Atch 12_USDA Ames IFC Volume 2 Dwgs 3 of 3.pdf

PDF 8 MB Posted

Attached to
Lab Renovation, National Centers for Animal Health, Ames, IA
Solicitation number
12639525R0012
Issued by

About this file

These drawings detail a demolition and modification plan for Building 401 at the USDA National Centers for Animal Health in Ames, Iowa, as part of a laboratory relocation project. The comprehensive set of architectural, mechanical, electrical, plumbing, and fire protection plans cover both first and second floor modifications, focusing on the Mycobacteriology Laboratory renovation. Key demolition activities include removing existing HVAC systems, electrical panels, fire protection infrastructure, plumbing fixtures, and interior architectural elements to prepare the space for reconfiguration.

The drawings specify technical details for systematic removal and replacement of building systems, including specifications for capping utilities, protecting remaining infrastructure, and preparing surfaces for new construction. Specific modifications include installing new doors, patching and repairing floor and wall surfaces, updating electrical panels and lighting circuits, modifying HVAC ductwork and controls, and reconfiguring fire protection systems. The plans are dated May 31, 2019, and were prepared by Stanley Consultants, indicating a detailed engineering approach to repurposing the laboratory facility while maintaining critical research infrastructure functionality.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

B U I L D I N G 401

D

A

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

MYCOBACTERIOLOGY LABORATORY RELOCATION

AMES, IOWA

27100.10

316 315

315B

209 211

M01

307306305304

311 312

201 214

112111110

204B

205309

310 207

104 103

102 101

EQUIP ROOM

WATER

DNA ROOM TB ID ROOM BACTEC

SCOPE

ROOM

EQUIPMENT

ROOM

WALK-IN

COOLER

OUTGOING RECEIVING

VESTIBULE

EQUIPMENT

ROOM

PROCESSING

LAB

ELECTRICAL

MECHANICAL

STAIRS

BSL-2 CORRIDOR

WALK-IN

COOLER

AIRLOCK

LOBBY

BSL-3 CORRIDOR

TECH ROOM

STORAGE

BRUCELLA

ROOM

ESP ROOM

TB PROC

#3

TB PROC

#2

TB PROC

#1

CHANGING

ROOM SHOWER

LOCKER

HALLWAY

MOL

LAB 1

MOL

LAB 2

MOL

LAB 3

MOL

LAB 4

TANK

ROOM

RECEPTION

TECH

ROOMOFFICE OFFICE

SCOPE

RM

JANITOR

CHANGING

ROOM

SHOWER LOCKER

ELEC

DATA HALLWAY

VESTIBULE

OFFICEOFFICEOFFICEOFFICE

OFFICE

CLOSET

CONFERENCE/

BREAKROOM

A/V

CLOSET

PHENOL RM

321 4 4.7 5 6 7 8

A

A.4

B

C

D

A

A.4

B

C

D

C.3

C.6

7 87.2

BUILDING 401

FIRST FLOOR ARCHITECTURAL

DEMOLITION PLAN

DA150 0

1/8"=1'-0"

D SARKAR

KS HENNEMAN

FIRST FLOOR ARCHITECTURAL DEMOLITION PLAN

LEGEND:

INDICATES DEMOLITION LIMITS

W A

L L T

O R

E M

A

IN

1" DRAIN

CABINETS, FURNITURE, ETC.

DEMOLISH BUILT-IN COUNTERTOPS, BASE CABINETS, WALL 7.

DEMOLISH INTERIOR FINISHES (FLOORING, CEILING, ETC.)6.

DEMOLISH INTERIOR DOORS AND FRAMES SHOWN IN DASHED.5.

DEMOLISH INTERIOR PARTITIONS SHOWN IN DASHED, UNO.4.

EXISTING INTERIOR PARTITIONS TO REMAIN.3.

DOUBLE DOOR.

DEMOLISH EXTERIOR WALL AS REQUIRED FOR AN 2 - 4'-0" X 8'-0" 2.

DEMOLISH EXTERIOR DOOR AND FRAME.1.

WITHIN THE DEMOLITION LIMIT -

DEMOLITION KEYNOTES:

4 5 6 7

PROTECT SURROUNDING STRUCTURE.

AREA OF SPECIFIC ELEMENT AND ALL CAUTION SHOULD BE TAKEN TO

ALL DEMO WORK MUST BE SAFELY CONTAINED WITHIN THE IMMEDIATE 4.

BECAUSE ITEM WILL BE REUSED ON PROJECT.

"REMOVE AND SALVAGE" MEANS TO TAKE CAUTION WHEN REMOVING 3.

SPECIFICATIONS.

MATERIAL RESTORATION AND/OR REFURBISHMENT WITHIN THE

REPAIR PRACTICES AS WELL AS METHODS SPECIFICALLY STATED FOR

TO GENERALIZE SPECIFIED METHODS CONSISTENT WITH COMMON

THE TERM "REPAIR" WITHIN THE DEMO DOCUMENTS SHALL BE USED 2.

PROCEEDING WITH THE WORK IN THAT AREA.

CONTRACTING OFFICER IMMEDIATELY FOR DIRECTION, PRIOR TO

EXECUTION OF THE NEW WORK AS INDICATED, CONTACT THE

ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT

EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF

THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL

DRAWINGS FURNISHED BY USDA OR GENERAL FIELD OBSERVATIONS.

INFORMATION IN THESE DRAWINGS ARE BASED, IN PART, ON EXISTING

EXISTING CONDITIONS. ILLUSTRATIONS, DIMENSIONS AND

DOCUMENTS AND ARE INTENDED TO REASONABLY REPRESENT

THE DEMOLITION DRAWINGS ARE DERIVED FROM EXISTING BUILDING 1.

DEMOLITION NOTES:

DOCUMENTS.

ACCORDANCE WITH THE MECHANICAL, ELECTRICAL, AND PLUMBING

THE PARTITIONS SHALL BE REMOVED, TERMINATED, CAPPED, IN

OTHERWISE. ALL UTILITIES WITHIN THE DEMOLISHED PORTIONS OF

FLOOR TO UNDERSIDE OF SUBSTRATE ABOVE UNLESS NOTED

DEMOLITION OF EXISTING PARTITIONS SHALL BE COMPLETE FROM 7.

NOTED OTHERWISE.

TO MEET A SPECIFIC FIRE RATING, SHALL REMAIN AS IS UNLESS

RECEIVE FURRING OR A SUSPENDED FINISH, AND ARE NOT DETAILED

AREAS WHERE THESE EXPOSED SURFACES ARE SCHEDULED TO

PATCHWORK WILL NOT BE NOTICEABLE ONCE NEW FINISH IS APPLIED.

DEPRESSIONS ARE LEVEL WITH ADJOINING SURFACES SO

SURFACES SUCH THAT ALL HOLES, CORES, VOIDS, AND OR

WHERE EXISTING CONSTRUCTION IS REMOVED; PATCH AND LEVEL 6.

CONTRACTING OFFICER FOR FURTHER DIRECTION.

STOP FURTHER DEMOLITION IN SPECIFIC AREA AND CONTACT

STRUCTURAL ELEMENT THAT HAS NOT BEEN IDENTIFIED AS SUCH,

INTEGRITY. IF ANY DEMOLITION DIRECTION APPEARS TO BE ON A

DEMOLITION OF WALLS SHALL BE INVESTIGATED FOR STRUCTURAL 5.

COORDINATED WITH CONTRACTING OFFICER OF USDA.

ADVERSELY AFFECT ANY REMAINING OCCUPANTS SHALL BE

ALL WORK TO CONTROL NOISE, DUST, AND HAZARDS AS TO NOT 11.

WALLS AND CEILINGS DAMAGED AS PART OF THE DEMOLITION WORK.

CONTRACTOR SHALL REPAIR OR REPLACE IN KIND PORTIONS OF 10.

PLACE SHALL BE PROTECTED FROM DAMAGE.

ALL BUILDING COMPONENTS AND FINISHES THAT ARE TO REMAIN IN 9.

SUBCONTRACTOR.

IS COMPLETE PRIOR TO TURN OVER TO NEXT SCHEDULED

COORDINATE THE DEMOLITION WITH NEW WORK SO THAT DEMOLITION

THE CONTRACTOR SHALL VERIFY ACTUAL CONDITIONS AND

MAY NOT BE COMPLETE IN THE IDENTIFICATION OF ALL REMOVALS.

THE DEMOLITION KEYNOTES IDENTIFY SPECIFIC AREAS OF WORK BUT 8.

CONSTRUCTION.

RELOCATION OF FURNITURE AND EQUIPMENT PRIOR TO BEGINNING

COORDINATE WITH CONTRACTING OFFICER OF USDA FOR THE 14.

OFFICER OF USDA.

COORDINATION MUST BE MADE WITH OCCUPANTS VIA CONTRACTING 13.

ALL EDGE CONDITIONS AND SHEET METAL FABRICATIONS.

DISCOVERIES. THE WORK PLAN SHALL INCLUDE SHOP DRAWINGS FOR

PLAN BASED ON THE CONTRACT DOCUMENTS AS MODIFIED BY

SPECIALIST SHALL PREPARE, FOR APPROVAL, A WORK CONTROL

BE REINSTALLED OR TEMPORARILY WATERPROOFED. THE QUALITY

AS REQUIRED TO FULLY UNDERSTAND THE WORK. REMOVALS SHALL

EXPLORATORY INVESTIGATIONS AND SHALL REMOVE COMPONENTS

PRIOR TO PERFORMING THE WORK THE CONTRACTOR SHALL MAKE 12.

N O

R

TH

MAY 31, 2019

D SARKAR

CM CHAMBERLIN

RJ LUKKARINEN

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

SYSTEM TO REMAIN (TYP)

STANDING SEAM METAL ROOF

REMAIN (TYP)

GUTTER TO TO REMAIN (TYP)

DOWNSPOUT

FLUEVTR

V

V

VTR

VTR

VTR

HS

HS

VTR

VTR

V

V V

321 4 4.7 5 6 7 8

A

A.4

B

C

D

A

A.4

B

C

D

C.3

C.6

7.2

+0'-0"

FIRST FLOOR

T/S 18'-2 1/2"

EXHAUST STACKS

EXHAUST STACKS

METAL PANEL

TO REMAIN (TYP)

STANDING SEAM MTL ROOF

T/S 29'-7"

T/S 18'-2 1/2"

T/S 29'-7"

FIRST FLOOR

+0'-0"

SECOND FLOOR

+11'-8"+11'-8"

SECOND FLOOR

4.78 7 6 5 4 2 13

FOUNDATION

CONCRETE

(TYP, UNO)

DOOR TO REMAIN

HOLLOW METAL DOUBLE DOOR.

NEW 2 - 4'-0" X 8'-0" INSULATED

FRAME TO BE REMOVED

EXISTING DOOR AND

REMAIN (TYP)

WINDOW TO

REMAIN (TYP)

GUTTER TO

TO REMAIN (TYP)

DOWNSPOUT

ON DWG SS551 (TYP FOR 2)

FLOOR BEAM; SEE SECTIONS A AND B

OF EXST FDN TO EXST SECOND

DOOR SUPPORT FRAMING FROM TOP

AND SEALANT FOR A WATERTIGHT CONSTRUCTION

PROVIDE INSULATED ROOF CURB CAP WITH FLASHING

EXISTING ROOF CURB TO REMAIN.

(SEE PLAN FOR LOCATIONS).

EXISTING EXHAUST STACKS TO BE REMOVED (TYP)

ROOF ARCHITECTURAL

DEMOLITION PLAN AND ELEVATION

DA151 0

ROOF ARCHITECTURAL DEMOLITION PLAN

INDICATES DEMOLITION LIMITS

N O

R

TH

DEMOLITION NOTES:

KEYNOTES:

CONSTRUCTION

TO DRAIN. SEE TYPICAL DETAIL ON THIS DRAWING.

CAP SHALL BE SECURED TO THE EXISTING ROOF CURB AND SLOPE

PROVIDE NEW FACTORY FINISH CURB CAP TO CLOSE THE OPENING. 2.

REMAIN.

REMOVE EXHAUST STACKS AND ACCESSORIES - ROOF CURB TO 1.

WITHIN THE DEMOLITION LIMIT -

FOR DEMOLITION NOTES SEE DRAWING DA150.

TO REMAIN

METAL ROOF SYSTEM

STANDING SEAM

CURB CAP DETAIL

TYPICAL EXHAUST STACK

NO SCALE

A-SS551

B-SS551

A-DA151

NORTH ELEVATION

A-DA151

DA151 MAY 31, 2019

D SARKAR

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

321 4 4.7 5 6 7 8

A.4

B

C

D

A

A.4

B

C

D

C.3

C.6

7 87.2

CD-2

LD-1

LD-1

LD-1

LD-1

LD-1

LD-1

LD-1

LD-1

CD-2

CD-2

CD-2

CD-2

CD-2

CD-2

CD-2

RG-6

22x22

22x22

RG-6

22x22

RG-6

22x22

RG-6

22x22

RG-6

22x22

RG-6

22x22

RG-6

22x22

RG-6

22x22

RG-6

22x22

RG-6

CD-2

CD-2

CD-2

T

CD-7

330 325

CD-7

CD-7CD-2

330440

CD-2

CD-2

12x12

EG-5

CD-2

EG-5

12x12

12x12

EG-5

EG-5

12x12

CD-2

CD-2

12x12

EG-5

12x12

EG-5

CD-3

16x16

EG-5

CD-3

12x12

EG-5

CD-4

RG-6

8x8

CD-4

12x12

EG-5

12x12

EG-5

12x12

EG-5

12x12

EG-5

16x16

EG-5

T

CD-2

x

LD-1

24x12 16x12

10x12

FRN-1

x

8x12

FRN-2

8x8 x

SG-8

8x4

CD-4

(SUSPENDED)

CD-4

CD-4

ELBOW W/SCREEN

ELBOW W/SCREEN620

CD-4

CD-4

16x16

EG-5

CD-4

22x22

EG-5

CD-3

CD-3

CD-4

12x12

EG-5

16x16

EG-5

CD-4

16x16

EG-5

22x22

EG-5

CD-3

CD-3

CD-2

CD-2

CD-7

CD-7

CD-2

12x12

EG-5

CD-2

EG-5

12x12

16x16

EG-5

CD-3

CD-3

OFFSET AROUND

BEAM

66x42x18d CANOPY

HOOD - 305 CFM

16x16

EG-5

16x16

EG-5

12x12

EG-5

12x12

EG-5

x1

6x6

SG-8

6x6

SG-8

36x12 w/OBD

5"CHWS UP

5"CHWR UP

4"HWR UP

4"HWS UP

1 1/2"

1 1/2"

C H

W S

W R

W S

W R

4" HWR

4" HWS

4" HWS

4" HWR

R L

R S

T T T T T

T

T

T

T

T

T T T T T

T

T

T

T

T

T T T

T

T

T

T

ANNUNICATOR PANEL

PIPE SUPPORT

20x6 EA.

UP & DN

DAMPERS INTERCONNECTED

TO HPB-1

3/4" HPR,

3/4" LPR UP

H P

R

L P

R

3/4"LPR UP

3/4"LPR

2" BSD VENT UP

D R

O P

W/OBD

W/OBD

W/OBD

FIRST FLOOR HVAC

DEMOLITION PLAN

DM150 0

JJ BOVENKAMP

1. REMOVE CEILING DIFFUSER, DUCT AND DUCT ACCESSORIES TO POINT

6” BELOW BOTTOM OF SECOND FLOOR SLAB. COVER OPENING WITH

1/2” X 1/2” WIRE MESH METAL.

2. REMOVE CEILING EXHAUST GRILL, DUCT AND DUCT ACCESSORIES TO

POINT 6” BELOW BOTTOM OF SECOND FLOOR SLAB. COVER OPENING

WITH 1/2” X 1/2” WIRE MESH METAL.

3. REMOVE FUME OR BSC EXHAUST DUCT AND ACCESSORIES TO POINT

6” BELOW BOTTOM OF SECOND FLOOR SLAB. COVER OPENING WITH

1/2” X 1/2” WIRE MESH METAL.

4. REMOVE TEMPERATURE AND PRESSURE CONTROLS TO HVAC PANELS

LOCATED IN SECOND FLOOR MECHANICAL ROOM. REMOVE

CONTROLLERS AND DEVICES NOT REQUIRED FOR NEW WORK AND

RETURN TO OWNER.

5. REMOVE UNIT HEATER AND CONTROL.

6. REMOVE DUCT AND FAN. BLANK OFF LOUVER OPENING WITH MINIMUM

1 1/2" INSULATED PANEL.

7. REMOVE CEILING DIFFUSER DUCT AND DUCT ACCESSORIES TO DUCT

CONNECTION TO MAIN DUCT.

8. REMOVE FUME HOOD OR BSC EXHAUST DUCT AND ACCESSORIES TO

DUCT CONNECTION TO MAIN DUCT. CAP CONNECTION TO MEET DUCT

SEALING REQUIREMENTS SPECIFIED.

DEMOLITION KEYNOTES:

FIRST FLOOR HVAC DEMOLITION PLAN

N O

R

TH

2 2

2 2

2 22222

3 3

44 4

LEGEND:

INDICATES DEMOLITION LIMITS

INDICATES DEMOLITION OF PIPES

MAY 31, 2019

KL GRAVES

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

A.4

B

C

D x

6x6 x

10x8

10x6 x

C O

O L

IN

G

C O

IL

C O

IL

C O

O L

IN

G

F

IL

T E

R

F

IL

T

44x18 x

M M x

M x x

M x

M

M x

26x18

M x x

M x

M M x

12x12

M x

M x x

M x

M

12x16 x x

M x1 x

M M x

18x16

M x

M x

12x16 x x x

M

C O

O L

IN

G

O

IL

C E

S S

H U

M

ID

IF

IE

R

H E

A T

IL

C E

S S

F

IL

T E

R S

E R

L

IL

C O

O L

IL

F

IL

T E

R S

E

IL

C E

S S

H E

A T

IL

C O

O L

IL

H U

M

ID

IF

IE

R

C E

S S

C O

O L

IL

72x18

72x54 OA

LOUVER

LOUVER

54x54 OA

54x18 6

18"

M

M

36x16

12x16 x x x

36x16 x

D R

O P

S

L O

P E

W

S T

R U

C T

U R

E

M x x

E

IL

M x x

24x20

F

IL

T E

R

18x36

AC. DR.

x

1 1/2" HPS DN

1" HPS1" HPS

1 1/2" LPS

S

1" LPS

1" LPS

(SUSPENDED)

(SUSPENDED)

(SUSPENDED)

THC1-12

5" CHWS

5" CHWR

4" HWS

4" HWR

4" CHWS

4" CHWR

4" HWR

4" HWS

3"

4"

C H

W S

C H

W R

2 1/2"

4"

C H

W R

C H

W S

2 1/2"

4" CHWR

4" CHWS

4" HWR

4" HWS

3"

2 1/2"

3"

2 1/2"2 1/2" 2 1/2"

1" 1"

1 1/2"

1"

1 1/2" 1 1/2"

1"

1 1/2"

1 1/2"

1"

1"1"

1"

1"

1"

S

R

4" HWS

4" HWR

4" CHWR

4" CHWS

16x12 24x16

24x16

RL

RS

RL

RS

4"HWS & HWR DN

5"CHWS & CHWR DN

1"

1"1"

1 1/2"

EXHAUST/VENT

TERMINATION

E

R L S

E

R L

R

3"ERL

3"ERLR

3"ERLS

24x16

24x16

3/4" HPR

1"LPS

EQUIP. END

OF MAIN

24x16

1"LPS

3/4" HPR

3/4" LPR

L P

R

3/4" LPR 3/4" LPR

3/4"HPR DN

3/4"LPR DN

END OF

MAIN

1"LPS

1"LPS

M

M

AUTO DAMPER

32x32 EA

D R O P

D R O

PD

R O P

R

IS

E

S

L O

S T

R U

C T

U R

E

FOB

ET-2

THRU ROOF,

2"BDS VENT UP

(SUSPENDED) (SUSPENDED)

SG-8

24x16 w/OBD

SG-8

24x16 w/OBD

SG-8

24x16 w/OBD

1" HPS DN

TO AUTOCLAVE

60x84

E

IL

60x84

(SUSPENDED)

24x12

VD

30x20

AC. DR.

18x36

48x20

END OF MAIN

FROM EQUIP.

3/4"LPR DN

M

M

M

ROOF.

ROOF.

4"

SECOND FLOOR HVAC

DEMOLITION PLAN

DM151 0

DEMOLITION KEYNOTES:

1. REMOVE FILTER HOUSING AND DUCT TRANSITIONS UPSTREAM AND

DOWN STREAM OF EACH FILTER HOUSING.

2. REMOVE HEAT RECOVERY COIL FROM EXISTING HOUSING. BLANK OFF

ALL OPENINGS IN HOUSING PANELS WITH MINIMUM 24 GAGE

GALVANIZED STEEL SCREWED TO HOUSING. SEAL WITH DUCT

SEALANT TO PREVENT AIR LEAKS.

3. REMOVE EXISTING UNIT, COILS, FANS ETC., CAP PIPING SERVING

COILS.

4. REMOVE HEAT RECOVERY PIPING, PUMPS AND ACCESSORIES

(VALVES, CHEMICAL POT FEEDER, EXPANSION TANK, ETC.).

5. REMOVE EXHAUST DUCT FROM FAN DISCHARGE TO TERMINATION

ABOVE ROOF.

6. SEE ARCHITECTURAL DRAWINGS FOR CLOSURE OF EXISTING ROOF

OPENING.

7. REMOVE AUXILIARY SUPPLY FAN AND BLANK OFF DUCT OPENINGS IN

UNIT AND SUPPLY AIR DUCTWORK. OPENINGS SHALL BE SEALED WITH

MINIMUM 24 GAGE SHEET METAL SCREWED TO DUCT OR UNIT PANEL.

SEAL WITH DUCT SEALANT.

8. REMOVE EXHAUST AIR ACTUATOR AND RETURN TO OWNER. LOCK

DAMPER IN FULL OPEN POSITION.

9. REMOVE DUCT TO POINT SHOWN. REMOVE TRANSITION AND CAP

DUCT.

10. REMOVE EXHAUST DUCT, EF-3 AND EF-4 . REMOVE EXHAUST STACK

FROM FAN DISCHARGE TO TERMINATION ABOVE ROOF.

11. REMOVE EXISTING CONTROLLERS AND CONTROL DEVICES NOT

REQUIRED FOR NEW WORK AND RETURN TO OWNER.

12. REMOVE EXISTING CONTROL PANELS AND ENCLOSURES NOT

REQUIRED FOR NEW WORK AND RETURN TO OWNER.

13. REMOVE DUCT TO LOUVER AND BLANK OFF WITH MINIMUM 3"

INSULATED METAL PANEL.

14. REMOVE DUCT TO EXTENT SHOWN AND CAP OPEN END.

15. REMOVE PIPING TO EXTENT SHOWN AND CAP OPEN END.

16. EXISTING EXHAUST FAN TO REMAIN.

SECOND FLOOR HVAC DEMOLITION PLAN

LEGEND:

INDICATES DEMOLITION LIMITS

4 12

5 6

5 62

11 12

PANELS

CONTROL

EXST HVAC

INDICATES DEMOLITION OF PIPES

N O

R

TH

8 8 8

5 6

MAY 31, 2019

KL GRAVES

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

A.4

A

A.4

B

C

D

C.3

C.6

7 87.2

FDB

M

SPRINKLER

ENTRANCE

ENTRANCE

2" WATER SERVICE

FDC

S1

FDDES

S2

RAD-1

WS

RO

FDC

FDB

FDB

FDB

DF1

FSB

SH

L1

FDA

FDA

L1

L1

MS

S3

WC1

WC1

SH

HWC

(TYP 2)

2"V UP

2"AV DN

2"V UP & DN

2"HLW DN AND 2"HLV UP

VENT UP & DN

4" MAIN STACK

S1

EE

EE

S1

EE

S1

EE

S1

EE

ES

3/4"CW UP

2"HV UP

2"HLW DN

3/4"HW UP

THRU FLOOR

TO 2" HLW DN

1 1/2"HLV DN

UP & DN

1 1/2"HLV

1/2"CW UP

1/2"HW UP

1/2"CW UP

1 1/2"V UP

1 1/2"W DN

1/2"HW UP

4" W DN

2"V UP & DN

2" CW UP

UP & DN

1 1/2"HLV

3/4"CW UP

2"AV UP

2"AW DN

3/4"HW UP

1/2" G UP

1/2"CW UP

1/2"HW UP

1/2"CW UP

1 1/4"V UP

1 1/4"W DN

1/2"HW UP

1/2"HW UP

1/2"CW UP

1/2"CW UP

2"V UP

1/2"HW UP

1/2"G UP

3/4"HW UP

1 1/2"AV UP

2"AW DN

3/4"CW UP

1/2"DW UP

1/2"CW UP

1/2"G UP

3/4"HW UP

1 1/2"AV UP

2"AW DN

3/4"CW UP

1/2"G UP

3/4"HW UP

1 1/2"AV UP

2"AW DN

3/4"CW UP

2"CW UP

1 1/4"W DN

1 1/4"V DN TO

1 1/4"W DN

1 1/2"V UP

1 1/2"V DN

EE

& DN

2"AV UP

SERVICE TO RO SYSTEM

1/2" BACKFLOW ASSY FOR

M

FDP SIAMESE

CONNECTION

FDB

ASSY

BACKFLOW

1 1/4"CW

WC2

UR1

FDB

FDB

S4

1 1/2"HLV DN

4"HLV UP & DN.

4"HLV DN

EE

S1

GTGT

S1

GT

EE

3/4"CW UP

3/4"HW UP

2"HV UP

2"HLW DN

S1

3/4"CW UP

2"HV UP

2"HLW DN

3/4"HW UP

EEEE

S1

GTGT

S1

3/4"CW UP

2"HV UP

2"HLW DN

3/4"HW UP

EE

GT

FDD

ES

S1

EE

GT

EE

S1

GT

2"HLV UP & DN

1 1/4" TW UP

FDE

CLEANOUT IN RISER

PROVIDE WALL

2"HLV UP & DN -

REQUIRED LATERAL BRACING

COORDINATE LOCATION WITH

PROVIDE WALL CLEANOUT -

FDE

FDE

1 1/2"V DN

2"V DN TO

4"W DN

OF ADJACENT LAV

RISER ABOVE FLOOD RIM

DN - CONNECT TO VENT

1 1/4"V DN TO 1 1/4"W

1 1/2"V DN

VENT RISER

CONNECT TO MAIN STACK

1 1/2"V DN TO 2"W DN -

GT

GT

GT

GT

GT

2"V DN (TYP 2)

2"V DN

(TYP 3)

2"

1 1/2"V UP

2"W DN AND

GWH-1A

GWH-1B

1 1/4"TW UP

2"V DN

SW

S W

CO

WH

HB

WH

HB

G G

G

ROUTE TIGHT

GAS SHUT-OFF VALVE

AND CHECK VALVE

(FOR BL3 LABS ONLY)

1" G UP

1/2" CO2 UP

1/2" CO2 UP

1/2" MG UP

40 FT3

A

3/4"A DN

1/2"G UP

IM

C O

C

O

S P

A

T

N K

S T

O R

A

C K

S

M G

N

H

1/2" CO2 UP

SEE 10/P2.1

1/2"

1/2"

1/2" CO2 UP

SEE 10/P2.1

1/2" CO2 UP

SEE 10/P2.1

30 FT3

30 FT3 30 FT3 30 FT3

1/2"1/2"

1/2"

G

1/2"

1/2" CO2 UP

SEE 10/P2.1

7 FT3

1/2"

1/2"1/2"

1/2" CO2 UP

7 FT3

1/2" CO2 UP

1/2" MG UP

C

1/2"G UP

2"CW UP

1 1/2"HW UP

3/4"HWC UP

3/4"A UP

2"G UP

3/4"A UP

1 1/4"CW UP

(FUT)

30 FT3

1/2"CW UP

1/2"HW UP

3/4"CW UP

HB

4"W DN

4"W UP

D

1"

1"D UP

4"W DN

& DN

4"V UP

2"V UP

4"W UP

2"

2"

1 1/4"

1 1/4"

2"

1 1/2"

2"

2"

2"

2"

3/4"

1 1/2"

1 1/2"

3/4"

3/4" 3/4"

3/4"

3/4"

3/4"

3/4"

1/2"

1 1/2"

3/4"

1 1/2"

2"

1"

3/4"

1/2"

1/2"

3/4"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

3/4"3/4"

1/2"

1" 1"

2"

H

N2

MG

3"

1"D UP

CO

FIRST FLOOR PLUMBING

DEMOLITION PLAN

DM152 0

DEMOLITION KEYNOTES:

FIRST FLOOR PLUMBING DEMOLITION PLAN

N O

R

TH

LEGEND:

INDICATES DEMOLITION LIMITS

INDICATES DEMOLITION OF PIPES

3 3

5 5

1 1

1 1 1

4 3

5 1

REMOVE VENT TO ABOVE SECOND FLOOR SLAB AND CAP.17.

OPERATION.

CONNECTION TO GAS SERVICE. EXISTING GAS SERVICE TO REMAIN IN

PIPING. SEAL BUILDING OPENING WHERE PIPES ARE REMOVED. CAP

REMOVE LPG TANK, VAPORIZER AND ASSOCIATED ABOVE GROUND 16.

CAP CLEANOUT FLUSH WITH FLOOR.15.

REMOVE VENT.14.

FROM FCU-2.

SEE NEW WORK DRAWINGS FOR NEW ROUTE OF CONDENSATE DRAIN

REMOVE VERTICAL DRAIN FROM FCU-2 TO EXISTING FLOOR DRAIN. 13.

SERVING EXISTING AUTOCLAVE.

REMOVE COMPRESSED AIR PIPE, FITTINGS AND ACCESSORIES 12.

ACCESSORIES SERVING EXISTING AUTOCLAVE.

REMOVE BACKFLOW PREVENTER, COLD WATER PIPE, FITTINGS, AND 11.

CLEANOUT ACCESS COVER.

PIPING TO FLOOR. CAP WITH CLEANOUT AND FLUSH WITH FLOOR

REMOVE DRAIN FROM COOLER UNIT. REMOVE FUNNEL, TRAP AND 10.

AND ACCESSORIES TO ABOVE SECOND FLOOR SLAB.

REMOVE AIR COMPRESSOR AND COMPRESSED AIR PIPE, FITTINGS 9.

REMOVE CYLINDERS AND PIPING FOR ALL GAS SYSTEMS.8.

AND FLUSH WITH FLOOR CLEANOUT ACCESS COVER.

REMOVE FLOOR DRAIN AND TRAP. CAP DRAIN PIPE WITH CLEANOUT 7.

IN SECOND FLOOR SLAB.

PIPE AND FITTINGS TO ABOVE SECOND FLOOR SLAB. SEAL OPENINGS

REMOVE SHOWER VALVE. REMOVE HOT WATER AND COLD WATER 6.

CLEANOUT ACCESS COVER. SEAL OPENINGS IN SECOND FLOOR SLAB.

SANITARY DRAIN AND CAP FLUSH WITH FLOOR WITH CLEANOUT AND

PIPES AND FITTINGS TO ABOVE SECOND FLOOR SLAB. REMOVE

REMOVE LAB SINK. REMOVE VENT, COLD WATER AND HOT WATER 5.

REMOVE MG PIPE, VALVES, FITTINGS OUTLETS AND ACCESSORIES.4.

ACCESSORIES.

REMOVE CARBON DIOXIDE PIPE, VALVES, FITTINGS, OUTLETS AND 3.

RETURN EYEWASH SHOWER AND MIXING VALVE TO OWNER.

WATER, HOT WATER PIPING, MIXING VALVE AND OTHER ACCESSORIES.

REMOVE EMERGENCY EYEWASH/SHOWER AND ASSOCIATED COLD 2.

REMOVE GAS PIPE, VALVES, FITTINGS, OUTLETS AND ACCESSORIES.1.

PROPANE TANK

VAPORIZER

M

2" LP GAS

ABOVE

BLOW-UP

SEE AREA

G

OF EXST VALVE

CAP DOWNSTREAM

MAY 31, 2019

KL GRAVES

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

A.4

B

C

D

2"CW DN

1 1/4"TW DN

TMV

1"

1 1/4"TW DN

TMV

4"HLV DN

4"V DN

2"HLV DN

1/2"HW DN

1/2"CW DN

HLV DN

1 1/2"

2"V DN

1/2"HW DN

1/2"CW DN

1/2"HW DN

1 1/4"V DN

1/2"CW DN

1/2"HW DN

2"V DN

1/2"CW DN

3/4"HW DN

3" VTR

1 1/2"AV DN

3/4"CW DN

1/2"G DN

2"AV DN

1/2"G DN

3/4"HW DN

1 1/2"AV DN

3/4"CW DN

3/4"HW DN

1 1/2"AV DN

3/4"CW DN

3/4"HW DN

1 1/2"AV DN

3/4"CW DN

REMOTE DF

CHILLER

1/2"DW DN

1/2"CW

1/2"CW DN

1 1/2"V DN

3/4"HW DN

1 1/2"AV DN

3/4"CW DN

1/2"HW DN

1 1/2"V DN

1/2"CW DN

1/2"HW DN

1/2"CW DN

1/2"HW DN

1/2"CW DN

3/4"A DN

1 1/4"CW DN

4"V UP

6" VTR

1"

3/4"CW DN

2"HLV DN

3/4"HW DN

3/4"CW DN

2"HLV DN

3/4"HW DN 2" HLV DN

3/4"CW DN

2"HLV DN

3/4"HW DN

3/4"CW DN

2"HLV DN

3/4"HW DN

HLV DN

1 1/2"

UP AND DN - 6" VTR

4" MAIN STACK VENT

2"

4" VTR

2"V UP & DN

3" AVTR

1 1/2"AV UP

1 1/2"V UP

3" VTR

4" AVTR

2"AV UP

4" VTR

2"V UP & DN

1"G DN

G

G G

G G

MG

MG

1"CO2 DN

3/4"MG DN

CO2

CO2

MG

MG

1/2"MG DN

MGMG

MG

1/2"MG DN

BL3 LABS

ISO VLV

BL2 LABS

ISO VLV

BL3 LABS

ISO VLV

ISO VLV

BL2 LABS

1/2"G DN

2"CW DN

1/2"G DN

1/2"CO2 DN

1/2"CO2 DN

C02

1/2"CO2 DN

CO2CO2

CO2

1/2"CO2 DN

1/2"CO2 DN

1/2"CO2 DN

1/2"CO2 DN

1/2"CO2 DN

CO2CO2

BALL VALVE (TYP)

BUBBLE TIGHT

2" 2"

2"

3/4"CW DN

2"HLV DN

3/4"HW DN

BALL VALVE (TYP)

BUBBLE TIGHT

2"HLV DN

2"

2"

2"

2"

1"

D

PLENUM

DRAIN

3/4"1 1/4"

1"3/4"

D

D

1"

1"1"

1"D DN -

SPILL OVER

MOP SINK

D

1"

2"V DN

36x20

24x24

36x36

1"

1"D DN

1"

FDB

FDB

2"V DN

1 1/4"

DRAIN

PLENUM

D

1 1/4"

1"

1 1/4"

3/4"

OF STEAM TRAP

3/4" DRAIN OFF

DD

1"

1 1/2"

1/2"

1/2"

3/4" 1"

1"1"1"

1"

1/2"

1/2" 3/4" 3/4" 1"

1"

1/4"/FT

F T

1"

1"

1 1/4"

2" 1"

1" 1" 1"

1 1/4" 2"

1/2"

1/2"

ROUTE PIPING AS

HIGH AS POSSIBLE

3/4"

1 1/4"

1/2"

1"

2" 1 1/4" 2" 1 1/4"

1/2"

1"

3/4"

1"

2"

2"

2.5 GPM

BALANCE TO

3/4"

1"

1" 1/2"

1"

1/2"

1/2"

2"

1 1/4"

2"

3/4"

1 1/4"

1/2"

3/4"

1 1/4"

3/4"

1/2"

1"

3/4"

1 1/2"

1 1/4"

1 1/4"

2"

3/4"

1/2"

1/2"

1"

3/4"

2"G DN

3/4"A DN

3/4"HWC DN

1 1/2"HW DN

2"CW DN

1/2"

1/2"

1"

1 1/4"3/4"

3/4"

1"

A

3/4"

A

1"

DRAIN PAN

RECOVERY COIL

DRAIN OFF OF

1"D DN

SECOND FLOOR PLUMBING

DEMOLITION PLAN

DM153 0

AS SHOWN.

REMOVE HOT WATER CIRCULATION PIPE, FITTINGS AND ACCESSORIES 7.

REMOVE HOT WATER PIPE, FITTINGS, AND ACCESSORIES AS SHOWN.6.

REMOVE COLD WATER PIPE, FITTINGS AND ACCESSORIES AS SHOWN.5.

MATERIAL AND DUCT SEALANT.

VALVE. REMOVE VALVES AND SEAL DUCT WITH SIMILAR DUCT

REMOVE HIGH LEVEL VENT LINE FROM FLOOR SLAB TO INLET OF 4.

SECOND FLOOR.

REMOVE MG PIPE, FITTINGS AND ACCESSORIES FROM ENTIRE 3.

ENTIRE SECOND FLOOR.

REMOVE CARBON DIOXIDE PIPE, FITTINGS, AND ACCESSORIES FROM 2.

VALVES TO REMAIN.

LOCATIONS SHOWN. PROVIDE THREADED CAP DOWNSTREAM OF

REMOVE GAS PIPE, FITTINGS, VALVES AND ACCESSORIES TO 1.

DEMOLITION KEYNOTES:

SECOND FLOOR PLUMBING DEMOLITION PLAN

LEGEND:

INDICATES DEMOLITION LIMITS

INDICATES DEMOLITION OF PIPES

654 65

5 6

4 5

5 6

44 2

8 2

N O

R

TH

ROOM

MECHANICAL

M02

MAY 31, 2019

KL GRAVES

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

316 315

315B

209 211

M01

307306305304

311 312

201 214

112111110

204B

205309

310 207

104 103

102 101

EQUIP ROOM

WATER

DNA ROOM TB ID ROOM BACTEC

SCOPE

ROOM

EQUIPMENT

ROOM

WALK-IN

COOLER

OUTGOING RECEIVING

VESTIBULE

EQUIPMENT

ROOM

PROCESSING

LAB

ELECTRICAL

MECHANICAL

STAIRS

BSL-2 CORRIDOR

WALK-IN

COOLER

AIRLOCK

LOBBY

BSL-3 CORRIDOR

TECH ROOM

STORAGE

BRUCELLA

ROOM

ESP ROOM

TB PROC

#3

TB PROC

#2

TB PROC

#1

CHANGING

ROOM SHOWER

LOCKER

HALLWAY

MOL

LAB 1

MOL

LAB 2

MOL

LAB 3

MOL

LAB 4

TANK

ROOM

RECEPTION

TECH

ROOMOFFICE OFFICE

SCOPE

RM

JANITOR

CHANGING

ROOM

SHOWER LOCKER

ELEC

DATA HALLWAY

VESTIBULE

OFFICEOFFICEOFFICEOFFICE

OFFICE

CLOSET

CONFERENCE/

BREAKROOM

A/V

CLOSET

PHENOL RM

321 4 4.7 5 6 7 8

A

A.4

B

C

D

A

A.4

B

C

D

C.3

FIRST FLOOR FIRE PROTECTION

DEMOLITION PLAN

DM154 0

AS NOTED

ML MARTZ

FIRST FLOOR FIRE PROTECTION DEMOLITION PLAN

INDICATES DEMOLITION LIMITS

ACCESSORIES.

REMOVE ALL SPRINKLER HEADS, PIPING AND ASSOCIATED 1.

N O

R

TH

EXISTING FIRE PROTECTION RISER DIAGRAM

FS

P

SCALE: 1/8"=1'-0"

NO SCALE

CONNECTION

DEPARTMENT

FIRE

BACKFLOW ASSEMBLY

DOUBLE CHECK

6"

MAIN DRAIN

TEE CONNECTION

FIRST FLOOR

DIAGRAM THIS DWG

TO BUILDING 401, SEE RISER

EXST 6" FIRE WATER SERVICE

DEMOLITION KEYNOTES:

MAY 31, 2019

KL GRAVES

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

A.4

B

SECOND FLOOR FIRE PROTECTION

DEMOLITION PLAN

DM155 0

SECOND FLOOR FIRE PROTECTION DEMOLITION PLAN

O

R

TH

LEGEND:

INDICATES DEMOLITION LIMITS

ACCESSORIES.

REMOVE ALL SPRINKLER HEADS, PIPING AND ASSOCIATED 1.

DEMOLITION NOTES:

ROOM

MECHANICAL

M02

MAY 31, 2019

KL GRAVES

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

316 315

315B

209 211

M01

307306305304

311 312

201 214

112111110

204B

205309

310 207

104 103

102 101

EQUIP ROOM

WATER

DNA ROOM TB ID ROOM BACTEC

SCOPE

ROOM

EQUIPMENT

ROOM

WALK-IN

COOLER

OUTGOING RECEIVING

VESTIBULE

EQUIPMENT

ROOM

PROCESSING

LAB

ELECTRICAL

MECHANICAL

STAIRS

BSL-2 CORRIDOR

WALK-IN

COOLER

AIRLOCK

LOBBY

BSL-3 CORRIDOR

TECH ROOM

STORAGE

BRUCELLA

ROOM

ESP ROOM

TB PROC

#3

TB PROC

#2

TB PROC

#1

CHANGING

ROOM SHOWER

LOCKER

HALLWAY

MOL

LAB 1

MOL

LAB 2

MOL

LAB 3

MOL

LAB 4

TANK

ROOM

RECEPTION

TECH

ROOMOFFICE OFFICE

SCOPE

RM

JANITOR

CHANGING

ROOM

SHOWER LOCKER

ELEC

DATA HALLWAY

VESTIBULE

OFFICEOFFICEOFFICEOFFICE

OFFICE

CLOSET

CONFERENCE/

BREAKROOM

A/V

CLOSET

PHENOL RM

321 4 4.7 5 6 7 8

A

A.4

B

C

D

A

A.4

B

C

D

C.3

FIRST FLOOR ELECTRICAL

DEMOLITION PLAN

DE150 0

JM DANIELSON

FIRST FLOOR ELECTRICAL DEMOLITION PLAN

1. SEE REFERENCE DRAWINGS FOR BUILDING 401 ELECTRICAL AS BUILT

PLANS SHOWING DETAILED PLACEMENT OF EXISTING ELECTRICAL

AND COMMUNICATIONS EQUIPMENT.

2. WITHIN THE DEMOLITION HASH LINES: DEMOLISH ALL LIGHT FIXTURES,

ELECTRICAL PANELS AND RECEPTACLES, FIRE ALARM, CONTROLS,

AND COMMUNICATION DEVICES. FOR CONDUIT AND WIRING

EXTENDING BEYOND THE DEMOLITION AREA, REMOVE CONDUIT TO

THE NEAREST JUNCTION BOX OR FITTING TO REMAIN, REMOVE

WIRING TO THE SOURCE OF SUPPLY, AND COVER OR FILL OPENING IN

BOXES OR FITTINGS. REMOVE EXPOSED ABANDONED CONDUIT.

3. EXISTING SECURITY DEVICES ON EXTERIOR DOORS, AND INTERIOR

DOORS THAT REMAIN IN PLACE AFTER DEMOLITION, SHALL REMAIN

INTACT AND FUNCTIONING. DEMOLISH SECURITY DEVICES, CONDUITS,

AND BOXES ONLY ON DOORS AND WALLS TO BE DEMOLISHED.

CONTRACTOR RESPONSIBLE FOR RE-ROUTING CONDUITS AND

RELOCATING JUNCTION BOXES AS REQUIRED TO MAINTAIN SECURITY

SYSTEM INTEGRITY. COORDINATE WITH SECURITY SYSTEM

INTEGRATOR.

4. SEE MECHANICAL AND PLUMBING DEMOLITION DRAWINGS. DEMOLISH

ASSOCIATED ELECTRICAL CONTROLS AND FEEDERS FOR MECHANICAL

EQUIPMENT GETTING DEMOLISHED AS DESCRIBED IN NOTE 2.

5. CONTRACTOR SHALL ENSURE THAT FIRE ALARM CIRCUITS FOR

DEVICES LOCATED IN THE MEZZANINE REMAIN IN SERVICE DURING

DEMOLITION OF FIRST FLOOR. IF DEVICES IN THE MEZZANINE ARE A

PART OF A FIRE ALARM CIRCUIT THAT IS TO BE DEMOLISHED ON THE

MAIN FLOOR, CONTRACTOR SHALL ROUTE NEW CONDUIT AND CIRCUIT

CABLING FROM DEVICES TO REMAIN BACK TO EXISTING FACP.

PROVIDE FIRE WATCH SERVICE IF REQUIRED.

DEMOLITION NOTES:

1. LIGHTING AND RECEPTACLES CURRENTLY FED FROM PANEL BL2.

FEED EXISTING LIGHTING FROM PANEL LA, CIRCUIT 22. FEED

EXISTING RECEPTACLES FROM PANEL LA, CIRCUIT 23. 2-#12, 1-#12G,

3/4"C TYPICAL. CONTRACTOR SHALL UPDATE PANEL SCHEDULE FOR

PANEL LA. SEE REFERENCE DRAWINGS.

2. LIGHTING AND RECEPTACLES CURRENTLY FED FROM PANEL BL3.

FEED EXISTING LIGHTING FROM PANEL LA, CIRCUIT 24. FEED

EXISTING RECEPTACLES FROM PANEL LA, CIRCUIT 25. 2-#12, 1-#12G,

3/4"C TYPICAL. CONTRACTOR SHALL UPDATE PANEL SCHEDULE FOR

PANEL LA. SEE REFERENCE DRAWINGS.

3. THERE ARE TWO EXISTING RECEPTACLES IN THIS AREA. LEAVE IN

PLACE. THESE RECEPTACLES WILL BE FED FROM A NEW PANEL LB.

SEE PANEL SCHEDULE AND DRAWING EP150.

4. REMOVE EXISTING EMERGENCY GENERATOR, ALL ASSOCIATED

UTILITY CONNECTIONS, AND ANY ANCILLARY EQUIPMENT COMPLETE.

REMOVE EXISTING EQUIPMENT PADS AND ASSOCIATED SUPPORTS.

THE FINISHED PRODUCT SHALL BE LEVEL WITH THE SURROUNDING

GRADE AND FINISH TO MATCH EXISTING. DEMOLISH AND REMOVE

PIPING BACK TO ACTIVE MAINS AND CAP. THE CONTRACTOR MAY

CHOOSE TO SALVAGE/SELL THIS EQUIPMENT AT THEIR OWN

DISCRETION, UPON DEMOLITION, THE EQUIPMENT MUST BE REMOVED

FROM THE SITE - IT CANNOT BE TEMPORARILY STORED ON-SITE.

5. DEMOLISH AUTOMATIC TRANSFER SWITCH AND CONCRETE PAD.

6. DEMOLISH CABLES IN DUCTBANK TO PANEL FDP.

7. DEMOLISH SECONDARY CABLES IN DUCTBANK TO PAD MOUNT

500KVA TRANSFORMER, APPROXIMATELY 80'.

DEMOLITION KEYNOTES:

N O

R

TH

LEGEND:

INDICATES DEMOLITION LIMITS

BL2 EQ2

PANEL "LA"

RACK

EXST COMM

EQ3BL3

GEN

ATS 7

FDP

MAY 31, 2019

NC VEEN

NC VEEN

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

EXISTING

HIGH VOLTAGE

SWITCHGEAR

PAD MTD XFMR

SECONDARY

PANEL PANEL PANEL

BL2

120/208V/3

M/B

PANEL

BL3

PANELPANEL

EQ3

EQ2

TVSS

EF-1AEF-1BEF-2EF-3EF-4AHU-2AHU-1

ABOVE GRADE

SPLICE CAB

TO ANIMAL BARNS

LA

120/208V/3

(OFFICE)

M/B

FDP

120/208V/3

M/B

60/3 C/B

DISC. SW.

CHLR-1

TX

BY ELECTRICAL CONTRACTOR

500 KVA

120/208V/3

VFD-1

208V/3

VFD-2

208V/3

MS-2 MS-1

VFD-4

208V/3

VFD-5

208V/3

VFD-3

208V/3

M2

120/208V/3

M/B

M1

120/208V/3

MLO

GEN

500KW

GENERATOR

ATS

ELECTRICAL DEMOLITION

ONE-LINE DIAGRAM AND PANELS

DE650 0

NONE

SPARES IN OFF POSITION. SEE DRAWING EO650.

BREAKER NUMBERS 4, 5,11 AND 12 IN PANEL FDP SHALL REMAIN AS 2.

THIS SCHEMATIC REPRESENTATION TO BE REMOVED.

DEMOLITION. THERE MAY BE ADDITIONAL EQUIPMENT NOT SHOWN ON

HASH LINES SHOW SCHEMATIC REPRESENTATION OF PANELS DURING 1.

DEMOLITION NOTES:

PANEL BL2 SCHEDULE

(SECTION A)

TYPE: 120/208 VOLTS, 3 PHASE, 4 WIRE LOCATION: BL2 CORRIDOR

MAIN BUS 225A MOUNTING: FLUSH

M/B FRAME 225A TRIPS 150 FEEDER: 4-#2/0 CU

A.I.C. 10,000 #6 GND

2" C

DESCRIPTION LOAD C/B NO NO C/B LOAD DESCRIPTION

LTS-MOL LAB 1,2,3 0.8 20-1 1 2 20-1 0.6 LTS-MOL LAB 4

LTS-PROCESS LAB 1.0 20-1 3 4 20-1 1.3 LTS-BL2 CORRIDOR

REC-BL2 CORRIDOR 0.4 20-1 5 6 20-1 1.0 ICE MACH #33

REC-MOL1 0.6 20-1 7 8 20-1 0. SPARE MOL1

REC-MOL1 0.6 20-1 9 10 20-1 0.8 MOL1 MICROWAVE #57

MOL1 WATER BATH #27 1.9 20-1 11 12 20-1 1.9 MOL1 WATER BATH #27

REC-MOL2 0.6 20-1 13 14 30-2 3.8 MOL2 TAQ MONITOR #17

REC-MOL2 0.6 20-1 15 16 -- -- 3-#10, #10 GND, WM

SPARE 0. 20-1 17 18 20-1 0. SPARE

REC-MOL3 0.6 20-1 19 20 20-2 0. SPARE MOL3

REC-MOL3 0.6 20-1 21 22 -- -- --

REC-MOL3 0.6 20-1 23 24 20-1 0.6 REC-MOL3

REC-MOL4 0.6 20-1 25 26 20-2 0. SPARE MOL4

REC-MOL4 0.6 20-1 27 28 -- -- --

MOL4 BSC2 #12 UPS-1 1.5 20-1 29 30 20-1 1.0 MOL4 HPLC #19

SPARE MOL4 0. 20-1 31 32 20-1 0. SPARE MOL4

REC-PL211 NORTH 0.4 20-1 33 34 30-2 4.4 PL211 CENTRIFUGE #29

PL211 ESP #4 1.5 20-1 35 36 -- -- 3-#10, #10 GND, WM

PL211 INCUBATOR #6 1.9 20-1 37 38 20-1 1.9 PL211 INCUBATOR #6

PL211 BSC2 #11 UPS-2 1.5 20-1 39 40 20-1 0.4 REC-PL211 SOUTH

REC-PL211 WEST 0.5 20-1 41 42 20-1 0.5 REC-PL211 WEST

TOTAL LOAD (KW) 16.8 18.2

NOTE: CIRCUITS SHALL BE ARRANGED AS SHOWN IN THIS SCHEDULE.

PANEL BL2 SCHEDULE

(SECTION B)

TYPE: 120/208 VOLTS, 3 PHASE, 4 WIRE LOCATION: BL2 CORRIDOR

MAIN BUS 225A MOUNTING: FLUSH

MAIN LUGS ONLY FEEDER: 4-#2/0 CU

A.I.C. 10,000 #6 GND

2" C

DESCRIPTION LOAD C/B NO NO C/B LOAD DESCRIPTION

REC-PL209 ISLAND 0.5 20-1 43 44 20-1 0.5 REC-PL209 ISLAND

SPARE PL209 0. 20-1 45 46 20-1 0. SPARE PL209

SPARE PL209 0. 20-1 47 48 20-1 0. SPARE PL209

REC-BL2 LOCKER RMS 1.0 20-1 49 50 20-1 0. SPARE

SPARE 0. 20-1 51 52 20-1 0. SPARE

SPARE 0. 20-1 53 54 20-1 0. SPARE

SPARE 0. 20-1 55 56 20-1 0. SPARE

SPARE 0. 20-1 57 58 20-1 0. SPARE

SPARE 0. 20-1 59 60 20-1 0. SPARE

SPACE 0. 20-1 61 62 20-1 0. SPACE

SPACE 0. 20-1 63 64 20-1 0. SPACE

SPACE 0. 20-1 65 66 20-1 0. SPACE

SPACE 0. 20-1 67 68 20-1 0. SPACE

SPACE 0. 20-1 69 70 20-1 0. SPACE

SPACE 0. 20-1 71 72 20-1 0. SPACE

SPACE 0. 20-1 73 74 20-1 0. SPACE

SPACE 0. 20-1 75 76 20-1 0. SPACE

SPACE 0. 20-1 77 78 20-1 0. SPACE

SPACE 0. 20-1 79 80 20-1 0. SPACE

SPACE 0. 20-1 81 82 20-1 0. SPACE

SPACE 0. 20-1 83 84 20-1 0. SPACE

TOTAL LOAD (KW) 1.5 .5

TOTAL PANEL LOAD (KW) 18.3 37.0 18.7

NOTE: CIRCUITS SHALL BE ARRANGED AS SHOWN IN THIS SCHEDULE.

PANEL EQ2 SCHEDULE

TYPE: 120/208 VOLTS, 3 PHASE, 4 WIRE LOCATION: BL2 CORRIDOR

MAIN BUS 100A MOUNTING: FLUSH

M/B FRAME 100A TRIPS 100A FEEDER: 4-#2 CU

A.I.C. 10,000 #8 GND

1-1/2" C

DESCRIPTION LOAD C/B NO NO C/B LOAD DESCRIPTION

LTS-BL2 EQUIPMENT RM 0.4 20-1 1 2 20-1 0. SPARE

REC-BL2 EQUIPMENT RM 0.2 20-1 3 4 20-1 0.8 BL2 WALK-IN COOLER

SPARE 0. 20-1 5 6 20-1 0. SPARE

BL2 -80 FREEZER #9 2.0 20-1 7 8 20-1 2.0 BL2 -80 FREEZER #9

BL2 -80 FREEZER #9 2.0 20-1 9 10 20-2 2.0 BL2 -80 FREEZER #64

BL2 -20 FREEZER #20 2.0 20-1 11 12 -- -- 2-#12, #12 GND, 3/4"

SPARE FUTURE 0. 20-1 13 14 20-1 0. SPARE FUTURE

BL2 -80 FREEZER #54 2.6 20-2 15 16 20-2 0. SPARE FUTURE

2-#12, #12 GND, 3/4" -- -- 17 18 -- -- --

BL2 WALK-IN COOLER 3.0 20-3 19 20 20-1 0. SPARE

208V/3, 3 HP MAX -- -- 21 22 20-1 0. SPARE

3-#12, #12 GND, 3/4" -- -- 23 24 20-1 0. SPARE

SPACE 0. 20-1 25 26 20-1 0. SPACE

SPACE 0. 20-1 27 28 20-1 0. SPACE

SPACE 0. 20-1 29 30 20-1 0. SPACE

TOTAL LOAD (KW) 12.2 17.0 4.8

NOTE: CIRCUITS SHALL BE ARRANGED AS SHOWN IN THIS SCHEDULE.

PANEL BL3 SCHEDULE

(SECTION A)

TYPE: 120/208 VOLTS, 3 PHASE, 4 WIRE LOCATION: BL2 CORRIDOR

MAIN BUS 225A MOUNTING: FLUSH

M/B FRAME 225A TRIPS 225A FEEDER: 4-#4/0 CU

A.I.C. 10,000 #4 GND

2-1/2" C

DESCRIPTION LOAD C/B NO NO C/B LOAD DESCRIPTION

LTS-BL3 BRUCELLA CORR 1.2 20-1 1 2 20-1 1.1 LTS-BL3 LAB 304 305

LTS-BL3 LAB 306 307 1.1 20-1 3 4 20-1 0.9 LTS-BL3 LAB 317 318

LTS-BL3 LAB 315 316 1.1 20-1 5 6 20-1 1.1 LTS-BL3 RECEIVING

REC-ESP 304 0.6 20-1 7 8 20-1 1.2 ESP 304 MGIT #52

REC-ESP 304 0.6 20-1 9 10 20-1 1.5 ESP 304 INCUBATOR #7

REC-ESP 304 MACH #4 1.5 20-1 11 12 20-1 0. SPARE ESP 304

REC-TB305 0.6 20-1 13 14 30-2 4.4 TB305 CENTRIFUGE #29

REC-TB305 0.6 20-1 15 16 -- -- 3-#10, #10 GND, WM

TB305 BSC3 #18 UPS-3 1.5 20-1 17 18 20-1 1.5 TB305 BSC2 #11 UPS-4

TB305 INCUBATOR #13 1.2 20-1 19 20 20-1 0. SPARE TB305

REC-TB306 0.6 20-1 21 22 30-2 4.8 TB306 CENTRIFUGE #2

REC-TB306 0.6 20-1 23 24 -- -- 3-#10, #10 GND, WM

TB306 BSC3 #18 UPS-5 1.5 20-1 25 26 20-1 1.5 TB306 BSC2 #11 UPS-6

TB306 INCUBATOR #13 1.2 20-1 27 28 20-1 0. SPARE TB306

REC-TB307 0.6 20-1 29 30 30-2 4.8 TB307 CENTRIFUGE #2

REC-TB307 0.6 20-1 31 32 -- -- 3-#10, #10 GND, WM

TB307 BSC3 #18 UPS-7 1.5 20-1 33 34 20-1 1.5 TB307 BSC2 #11 UPS-8

TB307 INCUBATOR #13 1.2 20-1 35 36 20-1 0. SPARE TB307

REC-BACTEC 315 0.6 20-1 37 38 30-2 0. SPARE BACTEC 315

REC-BACTEC 315 0.6 20-1 39 40 -- -- --

BACTEC 315 INCUBATOR #7 1.5 20-1 41 42 20-1 1.5 315 BSC3 #18 UPS-9

TOTAL LOAD (KW) 20.5 25.8

NOTE: CIRCUITS SHALL BE ARRANGED AS SHOWN IN THIS SCHEDULE.

PANEL BL3 SCHEDULE

(SECTION B)

TYPE: 120/208 VOLTS, 3 PHASE, 4 WIRE LOCATION: BL2 CORRIDOR

MAIN BUS 225A MOUNTING: FLUSH

MAIN LUGS ONLY FEEDER: 4-#4/0 CU

A.I.C. 10,000 #4 GND

2-1/2" C

DESCRIPTION LOAD C/B NO NO C/B LOAD DESCRIPTION

SPARE BACTEC 315 0. 20-1 43 44 20-1 0. SPARE BACTEC 315

REC-TBID 316 0.6 20-1 45 46 20-1 0. SPARE TBID 316

REC-TBID 316 0.6 20-1 47 48 20-1 1.4 TBID 316 AUTOCLAVE 8

TBID 316 INCUBATOR #13 1.2 20-1 49 50 20-1 1.5 316 BSC3 #18 UPS-10

TBID 316 INCUBATOR #30 1.2 20-1 51 52 20-1 1.2 316 INCUBATOR #30

REC-DNA 317 0.6 20-1 53 54 30-2 4.8 DNA 317 CENTRIFUGE 2

REC-DNA 317 0.6 20-1 55 56 -- -- 3-#10, #10 GND WM

DNA 317 BSC3 #18 UPS-11 1.5 20-1 57 58 20-1 1.2 317 WATER BATH #21

317 WATER BATH #21 1.2 20-1 59 60 20-1 0. SPARE DNA 317

REC-TECH 318 0.6 20-1 61 62 20-1 0.6 REC-TECH 318

REC-TECH 318 0.6 20-1 63 64 20-1 0.2 REC-STORAGE 302 303

REC-CORRIDOR 0.2 20-1 65 66 20-1 0. SPARE

REC-BRUCELLA 301 0.6 20-1 67 68 20-1 1.8 301 WATER BATH #45

REC-BRUCELLA 301 0.6 20-1 69 70 20-1 1.1 301 WATER BATH #46

301 BSC2 #37 UPS-12 1.5 20-1 71 72 20-1 1.5 301 CENTRIFUGE #38

301 INCUBATOR #35 1.5 20-1 73 74 20-1 0.5 301 INCUBATOR #36

SPARE BRUCELLA 301 0. 20-1 75 76 20-1 0. SPARE BRUCELLA 301

SPARE 0. 20-1 77 78 20-1 0. SPARE

SPARE 0. 20-1 79 80 20-1 0. SPARE

SPARE 0. 20-1 81 82 20-1 0. SPARE

SPARE 0. 20-1 83 84 20-1 0. SPARE

TOTAL LOAD (KW) 13.1 15.8

TOTAL PANEL LOAD (KW) 33.6 75.2 41.6

NOTE: CIRCUITS SHALL BE ARRANGED AS SHOWN IN THIS SCHEDULE.

PANEL EQ3 SCHEDULE

TYPE: 120/208 VOLTS, 3 PHASE, 4 WIRE LOCATION: BL2 CORRIDOR

MAIN BUS 225A MOUNTING: FLUSH

M/B FRAME 225A TRIPS 150A FEEDER: 4-#2/0 CU

A.I.C. 10,000 #6 GND

2" C

DESCRIPTION LOAD C/B NO NO C/B LOAD DESCRIPTION

LTS-BL3 EQUIPMENT RM 0.3 20-1 1 2 20-1 0. SPARE

REC-BL3 EQUIPMENT RM 0.2 20-1 3 4 20-1 0.8 BL3 WALK-IN COOLER

AUTOCLAVE CONTROL 0.5 20-1 5 6 20-1 1.2 BP1 PUMP MS-14

BL3 -80 FREEZER #9 2.0 20-1 7 8 20-1 2.0 BL3 -80 FREEZER #9

BL3 -80 FREEZER #9 2.0 20-1 9 10 20-1 2.0 BL3 -80 FREEZER #9

BL3 -20 FREEZER #20 2.0 20-1 11 12 20-1 2.0 BL3 -20 FREEZER #20

BL3 -20 FREEZER #20 2.0 20-1 13 14 20-1 2.0 BL3 -20 FREEZER #20

BL3 -80 FREEZER #9 2.0 20-1 15 16 20-2 0. SPARE FUTURE

SPARE FUTURE 0. 20-1 17 18 -- -- --

BL3 WALK-IN COOLER 3.0 20-3 19 20 20-1 0.4 REC-RECEIVING

208V/3, 3 HP MAX -- -- 21 22 20-1 0.4 REC-RECEIVE/OUTGOING

3-#12, #12 GND, 3/4" -- -- 23 24 20-1 0. SPARE

SPARE 0. 20-1 25 26 20-1 0. SPARE

SPARE 0. 20-1 27 28 20-1 0. SPARE

SPARE 0. 20-1 29 30 20-1 0. SPARE

TOTAL LOAD (KW) 14.0 24.8 10.8

NOTE: CIRCUITS SHALL BE ARRANGED AS SHOWN IN THIS SCHEDULE.

ELECTRICAL ONE-LINE DIAGRAM DEMOLITION

LEGEND:

INDICATES DEMOLITION LIMITS

ELECTRICAL PANELS DEMOLITION

MAY 31, 2019

NC VEEN

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

213A

200A

204B

206A

108 109

110 111 112

100B 100A

101102103

310B

310A

213B

312A

312B

308D

206B

308E

M01

311 312

112111110

204B

205309

310 207

104 103

102 101

EQUIP ROOM

WATER

ELECTRICAL

MECHANICAL

STAIRS

CHANGING

ROOM SHOWER

LOCKER

HALLWAY

RECEPTION

TECH

ROOMOFFICE OFFICE

SCOPE

RM

JANITOR

CHANGING

ROOM

SHOWER LOCKER

ELEC

DATA HALLWAY

VESTIBULE

OFFICEOFFICEOFFICEOFFICE

OFFICE

CLOSET

CONFERENCE/

BREAKROOM

A/V

CLOSET

321 4 4.7 5 6 7 8

A

A.4

B

C

D

A

A.4

B

C

D

C.3

C.6

7 87.2

8'-4"30'-0" 22'-5"10'-0"20'-0"24'-3"24'-3"24'-3"

2'-0" 6'-4"

163'-6"

FIRST FLOOR ARCHITECTURAL

MODIFICATIONS PLAN

AE150 0

FIRST FLOOR ARCHITECTURAL MODIFICATIONS PLAN

S T O R A G E

THE EXISTING FLOOR SLAB.

WHEEL LOADS: NONE - FORK LIFT TRAFFIC IS NOT ALLOWED ON

BEARING PLATE AT MINIMUM SPACING OF 8'-4" EACH WAY.

CONCENTRATED POST LOAD: 1.85 KIP WITH 6" X 6" MINIMUM

UNIFORM LIVE LOAD: 500 PSF

MAXIMUM ALLOWABLE LIVE LOADS ON EXISTING FLOOR SLAB:6.

EXISTING PARTITION TO REMAIN.5.

CLEAN EXPOSED CEILING/DECK AND STRUCTURE TO RECEIVE PAINT.4.

SMOOTH SURFACE TO RECEIVE PAINT.

WALLS SHALL BE PATCHED, REPAIRED AND CLEANED FOR A 3.

NEW 2 - 4'-0" X 8'-0" INSULATED HOLLOW METAL DOUBLE DOOR.2.

COATING.

WITH A SMOOTH LEVEL FINISH AND SEALED WITH AN EPOXY

EXPOSED CONCRETE FLOOR SHALL BE PATCHED AND REPAIRED 1.

3 4

N O

R

TH

MAY 31, 2019

D SARKAR

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

MISCELLANEOUS

STRUCTURAL DETAILS

SS551 0

AL BICKFORD

NJ PIERSON

AL BICKFORD

SECTION

B-SS551

SCALE:3"=1'-0"

DA151

PL1/4"X3"X8 1/2"

WELDED TO C6 AT TOP

L3X3X1/4 X 4 1/4" LG

DOOR SUPPORT FRAMING

C6X8.2

EXST 2ND FLR BEAM

(3) 1/2" DIA A325 BOLTS

/2

DOOR SUPPORT FRAMING

C6X8.2

ADHESIVE ANCHORS

(2) 1/2" DIA

AT BOTTOM

WELDED TO C6

L3X3X1/4 X 4 1/4" LG

EXST FDN WALL

SECTION

A-SS551

SCALE:3"=1'-0"

DA151

3 SIDES

MAY 31, 2019

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

M01

311 312

112111110

204B

205309

310 207

104 103

102 101

EQUIP ROOM

WATER

ELECTRICAL

MECHANICAL

STAIRS

CHANGING

ROOM SHOWER

LOCKER

HALLWAY

RECEPTION

TECH

ROOMOFFICE OFFICE

SCOPE

RM

JANITOR

CHANGING

ROOM

SHOWER LOCKER

ELEC

DATA HALLWAY

VESTIBULE

OFFICEOFFICEOFFICEOFFICE

OFFICE

CLOSET

CONFERENCE/

BREAKROOM

A/V

CLOSET

321 4 4.7 5 6 7 8

A

A.4

B

C

D

A

A.4

B

C

D

C.3

C.6

7 87.2

CD-2

LD-1

LD-1

LD-1

LD-1

LD-1

LD-1

LD-1

LD-1

CD-2

CD-2

CD-2

CD-2

CD-2

CD-2

CD-2

RG-6

22x22

22x22

RG-6

22x22

RG-6

22x22

RG-6

22x22

RG-6

22x22

RG-6

22x22

RG-6

22x22

RG-6

22x22

RG-6

22x22

RG-6

CD-2

CD-2

CD-2

T

12x12

EG-5

CD-2

EG-5

12x12

12x12

EG-5

EG-5

12x12

CD-2

CD-2

12x12

EG-5

RG-6

8x8

T

CD-2

x

LD-1

24x12 16x12

10x12

FRN-1

x

8x12

FRN-2

8x8 x

SG-8

8x4

(SUSPENDED)

ELBOW W/SCREEN

ELBOW W/SCREEN

CD-3

OFFSET AROUND

BEAM

x1

6x6

SG-8

6x6

SG-8

36x12 w/OBD

5"CHWS UP

5"CHWR UP

4"HWR UP

4"HWS UP

1 1/2"

1 1/2"

W S

W R

W S

W R

4" HWR

4" HWS

4" HWS

4" HWR

R L

R S

T

T

T

T

ANNUNICATOR PANEL

PIPE SUPPORT

20x6 EA.

UP & DN

DAMPERS INTERCONNECTED

TO HPB-1

D R

O P

W/OBD

W/OBD

W/OBD

T H

FIRST FLOOR HVAC PLAN

MH150 0

FIRST FLOOR HVAC PLAN

O

1. 95 CFM SUPPLY AIR

2. 75 CFM RETURN AIR

3. 65 CFM RETURN AIR

KEYNOTES:

2 2 2

2 2

1 1 1

1 1 1

S T O R A G E

MAY 31, 2019

KL GRAVES

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

A.4

B

C

D x

6x6 x

10x8

10x6 x

C O

O L

IN

G

C O

IL

C O

IL

C O

O L

IN

G

F

IL

T E

R

F

IL

T x

M M x

M x x

M x

M

M x

M x x

M x

M M x

M x x

M x

M

12x16 x x

M x1 x

M M x

18x16

M x

M x x x x

M

F

IL

T E

R S

C E

S S

H E

A T

IL

C O

O L

IL

H U

M

ID

IF

IE

R

C E

S S

C O

O L

IL

LOUVER

54x54 OA

54x18 6

18"

M

M

36x16 x x

36x16 x

D R

O P

S

L O

S T

R U

C T

U R

E

M x x

M x x

24x20 x

(SUSPENDED)

(SUSPENDED)

(SUSPENDED)

5" CHWS

5" CHWR

4" HWS

4" HWR

4" CHWS

4" CHWR

4" HWR

4" HWS

3"

4"

4" CHWR

4" CHWS

4" HWR

4" HWS

3"

2 1/2"

3"

2 1/2"2 1/2" 2 1/2"

1" 1"

1 1/2"

1"

1 1/2" 1 1/2"

1"

1 1/2"

1 1/2"

1"

1"1"

1"

1"

1"

4" HWS

4" HWR

4" CHWR

4" CHWS

16x12 24x16

24x16

RL

RS

RL

RS

4"HWS & HWR DN

5"CHWS & CHWR DN

1"

1"1"

1 1/2"

EXHAUST/VENT

TERMINATION

24x16

24x16

24x16

D R O P

D R O

PD

R O P

R

IS

E

S

L O

S T

R U

C T

U R

E

THRU ROOF,

2"BDS VENT UP

SG-8

24x16 w/OBD

SG-8

24x16 w/OBD

SG-8

24x16 w/OBD

(SUSPENDED)

24x12

VD

30x2048x20

M

M

M

SECOND FLOOR HVAC PLAN

MH151 0

SECOND FLOOR HVAC PLAN

O

BALANCE AHU TO 2,660 CFM. 4.

BALANCE FAN TO 2,230 CFM.

EXISTING EXHAUST FAN TO BE RE-BALANCED AS RETURN FAN. 3.

CONTROL SHOWN ON DRAWING MH750.

REPROGRAM EXISTING CONTROL PANEL TO PROVIDE SEQUENCE OF 2.

CONNECT DUCT TO EXISTING PLENUM OF AIR HANDLING UNIT.1.

KEYNOTES:36X16

X

36X16

18X16

WALL CAPEF-10

FOR CONTINUATION

SEE DWG MH150 FOR

3 EXST EXHAUST FAN

ROOM

MECHANICAL

M02

MAY 31, 2019

KL GRAVES

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

HVAC CONTROL SCHEMATICS

MH750 0

BK GROTHE

GENERAL REQUIREMENTS

1. HVAC SYSTEMS SHALL BE CONTROLLED BY UNIT MOUNTED STAND ALONE DIRECT DIGITAL CONTROLLER, UNLESS NOTED OTHERWISE. CONTROLLERS SHALL BE

INTEGRATED INTO BUILDING DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR REMOTE CONTROL AND MONITORING. DDC SYSTEM COMMUNICATION SHALL BE AS

SPECIFIED.

2. SET POINTS LABELED AS ADJUSTABLE SHALL BE FULLY ADJUSTABLE FROM OPERATOR WORKSTATIONS. SET POINTS FOR THERMOSTATS WITH INTEGRAL SET POINT

ADJUSTMENT SHALL BE ADJUSTABLE FROM BOTH THE THERMOSTAT AND THE OPERATOR WORKSTATION. SET POINT ADJUSTMENT SHALL NOT REQUIRE

PROGRAMMING OF DDC PANELS.

3. ALARM REPORTING SHALL BE DONE AT PANEL ASSOCIATED WITH EQUIPMENT AND SHALL BE AVAILABLE AT OPERATOR WORK STATIONS.

4. VENTILATION OUTDOOR AIR AND EXHAUST DAMPERS SHALL BE CAPABLE OF AUTOMATICALLY SHUTTING OFF DURING PREOCCUPANCY BUILDING WARM-UP, COOL

DOWN, AND SETBACK PERIODS.

NORMAL CONTROL POSITIONS

1. NORMAL POSITIONS OF CONTROLLED DEVICES SHALL BE POSITION DEVICE RETURNS TO ON POWER FAILURE OR CONTROLLER FAILURE. NORMAL POSITIONS SHALL

BE AS FOLLOWS:

A. OUTDOOR AIR DAMPER: CLOSED

B. EXHAUST AIR DAMPER: CLOSED

C. RETURN AIR DAMPER: OPEN

D. AUTOMATIC CONTROL VALVE (ACV) ON COOLING COILS: CLOSED TO COIL

E. AUTOMATIC CONTROL VALVE (ACV) ON HEATING COILS: OPEN TO COIL

SINGLE ZONE VARIABLE AIR VOLUME AIR-HANDLING UNIT (AHU-XX) CONTROL SEQUENCE

1. AHU SHALL BE CONTROLLED BY STAND ALONE DIRECT DIGITAL CONTROLLER.

2. SUPPLY AND EXHAUST FANS SHALL BE CONTROLLED BY OCCUPIED/UNOCCUPIED SCHEDULE FROM DDC SYSTEM.

3. WHEN AHU-XX IS SCHEDULED ON, SUPPLY FAN SHALL START AND RUN CONTINUOUSLY. SUPPLY FAN AIR FLOW SHALL BE CONTROLLED AS INDICATED BELOW.

OUTDOOR AIR DAMPER SHALL OPEN TO MINIMUM POSITION.

4. WHEN AHU-XX IS SCHEDULED ON, EXHAUST AIR DAMPER SHALL OPEN FULLY. AS DIFFERENTIAL BETWEEN SUPPLY AIRFLOW AND RETURN AIRFLOW INCREASES

ABOVE SET POINT (430 CFM, ADJUSTABLE) EXHAUST FAN VARIABLE FREQUENCY DRIVE SHALL MODULATE FAN SPEED TO MAINTAIN AIRFLOW DIFFERENTIAL AT SET

POINT.

5.

ADJUSTABLE). AS SPACE TEMPERATURE RISES ABOVE HEATING SET POINT, SUPPLY FAN VFD SHALL MODULATE SUPPLY FAN AIRFLOW TO MINIMUM AIRFLOW

(GREATER OF MINIMUM OUTDOOR AIR 430 CFM, ADJUSTABLE OR MINIMUM FAN SPEED). ON FURTHER RISE IN SPACE TEMPERATURE HEATING COIL DISCHARGE AIR

6.

TEMPERATURE RISES ABOVE COOLING SET POINT, OUTDOOR AIR AND RETURN AIR DAMPERS SHALL MODULATE TO MAINTAIN MIXED AIR TEMPERATURE AT COOLING

COIL DISCHARGE SET POINT (AS DETERMINED BELOW). AFTER OUTDOOR AIR DAMPER IS FULLY OPEN, ON FURTHER RISE IN SPACE TEMPERATURE WCC-XX ACV SHALL

ON FURTHER RISE IN SPACE TEMPERATURE SUPPLY FAN VFD SHALL MODULATE AIRFLOW FROM MINIMUM SPEED TO MAXIMUM SUPPLY AIRFLOW TO MAINTAIN SPACE

7. OPTIMUM START: UNIT SHALL BE CAPABLE OF STARTING PRIOR TO SCHEDULED OCCUPANCY BASED ON THE CALCULATED TIME NECESSARY FOR ZONES TO REACH

OCCUPIED SET POINT TEMPERATURE. WHEN BELOW HEATING SET POINT, OUTSIDE AIR DAMPER SHALL REMAIN CLOSED AND RETURN AIR DAMPER OPEN DURING

OPTIMAL START PERIOD. WHEN ABOVE COOLING SET POINT OUTDOOR AIR DAMPER SHALL REMAIN CLOSED AND RETURN DAMPER OPEN UNLESS ECONOMIZER

CONTROL INDICATED ABOVE IS ENABLED.

8. WHEN SPACE RELATIVE HUMIDITY IS ABOVE SET POINT (55% ADJUSTABLE) SYSTEM SHALL OPERATE IN DEHUMIDIFICATION MODE AS FOLLOWS:

A. UNIT COOLING COIL DISCHARGE AIR TEMPERATURE SHALL BE RESET TO MINIMUM COOLING SET POINT. WCC-XX ACV SHALL MODULATE TO MAINTAIN COOLING

COIL DISCHARGE AIR TEMPERATURE AT SET POINT.

B. ON RISE IN SPACE RELATIVE HUMIDITY SUPPLY FAN VFD SHALL MODULATE FAN TO DESIGN AIRFLOW TO MAINTAIN SPACE RELATIVE HUMIDITY SET POINT.

C. ALL RHC-XX ACV SHALL MODULATE IN PARALLEL TO MAINTAIN SPACE TEMPERATURE AT COOLING SET POINT.

9. WHEN SYSTEM IS IN THE "UNOCCUPIED" MODE, SYSTEM SHALL OPERATE AS SPECIFIED ABOVE EXCEPT THE OUTDOOR AND EXHAUST DAMPERS SHALL REMAIN

CLOSED. FAN SHALL CYCLE BASED ON DEMAND FROM SPACE.

10. SAFETY SHUTDOWN: SAFETY SHUTDOWN CIRCUIT SHALL BE PROVIDED EXTERNAL TO SYSTEM CONTROLLER. CIRCUIT SHALL BE DIRECTLY CONNECTED TO

STARTERS OF MOTOR-POWERED EQUIPMENT AND SHALL FUNCTION REGARDLESS OF STATUS OF SYSTEM CONTROLLER. IN EVENT OF SYSTEM SHUTDOWN, DEVICES

SHALL RETURN TO NORMAL POSITION. CIRCUITS SHALL BE RESET MANUALLY. FOLLOWING SHALL COMPRISE SAFETY SHUT-DOWN CIRCUIT:

A. SPACE FIRE ALARM

B. SMOKE DETECTION IN SUPPLY AIR DUCT

C. TEMPERATURE ENTERING COOLING COIL FALLS BELOW 40°F (FREEZESTAT)

SCHEMATIC

SINGLE ZONE VARIABLE AIR VOLUME (VAV) AIR HANDLING UNIT (AHU) CONTROL

PLAN DESIGNATION POINT DESCRIPTION

POINT TYPE

NOTES

AO DO AI DI VP ALARMS

RHC-XX ACV REHEAT COIL-XX ACV X MODULATE ALL REHEAT COILS IN PARALLEL

OATEMP OUTDOOR AIR TEMPERATURE X

AHU-XX OA DAMP AHU-XX OUTDOOR AIR DAMPER X

AHU-XX OA FE AHU-XX OUTDOOR AIR FLOW X X ALARM WHEN +/- 10% FROM SETPOINT

AHU-XX OA FE SP AHU-XX OUTDOOR AIR FLOW SETPOINT X SET POINT AS SCHEDULED FOR MINIMUM OUTDOOR AIRFLOW (ADJUSTABLE)

AHU-XX OA FILTER DP

DIFFERENTIAL PRESSURE

AHU-XX FILTER OUTDOOR AIR

X X ALARM ABOVE 0.9 IN W.G (225 PA) (ADJUSTABLE)

AHU-XX RA DAMP AHU-XX RETURN AIR DAMPER X

AHU-XX MAT AHU-XX MIXED AIR TEMPERATURE X

AHU-XX SA FILTER DP

DIFFERENTIAL PRESSURE

AHU-XX FILTER SUPPLY AIR

X X ALARM ABOVE 0.9 IN W.G (225 PA) (ADJUSTABLE)

AHU-XX HC-XX ACV

CONTROL VALVE

AHU-XX HEATING COIL AUTOMATIC

X

AHU-XX WCC-XX ACV

AUTOMATIC CONTROL VALVE

AHU-XX WATER COOLING COIL

X

AHU-XX SF STATUS AHU-XX SUPPLY FAN STATUS X X ALARM MISMATCH WITH AHU-XX SF S/S

AHU-XX SF S/S AHU-XX SUPPLY FAN START/STOP X

AHU-XX SF VFD AHU-XX SUPPLY FAN VFD X X COMMUNICATION VIA PROTOCOL AS SPECIFIED; ALARM WHEN VFD FAILS

AHU-XX DAT

TEMPERATURE

AHU-XX UNIT DISCHARGE AIR

X

AHU-XX DAT SP

SET POINT

AHU-XX DISCHARGE AIR TEMPERATURE

X (ADJUSTABLE)

AHU-XX SUPPLY DD AHU-XX SUPPLY DUCT DETECTOR X PROVIDE AUX CONTACT TO DDC SYSTEM

AHU-XX SA FE AHU-XX SUPPLY AIR FLOW X

AHU-XX SA FE SP AHU-XX SUPPLY AIR FLOW SET POINT X

AHU-XX SAP SP

POINT

AHU-XX DUCT STATIC PRESSURE SET

X

AHU-XX RA FE SP AHU-XX RETURN AIR FLOW SET POINT X

AHU-XX RAT AHU-XX RETURN AIR TEMPERATURE X

AHU-XX RAH AHU-XX RETURN AIR HUMIDITY X

AHU-XX RF STATUS AHU-XX EXHAUST FAN STATUS X X ALARM MISMATCH WITH AHU-XX EF S/S

AHU-XX RF S/S AHU-XX EXHAUST FAN START/STOP X

AHU-XX RF VFD AHU-XX EXHAUST FAN VFD X X COMMUNICATION VIA PROTOCOL AS SPECIFIED; ALARM WHEN VFD FAILS

AHU-XX EA DAMP AHU-XX EXHAUST AIR DAMPER X

AHU-XX FRZ AHU-XX FREEZESTAT X X

NOTE:

XXX REFERS TO ROOM NUMBER SHOWN ON SHEETS.3.

XX REFERS TO AHU DESIGNATIONS AS SCHEDULED.2.

BY DIVISION 28 3176.

PROVIDE BY FIRE ALARM INSTALLER AS REQUIRED 1.

SINGLE ZONE VARIABLE AIR VOLUME (VAV) AIR HANDLING UNIT (AHU) CONTROL SCHEMATIC

(HEATING WATER/CHILLED WATER COOLING) (EXISTING AHU IN BLDG 401)

M

OUTSIDE AIR

IT

M

D

VFD

FE

FE

SF VFD

AHU-XX.XX

T

RAT

AHU-XX.X

SEE NOTE 1

SUPPLY DD

AHU-XX.X

FE SA

AHU-XX.X

SF S/S

AHU-XX.XX

SF STATUS

AHU-X.XX

DAMP

OA

AHU-XX.X

FE OA

AHU-XX.X

P

SAP

AHU-XX.X

TI

ACV

WCC-X

W C

C -X

RETURN AIR

SUPPLY AIR

T

HCDAT

AHU-XX.X

H C -X

ACV

HC-X

T

STAT

FREEZE

AHU-XX.X

T OA TEMP

SHUTDOWN

HVAC EMERGENCY

FE

RA FE

AHU-XX.X

T

MAT

AHU-XX.X

M

EA DAMP

AHU-XX.X

RAH

AHU-XX.X

H

EXTENT OF AHU

T

CCDAT

AHU-XX.X

TI

M

DAMP

RA

AHU-XX.X

IT

M

VFD

RR VFD

AHU-XX.XX

RR S/S

AHU-XX.XX

RR STATUS

AHU-X.XX

T

SATSPH-XXX SATSPC-XXX

SAT-XXX

H SAH-XXX

OS OS-XXX

SEQUENCE OF OPERATION

R H

C -X

MAY 31, 2019

KL GRAVES

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

M01

311 312

112111110

204B

205309

310 207

104 103

102 101

EQUIP ROOM

WATER

ELECTRICAL

MECHANICAL

STAIRS

CHANGING

ROOM SHOWER

LOCKER

HALLWAY

RECEPTION

TECH

ROOMOFFICE OFFICE

SCOPE

RM

JANITOR

CHANGING

ROOM

SHOWER LOCKER

ELEC

DATA HALLWAY

VESTIBULE

OFFICEOFFICEOFFICEOFFICE

OFFICE

CLOSET

CONFERENCE/

BREAKROOM

A/V

CLOSET

321 4 4.7 5 6 7 8

A

A.4

B

C

D

A

A.4

B

C

D

C.3

FIRST FLOOR

FIRE PROTECTION PLAN

MF150 0

FIRST FLOOR FIRE PROTECTION PLAN

S T O R A G E

3 4

N O

R

TH

LEGEND:

LIGHT HAZARD

ORDINARY HAZARD GROUP 1

CLASS IV STORAGE

FIRE PROTECTION RISER MODIFICATIONS DIAGRAM

P

NO SCALE

CONNECTION

DEPARTMENT

EXST FIRE

BACKFLOW ASSEMBLY

EXST DOUBLE CHECK

6"

FIRST FLOOR

SCALE: 1/8"=1'-0"

FS

P

ALARM VALVE

MAIN DRAIN

FS

P

ALARM VALVE

MAIN DRAIN

TO OFFICE AREATO STORAGE AREA& PENTHOUSE

TO MECHANICAL ROOM

FS

P

ALARM VALVE

MAIN DRAIN

MAY 31, 2019

KL GRAVES

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

A.4

B

C

D

M02

MECHANICAL ROOM

M01

STAIRS

SECOND FLOOR

FIRE PROTECTION PLAN

MF151 0

SECOND FLOOR FIRE PROTECTION PLAN

O

SEE SHEET MF150 FOR PROTECTION IN THIS AREA.1.

LEGEND:

LIGHT HAZARD

ORDINARY HAZARD GROUP 1

MAY 31, 2019

KL GRAVES

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

ELECTRICAL ONE-LINE DIAGRAM

EO650 0

PARTIAL PANEL FDP ELECTRICAL ONE-LINE DIAGRAM

FOR ELECTRICAL LEGEND SEE DRAWING GG9.1.

NOTES:

MOUNT TRANSFORMER. SEE DRAWING EP150.

ROUTE IN EXISTING 4x4" DUCT BANK TO NEW HH-1 AND ON TO PAD 2.

KA36150 3P.

RE-USE DEMOLISHED SPACE FOR NEW 150A BREAKER. SQUARE D 1.

KEYNOTES:

700A 100A 150A 300A 300A 50A 100A

C H

IL

L E

R

T R

A

2 3 4 5 6 7 8 9 10 11 12 13 14

S P

A C

E

P A

N E

L L

A

S P

A R

E

S P

A R

E

S P

A C

E

S P

A R

E

S P

A R

E

S P

A C

E

P A

N E

L M

S P

A C

E

P A

N E

L M

T V

S S

LB

PANEL

/0

G

N D -1 /2 "C

208Y/120V

42 SPACE

100A MAIN

150A RATED BUS

PANEL FDP, 1600A, 1500AT, 208Y/120, 3PH, 4W

MOUNT TRANSFORMER

TO EXISTING PAD

LOCATION: ELECTRICAL ROOM 212

NUMBER (TYP)

SPACE

150A 225A 150A

#3/0 GND

(4) SETS 4-500KCMIL,

"LI"

INVERTER

LIGHTING

1KVA

MAY 31, 2019

NC VEEN

1 2

C A

D D D

-R

C

B

3 4 5

F

E

G

D

6 7 8 9

REV.

10 11

CHECKED

DESIGNED

APPROVED

APPROVED

DATE

DRAWN

SCALE:

NO.

A

DATENO. REVISIONS APVDCHKDDSGN

B

C

E

F

G

C STANLEY CONSULTANTS

www.stanleyconsultants.com

225 Iowa Avenue, Muscatine, Iowa 52761-3764

0 1 2 3

AT FULL SIZE

IN

cm0 1 2 3 4 5 6 7 8

USDA NATIONAL CENTERS FOR ANIMAL HEALTH

M01

311 312

112111110

204B

205309

310 207

104 103

102 101

EQUIP ROOM

WATER

ELECTRICAL

MECHANICAL

STAIRS

CHANGING

ROOM SHOWER

LOCKER

HALLWAY

RECEPTION

TECH

ROOMOFFICE OFFICE

SCOPE

RM

JANITOR

CHANGING

ROOM

SHOWER LOCKER

ELEC

DATA HALLWAY

VESTIBULE

OFFICEOFFICEOFFICEOFFICE

OFFICE

CLOSET

CONFERENCE/

BREAKROOM

A/V

CLOSET

321 4 4.7 5 6 7 8

A

A.4

B

C

D

A

A.4

B

C

D

C.3

C.6

F

SS

4 4

SS

30 STORAGE

6 6

15 17

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

FIRST FLOOR ELECTRICAL

POWER AND COMMUNICATION PLAN

EP150 0

FIRST FLOOR…