Attachment 01 - Drawings Electrical 672-CSI-124 - Part V of VI - 15 Pages.pdf

PDF 13 MB Posted

Attached to
Z2DA--Construct New Hybrid Operating Room
Solicitation number
36C24825R0026
Issued by

About this file

This is an electrical drawings file for a construction project to build a new hybrid operating room at the VA Caribbean Healthcare System in San Juan, Puerto Rico. The 15-page set of electrical drawings, prepared by strollo & strollo architects and MES Group, Inc., provides comprehensive electrical design details including:

The drawings cover electrical demolition, lighting, power, telecommunications, auxiliary systems, conduit and raceway plans, and electrical schedules for various panels. Key electrical components include new electrical panels (1LXR, 1LX-OR-C, Hybrid-OR, IPP-1-C, IPP-2), transformer specifications, emergency power systems, and detailed wiring and circuit breaker configurations. The design focuses on supporting the hybrid operating room's complex electrical infrastructure, with specific attention to medical equipment power requirements, emergency lighting, isolated power systems, and compliance with electrical codes and VA healthcare facility standards.

View the file

Other files

File Type Posted
S06 - Amendment 0001 Attachment - Site Visit sign-in sheet 4-21-2025 - 36C24825R0026 BB 672-CSI-124 Hybrid OR.pdf PDF
36C24825R0026 0001 RFIs responses and Site Visit Roster.docx DOCX document
S06 - Amendment 0001 Attachment - 02 82 11 Abatement FINAL - 1 page.pdf PDF
S06 - Amendment 0001 Attachment - Specification 10 44 13 - 2 pages.pdf PDF
S06 - Amendment 0001 Attachment - Specification 01 42 19 - 9 pages.pdf PDF
S06 - Amendment 0001 Attachment - AQ-100 Arch PR VA Hybrid OR 100 Percent Final S-S - 1 page.pdf PDF
S06 - Amendment 0001 Attachment - Rigging Plan - 1 Page.pdf PDF
Attachment 01 - Drawings Fire Alarm 672-CSI-124 - Part VI of VI - 3 Pages.pdf PDF
Attachment 01 - Drawings General and Architectural 672-CSI-124 - Part I of VI - 23 Pages.pdf PDF
Attachment 02 - Specifications 672-CSI-124 - Part 2 of 2 - 1026 Pages.pdf PDF
Attachment 02 - Specifications 672-CSI-124 - Part 1 of 2 - 577 Pages.pdf PDF
Attachment 01 - Drawings Fire Protection 672-CSI-124 - Part II of VI - 3 Pages.pdf PDF
Attachment 06 - Letter of Commitment Key Subcontractors - 1 Page.pdf PDF
Attachment 08 - Subcontractor Past Performance Consent Form - 2 Pages.docx DOCX document
Attachment 03 - Contractor Safety and EMR - 2 Pages.docx DOCX document
Attachment 05 - Specialized Experience Form - 3 Pages.pdf PDF
Attachment 07 - Past Performance Questionnaire - 4 Pages.pdf PDF
Attachment 04 - Key Personnel Resume Form Sample - 1 Page.pdf PDF
Attachment 01 - Drawings Plumbing 672-CSI-124 - Part III of VI - 6 Pages.pdf PDF
Attachment 01 - Drawings Mechanical 672-CSI-124 - Part IV of VI - 4 Pages.pdf PDF
36C24825R0026 - BB 672-CSI-124 Hybrid OR.docx DOCX document
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive

Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group

COA # 8304

ELECTRICAL SYMBOLS AND

LEGENDS

E000

GENERAL PROJECT NOTES

1. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED

FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.

2. LIGHTING FIXTURES WITH MORE THAN TWO LAMPS SHALL HAVE TWO OUTER LAMPS

CONTROLLED WITH ONE SWITCH AND INNER LAMP(S) CONTROLLED BY A SECOND SWITCH.

3. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH

BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT

GROUNDING CONDUCTOR.

4. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND

NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

5. ALL WORK SHALL CONFORM TO FEDERAL, STATE AND LOCAL LAWS, CODES AND

ORDINANCES.

6. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY.

7. THE CONTRACTOR SHALL SEISMICALLY BRACE ALL EXISTING AND NEW NON STRUCTURAL

ELEMENTS FALLING WITHIN RENOVATION “LIMITS OF CONSTRUCTION” AS REQUIRED BY

CODE. REFER TO SPECIFICATION SECTION 130541 (SEISMIC RESTRAINT REQUIREMENTS

FOR NON-STRUCTURAL COMPONENTS) FOR ADDITIONAL INSTRUCTIONS.

8. THE ELECTRICAL DRAWINGS ARE SCHEMATIC IN NATURE. BEFORE STARTING THE WORK

THE CONTRACTOR SHALL REVIEW ALL OTHER DISCIPLINE DRAWINGS AND VERIFY FIELD

CONDITIONS AND SHALL MAKE ANY REQUIRED MINOR ADJUSTMENTS WITHOUT EXTRA

COST TO THE VA. ANY MAJOR DISCREPANCIES FOUND SHALL BE BROUGHT TO THE

ATTENTION OF THE ARCHITECT/ENGINEER.

RECEPTACLE, DUPLEX (18" AFF)

RECEPTACLE, QUADRAPLEX (18" AFF)

ELECTRICAL POWER SYMBOLS LEGEND

(MOUNTING HEIGHT TO CENTER LINE OF BOX UNLESS NOTED OTHERWISE)

PANELBOARD, SURFACE MOUNTED

TRANSFORMER

MOTOR, SINGLE - PHASE, HORSE POWER AS NOTED

DISCONNECT SWITCH - FUSED - FRAME/FUSE/POLES/NEMA

AS NOTED ON PLANS, ALL DISCONNECTS SHALL BE HEAVY

DUTY AND NEMA TYPE 1 U.O.N.

DISCONNECT SWITCH - MOTOR/STARTER COMBINATION

NEMA SIZE TO MATCH HP SHOWN ON PLANS AT THE

SPECIFIED VOLTAGE, HEAVY DUTY

JUNCTION BOX OR PULL BOX - SINGLE GANG U.O.N.

SM

30/15/2/3R

DISCONNECT SWITCH - NON-FUSED -

FRAME/FUSE/POLES/NEMA AS NOTED ON PLANS, ALL

DISCONNECTS SHALL BE HEAVY DUTY AND NEMA TYPE 1

U.O.N.

30/2/3R

MANUAL MOTOR STARTING SWITCH

J

COMMUNICATION SYMBOLS LEGEND

OUTLET, COMBINATION TELEPHONE/DATA COMMUNICATION

(18" AFF)

COMMUNICATION CABLE TRAY MOUNTED ABOVE

SUSPENDED CEILING - SIZE AS NOTED ON PLANS

8" CEILING MOUNTED PAGING SPEAKER; PROVIDED WITH

BAFFLE, GRILL AND MATCHING TRANSFORMER

(MOUNTING HEIGHT TO CENTER LINE OF BOX UNLESS NOTED OTHERWISE)

S

CONDUIT AND WIRING

2A-1,3,5

BRANCH CIRCUIT RUN CONCEALED

BRANCH CIRCUIT RUN UNDER FLOOR

BRANCH CIRCUIT DOWN

BRANCH CIRCUIT UP

HOME RUN TO PANEL 2A SPACES 1, 3, & 5, REFER TO PANEL

SCHEDULES

LINE TYPES

NEW WORK SCOPE OF WORK

EXISTING SCOPE OF WORK

DEMOLITION SCOPE OF WORK

FUTURE SCOPE OF WORK

GENERAL SYMBOLS

KEY NOTE INDICATOR

DRAWING REVISION INDICATORX

X X X X

NURSE CALL STATION.

D = DUTY STATION. MTD 5'-0" AFF UON

U = UTILITY CALL STATION, MTD 5'-0" AFF UON

C = CODE BLUE

T = TOILET

NURSE CALL SYMBOLS LEGEND

N

1PH SINGLE-PHASE

1P SINGLE POLE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3PH THREE-PHASE

4/C FOUR-CONDUCTOR

4W FOUR-WIRE

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED

CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR AVAILABLE

FAULT CURRENT

AFCI ARC-FAULT CURRENT INTERRUPTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

Ah AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BAT BATTERY

BD BOARD

BFF BELOW FINISH FLOOR

BLDG BUILDING

BRKR BREAKER

BYP BY PASS

C CONDUIT

CAB CABINET

CALC CALCULATE

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/CONTRACTOR

INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

OR C/B

CLF CURRENT LIMITING FUSE

CLG CEILING

COAX COAX CABLE

COMM COMMUNICATION

COMPT COMPARTMENT

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CUR CURRENT

dB DECIBEL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR PNL DISTRIBUTION PANEL

DMR SW DIMMER SWITCH

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

EPRF EXPLOSION PROOF

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST OR EXISTING

(E)

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FIXT FIXTURE

FLA FULL LOAD AMPS

FLUOR FLUORESCENT

FP FIRE PROTECTION

FT FEET OR FOOT

FU SW FUSED SWITCH

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G ELECTRICAL GROUND

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

IESNA ILLUMINATION ENGINEERING SOCIETY OF

NORTH AMERICA

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

kV KILOVOLT kVA KILOVOLT AMPERE kVAh KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWh KILOWATT HOUR kWhM KILOWATT HOUR METER

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MECH MECHANICAL

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NEUT OR N NEUTRAL

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

P POLE

PB PULL BOX

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

RM ROOM

RMS ROOT MEAN SQUARE

REQD REQUIRED

SCC SHORT CIRCUIT CAPACITY

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TEL TELEPHONE

TV TELEVISION

TYP TYPICAL

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

W WATT

WH WATER HEATER

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

ELECTRICAL ABBREVIATIONS

ECB ENCLOSED CIRCUIT BREAKER

ST SHUNT TRIP

RSAP REMOTE STATUS ALARM PANEL

ERB EQUI-POTENTIAL REFERENCE BAR

GBB GROUND BUS BAR

LIGHT FIXTURE, RECESSED (2'X4') - LETTER INDICATES TYPE.

LIGHT FIXTURE, RECESSED, EMERGENCY - LETTER

INDICATES TYPE.

2X2 FIXTURE - RECESSED, SURFACE, OR PENDANT

MOUNTED - LETTER INDICATES TYPE.

2X2 CRITICAL BRANCH FIXTURE - RECESSED, SURFACE, OR

PENDANT MOUNTED - LETTER INDICATES TYPE.

1X4 FIXTURE - RECESSED, SURFACE, OR PENDANT

MOUNTED - LETTER INDICATES TYPE.

1X4 CRITICAL BRANCH FIXTURE - RECESSED, SURFACE, OR

PENDANT MOUNTED - LETTER INDICATES TYPE.

EXIT SIGN-CEILING MOUNTED - TYPE AS SPECIFIED,

ARROWS AS SHOWN ON PLANS

CEILING MOUNTED VACANCY SENSOR;

DUAL TECHNOLOGY

(PASSIVE INFRARED/ULTRASONIC)

S

VS

A

A

B

B

C

C

SWITCH (# SUBSCRIPT AS INDICATED BELOW):

BLANK = SINGLE POLE 2 = DOUBLE POLE

3 = THREE-WAY 4 = FOUR-WAY

D = DIMMER K = KEY OPERATED

LV= LOW VOLTAGE P = WITH PILOT LIGHT

LM= LOW VOLTAGE MASTER RC= REMOTE CONTROL

PB= PUSH BUTTON STATION WP= WEATHER PROOF

T = TIMER OPERATED Mo= OCCUPANCY SENSOR

ELECTRICAL LIGHTING SYMBOLS LEGEND

(REFER TO LIGHTING FIXTURE SCHEDULE FOR MORE INFORMATION)

6" RECESSED DOWNLIGHT FIXTURE - LETTER INDICATES

TYPE.

6" RECESSED DOWNLIGHT FIXTURE - CRITICAL BRANCH

FIXTURE - LETTER INDICATES TYPE.

D

D

CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:

M = MOUNT

W - WALL

T = TECHNOLOGY / TYPE

M - MAG STRIP

M

T

RECEPTACLE, DUPLEX ON EMERGENCY POWER (18" AFF)

HP

D

N

D NURSE CALL STATION.

D = CORRIDOR DOME LIGHT

SAFETY AND SECURITY SYMBOLS LEGEND

(MOUNTING HEIGHT TO CENTER LINE OF BOX UNLESS NOTED OTHERWISE)

T

M T

ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:

M = MOUNT

W - WALL

T = TECHNOLOGY / TYPE

H - HYBRID L- LATCH SET M - MAGNETIC S - STRIKE

T

EXIT DEVICE; LETTER INDICATES AS FOLLOWS:

T = TECHNOLOGY / TYPE

D - DELAYED EGRESS E - ELECTRIFIED M - MECHANICAL

X - HIGH SECURITY

M T

INTERCOM ; LETTER INDICATES AS FOLLOWS:

M = MOUNT

W - WALL

T = TECHNOLOGY / TYPE

M - MASTER S - SUBSTATION

M T

PUSH BUTTON ; LETTER INDICATES AS FOLLOWS:

M = MOUNT

W - WALL

T = TECHNOLOGY / TYPE

B - BELL PUSH D - DURESS P - PANIC

R - DOOR RELEASE X - REQUEST TO EXIT

PTZ

SECURITY ACCESS, VIDEO CAMERA WITH LENS

M = MOTION DETECTOR

PZ = MOTION DETECTOR WITH PAN AND ZOOM

PTZ = MOTION DETECTOR WITH PAN, TILT, AND ZOOM

CEILING RECEPTACLE, DUPLEX

RECEPTACLE, QUADRAPLEX ON EMERGENCY POWER (18"

AFF)

RELAY LIGHTING RELAY - 110V OR 24V

RC# ELCU#

ROOM CONTROLLER

EMERGENCY ROOM CONTROLLER

EXIT SIGN-WALL MOUNTED - TYPE AS SPECIFIED, ARROWS

AS SHOWN ON PLANS

LIGHT FIXTURE - WALL MOUNT - LETTER INDICATES TYPE.

RECEPTACLE, SIMPLEX

RECEPTACLE, SPECIALTY

CEILING MOUNTED PASSIVE INFRARED SENSOR;

PROVIDED BY CONTRACTOR

(PASSIVE INFRARED/ULTRASONIC)

PIR

Sheet List Table Sheet Number Sheet Title

E000 ELECTRICAL SYMBOLS AND LEGENDS

ED100 ELECTRICAL DEMOLITION PLAN

EL100 ELECTRICAL LIGHTING PLAN

EP100 ELECTRICAL POWER PLAN

EP101 ELECTRICAL CONDUIT AND RACEWAY PLAN

EP200 ELECTRICAL PENTHOUSE PLAN

ET100 ELECTRICAL TELECOMMUNICATIONS PLAN

EY100 ELECTRICAL AUXILIARY SYSTEMS PLAN

E500 BASIS OF DESIGN DETAILS

E501 BASIS OF DESIGN DETAILS

E502 BASIS OF DESIGN DETAILS

E503 BASIS OF DESIGN DETAILS

E504 ELECTRICAL DETAILS

E600 ELECTRICAL ONE-LINE DIAGRAM

E700 ELECTRICAL SCHEDULES

04/03/2024

WAITING AREA

CONTROL

ROOM CLOSET

FILES

RADIOGRAPHIC

RAD. SUPERVISOR

C O R R I D O R

OFFICE

BUDGET

A-160

CARDIAC.

ROOM

A-158

OFFICE

A-159

PHYSICS

MEDICAL

A-158

ROOM

CONTROL

A-172b

TOILET

LOUNGE STAFF RM.

A-

2a

LO

C

K R

M

A-172

A-173

ECOCARDIO-

GRAPHY RM.

B-117 B-115

B-114

B-109

C O

R R

I D

O R

MALE LOCKERS

SIGNAL

CLOS. FEMALE LOCKERS

PHYSICIAN'S

LOCKERS

C O R R I D O R C1-8

S

S

CONTROLS

S C

C

WAP

WAP

S S

S

S

CONTROL

CYSTOSCOPY ROOM

ROOM

A-164

STORAGE

CLERICAL

AREA

STORAGE

TOILET

EXAM

ROOM

A-173

CYSTOSCOPY ROOM

A-167

A-171

EXAM

ROOM

A-172

EXAM

ROOM

S C

S S

WAP

S

S C

S

J

CONTROLS

S

S

N

J

S C

J

X-RAY RCPT

WAP

J

S

CONTROLS

S

J

CONTROLS

J

J

J

MINI SPLIT

J

MINI SPLIT

PANEL

1LA1C

(E)

ELECTRICAL CLOSET

B-117a

1HX(1)(E) 1HX(2)(E)

1LX-OR-A (E)

1LX-OR-B (E)

1LX-OR-C

(DEMO)

SUPERVISOR OFFICE

A-168

S

S

TECHNICAL PROCEDURES

A-168

S

J

J

S

CONTROLS

J

WAP

EXAM ROOM

A-170

EXAM ROOM

A-169

J

J

CONTROLS

J J

J J J

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

S

T

U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive

Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group

COA # 8304

ELECTRICAL DEMOLITION PLAN - FIRST FLOOR

1/4" = 1'-0"

ED100

ELECTRICAL DEMOLITION

PLAN

ED100

GENERAL NOTES - DEMOLITION

KEYNOTES

1. ELECTRICAL PANEL '1LA1C' IS EXISTING TO REMAIN. DISCONNECT ALL

ASSOCIATED CIRCUITS CURRENTLY FEEDING DEVICES AND EQUIPMENT

FROM AREA IN SCOPE OF WORK AND LABEL AS "SPARE".

2. EXISTING PANEL '1LX-OR-C' IS OUTDATED AND SHALL BE REPLACED

WITH NEW ELECTRICAL PANEL TO COMPLY WITH CURRENT CODES.

3. TYPICAL FOR ALL ROOMS - DEMOLISH ALL ELECTRICAL EQUIPMENT,

FIRE ALARM DEVICES, RECEPTACLES, DATA DEVICES, JUNCTION

BOXES, ETC. AND ASSOCIATED WIRING AND CONDUIT BACK TO THE

SOURCE, UNLESS OTHERWISE NOTED. ALL DEMOLISHED EQUIPMENT

AND DEVICES SHALL BE RETURNED TO THE VA.

4. TYPICAL FOR ALL ROOMS - LIGHTING FIXTURES AND EXIT SIGNS SHALL

BE DEMOLISHED AND RETURNED TO THE VA. ELECTRICAL CIRCUITS

FROM PANEL '1HA1' (ELECTRICAL CLOSET A-133-X) CURRENTLY

FEEDING NORMAL LIGHTING SHALL REMAIN FOR CONNECTION OF NEW

LIGHTING FIXTURES. EMERGENCY FIXTURES' CONDUIT AND WIRING

SHALL BE DEMOLISHED BACK TO THE SOURCE AND LABELED AS

"SPARE" IN PANEL (IF APPLICABLE). NEW EMERGENCY FIXTURES SHALL

BE CONNECTED TO EMERGENCY PANEL '1HX(2)' IN ELECTRICAL CLOSET

B-117a.

5. FOR ALL WAP DEVICES IN SCOPE OF PROJECT, THE CONTRACTOR

SHALL CAREFULLY REMOVE, INVENTORY, STORE AND PRESENT TO THE

VA FOR FIRST RIGHT OF REFUSAL.

A. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING

DEVICES, CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED,

COMPLETELY CUT/CAP CONDUITS AT THE AREA OF WORK PERIMETER

AND REMOVE CONDUIT AND REMOVE CONDUIT WITHIN THE WORK AREA,

DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND

REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS FROM

THE SOURCE POINT CONNECTION.

B. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE

OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL

ABANDONED WIRING..

C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND

CONDUCTORS PASSING THRU RENOVATED AREAS AND SERVICING

UNDISTURBED AREAS.

D. PRIOR TO REMOVAL OF EXISTING FIRE ALARM DEVICES, THE FIRE ALARM

CONTRACTOR SHALL VERIFY AND PERFORM TESTING OF THE EXISTING

FIRE ALARM SYSTEM TO ENSURE IT IS COMPLETELY OPERATIONAL AND

FUNCTIONAL OF ALL FIRE ALARM COMPONENTS/DEVICES WITHIN THE

AREA BEFORE MAKING CHANGES OR CONNECTIONS. THIS IS NOT

REQUIRED IF THE SYSTEM IS BEING MAINTAINED BY A CONTRACTOR BY

THE VA.

E. CONTRACTOR SHALL IDENTIFY ALL EXISTING FIRE ALARM DEVICES IN

AREA OF WORK. ALL FIRE ALARM DEVICES UNDER THE SCOPE OF THIS

PROJECT SHALL BE CAREFULLY REMOVED, INVENTORIED, STORED, AND

HANDED OVER TO THE VA AS SPARE PARTS.

F. CONTRACTOR SHALL IDENTIFY ALL EXISTING WAP DEVICES IN AREA OF

WORK. ALL WAP DEVICES UNDER THE SCOPE OF THIS PROJECT SHALL

BE CAREFULLY REMOVED, INVENTORIED, STORED AND PRESENTED TO

THE VA FOR FIRST RIGHT OF REFUSAL.

F. CONTRACTOR SHALL IDENTIFY NURSE CALL IN AREA OF WORK. ALL

NURSE CALL DEVICES UNDER THE SCOPE OF THIS PROJECT SHALL BE

CAREFULLY REMOVED, INVENTORIED, STORED AND PRESENTED TO THE

VA FOR FIRST RIGHT OF REFUSAL.

8.8

9.8

CBA

2.3

2.3

2.3

3.0 3.0

3.0 3.0

3.0 3.0

3.0 3.0

3.0 3.0

3.0 3.0

2.3

2.3

3.0 3.0

3.0 3.0

3.03.0 3.0

3.0

3.0 3.0

3.0 3.0

2.3

2.3

2.3

2.3

2.3

3.0 3.0

3.0 3.0

2.3

2.3

2.3

2.3

2.3

PIR

PIR PIR

PIR

VS

VS

VS

VS

VS

VS

TREATMENT

PLANNING

COMPUTER

WAITING AREA

CONTROL

ROOM

CLOSET

FILES

264.96n.s.f.

RADIOGRAPHIC

ROOM 1

A-140 104.56n.s.f.

A-

8a

ST

O

31.41n.s.f.

H.A.C.

A-171

B-117 B-115

ELEC.

CLOS.

MALE LOCKERS CLOS. FEMALE LOCKERS

25.58n.s.f.

25.75n.s.f.

152.44n.s.f.122.11n.s.f.

DN.DN.

C O R R I D O R C1-8

FX

C CE

BE B B

A1

HYBRID

OPERATING

ROOM

CONTROL

ROOM

SCRUB STN.

IMAGING

COMPONENT

ROOM

STERILE

SUPPLY

GURNEY

X

SD SD

RC1

RC2

ELCU

VS

SD

S S b

RC1

RC2

ELCU

S D S D c c b bbc d e f g f g

RC1

RC2

ELCUVS

VS

VS

SDSD

hk h k k h,k h,k d,e b,c

VS

b,c

1HX(2) - 08

J

S D

J

(TYPICAL)

(TYPICAL)

X

J

SD

A1E c

A1 b

A1 b d e e c b

VS

h,k

AE

e

A d

S 3 S 3 k h

AE

e

AE

e

AE

h

AE

h

AE

h

A k

A k

A k

J

RELAY

IPP-1-C-14

J

1HX(2)-20

1HX(2)-18

(TYPICAL)

J J

A d

SD

b,c

SD

HYBRID OR-3

J

'MA'

RELAY

(TYPICAL)

(TYPICAL)

(TYPICAL)

(TYPICAL)

(TYPICAL)

NO WORK IN THIS ROOM

NO WORK IN THIS

ROOM

NO WORK IN THIS

ROOM

(TYPICAL)

FIRST FLOOR PLAN - RENO. - LIGHTING

1/4" = 1'-0"

EL100

ELECTRICAL LIGHTING PLAN

EL100

GENERAL NOTES

A. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC/SCHEMATIC IN NATURE AND

REPRESENT THE GENERAL SCOPE OF WORK. IT IS NOT WITHIN THE

SCOPE OF THE ELECTRICAL DRAWINGS TO SHOW ALL NECESSARY

RACEWAY ROUTING, BENDS, OFFSET, PULL BOXES AND OBSTRUCTIONS.

CONTRACTOR SHALL COORDINATE THE FINAL LOCATION OF EQUIPMENT

FOR PROPER OPERATION IN ACCORDANCE WITH CODE, OWNER, AND

MANUFACTURER RECOMMENDATIONS.

B. CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFICATION OF ALL

RATED WALLS, CEILINGS AND SLABS AND THEIR SPECIFIED RATING ON

THE ARCHITECTURAL DRAWINGS. ALL DEVICES AND MATERIALS SHALL

MEET THE UL RATING OF THE RATED WALLS, CEILINGS AND SLABS

ASSEMBLY. CONTRACTOR SHALL PROVIDE AN ASSEMBLY INSTALLED IN

ACCORDANCE WITH THE RATED APPLICATION.

C. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD

OBSERVATION. ELECTRICAL CONTRACTOR SHALL REPORT

DISCREPANCIES TO ENGINEER PRIOR TO DISTURBING EXISTING

INSTALLATION.

D. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH OTHER TRADES AS

REQUIRED TO KEEP THE PROJECT PROGRESSING.

E. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND

CONDUCTORS PASSING THROUGH AREAS AND SERVICING UNDISTURBED

AREAS.

F. LIGHTING FIXTURES CONNECTED TO THE EMERGENCY CIRCUITS AND

EXIT SIGNS SHALL HAVE A 24/7 OPERATION.

G. DO NOT INSTALL CEILING SENSORS WITHIN 48" OF AIR DIFFUSERS OR

SIMILAR OBSTRUCTION THAT MAY ADVERSELY AFFECT THE SENSOR'S

PERFORMANCE. COORDINATE FINAL LOCATION OF SENSORS WITH

OTHER TRADES AND INSTALL IN ACCORDANCE WITH MANUFACTURER'S

RECOMMENDATIONS.

H. ALL JUNCTION BOXES SHALL BE RIGIDLY ATTACHED TO STRUCTURE OR

MILLWORK.

I. ALL LIGHTING CONTROLS SHALL BE IN ACCORDANCE WITH THE VA

LIGHTING DESIGN MANUAL.

J. PROVIDE DUAL TECHNOLOGY OCCUPANCY/VACANCY SENSORS FOR

AUTOMATIC LIGHTING CONTROL IN EQUIPMENT ROOM AND

MAINTENANCE SPACES.

K. LIGHTING CONTROLS CONTRACTOR SHALL PROVIDE CONTROLS AND

SENSORS WITH APPROPRIATE COVERAGE PATTERNS, AND

ADJUSTMENTS OF SENSITIVITY LEVELS TO PREVENT NUANCE

SWITCHING ON AND OFF OF LIGHTS.

L. THE CONTROL SYSTEMS SHALL BE A STAND ALONE, NON NETWORKED

SYSTEM FOLLOWING THE BASIS OF DESIGN, OR O/A/E APPROVED EQUAL.

M. PROVIDE TEMPORARY AND/OR MODIFY EXISTING LIGHTING AND POWER,

AND RELATED SERVICES AS REQUIRED FOR CONSTRUCTION-PERIOD’S

INTERIM LIFE SAFETY MEASURES.

KEYNOTES

1. PROVIDE JUNCTION BOX/ES AS REQUIRED PER MANUFACTURER'S

SPECIFICATIONS.

2. EACH LUMINAIRE ABOVE THE SURGERY TABLE SHALL BE POWERED

THROUGH THE BATTERY INVERTER SYSTEM.

3. MODULAR CEILING DIFFUSER SYSTEM INTEGRATED LIGHTING SYSTEM.

COORDINATE ELECTRICAL CONNECTIONS WITH SYSTEM MANUFACTURER.

INSTALL PER MANUFACTURER'S REQUIREMENTS. SEE ARCHITECTURAL

SHEETS FOR ADDITIONAL INFORMATION.

4. CONTRACTOR SHALL COORDINATE WITH EQUIPMENT MANUFACTURER FOR

CONNECTION OF X-RAY IN-USE LIGHT, EXAM ROOM LIGHTS AND DOOR

SWITCH.

5. CONTRACTOR SHALL SUPPLY AND LOCATE 110V RELAY BOX IN CEILING

SPACE AWAY FROM IMAGING HYBRID OR EQUIPMENT AND CONNECT TO

LOCAL LIGHTING CONTROL. CONTRACTOR SHALL PROVIDE SWITCH LEGS

TO EQUIPMENT AS SPECIFIED BY MANUFACTURER.

6. 20A SPARE NORMAL BRANCH LIGHTING CIRCUIT FROM PANEL '1HA1'

(ELECTRICAL CLOSET A-133-X) CREATED FROM DEMOLITION TO BE REUSED

AND LISTED ON EXISTING PANEL SCHEDULE.

7. VERIFY LOCATION OF POINT OF CONNECTION TO INTEGRATED LIGHTING

SYSTEM. DRIVER BOX REQUIRES A SINGLE POWER CONNECTION AND

SINGLE DIMMING CONTROL CONNECTION.

8. EMERGENCY BATTERY INVERTER. REFER TO EP100 FOR ADDITIONAL

POWER INFORMATION.

9. JUNCTION BOX WITH BLANK COVER FOR SURGICAL LIGHT MOUNTING

PLATE. COORDINATE EXACT LOCATION WITH CEILING MODULAR SYSTEM

AND HYBRID OR EQUIPMENT PRIOR TO ROUGH-IN.

10. MOUNT LIGHTING CONTROLLER AT 60" AFF. VERIFY LOCATION WITH VA

AND CEILING MODULAR SYSTEM VENDOR PRIOR TO ROUGH-IN.

11. REFER TO THE SUPPLEMENTARY PHOTOMETRIC DESIGN DRAWINGS

REFLECTING PROPOSED ILLUMINATION LEVELS AND DISTRIBUTION

ATTRIBUTES.

12. REFER TO THE OR MODULAR CEILING DIFFUSER INTEGRATED LIGHTING

SYSTEM FOR PROPOSED PHOTOMETRIC PLAN FOR FIXTURE TYPE AND

DESCRIPTION.

13. PASSIVE INFRARED DEVICES SUPPLIED AND LOCATED BY MANUFACTURER.

14. BOOM LOCATIONS AND QUANTITIES ARE SUBJECT TO CHANGE PER VA

FINAL SELECTION. REFER TO SHEET EP100 FOR ADDITIONAL INFORMATION.

MODULAR CEILING DIFFUSER INTEGRATED

BASIS OF DESIGN OF THE PROPOSED OR LAYOUT PROVIDED BY SLD. CONTRACTOR SHALL PROVIDE REVISED PHOTOMETRIC PLAN AS A PART OF THE OR ROOM LIGHTING SUBMITTAL. FIXTURES SHOWN TO SCALE FOR CLARITY PURPOSES.

8.8

9.8

CBA

LIGHTING CONTROL NOTES

A. CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFICATION OF ALL

RATED WALLS, CEILINGS, SLABS, AND THEIR SPECIFIED RATING ON THE

ARCHITECTURAL DRAWINGS. ALL DEVICES AND MATERIALS SHALL MEET

THE UL RATING OF THE RATED WALLS, CEILINGS AND SLABS ASSEMBLY.

CONTRACTOR SHALL PROVIDE AN ASSEMBLY, INSTALLED IN

ACCORDANCE WITH UL WHERE NECESSARY.

B. CONTRACTOR SHALL COORDINATE ANY WALL MOUNTED LIGHT FIXTURE

WITH ARCHITECT AND OWNER PRIOR TO INSTALLATION.

C. ALL OCCUPANCY SENSOR CONTROLLED LOADS SHALL TURN OFF WITHIN

20 MINUTES OF THE OCCUPANT LEAVING THE ROOM.

D. WHERE MULTIPLE SWITCHES ARE SHOWN AT THE SAME LOCATION, THEY

SHALL BE GANGED TOGETHER WITH A COMMON GANG PLATE.

E. ALL EXIT LIGHTS AND EMERGENCY BATTERY PACKS SHALL BE

CONNECTED TO UNSWITCHED LEG OF THE LOCAL LIGHTING BRANCH

CIRCUIT.

F. ALL LIGHTING CONTROLS SHALL BE IN ACCORDANCE WITH 2018 PUERTO

RICO BUILDING CODE, ENERGY CONSERVATION.

G. PROVIDE DUAL TECH OCCUPANCY/VACANCY SENSORS IN ALL OFFICES,

CORRIDORS, OPEN OFFICES, LOUNGES/BREAKROOMS, RESTROOMS,

STORAGE ROOMS, AND ALL OTHER SPACES 300 SQUARE FEET OR LESS

ENCLOSED BY FLOOR TO CEILING HEIGHT PARTITIONS. THIS EXCLUDES

MECHANICAL ROOMS, ELECTRICAL ROOMS, TELECOMMUNICATION

SPACES, AND OTHER AREA WHERE THE AUTOMATIC SHUT OFF OF

LIGHTS WILL CAUSE A DANGER TO LIFE SAFETY.

H. WHERE VACANCY SENSORS ARE REQUIRED, LIGHTS SHALL BE MANUAL

ON, AUTOMATIC OFF. LIGHTS SHALL TURN OFF AUTOMATICALLY WITHIN

20 MINUTES OF THE SPACE BECOMING VACANT.

I. WHERE OCCUPANCY SENSORS ARE REQUIRED, LIGHTS SHALL TURN ON

TO FULL AUTOMATICALLY, TURN OFF AUTOMATICALLY WITHIN 20

MINUTES OF THE SPACE BECOMING UNOCCUPIED, AND SHALL HAVE A

SWITCH FOR MANUAL OVERRIDE.

J. CONTRACTOR SHALL PROVIDE QUANTITY OF SENSORS REQUIRED WITH

PROPER COVERAGE PATTERN TO ACHIEVE REQUIRED LIGHTING

CONTROL WITHIN THE SPACE.

K. CONTRACTOR SHALL PROVIDE SHOP DRAWINGS FROM THE CONTROLS

MANUFACTURER'S REPRESENTATIVE SHOWING LAYOUT, QUANTITY,

COVERAGE PATTERNS, AND WIRING DIAGRAM OF COMPLETE SYSTEM.

L. FOR CLARITY, ONLY VACANCY (VS) OR OCCUPANCY (OC) ARE SHOWN IN

SPACES REQUIRING THAT MODE OF CONTROL.

M. PROVIDE LOW VOLTAGE OVERRIDE DIMMING SWITCHES IN ALL SPACES

REQUIRING VACANCY/OCCUPANCY SENSORS WITH CONTROL FUNCTION

AS OUTLINED.

N. PROVIDE ROOM CONTROLLERS AS REQUIRED TO INTERFACE ALL

LIGHTS, SWITCHES, SENSORS, ETC. IN ALL SPACES SHOWN TO RECEIVE

AUTOMATIC LIGHTING CONTROLS.

O. EXTERIOR LIGHTING SHALL BE CONTROLLED BY PHOTOCELL ON/TIME

CLOCK OFF. PROVIDE TIME CLOCK FOR CONTROLS. COORDINATE TIME

OF DAY SCHEDULING WITH STATION REPRESENTATIVE.

P. LIGHTING CONTROL SYSTEM SHALL BE A STAND ALONE

NON-NETWORKED SYSTEM AS MANUFACTURED BY ACUITY. ALTERNATE

APPROVED MANUFACTURERS ARE GREENGATE, WATTSTOPPER, AND

HUBBELL.

D

E

F

G

LIGHTING SYSTEM

D

D

D

D D

D

D

D

DD

E

E

E

E

G

G

F

U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive

Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group

COA # 8304 04/03/2024

ROOM

CLOSET

FILES

RADIOGRAPHIC

C O R R I D O R

OFFICE

BUDGET

A-160

CARDIAC.

ROOM

A-158

OFFICE

A-159

PHYSICS

MEDICAL

A-158

ROOM

CONTROL

A-

8a

ST

O

H.A.C.

A-171

A-172b

TOILET

A-172 ECOCARDIO-

GRAPHY RM.

B-117 B-115

B-114

LOUNGE STAFF RM.

A-172a

LOCK RM.

ELEC.

CLOS.

MALE LOCKERS

SIGNAL

CLOS. FEMALE LOCKERS

PHYSICIAN'S

LOCKERS

DN.DN.

C O R R I D O R C1-8

NO WORK IN THIS ROOM

NO WORK IN

THIS ROOM

NO WORK

IN THIS

ROOM

PANEL

1LA1C

(E)

ELECTRICAL CLOSET

B-117a

1HX(1)(E) 1HX(2)(E)

1LX-OR-A (E)

1LX-OR-B (E)

1LX-OR-C

(NEW)

CONTROL

ROOM

SCRUB STN.

IMAGING

COMPONENT

ROOM

STERILE

SUPPLY

GURNEY

GFCI

EPO

EPO

2 (TYP)

J

J

J

PANEL

1PP-1

IPP-1-1

IPP-1-3

IPP-1-5

IPP-1-7

1LXR-1

1LXR-3

1LXR-5

1LXR-C-24

1LXR-2

1LXR-4

IPP-2-6

IPP-2-5

IPP-2-4IPP-2-3

IPP-2-2

IPP-2-1

(TYPICAL)

PANEL

1PP-2

J

J

IPP-1-C-12

J

1LXR-7

1LXR-6

1LXR-8

IPP-1-4

IPP-1-2

IPP-1-6IPP-1-8

HYBRID

OPERATING

ROOM

GURNEY

PANEL

HYBRID-OR

(NEW)

PANEL

1LXR

(NEW)

XFMR

1LXR

(NEW)

XFMR

PAD

J

1LXR-OR

-C-25

1LXR-OR-C-26

1LXR-OR-C-27

1LXR-OR-C-29

J

1LXR-OR-C-22

+44"

1LXR-9

+44"

J

J

J

J

J

1LX-OR-C-28

J

1LX-OR-C-28

J

1LX-OR-C-28

J

UPS

150A

ECB/ST

80A

ECB

RASP

GBB

ERB

J

SM

IPP-1-C-9

IPP-1-C-10

IPP-1-C-11

J

IPP-2-7

IPP-2-8

15IPP-2-10 SM

15IPP-2-12 SM

HYBRID-OR-1

J

XFC

IPP-1-C-14

J

1LX-OR-C-28

J J

1HX(2)-20

1HX(2)-18

1 9

1 9

RIC

HYBRID-OR-2

HYBRID-OR-4

HYBRID-OR-3

J

J 1 9

ATU-1-2

ATU-1-3

ATU-1-4

ATU-1-1

ATU-1-5

ATU-1-6

J

J

1-LX-OR-C-6

SM

SM

J

SM

J

SM

J

SM

J

SM

JSM

AFCV

AFCV

AFCV

AFCV

J SM

JSM

J

SM

J J J

J J

1LXR-OR-C-30

1LXR-OR-C-31

(TYP)

U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive

Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group

COA # 8304

ELECTRICAL POWER PLAN - FIRST FLOOR

1/4" = 1'-0"

EP100

ELECTRICAL POWER PLAN

EP100

GENERAL NOTES

A. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD

OBSERVATION. NOTIFY ENGINEER OF ANY DISCREPANCIES BETWEEN

THESE DRAWINGS AND EXISTING CONDITIONS PRIOR TO DISTURBING

EXISTING INSTALLATION.

B. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE

SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A

MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE

REQUIREMENTS WITH THE VA/COR.

C. ELECTRICAL POWER SERVICES PASSING THROUGH CONSTRUCTION

AREA SHALL BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD.

D. ALL CIRCUITS SERVING AREAS ADJACENT TO THE CONSTRUCTION AREA

THAT ARE MODIFIED, AS PART OF THE CONSTRUCTION PROJECT, SHALL

BE RE-CIRCUITED AS PART OF THE CONSTRUCTION PROJECT.

E. REFER TO SHEEP EP101 FOR MINIMUM RECOMMENDED CONDUIT SIZE

AND ADDITIONAL INFORMATION.

KEYNOTES

1. FOR THE PROPOSED BOOMS (PROVIDED BY OTHERS), PROVIDE

JUNCTION BOX AS REQUIRED PER MANUFACTURER'S SPECIFICATIONS

AND AS REQUIRED BY THE NEC. RUN POWER FROM THE PANEL TO

JUNCTION BOX AND LEAVE ELECTRICAL PROVISION PROTECTED WITH

WIRE NOTES. PROVIDE BLANK PLATE TO JUNCTION BOX. REFER TO

MODULAR CEILING DIFFUSER SYSTEM SPECIFICATIONS FOR ADDITIONAL

INFORMATION.

2. REFER TO SHEETS E500 - E504 FOR DETAILS AND LEGEND OF

EQUIPMENT. INFORMATION PROVIDED AS A BASIS OF DESIGN ONLY.

FINAL MANUFACTURER HAS NET BEING FINALIZED YET, ADDITIONAL ITEM

MIGHT BE REQUIRED AND SHALL BE PROVIDED AS A DESIGN ADDENDUM,

AND SHALL BE INCLUDED IN PROJECT BID.

3. RECEPTACLES SHALL BE HOSPITAL GRADE. TYPICAL FOR ALL

RECEPTACLES IN THE HYBRID OPERATION ROOM AREA.

4. NEW RECESSED ISOLATED PANEL SOURSE PANEL. PANEL SHALL

INCLUDE AN INTEGRATED 7.5 KVA, 208V PRIMARY, 120V SECONDARY

TRANSFORMER. PANEL SHALL INCLUDE LINE ISOLATION MONITORING

AND AN INTEGRATED POWER MODULE WITH 4 DUPLEX RECEPTACLES

AND 4 GROUND RECEPTACLES. BREAKERS 2 AND 4 SHALL BE USED TO

POWER THE RECEPTACLES OF THE POWER MODULE. COORDINATE

INSTALLATION WITH EXISTING UTILITIES IN THE AREA.

5. ALL WIRING WITHIN THE ISOLATED POWER SYSTEM SHALL BE TYPE

XHHW OR XHHW-2. NO WIRE-PULLING COMPOUND SHALL BE USED TO

INSTALL WIRES IN THE ISOLATED POWER SYSTEM.

6. PROVIDE 120V/5A SWITCH LIMITED TO OPEN WHEN DOOR IS OPEN FOR

DOOR SWITCH. CONTRACTOR TO VERIFY MANUFACTURER'S IMAGING

EQUIPMENT AUXILIARY BOX CONNECTION ALLOCATION. REFER TO DOOR

SWITCH DIAGRAM DETAIL ON SHEET E503 FOR ADDITIONAL

INFORMATION.

7. IPS POWER MODULE: 4 DUPLEX AND 4 GROUND RECEPTACLES. 2

BRANCH CIRCUITS SHALL BE ROUTED TO EACH MODULE, 2 DUPLEX

RECEPTACLES PER CIRCUIT. SEE DETAILS FOR MORE INFORMATION.

PROVIDE ISOLATED GROUND. E.G. SHALL BE TIED TO MAIN BUILDING

GROUND BUS BAR WITH MINIMUM #8 CU G.E.C

8. NEW AHU SHALL HAVE INTEGRATED DISCONNECT MEANS. UNIT SHALL BE

ISSUED WITH A SINGLE POWER CONNECTION POINT. IF FEEDER

DISTANCE IS UNKNOWN, CONTRACTOR SHALL INCLUDE 500 FEET OF

FEEDER LENGTH IN BID. FEEDERS FOR UNITS SHALL BE #12 AWG

MINIMUM.

9. BOOM MOUNTING LOCATION AND CONNECTION FROM POWER

SUPPLY. VERIFY AND COORDINATE QUANTITY AND LOCATIONS WITH VA.

BOOMS, THEIR EQUIPMENT, AND BOOM CONNECTIVITY TO THE MODULAR

CEILING DIFFUSER STRUCTURE ARE NOT IN CONTRACT. REFER TO

SHEET EP101 FOR ADDITIONAL INFORMATION.

10. CONTRACTOR SHALL VERIFY LOCATION OF MEDICAL GAS ALARM AND

ZVA PANEL WITH MEDICAL GASSES PLAN.

11. PROVIDE 120V POWER TO NEW PRESSURE SWITCHES ON MEDICAL AIR,

MEDICAL VACUUM, MEDICAL OXYGEN, CARBON DIOXIDE, NITROUS OXIDE

AND NITROGEN PIPING. REFER TO MEDICAL GASSES DRAWINGS FOR

ADDITIONAL INFORMATION.

12. REMOTE STATUS ALARM PANEL - WALL MOUNTED. EXACT LOCATION TO

BE DETERMINED BY THE VA.

13. PROVIDE (5) 120V/20A POWER SUPPLY FOR THE EP POWER BOOM

CONVENIENCE AND EMERGENCY OUTLETS. CONTRACTOR TO INSTALL

POWER TO THE EP BOOM. COORDINATE WITH MANUFACTURER FOR

EXACT LOCATION OF CONNECTION TO EP BOOM.

14. PROVIDE A DEDICATED 6A FUSED SWITCHABLE CIRCUIT FOR THE EP

BOOM ELECTRICAL BRAKES. CONTRACTOR SHALL INSTALL POWER TO

THE EP BOOM.

15. PROVIDE DEDICATED DUPLEX OUTLET FOR POWER SUPPLY UNIT AND

ONE DATA ENABLER FOR HYBRID IMAGING EQUIPMENT. LOCATE IN COVE

OR ABOVE CEILING.

16. STUB UP LOCATION FOR CONTROL ROOM CONNECTION BOX. VERIFY

LOCATION PRIOR TO INSTALLATION WITH VA. INSTALL PER

MANUFACTURER'S REQUIREMENTS.

17. REMOTE ANNUNCIATOR FOR ISOLATION PANELS/ LINE ISOLATION

MONITORS. VERIFY LOCATION WITH VA PRIOR TO INSTALLATION,

DESIRABLE LOCATION SHALL BE VISIBLE FOR PERSON(S) IN THE

ANESTHETIZING LOCATION.

18. PROPOSED LOCATION OF EMERGENCY BATTERY INVERTERS.

CONTRACTOR TO PROVIDE TWO (2) EMERGENCY LIGHTING INVERTERS

TO SUPPORT CEILING MODULAR LIGHTING INTEGRATED SYSTEM. EACH

EMERGENCY BATTERY INVERTER SHALL SUPPLY 1500 WATTS, SHALL BE

LABELED WITH PANEL AND CIRCUIT BREAKER AND REQUIRE

STRUCTURAL SEISMIC CEILING SUPPORT. ENSURE STRUCTURES ARE

NOT FURTHER THAN 6 INCHES BACK FROM THE FRONT OF THE

TRANSFORMER. SHOP DRAWINGS WILL INCLUDE PROPOSED MOUNTING

SUPPORT DESIGN AND SHALL BE PRESENTED TO THE VA FOR

APPROVAL.

19. AUTO FLOW CONTROL VALVE (AFCV) LOCATED IN VERTICAL DUCT IN

CHASE. ACCESS PANEL PROVIDED BY MECHANICAL. COORDINATE WITH

MECHANICAL CONTRACTOR FOR EXACT LOCATION AND INSTALL PER

MANUFACTURER'S RECOMMENDATIONS.

20. CONTRACTOR SHALL PROVIDE FIRESTOP PUTTY PADS, FIRESTOP BOX

INSERTS, FIRESTOP PLATE GASKETS, ETC. FOR RECESSED BOX

PROTECTION IN FIRE RATED WALLS. ENSURE DEVICES ARE UL LISTED

PER 90G9.

8.8

9.8

CBA

ROOM

CLOSET

FILES

RADIOGRAPHIC

C O R R I D O R

OFFICE

BUDGET

A-160

CARDIAC.

ROOM

A-158

OFFICE

A-159

PHYSICS

MEDICAL

A-158

ROOM

CONTROL

A-

8a

ST

O

H.A.C.

A-171

A-172b

TOILET

A-172 ECOCARDIO-

GRAPHY RM.

B-117 B-115

B-114

LOUNGE STAFF RM.

A-172a

LOCK RM.

ELEC.

CLOS.

MALE LOCKERS

SIGNAL

CLOS. FEMALE LOCKERS

PHYSICIAN'S

LOCKERS

DN.DN.

C O R R I D O R C1-8

NO WORK IN THIS ROOM

NO WORK IN

THIS ROOM

NO WORK

IN THIS

ROOM

PANEL

1LA1C

(E)

ELECTRICAL CLOSET

B-117a

CONTROL

ROOM

SCRUB STN.

IMAGING

COMPONENT

ROOM

STERILE

SUPPLY

GURNEY

EPO

EPO

HYBRID

OPERATING

ROOM

GURNEY

UPS

ERB

RSAP

RIC

IVUS

VB2

VB9

VB7

VB1

NVA

PEA

QBS

QCD

CY

XFC

tUPS

ATY

MSA

SP

BC

IC

UPS

MBMRMEMA

1DS

1WL

A

B

TV

C

D

E

TV

DH

EPIQ

VB8

1 6

4 5

WM

(TYP)

U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive

Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group

COA # 8304

ELECTRICAL CONDUIT AND RACEWAY PLAN - FIRST FLOOR

1/4" = 1'-0"

EP101

ELECTRICAL CONDUIT AND

RACEWAY PLAN

EP101

GENERAL NOTES

A. THIS DRAWING IS PROVIDED FOR COORDINATION PURPOSES ONLY. THE

FINAL APPROVED DESIGN FROM THE VA AND IMAGING EQUIPMENT

MANUFACTURER SHALL BE PRESENTED TO THE VA FOR APPROVAL. THE

GENERAL CONTRACTOR SHALL INCLUDE IN BID TO PROVIDE DESIGN

UPDATES IF MANUFACTURER REQUIREMENTS DIFFER FROM SHOWN.

B. ALL CONDUIT RUNS MUST TAKE MOST DIRECT ROUTE POINT TO POINT.

C. ALL CONDUIT RUNS MUST HAVE A PULL STRING.

D. ALL CONDUIT SHALL BE SUPPLIED BY AND INSTALLED BY THE

CONTRACTOR. CABLES FOR EQUIPMENT SHALL BE PROVIDED BY THE

IMAGING EQUIPMENT MANUFACTURER. VERIFY LOCATION OF ALL

DEVICES AND REQUIREMENTS WITH MANUFACTURER PRIOR TO

ROUGH-IN AND INSTALLATION.

E. CONDUIT MUST MEET THESE 3 CRITERIA:

a. ACCESSIBLE FOR THE FSE DURING INSTALL & ANNUAL PM

ELECTRICAL SAFETY TESTING.

b. MAX LENGTH OF THE GROUND WIRE STAYS BELOW 60'-0".

c. A # 6 GROUND TO BE USED.

THE CALCULATED GROUND RESISTANCE TO THE ADDED WIRE WOULD

NEED TO BE SUBTRACTED FROM THE MEASURED GROUND BONDING

BETWEEN THE ERB AND ACCESSIBLE PART.

CONDUIT IS ADDED TO BYPASS LONG HALLWAYS DURING TESTING

PURPOSES. CONDUIT MUST BE ALONE. VERIFY WITH FIELD AND

CUSTOMER REQUIREMENT.

EXAM ROOM PLACEMENT OF CONDUIT TERMINATION SHOULD BE ON

SHARED WALL WITH EQUIPMENT ROOM, IF POSSIBLE, IF NOT, EXAM

ROOM WALL CLOSEST TO THE EQUIPMENT ROOM.

E. VERIFY EXACT CEILING HEIGHT OF EQUIPMENT AND CONTROL ROOM

AREA.

F. ARCHITECT TO COORDINATE WITH END USERS/TECHNICIANS TO

DETERMINE FINAL PLACEMENT OF CONTROL DESK COMPONENTS PRIOR

TO INSTALLATION IN ORDER TO AVOID REWORK.

G. ARCHITECT TO COORDINATE WITH IMAGING EQUIPMENT

MANUFACTURER FOR PROVISIONAL CONSTRUCTION DRAWINGS.

H. VERIFY MAXIMUM CONDUIT LENGTH FROM IMAGING EQUIPMENT

MANUFACTURER.

I. REFER TO SHEETS E500 - E504 FOR DEVICE LEGEND AND BASIS OF

DESIGN.

KEYNOTES

1. (1) MINIMUM RACEWAY 3/4" CONDUIT.

2. (1) MINIMUM RACEWAY 1" CONDUIT.

3. (1) MINIMUM RACEWAY 1-1/2" CONDUIT.

4. (1) MINIMUM RACEWAY 2" CONDUIT.

5. (1) MINIMUM RACEWAY 2-1/2" CONDUIT.

6. (3) MINIMUM RACEWAY 1-1/2" CONDUIT. (1) MINIMUM RACEWAY 1"

CONDUIT. (1) MINIMUM RACEWAY 2-1/2" CONDUIT.

7. (2) MINIMUM RACEWAY 2" CONDUIT.

8. (2) MINIMUM RACEWAY 1-1/2" CONDUIT.

9. (7) MINIMUM RACEWAY 1" CONDUIT.

10. ALL VIDEO CONNECTION BOXES TO CONTROL ROOM BOX SHALL BE RAN

WITH 0-1/2" CONDUIT.

11. DEVICES CONNECTED TO THE EMERGENCY POWER OFF SHALL BE RAN

IN 2-1/2" CONDUIT UON.

8.8

9.8

CBA

NOTE:

THE USE OF 90 DEGREE ELLS IS NOT ACCEPTABLE. USE 45 DEGREE

BENDS AT ALL RACEWAY CORNERS. FOR RACEWAY (CONDUIT) RUNS,

USE THE MINIMUM BENDING RADIUS SPECIFIC TO THE RACEWAY

(CONDUIT) DIAMETER. THE USE OF CROSSOVER TUNNELS AT ALL

APPLICABLE LOCATIONS IS REQUIRED. THE ABOVE MENTIONED

RECOMMENDATIONS WILL HELP TO ENSURE THE INTEGRITY OF THE

CABLES AND FIBER OPTIC RUNS.

* ALL CONDUIT SHALL HAVE SEPARATE RACEWAYS. VERIFY CABLE TYPE

WITH VENDOR.

F G H J K

P-2

P-1

10.1

STAIR # 1

UP. DN.

P-3

P-4

9.4

8.9

S-5 S-6 S-7

NL M

DN.

5.9

STAIR # 2

SERV. ELEV.

LOBBY

ROOM

A-309-X

ROOM

B-340-X

F G H J K NL MFE

EF-1BEF-1A

AHU-1BAHU-1A

3HP3HP

5 HP 5 HP

EF-1B

30/3/3R

HORAC - 14,16,18

EF-1A

30/3/3R

HORAC - 8,10,12

4 4

AHU-1B UV LIGHTS

TPS-2

AHU-1B LIGHTS AND

SWITCH TPS-4

AHU-1B RECEPTACLES

TPS-6

J J

JAHU-1A UV LIGHTS

TPS-1

AHU-1A LIGHTS AND

SWITCH TPS-3

AHU-1A RECEPTACLES

TPS-5

WP/GFCI

TPS-75

WP/GFCI

TPS-7

REFER TO ENLARGED

VIEWS THIS SHEET FOR

ADDITIONAL DETAILS

REFER TO ENLARGED

VIEWS THIS SHEET FOR

ADDITIONAL DETAILS

AHU-3-01

(E)

FC-P4-01

(E)

EF-3-01-01

(E)

EF-3-01-02

(E)

FC-P4-04

(E)

FC-P4-03

(E)

AHU-1-05

(E)

FC-P4-02

(E)

WP

WP

WP

COORDINATION NOTE:

PENTHOUSE IS AN ENCLOSED

AREA FROM ELEMENTS.

AHU-1A SF-1

HORAC-1,3,5

AHU-1A SF-2

HORAC-13,15,17

AHU-1A RF-1

HORAC-20,22,24

VF

D

AHU-1B SF-1

HORAC-7,9,11

AHU-1B SF-2

HORAC-19,21,23

AHU-1B RF-1

HORAC-26,28,30

WP/GFCI

TPS-7

J

VF

D

VF

D

VF

D

VF

D

VF

D

J J

J

WP

WP

WP

JTPS-8 TPS-8WP WP

J

TPS-8

WP J

TPS-8

WP

8 8

J

TPS-8

WP

J

TPS-8

WP

5 HP

5 HP 5 HP

5 HP

STAIR # 1

UP. DN.

ROOM

A-309-X

3HA

3LA

S1

3LA

S2

DN.

STAIR # 2

ROOM

B-340-X

3HD

3LD

EXH EXL

EXL-1

DTT

45KVA

HORAC

TPS

U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive

Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group

COA # 8304

ELECTRICAL PENTHOUSE PLAN

1/8" = 1'-0"

EP200

ELECTRICAL PENTHOUSE

PLAN

EP200

GENERAL NOTES

A. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD

OBSERVATION. NOTIFY ENGINEER OF ANY DISCREPANCIES BETWEEN

THESE DRAWINGS AND EXISTING CONDITIONS PRIOR TO DISTURBING

EXISTING INSTALLATION.

B. ALL SERVICE INTERRUPTIONS TO THIS EXISTING FACILITY MUST BE

SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A

MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE

REQUIREMENTS WITH THE VA/COR.

C. ELECTRICAL POWER SERVICES PASSING THROUGH CONSTRUCTION

AREA SHALL BE MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD.

D. ALL CIRCUITS SERVING AREAS ADJACENT TO THE CONSTRUCTION AREA

THAT ARE MODIFIED, AS PART OF THE CONSTRUCTION PROJECT, SHALL

BE RE-CIRCUITED AS PART OF THE CONSTRUCTION PROJECT.

E. CONTRACTOR SHALL COORDINATE ALL CONDUIT RUNS IN FIELD. ALL

CONDUIT SHALL BE CEILING SUSPENDED OR WALL MOUNTED. NO

CONDUIT SHALL RUN ALONG THE FLOOR.

KEYNOTES

ELECTRICAL ROOM A-309-X

1/4" = 1'-0"

EP200

ELECTRICAL ROOM B-340-X

1/4" = 1'-0"

EP200

1. SHOWN FOR REFERENCE ONLY.

2. COORDINATE FINAL LOCATION IN FIELD. GENERAL CONTRACTOR SHALL

INCLUDE IN BID ALL HARDWARE FOR A STAND ALONE INSTALLATION, IF

SUITABLE WALL SPACE IS NOT AVAILABLE.

3. REUSE EXISTING 125A BREAKER ON PANEL EXH. RUN NEW WIRING AND

CONDUIT TO PANEL HORAC. ACCOUNT FOR A FEEDER LENGTH OF 150'.

LOCATION CANNOT BE DETERMINED IN FIELD PRIOR TO BID ISSUANCE.

4. NEW AHU SHALL BE PROVIDED WITH VFD WITH NEMA 3R ENCLOSURE,

WITH SOFT START, MANUAL BYPASS SWITCH, SURGE PROTECTION, AND

FUSED DISCONNECT. UNIT SHALL BE ISSUED WITH A SINGLE POWER

CONNECTION POINT. PROVIDE ALL INTERCONNECTING WIRING PER

MANUFACTURER'S INSTALLATION DIAGRAMS. COORDINATE WITH

MECHANICAL FOR EXACT LOCATION.

5. CONTRACTOR SHALL PROVIDE STAND ALONE SUPPORTING HARDWARE.

PROVIDE UNISTRUT FOR MOUNTING OF VFD'S WITH INTEGRAL FUSED

DISCONNECT AND ELECTRICAL DEVICE. FIELD VERIFY EXACT LOCATION

ON SITE PRIOR TO INSTALLATION.

6. CONTRACTOR SHALL PROVIDE PROVIDE NEMA 3R 30 AMPS 3 POLE NON

FUSED MEANS OF DISCONNECT FOR EXHAUST FANS. DISCONNECT

SHALL BE PROVIDED WITH STAND ALONE HARDWARE AND PROPER

LABELING. DISCONNECT SHALL NOT BE INSTALLED IN THE BODY OF THE

FAN. ELECTRICAL CONDUIT SHALL NOT BE USED AS A MEANS OF

SUPPORT DISCONNECT.

7. CONTRACTOR SHALL INSTALL A TRANSFORMER AND CIRCUIT BREAKER

DISTRIBUTION PANEL COMBINED INTO ONE WALL MOUNTED SUBSTATION

BOLT ON BRANCH, 1 PHASE, 10kVA, 480V PRIMARY, 120/240V SECONDARY, TYPE 3R TRANSFORMER PANEL. REFER TO SHEET E600 AND E700 FOR

ADDITIONAL INFORMATION.

8. WP JUNCTION BOX FOR MOTORIZED DAMPERS. COORDINATE WITH

MECHANICAL CONTRACTOR FOR EXACT LOCATION.

9. CONTRACTOR SHALL PROVIDE STAND ALONE SUPPORTING HARDWARE.

PROVIDE UNISTRUT FOR MOUNTING OF ELECTRICAL DISCONNECT AND

ELECTRICAL DEVICE. FIELD VERIFY EXACT LOCATION ON SITE PRIOR TO

INSTALLATION.

X

2 3

G H

L M

9.4

ROOM

CLOSET

FILES

A-

8a

ST

O

H.A.C.

A-171

B-117 B-115

B-114ELEC.

CLOS.

MALE LOCKERS

SIGNAL

CLOS. FEMALE LOCKERS

PHYSICIAN'S

LOCKERS

DN.DN.

C O R R I D O R C1-8

NO WORK IN THIS ROOM

NO WORK IN

THIS ROOM

NO WORK

IN THIS

ROOM

ELECTRICAL CLOSET

B-117a

HYBRID

OPERATING

ROOM

CONTROL

ROOM

SCRUB STN.

IMAGING

COMPONENT

ROOM

STERILE

SUPPLY

GURNEY

4D

4D

4D

4D

4D

4D

J J

4D

4D

4D

J

J

J

J

4D

1 3 4 (TYP)

J

J

RSAP

RIC

IVUS

VB2

5 (TYP)

VB9

VB7

VB1

NVA

PEA

QBS

QCD

CY

XFC

tUPS

PDR

ATY

EPIQ

VB8

MSA

SP

4D

4D

BC

IC

UPS

MBMRMEMA

J J

WAPWAP

WAP

(TYP)

J

7 J

W. BATH.ROOM 5

SUPPLIES

ROOM

OFFICE

A-190b

A-190

WAITING

AREA

ELEC. CLOS.

M. BATH.

DRESSING

DRESSING

A-130d

BATHROOM

A-135

BATHROOM

A-134 A-132b

BATH.

A-136 A-131

RADIOGRAPHIC

A-132

ROOM 3

STORAGE

RECEPTION

ELEC. CLOS.

STORAGE

ELEC. CLOS.

TREATMENT

PLANNING

COMPUTER

A-188

A-184

STORAGE

WAITING AREA

CONTROL ROOM

A-143

LIGHT AREA

ROOMDIAGNOSTIC

RADIOGRAPHIC

ROOM

A-137

A-139

THERAPY

A-187

RADIATION

STORAGE

A-137b

FILM

RADIOGRAPHIC

ROOM 4

A-142

DARK ROOM

C O R R I D O R

BIO HAZARD

BATH

CONTROL

ROOM

CLOSET

FILES

RADIOGRAPHIC

ROOM 1

A-140

RADIOGRAPHIC

ROOM 1

A-131

ELCT. CL.

A-145

RADIOLOGIST

CONSULTATION

A-146

RAD. SUPERVISOR

C O R R I D O R

FLUOROSCOPIC

A-144

ROOM 2

OFFICE

BUDGET

A-160

CARDIAC.

ROOM

A-158

OFFICE

A-159

PHYSICS

MEDICAL

A-158

ROOM

CONTROL

GENERAL

A-157

OFFICE

ROOM

CLEAN

CARDIO

A-156

A-

8a

ST

O

H.A.C.

A-171

A-172b

TOILET

A-172

C O R R I D O R C1-8

MAN'S

ROOM

CONFERENCE

A-129

C O

R R

I D

READING

ROOM

A-175

A-174A-173

ROOM

G.X.T.ECOCARDIO-

GRAPHY RM.

PHARMACY

BIO CHEMISTRY

B-109

C O

R R

I D

A-155

LOUNGE STAFF RM.

A-172a

LOCK RM.

WAITING

A-147a

AREA

A-147

X-RAY

FRONT

COUNTER

WAITING

AREA

CLOS.

DN.DN.

C O R R I D O R C1-8

LOUNGE/

LOCKER

ROOM

8.8

9.8

CBA

NO WORK IN THIS ROOM

NO WORK IN

THIS ROOM

NO WORK

IN THIS

ROOM

ELECTRICAL CLOSET

B-117a

HYBRID

OPERATING

ROOM

CONTROL

ROOM

SCRUB STN.

IMAGING

COMPONENT

ROOM

STERILE

SUPPLY

GURNEY

1 3 4 (TYP)

U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive

Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group

COA # 8304

ELECTRICAL TELECOMMUNICATIONS PLAN - FIRST FLOOR

1/4" = 1'-0"

ET100

ELECTRICAL

TELECOMMUNICATIONS PLAN

ET100

GENERAL NOTES

A. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD

OBSERVATION. ELECTRICAL CONTRACTOR SHALL REPORT

DISCREPANCIES TO ENGINEER PRIOR TO DISTURBING EXISTING

INSTALLATION.

B. PROVIDE JUNCTION BOXES, WIRE, CABLING, CONDUIT, ETC, AS

REQUIRED TO MAINTAIN CONTINUITY TO EXISTING TO REMAIN DEVICES,

FIXTURES, EQUIPMENT, ETC.

C. ALL UNUSED OR ABANDONED WIRE, CONDUIT, CABLING, ETC. SHALL BE

REMOVED BACK TO POINT OF ORIGIN.

D. THE CONTRACTOR IS RESPONSIBLE FOR ALL TELE/DATA CONDUIT,

WIRING, TERMINATIONS, ANY REQUIRED PATCH PANELS, ETC.

NECESSARY FOR ALL SPECIAL SYSTEMS IN COORDINATION WITH THE VA

OIT DEPARTMENT, UNLESS OTHERWISE NOTED.

E. JUNCTION BOXES SHALL BE MOUNTED IN ACCESSIBLE LOCATIONS.

PROVIDE AND COORDINATE ACCESS PANELS IN HARD CEILINGS WITH

ARCHITECTURAL REFLECTED CEILING PLAN.

F. CONTRACTOR SHALL TERMINATE CABLING AND PERFORM INITIAL

CONFIGURATION OF ALL NEWLY INSTALLED HARDWARE / SYSTEM

SOFTWARE LOCATED IN THE SECURITY AND SURVEILLANCE ROOMS.

G. FINAL MOUNTING HEIGHTS AND LOCATIONS OF BOXES, JUNCTION BOXES

AND DATA CONNECTIONS SHALL BE VERIFIED WITH VENDORS AND VA

PRIOR TO CONSTRUCTION.

H. ALL COMMUNICATIONS CABLES SHALL BE INSTALLED IN CONDUIT, CABLE

TRAY, OR SUPPORTED BY CABLE HOOKS. PROVIDE BUSHINGS AT THE

ENDS OF ALL CONDUIT WHERE STUBBED ABOVE ACCESSIBLE CEILINGS

OF WHERE DROPPED INTO CABLE TRAY. PROVIDE CABLE HOOKS IN

ABOVE ACCESSIBLE CEILINGS WHERE AREAS ARE TOO TIGHT TO RUN

CABLE TRAY.

I. TELECOMMUNICATION OUTLETS (TCO) WILL BE A 4-11/16" SQUARE x 2-1/8"

DEEP JUNCTION BOX WITH A 1-1/4" CONDUIT TO THE ABOVE CEILING

TRAY SYSTEM. EACH TCO WILL HAVE A FOUR (4) PORT FACEPLATE WITH

THE FOLLOWING CONNECTIONS:

• 1 - CAT 6A 8 PIN MODULAR JACKS - VOICE

• 3 - CAT 6A 8 PIN MODULAR JACKS - DATA

KEYNOTES

1. PROVIDE BASKET - 12" WIDE x 2" DEPTH CABLE TRAY. WIRE MESH SPACING SHALL NOT EXCEED 2" x 4." FURNISH AND INSTALL WITH A

CONTINUOUS BARRIER STRIP FOR ENTIRE TRAY ROUTE TO PROVIDE

PARTITION FOR NURSE CALL AND OTHER CLASS LIMITED POWER

CIRCUITS.

2. PROVIDE (1) 3" CONDUIT SLEEVE FOR DATA CABLE PENETRATION THRU

WALL INTO CEILING OF OR TO TERMINATE INTO A LARGE DATA JUNCTION

BOX TO ALLOW THE TRANSITION TO 3/4" CONDUIT PUNCH OUTS FOR

DATA DEVICES. PROVIDE 3/4" CONDUIT, IN CEILING, FOR DATA RUN TO

EACH DATA DEVICE LOCATION. COORDINATE CLEARANCE WITH CEILING

LEVEL AND ANY OTHER DEVICES IN PATH OF DATA RUNS.

3. CABLE TRAY SHALL BE MOUNTED ABOVE DROP ACCESSIBLE CEILING.

COORDINATE FINAL CONNECTIONS TO DATA EQUIPMENT IN ELEC ROOM

AND VERIFY ROUTING AND CABLE TRAY SIZING WITH VA OIT

DEPARTMENT.

4. PROVIDE CABLE TRAY PARTITION TO SEPARATE NURSE CALL CLASS 2

WIRING FROM ALL OTHER SYSTEM CONDUCTORS.

5. REFER TO SHEET E501 AND E502 FOR DETAILS AND LEGEND OF

EQUIPMENT.

6. ROUTE CAT 6A CABLE BACK TO DATA RACKS IN ELEC CLOSET AS SHOWN

ON ET100 - 2.

7. PROVIDE 4 DATA FACE PLATES FOR SURGICAL EQUIPMENT. REFER TO

MANUFACTURER'S CUT SHEETS FOR ADDITIONAL INFORMATION AND

LOCATION.

8. WIRELESS ACCESS POINT (WAP) SYSTEM IS NOT IN SCOPE OF THE

PROJECT AND WILL BE PROVIDED BY THE VA. SHOWN FOR REFERENCE

ONLY. FINAL LOCATION AND QUANTITY WILL BE DETERMINED BY THE VA

OIT DEPARTMENT.

I.T. CLOSET - FIRST FLOOR

3/32" = 1'-0"

ET100

8.8

9.8

CBA

ROOM

CLOSET

FILES

RADIOGRAPHIC

C O R R I D O R

OFFICE

BUDGET

A-160

CARDIAC.

ROOM

A-158

OFFICE

A-159

PHYSICS

MEDICAL

A-158

ROOM

CONTROL

A-

8a

ST

O

H.A.C.

A-171

A-172b

TOILET

A-172 ECOCARDIO-

GRAPHY RM.

B-117 B-115

B-114

LOUNGE STAFF RM.

A-172a

LOCK RM.

ELEC.

CLOS.

MALE LOCKERS

SIGNAL

CLOS. FEMALE LOCKERS

PHYSICIAN'S

LOCKERS

C O

R R

I D

DN.DN.

C O R R I D O R C1-8

NO WORK IN THIS ROOM

NO WORK IN

THIS ROOM

NO WORK

IN THIS

ROOM

PANEL

1LA1C

(E)

ELECTRICAL CLOSET

B-117a

HYBRID

OPERATING

ROOM

CONTROL

ROOM

SCRUB STN.

IMAGING

COMPONENT

ROOM

STERILE

SUPPLY

GURNEY

N D

N D

N D

RSAP

RIC

IVUS

VB2

VB9

VB7

VB1

NVA

PEA

QBS

QCD

CY

XFC

tUPS

PDR

ATY

EPIQ

VB8

MSA

SP

BCUPS

MBMRMEMA

1 (TYP)

N D

W M

W M

W M

W X

S

W R

W R

PT

Z

PTZ

M S

W M

W M

W M

M S

M S

M S

W S

S

3 3

DC DC

ADOADO N DN C N U

IC

U.S. Department of Veterans Affairs strollo & strollo 718 Virginia Drive

Orlando, FL. 32803 T: (407) 423-5355 F: (407) 422-5994

MES Group, Inc.

550 North Reo Street, Suite 203 Tampa, FL, 33609 813.289.4700 mes group

COA # 8304

ELECTRICAL AUXILIARY SYSTEMS PLAN - FIRST FLOOR

1/4" = 1'-0"

EY100

ELECTRICAL AUXILIARY

SYSTEMS PLAN

EY100

GENERAL NOTES

A. CONTRACTOR SHALL COORDINATE ANY WALL MOUNTED ITEM (CARD

READERS, PUSHPLATES, NURSE CALL SYSTEM) WITH ARCHITECT AND VA

PRIOR TO INSTALLATION.

B. CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFICATION OF ALL

RATED WALLS, CEILINGS, AND SLAB AND THEIR SPECIFIED RATING ON

THE ARCHITECTURAL DRAWINGS. ALL DEVICES AND MATERIAL SHALL

MEET THE UL RATING OF THE RATED WALL ASSEMBLY. CONTRACTOR

SHALL PROVIDE AN ASSEMBLY INSTALLED IN ACCORDANCE WITH UL FOR

THE RATED APPLICATION.

C. EXISTING CONDITIONS ARE BASED ON RECORD DOCUMENTS AND FIELD

OBSERVATION. ELECTRICAL CONTRACTOR SHALL REPORT

DISCREPANCIES TO ENGINEER PRIOR TO DISTURBING EXISTING

INSTALLATION.

D. PROVIDE JUNCTION BOXES, WIRE, CABLING, CONDUIT, ETC, AS

REQUIRED TO MAINTAIN CONTINUITY TO EXISTING TO REMAIN DEVICES,

FIXTURES, EQUIPMENT, ETC.

E. ALL UNUSED OR ABANDONED WIRE, CONDUIT, CABLING, ETC. SHALL BE

REMOVED BACK TO POINT OF ORIGIN.

F. THE GC IS RESPONSIBLE FOR PROVIDING ALL CONDUITS, J-BOXES AND

PULL STRINGS FOR THE SECURITY EQUIPMENT.

G. ELECTRICAL CONTRACTOR SHALL COORDINATE ELECTRICAL

CHARACTERISTICS AND REQUIREMENTS OF ALL SECURITY DEVICES

WITH VA PRIOR TO ORDERING AND INSTALLATION.

H. FINAL LOCATION OF SECURITY DEVICES SHALL BE COORDINATED WITH

THE VA DURING WALK THROUGH PRIOR TO ROUGH-IN.

I. COORDINATE ALL DOOR HARDWARE AND SEQUENCE OF OPERATION

WITH ARCHITECTURAL DOOR HARDWARE SPECIFICATIONS.

J. MAGNETIC LOCKS SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM

THROUGH A SET OF NORMALLY CLOSED, DRY CONTACTS SUPPLIED BY

FIRE ALARM CONTRACTOR.

K. DOOR HARDWARE SHALL BE COORDINATED WITH FIRE ALARM SYSTEM

TO DISENGAGE UPON FIRE ALARM SYSTEM ACTIVATION. COORDINATE

FINAL LOCATION OF CONDUIT AND JUNCTION BOXES WITH SUCCESSFUL

DOOR SECURITY HARDWARE PROVIDER PRIOR TO CONSTRUCTION.

L. FOR ALL NEW CAMERAS - SECURITY & CCTV DEVICES, THE CONTRACTOR

SHALL ENGAGE THE SECURITY CONTRACTOR, MAINTAINED BY THE VA,

TO VERIFY AND PERFORM TESTING OF THE SECURITY & CCTV SYSTEM,

TO ENSURE IT IS COMPLETELY OPERATIONAL AND FUNCTIONAL OF ALL

SECURITY COMPONENTS/DEVICES WITHIN THE AREA OF SCOPE.

M. THE EXISTING VIDEO CAMERA SYSTEM, SOFTWARE, AND WIRING IS THE

RESPONSIBILITY OF THE VA. PROVIDE ADDITIONAL HARDWARE TO

EXPAND CAMERA SYSTEM AS NEEDED. COORDINATE WITH COR.

N. ALL NEW PHYSICAL ACCESS CONTROL DEVICES AND CCTV SHALL BE

INTEGRATED WITH THE EXISTING SECURITY EQUIPMENT AND TIE INTO

THE NEAREST COMM ROOM.

O. NEW NURSE CALL DEVICES SHALL BE COMPATIBLE WITH THE EXISTING

VA NURSE CALL SYSTEM. TIE NEW DEVICES INTO THE EXISTING NURSE

CALL SYSTEM IN AREA OF WORK.

KEYNOTES

1. REFER TO SHEET E501 AND E502 FOR DETAILS AND LEGEND OF

EQUIPMENT. INFORMATION PROVIDED AS A BASIS OF DESIGN ONLY.

FINAL MANUFACTURER HAS NET BEING FINALIZED YET, SO ADDITIONAL

ITEM MIGHT BE REQUIRED AND SHALL BE PROVIDED UNDER THIS

PROJECT.

2. DOOR CONTACTS TO BE TIED INTO CONTROL SYSTEM FOR HYBRID

OPERATION IMAGING EQUIPMENT. REFER TO MANUFACTURER

DOCUMENTATION FOR ADDITIONAL DETAILS.

3. TIE INTO EXISTING PUBLIC ADDRESS SYSTEM. SPEAKERS SHALL BE

COMPATIBLE WITH EXISTING VA PA SYSTEM IN HOSPITAL.

8.8

9.8

CBA

BASIS OF DESIGN DETAILS

E500

GENERAL NOTES

A. DRAWINGS ARE SHOWN FOR REFERENCE ONLY. ELECTRICAL

CONTRACTOR TO PROVIDE DEVICES, WIRING AND CONDUIT PER

MANUFACTURER'S RECOMMENDATIONS AND REQUIREMENTS

PER VA APPROVED DESIGN.

B. CONTRACTOR SHALL MEET ALL REQUIRED CLEARANCES PER

NEC 110.26 (A) FOR ELECTRICAL EQUIPMENT.

ELECTRICAL REQUIREMENT NOTES FOR SYSTEMS WITH MAINS CABINET

ELECTRICAL POWER DISTRIBUTION AT THE FACILITY SHALL COMPLY WITH:

UTILIZATION VOLTAGES PER ANSI C84.1 - 2006 RANGE A.

VOLTAGE TO BE SUPPLIED IS 3 PHASE, WYE OR SYMMETRIC DELTA 3-LINE +PE.

PHASE CONDUCTORS TO BE SIZED FOR INSTANTANEOUS VOLTAGE DROP PER NEC 517.73 AND MANUFACTURER RECOMMENDATIONS.

ALL MANUFACTURER EQUIPMENT IS GROUNDED VIA THE EQUIPMENT INSULATED GROUND WIRE. METAL RACEWAY BONDING SHALL BE USED AS A SECONDARY GROUND FAULT RETURN PATH ONLY FOR THE SUPPLY MAINS TO THE EQUIPMENT. THE RACEWAY SYSTEM GROUND AND ISOLATED EQUIPMENT GROUND SHALL BE BONDED TOGETHER VIA THE ERB

TERMINAL JUMPERS.

THE MANUFACTURER SYSTEM HAS A PRIVATE GROUND DOMAIN PER CLAUSE 250.96B OF THE NEC. THE RACEWAY FRO1M THE X-RAY BREAKER (CB) TO THE CABINET SHALL BE SUPPLEMENTED BY AN INTERNAL INSULATED EQUIPMENT GROUNDING CONDUCTOR INSTALLED IN ACCORDANCE WITH CLAUSE 250.146(D) OF THE NEC. THE EQUIPMENT GROUND DOMAIN AND THE BRANCH CIRCUIT GROUND DOMAIN ARE BONDED TOGETHER IN THE ERB VIA A GROUND BONDING JUMPER.

ANSI / NFPA 70 - NATIONAL ELECTRICAL CODE

ARTICLE 250 - GROUNDING

ARTICLE 517 - HEALTHCARE FACILITIES

ANSI / NFPA 99 - HEALTHCARE FACILITIES

POWER QUALITY GUIDELINES

1. POWER SUPPLIED TO MEDICAL IMAGING EQUIPMENT MUST BE SEPARATE FROM POWER FEEDS TO AIR CONDITIONING, ELEVATORS, OUTDOOR LIGHTING, AND OTHER FREQUENTLY SWITCHED OR MOTORIZED LOADS. SUCH LOADS CAN CAUSE WAVEFORM DISTORTION AND VOLTAGE FLUCTUATIONS THAT CAN HINDER HIGH QUALITY IMAGING.

2. EQUIPMENT THAT UTILIZES THE FACILITY POWER SYSTEM TO TRANSMIT CONTROL SIGNALS (ESPECIALLY CLOCK SYSTEMS) MAY INTERFERE WITH MEDICAL IMAGING EQUIPMENT, THUS REQUIRING SPECIAL FILTERING.

3. THE FOLLOWING DEVICES PROVIDE A HIGH IMPEDANCE, NONLINEAR VOLTAGE SOURCE, WHICH MAY AFFECT IMAGE QUALITY:

STATIC UPS SYSTEMS, SERIES FILTERS, POWER CONDITIONERS, AND VOLTAGE REGULATORS.

DO NOT INSTALL SUCH DEVICES IN THE SUPPLY MAINS BRANCH CIRCUIT OF THE EQUIPMENT WITHOUT CONSULTING MANUFACTURER INSTALLATION OR SERVICE PERSONNEL.

4. LINE IMPEDANCE IS THE COMBINED RESISTANCE AND INDUCTIVE REACTANCE OF THE ELECTRICAL SYSTEM AND INCLUDES THE IMPEDANCE OF THE POWER SOURCE, THE FACILITY DISTRIBUTION SYSTEM, AND ALL PHASE CONDUCTORS BETWEEN THE SOURCE AND THE IMAGING EQUIPMENT. THE MINIMUM CONDUCTOR SIZE IS BASED ON THE TOTAL LINE IMPEDANCE AND NEC REQUIREMENTS. IMPEDANCE CALCULATIONS ARE TO BE PERFORMED BY AN ELECTRICAL ENGINEER.

EMERGENCY POWER

MANUFACTURER DOES NOT REQUIRE EQUIPMENT TO BE ON EMERGENCY POWER. IF THE CUSTOMER DEEMS IT NECESSARY FOR THE EQUIPMENT TO BE SUPPLIED WITH EMERGENCY

POWER, THE FOLLOWING SPECIFICATIONS MUST BE APPLIED:

THE CABINET FEEDING AN EQUIPMENT WILL HAVE AN ABSOLUTE PEAK CURRENT OF <=300A @ 480V. MAXIMUM MOMENTARY CURRENT <=80A PER PHASE WHEN AVERAGED OVER A 5-SECOND WINDOW. NOTE THAT DURING ACQUISITION, THE CURRENT HARMONICS (INCLUDING SUB- AND INTER-HARMONICS) UP TO 1 KHZ CAN BE SUBSTANTIAL. ACCOUNT FOR: 30% FOR THE MAINS FREQUENCY +/- THE FRAME SPEED, UP TO 20% FOR THE 5TH HARMONICS, UP TO 10% FOR THE 7TH HARMONICS.

MAXIMUM DIFFERENTIAL MODE INDUCED DISTURBANCE VOLTAGE ON THESE WIRES SHALL BE A <3V PEAK AT ALL FREQUENCIES. MAXIMUM COMMON MODE CURRENT ON THESE WIRES SHALL BE LESS THAN 3 MICRO-AMP AT FREQUENCIES BETWEEN 30-1000MHZ TO MEET EMC REGULATIONS.

FOR SYSTEMS DELIVERED TO SITE BEFORE JAN 2016 OR WITH SIB (SYSTEM INTERFACE BOX) 4522163320978.