These drawings detail a demolition and modification plan for Building 401 at the USDA National Centers for Animal Health in Ames, Iowa, as part of a laboratory relocation project. The comprehensive set of architectural, mechanical, electrical, plumbing, and fire protection plans cover both first and second floor modifications, focusing on the Mycobacteriology Laboratory renovation. Key demolition activities include removing existing HVAC systems, electrical panels, fire protection infrastructure, plumbing fixtures, and interior architectural elements to prepare the space for reconfiguration.
The drawings specify technical details for systematic removal and replacement of building systems, including specifications for capping utilities, protecting remaining infrastructure, and preparing surfaces for new construction. Specific modifications include installing new doors, patching and repairing floor and wall surfaces, updating electrical panels and lighting circuits, modifying HVAC ductwork and controls, and reconfiguring fire protection systems. The plans are dated May 31, 2019, and were prepared by Stanley Consultants, indicating a detailed engineering approach to repurposing the laboratory facility while maintaining critical research infrastructure functionality.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B U I L D I N G 401
D
A
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
MYCOBACTERIOLOGY LABORATORY RELOCATION
AMES, IOWA
27100.10
316 315
315B
209 211
M01
307306305304
311 312
201 214
112111110
204B
205309
310 207
104 103
102 101
EQUIP ROOM
WATER
DNA ROOM TB ID ROOM BACTEC
SCOPE
ROOM
EQUIPMENT
ROOM
WALK-IN
COOLER
OUTGOING RECEIVING
VESTIBULE
EQUIPMENT
ROOM
PROCESSING
LAB
ELECTRICAL
MECHANICAL
STAIRS
BSL-2 CORRIDOR
WALK-IN
COOLER
AIRLOCK
LOBBY
BSL-3 CORRIDOR
TECH ROOM
STORAGE
BRUCELLA
ROOM
ESP ROOM
TB PROC
#3
TB PROC
#2
TB PROC
#1
CHANGING
ROOM SHOWER
LOCKER
HALLWAY
MOL
LAB 1
MOL
LAB 2
MOL
LAB 3
MOL
LAB 4
TANK
ROOM
RECEPTION
TECH
ROOMOFFICE OFFICE
SCOPE
RM
JANITOR
CHANGING
ROOM
SHOWER LOCKER
ELEC
DATA HALLWAY
VESTIBULE
OFFICEOFFICEOFFICEOFFICE
OFFICE
CLOSET
CONFERENCE/
BREAKROOM
A/V
CLOSET
PHENOL RM
321 4 4.7 5 6 7 8
A
A.4
B
C
D
A
A.4
B
C
D
C.3
C.6
7 87.2
BUILDING 401
FIRST FLOOR ARCHITECTURAL
DEMOLITION PLAN
DA150 0
1/8"=1'-0"
D SARKAR
KS HENNEMAN
FIRST FLOOR ARCHITECTURAL DEMOLITION PLAN
LEGEND:
INDICATES DEMOLITION LIMITS
W A
L L T
O R
E M
A
IN
1" DRAIN
CABINETS, FURNITURE, ETC.
DEMOLISH BUILT-IN COUNTERTOPS, BASE CABINETS, WALL 7.
DEMOLISH INTERIOR FINISHES (FLOORING, CEILING, ETC.)6.
DEMOLISH INTERIOR DOORS AND FRAMES SHOWN IN DASHED.5.
DEMOLISH INTERIOR PARTITIONS SHOWN IN DASHED, UNO.4.
EXISTING INTERIOR PARTITIONS TO REMAIN.3.
DOUBLE DOOR.
DEMOLISH EXTERIOR WALL AS REQUIRED FOR AN 2 - 4'-0" X 8'-0" 2.
DEMOLISH EXTERIOR DOOR AND FRAME.1.
WITHIN THE DEMOLITION LIMIT -
DEMOLITION KEYNOTES:
4 5 6 7
PROTECT SURROUNDING STRUCTURE.
AREA OF SPECIFIC ELEMENT AND ALL CAUTION SHOULD BE TAKEN TO
ALL DEMO WORK MUST BE SAFELY CONTAINED WITHIN THE IMMEDIATE 4.
BECAUSE ITEM WILL BE REUSED ON PROJECT.
"REMOVE AND SALVAGE" MEANS TO TAKE CAUTION WHEN REMOVING 3.
SPECIFICATIONS.
MATERIAL RESTORATION AND/OR REFURBISHMENT WITHIN THE
REPAIR PRACTICES AS WELL AS METHODS SPECIFICALLY STATED FOR
TO GENERALIZE SPECIFIED METHODS CONSISTENT WITH COMMON
THE TERM "REPAIR" WITHIN THE DEMO DOCUMENTS SHALL BE USED 2.
PROCEEDING WITH THE WORK IN THAT AREA.
CONTRACTING OFFICER IMMEDIATELY FOR DIRECTION, PRIOR TO
EXECUTION OF THE NEW WORK AS INDICATED, CONTACT THE
ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT
EXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF
THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUAL
DRAWINGS FURNISHED BY USDA OR GENERAL FIELD OBSERVATIONS.
INFORMATION IN THESE DRAWINGS ARE BASED, IN PART, ON EXISTING
EXISTING CONDITIONS. ILLUSTRATIONS, DIMENSIONS AND
DOCUMENTS AND ARE INTENDED TO REASONABLY REPRESENT
THE DEMOLITION DRAWINGS ARE DERIVED FROM EXISTING BUILDING 1.
DEMOLITION NOTES:
DOCUMENTS.
ACCORDANCE WITH THE MECHANICAL, ELECTRICAL, AND PLUMBING
THE PARTITIONS SHALL BE REMOVED, TERMINATED, CAPPED, IN
OTHERWISE. ALL UTILITIES WITHIN THE DEMOLISHED PORTIONS OF
FLOOR TO UNDERSIDE OF SUBSTRATE ABOVE UNLESS NOTED
DEMOLITION OF EXISTING PARTITIONS SHALL BE COMPLETE FROM 7.
NOTED OTHERWISE.
TO MEET A SPECIFIC FIRE RATING, SHALL REMAIN AS IS UNLESS
RECEIVE FURRING OR A SUSPENDED FINISH, AND ARE NOT DETAILED
AREAS WHERE THESE EXPOSED SURFACES ARE SCHEDULED TO
PATCHWORK WILL NOT BE NOTICEABLE ONCE NEW FINISH IS APPLIED.
DEPRESSIONS ARE LEVEL WITH ADJOINING SURFACES SO
SURFACES SUCH THAT ALL HOLES, CORES, VOIDS, AND OR
WHERE EXISTING CONSTRUCTION IS REMOVED; PATCH AND LEVEL 6.
CONTRACTING OFFICER FOR FURTHER DIRECTION.
STOP FURTHER DEMOLITION IN SPECIFIC AREA AND CONTACT
STRUCTURAL ELEMENT THAT HAS NOT BEEN IDENTIFIED AS SUCH,
INTEGRITY. IF ANY DEMOLITION DIRECTION APPEARS TO BE ON A
DEMOLITION OF WALLS SHALL BE INVESTIGATED FOR STRUCTURAL 5.
COORDINATED WITH CONTRACTING OFFICER OF USDA.
ADVERSELY AFFECT ANY REMAINING OCCUPANTS SHALL BE
ALL WORK TO CONTROL NOISE, DUST, AND HAZARDS AS TO NOT 11.
WALLS AND CEILINGS DAMAGED AS PART OF THE DEMOLITION WORK.
CONTRACTOR SHALL REPAIR OR REPLACE IN KIND PORTIONS OF 10.
PLACE SHALL BE PROTECTED FROM DAMAGE.
ALL BUILDING COMPONENTS AND FINISHES THAT ARE TO REMAIN IN 9.
SUBCONTRACTOR.
IS COMPLETE PRIOR TO TURN OVER TO NEXT SCHEDULED
COORDINATE THE DEMOLITION WITH NEW WORK SO THAT DEMOLITION
THE CONTRACTOR SHALL VERIFY ACTUAL CONDITIONS AND
MAY NOT BE COMPLETE IN THE IDENTIFICATION OF ALL REMOVALS.
THE DEMOLITION KEYNOTES IDENTIFY SPECIFIC AREAS OF WORK BUT 8.
CONSTRUCTION.
RELOCATION OF FURNITURE AND EQUIPMENT PRIOR TO BEGINNING
COORDINATE WITH CONTRACTING OFFICER OF USDA FOR THE 14.
OFFICER OF USDA.
COORDINATION MUST BE MADE WITH OCCUPANTS VIA CONTRACTING 13.
ALL EDGE CONDITIONS AND SHEET METAL FABRICATIONS.
DISCOVERIES. THE WORK PLAN SHALL INCLUDE SHOP DRAWINGS FOR
PLAN BASED ON THE CONTRACT DOCUMENTS AS MODIFIED BY
SPECIALIST SHALL PREPARE, FOR APPROVAL, A WORK CONTROL
BE REINSTALLED OR TEMPORARILY WATERPROOFED. THE QUALITY
AS REQUIRED TO FULLY UNDERSTAND THE WORK. REMOVALS SHALL
EXPLORATORY INVESTIGATIONS AND SHALL REMOVE COMPONENTS
PRIOR TO PERFORMING THE WORK THE CONTRACTOR SHALL MAKE 12.
N O
R
TH
MAY 31, 2019
D SARKAR
CM CHAMBERLIN
RJ LUKKARINEN
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
SYSTEM TO REMAIN (TYP)
STANDING SEAM METAL ROOF
REMAIN (TYP)
GUTTER TO TO REMAIN (TYP)
DOWNSPOUT
FLUEVTR
V
V
VTR
VTR
VTR
HS
HS
VTR
VTR
V
V V
321 4 4.7 5 6 7 8
A
A.4
B
C
D
A
A.4
B
C
D
C.3
C.6
7.2
+0'-0"
FIRST FLOOR
T/S 18'-2 1/2"
EXHAUST STACKS
EXHAUST STACKS
METAL PANEL
TO REMAIN (TYP)
STANDING SEAM MTL ROOF
T/S 29'-7"
T/S 18'-2 1/2"
T/S 29'-7"
FIRST FLOOR
+0'-0"
SECOND FLOOR
+11'-8"+11'-8"
SECOND FLOOR
4.78 7 6 5 4 2 13
FOUNDATION
CONCRETE
(TYP, UNO)
DOOR TO REMAIN
HOLLOW METAL DOUBLE DOOR.
NEW 2 - 4'-0" X 8'-0" INSULATED
FRAME TO BE REMOVED
EXISTING DOOR AND
REMAIN (TYP)
WINDOW TO
REMAIN (TYP)
GUTTER TO
TO REMAIN (TYP)
DOWNSPOUT
ON DWG SS551 (TYP FOR 2)
FLOOR BEAM; SEE SECTIONS A AND B
OF EXST FDN TO EXST SECOND
DOOR SUPPORT FRAMING FROM TOP
AND SEALANT FOR A WATERTIGHT CONSTRUCTION
PROVIDE INSULATED ROOF CURB CAP WITH FLASHING
EXISTING ROOF CURB TO REMAIN.
(SEE PLAN FOR LOCATIONS).
EXISTING EXHAUST STACKS TO BE REMOVED (TYP)
ROOF ARCHITECTURAL
DEMOLITION PLAN AND ELEVATION
DA151 0
ROOF ARCHITECTURAL DEMOLITION PLAN
INDICATES DEMOLITION LIMITS
N O
R
TH
DEMOLITION NOTES:
KEYNOTES:
CONSTRUCTION
TO DRAIN. SEE TYPICAL DETAIL ON THIS DRAWING.
CAP SHALL BE SECURED TO THE EXISTING ROOF CURB AND SLOPE
PROVIDE NEW FACTORY FINISH CURB CAP TO CLOSE THE OPENING. 2.
REMAIN.
REMOVE EXHAUST STACKS AND ACCESSORIES - ROOF CURB TO 1.
WITHIN THE DEMOLITION LIMIT -
FOR DEMOLITION NOTES SEE DRAWING DA150.
TO REMAIN
METAL ROOF SYSTEM
STANDING SEAM
CURB CAP DETAIL
TYPICAL EXHAUST STACK
NO SCALE
A-SS551
B-SS551
A-DA151
NORTH ELEVATION
A-DA151
DA151 MAY 31, 2019
D SARKAR
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
321 4 4.7 5 6 7 8
A.4
B
C
D
A
A.4
B
C
D
C.3
C.6
7 87.2
CD-2
LD-1
LD-1
LD-1
LD-1
LD-1
LD-1
LD-1
LD-1
CD-2
CD-2
CD-2
CD-2
CD-2
CD-2
CD-2
RG-6
22x22
22x22
RG-6
22x22
RG-6
22x22
RG-6
22x22
RG-6
22x22
RG-6
22x22
RG-6
22x22
RG-6
22x22
RG-6
22x22
RG-6
CD-2
CD-2
CD-2
T
CD-7
330 325
CD-7
CD-7CD-2
330440
CD-2
CD-2
12x12
EG-5
CD-2
EG-5
12x12
12x12
EG-5
EG-5
12x12
CD-2
CD-2
12x12
EG-5
12x12
EG-5
CD-3
16x16
EG-5
CD-3
12x12
EG-5
CD-4
RG-6
8x8
CD-4
12x12
EG-5
12x12
EG-5
12x12
EG-5
12x12
EG-5
16x16
EG-5
T
CD-2
x
LD-1
24x12 16x12
10x12
FRN-1
x
8x12
FRN-2
8x8 x
SG-8
8x4
CD-4
(SUSPENDED)
CD-4
CD-4
ELBOW W/SCREEN
ELBOW W/SCREEN620
CD-4
CD-4
16x16
EG-5
CD-4
22x22
EG-5
CD-3
CD-3
CD-4
12x12
EG-5
16x16
EG-5
CD-4
16x16
EG-5
22x22
EG-5
CD-3
CD-3
CD-2
CD-2
CD-7
CD-7
CD-2
12x12
EG-5
CD-2
EG-5
12x12
16x16
EG-5
CD-3
CD-3
OFFSET AROUND
BEAM
66x42x18d CANOPY
HOOD - 305 CFM
16x16
EG-5
16x16
EG-5
12x12
EG-5
12x12
EG-5
x1
6x6
SG-8
6x6
SG-8
36x12 w/OBD
5"CHWS UP
5"CHWR UP
4"HWR UP
4"HWS UP
1 1/2"
1 1/2"
C H
W S
W R
W S
W R
4" HWR
4" HWS
4" HWS
4" HWR
R L
R S
T T T T T
T
T
T
T
T
T T T T T
T
T
T
T
T
T T T
T
T
T
T
ANNUNICATOR PANEL
PIPE SUPPORT
20x6 EA.
UP & DN
DAMPERS INTERCONNECTED
TO HPB-1
3/4" HPR,
3/4" LPR UP
H P
R
L P
R
3/4"LPR UP
3/4"LPR
2" BSD VENT UP
D R
O P
W/OBD
W/OBD
W/OBD
FIRST FLOOR HVAC
DEMOLITION PLAN
DM150 0
JJ BOVENKAMP
1. REMOVE CEILING DIFFUSER, DUCT AND DUCT ACCESSORIES TO POINT
6” BELOW BOTTOM OF SECOND FLOOR SLAB. COVER OPENING WITH
1/2” X 1/2” WIRE MESH METAL.
2. REMOVE CEILING EXHAUST GRILL, DUCT AND DUCT ACCESSORIES TO
POINT 6” BELOW BOTTOM OF SECOND FLOOR SLAB. COVER OPENING
WITH 1/2” X 1/2” WIRE MESH METAL.
3. REMOVE FUME OR BSC EXHAUST DUCT AND ACCESSORIES TO POINT
6” BELOW BOTTOM OF SECOND FLOOR SLAB. COVER OPENING WITH
1/2” X 1/2” WIRE MESH METAL.
4. REMOVE TEMPERATURE AND PRESSURE CONTROLS TO HVAC PANELS
LOCATED IN SECOND FLOOR MECHANICAL ROOM. REMOVE
CONTROLLERS AND DEVICES NOT REQUIRED FOR NEW WORK AND
RETURN TO OWNER.
5. REMOVE UNIT HEATER AND CONTROL.
6. REMOVE DUCT AND FAN. BLANK OFF LOUVER OPENING WITH MINIMUM
1 1/2" INSULATED PANEL.
7. REMOVE CEILING DIFFUSER DUCT AND DUCT ACCESSORIES TO DUCT
CONNECTION TO MAIN DUCT.
8. REMOVE FUME HOOD OR BSC EXHAUST DUCT AND ACCESSORIES TO
DUCT CONNECTION TO MAIN DUCT. CAP CONNECTION TO MEET DUCT
SEALING REQUIREMENTS SPECIFIED.
DEMOLITION KEYNOTES:
FIRST FLOOR HVAC DEMOLITION PLAN
N O
R
TH
2 2
2 2
2 22222
3 3
44 4
LEGEND:
INDICATES DEMOLITION LIMITS
INDICATES DEMOLITION OF PIPES
MAY 31, 2019
KL GRAVES
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
A.4
B
C
D x
6x6 x
10x8
10x6 x
C O
O L
IN
G
C O
IL
C O
IL
C O
O L
IN
G
F
IL
T E
R
F
IL
T
44x18 x
M M x
M x x
M x
M
M x
26x18
M x x
M x
M M x
12x12
M x
M x x
M x
M
12x16 x x
M x1 x
M M x
18x16
M x
M x
12x16 x x x
M
C O
O L
IN
G
O
IL
C E
S S
H U
M
ID
IF
IE
R
H E
A T
IL
C E
S S
F
IL
T E
R S
E R
L
IL
C O
O L
IL
F
IL
T E
R S
E
IL
C E
S S
H E
A T
IL
C O
O L
IL
H U
M
ID
IF
IE
R
C E
S S
C O
O L
IL
72x18
72x54 OA
LOUVER
LOUVER
54x54 OA
54x18 6
18"
M
M
36x16
12x16 x x x
36x16 x
D R
O P
S
L O
P E
W
S T
R U
C T
U R
E
M x x
E
IL
M x x
24x20
F
IL
T E
R
18x36
AC. DR.
x
1 1/2" HPS DN
1" HPS1" HPS
1 1/2" LPS
S
1" LPS
1" LPS
(SUSPENDED)
(SUSPENDED)
(SUSPENDED)
THC1-12
5" CHWS
5" CHWR
4" HWS
4" HWR
4" CHWS
4" CHWR
4" HWR
4" HWS
3"
4"
C H
W S
C H
W R
2 1/2"
4"
C H
W R
C H
W S
2 1/2"
4" CHWR
4" CHWS
4" HWR
4" HWS
3"
2 1/2"
3"
2 1/2"2 1/2" 2 1/2"
1" 1"
1 1/2"
1"
1 1/2" 1 1/2"
1"
1 1/2"
1 1/2"
1"
1"1"
1"
1"
1"
S
R
4" HWS
4" HWR
4" CHWR
4" CHWS
16x12 24x16
24x16
RL
RS
RL
RS
4"HWS & HWR DN
5"CHWS & CHWR DN
1"
1"1"
1 1/2"
EXHAUST/VENT
TERMINATION
E
R L S
E
R L
R
3"ERL
3"ERLR
3"ERLS
24x16
24x16
3/4" HPR
1"LPS
EQUIP. END
OF MAIN
24x16
1"LPS
3/4" HPR
3/4" LPR
L P
R
3/4" LPR 3/4" LPR
3/4"HPR DN
3/4"LPR DN
END OF
MAIN
1"LPS
1"LPS
M
M
AUTO DAMPER
32x32 EA
D R O P
D R O
PD
R O P
R
IS
E
S
L O
S T
R U
C T
U R
E
FOB
ET-2
THRU ROOF,
2"BDS VENT UP
(SUSPENDED) (SUSPENDED)
SG-8
24x16 w/OBD
SG-8
24x16 w/OBD
SG-8
24x16 w/OBD
1" HPS DN
TO AUTOCLAVE
60x84
E
IL
60x84
(SUSPENDED)
24x12
VD
30x20
AC. DR.
18x36
48x20
END OF MAIN
FROM EQUIP.
3/4"LPR DN
M
M
M
ROOF.
ROOF.
4"
SECOND FLOOR HVAC
DEMOLITION PLAN
DM151 0
DEMOLITION KEYNOTES:
1. REMOVE FILTER HOUSING AND DUCT TRANSITIONS UPSTREAM AND
DOWN STREAM OF EACH FILTER HOUSING.
2. REMOVE HEAT RECOVERY COIL FROM EXISTING HOUSING. BLANK OFF
ALL OPENINGS IN HOUSING PANELS WITH MINIMUM 24 GAGE
GALVANIZED STEEL SCREWED TO HOUSING. SEAL WITH DUCT
SEALANT TO PREVENT AIR LEAKS.
3. REMOVE EXISTING UNIT, COILS, FANS ETC., CAP PIPING SERVING
COILS.
4. REMOVE HEAT RECOVERY PIPING, PUMPS AND ACCESSORIES
(VALVES, CHEMICAL POT FEEDER, EXPANSION TANK, ETC.).
5. REMOVE EXHAUST DUCT FROM FAN DISCHARGE TO TERMINATION
ABOVE ROOF.
6. SEE ARCHITECTURAL DRAWINGS FOR CLOSURE OF EXISTING ROOF
OPENING.
7. REMOVE AUXILIARY SUPPLY FAN AND BLANK OFF DUCT OPENINGS IN
UNIT AND SUPPLY AIR DUCTWORK. OPENINGS SHALL BE SEALED WITH
MINIMUM 24 GAGE SHEET METAL SCREWED TO DUCT OR UNIT PANEL.
SEAL WITH DUCT SEALANT.
8. REMOVE EXHAUST AIR ACTUATOR AND RETURN TO OWNER. LOCK
DAMPER IN FULL OPEN POSITION.
9. REMOVE DUCT TO POINT SHOWN. REMOVE TRANSITION AND CAP
DUCT.
10. REMOVE EXHAUST DUCT, EF-3 AND EF-4 . REMOVE EXHAUST STACK
FROM FAN DISCHARGE TO TERMINATION ABOVE ROOF.
11. REMOVE EXISTING CONTROLLERS AND CONTROL DEVICES NOT
REQUIRED FOR NEW WORK AND RETURN TO OWNER.
12. REMOVE EXISTING CONTROL PANELS AND ENCLOSURES NOT
REQUIRED FOR NEW WORK AND RETURN TO OWNER.
13. REMOVE DUCT TO LOUVER AND BLANK OFF WITH MINIMUM 3"
INSULATED METAL PANEL.
14. REMOVE DUCT TO EXTENT SHOWN AND CAP OPEN END.
15. REMOVE PIPING TO EXTENT SHOWN AND CAP OPEN END.
16. EXISTING EXHAUST FAN TO REMAIN.
SECOND FLOOR HVAC DEMOLITION PLAN
LEGEND:
INDICATES DEMOLITION LIMITS
4 12
5 6
5 62
11 12
PANELS
CONTROL
EXST HVAC
INDICATES DEMOLITION OF PIPES
N O
R
TH
8 8 8
5 6
MAY 31, 2019
KL GRAVES
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
A.4
A
A.4
B
C
D
C.3
C.6
7 87.2
FDB
M
SPRINKLER
ENTRANCE
ENTRANCE
2" WATER SERVICE
FDC
S1
FDDES
S2
RAD-1
WS
RO
FDC
FDB
FDB
FDB
DF1
FSB
SH
L1
FDA
FDA
L1
L1
MS
S3
WC1
WC1
SH
HWC
(TYP 2)
2"V UP
2"AV DN
2"V UP & DN
2"HLW DN AND 2"HLV UP
VENT UP & DN
4" MAIN STACK
S1
EE
EE
S1
EE
S1
EE
S1
EE
ES
3/4"CW UP
2"HV UP
2"HLW DN
3/4"HW UP
THRU FLOOR
TO 2" HLW DN
1 1/2"HLV DN
UP & DN
1 1/2"HLV
1/2"CW UP
1/2"HW UP
1/2"CW UP
1 1/2"V UP
1 1/2"W DN
1/2"HW UP
4" W DN
2"V UP & DN
2" CW UP
UP & DN
1 1/2"HLV
3/4"CW UP
2"AV UP
2"AW DN
3/4"HW UP
1/2" G UP
1/2"CW UP
1/2"HW UP
1/2"CW UP
1 1/4"V UP
1 1/4"W DN
1/2"HW UP
1/2"HW UP
1/2"CW UP
1/2"CW UP
2"V UP
1/2"HW UP
1/2"G UP
3/4"HW UP
1 1/2"AV UP
2"AW DN
3/4"CW UP
1/2"DW UP
1/2"CW UP
1/2"G UP
3/4"HW UP
1 1/2"AV UP
2"AW DN
3/4"CW UP
1/2"G UP
3/4"HW UP
1 1/2"AV UP
2"AW DN
3/4"CW UP
2"CW UP
1 1/4"W DN
1 1/4"V DN TO
1 1/4"W DN
1 1/2"V UP
1 1/2"V DN
EE
& DN
2"AV UP
SERVICE TO RO SYSTEM
1/2" BACKFLOW ASSY FOR
M
FDP SIAMESE
CONNECTION
FDB
ASSY
BACKFLOW
1 1/4"CW
WC2
UR1
FDB
FDB
S4
1 1/2"HLV DN
4"HLV UP & DN.
4"HLV DN
EE
S1
GTGT
S1
GT
EE
3/4"CW UP
3/4"HW UP
2"HV UP
2"HLW DN
S1
3/4"CW UP
2"HV UP
2"HLW DN
3/4"HW UP
EEEE
S1
GTGT
S1
3/4"CW UP
2"HV UP
2"HLW DN
3/4"HW UP
EE
GT
FDD
ES
S1
EE
GT
EE
S1
GT
2"HLV UP & DN
1 1/4" TW UP
FDE
CLEANOUT IN RISER
PROVIDE WALL
2"HLV UP & DN -
REQUIRED LATERAL BRACING
COORDINATE LOCATION WITH
PROVIDE WALL CLEANOUT -
FDE
FDE
1 1/2"V DN
2"V DN TO
4"W DN
OF ADJACENT LAV
RISER ABOVE FLOOD RIM
DN - CONNECT TO VENT
1 1/4"V DN TO 1 1/4"W
1 1/2"V DN
VENT RISER
CONNECT TO MAIN STACK
1 1/2"V DN TO 2"W DN -
GT
GT
GT
GT
GT
2"V DN (TYP 2)
2"V DN
(TYP 3)
2"
1 1/2"V UP
2"W DN AND
GWH-1A
GWH-1B
1 1/4"TW UP
2"V DN
SW
S W
CO
WH
HB
WH
HB
G G
G
ROUTE TIGHT
GAS SHUT-OFF VALVE
AND CHECK VALVE
(FOR BL3 LABS ONLY)
1" G UP
1/2" CO2 UP
1/2" CO2 UP
1/2" MG UP
40 FT3
A
3/4"A DN
1/2"G UP
IM
C O
C
O
S P
A
T
N K
S T
O R
A
C K
S
M G
N
H
1/2" CO2 UP
SEE 10/P2.1
1/2"
1/2"
1/2" CO2 UP
SEE 10/P2.1
1/2" CO2 UP
SEE 10/P2.1
30 FT3
30 FT3 30 FT3 30 FT3
1/2"1/2"
1/2"
G
1/2"
1/2" CO2 UP
SEE 10/P2.1
7 FT3
1/2"
1/2"1/2"
1/2" CO2 UP
7 FT3
1/2" CO2 UP
1/2" MG UP
C
1/2"G UP
2"CW UP
1 1/2"HW UP
3/4"HWC UP
3/4"A UP
2"G UP
3/4"A UP
1 1/4"CW UP
(FUT)
30 FT3
1/2"CW UP
1/2"HW UP
3/4"CW UP
HB
4"W DN
4"W UP
D
1"
1"D UP
4"W DN
& DN
4"V UP
2"V UP
4"W UP
2"
2"
1 1/4"
1 1/4"
2"
1 1/2"
2"
2"
2"
2"
3/4"
1 1/2"
1 1/2"
3/4"
3/4" 3/4"
3/4"
3/4"
3/4"
3/4"
1/2"
1 1/2"
3/4"
1 1/2"
2"
1"
3/4"
1/2"
1/2"
3/4"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
3/4"3/4"
1/2"
1" 1"
2"
H
N2
MG
3"
1"D UP
CO
FIRST FLOOR PLUMBING
DEMOLITION PLAN
DM152 0
DEMOLITION KEYNOTES:
FIRST FLOOR PLUMBING DEMOLITION PLAN
N O
R
TH
LEGEND:
INDICATES DEMOLITION LIMITS
INDICATES DEMOLITION OF PIPES
3 3
5 5
1 1
1 1 1
4 3
5 1
REMOVE VENT TO ABOVE SECOND FLOOR SLAB AND CAP.17.
OPERATION.
CONNECTION TO GAS SERVICE. EXISTING GAS SERVICE TO REMAIN IN
PIPING. SEAL BUILDING OPENING WHERE PIPES ARE REMOVED. CAP
REMOVE LPG TANK, VAPORIZER AND ASSOCIATED ABOVE GROUND 16.
CAP CLEANOUT FLUSH WITH FLOOR.15.
REMOVE VENT.14.
FROM FCU-2.
SEE NEW WORK DRAWINGS FOR NEW ROUTE OF CONDENSATE DRAIN
REMOVE VERTICAL DRAIN FROM FCU-2 TO EXISTING FLOOR DRAIN. 13.
SERVING EXISTING AUTOCLAVE.
REMOVE COMPRESSED AIR PIPE, FITTINGS AND ACCESSORIES 12.
ACCESSORIES SERVING EXISTING AUTOCLAVE.
REMOVE BACKFLOW PREVENTER, COLD WATER PIPE, FITTINGS, AND 11.
CLEANOUT ACCESS COVER.
PIPING TO FLOOR. CAP WITH CLEANOUT AND FLUSH WITH FLOOR
REMOVE DRAIN FROM COOLER UNIT. REMOVE FUNNEL, TRAP AND 10.
AND ACCESSORIES TO ABOVE SECOND FLOOR SLAB.
REMOVE AIR COMPRESSOR AND COMPRESSED AIR PIPE, FITTINGS 9.
REMOVE CYLINDERS AND PIPING FOR ALL GAS SYSTEMS.8.
AND FLUSH WITH FLOOR CLEANOUT ACCESS COVER.
REMOVE FLOOR DRAIN AND TRAP. CAP DRAIN PIPE WITH CLEANOUT 7.
IN SECOND FLOOR SLAB.
PIPE AND FITTINGS TO ABOVE SECOND FLOOR SLAB. SEAL OPENINGS
REMOVE SHOWER VALVE. REMOVE HOT WATER AND COLD WATER 6.
CLEANOUT ACCESS COVER. SEAL OPENINGS IN SECOND FLOOR SLAB.
SANITARY DRAIN AND CAP FLUSH WITH FLOOR WITH CLEANOUT AND
PIPES AND FITTINGS TO ABOVE SECOND FLOOR SLAB. REMOVE
REMOVE LAB SINK. REMOVE VENT, COLD WATER AND HOT WATER 5.
REMOVE MG PIPE, VALVES, FITTINGS OUTLETS AND ACCESSORIES.4.
ACCESSORIES.
REMOVE CARBON DIOXIDE PIPE, VALVES, FITTINGS, OUTLETS AND 3.
RETURN EYEWASH SHOWER AND MIXING VALVE TO OWNER.
WATER, HOT WATER PIPING, MIXING VALVE AND OTHER ACCESSORIES.
REMOVE EMERGENCY EYEWASH/SHOWER AND ASSOCIATED COLD 2.
REMOVE GAS PIPE, VALVES, FITTINGS, OUTLETS AND ACCESSORIES.1.
PROPANE TANK
VAPORIZER
M
2" LP GAS
ABOVE
BLOW-UP
SEE AREA
G
OF EXST VALVE
CAP DOWNSTREAM
MAY 31, 2019
KL GRAVES
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
A.4
B
C
D
2"CW DN
1 1/4"TW DN
TMV
1"
1 1/4"TW DN
TMV
4"HLV DN
4"V DN
2"HLV DN
1/2"HW DN
1/2"CW DN
HLV DN
1 1/2"
2"V DN
1/2"HW DN
1/2"CW DN
1/2"HW DN
1 1/4"V DN
1/2"CW DN
1/2"HW DN
2"V DN
1/2"CW DN
3/4"HW DN
3" VTR
1 1/2"AV DN
3/4"CW DN
1/2"G DN
2"AV DN
1/2"G DN
3/4"HW DN
1 1/2"AV DN
3/4"CW DN
3/4"HW DN
1 1/2"AV DN
3/4"CW DN
3/4"HW DN
1 1/2"AV DN
3/4"CW DN
REMOTE DF
CHILLER
1/2"DW DN
1/2"CW
1/2"CW DN
1 1/2"V DN
3/4"HW DN
1 1/2"AV DN
3/4"CW DN
1/2"HW DN
1 1/2"V DN
1/2"CW DN
1/2"HW DN
1/2"CW DN
1/2"HW DN
1/2"CW DN
3/4"A DN
1 1/4"CW DN
4"V UP
6" VTR
1"
3/4"CW DN
2"HLV DN
3/4"HW DN
3/4"CW DN
2"HLV DN
3/4"HW DN 2" HLV DN
3/4"CW DN
2"HLV DN
3/4"HW DN
3/4"CW DN
2"HLV DN
3/4"HW DN
HLV DN
1 1/2"
UP AND DN - 6" VTR
4" MAIN STACK VENT
2"
4" VTR
2"V UP & DN
3" AVTR
1 1/2"AV UP
1 1/2"V UP
3" VTR
4" AVTR
2"AV UP
4" VTR
2"V UP & DN
1"G DN
G
G G
G G
MG
MG
1"CO2 DN
3/4"MG DN
CO2
CO2
MG
MG
1/2"MG DN
MGMG
MG
1/2"MG DN
BL3 LABS
ISO VLV
BL2 LABS
ISO VLV
BL3 LABS
ISO VLV
ISO VLV
BL2 LABS
1/2"G DN
2"CW DN
1/2"G DN
1/2"CO2 DN
1/2"CO2 DN
C02
1/2"CO2 DN
CO2CO2
CO2
1/2"CO2 DN
1/2"CO2 DN
1/2"CO2 DN
1/2"CO2 DN
1/2"CO2 DN
CO2CO2
BALL VALVE (TYP)
BUBBLE TIGHT
2" 2"
2"
3/4"CW DN
2"HLV DN
3/4"HW DN
BALL VALVE (TYP)
BUBBLE TIGHT
2"HLV DN
2"
2"
2"
2"
1"
D
PLENUM
DRAIN
3/4"1 1/4"
1"3/4"
D
D
1"
1"1"
1"D DN -
SPILL OVER
MOP SINK
D
1"
2"V DN
36x20
24x24
36x36
1"
1"D DN
1"
FDB
FDB
2"V DN
1 1/4"
DRAIN
PLENUM
D
1 1/4"
1"
1 1/4"
3/4"
OF STEAM TRAP
3/4" DRAIN OFF
DD
1"
1 1/2"
1/2"
1/2"
3/4" 1"
1"1"1"
1"
1/2"
1/2" 3/4" 3/4" 1"
1"
1/4"/FT
F T
1"
1"
1 1/4"
2" 1"
1" 1" 1"
1 1/4" 2"
1/2"
1/2"
ROUTE PIPING AS
HIGH AS POSSIBLE
3/4"
1 1/4"
1/2"
1"
2" 1 1/4" 2" 1 1/4"
1/2"
1"
3/4"
1"
2"
2"
2.5 GPM
BALANCE TO
3/4"
1"
1" 1/2"
1"
1/2"
1/2"
2"
1 1/4"
2"
3/4"
1 1/4"
1/2"
3/4"
1 1/4"
3/4"
1/2"
1"
3/4"
1 1/2"
1 1/4"
1 1/4"
2"
3/4"
1/2"
1/2"
1"
3/4"
2"G DN
3/4"A DN
3/4"HWC DN
1 1/2"HW DN
2"CW DN
1/2"
1/2"
1"
1 1/4"3/4"
3/4"
1"
A
3/4"
A
1"
DRAIN PAN
RECOVERY COIL
DRAIN OFF OF
1"D DN
SECOND FLOOR PLUMBING
DEMOLITION PLAN
DM153 0
AS SHOWN.
REMOVE HOT WATER CIRCULATION PIPE, FITTINGS AND ACCESSORIES 7.
REMOVE HOT WATER PIPE, FITTINGS, AND ACCESSORIES AS SHOWN.6.
REMOVE COLD WATER PIPE, FITTINGS AND ACCESSORIES AS SHOWN.5.
MATERIAL AND DUCT SEALANT.
VALVE. REMOVE VALVES AND SEAL DUCT WITH SIMILAR DUCT
REMOVE HIGH LEVEL VENT LINE FROM FLOOR SLAB TO INLET OF 4.
SECOND FLOOR.
REMOVE MG PIPE, FITTINGS AND ACCESSORIES FROM ENTIRE 3.
ENTIRE SECOND FLOOR.
REMOVE CARBON DIOXIDE PIPE, FITTINGS, AND ACCESSORIES FROM 2.
VALVES TO REMAIN.
LOCATIONS SHOWN. PROVIDE THREADED CAP DOWNSTREAM OF
REMOVE GAS PIPE, FITTINGS, VALVES AND ACCESSORIES TO 1.
DEMOLITION KEYNOTES:
SECOND FLOOR PLUMBING DEMOLITION PLAN
LEGEND:
INDICATES DEMOLITION LIMITS
INDICATES DEMOLITION OF PIPES
654 65
5 6
4 5
5 6
44 2
8 2
N O
R
TH
ROOM
MECHANICAL
M02
MAY 31, 2019
KL GRAVES
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
316 315
315B
209 211
M01
307306305304
311 312
201 214
112111110
204B
205309
310 207
104 103
102 101
EQUIP ROOM
WATER
DNA ROOM TB ID ROOM BACTEC
SCOPE
ROOM
EQUIPMENT
ROOM
WALK-IN
COOLER
OUTGOING RECEIVING
VESTIBULE
EQUIPMENT
ROOM
PROCESSING
LAB
ELECTRICAL
MECHANICAL
STAIRS
BSL-2 CORRIDOR
WALK-IN
COOLER
AIRLOCK
LOBBY
BSL-3 CORRIDOR
TECH ROOM
STORAGE
BRUCELLA
ROOM
ESP ROOM
TB PROC
#3
TB PROC
#2
TB PROC
#1
CHANGING
ROOM SHOWER
LOCKER
HALLWAY
MOL
LAB 1
MOL
LAB 2
MOL
LAB 3
MOL
LAB 4
TANK
ROOM
RECEPTION
TECH
ROOMOFFICE OFFICE
SCOPE
RM
JANITOR
CHANGING
ROOM
SHOWER LOCKER
ELEC
DATA HALLWAY
VESTIBULE
OFFICEOFFICEOFFICEOFFICE
OFFICE
CLOSET
CONFERENCE/
BREAKROOM
A/V
CLOSET
PHENOL RM
321 4 4.7 5 6 7 8
A
A.4
B
C
D
A
A.4
B
C
D
C.3
FIRST FLOOR FIRE PROTECTION
DEMOLITION PLAN
DM154 0
AS NOTED
ML MARTZ
FIRST FLOOR FIRE PROTECTION DEMOLITION PLAN
INDICATES DEMOLITION LIMITS
ACCESSORIES.
REMOVE ALL SPRINKLER HEADS, PIPING AND ASSOCIATED 1.
N O
R
TH
EXISTING FIRE PROTECTION RISER DIAGRAM
FS
P
SCALE: 1/8"=1'-0"
NO SCALE
CONNECTION
DEPARTMENT
FIRE
BACKFLOW ASSEMBLY
DOUBLE CHECK
6"
MAIN DRAIN
TEE CONNECTION
FIRST FLOOR
DIAGRAM THIS DWG
TO BUILDING 401, SEE RISER
EXST 6" FIRE WATER SERVICE
DEMOLITION KEYNOTES:
MAY 31, 2019
KL GRAVES
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
A.4
B
SECOND FLOOR FIRE PROTECTION
DEMOLITION PLAN
DM155 0
SECOND FLOOR FIRE PROTECTION DEMOLITION PLAN
O
R
TH
LEGEND:
INDICATES DEMOLITION LIMITS
ACCESSORIES.
REMOVE ALL SPRINKLER HEADS, PIPING AND ASSOCIATED 1.
DEMOLITION NOTES:
ROOM
MECHANICAL
M02
MAY 31, 2019
KL GRAVES
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
316 315
315B
209 211
M01
307306305304
311 312
201 214
112111110
204B
205309
310 207
104 103
102 101
EQUIP ROOM
WATER
DNA ROOM TB ID ROOM BACTEC
SCOPE
ROOM
EQUIPMENT
ROOM
WALK-IN
COOLER
OUTGOING RECEIVING
VESTIBULE
EQUIPMENT
ROOM
PROCESSING
LAB
ELECTRICAL
MECHANICAL
STAIRS
BSL-2 CORRIDOR
WALK-IN
COOLER
AIRLOCK
LOBBY
BSL-3 CORRIDOR
TECH ROOM
STORAGE
BRUCELLA
ROOM
ESP ROOM
TB PROC
#3
TB PROC
#2
TB PROC
#1
CHANGING
ROOM SHOWER
LOCKER
HALLWAY
MOL
LAB 1
MOL
LAB 2
MOL
LAB 3
MOL
LAB 4
TANK
ROOM
RECEPTION
TECH
ROOMOFFICE OFFICE
SCOPE
RM
JANITOR
CHANGING
ROOM
SHOWER LOCKER
ELEC
DATA HALLWAY
VESTIBULE
OFFICEOFFICEOFFICEOFFICE
OFFICE
CLOSET
CONFERENCE/
BREAKROOM
A/V
CLOSET
PHENOL RM
321 4 4.7 5 6 7 8
A
A.4
B
C
D
A
A.4
B
C
D
C.3
FIRST FLOOR ELECTRICAL
DEMOLITION PLAN
DE150 0
JM DANIELSON
FIRST FLOOR ELECTRICAL DEMOLITION PLAN
1. SEE REFERENCE DRAWINGS FOR BUILDING 401 ELECTRICAL AS BUILT
PLANS SHOWING DETAILED PLACEMENT OF EXISTING ELECTRICAL
AND COMMUNICATIONS EQUIPMENT.
2. WITHIN THE DEMOLITION HASH LINES: DEMOLISH ALL LIGHT FIXTURES,
ELECTRICAL PANELS AND RECEPTACLES, FIRE ALARM, CONTROLS,
AND COMMUNICATION DEVICES. FOR CONDUIT AND WIRING
EXTENDING BEYOND THE DEMOLITION AREA, REMOVE CONDUIT TO
THE NEAREST JUNCTION BOX OR FITTING TO REMAIN, REMOVE
WIRING TO THE SOURCE OF SUPPLY, AND COVER OR FILL OPENING IN
BOXES OR FITTINGS. REMOVE EXPOSED ABANDONED CONDUIT.
3. EXISTING SECURITY DEVICES ON EXTERIOR DOORS, AND INTERIOR
DOORS THAT REMAIN IN PLACE AFTER DEMOLITION, SHALL REMAIN
INTACT AND FUNCTIONING. DEMOLISH SECURITY DEVICES, CONDUITS,
AND BOXES ONLY ON DOORS AND WALLS TO BE DEMOLISHED.
CONTRACTOR RESPONSIBLE FOR RE-ROUTING CONDUITS AND
RELOCATING JUNCTION BOXES AS REQUIRED TO MAINTAIN SECURITY
SYSTEM INTEGRITY. COORDINATE WITH SECURITY SYSTEM
INTEGRATOR.
4. SEE MECHANICAL AND PLUMBING DEMOLITION DRAWINGS. DEMOLISH
ASSOCIATED ELECTRICAL CONTROLS AND FEEDERS FOR MECHANICAL
EQUIPMENT GETTING DEMOLISHED AS DESCRIBED IN NOTE 2.
5. CONTRACTOR SHALL ENSURE THAT FIRE ALARM CIRCUITS FOR
DEVICES LOCATED IN THE MEZZANINE REMAIN IN SERVICE DURING
DEMOLITION OF FIRST FLOOR. IF DEVICES IN THE MEZZANINE ARE A
PART OF A FIRE ALARM CIRCUIT THAT IS TO BE DEMOLISHED ON THE
MAIN FLOOR, CONTRACTOR SHALL ROUTE NEW CONDUIT AND CIRCUIT
CABLING FROM DEVICES TO REMAIN BACK TO EXISTING FACP.
PROVIDE FIRE WATCH SERVICE IF REQUIRED.
DEMOLITION NOTES:
1. LIGHTING AND RECEPTACLES CURRENTLY FED FROM PANEL BL2.
FEED EXISTING LIGHTING FROM PANEL LA, CIRCUIT 22. FEED
EXISTING RECEPTACLES FROM PANEL LA, CIRCUIT 23. 2-#12, 1-#12G,
3/4"C TYPICAL. CONTRACTOR SHALL UPDATE PANEL SCHEDULE FOR
PANEL LA. SEE REFERENCE DRAWINGS.
2. LIGHTING AND RECEPTACLES CURRENTLY FED FROM PANEL BL3.
FEED EXISTING LIGHTING FROM PANEL LA, CIRCUIT 24. FEED
EXISTING RECEPTACLES FROM PANEL LA, CIRCUIT 25. 2-#12, 1-#12G,
3/4"C TYPICAL. CONTRACTOR SHALL UPDATE PANEL SCHEDULE FOR
PANEL LA. SEE REFERENCE DRAWINGS.
3. THERE ARE TWO EXISTING RECEPTACLES IN THIS AREA. LEAVE IN
PLACE. THESE RECEPTACLES WILL BE FED FROM A NEW PANEL LB.
SEE PANEL SCHEDULE AND DRAWING EP150.
4. REMOVE EXISTING EMERGENCY GENERATOR, ALL ASSOCIATED
UTILITY CONNECTIONS, AND ANY ANCILLARY EQUIPMENT COMPLETE.
REMOVE EXISTING EQUIPMENT PADS AND ASSOCIATED SUPPORTS.
THE FINISHED PRODUCT SHALL BE LEVEL WITH THE SURROUNDING
GRADE AND FINISH TO MATCH EXISTING. DEMOLISH AND REMOVE
PIPING BACK TO ACTIVE MAINS AND CAP. THE CONTRACTOR MAY
CHOOSE TO SALVAGE/SELL THIS EQUIPMENT AT THEIR OWN
DISCRETION, UPON DEMOLITION, THE EQUIPMENT MUST BE REMOVED
FROM THE SITE - IT CANNOT BE TEMPORARILY STORED ON-SITE.
5. DEMOLISH AUTOMATIC TRANSFER SWITCH AND CONCRETE PAD.
6. DEMOLISH CABLES IN DUCTBANK TO PANEL FDP.
7. DEMOLISH SECONDARY CABLES IN DUCTBANK TO PAD MOUNT
500KVA TRANSFORMER, APPROXIMATELY 80'.
DEMOLITION KEYNOTES:
N O
R
TH
LEGEND:
INDICATES DEMOLITION LIMITS
BL2 EQ2
PANEL "LA"
RACK
EXST COMM
EQ3BL3
GEN
ATS 7
FDP
MAY 31, 2019
NC VEEN
NC VEEN
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
EXISTING
HIGH VOLTAGE
SWITCHGEAR
PAD MTD XFMR
SECONDARY
PANEL PANEL PANEL
BL2
120/208V/3
M/B
PANEL
BL3
PANELPANEL
EQ3
EQ2
TVSS
EF-1AEF-1BEF-2EF-3EF-4AHU-2AHU-1
ABOVE GRADE
SPLICE CAB
TO ANIMAL BARNS
LA
120/208V/3
(OFFICE)
M/B
FDP
120/208V/3
M/B
60/3 C/B
DISC. SW.
CHLR-1
TX
BY ELECTRICAL CONTRACTOR
500 KVA
120/208V/3
VFD-1
208V/3
VFD-2
208V/3
MS-2 MS-1
VFD-4
208V/3
VFD-5
208V/3
VFD-3
208V/3
M2
120/208V/3
M/B
M1
120/208V/3
MLO
GEN
500KW
GENERATOR
ATS
ELECTRICAL DEMOLITION
ONE-LINE DIAGRAM AND PANELS
DE650 0
NONE
SPARES IN OFF POSITION. SEE DRAWING EO650.
BREAKER NUMBERS 4, 5,11 AND 12 IN PANEL FDP SHALL REMAIN AS 2.
THIS SCHEMATIC REPRESENTATION TO BE REMOVED.
DEMOLITION. THERE MAY BE ADDITIONAL EQUIPMENT NOT SHOWN ON
HASH LINES SHOW SCHEMATIC REPRESENTATION OF PANELS DURING 1.
DEMOLITION NOTES:
PANEL BL2 SCHEDULE
(SECTION A)
TYPE: 120/208 VOLTS, 3 PHASE, 4 WIRE LOCATION: BL2 CORRIDOR
MAIN BUS 225A MOUNTING: FLUSH
M/B FRAME 225A TRIPS 150 FEEDER: 4-#2/0 CU
A.I.C. 10,000 #6 GND
2" C
DESCRIPTION LOAD C/B NO NO C/B LOAD DESCRIPTION
LTS-MOL LAB 1,2,3 0.8 20-1 1 2 20-1 0.6 LTS-MOL LAB 4
LTS-PROCESS LAB 1.0 20-1 3 4 20-1 1.3 LTS-BL2 CORRIDOR
REC-BL2 CORRIDOR 0.4 20-1 5 6 20-1 1.0 ICE MACH #33
REC-MOL1 0.6 20-1 7 8 20-1 0. SPARE MOL1
REC-MOL1 0.6 20-1 9 10 20-1 0.8 MOL1 MICROWAVE #57
MOL1 WATER BATH #27 1.9 20-1 11 12 20-1 1.9 MOL1 WATER BATH #27
REC-MOL2 0.6 20-1 13 14 30-2 3.8 MOL2 TAQ MONITOR #17
REC-MOL2 0.6 20-1 15 16 -- -- 3-#10, #10 GND, WM
SPARE 0. 20-1 17 18 20-1 0. SPARE
REC-MOL3 0.6 20-1 19 20 20-2 0. SPARE MOL3
REC-MOL3 0.6 20-1 21 22 -- -- --
REC-MOL3 0.6 20-1 23 24 20-1 0.6 REC-MOL3
REC-MOL4 0.6 20-1 25 26 20-2 0. SPARE MOL4
REC-MOL4 0.6 20-1 27 28 -- -- --
MOL4 BSC2 #12 UPS-1 1.5 20-1 29 30 20-1 1.0 MOL4 HPLC #19
SPARE MOL4 0. 20-1 31 32 20-1 0. SPARE MOL4
REC-PL211 NORTH 0.4 20-1 33 34 30-2 4.4 PL211 CENTRIFUGE #29
PL211 ESP #4 1.5 20-1 35 36 -- -- 3-#10, #10 GND, WM
PL211 INCUBATOR #6 1.9 20-1 37 38 20-1 1.9 PL211 INCUBATOR #6
PL211 BSC2 #11 UPS-2 1.5 20-1 39 40 20-1 0.4 REC-PL211 SOUTH
REC-PL211 WEST 0.5 20-1 41 42 20-1 0.5 REC-PL211 WEST
TOTAL LOAD (KW) 16.8 18.2
NOTE: CIRCUITS SHALL BE ARRANGED AS SHOWN IN THIS SCHEDULE.
PANEL BL2 SCHEDULE
(SECTION B)
TYPE: 120/208 VOLTS, 3 PHASE, 4 WIRE LOCATION: BL2 CORRIDOR
MAIN BUS 225A MOUNTING: FLUSH
MAIN LUGS ONLY FEEDER: 4-#2/0 CU
A.I.C. 10,000 #6 GND
2" C
DESCRIPTION LOAD C/B NO NO C/B LOAD DESCRIPTION
REC-PL209 ISLAND 0.5 20-1 43 44 20-1 0.5 REC-PL209 ISLAND
SPARE PL209 0. 20-1 45 46 20-1 0. SPARE PL209
SPARE PL209 0. 20-1 47 48 20-1 0. SPARE PL209
REC-BL2 LOCKER RMS 1.0 20-1 49 50 20-1 0. SPARE
SPARE 0. 20-1 51 52 20-1 0. SPARE
SPARE 0. 20-1 53 54 20-1 0. SPARE
SPARE 0. 20-1 55 56 20-1 0. SPARE
SPARE 0. 20-1 57 58 20-1 0. SPARE
SPARE 0. 20-1 59 60 20-1 0. SPARE
SPACE 0. 20-1 61 62 20-1 0. SPACE
SPACE 0. 20-1 63 64 20-1 0. SPACE
SPACE 0. 20-1 65 66 20-1 0. SPACE
SPACE 0. 20-1 67 68 20-1 0. SPACE
SPACE 0. 20-1 69 70 20-1 0. SPACE
SPACE 0. 20-1 71 72 20-1 0. SPACE
SPACE 0. 20-1 73 74 20-1 0. SPACE
SPACE 0. 20-1 75 76 20-1 0. SPACE
SPACE 0. 20-1 77 78 20-1 0. SPACE
SPACE 0. 20-1 79 80 20-1 0. SPACE
SPACE 0. 20-1 81 82 20-1 0. SPACE
SPACE 0. 20-1 83 84 20-1 0. SPACE
TOTAL LOAD (KW) 1.5 .5
TOTAL PANEL LOAD (KW) 18.3 37.0 18.7
NOTE: CIRCUITS SHALL BE ARRANGED AS SHOWN IN THIS SCHEDULE.
PANEL EQ2 SCHEDULE
TYPE: 120/208 VOLTS, 3 PHASE, 4 WIRE LOCATION: BL2 CORRIDOR
MAIN BUS 100A MOUNTING: FLUSH
M/B FRAME 100A TRIPS 100A FEEDER: 4-#2 CU
A.I.C. 10,000 #8 GND
1-1/2" C
DESCRIPTION LOAD C/B NO NO C/B LOAD DESCRIPTION
LTS-BL2 EQUIPMENT RM 0.4 20-1 1 2 20-1 0. SPARE
REC-BL2 EQUIPMENT RM 0.2 20-1 3 4 20-1 0.8 BL2 WALK-IN COOLER
SPARE 0. 20-1 5 6 20-1 0. SPARE
BL2 -80 FREEZER #9 2.0 20-1 7 8 20-1 2.0 BL2 -80 FREEZER #9
BL2 -80 FREEZER #9 2.0 20-1 9 10 20-2 2.0 BL2 -80 FREEZER #64
BL2 -20 FREEZER #20 2.0 20-1 11 12 -- -- 2-#12, #12 GND, 3/4"
SPARE FUTURE 0. 20-1 13 14 20-1 0. SPARE FUTURE
BL2 -80 FREEZER #54 2.6 20-2 15 16 20-2 0. SPARE FUTURE
2-#12, #12 GND, 3/4" -- -- 17 18 -- -- --
BL2 WALK-IN COOLER 3.0 20-3 19 20 20-1 0. SPARE
208V/3, 3 HP MAX -- -- 21 22 20-1 0. SPARE
3-#12, #12 GND, 3/4" -- -- 23 24 20-1 0. SPARE
SPACE 0. 20-1 25 26 20-1 0. SPACE
SPACE 0. 20-1 27 28 20-1 0. SPACE
SPACE 0. 20-1 29 30 20-1 0. SPACE
TOTAL LOAD (KW) 12.2 17.0 4.8
NOTE: CIRCUITS SHALL BE ARRANGED AS SHOWN IN THIS SCHEDULE.
PANEL BL3 SCHEDULE
(SECTION A)
TYPE: 120/208 VOLTS, 3 PHASE, 4 WIRE LOCATION: BL2 CORRIDOR
MAIN BUS 225A MOUNTING: FLUSH
M/B FRAME 225A TRIPS 225A FEEDER: 4-#4/0 CU
A.I.C. 10,000 #4 GND
2-1/2" C
DESCRIPTION LOAD C/B NO NO C/B LOAD DESCRIPTION
LTS-BL3 BRUCELLA CORR 1.2 20-1 1 2 20-1 1.1 LTS-BL3 LAB 304 305
LTS-BL3 LAB 306 307 1.1 20-1 3 4 20-1 0.9 LTS-BL3 LAB 317 318
LTS-BL3 LAB 315 316 1.1 20-1 5 6 20-1 1.1 LTS-BL3 RECEIVING
REC-ESP 304 0.6 20-1 7 8 20-1 1.2 ESP 304 MGIT #52
REC-ESP 304 0.6 20-1 9 10 20-1 1.5 ESP 304 INCUBATOR #7
REC-ESP 304 MACH #4 1.5 20-1 11 12 20-1 0. SPARE ESP 304
REC-TB305 0.6 20-1 13 14 30-2 4.4 TB305 CENTRIFUGE #29
REC-TB305 0.6 20-1 15 16 -- -- 3-#10, #10 GND, WM
TB305 BSC3 #18 UPS-3 1.5 20-1 17 18 20-1 1.5 TB305 BSC2 #11 UPS-4
TB305 INCUBATOR #13 1.2 20-1 19 20 20-1 0. SPARE TB305
REC-TB306 0.6 20-1 21 22 30-2 4.8 TB306 CENTRIFUGE #2
REC-TB306 0.6 20-1 23 24 -- -- 3-#10, #10 GND, WM
TB306 BSC3 #18 UPS-5 1.5 20-1 25 26 20-1 1.5 TB306 BSC2 #11 UPS-6
TB306 INCUBATOR #13 1.2 20-1 27 28 20-1 0. SPARE TB306
REC-TB307 0.6 20-1 29 30 30-2 4.8 TB307 CENTRIFUGE #2
REC-TB307 0.6 20-1 31 32 -- -- 3-#10, #10 GND, WM
TB307 BSC3 #18 UPS-7 1.5 20-1 33 34 20-1 1.5 TB307 BSC2 #11 UPS-8
TB307 INCUBATOR #13 1.2 20-1 35 36 20-1 0. SPARE TB307
REC-BACTEC 315 0.6 20-1 37 38 30-2 0. SPARE BACTEC 315
REC-BACTEC 315 0.6 20-1 39 40 -- -- --
BACTEC 315 INCUBATOR #7 1.5 20-1 41 42 20-1 1.5 315 BSC3 #18 UPS-9
TOTAL LOAD (KW) 20.5 25.8
NOTE: CIRCUITS SHALL BE ARRANGED AS SHOWN IN THIS SCHEDULE.
PANEL BL3 SCHEDULE
(SECTION B)
TYPE: 120/208 VOLTS, 3 PHASE, 4 WIRE LOCATION: BL2 CORRIDOR
MAIN BUS 225A MOUNTING: FLUSH
MAIN LUGS ONLY FEEDER: 4-#4/0 CU
A.I.C. 10,000 #4 GND
2-1/2" C
DESCRIPTION LOAD C/B NO NO C/B LOAD DESCRIPTION
SPARE BACTEC 315 0. 20-1 43 44 20-1 0. SPARE BACTEC 315
REC-TBID 316 0.6 20-1 45 46 20-1 0. SPARE TBID 316
REC-TBID 316 0.6 20-1 47 48 20-1 1.4 TBID 316 AUTOCLAVE 8
TBID 316 INCUBATOR #13 1.2 20-1 49 50 20-1 1.5 316 BSC3 #18 UPS-10
TBID 316 INCUBATOR #30 1.2 20-1 51 52 20-1 1.2 316 INCUBATOR #30
REC-DNA 317 0.6 20-1 53 54 30-2 4.8 DNA 317 CENTRIFUGE 2
REC-DNA 317 0.6 20-1 55 56 -- -- 3-#10, #10 GND WM
DNA 317 BSC3 #18 UPS-11 1.5 20-1 57 58 20-1 1.2 317 WATER BATH #21
317 WATER BATH #21 1.2 20-1 59 60 20-1 0. SPARE DNA 317
REC-TECH 318 0.6 20-1 61 62 20-1 0.6 REC-TECH 318
REC-TECH 318 0.6 20-1 63 64 20-1 0.2 REC-STORAGE 302 303
REC-CORRIDOR 0.2 20-1 65 66 20-1 0. SPARE
REC-BRUCELLA 301 0.6 20-1 67 68 20-1 1.8 301 WATER BATH #45
REC-BRUCELLA 301 0.6 20-1 69 70 20-1 1.1 301 WATER BATH #46
301 BSC2 #37 UPS-12 1.5 20-1 71 72 20-1 1.5 301 CENTRIFUGE #38
301 INCUBATOR #35 1.5 20-1 73 74 20-1 0.5 301 INCUBATOR #36
SPARE BRUCELLA 301 0. 20-1 75 76 20-1 0. SPARE BRUCELLA 301
SPARE 0. 20-1 77 78 20-1 0. SPARE
SPARE 0. 20-1 79 80 20-1 0. SPARE
SPARE 0. 20-1 81 82 20-1 0. SPARE
SPARE 0. 20-1 83 84 20-1 0. SPARE
TOTAL LOAD (KW) 13.1 15.8
TOTAL PANEL LOAD (KW) 33.6 75.2 41.6
NOTE: CIRCUITS SHALL BE ARRANGED AS SHOWN IN THIS SCHEDULE.
PANEL EQ3 SCHEDULE
TYPE: 120/208 VOLTS, 3 PHASE, 4 WIRE LOCATION: BL2 CORRIDOR
MAIN BUS 225A MOUNTING: FLUSH
M/B FRAME 225A TRIPS 150A FEEDER: 4-#2/0 CU
A.I.C. 10,000 #6 GND
2" C
DESCRIPTION LOAD C/B NO NO C/B LOAD DESCRIPTION
LTS-BL3 EQUIPMENT RM 0.3 20-1 1 2 20-1 0. SPARE
REC-BL3 EQUIPMENT RM 0.2 20-1 3 4 20-1 0.8 BL3 WALK-IN COOLER
AUTOCLAVE CONTROL 0.5 20-1 5 6 20-1 1.2 BP1 PUMP MS-14
BL3 -80 FREEZER #9 2.0 20-1 7 8 20-1 2.0 BL3 -80 FREEZER #9
BL3 -80 FREEZER #9 2.0 20-1 9 10 20-1 2.0 BL3 -80 FREEZER #9
BL3 -20 FREEZER #20 2.0 20-1 11 12 20-1 2.0 BL3 -20 FREEZER #20
BL3 -20 FREEZER #20 2.0 20-1 13 14 20-1 2.0 BL3 -20 FREEZER #20
BL3 -80 FREEZER #9 2.0 20-1 15 16 20-2 0. SPARE FUTURE
SPARE FUTURE 0. 20-1 17 18 -- -- --
BL3 WALK-IN COOLER 3.0 20-3 19 20 20-1 0.4 REC-RECEIVING
208V/3, 3 HP MAX -- -- 21 22 20-1 0.4 REC-RECEIVE/OUTGOING
3-#12, #12 GND, 3/4" -- -- 23 24 20-1 0. SPARE
SPARE 0. 20-1 25 26 20-1 0. SPARE
SPARE 0. 20-1 27 28 20-1 0. SPARE
SPARE 0. 20-1 29 30 20-1 0. SPARE
TOTAL LOAD (KW) 14.0 24.8 10.8
NOTE: CIRCUITS SHALL BE ARRANGED AS SHOWN IN THIS SCHEDULE.
ELECTRICAL ONE-LINE DIAGRAM DEMOLITION
LEGEND:
INDICATES DEMOLITION LIMITS
ELECTRICAL PANELS DEMOLITION
MAY 31, 2019
NC VEEN
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
213A
200A
204B
206A
108 109
110 111 112
100B 100A
101102103
310B
310A
213B
312A
312B
308D
206B
308E
M01
311 312
112111110
204B
205309
310 207
104 103
102 101
EQUIP ROOM
WATER
ELECTRICAL
MECHANICAL
STAIRS
CHANGING
ROOM SHOWER
LOCKER
HALLWAY
RECEPTION
TECH
ROOMOFFICE OFFICE
SCOPE
RM
JANITOR
CHANGING
ROOM
SHOWER LOCKER
ELEC
DATA HALLWAY
VESTIBULE
OFFICEOFFICEOFFICEOFFICE
OFFICE
CLOSET
CONFERENCE/
BREAKROOM
A/V
CLOSET
321 4 4.7 5 6 7 8
A
A.4
B
C
D
A
A.4
B
C
D
C.3
C.6
7 87.2
8'-4"30'-0" 22'-5"10'-0"20'-0"24'-3"24'-3"24'-3"
2'-0" 6'-4"
163'-6"
FIRST FLOOR ARCHITECTURAL
MODIFICATIONS PLAN
AE150 0
FIRST FLOOR ARCHITECTURAL MODIFICATIONS PLAN
S T O R A G E
THE EXISTING FLOOR SLAB.
WHEEL LOADS: NONE - FORK LIFT TRAFFIC IS NOT ALLOWED ON
BEARING PLATE AT MINIMUM SPACING OF 8'-4" EACH WAY.
CONCENTRATED POST LOAD: 1.85 KIP WITH 6" X 6" MINIMUM
UNIFORM LIVE LOAD: 500 PSF
MAXIMUM ALLOWABLE LIVE LOADS ON EXISTING FLOOR SLAB:6.
EXISTING PARTITION TO REMAIN.5.
CLEAN EXPOSED CEILING/DECK AND STRUCTURE TO RECEIVE PAINT.4.
SMOOTH SURFACE TO RECEIVE PAINT.
WALLS SHALL BE PATCHED, REPAIRED AND CLEANED FOR A 3.
NEW 2 - 4'-0" X 8'-0" INSULATED HOLLOW METAL DOUBLE DOOR.2.
COATING.
WITH A SMOOTH LEVEL FINISH AND SEALED WITH AN EPOXY
EXPOSED CONCRETE FLOOR SHALL BE PATCHED AND REPAIRED 1.
3 4
N O
R
TH
MAY 31, 2019
D SARKAR
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
MISCELLANEOUS
STRUCTURAL DETAILS
SS551 0
AL BICKFORD
NJ PIERSON
AL BICKFORD
SECTION
B-SS551
SCALE:3"=1'-0"
DA151
PL1/4"X3"X8 1/2"
WELDED TO C6 AT TOP
L3X3X1/4 X 4 1/4" LG
DOOR SUPPORT FRAMING
C6X8.2
EXST 2ND FLR BEAM
(3) 1/2" DIA A325 BOLTS
/2
DOOR SUPPORT FRAMING
C6X8.2
ADHESIVE ANCHORS
(2) 1/2" DIA
AT BOTTOM
WELDED TO C6
L3X3X1/4 X 4 1/4" LG
EXST FDN WALL
SECTION
A-SS551
SCALE:3"=1'-0"
DA151
3 SIDES
MAY 31, 2019
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
M01
311 312
112111110
204B
205309
310 207
104 103
102 101
EQUIP ROOM
WATER
ELECTRICAL
MECHANICAL
STAIRS
CHANGING
ROOM SHOWER
LOCKER
HALLWAY
RECEPTION
TECH
ROOMOFFICE OFFICE
SCOPE
RM
JANITOR
CHANGING
ROOM
SHOWER LOCKER
ELEC
DATA HALLWAY
VESTIBULE
OFFICEOFFICEOFFICEOFFICE
OFFICE
CLOSET
CONFERENCE/
BREAKROOM
A/V
CLOSET
321 4 4.7 5 6 7 8
A
A.4
B
C
D
A
A.4
B
C
D
C.3
C.6
7 87.2
CD-2
LD-1
LD-1
LD-1
LD-1
LD-1
LD-1
LD-1
LD-1
CD-2
CD-2
CD-2
CD-2
CD-2
CD-2
CD-2
RG-6
22x22
22x22
RG-6
22x22
RG-6
22x22
RG-6
22x22
RG-6
22x22
RG-6
22x22
RG-6
22x22
RG-6
22x22
RG-6
22x22
RG-6
CD-2
CD-2
CD-2
T
12x12
EG-5
CD-2
EG-5
12x12
12x12
EG-5
EG-5
12x12
CD-2
CD-2
12x12
EG-5
RG-6
8x8
T
CD-2
x
LD-1
24x12 16x12
10x12
FRN-1
x
8x12
FRN-2
8x8 x
SG-8
8x4
(SUSPENDED)
ELBOW W/SCREEN
ELBOW W/SCREEN
CD-3
OFFSET AROUND
BEAM
x1
6x6
SG-8
6x6
SG-8
36x12 w/OBD
5"CHWS UP
5"CHWR UP
4"HWR UP
4"HWS UP
1 1/2"
1 1/2"
W S
W R
W S
W R
4" HWR
4" HWS
4" HWS
4" HWR
R L
R S
T
T
T
T
ANNUNICATOR PANEL
PIPE SUPPORT
20x6 EA.
UP & DN
DAMPERS INTERCONNECTED
TO HPB-1
D R
O P
W/OBD
W/OBD
W/OBD
T H
FIRST FLOOR HVAC PLAN
MH150 0
FIRST FLOOR HVAC PLAN
O
1. 95 CFM SUPPLY AIR
2. 75 CFM RETURN AIR
3. 65 CFM RETURN AIR
KEYNOTES:
2 2 2
2 2
1 1 1
1 1 1
S T O R A G E
MAY 31, 2019
KL GRAVES
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
A.4
B
C
D x
6x6 x
10x8
10x6 x
C O
O L
IN
G
C O
IL
C O
IL
C O
O L
IN
G
F
IL
T E
R
F
IL
T x
M M x
M x x
M x
M
M x
M x x
M x
M M x
M x x
M x
M
12x16 x x
M x1 x
M M x
18x16
M x
M x x x x
M
F
IL
T E
R S
C E
S S
H E
A T
IL
C O
O L
IL
H U
M
ID
IF
IE
R
C E
S S
C O
O L
IL
LOUVER
54x54 OA
54x18 6
18"
M
M
36x16 x x
36x16 x
D R
O P
S
L O
S T
R U
C T
U R
E
M x x
M x x
24x20 x
(SUSPENDED)
(SUSPENDED)
(SUSPENDED)
5" CHWS
5" CHWR
4" HWS
4" HWR
4" CHWS
4" CHWR
4" HWR
4" HWS
3"
4"
4" CHWR
4" CHWS
4" HWR
4" HWS
3"
2 1/2"
3"
2 1/2"2 1/2" 2 1/2"
1" 1"
1 1/2"
1"
1 1/2" 1 1/2"
1"
1 1/2"
1 1/2"
1"
1"1"
1"
1"
1"
4" HWS
4" HWR
4" CHWR
4" CHWS
16x12 24x16
24x16
RL
RS
RL
RS
4"HWS & HWR DN
5"CHWS & CHWR DN
1"
1"1"
1 1/2"
EXHAUST/VENT
TERMINATION
24x16
24x16
24x16
D R O P
D R O
PD
R O P
R
IS
E
S
L O
S T
R U
C T
U R
E
THRU ROOF,
2"BDS VENT UP
SG-8
24x16 w/OBD
SG-8
24x16 w/OBD
SG-8
24x16 w/OBD
(SUSPENDED)
24x12
VD
30x2048x20
M
M
M
SECOND FLOOR HVAC PLAN
MH151 0
SECOND FLOOR HVAC PLAN
O
BALANCE AHU TO 2,660 CFM. 4.
BALANCE FAN TO 2,230 CFM.
EXISTING EXHAUST FAN TO BE RE-BALANCED AS RETURN FAN. 3.
CONTROL SHOWN ON DRAWING MH750.
REPROGRAM EXISTING CONTROL PANEL TO PROVIDE SEQUENCE OF 2.
CONNECT DUCT TO EXISTING PLENUM OF AIR HANDLING UNIT.1.
KEYNOTES:36X16
X
36X16
18X16
WALL CAPEF-10
FOR CONTINUATION
SEE DWG MH150 FOR
3 EXST EXHAUST FAN
ROOM
MECHANICAL
M02
MAY 31, 2019
KL GRAVES
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
HVAC CONTROL SCHEMATICS
MH750 0
BK GROTHE
GENERAL REQUIREMENTS
1. HVAC SYSTEMS SHALL BE CONTROLLED BY UNIT MOUNTED STAND ALONE DIRECT DIGITAL CONTROLLER, UNLESS NOTED OTHERWISE. CONTROLLERS SHALL BE
INTEGRATED INTO BUILDING DIRECT DIGITAL CONTROL (DDC) SYSTEM FOR REMOTE CONTROL AND MONITORING. DDC SYSTEM COMMUNICATION SHALL BE AS
SPECIFIED.
2. SET POINTS LABELED AS ADJUSTABLE SHALL BE FULLY ADJUSTABLE FROM OPERATOR WORKSTATIONS. SET POINTS FOR THERMOSTATS WITH INTEGRAL SET POINT
ADJUSTMENT SHALL BE ADJUSTABLE FROM BOTH THE THERMOSTAT AND THE OPERATOR WORKSTATION. SET POINT ADJUSTMENT SHALL NOT REQUIRE
PROGRAMMING OF DDC PANELS.
3. ALARM REPORTING SHALL BE DONE AT PANEL ASSOCIATED WITH EQUIPMENT AND SHALL BE AVAILABLE AT OPERATOR WORK STATIONS.
4. VENTILATION OUTDOOR AIR AND EXHAUST DAMPERS SHALL BE CAPABLE OF AUTOMATICALLY SHUTTING OFF DURING PREOCCUPANCY BUILDING WARM-UP, COOL
DOWN, AND SETBACK PERIODS.
NORMAL CONTROL POSITIONS
1. NORMAL POSITIONS OF CONTROLLED DEVICES SHALL BE POSITION DEVICE RETURNS TO ON POWER FAILURE OR CONTROLLER FAILURE. NORMAL POSITIONS SHALL
BE AS FOLLOWS:
A. OUTDOOR AIR DAMPER: CLOSED
B. EXHAUST AIR DAMPER: CLOSED
C. RETURN AIR DAMPER: OPEN
D. AUTOMATIC CONTROL VALVE (ACV) ON COOLING COILS: CLOSED TO COIL
E. AUTOMATIC CONTROL VALVE (ACV) ON HEATING COILS: OPEN TO COIL
SINGLE ZONE VARIABLE AIR VOLUME AIR-HANDLING UNIT (AHU-XX) CONTROL SEQUENCE
1. AHU SHALL BE CONTROLLED BY STAND ALONE DIRECT DIGITAL CONTROLLER.
2. SUPPLY AND EXHAUST FANS SHALL BE CONTROLLED BY OCCUPIED/UNOCCUPIED SCHEDULE FROM DDC SYSTEM.
3. WHEN AHU-XX IS SCHEDULED ON, SUPPLY FAN SHALL START AND RUN CONTINUOUSLY. SUPPLY FAN AIR FLOW SHALL BE CONTROLLED AS INDICATED BELOW.
OUTDOOR AIR DAMPER SHALL OPEN TO MINIMUM POSITION.
4. WHEN AHU-XX IS SCHEDULED ON, EXHAUST AIR DAMPER SHALL OPEN FULLY. AS DIFFERENTIAL BETWEEN SUPPLY AIRFLOW AND RETURN AIRFLOW INCREASES
ABOVE SET POINT (430 CFM, ADJUSTABLE) EXHAUST FAN VARIABLE FREQUENCY DRIVE SHALL MODULATE FAN SPEED TO MAINTAIN AIRFLOW DIFFERENTIAL AT SET
POINT.
5.
ADJUSTABLE). AS SPACE TEMPERATURE RISES ABOVE HEATING SET POINT, SUPPLY FAN VFD SHALL MODULATE SUPPLY FAN AIRFLOW TO MINIMUM AIRFLOW
(GREATER OF MINIMUM OUTDOOR AIR 430 CFM, ADJUSTABLE OR MINIMUM FAN SPEED). ON FURTHER RISE IN SPACE TEMPERATURE HEATING COIL DISCHARGE AIR
6.
TEMPERATURE RISES ABOVE COOLING SET POINT, OUTDOOR AIR AND RETURN AIR DAMPERS SHALL MODULATE TO MAINTAIN MIXED AIR TEMPERATURE AT COOLING
COIL DISCHARGE SET POINT (AS DETERMINED BELOW). AFTER OUTDOOR AIR DAMPER IS FULLY OPEN, ON FURTHER RISE IN SPACE TEMPERATURE WCC-XX ACV SHALL
ON FURTHER RISE IN SPACE TEMPERATURE SUPPLY FAN VFD SHALL MODULATE AIRFLOW FROM MINIMUM SPEED TO MAXIMUM SUPPLY AIRFLOW TO MAINTAIN SPACE
7. OPTIMUM START: UNIT SHALL BE CAPABLE OF STARTING PRIOR TO SCHEDULED OCCUPANCY BASED ON THE CALCULATED TIME NECESSARY FOR ZONES TO REACH
OCCUPIED SET POINT TEMPERATURE. WHEN BELOW HEATING SET POINT, OUTSIDE AIR DAMPER SHALL REMAIN CLOSED AND RETURN AIR DAMPER OPEN DURING
OPTIMAL START PERIOD. WHEN ABOVE COOLING SET POINT OUTDOOR AIR DAMPER SHALL REMAIN CLOSED AND RETURN DAMPER OPEN UNLESS ECONOMIZER
CONTROL INDICATED ABOVE IS ENABLED.
8. WHEN SPACE RELATIVE HUMIDITY IS ABOVE SET POINT (55% ADJUSTABLE) SYSTEM SHALL OPERATE IN DEHUMIDIFICATION MODE AS FOLLOWS:
A. UNIT COOLING COIL DISCHARGE AIR TEMPERATURE SHALL BE RESET TO MINIMUM COOLING SET POINT. WCC-XX ACV SHALL MODULATE TO MAINTAIN COOLING
COIL DISCHARGE AIR TEMPERATURE AT SET POINT.
B. ON RISE IN SPACE RELATIVE HUMIDITY SUPPLY FAN VFD SHALL MODULATE FAN TO DESIGN AIRFLOW TO MAINTAIN SPACE RELATIVE HUMIDITY SET POINT.
C. ALL RHC-XX ACV SHALL MODULATE IN PARALLEL TO MAINTAIN SPACE TEMPERATURE AT COOLING SET POINT.
9. WHEN SYSTEM IS IN THE "UNOCCUPIED" MODE, SYSTEM SHALL OPERATE AS SPECIFIED ABOVE EXCEPT THE OUTDOOR AND EXHAUST DAMPERS SHALL REMAIN
CLOSED. FAN SHALL CYCLE BASED ON DEMAND FROM SPACE.
10. SAFETY SHUTDOWN: SAFETY SHUTDOWN CIRCUIT SHALL BE PROVIDED EXTERNAL TO SYSTEM CONTROLLER. CIRCUIT SHALL BE DIRECTLY CONNECTED TO
STARTERS OF MOTOR-POWERED EQUIPMENT AND SHALL FUNCTION REGARDLESS OF STATUS OF SYSTEM CONTROLLER. IN EVENT OF SYSTEM SHUTDOWN, DEVICES
SHALL RETURN TO NORMAL POSITION. CIRCUITS SHALL BE RESET MANUALLY. FOLLOWING SHALL COMPRISE SAFETY SHUT-DOWN CIRCUIT:
A. SPACE FIRE ALARM
B. SMOKE DETECTION IN SUPPLY AIR DUCT
C. TEMPERATURE ENTERING COOLING COIL FALLS BELOW 40°F (FREEZESTAT)
SCHEMATIC
SINGLE ZONE VARIABLE AIR VOLUME (VAV) AIR HANDLING UNIT (AHU) CONTROL
PLAN DESIGNATION POINT DESCRIPTION
POINT TYPE
NOTES
AO DO AI DI VP ALARMS
RHC-XX ACV REHEAT COIL-XX ACV X MODULATE ALL REHEAT COILS IN PARALLEL
OATEMP OUTDOOR AIR TEMPERATURE X
AHU-XX OA DAMP AHU-XX OUTDOOR AIR DAMPER X
AHU-XX OA FE AHU-XX OUTDOOR AIR FLOW X X ALARM WHEN +/- 10% FROM SETPOINT
AHU-XX OA FE SP AHU-XX OUTDOOR AIR FLOW SETPOINT X SET POINT AS SCHEDULED FOR MINIMUM OUTDOOR AIRFLOW (ADJUSTABLE)
AHU-XX OA FILTER DP
DIFFERENTIAL PRESSURE
AHU-XX FILTER OUTDOOR AIR
X X ALARM ABOVE 0.9 IN W.G (225 PA) (ADJUSTABLE)
AHU-XX RA DAMP AHU-XX RETURN AIR DAMPER X
AHU-XX MAT AHU-XX MIXED AIR TEMPERATURE X
AHU-XX SA FILTER DP
DIFFERENTIAL PRESSURE
AHU-XX FILTER SUPPLY AIR
X X ALARM ABOVE 0.9 IN W.G (225 PA) (ADJUSTABLE)
AHU-XX HC-XX ACV
CONTROL VALVE
AHU-XX HEATING COIL AUTOMATIC
X
AHU-XX WCC-XX ACV
AUTOMATIC CONTROL VALVE
AHU-XX WATER COOLING COIL
X
AHU-XX SF STATUS AHU-XX SUPPLY FAN STATUS X X ALARM MISMATCH WITH AHU-XX SF S/S
AHU-XX SF S/S AHU-XX SUPPLY FAN START/STOP X
AHU-XX SF VFD AHU-XX SUPPLY FAN VFD X X COMMUNICATION VIA PROTOCOL AS SPECIFIED; ALARM WHEN VFD FAILS
AHU-XX DAT
TEMPERATURE
AHU-XX UNIT DISCHARGE AIR
X
AHU-XX DAT SP
SET POINT
AHU-XX DISCHARGE AIR TEMPERATURE
X (ADJUSTABLE)
AHU-XX SUPPLY DD AHU-XX SUPPLY DUCT DETECTOR X PROVIDE AUX CONTACT TO DDC SYSTEM
AHU-XX SA FE AHU-XX SUPPLY AIR FLOW X
AHU-XX SA FE SP AHU-XX SUPPLY AIR FLOW SET POINT X
AHU-XX SAP SP
POINT
AHU-XX DUCT STATIC PRESSURE SET
X
AHU-XX RA FE SP AHU-XX RETURN AIR FLOW SET POINT X
AHU-XX RAT AHU-XX RETURN AIR TEMPERATURE X
AHU-XX RAH AHU-XX RETURN AIR HUMIDITY X
AHU-XX RF STATUS AHU-XX EXHAUST FAN STATUS X X ALARM MISMATCH WITH AHU-XX EF S/S
AHU-XX RF S/S AHU-XX EXHAUST FAN START/STOP X
AHU-XX RF VFD AHU-XX EXHAUST FAN VFD X X COMMUNICATION VIA PROTOCOL AS SPECIFIED; ALARM WHEN VFD FAILS
AHU-XX EA DAMP AHU-XX EXHAUST AIR DAMPER X
AHU-XX FRZ AHU-XX FREEZESTAT X X
NOTE:
XXX REFERS TO ROOM NUMBER SHOWN ON SHEETS.3.
XX REFERS TO AHU DESIGNATIONS AS SCHEDULED.2.
BY DIVISION 28 3176.
PROVIDE BY FIRE ALARM INSTALLER AS REQUIRED 1.
SINGLE ZONE VARIABLE AIR VOLUME (VAV) AIR HANDLING UNIT (AHU) CONTROL SCHEMATIC
(HEATING WATER/CHILLED WATER COOLING) (EXISTING AHU IN BLDG 401)
M
OUTSIDE AIR
IT
M
D
VFD
FE
FE
SF VFD
AHU-XX.XX
T
RAT
AHU-XX.X
SEE NOTE 1
SUPPLY DD
AHU-XX.X
FE SA
AHU-XX.X
SF S/S
AHU-XX.XX
SF STATUS
AHU-X.XX
DAMP
OA
AHU-XX.X
FE OA
AHU-XX.X
P
SAP
AHU-XX.X
TI
ACV
WCC-X
W C
C -X
RETURN AIR
SUPPLY AIR
T
HCDAT
AHU-XX.X
H C -X
ACV
HC-X
T
STAT
FREEZE
AHU-XX.X
T OA TEMP
SHUTDOWN
HVAC EMERGENCY
FE
RA FE
AHU-XX.X
T
MAT
AHU-XX.X
M
EA DAMP
AHU-XX.X
RAH
AHU-XX.X
H
EXTENT OF AHU
T
CCDAT
AHU-XX.X
TI
M
DAMP
RA
AHU-XX.X
IT
M
VFD
RR VFD
AHU-XX.XX
RR S/S
AHU-XX.XX
RR STATUS
AHU-X.XX
T
SATSPH-XXX SATSPC-XXX
SAT-XXX
H SAH-XXX
OS OS-XXX
SEQUENCE OF OPERATION
R H
C -X
MAY 31, 2019
KL GRAVES
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
M01
311 312
112111110
204B
205309
310 207
104 103
102 101
EQUIP ROOM
WATER
ELECTRICAL
MECHANICAL
STAIRS
CHANGING
ROOM SHOWER
LOCKER
HALLWAY
RECEPTION
TECH
ROOMOFFICE OFFICE
SCOPE
RM
JANITOR
CHANGING
ROOM
SHOWER LOCKER
ELEC
DATA HALLWAY
VESTIBULE
OFFICEOFFICEOFFICEOFFICE
OFFICE
CLOSET
CONFERENCE/
BREAKROOM
A/V
CLOSET
321 4 4.7 5 6 7 8
A
A.4
B
C
D
A
A.4
B
C
D
C.3
FIRST FLOOR
FIRE PROTECTION PLAN
MF150 0
FIRST FLOOR FIRE PROTECTION PLAN
S T O R A G E
3 4
N O
R
TH
LEGEND:
LIGHT HAZARD
ORDINARY HAZARD GROUP 1
CLASS IV STORAGE
FIRE PROTECTION RISER MODIFICATIONS DIAGRAM
P
NO SCALE
CONNECTION
DEPARTMENT
EXST FIRE
BACKFLOW ASSEMBLY
EXST DOUBLE CHECK
6"
FIRST FLOOR
SCALE: 1/8"=1'-0"
FS
P
ALARM VALVE
MAIN DRAIN
FS
P
ALARM VALVE
MAIN DRAIN
TO OFFICE AREATO STORAGE AREA& PENTHOUSE
TO MECHANICAL ROOM
FS
P
ALARM VALVE
MAIN DRAIN
MAY 31, 2019
KL GRAVES
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
A.4
B
C
D
M02
MECHANICAL ROOM
M01
STAIRS
SECOND FLOOR
FIRE PROTECTION PLAN
MF151 0
SECOND FLOOR FIRE PROTECTION PLAN
O
SEE SHEET MF150 FOR PROTECTION IN THIS AREA.1.
LEGEND:
LIGHT HAZARD
ORDINARY HAZARD GROUP 1
MAY 31, 2019
KL GRAVES
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
ELECTRICAL ONE-LINE DIAGRAM
EO650 0
PARTIAL PANEL FDP ELECTRICAL ONE-LINE DIAGRAM
FOR ELECTRICAL LEGEND SEE DRAWING GG9.1.
NOTES:
MOUNT TRANSFORMER. SEE DRAWING EP150.
ROUTE IN EXISTING 4x4" DUCT BANK TO NEW HH-1 AND ON TO PAD 2.
KA36150 3P.
RE-USE DEMOLISHED SPACE FOR NEW 150A BREAKER. SQUARE D 1.
KEYNOTES:
700A 100A 150A 300A 300A 50A 100A
C H
IL
L E
R
T R
A
2 3 4 5 6 7 8 9 10 11 12 13 14
S P
A C
E
P A
N E
L L
A
S P
A R
E
S P
A R
E
S P
A C
E
S P
A R
E
S P
A R
E
S P
A C
E
P A
N E
L M
S P
A C
E
P A
N E
L M
T V
S S
LB
PANEL
/0
G
N D -1 /2 "C
208Y/120V
42 SPACE
100A MAIN
150A RATED BUS
PANEL FDP, 1600A, 1500AT, 208Y/120, 3PH, 4W
MOUNT TRANSFORMER
TO EXISTING PAD
LOCATION: ELECTRICAL ROOM 212
NUMBER (TYP)
SPACE
150A 225A 150A
#3/0 GND
(4) SETS 4-500KCMIL,
"LI"
INVERTER
LIGHTING
1KVA
MAY 31, 2019
NC VEEN
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
M01
311 312
112111110
204B
205309
310 207
104 103
102 101
EQUIP ROOM
WATER
ELECTRICAL
MECHANICAL
STAIRS
CHANGING
ROOM SHOWER
LOCKER
HALLWAY
RECEPTION
TECH
ROOMOFFICE OFFICE
SCOPE
RM
JANITOR
CHANGING
ROOM
SHOWER LOCKER
ELEC
DATA HALLWAY
VESTIBULE
OFFICEOFFICEOFFICEOFFICE
OFFICE
CLOSET
CONFERENCE/
BREAKROOM
A/V
CLOSET
321 4 4.7 5 6 7 8
A
A.4
B
C
D
A
A.4
B
C
D
C.3
C.6
F
SS
4 4
SS
30 STORAGE
6 6
15 17
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
FIRST FLOOR ELECTRICAL
POWER AND COMMUNICATION PLAN
EP150 0
FIRST FLOOR…