Atch 4_USDA Ames IFC Volume 1 Dwgs 1 of 6.pdf
PDF 14 MB Posted
- Solicitation number
- 12639525R0012
About this file
This document is a set of architectural and engineering demolition and site plans for the USDA National Centers for Animal Health Mycobacteriology Laboratory Relocation project in Ames, Iowa. The comprehensive plan includes detailed demolition drawings for multiple building systems across ground level, penthouse, and roof levels, covering architectural, HVAC, electrical, plumbing, and security systems.
Key elements of the demolition plan include removing interior walls, partitions, mechanical equipment, electrical fixtures, piping, and security devices within Building 21. The site plans also outline utility relocations, landscaping changes, and site grading, with specific notes about maintaining egress paths, protecting existing infrastructure, and coordinating with the owner during demolition activities. The plans are prepared by Stanley Consultants and dated May 31, 2019, indicating a planned renovation of the existing laboratory facility to support the USDA's animal and zoonotic disease research capabilities.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D
A
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
MYCOBACTERIOLOGY LABORATORY RELOCATION
AMES, IOWA
27100.10
DRAWING INDEX - SHEET 1
GG2 0
NONE
ML MARTZ
MAY 31, 2019
RJ LUKKARINEN
V O
L U
M E
V O
L U
M E
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
DRAWING INDEX - SHEET 2
GG3 0
MAY 31, 2019
L U
M E
V O
L U
M
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
GENERAL NOTES
OR CL
OR PL
SQUARE
DIAMETER OR ROUND
CENTERLINE
PROPERTY LINE
OPENING OR DEPRESSION IN SLAB OR WALL
OPENING WITH GRATING COVER (PLAN)
ROUGHENED CONSTRUCTION JOINT
CONSTRUCTION JOINT (KEYWAY)
CONSTRUCTION JOINT (KEYWAY) WITH WATERSTOP
MASONRY CONTROL JOINT (IN PLAN)
MASONRY EXPANSION JOINT (IN PLAN)
GUARDRAIL/HANDRAIL
FIELD MEASUREMENT NOTES
ROUGHENED CONSTRUCTION JOINT WITH WATERSTOP
OPENING WITH CHECKERED PLATE COVER (PLAN)
S P
A N
SAND, CMU, PLASTER
ROCK
EARTH
CRUSHED ROCK
CONCRETE
GRANULAR FILL
GENERAL MATERIALS LEGEND
DIMENSIONS AND SCALE
VIEW MARKERS GENERAL SYMBOLS
CALLED OUT
ON WHICH VIEW IS
DRAWING NUMBER(S)
NUMBER
VIEW IDENTIFICATION
OF DETAIL
DESIGNATES LOCATION
ELEVATION IS VIEWED
FROM WHICH PLAN OR
DESIGNATES DIRECTION
PLANE OF SECTION
DESIGNATES CUTTING
EL 100'-0"
ENTIRE DRAWING, PRINCIPAL ASPECTS OF REVISIONS ARE "CLOUDED".
A CONTRACT ADDENDUM. WHEN REVISIONS INVOLVE LESS THAN
RIGHT OF THE TRIANGLE INDICATES THE REVISION IS PART OF
NUMBER IDENTIFIED. THE LETTER "A" IMMEDIATELY TO THE
THE NUMBER IN THE TRIANGLE INDICATES THE REVISION
REVISION IDENTIFICATION SYMBOL:
SUBSTITUTE LETTER OR NUMBER FOR ASTERISK
COLUMN IDENTIFICATION:
OUTLINE OF FUTURE OBJECT
OUTLINE OF NEW OR RELOCATED OBJECT
EXISTING OBJECT TO BE REMOVED OR RELOCATED
EXISTING OBJECT LINE
MATCH LINE
MATERIAL BREAK LINE
SURFACE BREAK LINE
HIDDEN LINE
CENTER LINE
ELEVATION DESIGNATION
NUMBER AT RIGHT INDICATES CONTRACT INSTALLING.
NUMBER AT LEFT INDICATES CONTRACT FURNISHING,
CONTRACT IDENTIFICATION:
REINFORCING BARS IN CONCRETE
WELDED WIRE FABRIC
NON-FERROUS METAL
GLASS (ELEVATION)
STEEL (IN SECTION)
BATT INSULATION
RIGID INSULATION
PLYWOOD
ROUGH WOOD (IN SECTION)
BRICK IN SECTION
ROOM AND OPENING IDENTIFICATION SYMBOLS
1. ALL DIMENSIONS OF EXISTING CONSTRUCTION ARE APPROXIMATE. CONTRACTOR SHALL SURVEY AND MAKE
ALL NECESSARY FIELD MEASUREMENTS OF EXISTING STRUCTURES AND EQUIPMENT TO VERIFY DIMENSIONS
SHOWN ON DRAWINGS, AND TO PROVIDE DIMENSIONS NOT SHOWN, PRIOR TO FABRICATION. ERRORS, INCONSISTENCIES OR OMISSIONS DISCOVERED SHALL BE REPORTED IN WRITING TO THE DESIGN
PROFESSIONAL AND OWNER'S REPRESENTATIVE WITHIN TWENTY-FOUR (24) HOURS. COSTS FOR
MODIFICATIONS OF NEW CONSTRUCTION, DUE TO LACK OF CONFIRMATION OF DIMENSIONS BY FIELD
MEASUREMENTS, SHALL BE BORNE BY CONTRACTOR.
2. CONTRACTOR SHALL REVIEW CONTRACT DOCUMENTS TO DETERMINE THE EXACT LOCATION OF ALL WORK
AND VERIFY SPATIAL RELATIONSHIPS OF ALL WORK. ANY QUESTION CONCERNING LOCATION OR SPATIAL
RELATIONSHIPS SHALL BE SUBMITTED TO THE OWNER'S REPRESENTATIVE. SPECIFIC LOCATIONS FOR
EQUIPMENT, PIPELINES, DUCTWORK AND OTHER SUCH ITEMS OF WORK, WHERE NOT DIMENSIONED ON
DRAWINGS, SHALL BE DETERMINED BY CONTRACTOR. CONTRACTOR SHALL BE RESPONSIBLE FOR THE
PROPER FITTING OF THE WORK IN PLACE.
ELEVATION
B-SF1
SF1,SF2
DETAIL
C-SF1
SECTION
A-SF1
A-SF1
C-SF1
B-SF1
DOOR OPENING
WINDOW OPENING
LOUVER OPENING
ROOM NUMBER
ROOM NAME101
W101
LV101
1 A
NUMERIC SCALE VALUES (1/4"=1'-0", ETC) APPLY ONLY AT FULL SIZE.
TO SCALE) IS SHOWN ONLY WHERE DIMENSION IS OBVIOUSLY OUT OF SCALE.
DIMENSIONS ARE GENERALLY TO SCALE, BUT SHOULD NOT BE SCALED. USE DIMENSIONS SHOWN. NTS (NOT
DIMENSIONS AND/OR ELEVATIONS MARKED THUS (+/-) MUST BE VERIFIED IN THE FIELD BY THE CONTRACTOR.
REVIEW OF THE ENGINEER.
REQUIRED BY THE CONTRACTOR TO SUIT EQUIPMENT FURNISHED. FINAL DIMENSIONS ARE SUBJECT TO THE
DIMENSIONS AND/OR ELEVATIONS MARKED THUS ( ) ARE ASSUMED AND SHALL BE VERIFIED OR MODIFIED AS
CONSTRUCTION FROM THE ENGINEER.
DIMENSIONS AND/OR ELEVATIONS MARKED THUS ( ) ARE APPROXIMATE. OBTAIN FINAL DIMENSIONS FOR
1. ALL SYMBOLS AND ABBREVIATIONS SHOWN ON THIS LEGEND
MAY NOT APPEAR ON THIS SET OF DRAWINGS.
GENERAL LEGEND
GG4 0
DL GEORGE
MAY 31, 2019
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
ABBREVIATIONS
ABBREVIATION TERM
A AMPERE
AA ADHESIVE ANCHOR
AB ANCHOR BOLT(S)
AC ACRE; ALTERNATING CURRENT
A/C ACCESS CONTROL; AIR CONDITION(ING)
ACB AIR CIRCUIT BREAKER
ACI AMERICAN CONCRETE INSTITUTE
ACCUR ACCURATE
ACV AUTOMATIC CONTROL VALVE
ACV-3 3 WAY AUTOMATIC CONTROL VALVE
AD ACCESS DOOR
ADA AMERICAN DISABILITIES ACT
ADDL ADDITIONAL
ADJ ADJACENT; ADJOINING; ADJUST(ABLE)
AF AMPERE FRAME; AUDIO FREQUENCY
AFF ABOVE FINISH(ED) FLOOR
AFG ABOVE FINISH(ED) GRADE
AGGR AGGREGATE
AH AMPERE HOUR
AHU AIR HANDLING UNIT
AI ANALOG INPUT
AIC AMPERE INTERRUPTING CURRENT (CAPACITY)
AL ALUMINUM
ALT ALTERNATE; ALTITUDE
AMP AMPERE
AMT AMOUNT
ANN ANNUNCIATOR
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
AO ANALOG OUTPUT
APPROX APPROXIMATE
APU AUXILIARY POWER UNIT
APVD APPROVED
ARC AUTOMATIC RECEPTACLE CONTROL
ARCH ARCHITECTURE; ARCHITECTURAL
AS AIR SUPPLY, AIR SEPARATOR
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASD ADJUSTABLE SPEED DRIVE
ASSY ASSEMBLY
ASTM AMERICAN SOCIETY FOR TESTING MATERIALS
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BAT BATTEN; BATTERY
B/B BACK TO BACK
BC
CHORD; BUILDING CODE
BETWEEN CENTERS; BOLT CIRCLE; BOTTOM
BD BOARD
BDRY BOUNDARY
BF BOTH FACES
BFF BELOW FINISH FLOOR
BITUM BITUMINOUS
BL BASELINE; BUILDING LINE
BLDG BUILDING
BLR BOILER
BLW BELOW
BM BEAM(S); BENCHMARK; BENDING MOMENT
BNDG BONDING
BOC BACK OF CURB
BOD BOTTOM OF DUCT
BOF BOTTOM OF FOOTING
BOG BOTTOM OF GIRT
BOS BOTTOM OF STEEL
BOT BOTTOM
BOTR BOTTOM OF TRENCH
B PL BASE PLATE
BRG BEARING
BRKR BREAKER
BTU BRITISH THERMAL UNIT
BTWN BETWEEN
BSMT BASEMENT
C CELSIUS; CHANNEL
CA CABLE
CAB CABINET
CAP CAPACITOR; CAPACITY
CB CARRIAGE BOLT; CATCH BASIN; CIRCUIT BREAKER
C TO C CENTER TO CENTER
CCTV CLOSED CIRCUIT TELEVISION
CCVT COUPLING CAPACITIVE VOLTAGE TRANSFORMER
CCW COUNTERCLOCKWISE
CD CEILING DIFFUSER
CEB CONCRETE EQUIPMENT BASE
CEMS CONTROL EMISSIONS MONITORING
CFM CUBIC FEET PER MINUTE
CFS CUBIC FEET PER SECOND
CG CEILING GRILLE
C&G CURB AND GUTTER
CHAN CHANNEL
CHEM CHEMICAL
CHFR CHAMFER
CHGR CHARGER
CHKR PL CHECKER PLATE
CIP CAST IN PLACE; CAST IRON PIPE
CIRC CIRCULAR
CISP CAST IRON SOIL PIPE
CJ CONSTRUCTION JOINT
CKT CIRCUIT
CL CENTERLINE; CLEARANCE; CLOSE
CLF CURRENT LIMITING FUSE
CLG CEILING; COOLING
CLJ CONTROL JOINT
CLO CLOSET
CLR CLEAR
cm CENTIMETER (DIMENSION)
ABBREVIATION TERM
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNIT
CND CONDUIT
CNTOR CONTACTOR
CNTRL CONTROL
CNSL CONSOLE
CNVR CONVEYOR
CO CLEANOUT
COL COLUMN
COMB COMBINATION
COMM COMMUNICATION
CONC CONCENTRIC; CONCRETE
CONN CONNECT(ION) (OR)
CONT CONTINUATION; CONTINUOUS
CONST CONSTRUCTION
CP CONTROL PANEL
CPT CONTROL POWER TRANSFORMER
CR CONTROL RELAY; CURRENT RELAY
CS LOCAL CONTROL STATION
CT CERAMIC TILE; CURRENT TRANSFORMER
CTR CENTER
CTRL CONTROL
CTV CABLE TELEVISION
CU COPPER
CU CM CUBIC CENTIMETER
CU FT CUBIC FOOT
CU IN CUBIC INCH
CU M CUBIC METER
CU MM CUBIC MILLIMETER
CU YD CUBIC YARD
D DEEP
DB DUCT BANK
DBL DOUBLE
DBM DECIBEL METER
DC DIRECT CURRENT
DCS DISTRIBUTED CONTROL SYSTEM
DDC DIRECT DIGITAL CONTROLS
DEG DEGREES
DET DETAIL
DF DRINKING FOUNTAIN
DG DIESEL GENERATOR
DI DIGITAL INPUT; DUCTILE IRON
DIM DIMENSION(S)
DIP DUCTILE IRON PIPE
DIA DIAMETER
DIAG DIAGONAL
DISC DISCONNECT
DIST DISTANCE
DISTR DISTRIBUTION
DM DEMAND METER
DN DOWN
DO DIGITAL OUTPUT; DITTO
DOT DEPARTMENT OF TRANSPORTATION
DP DEPTH
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DR DRAIN
DS DOWNSPOUT
DWG DRAWING(S)
E EAST
EA EACH
EAT ENTERING AIR TEMPERATURE
ED EQUIPMENT DRAIN
E-E EDGE TO EDGE
EF EACH FACE; EXHAUST FAN
EG ENGINE GENERATOR; EXHAUST GRILLE
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EMBED EMBEDMENT
EMER EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EP EXPLOSION PROOF
EQ EQUAL
EQL SP EQUALLY SPACED
EQPT EQUIPMENT
ER EMERGENCY REMOTE
ES ELECTRICAL SUPPLY
ESO EMERGENCY SHUTDOWN
EST ESTIMATE
ET EXPANSION TANK
ETC ET CETERA
ETR EXISTING TO REMAIN
EW EACH WAY
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXP EXPANSION; EXPOSED
EXST EXISTING
EXT EXTENSION; EXTERIOR
FACP FIRE ALARM CONTROL PANEL
FC FAIL CLOSED
FCO FLOOR CLEANOUT
FCU FAN COIL UNIT
FD FIRE DAMPER; FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FAR FACE
F/I FREQUENCY TO CURRENT
FIP FAIL IN PLACE
FIN FLR FINISH(ED) FLOOR
ABBREVIATION TERM
FL FAIL LAST; FLOOR
FLL FLOWLINE
FLA FULL LOAD AMPS
FLEX FLEXIBLE
FLG FLANGE(S)
FMC FLEXIBLE METAL CONDUIT
FO FAIL OPEN; FIBER OPTIC
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FRP FIBERGLASS REINFORCED PIPE (OR PLASTIC)
FS FAR SIDE
FT FEET; FOOT
FTG FOOTING
FU FUSE
FWD FORWARD
FXTR FIXTURE
GA GAUGE (GAGE)
GALV GALVANIZE(D)
GD GROUND DETECTOR
GEN GENERATOR
GFI GROUND FAULT INTERRUPTER
GL GIRT LINE
GND GROUND
GR GRADE
GRAN GRANULAR
GRS GALVANIZED RIGID STEEL CONDUIT
GRTG GRATING
GS GAS SUPPLY
GWB GYPSUM WALL BOARD
GYP GYPSUM
H HIGH
HA HAND-AUTO
HB HOSE BIBB
HGR HANGER
HH HANDHOLE
HID HIGH INTENSITY DISCHARGE
HM HOLLOW METAL
HOA HAND-OFF-AUTO
HOR HAND-OFF-REMOTE
HORIZ HORIZONTAL
HP HIGH POINT; HORSE POWER
HPS HIGH PRESSURE SODIUM
HR HOUR
HRSG HEAT RECOVERY STEAM GENERATOR
HS HIGH STRENGTH; HYDRAULIC SUPPLY
HSS HOLLOW STRUCTURAL SECTION
HT HEIGHT; HIGH TENSION
HV HIGH VOLTAGE
HVAC HEATING, VENTILATION, AND AIR CONDITIONING
HWH HOT WATER HEATER
HZ HERTZ
I/I CURRENT TO CURRENT
I/O INPUT/OUTPUT
I/P CURRENT TO PNEUMATIC
IA INSTRUMENT AIR
ID INSIDE DIAMETER
IE INVERT ELEVATION
IF INSIDE FACE
IG ISOLATED GROUND
IMC INTERMEDIATE METALLIC CONDUIT
IN. INCH(ES)
INL INLET
INST INSTANTANEOUS
INSTR INSTRUMENTATION
INSUL INSULATION
INT INTERIOR
INTLK INTERLOCK
INV INVERT
ISA INTERNATIONAL SOCIETY OF AUTOMATION
JB JUNCTION BOX
JOA JOG-OFF-AUTO
JT JOINT
KB KNEE BRACE
KCM KILOGRAMS PER CUBIC CENTIMETER
KCMIL THOUSAND CIRCULAR MIL
KO KNOCKOUT
KPL KICK PLATE
KSCM KILOGRAMS PER SQUARE CENTIMETER
KSM KILOGRAMS PER SQUARE METER
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWY KEYWAY
L LENGTH, ANGLE
LAT LEAVING AIR TEMPERATURE
LAV LAVATORY
LB POUND(S)
LC LOAD CENTER
LF LINEAL FEET
LFMC LIQUIDTIGHT FLEXIBLE METAL CONDUIT
LG LENGTH; LONG
LLBB&H LONG LEGS BACK TO BACK AND HORIZONTAL
LLBB&V LONG LEGS BACK TO BACK AND VERTICAL
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LMT LIMIT
LOA LOCAL-OFF-AUTO
LOR LOCAL-OFF-REMOTE
LP LOW POINT; 3 PH, 4W POWER PANEL
LPG LIQUIFIED PETROLEUM GAS
LR LOCAL-REMOTE
L/S LITERS PER SECOND
ABBREVIATION TERM
LT LEFT
LTG LIGHTING
LTWT LIGHTWEIGHT
LV LOW VOLTAGE
LVR LOUVER
LWC LIGHTWEIGHT CONCRETE
LWT LEAVING WATER TEMPERATURE
m METER (DIMENSION)
M METER (DEVICE)
mm MILLIMETER (DIMENSION)
MA MECHANICAL ANCHOR; MILLIAMPERE
MAG MAGNETIC
MAN MANUAL
MATL MATERIAL
MAX MAXIMUM
MB MOP BASIN
MBH 1000 BTU'S PER HOUR
MCB MINIATURE CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCCB MOLDED CASE CIRCUIT BREAKER
MCOV MAXIMUM CONTINUOUS OPERATING VOLTAGE
MCP MOTOR CIRCUIT PROTECTOR
MECH MECHANICAL
MFR MANUFACTURER; MULTIFUNCTION RELAY
MH MANHOLE; METAL HALIDE
MIN MINIMUM
MISC MISCELLANEOUS
MJ MECHANICAL JOINT
MLO MAIN LUG ONLY
MO MASONRY OPENING
MOR MAINT-OFF-REMOTE
MOT MOTOR
MOV METAL OXIDE VARISTOR; MOTOR OPERATED VALVE
MPR MOTOR PROTECTION RELAY
MS MOP SINK
M/S METERS PER SECOND
MTG MOUNTING
MV MEDIUM VOLTAGE
MVA MEGAVOLT AMPERE
MVMCC MEDIUM VOLTAGE MOTOR CONTROL CENTER
MVMS MEDIUM VOLTAGE MOTOR STARTER
N NEW; NORTH
NC NORMAL CROWN
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
NEC NATIONAL ELECTRICAL CODE
NEMA
ASSOCIATION
NATIONAL ELECTRICAL MANUFACTURERS
NESC NATIONAL ELECTRICAL SAFETY CODE
NEUT NEUTRAL
NF NEAR FACE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO. NUMBER
NOM NOMINAL
NPT NATIONAL PIPE THREAD
NS NEAR SIDE
NTS NOT TO SCALE
OA OUTSIDE AIR
OC ON CENTER; OPEN-CLOSE; OVERCURRENT
OCR OPEN-CLOSE-REMOTE
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OIC OPERATOR INTERFACE STATION
OMR ON-MAINTENANCE-REMOTE
OPNG OPENING
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
OSC OPEN-STOP-CLOSE
OSHA OCCUPATIONAL SAFETY AND HEALTH ASSOCIATION
OVLD OVERLOAD
P POLE
P&ID PIPING & INSTRUMENTATION DIAGRAM
P/I PNEUMATIC TO CURRENT
PA PLANT AIR; PUBLIC ADDRESS
PB PULLBOX
PC PERSONAL COMPUTER; POINT OF CURVATURE
PCB POWER CIRCUIT BREAKER
PCC PORTLAND CEMENT CONCRETE
PF POWER FACTOR
PFD PROCESS FLOW DIAGRAM
PFM POWER FACTOR METER
PH PHASE
PI POINT OF INTERSECTION OF HORIZONTAL CURVE
PL PLATE; PROPERTY LINE
PLC PROGRAMMABLE LOGIC CONTROLLER
PLTF PLATFORM
PMCS POWER MANAGEMENT CONTROL SYSTEM
PNL PANEL
POT POINT OF TANGENT
PP 3 PH, 3W POWER PANEL
PPW PRETREATED PUMPED WASTE
PRC POINT OF REVERSE CURVE
PRCST PRECAST
PRE POWER ROOF EXHAUSTER
PRESS PRESSURE
PROJ PROJECT; PROJECTED; PROJECTION
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PT POINT OF TANGENCY
PVC POLYVINYL CHLORIDE
PWR POWER
QTY QUANTITY
ABBREVIATION TERM
R RADIUS; RELOCATED; RISER(S)
R/I RESISTANCE TO CURRENT
RA RETURN AIR
RC REMOVE CROWN
RCCP REINFORCED CONCRETE CULVERT PIPE
RCP REINFORCED CONCRETE PIPE
RCPT RECEPTACLE
RD ROOF DRAIN, RETURN DIFFUSER
RECT RECTANGLE
REF REFERENCE
REFRIG REFRIGERATOR
REINF REINFORCING
RELOC RELOCATED
REQD REQUIRED
REV REVERSE; REVISION
RG RETURN GRILLE
RGS RIGID GALVANIZED STEEL
RH REHEAT COIL
RLA RATED LOAD AMPS
RLY RELAY
RM ROOM
RMS ROOT MEAN SQUARE
RO ROUGH OPENING
ROW RIGHT OF WAY
RPM REVOLUTIONS PER MINUTE
RR RAILROAD
RT RIGHT
S SOUTH
S/S START/STOP
SA SUPPLY AIR; SURGE ARRESTOR
SAN SANITARY SEWER
SC SLIP-CRITICAL
SCHED SCHEDULE
SD SANITARY DRAIN
SEC SECONDS
SECT SECTION
SG SUPPLY GRILLE
SH SHOWER
SHT SHEET
SIM SIMILAR
SK SINK
SLBB&H SHORT LEGS BACK TO BACK AND HORIZONTAL
SLBB&V SHORT LEGS BACK TO BACK AND VERTICAL
SP SPACE
SPDT SINGLE POLE, DOUBLE THROW
SPEC SPECIFICATION(S)
SPST SINGLE POLE, SINGLE THROW
SQ SQUARE
SQ CM SQUARE CENTIMETERS
SQ FT SQUARE FEET
SQ IN SQUARE INCHES
SQ M SQUARE METERS
SQ MM SQUARE MILLIMETERS
SS SERVICE SINK
SST STAINLESS STEEL; SOLID STATE TRIP
SSW SYNC SELECTOR SWITCH
ST SHUNT TRIP
STBY STANDBY
STD STANDARD; STORM DRAIN
STIFF STIFFENER
STL STEEL
STR STARTER
STRL STRUCTURAL
STS STORM SEWER
SUS SECONDARY UNIT SUBSTATION
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SWYD SWITCHYARD
SYMM SYMMETRICAL
SYNC SYNCHRONIZE
T TREAD(S)
T/ TOP OF
T&B TOP AND BOTTOM
TB TERMINAL BLOCK
TBX TERMINAL BOX
TC TEST CONNECTION; TRIP COIL
TD TRENCH DRAIN
TEL TELEPHONE
TEMP TEMPORARY
TERM TERMINAL
THD THREAD(ED)
THK THICK(NESS)
THRU THROUGH
TOB TOP OF BOLT
TOC TOP OF CONCRETE; TOP OF CURB
TOG TOP OF GIRT; TOP OF GRATING
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOW TOP OF WALL
TRI TRIAD; TRIPLEX
TS TUBULAR STEEL
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR
TW TWISTED
TYP TYPICAL
UBC UNIFORM BUILDING CODE
UFC UNIFORM FIRE CODE
UG UNDERGROUND
ABBREVIATION TERM
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UR URINAL
UTIL UTILITY
UV UNIT VENTILATOR
V VENT; VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VC VERTICAL CURVE
VCU VOLUME CONTROL UNIT
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VH VOLT HOUR
VPC VERTICAL POINT OF CURVE
VPI VERTICAL POINT OF INTERSECTION
VPT VERTICAL POINT OF TANGENCY
VS VOLTMETER SWITCH
VSD VARIABLE SPEED DRIVE
VT VOLTAGE TRANSFORMER
VTR VENT THRU ROOF
VV VALVE VAULT
W WATER; WEST; WIDE; WIDE FLANGE
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WAP WIRELESS ACCESS POINT
WCO WALL CLEANOUT
WD WIDTH
WF WIDE FLANGE
WG WATER GAUGE
WH WALL HYDRANT; WATER HEATER; WATTHOUR
WIV WATER INLET VALVE
WP WEATHER PROOF; WORKING POINT
WS WATER SUPPLY
WT WEIGHT
WWF WELDED WIRE FABRIC
X/R REACTIVE/RESISTANCE
XFMR TRANSFORMER
XFR TRANSFER
YCO YARD CLEANOUT
ZCV ZONE CONTROL VALVE
ABBREVIATIONS
GG5 0
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
GENERAL PLAN SYMBOLS GENERAL SECTION SYMBOLS UTILITY PLAN SYMBOLS PAVEMENT MARKING SYMBOLS GENERAL NOTES
ROAD SIGN SYMBOLSVALVE SYMBOLSGENERAL TREE SYMBOLS
3:1
(STRAIGHT ONLY)
TRAFFIC FLOW ARROW
(TURN ONLY)
TRAFFIC FLOW ARROW
(STRAIGHT OR TURN ONLY)
TRAFFIC FLOW ARROW
HANDICAP PAVEMENT MARKING
PAVEMENT MARKING
RAILROAD CROSSING
PAINTED TRAFFIC STRIPE
INTERSTATE HIGHWAY
US HIGHWAY
STATE HIGHWAYOR
MANHOLE
MANHOLE WITH VALVE
CATCH BASIN
HEADWALL
CULVERT END SECTION
YARD/FIRE HYDRANT
YARD CLEAN OUT
DEWATERING WELL
UTILITY POLE
LIGHT POLE
POLE SUPPORT
TOWER
TELEPHONE REDESTAL
GATE VALVE
CHECK VALVE
PLUG VALVE
GLOBE VALVE
BALL VALVE
POST INDICATOR VALVE
MH
MH
CB
YCO
DW
EARTH
ROCK
CRUSHED ROCK
SAND, CMU, PLASTER
GRANULAR FILL
CONCRETE
RIPRAP
RIPRAP (LARGE)
WATER LEVEL
CORRUGATED METAL PIPE (SMALL)
CORRUGATED METAL PIPE (LARGE)
BUSH (SMALL)
DECIDUOUS TREE (MEDIUM)
DECIDUOUS TREE (LARGE)
CONIFEROUS TREE (SMALL)
CONIFEROUS TREE (MEDIUM)
CONIFEROUS TREE (LARGE)
PALM TREE (SMALL)
PALM TREE (LARGE)
SHRUB LINE
TREE LINE (SMALL)
PROPERTY LINE
RIGHT-OF-WAY
BASE LINE, DATUM LINE
ONE STATION MARK
FIVE STATION MARK
POINT OF TANGENT
POINT OF CURVE,
POINT OF INTERSECTION
SURVEY HUB,
SURVEY MONUMENT
PROPOSED CONTOUR
EDGE OF WATER
DITCH FLOWLINE
SWALE OR DEPRESSION
SLOPE (3 HORIZ TO 1 VERT)
SWAMP OR WETLAND)
BENCH MARK
SOIL BORING
FENCE
GUARD RAIL
RIPRAP
SIGN (ONE POST)
SIGN (TWO POST)
EXISTING SPOT ELEVATION
PROPOSED SPOT ELEVATION
ARROWS POINT DOWN SLOPE
EXISTING CUT OR FILL SLOPE;
ARROWS POINT DOWN SLOPE
NEW CUT OR FILL SLOPE;
GUTTER OR GROUND ELEVATION
TOP OF CURB ELEVATION
110.00
110.50
110.50
120.0
ROW
1. ALL SYMBOLS AND ABBREVIATIONS SHOWN ON THIS LEGEND
MAY NOT APPEAR ON THIS SET OF DRAWINGS.
2. FOR GENERAL LEGEND AND ABBREVIATIONS, SEE ADDITIONAL
"GG" DRAWINGS.
3. ALL UTILITY LINES ARE APPROXIMATE. CONTRACTOR TO VERIFY
IN FIELD.
EXISTING CONTOUR
CIVIL LEGEND
GG6 0
JE TURNER
UTILITY LINE SYMBOLS
WATER
X" W
STORM WATER
X" STS
SANITARY SEWER
X" SAN
ELECTRIC
ELEC
PRETREATED PUMPED WASTE
PPW
GAS
GS
MAY 31, 2019
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
PLUMBING/PIPING FITTINGS
OPEN
NORMALLY
CLOSED
NORMALLY
SOLENOID AUTOMATED VALVE
CONTROL VALVE ASSEMBLY
TYP FAIL POSITION)
FOUR-WAY (WITH
TYP FAIL POSITION)
THREE-WAY (WITH
DIRECTION)
(ARROW INDICATES FLOW
WITH EXTERNAL TAP
PRESSURE REDUCING
SELF-CONTAINED
PRESSURE REDUCING,
DIRECTION)
(ARROW INDICATES FLOW
DIRECTION)
(ARROW INDICATES FLOW
SELF-CONTAINED
BACK PRESSURE REGULATOR
DIRECTION)
(ARROW INDICATES FLOW
REGULATOR EXTERNAL TAP
BACK PRESSURE
DIRECTION OF FLOW
PITCH DOWN IN
= TIE POINT NUMBERZZZ
= P&ID NUMBERYY
= EQUIPMENT OR CONTRACT DESIGNATORX
TIE POINT TO EQUIPMENT OR ANOTHER CONTRACT
XX = TIE POINT NUMBER
YYY = P&ID DRAWING NUMBER
TIE POINT INTO AN EXISTING SYSTEM
VALVES
TIE POINT DESIGNATORS
GENERAL
BALL CHECK
ANGLE SAFETY RELIEF
BACKFLOW PREVENTER
GAGE COCK
VACUUM RELIEF
BALANCING
FLOAT
WAFER CHECK
VALVES
SWING CHECK
WALL HYDRANT
HOSE BIBB OR
PLUMBING LINE TYPES
TRAP (LAV, DRAIN, ECT.)
WATER HAMMER ARRESTOR
SHOCK ABSORBER OR
STATED (PLAN) ONLY.
ALL FITTINGS AND VALVES MAYBE SHOWN AS INDICATED UNLESS
SCHEMATIC/FITTINGS AND VALVES
VTR
GENERAL NOTES
XX
XYY
ZZZ
-TPYYY XX
F
F
F
ED
FD
M
A
W
NEW WORK
EXISTING
FUTURE
STREAM IDENTIFICATION
FLOW ARROW
(LETTER, IF ANY, DESIGNATES TYPE)
UTILITY STATION
FLOW STRAIGHTENING VANE
Y-STRAINER
Y-STRAINER W/ DRAIN
BALL VALVE
CAPPED Y-STRAINER W/ N.C.
SIMPLEX STRAINER
DUPLEX STRAINER
START-UP STRAINER
TEMPORARY STRAINER IN-LINE
DRAIN
SPRAY NOZZLE
VENT THRU ROOF (PLAN)
STEAM VENT
(AUTOMATIC VENT) AV
(MANUAL VENT) MV
CONSERVATION VENT
CENTRIFUGAL PUMP
INLINE PUMP
BUCKET STRAINER
SEAL WATER CONTROL UNIT
GLOBE
BALL
STOP CHECK
PLUG
BUTTERFLY
NEEDLE
ANGLE GATE
ANGLE GLOBE
GATE
BLIND FLANGE
WELDED CAP
THREADED CAP
PIPE PLUG
CONCENTRIC REDUCER
ECCENTRIC REDUCER
ROOF DRAIN
EQUIP DRAIN
FLOOR DRAIN
FLOOR CLEANOUT
WALL CLEANOUT
EXPANSION JOINT
END
EXPANSION JOINT SINGLE
DOUBLE END
EXPANSION JOINT
FLEX CONNECTION
FLEX CONNECTOR W/SPARE
QUICK DISCONNECT
METER
UNION
PIPE GUIDE
PIPE ANCHOR
ROOF
VENT THRU
HOT WATER (DHW)
COLD WATER (DCW)
DOMESTIC HOT WATER CIRCULATING (HWC)
1. ALL SYMBOLS AND ABBREVIATIONS SHOWN ON THIS LEGEND
MAY NOT APPEAR ON THIS SET OF DRAWINGS.
2. FOR GENERAL LEGEND AND ABBREVIATIONS, SEE ADDITIONAL
"GG" DRAWINGS.
F
F
F
F
CO
MECHANICAL LEGEND - SHEET 1
GG7 0
JJ BOVENKAMP
M
OR
INLINE CLEANOUTCO
WH OR HB
VENT (V)
SPECIAL WASTE - DOUBLE WALL (BSL3)SW-DW
SPECIAL VENT (BSL3)SV
STORM DRAINSTD
SUBSOIL DRAINAGESSD
SANITARY DRAINSAN
REVERSE OSMOSISRO
OVERFLOW STORM DRAINOSTD
LABORATORY WASTELW
LABORATORY VENTLV
GASG
DE-IONIZED WATERDI
CARBON DIOXIDECO2
COMPRESSED AIRA
* INDICIATES SERVICE FROM LIST BELOW:
AFU AIR FILTER UNIT
ABBREVIATION TERM
SUPPLEMENTAL MECHANICAL ABBREVIATIONS
EV
HC
HPR
HRC
JSS
LV
LW
P
PC
RHP
SSD
SV
SW-DW
VAV
HRU
EXHAUST VALVE
HOT WATER COIL
HIGH PRESSURE RETURN
HEAT RECOVERY COIL
HEAT RECOVERY UNIT
LABORATORY VENT
LABORATORY WASTE
PUMP
PUMPED CONDENSATE
RADIENT CEILING HEATING PANEL
SUBSOIL DRAIN
SPECIAL VENT, SUPPLY VALVE
VARIABLE AIR VOLUME BOX
SPECIAL WASTE - DOUBLE WALL
JANITORIAL SERVICE SINK
A AIR
EA EXHAUST AIR
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
DHW DOMESTIC HOT WATER
DCW DOMESTIC COLD WATER
LPR LOW PRESSURE RETURN
FS FIRE WATER SUPPLY
LPS LOW PRESSURE SUPPLY
LS LABORATORY SINK
RO REVERSE OSMOSIS
OSTD OVERFLOW STORM DRAIN
HPS HIGH PRESSURE STEAM
HRCR HEAT RECOVERY COIL RETURN
HRCS HEAT RECOVERY COIL SUPPLY
HUM HUMIDIFIER
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
MPR MEDIUM PRESSURE RETURN
IM ICE MACHINE
CH CHILLER
CMP AIR COMPRESSOR
CP CONDENSATE PUMP
HX HEAT EXCHANGER
HWC HOT WATER CIRCULATING
PH PENTHOUSE
RF RETURN FAN
RHC REHEAT COIL
SF SUPPLY FAN
UH-HW UNIT HEATER HOT WATER
WCC WATER COOLING COIL
VAVR RETURN/EXHAUST VARIABLE AIR VOLUME BOX
MAY 31, 2019
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
AD
M
R
D
HVAC FIRE PROTECTION SYSTEM GENERAL NOTES
SD
CFM
TAG#
FIGURE = SIDE NOT SHOWN
FIRST FIGURE = SIDE SHOWN SECOND
DUCT-(INSIDE CLEAR DIMENSIONS)
ROUND DUCT
FLAT OVAL DUCT
FLOW IN DUCT
DIRECTION OF
SQUARE TO ROUND TRANSITION
18 X 18
TURNING VANES
SQUARE ELBOW WITH
18 X 14
12/12
TEE WITH TURNING VANES
VOLUME DAMPER (MANUAL)
FLEXIBLE DUCT CONNECTION
DUCT WITH RESPECT TO AIR FLOW
INCLINED DROP IN ELEVATION OF
WITH RESPECT TO AIR FLOW
INCLINED RISE IN ELEVATION OF DUCT
OPPOSED BLADE-PLAN VIEW
MOTORIZED DAMPER-PARALLEL OR
EXHAUST FAN
FAN
SUPPLY/VENTILATING AIR
RETURN/EXHAUST AIR
INLINE EXHAUST FAN
BACKDRAFT DAMPER-PLAN VIEW
BACKDRAFT DAMPER-SECTION VIEW
COIL IN DUCT
REHEAT OR PREHEAT
SIDE OR BOTTOM
ACCESS DOOR IN DUCT
DUCT TURNING DOWN
DUCT TURNING UP
SMOKE DAMPER
TAP FROM BOTTOM OF DUCT
RETURN OR EXHAUST DUCT
DUCT W/VOLUME DAMPER
BRANCH DUCT IN SIDE OF
RETURN, SUPPLY, OR EXHAUST
UNIT HEATER
CFM VALUE
EQUIPMENT TAG NUMBER
FIRE LINE SERVICE
FIRE SPRINKLER LINE
WET STANDPIPE
DRY STANDPIPE
UPRIGHT SPRINKLER HEAD
PENDANT SPRINKLER HEAD
SIDEWALL SPRINKLER HEAD
POST INDICATOR AND VALVE
OUTSIDE SCREW AND YOKE GATE VALVE
TAMPER PROOF VALVE
ALARM CHECK VALVE
DRY PIPE VALVE
DELUGE VALVE
SIDEWALL SPRINKLER HEAD
FLOW DETECTOR/SWITCH
FREE STANDING FIRE DEPT CONNECTION (SIAMESE)
WALL MOUNTED FIRE DEPT CONNECTION (SIAMESE)
DSP
WSP
FS
F
1. ALL SYMBOLS AND ABBREVIATIONS SHOWN ON THIS LEGEND
MAY NOT APPEAR ON THIS SET OF DRAWINGS.
2. FOR GENERAL LEGEND AND ABBREVIATIONS, SEE ADDITIONAL
"GG" DRAWINGS.
MECHANICAL LEGEND - SHEET 2
GG8 0
H
T
AND FIXTURE TYPE SHOWN
SUPPLY DIFFUSER OR GRILLE W/FLOWRATE
TYPE SHOWN
RETURN GRILLE W/FLOWRATE AND FIXTURE
FIXTURE TYPE SHOWN
EXHAUST GRILLE W/FLOWRATE AND
SUPPLY DUCT
RETURN DUCT
EXHAUST DUCT
HVAC CONTROLS
OTHER THAN 1 HOUR)
NUMBER INDICATES FIRE RATING
SMOKE DAMPER (SCHEMATIC) (*
RATING OTHER THAN 1 HOUR)
(* NUMBER INDICATES FIRE
SMOKE DAMPER (PLAN)
RATING OTHER THAN 1 HOUR)
(* NUMBER INDICATES FIRE
FIRE DAMPER (SCHEMATIC)
RATING OTHER THAN 1 HOUR)
(* NUMBER INDICATES FIRE
FIRE DAMPER (PLAN)
RATING OTHER THAN 1 HOUR)
(* NUMBER INDICATES FIRE
DAMPER (SCHEMATIC)
COMBINATION FIRE/SMOKE
RATING OTHER THAN 1 HOUR)
(* NUMBER INDICATES FIRE
DAMPER (PLAN)
COMBINATION FIRE/SMOKE
OS
SPS
FE
SP
TI
PI
IT
OV
M
M
TE
DP
P
DPS
VFD
BTU
M
M
XXX
REFRIGERANTR
NITROUS DIOXIDENO2
NATURAL GASNG
LIQUIFIED PETROLEUM GASLPG
HYDROGENH
CARBON DIOXIDECO2
CARBON MONOXIDECO
SD
FLEX DUCTOROR
CFM
LD-1 350
350 CFM
CD-1
350 CFM
RG-1
350 CFM
EG-1
OR
SD
SD
FD
FD
FSD
FSD
FIRE DEPARTMENT CONNECTIONFDC
FS
PARALLEL BLADE DAMPER
OR
OR
OPPOSED BLADE DAMPER
FILTER
H = HUMIDISTAT
TE = TEMPERATURE ELEMENT
T = THERMOSTAT
XXX =
OCCUPANCY SENSOR
STATIC PRESSURE SENSOR
SWITCH
DIFFERENTIAL PRESSURE SWITCH
DIFFERENTIAL PRESSURE SENSOR
FLOW ELEMENT
SETPOINT, STATIC PRESSURE
TEMPERATURE INDICATOR
PRESSURE SENSOR
PRESSURE INDICATOR
CURRENT TRANSDUCER
OVERRIDE
VARIABLE FREQUENCY DRIVE
(EXCLUDING ELECTRIC)
ENERGY METERING DEVICE
ELECTRIC MOTOR
PNEUMATIC ACTUATOR
MOTORIZED ACTUATOR
SMOKE DETECTOR
ROOM PRESSURE MONITORM
MAY 31, 2019
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
= HAND/OFF/REMOTE
= CONTROL STATION
BROKEN DELTA
OPEN DELTA
SOLID GROUNDED WYE
IMPEDANCE GROUNDED WYE
= AMMETER
= DEMAND METER
= ELAPSED TIME METER
= FREQUENCY METER
= POWER FACTOR METER
= VOLTAGE METER
= VOLTAMPERE METER
= VAR METER
= WATT METER
= WATTHOUR METER
RELAYING LIST BELOW)
MULTIFUNCTION RELAY (LIST FUNCTIONS FROM
RELAY (NOTE 4)
= PHASE DIRECTIONAL OVERCURRENT
= SPEED OR FREQUENCY MATCHING RELAY
= DISTANCE RELAY
= VOLTS PER HERTZ RELAY
= SYNC CHECK RELAY
= UNDERVOLTAGE RELAY
= DIRECTIONAL POWER RELAY
= POSITION SWITCH
= FIELD RELAY
= CONTACTOR
= MANUAL TRANSFER OR SELECTOR DEVICE
= REVERSE PHASE CURRENT RELAY
= REVERSE PHASE VOLTAGE RELAY
= MACHINE OR TRANSFORMER THERMAL RELAY
= INSTANTANEOUS OVERCURRENT RELAY
= PHASE TIME OVERCURRENT RELAY
= GROUND TIME OVERCURRENT RELAY
= NEUTRAL OVERCURRENT RELAY
= VOLTAGE RESTRAINED OVERCURRENT RELAY
= AC CIRCUIT BREAKER
= OVERVOLTAGE RELAY
= VOLTAGE OR CURRENT BALANCE RELAY
= TIME DELAY RELAY
= PRESSURE SWITCH
= ALARM RELAY
= OVERFREQUENCY RELAY
= UNDERFREQUENCY RELAY
= LOCKOUT RELAY
= DIFFERENTIAL CURRENT RELAY
= TRIPPING OR TRIP FREE RELAY
RELAYING (NOTE 3):
= AMMETER SWITCH
= EMERGENCY STOP PUSHBUTTON
= GROUND FAULT SENSOR
= JOG PUSHBUTTON
= LOCAL/REMOTE SWITCH
= HAND/OFF/AUTO SWITCH
= LIMIT SWITCH
= OVERTORQUE SWITCH
= SYNCHRONIZING SWITCH
= VOLTMETER SWITCH
RELAY (NOTE 4)
= NEUTRAL DIRECTIONAL OVERCURRENT
AF
AMP
FUSE
HOR
CS
51G
51N
51V
81O
81U
67N
AS
E
DEVICES:
J
LR
HOA
LS
OT
SS
GFS
VS
CAP
R
OHM
KV
MCOV
MEDIUM VOLTAGE MOTOR STARTER
BREAKER, NON-DRAWOUT
MEDIUM VOLTAGE CIRCUIT
= SENSOR RATINGS
= SHORT TIMEST
= MANUALLY OPERATEDM.O.
= LONG TIME LT
= INSTANTANEOUS AMPSIA
= INSTANTANEOUSI
= GROUNDG
= ELECTRICALLY OPERATEDE.O.
DRAWOUT:
LOW VOLTAGE CIRCUIT BREAKER,
FUSE
AMP
BATTERY
MOLDED CASE CIRCUIT BREAKER
= KEY INTERLOCKK
= SHUNT TRIPST
MOLDED CASE CIRCUIT BREAKER:
MINIATURE CIRCUIT BREAKER
FUSED CUT-OUT SWITCH
SURGE ARRESTOR
CAPACITOR
RESISTOR
INDUCTOR
BIMETALLIC THERMAL OVERLOAD
CONTACT N.O. (NORMALLY OPEN)
CONTACT N.C. (NORMALLY CLOSED)
FUSE
KVA,CLG
HV-LV
Z
KVA,CLG
HV-LV1-LV2
Z(NV-LV1),Z(HV-LV-2),Z(LV1-LV2)
KVA
HV-LV
Z
KVA
HV-LV
Z
KVA
HV-LV
Z(HV-LV),Z(HV-TER),Z(LV-TER)
(QTY)
PRI:SEC
ACCUR
DELTA
GROUND
WYE
A
D
METERING:
F
PF
V
VA
VAR
W
ET
WH
SIZE
AF
AT
TRANSFORMER
POWER
SHIELDED TRANSFORMER
AUTO TRANSFORMER
3-WINDING
POWER TRANSFORMER,
MOTORHP
VOLTAGE TRANSFORMER
CURRENT TRANSFORMER
INDICATES POLARITY
INDICATES POLARITY
WITH TERTIARY
POWER TRANSFORMER
BUSHING TYPE
CURRENT TRANSFORMER,
ZERO SEQUENCE
CURRENT TRANSFORMER,
SIZE
FUSE
NON-FUSED DISCONNECT SWITCH
PANELBOARD
OR MANUAL)
TRANSFER SWITCH (AUTOMATIC
- = DC
~ = AC
CONVERTER OR VFD
ONE-LINE AND THREE LINE DIAGRAMS
(QTY)
PRI/SEC
ACCUR
(QTY)
PRI/SEC
ACCUR
PRI/SEC
ACCUR
= VARIABLE FREQUENCY DRIVEVFD
= SKID MOUNTED LOADSKD
= HEATERHTR
= CONTROL PANELCP
LOCAL CONTROL:
AF
BREAKER, DRAWOUT
MEDIUM VOLTAGE CIRCUIT
GENERATOR
GEN
KW
KVA
PF
Z
INDICATES CABLE NUMBER
BUS
LINE TYPE (DIAGRAMS AND SCHEMATICS)
POWER CIRCUIT
CT & VT CIRCUIT
CONTROL CIRCUIT
COMMUNICATION
ELECTRICAL ENCLOSURE
AMP
FUSED DISCONNECT SWITCH
1. ALL SYMBOLS AND ABBREVIATIONS SHOWN ON THIS LEGEND MAY
NOT APPEAR ON THIS SET OF DRAWINGS.
2. FOR GENERAL LEGEND AND ABBREVIATIONS, SEE ADDITIONAL
"GG" DRAWINGS.
3. IEEE STANDARD C37.2-1991, ELECTRICAL POWER SYSTEM DEVICE
FUNCTION NUMBERS, NOT ALL DEVICES SHOWN.
4. DIRECTIONAL ARROW REQUIRED.
IN POWER SECTION
SEE RECEPTACLE OPTIONS :
WELDING OUTLET:
COMBINATION CIRCUIT BREAKER WITH STARTER:
FVNR = FULL VOLTAGE NON-REVERSING
FVR = FULL VOLTAGE REVERSING
2S = TWO SPEED
1W = ONE WINDING
2W = TWO WINDING
C = CONTACTOR
SFT = SOFT START
COMBINATION FUSED DISC SW WITH STARTER:
FVNR = FULL VOLTAGE NON-REVERSING
FVR = FULL VOLTAGE REVERSING
2S = TWO SPEED
1W = ONE WINDING
2W = TWO WINDING
C = CONTACTOR
ELECTRICAL LEGEND - SHEET 1
GG9 0
JM DANIELSON
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
(SEE NOTE 3)
X,x
X,x
X,x
COMMUNICATION
TTB
TEL
AMP
COMBINATION TELEPHONE/DATA OUTLET, WALL
TELEPHONE TERMINAL BOARD
TELEPHONE OUTLET, WALL
AMPLIFIER
* WAP = WIRELESS ACCESS POINT
FOUR-PLEX DATA OUTLET, WALL, UNO
TELEPHONE PANEL
C
M
S
TV
I
B
K
R
A
V PUBLIC ADDRESS VOLUME CONTROL
DOOR ALARM CONTACT
CARD READER WITH PIN PAD
GLASS BREAK SENSOR
REQUEST TO EXIT (MANUAL PUSH BUTTON)
ELECTROMAGNETIC LOCK
INTERCOM
PUSHBUTTON
BALANCED MAGNETIC SWITCH
TELEPHONE OUTLET, FLOOR
TELEVISION OUTLET, WALL
PUBLIC ADDRESS SPEAKER
PUBLIC ADDRESS MICROPHONE OUTLET
CLOCK
DATA OUTLET, FLOOR
CCTV SURVEILLANCE CAMERA, FIXED
EXIT SIGN, ARROW INDICATES DIRECTION
WALL MOUNT
PENDANT/ RECESSED DOWNLIGHT
WALL MOUNTED DOWNLIGHT
POLE MOUNTED DOWNLIGHT
EMERGENCY BATTERY OPERATED UNIT
WALL MOUNT AS INDICATED BY WALL MOUNT SYMBOL
EXIT SIGN, SINGLE FACE, CEILING MOUNT SHOWN,
WALL MOUNT AS INDICATED BY WALL MOUNT SYMBOL
EXIT SIGN, DOUBLE FACE, CEILING MOUNT SHOWN,
SURFACE/ PENDANT MOUNTED FIXTURE
EMERGENCY RECESSED FIXTURE
EMERGENCY SURFACE/ PENDANT MOUNTED FIXTURE
LIGHTING
RECESSED FIXTURE
WALL MOUNT
CCTV SURVEILLANCE CAMERA, PAN/ZOOM/TILT
POWER
TRANSFORMER
FUSED DISCONNECT SWITCH
T
HORSEPOWER RATED DISCONNECT SWITCH
NON-FUSED DISCONNECT SWITCH
COMBINATION DISCONNECT WITH STARTER
MOTOR
LOCAL CONTROL PANEL
GENERATOR
XFR
GEN
M
MANHOLE
HANDHOLE
FLOOR RECEPTACLE
DUPLEX RECEPTACLE
FOURPLEX RECEPTACLE
SINGLE RECEPTACLE
MH
HH
PANELBOARD, 208Y/120V OR 120/240V
TRANSFER SWITCH (AUTOMATIC OR MANUAL)
SPECIAL PURPOSE RECEPTACLE OR CONNECTION, 480V
208V SINGLE PHASE NEMA 6-20R
SPECIAL PURPOSE RECEPTACLE OR CONNECTION,
PANELBOARD, 480Y/277V OR 480V
GROUND CONDUCTOR
GROUNDING
GROUND ROD
GROUND
GROUNDING PIGTAIL
CATHODIC PROTECTION ANODE
CATHODIC PROTECTION
CONDUIT
RACEWAY
CONDUIT:
DUCTBANK
EMBEDDED
CONDUIT STUB WITH CAP
EXPOSED
FLUSH GROUND PLATE
LIGHTNING PROTECTION CONDUCTOR
LIGHTNING PROTECTION AIR TERMINAL
GROUND CONDUCTOR CONNECTION
GROUNDING CONNECTION TO STRUCTURE
CATHODIC PROTECTION TEST STATION NUMBER XX
REFERENCE ELECTRODE
CATHODIC PROTECTION UNDERGROUND
CATHODIC PROTECTION RECTIFIER NUMBER XX
UNDERGROUND DIRECT BURIAL
MEDIUM VOLTAGE POTHEAD TERMINATION
TXX
RXX
POWER SERVICE POLE
THERMOSTATT
COMBINATION TELE-POWER SERVICE POLE
COMM/POWER MOUNTED DIRECTLY ABOVE BACKSPLASH OR AT 1'-6" AFF.
SURFACE RACEWAY (WIREMOLD 4100, OR EQUAL) DUAL COMPARTMENT
FINISHED FLOOR
CONDUIT TURN-DOWN
JUNCTION BOX
CONDUIT TEE BELOW
CONDUIT TURN-UP
FIRE ALARM
J
MOUNTING HEIGHT
ELECTRICAL DEVICE
MEDIUM VOLTAGE STRESS CONE TERMINATION
SERVICE ENTRANCE METER
LIGHTNING PROTECTION SPHERE
THROUGH ROOF TERMINAL
= END OF LINE RESISTOREOL
1. ALL SYMBOLS AND ABBREVIATIONS SHOWN ON THIS LEGEND
MAY NOT APPEAR ON THIS SET OF DRAWINGS.
2. FOR GENERAL LEGEND AND ABBREVIATIONS, SEE ADDITIONAL
"GG" DRAWINGS.
3. FIXTURE SIZES MAY VARY ON PLANS. X ON FIXTURE SYMBOL
DENOTES FIXTURE TYPE DESIGNATION AND SWITCHING ZONE, IF
APPLICABLE. SEE LIGHT FIXTURE SCHEDULE. # ON FIXTURE
SYMBOL DENOTES CIRCUIT NUMBER. SEE LIGHTING PLANS.
4. USE DIRECTIONAL ARROW ON EXIT SIGNS AS REQUIRED.
5. SEE TYPICAL WIRING SCHEMATIC PLANS FOR DIGITAL SMART
SWITCH REQUIREMENTS PER ROOM.
6. # ON RECEPTACLE SYMBOL DENOTES CIRCUIT NUMBER. SEE
POWER PLANS.
HP
RECEPTACLE OPTIONS, IF REQ'D:
ARC = AUTOMATIC RECEPTACLE CONTROL
GFI = GROUND FAULT INTERRUPTING
IG = ISOLATED GROUND
S = SWITCH AND OUTLET
WP = WEATHERPROOF
XP = EXPLOSIONPROOF
TW = NEMA 5-30R TWIST-LOCK
UC = UNDER COUNTER (1'-6" AFF)
LIGHTING CONTROL:
LC = LIGHTING CONTACTOR
PE = PHOTOELECTRIC CELL
TC = TIME CLOCK
SWITCH, SINGLE POLE, LINE VOLTAGE
LINE VOLTAGE SWITCH OPTIONS:
3 = THREE-WAY
4 = FOUR-WAY
D = DIMMER
K = KEY OPERATED
P = PILOT
T = TIMER
a,b,c = DENOTES SWITCHING ZONE CONTROL
FACP = FIRE ALARM CONTROL PANEL
FAA = FIRE ALARM ANNUNCIATOR
FTR = FIRE ALARM TRANSPONDER OR
TRANSMITTER
ESR = ELEVATOR STATUS/RECALL
FAC = FIRE ALARM COMMUNICATOR
MIC = REMOTE MIC
EVAC = VOICE EVACUATION PANEL
AMP = AMPLIFIER RACK
BATT = BATTERY PACK AND CHARGER
= MANUAL PULL STATION - DELUGE SPRINKLERDL
= MANUAL PULL STATION - WATER MISTWM
= MANUAL PULL STATION - CLEAN AGENTCA
= MANUAL PULL STATION - WET CHEMICALWC
= MANUAL PULL STATION - FOAMFO
= MANUAL PULL STATION - DRY CHEMICALDC
= MANUAL PULL STATION - CARBON DIOXIDE2CO
= MANUAL PULL STATIONF
CA - CLEAN AGENT
WC - WET CHEMICAL
FO - FOAM
DC - DRY CHEMICAL
- CARBON DIOXIDE2CO
WHERE X:
FIRE SYSTEM CONTROL PANEL
DL - DELUGE SPRINKLER
WM - WATER MIST
CA - CLEAN AGENT
WC - WET CHEMICAL
FO - FOAM
DC - DRY CHEMICAL
- CARBON DIOXIDE2CO
WHERE X:
RELEASING SERVICE FIRE ALARM CONTROL UNIT
EMERGENCY TEXTUAL VISIBLE APPLIANCE
BLANK = FIRE SERVICE OR EMERGENCY TELEPHONE STATION
A = FIRE SERVICE OR EMERGENCY TELEPHONE STATION - ACCESSIBLE
H = FIRE SERVICE OR EMERGENCY TELEPHONE STATION - HANDSET
= ABORT SWITCH - EMERGENCY POWER OFFEPO
= ABORT SWITCH - PREACTION SYSTEMPRE
= ABORT SWITCH - DELUGE SPRINKLERDL
= ABORT SWITCH - WATER MISTWM
= ABORT SWITCH - CLEAN AGENTCA
= ABORT SWITCH - WET CHEMICALWC
= ABORT SWITCH - FOAMFO
= ABORT SWITCH - DRY CHEMICALDC
= ABORT SWITCH - CARBON DIOXIDE2CO
= ABORT SWITCHBLANK
HEAT DETECTOR - COMBINATION: RATE OF RISE
AND FIXED TEMPERATURE
WHERE X:
R/F - COMBINATION; RATE OF RISE AND
FIXED TEMPERATURE
R/C - RATE COMPENSATION
F - FIXED TEMPERATURE
R - RATE OF RISE ONLY
TSS -TEMPERATURE SUPERVISORY SWITCH
HEAT DETECTOR - LINE TYPE DETECTOR (HEAT-
SENSITIVE CABLE)
SMOKE/HEAT DETECTOR
SMOKE DETECTOR
WHERE X:
P - PHOTOELECTRIC PRODUCTS OF
COMBUSTION DETECTOR
I - IONIZATION PRODUCTS OF
COMBUSTION DETECTOR
BT - BEAM TRANSMITTER
BR - BEAM RECEIVER
ASD - AIR SAMPLING
GAS DETECTOR
WHERE X:
H - HYDROGEN
FLAME DETECTOR
WHERE X:
F - FLAME
UV - ULTRAVIOLET
IR - INFRARED
UV/IR - COMBINATION ULTRAVIOLET INFRARED
VR - VISIBLE RADIATION
FS = FLOW DETECTOR/SWITCH
PS = PRESSURE DETECTOR/SWITCH
LS = LEVEL DETECTOR/SWITCH
TS = VALVE TAMPER SWITCH
R = OUTPUT RELAY
HT = TEMPERATURE SWITCH - HIGH TEMPERATURE
LT = TEMPERATURE SWITCH - LOW TEMPERATURE
=X
BLANK = GONG
V = BELL - VIBRATING
VS = BELL - VIBRATING/STROBE
G = BELL - SINGLE STROKE GONG
GS = BELL - SINGLE STROKE GONG/STROBE
=X
ROTATING BEACON TO INDICATE EMERGENCY
RESPONSE POINTS
SMOKE DETECTOR FOR DUCT
REMOTE ALARM INDICATING AND TEST SWITCH
X
H = HORN
S = SPEAKER
V = STROBE
SS = SPEAKER/STROBE
HS = HORN/STROBE
WP = PROVIDE CLEAR BUBBLE
TYPE COVER
WHEELOCK EWP,
OR EQUAL
WHERE X:
X - CANDELA RATING
ADDRESSABLE INPUT MODULE
ADDRESSABLE OUTPUT MODULE
ET
X
FSCP
X
RTS
X
RSFACU
X
X
R
X
AIM
AOM
X,x
X
X
X
SYMBOL
WALL MOUNT AS INDICATED BY WALL MOUNT
EXTERIOR WEATHERPROOF CUTOFF FIXTURE
X
X
X
X
* OC = OCCUPANCY SENSOR
DS = DAYLIGHT SENSOR
DIGITAL SMART SWITCH WALL STATION, CAT-5E
(SEE NOTE 5)
S
GROUND ROD TEST WELL
ELECTRICAL LEGEND - SHEET 2
GG10 0
G
M
EMERGENCY EGRESS PULL STATION
X
EMERGENCY PENDANT DOWNLIGHT
J
COUNTERTOP
BSL3
SEE NOTE 6
MAY 31, 2019
CONTRACTOR LAYDOWN
AREA - OPTION 1
CONTRACTOR LAYDOWN
AREA - OPTION 2
HAUL ROUTE
H-3
443H-4
Z-3423
446Y-3445Y-2
H-6
CONSOLIDATED
LABORATORY
FACILITY (CLF)
CLF
SUPPORT
USDA/APHIS SUPPLEMENTAL
LABORATORY BUILDING
MB
BUILDING
D
AY
TO
N
AV
E
D
AY
TO
N
AV
E
HAUL ROUTE
TO
E
TH
ST
IN
TE
R
ST
AT
E
35BUILDING 21
NEW ADDITION
POTENTIAL GRAVEL
CONSTRUCTION
ACCESS PATHS
CONTRACTOR LAYDOWN
AREA - BUILDING 401
D
A
1 2
C
AD
D D
3- R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
MYCOBACTERIOLOGY LABORATORY RELOCATION
AMES, IOWA
27100.10
SITE PLAN
LAYDOWN AND HAUL ROUTES
CM100 0
NONE
JE TURNER
BK GROTHE
MAY 31, 2019
CS WEIKEL
CS WEIKEL
RJ LUKKARINENSITE PLAN LAYDOWN AND HAUL ROUTES
NORTH
GENERAL NOTES:
1. CONTRACTOR SHALL COORDINATE WITH USDA ON
WHICH CONTRACTOR LAYDOWN OPTION WILL BE USED.
2. CONTRACTOR SHALL COORDINATE ACCESS PATHS TO
SITE WITH USDA. ANY DAMAGE TO EXISTING UTILITIES
WILL BE REPAIRED AT CONTRACTOR'S EXPENSE.
3. CONTRACTOR SHALL VERIFY THE LOCATION OF THE
EXISTING UTILITIES PRIOR TO BEGINNING WORK IN THE
PROJECT AREA.
CONSOLIDATED
LABORATORY
FACILITY (CLF)
USDA/APHIS SUPPLEMENTAL
LABORATORY BUILDING
D
A
1 2
C
AD
D D
3- R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
MYCOBACTERIOLOGY LABORATORY RELOCATION
AMES, IOWA
27100.10
SITE CLEARING AND
DEMOLITION PLAN
DC100 0
1"=10'
JE TURNER
BK GROTHE
MAY 31, 2019
CS WEIKEL
CS WEIKEL
RJ LUKKARINENSITE CLEARING AND DEMOLITION PLAN
1. REMOVE SHRUB (REMOVE AS APPLICABLE)
2. REMOVE TREE
3. REMOVE LANDSCAPING ROCK AND STONE EDGING
4. REMOVE GRAVEL PATH
5. DEMOLISH PCC SIDEWALK
6. REMOVE, SALVAGE AND REINSTALL FIELD HYDRANT
7. REMOVE PCC PAD
8. REMOVE SIDEWALK WHEN REPLACING STORM WATER
LINE
9. DEMOLISH MANHOLE
10. DEMOLISH CLEANOUT
11. REMOVE STONE RAIN GARDEN WITH STONE EDGING
12. REMOVE GUARD POSTS.
13. PROTECT LIGHT BOLLARD
14. REMOVE LIGHT POLE
15. NOT USED
16. REMOVE PIPE, REMOVE DEBRIS, INSTALL FORMS, AND
PLACE CONCRETE TO FILL OPENING.
17. WATER LINE UNDER THE WALKWAY SHALL BE
ABANDONED IN PLACE. PLUG EACH END OF PIPE WITH
CONCRETE FOR A MINIMUM OF 2 FEET.
DEMOLITION
KEYNOTES:
LEGEND:
INDICATES UTILITY DEMOLITION
2 11
2 2 2
EXISTING
USDA/APHS SUPPLEMENTAL LABORATORY
BUILDING #21
EXISTING
CONSOLIDATED LABORATORY FACILITY
BUILDING #20
NORTH
E
XI
ST
IN
G W
A
LK
W
AY
8" SAN
"S
TS
8"
SA
N
"S
TS
8"
SA
N
8" W 8" W
18" STS
12" STS
8"
ST
S
E
LE
C
8" SAN
STS
6" STS
6" STS
GS
GS
G S
G S
SEE DRAWING CM100 FOR USDA SITE LAYOUT.
KEYPLAN
8" W
8" W
8" W
GRAVEL PATH
GRAVEL PATH
PCC PAD
PCC PAD
P C
C S
ID
EW
AL
K
ELEC
ELEC
PCC
SIDEW
ALK
P C
C
PA
D
4" PPW
3" PPW
6" PPW
(GRAVITY FLOW)
ELEC
E
LE
C
RAIN GARDEN
G S6"
ST
S
GENERAL NOTES:
1. CONTRACTOR SHALL REMOVE EXISTING BENCHES AND
PICNIC TABLES. REMOVAL WILL BE COORDINATED WITH
OWNER.
2. EXISTING SIDEWALK (TO REMAIN) SHALL BE PROTECTED
OR REPLACED AT CONTRACTOR'S EXPENSE.
3. ALL UTILITIES TO BE RELOCATED NEED TO BE PLACED IN
SERVICE BEFORE DEMOLISHING EXISTING UTILITIES.
G R
A
VE
L
PA
TH
EXST CHILLED
WATER
SUPPLY &
RETURN
LINES
EXST ELEC DUCTBANK
EXST ELEC DUCTBANK
EXST TELECOMMUNICATIONS
DUCTBANK
995994
H-4
CONSOLIDATED
LABORATORY
FACILITY (CLF)
CLF
SUPPORT
USDA/APHIS SUPPLEMENTAL
LABORATORY BUILDING
4.7% 6.5:1
5.0%
3:1
4.00' DITCH BOTTOM
PCC SIDEWALK
EXST GRADE
BLDG 21 NEW ADDITIONEXST BLDG #20
0+00 0+25 0+50 0+75 1+00 1020.00
1010.00
1000.00
990.00
980.00
FIN FLR EL 995.25'
FIN FLR EL 1001.25'
1.40' (+/-)
SITE LAYOUT AND GRADING PLAN
CG100 0
AS NOTED
JE TURNER
BK GROTHE
MAY 31, 2019
CS WEIKEL
CS WEIKEL
RJ LUKKARINEN
SITE LAYOUT AND GRADING PLAN
EXISTING
CONSOLIDATED LABORATORY FACILITY
BUILDING #20
EXISTING PLAN
EL: 0'-0"=1001.25'
NORTH
BUILDING 21
NEW ADDITION
FINISHED FLOOR EL:
ARCH EL: 0'-0"=995.25'
PCC SIDEWALK
PICNIC PAD
20'X20'
TOC EL 1000.75
PICNIC PAD
(SEE NOTE 3)
PCC SIDEWALK
PCC PAD, SEE
DWG SF501
PCC SIDEWALK
E
XI
ST
IN
G
PC
C
SI
D E
W
AL
K
E
XI
ST
IN
G C
O
VE
R E
D W
AL
KW
AY
LIMITS OF GRADING
N 3,478,233.04 E 4,900,366.93
N 3,478,358.95 E 4,900,422.00
N 3,478,358.68 E 4,900,531.39
5.
0'
SEE DRAWING CM100 FOR USDA SITE LAYOUT.
KEYPLAN
GENERAL NOTES:
1. ALL SPOT ELEVATIONS ARE TO FINISHED SURFACE.
2. COORDINATES ARE IN IOWA STATE PLANE, NORTH ZONE,
US SURVEY FEET. VERTICAL DATUM IS NAVD88.
3. BUILD SAME AS OTHER PICNIC PADS EXCEPT PAD SHALL BE
PLAIN CONCRETE THAT IS NOT COLORED NOR STAMPED.
4. ALL EROSION AND SEDIMENT CONTROL ITEMS SHALL
CONFORM TO IOWA SUDAS STANDARDS INCLUDING THE
CITY OF AMES SUPPLEMENTAL SPECIFICATIONS TO IOWA
SUDAS.
5. CONTRACTOR SHALL DEVELOP THE SWPP AND OBTAIN THE
NPDES PERMIT. SWPP SHALL CONFORM TO CRITERIA
LISTED IN NOTE 4, THIS DRAWING.
6. THE MINIMUM DESIRABLE SLOPE FOR TURF AREAS SHALL
BE NOT LESS THAN 1.5 PERCENT. MAXIMUM SLOPE FOR
TURF AREAS SHALL NOT EXCEED ONE FOOT RISE IN THREE
FEET OF RUN.
D
A
1 2
C
AD
D D
3- R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
MYCOBACTERIOLOGY LABORATORY RELOCATION
AMES, IOWA
27100.10
EXISTING
CONSOLIDATED LABORATORY FACILITY
BUILDING #20
EXISTING PLAN
EL: 0'-0"=1001.25'
A-CG100
A-CG100
SECTION A-CG100
SCALE: 1"=10'
CG100
SCALE: 1"=20'
PICNIC PAD
20'X20'
TOC EL 1000.56
TOC EL 1001.07' (+/-)
EXST PCC PAD
EL 999.00
4.
3:
16.
5:
3:
2.
6%
TOC EL 1001.14' (+/-)
4.4:1
6.2%
1.5%
PCC PAD, SEE
DWG SF501
BEGIN DITCH BOTTOM
EL 993.21
EL 994.75
EL 994.75
EL 991.45
EL 999.00
EL 994.75
5.
0'
5.0'
19.0'9.0'
EL 994.91
EL 994.61
EL 994.75
.0
EL 994.53
EL 994.55
5.
0'
5.
0'
4.
0%
1.
0%
YARD
HYDRANT
BEGIN DITCH BOTTOM
EL 993.91
BEGIN DITCH BOTTOM
EL 992.87
TOP OF DITCH
EMBANKMENT
EL 994.25
EL 994.25
EL 994.35
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
6" PCC
4" AGGREGATE BASE
EARTH STAMPED PCC
4" INTEGRAL COLORED,
4" AGGREGATE BASE
EXST GROUND EXST GROUND
PER ASTM A1064
WWF 6"X6" W2.9XW2.9
/2
SITE DETAILS
CG500 0
MAY 31, 2019
CS WEIKEL
CS WEIKEL
TYPICAL 6" PCC SIDEWALK DETAIL TYPICAL 4" (MIN) PICNIC PAD DETAIL
NOTES:
1. CONCRETE SHALL BE COLORED IN ACCORDANCE WITH SPECIFICATION IN 32 13 16-26.
2. CONCRETE SHALL BE STAMPED IN ACCORDANCE WITH SPECIFICATION 32 13 16-23.
NOTES:
1. MAXIMUM CROSS SLOPE 2.0%.
2. MAXIMUM RUNNING SLOPE 5.0%.
"S
TS
8" SAN
4"
ST
S 4"
ST
S
4" STS
18" STS 18" STS18" STS
6"
ST
S
6" STS
"S
TS
8"
SA
N
24" STS
"S
TS
24" STS
" S
TS
8" S A
N
E
LE
C
8" W 8" W
8" W
H-4
CONSOLIDATED
LABORATORY
FACILITY (CLF)
CLF
SUPPORT
USDA/APHIS SUPPLEMENTAL
LABORATORY BUILDING
D
A
1 2
C
AD
D D
3- R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764 www.stanleyconsultants.com
0 1 2 3
AT FULL SIZE
IN
cm0 1 2 3 4 5 6 7 8
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
MYCOBACTERIOLOGY LABORATORY RELOCATION
AMES, IOWA
27100.10
SITE UTILITIES PLAN
CU100 0
1"=20'
JE TURNER
BK GROTHE
MAY 31, 2019
CS WEIKEL
CS WEIKEL
RJ LUKKARINEN
E1 E2 E3
CB2
E13 E12
MH12
E4
E5
E6
E7
8" W
4"
SA
N
PRETREATED PUMPED WASTE LINE
(GRAVITY FLOW), SEE NOTE 3. SEE
DWG CU501 FOR CONNECTION DETAILS.
15" STS
RELOCATED YARD
HYDRANT
8" W
8" W
12" STS
EXISTING
CONSOLIDATED LABORATORY FACILITY
BUILDING #20
EXISTING
USDA/APHS SUPPLEMENTAL LABORATORY
BUILDING #21
BUILDING 21
NEW ADDITION
E
XI
ST
IN
G W
A
LK
W
AY
NORTH
SITE UTILITIES PLAN
CB1
C-TYPE INLET
C-TYPE INLET
SEE DRAWING CM100 FOR USDA SITE LAYOUT.
KEYPLAN
E10
E9
E8
E11
N 3,478,240.76 E 4,900,413.93
CO
" S
TS
N 3,478,305.68 E 4,900,416.25
N 3,478,240.76 E 4,900,371.56
N 3,478,239.94 E 4,900,311.80
TEE
GENERAL NOTES:
1. ELEVATIONS ARE BASED NAVD88.
2. NORTHINGS AND EASTINGS ARE BASED ON NAD83 (CORS) IOWA STATE
PLANE, NORTH ZONE, US SURVEY FEET.
3. THE SIZE, NUMBER, AND LOCATION OF EXISTING UTILITIES SHOWN ON
THIS DRAWING ARE APPROXIMATE AND ARE GENERAL INFORMATION
ONLY. CONTRACTOR RESPONSIBLE FOR OBTAINING EXACT LOCATIONS
OF EXISTING UTILITIES. SOME EXISTING UTILITIES MAY NOT BE SHOWN.
8" W
N 3,478,306.71 E 4,900,644.20 (+/-)
MH13
4"
SA
N
IE 991.16
IE 989.57
18" STS
4"
ST
S
MANHOLE
NO. INFORMATION
E1
E2
E3
E4
E5
E6
E7
E8
E9
E10
E11
E12
E13
CB1
CB2
MH12
MH13
GRATE/RIM NORTH EAST SOUTH WEST
1000.23
998.61
997.19
993.27
996.62
996.20
1000.31
999.91
1000.29
999.95
995.63
993.70
991.45
996.23
998.00
952.48
994.80
992.63
989.87
987.60/987.60
987.11
988.28
992.70
987.80
991.73
992.05
992.16
988.11
985.35
988.35
988.10
987.90
987.60
987.11
990.81
985.35
988.10
987.80
991.73
992.05
992.16
988.11
988.95
988.35
988.28
987.90
987.80
E
XI
ST
IN
G P
R O
P O
SE
D
N 3,478,306.35 E 4,900,566.00
PLUG
24" CASING PIPE,
SEE NOTE 1
TEE
14" DIA CASING
PIPE, SEE NOTE 1
90° BEND
(TYP FOR 3)
NOTES:
1. AUGER BORE STEEL CASING PIPE UNDER EXISTING WALKWAY FOUNDATION.
VERIFY EXTENT AND ELEVATIONS OF EXISTING FOUNDATIONS. CASING PIPE
SHALL COMPLY WITH SPECIFICATION SECTION 31 23 00 EXCAVATION AND
FILL.
2. WATER, STORM SEWER, AND PPW RELOCATIONS SHALL BE PLACED IN
SERVICE BEFORE DEMOLISHING EXISTING UTILITIES.
3. FOR PRETREATED PUMPED WASTE PIPE TYPE, SEE SPECIFICATION SECTION
20 05 13.
4. MAINTAIN CONSTANT SLOPE IN GRAVITY LINE. MINIMUM SLOPE OF 0.4%.
5. CONNECT 4" BSL-2 WASTE LINE TO EXISTING 8" SANITARY LINE WITH A
VERTICAL DOWN 45 ELBOW CONNECTING INTO A 8"X4" TEE.
6. AT GRAVITY PIPE CROSSING, BACKFILL WITH FLOWABLE FILL.
7. INSTALL YARD CLEANOUT FOR 4" PRETREATED PUMPED WASTE LINE. SEAL
WASTE LINE CARRIER PIPE AROUND CLEANOUT SO NO WATER CAN ENTER
SPACE BETWEEN 4" WASTE LINE AND CARRIER PIPE.
8. 4" STS LINE SHALL BE CONNECTED INTO 15" STS LINE.
9. EXTEND PIPE. SEE DRAWINGS ML101 and ML102.
E
XS
T C
H
IL
LE
D
W
AT
ER
S
U P
PL
Y
R
E
TU
R N
LI
N
ES
EXST ELEC DUCTBANK
EXST TELECOMMUNICATIONS
DUCTBANK
120' PERFORATED PIPE
4 0 'P
ER
FO
R A
TE
D
PI
PE
YCO
P
ER
FO
R
AT
ED
P
IP
E
8"
ST
S
OUTLETS INTO STORM
PIPE (TYP FOR 5), NOTE 8
SEE MECHANICAL
DRAWINGS
OUTSIDE FACE OF
CRAWLSPACE WALL
NOTE 6
4" BSL-2 WASTE LINE
NOTE 4
NOTE 5 NOTE 4
IE 983.17,
SEE DWG CU501 FOR
CONNECTION DETAILS.
YCO
YCO, SEE
NOTE 7
YCO
NOTE 9 4"
ST
S
4"
ST
S
4"
ST
S
YCO
YCO
4" STS
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
SITE UTILITIES
TYPICAL DETAILS
CU500 0
MAY 31, 2019
CS WEIKEL
NOTES:
1. FOR INLETS HAVING PIPES ENTERING AND LEAVING, REVISE CONCRETE FILL TO SUIT.
2.
SEE PLANS
FOR ELEVATIONS
FINISHED GRADE
1 1
5 5
33 30 00
SEE SPECIFICATION
FOR WALL MATERIAL
#4 - TOP
SHOWN ON PLANS
EXCEPT AS
12" INLET PIPE
OPENING (BOT)
4 - #4 AROUND
A
#4 @ 12CONCRETE
CLASS B
REINFORCING
SEE PLAN FOR
SPECIFICATION 33 30 00
BEEHIVE GRATE, SEE
FOUNDATION
CONCRETE
IN PLACE CONCRETE - 8". PRECAST CONCRETE PIPE - TO CONFORM TO PIPE CLASS SPECIFIED.
WALL DIMENSIONS MARKED THUS (*) VARY WITH MATERIAL USED IN CONSTRUCTION. BRICK OR POURED
A
6" *
SQ OR ROUND
2'-8" MIN * 6"
S Q O
R R
O U
N D
M
IN
O R A
S R
E Q 'D
4" MIN
OPENING
FRAME
4" MIN
(TYP)
STORM SEWER TYPE "C" INLET DETAIL
PLAN
SECTION A-A
NOTES:
1. SEE SPECIFICATION 33 30 00 FOR ALLOWABLE TRENCH WIDTH.
CENTER LINE
OF PIPE
PIPE
GRAVITY
FLEXIBLE
BACKFILL
REMAINING
M
IN
F
O R P
IP
E
A N
D L
A R
G E
R I
N D
IA
SEE NOTE 1
M
IN
M
IN
F
O R P
IP
E
A N
D L
E S
S I
N D
IA
HAUNCHING
PIPE BEDDING
INITIAL BACKFILL
PLASTIC PIPE BEDDING DETAIL
TYPICAL TRENCH CROSS-SECTION
BACKFILL
REMAINING
PIPE BEDDING
PIPE
PRESSURE
BACKFILL
INITIAL
SEE NOTE 1
M
IN
M
IN4
P
IP
E E
N V
E L
O P
E
MAXIMUM TRENCH WIDTH = PIPE OUTSIDE DIAMETER PLUS 2''-0".1.
NOTES:
PRESSURE PIPE BEDDING DETAIL
TYPICAL TRENCH CROSS-SECTION
1" DIAMETER
FINISHED GRADE
M
IN
1'-0"
F O
R M
IN
C
O V
E R
S E
E S
P E
C
IF
IC
A T
IO
N
FREEZELESS YARD HYDRANT DETAIL
WASHED GRAVEL
2 CUBIC FEET
DRAIN
AUTOMATIC
BREAK
SIPHON
HOSE BIB SHALL ACCOMMODATE STANDARD 3/4" GARDEN HOSE.1.
NOTES:
TEE
NOTE 2
NOTE 4
NOTE 3
NOTE 1
NOTE 2
HYDRANT
BOX
VALVE
1. 2" STANDARD WEIGHT STEEL PIPE W/1/4" X 4" X 4" STEEL PLATES.
2. CONCRETE THRUST BLOCK AGAINST UNDISTURBED EARTH.
3.
4. SEE SPECIFICATION 33 11 00 FOR TYPE OF JOINTS.
WALL
TRENCH
MAIN
VALVE
GATE
LINE
MAIN PIPE
CONCRETE PAD
CLASS B
4" X 12" X 12"
BACKFILL WITH GRAVEL TO 18" ABOVE BOTTOM OF HYDRANT STAND PIPE.
GROUND SURFACE
D
E P
T H O
F C
O V
E R A
S S
P E
C
IF
IE
D
STANDARD HYDRANT DETAIL
NOTES:
ECCENTRIC MANHOLE DETAIL
IN GROUT
SET FRAME
(IF SPECIFIED)
WATERPROOFING
CONCRETE
CLASS B
OF MAIN SEWER
DIAMETER
AND LID
MANHOLE FRAME
SHOWN ROTATED
TOP SECTION
(1'-0" MAXIMUM)
MEET GRADE LINE
AS REQUIRED TO
ADJUSTING RINGS
(IF SPECIFIED)
MANHOLE STEPS
(IF SPECIFIED)
CONNECTION,
WATERTIGHT
FLEXIBLE,
ON 6" SAND CUSHION. SEE NOTE 3.
OR PRECAST REINFORCED CONCRETE
BOTTOM SLAB: CLASS A CONCRETE
WATERPROOFING REQUIREMENTS AND CONCRETE.
SEE SPECIFICATION 33 30 00 FOR MATERIALS, CASTINGS,
(M
A X
(M
IN
M
IN
DIA
6"6"
/4 d
/2 d
FINISH GRADE LINE
SEE NOTE 4
MANHOLE WALL
MAIN SEWER
#4@12
24" AND UNDER
27" TO 42" INCLUSIVE
DIA
4'-0"
5'-0"
NOTES:
1.
2.
3.
4. SEE SPECIFICATION 33 30 00 FOR CHIMNEY SEALS IF REQUIRED.
INTEGRAL FLOOR AND WALL SECTION MAY BE USED.
MANHOLE COVER TO BE CENTERED DIRECTLY OVER FLOW LINE OF MAIN SEWER.
18"
D (S
Q
C (S
Q
1/2A
A
1/2A
A
/2
B
B
AND SOIL BEARING PRESSURE OF 1500 psf.
HYDROSTATIC PRESSURE TEST OF 225 psi
TYPICAL THRUST BLOCK SIZES BASED ON A
GROUND
UNDISTURBED
GROUND
UNDISTURBED
MIN
(Ft) (Ft) TEE(Ft) PLUG(Ft)
SIZE A
2.0'
3.5'
4.0'
B
2.0'
3.5'
4.0'
A
1.5'
3.0'
3.5'
B
1.5'
3.0'
3.5'
A
1.5'
2.5'
3.5'
B
1.5'
2.5'
3.5'
C
0.5'
0.75'
1.0'
D
1.5'
2.5'
4.0'
TYPICAL THRUST BLOCK FOR WATER MAINS DETAIL
ARE TO MANHOLE
PLAN COORDINATES
2.
TO THE UNDERSIDE OF THE RIVER ROCK.
AT PERFORATED PIPE LOCATIONS ,EXTEND INITIAL BACKFILL
3. ATTACH CASTING FRAME TO STRUCTURE WITH FOUR ANCHOR BOLTS.
TAPE
WARNING
WARNING TAPE WARNING TAPE
WIRE
TRACER
1 2
C A
D D D
-R
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
www.stanleyconsultants.com
225 Iowa Avenue, Muscatine, Iowa 52761-3764
USDA NATIONAL CENTERS FOR ANIMAL HEALTH
SITE UTILITIES
PIPE DETAILS
CU501 0
AS NOTED
LJ HEINLEIN
BUILDING WALL
CARRIER PIPE
PIPE SERVICE PIPE, FRP
COUPLING, TYP
1" THREADED
END SEAL
SWITCH, SEE NOTE 2
TOP LEAK DETECTION
SWITCH, SEE NOTE 2
BOTTOM LEAK DETECTION
UNION, TYP
1" PIPE LATERAL
BALL VALVE, TYP
(QUICK CONNECT), TYP
1" PPW HOSE END DRAIN
SEE NOTE 3
LEAK DETECTION SWITCH
SIZE AS REQUIRED FOR
SEE NOTE 3
PPW FLANGE
PPW 150# FLANGE
LOW END PPW DISTRIBUTION PIPE CONNECTION DETAIL
NOTES:
DETECTION SENSOR CABLE TO JUNCTION BOX.
PROVIDE ADEQUATE AMOUNT OF CABLE TO CONNECT LEAK 3.
BUILDING 20.
THE PERMALERT PAL-AT LEAK DETECTION PANEL LOCATED IN
SWITCHES SHALL BE PROVIDED AND WIRED SEPARATELY BACK TO
TOP AND BOTTOM CONNECTIONS TO THE CARRIER PIPE, SEPARATE
A LEAK DETECTION SWITCH ASSEMBLY SHALL BE PROVIDED AT THE 2.
SLOPES DOWN INTO A BUILDING.
THIS DETAIL IS FOR LOCATIONS WHERE THE PPW PIPE SYSTEM 1.
NO SCALE
HIGH END PPW DISTRIBUTION PIPE CONNECTION DETAIL
NOTES:
SLOPES DOWN AWAY FROM A BUILDING.
THIS DETAIL IS FOR LOCATIONS WHERE THE PPW PIPE SYSTEM 1.
NO SCALE
PPW PIPE, SCH 80
CARRIER PIPE
PIPE SERVICE PIPE, FRP
COUP…