHALL BE TYPE
XHHW OR XHHW-2. NO WIRE-PULLING COMPOUND SHALL BE USED TO
INSTALL WIRES IN THE ISOLATED POWER SYSTEM.
6. PROVIDE 120V/5A SWITCH LIMITED TO OPEN WHEN DOOR IS OPEN FOR
DOOR SWITCH. CONTRACTOR TO VERIFY MANUFACTURER'S IMAGING
EQUIPMENT AUXILIARY BOX CONNECTION ALLOCATION. REFER TO DOOR
SWITCH DIAGRAM DETAIL ON SHEET E503 FOR ADDITIONAL
INFORMATION.
7. IPS POWER MODULE: 4 DUPLEX AND 4 GROUND RECEPTACLES. 2
BRANCH CIRCUITS SHALL BE ROUTED TO EACH MODULE, 2 DUPLEX
RECEPTACLES PER CIRCUIT. SEE DETAILS FOR MORE INFORMATION.
PROVIDE ISOLATED GROUND. E.G. SHALL BE TIED TO MAIN BUILDING
GROUND BUS BAR WITH MINIMUM #8 CU G.E.C
8. NEW AHU SHALL HAVE INTEGRATED DISCONNECT MEANS. UNIT SHALL BE
ISSUED WITH A SINGLE POWER CONNECTION POINT. IF FEEDER
DISTANCE IS UNKNOWN, CONTRACTOR SHALL INCLUDE 500 FEET OF
FEEDER LENGTH IN BID. FEEDERS FOR UNITS SHALL BE #12 AWG
MINIMUM.
9. BOOM MOUNTING LOCATION AND CONNECTION FROM POWER
SUPPLY. VERIFY AND COORDINATE QUANTITY AND LOCATIONS WITH VA.
BOOMS, THEIR EQUIPMENT, AND BOOM CONNECTIVITY TO THE MODULAR
CEILING DIFFUSER STRUCTURE ARE NOT IN CONTRACT. REFER TO
SHEET EP101 FOR ADDITIONAL INFORMATION.
10. CONTRACTOR SHALL VERIFY LOCATION OF MEDICAL GAS ALARM AND
ZVA PANEL WITH MEDICAL GASSES PLAN.
11. PROVIDE 120V POWER TO NEW PRESSURE SWITCHES ON MEDICAL AIR,
MEDICAL VACUUM, MEDICAL OXYGEN, CARBON DIOXIDE, NITROUS OXIDE
AND NITROGEN PIPING. REFER TO MEDICAL GASSES DRAWINGS FOR
ADDITIONAL INFORMATION.
12. REMOTE STATUS ALARM PANEL - WALL MOUNTED. EXACT LOCATION TO
BE DETERMINED BY THE VA.
13. PROVIDE (5) 120V/20A POWER SUPPLY FOR THE EP POWER BOOM
CONVENIENCE AND EMERGENCY OUTLETS. CONTRACTOR TO INSTALL
POWER TO THE EP BOOM. COORDINATE WITH MANUFACTURER FOR
EXACT LOCATION OF CONNECTION TO EP BOOM.
14. PROVIDE A DEDICATED 6A FUSED SWITCHABLE CIRCUIT FOR THE EP
BOOM ELECTRICAL BRAKES. CONTRACTOR SHALL INSTALL POWER TO
THE EP BOOM.
15. PROVIDE DEDICATED DUPLEX OUTLET FOR POWER SUPPLY UNIT AND
ONE DATA ENABLER FOR HYBRID IMAGING EQUIPMENT. LOCATE IN COVE
OR ABOVE CEILING.
16. STUB UP LOCATION FOR CONTROL ROOM CONNECTION BOX. VERIFY
LOCATION PRIOR TO INSTALLATION WITH VA. INSTALL PER
MANUFACTURER'S REQUIREMENTS.
17. REMOTE ANNUNCIATOR FOR ISOLATION PANELS/ LINE ISOLATION
MONITORS. VERIFY LOCATION WITH VA PRIOR TO INSTALLATION,
DESIRABLE LOCATION SHALL BE VISIBLE FOR PERSON(S) IN THE
ANESTHETIZING LOCATION.
18. PROPOSED LOCATION OF EMERGENCY BATTERY INVERTERS.
CONTRACTOR TO PROVIDE TWO (2) EMERGENCY LIGHTING INVERTERS
TO SUPPORT CEILING MODULAR LIGHTING INTEGRATED SYSTEM. EACH
EMERGENCY BATTERY INVERTER SHALL SUPPLY 1500 WATTS, SHALL BE
LABELED WITH PANEL AND CIRCUIT BREAKER AND REQUIRE
STRUCTURAL SEISMIC CEILING SUPPORT. ENSURE STRUCTURES ARE
NOT FURTHER THAN 6 INCHES BACK FROM THE FRONT OF THE
TRANSFORMER. SHOP DRAWINGS WILL INCLUDE PROPOSED MOUNTING
SUPPORT DESIGN AND SHALL BE PRESENTED TO THE VA FOR
APPROVAL.
19. AUTO FLOW CONTROL VALVE (AFCV) LOCATED IN VERTICAL DUCT IN
CHASE. ACCESS PANEL PROVIDED BY MECHANICAL. COORDINATE WITH
MECHANICAL CONTRACTOR FOR EXACT LOCATION AND INSTALL PER
MANUFACTURER'S RECOMMENDATIONS.
20. CONTRACTOR SHALL PROVIDE FIRESTOP PUTTY PADS, FIRESTOP BOX
INSERTS, FIRESTOP PLATE GASKETS, ETC. FOR RECESSED BOX
PROTECTION IN FIRE RATED WALLS. ENSURE DEVICES ARE UL LISTED
PER 90G9.
8.8
9.8
CBA
ROOM
CLOSET
FILES
RADIOGRAPHIC
C O R R I D O R
OFFICE
BUDGET
A-160
CARDIAC.
ROOM
A-158
OFFICE
A-159
PHYSICS
MEDICAL
A-158
ROOM
CONTROL
A-
8a
ST
O
H.A.C.
A-171
A-172b
TOILET
A-172 ECOCARDIO-
GRAPHY RM.
B-117 B-115
B-114
LOUNGE STAFF RM.
A-172a
LOCK RM.
ELEC.
CLOS.
MALE LOCKERS
SIGNAL
CLOS. FEMALE LOCKERS
PHYSICIAN'S
LOCKERS
DN.DN.
C O R R I D O R C1-8
NO WORK IN THIS ROOM
NO WORK IN
THIS ROOM
NO WORK
IN THIS
ROOM
PANEL
1LA1C
(E)
ELECTRICAL CLOSET
B-117a
CONTROL
ROOM
SCRUB STN.
IMAGING
COMPONENT
ROOM
STERILE
SUPPLY
GURNEY
EPO
EPO
HYBRID
OPERATING
ROOM
GURNEY
UPS
ERB
RSAP
RIC
IVUS
VB2
VB9
VB7
VB1
NVA
PEA
QBS
QCD
CY
XFC
tUPS
ATY
MSA
SP
BC
IC
UPS
MBMRMEMA
1DS
1WL
A
B
TV
C
D
E
TV
DH
EPIQ
VB8
1 6
4 5
WM
(TYP)
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
ELECTRICAL CONDUIT AND RACEWAY PLAN - FIRST FLOOR
1/4" = 1'-0"
EP101
ELECTRICAL CONDUIT AND
RACEWAY PLAN
EP101
GENERAL NOTES
A. THIS DRAWING IS PROVIDED FOR COORDINATION PURPOSES ONLY. THE
FINAL APPROVED DESIGN FROM THE VA AND IMAGING EQUIPMENT
MANUFACTURER SHALL BE PRESENTED TO THE VA FOR APPROVAL. THE
GENERAL CONTRACTOR SHALL INCLUDE IN BID TO PROVIDE DESIGN
UPDATES IF MANUFACTURER REQUIREMENTS DIFFER FROM SHOWN.
B. ALL CONDUIT RUNS MUST TAKE MOST DIRECT ROUTE POINT TO POINT.
C. ALL CONDUIT RUNS MUST HAVE A PULL STRING.
D. ALL CONDUIT SHALL BE SUPPLIED BY AND INSTALLED BY THE
CONTRACTOR. CABLES FOR EQUIPMENT SHALL BE PROVIDED BY THE
IMAGING EQUIPMENT MANUFACTURER. VERIFY LOCATION OF ALL
DEVICES AND REQUIREMENTS WITH MANUFACTURER PRIOR TO
ROUGH-IN AND INSTALLATION.
E. CONDUIT MUST MEET THESE 3 CRITERIA:
a. ACCESSIBLE FOR THE FSE DURING INSTALL & ANNUAL PM
ELECTRICAL SAFETY TESTING.
b. MAX LENGTH OF THE GROUND WIRE STAYS BELOW 60'-0".
c. A # 6 GROUND TO BE USED.
THE CALCULATED GROUND RESISTANCE TO THE ADDED WIRE WOULD
NEED TO BE SUBTRACTED FROM THE MEASURED GROUND BONDING
BETWEEN THE ERB AND ACCESSIBLE PART.
CONDUIT IS ADDED TO BYPASS LONG HALLWAYS DURING TESTING
PURPOSES. CONDUIT MUST BE ALONE. VERIFY WITH FIELD AND
CUSTOMER REQUIREMENT.
EXAM ROOM PLACEMENT OF CONDUIT TERMINATION SHOULD BE ON
SHARED WALL WITH EQUIPMENT ROOM, IF POSSIBLE, IF NOT, EXAM
ROOM WALL CLOSEST TO THE EQUIPMENT ROOM.
E. VERIFY EXACT CEILING HEIGHT OF EQUIPMENT AND CONTROL ROOM
AREA.
F. ARCHITECT TO COORDINATE WITH END USERS/TECHNICIANS TO
DETERMINE FINAL PLACEMENT OF CONTROL DESK COMPONENTS PRIOR
TO INSTALLATION IN ORDER TO AVOID REWORK.
G. ARCHITECT TO COORDINATE WITH IMAGING EQUIPMENT
MANUFACTURER FOR PROVISIONAL CONSTRUCTION DRAWINGS.
H. VERIFY MAXIMUM CONDUIT LENGTH FROM IMAGING EQUIPMENT
MANUFACTURER.
I. REFER TO SHEETS E500 - E504 FOR DEVICE LEGEND AND BASIS OF
DESIGN.
KEYNOTES
1. (1) MINIMUM RACEWAY 3/4" CONDUIT.
2. (1) MINIMUM RACEWAY 1" CONDUIT.
3. (1) MINIMUM RACEWAY 1-1/2" CONDUIT.
4. (1) MINIMUM RACEWAY 2" CONDUIT.
5. (1) MINIMUM RACEWAY 2-1/2" CONDUIT.
6. (3) MINIMUM RACEWAY 1-1/2" CONDUIT. (1) MINIMUM RACEWAY 1"
CONDUIT. (1) MINIMUM RACEWAY 2-1/2" CONDUIT.
7. (2) MINIMUM RACEWAY 2" CONDUIT.
8. (2) MINIMUM RACEWAY 1-1/2" CONDUIT.
9. (7) MINIMUM RACEWAY 1" CONDUIT.
10. ALL VIDEO CONNECTION BOXES TO CONTROL ROOM BOX SHALL BE RAN
WITH 0-1/2" CONDUIT.
11. DEVICES CONNECTED TO THE EMERGENCY POWER OFF SHALL BE RAN
IN 2-1/2" CONDUIT UON.
8.8
9.8
CBA
NOTE:
THE USE OF 90 DEGREE ELLS IS NOT ACCEPTABLE. USE 45 DEGREE
BENDS AT ALL RACEWAY CORNERS. FOR RACEWAY (CONDUIT) RUNS,
USE THE MINIMUM BENDING RADIUS SPECIFIC TO THE RACEWAY
(CONDUIT) DIAMETER. THE USE OF CROSSOVER TUNNELS AT ALL
APPLICABLE LOCATIONS IS REQUIRED. THE ABOVE MENTIONED
RECOMMENDATIONS WILL HELP TO ENSURE THE INTEGRITY OF THE
CABLES AND FIBER OPTIC RUNS.
* ALL CONDUIT SHALL HAVE SEPARATE RACEWAYS. VERIFY CABLE TYPE
WITH VENDOR.
F G H J K
P-2
P-1
10.1
STAIR # 1
UP. DN.
P-3
P-4
9.4
8.9
S-5 S-6 S-7
NL M
DN.
5.9
STAIR # 2
SERV. ELEV.
LOBBY
ROOM
A-309-X
ROOM
B-340-X
F G H J K NL MFE
EF-1BEF-1A
AHU-1BAHU-1A
3HP3HP
5 HP 5 HP
EF-1B
30/3/3R
HORAC - 14,16,18
EF-1A
30/3/3R
HORAC - 8,10,12
4 4
AHU-1B UV LIGHTS
TPS-2
AHU-1B LIGHTS AND
SWITCH TPS-4
AHU-1B RECEPTACLES
TPS-6
J J
JAHU-1A UV LIGHTS
TPS-1
AHU-1A LIGHTS AND
SWITCH TPS-3
AHU-1A RECEPTACLES
TPS-5
WP/GFCI
TPS-75
WP/GFCI
TPS-7
REFER TO ENLARGED
VIEWS THIS SHEET FOR
ADDITIONAL DETAILS
REFER TO ENLARGED
VIEWS THIS SHEET FOR
ADDITIONAL DETAILS
AHU-3-01
(E)
FC-P4-01
(E)
EF-3-01-01
(E)
EF-3-01-02
(E)
FC-P4-04
(E)
FC-P4-03
(E)
AHU-1-05
(E)
FC-P4-02
(E)
WP
WP
WP
COORDINATION NOTE:
PENTHOUSE IS AN ENCLOSED
AREA FROM ELEMENTS.
AHU-1A SF-1
HORAC-1,3,5
AHU-1A SF-2
HORAC-13,15,17
AHU-1A RF-1
HORAC-20,22,24
VF
D
AHU-1B SF-1
HORAC-7,9,11
AHU-1B SF-2
HORAC-19,21,23
AHU-1B RF-1
HORAC-26,28,30
WP/GFCI
TPS-7
J
VF
D
VF
D
VF
D
VF
D
VF
D
J J
J
WP
WP
WP
JTPS-8 TPS-8WP WP
J
TPS-8
WP J
TPS-8
WP
8 8
J
TPS-8
WP
J
TPS-8
WP
5 HP
5 HP 5 HP
5 HP
STAIR # 1
UP. DN.
ROOM
A-309-X
3HA
3LA
S1
3LA
S2
DN.
STAIR # 2
ROOM
B-340-X
3HD
3LD
EXH EXL
EXL-1
DTT
45KVA
HORAC
TPS
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
ELECTRICAL PENTHOUSE PLAN
1/8" = 1'-0"
EP200
ELECTRICAL PENTHOUSE
PLAN
EP200
GENERAL NOTES
A. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD
OBSERVATION. NOTIFY ENGINEER OF ANY DISCREPANCIES BETWEEN
THESE DRAWINGS AND EXISTING CONDITIONS PRIOR TO DISTURBING
EXISTING INSTALLATION.
B. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A
MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE
REQUIREMENTS WITH THE VA/COR.
C. ELECTRICAL POWER SERVICES PASSING THROUGH CONSTRUCTION
AREA SHALL BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD.
D. ALL CIRCUITS SERVING AREAS ADJACENT TO THE CONSTRUCTION AREA
THAT ARE MODIFIED, AS PART OF THE CONSTRUCTION PROJECT, SHALL
BE RE-CIRCUITED AS PART OF THE CONSTRUCTION PROJECT.
E. CONTRACTOR SHALL COORDINATE ALL CONDUIT RUNS IN FIELD. ALL
CONDUIT SHALL BE CEILING SUSPENDED OR WALL MOUNTED. NO
CONDUIT SHALL RUN ALONG THE FLOOR.
KEYNOTES
ELECTRICAL ROOM A-309-X
1/4" = 1'-0"
EP200
ELECTRICAL ROOM B-340-X
1/4" = 1'-0"
EP200
1. SHOWN FOR REFERENCE ONLY.
2. COORDINATE FINAL LOCATION IN FIELD. GENERAL CONTRACTOR SHALL
INCLUDE IN BID ALL HARDWARE FOR A STAND ALONE INSTALLATION, IF
SUITABLE WALL SPACE IS NOT AVAILABLE.
3. REUSE EXISTING 125A BREAKER ON PANEL EXH. RUN NEW WIRING AND
CONDUIT TO PANEL HORAC. ACCOUNT FOR A FEEDER LENGTH OF 150'.
LOCATION CANNOT BE DETERMINED IN FIELD PRIOR TO BID ISSUANCE.
4. NEW AHU SHALL BE PROVIDED WITH VFD WITH NEMA 3R ENCLOSURE,
WITH SOFT START, MANUAL BYPASS SWITCH, SURGE PROTECTION, AND
FUSED DISCONNECT. UNIT SHALL BE ISSUED WITH A SINGLE POWER
CONNECTION POINT. PROVIDE ALL INTERCONNECTING WIRING PER
MANUFACTURER'S INSTALLATION DIAGRAMS. COORDINATE WITH
MECHANICAL FOR EXACT LOCATION.
5. CONTRACTOR SHALL PROVIDE STAND ALONE SUPPORTING HARDWARE.
PROVIDE UNISTRUT FOR MOUNTING OF VFD'S WITH INTEGRAL FUSED
DISCONNECT AND ELECTRICAL DEVICE. FIELD VERIFY EXACT LOCATION
ON SITE PRIOR TO INSTALLATION.
6. CONTRACTOR SHALL PROVIDE PROVIDE NEMA 3R 30 AMPS 3 POLE NON
FUSED MEANS OF DISCONNECT FOR EXHAUST FANS. DISCONNECT
SHALL BE PROVIDED WITH STAND ALONE HARDWARE AND PROPER
LABELING. DISCONNECT SHALL NOT BE INSTALLED IN THE BODY OF THE
FAN. ELECTRICAL CONDUIT SHALL NOT BE USED AS A MEANS OF
SUPPORT DISCONNECT.
7. CONTRACTOR SHALL INSTALL A TRANSFORMER AND CIRCUIT BREAKER
DISTRIBUTION PANEL COMBINED INTO ONE WALL MOUNTED SUBSTATION
BOLT ON BRANCH, 1 PHASE, 10kVA, 480V PRIMARY, 120/240V SECONDARY, TYPE 3R TRANSFORMER PANEL. REFER TO SHEET E600 AND E700 FOR
ADDITIONAL INFORMATION.
8. WP JUNCTION BOX FOR MOTORIZED DAMPERS. COORDINATE WITH
MECHANICAL CONTRACTOR FOR EXACT LOCATION.
9. CONTRACTOR SHALL PROVIDE STAND ALONE SUPPORTING HARDWARE.
PROVIDE UNISTRUT FOR MOUNTING OF ELECTRICAL DISCONNECT AND
ELECTRICAL DEVICE. FIELD VERIFY EXACT LOCATION ON SITE PRIOR TO
INSTALLATION.
X
2 3
G H
L M
9.4
ROOM
CLOSET
FILES
A-
8a
ST
O
H.A.C.
A-171
B-117 B-115
B-114ELEC.
CLOS.
MALE LOCKERS
SIGNAL
CLOS. FEMALE LOCKERS
PHYSICIAN'S
LOCKERS
DN.DN.
C O R R I D O R C1-8
NO WORK IN THIS ROOM
NO WORK IN
THIS ROOM
NO WORK
IN THIS
ROOM
ELECTRICAL CLOSET
B-117a
HYBRID
OPERATING
ROOM
CONTROL
ROOM
SCRUB STN.
IMAGING
COMPONENT
ROOM
STERILE
SUPPLY
GURNEY
4D
4D
4D
4D
4D
4D
J J
4D
4D
4D
J
J
J
J
4D
1 3 4 (TYP)
J
J
RSAP
RIC
IVUS
VB2
5 (TYP)
VB9
VB7
VB1
NVA
PEA
QBS
QCD
CY
XFC
tUPS
PDR
ATY
EPIQ
VB8
MSA
SP
4D
4D
BC
IC
UPS
MBMRMEMA
J J
WAPWAP
WAP
(TYP)
J
7 J
W. BATH.ROOM 5
SUPPLIES
ROOM
OFFICE
A-190b
A-190
WAITING
AREA
ELEC. CLOS.
M. BATH.
DRESSING
DRESSING
A-130d
BATHROOM
A-135
BATHROOM
A-134 A-132b
BATH.
A-136 A-131
RADIOGRAPHIC
A-132
ROOM 3
STORAGE
RECEPTION
ELEC. CLOS.
STORAGE
ELEC. CLOS.
TREATMENT
PLANNING
COMPUTER
A-188
A-184
STORAGE
WAITING AREA
CONTROL ROOM
A-143
LIGHT AREA
ROOMDIAGNOSTIC
RADIOGRAPHIC
ROOM
A-137
A-139
THERAPY
A-187
RADIATION
STORAGE
A-137b
FILM
RADIOGRAPHIC
ROOM 4
A-142
DARK ROOM
C O R R I D O R
BIO HAZARD
BATH
CONTROL
ROOM
CLOSET
FILES
RADIOGRAPHIC
ROOM 1
A-140
RADIOGRAPHIC
ROOM 1
A-131
ELCT. CL.
A-145
RADIOLOGIST
CONSULTATION
A-146
RAD. SUPERVISOR
C O R R I D O R
FLUOROSCOPIC
A-144
ROOM 2
OFFICE
BUDGET
A-160
CARDIAC.
ROOM
A-158
OFFICE
A-159
PHYSICS
MEDICAL
A-158
ROOM
CONTROL
GENERAL
A-157
OFFICE
ROOM
CLEAN
CARDIO
A-156
A-
8a
ST
O
H.A.C.
A-171
A-172b
TOILET
A-172
C O R R I D O R C1-8
MAN'S
ROOM
CONFERENCE
A-129
C O
R R
I D
READING
ROOM
A-175
A-174A-173
ROOM
G.X.T.ECOCARDIO-
GRAPHY RM.
PHARMACY
BIO CHEMISTRY
B-109
C O
R R
I D
A-155
LOUNGE STAFF RM.
A-172a
LOCK RM.
WAITING
A-147a
AREA
A-147
X-RAY
FRONT
COUNTER
WAITING
AREA
CLOS.
DN.DN.
C O R R I D O R C1-8
LOUNGE/
LOCKER
ROOM
8.8
9.8
CBA
NO WORK IN THIS ROOM
NO WORK IN
THIS ROOM
NO WORK
IN THIS
ROOM
ELECTRICAL CLOSET
B-117a
HYBRID
OPERATING
ROOM
CONTROL
ROOM
SCRUB STN.
IMAGING
COMPONENT
ROOM
STERILE
SUPPLY
GURNEY
1 3 4 (TYP)
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
ELECTRICAL TELECOMMUNICATIONS PLAN - FIRST FLOOR
1/4" = 1'-0"
ET100
ELECTRICAL
TELECOMMUNICATIONS PLAN
ET100
GENERAL NOTES
A. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD
OBSERVATION. ELECTRICAL CONTRACTOR SHALL REPORT
DISCREPANCIES TO ENGINEER PRIOR TO DISTURBING EXISTING
INSTALLATION.
B. PROVIDE JUNCTION BOXES, WIRE, CABLING, CONDUIT, ETC, AS
REQUIRED TO MAINTAIN CONTINUITY TO EXISTING TO REMAIN DEVICES,
FIXTURES, EQUIPMENT, ETC.
C. ALL UNUSED OR ABANDONED WIRE, CONDUIT, CABLING, ETC. SHALL BE
REMOVED BACK TO POINT OF ORIGIN.
D. THE CONTRACTOR IS RESPONSIBLE FOR ALL TELE/DATA CONDUIT,
WIRING, TERMINATIONS, ANY REQUIRED PATCH PANELS, ETC.
NECESSARY FOR ALL SPECIAL SYSTEMS IN COORDINATION WITH THE VA
OIT DEPARTMENT, UNLESS OTHERWISE NOTED.
E. JUNCTION BOXES SHALL BE MOUNTED IN ACCESSIBLE LOCATIONS.
PROVIDE AND COORDINATE ACCESS PANELS IN HARD CEILINGS WITH
ARCHITECTURAL REFLECTED CEILING PLAN.
F. CONTRACTOR SHALL TERMINATE CABLING AND PERFORM INITIAL
CONFIGURATION OF ALL NEWLY INSTALLED HARDWARE / SYSTEM
SOFTWARE LOCATED IN THE SECURITY AND SURVEILLANCE ROOMS.
G. FINAL MOUNTING HEIGHTS AND LOCATIONS OF BOXES, JUNCTION BOXES
AND DATA CONNECTIONS SHALL BE VERIFIED WITH VENDORS AND VA
PRIOR TO CONSTRUCTION.
H. ALL COMMUNICATIONS CABLES SHALL BE INSTALLED IN CONDUIT, CABLE
TRAY, OR SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE
ENDS OF ALL CONDUIT WHERE STUBBED ABOVE ACCESSIBLE CEILINGS
OF WHERE DROPPED INTO CABLE TRAY. PROVIDE CABLE HOOKS IN
ABOVE ACCESSIBLE CEILINGS WHERE AREAS ARE TOO TIGHT TO RUN
CABLE TRAY.
I. TELECOMMUNICATION OUTLETS (TCO) WILL BE A 4-11/16" SQUARE x 2-1/8"
DEEP JUNCTION BOX WITH A 1-1/4" CONDUIT TO THE ABOVE CEILING
TRAY SYSTEM. EACH TCO WILL HAVE A FOUR (4) PORT FACEPLATE WITH
THE FOLLOWING CONNECTIONS:
• 1 - CAT 6A 8 PIN MODULAR JACKS - VOICE
• 3 - CAT 6A 8 PIN MODULAR JACKS - DATA
KEYNOTES
1. PROVIDE BASKET - 12" WIDE x 2" DEPTH CABLE TRAY. WIRE MESH SPACING SHALL NOT EXCEED 2" x 4." FURNISH AND INSTALL WITH A
CONTINUOUS BARRIER STRIP FOR ENTIRE TRAY ROUTE TO PROVIDE
PARTITION FOR NURSE CALL AND OTHER CLASS LIMITED POWER
CIRCUITS.
2. PROVIDE (1) 3" CONDUIT SLEEVE FOR DATA CABLE PENETRATION THRU
WALL INTO CEILING OF OR TO TERMINATE INTO A LARGE DATA JUNCTION
BOX TO ALLOW THE TRANSITION TO 3/4" CONDUIT PUNCH OUTS FOR
DATA DEVICES. PROVIDE 3/4" CONDUIT, IN CEILING, FOR DATA RUN TO
EACH DATA DEVICE LOCATION. COORDINATE CLEARANCE WITH CEILING
LEVEL AND ANY OTHER DEVICES IN PATH OF DATA RUNS.
3. CABLE TRAY SHALL BE MOUNTED ABOVE DROP ACCESSIBLE CEILING.
COORDINATE FINAL CONNECTIONS TO DATA EQUIPMENT IN ELEC ROOM
AND VERIFY ROUTING AND CABLE TRAY SIZING WITH VA OIT
DEPARTMENT.
4. PROVIDE CABLE TRAY PARTITION TO SEPARATE NURSE CALL CLASS 2
WIRING FROM ALL OTHER SYSTEM CONDUCTORS.
5. REFER TO SHEET E501 AND E502 FOR DETAILS AND LEGEND OF
EQUIPMENT.
6. ROUTE CAT 6A CABLE BACK TO DATA RACKS IN ELEC CLOSET AS SHOWN
ON ET100 - 2.
7. PROVIDE 4 DATA FACE PLATES FOR SURGICAL EQUIPMENT. REFER TO
MANUFACTURER'S CUT SHEETS FOR ADDITIONAL INFORMATION AND
LOCATION.
8. WIRELESS ACCESS POINT (WAP) SYSTEM IS NOT IN SCOPE OF THE
PROJECT AND WILL BE PROVIDED BY THE VA. SHOWN FOR REFERENCE
ONLY. FINAL LOCATION AND QUANTITY WILL BE DETERMINED BY THE VA
OIT DEPARTMENT.
I.T. CLOSET - FIRST FLOOR
3/32" = 1'-0"
ET100
8.8
9.8
CBA
ROOM
CLOSET
FILES
RADIOGRAPHIC
C O R R I D O R
OFFICE
BUDGET
A-160
CARDIAC.
ROOM
A-158
OFFICE
A-159
PHYSICS
MEDICAL
A-158
ROOM
CONTROL
A-
8a
ST
O
H.A.C.
A-171
A-172b
TOILET
A-172 ECOCARDIO-
GRAPHY RM.
B-117 B-115
B-114
LOUNGE STAFF RM.
A-172a
LOCK RM.
ELEC.
CLOS.
MALE LOCKERS
SIGNAL
CLOS. FEMALE LOCKERS
PHYSICIAN'S
LOCKERS
C O
R R
I D
DN.DN.
C O R R I D O R C1-8
NO WORK IN THIS ROOM
NO WORK IN
THIS ROOM
NO WORK
IN THIS
ROOM
PANEL
1LA1C
(E)
ELECTRICAL CLOSET
B-117a
HYBRID
OPERATING
ROOM
CONTROL
ROOM
SCRUB STN.
IMAGING
COMPONENT
ROOM
STERILE
SUPPLY
GURNEY
N D
N D
N D
RSAP
RIC
IVUS
VB2
VB9
VB7
VB1
NVA
PEA
QBS
QCD
CY
XFC
tUPS
PDR
ATY
EPIQ
VB8
MSA
SP
BCUPS
MBMRMEMA
1 (TYP)
N D
W M
W M
W M
W X
S
W R
W R
PT
Z
PTZ
M S
W M
W M
W M
M S
M S
M S
W S
S
3 3
DC DC
ADOADO N DN C N U
IC
U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive
Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994
MES Group, Inc.
550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group
COA # 8304
ELECTRICAL AUXILIARY SYSTEMS PLAN - FIRST FLOOR
1/4" = 1'-0"
EY100
ELECTRICAL AUXILIARY
SYSTEMS PLAN
EY100
GENERAL NOTES
A. CONTRACTOR SHALL COORDINATE ANY WALL MOUNTED ITEM (CARD
READERS, PUSHPLATES, NURSE CALL SYSTEM) WITH ARCHITECT AND VA
PRIOR TO INSTALLATION.
B. CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFICATION OF ALL
RATED WALLS, CEILINGS, AND SLAB AND THEIR SPECIFIED RATING ON
THE ARCHITECTURAL DRAWINGS. ALL DEVICES AND MATERIAL SHALL
MEET THE UL RATING OF THE RATED WALL ASSEMBLY. CONTRACTOR
SHALL PROVIDE AN ASSEMBLY INSTALLED IN ACCORDANCE WITH UL FOR
THE RATED APPLICATION.
C. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD
OBSERVATION. ELECTRICAL CONTRACTOR SHALL REPORT
DISCREPANCIES TO ENGINEER PRIOR TO DISTURBING EXISTING
INSTALLATION.
D. PROVIDE JUNCTION BOXES, WIRE, CABLING, CONDUIT, ETC, AS
REQUIRED TO MAINTAIN CONTINUITY TO EXISTING TO REMAIN DEVICES,
FIXTURES, EQUIPMENT, ETC.
E. ALL UNUSED OR ABANDONED WIRE, CONDUIT, CABLING, ETC. SHALL BE
REMOVED BACK TO POINT OF ORIGIN.
F. THE GC IS RESPONSIBLE FOR PROVIDING ALL CONDUITS, J-BOXES AND
PULL STRINGS FOR THE SECURITY EQUIPMENT.
G. ELECTRICAL CONTRACTOR SHALL COORDINATE ELECTRICAL
CHARACTERISTICS AND REQUIREMENTS OF ALL SECURITY DEVICES
WITH VA PRIOR TO ORDERING AND INSTALLATION.
H. FINAL LOCATION OF SECURITY DEVICES SHALL BE COORDINATED WITH
THE VA DURING WALK THROUGH PRIOR TO ROUGH-IN.
I. COORDINATE ALL DOOR HARDWARE AND SEQUENCE OF OPERATION
WITH ARCHITECTURAL DOOR HARDWARE SPECIFICATIONS.
J. MAGNETIC LOCKS SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM
THROUGH A SET OF NORMALLY CLOSED, DRY CONTACTS SUPPLIED BY
FIRE ALARM CONTRACTOR.
K. DOOR HARDWARE SHALL BE COORDINATED WITH FIRE ALARM SYSTEM
TO DISENGAGE UPON FIRE ALARM SYSTEM ACTIVATION. COORDINATE
FINAL LOCATION OF CONDUIT AND JUNCTION BOXES WITH SUCCESSFUL
DOOR SECURITY HARDWARE PROVIDER PRIOR TO CONSTRUCTION.
L. FOR ALL NEW CAMERAS - SECURITY & CCTV DEVICES, THE CONTRACTOR
SHALL ENGAGE THE SECURITY CONTRACTOR, MAINTAINED BY THE VA,
TO VERIFY AND PERFORM TESTING OF THE SECURITY & CCTV SYSTEM,
TO ENSURE IT IS COMPLETELY OPERATIONAL AND FUNCTIONAL OF ALL
SECURITY COMPONENTS/DEVICES WITHIN THE AREA OF SCOPE.
M. THE EXISTING VIDEO CAMERA SYSTEM, SOFTWARE, AND WIRING IS THE
RESPONSIBILITY OF THE VA. PROVIDE ADDITIONAL HARDWARE TO
EXPAND CAMERA SYSTEM AS NEEDED. COORDINATE WITH COR.
N. ALL NEW PHYSICAL ACCESS CONTROL DEVICES AND CCTV SHALL BE
INTEGRATED WITH THE EXISTING SECURITY EQUIPMENT AND TIE INTO
THE NEAREST COMM ROOM.
O. NEW NURSE CALL DEVICES SHALL BE COMPATIBLE WITH THE EXISTING
VA NURSE CALL SYSTEM. TIE NEW DEVICES INTO THE EXISTING NURSE
CALL SYSTEM IN AREA OF WORK.
KEYNOTES
1. REFER TO SHEET E501 AND E502 FOR DETAILS AND LEGEND OF
EQUIPMENT. INFORMATION PROVIDED AS A BASIS OF DESIGN ONLY.
FINAL MANUFACTURER HAS NET BEING FINALIZED YET, SO ADDITIONAL
ITEM MIGHT BE REQUIRED AND SHALL BE PROVIDED UNDER THIS
PROJECT.
2. DOOR CONTACTS TO BE TIED INTO CONTROL SYSTEM FOR HYBRID
OPERATION IMAGING EQUIPMENT. REFER TO MANUFACTURER
DOCUMENTATION FOR ADDITIONAL DETAILS.
3. TIE INTO EXISTING PUBLIC ADDRESS SYSTEM. SPEAKERS SHALL BE
COMPATIBLE WITH EXISTING VA PA SYSTEM IN HOSPITAL.
8.8
9.8
CBA
BASIS OF DESIGN DETAILS
E500
GENERAL NOTES
A. DRAWINGS ARE SHOWN FOR REFERENCE ONLY. ELECTRICAL
CONTRACTOR TO PROVIDE DEVICES, WIRING AND CONDUIT PER
MANUFACTURER'S RECOMMENDATIONS AND REQUIREMENTS
PER VA APPROVED DESIGN.
B. CONTRACTOR SHALL MEET ALL REQUIRED CLEARANCES PER
NEC 110.26 (A) FOR ELECTRICAL EQUIPMENT.
ELECTRICAL REQUIREMENT NOTES FOR SYSTEMS WITH MAINS CABINET
ELECTRICAL POWER DISTRIBUTION AT THE FACILITY SHALL COMPLY WITH:
UTILIZATION VOLTAGES PER ANSI C84.1 - 2006 RANGE A.
VOLTAGE TO BE SUPPLIED IS 3 PHASE, WYE OR SYMMETRIC DELTA 3-LINE +PE.
PHASE CONDUCTORS TO BE SIZED FOR INSTANTANEOUS VOLTAGE DROP PER NEC 517.73 AND MANUFACTURER RECOMMENDATIONS.
ALL MANUFACTURER EQUIPMENT IS GROUNDED VIA THE EQUIPMENT INSULATED GROUND WIRE. METAL RACEWAY BONDING SHALL BE USED AS A SECONDARY GROUND FAULT RETURN PATH ONLY FOR THE SUPPLY MAINS TO THE EQUIPMENT. THE RACEWAY SYSTEM GROUND AND ISOLATED EQUIPMENT GROUND SHALL BE BONDED TOGETHER VIA THE ERB
TERMINAL JUMPERS.
THE MANUFACTURER SYSTEM HAS A PRIVATE GROUND DOMAIN PER CLAUSE 250.96B OF THE NEC. THE RACEWAY FRO1M THE X-RAY BREAKER (CB) TO THE CABINET SHALL BE SUPPLEMENTED BY AN INTERNAL INSULATED EQUIPMENT GROUNDING CONDUCTOR INSTALLED IN ACCORDANCE WITH CLAUSE 250.146(D) OF THE NEC. THE EQUIPMENT GROUND DOMAIN AND THE BRANCH CIRCUIT GROUND DOMAIN ARE BONDED TOGETHER IN THE ERB VIA A GROUND BONDING JUMPER.
ANSI / NFPA 70 - NATIONAL ELECTRICAL CODE
ARTICLE 250 - GROUNDING
ARTICLE 517 - HEALTHCARE FACILITIES
ANSI / NFPA 99 - HEALTHCARE FACILITIES
POWER QUALITY GUIDELINES
1. POWER SUPPLIED TO MEDICAL IMAGING EQUIPMENT MUST BE SEPARATE FROM POWER FEEDS TO AIR CONDITIONING, ELEVATORS, OUTDOOR LIGHTING, AND OTHER FREQUENTLY SWITCHED OR MOTORIZED LOADS. SUCH LOADS CAN CAUSE WAVEFORM DISTORTION AND VOLTAGE FLUCTUATIONS THAT CAN HINDER HIGH QUALITY IMAGING.
2. EQUIPMENT THAT UTILIZES THE FACILITY POWER SYSTEM TO TRANSMIT CONTROL SIGNALS (ESPECIALLY CLOCK SYSTEMS) MAY INTERFERE WITH MEDICAL IMAGING EQUIPMENT, THUS REQUIRING SPECIAL FILTERING.
3. THE FOLLOWING DEVICES PROVIDE A HIGH IMPEDANCE, NONLINEAR VOLTAGE SOURCE, WHICH MAY AFFECT IMAGE QUALITY:
STATIC UPS SYSTEMS, SERIES FILTERS, POWER CONDITIONERS, AND VOLTAGE REGULATORS.
DO NOT INSTALL SUCH DEVICES IN THE SUPPLY MAINS BRANCH CIRCUIT OF THE EQUIPMENT WITHOUT CONSULTING MANUFACTURER INSTALLATION OR SERVICE PERSONNEL.
4. LINE IMPEDANCE IS THE COMBINED RESISTANCE AND INDUCTIVE REACTANCE OF THE ELECTRICAL SYSTEM AND INCLUDES THE IMPEDANCE OF THE POWER SOURCE, THE FACILITY DISTRIBUTION SYSTEM, AND ALL PHASE CONDUCTORS BETWEEN THE SOURCE AND THE IMAGING EQUIPMENT. THE MINIMUM CONDUCTOR SIZE IS BASED ON THE TOTAL LINE IMPEDANCE AND NEC REQUIREMENTS. IMPEDANCE CALCULATIONS ARE TO BE PERFORMED BY AN ELECTRICAL ENGINEER.
EMERGENCY POWER
MANUFACTURER DOES NOT REQUIRE EQUIPMENT TO BE ON EMERGENCY POWER. IF THE CUSTOMER DEEMS IT NECESSARY FOR THE EQUIPMENT TO BE SUPPLIED WITH EMERGENCY
POWER, THE FOLLOWING SPECIFICATIONS MUST BE APPLIED:
THE CABINET FEEDING AN EQUIPMENT WILL HAVE AN ABSOLUTE PEAK CURRENT OF <=300A @ 480V. MAXIMUM MOMENTARY CURRENT <=80A PER PHASE WHEN AVERAGED OVER A 5-SECOND WINDOW. NOTE THAT DURING ACQUISITION, THE CURRENT HARMONICS (INCLUDING SUB- AND INTER-HARMONICS) UP TO 1 KHZ CAN BE SUBSTANTIAL. ACCOUNT FOR: 30% FOR THE MAINS FREQUENCY +/- THE FRAME SPEED, UP TO 20% FOR THE 5TH HARMONICS, UP TO 10% FOR THE 7TH HARMONICS.
MAXIMUM DIFFERENTIAL MODE INDUCED DISTURBANCE VOLTAGE ON THESE WIRES SHALL BE A <3V PEAK AT ALL FREQUENCIES. MAXIMUM COMMON MODE CURRENT ON THESE WIRES SHALL BE LESS THAN 3 MICRO-AMP AT FREQUENCIES BETWEEN 30-1000MHZ TO MEET EMC REGULATIONS.
FOR SYSTEMS DELIVERED TO SITE BEFORE JAN 2016 OR WITH SIB (SYSTEM INTERFACE BOX) 4522163320978.