ATT 8 - 578-371_Joliet_CBOC_Add_3_Part_7.pdf

PDF 19 MB Posted

Attached to
578-371 Expansion of Parking Structure at Joliet CBOC Revised
Solicitation number
36C77624B0009
Issued by

About this file

This document provides details on a federal contract opportunity for expansion of a parking structure at a Veterans Affairs community-based outpatient clinic in Joliet, Illinois. The solicitation number is 36C77624B0009 and is seeking proposals to expand the existing parking structure to add approximately 150 additional parking spaces. The opportunity was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. Interested parties should submit proposals in response to the revised solicitation by the upcoming deadline in order to be considered for the contract award scheduled for later this year. The contract aims to address parking capacity issues at the outpatient clinic through expanding the current parking facility.

View the file

Other files

File Type Posted
36C77624B0009 0011 signed.pdf PDF
Joliet CBOC Parking Expansion - Bid Opening Attendance.pdf PDF
S07 - Abstract of Bids OF 1419 Joliet -S.pdf PDF
Amend 0010 ATT 1 - 578-371 Joliet CBOC Addendum 3 PM R 240502.pdf PDF
36C77624B0009 0010 signed.pdf PDF
36C77624B0009 0009.pdf PDF
Joliet CBOC Technical Questions 1-41 VA Responses Final.pdf PDF
36C77624B0009 0008.pdf PDF
36C77624B0009 0007.pdf PDF
S05 - Joliet CBOC - Technical Questions - Updated 041524.pdf PDF
13974 - Joliet Geotechnical Report.pdf PDF
S05 - Joliet CBOC - Technical Questions 1-41 VA Responses.pdf PDF
26 24 13 Distribution Switchboards.pdf PDF
36C77624B0009 0006.pdf PDF
26 05 73 Overcurrent Protective Device Coordination Study.pdf PDF
26 22 00 Low Voltage Transformers.pdf PDF
13974 - Proposed Parking Addition REV01.pdf PDF
26 24 16 Panelboard.pdf PDF
Pre-bid Site Visit 2 Sign-in Sheet.pdf PDF
36C77624B0009 0005.pdf PDF
36C77624B0009 0004.pdf PDF
36C77624B0009 0003.pdf PDF
Updated - Wage Rates - Will County 2.23.24.pdf PDF
Site Visit 2 Details.pdf PDF
578-371 Pre-bid Site Visit 031824.pdf PDF
36C77624B0009 0002.pdf PDF
Att - 4 -578-371_Joliet_CBOC_Add_3_Part_3_R1.pdf PDF
36C77624B0009 0001.pdf PDF
ATT 10 - 578-371_Joliet_CBOC_Add_3_Parts_Index.pdf PDF
ATT 9 - 578-371_Joliet_CBOC_Add_3_Part_8.pdf PDF
ATT 12 - Limitations on Subcontracting.pdf PDF
ATT 7 - 578-371_Joliet_CBOC_Add_3_Part_6.pdf PDF
ATT 13 - Wage Rates - Will County 2.23.24.pdf PDF
S02 - 36C77624B0009 - Solicitation - Joliet Parking Expansion.pdf PDF
ATT 1 - Specifications Book.pdf PDF
ATT 5 - 578-371_Joliet_CBOC_Add_3_Part_4.pdf PDF
ATT 3 - 578-371_Joliet_CBOC_Add_3_Part_2.pdf PDF
ATT 6 - 578-371_Joliet_CBOC_Add_3_Part_5.pdf PDF
ATT 11 - 578-371 Construction SOW Final.pdf PDF
ATT 4 - 578-371_Joliet_CBOC_Add_3_Part_3.pdf PDF
ATT 2 - 578-371_Joliet_CBOC_Add_3_Part_1.pdf PDF
ATT 14 - Site Visit Instructions.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ABBREVIATIONS

ADJ ADJUSTABLE

AFF ABOVE FINISHED FLOOR

AL ALUMINUM

ALT ALTERNATE

AP ACCESS PANEL

APD AIR PRESSURE DROP

BAS BUILDING AUTOMATION SYSTEM

BHP BRAKE HORSEPOWER

BLDG BUILDING

BOD BOTTOM OF DUCT

BOP BOTTOM OF PIPE

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNITS PER HOUR

BYP BYPASS

CA COMBUSTION AIR

CAV CONSTANT AIR VOLUME

CFM CUBIC FEET PER MINUTE

CHW CHILLED WATER

CL CENTERLINE

CLG CEILING

CONC CONCRETE

COND CONDENSATE

COP COEFFICIENT OF PERFORMANCE

CNDW CONDENSER WATER

CPD CONDENSATE PUMP DISCHARGE

DB DRY BULB

DCW DOMESTIC COLD WATER

DDC DIRECT DIGITAL CONTROL

DEG DEGREE

DP DIFFERENTIAL PRESSURE

DX DIRECT EXPANSION

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC ELECTRICAL CONTRACTOR

ECON ECONOMIZER

EER ENERGY EFFICIENCY RATIO

EFF EFFICIENCY

EL ELEVATION

ELEC ELECTRIC/ELECTRONIC

ENGR ENGINEER

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE

EX EXISTING

EXH EXHAUST

EXP EXPANSION

FA FIELD ADJUSTABLE

FC FAIL CLOSED

FE FUME HOOD EXHAUST

FLA FULL LOAD AMPS

FLR FLOOR

FO FAIL OPEN

FOF FUEL OIL FILL

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FPI FINS PER INCH

FPM FEET PER MINUTE

FPS FEET PER SECOND

GA GAUGE

GAL GALLONS

GALV GALVANIZED

GC GENERAL CONTRACTOR

GE GENERAL EXHAUST

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

HHW HEATING HOT WATER

HOA HAND-OFF-AUTOMATIC

HP HORSE POWER

HPC HIGH PRESSURE CONDENSATE

HPS HIGH PRESSURE STEAM

HW HOT WATER

HZ HERTZ

IA INSTRUMENT AIR

KE KITCHEN EXHAUST

KEF KITCHEN EXHAUST FAN

KW KILOWATT

LAT LEAVING AIR TEMPERATURE

LPC LOW PRESSURE CONDENSATE

LPS LOW PRESSURE STEAM

LRA LOCKED ROTOR AMPS

LWT LEAVING WATER TEMPERATURE

MBH THOUSANDS OF BTU PER HOUR

MC MECHANICAL CONTRACTOR

MCA MINIMUM CIRCUIT AMPS

MEP MECHANICAL, ELECTRICAL AND PIPING

MER MECHANICAL EQUIPMENT ROOM

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

NA NOT APPLICABLE

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OA OUTSIDE AIR

OC ON CENTER

OV OUTLET VELOCITY

PC PLUMBING CONTRACTOR

PD PRESSURE DROP

PH PHASE

PP POLYPROPYLENE

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH ABSOLUTE

PSIG POUNDS PER SQUARE INCH GAUGE

R RETURN

RA RETURN AIR

RH RELATIVE HUMIDITY

RPM REVOLUTIONS PER MINUTE

S SUPPLY

SA SUPPLY AIR

SCH SCHEDULE

SF SQUARE FOOT

SP STATIC PRESSURE

SS STAINLESS STEEL

TA TRANSFER AIR

TDH TOTAL DYNAMIC HEAD

TP TOTAL PRESSURE

TSP TOTAL STATIC PRESSURE

TYP TYPICAL

UC UNDERCUT

UV ULTRAVIOLET

V VOLTS

VAV VARIABLE AIR VOLUME

VP VELOCITY PRESSURE

VTR VENT THRU ROOF

WB WET BULB

WC WATER COLUMN

WG WATER GAUGE

AO ANALOG OUTPUT (CONTROLS)

AI ANALOG INPUT (CONTROLS)

DI DIGITAL INPUT (CONTROLS)

DO DIGITAL OUTPUT (CONTROLS)

EQUIPMENT ABBREVIATIONS

AAV AUTOMATIC AIR VENT

AC AIR CONDITIONING

ACC AIR COOLED CONDENSER

ACCU AIR COOLED CONDENSING UNIT

ACU AIR CONDITIONING UNIT

AHU AIR HANDLING UNIT

CC COOLING COIL

CH CHILLER

CP CONDENSATE PUMP/CONTROL PANEL

CT COOLING TOWER

CUH CABINET UNIT HEATER

CV CONVERTOR

AS AIR SEPARATOR

AT AIR TERMINAL DEVICE

B BOILER

BBS BOILER BLOWDOWN SEPARATOR

BDD BACKDRAFT DAMPER

BFP BACKFLOW PREVENTER

BFS BOILER FEEDWATER SYSTEM

BH BOOSTER HUMIDIFIER

D DAMPER

DOAS DEDICATED OUTDOOR AIR SYSTEM

EF EXHAUST FAN

EH EXHAUST HOOD

EBH ELECTRIC BASEBOARD HEATER

ERU ENERGY RECOVERY UNIT

ERV ENERGY RECOVERY VENTILATOR

ET EXPANSION TANK

EUH ELECTRIC UNIT HEATER

EV EXHAUST VALVE

EVAP EVAPORATOR

F FILTER

FACP FIRE ALARM CONTROL PANEL

FCU FAN COIL UNIT

FD FLOOR DRAIN

FOP FUEL OIL PUMP

FOT FUEL OIL TANK

FPB FAN POWERED BOX

FT FLASH TANK

FTR FIN TUBE RADIATION

GEN GENERATOR

H HUMIDIFIER

HC HEATING COIL

HP HEAT PUMP

HRC HEAT RECOVERY COIL

HT HEAT TRACE

HX HEAT EXCHANGER

IH INTAKE HOOD

MAU MAKEUP AIR UNIT

MCC MOTOR CONTROL CENTER

P PUMP

PHC PREHEAT COIL

PRV PRESSURE REDUCING VALVE

PTAC PACKAGED TERMINAL AIR CONDITIONER

RCP RADIANT CEILING PANEL

RF RETURN FAN

RH RELIEF HOOD

RHC REHEAT COIL

RTU ROOFTOP UNIT

SAD SOUND ATTENUATING DEVICE

SD SMOKE DETECTOR

SF SUPPLY FAN

SRV SAFETY RELIEF VALVE

ST STORAGE TANK

T TANK

UH UNIT HEATER

UV UNIT VENTILATOR

V VALVE

VAV VARIABLE AIR TERMINAL DEVICE

VFD VARIABLE FREQUENCY DRIVE

WCC WATER COOLED CONDENSER

WF WATER FILTER

DAMPERS AND ACTUATORS

MANUAL BALANCING DAMPER

CONTROL DAMPER (MOTORIZED)

M

BACKDRAFT DAMPER

BD

1 1/2 HOUR RATED FIRE DAMPER

F2

3 HOUR RATED FIRE DAMPER

F3

1 1/2 HOUR RATED FIRE/SMOKE DAMPER

FS

OPPOSED BLADE DAMPER

PARALLEL BLADE DAMPER

MANUAL ACTUATOR

MOTORIZED ACTUATOR

M

SOLENOID ACTUATOR

S

DUCT SYMBOLS

SUPPLY DIFFUSER ANNOTATION

DUCT SIZE (INCHES)

∅ INDICATES ROUND

SUPPLY AIR

DUCT (SA)

AIR QUANTITY

(CFM)

SUPPLY

DIFFUSERS (S)

EXISTING

S-1

4508"Ø SA

RETURN/EXHAUST GRILLE ANNOTATION

RETURN AIR DUCT

(RA)

DUCT SIZES

IN INCHES

AIR QUANTITY

(CFM)

RETURN

GRILLE (R)

EXISTING

R-1

25010x10 RA

EXHAUST AIR DUCT

(EA)

DUCT SIZES

IN INCHES

AIR QUANTITY

(CFM)

EXHAUST

GRILLE (E)

EXISTING

E-1

25010"Ø EA

(X)SNEW

(X)RNEW

(X)EEXISTING

DUCTWORK

SINGLE LINE

EXISTING DUCT TO BE REMOVED

DOUBLE LINE

EXISTING DUCT TO REMAIN

FLOW DIRECTION DESIGNATION

DUCT CONTINUATION BREAK

SUPPLY AIR (SA) OR

OUTDOOR AIR (OA) DUCT

EXHAUST AIR (EA) DUCT

RETURN AIR (RA), RELIEF AIR,

OR TRANSFER AIR (TA) DUCT

GENERAL SYMBOLS

EQUIPMENT TAG

KEYNOTE

POINT OF NEW CONNECTION TO EXISTING

WHEN ON DEMO SHEET: END POINT OF DEMO

DETAIL REFERENCE (TOP=DETAIL NUMBER,

BOTTOM=DRAWING NUMBER)

M-1

PLAN CONTINUATION REFERENCE

(BOTTOM=DRAWING NUMBER)

REFER

M-1

SECTION DESIGNATION (TOP=SECTION

NUMBER, BOTTOM=DRAWING NUMBER)

M-1

PIPING

SINGLE LINE

EXISTING PIPING TO BE REMOVED

DOUBLE LINE

EXISTING PIPING TO REMAIN

FLOW DIRECTION DESIGNATION

PIPE CONTINUATION BREAK

ELBOW DOWN

ELBOW UP

BOTTOM CONNECTION

TOP CONNECTION

PIPE TEE

PIPING ANNOTATION

CHILLED WATER SUPPLY/RETURNCHWS/R

CONDENSER WATER SUPPLY/RETURNCWS/R

HEATING HOT WATER SUPPLY/RETURNHWS/R

HEAT RECLAIM WATER SUPPLY/RETURNHRWS/R

LOW PRESSURE STEAM (<15 PSI)LPS

LOW PRESSURE CONDENSATELPC

HIGH PRESSURE STEAM (XX=PRESSURE)HPS (XX)

HIGH PRESSURE COND. (XX=PRESSURE)HPC (XX)

PROCESS CHILLED WATER SUPPLY/RETURNPCHWS/R

REFRIGERANT LIQUIDRL

REFRIGERANT SUCTIONRS

NATURAL GASNG

PIPING SPECIALTIES

GENERAL PIPELINE STRAINER WITHOUT DRAIN

GENERAL PIPELINE STRAINER WITH DRAIN

BASKET STRAINER

FLANGE

UNION

CAP

THERMOMETER

PRESSURE GAUGE

MANUAL AIR VENT

TEST PORT (PRESSURE/TEMP.)

PIPING VALVES

BUTTERFLY VALVE

GATE VALVE

GLOBE VALVE

BALL VALVE

BALANCING VALVE

AUTO FLOW BALANCING VALVE

CHECK VALVE

SOLENOID VALVE

S

STEAM PRESSURE REDUCING VALVE (PRV)

2-WAY CONTROL VALVE

3-WAY MIXING VALVE

3-WAY DIVERTING VALVE

DRAIN VALVE WITH CAP

GAS PRESSURE REGULATOR

GAS SHUTOFF VALVE

REDUCED PRESSURE

BACKFLOW PREVENTER (RPP)

PRESSURE RELIEF VALVE (RV)

OR SAFETY VALVE (SV)

VACUUM RELIEF/VACUUM BREAKER

GENERAL MECHANICAL NOTES

1. THE CONTRACTORS WORK SHALL CONFORM TO ALL VA

POLICIES ON CONSTRUCTION PROCEDURES AND SHALL

COMPLY WITH ALL LOCAL CODES AND VA STANDARDS.

2. COORDINATE WITH THE VA FOR ANY EQUIPMENT

REMOVED THAT NEEDS TO BE RETURNED TO THE

OWNER.

3. COORDINATE WITH VA FOR TEMPORARY SYSTEM

SHUTDOWN PER REQUIREMENTS IN THE

SPECIFICATIONS.

4. ALL DUCTWORK SHALL BE FABRICATED OF SHEET METAL

IN ACCORDANCE WITH SMACNA STANDARDS.

5. RE-INSULATE AND PATCH EXISTING DUCTWORK AS

REQUIRED AFTER INSTALLATION OF NEW DUCTWORK OR

OTHER DEMOLITION THAT DISTURBS EXISTING

DUCTWORK AND INSULATION.

6. PROVIDE LOCKING TYPE BALANCING DAMPER AT EACH

DIFFUSER, GRILLE, AND BRANCH TAKE-OFF IN ALL

SUPPLY, RETURN, AND EXHAUST DUCTWORK. LOCATE

BALANCING DAMPER AS CLOSE TO THE BRANCH

TAKEOFF AS POSSIBLE.

7. DUCT SIZE TO DIFFUSERS, REGISTERS, AND GRILLES

SHALL BE SAME AS NECK SIZE UNLESS OTHERWISE

NOTED.

8. DUCT SIZE TO AIR TERMINAL DEVICES SHALL BE SAME AS

INLET SIZE UNLESS OTHERWISE NOTED.

9. COORDINATE DIFFUSER, REGISTER, AND GRILLE

LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING

PLAN AND ALL OTHER CEILING DEVICES.

10. PROVIDE FLEXIBLE DUCTWORK FOR DIFFUSERS,

REGISTERS, AND GRILLES. FLEXIBLE DUCT SIZE SHALL BE

SAME AS NECK SIZE OF DIFFUSER OR GRILLE AND SHALL

HAVE MAXIMUM LENGTH OF 5'-0". REFER TO

SPECIFICATIONS FOR REQUIREMENTS.

11. LOCATE AIR TERMINAL DEVICES TO ALLOW ACCESS TO

AIR TERMINAL DEVICE CONTROLLERS. ACCESS

CLEARANCE IS SHOWN ON PLANS.

444 W. Lake St. Suite 1700 Chicago, IL 60606

312.583.7023 www.virtualenergysolutions.com

Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432

Drawing No.

Scale:

Date:

Checked By:Drawn By:Designed By:

Drawing Title:

Contract No.

File No.Building No.

Client Project No.

Project Title:Approved: Chief, failites Management Services

Approved: Medical Center Director

Approved:

Approved: Location:

VES Project Number: 191006

AS NOTED

VA JOLIET CBOC

JOLIET, ILLINOIS

578-371 36C25219D0020

© 2020 Virtual Energy Solutions, INC.

B

IM

/2

-M

A T

O C

-P a rk in g E x p a n s io n a t J o lie t C

B O

C

-3

/2

-J o lie t C

B O

C P a rk in g

E x p a n s io n M

E C

H

.r v t

/6 /2

:4

:0

P M

M001

MECHANICAL SYMBOLS AND

ABBREVIATIONS

PARKING EXPANSION AT

JOLIET CBOC

10/11/2023

EPTHEP

Revisions Date

ISSUED FOR 60% DD 12/30/2022

ISSUED FOR 90% CD 02/10/2023

ISSUED FOR 100% CD 03/07/2023

ISSUED FOR BID 03/24/2023

ISSUED FOR BID ADDENDUM 3 10/11/2023

F

F

F

Elev. Equip.

B003

Badge

B004

Phone

B002C

Home Based Primary

Care

B002

Stair #2

S-2

Comm.

B005

Reception

B001

Women's Restroom

B006

Men's Restroom

B011

HAC

B007

Copy Room

B009

Phone

B002A

Phone

B002B

Phone

B017

Phone

B016

A.O.

B015

Clinical Nurse Manager

B014

Chief Medical Director

B013

Patient Education/Group

Room

B011

Patient

Education/Exercise

B022

Store

B012

Corridor

C0-2

Corridor

C0-3

Corridor

C0-4

Corridor

C0-1

Mech.

B018

Elec.

B019

Gen Room

B020

PAS Call Center

B024

Education Storage

B022

Nutrition Services

B021

Main Conference Room

B023

Mech.

B025

Elevator

EL-1

New North Vestibule

Elec.

B026B

Lobby

S-1

200 CFM

S-1

100 CFM

12x10 SAVAV

Dx

Ex

Gx

Hx

Jx

Kx

K'x

Lx

1x 4x 6x 9x 12x 13x 14x

Cx

Bx

Ax

3x 5x 5.8x 8x 10x6.1x

Fx

A.E

15x

15y

15z 15aa

15bb

15cc

15dd

15ee

15ff

15gg15hh

15ii

9.5x1.2x

A

1 2

B

AHU-2

EXIST.

UH

003A

Mach. Room

003A

Elevator-2

E-2-2

T

T

S-3

260 CFM8x8 SA x S

A

12x10 SA

T

S-3

250 CFM

12x8 SA

VAV

B003A

AHU-1

EXIST.

AHU-3

EXIST.

AHU-4

EXIST.

EUH

EXISTING

DEMOLITION

NEW

PHASE LEGEND

444 W. Lake St. Suite 1700 Chicago, IL 60606

312.583.7023 www.virtualenergysolutions.com

Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432

Drawing No.

Scale:

Date:

Checked By:Drawn By:Designed By:

Drawing Title:

Contract No.

File No.Building No.

Client Project No.

Project Title:Approved: Chief, failites Management Services

Approved: Medical Center Director

Approved:

Approved: Location:

VES Project Number: 191006

AS NOTED

VA JOLIET CBOC

JOLIET, ILLINOIS

578-371 36C25219D0020

© 2020 Virtual Energy Solutions, INC.

N

B

IM

/2

-M

A T

O C

-P a rk in g E x p a n s io n a t J o lie t C

B O

C

-3

/2

-J o lie t C

B O

C P a rk in g

E x p a n s io n M

E C

H

.r v t

/6 /2

:4

:2

P M

MH100-N

BASEMENT LEVEL -

MECHANICAL VENTILATION

PLAN - NORTH

PARKING EXPANSION AT

JOLIET CBOC

10/11/2023

EPTHEP

1/8" = 1'-0"

1 BASEMENT LEVEL - MECHANICAL VENTILATION PLAN - NORTH

0 4' 8' 16'

Revisions Date

ISSUED FOR 60% DD 12/30/2022

ISSUED FOR 90% CD 02/10/2023

ISSUED FOR 100% CD 03/07/2023

ISSUED FOR BID 03/24/2023

ISSUED FOR BID ADDENDUM 1 04/21/2023

ISSUED FOR BID ADDENDUM 3 10/11/2023

Engineering Space

F

F

F2

Boiler Plant

Sound Booth

Control

Sound Booth

FMS

Elevator

EL-1

EXISTING STAIR

S-2

Corridor

C1-15

Rad Control

Dispensary

Storage

1116A

Diagnostic

Marco

Rad Room

Corridor

C1-13

Corridor

C1-15A

Corridor

C1-11

Toilet

Toilet

HAC

Toilet

1112E

Soiled Utility

1112A Storage

1112B

PM&R

Treatment

1112D

Eye Tech

Visual Fields

Treatment

1112C

Toilet

Toilet

1102A

Eye

Blood Draw

1114D

Eye

Blood Draw

1114C

Draw Analysis

1114E

Toilet

1114F

Blood Draw

1114B

Eye

Eye

Women Health Exam 21

Women Health Exam 20

Mobile Port Waiting

Toilet

1068A

Toilet

1031A

Pharm. D

Pharm. D

Nutritionist

Teleretinal

Cardio/Pod Shared

Office

Soiled Utility

Clean Utility

Social Worker

Shell Space

Corridor

C1-10

Podiatry Exam

Podiatry Exam

Tech Work Room

Audiology Exam

Cast Room

Podiatry Exam

Audiology Exam

Oxygen Evaluation

Pulminary Fuction

Arterial Blood Gas

Clean Utility

Soiled Utility

Control

Stor.

Corridor

C1-12

Corridor

C1-9 Corridor

Ambulance Bay

C1-36

Corridor

C1-8--

1065B

Elec. Clos.

1089A

Scale Alcove

PAS

Elec.

1114 --

1114A

Lobby

Elevator-1

E-2-1

Office

Vestibule

Dx

Ex

Gx

Hx

Jx

Kx

K'x

Lx

1x 4x 6x 9x 12x 13x 14x

Cx

Bx

Ax

3x 5x 5.8x 8x 10x6.1x

Fx

A.E

15x

15y

15z 15aa

15bb

15cc

15dd

15ee

15ff

15gg15hh

15ii

9.5x1.2x

A

1 2

B

T

T

T

T

T

T

T

T

T

T

T

T

TT

T

T

T

T

T

T

T

T

T

T

T

T

S-1

100 CFM

VAV

S-1

140 CFM

S-1

250 CFM

10x10 SA

EUH

R-1

100 CFM R-1

250 CFM

R-1

140 CFM

10x10 RA T

EXISTING

DEMOLITION

NEW

PHASE LEGEND

444 W. Lake St. Suite 1700 Chicago, IL 60606

312.583.7023 www.virtualenergysolutions.com

Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432

Drawing No.

Scale:

Date:

Checked By:Drawn By:Designed By:

Drawing Title:

Contract No.

File No.Building No.

Client Project No.

Project Title:Approved: Chief, failites Management Services

Approved: Medical Center Director

Approved:

Approved: Location:

VES Project Number: 191006

AS NOTED

VA JOLIET CBOC

JOLIET, ILLINOIS

578-371 36C25219D0020

© 2020 Virtual Energy Solutions, INC.

N

B

IM

/2

-M

A T

O C

-P a rk in g E x p a n s io n a t J o lie t C

B O

C

-3

/2

-J o lie t C

B O

C P a rk in g

E x p a n s io n M

E C

H

.r v t

/6 /2

:4

:2

P M

MH101-N

FIRST FLOOR - MECHANICAL

VENTILATION PLAN - NORTH

PARKING EXPANSION AT

JOLIET CBOC

10/11/2023

EPBBEP

1/8" = 1'-0"

1 FIRST FLOOR - MECHANICAL VENTILATION PLAN - NORTH

0 4' 8' 16'

Revisions Date

ISSUED FOR 60% DD 12/30/2022

ISSUED FOR 90% CD 02/10/2023

ISSUED FOR 100% CD 03/07/2023

ISSUED FOR BID 03/24/2023

ISSUED FOR BID ADDENDUM 1 04/21/2023

ISSUED FOR BID ADDENDUM 3 10/11/2023

MECHANICAL KEYNOTES

NUMBER KEYNOTE

9 CONNECT NEW RETURN DUCT TO EXISTING RETURN

MAIN/RISER IN THE AREA. VERIFY EXACT CONNECT POINT

IN FIELD.

W1

NOTE:

1.

2.

3.

4.

ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY

SMACNA.

WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE

REGARDLESS OF W DIMENSION.

ALL SINGLE THICKNESS VANES SHALL HAVE A 2" RADIUS, 1 1/2"

MAXIMUM SPACE BETWEEN VANES AND A 3/4" TRAILING EDGE.

WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" VANES SHALL BE

DOUBLE VANE TYPE.

DUCTWORK SQUARE VANE ELBOWS

N.T.S.

VANE

VANE

W

R 2/3W

W

W W

1/2W

W

1/6W

NOTE:

1.

2.

THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS

ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE

CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.

R SHALL

EQUAL

OR BE

GREATER

THAN W.

R SHALL

EQUAL

OR BE

GREATER

THAN

1/3W.

R

R SHALL

EQUAL

OR BE

GREATER

THAN

1/6W.

STANDARD RADIUS OR

LONG RADIUS ELBOW

SHORT RADIUS ELBOW

WITH ONE VANE

SHORT RADIUS ELBOW

WITH TWO VANES

R

DUCTWORK RADIUS ELBOWS

N.T.S.

W

DESIGNER'S NOTES:

1. THE SUPPLY REGISTER TAKE-OFF MAY BE USED FOR UP UP TO 25% OF THE MAIN

DUCT CFM. THE BRANCH DUCT TAKE-OFF MAY BE USED FOR UP TO 15% OF THE

MAIN DUCT CFM ANYTIME AND UP TO 40% WHEN THE MAIN DUCT VELOCITY IS 1000

FPM OR LESS. THE AIR SPLIT DUCT TAKE-OFF SHALL BE USED IN ALL

OTHER CASES AND MAY BE USED AT ANYTIME.

2. SHOW ALL VOLUME DAMPERS ON FLOOR PLANS.

AIR SPLIT DUCT TAKE-OFF

PLAN VIEW

BRANCH DUCT TAKE-OFF PLAN VIEW

SUPPLY REGISTER TAKE-OFF

PLAN VIEW

AIR

FLOW

AIR

FLOW

A

IR

F L

O W

SUPPLY REGISTER

OR BRANCH DUCT

TURNING VANES

MAIN

SUPPLY

DUCT

SEE FLOOR PLAN FOR

SPLIT DIMENSION

PROVIDE VOLUME

DAMPER

PROVIDE VOLUME

DAMPER

ADJUSTABLE

METAL ROD

OR LINKAGE

TOP REGISTER

MAIN

SUPPLY

DUCT

VOLUME EXTRACTOR; ADJUSTABLE

FROM FULLY CLOSED POSITION TO

CFM NOTED ON FLOOR PLANS

AIR

FLOW

AIR

FLOW

1/4 W OR 4"

MIN.

AIR

FLOW

MAIN SUPPLY

DUCT

A

IR

F L

O W

SUPPLY DUCTWORK TAKE-OFFS

N.T.S.

MAIN EXHAUST OR RETURN

PLAN VIEW

W

AIR

FLOW AIR

FLOW

PROVIDE VOLUME DAMPER

AT EACH BRANCH DUCT

1/4W OR 4"

MIN.

BRANCH DUCT

VD

EXHAUST OR RETURN BRANCH DUCTWORK

N.T.S.

NOTE:

1.

2.

DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR

FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.

INSULATION SEE

SPECIFICATION

DAMPER BLADE

1/8"

CLEARANCE

ALL AROUND

OUTSIDE END BEARING

INSIDE END BEARING

HANDLE WITH

LOCKING

QUADRANT

INSULATION

STAND-OFF

1/2"

ROUND ROD PIN

DUCT

STIFFEN BLADE

AS REQUIRED

SIDE ELEVATION SECTION

VOLUME DAMPER DETAIL

N.T.S.

SECTION "A-A"

"B" "B"

NOTES:

1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS

TIGHTLY.

2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE

PINS.

3. SEE SMACNA 2005, FIGURE 9-15

ACCESS PANEL

ACCESS DOOR

CASING

GASKET

HANDLE INSIDE

FLEXIBLE

WASHER

FACTORY

FABRICATED

LATCH

SECTION "B-B"

INSULATION

DUCT

GASKET

INSULATION

INSULATION

"A"

"A"

ACCESS PANEL AND DOOR DETAIL

N.T.S.

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

1/2" 1/2"

1/2"

FLANGED CONNECTION

ON FAN SIDE

WASHER 1-1/2" MIN. TO 3"

MAX. INSTALLED. 6"

NOMINAL WITH MATERIAL TAUT

FLEXIBLE

MATERIAL AS

SPECIFIED

1"x1/8" DRAW BAND

1"x1/8" BAND IRON

BOLT ON 4" CENTERS

5/16" FLANGE

DUCT

SHEET METAL SCREWS ON

12" CENTERS

RIVET ON 4"

CENTERS

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1"x1/8" BAND IRON

BOLT ON 4" CENTERS

1" FLANGE & HEMALTERNATE

POSITION

OF BOLT 1 1/2"

POCKET SLIP

DUCT

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1 1/2" MIN. TO 3"

MAX. INSTALLED. 6"

NOMINAL WITH MATERIAL TAUT

FLANGED

CONNECTION

ON FAN SIDE

WASHER

FLEXIBLE MATERIAL

AS SPECIFIED

FLEXIBLE DUCT CONNECTIONS AT EQUIPMENT

N.T.S.

420ONE 1 x 18 GA STRAP36

TWO 1/2∅ RODS

TWO 3/8∅. RODS

ONE 1 x 16 GA STRAP

50 700

ONE 1 x 22 GA STRAP

QUANTITY/SIZEMAX. DUCT ∅

HANGER STRAPS OR RODS

MAX. LOAD

LBS.

MAX.

IN.

SPACING

IN. IN.

NOTE:

TABULATED DATA FROM SMACNA

ALLOWS FOR DUCT REINFORCING AND

INSULATION, BUT NO EXTERNAL LOAD.

BAND

OVER 50"∅

HANGER RODS

BAND OF SAME

SIZE AS HANGER

STRAP

LOAD RATED

FASTENERS

50"∅

& UNDER

ROUND DUCT HANGERS

N.T.S.

NOTE:

ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS

AND FAN ROOM FLOORS SHALL BE PROVIDED WITH A 3" HIGH CONCRETE

CURB AROUND OPENING FOR DUCT.

SEAL HOLE WITH FIREPROOFING

MATERIAL AFTER DUCT INSTALLATION

2"x2"x1/4" ANGLE INSTALL

ON BOTH LONG

DIMENSION SIDES OF DUCT.

DUCT RISER - SEE FLOOR

PLANS FOR DETAILS

SEAL HOLE WITH FIREPROOFING

MATERIAL AFTER DUCT INSTALLATION

FLOOR

EXTEND ANGLE 3"

BEYOND DUCT

DUCT RISER - SEE FLOOR

PLANS FOR SIZES SHEET METAL SCREWS 4"

ON CENTER

1 1/2"x1 1/2"x1/8"

ANGLE INSTALL ON BOTH LONG

DIMENSION SIDES OF DUCT. FOR

DUCTS OVER 60" USE

2"x2"x1/8" ANGLE.

HOLE IN STRUCTURAL FLOOR

DUCT RISER

0.5 INCH WG TO 2 INCHES WG DUCT RISER SUPPORT

ARRANGE RISER SO

REINFORCER TRANSVERSE JOINT

IS AT RISER SUPPORT POINT

FLOOR

2 INCHES WG TO 4 INCHES WG DUCT RISER SUPPORT

HOLE IN STRUCTURAL FLOOR

DUCT RISER

DUCT RISER SUPPORTS

N.T.S.

BRANCH DUCT INSULATED FLEXIBLE AIR DUCT

CONNECTOR LENGTH NOT TO

EXCEED 3'

VOLUME

DAMPER

ROUND OR OVAL

INLET COLLAR

MINIMUM 2"

EXTENSION

INACTIVE LENGTHS

TYP.

PLENUM WITH

INTERNALLY LINED

INSULATION

NOTES:

1.COORDINATE SLOT DIFFUSER FRAME/BORDER

TYPE AND END BORDER CONFIGURATION WITH

CEILING TYPE.

INSULATED PLENUM

INLET COLLAR

LINEAR

DIFFUSER

CEILING

ACTIVE LENGTH

SUPPLY DUCT

LINEAR SLOT DIFFUSER

N.T.S.

DUCT

SEAL OPENING WITH FIRE

STOPPING SEAL FOR RATED

WALL SEE NOTE 2).

DUCT INSULATION

NOTES:

1. DUCT PENETRATION THROUGH NON-RATED OR 1 HR FIRE RATED WALL.

2. IF WALL IS FIRE RATED, SEALANT AND INSULATION SHALL CONFORM

TO THE ASSOCIATED FIRE RATING.

DUCT PENETRATION THROUGH INTERIOR WALL

N.T.S.

444 W. Lake St. Suite 1700 Chicago, IL 60606

312.583.7023 www.virtualenergysolutions.com

Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432

Drawing No.

Scale:

Date:

Checked By:Drawn By:Designed By:

Drawing Title:

Contract No.

File No.Building No.

Client Project No.

Project Title:Approved: Chief, failites Management Services

Approved: Medical Center Director

Approved:

Approved: Location:

VES Project Number: 191006

AS NOTED

VA JOLIET CBOC

JOLIET, ILLINOIS

578-371 36C25219D0020

© 2020 Virtual Energy Solutions, INC.

B

IM

/2

-M

A T

O C

-P a rk in g E x p a n s io n a t J o lie t C

B O

C

-3

/2

-J o lie t C

B O

C P a rk in g

E x p a n s io n M

E C

H

.r v t

/6 /2

:4

:0

P M

M501

MECHANICAL DETAILS

PARKING EXPANSION AT

JOLIET CBOC

10/11/2023

EPTHEP

Revisions Date

ISSUED FOR 60% DD 12/30/2022

ISSUED FOR 90% CD 02/10/2023

ISSUED FOR 100% CD 03/07/2023

S E E

N O T E

SEE NOTE

SEE NOTE

SEE NOTE

NOTE:

1.

2.

3.

4.

5.

RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A

MINIMUM OF 3 TIMES THE DIAMETER OF INLET

A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO

THIS BOX, BUT ALLOWED TO ACCOMMODATE MINOR OFFSETS. MAXIMUM

LENGTH 3'-0".

A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE

AS THE BOX INLET, PROVIDED THE EQUIVALENT LENGTH OF THE

BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET.

FOR LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A

DUCT TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE DROP AT

OR BELOW 0.2"/100'.

FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT

SUPPLY AIR DUCT TO DIFFUSER, SHALL NOT EXCEED 5'-0".

USE RIGID ELBOWS FOR CHANGE OF DIRECTION GREATER

THAN 45°.

COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE

INSULATION W/VAPOR BARRIER FOR CONNECTING DUCT SECTIONS.

AIR TERMINAL UNIT

(CV OR VAV)

REHEAT COIL

SOUND ATTENUATOR (IF SPECIFIED)

SEE EQUIPMENT SCHEDULE

FLEXIBLE AIR DUCT

CONNECTOR. SEE DETAIL

DIFFUSER (TYP.)

SEE SPECIFICATIONS FOR

CLAMPS AND SEALANT (TYP.)

SEE NOTE 5

DUCT CONNECTIONS - AIR TERMINAL UNITS

N.T.S.

DRAW BAND ON OUTER LINER. SEE NOTE 2

DRAW BAND ON INNER LINER. SEE NOTE 1

FLEXIBLE DUCT

(5' MAX LENGTH)

FSK TAPE BETWEEN

FLEX DUCT AND

RIGID DUCT INSULATION

DUCT INSULATION

ROUND DUCT

NOTES:

1. MINIMUM 4" OVERLAP.

SECURE WITH STAINLESS

STEEL DRAW BAND.

2. METAL OR PLASTIC DRAW

BAND.

FLEX. DUCT CONNECTION TO INSULATED ROUND DUCT

N.T.S.

FROM STRUCTURE

SAME AS DIFFUSER

INLET: 5'-0" MAX

FLEXIBLE DUCT SIZE

LENGTH.

12"

CEILING

SUPPORT SADDLE

VOLUME DAMPER W/

LOCKING QUADSADDLE

SHEET METAL

CONICAL OUTLET

BRANCH DUCT

FOR CHANGE OF

DIRECTION GREATER

USE RIGID ELBOWS

THAN 45°

SEE SPECIFICATIONS FOR CLAMPS

AND SEALANT (TYP.)

NOTE:

THE USE OF FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED

FOR THE DEDICATED AHU SERVING THE SURGICAL SUITE.

TYPICAL

DIFFUSER OR

REGISTER IN

LAY-IN CLG.

THERMAL INSULATION

SEE SPECIFICATIONS

FLEXIBLE AIR DUCT CONNECTOR

N.T.S.

NOTE:

1.

2.

3.

4.

5.

6.

A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, 1S SIMILAR.

FOLLOW DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND

GAGES FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN

THE PARTITION OR FLOOR AND NOT OUTSIDE THE PENETRATION.

GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO

DAMPER FRAME AND TO PERIMETER ANGLES.

PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1 1/2"x1 1/2", 14 GAGE, TO PROVIDE 1" MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.

BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.

ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR

LINKS.

PROVIDE 1/4" TO 1/2" CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN

SPACE WITH ROCK WOOL FIRESTOP FIBER.

ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS

AND MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" HIGH

CONCRETE CURB AROUND OPENING FOR DUCT.

SLEEVE, NOTE 2

DUCT

CONNECTION

NOTE 4

DAMPER,

NOTE 1

DAMPER COLLAR

EXTENSION INTEGRAL

PART OF SLEEVE

SLEEVE, NOTE 2

NOTE 6FIRE BARRIER

PARTITION OR CHASE

TYPICAL DUCT

INSULATION

PERIMETER ANGLE, NOTE 3

(NOTE FASTENED TO PARTITION)

ACCESS

PANEL

NOTE 5

SECTION THRU FIRE DAMPER INSTALLATION

N.T.S.

444 W. Lake St. Suite 1700 Chicago, IL 60606

312.583.7023 www.virtualenergysolutions.com

Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432

Drawing No.

Scale:

Date:

Checked By:Drawn By:Designed By:

Drawing Title:

Contract No.

File No.Building No.

Client Project No.

Project Title:Approved: Chief, failites Management Services

Approved: Medical Center Director

Approved:

Approved: Location:

VES Project Number: 191006

AS NOTED

VA JOLIET CBOC

JOLIET, ILLINOIS

578-371 36C25219D0020

© 2020 Virtual Energy Solutions, INC.

B

IM

/2

-M

A T

O C

-P a rk in g E x p a n s io n a t J o lie t C

B O

C

-3

/2

-J o lie t C

B O

C P a rk in g

E x p a n s io n M

E C

H

.r v t

/6 /2

:4

:1

P M

M502

MECHANICAL DETAILS

PARKING EXPANSION AT

JOLIET CBOC

10/11/2023

EPTHEP

Revisions Date

ISSUED FOR 60% DD 12/30/2022

ISSUED FOR 90% CD 02/10/2023

ISSUED FOR 100% CD 03/07/2023

444 W. Lake St. Suite 1700 Chicago, IL 60606

312.583.7023 www.virtualenergysolutions.com

Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432

Drawing No.

Scale:

Date:

Checked By:Drawn By:Designed By:

Drawing Title:

Contract No.

File No.Building No.

Client Project No.

Project Title:Approved: Chief, failites Management Services

Approved: Medical Center Director

Approved:

Approved: Location:

VES Project Number: 191006

AS NOTED

VA JOLIET CBOC

JOLIET, ILLINOIS

578-371 36C25219D0020

© 2020 Virtual Energy Solutions, INC.

B

IM

/2

-M

A T

O C

-P a rk in g E x p a n s io n a t J o lie t C

B O

C

-3

/2

-J o lie t C

B O

C P a rk in g

E x p a n s io n M

E C

H

.r v t

/6 /2

:4

:1

P M

M601

MECHANICAL SCHEDULES

PARKING EXPANSION AT

JOLIET CBOC

10/11/2023

EPTHEP

UNIT HEATER SCHEDULE (ELEC)

TAG LOCATION HTG. ELEMENT DATA FAN MOTOR DATA UNIT ELECTRICAL DATA DIMENSIONS (IN) UNIT

WEIGHT

(LBS)

BASIS OF DESIGN

REMARKS

TYPE MARK

ROOM

NUMBER

ROOM NAME

CAPACITY

(KW)

L.A.T.

(DEG. F)

FAN AIRFLOW

(CFM)

QTY FLA V PH HZ L W H MANUFACTURER MODEL

UH 003A 003A Mach. Room 3 105 350 1 15 480 3 60 21 5 19 24 MARLEY MUH0381 REMOTE THERMOSTAT

CABINET UNIT HEATER SCHEDULE (ELEC)

TAG LOCATION HTG. ELEMENT DATA FAN MOTOR DATA UNIT ELECTRICAL DATA

DIMENSIONS

LxWxH

BASIS OF DESIGN

REMARKS

TYPE MARK

ROOM

NUMBER

ROOM NAME KW L.A.T. (DEG. F) CFM QTY FLA V PH HZ L W H MANUFACTURER MODEL

EUH 001 001 New North Vestibule 20 123 1000 2 26 480 3 60 85 25 10 MARLEY CU978 PROVIDE WITH REMOTE THERMOSTAT

EUH 104 104 Vestibule 6 98 500 1 8 480 3 60 45 10 26 MARLEY CU945

DIFFUSER/ REGISTER/ GRILLE SCHEDULE

TAG SYSTEM DESCRIPTION

FACE SIZE

(IN.) NECK SIZES CFM RANGE

MOUNITNG TYPE DAMPER

MATERIAL /

FINISH MAX. N.C. REMARKSW L

NECK

DIAMETER

NECK

WIDTH

NECK

LENGTH MIN. MAX

R-1 Return Air SQUARE PERFORATED 24 24 6 0 135 LAY-IN No WHITE STEEL 30

R-1 Return Air SQUARE PERFORATED 24 24 8 136 245 LAY-IN No WHITE STEEL 30

R-1 Return Air SQUARE PERFORATED 24 24 10 246 380 LAY-IN No WHITE STEEL 30

S-1 Supply Air SQUARE PLAQUE 24 24 6 0 100 LAY-IN No WHITE STEEL 30

S-1 Supply Air SQUARE PLAQUE 24 24 8 101 250 LAY-IN No WHITE STEEL 30

S-3 Supply Air LOUVERED 10 10 8 8 0 300 SURFACE MOUNT No WHITE STEEL 30

VAV SCHEDULE

TAG COOLING CFM

INLET SIZE

MIN. INLET S.P.

INCH W.C.

SOUND

ATTENUATOR

(Y/N)

MAX N.C. BASIS OF DESIGN

REMARKSTYPE MARK MAX MIN DISCHARGE RADIATED MANUFACTURER MODEL

VAV 002 560 187 8 0.50 No 30 30 NAILOR D3001

VAV B003A 250 83 6 0.50 No 30 30 NAILOR D3001

VAV SCHEDULE (ELEC REHEAT)

TAG COOLING CFM HEATING CFM

INLET SIZE

MIN. INLET S.P.

INCH W.C.

HEATING COIL DATA SOUND

ATTENUATOR

(Y/N) REMARKSTYPE MARK MAX MIN MAX MIN TOTAL MBH KW V PH HZ EAT DWG. F LAT DEG. F

VAV 103 490 50 490 50 6 0.50 20478.0 6 480 3 60 55 95 No

VAV: 1

Revisions Date

ISSUED FOR 60% DD 12/30/2022

ISSUED FOR 90% CD 02/10/2023

ISSUED FOR 100% CD 03/07/2023

ABBREVIATIONS

ABOVE COUNTER

ABOVE FINISHED FLOOR

AUTOMATIC TRANSFER SWITCH

BOLTED PRESSURE SWITCH

BLOWN FUSE PROTECTION

CIRCUIT BREAKER

CIRCUIT

CONDUIT ONLY

DISCONNECT

DOWN

DOUBLE POLE DOUBLE THROW

EXISTING TO REMAIN

EMERGENCY

EMERGENCY POWER OFF

ELECTRIC WATER COOLER

FIRE ALARM

FAN COIL UNIT

FAN POWERED BOX

FORCED FLOW CONVECTOR

GROUND FAULT INTERRUPTER

GROUND

HIGH INTENSITY DISCHARGE

HAND OFF AUTOMATIC

HORSEPOWER

JUNCTION BOX

ISOLATED GROUND

KILOVOLT

KILOWATT

LIGHTING

MAIN CIRCUIT BREAKER

MAIN LUGS ONLY

MEDIUM VOLTAGE

NORMALLY CLOSED (CONTACTS)

NOT IN CONTRACT

NORMALLY OPEN (CONTACTS)

NOT TO SCALE

PANEL

PRIMARY

POTENTIAL TRANSFORMER

REFLECTED CEILING PLAN

SECONDARY

SINGLE POLE DOUBLE THROW

SWITCH

TELEPHONE

TAMPER PROOF

UNIT HEATER

VAPOR PROOF

WEATHERPROOF

WATERTIGHT

EXPLOSION PROOF

AC

AFF

ATS

BPS

BFP

CB

CCT

CO

DISC

DN

DPDT

EX

EM

EPO

EWC

FA

FCU

FPB

FFC

GFI

GRD

HID

HDA

HP

JB

IG

KV

KW

LTG

MCB

MLO

MV

NC

NIC

NO

NTS

PNL

PRI

PT

RCP

SEC

SPDT

SW

T

TP

UH

VP

WP

WT

XP

EXISTING RELOCATEDEXR

CONDUIT

CONDUIT RUN CONCEALED IN CEILING OR WALL.

ARROWHEAD DENOTES HOMERUN TO

PANELBOARD

SLASH LINES INDICATE QUANTITY OF WIRE.

GROUND WIRE INDICATED AS LONG LINE WITH

DOT, NEUTRAL INDICATED AS LONG LINE AND

PHASE CONDUCTORS INDICATED AS SHORT LINES.

CONDUIT RUN CONCEALED IN SLAB OR BELOW

SLAB. DITTO FOR ARROW AND NUMBER OF WIRES

INDICATED

CONDUIT RUN EXPOSED. DITTO FOR ARROW AND

NUMBER OF WIRES INDICATED

CONDUIT RUN STUBBED UP

CONDUIT RUN STUBBED DOWN

FLEXIBLE CONDUIT CONNECTION

CONDUIT TERMINATION, STUB OUT.

STAIRS

EXIT

FIRE ESCAPE

EXIT

FIRE ESCAPE

STAIRS

STAIRS

EXIT

FIRE ESCAPE

EXIT

BATTERY PACK FIXTURES WITH

NUMBER OF HEADS SHOWN

24 EXIT

STAIRS

FIRE ESCAPE

EXIT

STAIRS

FIRE ESCAPE

EXIT

FIRE ESCAPE

STAIRS

ELEVATOR

SYMBOL

CHICAGO

CODE No.

STAIRS

DESCRIPTION

FIRE ESCAPE

SINGLE FACE

SYMBOL

CHICAGO

CODE No.

DESCRIPTION

TRIANGLE

FLUSH OR

RECESSED

DOUBLE FACE

EXIT SIGN SCHEDULE

MAGNETIC MOTOR STARTER

COMBINATION MOTOR STARTER

EQUIPMENT IDENTIFICATION

DISCONNECT SWITCH, RATING AS INDICATED

FUSIBLE DISCONNECT, RATING AS INDICATED

SINGLE POLE MANUAL STARTER WITH THERMAL

OVERLOAD PROTECTION FOR FRACTIONAL SINGLE

PHASE MOTORS. 'P' INDICATES PILOT LIGHT AND

'2T' INDICATES DOUBLE POLE

P

2T

MOTORS AND CONTROLS

MOTOR, REFER TO SCHEDULE FOR HORSEPOWER,

DESCRIPTION, WIRING AND PANEL FED FROM1

M

MOTOR, NUMBER INDICATES HORSEPOWER5

CABLE TERMINATION

POT HEAD

SINGLE THROW SWITCH

MOLDED CASE CIRCUIT BREAKER (NUMBER

INDICATES POLES)2

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

TRANSFORMER

ONE-LINE ELECTRICAL DIAGRAM SYMBOL

GROUND

INCOMING LINE

UM UTILITY METER

JUNCTION BOX

RACEWAYS AND WIREWAYS

JUNCTION BOX - WALL MOUNTED

JUNCTION BOX WITH FLEXIBLE CONNECTIONJ

J

J

JUNCTION BOX FOR FURNITURE POWER IN-FEEDSP

JUNCTION BOX FOR TELE/DATA IN-FEEDSC

SINGLE GANG JUNCTION BOX WITH 1"C TO

TECHNOLOGY CLOSET.

PROVIDE DUAL CHANNEL LEGRAND 25DTP SERIES

POWER POLE FOR POWER AND LOW VOLTAGE

CABLING. SUPPORT RACEWAY AT BOTH ENDS.

NOTES:

"F1" DENOTES FIXTURE TYPE, REFER TO LIGHTING FIXTURE

SCHEDULE FOR DESCRIPTION AND MOUNTING. THE CIRCUIT

NUMBER "EM1" DENOTES LIGHT FIXTURE WIRED TO LIFE SAFETY

SYSTEM.

LIFE SAFETY LUMINARIES

F1

EM1

LIGHTING FIXTURE WIRED TO LIFE

SAFETY SYSTEM

FLUORESCENT STRIP LIGHT

WIRED TO LIFE SAFETY SYSTEM

2x4 FLUORESCENT LIGHTING

FIXTURE WIRED TO LIFE SAFETY

SYSTEM

1x4 FLUORESCENT LIGHTING

FIXTURE WIRED TO LIFE SAFETY

SYSTEM

DUPLEX RECEPTACLE - POKE-THROUGH FITTING

INCLUDING DRILLING ALL OTHER COMPONENTS.

WIREMOLD 880CS3-1, 3-GANG W/ (2) DUPLEX

RECEPTACLES AND 1 GANG FOR LOW VOLTAGE

CABLING.

A

WIREMOLD RFB4 4-GANG W/ (2) DUPLEX

RECEPTACLES AND (2) GANGS FOR LOW VOLTAGE

CABLING.

B

FL

CTR

CONTROL PANEL CIRCUIT. PROVIDE DEDICATED

CIRCUIT CONNECT TO MECHANICAL OR PLUMBING

CONTROL PANEL. VERIFY LOCATION IN FIELD.

HL

S

INTERCOM SPEAKER. DISCONNECT AND STORE

FOR RE-INSTALL AT THE END OF CONSTRUCTION.

EXTEND CABLING AND CONDUIT AS REQUIRED.

50% SWITCHED RECEPTACLE

DUPLEX

DUPLEX

DOUBLE

ABOVE COUNTER RECEPTACLE

USB RECEPTACLE

TAMPER PROOF RECEPTACLE

GFI RECEPTACLE

CRITICAL RECEPTACLE

SPECIAL RECEPTACLE - REFER TO PLANS FOR

NEMA TYPE

FIXED EQUIPMENT CONNECTION

STANDARD RECEPTACLE

CEILING MOUNTED RECEPTACLES (W / CIRCLE)

FLOOR MOUNTED RECEPTACLES (W / SQUARE)

WALL MOUNTED RECEPTACLES (W / STEM)

INSTALL LEVEL WITH FINISHED CEILING.

ABOVE COUNTER GFI RECEPTACLE

JUNCTION BOXES FOR ELECTRIC LAVATORIES

SENSORS. CONTRACTOR TO PROVIDE CIRCUIT

SHOWN AND ALL ASSOCIATED CONDUIT AND

WIRING FOR A COMPLETE OPERATING SYSTEM.

TYPICAL FOR EVERY LAVATORY, URINAL AND

TOILET FLUSH LOCATION. MULTIPLE LAVATORIES

AT TOILETS REQUIRED A SINGLE CONNECTION.

PROVIDE TRANSFORMERS ABOVE CEILING W/

ACCESS PANELS AND PROVIDE GFI CKT BREAKER

AT CORRESPONDING BREAKER.

JUNCTION BOXES FOR FLUSH SENSORS.

CONTRACTOR TO PROVIDE CIRCUIT SHOWN AND

ALL ASSOCIATED CONDUIT AND WIRING FOR A

COMPLETE AND OPERATING SYSTEM.

TYPICAL FOR EVERY LAVATORY, URINAL AND

TOILET FLUSH LOCATION. MULTIPLE LAVATORIES

AT TOILETS REQUIRED A SINGLE CONNECTION.

PROVIDE TRANSFORMERS ABOVE CEILING W/

ACCESS PANELS AND PROVIDE GFI CKT BREAKER

AT CORRESPONDING BREAKER.

MOUNTING HEIGHT 1'-6"

SUPPORT TO STRUCTURE.

ELECTRICAL HAND DRYER. PROVIDE DEDICATEDH

CIRCUIT.

WEATHERPROOF, GFI RECEPTACLE

RECEPTACLES

TAMPER SWITCH

WATER FLOW DETECTOR

DUCT SMOKE DETECTOR

AUDIBLE ALARM DEVICE

SMOKE DETECTOR

PULL STATION

RELAY MODULE

HEAT DETECTOR

FIRE ALARM CONTROL PANEL

FIRE ALARM ANNUNCIATOR PANEL

ANSUL PANEL

REMOTE TEST SWITCH AND ANNUNCIATOR

REMOTE ANNUNCIATOR

VISUAL ALARM DEVICE

FIREMAN'S 2-WAY COMM PHONE

SPEAKER / VISUAL ALARM DEVICE

SPEAKER

DOOR HOLD OPEN

KNOCKBOX

ANSUL

FAAP

FACP

HD

FIRE ALARM SYMBOLS

CEILING MOUNTED DEVICES (W / CIRCLE)

WALL MOUNTED DEVICES (W / STEM)

H

SD

DD

SD

SD

MM

RTS

TS

WF

S

A

T

RA

SV

S

V

K

171'-250' IN LENGTH: 6#8,1#8G,1"C

101'-170' IN LENGTH: 6#10,1#10G,3/4"C

0'-100' IN LENGTH: 6#12,1#12G,3/4"C

C) THREE (3) BRANCH CIRCUITS PER HOMERUN-

171'-250' IN LENGTH: 4#8,1#8G,3/4"C

101'-170' IN LENGTH: 4#10,1#10G,3/4"C

0'-100' IN LENGTH: 4#12,1#12G,3/4"C

B) TWO (2) BRANCH CIRCUITS PER HOMERUN-

CONNECTED TO 208Y/120 VOLT SYSTEMS SHALL BE, U.N.O.:

BRANCH CIRCUIT WIRING FOR 20 AMP, 120 VOLT CIRCUITS

BRANCH CIRCUITS SHALL BE CONNECTED TO 20A,1P CB'S, U.N.O.1.

2.

171'-250' IN LENGTH: 2#8,1#8G,3/4"C

101'-170' IN LENGTH: 2#10,1#10G,3/4"C

0'-100' IN LENGTH: 2#12,1#12G,3/4"C

A) ONE (1) BRANCH CIRCUIT PER HOMERUN-

PROVIDE A DEDICATED NEUTRAL WITH EACH BRANCH CIRCUIT.4.

PROVIDE AN INSULATED GROUND WIRE WITH EACH CIRCUIT.5.

351'-550' IN LENGTH: 6#8,1#8G,1"C

201'-350' IN LENGTH: 6#10,1#10G,3/4"C

0'-200' IN LENGTH: 6#12,1#12G,3/4"C

C) THREE (3) BRANCH CIRCUITS PER HOMERUN-

351'-550' IN LENGTH: 4#8,1#8G,3/4"C

201'-350' IN LENGTH: 4#10,1#10G,3/4"C

0'-200' IN LENGTH: 4#12,1#12G,3/4"C

B) TWO (2) BRANCH CIRCUITS PER HOMERUN-

CONNECTED TO 480Y/277 VOLT SYSTEMS SHALL BE, U.N.O.:

BRANCH CIRCUIT WIRING FOR 20 AMP, 277 VOLT CIRCUITS3.

351'-550' IN LENGTH: 2#8,1#8G,3/4"C

201'-350' IN LENGTH: 2#10,1#10G,3/4"C

0'-200' IN LENGTH: 2#12,1#12G,3/4"C

A) ONE (1) BRANCH CIRCUIT PER HOMERUN-

GENERAL BRANCH CIRCUIT NOTES

1. REFER TO MECHANICAL DRAWINGS FOR LOCATIONS OF

HVAC, PLUMBING AND FIRE PROTECTION EQUIPMENT.

2. CAREFULLY REVIEW THE ARCHITECTURAL, STRUCTURAL,

MECHANICAL, HVAC AND PLUMBING PLANS AND

SPECIFICATIONS FOR FURTHER WORK SCOPE AND FOR

ADDITIONAL INFORMATION.

3. PROVIDE RACEWAY AND 120V POWER FOR SECURITY

SYSTEM DEVICES. COORDINATE WORK WITH SECURITY

CONTRACTOR, PRIOR TO INSTALLATION.

4. PROVIDE RACEWAY, 120V POWER AND GROUNDING FOR

COMMUNICATIONS SYSTEMS INCLUDING TELEPHONE,

DATA, CABLE TELEVISION, INTERCOM, AUDIOVISUAL, ETC.

COORDINATE WORK WITH TELECOMMUNICATIONS

CONTRACTOR, PRIOR TO INSTALLATION.

5. THE CONTRACTOR SHALL PROVIDE OVERSIZED PULL

BOXES UTILIZED FOR TELECOMMUNICATIONS, SECURITY

AND A/V WIRING AT CEILING MOUNTED ACCESS PANEL

LOCATIONS. ACCESS PANEL LOCATIONS SHALL BE

COORDINATED WITH ARCHITECT AND GENERAL

CONTRACTOR, PRIOR TO INSTALLATION.

6. FEEDER AND BRANCH CIRCUIT WIRING SHALL BE SIZED

FOR A MAXIMUM 5% VOLTAGE DROP TOTAL. UPSIZE

FEEDER AND BRANCH CIRCUIT WIRING AS REQUIRED FOR

RUN LENGTH IN THE FIELD.

7. THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN A

COMPLETE AND SEPARATE RACEWAY SYSTEM AND THE

RACEWAY SHALL BE RED IN COLOR.

8. THESE DRAWINGS ARE DIAGRAMMATICAL IN NATURE,

AND INDICATE THE GENERAL ARRANGEMENT OF

EQUIPMENT, BUT ACCURACY IS NOT GUARANTEED. FIELD

VERIFICATION OF LOCATIONS AND DIMENSIONS MAY BE

REQUIRED.

9. THESE DRAWINGS WILL NOT SHOW ALL INSTALLATION

DETAILS. IT SHALL BE THE RESPONSIBILITY OF THE

CONTRACTOR TO MAKE A COMPLETE AND SATISFACTORY

INSTALLATION IN ACCORDANCE WITH NECA 1 AND

MODERN PRACTICE METHODS.

10. EQUIPMENT DIMENSIONS SHOWN ON PLANS AND

ELEVATIONS ARE APPROXIMATE ONLY. THE CONTRACTOR

SHALL USE THE SHOP DRAWINGS FOR PROPER LAYOUT,

FOR FINAL INSTALLATION, WITHOUT ANY ADDITIONAL

COST TO THE OWNER.

11. ELECTRICAL CONTRACTOR SHALL MAKE THEIR OWN

COUNT OF ALL EQUIPMENT TO BE WIRED BASED ON

PLANS AND SPECIFICATIONS.

12. PROVIDE ARC FLASH WARNING LABELS ON ALL NEW

PANELBOARDS AS DESCRIBED IN 2014 NEC 110.16.

13. ALL NEW CIRCUITS SHALL BE RUN WITH DEDICATED

NEUTRALS PER 2014 NEC 200.4. SHARED NEUTRALS ARE

NOT ALLOWED.

14. PROVIDE AN INSULATED GROUND WIRE WITH ALL

CIRCUITS.

15. LABEL EACH RECEPTACLE WITH THE PANEL NAME AND

CIRCUIT NUMBER SERVING THEM.

16. ALL NEW RECEPTACLES CONNECTED TO CRITICAL

POWER SHALL HAVE RED BODIES AND COVER PLATES.

17. ALL NEW SWITCHES CONNECTED TO CRITICAL POWER

SHALL HAVE RED HANDLES.

18. ALL RECEPTACLES IN PATIENT CARE AREAS SHALL BE

BOTH TAMPER RESISTANT AND HOSPITAL GRADE TYPES.

19. THE ELECTRICAL CONTRACTOR SHALL SUBMIT AND

RECEIVE REVIEWED SHORT CIRCUIT AND SELECTIVE

COORDINATION STUDIES, PRIOR TO SUBMITTING

SWITCHBOARD, PANELBOARD AND OVERCURRENT

DEVICES FOR REVIEW.

20. LIGHTING SHALL BE 277 VOLTS, EXCEPT WITHIN PATIENT

ROOMS, PATIENT BATHROOMS, SECLUSION ROOMS, ANTE

ROOMS, AND THE ELEVATOR PIT WHERE THE LIGHTING

SEE SPECIFICATIONS.

21. RECEPTACLES AND LIGHT SWITCHES IN PATIENT CARE

AREAS SHALL UTILIZE TAMPER RESISTANT SCREWS.

SHALL BE 120 VOLTS.

GENERAL NOTES

S

S

J

XX

LO

2W

FA

TEL

FA

1W

ELEVATOR CAB CONNECTIONS

J J J J

FA = FIRE ALARM CONNECTION

TEL = TELEPHONE CONNECTION

LO = LOCKOUT SWITCH FOR CAB LIGHTING

XX

ELEV

ELEVATOR CAB CONNECTIONS

S

SECURITY CAMERA

WIRELESS ACCESS POINT

CARD READER.

INTERCOM. PROVIDE MANUFACTURER BACKBOX

COORDINATE INSTALLATION WITH COMMUNICATION

DEVICE INSTALLER. ALL CABLING IN RACEWAY.

SPEAKER.

TELEPHONE/DATA OUTLET 18"AFF, UNLESS NOTED

OTHERWISE.

ELECTRIC STRIKE

DOOR CONTACT

REQUEST FOR EXIT

MAGNETIC LOCK

DOOR RELEASE. PROVIDE 1/2" CONDUIT TO DOOR

RELEASE BUTTON (DRB).

DOOR RELEASE BUTTON MOUNTED ABOVE COUNTER

FOR A SINGLE DOOR RELEASE.

PROVIDE 1/2" CONDUIT TO DOOR RELEASE.

KEY PAD

WALL MOUNTED TELEPHONE OUTLET 48"AFF,

UNLESS NOTED OTHERWISE.

TELEVISION OUTLET

DOOR RELEASE BUTTON MOUNTED ON WALL.

FOR MAGNETIC DOOR RELEASE. CONNECT TO

DOOR ACCESS SYSTEM.

NURSE CALL DOME LIGHTS

INTERCOM ACCESS WITH VIDEO BY AIPHONE

IX-SERIES www.aiphone.com/products/ix-series

INTERCOM ACCESS WITH VIDEO HEADEND EQUIPMENT

AND ACCESS CONTROL STATION

www.aiphone.com/products/ix-series

KEY OPERATED SWITCH

SWITCH WITH PILOT LIGHT

DIMMER SWITCH WATTAGE AS NECESSARY

P

K

SWITCHES

THREE WAY SWITCH

SINGLE POLE SWITCH. THE NUMBER DENOTES

CIRCUIT NUMBER AND THE LETTER "a"

SWITCH CONTROL

3W

1a

3-WAY DIMMER SWITCH WATTAGE AS NECESSARY

VOLUME CONTROL

"LCC"

"MC"

"LV(2)"

"LM"

LCC

3 a

K

SWITCH LEG TO LTG CONTACTOR COIL "LCC"

LOW VOLTAGE SWITCHING SYSTEM #

QUANTITY OF LV SWITCHES

MASTER SWITCH FOR LOW VOLTAGE

SWITCHING SYSTEM

5 3W,b

MOMENTARY CONTACT SWITCH

"a-z"

"D"

"2P"

"3P"

"3W"

"4W"

"K"

"OS"

"P"

"RS"

SWITCH LEG CONTROL LETTER CODE(S)

DIMMER 1,000W CONTROL SWITCH

DOUBLE-POLE TOGGLE SWITCH

TRIPLE POLE TOGGLE SWITCH

THREE WAY SWITCH

FOUR WAY SWITCH

KEY OPERATED SWITCH

OCCUPANCY SENSOR SWITCH

TOGGLE SWITCH WITH PILOT LIGHT

ROTARY SWITCH WITH TIMER CONTROL

"T"

"WS"

"T/S"

"W-STAT"

THERMAL SWITCH

WALL SWITCH

TEMP/SENSOR SWITCH

WALL LINE VOLTAGE STAT

DS

OC

CEILING MOUNTED PASSIVE INFRARED 360°

DAYLIGHT HARVESTING LIGHT SENSOR

CEILING MOUNTED DUAL

TECHNOLOGY 360° OCCUPANCY

SENSOR

OC WALL MOUNTED DUAL TECHNOLOGY

360° VACANCY/OCCUPANCY SENSOR

D

D3

LOW VOLTAGE CONTACTOR CONTROL SWITCH

TO BE CONNECTED TO THE DELTA CONTROL

PANEL.

LV

PH PHOTOCELL CONTROL

LUMINARIES

F1

2x4 FLUORESCENT/LED LIGHTING

FIXTURE.

1x4 FLUORESCENT/LED LIGHTING

FIXTURE.

FLOURESCENT/LED DOWNLIGHT

OR HIGH BAY.

PARKING LOT FIXTURE

TECHNOLOGY SYMBOLS

CR

I

ES

DC

REX

ML

DR

DRB

KP

W

TV

CEILING MOUNTED DEVICES (W / CIRCLE)

WALL MOUNTED DEVICES (W / STEM)XX

XX

DOOR FRAME MOUNTED DEVICESXX

PROVIDE 4” x 4” x 2-1/2” BACKBOX WITH MUDRING AND 1” CONDUIT TO

ACCESSIBLE CEILING SPACE ABOVE. WHERE AUTHORITY HAVING JURISDICTION

MANDATES PROVIDE CONDUIT CONTINUATION THROUGH PLENUM SPACES.

AI

HE

444 W. Lake St. Suite 1700 Chicago, IL 60606

312.583.7023 www.virtualenergysolutions.com

Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432

Drawing No.

Scale:

Date:

Checked By:Drawn By:Designed By:

Drawing Title:

Contract No.

File No.Building No.

Client Project No.

Project Title:Approved: Chief, failites Management Services

Approved: Medical Center Director

Approved:

Approved: Location:

VES Project Number: 191006

AS NOTED

VA JOLIET CBOC

JOLIET, ILLINOIS

578-371 36C25219D0020

© 2020 Virtual Energy Solutions, INC.

B

IM

/2

-M

A T

O C

-P a rk in g E x p a n s io n a t J o lie t C

B O

C

-3

/2

-M A

T O

C -J o lie t C

B O

C P a rk in g E x p a n s io n E

L E

C

.r v t

/1 /2

:0

:2

P

M

E001

ELECTRICAL SYMBOLS AND

ABBREVIATIONS

PARKING EXPANSION AT

JOLIET CBOC

10/11/2023

AGSAVSDV

Revisions Date

ISSUED FOR 60% DD 12/30/2022

ISSUED FOR 90% CD 02/10/2023

ISSUED FOR 100% CD 03/07/2023

ISSUED FOR BID 03/24/2023

ISSUED FOR BID ADDENDUM 1 04/21/2023

0.2

0.6

EXISTING JOLIET

CBOC

SECURITY

FENCE

FP

T

T

T

E

E

EE

WALL

1 10

1 2 3 4 5

6 7 8 9

P1 P1

P1

P1

P3 P4

P2 P2

P2 P2

P2

P2

P2

P2

P2

P2

P2

P2 P2

P2

P2

P2

P1

P1

P1

P1

P1

P5

P1

P1

P1

P1

P1

P5

P7

P7

P8 P8

P4 P4

P1

P1

P2 P2 P2

P1

P1

444 W. Lake St. Suite 1700 Chicago, IL 60606

312.583.7023 www.virtualenergysolutions.com

Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432

Drawing No.

Scale:

Date:

Checked By:Drawn By:Designed By:

Drawing Title:

Contract No.

File No.Building No.

Client Project No.

Project Title:Approved: Chief, failites Management Services

Approved: Medical Center Director

Approved:

Approved: Location:

VES Project Number: 191006

AS NOTED

VA JOLIET CBOC

JOLIET, ILLINOIS

578-371 36C25219D0020

© 2020 Virtual Energy Solutions, INC.

B

IM

/2

-M

A T

O C

-P a rk in g E x p a n s io n a t J o lie t C

B O

C

-3

/2

-M A

T O

C -J o lie t C

B O

C P a rk in g E x p a n s io n E

L E

C

.r v t

/1 /2

:5

:1

P

M

ESD101

ELECTRICAL DEMOLITION SITE

PLAN

PARKING EXPANSION AT

JOLIET CBOC

10/11/2023

AGSAVSDV

1/32" = 1'-0"

1 DEMO SITE LIGHTING

KEYNOTES:

1. DEMOLISH COMPLETE BACK TO SOURCE ALL EXTERIOR PANELS,

POLES, LIGHT FIXTURES, POLE BASES, CONDUITS, CABLING, POWER

CIRCUITS, AND ANCILLARY EQUIPMENT BACK TO SOURCE. EXISTING

EQUIPMENT NOT SHOWN ON PLANS SHALL REMAIN. PROVIDE WIRING

CONTINUITY FOR ALL DEVICES TO REMAIN. VERIFY QUANTITIES IN

FIELD PRIOR TO SUBMITTING BID. COORDINATE DEMOLITION OF ALL

EQUIPMENT WITH ARCHITECT, ENGINEER AND OWNER PRIOR TO

START OF DEMOTION THROUGH SHOP DRAWING SUBMITTAL. PROVIDE

FOR WIRING CONTINUITY FOR ALL EXISTING DEVICES TO REMAIN.

Revisions Date

ISSUED FOR 100% CD 03/07/2023

ISSUED FOR BID 03/24/2023

0.2

0.6

FP

(V A C A T E D

ASPHALT

PARKING

AREA

ASPHALT

PARKING

AREA

ASPHALT

ROAD

11218

1 10

1 2 3 4 5

6 7 8 9

11.005.00 11.0011.00

11.00

SL5

SL5

SL5

SL5

SL5

SL5

B5

B5

B5

B5

B5

RP-QD1

27,29

S3

CALL BOX

RP-QD1

S3

CALL BOX

RP-QD1

S3

CALL BOX

RP-

QD1-24

W4

RP-QD1

31,33

RP-QD1

21,23

RP-QD1

21,23RP-QD1

21,23

RP-QD1

21,23

RP-QD1

21,23

RP-QD1

27,29

RP-QD1

27,29

RP-QD1

27,29

RP-QD1

27,29

RP-QD1

27,29

W4

RP-QD1

31,33

W4

RP-QD1

31,33

W4

RP-QD1

31,33

W2

RP-QD1

31,33

W2

RP-QD1

31,33

W2

RP-QD1

31,33

W4

RP-QD1

31,33

W4

RP-QD1

31,33

SL4s

RP-QD1

27,29

SL4s

LP1-A

17,19

SL5

LP1-A

17,19

SL5

LP1-A

17,19

SL5

LP1-A

17,19

SL5

RP-QD1

35,37

SL5

RP-QD1

35,37

SL5

RP-QD1

35,37

SL5

RP-QD1

35,37

SL5

LP1-A

13,15

SL5

LP1-A

13,15

SL3s

LP1-A

13,15

SL3s

LP1-A

13,15

SL5

LP1-A

1,3

SL5

LP1-A

1,3

SL5

LP1-A

1,3

SL5

LP1-A

1,3

SL4s

LP1-A

1,3

SL4s

LP1-A

1,3

SL5

RP-QD1

20,22

SL5

RP-QD1

20,22

SL5

RP-QD1

20,22

SL5

RP-QD1

20,22

SL3s

RP-QD1

20,22

S3

CALL BOX

RP-

QD1-24

SL5

LP1-A

13,15

SL4s

LP1-A

17,19

444 W. Lake St. Suite 1700 Chicago, IL 60606

312.583.7023 www.virtualenergysolutions.com

Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432

Drawing No.

Scale:

Date:

Checked By:Drawn By:Designed By:

Drawing Title:

Contract No.

File No.Building No.

Client Project No.

Project Title:Approved: Chief, failites Management Services

Approved: Medical Center Director

Approved:

Approved: Location:

VES Project Number: 191006

AS NOTED

VA JOLIET CBOC

JOLIET, ILLINOIS

578-371 36C25219D0020

© 2020 Virtual Energy Solutions, INC.

B

IM

/2

-M

A T

O C

-P a rk in g E x p a n s io n a t J o lie t C

B O

C

-3

/2

-M A

T O

C -J o lie t C

B O

C P a rk in g E x p a n s io n E

L E

C

.r v t

/1 /2

:5

:1

P

M

ES101

ELECTRICAL SITE PLAN

PARKING EXPANSION AT

JOLIET CBOC

10/11/2023

AGSAVSDV

1/32" = 1'-0"

1 ELECTRCIAL SITE PLAN

0 16' 32' 64'

Revisions Date

ISSUED FOR 60% DD 12/30/2022

ISSUED FOR 90% CD 02/10/2023

ISSUED FOR 100% CD 03/07/2023

ISSUED FOR BID 03/24/2023

ISSUED FOR BID ADDENDUM 1 04/21/2023

ISSUED FOR BID ADDENDUM 3 10/11/2023

GENERAL NOTES:

1. FOR SECURITY CALL BOX PROVIDE A SEPARATE PHASE AND

NUETRAL CONDUCTOR 2#6 & 1#8 GROUND IN 1" CONDUIT AND CIRCUIT

TO LIGHTING POLE CIRCUIT AHEAD OF SWITCHING AND LIGHTING

CONTROLS. POWER SHALL NOT BE INTERRUPTED BY CONTROLS.

2. ALL EXTERIOR LIGHTING FIXTURES SHALL BE CIRCUITED THROUGH

RELAY PANELS LCP-NORTH AND LCP-SITE. MINIMUM CIRCUIT FEEDER

SHALL BE 2#6 AND 1#8 GROUND IN 1" CONDUIT MINIMUM.

3. MAINTAIN EXISTING EXTERIOR FIXTURE AND CONTROLS FEED

THROUGH EXISTING PANEL LP1A FOR ALL PARKING LOT LIGHTS,

BOLLARDS, PUMPS, CANOPY LIGHTS, ETC. TO REMAIN. PROVIDE FOR

WIRING CONTINUITY FOR ALL DEVICES TO REMAIN. FOR NEW

FIXTURES PROVIDE NEW POLE BASE, CONDUIT & WIRE, CIRCUITS,

ETC. CIRCUIT NEW DEVICES THROUGH NEW LIGHTING CONTROL

PANELS LCP-SITE AND LCP-NORTH.

SD SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SDSDSD

SD

SD

SD

SD

SD

SD

Dx

Ex

Gx

Hx

Jx

Kx

K'x

Lx

1x 4x 6x 9x 12x 13x 14x

Cx

Bx

Ax

A1x

3x 5x 5.8x 8x 10x6.1x

Fx

A.E

15x

15y

15z 15aa

15bb

15cc

15dd

15ee

15ff

15gg15hh

15ii

9.5x1.2x

A

1 2

B

M

M

M

M

M

M

EXISTING

DEMOLITION

NEW

PHASE LEGEND

444 W. Lake St. Suite 1700 Chicago, IL 60606

312.583.7023 www.virtualenergysolutions.com

Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432

Drawing No.

Scale:

Date:

Checked By:Drawn By:Designed By:

Drawing Title:

Contract No.

File No.Building No.

Client Project No.

Project Title:Approved: Chief, failites Management Services

Approved: Medical Center Director

Approved:

Approved: Location:

VES Project Number: 191006

AS NOTED

VA JOLIET CBOC

JOLIET, ILLINOIS

578-371 36C25219D0020

© 2020 Virtual Energy Solutions, INC.

N

B

IM

/2

-M

A T

O C

-P a rk in g E x p a n s io n a t J o lie t C

B O

C

-3

/2

-M A

T O

C -J o lie t C

B O

C P a rk in g E x p a n s io n E

L E

C

.r v t

/1 /2

:5

:3

P

M

ED100-N

BASEMENT LEVEL - ELECTRICAL

DEMOLITION PLAN - NORTH

PARKING EXPANSION AT

JOLIET CBOC

10/11/2023

AGSAVSDV

1/8" = 1'-0"

2 BASEMENT LEVEL - ELECTRICAL DEMOLITION PLAN - NORTH

GENERAL NOTES:

1 FOR ELECTRICAL DEVICES IN THIS ROOM REMOVE CONDUIT, WIRE AND ANCILLARY

ELECTRICAL DISTRIBUTION EQUIPMENT BACK TO SOURCE. LABEL EXISTING CIRCUIT

BREAKER AS SPARE.

2. ALL EXISTING EGRESS AND EMERGENCY EXIT SIGNS SHALL REMAIN UNTIL SHELL

SPACE IS TO BE DEVELOPED.

3. REFER TO DEMOLITION PLANS FOR OTHER TRADES AND REMOVE POWER FOR

EQUIPMENT TO BE REMOVED BACK TO SOURCE. LABEL CIRCUIT BREAKERS FEEDING

EQUIPMENT TO BE REMOVED AS SPARE.

4. LABEL EACH CIRCUIT FOR LIGHTING FIXTURES TO BE DEMOLISHED FOR INSTALLATION

OF NEW LIGHTING FIXTURE TO BE CONNECTED TO SAME CIRCUIT. MAINTAIN EXISTING

SWITCHING SCHEME.

0 4' 8' 16'

ELECTRCIAL DEMOLITION KEYNOTES

NUMBER KEYNOTE

2 REMOVE ALL ELECTRICAL DEVICES AS REQUIRED FOR NEW

CONSTRUCTION. MAINTAIN EXISTING CONTROL SCHEMES. CIRCUIT

LIGHTING TO NEW SPACE SUCH THAT FUNCTION MIMICS EXISTING

THROUGH NEW LIGHTING CONTROL PANEL.

Revisions Date

ISSUED FOR 60% DD 12/30/2022

ISSUED FOR 90% CD 02/10/2023

ISSUED FOR 100% CD 03/07/2023

ISSUED FOR BID 03/24/2023

SD

SD

SD

SD

SD

SD

SD

SD

SD

SDSD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

4 4

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

Dx

Ex

Gx

Hx

Jx

Kx

K'x

Lx

1x 4x 6x 9x 12x 13x 14x

Cx

Bx

Ax

3x 5x 5.8x 8x 10x6.1x

Fx

A.E

15x

15y

15z 15aa

15bb

15cc

15dd

15ee

15ff

15gg15hh

15ii

9.5x1.2x

A

1 2

B

AV

AV

W

W

W

W

W

W

W

W

W

W

S

S

S S

S

W

S

S

S S

S

S

S

S S

S

S

S

S

S

S

SS

S

S

S

S

EXR

EXR

EXR

EXR

EXR

M

M

EXR

EXR

M

R R

R

R

R

R

R

R

R

R

R

R

R

R

SP

SP

VS

H

H

EXR

EXR

EXR

EXR

R REXR

R

R

R

R

R

R

R

R

R

R

EXISTING

DEMOLITION

NEW

PHASE LEGEND

444 W. Lake St. Suite 1700 Chicago, IL 60606

312.583.7023 www.virtualenergysolutions.com

Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432

Drawing No.

Scale:

Date:

Checked By:Drawn By:Designed By:

Drawing Title:

Contract No.

File No.Building No.

Client Project No.

Project Title:Approved: Chief, failites Management Services

Approved: Medical Center Director

Approved:

Approved: Location:

VES Project Number: 191006

AS NOTED

VA JOLIET CBOC

JOLIET, ILLINOIS

578-371 36C25219D0020

© 2020 Virtual Energy Solutions, INC.

N

B

IM

/2

-M

A T

O C

-P a rk in g E x p a n s io n a t J o lie t C

B O

C

-3

/2

-M A

T O

C -J o lie t C

B O

C P a rk in g E x p a n s io n E

L E

C

.r v t

/1 /2

:5

:3

P

M

ED101-N

FIRST FLOOR - ELECTRICAL

DEMOLITION PLAN - NORTH

PARKING EXPANSION AT

JOLIET CBOC

10/11/2023

AGSAVSDV

1/8" = 1'-0"

2 FIRST FLOOR - ELECTRICAL DEMOLITION PLAN - NORTH

GENERAL NOTES:

1 FOR ELECTRICAL DEVICES IN THIS ROOM REMOVE CONDUIT, WIRE AND ANCILLARY

ELECTRICAL DISTRIBUTION EQUIPMENT BACK TO SOURCE. LABEL EXISTING CIRCUIT

BREAKER AS SPARE.

2. ALL EXISTING EGRESS AND EMERGENCY EXIT SIGNS SHALL REMAIN UNTIL SHELL SPACE

IS TO BE DEVELOPED.

3. REFER TO DEMOLITION PLANS FOR OTHER TRADES AND REMOVE POWER FOR

EQUIPMENT TO BE REMOVED BACK TO SOURCE. LABEL CIRCUIT BREAKERS FEEDING

EQUIPMENT TO BE REMOVED AS SPARE.

4. LABEL EACH CIRCUIT FOR LIGHTING FIXTURES TO BE DEMOLISHED FOR INSTALLATION

OF NEW LIGHTING FIXTURE TO BE CONNECTED TO SAME CIRCUIT. MAINTAIN EXISTING

SWITCHING SCHEME.

0 4' 8' 16'

ELECTRCIAL DEMOLITION KEYNOTES

NUMBER KEYNOTE

2 REMOVE ALL ELECTRICAL DEVICES AS REQUIRED FOR NEW

CONSTRUCTION. MAINTAIN EXISTING CONTROL SCHEMES. CIRCUIT

LIGHTING TO NEW SPACE SUCH THAT FUNCTION MIMICS EXISTING

THROUGH NEW LIGHTING CONTROL PANEL.

Revisions Date

ISSUED FOR 60% DD 12/30/2022

ISSUED FOR 90% CD 02/10/2023

ISSUED FOR 100% CD 03/07/2023

ISSUED FOR BID 03/24/2023

Elev. Equip.

B003

Badge

B004

Phone

B002C

Home Based Primary

Care

B002

Stair #2

S-2

Comm.

B005

Reception

B001

Women's Restroom

B006

Men's Restroom

B011

HAC

B007

Copy Room

B009

Phone

B002A

Phone

B002B

Phone

B017

Phone

B016

A.O.

B015

Clinical Nurse Manager

B014

Chief Medical Director

B013

Patient Education/Group

Room

B011

Patient

Education/Exercise

B022

Store

B012

Corridor

C0-2

Corridor

C0-3

Corridor

C0-4

Corridor

C0-1

Mech.

B018

Elec.

B019

Gen Room

B020

PAS Call Center

B024

Education Storage

B022

Nutrition Services

B021

Main Conference Room

B023

Mech.

B025

Patient Education/Group

Room

B033

Patient Education/Group

Room

B032 Patient Ed/Internet Cafe

B031

Elec.

B028

Elevator

EL-1

New North Vestibule

Vending

Cooking Classroom

0023A

Elec.

B026B

Lobby

Elevator-2

E-2-2

Dx

Ex

Gx

Hx

Jx

Kx

K'x

Lx

1x 4x 6x 9x 12x 13x 14x

Cx

Bx

Ax

A1x

3x 5x 5.8x 8x 10x6.1x

Fx

A.E

15x

15y

15z 15aa

15bb

15cc

15dd

15ee

15ff

15gg15hh

15ii

9.5x1.2x

A

1 2

B

F1A F1A F1A

F1A F1A

F2A

F2A

F2AF2AF2A

F2A

F2A

EX-1

EX-1EX-1

EX-1

11 RP-QD1 11 RP-QD1 11 RP-QD1

11 RP-QD111 RP-QD1

12 RP-QD1

12 RP-QD1

12 RP-QD112 RP-QD112 RP-QD1

EM1

EM1

EM1

EX-1

F7

12 RP-QD1

13 RP-QD1

12 RP-QD1

12 RP-QD1

12 RP-QD1

a b

ETR

ETR

ETR

ETR ETR

ETRETR

ETR ETR ETR

ETR

ETR

ETR

11 RP-QD1

12 RP-QD1

EXISTING

DEMOLITION

NEW

PHASE LEGEND

444 W. Lake St. Suite 1700 Chicago, IL 60606

312.583.7023 www.virtualenergysolutions.com

Joliet Community Based Outpatient Clinic 1201 Eagle Street Joliet, Illinois 60432

Drawing No.

Scale:

Date:

Checked By:Drawn By:Designed By:

Drawing Title:

Contract No.

File No.Building No.

Client Project No.

Project Title:Approved: Chief, failites Management Services

Approved: Medical Center Director

Approved:

Approved: Location:

VES Project Number: 191006

AS NOTED

VA JOLIET CBOC

JOLIET, ILLINOIS

578-371 36C25219D0020

© 2020 Virtual Energy Solutions, INC.

N

B

IM

/2

-M

A T

O C

-P a rk in g E x p a n s io n a t J o lie t C

B O

C

-3

/2

-M A

T O

C -J o lie t C

B O

C P a rk in g E x p a n s io n E

L E

C

.r v t

/1 /2

:5

:4

P

M

EL100-N

BASEMENT LEVEL - ELECTRICAL

LIGHTING PLAN - NORTH

PARKING EXPANSION AT

JOLIET CBOC

10/11/2023

AGSAVSDV

1/8" = 1'-0"

1 BASEMENT LEVEL - ELECTRICAL LIGHTING PLAN - NORTH

GENERAL LIGHTING NOTES:

1. SEE DRAWING E001 FOR SYMBOLS.

2. CONNECT NEW AND EXISTING TO BE REMOVED AND REINSTALLED LIGHT

FIXTURES TO EXISTING CIRCUIT MADE SPARE DUE TO DEMOLITION UNLESS

INDICATED OTHERWISE. MAINTAIN EXISTING SWITCHING SCHEME. LIGHT

FIXTURES ARE LESS WATTAGE THAN EXISTING TO BE DEMOLISHED. PROVIDE

FOR NEW LIGHTING CONTROLS AS DIRECTED ON LIGHTING CONTROLS RISER

DIAGRAM #1/E603.

3. CONTRACTOR SHALL PATCH, REPAIR AND FINISH WALLS WHERE DEVICES

HAVE BEEN REMOVED RELOCATED AND/OR REPLACED TO MATCH EXISTING

SUCH THAT WORK IS NOT DISTINGISHABLE FROM EXISTING CONDITIONS.

4. PROVIDE RELAY PANEL FOR LIGHTING CONTROLS. MATCH EXISTING

CONTROLS AND SWITCHING SCHEMES. PROVIDE FOR WIRING CONTINUITY

FOR ALL DEVICES TO REMAINING.

0 4' 8' 16'

Revisions Date

ISSUED FOR 60% DD 12/30/2022

ISSUED FOR 90% CD 02/10/2023

ISSUED FOR 100% CD 03/07/2023

ISSUED FOR BID 03/24/2023

ISSUED FOR BID ADDENDUM 1 04/21/2023

ISSUED FOR BID ADDENDUM 2 07/21/2023

ISSUED FOR BID ADDENDUM 3 10/11/2023

LIGHTING KEYNOTES

NUMBER KEYNOTE

1 CONNECT…