Atch 6_USDA Ames IFC Volume 1 Dwgs 3 of 6.pdf
PDF 9 MB Posted
- Solicitation number
- 12639525R0012
About this file
This document is a set of structural engineering drawings for Building 21 at the USDA National Centers for Animal Health in Ames, Iowa, as part of a laboratory relocation project. The drawings, prepared by Stanley Consultants, detail the structural design, framing, foundation, and architectural elements for the building, which includes multiple levels such as a crawl space, ground level, low roof, penthouse, clerestory, and roof framing.
The comprehensive set of drawings covers critical structural components including foundation details, slab and framing plans, steel connections, stair and guardrail configurations, and roof framing specifications. Key technical details include W-shape and HSS steel sections for columns and beams, concrete slab thicknesses ranging from 6" to 9", roof deck specifications (3" depth, 18 gauge), design live loads (150 PSF for ground floor, 200 PSF for penthouse), and specific structural notes on reinforcing steel, welding, and connection requirements. The drawings also include specialized details for mechanical stack supports, roof drain framing, and ladder/guardrail installations, reflecting the complex engineering needed for a specialized laboratory facility.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D
A
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
MYCOBACTERIOLOGY LABORATORY RELOCATION
AMES, IOWA
27100.10
STRUCTURAL NOTES AND LEGENDS
SHEET 1
SG1 0
AL BICKFORD
ML MARTZ
NJ PIERSON
INTERNATIONAL CODE COUNCIL, INC.
BUILDING CODE: INTERNATIONAL BUILDING CODE (IBC) 2015; PUBLISHED BY
(WHERE APPLICABLE) HAS ACHIEVED DESIGN STRENGTH:
LATERAL STABILITY UNTIL THESE COMPONENTS ARE COMPLETELY INSTALLED AND CONCRETE
STABILITY SYSTEM. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING AS REQUIRED FOR
COMPONENTS OF THE BUILDING STRUCTURE FORM A PART OF THE BUILDING LATERAL
THE BUILDING STEEL STRUCTURE IS NOT A SELF-SUPPORTING FRAME. THE FOLLOWING
PUBLISHED BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION.
ALLOWABLE STRESS DESIGN (ASD) LOAD AND RESISTANCE FACTOR DESIGN (LRFD) 2010;
STEEL DESIGN CODE: AISC 360-10 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS,
ACI 318-14; PUBLISHED BY AMERICAN CONCRETE INSTITUTE.
CONCRETE DESIGN CODE: BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE,
PUBLISHED BY AMERICAN SOCIETY OF CIVIL ENGINEERS.
ASCE 7-10 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES;
BUILDING STABILITY:
STRUCTURAL DESIGN CRITERIA:
ROOF LIVE LOADS: 20 PSF
FLOOR LIVE LOADS:
ROOF SNOW LOAD:
WIND DESIGN DATA:
EARTHQUAKE DESIGN DATA:
A.
PENTHOUSE FLOOR: 200 PSF
GROUND FLOOR: 150 PSF.
CRAWL SPACE FLOOR: 100 PSF.UNIFORM LIVE LOAD:
GROUND SNOW LOAD (Pg): 25 PSF
FLAT ROOF SNOW LOAD (Pf): 24 PSF
SNOW EXPOSURE FACTOR (Ce): 1.0
SNOW IMPORTANCE FACTOR (I): 1.2
THERMAL FACTOR (Ct): 1.0
A.
B.
C.
D.
E.
B.
D.
G.
WIND EXPOSURE: C
ZONE WIDTH A: 9 FT
WALL ZONE 5: 46.321 PSF
WALL ZONE 4: 37.636 PSF
ROOF ZONE 3: 95.860 PSF
ROOF ZONE 2: 63.692 PSF
ROOF ZONE 1: 37.958 PSF
SEE ASCE 7 FOR ADJUSTMENTS FOR OVERHANGS AND OTHER EFFECTIVE AREAS.)
(ALL PRESSURES ARE (+/-) AND ARE BASED ON 10 SF EFFECTIVE AREA -
COMPONENTS AND CLADDING PRESSURE:
19.
FIELD MEASUREMENT NOTES:
AS DETAILED.
ON SHOP DRAWINGS ARE COMPATIBLE WITH EXISTING CONNECTIONS AND ARE CONSTRUCTIBLE
OF EXISTING STRUCTURAL STEEL CONNECTIONS TO ENSURE NEW CONNECTION DETAILS SHOWN
CONTRACTOR'S STRUCTURAL STEEL DETAILER SHALL MAKE NECESSARY FIELD MEASUREMENTS 2.
CONFIRMATION OF DIMENSIONS BY FIELD MEASUREMENTS SHALL BE BORNE BY CONTRACTOR.
FABRICATION. COSTS FOR MODIFICATIONS OF NEW CONSTRUCTION, DUE TO LACK OF
DIMENSIONS SHOWN ON DRAWINGS AND TO PROVIDE DIMENSIONS NOT SHOWN, PRIOR TO
ALL NECESSARY FIELD MEASUREMENTS OF EXISTING STRUCTURES AND EQUIPMENT TO VERIFY
ALL DIMENSIONS OF EXISTING CONSTRUCTION ARE APPROXIMATE; CONTRACTOR SHALL MAKE 1.
GENERAL STRUCTURAL SYMBOLS
DECK SPAN
METAL DECKSLAB CONTROL JOINT
SLAB CONSTRUCTION JOINT
SLOPESLOPE ARROW
SLAB EXPANSION JOINT
DECK SPAN
GUARDRAIL
S
DS
D1
S
C.
RISK CATEGORY: IV
E.
F.
BUILDING ENCLOSURE: ENCLOSED
GUST EFFECT FACTOR: 0.85
TOPOGRAPHIC FACTOR, (Kzt): 1.0
ANCHOR BOLT (AB)
(EXPANSION ANCHOR, UNO)
MECHANICAL ANCHOR (MA)
ADHESIVE ANCHOR (AA)
RISK CATEGORY: IV
F.
1.
2.
3.
6.
8. STRUCTURAL STEEL: SEE SPECIFICATION 05 10 00.
CONCRETE COMPRESSIVE STRENGTH: 4500 PSI AT 28 DAYS.9.
10. REINFORCING STEEL: ASTM A615, GRADE 60.
11. WELDED WIRE FABRIC: ASTM A185.
12.
ALLENDER BUTZKE ENGINEERS (ABE), DATED NOVEMBER 30, 2017, AND ADDENDUM DATED MAY 30, 2018.
REQUIRED SAFE NET ALLOWABLE SOIL BEARING PRESSURE: 2000 PSF PER GEOTECHNICAL REPORT BY
13. FROST DEPTH: 3.5 FEET, PER GEOTECHNICAL REPORT BY ABE.
15.
16.
17.
18.
BASIC WIND SPEED (3 SEC GUST): 120 MPH
A.
A. RISK CATEGORY: IV
B. SEISMIC IMPORTANCE FACTOR (I): 1.5
C. SHORT PERIOD SPECTRAL RESPONSE ACCELERATION (S ): 0.06g
D. 1 SECOND SPECTRAL RESPONSE ACCELERATION (S ): 0.043g
E. SITE CLASS: C
F. SHORT PERIOD SPECTRAL RESPONSE PARAMETER (S ): 0.048g
G. 1 SECOND SPECTRAL RESPONSE PARAMETER (S ): 0.049g
H. SEISMIC DESIGN CATEGORY (SDC): A
I. ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL FORCE
J.
FOR SEISMIC RESISTANCE/STEEL ORDINARY CONCENTRICALLY BRACED FRAMES.
BASIC SEISMIC-FORCE-RESISTING SYSTEM: STEEL SYSTEMS NOT SPECIFICALLY DETAILED
K. RESPONSE MODIFICATION FACTOR (R): 3.0
L. SEISMIC RESPONSE COEFFICIENT (C ): 0.024
1.
A. CONCRETE SLABS WHICH FUNCTION AS HORIZONTAL DIAPHRAGMS.
B. ROOF/FLOOR DECK WHICH FUNCTION AS HORIZONTAL DIAPHRAGMS.
GENERAL NOTES
FOR GENERAL LEGEND AND ABBREVIATIONS, SEE "GG" DRAWINGS.2.
ALL SYMBOLS SHOWN ON THIS LEGEND MAY NOT APPEAR ON THIS SET OF DRAWINGS.1.
CONCRETE NOTES:
TO ENGINEER ANY EVIDENCE OF DAMAGED CONDITIONS.
PROCESS. INSPECT CONCRETE TO REMAIN AT DEMOLITION LIMITS AND REPORT
EXISTING CONCRETE TO REMAIN SHALL NOT BE DAMAGED BY CONCRETE REMOVAL
BY USE OF HAND HELD JACK HAMMERS.
ALONG LINE OF REMOVAL TO WEAKEN CONCRETE AND THEN REMOVE CONCRETE
EXISTING REINFORCING, REMOVE CONCRETE BY PRE-DRILLING SERIES OF HOLES
LIMITATIONS FOR EQUIPMENT OR WHERE NOT PERMITTED DUE TO RETENTION OF
WHERE SAW CUTTING THROUGH ENTIRE SECTION IS NOT POSSIBLE DUE TO SPACE
OVER CUTTING BY SAW AT CORNERS IS NOT PERMITTED.
(3" DIA MINIMUM) CONCRETE AT CORNER PRIOR TO SAW CUTTING.
WHERE LIMITS OF CONCRETE REMOVAL FORM A CORNER, CORE DRILL
CONTRACTOR'S EXPENSE.
DEMOLITION PROCESS SHALL BE CUT AND MECHANICALLY SPLICED AT
BY DEMOLITION PROCESS. DAMAGED BARS OR BARS BENT EXCESSIVELY BY
EXISTING REINFORCING BARS THAT ARE TO BE RETAINED SHALL NOT BE DAMAGED
AND EXTEND INTO SUBSEQUENT NEW CONCRETE CONSTRUCTION.
THICKNESS OF CONCRETE UNLESS EXISTING REINFORCING IS SHOWN TO REMAIN
INITIATE REMOVAL BY SAW CUT. SAW CUTS MAY BE MADE THROUGH ENTIRE
PERFORM REMOVAL AS FOLLOWS:
AT LIMITS OF CONCRETE TO BE REMOVED WHERE EXISTING CONCRETE IS TO REMAIN,
CONCRETE DEMOLITION NOTES:
ROUGHEN SURFACE BEFORE PLACING CONCRETE FOR HORIZONTAL SECTION.
FOR SLABS, BEAMS OR GIRDERS SUPPORTED THEREON. REMOVE LAITANCE AND
HOURS, OR UNTIL CONCRETE IS NO LONGER PLASTIC, BEFORE CONCRETE IS PLACED
CONCRETE IN VERTICAL COLUMNS OR WALLS SHALL BE IN PLACE A MINIMUM OF TWO
SHOP DRAWINGS.
APPROVED BY THE ENGINEER PRIOR TO PREPARATION OF REINFORCING STEEL
PROVIDED THE RELOCATION, ADDITION, OR DELETION OF CONSTRUCTION JOINTS IS
CONSTRUCTION JOINTS AS SHOWN MAY BE VARIED TO SUIT PLACING SEQUENCE
SHOWN OTHERWISE.
KEYWAY DIMENSIONS: DEPTH 1-1/2"; WIDTH ONE-THIRD THAT OF MEMBER UNLESS
WITHSTAND LOADING AND UNTIL REQUIRED SHORING AND BRACING HAVE BEEN INSTALLED.
CONCRETE SHALL NOT BE LOADED UNTIL IT HAS ATTAINED SUFFICIENT STRENGTH TO SAFELY
DURING CONSTRUCTION.
CONTRACTOR IS RESPONSIBLE FOR PREVENTION OF FLOATATION OF STRUCTURES
BY OWNER.
DO NOT PLACE CONCRETE UNTIL REINFORCING STEEL PLACEMENT HAS BEEN VERIFIED
MAXIMUM LENGTH OF CONCRETE PLACEMENT IN ANY DIRECTION, UNLESS SHOWN OTHERWISE:
APPROVAL OF OWNER.
ON SLABS. LOCATIONS OF CONSTRUCTION CRANES ON SITE ARE SUBJECT TO
CONSTRUCTION CRANE OR OTHER HEAVY ERECTION EQUIPMENT WILL NOT BE PERMITTED
7 DAYS AFTER SLAB IS PLACED.
CAUSE VIBRATION OR SETTLEMENT OF THE SUPPORTING SOIL STRATA FOR AT LEAST
DO NOT PERFORM ANY OPERATIONS NEAR GROUND FLOOR SLAB PLACEMENT WHICH COULD
LEAST 7 DAYS AFTER SLAB IS PLACED.
DO NOT PLACE LOADS WITHIN 6 FEET OF CONSTRUCTION JOINT IN SLABS FOR AT
WITH ASTM A123 AND ASTM A386 AS APPLICABLE.
ANCHOR BOLTS, SHALL BE HOT-DIP GALVANIZED AFTER FABRICATION IN ACCORDANCE
ALL METAL FABRICATIONS EMBEDDED IN CONCRETE, OTHER THAN REINFORCING AND
HORIZONTAL LOCATION TO MATCH STEEL OR EQUIPMENT BOLT PATTERN.
CONCRETE. ACCURATELY POSITION BOLTS TO ASSURE CORRECT VERTICAL AND
PROVIDE SETTING TEMPLATES TO POSITION ANCHOR BOLTS PRIOR TO PLACING
ENGINEER'S APPROVAL.
PIPE AND PIPE SLEEVES FOR PIPES ARE NOT SHOWN. FINAL LOCATION SUBJECT TO
FLOOR UNLESS SHOWN OTHERWISE.
MAKE SLEEVES IN WALLS FLUSH AND EXTEND SLEEVES IN FLOORS 4" ABOVE TOP OF
PROVIDE PIPE SLEEVE FOR ALL PIPES AND CONDUITS THAT PASS THROUGH CONCRETE.
SLAB HAS BEEN INSTALLED AND ALL CONCRETE HAS ATTAINED 100% OF DESIGN STRENGTH.
UNLESS NOTED OTHERWISE, DO NOT BACKFILL TUNNELS, VAULTS OR PIT WALLS UNTIL TOP
DESIGN STRENGTH.
TOP OF WALL HAS BEEN INSTALLED COMPLETE AND ALL CONCRETE HAS ATTAINED 100% OF
UNLESS NOTED OTHERWISE, DO NOT BACKFILL BASEMENT WALLS UNTIL FLOOR SUPPORTING
1. REMOVE CONCRETE TO LIMITS SHOWN.
2.
A.
B.
C.
D.
E.
1. EXPOSED CONCRETE CORNER CHAMFER: 1" UNLESS SHOWN OTHERWISE.
2.
3. ALL CONSTRUCTION JOINTS SHALL HAVE KEYWAYS UNLESS SHOWN OTHERWISE.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14. FOUNDATION WALLS SHALL BE ADEQUATELY BRACED DURING CONSTRUCTION.
15.
16.
17.
A. SLABS: 50 FEET.
B. OTHER SECTIONS: 50 FEET.
18.
19.
REINFORCING STEEL NOTES:
ENGINEER. CUTTING OF REINFORCING BARS NOT PERMITTED.
ENGINEER'S APPROVAL AND ADD EXTRA REINFORCING BAR IF REQUESTED BY
SHIFT REINFORCING BARS TO CLEAR ANCHOR BOLTS AND EMBEDDED ITEMS; OBTAIN
OTHERWISE BY ENGINEER.
OR MECHANICALLY CONNECT ALL #14 AND LARGER BAR SPLICES UNLESS APPROVED
LAP OR MECHANICALLY CONNECT ALL #11 AND SMALLER BAR SPLICES AND WELD
CONCRETE REINFORCEMENT."
CONFORM WITH ACI 318 AND ACI STANDARD FOR "DETAILS AND DETAILING OF
OTHERWISE.
REINFORCING SHALL BE CONTINUOUS THROUGH CONSTRUCTION JOINTS UNLESS SHOWN
1.
2. REINFORCING SHALL BE CONTINUOUS AROUND ALL CORNERS UNLESS SHOWN OTHERWISE.
3.
4.
5. TERMINATE ALL REINFORCING STEEL AT EXPANSION JOINTS UNLESS SHOWN OTHERWISE.
6.
7.
TACK WELDING TO REINFORCING BARS IS NOT PERMITTED.
REINFORCING STEEL NOTES (continued):
#8
#9
70 78 87
#10 #11
102 113
#4
#5
#6
#7
BAR SIZE
TOP BARS
OTHER BARS
#3
SHOWN ON DRAWINGS, USE MINIMUM LENGTH SHOWN IN THE FOLLOWING TABLE.
MINIMUM BAR SPLICE LAP LENGTH SHALL BE AS SHOWN. WHERE LAP LENGTH IS NOT
MINIMUM SPLICE LAP LENGTH IN INCHES
REINFORCING BAR
CONCRETE, UNCOATED BARS AND FOLLOWING:
CLASS B SPLICE FOR fy = 60,000 PSI, f'c = 4000 PSI, NORMAL WEIGHT
CLEAR SPACING OF BARS 2 BAR DIA AND COVER BAR DIA, OR
ACI CODE MINIMUM.
STIRRUPS OR TIES THROUGHOUT LAP NOT LESS THAN
CLEAR SPACING OF BARS DIA BAR AND COVER DIA BAR, AND
THAN 12" OF CONCRETE IS CAST IN THE MEMBER BELOW THE BAR.
TOP BARS ARE DEFINED AS HORIZONTAL BARS PLACED SO THAT MORE
SUPPORTS AND BOTTOM REINFORCING MAY BE SPLICED OVER OR NEAR SUPPORTS.
IN SLABS AND BEAMS MAY BE SPLICED IN MIDDLE ONE-HALF OF SPAN BETWEEN
LOCATE SPLICES WHERE SHOWN. WHERE NO SPLICES ARE SHOWN, TOP REINFORCING
ENGINEER.
REINFORCING BAR SPLICES PERMITTED ONLY WHERE SHOWN OR APPROVED BY
MINIMUM CONCRETE COVER SPECIFIED UNLESS SHOWN OTHERWISE.
FOR SLAB REINFORCING BARS, PLACE BARS SPANNING IN THE SHORT DIRECTION WITH
CIRCULAR OPENINGS UNLESS SHOWN OTHERWISE.
ALL RECTANGULAR OPENINGS AND AT 45 DEGREES TO MAIN REINFORCING FOR
PROVIDE ONE #4 X 4'-6" EXTRA DIAGONAL REINFORCING EACH FACE AT CORNERS OF
OTHERWISE.
PERPENDICULAR PROJECTION OF ROUND OPENING ON REINFORCING BAR UNLESS SHOWN
MINIMUM OF 2'-0" BEYOND EDGE OF RECTANGULAR OPENING AND BEYOND
PROVIDE ONE #4 EXTRA REINFORCING ALONG OPENING EDGE EACH FACE; EXTEND BARS
APPROVED BY ENGINEER.
SHOWN OTHERWISE. 180 DEGREE HOOKS ARE AN ACCEPTABLE ALTERNATE WHERE
ALL BARS INDICATED AS BEING BENT SHALL HAVE STANDARD 90 DEGREE HOOKS UNLESS
RE-ENTRANT CORNER.
FLANGE TIP OF STEEL COLUMNS PENETRATING FLOOR SLAB AND AT EACH
PROVIDE ONE #4 X 4'-6" EXTRA DIAGONAL REINFORCING TOP BAR IN SLABS AT EACH
SPLICE LAP LENGTH UNLESS SHOWN OTHERWISE.
HORSEPOWER SHALL BE INCREASED 30 PERCENT OVER THAT LISTED IN TABLE FOR BAR
MINIMUM BAR SPLICE LAP LENGTH OF HEAVY MACHINE FOUNDATIONS LARGER THAN 100
OF WIRES PLUS 2" WHICHEVER IS GREATER.
SPLICE LAP LENGTH FOR WELDED WIRE FABRIC SHALL BE NOT LESS THAN 6" OR SPACING
8.
A.
1)
2)
B.
9.
10.
11.
12.
13.
14. EXTRA REINFORCING SHALL BE IN ADDITION TO REINFORCING SHOWN OR NOTED.
15.
16.
17.
18.
UNLESS SHOWN OTHERWISE
HAIRPIN SIZE
UPPER 1/3 OF ANCHOR BOLT EMBEDMENT (8" MAXIMUM).
SPACE HAIRPINS, ALONG BOLT, 1-1/2" FROM SURFACE AND AT 3" ON CENTER AROUND
3/4" DIAMETER. EXTEND LEGS OF HAIRPIN THE STANDARD EMBEDMENT LENGTH.
PROVIDE EXTRA HAIRPIN REINFORCING AROUND ALL ANCHOR BOLTS LARGER THAN
SIZE AS COLUMN, PIER, OR WALL REINFORCING UNLESS SHOWN OTHERWISE.
PROVIDE REINFORCING BAR DOWELS IN FOOTINGS OF THE SAME NUMBER, SPACING AND
D > 12"
-1/8", +3/8"
COVER
SPECIFIED
GREATER
1-1/2" OR
D 12"
3/8"
3/4"
TOLERANCE
-1/8", +1/4"
+ TOLERANCE
SPECIFIED COVER
D
EXPOSED TO EARTH OR WEATHER.
WEATHER; 3" WHEN DEPOSITED AGAINST EARTH; 3/4" FOR WALLS AND SLABS NOT
EXCEPTIONS; 2" FOR #6 BARS AND LARGER FOR CONCRETE EXPOSED TO EARTH OR
REINFORCING CONCRETE COVER UNLESS OTHERWISE SHOWN: 1 1/2" WITH FOLLOWING
RELATIVE TO FORMED OR UNFORMED CONCRETE SURFACE:
CONCRETE REINFORCEMENT SHALL BE PLACED WITHIN FOLLOWING TOLERANCE
SIZE CHAIRS AND SPACERS FOR SPECIFIED COVER.
TOLERANCES APPLY ONLY AT LOCAL ANOMALIES.
CONCRETE. PLACING BARS INTO WET CONCRETE IS PROHIBITED.
ALL BARS SHALL BE SECURELY PLACED IN FINAL POSITION PRIOR TO PLACING
-1/4", +3/8"1" 1/4"
-3/8", +1/2"
19.
ANCHOR BOLT DIAMETER
<1-1/2"
1-5/8" TO 2" INCL
>2"
#3
#4
#5
20.
21.
22.
23.
NOTE:
MOMENT CONNECTION
FOR STEEL JOISTS AND JOIST GIRDERS, 44TH EDITION, BY STEEL JOIST INSTITUTE (SJI).
STEEL JOIST DESIGN: STANDARD SPECIFICATIONS LOAD TABLES AND WEIGHT TABLES4.
FLOOR DECK AND DIAPHRAGM DESIGN.
STEEL DECK DESIGN: STEEL DECK INSTITUTE (SDI) DESIGN MANUALS FOR ROOF DECK,5.
DIAPHRAGM BRACING CRAWL SPACE WALLS.
BEFORE ADJACENT SPREAD FOOTINGS ARE LOADED. ELEVATED FLOOR SLAB ACTS AS A
ELEVATED FLOOR SLAB AT GROUND LEVEL (ABOVE CRAWL SPACE) SHALL BE INSTALLED 2.
7. ARS DESIGN CODE: MANUAL 242.1-ARS FACILITIES DESIGN STANDARDS.
IMPACT FACTOR FOR DYNAMIC EQUIPMENT: 1.5 20.
MODULUS OF SUBGRADE REACTION:
A.
B.
175 PCI PER GEOTECHNICAL REPORT ADDENDUM BY ABE FOR CRAWLSPACE SLAB.
14.
125 PCI PER GEOTECHNICAL REPORT BY ABE FOR GROUND FLOOR SLAB.
DRIFT LOADS: SEE PLANSG.
M. DESIGN BASE SHEAR (V): 63 KIPS
MAY 31, 2019
RJ LUKKARINEN
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
STRUCTURAL NOTES AND LEGENDS
SHEET 2
SG2 0
GENERAL NOTES
FOR GENERAL LEGEND AND ABBREVIATIONS, SEE "GG" DRAWINGS.2.
ALL SYMBOLS SHOWN ON THIS LEGEND MAY NOT APPEAR ON THIS SET OF DRAWINGS.1.
ORIENTATION MAY TRAP WATER.
PROVIDE 2" DIAMETER DRAINAGE HOLES @ 4'-0" 0C WHERE FRAMING MEMBER
NUTS.
ANCHOR BOLTS FOR ALL MACHINERY OVER 30 HORSEPOWER SHALL HAVE TWO HEAVY HEX
SHALL DEVELOP FULL STRENGTH OF MEMBERS ATTACHED.
ACCORDANCE WITH AWS D1.1, 5.14. ALL OTHER TYPE WELDS NOT SIZED ON DRAWINGS
WHERE FILLET WELD SIZES ARE NOT NOTED ON DRAWINGS, PROVIDE MINIMUM SIZE IN
CONSISTENT WITH OWNER'S PLANT OPERATIONS.
WELDING WILL BE ALLOWED ONLY AT SCHEDULED TIMES AND IN LOCATIONS
VERTICAL UNLESS SHOWN OTHERWISE.
ALL DIAGONAL BRACING SHOWN ON STEEL FRAMING ELEVATIONS SHALL HAVE WEB
BOLT. DO NOT WORK FROM TOP OF CONCRETE.
SET ELEVATION OF BASEPLATES TO TOP OF BASEPLATE AND ANCHOR BOLTS TO TOP OF
MORE MEMBERS OR ELEMENTS ARE STAINLESS STEEL MATERIAL.
PROVIDE STAINLESS STEEL FASTENERS FOR ALL BOLTED CONNECTIONS WHERE ONE OR
MEMBERS OR ELEMENTS ARE GALVANIZED MATERIAL.
PROVIDE GALVANIZED FASTENERS FOR ALL BOLTED CONNECTIONS WHERE ONE OR MORE
BUT NECESSARY FOR COMPLETE CONSTRUCTION OF PROJECT.
CONTRACTOR SHALL FURNISH AND INSTALL MISCELLANEOUS STEEL ITEMS NOT SHOWN
EXTENSION FOR TWO HEAVY HEX NUTS.
DRAWINGS, BUT ARE FURNISHED UNDER THIS CONTRACT, SHALL HAVE SUFFICIENT
ANCHOR BOLTS FOR MECHANICAL EQUIPMENT WHICH ARE NOT DETAILED ON
OTHERWISE ON DRAWINGS:
ANCHOR BOLT HOLES IN BASEPLATES SHALL BE SIZED AS FOLLOWS UNLESS INDICATED
OTHERWISE.
BEAM WEB, CONTINUOUSLY FILLET WELDED TO WEB AND FLANGE, UNLESS NOTED
FLANGE BEAMS, FURNISH 3/8" WEB VERTICAL STIFFENER PLATE ON EACH SIDE OF
WHERE HANGERS OR POSTS CONNECT TO TOP OR BOTTOM FLANGE OF HORIZONTAL WIDE-
AND LOCATED DIRECTLY BENEATH BEAM WEB.
ATTACHES TO BEAM BOTTOM FLANGE AND CONSISTS OF LUG PLATE IN PLANE OF
WELDED TO WEB AND FLANGE. STIFFENER PLATE MAY BE OMITTED IF HANGER
FURNISH MINIMUM 3/8" STIFFENER PLATE ON EACH SIDE OF BEAM WEB, CONTINUOUSLY
WHERE PIPE OR EQUIPMENT HANGERS ATTACH TO BOTTOM OR TOP BEAM FLANGE,
ANCHORAGE WILL BE SUBJECT TO REVIEW BY ENGINEER.
MATERIALS, SHALL BE PROVIDED (AS RECOMMENDED BY MANUFACTURER OF ITEMS).
FASTENERS NOT INDICATED, BUT REQUIRED FOR ANCHORAGE OF EQUIPMENT AND
MISCELLANEOUS ANCHOR BOLTS, MECHANICAL ANCHORS, ADHESIVE ANCHORS, AND
OBSTRUCTIONS TO NORMAL SUPPORT STEEL.
PLATE, CONCRETE FORM DECK AND ROOF DECK AT COLUMN PENETRATIONS AND OTHER
PROVIDE MISCELLANEOUS STEEL AS REQUIRED FOR SUPPORT OF GRATING, CHECKERED
PLATES UNLESS SHOWN OTHERWISE.
AND ANGLES; TOP SURFACES OF BEAMS AND TUBES, AND INSIDE OF BREECHING
DIMENSIONS: TO CENTERLINES OF COLUMNS, BEAMS AND PIPES; BACKS OF CHANNELS
PIPES) UNLESS SHOWN OTHERWISE.
ELEVATIONS: REFER TO TOP SURFACE OF FLANGE OF MEMBER (AND CENTERLINE OF
PROVIDE GUARDRAIL AND KICK PLATE AROUND ALL NEW AND MODIFIED PLATFORMS.
IS INDICATED BY A GUARDRAIL CENTERLINE TOGETHER WITH KICK PLATE DETAILS.
THE EXTENT OF GUARDRAIL AND KICK PLATE AROUND FLOORS, PLATFORMS, AND STAIRS
WELDED TO THE GRATING.
COLUMNS, OR OTHER STRUCTURAL STEEL, EDGE BIND OPENING WITH 1/4" KICK PLATE
WHERE OPENINGS IN GRATING ARE SHOWN OR REQUIRED FOR PASSAGE OF PIPING,
ANOTHER PLAN OR ELEVATION.
SPECIFICATION. FRAMING MEMBERS NOTED BY DEPTH ONLY ARE FULLY SIZED ON
FRAMING MEMBERS NOTED BY DEPTH AND WEIGHT SHALL CONFORM TO THE AISC
MEASUREMENTS AND MINOR MODIFICATIONS WHERE CONFLICTS OCCUR.
BREECHING CONNECTIONS WITH EXISTING PRIOR TO FABRICATION. MAKE FIELD
COORDINATE NEW GUARDRAIL, PLATFORMS, DOOR FRAMES, GIRTS, BRACING, AND
BOTTOM OF DRAWING.
CROSS SECTION OF MEMBER SHOWN THUS WITH VIEW LOOKING TO LEFT OR
FIELD AND SHOP WELDING.
CONTRACTOR'S SHOP DRAWINGS SHALL SHOW ALL WELDING AND DISTINGUISH BETWEEN
CONTRACTOR SHALL PROVIDE AS MUCH WELDING AS PRACTICAL IN THE SHOP.
WELD SYMBOLS SHOWN MAY NOT DISTINGUISH BETWEEN FIELD AND SHOP WELDING.
STEEL NOTES:
1.
2.
3.
4.
5. K4 INDICATES KICK PLATE DETAIL.
6.
7.
8.
9. ALL KICK PLATES SHALL EXTEND A MINIMUM OF 4 INCHES ABOVE WALKING SURFACE.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
DIAMETER OF ANCHOR BOLT
5/8"
3/4"
7/8"
1" TO 2"
OVER 2"
HOLE DIAMETER
7/8"
1 1/16"
1 3/16"
ANCHOR BOLT DIA + 1/2"
ANCHOR BOLT DIA + 1"
23.
24.
25.
DIMENSIONS ARE REQUIRED ON BOTH SYMBOLS, EVEN IF SAME DIMENSIONS.
SHOWN ON SAME SIDE OF REFERENCE LINE AS THE WELD SYMBOL. IF "WELD BOTH SIDES",
TAIL AND ARROW ARE REVERSED
REMAIN AS SHOWN WHEN
S T
REFERENCE
OR OTHER
PROCESS
SPECIFICATION
NOT USED
REFERENCE IS
PROCESS OR
WHEN SPECIFICATION
TAIL-OMITTED
A
R
@L(E) ( )
P
OR SURFACE (MOST COMMON)
OF JOINTARROW SIDEON
BASIC WELD SYMBOL-WELD
(NOTE 2)
(OMIT FOR CONTINUOUS WELDS)
TO-CENTER SPACING
PITCH OF WELDS-CENTER
(NOTE 1)
FIELD WELD SYMBOL
(NOTE 1)
WELD ALL AROUND SYMBOL
JOINT OR SURFACE.
LINE TO ONE SIDE OF A
ARROW-CONNECTS REFERENCE
(BEVEL FLUSH)
GROOVE WELD
(BEVEL CONVEX)
GROOVE WELD
WELD SYMBOLS
(SQUARE CONVEX)
GROOVE WELD
(SQUARE FLUSH)
GROOVE WELD
DOUBLE STAGGERED
FILLET WELD
OF A WELDING SYMBOL
LOCATION OF ELEMENTS
FOR PLUG WELDS
OF COUNTERSINK
OR INCLUDED ANGLE
GROOVE ANGLE
(NOTE 2)
EFFECTIVE THROAT
F
FINISH SYMBOL
(NOTE 1)
CONTOUR SYMBOL
OR SURFACE
OF JOINTOTHER SIDE
BASIC WELD SYMBOL-WELD ON
(NOTE 2)
(OMIT FOR CONTINUOUS WELDS)
LENGTH OF WELD
WELDS
FILLING FOR PLUG AND SLOT
ROOT OPENING-DEPTH OF
FILLET WELD DOUBLE SIDE
FILLET WELD SINGLE SIDE
GROOVE WELD (FLARE V)
GROOVE WELD (FLARE BEVEL)
GROOVE WELD (SQUARE)
GROOVE WELD (V)
GROOVE WELD (BEVEL)
GROOVE WELD (U)
GROOVE WELD (J)
PLUG WELD
BACK OR BACKING WELD
SURFACING WELD
SIZE (NOTE 2)
REFERENCE LINE
(1) SUPPLEMENTARY SYMBOL.
(2)
NOTES:
ELEMENTS IN THIS AREA
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
(6" MIN)
DEPTH AS SHOWN OR SPECIFIED
COMPACTED GRANULAR MATERIAL
REINFORCEMENT
SLAB
JOINT SEALANT
SAWCUT - FILL WITH
(SEE PLAN)
SLAB THICKNESS (T)
6" 6"
C L
R
/4 S
L A
B T
H
IC
K N
E S
S
(M
IN
REINFORCEMENT
DISCONTINUE
VAPOR BARRIER
UNDISTURBED SOIL
REINFORCEMENT
SLAB
VAPOR BARRIER
(6" MIN)
DEPTH AS SHOWN OR SPECIFIED
COMPACTED GRANULAR MATERIAL
(SEE PLAN)
SLAB THICKNESS (T)
SIDE OF JOINT
1/8" RADIUS EACH
C L
R
UNDISTURBED SOIL
1'- O
(T
YP
2'-O " (M
IN)
COL
(TYP)
3"
2'-0" MIN (TYP)
LAP LENGTH EXCEPT
REINFORCEMENT SIZE.
BAR SIZE TO MATCH INTERRUPTED
TYP FOR 4 GROUPS, EACH FACE.
BARS INTERRUPTED BY OPENING;
1/2 OF NUMBER OF PARALLEL SLAB/WALL
ADDTIONAL BARS: MINIMUM OF
BARS (TYP)
LOCATIONS W/ SLAB/WALL
SPACING; STAGGER
MATCH SLAB/WALL BAR
BAR SPACING TO
REINFORCEMENT SIZE.
BAR SIZE TO MATCH INTERRUPTED
TYP FOR 4 GROUPS, TOP AND BOTTOM.
BARS INTERRUPTED BY OPENING;
1/2 OF NUMBER OF PARALLEL SLAB
ADDTIONAL BARS: MINIMUM OF
(TYP FOR 4)
BETWEEN REINF MATS
ADDITIONAL #5 BAR LOCATED
BARS (TYP)
W/ SLAB/WALL
STAGGER LOCATIONS
SLAB/WALL BAR SPACING;
BAR SPACING TO MATCH
2'-0" MIN (TYP)
LAP LENGTH EXCEPT
(SEE PLANS)
SLAB EDGE
SLAB EDGE
BEND BARS AT
ON PLANS
BARS ARE SHOWN
WHERE DIAGONAL
MATS); OMIT BAR
(LOCATE BETWEEN
TOP & BOT
#4 X 4'-0" LG,
REMOVABLE SLAB
OPENING OR
(T Y
P
3"
LOCATED BETWEEN REINF MATS (TYP FOR 4)
#6 FOR SLABS/WALLS THICKER THAN 8";
#5 FOR 8" SLABS/WALLS;
ADDITIONAL #3 FOR 6" SLABS/WALLS;
TOP MAT (TYP)
LOCATE BENEATH
#5 X 4'-0" LG TOP;
BEAM
ON BEAM CENTERLINE
CONSTRUCTION JOINT
SEE PLAN
FOR ORIENTATION
FORM DECK;
DRAPED REINF
W12X26
W
X
W12X26
WIDTH
D E
C K
S P
A N
"X"
"Y
2'-0" (TYP.) WIDTH 2'-6" MAX
WIDE OPENINGS
THAT SHOWN FOR 1'-0" TO 2'-6"
OPENING IN ACCORDANCE WITH
PROVIDE REINF. BARS AROUND
= 5" U.N.O.
EDGE OF DECK
VARIES
THAN 1'-2"
IS LESS
BEAM IF "X"
DELETE THIS
OPENING.
ADJACENT TO
DECK VALLEY
PLACE BARS IN
CENTERLINES.
SUPPORTING BEAM
DECK SPAN TO
IN DIRECTION OF
WIDE. EXTEND BARS
LESS THAN 1'-3"
FOR OPENINGS
WIDE. 1-#7 EA. SIDE
GREATER THAN 1'-3"
FOR OPENINGS
2-#7 EACH SIDE
T Y
P
M A
X
W
X
BEAMS
STRUCTURAL
MAIN
TO 5'-0" WIDE
FOR OPENINGS 2'-6"
LESS THAN 1'-2"
BEAM IF "Y" IS
DELETE THIS
BEAMS
STRUCTURAL
MAIN
BARS AT OPENING
HOOK SLAB TOP
REINF
BOTTOM
D E
C K
S P
A N
BEAM
MAIN STRUCTURAL
1'-0" TO 2'-6" WIDE
FOR OPENINGS
TYPICAL SLAB DETAILS
SG3 0
NO SCALE
SLAB-ON-GRADE CONTROL JOINT
NO SCALE
SLAB-ON-GRADE KEYED CONSTRUCTION JOINT
NOTE:
REINFORCING SHOWN IS IN ADDITION TO REINFORCING SHOWN ON SLAB PLANS, UNLESS NOTED OTHERWISE.
NOTE:
CONSTRUCTION JOINTS: 50 FEET
MAXIMUM ORTHOGONAL DISTANCE BETWEEN
NO SCALE
ADDITIONAL REINFORCING AT CONCRETE OPENINGS AND DISCONTINIUITIES
1" = 1'-0"SCALE:
TYPICAL OPENING THRU FLOOR DECK
NO SCALE
ELEVATED SLAB CONSTRUCTION JOINT DETAIL
AT COLUMNS PENETRATING SLAB AT SLAB/WALL ROUND OPENINGS
AT RE-ENTRANT CORNERS
5.
7.
6.
AND AT COLUMN PENETRATIONS WHERE SUPPORT OF DECK TO BEAMS IS INTERRUPTED.
CONTRACTOR TO PROVIDE AND INSTALL MISCELLANEOUS FORM DECK SUPPORT ANGLES AT IRREGULAR CUTS, OPENINGS
CONTAINMENT.
END CLOSURES, COLUMN CLOSURES AND GIRDER CLOSURES, ALL AS REQUIRED TO PROVIDE WET CONCRETE
CONTRACTOR TO PROVIDE AND INSTALL MISCELLANEOUS SHEET METAL CLOSURES SUCH AS "Z" CLOSURES, "L" FLUTE
CONCRETE. PROMPTLY CLEAN ALL SURFACES OF CONCRETE OR PASTE DUE TO LEAKAGE THROUGH FORM DECK SYSTEM.
CONTRACTOR TO PROVIDE MISCELLANEOUS SHEET METAL, CAULK AND OTHER MATERIALS AS REQUIRED TO CONTAIN WET
AT SLAB/WALL RECTANGULAR OPENINGS
4.
NOTED ON STRUCTURAL DRAWINGS, CONFIRM LOCATION & SIZE WITH ARCH & MEP DRAWINGS.
SEE ARCH & MEP DRAWINGS FOR OPNG LOCATION & SIZE UNLESS NOTED ON STRUCTURAL DRAWINGS. IF OPENINGS
3.
DAY STRENGTH.
FORM OPENINGS WITH SHEET METAL OR WOOD. DECK CAN BE CUTOUT AFTER CONCRETE HAS ATTAINED 75% OF ITS 28
2. NO REINFORCING REQUIRED FOR OPENINGS OF LESS THAN 1'-0" WITH 2'-0" CLEAR TO ADJACENT OPENING.
1. ROUND OPENINGS ARE SIMILAR.
NOTES:
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
E
X
I
S
T
N
G
W
L
K
Y
E X I S T I N G B U I L D I N G 2 1
BUILDING 21
FOUNDATION AND
CRAWL SPACE SLAB PLAN
SF101 0
1/8"=1'-0"
KS HENNEMAN
MAY 31, 2019
NJ PIERSON
FOUNDATION AND CRAWL SPACE SLAB PLAN
11.5 12 12.5 13 14 15 16 17 18 19 17.1 17.718.5
A.5
A.4
DD
EE
A.3
A.2
FF
A.1
B
GG
B.6
HH
C
JJ
9'-0" 10'-6" 10'-6" 21'-0" 21'-0" 21'-0" 21'-0"
1'-6"
9'-4"
BLDG 21
WALKWAY
D
WITH MECHANICAL.
COORDINATE OPENING LOCATIONS IN CONCRETE FLOOR AND WALLS 6.
DESIGN LIVE LOAD ON CRAWL SPACE FLOOR SLAB: 100 PSF.5.
FILLED WITH COMPACTED ENGINEERED FILL.
OVER EXCAVATIONS DUE TO REMOVAL OF EXISTING FILL SHALL BE
BELOW EXISTING GRADE, PER GEOTECHNICAL RECOMMENDATIONS.
STRUCTURE TO A LEVEL OF APPROXIMATELY 2.5 FEET TO 4 FEET
EXISTING FILL SHALL BE REMOVED FROM ENTIRE FOOTPRINT OF NEW 4.
PARALLEL TO AND NEAR GRID LINE A.5 BELOW EXISTING WALKWAY.
CARE NOT TO DAMAGE EXISTING WATER LINE TO REMAIN, RUNNING
CONTRACTOR SHALL PROTECT EXISTING UTILITIES TO REMAIN. TAKE 3.
MEANS NECESSARY TO PROTECT EXISTING FOUNDATIONS.
CONTRACTOR SHALL DESIGN AND PROVIDE SHEET PILE OR OTHER 2.
UNDERMINING OF EXISTING FOUNDATIONS.
WITHIN 5'-0" OF FACE OF EXISTING FOUNDATION WALL TO AVOID
FROM FACE OF EXISTING FOUNDATION WALL. DO NOT DISTURB SOIL
EXCAVATION LIMITS SHALL BE MAINTAINED AT A MINIMUM OF 5'-0" 1.
NOTES:
FOUNDATION WALL
FACE OF EXST
NORTH
FOUNDATION WALL
FACE OF EXST
ON DWG SF502 (TYP)
SCHEDULE & DETAIL
SPREAD FOOTING; SEE
FOUNDATION WALL
CONTINUOUS
LIMITS
EXCAVATION
FOUNDATION
(M
IN
S E
E N
O T
E
5'-0" (MIN)
SEE NOTE 1
1'-1"
2'-0"
1'-0"
1'-0" 6'-0"
11'-6" 17'-5"
1'-0"
CRAWL SPACE LIMITS
1'-0"
10'-8"
TOP OF SLAB EL = -9'-5"
1'-6" MAT FDN SLAB W/ #6@10 EW, T&B;
WELL
STAIR-
CONC
UP
UP
TOC EL VARIES
A-SF500
A-SF500
1'-4"
B-SF500
C-SF500
(SIM)(SIM)
A-SF500A-SF500
B-SF500
D-SF500
5'-3"
14'-8"6'-7"
W E
L L
S T
A
IR
C O
C
JOINT
WALL CONST
CONST JOINT
WALL
145'-3"
1'-0" 4'-0"
CONST JOINT
WALL
CONST JOINT
WALL
BEARS AT EL -2'-9-1/2"
BOT EXST FTG
AT EL -2'-9-1/2"
BOT EXST FTG BEARS
BEARS AT EL -4'-10"
BOT EXST FTG
EXST STEP FTG
OF EXST BLDG 21)
(TYP AT EXTERIOR
BEARS AT EL -3'-0"
BOT EXST FTG
SEE NOTE 2
PROTECTION,
SHEET PILE
OPTIONAL
A-SF501
HAND)
(SIM; OPP
A-SF501
FLOOR SLAB), SEE "ML" PLAN DWGS
SUMP OPENING (BLOCKOUT IN
DRAINS
CLEANOUTS & FLOOR
SEE "ML" PLAN DWGS FOR
F1 F1 F1
F1
F1
F1 F1 F1
AT F1)
(TYP
COLS)
PERIMETER
2'-1" (TYP AT
COLS)
PERIMETER
1'-6" (TYP AT
B-SF501
F2
F3
(SIM)
F4
F5
F5
F2
C-SF501
F3
F4 F4 F4 F4 F4 F4 F4
F6
INTERIOR COLS)
2'-0" (TYP AT
INTERIOR COLS)
2'-0" (TYP AT
17.1
6"
5'-3"
2'-0"
CO
CO
DEPTH @ FLOOR DRAINS
2'-0" DIA DISH X 1/2"
FD FD FD
FD
FD
O U
T T
O O
U T O
F F
D N W
A L L
OUT TO OUT OF FDN WALL
18.5
10'-6"
9'-0"
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
E X I S T I N G B U I L D I N G 2 1
GROUND LEVEL
SLAB AND FRAMING PLAN
SF111 0
GROUND LEVEL SLAB AND FRAMING PLAN
A.5
A.4
DD
EE
A.3
A.2
FF
A.1
B
GG
B.6
HH
C
JJ
9'-0" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 9'-0"
BLDG 21
WALKWAY
D
SEE DRAWING SF501 FOR HSS POST MOUNTING DETAILS.5.
SEE DRAWING SS507 FOR GUARDRAIL (TYPE 2) DETAILS.4.
SEE DRAWING SS506 FOR HANDRAIL DETAILS.3.
STRUCTURAL FLOOR FRAMING MAY BE REQUIRED.
THE DESIGN FLOOR LIVE LOAD SHALL BE IDENTIFIED AND ADDITIONAL
THE FOOTPRINT OF THE EQUIPMENT. ANY EQUIPMENT EXCEEDING
DESIGN FLOOR LIVE LOAD WHEN OPERATING WEIGHT IS DIVIDED BY
THAT WEIGHTS OF LAB EQUIPMENT PROVIDED DO NOT EXCEED
DESIGN FLOOR LIVE LOAD: 150 PSF. CONTRACTOR SHALL VERIFY 2.
ATTACHMENTS AT SIDE LAPS SHALL BE #10 SDS AT 1'-6" OC.
PARALLEL SUPPORTS SHALL BE 5/8" PUDDLE WELDS AT 1'-6" OC. DECK
PATTERN USING 5/8" PUDDLE WELDS. DECK ATTACHMENTS AT
ATTACHMENTS AT PERPENDICULAR SUPPORTS SHALL BE 36/4
REINFORCED WITH 4X4-W5.0XW5.0 WWF, DRAPED. DECK
AND CONCRETE = 8" THICKNESS). CONCRETE TOPPING SHALL BE
DECKING WITH 5" THICK CONCRETE TOPPING (TOTAL FLOOR DECK
FLOOR DECK SHALL BE 3" DEPTH, 18 GAUGE, NON-COMPOSITE 1.
NOTES:
NORTH
OF SLAB)
(TYP AT PERIMETER
EXPANSION JOINT
OF SLAB)
(TYP AT PERIMETER
EXPANSION JOINT
1'-0"
3'-0"
GRADE
6" SLAB ON
19 20
W
X
W
X
W
X
W
X
W24X68
W24X68
W24X68 W24X68
W24X68W24X68W24X68W24X68
W24X68W24X68W24X68W24X68
W24X68W24X68W24X68W24X68
DECK SPAN
D E
C K S
P A
N
TOC EL 0'-0", UNO TOS EL -0'-8", UNO
DN
DN
(TYP)
SEE NOTE 3
HANDRAIL;
A-SF500
(SIM)
W 10X33
W 10X33
W 10X33
W 10X33
W 10X33
W
X3
W
X3
W
X3
1'-4"
W
X3
W
X3
W
X3
(TYP, UNO)
W14X90 COL
WALL (SEE NOTE 5)
EXST WALKWAY CONC
CENTERED ON TOP OF
HSS4-1/2X4-1/2X1/4 POST
WALL (SEE NOTE 5)
EXST WALKWAY CONC
CENTERED ON TOP OF
HSS4-1/2X4-1/2X1/4 POST
B-SF500
C-SF500
A-SF500 A-SF500
(SIM)
C O
N T
R O
L J
O
IN
T
T Y
P
C O
N T
R O
L J
O
IN
T
T Y
P
GRADE
6" SLAB ON
B-SF500
D-SF500
L
X
X /4
L
X
X /4
L3X3X1/4
L
X
X /4
L3X3X1/4
L3X3X1/4
L3X3X1/4
W24X68
W
X
W
X
W24X68
W
X
ARCH FOR SIZE
STORAGE; SEE
2" (MIN) AT COLD
RECESS SLAB
CONDITION)
3-SPAN
(2-SPAN OR
DECK SPAN
CONDITION)
3-SPAN
(2-SPAN OR
W
X
10'-0" 11'-0" 10'-6" 10'-6"
(TYP, UNO) (TYP, UNO)
11'-0" 10'-0"
(TYP, UNO)
W14X90 COL
A-SF501
W
X3
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
HAND)
(SIM; OPP
A-SF501
C-SF501
B-SF501
9'-4" 1'-0"
17.1
1'-6"
C O
N D
IT
IO
N
(S
IN
G L E -S
P A
N
ARCH FOR SIZE
AT COLD STORAGE; SEE
RECESS SLAB 2" (MIN)
W24X68 W24X68
W
X
W
X
ARCH FOR SIZE
AT SHOWER; SEE
RECESS SLAB 1 1/2"
SIZE
ARCH FOR
SHOWER; SEE
1 1/2" AT
RECESS SLAB
(TYP FOR 10)
WIND COLUMN
HSS6X6X1/2
1'-1"
1'-1"
10'-8"
FLOOR
FLOOR
F L
O O
R
UP
RAMP
UP
8'-0 1/2"
/2
PAD DETAIL ON DWG SF502
SEE EXTERIOR EQPT
3'-0" X 3'-0" CONC PAD,
LADDER
1'-3" 3'-8"
A-SF500
(TYP)
SEE NOTE 4
(TYPE 2);
GUARDRAIL
NOTE 1 (TYP)
SLAB/DECK; SEE
8" FLOOR
TOS EL VARIES
STAIR STRINGER
C12X20.7
A-SS505
A-SS502
/2
1'-0"
4'-10"
D-SF501
TOC EL +1'-6"
9'-4"
CO
CO
FD
CO
CO
SH
SH
JSS
CO
CO
FD
FD
FD
FDFD
FD
FD
FD
FD
FD
FD
FD
FD
FDFD
FD
FD
11'-6"
FD
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
FOUNDATION DETAILS - SHEET 1
SF500 0
AS NOTED
TOP OF FTG
TOC EL 0'-0"
TOC EL -9'-5"
CRAWL SPACE SLAB
FLOOR SLAB
ELEVATED
3" STEEL DECK
EL -4'-0"
1'-0"
5'-0" SQ
1'-2"1'-1"2'-9"
1/2" EXP JOINT (TYP)
6" CONC SLAB-ON-GRADE
COL BEYOND
W10 BLDG
GRADE
SECTION
A-SF500
SCALE:3/4"=1'-0"
SF101, SF111
SECTION
B-SF500
SCALE:3/4"=1'-0"
SF101, SF111
SECTION
C-SF500
SCALE:3/4"=1'-0"
SF101, SF111
A.4 OR 12.5 A.5 OR 11.5
2'-0"
EXST FDN WALL
TOC EL 0'-0" GROUND FLOOR SLAB
EXST SLAB
A.1 OR 18.5
W24
W14 COL BEYOND
SEE METAL DECKING SPEC
BENT CLOSURE PLATE;
2'-1"
1'-4"
SEE FOOTING SCHEDULE FOR REINFORCING AND FOOTING SIZE
2'-0" SQ
TOC EL -9'-5"
CRAWL SPACE SLAB
6"6"
L3X3X1/4
1/2" EXP JOINT
2'-0"
1/2" EXP JOINT
TOC EL 6'-0"
EXSTING WALL
EXST TOC EL
VARIES
1'-4"
VARIES
SECTION
D-SF500
SCALE:3/4"=1'-0"
SF101, SF111
WALKWAY SLAB
EXSTING COVERED
WALKWAY FOUNDATION
EXSTING COVERED
ROTATE ORIENTATION OF STEEL DECK
NOTE:
(M
IN
TOC EL VARIES
EXSTING FTG
FOR DECK REINF
SEE DWG SF111 #4@14 EW, TOP
#4@12 EW, EF
GRANULAR FILL
6" LAYER
VAPOR BARRIER
ENGINEERED FILL
COMPACTED
1'-6" (MIN) LAYER,
ROUGHENED JOINT
#6@12 DOWEL, EF
SEE FOOTING SCHEDULE FOR REINFORCING
EW, EF
#4@12
#6@12 EW, EF
ROCK
1'-0" LAYER CRUSHED
1'-0"
MECHANICAL DWGS
DRAINAGE, SEE
SUB-SURFACE
EXCAVATION LIMITS
CRAWL SPACE
AT CRAWL SPACE WALLS
CRUSHED ROCK BACK FILL
WELL-COMPACTED
1/2" EXP JOINT (TYP)
6" CONC SLAB-ON-GRADE (TYP)
#4@14 EW, TOP
#4@12 EW, EF
GRANULAR FILL
6" LAYER
VAPOR BARRIER
AT CRAWL SPACE WALLS
CRUSHED ROCK BACK FILL
WELL-COMPACTED
EXCAVATION LIMITS
CRAWL SPACE
MECHANICAL DWGS
DRAINAGE, SEE
SUB-SURFACE
ROCK
1'-0" LAYER CRUSHED
ROUGHENED JOINT
#6@12 DOWEL, EF
#6@12 EW, EF
1'-0"
(SIM) SECTION.
NOTE:
ENGINEERED FILL
COMPACTED 1'-0"
3" STEEL DECK
FOR DECK REINF
SEE DWG SF111
TOC EL 0'-0"
FLOOR SLAB
ELEVATED
REINFORCING
ON DWG SF502, FOR PIER
SEE FOOTING SCHEDULE,
B
#4@14 EW, TOP
VAPOR BARRIER
GRANULAR FILL
6" LAYER
ENGINEERED FILL
COMPACTED
1'-6" (MIN) LAYER,
2-#4
#4@14
TOC EL 0'-0"
EXSTING SLAB
#4@14 EW, TOP
VAPOR BARRIER
GRANULAR FILL
6" LAYER
ENGINEERED FILL
COMPACTED
1'-6" (MIN) LAYER,
2-#4
#3 DOWEL @ 2'-0" OC
5 1/2"
GROUND FLOOR SLAB
TOC EL 0'-0"
6 1/2"
PIER BEYOND
FOOTING &
COL BEYOND
HSS6X6 WIND
EXCAVATION LIMITS
CRAWL SPACE
6" LAYER GRANULAR FILL (TYP)
E-SF500
#4 CONT
HAIRPIN
#4@12
SECTION
E-SF500
SCALE:1 1/2"=1'-0"
SF500
A.5 OR 11.5
6 1/2"
/2
/2
(T Y
P
(T Y
P
(T Y
P
HSS6X6 WIND COL
1" MIN GROUT
PL 1/2X6-1/2 X 1'-0" ON
(DOUBLE NUT)
W/ 1'-4" EMBEDMENT
(2) 3/4" DIA ANCHOR BOLTS
FOUNDATION WALL
1/2" EXP JOINT
SLAB-ON-GRADE
6" CONC
HSS6X6 & PL
HSS6X6 & PL
DETAIL & FOOTING SCHEDULE ON DWG SF502
ANCHOR BOLTS; SEE TYPICAL FOOTING
5/8" DIA MA @ 2'-0" OC
SECTION A-SF502
"TYPICAL BASE PLATE DETAIL"
BASE PLATE; SEE
BARRIER (TYP)
VAPOR
ROUGHENED JOINT
#4@14
6"
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
FOUNDATION DETAILS - SHEET 2
SF501 0
SECTION
A-SF501
SCALE:3/8"=1'-0"
SF101, SF111
18.5
5'-3" 15 T @ 11" = 13'-9"
R
/1
F-SF501
IN WALL (TYP)
@ 12 CENTERED
#4 HOOKED DOWEL
T/ FDN WALL EL +0'-0"
TOC EL -9'-5"
6"1'-6"
ABRASIVE NOSING (TYP)
CAST-IN-PLACE CAST IRON
NOSING 1/2" MIN
1 1/2" MAX (TYP)
NOSING WORKING LINE
WORK POINT
MATCH TOP REINF
#3 SPACED TO
TREAD
EFFECTIVE
R
IS
E R
WORK POINT
(TYP)
MATCH TOP REINF
#3 SPACED TO
NOSING WORKING LINE
#4@8
#4@12 (TYP)
#4 (TYP)
M
IN
DETAIL
F-SF501
SCALE: 1"=1'-0"
SF501
STAIR NOSING DETAIL
THIS DWG
NOSING, SEE DETAIL
NO SCALE
17 OR A.2 16 OR A.3
T/ FTG EL -4'-0"
T/ FTG EL -9'-5"
& EXST CONC WALL
HSS 4-1/2X4-1/217.1
1'-1"
TOC EXST WALL EL +6'-0"
6" 1'-6"
T/FDN WALL EL +0'-0"
T/FTG EL -4'-0"
B/ FTG EL -2'-9 1/2"
EXST WALKWAY FDN
SECTION
B-SF501
SCALE:3/8"=1'-0"
SF101, SF111
A.1 B
1'-4"
T/ FDN WALL
T/ FTG EL -4'-0"
6" 1'-6"
4"
1'-6"
CENTERED IN WALL
#4 DOWEL @ 12
EXST FDN WALL
SECTION
C-SF501
SCALE:3/8"=1'-0"
SF101, SF111
1'-0"
8'-0 1/2"
4'-0"
E-SF501
#4@12 EW, TOP
WALL (TYP)
CENTERED IN
#4 DOWEL @ 12
6"
6"
#6@12 EW, T&B#6@12 EW, T&B
WALL REINF
#4@12 EW, EF
DOWEL EF
#6@12 VERT
DETAIL
E-SF501
SCALE: 1"=1'-0"
SF501
N O
T C
H
N O
T C
H
N O
T C
H
T/ PAD EL -0'-6"
EL -0'-4"
T/ STAIRWELL WALL
SECTION
D-SF501
SCALE:3/4"=1'-0"
SF111
TOC EL 1'-6"
FIN FLR
18'-0" RAMP
TOC EL 0'-0"
SLOPE 1:12
SLAB REINF, SEE PLAN
EW, TOP
#6@14
ADDL 2-#4
ROUGHENED JOINT
PERIMETER SIDES)
#4@14 (TYP 3
5'-8 1/2" LANDING
SCALE: 1 1/2"=1'-0"
HSS POST MOUNTING DETAILS
SECTION THRU EXISTING WALKWAY CONCRETE WALL ELEVATION @ EXISTING WALKWAY CONCRETE WALL
EL +0'-0"
8" 1'-0" 1'-0"
CONC WALL
POST & EXST POST & ANCHORS
HSS 4-1/2X4-1/2 POST
1/2" PL
(OFFSET FROM OPP SIDE)
3/4" DIA MA @ 1'-0" OC
(BEYOND)
@ 1'-0" OC
3/4" DIA MA
CONC WALL
EXST WALKWAY
HSS 4-1/2X4-1/2 POST
1/2" PL
(TYP FOR 5)
3/4" DIA MA
SECTION
G-SF501
SCALE:1"=1'-0"
SF501
G-SF501
G-SF501
/2
5 1/2"
1'-1"
D O
O R O
P E
N
IN
G
#6@12 EW, T&B
#4@12 EW, EF HAIRPIN
#4@12
JOINT
ROUGHENED
JOINT
ROUGHENED
#6@14 EW, TOP
8" (BEYOND)
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
NEW SLAB
EXISTING OR
PADS FOR EQUIPMENT WHICH DOES NOT REQUIRE ANY ANCHORAGE.
DOWELS AROUND PERIMETER ARE NOT REQUIRED FOR HOUSEKEEPING
(ALTERNATE)
SLAB CONSTRUCTION
PERIMETER FOR NEW
#4@12 DOWEL AROUND
SLAB CONSTRUCTION)
(FOR NEW OR EXISTING
REINFORCING AROUND PERIMETER;
#4@12 ADHESIVE ANCHORED
ANCHOR BOLT/ROD SIZE AND LOCATION TO SUIT EQUIPMENT.
WHERE T < 8")
INTO SLAB 4" MIN
ANCHOR ROD (EXTEND
(ALTERNATE)
IN PAD WHERE T > 8"
ANCHOR BOLT CAST
(M
IN
(M
IN
2" MIN (TYP)
GROUT (1" MIN)
ROUGHENED SURFACE
NOTES:
1.
2.
EQUIPMENT BASE
EQUIPMENT PAD
#5@12 EW
5" MIN (TYP)
DYNAMIC/VIBRATING EQUIPMENT REQUIRES ANCHORAGE AND DOWELS.3.
LAP LENGTH
(TYP)
REINFORCEMENT
MATCH HORIZONTAL
CORNER BARS TO
STD HOOK
MATERIAL
COMPACTED GRANULAR
8"
SIZE VARIES
#4@12 TOP
EQUIPMENT
COORDINATE SIZE W/ OTHER TRADES
3"
#4@12
8"
#5@12 EW
FOUNDATION DETAILS - SHEET 3
SF502 0
A-SF502
TYPICAL FOOTING DETAIL
FTG L X W (SEE SCHEDULE)
TOC EL 0'-0"
NO SCALE
SECTION
A-SF502
NO SCALE
SF502
TYPICAL BASE PLATE DETAIL
T/ FOOTING EL
(SEE SCHEDULE)
PIER WIDTH
D
(S E
E S
C H
E D
U L E
FOOTING SCHEDULE
MARK
F1
F2
F3
F4
F5
F6
L W
ELEVATION
T/ FOOTING
5'-0"
8'-3"
4'-3"
7'-3"
14'-6"
3'-6"
5'-0"
8'-3"
4'-3"
7'-3"
5'-6"
3'-6"
D
1'-0"
1'-3"
1'-0"
1'-3"
1'-6"
1'-0"
REINFORCING
FOOTING
-4'-0"
-9'-5"
-4'-0"
-1'-9"
-1'-6"
-2'-0"
SEE SCHEDULE
FOOTING REINF,
(SEE PLAN)
REINFORCEMENT DETAIL
TYPICAL CONCRETE WALL CORNER
NO SCALE
10" EMBEDMENT
ANCHOR BOLTS W/
(4) 1" DIA F1554 (GR 36)
DOWELS
8-#6 VERTICAL
2"2"
NO SCALE
INTERIOR EQUIPMENT PAD DETAIL
NO SCALE
EXTERIOR EQUIPMENT PAD DETAIL
1/2" 1/2"
/2
/2
1/4
TOC EL
SINGLE NUT
(SEE SPEC SECTION 05 50 00)
ALL THREADED ROD
ADHESIVE ANCHOR (AA) DETAIL
(IF APPLICABLE)
THICKNESS PLUS GROUT
TO SUIT ATTACHMENT
B
E M
B E
D M
E N
T
D (DIAMETER)
D
M
IN
DRILL HOLE;
(SEE SPEC SECTION 05 50 00)
ADHESIVE
TOC EL
SINGLE NUT
SPEC SECTION 05 50 00)
EXPANSION ANCHOR (SEE
MECHANICAL ANCHOR (MA) DETAIL
(IF APPLICABLE)
THICKNESS PLUS GROUT
TO SUIT ATTACHMENT
B
D (DIAMETER)
D
M
IN
U N
O O
N D
R A
W
IN
G S
U S
E V
A L
U E I
N T
A B
M
B E
D M
E N
T
(E F F
E C
T
IV
E M
IN
EMBEDMENT (UNO)
MECHANICAL ANCHOR
D (IN) B (IN)
1/2"
5/8"
3/4"
2"
3 1/8"
3 3/4"
INSTRUCTION
MANUFACTURERS
DIAMETER PER
TOC EL
SINGLE HEAVY HEX NUT
WASHER
BURR LAST THREAD
HEAVY HEX NUT
BEARING PL
GROUT
THREADED ROD
ANCHOR BOLT (AB) DETAIL
INDICATED AS (DN)
DOUBLE NUT WHERE
TOP OF BOLT (TOB) EL
B
E M
B E
D M
E N
T
D /2
D (DIAMETER)
NO SCALE
NO SCALENO SCALE
2D + 1" FOR DOUBLE NUT
FOR SINGLE NUT;D +1"
5 1/2"
1" NON-SHRINK GROUT
8-#4 EW, T&B, HOOKED
10-#5 EW, T&B
7-#4 EW, T&B, HOOKED
9-#5 EW, T&B
6-#4 EW, T&B, HOOKED
9-#8 LONG BARS, T&B
12-#8 SHORT BARS, T&B, HOOKED;
1/2" PL
#4@6 STIRRUPS
(M
IN
JOINT
ROUGHENED
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
E X I S T I N G B U I L D I N G 2 1
LOW ROOF FRAMING PLAN
SS121 0
LOW ROOF FRAMING PLAN
A.5
A.4
DD
EE
A.3
A.2
FF
A.1
B
GG
B.6
HH
C
JJ
9'-0" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 10'-6" 9'-0" 1'-6"
BLDG 21
WALKWAY
D
ROOF SNOW LOAD.
FEET. SNOWDRIFT LOAD SHALL BE APPLIED IN ADDITION TO FLAT
PROJECTIONS = 46 PSF TRIANGULAR LOAD WITH DRIFT WIDTH OF 10.7
DESIGN SNOWDRIFT LOAD ON LOW ROOF AT PARAPETS AND 3.
DRAWINGS FOR CLOSURE DETAILS AT GUARDRAIL POST.
DETAILS. USE GUARDRAIL TYPE B MOUNTING. SEE ARCHITECTURAL
2) AT ROOF. SEE DRAWING SS507 FOR LADDER, GATE AND GUARDRAIL
THROUGH LADDER WITH SELF CLOSING GATE AND GUARDRAIL (TYPE 2.
ATTACHMENTS SHALL BE SPACED AT 1'-0" OC.
SELF DRILLING SCREWS AT 1'-0" OC. PARALLEL SUPPORT
SHALL BE 5/8" PUDDLE WELDS. SIDELAP FASTENERS SHALL BE #10
PATTERN AT PERPENDICULAR SUPPORTS. SUPPORT FASTENERS
ROOF DECK SHALL BE 3" DEPTH, 18 GAUGE, WITH 24/4 ATTACHMENT 1.
NOTES:
SPAN
DECK
ROOF
OPEN
O P
E N
(TYP FOR 10)
WIND COLUMN
HSS6X6X1/2
NORTH
1'-1"( )
COLUMN (TYP)
EXST WALKWAY
LOCATIONS)
VARIES (TYP 4
WT13.5X42; TOS EL
GIRDER WITH
W14 WALKWAY
STRENGTHEN EXST
COL (TYP)
EXST BLDG
(TYP FOR 20)
ROOF FRAMING
SUPPORTED BY LOW
CLERESTORY POST
HSS4X4X1/4
W16X36 W16X36 W16X36 W16X36 W16X36 W16X36 W16X36 W16X36
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W12X26
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W16X36 W16X36 W16X36 W16X36 W16X36 W16X36 W16X36 W16X36
W
X
W
X
W
X
W
X
W
X
W
X
W16X36
W16X36
W16X36
7'-7"5'-11 1/2"5'-11 1/2"
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W16X36 W16X36 W16X36 W16X36 W16X36 W16X36
W16X36W16X36 W16X36 W16X36 W16X36 W16X36 W16X36 W16X36 W16X36 W16X36 W16X36
WALL
WALKWAY CONC
ON TOP OF EXST
POST CENTERED
HSS4-1/2X4-1/2X1/4
WALL
WALKWAY CONC
ON TOP OF EXST
POST CENTERED
HSS4-1/2X4-1/2X1/4
W
X
W
X
W
X
W
X
W
X
W
X
W16X36
W16X36
W12X26
W
X
SPAN
DECK
ROOF
B-SS500
A-SS500
FRAMING DETAIL ON DWG SS510
SEE SUPPLEMENTARY ROOF
COORDINATE W/ MECH DWGS;
FAN PERIMETER;
PENETRATIONS; LOCATE UNDER
FRAMING FOR EXHAUST FAN
SUPPLEMENTARY ROOF
W12X26
W12X26
CONDITION)
3-SPAN
(2-SPAN OR
SPAN
DECK
ROOF
CONDITION)
3-SPAN
(2-SPAN OR
CONDITION)
(2-SPAN
B-SS500
(SIM)
E-SS501
F-SS501
C-SS501
1'-1"
TOS EL +15'-3", UNO
10'-8"
VARIES
ELEV AT WALKWAY
EXSTING STEEL
EXST W14; TOP OF
17.120
1'-0"9'-4"
MECH DWGS
COORDINATE W/
CHILLER RAILS;
LOCATE UNDER
SUPPORT -
FOR CHILLER
ROOF FRAMING
SUPPLEMENTARY
PENTHOUSE
STAIR UP TO
(SEE NOTE 2)
LADDER
UP
DN
STAIR STRINGERS)
C12X20.7 (TYP FOR 4;
TOS EL +12'-3 5/8"
SUPPORT BEAM @
W12X26 STAIR LANDING
SEE NOTE 1 (TYP)
3" ROOF DECK;
A-SS505
COLUMN SIZES (TYP)
SEE DWG SF111 FOR
1'-3"
W16X36
A-SS502
ON DWG SS510
SEE ROOF DRAIN FRAME DETAIL
LOCATIONS (TYP 6 PLACES);
DRAIN, SEE ARCH DWGS FOR
FRAMING FOR RD W/ OVERFLOW
SUPPLEMENTARY ROOF
E-SS505
0"0"
STAIR SUPPORT
ROOF FRAMING FOR
SUPPLEMENTARY
W12X26
2'-2"
5'-0"
FOR 2) (TOS EL +18'-1 1/2")
STRINGER ABOVE (TYP
C10X15.3 PLATFORM/STAIR
5'-5" 5'-4"
W
X
5'-5" 5'-4"
/4
2'-11" 3'-0"
(TOS EL +19'-0")
PLATFORM ABOVE
C10X15.3 CHILLER
C-SS502
/2
1'-6"
18.5
10'-6"
9'-0"
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
PENTHOUSE LEVEL
SLAB AND FRAMING PLAN
SS122 0
PENTHOUSE LEVEL SLAB AND FRAMING PLAN
A.5
A.4
DD
EE
A.3
A.2
FF
A.1
B
GG
NOTES:
NORTH
12.5 13 14 15 16 17 18 17.1 17.718.5
10'-6" 21'-0" 10'-6" 9'-0"21'-0" 21'-0" 21'-0"
W
X
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W24X68
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W
X
W24X68
W24X68
W24X68
W24X68
W
X
W
X
W
X
W
X
W
X
W
X
1'-9"
HSS4 1/2X4 1/2X1/4
POST CENTERED
ON TOP OF EXST
WALKWAY CONC WALL
F-SS501
D-SS501
C-SS501
B-SS500
A-SS500
SPAN
DECK
FLOOR
CONDITION)
(3-SPAN
B-SS501
11'-10"
1'-1"
D-SS501
1'-1"
TOS EL +17'-6"
10'-6" 10'-6"
(TYP, UNO) (TYP, UNO)
EQUIPMENT PAD DETAIL ON DRAWING SF502.
4" THICK CONCRETE EQUIPMENT PAD IN ACCORDANCE WITH INTERIOR
ISOLATORS PER SPEC SECTION 20 05 48 AND SHALL BE PLACED ON A
EQUIPMENT WITH DYNAMIC LOADS/VIBRATION SHALL HAVE 7.
EQUIPMENT THAT IS LESS THAN DESIGN FLOOR LIVE LOAD.
EQUIPMENT LOADS TO OBTAIN A UNIFORM LOAD FROM PAD AND
SF502); PAD SIZES SHALL BE LARGE ENOUGH TO SPREAD OUT HEAVY
DRAWINGS (SEE INTERIOR EQUIPMENT PAD DETAIL ON DRAWING
SLAB, COORDINATE LOCATIONS WITH MECHANICAL AND ELECTRICAL
DASHED BOX INDICATES CONCRETE EQUIPMENT PAD ON TOPPING 6.
EXISTING WALKWAY WALL. SEE SECTION C-SS501.
EDGE OF DOGHOUSE FLOOR SHALL BE COORDINATED WITH FACE OF 5.
SEE DRAWING SS507.
LADDER WITH SAFETY CAGE, ATTACH TO WALL FRAMING. FOR DETAILS 4.
STRUCTURAL FLOOR FRAMING MAY BE REQUIRED.
DESIGN FLOOR LIVE LOAD SHALL BE IDENTIFIED AND ADDITIONAL
FOOTPRINT OF THE EQUIPMENT. ANY EQUIPMENT EXCEEDING THE
FLOOR LIVE LOAD WHEN OPERATING WEIGHT IS DIVIDED BY THE
THAT WEIGHTS OF EQUIPMENT PROVIDED DO NOT EXCEED DESIGN
DESIGN FLOOR LIVE LOAD: 200 PSF. CONTRACTOR SHALL VERIFY 3.
ATTACHMENTS, SEE NOTE 1.
THICKNESS VARIES FROM 5" TO 1'-0 1/2". FOR REINFORCEMENT AND
TEMPORARY SUPPORTS CAN BE REMOVED. CONCRETE TOPPING
WET CONCRETE. ONCE CONCRETE CAN SUPPORT ITS OWN WEIGHT,
DOGHOUSE. EXISTING METAL DECK CANNOT SUPPORT WEIGHT OF
AT HALF SPAN DURING POUR AND CURING OF NEW TOPPING SLAB AT
PROVIDE TEMPORARY SUPPORT OF EXISTING WALKWAY METAL DECK 2.
ATTACHMENTS AT SIDE LAPS SHALL BE #10 SDS AT 1'-6" OC.
PARALLEL SUPPORTS SHALL BE 5/8" PUDDLE WELDS AT 1'-6" OC. DECK
PATTERN USING 5/8" PUDDLE WELDS. DECK ATTACHMENTS AT
ATTACHMENTS AT PERPENDICULAR SUPPORTS SHALL BE 36/4
REINFORCED WITH 4X4-W5.0XW5.0 WWF, DRAPED. DECK
AND CONCRETE = 9" THICKNESS). CONCRETE TOPPING SHALL BE
DECKING WITH 6" THICK CONCRETE TOPPING (TOTAL FLOOR DECK
FLOOR DECK SHALL BE 3" DEPTH, 18 GAUGE, NON-COMPOSITE 1.
(TYP)
10 3/4"(T Y
P
/4
(T Y
P
/4
1'-7" (+/-)
(TYP)
10 3/4"
EDGE OF FLOOR DECK
AND CONCRETE TOPPING
SLAB AT PERIMETER
HSS4X4X1/2
TUBE COLUMN ON
TOP OF EXST
WALKWAY GIRDER
HSS4X4X1/2
TUBE COLUMN ON
TOP OF EXST
WALKWAY GIRDERSEE NOTE 6 (TYP)
LOCATIONS WITH MECH DWGS;
TOPPING SLAB, COORDINATE
INDICATES CONC EQPT PAD ON
STAIR AND LANDING
INDICATES CONC EQPT PAD ON
TOPPING SLAB, COORDINATE
LOCATIONS WITH ELEC DWGS;
SEE NOTE 6 (TYP)
(SIM)
DN
NOTE 4
SEE
6" SLAB EDGE
AT DOGHOUSE
EXPANSION JOINT
AT STAIRWELL OPENING
AND CONC TOPPING SLAB
EDGE OF FLOOR DECK
(TYP, UNO)
SEE NOTE 1
SLAB/DECK;
9" FLOOR
TOC EL +18'-3"
TOPPING, SEE NOTE 2
W/ NEW CONCRETE
EXST METAL DECK
A-SS505
(TYP FOR 4)
WALKWAY COLUMN
ON TOP OF EXST
COLUMN CENTERED
HSS8X6X5/8 TUBE
W
X
W
X
W
X
GUARDRAIL
(SEE NOTE 5)
CO
FD
CO
FD
FD
FD
FD FD FD
FD
FD
DEPTH @ FLOOR DRAINS
2'-0" DIA DISH X 1/2"
D-SS502
(OPP HAND)
D-SS502
D-SS502
D-SS502 (OPP HAND)
10'-8"
HSS4 1/2X4 1/2X1/4
POST CENTERED
ON TOP OF EXST
WALKWAY CONC WALL
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
CLERESTORY FRAMING PLAN
SS131 0
CLERESTORY FRAMING PLAN
NORTH
12.5 13 14 15 16 17 17.1 17.718.5
A.4
EE
A.3
A.2
FF
A.1
10'-6" 21'-0" 21'-0" 21'-0" 21'-0" 11'-10" 10'-8"10'-6"
W16X36
7'-7"
9'-0"
W
X
W
X
W
X
W16X36 W16X36 W16X36 W16X36 W16X36
SPAN
DECK
ROOF
S P
A N
D E
C K
R O
O F
HSS4X4X1/4
CLERESTORY
FRAMING
(TYP, UNO)
B-SS500
TOS EL +22'-6 3/4"
A-SS500
NOTES:
ATTACHMENTS SHALL BE SPACED AT 1'-0" OC.
SELF DRILLING SCREWS AT 1'-0" OC. PARALLEL SUPPORT
SHALL BE 5/8" PUDDLE WELDS. SIDELAP FASTENERS SHALL BE #10
PATTERN AT PERPENDICULAR SUPPORTS. SUPPORT FASTENERS
ROOF DECK SHALL BE 3" DEPTH, 18 GAUGE, WITH 24/4 ATTACHMENT 1.
3" ROOF DECK;
SEE NOTE 1 (TYP)
SNOW LOAD.
SNOWDRIFT LOAD SHALL BE APPLIED IN ADDITION TO FLAT ROOF
DESIGN SNOWDRIFT LOAD ON CLERESTORY ROOF = 46 PSF. 2.
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
PENTHOUSE ROOF FRAMING PLAN
SS132 0
/4 P
E R F
O O
T /4 P
E R F
O O
T
PENTHOUSE ROOF FRAMING PLAN
1/4"
PER
FOOT
NORTH
12.5 13 14 15 16 17 17.1 17.718.5
A.4
EE
A.3
A.2
FF
A.1
10'-6" 21'-0" 21'-0" 21'-0" 21'-0" 11'-10" ( ) 10'-8"10'-6"
3 EQUAL SPACES 3 EQUAL SPACES 3 EQUAL SPACES 3 EQUAL SPACES2 EQUAL SPACES 2 EQUAL SPACES 2 EQUAL SPACES
W16X36
HSS4-1/2X4-1/2X1/4
VERT DIAG BRACING
K S
T E
E L J
O
IS
T
T Y
P
U N
O
NOTES:
9'-0"
W
X
W
X
W
X
W
X
W
X
W
X
K S
T E
E L J
O
IS
T
T Y
P
U N
O
W16X36 W16X36 W16X36 W16X36 W16X36 W16X36
W
X
H S
S -1 /2
X -1 /2
X /4
V E
R T D
IA
G B
R A
C
IN
G
H S
S -1 /2
X -1 /2
X /4
V E
R T D
IA
G B
R A
C
IN
G
H S
S -1 /2
X -1 /2
X /4
V E
R T D
IA
G B
R A
C
IN
G
H S
S -1 /2
X -1 /2
X /4
V E
R T D
IA
G B
R A
C
IN
G
W16X36W16X36
W16X36
W16X36W16X36 W16X36 W16X36 W16X36 W16X36 W16X36
W16X36 W16X36 W16X36 W16X36 W16X36 W16X36
W14X90 COLUMN (TYP)
HSS4-1/2X4-1/2X1/4
VERT DIAG BRACING
EAVE TOS EL 36'-4"
RIDGE - TOS EL 37'-2 1/2"
HSS8X6X5/8 TUBE COLUMN
CENTERED ON TOP OF EXST
WALKWAY COLUMN
HSS4X4X1/4 TUBE COLUMN CENTERED ON
TOP OF EXST WALKWAY ROOF GIRDER
HSS4X4X1/4 TUBE COLUMN CENTERED ON
TOP OF EXST WALKWAY ROOF GIRDER
W
X
W
X
W
X
W
X
W
X
W
X
W
X
B-SS500
A-SS500
A-SS501
C-SS500
SPAN
DECK
ROOF
CONDITION)
3-SPAN
(2-SPAN OR
W16X36
TOS EL VARIES; (+36'-4" AT - NORTH EAVE)
(+37'-2 1/2" AT RIDGE)
(+36'-9 1/4" AT SOUTH EAVE)
HSS8X6X5/8 TUBE COLUMN
CENTERED ON TOP OF EXST
WALKWAY COLUMN
EAVE TOS EL 36'-9 1/4"
ROOF SNOW LOAD.
FEET. SNOWDRIFT LOAD SHALL BE APPLIED IN ADDITION TO FLAT
PROJECTIONS = 12 PSF TRIANGULAR LOAD WITH DRIFT WIDTH OF 5.6
DESIGN SNOWDRIFT LOAD ON PENTHOUSE ROOF AT PARAPET AND 5.
ARCHITECTURAL DRAWINGS FOR ROOF HATCH DETAIL.
DRAWING SS510 FOR SUPPLEMENTARY ROOF FRAMING DETAIL AND
SUPPLEMENTARY FRAMING FOR ROOF HATCH AT LADDER. SEE 4.
DRAWING SS511.
JOIST REINFORCEMENT AT CONCENTRATED LOADS DETAIL ON
JOIST STRUT AT POINT OF CONCENTRATED LOADS. SEE TYPICAL
COORDINATE LOCATION WITH MECHANICAL DRAWINGS; PROVIDE
MECHANICAL EQUIPMENT BELOW (SUSPENDED FROM ROOF FRAMING), 3.
STEEL JOISTS SHALL BE DESIGNED FOR 5 PSF NET UPLIFT.2.
ATTACHMENTS SHALL BE SPACED AT 1'-0" OC.
SELF DRILLING SCREWS AT 1'-0" OC. PARALLEL SUPPORT
SHALL BE 5/8" PUDDLE WELDS. SIDELAP FASTENERS SHALL BE #10
PATTERN AT PERPENDICULAR SUPPORTS. SUPPORT FASTENERS
ROOF DECK SHALL BE 3" DEPTH, 18 GAUGE, WITH 24/4 ATTACHMENT 1.
SEE NOTE 1 (TYP)
3" ROOF DECK;
3 EQUAL SPACES
DETAIL ON DWG SS510
SUPPLEMENTARY ROOF FRAMING
COORDINATE W/ MECH DWGS; SEE
LOCATE UNDER FAN PERIMETER;
FOR EXHAUST FAN PENETRATIONS;
SUPPLEMENTARY ROOF FRAMING
ROOF DRAIN FRAME DETAIL ON DWG SS510
FOR LOCATIONS (TYP 4 PLACES); SEE
W/ OVERFLOW DRAIN, SEE ARCH DWGS
SUPPLEMENTARY ROOF FRAMING FOR RD
FRAMING DETAIL ON DWG SS510
SEE SUPPLEMENTARY ROOF
LOCATIONS WITH MECH DWGS;
PENTHOUSE, COORDINATE
FRAMING FOR MECH
SUPPLEMENTARY ROOF
NOTE 3
D-SS502
HSS6X6X1/4 GIRT (TOS EL +30'-6"(+/-)) SEE TYP
GIRT DETAIL AT PENTHOUSE ON DWG SS502
HSS6X6X1/4 GIRT (TOS EL +30'-6"(+/-)) SEE TYP
GIRT DETAIL AT PENTHOUSE ON DWG SS502
W16X67 OVER COILING
DOOR AND HOOD;
COORDINATE WITH ARCH
D-SS502
HAND)
(OPP
(OPP HAND)
D-SS502
D-SS502
BRIDGING
CROSS
HORIZ
BRIDGING
CROSS
HORIZ
BRIDGING
CROSS
HORIZ
NOTE 4
HAND)
(OPP
A-SS501
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
STRUCTURAL ELEVATIONS
SS200 0
SCALE:1/8"=1'-0"
12.5 13 14 15 16 17 17.1 17.718.5
PENTHOUSE FRAMING ELEVATION @ COLUMN ROW "A.1"
TOS EL 17'-6"
TOS EL 24'-4"
TOS EL 36'-9 1/4"
TOS EL 33'-0 1/4"
W24X68
W24X68 W24X68 W24X68 W24X68 W24X68 W24X68
W12X26 W12X26 W12X26 W12X26 W12X26 W12X26
W12X26
W16X36
W12X26
W16X36
W12X26
W16X36
W12X26
W16X36
W12X26
W16X36
W12X26
W16X36W16X36 W16X36
(TYP, UNO)
W14X90 COLUMN
HSS4X4X1/4 COL
ROW "FF")
(BEYOND @ COL
HSS8X6X5/8 COL
DWG SS511
WALL FRAMING DETAIL ON
OPENING; SEE SUPPLEMENTARY
REINFORCE WALL PANEL AT
PANEL FOR STACK (TYP);
CUT OPENING IN METAL WALL
WALL FRAMING DETAIL ON DWG SS511
PANEL AT OPENING; SEE SUPPLEMENTARY
LOUVER (TYP, UNO); REINFORCE WALL
OPENING IN METAL WALL PANEL FOR
H S S -1 /2
X -1 /2
X /4
WALL FRAMING DETAIL ON DWG SS511
OPENING; SEE SUPPLEMENTARY
DOOR; REINFORCE WALL PANEL AT
OPENING IN METAL WALL PANEL FOR
W12X26
(1
M A
X S
T U
D S
P A
N
A.1
FF
A.2
EE
A.4
SCALE:1/8"=1'-0"
PENTHOUSE FRAMING ELEVATION @ COLUMN ROW "17.7"
(LOOKING NORTH)
(LOOKING WEST)
TOS EL 36'-9 1/4"
TOS EL 33'-0 1/4"
EXST W14 (BEYOND) EXST W14 EXST W14 (BEYOND)
EXST TOS EL VARIES 17'-1" MIN; 17'-8 1/2" MAX
WT13.5
WT13.5
WT13.5
OVER COILING DOOR & HOOD
W16X67
HSS6X6X1/4
GIRT (BEYOND)
HSS6X6X1/4
GIRT (BEYOND)
(BEYOND @ COL ROW "17.1")
HSS4X4X1/4 COLUMN
HSS8X6X5/8 COLUMN
W16X67
@ SOUTH EAVE
W16X36W16X36
TOS EL 37'-2 1/2"
@ RIDGE (BEYOND)
TOS EL 36'-4"
@ NORTH EAVE
@ COL ROW "17.1")
COLUMN; (BEYOND
HSS4X4X1/4
DRAWIING SS511
SEE DETAIL ON
FOR 2 EACH STACK);
STACK COLLAR (TYP
MECH DRAWINGS)
(BEYOND) (SEE
MECH STACK
H S S -1 /2
X -1 /2
X /4H
S S 4-1/2X
4-1/2X 1/4
2 EACH STACK)
GUY WIRE (TYP FOR
FOR DOOR
COILING
WALL PANEL
IN METAL
OPENING
(BEYOND)
(B E
Y O
N D
(BEYOND)
HSS6X6X1/4 GIRT
(BEYOND) (BEYOND)
(BEYOND) (BEYOND)
(B E Y O
N D ) (B
E Y
O N
D
(1
M A
X S
T U
D S
P A
N
EXST WALKWAY COL
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
FRAMING DETAILS - SHEET 1
SS500 0
B A.1
10'-6"
TOS EL +36'-9 1/4" (LP - SOUTH)
TOS EL +17'-6"
(PENTHOUSE ROOF)
TOC EL +18'-3"
(PENTHOUSE FLOOR)
EXST W12 OR W16
TOS EL +15'-3"
(LOW ROOF)
TOS EL +22'-6 3/4"
(CLERESTORY ROOF)
TOS EL +36'-4" (LP - NORTH)
(PENTHOUSE ROOF)
7'-7"
A.2
SECTION
C-SS500
SS132
SCALE:1 1/2"=1'-0"
SECTION
NO SCALE
SECTION
A-SS500
NO SCALE
SS131,SS132
SS121,SS122
SS131,SS132
SS121,SS122
TOS EL…