S06 - Amendment 0001 Attachment - Specification 10 44 13 - 2 pages.pdf

PDF 73 KB Posted

Attached to
Z2DA--Construct New Hybrid Operating Room Federal contract opportunity
Solicitation number
36C24825R0026
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8

About this file

This document is a two-page specification for fire extinguisher cabinets (Section 10 44 13) associated with a VA construction project for a new hybrid operating room in San Juan, Puerto Rico. The specification details technical requirements for recessed fire extinguisher cabinets, including fabrication specifications such as forming the cabinet body from 0.9 mm thick sheet steel, creating doors and trim from 1.2 mm thick sheet steel, and using 6 mm thick clear acrylic glazing. Key construction details include fully welded and ground smooth face joints, doors designed to open 180 degrees, continuous hinges, pull handles, and adjustable roller catches. The cabinets will have a baked-on semigloss white enamel interior and a manufacturer's standard prime coat on doors and frames suitable for field painting. Installation instructions mandate mounting the cabinets in prepared openings according to manufacturer guidelines and ensuring the extinguisher height meets NFPA 10 requirements.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--Construct New Hybrid Operating Room, newest first.
File Type Posted
S06 - Amendment 0001 Attachment - Specification 01 42 19 - 9 pages.pdf PDF
36C24825R0026 0001 RFIs responses and Site Visit Roster.docx DOCX document
S06 - Amendment 0001 Attachment - AQ-100 Arch PR VA Hybrid OR 100 Percent Final S-S - 1 page.pdf PDF
S06 - Amendment 0001 Attachment - Rigging Plan - 1 Page.pdf PDF
S06 - Amendment 0001 Attachment - 02 82 11 Abatement FINAL - 1 page.pdf PDF
S06 - Amendment 0001 Attachment - Site Visit sign-in sheet 4-21-2025 - 36C24825R0026 BB 672-CSI-124 Hybrid OR.pdf PDF
Attachment 07 - Past Performance Questionnaire - 4 Pages.pdf PDF
Attachment 05 - Specialized Experience Form - 3 Pages.pdf PDF
Attachment 04 - Key Personnel Resume Form Sample - 1 Page.pdf PDF
Attachment 02 - Specifications 672-CSI-124 - Part 2 of 2 - 1026 Pages.pdf PDF
Attachment 01 - Drawings Fire Alarm 672-CSI-124 - Part VI of VI - 3 Pages.pdf PDF
Attachment 01 - Drawings Electrical 672-CSI-124 - Part V of VI - 15 Pages.pdf PDF
36C24825R0026 - BB 672-CSI-124 Hybrid OR.docx DOCX document
Attachment 08 - Subcontractor Past Performance Consent Form - 2 Pages.docx DOCX document
Attachment 06 - Letter of Commitment Key Subcontractors - 1 Page.pdf PDF
Attachment 03 - Contractor Safety and EMR - 2 Pages.docx DOCX document
Attachment 02 - Specifications 672-CSI-124 - Part 1 of 2 - 577 Pages.pdf PDF
Attachment 01 - Drawings Mechanical 672-CSI-124 - Part IV of VI - 4 Pages.pdf PDF
Attachment 01 - Drawings Plumbing 672-CSI-124 - Part III of VI - 6 Pages.pdf PDF
Attachment 01 - Drawings Fire Protection 672-CSI-124 - Part II of VI - 3 Pages.pdf PDF
Attachment 01 - Drawings General and Architectural 672-CSI-124 - Part I of VI - 23 Pages.pdf PDF
Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

08-01-18

10 44 13 - 1

SECTION 10 44 13

FIRE EXTINGUISHER CABINETS

SPEC WRITER NOTE:

1. Delete between //----// If not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs.

2. Use fully recessed cabinets. Do not allow projection of doors and frames into corridor areas other than frame flange thickness.

3. Insure details show cabinet recessed in wall with no penetration of fire rating when applicable.

4. Insure detail shows elevation of cabinet with glazing.

PART 1 - GENERAL

1.1 DESCRIPTION

This section covers recessed fire extinguisher cabinets.

1.2 RELATED WORK

A. Acrylic glazing: Section 08 80 00, GLAZING.

B. Field Painting: Section 09 91 00, PAINTING.

1.3 SUBMITTALS

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT

DATA, AND SAMPLES.

B. Manufacturer's Literature and Data: Fire extinguisher cabinet including installation instruction and rough opening required.

1.4 APPLICATION PUBLICATIONS

A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.

B. American Society of Testing and Materials (ASTM):

D4802-15................Poly (Methyl Methacrylate) Acrylic Plastic

Sheet

PART 2 - PRODUCTS

2.1 FIRE EXTINGUISHER CABINET

Recessed type with flat trim of size and design shown.

2.2 FABRICATION

A. Form body of cabinet from 0.9 mm (0.0359 inch) thick sheet steel.

08-01-18

10 44 13 - 2

B. Fabricate door and trim from 1.2 mm (0.0478 inch) thick sheet steel with all face joints fully welded and ground smooth.

1. Glaze doors with 6 mm (1/4 inch) thick ASTM D4802, clear acrylic sheet, Category B-1, Finish 1.

2. Design doors to open 180 degrees.

3. Provide continuous hinge, pull handle, and adjustable roller catch.

2.3 FINISH

A. Finish interior of cabinet body with baked-on semigloss white enamel.

B. Finish door, frame with manufacturer's standard baked-on prime coat suitable for field painting.

PART 3 - EXECUTION

A. Install fire extinguisher cabinets in prepared openings and secure in accordance with manufacturer's instructions.

B. Install cabinet so that the extinguisher height within meets the requirements of NFPA 10

- - - E N D - - -