ATT_B_E0.00.pdf

PDF 2 MB Posted

Attached to
OCYCF Med/Dental Remodel
Solicitation number
S-DASOBO-00001428
Issued by
Lake County, Albany City, Oregon

About this file

This document contains information related to a state and local government contract opportunity for the OCYCF Med/Dental Remodel project in Marion County and the City of Salem, Oregon. The project involves demolition, electrical, and lighting work for the remodel of an existing facility. The document provides detailed specifications, drawings, and schedules for the electrical and lighting systems. It includes general notes, abbreviations, legends, demolition plans, lighting plans, power plans, an electrical one-line diagram, and equipment schedules. The contract opportunity is being issued by the Oregon Youth Authority.

The document does not provide specific details on pricing terms, set asides, incumbents, funding requirements and sources, or other commercial terms. It appears to be focused on the technical specifications and requirements for the electrical and lighting work to be performed as part of the overall remodel project.

View the file

Other files

File Type Posted
Questions and Answers.pdf PDF
ATT_B_G0.01.pdf PDF
Pre_Bid_Conference_Attendance.pdf PDF
E0.02-ELECTRICAL_LIGHTING_SCHEDULES.pdf PDF
S-DASOBO-00001190 Addendum 1.pdf PDF
Bid Tabulation.jpg JPG image
ATT_B_M0.00.pdf PDF
S-DASOBO-00001190 Addendum 2.pdf PDF
ATT_B_P0.00.pdf PDF
A5.01-INTERIOR_ELEVATIONS~1.pdf PDF
2021200020_G1_Notice of Award.pdf PDF
Vendor Pricing.pdf PDF
ATT_B_S1.10.pdf PDF
Exhibit_7 Oregon Youth Authority Facility Access agreements.pdf PDF
_EO21-29_Form.pdf PDF
ATT A_Specs.pdf PDF
S-DASOBO-00001190_OCYCF MedDental Remodel.pdf PDF
Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A. THE EXISTING CONDITIONS SHOWN WERE TAKEN FROM AVAILABLE RECORD INFORMATION. FIELD VERIFY ALL CONDITIONS THAT MAY AFFECT CONSTRUCTION. IF ANY DISCREPANCIES ARE DISCOVERED, NOTIFY THE

ENGINEER IN WRITING AND REQUEST DIRECTION PRIOR TO COMMENCING WORK.

B. EXISTING LIGHT FIXTURES SHALL BE CAREFULLY REMOVED (DO NOT DAMAGE) AND RETURNED TO THE OWNER.

C. ANY AND ALL EQUIPMENT HAVING ELECTRICAL CONNECTIONS THAT REQUIRE DISCONNECTING AND/OR RE- CONNECTING AS A RESULT OF CONSTRUCTION SHALL BE INCLUDED AS A PART OF THIS CONTRACT.

D. THE EXISTING ELECTRICAL DEVICES, CONDUIT, AND/OR EQUIPMENT THAT FOR ANY REASON OBSTRUCTS CONSTRUCTION SHALL BE RELOCATED UNLESS OTHERWISE NOTED. LOCATION IS TO BE AS CLOSE AS

POSSIBLE TO THE ORIGINAL LOCATION.

E. ALL CIRCUITS, CONDUIT AND WIRE THAT ARE NOT TO REMAIN IN SERVICE SHALL BE REMOVED BACK TO THE FIRST ACCESSIBLE JUNCTION BOX WHERE IT SHALL BE TIED OFF AND LABELED AS SPARE WITH CIRCUIT

NUMBER INDICATED.

F. REMOVE ALL ABANDONED WIRE AND CABLING.

DEMOLITION NOTES:

1. SYMBOLS LEGENDS ARE PROVIDED FOR REFERENCE PURPOSES ONLY. THE SYMBOLS REPRESENT THE TYPE OF DEVICES THAT MAY BE REQUIRED IN THE WORK; QUANTITIES AND LOCATIONS ARE AS SHOWN ON THE PLAN

SHEETS.

2. PROVIDE 3/4" CONDUIT & #12 CONDUCTORS UNLESS NOTED OTHERWISE. PROVIDE ONE NEUTRAL CONDUCTOR FOR EACH UNGROUNDED CONDUCTOR OF SINGLE PHASE LINE-NEUTRAL BRANCH CIRCUITS. DO NOT SHARE

NEUTRAL CONDUCTORS.

3. EACH FEEDER AND BRANCH CIRCUIT CONDUIT SHALL HAVE AN EQUIPMENT GROUNDING CONDUCTOR SIZED

IN ACCORDANCE WITH NFPA 70, ARTICLE 250.

4. ALL ELECTRICAL EQUIPMENT IN PORTIONS OF THE BUILDING NOT BEING REMODELED SHALL BE LEFT IN

WORKING CONDITION. RESTORE ANY CIRCUITS INTERRUPTED.

5. ALL NEW LIGHT FIXTURES AND FIXTURES IN AREAS ADJACENT DEMOLITION & CONSTRUCTION AREAS ARE TO

BE THOROUGHLY CLEANED IMMEDIATELY PRIOR TO NOTICE OF SUBSTANTIAL COMPLETION.

6. THE FOLLOWING IS PART OF THIS PROJECT AND ALL COSTS PERTAINING THERETO SHALL BE INCLUDED IN THE

BASE BID:

A. NEW ELECTRICAL EQUIPMENT AND APPARATUS SHALL BE COORDINATED AND CONNECTED INTO THE

EXISTING SYSTEM AS REQUIRED.

B. POWER WIRING AND CABLE INSTALLATIONS SHALL BE CONCEALED ABOVE ACCESSIBLE CEILINGS AND IN

WALLS. EXPOSED WIRING SHALL BE INSTALLED IN APPROVED SURFACE METAL RACEWAY WHERE

INDICATED.

C. WHERE EXISTING CONDUITS ARE INDICATED FOR REUSE, FIELD VERIFY INTEGRITY OF REUSED RACEWAYS PRIOR TO INSTALLATION OF CONDUCTORS. PROVIDE NEW RACEWAYS WHERE EXISTING ARE UNUSABLE.

D. LOCATIONS OF ALL WALL MOUNTED DEVICES SUCH AS SWITCHES, RECEPTACLE, AND OUTLETS ARE SHOWN DIAGRAMMATICALLY. VISIT THE SITE TO CONFIRM EXACT DEVICE LOCATIONS AND COORDINATE

INSTALLATIONS WITH FIXED CASEWORK, DOORS AND RELITES.

E. PROVIDE PENETRATIONS THROUGH WALLS, FLOORS, AND CEILINGS AS REQUIRED. PROVIDE SUITABLE FIRE RATED MATERIALS AND SEAL ALL CEILING, FLOOR, AND WALL PENETRATIONS TO MATCH FIRE RATING

OF SURFACES PENETRATED.

GENERAL NOTES:

1. LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS ZONED ON THE LIGHTING PLANS. SWITCHING AND

DIMMING ZONES ARE INDICATED ADJACENT TO EACH FIXTURE.

2. MANUAL CONTROLS SHALL ALLOW OCCUPANTS TO UNIFORMLY REDUCE ILLUMINATION LEVELS AT LEAST 50%.

EXCEPTION: CORRIDORS, RESTROOMS, LOBBIES, MECHANICAL, ELECTRICAL, AND INFORMATION TECHNOLOGY

(IDF) ROOMS CONTROLLED BY OCCUPANCY SENSORS.

3. EACH AREA THAT IS REQUIRED TO HAVE A MANUAL CONTROL SHALL ALSO HAVE AUTOMATIC TIME SWITCH CONTROL. PROVIDE TIMED OVERRIDE SWITCHES THAT WILL SERVE A MAXIMUM AREA OF 2500 SF IN LOCATIONS

SHOWN ON PLANS.

4. EXCEPTIONS:

A. EMERGENCY EGRESS LIGHTING CONTROLLED BY OCCUPANCY SENSORS.

B. LIGHTING IN SPACES CONTROLLED BY OCCUPANCY SENSORS.

5. LUMINAIRES PROVIDING MEANS OF EGRESS ILLUMINATION AND HAVING BOTH NORMAL AND EMERGENCY POWER SOURCES SHALL BE CONTROLLED BY A COMBINATION OF U.L. 924 LISTED EMERGENCY RELAYS AND OCCUPANCY SENSORS THAT ENABLES THE LIGHTING TO BE SHUT OFF WHEN THE AREAS SERVED ARE UNOCCUPIED AND AUTOMATICALLY ILLUMINATES IN THE EVENT OF NORMAL POWER SOURCE FAILURE.

6. THE MAXIMUM LIGHTING POWER THAT MAY BE CONTROLLED FROM A SINGLE SWITCH OR AUTOMATIC CONTROL SHALL NOT EXCEED THAT WHICH IS PROVIDED BY A 20 AMPERE CIRCUIT LOADED TO NOT MORE THAN 80

PERCENT.

7. PROVIDE FUNCTIONAL TESTING OF AUTOMATIC LIGHTING CONTROLS. SUBMIT WRITTEN PROCEDURES FOR FUNCTIONAL TESTING OF ALL AUTOMATIC CONTROLS WITH DESCRIPTION OF THE EXPECTED SYSTEM

RESPONSE.

LIGHTING NOTES:

@ AT

A/C AIR CONDITIONING(ER)

A (AMP) AMPERE

AC ABOVE COUNTER, ALTERNATING

CURRENT

ADJ ADJUSTABLE

ADJT ADJACENT

AFF ABOVE FINISHED FLOOR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERES INTERRUPTING CAPACITY

ALT ALTERNATE

ANN ANNUNCIATOR

ARCH ARCHITECT; ARCHITECTURAL

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AWG AMERICAN WIRE GAUGE

BKBD BACKBOARD

BKR BREAKER

BLDG BUILDING

C CONDUIT

CAP CAPACITY

CB CIRCUIT BREAKER

CKT CIRCUIT

CLG CEILING

CLR CLEAR

COL COLUMN

COM COMMUNICATION

CPS CYCLES PER SECOND

CT CURRENT TRANSFORMER

CTL CONTROL

CU COPPER

DC DIRECT CURRENT

DISC SW DISCONNECT SWITCH

DISC DISCONNECT

DN DOWN

DWG DRAWING

E EXIST, EAST

EDH ELECTRIC DUCT HEATER

EF EXHAUST FAN

EGC EQUIPMENT GROUNDING CONDUCTOR

EL ELEVATION

ELEC ELECTRIC(AL)

ELEV ELEVATOR

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

ENTR ENTRANCE

EP EXPLOSION PROOF

EPO EMERGENCY POWER OFF

EQUIP/EQP EQUIPMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXH EXHAUST

EXT EXTERIOR

EXIST EXISTING

F FAHRENHEIT/FUSE

FA FIRE ALARM

FAA FIRE ALARM ANNUNCIATOR

FAP FIRE ALARM PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FD FIRE DAMPER

FDR FEEDER

FIXT FIXTURE

FLA FULL LOAD AMPS

FSD FIRE/SMOKE DAMPER

GEC GROUNDING ELECTRODE CONDUCTOR

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GFR GROUND FAULT RELAY

H HEIGHT

HOA HAND OFF AUTOMATIC

HOR HORIZONTAL

HP HORSEPOWER

HR HOUR

HT HEIGHT

HW HOT WATER

HZ HERTZ

IBC INTERNATIONAL BUILDING CODE

IC INTERCOM

IES ILLUMINATING

IEEE INSTITUTE OF ELECTRICAL AND

ELECTRONIC ENGINEERS

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IN INCH

JB JUNCTION BOX

KCMIL THOUSAND CIRCULAR MILLS

KVA KILOVOLT AMPERES

KVAR KILOVOLT AMPERES REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LBS POUNDS

LF LINEAR FEET (FEET)

LRA LOCKED ROTOR AMPS

LS LIFE SAFETY

LT LIGHT

LTG LIGHTING

LV LOW VOLTAGE

ABBREVIATIONS

MAG MAGNETIC

MAN MANUAL

MAT MATERIAL

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MECH MECHANICAL

MEZZ MEZZANINE

MG MOTOR GENERATOR

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUG ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

MS MAGNETIC STARTER

MTD MOUNTED

MTG MOUNTING

MTR MOTOR

N NORTH; NEUTRAL

N/A NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRIC MANUFACTURERS

ASSOCIATION

NESC NATIONAL ELECTRICAL SAFETY CODE

NEUT NEUTRAL

NFPA NATIONAL FIRE PROTECTION ASSOC.

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED CONTRACTOR

INSTALLED

OFOI OWNER FURNISHED OWNER INSTALLED

OL OVERLOAD

OS OPTIONAL STANDBY

P PRIMARY

PA PUBLIC ADDRESS

PAR PARALLEL

PB PULL BOX

PE PHOTO ELECTRIC

PF POWER FACTOR

PH PHASE

PIV POST INDICATOR VALVE

PNL PANEL

POC POINT OF CONNECTION

PWR POWER

QTY QUANTITY

R (R) RELOCATE (D)

RAD RADIUS

RECPT RECEPTACLE

REF REFRIGERATOR

RLA RATED LOAD AMPS

RPM REVOLUTIONS PER MINUTE

S SOUTH

SC SECURITY

SD SMOKE DETECTOR

SECT SECTION

SF SUPPLY FAN

SHT SHEET

SPEC SPECIFICATION

SPL SPECIAL

SQ SQUARE

STOR STORAGE

SPD SURGE PROTECTION DEVICE

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

T THERMOSTAT

TB TERMINAL BOX

TC TIME CLOCK

TEL TELEPHONE

TV TELEVISION

TYP TYPICAL

UFC UNIFORM FIRE CODE

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITERS LABORATORIES

UON UNLESS OTHERWISE NOTED

UV UNIT VENTILATOR

V VOLT

VAV VARIABLE AIR VOLUME

VEL VELOCITY

VM VOLTMETER

VOL VOLUME

W WATT, WEST

W/ WITH

W/O WITHOUT

WH WATER HEATER

WHM WATTHOUR METER

WP WEATHERPROOF

(X) EXISTING TO BE REMOVED

XFMR TRANSFORMER

XMTR TRANSMITTER

Z IMPEDANCE

& AND

IE: THAT IS

1. SYSTEM CABLING PATHWAYS SHALL BE INSTALLED IN ACCORDANCE WITH THE MOST CURRENT VERSION OF

TIA-569.

2. J-HOOKS SHALL NOT BE PLACED MORE THAT 5' APART.

3. IF A CABLE PATH WILL EXCEED 295', INFORM THE ICT ENGINEER IMMEDIATELY BEFORE INSTALLATION.

4. PROVIDE (1) 2' CONDUIT SLEEVE FOR PENETRATION INTO OFFICES, ETC. FOR CABLING PATHWAYS.

5. ALL PENETRATIONS MUST BE FIRE-STOPPED IN ACCORDANCE OF THE NFPA, NEC AND TO THE SATISFACTION

OF THE AHJ.

STRUCTURED CABLE SYSTEM PATHWAY NOTES:

PROJECT NO.:

ISSUE DATE:

REVISIONS:

C

LA

R K

K

JO

S A

R C

H

IT

E C

T S

LL

C

O

P Y

R

IG

H T

S W

A ld er S t., S ui te

P or tla nd

, O R

P ho ne

: 5

/2

-4

111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204

Tel 503.416.2400 Fax 206.267.1701

SAZAN# 257-20047

/2

/2

:3

:2

A

M

GENERAL NOTES,

ABBREVIATIONS AND

SHEET INDEX

04.02.21

E0.00

IS

S

U E

D F

O R

P E

R M

IT

20018

O A

K C

R E

E K

E X

P A

N S

IO

N

L O

C H

N E

R R

D S

E A

L B

A N

Y

O R

O R

E G

O N

Y O

U T

H A

U T

H O

R

IT

Y

ELECTRICAL SHEET INDEX

E0.00 GENERAL NOTES, ABBREVIATIONS AND SHEET INDEX

E0.01 ELECTRICAL LEGEND

E0.02 ELECTRICAL LIGHTING SCHEDULES

E0.03 ELECTRICAL SCHEDULES

ED2.01 LIGHTING DEMOLITION - FLOOR PLAN

ED3.01 ELECTRICAL DEMOLITION - FLOOR PLAN

E1.01 LIGHTING - FLOOR PLAN

E2.01 ELECTRICAL - FLOOR PLAN

E2.02 ELECTRICAL - ROOF PLAN

E6.00 ELECTRICAL ONE-LINE DIAGRAM

Expires: 12/31/2021

J

OS

OS

OS

PC

ESR

F

S

S

AIM

AOM

ISOIM

R

S

S Z

NCCP

NCMA

NCMN

XXXX

CR

WP

K

WP

MD

ES

DC

REX

A

BG

X-XX-X

T

M

MM

AM

SYMBOLS LEGEND - POWER

DESCRIPTIONSYMBOL

TRANSFORMER

S2

AS

POLE-MOUNTED TRANSFORMER

POLE

DELTA

WYE

MEDIUM VOLTAGE CABLE TERMINATOR

LIGHTNING ARRESTORS

SURGE ARRESTORS

NEUTRAL GROUNDING RESISTOR

METER

MICROPROCESSOR CONTROLLED MONITOR

REFER TO SPECIFICATIONS FOR METERING VALUES AND

PROTECTIVE FUNCTIONS

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

INDICATING INSTRUMENT

AM-AMMETER; VM-VOLTMETER; FM-FREQUENCY METER;

kVAR-KILOVAR METER; kWH-KILOWATT HOUR METER;

kWH/D-KILOWATT HOUR DEMAND METER

INSTRUMENT SWITCH

AS-AMMETER SWITCH; VS-VOLTMETER SWITCH;

SS-SYNCHRONIZING SWITCH;

SV-SUPERVISORY (LOCAL-REMOTE) SWITCH

SEPARABLE CONNECTOR

DRAWOUT AC TYPE POWER CIRCUIT BREAKER

SYMBOLS LEGEND - POWER

DESCRIPTIONSYMBOL

M

C

G

M

M

SD

M

FSD

M

2-POSITION SELECTOR SWITCH

3-POSITION SELECTOR SWITCH HAND-OFF-AUTOMATIC

ON-OFF SELECTOR SWITCH

2-CIRCUIT PUSHBUTTON

PUSHBUTTON SWITCH MOMENTARY CONTACT

EQUIPMENT CONNECTION

GENERATOR

MOTOR CONNECTION

SMOKE DAMPER

FIRE SMOKE DAMPER

STARTER 3-POLE, NEMA SIZE 1 MINIMUM UNLESS NOTED OTHERWISE

COMBINATION STARTER

HP RATED, 3-POLE, NEMA SIZE 1 MINIMUM, UNLESS NOTED

OTHERWISE - OVERCURRENT PROTECTION AS REQUIRED BY

EQUIPMENT MANUFACTURER OR AS NOTED

DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

CONTACTOR

RELAY COIL

CR-CONTROL RELAY; TD-TIME DELAY RELAY;

UV-UNDERVOLTAGE RELAY; M-MOTOR

CONTACTOR;

MOTOR-RATED SWITCH - SIZE OL PER MOTOR REQUIREMENTS

EQUIPMENT EMERGENCY SHUTDOWN SWITCH

3-POLE UNLESS NOTED OTHERWISE

SYMBOLS LEGEND - POWER

DESCRIPTIONSYMBOL

ST

CB

G

G

SV

M

A

M

G

CIRCUIT BREAKER

ST - INDICATES SHUNT TRIP

BREAKER WITH EXTERNAL GROUND FAULT RELAY AND CT

CIRCUIT BREAKER WITH GROUND FAULT PROTECTION

MOTOR-OPERATED CIRCUIT BREAKER

SWITCH WITH EXTERNAL GROUND FAULT RELAY AND CT

MOV SURGE PROTECTION

RESISTOR

FUSE

MOTOR THERMAL OVERLOADS - (3) UNLESS OTHERWISE NOTED

NORMALLY OPEN CONTACT

NORMALLY CLOSED CONTACT

SOLENOID VALVE

MOTOR-OPERATED VALVE

TERMINAL BLOCK

THERMOSTAT

INDICATING LIGHT - TYPE AS NOTED

A-AMBER; B-BLUE; G-GREEN; R-RED; W-WHITE

BATTERY

T 65°

SYMBOLS LEGEND - GENERAL

DESCRIPTIONSYMBOL

UG

LV

A-1,3,5

PB

HH

MH

MINIMUM 3/4" CONDUIT CONCEALED IN CEILING SPACE OR IN WALL

MINIMUM 3/4" WITH #12 AWG CONDUCTORS WITH DEDICATED NEUTRAL

EACH CIRCUIT, UNLESS OTHERWISE NOTED ON PLAN. PROVIDE

EQUIPMENT GROUNDING CONDUCTORS SIZED PER NFPA 70.

CONDUIT - CONCEALED IN OR UNDER FLOOR

CONDUIT - ROUTED UNDERGROUND

LOW-VOLTAGE WIRING (CLASS B)

CONDUIT OR CABLE VERTICAL DOWN

CONDUIT OR CABLE VERTICAL UP

CONDUIT STUB - TERMINATE WITH BUSHING OR CAP IF UNDERGROUND

BREAK LINE

CONDUIT SEAL

EXPANSION FITTING

CABLE TRAY

CONDUCTORS - CONNECTED

CONDUCTORS - NOT CONNECTED

JUNCTION BOX

PULLBOX - SIZE AS INDICATED OR AS REQUIRED BY CODE

HANDHOLE

MANHOLE

FLEXIBLE METAL CONDUIT

BRANCH CIRCUIT NUMBERS

PANEL DESIGNATION

HOME RUN TO SOURCE OF SUPPLY

SYMBOLS LEGEND - POWER

DESCRIPTIONSYMBOL

XX

XXXXXX

SYMBOLS LEGEND - GROUNDING

DESCRIPTIONSYMBOL

480Y/277V, 3Ø, 4W PANELBOARD

208Y/120V, 3Ø, 4W PANELBOARD

EQUIPMENT CABINET - TYPE AS NOTED

PANELBOARD

TRANSFER SWITCH ( AUTO )

AMPERES SHORT CIRCUIT AVAILABLE (SYMMETRICAL)

FEEDER TAG - REFER TO FEEDER SCHEDULE

GROUND CONNECTION

GROUND ROD

GROUND WELL

AIR TERMINAL

SYMBOLS LEGEND - WIRING DEVICES

DESCRIPTIONSYMBOL

SINGLE-POLE WALL SWITCH MOUNT SWITCHES AT 48" AFF. TO CL, UON.

TT

IGIG

T T

WALL SWITCH - SUBSCRIPT

SPECIAL PURPOSE RECEPTACLE TYPE AS SHOWN ON PLANS

SINGLE SERVICE OR COMBINATION FLUSH FLOOR POKE THRU. REFER TO

FLOOR PLANS FOR DEVICES.

POWER/COMM POLE - FLOOR TO CEILING.

SURFACE MOUNTED FLOOR BOX (PEDESTAL TYPE).

PUSH BUTTON

SIMPLEX RECEPTACLE NEMA 5-20R, +18" AFF UON

NEMA 5-20R, +18" AFF UON

TAMPER RESISTANT, NEMA 5-20R, +18" AFF UON

ISOLATED GROUND, NEMA 5-20R, +18" AFF UON

NEMA 5-20R W/ GROUND FAULT CIRCUIT INTERRUPTER, +18" AFF UON

SPLIT WIRED, NEMA 5-20R, +18" AFF UON

CONTROLLED, NEMA 5-20R, +18" AFF UON

NEMA 5-20R, ABOVE COUNTER, +18" AFF UON

NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER, ABOVE

COUNTER. COORDINATE WITH CASEWORK SHOP DRAWINGS AND

ARCHITECTURAL DRAWINGS.

TAMPER RESISTANT, NEMA 5-20R WITH GROUND FAULT CIRCUIT

INTERRUPTER, ABOVE COUNTER. COORDINATE WITH CASEWORK SHOP

DRAWINGS AND ARCHITECTURAL DRAWINGS.

NEMA 5-20R, CONNECTED TO EMERGENCY CIRCUIT, +18" AFF UON

NEMA 5-20R MOUNTED ABOVE COUNTER. COORDINATE WITH CASEWORK

SHOP DRAWINGS AND ARCHITECTURAL DRAWINGS.

CEILING-MOUNTED, NEMA 5-20R

2 = 2-POLE

3 = 3-WAY

4 = 4-WAY

K = KEYED

LV = LOW-VOLTAGE

OS = OCCUPANCY SENSOR TYPE

OP = OCCUPANCY/PHOTOELECTRIC TYPE

WP = WEATHERPROOF

LOWER CASE LETTER INDICATES SWITCHING GROUP

MOUNT SWITCHES AT +48" AFF. TO CL, UON. ANY COMBINATION OF

SWITCH TYPES CAN BE USED (IE. 3K = 3-WAY KEYED SWITCH)

SYMBOLS LEGEND - LIGHTING

DESCRIPTIONSYMBOL

TC

SB

PP

ICS1-1

OS

PC

1x4 LUMINAIRE

2x2 LUMINAIRE

UNDER-CABINET LUMINAIRE

TRACK LIGHT - LENGTH AS INDICATED ON PLANS

NUMBER OF LUMINAIRES AS SHOWN

POLE-MOUNTED LUMINAIRE - NUMBER OF LUMINAIRES AS

SHOWN ON PLANS

IN-GROUND LANDSCAPE LUMINAIRE

TIME CLOCK - TYPE AS NOTED

LIGHTING CONTROL SYSTEM POWER PACK

SWITCH BYPASS DEVICE

ILLUMINATION CONTROL STATION

OCCUPANCY SENSOR CEILING MOUNTED WITH POWER PACK - DUAL

TECHNOLOGY TYPE UNLESS NOTED:

U = ULTRASONIC

U

P

OCCUPANCY SENSOR WALL MOUNTED

P = PASSIVE INFRARED

PHOTOELECTRIC CONTROL WALL MOUNTED

SYMBOLS LEGEND - FIRE ALARM

DESCRIPTIONSYMBOL

FIRE ALARM SYSTEM CONTROL PANEL

SINGLE SERVICE OR COMBINATION FLUSH MOUNTED FLOOR BOX. REFER

TO FLOOR PLANS FOR DEVICES.

NEMA 5-20R WITH USB CHARGER - (2) TYPE A USB PORTS

TAMPER RESISTANT, NEMA 5-20R WITH USB CHARGER - (2) TYPE A USB PORTST

F

XX

S

XX

XX

XX

F

PIV

VS

PS

FS

SD

SD

FIRE ALARM FLOW SWITCH

HI/LO AIR PRESSURE SWITCH

VALVE SUPERVISORY SWITCH

POST INDICATOR VALVE SUPERVISORY SWITCH

FIRE ALARM PULL STATION

FIRE/SMOKE DAMPER

SMOKE DAMPER

FIRE ALARM HORN ONLY

FIRE ALARM HORN STROBE

FIRE ALARM SPEAKER ONLY

FIRE ALARM SPEAKER STROBE

FIRE ALARM STROBE ONLY - WALL

FIRE ALARM STROBE ONLY - CEILING

FIRE ALARM BELL

FIRE FIGHTER PHONE JACK

HEAT DETECTOR

SMOKE DETECTOR

FIRE ALARM DUCT SMOKE DETECTOR WITH SAMPLING TUBE

FLAME DETECTOR

GAS DETECTOR

ADDRESSABLE INPUT MODULE

ADDRESSABLE OUTPUT MODULE

ISOLATION MODULE

FIRE ALARM EQUIPMENT CONNECTION

RELAY BLOCK

ESR - ELEVATOR STATUS/RECALL

FAC - FIRE ALARM COMMUNICATOR

FACP - FIRE ALARM CONTROL PANEL

FAA OR FARA - FIRE ALARM ANNUNCIATOR

HVA - HVAC OR EXHAUST STAIRWELL PRESSURIZATION

LCD - FIRE ALARM LCD ANNUNCIATOR

F - FIXED TEMPERATURE

R - RATE OF RISE ONLY

R/C - RATE COMPENSATION

R/F - RATE OF RISE AND FIXED TEMPERATURE

BT - BEAM TRANSMITTER

BR - BEAM RECEIVER

I - IONIZATION

P - PHOTOELECTRIC

SYMBOLS LEGEND - AUDIO VISUAL / CLOCK

DESCRIPTIONSYMBOL

TV

S

S a a

TV OUTLET

a a

PAGING SYSTEM SPEAKER - CEILING RECESSED MOUNTED. LOWER CASE

DENOTES ZONE GROUP (TYP.)

PAGING SYSTEM SPEAKER - CEILING SURFACE MOUNTED. LOWER CASE

DENOTES ZONE GROUP (TYP.)

PAGING SYSTEM SPEAKER - WALL RECESSED MOUNTED. LOWER CASE

DENOTES ZONE GROUP (TYP.)

PAGING SYSTEM SPEAKER - WALL SURFACE MOUNTED. LOWER CASE

DENOTES ZONE GROUP (TYP.)

CLOCK - WALL SURFACE MOUNTED

CLOCK - RECESSED MOUNTED

SYMBOLS LEGEND - NURSE CALL

DESCRIPTIONSYMBOL

NURSE CALL CONTROL EQUIPMENT PANEL

E

CB

E

D

S

L

WP

A

MES

MES

NURSE CALL MASTER STATION - AUDIO

NURSE CALL MASTER STATION - NON AUDIO

ZONE DOME LIGHT, CEILING MOUNTED (NUMBER DENOTES ZONE)

DOME LIGHT, CEILING MOUNTED

DOME LIGHT, WALL MOUNTED

MEDICAL EMERGENCY STATION (MES)

CODE BLUE STATION

DUTY STATION

STAFF STATION

IN/OUT PUSH BUTTON

TOILET PULL STATION

SHOWER PULL STATION

NURSE CALL ANNUNCIATOR

SINGLE PATIENT STATION (PS)

SINGLE PATIENT STATION (PS) WITH EMERGENCY CALL BUTTON

DUAL PATIENT STATION (PS)

DUAL PATIENT STATION (PS) WITH EMERGENCY CALL BUTTON

SYMBOLS LEGEND - COMMUNICATIONS

DESCRIPTIONSYMBOL

COMMUNICATIONS - OUTLET

(# = REPRESENTS THE NUMBER OF COMMUNICATION PORTS. (IE 1,2,3))

(W = SINGLE COMMUNICATIONS PORT WALL MOUNTED AT +48" AFF.)

(P = PAYPHONE, WALL MOUNTED AT +48" AFF)

XX

D

M

D

INTERCOM - OUTLET

(D = DESK MOUNTED)

(W = WALL MOUNTED AT +48" AFF.)

COMMUNICATIONS - MICROPHONE

(D = DESK MOUNTED)

(W = WALL MOUNTED AT +48" AFF.)

COMPUTER NETWORK WIRELESS ACCESS POINT - CEILING MOUNTED

COMMUNICATIONS - PAINTED FIRE RESISTANT 3/4" PLYWOOD

BACKBOARD

19" COMMUNICATIONS RACK - FLOOR MOUNTED

19" COMMUNICATIONS RACK - WALL MOUNTED

SYMBOLS LEGEND - GENERAL

DESCRIPTIONSYMBOL

X-XX

X

XX.XX

X

XX.XX

X

XX.XX

N

DRAWING CONSTRUCTION ("FLAG") NOTE

EQUIPMENT IDENTIFIER

MATCHLINE

REVISION CLOUD (ENCIRCLES DRAWING CHANGES MADE SINCE THE

PREVIOUS RELEASE)

REVISION REFERENCE

EXISTING TO BE REMOVED (HATCH)

HEAVY LINEWEIGHT INDICATES NEW WORK

LIGHT LINEWEIGHT INDICATES EXISTING INFORMATION

POINT OF CONNECTION

DETAIL REFERENCE

DETAIL IDENTIFICATION NUMBER

SHEET WHERE DETAIL IS DRAWN

ELEVATION REFERENCE

ELEVATION IDENTIFICATION

NUMBER SHEET WHERE ELEVATION IS DRAWN

SECTION REFERENCE SECTION

IDENTIFICATION NUMBER

SHEET WHERE SECTION IS DRAWN

NORTH REFERENCE

SYMBOLS LEGEND - SECURITY

DESCRIPTIONSYMBOL

WP

WP

CARD READER. WP INDICATES WEATHERPROOF

KEYPAD. WP INDICATES WEATHERPROOF

MOTION DETECTOR - INFRARED TYPE UNLESS OTHERWISE NOTED

ELECTRIC DOOR STRIKE

DOOR/WINDOW CONTACT

REQUEST TO EXIT PUSHBUTTON

PANIC / DURESS BUTTON

ALARM BELL

BREAK GLASS SENSOR

CCTV CAMERA - FIXED TYPE. WP INDICATES WEATHERPROOF

CCTV CAMERA - PAN/TILT/ZOOM TYPE. WP INDICATES WEATHERPROOF

XX

SS SWITCHED RECEPTACLE, NEMA 5-20R, +18" AFF UON

3-POLE UNLESS NOTED OTHERWISE

L1 A - 1

Z-XXX-1

EM

LIGHT FIXTURE IDENTIFIER - REFER TO LUMINAIRE SCHEDULE

PANEL NAME - CIRCUIT NUMBER

SWITCH DESIGNATION - MIDDLE DIGITS REFER TO

ROOM NUMBER - END DIGITS REFER TO SWITCH LEG

SUBSCRIPT (IF APPLICABLE)

* IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: RL1 / A-1 / a / NL

SHADING INDICATES LUMINAIRE ON EMERGENCY CIRCUIT OR WITH

BATTERY BACKUP

2x4 LUMINAIRE

LINEAR LUMINARE

WALL WASH LUMINAIRE

STRIP LUMINAIRE

WALL MOUNTED LUMINAIRE

DOWNLIGHT

WALL WASH DOWNLIGHT LUMINAIRE

WALL MOUNTED LUMINAIRE

WALL MOUNTED DIRECTIONAL LUMINAIRE

PENDANT MOUNTED LUMINAIRE

STREET LIGHT

ILLUMINATED EXIT SIGN - SINGLE FACE ARROW INDICATES

DIRECTION OF EGRESS, UNIVERSAL MOUNT

ILLUMINATED EXIT SIGN - DOUBLE FACE ARROW INDICATES

DIRECTION OF EGRESS, UNIVERSAL MOUNT

BATTERY-POWERED EMERGENCY WALLPACK

COMBINATION BATTERY POWERED EMERGENCY WALLPACK

AND ILLUMINATED EXIT SIGN

PHOTOELECTRIC CONTROL CEILING MOUNTED

PROJECT NO.:

ISSUE DATE:

REVISIONS:

C

LA

R K

K

JO

S A

R C

H

IT

E C

T S

P Y

R

IG

H T

S W

A ld er S t., S ui te

P or tla nd

, O R

P ho ne

: 5

/2

-4

111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204

Tel 503.416.2400 Fax 206.267.1701

SAZAN# 257-20047

/2

/2

:3

:3

A

M

ELECTRICAL LEGEND

04.02.21

E0.01

IS

S

U E

D F

O R

P E

R M

IT

20018

O A

K C

R E

E K

E X

P A

N S

IO

N

L O

C H

N E

R R

D S

E A

L B

A N

Y

O R

O R

E G

O N

Y O

U T

H A

U T

H O

R

IT

Y

PROJECT NO.:

ISSUE DATE:

REVISIONS:

C

LA

R K

K

JO

S A

R C

H

IT

E C

T S

P Y

R

IG

H T

S W

A ld er S t., S ui te

P or tla nd

, O R

P h on e:

3/

4-

111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204

Tel 503.416.2400 Fax 206.267.1701

SAZAN# 257-20047

/2

/2

:3

:4

A

M

ELECTRICAL

SCHEDULES

04.02.21

E0.03

IS

S

U E

D F

O R

P E

R M

IT

20018

O A

K C

R E

E K

E X

P A

N S

IO

N

L O

C H

N E

R R

D S

E A

L B

A N

Y

O R

O R

E G

O N

Y O

U T

H A

U T

H O

R

IT

Y

HP-01 VRF HEAT PUMP 208 1 - - - 32.0 1" 2 8 10 2 50 - 60A

FCU-10 VRF FAN COIL 208 1 - - - 0.24. 3/4" 2 12 12 2 15 - 7

FCU-09 VRF FAN COIL 208 1 - - - 0.4 3/4" 2 12 12 2 15 - 7

FCU-08 VRF FAN COIL 208 1 - - - 0.4 3/4" 2 12 12 2 15 - 7

FCU-07 VRF FAN COIL 208 1 - - - .24. 3/4" 2 12 12 2 15 - 7

FCU-06 VRF FAN COIL 208 1 - - - .24. 3/4" 2 12 12 2 15 - 7

FCU-05 VRF FAN COIL 208 1 - - - .24. 3/4" 2 12 12 2 15 - 7

FCU-04 VRF FAN COIL 208 1 - - - .24. 3/4" 2 12 12 2 15 - 7

FCU-03 VRF FAN COIL 208 1 - - - .24. 3/4" 2 12 12 2 15 - 7

FCU-02 VRF FAN COIL 208 1 - - - 0.4 3/4" 2 12 12 2 15 - 7

FCU-01 VRF FAN COIL 208 1 - - - 0.24. 3/4" 2 12 12 2 15 - 7

ERV-01(H) AUXILLARY HEAT 208 3 - - - 5.5 3/4" 3 12 12 3 15 - 8

ERV-01 ENERGY RECOVER VENT UNIT 208 1 1.0 - - 13.9 3/4" 2 12 12 2 15 - 7

EDH-01 ELECTRIC DUCT HEATER 208 3 - 2.0 - 6.9 3/4" 3 12 12 3 15 - 8

BS-02 BRANCH SELECTOR BOX 208 1 - - - 2.0 3/4" 2 12 12 2 15 - 7

BS-01 BRANCH SELECTOR BOX 208 1 - - - 2.0 3/4" 2 12 12 2 15 - 7

NO. HP kW FLA SIZE NO. SIZE GND POLE AMPS SIZE SW

EQPT DESCRIPTION VOLTS PH LOAD MCA RCWY 75°C CU CONDUCTORS BREAKER STARTER DISC NOTES REMARKS

8. 208 VOLT, 3 POLE, 20A MOTOR RATED SWITCH

7. 208 VOLT, 2 POLE, 20A MOTOR RATED SWITCH

INSTALLED BY ELECTRICAL CONTRACTOR.

6. SPEED CONTROL FURNISHED BY MECHANICAL CONTRACTOR,

BY MECHANICAL CONTRACTOR, INSTALLED BY ELECTRICAL CONTRACTOR

5. SPEED CONTROL AND LINE VOLTAGE HEATING-ONLY THERMOSTAT FURNISHED W - WATTS

4. DIRECT CONNECTION MCA - MINIMUM CIRCUIT AMPACITY

3. FUSED DISCONNECT SWITCH C. FURNISHED AND INSTALLED UNDER DIVISION 26 kW - KILOWATTS

2. MANUAL STARTER B. FURNISHED BY OTHERS, INSTALLED UNDER DIVISION 26 HP - HORSEPOWER

1. COMBINATION STARTER A. FURNISHED AND INSTALLED BY OTHERS FLA - FULL LOAD AMPS

NOTES:

HVAC EQUIPMENT SCHEDULE

Notes:

Total Est. Demand Current: 92 A

Receptacle 13140 VA 88.05% 11570 VA Total Conn. Current: 95 A

Other 20205 VA 100.00% 20205 VA Total Est. Demand: 32978 VA

Mechanical 6 VA 100.00% 6 VA Total Conn. Load: 34296 VA

Lighting 996 VA 125.00% 1245 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 121 A 104 A 70 A

Total Load: 13978 VA 11898 VA 8448 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 DED RCPT - REFRIGERATOR - RM 110 20 A 1 180 VA 0 VA 1 20 A SPARE 38

35 RCP-1 20 A 1 124 VA 6 VA 1 20 A TPV-1 36

33 RCPT - FILE STORAGE 102 20 A 1 360 VA 360 VA 1 20 A ROOFTOP RECEPTS 34

31 LIGHTING 20 A 1 996 VA 662 VA -- -- -- -- 32

29 RCPT - EXAM 041 20 A 1 1080 VA 662 VA -- -- -- -- 30

27 RCPT - Room 112, 111, 100 20 A 1 900 VA 662 VA 3 15 A ERV-01 AUX HEAT 28

25 RCPT - MED EXAM 109 20 A 1 1080 VA 1446 VA -- -- -- -- 26

23 RCPT - MED EXAM 109 20 A 1 180 VA 1446 VA 2 15 A ERV-01 HEAT RECOV 24

21 RCPT - MED EXAM 109 20 A 1 1260 VA 835 VA -- -- -- -- 22

19 RCPT - Room 107, 113 20 A 1 540 VA 835 VA -- -- -- -- 20

17 RCPT - PSYCH OFFICE 106 20 A 1 540 VA 835 VA 3 20 A EDH-01 18

15 RCPT - PSYCH OFFICE 105 20 A 1 540 VA 716 VA -- -- -- -- 16

13 RCPT - DENTAL EXAM 104 20 A 1 180 VA 716 VA 2 20 A FCU-1,2,3,4,5,6,7,8,9,10,BS-1,2 14

11 RCPT - DENTAL EXAM 104 20 A 1 180 VA 1250 VA -- -- -- -- 12

9 RCPT - DENTAL EXAM 104 20 A 1 1080 VA 1250 VA 2 30 A WATER RECYCLER VACUUM 10

7 RCPT - Room 103, 104 20 A 1 1440 VA 1250 VA -- -- -- -- 8

5 RCPT - NURSE STATION 101 20 A 1 1080 VA 1250 VA 2 30 A COMPRESSOR 6

3 RCPT - NURSE STATION 101 20 A 1 720 VA 3328 VA -- -- -- -- 4

1 RCPT - W. GENERAL USE 20 A 1 1440 VA 3328 VA 2 50 A HP-01 2

C K T

# ITEM

N O T E

A M P S

P O L E A B C

P O L E

A M P S

N O T

E ITEM

C K T

MLO

225 A

A.I.C. RATING: 10,000A

EQUIPMENT GROUND BUS SKIRTS: NONE

GROUNDING: MOUNTING: RECESSED

FILE STORAGE 102 EDL TYPE: BOLT-ON

LOCATION: FED FROM: PANEL EDL VOLTAGE: 120/208 Wye 3-PH, 4-WIRE

NEW PANEL ELE SCHEDULE

Notes:

Mechanical 6 VA 100.00% 6 VA

Kitchen Equipment - Non-Dwelling Unit 75605 VA 65.00% 49143 VA

Equipment 3000 VA 100.00% 3000 VA

Receptacle 70088 VA 57.13% 40044 VA Total Est. Demand Current: 497 A

Power 21600 VA 100.00% 21600 VA Total Conn. Current: 638 A

Other 20403 VA 100.00% 20403 VA Total Est. Demand: 179130 VA

Lighting 23456 VA 125.00% 29320 VA Total Conn. Load: 229769 VA

HVAC 15723 VA 100.00% 15723 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 638 A

Total Conn. Load: 229769 VA

20 SPACE -- -- -- 0 VA --

19 SPACE -- -- -- 0 VA --

18 SPACE -- -- -- 0 VA --

17 SPACE -- -- -- 0 VA --

16 SPACE -- -- -- 0 VA --

15 SPACE -- -- -- 0 VA --

14 SPACE -- -- -- 0 VA --

13 SPACE -- -- -- 0 VA --

12 SPACE -- -- -- 0 VA --

11 SPACE -- -- -- 0 VA --

10 SPACE -- -- -- 0 VA --

9 SPACE -- -- -- 0 VA --

8 SPACE -- -- -- 0 VA --

7 PNL ELE 3 150 A 150 A 34296 VA

6 PNL ELD 3 100 A 100 A 21600 VA

5 GENERATOR DAMPER MOTOR 3 20 A 20 A 1680 VA

4 PNL EKA 3 350 A 350 A 90469 VA

3 PNL ELD 3 100 A 100 A 0 VA

2 PNL ELA 3 225 A 225 A 37697 VA

1 PNL ELB 3 225 A 225 A 44090 VA

CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks

Notes:

Enclosure: Type 1 MCB Rating: 1000 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: T2 Phases: 3 Mains Type:

Location: ELECTRICAL 115 Volts: 120/208 Wye A.I.C. Rating:

Switchboard: EDL EXISTING

S

K K

K

K

A T

S

2 3

B

A

C

(X)

(X)

(X) (X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)

(X)(X)

(X)

(X)

(X) (X) (X)

(X)

(X)

(X)(X)(X)

(X)

(X)

(X)

N.I.C.

N.I.C.

PROJECT NO.:

ISSUE DATE:

REVISIONS:

C

LA

R K

K

JO

S A

R C

H

IT

E C

T S

P Y

R

IG

H T

S W

A ld er S t., S ui te

P or tla nd

, O R

P h on e:

3/

4-

111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204

Tel 503.416.2400 Fax 206.267.1701

SAZAN# 257-20047

/2

/2

:3

:4

A

M

LIGHTING DEMOLITION -

FLOOR PLAN

04.02.21

ED2.01

IS

S

U E

D F

O R

P E

R M

IT

20018

O A

K C

R E

E K

E X

P A

N S

IO

N

L O

C H

N E

R R

D S

E A

L B

A N

Y

O R

O R

E G

O N

Y O

U T

H A

U T

H O

R

IT

Y

1/4" = 1'-0"ED2.01

1 LIGHTING DEMOLITION FLOOR PLAN

SHEET NOTES:

1. ALL ELECTRICAL IN WALLS AND PARTITIONS TO BE DEMOLISHED

(SHOWN OR NOT SHOWN) SHALL BE REMOVED BACK TO

SOURCE. REPAIR AND FINISH WALLS AT ALL EXISTING

COVERPLATES AND BOXES TO BE REMOVED.

2. CONTRACTOR MAY USE ANY CIRCUITS MADE AVAILABLE DUE

TO DEMOLITION. ANY EXTRA CIRCUITS MADE AVAILABLE AND

NOT USED SHALL BE LABELED AS SPARE.

3. CONTRACTOR TO RETURN ALL DEMOLISHED LIGHT FIXTURES,

EXIT SIGNS TO OWNER FOR OWNER'S DISPENSATION.

4. POWER AND LIGHTING IN AREAS NOT SHOWN ARE EXISTING TO

REMAIN.

A T

S

B

A

C

(E) TU 4-31

(E) TU 4-30

(E) (E)

(E)(E)

(X)

(X) (X)

(X)

(X) (X) (X) (X)

(X)

(X) (X)

(X)

(X)(X)

N.I.C.

PROJECT NO.:

ISSUE DATE:

REVISIONS:

C

LA

R K

K

JO

S A

R C

H

IT

E C

T S

P Y

R

IG

H T

S W

A ld er S t., S ui te

P or tla nd

, O R

P h on e:

3/

4-

111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204

Tel 503.416.2400 Fax 206.267.1701

SAZAN# 257-20047

/2

/2

:3

:4

A

M

ELECTRICAL

DEMOLITION - FLOOR

PLAN

04.02.21

ED3.01

IS

S

U E

D F

O R

P E

R M

IT

20018

O A

K C

R E

E K

E X

P A

N S

IO

N

L O

C H

N E

R R

D S

E A

L B

A N

Y

O R

O R

E G

O N

Y O

U T

H A

U T

H O

R

IT

Y

1/4" = 1'-0"ED3.01

1 ELECTRICAL DEMOLITION FLOOR PLAN

1. TERMINAL UNIT TO BE DEMOLISHED. COORDINATE DE-

ENERGIZING OF MECHANICAL TERMINAL UNIT AND REMOVE

CONDUIT, CONDUCTORS, AND DISCONNECTING MEANS.

1FLAG NOTES:

SHEET NOTES:

1. ALL ELECTRICAL IN WALLS AND PARTITIONS TO BE DEMOLISHED

(SHOWN OR NOT SHOWN) SHALL BE REMOVED BACK TO

SOURCE. REPAIR AND FINISH WALLS AT ALL EXISTING

COVERPLATES AND BOXES TO BE REMOVED.

2. CONTRACTOR MAY USE ANY CIRCUITS MADE AVAILABLE DUE

TO DEMOLITION. ANY EXTRA CIRCUITS MADE AVAILABLE AND

NOT USED SHALL BE LABELED AS SPARE.

3. CONTRACTOR TO RETURN ALL DEMOLISHED LIGHT FIXTURES,

EXIT SIGNS TO OWNER FOR OWNER'S DISPENSATION.

4. POWER AND LIGHTING IN AREAS NOT SHOWN ARE EXISTING TO

REMAIN.

64"

OS

O S

OS

D M

D M

OS

O S

O S

OS

OS

LV(b)

OS

OS

OS OS

LV(a)

B

A

C

57 SF

STAFF TLT

63 SF

FILE STORAGE

142 SF

MED EXAM

71 SF

DENTAL UTILITY

59 SF

OFFICE

87 SF

PSYCH OFFICE

107 SF

PSYCH OFFICE

108 SF

DENTAL EXAM

58 SF

MED UTILITY

45 SF

PAT TLT

45 SF

SOILED HOLDING/

POCT

144 SF

NURSE STATION

291 SF

HALLWAY

67 SF

WAITING

100 R6 /ELE-31 R6 /ELE-31

R6 /ELE-31

R3 /ELE-31

R3 /ELE-31

R3 /ELE-31

R3 /ELE-31

R3 /ELE-31

R3 /ELE-31

R3 /ELE-31

R3 /ELE-31

R6 /ELE-31

R7 /ELE-31

R4 /ELE-31

R6 /ELE-31

R1 /ELE-31

R2 /ELE-31

R2 /ELE-31

R2 /ELE-31

R1 /ELE-31

X1 /ELE-31

OS

N.I.C.

N.I.C.

X1 /ELE-31

R5 /ELE-31

R3 /ELE-31

(a)

(a)

(a)

(a)

(a)

(a)

(a)

(b) (b)

(b)

PROJECT NO.:

ISSUE DATE:

REVISIONS:

C

LA

R K

K

JO

S A

R C

H

IT

E C

T S

P Y

R

IG

H T

S W

A ld er S t., S ui te

P or tla nd

, O R

P h on e:

3/

4-

111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204

Tel 503.416.2400 Fax 206.267.1701

SAZAN# 257-20047

/2

/2

:3

:5

A

M

LIGHTING - FLOOR PLAN

04.02.21

E1.01

IS

S

U E

D F

O R

P E

R M

IT

20018

O A

K C

R E

E K

E X

P A

N S

IO

N

L O

C H

N E

R R

D S

E A

L B

A N

Y

O R

O R

E G

O N

Y O

U T

H A

U T

H O

R

IT

Y

1/4" = 1'-0"E1.01

1 ELECTRICAL LIGHTING - FIRST FLOOR PLAN

SHEET NOTES:

1. REFER TO E0.00 FOR GENERAL NOTES.

2. UNLESS OTHERWISE NOTED, WIRING SHALL BE 3/4"C, 2#12. 1#12

GND. THHN/THWN.

3. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF ALL

LIGHTING FIXTURES AND OTHER ELECTRICAL DEVICES WITH

ARCHITECTURAL DRAWINGS AND ACTUAL FIELD CONDITIONS.

4. ALL CONDUIT SHALL BE CONCEALED INSIDE WALLS OR ABOVE

CEILINGS WHENEVER POSSIBLE.

5. DYMO LABEL EACH JUNCTION BOX, COVERPLATE, AND/OR

SWITCH WITH CIRCUIT DESIGNATION.

6. PROVIDE UNSWITCHED CONDUCTORS TO EXIT SIGNS. PROVIDE

SWITCHED AND UNSWITCHED CONDUCTORS TO EMERGENCY

LIGHTING FIXTURES.

7. ALL EGRESS LIGHTING TO HAVE BATTERY BACKUP.

64"

CR

CR

4 4 4

J J

J

J

A T

S

FACP

9A

B

A

C

7A

8A

57 SF

STAFF TLT

63 SF

FILE STORAGE

142 SF

MED EXAM

71 SF

DENTAL UTILITY

59 SF

OFFICE

87 SF

PSYCH OFFICE

107 SF

PSYCH OFFICE

108 SF

DENTAL EXAM

58 SF

MED UTILITY

45 SF

PAT TLT

45 SF

SOILED HOLDING/

POCT

144 SF

NURSE STATION

291 SF

HALLWAY

67 SF

WAITING

FCU-10

BS-02

FCU-02

FCU-04

EDH-01

BS-01

+44" +44" +44"

+48"

+44" +44"+44"

+44"

+36"

+44"

+44"

+44"

+36"

+44"

+44"

+44"

+44"

+44"

AIR COMPRESSOR

WATER RECYCLE

VACUUM

+44"

FCU-06

FCU-05

FCU-07

FCU-09

FCU-03

FCU-08

FCU-01

(E)

(E)

(E)(E)

N.I.C.

ELE

ELE-17

ELE-17

ELE-17

ELE-15

ELE-15

ELE-15

ELE-9 ELE-9

ELE-19

ELE-19

ELE-27

ELE-1

ELE-27

ELE-29 ELE-29

ELE-37

ELE-7

ELE-7

ELE-14,16

ELE-14,16

ELE-14,16

ELE-14,16

ELE-14,16

ELE-14,16

ELE-14,16

ELE-14,16

ELE-14,16

ELE-25 ELE-25

ELE-21

ELE-25

ELE-21

ELE-19

ELE-21

ELE-21

ELE-29

ELE-29

ELE-27

ELE-27

ELE-5 ELE-5 ELE-5

ELE-3

ELE-3

ELE-1

ELE-1

ELE-1

ELE-1

ELE-7

ELE-7

ELE-7

ELE-9

ELE-9

ELE-10,12

ELE-6,8

ELE-14,16

ELE-14,16

ELE-18,20,22

ELE-23

ELE-11

ELE-13

EXISTING TO

REMAIN

ELE-33

ELE-14,16

ELE-35

RCP-1

2 2

TPV-1

ELE-36

EMERGENCY

GENERATOR

(E)

ELECTRICAL

(E)

ELECTRICAL

DOMESTIC HOT

WATER AND

SPRINKLER RISER

(E)

EDH

ATS

EDL

MDH

LA

T1 T2

MDL

SDP

ELD

ENGINEERING

(E)

PROJECT NO.:

ISSUE DATE:

REVISIONS:

C

LA

R K

K

JO

S A

R C

H

IT

E C

T S

P Y

R

IG

H T

S W

A ld er S t., S ui te

P or tla nd

, O R

P h on e:

3/

4-

111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204

Tel 503.416.2400 Fax 206.267.1701

SAZAN# 257-20047

/2

/2

:4

:4

P

M

ELECTRICAL - FLOOR

PLAN

04.02.21

E2.01

IS

S

U E

D F

O R

P E

R M

IT

20018

O A

K C

R E

E K

E X

P A

N S

IO

N

L O

C H

N E

R R

D S

E A

L B

A N

Y

O R

O R

E G

O N

Y O

U T

H A

U T

H O

R

IT

Y

1 Addendum 1 06-01-21

1/4" = 1'-0"E2.01

1 ELECTRICAL FLOOR PLAN

1. VERIFY EQUIPMENT LOCATION WITH ARCHITECT AND

EQUIPMENT VENDOR PRIOR TO ROUGH IN.

2. CONNECT EXISTING RECEPTACLES TO NEW PANELBOARD AS

SHOWN.

3. PROVIDE (1) 4" EMPTY CONDUIT WITH PULLSTRING FROM

MDF/IDF ROOM TO NEW REMODEL SPACE. STUB IN CEILING

SPACE AND LABEL FOR FUTURE". FIELD VERIFY EXACT MDF/IDF

ROOM AND APPROXIMATE LOCATION IN REMODEL SPACE PRIOR

TO BID.

1FLAG NOTES:

SHEET NOTES:

1. REFER TO E0.00 FOR GENERAL NOTES.

2. UNLESS OTHERWISE NOTED, WIRING SHALL BE 3/4"C, 2#12. 1#12

GND. THHN/THWN.

3. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF ALL

LIGHTING FIXTURES AND OTHER ELECTRICAL DEVICES WITH

ARCHITECTURAL DRAWINGS AND ACTUAL FIELD CONDITIONS.

4. ALL CONDUIT SHALL BE CONCEALED INSIDE WALLS OR ABOVE

CEILINGS WHENEVER POSSIBLE.

5. DYMO LABEL EACH JUNCTION BOX, COVERPLATE, AND/OR

SWITCH WITH CIRCUIT DESIGNATION.

1 Expires: 12/31/19

B

A

C

HP-01

ERV-01

(E) ACU - 4

ELE-28,30,32ELE-24,26

ELE-2,4

WP

(ROOF)

WP

(ROOF)

ELE-34

ELE-34

NEMA 3R

NEMA 3R NEMA 3R

PROJECT NO.:

ISSUE DATE:

REVISIONS:

C

LA

R K

K

JO

S A

R C

H

IT

E C

T S

P Y

R

IG

H T

S W

A ld er S t., S ui te

P or tla nd

, O R

P h on e:

3/

4-

111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204

Tel 503.416.2400 Fax 206.267.1701

SAZAN# 257-20047

/2

/2

:3

:0

A

M

ELECTRICAL - ROOF

PLAN

04.02.21

E2.02

IS

S

U E

D F

O R

P E

R M

IT

20018

O A

K C

R E

E K

E X

P A

N S

IO

N

L O

C H

N E

R R

D S

E A

L B

A N

Y

O R

O R

E G

O N

Y O

U T

H A

U T

H O

R

IT

Y

1/4" = 1'-0"E2.02

1 ELECTRICAL ROOF PLAN

SHEET NOTES:

1. REFER TO E0.00 FOR GENERAL NOTES.

2. UNLESS OTHERWISE NOTED, WIRING SHALL BE 3/4"C, 2#12. 1#12

GND. THHN/THWN.

3. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF ALL

LIGHTING FIXTURES AND OTHER ELECTRICAL DEVICES WITH

ARCHITECTURAL DRAWINGS AND ACTUAL FIELD CONDITIONS.

4. ALL CONDUIT SHALL BE CONCEALED INSIDE WALLS OR ABOVE

CEILINGS WHENEVER POSSIBLE.

5. DYMO LABEL EACH JUNCTION BOX, COVERPLATE, AND/OR

SWITCH WITH CIRCUIT DESIGNATION.

PANEL

"ELE"

8, 5 A

M

EUH-1

C

PANEL "K"PANEL "LA"PANEL "LB"

(IN GYM)

PANEL "LB"

400A ST

PANEL "R"

CL

LB

JO

PANEL "R"

JO

PANEL "R"

CL

LB

HA

PANEL "R"PANEL "R"PANEL "R"

M

JJ J J J J

PANEL

"ELA"

PANEL

"ELA2"

C

PANEL

"ELA"

PANEL

"ELA2"

C

PANEL

"ELA"

PANEL

"ELA2"

C

PANEL

"ELA"

PANEL

"ELA2"

C

GEN SET

DAMPER

MOTORS

PANEL

"ELB"

PANEL

"ELC"

PANEL

"ELD"

UPS

PANEL

"EKA"

PANEL

"EKB"

UTILITY

TRANSFORMER

1000A

UTILITY

METER

1000A

1000A, 480/277V, 3-PH, 4-W, 1/2N, 35kAIC

(3) 200A

SPACES

300/3

PANEL "MDL", 120/208V, 3-PH, 4-W, 600A BUS

T1

225KVA

TRANSFORMER

480-12/208V.

600/3 30/3 225/3

225A 3PDT

CONTACTOR

ENERGIZED

WHEN EMERGENCY

POWER PRESENT

600/3

600A/3P

AUTO TRANSFER

SWITCH "ATS-1"

3"C.(2) 3"C.

400/3100/3

3-1/2"C.

3-#350, 1#1/0 GND.

1-1/2"C.

4-#2, & GND.

100/3

1-1/2"C.

4-#2, & GND.

100/3

1-1/2"C.

4-#250, & GND.

(3) 200A

SPACES

PANEL "SDP", 480/277V, 3-PH, 4-W, 225A BUS

50/3, (CL, LB)

100/3 (JO)

1"C.

4-#6 (CL, LB)

1-1/2"C.

4-#2 (JO)

1-1/2"C.

4-#2

50/3

1"C.

4-#6

50/3

1-1/2"C.

4-#2.

1-1/2"C.

4-#2

50/3

1-1/4"C.

4-#3

(3) 200A

SPACES

PANEL "EDH", 480/277V, 3-PH, 4-W, 600A BUS

(2) 3"C.

3-#350, 1#2/0G 1#2 N

(2) 3"C.

3-#350, 1#2/0G 1#2 N

30/3

3/4"C.

4-#10

450/3

350KW

480/277V, 3-PH, 4W.

(2) 2-1/2"C.

3-#4/0.

1#2/G 1#2 N

GENERATOR SET

ACU-3

38 FLA

ACU-3

38 FLA

CL

LB

JO

CL LB JO

150/3

(CL, LB, JO)

80/3

(CR, HA)

1-1/2"C.

3-#3 1#8 G

(CL, JB, JO)

1-1/4"C.

3-#6 1#10G

1"C.

3-#6

1-#10 G

ACU-3

38 FLA

80/3

1-1/4"C.

3-#6 1#10 G

ACU-2

38 FLA

80/3

1-1/4"C.

3-#6 1#10 G

ACU-4

38 FLA

80/3

1-1/4"C.

3-#6 1#10 G

ACU-5

38 FLA

80/3

1-1/4"C.

3-#6 1#10 G

400/3

T2

300KVA

TRANSFORMER

480-12/208V.

(3) 3"C.3-1/2"C

PANEL "EDL", 120/208V, 3-PH, 4-W, 1000A BUS, 800A NEUT. 25K AIC

1000/3 225/3

2-1/2"C.

4-#4/0

2-1/2"C.

4-#4/0 1-#2G.

2"C.

4-#1 1-#4G.

125/3 225/3

2-1/2"C.

4-#4/0 1-#2G.

20/2 150/3

2-1/2"C.

4-#4/0

2"C.

4-#1/0

100/3

1-1/4"C 4-#2 1-#8G.

350/3

3-1/2"C 3-#500 1-#250 G.

1-1/4"C.

4-#4

3-#350, 1-#3/0 NEUT,

3-#350, 1-#4 GND.

3-#500, 1-#2 G.

4-#400

& GND.

150/3

1-1/2"C 4-#1/0 1-#6G.

PROJECT NO.:

ISSUE DATE:

REVISIONS:

C

LA

R K

K

JO

S A

R C

H

IT

E C

T S

P Y

R

IG

H T

S W

A ld er S t., S ui te

P or tla nd

, O R

P h on e:

3/

4-

111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204

Tel 503.416.2400 Fax 206.267.1701

SAZAN# 257-20047

/2

/2

:3

:1

A

M

ELECTRICAL ONE-LINE

DIAGRAM

04.02.21

E6.00

IS

S

U E

D F

O R

P E

R M

IT

20018

O A

K C

R E

E K

E X

P A

N S

IO

N

L O

C H

N E

R R

D S

E A

L B

A N

Y

O R

O R

E G

O N

Y O

U T

H A

U T

H O

R

IT

Y

12" = 1'-0"E6.00

1 EXISTING ONE-LINE DIAGRAM

SHEET NOTES:

1. PROVIDE NEW CIRCUIT BREAKER IN DISTRIBUTION BOARD 'ELD'

TO FEE NEW PANELBOARD 'ELE' PROVIDE NEW CONDUIT AND

CONDUCTORS.

257-20047 MEP Central v20_Theophilus.
E0.00 - GENERAL NOTES, ABBREVIATIONS AND SHEET INDEX
E0.01 - ELECTRICAL LEGEND
E0.03 - ELECTRICAL SCHEDULES
ED2.01 - LIGHTING DEMOLITION - FLOOR PLAN
ED3.01 - ELECTRICAL DEMOLITION - FLOOR PLAN
E1.01 - LIGHTING - FLOOR PLAN
E2.01 - ELECTRICAL - FLOOR PLAN
E2.02 - ELECTRICAL - ROOF PLAN
E6.00 - ELECTRICAL ONE-LINE DIAGRAM