Attachment 0010b.1 – E001 28VDC Pwr Supply Shelter Power-FMECA.xlsx
XLSX spreadsheet 44 KB Posted
- Attached to
- RFP for Integrated Battle Command System (IBCS) LRIP/FRP Federal contract opportunity
- Solicitation number
- W31P4Q-20-R-0015
About this file
This document contains a failure modes and effects criticality analysis (FMECA) worksheet for an E001 28VDC power supply shelter and related federal contract opportunity solicitation. The FMECA worksheet analyzes potential failure modes for the power supply shelter's components, potential effects, detection methods, severity classifications, and compensating provisions. The related federal contract opportunity is a solicitation for the Integrated Battle Command System Low Rate Initial Production/Full Rate Production segment. It seeks hardware production maintaining approved software/firmware updates and meeting cybersecurity and authority to operate requirements. Engineering changes may be required. Questions are due by December 10, 2020 by 4pm Central Time. The solicitation is only for contractors who met entrance criteria on Beta SAM and were approved by the Integrated Fires Mission Command Project Office. The Department of the Army Materiel Command Contracting Command at Redstone Arsenal is the contracting agency.
View the file
Other files for this federal contract opportunity
Show all 50
RFP for Integrated Battle Command System (IBCS) LRIP/FRP has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet2
| W31P4Q-20-R-0015 | ||
| ATTACHMENT 0010b.1 | ||
| TAB 1 OF 4 | ||
| Row Labels | Sum of Cm | Count of Failure Mode Description |
| Improper Output | 1.03E-05 | 2 |
| Improper Voltage | 1.03E-05 | 2 |
| Intermittent Operation | 2.31E-05 | 3 |
| No Output | 1.04E-03 | 5 |
| Short | 1.08E-04 | 2 |
| Grand Total | 1.19E-03 | 14 |
Prelim Analysis
| W31P4Q-20-R-0015 | ||||||
| ATTACHMENT 0010b.1 | ||||||
| TAB 2 OF 4 | ||||||
| PRELIMINARY ANALYSIS: | Major End Item: | Shelter -Power | ||||
| Parent LRU: | E001 - 28 VDC Power Supply # 1 | |||||
| Component: | 28 VDC Power Supply | |||||
| Mission Phase-Operational Mode: | All Phases | |||||
| Cr = ∑Cm = | 1.19E-03 | |||||
| Failure Modes | Count of | |||||
| Failure Modes | Severity | |||||
| Classifications | Count of |
Seveverity Classification Failure Modes Sum of Cm Count of Failure Modes
| No Output | 5 | 35.71% | Category I | 5 | Improper Output | 1.03E-05 | 2 |
| Intermittent Operation | 3 | 21.43% | No Output | 4 | Improper Voltage | 1.03E-05 | 2 |
| Improper Output | 2 | 14.29% | Short | 1 | Intermittent Operation | 2.31E-05 | 3 |
| Improper Voltage | 2 | 14.29% | Category III | 9 | No Output | 1.04E-03 | 5 |
| Short | 2 | 14.29% | Improper Output | 2 | Short | 1.08E-04 | 2 |
| Grand Total | 14 | Improper Voltage | 2 | Grand Total | 1.19E-03 | 14 | |
| Intermittent Operation | 3 | ||||||
| No Output | 1 | ||||||
| Short | 1 | ||||||
| Grand Total | 14 |
Cat I and II
| W31P4Q-20-R-0015 | |||||||||||||||||||||
| ATTACHMENT 0010b.1 | |||||||||||||||||||||
| TAB 3 OF 4 | |||||||||||||||||||||
| Major End Item: | Shelter -Power | ||||||||||||||||||||
| Parent LRU: | E001 - 28 VDC Power Supply # 1 | ||||||||||||||||||||
| Component: | 28 VDC Power Supply | ||||||||||||||||||||
| Mission Phase-Operational Mode: | All Phases | ||||||||||||||||||||
| FPMH: | 1.916 | ||||||||||||||||||||
| t: | 72 | ||||||||||||||||||||
| Cr = ∑Cm = | 2.29E-04 | ||||||||||||||||||||
| Modified Cr = | 2.27E-05 | (Redundancy) | |||||||||||||||||||
| Due to the EOC Redundancy the Severity Classifications can be reduced Severity Classification III-1R | |||||||||||||||||||||
| Failure Effect at | Failure Detection Method | Compemsating Provisions | |||||||||||||||||||
| ID# | Function | Failure Mode Description | Failure Cause | Local Failure Effects | Next Higher Level Failure Effects | Major End Item Failure Effects | Safety | ||||||||||||||
| Consideration | Safety | ||||||||||||||||||||
| Impact | Operator Observation | Visual Indicator | C-Bit | ||||||||||||||||||
| Capabilities | Severity | ||||||||||||||||||||
| Classification | Alternate Design | ||||||||||||||||||||
| Modifications | Modified Severity | ||||||||||||||||||||
| Classification | β | βmod | α | λP | Cm | Mod Cm | |||||||||||||||
| 1 | AC Input for AC/DC Power supply which supplies 28VDC/200A service to the Shelter | No Output | Hardware Failure | Loss of Shelter DC Power Supply | Loss of DC Input Power to Shelter | Loss of Shelter | N/A | N/A | N/A | N/A | TBD | Category I | EOCs are Redundant | Category III-1R | 1.00 | 0.05 | 0.3571 | 1.92E-06 | 4.93E-05 | 2.46E-06 | |
| 2 | Provides 28VDC RTN for the AC/DC Power Supply which supplies 28VDC/200A service to the Shelter | No Output | Hardware Failure | Loss of Shelter DC Power Supply Return | Loss of DC Input Power to Shelter | Loss of Shelter | N/A | N/A | N/A | N/A | TBD | Category I | EOCs are Redundant | Category III-1R | 1.00 | 0.05 | 0.3571 | 1.92E-06 | 4.93E-05 | 2.46E-06 | |
| 3 | DC output of AC/DC Power Supply which supplies 28VDC/200A service to the Shelter | No Output | Hardware Failure | Loss of Shelter DC Power Supply | Loss of DC Input Power to Shelter | Loss of Shelter | N/A | N/A | N/A | N/A | TBD | Category I | EOCs are Redundant | Category III-1R | 1.00 | 0.05 | 0.3571 | 1.92E-06 | 4.93E-05 | 2.46E-06 | |
| 7 | DC output of AC/DC Power Supply which supplies 28VDC/200A service to the Shelter | Short | Hardware Failure | Loss of Shelter DC Power Supply | Loss of DC Input Power to Shelter | Loss of Shelter | N/A | N/A | N/A | N/A | TBD | Category I | EOCs are Redundant | Category III-1R | 1.00 | 0.05 | 0.1429 | 1.92E-06 | 1.97E-05 | 9.85E-07 | |
| 8 | DC output of AC/DC Power Supply which supplies 28VDC/200A service to the Shelter | No Output | Hardware Failure | Loss of Shelter DC Power Supply | Loss of DC Input Power to Shelter | Loss of Shelter | N/A | N/A | OB-001-01 | N/A | TBD | Category I | EOCs are Redundant | Category III-1R | 1.00 | 0.05 | 0.3571 | 1.92E-06 | 4.93E-05 | 2.46E-06 |
E001 Data
| W31P4Q-20-R-0015 | |||||||||||||||||||||
| ATTACHMENT 0010b.1 | |||||||||||||||||||||
| TAB 4 OF 4 | |||||||||||||||||||||
| Major End Item: | Shelter -Power | ||||||||||||||||||||
| Parent LRU: | E001 - 28 VDC Power Supply # 1 | ||||||||||||||||||||
| Component: | 28 VDC Power Supply | ||||||||||||||||||||
| Mission Phase-Operational Mode: | All Phases | ||||||||||||||||||||
| FPMH: | 10.000 | ||||||||||||||||||||
| t: | 72 | ||||||||||||||||||||
| Cr = ∑Cm = | 1.19E-03 | ||||||||||||||||||||
| Modified Cr = | 1.18E-04 | (Redundancy) | |||||||||||||||||||
| Due to the EOC Redundancy the Severity Classifications can be reduced Severity Classification III-1R | |||||||||||||||||||||
| Failure Effect at | Failure Detection Method | Compemsating Provisions | |||||||||||||||||||
| ID# | Function | Failure Mode Description | Failure Cause | Local Failure Effects | Next Higher Level Failure Effects | Major End Item Failure Effects | Safety | ||||||||||||||
| Consideration | Safety | ||||||||||||||||||||
| Impact | Operator Observation | Visual Indicator | C-Bit | ||||||||||||||||||
| Capabilities | Severity | ||||||||||||||||||||
| Classification | Alternate Design | ||||||||||||||||||||
| Modifications | Modified Severity | ||||||||||||||||||||
| Classification | β | βmod | α | λP | Cm | Mod Cm | |||||||||||||||
| 1 | AC Input for AC/DC Power supply which supplies 28VDC/200A service to the Shelter | No Output | Hardware Failure | Loss of Shelter DC Power Supply | Loss of DC Input Power to Shelter | Loss of Shelter | N/A | N/A | N/A | N/A | TBD | Category I | EOCs are Redundant | Category III-1R | 1.00 | 0.05 | 0.3571 | 1.00E-05 | 2.57E-04 | 1.29E-05 | |
| 2 | Provides 28VDC RTN for the AC/DC Power Supply which supplies 28VDC/200A service to the Shelter | No Output | Hardware Failure | Loss of Shelter DC Power Supply Return | Loss of DC Input Power to Shelter | Loss of Shelter | N/A | N/A | N/A | N/A | TBD | Category I | EOCs are Redundant | Category III-1R | 1.00 | 0.05 | 0.3571 | 1.00E-05 | 2.57E-04 | 1.29E-05 | |
| 3 | DC output of AC/DC Power Supply which supplies 28VDC/200A service to the Shelter | No Output | Hardware Failure | Loss of Shelter DC Power Supply | Loss of DC Input Power to Shelter | Loss of Shelter | N/A | N/A | N/A | N/A | TBD | Category I | EOCs are Redundant | Category III-1R | 1.00 | 0.05 | 0.3571 | 1.00E-05 | 2.57E-04 | 1.29E-05 | |
| 4 | DC output of AC/DC Power Supply which supplies 28VDC/200A service to the Shelter | Improper Output | Hardware Failure | Possible loss of Shelter DC Power Supply | Possible loss of DC Input Power to Shelter | Possible loss of Shelter | N/A | N/A | N/A | N/A | TBD | Category III | EOCs are Redundant | Category III | 0.05 | 0.05 | 0.1429 | 1.00E-05 | 5.14E-06 | 5.14E-06 | |
| 5 | DC output of AC/DC Power Supply which supplies 28VDC/200A service to the Shelter | Improper Voltage | Hardware Failure | Possible loss of Shelter DC Power Supply | Possible loss of Shelter DC Power Supply | Possible loss of Shelter DC Power Supply | N/A | N/A | N/A | N/A | TBD | Category III | EOCs are Redundant | Category III | 0.05 | 0.05 | 0.1429 | 1.00E-05 | 5.14E-06 | 5.14E-06 | |
| 6 | DC output of AC/DC Power Supply which supplies 28VDC/200A service to the Shelter | Intermittent Operation | Hardware Failure | Possible loss of Shelter DC Power Supply | Possible loss of Shelter DC Power Supply | Possible loss of Shelter DC Power Supply | N/A | N/A | N/A | N/A | TBD | Category III | EOCs are Redundant | Category III | 0.05 | 0.05 | 0.2143 | 1.00E-05 | 7.71E-06 | 7.71E-06 | |
| 7 | DC output of AC/DC Power Supply which supplies 28VDC/200A service to the Shelter | Short | Hardware Failure | Loss of Shelter DC Power Supply | Loss of DC Input Power to Shelter | Loss of Shelter | N/A | N/A | N/A | N/A | TBD | Category I | EOCs are Redundant | Category III-1R | 1.00 | 0.05 | 0.1429 | 1.00E-05 | 1.03E-04 | 5.14E-06 | |
| 8 | DC output of AC/DC Power Supply which supplies 28VDC/200A service to the Shelter | No Output | Hardware Failure | Loss of Shelter DC Power Supply | Loss of DC Input Power to Shelter | Loss of Shelter | N/A | N/A | OB-001-01 | N/A | TBD | Category I | EOCs are Redundant | Category III-1R | 1.00 | 0.05 | 0.3571 | 1.00E-05 | 2.57E-04 | 1.29E-05 | |
| 9 | DC output of AC/DC Power Supply which supplies 28VDC for Status Lines. | No Output | Hardware Failure | Loss of AC/DC Status | Loss of AC/DC Status | Possible delay in starting a mission | N/A | N/A | N/A | N/A | TBD | Category III | EOCs are Redundant | Category III | 0.05 | 0.05 | 0.3571 | 1.00E-05 | 1.29E-05 | 1.29E-05 | |
| 10 | DC output of AC/DC Power Supply which supplies 28VDC for Status Lines. | Improper Output | Hardware Failure | Possible Loss of AC/DC Status | Possible Loss of AC/DC Status | Possible delay in starting a mission | N/A | N/A | N/A | N/A | TBD | Category III | EOCs are Redundant | Category III | 0.05 | 0.05 | 0.1429 | 1.00E-05 | 5.14E-06 | 5.14E-06 | |
| 11 | DC output of AC/DC Power Supply which supplies 28VDC for Status Lines. | Improper Voltage | Hardware Failure | Probable Loss of AC/DC Status | Probable Loss of AC/DC Status | Possible delay in starting a mission | N/A | N/A | N/A | N/A | TBD | Category III | EOCs are Redundant | Category III | 0.05 | 0.05 | 0.1429 | 1.00E-05 | 5.14E-06 | 5.14E-06 | |
| 12 | DC output of AC/DC Power Supply which supplies 28VDC for Status Lines. | Intermittent Operation | Hardware Failure | Probable Loss of AC/DC Status | Probable Loss of AC/DC Status | Possible delay in starting a mission | N/A | N/A | N/A | N/A | TBD | Category III | EOCs are Redundant | Category III | 0.05 | 0.05 | 0.2143 | 1.00E-05 | 7.71E-06 | 7.71E-06 | |
| 13 | DC output of AC/DC Power Supply which supplies 28VDC for Status Lines. | Short | Hardware Failure | Loss of AC/DC Status | Loss of AC/DC Status | Possible delay in starting a mission | N/A | N/A | N/A | N/A | TBD | Category III | EOCs are Redundant | Category III | 0.05 | 0.05 | 0.1429 | 1.00E-05 | 5.14E-06 | 5.14E-06 | |
| 14 | DC output of AC/DC Power Supply which supplies 28VDC for Status Lines. | Intermittent Operation | Hardware Failure | Loss of AC/DC Status | Loss of AC/DC Status | Possible delay in starting a mission | N/A | N/A | N/A | N/A | TBD | Category III | EOCs are Redundant | Category III | 0.05 | 0.05 | 0.2143 | 1.00E-05 | 7.71E-06 | 7.71E-06 |