ATT_B_E0.00.pdf
PDF 2 MB Posted
- Attached to
- OCYCF Med/Dental Remodel
- Solicitation number
- S-DASOBO-00001428
- Issued by
- Lake County, Albany City, Oregon
About this file
This document contains information related to a state and local government contract opportunity for the OCYCF Med/Dental Remodel project in Marion County and the City of Salem, Oregon. The project involves demolition, electrical, and lighting work for the remodel of an existing facility. The document provides detailed specifications, drawings, and schedules for the electrical and lighting systems. It includes general notes, abbreviations, legends, demolition plans, lighting plans, power plans, an electrical one-line diagram, and equipment schedules. The contract opportunity is being issued by the Oregon Youth Authority.
The document does not provide specific details on pricing terms, set asides, incumbents, funding requirements and sources, or other commercial terms. It appears to be focused on the technical specifications and requirements for the electrical and lighting work to be performed as part of the overall remodel project.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A. THE EXISTING CONDITIONS SHOWN WERE TAKEN FROM AVAILABLE RECORD INFORMATION. FIELD VERIFY ALL CONDITIONS THAT MAY AFFECT CONSTRUCTION. IF ANY DISCREPANCIES ARE DISCOVERED, NOTIFY THE
ENGINEER IN WRITING AND REQUEST DIRECTION PRIOR TO COMMENCING WORK.
B. EXISTING LIGHT FIXTURES SHALL BE CAREFULLY REMOVED (DO NOT DAMAGE) AND RETURNED TO THE OWNER.
C. ANY AND ALL EQUIPMENT HAVING ELECTRICAL CONNECTIONS THAT REQUIRE DISCONNECTING AND/OR RE- CONNECTING AS A RESULT OF CONSTRUCTION SHALL BE INCLUDED AS A PART OF THIS CONTRACT.
D. THE EXISTING ELECTRICAL DEVICES, CONDUIT, AND/OR EQUIPMENT THAT FOR ANY REASON OBSTRUCTS CONSTRUCTION SHALL BE RELOCATED UNLESS OTHERWISE NOTED. LOCATION IS TO BE AS CLOSE AS
POSSIBLE TO THE ORIGINAL LOCATION.
E. ALL CIRCUITS, CONDUIT AND WIRE THAT ARE NOT TO REMAIN IN SERVICE SHALL BE REMOVED BACK TO THE FIRST ACCESSIBLE JUNCTION BOX WHERE IT SHALL BE TIED OFF AND LABELED AS SPARE WITH CIRCUIT
NUMBER INDICATED.
F. REMOVE ALL ABANDONED WIRE AND CABLING.
DEMOLITION NOTES:
1. SYMBOLS LEGENDS ARE PROVIDED FOR REFERENCE PURPOSES ONLY. THE SYMBOLS REPRESENT THE TYPE OF DEVICES THAT MAY BE REQUIRED IN THE WORK; QUANTITIES AND LOCATIONS ARE AS SHOWN ON THE PLAN
SHEETS.
2. PROVIDE 3/4" CONDUIT & #12 CONDUCTORS UNLESS NOTED OTHERWISE. PROVIDE ONE NEUTRAL CONDUCTOR FOR EACH UNGROUNDED CONDUCTOR OF SINGLE PHASE LINE-NEUTRAL BRANCH CIRCUITS. DO NOT SHARE
NEUTRAL CONDUCTORS.
3. EACH FEEDER AND BRANCH CIRCUIT CONDUIT SHALL HAVE AN EQUIPMENT GROUNDING CONDUCTOR SIZED
IN ACCORDANCE WITH NFPA 70, ARTICLE 250.
4. ALL ELECTRICAL EQUIPMENT IN PORTIONS OF THE BUILDING NOT BEING REMODELED SHALL BE LEFT IN
WORKING CONDITION. RESTORE ANY CIRCUITS INTERRUPTED.
5. ALL NEW LIGHT FIXTURES AND FIXTURES IN AREAS ADJACENT DEMOLITION & CONSTRUCTION AREAS ARE TO
BE THOROUGHLY CLEANED IMMEDIATELY PRIOR TO NOTICE OF SUBSTANTIAL COMPLETION.
6. THE FOLLOWING IS PART OF THIS PROJECT AND ALL COSTS PERTAINING THERETO SHALL BE INCLUDED IN THE
BASE BID:
A. NEW ELECTRICAL EQUIPMENT AND APPARATUS SHALL BE COORDINATED AND CONNECTED INTO THE
EXISTING SYSTEM AS REQUIRED.
B. POWER WIRING AND CABLE INSTALLATIONS SHALL BE CONCEALED ABOVE ACCESSIBLE CEILINGS AND IN
WALLS. EXPOSED WIRING SHALL BE INSTALLED IN APPROVED SURFACE METAL RACEWAY WHERE
INDICATED.
C. WHERE EXISTING CONDUITS ARE INDICATED FOR REUSE, FIELD VERIFY INTEGRITY OF REUSED RACEWAYS PRIOR TO INSTALLATION OF CONDUCTORS. PROVIDE NEW RACEWAYS WHERE EXISTING ARE UNUSABLE.
D. LOCATIONS OF ALL WALL MOUNTED DEVICES SUCH AS SWITCHES, RECEPTACLE, AND OUTLETS ARE SHOWN DIAGRAMMATICALLY. VISIT THE SITE TO CONFIRM EXACT DEVICE LOCATIONS AND COORDINATE
INSTALLATIONS WITH FIXED CASEWORK, DOORS AND RELITES.
E. PROVIDE PENETRATIONS THROUGH WALLS, FLOORS, AND CEILINGS AS REQUIRED. PROVIDE SUITABLE FIRE RATED MATERIALS AND SEAL ALL CEILING, FLOOR, AND WALL PENETRATIONS TO MATCH FIRE RATING
OF SURFACES PENETRATED.
GENERAL NOTES:
1. LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS ZONED ON THE LIGHTING PLANS. SWITCHING AND
DIMMING ZONES ARE INDICATED ADJACENT TO EACH FIXTURE.
2. MANUAL CONTROLS SHALL ALLOW OCCUPANTS TO UNIFORMLY REDUCE ILLUMINATION LEVELS AT LEAST 50%.
EXCEPTION: CORRIDORS, RESTROOMS, LOBBIES, MECHANICAL, ELECTRICAL, AND INFORMATION TECHNOLOGY
(IDF) ROOMS CONTROLLED BY OCCUPANCY SENSORS.
3. EACH AREA THAT IS REQUIRED TO HAVE A MANUAL CONTROL SHALL ALSO HAVE AUTOMATIC TIME SWITCH CONTROL. PROVIDE TIMED OVERRIDE SWITCHES THAT WILL SERVE A MAXIMUM AREA OF 2500 SF IN LOCATIONS
SHOWN ON PLANS.
4. EXCEPTIONS:
A. EMERGENCY EGRESS LIGHTING CONTROLLED BY OCCUPANCY SENSORS.
B. LIGHTING IN SPACES CONTROLLED BY OCCUPANCY SENSORS.
5. LUMINAIRES PROVIDING MEANS OF EGRESS ILLUMINATION AND HAVING BOTH NORMAL AND EMERGENCY POWER SOURCES SHALL BE CONTROLLED BY A COMBINATION OF U.L. 924 LISTED EMERGENCY RELAYS AND OCCUPANCY SENSORS THAT ENABLES THE LIGHTING TO BE SHUT OFF WHEN THE AREAS SERVED ARE UNOCCUPIED AND AUTOMATICALLY ILLUMINATES IN THE EVENT OF NORMAL POWER SOURCE FAILURE.
6. THE MAXIMUM LIGHTING POWER THAT MAY BE CONTROLLED FROM A SINGLE SWITCH OR AUTOMATIC CONTROL SHALL NOT EXCEED THAT WHICH IS PROVIDED BY A 20 AMPERE CIRCUIT LOADED TO NOT MORE THAN 80
PERCENT.
7. PROVIDE FUNCTIONAL TESTING OF AUTOMATIC LIGHTING CONTROLS. SUBMIT WRITTEN PROCEDURES FOR FUNCTIONAL TESTING OF ALL AUTOMATIC CONTROLS WITH DESCRIPTION OF THE EXPECTED SYSTEM
RESPONSE.
LIGHTING NOTES:
@ AT
A/C AIR CONDITIONING(ER)
A (AMP) AMPERE
AC ABOVE COUNTER, ALTERNATING
CURRENT
ADJ ADJUSTABLE
ADJT ADJACENT
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERES INTERRUPTING CAPACITY
ALT ALTERNATE
ANN ANNUNCIATOR
ARCH ARCHITECT; ARCHITECTURAL
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BKBD BACKBOARD
BKR BREAKER
BLDG BUILDING
C CONDUIT
CAP CAPACITY
CB CIRCUIT BREAKER
CKT CIRCUIT
CLG CEILING
CLR CLEAR
COL COLUMN
COM COMMUNICATION
CPS CYCLES PER SECOND
CT CURRENT TRANSFORMER
CTL CONTROL
CU COPPER
DC DIRECT CURRENT
DISC SW DISCONNECT SWITCH
DISC DISCONNECT
DN DOWN
DWG DRAWING
E EXIST, EAST
EDH ELECTRIC DUCT HEATER
EF EXHAUST FAN
EGC EQUIPMENT GROUNDING CONDUCTOR
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
ENTR ENTRANCE
EP EXPLOSION PROOF
EPO EMERGENCY POWER OFF
EQUIP/EQP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXH EXHAUST
EXT EXTERIOR
EXIST EXISTING
F FAHRENHEIT/FUSE
FA FIRE ALARM
FAA FIRE ALARM ANNUNCIATOR
FAP FIRE ALARM PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FD FIRE DAMPER
FDR FEEDER
FIXT FIXTURE
FLA FULL LOAD AMPS
FSD FIRE/SMOKE DAMPER
GEC GROUNDING ELECTRODE CONDUCTOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFR GROUND FAULT RELAY
H HEIGHT
HOA HAND OFF AUTOMATIC
HOR HORIZONTAL
HP HORSEPOWER
HR HOUR
HT HEIGHT
HW HOT WATER
HZ HERTZ
IBC INTERNATIONAL BUILDING CODE
IC INTERCOM
IES ILLUMINATING
IEEE INSTITUTE OF ELECTRICAL AND
ELECTRONIC ENGINEERS
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IN INCH
JB JUNCTION BOX
KCMIL THOUSAND CIRCULAR MILLS
KVA KILOVOLT AMPERES
KVAR KILOVOLT AMPERES REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LBS POUNDS
LF LINEAR FEET (FEET)
LRA LOCKED ROTOR AMPS
LS LIFE SAFETY
LT LIGHT
LTG LIGHTING
LV LOW VOLTAGE
ABBREVIATIONS
MAG MAGNETIC
MAN MANUAL
MAT MATERIAL
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MECH MECHANICAL
MEZZ MEZZANINE
MG MOTOR GENERATOR
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUG ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MS MAGNETIC STARTER
MTD MOUNTED
MTG MOUNTING
MTR MOTOR
N NORTH; NEUTRAL
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRIC MANUFACTURERS
ASSOCIATION
NESC NATIONAL ELECTRICAL SAFETY CODE
NEUT NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOC.
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISHED CONTRACTOR
INSTALLED
OFOI OWNER FURNISHED OWNER INSTALLED
OL OVERLOAD
OS OPTIONAL STANDBY
P PRIMARY
PA PUBLIC ADDRESS
PAR PARALLEL
PB PULL BOX
PE PHOTO ELECTRIC
PF POWER FACTOR
PH PHASE
PIV POST INDICATOR VALVE
PNL PANEL
POC POINT OF CONNECTION
PWR POWER
QTY QUANTITY
R (R) RELOCATE (D)
RAD RADIUS
RECPT RECEPTACLE
REF REFRIGERATOR
RLA RATED LOAD AMPS
RPM REVOLUTIONS PER MINUTE
S SOUTH
SC SECURITY
SD SMOKE DETECTOR
SECT SECTION
SF SUPPLY FAN
SHT SHEET
SPEC SPECIFICATION
SPL SPECIAL
SQ SQUARE
STOR STORAGE
SPD SURGE PROTECTION DEVICE
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
T THERMOSTAT
TB TERMINAL BOX
TC TIME CLOCK
TEL TELEPHONE
TV TELEVISION
TYP TYPICAL
UFC UNIFORM FIRE CODE
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS LABORATORIES
UON UNLESS OTHERWISE NOTED
UV UNIT VENTILATOR
V VOLT
VAV VARIABLE AIR VOLUME
VEL VELOCITY
VM VOLTMETER
VOL VOLUME
W WATT, WEST
W/ WITH
W/O WITHOUT
WH WATER HEATER
WHM WATTHOUR METER
WP WEATHERPROOF
(X) EXISTING TO BE REMOVED
XFMR TRANSFORMER
XMTR TRANSMITTER
Z IMPEDANCE
& AND
IE: THAT IS
1. SYSTEM CABLING PATHWAYS SHALL BE INSTALLED IN ACCORDANCE WITH THE MOST CURRENT VERSION OF
TIA-569.
2. J-HOOKS SHALL NOT BE PLACED MORE THAT 5' APART.
3. IF A CABLE PATH WILL EXCEED 295', INFORM THE ICT ENGINEER IMMEDIATELY BEFORE INSTALLATION.
4. PROVIDE (1) 2' CONDUIT SLEEVE FOR PENETRATION INTO OFFICES, ETC. FOR CABLING PATHWAYS.
5. ALL PENETRATIONS MUST BE FIRE-STOPPED IN ACCORDANCE OF THE NFPA, NEC AND TO THE SATISFACTION
OF THE AHJ.
STRUCTURED CABLE SYSTEM PATHWAY NOTES:
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
K
JO
S A
R C
H
IT
E C
T S
LL
C
O
P Y
R
IG
H T
S W
A ld er S t., S ui te
P or tla nd
, O R
P ho ne
: 5
/2
-4
111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204
Tel 503.416.2400 Fax 206.267.1701
SAZAN# 257-20047
/2
/2
:3
:2
A
M
GENERAL NOTES,
ABBREVIATIONS AND
SHEET INDEX
04.02.21
E0.00
IS
S
U E
D F
O R
P E
R M
IT
20018
O A
K C
R E
E K
E X
P A
N S
IO
N
L O
C H
N E
R R
D S
E A
L B
A N
Y
O R
O R
E G
O N
Y O
U T
H A
U T
H O
R
IT
Y
ELECTRICAL SHEET INDEX
E0.00 GENERAL NOTES, ABBREVIATIONS AND SHEET INDEX
E0.01 ELECTRICAL LEGEND
E0.02 ELECTRICAL LIGHTING SCHEDULES
E0.03 ELECTRICAL SCHEDULES
ED2.01 LIGHTING DEMOLITION - FLOOR PLAN
ED3.01 ELECTRICAL DEMOLITION - FLOOR PLAN
E1.01 LIGHTING - FLOOR PLAN
E2.01 ELECTRICAL - FLOOR PLAN
E2.02 ELECTRICAL - ROOF PLAN
E6.00 ELECTRICAL ONE-LINE DIAGRAM
Expires: 12/31/2021
J
OS
OS
OS
PC
ESR
F
S
S
AIM
AOM
ISOIM
R
S
S Z
NCCP
NCMA
NCMN
XXXX
CR
WP
K
WP
MD
ES
DC
REX
A
BG
X-XX-X
T
M
MM
AM
SYMBOLS LEGEND - POWER
DESCRIPTIONSYMBOL
TRANSFORMER
S2
AS
POLE-MOUNTED TRANSFORMER
POLE
DELTA
WYE
MEDIUM VOLTAGE CABLE TERMINATOR
LIGHTNING ARRESTORS
SURGE ARRESTORS
NEUTRAL GROUNDING RESISTOR
METER
MICROPROCESSOR CONTROLLED MONITOR
REFER TO SPECIFICATIONS FOR METERING VALUES AND
PROTECTIVE FUNCTIONS
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
INDICATING INSTRUMENT
AM-AMMETER; VM-VOLTMETER; FM-FREQUENCY METER;
kVAR-KILOVAR METER; kWH-KILOWATT HOUR METER;
kWH/D-KILOWATT HOUR DEMAND METER
INSTRUMENT SWITCH
AS-AMMETER SWITCH; VS-VOLTMETER SWITCH;
SS-SYNCHRONIZING SWITCH;
SV-SUPERVISORY (LOCAL-REMOTE) SWITCH
SEPARABLE CONNECTOR
DRAWOUT AC TYPE POWER CIRCUIT BREAKER
SYMBOLS LEGEND - POWER
DESCRIPTIONSYMBOL
M
C
G
M
M
SD
M
FSD
M
2-POSITION SELECTOR SWITCH
3-POSITION SELECTOR SWITCH HAND-OFF-AUTOMATIC
ON-OFF SELECTOR SWITCH
2-CIRCUIT PUSHBUTTON
PUSHBUTTON SWITCH MOMENTARY CONTACT
EQUIPMENT CONNECTION
GENERATOR
MOTOR CONNECTION
SMOKE DAMPER
FIRE SMOKE DAMPER
STARTER 3-POLE, NEMA SIZE 1 MINIMUM UNLESS NOTED OTHERWISE
COMBINATION STARTER
HP RATED, 3-POLE, NEMA SIZE 1 MINIMUM, UNLESS NOTED
OTHERWISE - OVERCURRENT PROTECTION AS REQUIRED BY
EQUIPMENT MANUFACTURER OR AS NOTED
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
CONTACTOR
RELAY COIL
CR-CONTROL RELAY; TD-TIME DELAY RELAY;
UV-UNDERVOLTAGE RELAY; M-MOTOR
CONTACTOR;
MOTOR-RATED SWITCH - SIZE OL PER MOTOR REQUIREMENTS
EQUIPMENT EMERGENCY SHUTDOWN SWITCH
3-POLE UNLESS NOTED OTHERWISE
SYMBOLS LEGEND - POWER
DESCRIPTIONSYMBOL
ST
CB
G
G
SV
M
A
M
G
CIRCUIT BREAKER
ST - INDICATES SHUNT TRIP
BREAKER WITH EXTERNAL GROUND FAULT RELAY AND CT
CIRCUIT BREAKER WITH GROUND FAULT PROTECTION
MOTOR-OPERATED CIRCUIT BREAKER
SWITCH WITH EXTERNAL GROUND FAULT RELAY AND CT
MOV SURGE PROTECTION
RESISTOR
FUSE
MOTOR THERMAL OVERLOADS - (3) UNLESS OTHERWISE NOTED
NORMALLY OPEN CONTACT
NORMALLY CLOSED CONTACT
SOLENOID VALVE
MOTOR-OPERATED VALVE
TERMINAL BLOCK
THERMOSTAT
INDICATING LIGHT - TYPE AS NOTED
A-AMBER; B-BLUE; G-GREEN; R-RED; W-WHITE
BATTERY
T 65°
SYMBOLS LEGEND - GENERAL
DESCRIPTIONSYMBOL
UG
LV
A-1,3,5
PB
HH
MH
MINIMUM 3/4" CONDUIT CONCEALED IN CEILING SPACE OR IN WALL
MINIMUM 3/4" WITH #12 AWG CONDUCTORS WITH DEDICATED NEUTRAL
EACH CIRCUIT, UNLESS OTHERWISE NOTED ON PLAN. PROVIDE
EQUIPMENT GROUNDING CONDUCTORS SIZED PER NFPA 70.
CONDUIT - CONCEALED IN OR UNDER FLOOR
CONDUIT - ROUTED UNDERGROUND
LOW-VOLTAGE WIRING (CLASS B)
CONDUIT OR CABLE VERTICAL DOWN
CONDUIT OR CABLE VERTICAL UP
CONDUIT STUB - TERMINATE WITH BUSHING OR CAP IF UNDERGROUND
BREAK LINE
CONDUIT SEAL
EXPANSION FITTING
CABLE TRAY
CONDUCTORS - CONNECTED
CONDUCTORS - NOT CONNECTED
JUNCTION BOX
PULLBOX - SIZE AS INDICATED OR AS REQUIRED BY CODE
HANDHOLE
MANHOLE
FLEXIBLE METAL CONDUIT
BRANCH CIRCUIT NUMBERS
PANEL DESIGNATION
HOME RUN TO SOURCE OF SUPPLY
SYMBOLS LEGEND - POWER
DESCRIPTIONSYMBOL
XX
XXXXXX
SYMBOLS LEGEND - GROUNDING
DESCRIPTIONSYMBOL
480Y/277V, 3Ø, 4W PANELBOARD
208Y/120V, 3Ø, 4W PANELBOARD
EQUIPMENT CABINET - TYPE AS NOTED
PANELBOARD
TRANSFER SWITCH ( AUTO )
AMPERES SHORT CIRCUIT AVAILABLE (SYMMETRICAL)
FEEDER TAG - REFER TO FEEDER SCHEDULE
GROUND CONNECTION
GROUND ROD
GROUND WELL
AIR TERMINAL
SYMBOLS LEGEND - WIRING DEVICES
DESCRIPTIONSYMBOL
SINGLE-POLE WALL SWITCH MOUNT SWITCHES AT 48" AFF. TO CL, UON.
TT
IGIG
T T
WALL SWITCH - SUBSCRIPT
SPECIAL PURPOSE RECEPTACLE TYPE AS SHOWN ON PLANS
SINGLE SERVICE OR COMBINATION FLUSH FLOOR POKE THRU. REFER TO
FLOOR PLANS FOR DEVICES.
POWER/COMM POLE - FLOOR TO CEILING.
SURFACE MOUNTED FLOOR BOX (PEDESTAL TYPE).
PUSH BUTTON
SIMPLEX RECEPTACLE NEMA 5-20R, +18" AFF UON
NEMA 5-20R, +18" AFF UON
TAMPER RESISTANT, NEMA 5-20R, +18" AFF UON
ISOLATED GROUND, NEMA 5-20R, +18" AFF UON
NEMA 5-20R W/ GROUND FAULT CIRCUIT INTERRUPTER, +18" AFF UON
SPLIT WIRED, NEMA 5-20R, +18" AFF UON
CONTROLLED, NEMA 5-20R, +18" AFF UON
NEMA 5-20R, ABOVE COUNTER, +18" AFF UON
NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER, ABOVE
COUNTER. COORDINATE WITH CASEWORK SHOP DRAWINGS AND
ARCHITECTURAL DRAWINGS.
TAMPER RESISTANT, NEMA 5-20R WITH GROUND FAULT CIRCUIT
INTERRUPTER, ABOVE COUNTER. COORDINATE WITH CASEWORK SHOP
DRAWINGS AND ARCHITECTURAL DRAWINGS.
NEMA 5-20R, CONNECTED TO EMERGENCY CIRCUIT, +18" AFF UON
NEMA 5-20R MOUNTED ABOVE COUNTER. COORDINATE WITH CASEWORK
SHOP DRAWINGS AND ARCHITECTURAL DRAWINGS.
CEILING-MOUNTED, NEMA 5-20R
2 = 2-POLE
3 = 3-WAY
4 = 4-WAY
K = KEYED
LV = LOW-VOLTAGE
OS = OCCUPANCY SENSOR TYPE
OP = OCCUPANCY/PHOTOELECTRIC TYPE
WP = WEATHERPROOF
LOWER CASE LETTER INDICATES SWITCHING GROUP
MOUNT SWITCHES AT +48" AFF. TO CL, UON. ANY COMBINATION OF
SWITCH TYPES CAN BE USED (IE. 3K = 3-WAY KEYED SWITCH)
SYMBOLS LEGEND - LIGHTING
DESCRIPTIONSYMBOL
TC
SB
PP
ICS1-1
OS
PC
1x4 LUMINAIRE
2x2 LUMINAIRE
UNDER-CABINET LUMINAIRE
TRACK LIGHT - LENGTH AS INDICATED ON PLANS
NUMBER OF LUMINAIRES AS SHOWN
POLE-MOUNTED LUMINAIRE - NUMBER OF LUMINAIRES AS
SHOWN ON PLANS
IN-GROUND LANDSCAPE LUMINAIRE
TIME CLOCK - TYPE AS NOTED
LIGHTING CONTROL SYSTEM POWER PACK
SWITCH BYPASS DEVICE
ILLUMINATION CONTROL STATION
OCCUPANCY SENSOR CEILING MOUNTED WITH POWER PACK - DUAL
TECHNOLOGY TYPE UNLESS NOTED:
U = ULTRASONIC
U
P
OCCUPANCY SENSOR WALL MOUNTED
P = PASSIVE INFRARED
PHOTOELECTRIC CONTROL WALL MOUNTED
SYMBOLS LEGEND - FIRE ALARM
DESCRIPTIONSYMBOL
FIRE ALARM SYSTEM CONTROL PANEL
SINGLE SERVICE OR COMBINATION FLUSH MOUNTED FLOOR BOX. REFER
TO FLOOR PLANS FOR DEVICES.
NEMA 5-20R WITH USB CHARGER - (2) TYPE A USB PORTS
TAMPER RESISTANT, NEMA 5-20R WITH USB CHARGER - (2) TYPE A USB PORTST
F
XX
S
XX
XX
XX
F
PIV
VS
PS
FS
SD
SD
FIRE ALARM FLOW SWITCH
HI/LO AIR PRESSURE SWITCH
VALVE SUPERVISORY SWITCH
POST INDICATOR VALVE SUPERVISORY SWITCH
FIRE ALARM PULL STATION
FIRE/SMOKE DAMPER
SMOKE DAMPER
FIRE ALARM HORN ONLY
FIRE ALARM HORN STROBE
FIRE ALARM SPEAKER ONLY
FIRE ALARM SPEAKER STROBE
FIRE ALARM STROBE ONLY - WALL
FIRE ALARM STROBE ONLY - CEILING
FIRE ALARM BELL
FIRE FIGHTER PHONE JACK
HEAT DETECTOR
SMOKE DETECTOR
FIRE ALARM DUCT SMOKE DETECTOR WITH SAMPLING TUBE
FLAME DETECTOR
GAS DETECTOR
ADDRESSABLE INPUT MODULE
ADDRESSABLE OUTPUT MODULE
ISOLATION MODULE
FIRE ALARM EQUIPMENT CONNECTION
RELAY BLOCK
ESR - ELEVATOR STATUS/RECALL
FAC - FIRE ALARM COMMUNICATOR
FACP - FIRE ALARM CONTROL PANEL
FAA OR FARA - FIRE ALARM ANNUNCIATOR
HVA - HVAC OR EXHAUST STAIRWELL PRESSURIZATION
LCD - FIRE ALARM LCD ANNUNCIATOR
F - FIXED TEMPERATURE
R - RATE OF RISE ONLY
R/C - RATE COMPENSATION
R/F - RATE OF RISE AND FIXED TEMPERATURE
BT - BEAM TRANSMITTER
BR - BEAM RECEIVER
I - IONIZATION
P - PHOTOELECTRIC
SYMBOLS LEGEND - AUDIO VISUAL / CLOCK
DESCRIPTIONSYMBOL
TV
S
S a a
TV OUTLET
a a
PAGING SYSTEM SPEAKER - CEILING RECESSED MOUNTED. LOWER CASE
DENOTES ZONE GROUP (TYP.)
PAGING SYSTEM SPEAKER - CEILING SURFACE MOUNTED. LOWER CASE
DENOTES ZONE GROUP (TYP.)
PAGING SYSTEM SPEAKER - WALL RECESSED MOUNTED. LOWER CASE
DENOTES ZONE GROUP (TYP.)
PAGING SYSTEM SPEAKER - WALL SURFACE MOUNTED. LOWER CASE
DENOTES ZONE GROUP (TYP.)
CLOCK - WALL SURFACE MOUNTED
CLOCK - RECESSED MOUNTED
SYMBOLS LEGEND - NURSE CALL
DESCRIPTIONSYMBOL
NURSE CALL CONTROL EQUIPMENT PANEL
E
CB
E
D
S
L
WP
A
MES
MES
NURSE CALL MASTER STATION - AUDIO
NURSE CALL MASTER STATION - NON AUDIO
ZONE DOME LIGHT, CEILING MOUNTED (NUMBER DENOTES ZONE)
DOME LIGHT, CEILING MOUNTED
DOME LIGHT, WALL MOUNTED
MEDICAL EMERGENCY STATION (MES)
CODE BLUE STATION
DUTY STATION
STAFF STATION
IN/OUT PUSH BUTTON
TOILET PULL STATION
SHOWER PULL STATION
NURSE CALL ANNUNCIATOR
SINGLE PATIENT STATION (PS)
SINGLE PATIENT STATION (PS) WITH EMERGENCY CALL BUTTON
DUAL PATIENT STATION (PS)
DUAL PATIENT STATION (PS) WITH EMERGENCY CALL BUTTON
SYMBOLS LEGEND - COMMUNICATIONS
DESCRIPTIONSYMBOL
COMMUNICATIONS - OUTLET
(# = REPRESENTS THE NUMBER OF COMMUNICATION PORTS. (IE 1,2,3))
(W = SINGLE COMMUNICATIONS PORT WALL MOUNTED AT +48" AFF.)
(P = PAYPHONE, WALL MOUNTED AT +48" AFF)
XX
D
M
D
INTERCOM - OUTLET
(D = DESK MOUNTED)
(W = WALL MOUNTED AT +48" AFF.)
COMMUNICATIONS - MICROPHONE
(D = DESK MOUNTED)
(W = WALL MOUNTED AT +48" AFF.)
COMPUTER NETWORK WIRELESS ACCESS POINT - CEILING MOUNTED
COMMUNICATIONS - PAINTED FIRE RESISTANT 3/4" PLYWOOD
BACKBOARD
19" COMMUNICATIONS RACK - FLOOR MOUNTED
19" COMMUNICATIONS RACK - WALL MOUNTED
SYMBOLS LEGEND - GENERAL
DESCRIPTIONSYMBOL
X-XX
X
XX.XX
X
XX.XX
X
XX.XX
N
DRAWING CONSTRUCTION ("FLAG") NOTE
EQUIPMENT IDENTIFIER
MATCHLINE
REVISION CLOUD (ENCIRCLES DRAWING CHANGES MADE SINCE THE
PREVIOUS RELEASE)
REVISION REFERENCE
EXISTING TO BE REMOVED (HATCH)
HEAVY LINEWEIGHT INDICATES NEW WORK
LIGHT LINEWEIGHT INDICATES EXISTING INFORMATION
POINT OF CONNECTION
DETAIL REFERENCE
DETAIL IDENTIFICATION NUMBER
SHEET WHERE DETAIL IS DRAWN
ELEVATION REFERENCE
ELEVATION IDENTIFICATION
NUMBER SHEET WHERE ELEVATION IS DRAWN
SECTION REFERENCE SECTION
IDENTIFICATION NUMBER
SHEET WHERE SECTION IS DRAWN
NORTH REFERENCE
SYMBOLS LEGEND - SECURITY
DESCRIPTIONSYMBOL
WP
WP
CARD READER. WP INDICATES WEATHERPROOF
KEYPAD. WP INDICATES WEATHERPROOF
MOTION DETECTOR - INFRARED TYPE UNLESS OTHERWISE NOTED
ELECTRIC DOOR STRIKE
DOOR/WINDOW CONTACT
REQUEST TO EXIT PUSHBUTTON
PANIC / DURESS BUTTON
ALARM BELL
BREAK GLASS SENSOR
CCTV CAMERA - FIXED TYPE. WP INDICATES WEATHERPROOF
CCTV CAMERA - PAN/TILT/ZOOM TYPE. WP INDICATES WEATHERPROOF
XX
SS SWITCHED RECEPTACLE, NEMA 5-20R, +18" AFF UON
3-POLE UNLESS NOTED OTHERWISE
L1 A - 1
Z-XXX-1
EM
LIGHT FIXTURE IDENTIFIER - REFER TO LUMINAIRE SCHEDULE
PANEL NAME - CIRCUIT NUMBER
SWITCH DESIGNATION - MIDDLE DIGITS REFER TO
ROOM NUMBER - END DIGITS REFER TO SWITCH LEG
SUBSCRIPT (IF APPLICABLE)
* IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: RL1 / A-1 / a / NL
SHADING INDICATES LUMINAIRE ON EMERGENCY CIRCUIT OR WITH
BATTERY BACKUP
2x4 LUMINAIRE
LINEAR LUMINARE
WALL WASH LUMINAIRE
STRIP LUMINAIRE
WALL MOUNTED LUMINAIRE
DOWNLIGHT
WALL WASH DOWNLIGHT LUMINAIRE
WALL MOUNTED LUMINAIRE
WALL MOUNTED DIRECTIONAL LUMINAIRE
PENDANT MOUNTED LUMINAIRE
STREET LIGHT
ILLUMINATED EXIT SIGN - SINGLE FACE ARROW INDICATES
DIRECTION OF EGRESS, UNIVERSAL MOUNT
ILLUMINATED EXIT SIGN - DOUBLE FACE ARROW INDICATES
DIRECTION OF EGRESS, UNIVERSAL MOUNT
BATTERY-POWERED EMERGENCY WALLPACK
COMBINATION BATTERY POWERED EMERGENCY WALLPACK
AND ILLUMINATED EXIT SIGN
PHOTOELECTRIC CONTROL CEILING MOUNTED
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
K
JO
S A
R C
H
IT
E C
T S
P Y
R
IG
H T
S W
A ld er S t., S ui te
P or tla nd
, O R
P ho ne
: 5
/2
-4
111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204
Tel 503.416.2400 Fax 206.267.1701
SAZAN# 257-20047
/2
/2
:3
:3
A
M
ELECTRICAL LEGEND
04.02.21
E0.01
IS
S
U E
D F
O R
P E
R M
IT
20018
O A
K C
R E
E K
E X
P A
N S
IO
N
L O
C H
N E
R R
D S
E A
L B
A N
Y
O R
O R
E G
O N
Y O
U T
H A
U T
H O
R
IT
Y
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
K
JO
S A
R C
H
IT
E C
T S
P Y
R
IG
H T
S W
A ld er S t., S ui te
P or tla nd
, O R
P h on e:
3/
4-
111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204
Tel 503.416.2400 Fax 206.267.1701
SAZAN# 257-20047
/2
/2
:3
:4
A
M
ELECTRICAL
SCHEDULES
04.02.21
E0.03
IS
S
U E
D F
O R
P E
R M
IT
20018
O A
K C
R E
E K
E X
P A
N S
IO
N
L O
C H
N E
R R
D S
E A
L B
A N
Y
O R
O R
E G
O N
Y O
U T
H A
U T
H O
R
IT
Y
HP-01 VRF HEAT PUMP 208 1 - - - 32.0 1" 2 8 10 2 50 - 60A
FCU-10 VRF FAN COIL 208 1 - - - 0.24. 3/4" 2 12 12 2 15 - 7
FCU-09 VRF FAN COIL 208 1 - - - 0.4 3/4" 2 12 12 2 15 - 7
FCU-08 VRF FAN COIL 208 1 - - - 0.4 3/4" 2 12 12 2 15 - 7
FCU-07 VRF FAN COIL 208 1 - - - .24. 3/4" 2 12 12 2 15 - 7
FCU-06 VRF FAN COIL 208 1 - - - .24. 3/4" 2 12 12 2 15 - 7
FCU-05 VRF FAN COIL 208 1 - - - .24. 3/4" 2 12 12 2 15 - 7
FCU-04 VRF FAN COIL 208 1 - - - .24. 3/4" 2 12 12 2 15 - 7
FCU-03 VRF FAN COIL 208 1 - - - .24. 3/4" 2 12 12 2 15 - 7
FCU-02 VRF FAN COIL 208 1 - - - 0.4 3/4" 2 12 12 2 15 - 7
FCU-01 VRF FAN COIL 208 1 - - - 0.24. 3/4" 2 12 12 2 15 - 7
ERV-01(H) AUXILLARY HEAT 208 3 - - - 5.5 3/4" 3 12 12 3 15 - 8
ERV-01 ENERGY RECOVER VENT UNIT 208 1 1.0 - - 13.9 3/4" 2 12 12 2 15 - 7
EDH-01 ELECTRIC DUCT HEATER 208 3 - 2.0 - 6.9 3/4" 3 12 12 3 15 - 8
BS-02 BRANCH SELECTOR BOX 208 1 - - - 2.0 3/4" 2 12 12 2 15 - 7
BS-01 BRANCH SELECTOR BOX 208 1 - - - 2.0 3/4" 2 12 12 2 15 - 7
NO. HP kW FLA SIZE NO. SIZE GND POLE AMPS SIZE SW
EQPT DESCRIPTION VOLTS PH LOAD MCA RCWY 75°C CU CONDUCTORS BREAKER STARTER DISC NOTES REMARKS
8. 208 VOLT, 3 POLE, 20A MOTOR RATED SWITCH
7. 208 VOLT, 2 POLE, 20A MOTOR RATED SWITCH
INSTALLED BY ELECTRICAL CONTRACTOR.
6. SPEED CONTROL FURNISHED BY MECHANICAL CONTRACTOR,
BY MECHANICAL CONTRACTOR, INSTALLED BY ELECTRICAL CONTRACTOR
5. SPEED CONTROL AND LINE VOLTAGE HEATING-ONLY THERMOSTAT FURNISHED W - WATTS
4. DIRECT CONNECTION MCA - MINIMUM CIRCUIT AMPACITY
3. FUSED DISCONNECT SWITCH C. FURNISHED AND INSTALLED UNDER DIVISION 26 kW - KILOWATTS
2. MANUAL STARTER B. FURNISHED BY OTHERS, INSTALLED UNDER DIVISION 26 HP - HORSEPOWER
1. COMBINATION STARTER A. FURNISHED AND INSTALLED BY OTHERS FLA - FULL LOAD AMPS
NOTES:
HVAC EQUIPMENT SCHEDULE
Notes:
Total Est. Demand Current: 92 A
Receptacle 13140 VA 88.05% 11570 VA Total Conn. Current: 95 A
Other 20205 VA 100.00% 20205 VA Total Est. Demand: 32978 VA
Mechanical 6 VA 100.00% 6 VA Total Conn. Load: 34296 VA
Lighting 996 VA 125.00% 1245 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 121 A 104 A 70 A
Total Load: 13978 VA 11898 VA 8448 VA
41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42
39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40
37 DED RCPT - REFRIGERATOR - RM 110 20 A 1 180 VA 0 VA 1 20 A SPARE 38
35 RCP-1 20 A 1 124 VA 6 VA 1 20 A TPV-1 36
33 RCPT - FILE STORAGE 102 20 A 1 360 VA 360 VA 1 20 A ROOFTOP RECEPTS 34
31 LIGHTING 20 A 1 996 VA 662 VA -- -- -- -- 32
29 RCPT - EXAM 041 20 A 1 1080 VA 662 VA -- -- -- -- 30
27 RCPT - Room 112, 111, 100 20 A 1 900 VA 662 VA 3 15 A ERV-01 AUX HEAT 28
25 RCPT - MED EXAM 109 20 A 1 1080 VA 1446 VA -- -- -- -- 26
23 RCPT - MED EXAM 109 20 A 1 180 VA 1446 VA 2 15 A ERV-01 HEAT RECOV 24
21 RCPT - MED EXAM 109 20 A 1 1260 VA 835 VA -- -- -- -- 22
19 RCPT - Room 107, 113 20 A 1 540 VA 835 VA -- -- -- -- 20
17 RCPT - PSYCH OFFICE 106 20 A 1 540 VA 835 VA 3 20 A EDH-01 18
15 RCPT - PSYCH OFFICE 105 20 A 1 540 VA 716 VA -- -- -- -- 16
13 RCPT - DENTAL EXAM 104 20 A 1 180 VA 716 VA 2 20 A FCU-1,2,3,4,5,6,7,8,9,10,BS-1,2 14
11 RCPT - DENTAL EXAM 104 20 A 1 180 VA 1250 VA -- -- -- -- 12
9 RCPT - DENTAL EXAM 104 20 A 1 1080 VA 1250 VA 2 30 A WATER RECYCLER VACUUM 10
7 RCPT - Room 103, 104 20 A 1 1440 VA 1250 VA -- -- -- -- 8
5 RCPT - NURSE STATION 101 20 A 1 1080 VA 1250 VA 2 30 A COMPRESSOR 6
3 RCPT - NURSE STATION 101 20 A 1 720 VA 3328 VA -- -- -- -- 4
1 RCPT - W. GENERAL USE 20 A 1 1440 VA 3328 VA 2 50 A HP-01 2
C K T
# ITEM
N O T E
A M P S
P O L E A B C
P O L E
A M P S
N O T
E ITEM
C K T
MLO
225 A
A.I.C. RATING: 10,000A
EQUIPMENT GROUND BUS SKIRTS: NONE
GROUNDING: MOUNTING: RECESSED
FILE STORAGE 102 EDL TYPE: BOLT-ON
LOCATION: FED FROM: PANEL EDL VOLTAGE: 120/208 Wye 3-PH, 4-WIRE
NEW PANEL ELE SCHEDULE
Notes:
Mechanical 6 VA 100.00% 6 VA
Kitchen Equipment - Non-Dwelling Unit 75605 VA 65.00% 49143 VA
Equipment 3000 VA 100.00% 3000 VA
Receptacle 70088 VA 57.13% 40044 VA Total Est. Demand Current: 497 A
Power 21600 VA 100.00% 21600 VA Total Conn. Current: 638 A
Other 20403 VA 100.00% 20403 VA Total Est. Demand: 179130 VA
Lighting 23456 VA 125.00% 29320 VA Total Conn. Load: 229769 VA
HVAC 15723 VA 100.00% 15723 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 638 A
Total Conn. Load: 229769 VA
20 SPACE -- -- -- 0 VA --
19 SPACE -- -- -- 0 VA --
18 SPACE -- -- -- 0 VA --
17 SPACE -- -- -- 0 VA --
16 SPACE -- -- -- 0 VA --
15 SPACE -- -- -- 0 VA --
14 SPACE -- -- -- 0 VA --
13 SPACE -- -- -- 0 VA --
12 SPACE -- -- -- 0 VA --
11 SPACE -- -- -- 0 VA --
10 SPACE -- -- -- 0 VA --
9 SPACE -- -- -- 0 VA --
8 SPACE -- -- -- 0 VA --
7 PNL ELE 3 150 A 150 A 34296 VA
6 PNL ELD 3 100 A 100 A 21600 VA
5 GENERATOR DAMPER MOTOR 3 20 A 20 A 1680 VA
4 PNL EKA 3 350 A 350 A 90469 VA
3 PNL ELD 3 100 A 100 A 0 VA
2 PNL ELA 3 225 A 225 A 37697 VA
1 PNL ELB 3 225 A 225 A 44090 VA
CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks
Notes:
Enclosure: Type 1 MCB Rating: 1000 A
Mounting: SURFACE Wires: 4 Mains Rating:
Supply From: T2 Phases: 3 Mains Type:
Location: ELECTRICAL 115 Volts: 120/208 Wye A.I.C. Rating:
Switchboard: EDL EXISTING
S
K K
K
K
A T
S
2 3
B
A
C
(X)
(X)
(X) (X)
(X)
(X)
(X)
(X)
(X)
(X)
(X)
(X)
(X)(X)
(X)
(X)
(X) (X) (X)
(X)
(X)
(X)(X)(X)
(X)
(X)
(X)
N.I.C.
N.I.C.
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
K
JO
S A
R C
H
IT
E C
T S
P Y
R
IG
H T
S W
A ld er S t., S ui te
P or tla nd
, O R
P h on e:
3/
4-
111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204
Tel 503.416.2400 Fax 206.267.1701
SAZAN# 257-20047
/2
/2
:3
:4
A
M
LIGHTING DEMOLITION -
FLOOR PLAN
04.02.21
ED2.01
IS
S
U E
D F
O R
P E
R M
IT
20018
O A
K C
R E
E K
E X
P A
N S
IO
N
L O
C H
N E
R R
D S
E A
L B
A N
Y
O R
O R
E G
O N
Y O
U T
H A
U T
H O
R
IT
Y
1/4" = 1'-0"ED2.01
1 LIGHTING DEMOLITION FLOOR PLAN
SHEET NOTES:
1. ALL ELECTRICAL IN WALLS AND PARTITIONS TO BE DEMOLISHED
(SHOWN OR NOT SHOWN) SHALL BE REMOVED BACK TO
SOURCE. REPAIR AND FINISH WALLS AT ALL EXISTING
COVERPLATES AND BOXES TO BE REMOVED.
2. CONTRACTOR MAY USE ANY CIRCUITS MADE AVAILABLE DUE
TO DEMOLITION. ANY EXTRA CIRCUITS MADE AVAILABLE AND
NOT USED SHALL BE LABELED AS SPARE.
3. CONTRACTOR TO RETURN ALL DEMOLISHED LIGHT FIXTURES,
EXIT SIGNS TO OWNER FOR OWNER'S DISPENSATION.
4. POWER AND LIGHTING IN AREAS NOT SHOWN ARE EXISTING TO
REMAIN.
A T
S
B
A
C
(E) TU 4-31
(E) TU 4-30
(E) (E)
(E)(E)
(X)
(X) (X)
(X)
(X) (X) (X) (X)
(X)
(X) (X)
(X)
(X)(X)
N.I.C.
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
K
JO
S A
R C
H
IT
E C
T S
P Y
R
IG
H T
S W
A ld er S t., S ui te
P or tla nd
, O R
P h on e:
3/
4-
111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204
Tel 503.416.2400 Fax 206.267.1701
SAZAN# 257-20047
/2
/2
:3
:4
A
M
ELECTRICAL
DEMOLITION - FLOOR
PLAN
04.02.21
ED3.01
IS
S
U E
D F
O R
P E
R M
IT
20018
O A
K C
R E
E K
E X
P A
N S
IO
N
L O
C H
N E
R R
D S
E A
L B
A N
Y
O R
O R
E G
O N
Y O
U T
H A
U T
H O
R
IT
Y
1/4" = 1'-0"ED3.01
1 ELECTRICAL DEMOLITION FLOOR PLAN
1. TERMINAL UNIT TO BE DEMOLISHED. COORDINATE DE-
ENERGIZING OF MECHANICAL TERMINAL UNIT AND REMOVE
CONDUIT, CONDUCTORS, AND DISCONNECTING MEANS.
1FLAG NOTES:
SHEET NOTES:
1. ALL ELECTRICAL IN WALLS AND PARTITIONS TO BE DEMOLISHED
(SHOWN OR NOT SHOWN) SHALL BE REMOVED BACK TO
SOURCE. REPAIR AND FINISH WALLS AT ALL EXISTING
COVERPLATES AND BOXES TO BE REMOVED.
2. CONTRACTOR MAY USE ANY CIRCUITS MADE AVAILABLE DUE
TO DEMOLITION. ANY EXTRA CIRCUITS MADE AVAILABLE AND
NOT USED SHALL BE LABELED AS SPARE.
3. CONTRACTOR TO RETURN ALL DEMOLISHED LIGHT FIXTURES,
EXIT SIGNS TO OWNER FOR OWNER'S DISPENSATION.
4. POWER AND LIGHTING IN AREAS NOT SHOWN ARE EXISTING TO
REMAIN.
64"
OS
O S
OS
D M
D M
OS
O S
O S
OS
OS
LV(b)
OS
OS
OS OS
LV(a)
B
A
C
57 SF
STAFF TLT
63 SF
FILE STORAGE
142 SF
MED EXAM
71 SF
DENTAL UTILITY
59 SF
OFFICE
87 SF
PSYCH OFFICE
107 SF
PSYCH OFFICE
108 SF
DENTAL EXAM
58 SF
MED UTILITY
45 SF
PAT TLT
45 SF
SOILED HOLDING/
POCT
144 SF
NURSE STATION
291 SF
HALLWAY
67 SF
WAITING
100 R6 /ELE-31 R6 /ELE-31
R6 /ELE-31
R3 /ELE-31
R3 /ELE-31
R3 /ELE-31
R3 /ELE-31
R3 /ELE-31
R3 /ELE-31
R3 /ELE-31
R3 /ELE-31
R6 /ELE-31
R7 /ELE-31
R4 /ELE-31
R6 /ELE-31
R1 /ELE-31
R2 /ELE-31
R2 /ELE-31
R2 /ELE-31
R1 /ELE-31
X1 /ELE-31
OS
N.I.C.
N.I.C.
X1 /ELE-31
R5 /ELE-31
R3 /ELE-31
(a)
(a)
(a)
(a)
(a)
(a)
(a)
(b) (b)
(b)
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
K
JO
S A
R C
H
IT
E C
T S
P Y
R
IG
H T
S W
A ld er S t., S ui te
P or tla nd
, O R
P h on e:
3/
4-
111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204
Tel 503.416.2400 Fax 206.267.1701
SAZAN# 257-20047
/2
/2
:3
:5
A
M
LIGHTING - FLOOR PLAN
04.02.21
E1.01
IS
S
U E
D F
O R
P E
R M
IT
20018
O A
K C
R E
E K
E X
P A
N S
IO
N
L O
C H
N E
R R
D S
E A
L B
A N
Y
O R
O R
E G
O N
Y O
U T
H A
U T
H O
R
IT
Y
1/4" = 1'-0"E1.01
1 ELECTRICAL LIGHTING - FIRST FLOOR PLAN
SHEET NOTES:
1. REFER TO E0.00 FOR GENERAL NOTES.
2. UNLESS OTHERWISE NOTED, WIRING SHALL BE 3/4"C, 2#12. 1#12
GND. THHN/THWN.
3. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF ALL
LIGHTING FIXTURES AND OTHER ELECTRICAL DEVICES WITH
ARCHITECTURAL DRAWINGS AND ACTUAL FIELD CONDITIONS.
4. ALL CONDUIT SHALL BE CONCEALED INSIDE WALLS OR ABOVE
CEILINGS WHENEVER POSSIBLE.
5. DYMO LABEL EACH JUNCTION BOX, COVERPLATE, AND/OR
SWITCH WITH CIRCUIT DESIGNATION.
6. PROVIDE UNSWITCHED CONDUCTORS TO EXIT SIGNS. PROVIDE
SWITCHED AND UNSWITCHED CONDUCTORS TO EMERGENCY
LIGHTING FIXTURES.
7. ALL EGRESS LIGHTING TO HAVE BATTERY BACKUP.
64"
CR
CR
4 4 4
J J
J
J
A T
S
FACP
9A
B
A
C
7A
8A
57 SF
STAFF TLT
63 SF
FILE STORAGE
142 SF
MED EXAM
71 SF
DENTAL UTILITY
59 SF
OFFICE
87 SF
PSYCH OFFICE
107 SF
PSYCH OFFICE
108 SF
DENTAL EXAM
58 SF
MED UTILITY
45 SF
PAT TLT
45 SF
SOILED HOLDING/
POCT
144 SF
NURSE STATION
291 SF
HALLWAY
67 SF
WAITING
FCU-10
BS-02
FCU-02
FCU-04
EDH-01
BS-01
+44" +44" +44"
+48"
+44" +44"+44"
+44"
+36"
+44"
+44"
+44"
+36"
+44"
+44"
+44"
+44"
+44"
AIR COMPRESSOR
WATER RECYCLE
VACUUM
+44"
FCU-06
FCU-05
FCU-07
FCU-09
FCU-03
FCU-08
FCU-01
(E)
(E)
(E)(E)
N.I.C.
ELE
ELE-17
ELE-17
ELE-17
ELE-15
ELE-15
ELE-15
ELE-9 ELE-9
ELE-19
ELE-19
ELE-27
ELE-1
ELE-27
ELE-29 ELE-29
ELE-37
ELE-7
ELE-7
ELE-14,16
ELE-14,16
ELE-14,16
ELE-14,16
ELE-14,16
ELE-14,16
ELE-14,16
ELE-14,16
ELE-14,16
ELE-25 ELE-25
ELE-21
ELE-25
ELE-21
ELE-19
ELE-21
ELE-21
ELE-29
ELE-29
ELE-27
ELE-27
ELE-5 ELE-5 ELE-5
ELE-3
ELE-3
ELE-1
ELE-1
ELE-1
ELE-1
ELE-7
ELE-7
ELE-7
ELE-9
ELE-9
ELE-10,12
ELE-6,8
ELE-14,16
ELE-14,16
ELE-18,20,22
ELE-23
ELE-11
ELE-13
EXISTING TO
REMAIN
ELE-33
ELE-14,16
ELE-35
RCP-1
2 2
TPV-1
ELE-36
EMERGENCY
GENERATOR
(E)
ELECTRICAL
(E)
ELECTRICAL
DOMESTIC HOT
WATER AND
SPRINKLER RISER
(E)
EDH
ATS
EDL
MDH
LA
T1 T2
MDL
SDP
ELD
ENGINEERING
(E)
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
K
JO
S A
R C
H
IT
E C
T S
P Y
R
IG
H T
S W
A ld er S t., S ui te
P or tla nd
, O R
P h on e:
3/
4-
111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204
Tel 503.416.2400 Fax 206.267.1701
SAZAN# 257-20047
/2
/2
:4
:4
P
M
ELECTRICAL - FLOOR
PLAN
04.02.21
E2.01
IS
S
U E
D F
O R
P E
R M
IT
20018
O A
K C
R E
E K
E X
P A
N S
IO
N
L O
C H
N E
R R
D S
E A
L B
A N
Y
O R
O R
E G
O N
Y O
U T
H A
U T
H O
R
IT
Y
1 Addendum 1 06-01-21
1/4" = 1'-0"E2.01
1 ELECTRICAL FLOOR PLAN
1. VERIFY EQUIPMENT LOCATION WITH ARCHITECT AND
EQUIPMENT VENDOR PRIOR TO ROUGH IN.
2. CONNECT EXISTING RECEPTACLES TO NEW PANELBOARD AS
SHOWN.
3. PROVIDE (1) 4" EMPTY CONDUIT WITH PULLSTRING FROM
MDF/IDF ROOM TO NEW REMODEL SPACE. STUB IN CEILING
SPACE AND LABEL FOR FUTURE". FIELD VERIFY EXACT MDF/IDF
ROOM AND APPROXIMATE LOCATION IN REMODEL SPACE PRIOR
TO BID.
1FLAG NOTES:
SHEET NOTES:
1. REFER TO E0.00 FOR GENERAL NOTES.
2. UNLESS OTHERWISE NOTED, WIRING SHALL BE 3/4"C, 2#12. 1#12
GND. THHN/THWN.
3. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF ALL
LIGHTING FIXTURES AND OTHER ELECTRICAL DEVICES WITH
ARCHITECTURAL DRAWINGS AND ACTUAL FIELD CONDITIONS.
4. ALL CONDUIT SHALL BE CONCEALED INSIDE WALLS OR ABOVE
CEILINGS WHENEVER POSSIBLE.
5. DYMO LABEL EACH JUNCTION BOX, COVERPLATE, AND/OR
SWITCH WITH CIRCUIT DESIGNATION.
1 Expires: 12/31/19
B
A
C
HP-01
ERV-01
(E) ACU - 4
ELE-28,30,32ELE-24,26
ELE-2,4
WP
(ROOF)
WP
(ROOF)
ELE-34
ELE-34
NEMA 3R
NEMA 3R NEMA 3R
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
K
JO
S A
R C
H
IT
E C
T S
P Y
R
IG
H T
S W
A ld er S t., S ui te
P or tla nd
, O R
P h on e:
3/
4-
111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204
Tel 503.416.2400 Fax 206.267.1701
SAZAN# 257-20047
/2
/2
:3
:0
A
M
ELECTRICAL - ROOF
PLAN
04.02.21
E2.02
IS
S
U E
D F
O R
P E
R M
IT
20018
O A
K C
R E
E K
E X
P A
N S
IO
N
L O
C H
N E
R R
D S
E A
L B
A N
Y
O R
O R
E G
O N
Y O
U T
H A
U T
H O
R
IT
Y
1/4" = 1'-0"E2.02
1 ELECTRICAL ROOF PLAN
SHEET NOTES:
1. REFER TO E0.00 FOR GENERAL NOTES.
2. UNLESS OTHERWISE NOTED, WIRING SHALL BE 3/4"C, 2#12. 1#12
GND. THHN/THWN.
3. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF ALL
LIGHTING FIXTURES AND OTHER ELECTRICAL DEVICES WITH
ARCHITECTURAL DRAWINGS AND ACTUAL FIELD CONDITIONS.
4. ALL CONDUIT SHALL BE CONCEALED INSIDE WALLS OR ABOVE
CEILINGS WHENEVER POSSIBLE.
5. DYMO LABEL EACH JUNCTION BOX, COVERPLATE, AND/OR
SWITCH WITH CIRCUIT DESIGNATION.
PANEL
"ELE"
8, 5 A
M
EUH-1
C
PANEL "K"PANEL "LA"PANEL "LB"
(IN GYM)
PANEL "LB"
400A ST
PANEL "R"
CL
LB
JO
PANEL "R"
JO
PANEL "R"
CL
LB
HA
PANEL "R"PANEL "R"PANEL "R"
M
JJ J J J J
PANEL
"ELA"
PANEL
"ELA2"
C
PANEL
"ELA"
PANEL
"ELA2"
C
PANEL
"ELA"
PANEL
"ELA2"
C
PANEL
"ELA"
PANEL
"ELA2"
C
GEN SET
DAMPER
MOTORS
PANEL
"ELB"
PANEL
"ELC"
PANEL
"ELD"
UPS
PANEL
"EKA"
PANEL
"EKB"
UTILITY
TRANSFORMER
1000A
UTILITY
METER
1000A
1000A, 480/277V, 3-PH, 4-W, 1/2N, 35kAIC
(3) 200A
SPACES
300/3
PANEL "MDL", 120/208V, 3-PH, 4-W, 600A BUS
T1
225KVA
TRANSFORMER
480-12/208V.
600/3 30/3 225/3
225A 3PDT
CONTACTOR
ENERGIZED
WHEN EMERGENCY
POWER PRESENT
600/3
600A/3P
AUTO TRANSFER
SWITCH "ATS-1"
3"C.(2) 3"C.
400/3100/3
3-1/2"C.
3-#350, 1#1/0 GND.
1-1/2"C.
4-#2, & GND.
100/3
1-1/2"C.
4-#2, & GND.
100/3
1-1/2"C.
4-#250, & GND.
(3) 200A
SPACES
PANEL "SDP", 480/277V, 3-PH, 4-W, 225A BUS
50/3, (CL, LB)
100/3 (JO)
1"C.
4-#6 (CL, LB)
1-1/2"C.
4-#2 (JO)
1-1/2"C.
4-#2
50/3
1"C.
4-#6
50/3
1-1/2"C.
4-#2.
1-1/2"C.
4-#2
50/3
1-1/4"C.
4-#3
(3) 200A
SPACES
PANEL "EDH", 480/277V, 3-PH, 4-W, 600A BUS
(2) 3"C.
3-#350, 1#2/0G 1#2 N
(2) 3"C.
3-#350, 1#2/0G 1#2 N
30/3
3/4"C.
4-#10
450/3
350KW
480/277V, 3-PH, 4W.
(2) 2-1/2"C.
3-#4/0.
1#2/G 1#2 N
GENERATOR SET
ACU-3
38 FLA
ACU-3
38 FLA
CL
LB
JO
CL LB JO
150/3
(CL, LB, JO)
80/3
(CR, HA)
1-1/2"C.
3-#3 1#8 G
(CL, JB, JO)
1-1/4"C.
3-#6 1#10G
1"C.
3-#6
1-#10 G
ACU-3
38 FLA
80/3
1-1/4"C.
3-#6 1#10 G
ACU-2
38 FLA
80/3
1-1/4"C.
3-#6 1#10 G
ACU-4
38 FLA
80/3
1-1/4"C.
3-#6 1#10 G
ACU-5
38 FLA
80/3
1-1/4"C.
3-#6 1#10 G
400/3
T2
300KVA
TRANSFORMER
480-12/208V.
(3) 3"C.3-1/2"C
PANEL "EDL", 120/208V, 3-PH, 4-W, 1000A BUS, 800A NEUT. 25K AIC
1000/3 225/3
2-1/2"C.
4-#4/0
2-1/2"C.
4-#4/0 1-#2G.
2"C.
4-#1 1-#4G.
125/3 225/3
2-1/2"C.
4-#4/0 1-#2G.
20/2 150/3
2-1/2"C.
4-#4/0
2"C.
4-#1/0
100/3
1-1/4"C 4-#2 1-#8G.
350/3
3-1/2"C 3-#500 1-#250 G.
1-1/4"C.
4-#4
3-#350, 1-#3/0 NEUT,
3-#350, 1-#4 GND.
3-#500, 1-#2 G.
4-#400
& GND.
150/3
1-1/2"C 4-#1/0 1-#6G.
PROJECT NO.:
ISSUE DATE:
REVISIONS:
C
LA
R K
K
JO
S A
R C
H
IT
E C
T S
P Y
R
IG
H T
S W
A ld er S t., S ui te
P or tla nd
, O R
P h on e:
3/
4-
111 SW Fifth Ave, Ste 2120 Portland, Oregon 97204
Tel 503.416.2400 Fax 206.267.1701
SAZAN# 257-20047
/2
/2
:3
:1
A
M
ELECTRICAL ONE-LINE
DIAGRAM
04.02.21
E6.00
IS
S
U E
D F
O R
P E
R M
IT
20018
O A
K C
R E
E K
E X
P A
N S
IO
N
L O
C H
N E
R R
D S
E A
L B
A N
Y
O R
O R
E G
O N
Y O
U T
H A
U T
H O
R
IT
Y
12" = 1'-0"E6.00
1 EXISTING ONE-LINE DIAGRAM
SHEET NOTES:
1. PROVIDE NEW CIRCUIT BREAKER IN DISTRIBUTION BOARD 'ELD'
TO FEE NEW PANELBOARD 'ELE' PROVIDE NEW CONDUIT AND
CONDUCTORS.
| 257-20047 MEP Central v20_Theophilus. |
| E0.00 - GENERAL NOTES, ABBREVIATIONS AND SHEET INDEX |
| E0.01 - ELECTRICAL LEGEND |
| E0.03 - ELECTRICAL SCHEDULES |
| ED2.01 - LIGHTING DEMOLITION - FLOOR PLAN |
| ED3.01 - ELECTRICAL DEMOLITION - FLOOR PLAN |
| E1.01 - LIGHTING - FLOOR PLAN |
| E2.01 - ELECTRICAL - FLOOR PLAN |
| E2.02 - ELECTRICAL - ROOF PLAN |
| E6.00 - ELECTRICAL ONE-LINE DIAGRAM |