This document is an Existing and Proposed Settings Report for electrical protective devices at a facility, detailing comparisons between current and planned configurations for medium voltage (MV) fuses, MV relays, low voltage (LV) fuses, LV static trip breakers, and LV thermal magnetic breakers.

The report documents protective device settings across multiple voltage levels and equipment types. Section 4.2 covers MV fuses operating at 12,470 volts, listing manufacturers including Cooper, Bussmann, and GE, with cartridge sizes ranging from 5E to 200E and trip ratings from 5 to 125 amperes. Section 4.3 presents MV protective relay settings from Eaton EDR3000 and EDR5000 devices with CT ratios ranging from 400:5 to 1,200:5, documenting five segments of protection parameters including phase and ground protection functions. Section 4.4 catalogs LV fuses at 208, 240, and 480 volts from manufacturers Bussmann, Gould Shawmut, and Littelfuse, with amperage ratings between 30A and 600A and multiple cartridge types (FRS-R, A2K, TR, TRS, FLSR). Section 4.5 details LV static trip breakers with sensor amperage ratings from 150A to 4,000A, documenting long-time pickup (LTPU), long-time delay (LTD), short-time pickup (STPU), short-time delay (STD), instantaneous (INST), ground fault pickup (GFPU), and ground fault delay (GFD) settings. Section 4.6 provides thermal magnetic breaker configurations across multiple panels and switchboards with fixed, thermal curve, and instantaneous settings. Highlighted values throughout indicate proposed setting changes from existing configurations.

View the file

Other files

File Type Posted
36C24426Q0250 0013_1.docx DOCX document
36C24426Q0250 0012_1.docx DOCX document
36C24426Q0250 0011_1.docx DOCX document
36C24426Q0250 0010_1.docx DOCX document
36C24426Q0250 0009_1.docx DOCX document
36C24426Q0250 0008_1.docx DOCX document
36C24426Q0250 0007_1.docx DOCX document
36C24426Q0250 0006_1.docx DOCX document
36C24426Q0250 0005_1.docx DOCX document
36C24426Q0250 0004_1.docx DOCX document
36C24426Q0250 0003_1.docx DOCX document
36C24426Q0250 0002_1.docx DOCX document
36C24426Q0250 0001_1.docx DOCX document
Atch 3 ANSINETA MTS-2015 Reference Tables and Appendix A.pdf PDF
36C24426Q0250_1.docx DOCX document
Atch 9 36C24426Q0250.pdf PDF
Atch 8 VAAR 852.219-75 VA Notice of Limitations on Subcontracting.docx DOCX document
Atch 6 SCA WD No. 2015-4239 Rev31 12-03-2025.pdf PDF
Atch 7 Price Cost Schedule.docx DOCX document
Atch 5 Power Systems Study Drawings 1 through 22.pdf PDF
Atch 2 ANSINETA MTS-2015 Maintenance inspection and testing.pdf PDF
Atch 1 Inventory of Electrical Power Distribution System Equipment.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

4.2 Existing and Proposed Settings Report - MV Fuses

Prot Dev Voltage Manufacturer Type Description Cartridge

Cartridge

Size Trip Manufacturer Type Description Cartridge

Cartridge

Size Trip

01-CHALLENGER-XF-FU-BAY 12,470 COOPER Bay-O-Net Current Sensing Fuse Link, 23kV

C4-C17 353C14 65 65 COOPER Bay-O-Net Current Sensing Fuse Link, 23kV

C4-C17 353C14 65 65

01-MV-GE-XF-FU-BAY 12470 COOPER Bay-O-Net Current Sensing Fuse Link, 23kV

C4-C17 353C14 65 65 COOPER Bay-O-Net Current Sensing Fuse Link, 23kV

C4-C17 353C14 65 65

01-MV-USS-ADD-FDS-FU 12470 BUSSMANN MV155, 15.5kV E-Rated 5E-200E MV155-125E 125 125 BUSSMANN MV155, 15.5kV E-Rated 5E-200E MV155-125E 125 125

01-MV-USS-ADD-MVS-PS1-FU 12470 GE 9F60 EJ-1, 15kV E-Rated 125E-175E EJ-1, 125E 125 125 GE 9F60 EJ-1, 15kV E-Rated 125E-175E EJ-1, 125E 125 125

01-MV-USS-ADD-MVS-PS2-FU 12470 GE 9F60 EJ-1, 15kV E-Rated 125E-175E EJ-1, 125E 125 125 GE 9F60 EJ-1, 15kV E-Rated 125E-175E EJ-1, 125E 125 125

01-MV-USS-SWBD-A-XF-FU 12,470 GE 9F60 EJ0-1, 15.5kV E-Rated 1E-100E EJO-1, 100E 100 100 GE 9F60 EJ0-1, 15.5kV E-Rated 1E-100E EJO-1, 100E 100 100

01-MV-USS-SWBD-B-XF-FU 12470 GE 9F60 EJ0-1, 15.5kV E-Rated 1E-100E EJO-1, 100E 100 100 GE 9F60 EJ0-1, 15.5kV E-Rated 1E-100E EJO-1, 100E 100 100

11-MV-USS-SWBD-XF-FU 12470 CUTLER-

HAMMER

BHLE, 15.5kV E-Rated 40E-250E BHLE, 125E 125 125 CUTLER-

HAMMER

BHLE, 15.5kV E-Rated 40E-250E BHLE, 125E 125 125

27-MV-USS-XF-FU 12470 GE 9F60 EJ0-1, 15.5kV E-Rated 1E-100E EJO-1, 100E 100 100 GE 9F60 EJ0-1, 15.5kV E-Rated 1E-100E EJO-1, 100E 100 100

31A-MV-XF-PNL1-FU 12470 COOPER X-Limiter, 8.3-23kV E-Rated 1.5E-100E X-Limiter, 5E 5 5 COOPER X-Limiter, 8.3-23kV E-Rated 1.5E-100E X-Limiter, 5E 5 5

31B-MV-XF-PNL2-FU 12,470 COOPER X-Limiter, 8.3-23kV E-Rated 1.5E-100E X-Limiter, 5E 5 5 COOPER X-Limiter, 8.3-23kV E-Rated 1.5E-100E X-Limiter, 5E 5 5

Existing Proposed

Note: Highlighted values indicate a proposed setting change. 4.2-1

4.3 Existing and Proposed Protective Device Settings Report - MV Relays

Protective Device Func. Mfr.

Class

Desc. CT Ratio Seg. 1 Seg. 2 Seg. 3 Seg. 4 Seg. 5 Seg. 1 Seg. 2 Seg. 3 Seg. 4 Seg. 5

31A-MV-SUB-A-52-1 (50P/51P) Phase EATON

EDR-

400 : 5

51P[1], (0.02-

4 x In) 1

ANSI VINV

50P[1], (0.02-

40 x In) 10

Delay, 50P[1] 0.25

51P[1], (0.02-

4 x In) 1

ANSI VINV

50P[1], (0.02-

40 x In) 10

Delay, 50P[1] 0.25

31A-MV-SUB-A-52-1A (50P/51P) Phase EATON

EDR-

400 : 5

51P[1], (0.02-

4 x In) 0.40

ANSI VINV

50P[1], (0.02-

40 x In) 10

Delay, 50P[1] 0.25

51P[1], (0.02-

4 x In) 0.40

ANSI VINV

50P[1], (0.02-

40 x In) 10

Delay, 50P[1] 0.25

31A-MV-SUB-A-52-1B (50P/51P) Phase EATON

EDR-

400 : 5

51P[1], (0.02-

4 x In) 0.50

ANSI VINV

50P[1], (0.02-

40 x In) 10

Delay, 50P[1] 0.25

51P[1], (0.02-

4 x In) 0.50

ANSI VINV

50P[1], (0.02-

40 x In) 10

Delay, 50P[1] 0.25

31A-MV-SUB-A-52-1C (50P/51P) Phase EATON

EDR-

500 : 5

51P[1], (0.02-

4 x In) 0.40

ANSI VINV

50P[1], (0.02-

40 x In) 5

Delay, 50P[1] 0.25

51P[1], (0.02-

4 x In) 0.40

ANSI VINV

8.00

50P[1], (0.02-

40 x In) 5

Delay, 50P[1] 0.25

31A-MV-SUB-A-MB (50G/51G) Ground EATON

EDR-

1,200 : 5

51X (0.02 -

20 x In) 0.5

ANSI MINV

50X[1] (0.02

- 20 x In) 1

Delay, 50X[1] 0.5

51X (0.02 -

20 x In) 0.5

ANSI MINV

50X[1] (0.02

- 20 x In) 1

Delay, 50X[1] 0.5

31A-MV-SUB-A-MB (50P/51P) Phase EATON

EDR-

1,200 : 5

51P (0.02 -

40 x In) 1

ANSI VINV

50P[1] (0.02 -

40 x In) 40

Delay, 50P[1] 0.25

51P (0.02 -

40 x In) 1

ANSI VINV

50P[1] (0.02 -

40 x In) 40

Delay, 50P[1] 0.25

31B-MV-SUB-B-52-2 (50P/51P) Phase EATON

EDR-

400 : 5

51P[1], (0.02-

4 x In) 1

ANSI VINV

50P[1], (0.02-

40 x In) 10

Delay, 50P[1] 0.25

51P[1], (0.02-

4 x In) 1

ANSI VINV

50P[1], (0.02-

40 x In) 10

Delay, 50P[1] 0.25

31B-MV-SUB-B-52-2A (50P/51P) Phase EATON

EDR-

400 : 5

51P[1], (0.02-

4 x In) 0.40

ANSI VINV

50P[1], (0.02-

40 x In) 10

Delay, 50P[1] 0.25

51P[1], (0.02-

4 x In) 0.40

ANSI VINV

50P[1], (0.02-

40 x In) 10

Delay, 50P[1] 0.25

31B-MV-SUB-B-52-2B (50P/51P) Phase EATON

EDR-

400 : 5

51P[1], (0.02-

4 x In) 0.50

ANSI VINV

50P[1], (0.02-

40 x In) 10

Delay, 50P[1] 0.25

51P[1], (0.02-

4 x In) 0.50

ANSI VINV

50P[1], (0.02-

40 x In) 10

Delay, 50P[1] 0.25

31B-MV-SUB-B-52-2C (50P/51P) Phase EATON

EDR-

400 : 5

51P[1], (0.02-

4 x In) 0.40

ANSI VINV

50P[1], (0.02-

40 x In) 5

Delay, 50P[1] 0.25

51P[1], (0.02-

4 x In) 0.40

ANSI VINV

50P[1], (0.02-

40 x In) 5

Delay, 50P[1] 0.25

31B-MV-SUB-B-MB (50G/51G) Ground EATON

EDR-

1,200 : 5

51X (0.02 -

20 x In) 0.5

ANSI MINV

50X[1] (0.02

- 20 x In) 1

Delay, 50X[1] 0.5

51X (0.02 -

20 x In) 0.5

ANSI MINV

50X[1] (0.02

- 20 x In) 1

Delay, 50X[1] 0.5

31B-MV-SUB-B-MB (50P/51P) Phase EATON

EDR-

1,200 : 5

51P (0.02 -

40 x In) 1

ANSI VINV

50P[1] (0.02 -

40 x In) 40

Delay, 50P[1] 0.25

51P (0.02 -

40 x In) 1

ANSI VINV

50P[1] (0.02 -

40 x In) 40

Delay, 50P[1] 0.25

EXISTING PROPOSED

Note: Highlighted values indicate a proposed setting change. 4.3-1

4.4. Existing & Proposed Settings Report LV - Fuses

Prot Dev Voltage Manufacturer Type Descr. Cartridge

Cart.

Size Trip Type Descr. Cartridge

Cart.

Size Trip

01-C10-EL-FDS-FU 208 BUSSMANN FRS-R, 600V Class RK5 1-600A FRS-R 60 60 FRS-R, 600V Class RK5 1-600A FRS-R 60 60

01-C10L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 100 100 A2K, 250V Class RK1 15-600A A2K 100 100

01-C10P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-C11-E1-FDS-FU 208 BUSSMANN FRS-R, 600V Class RK5 1-600A FRS-R 60 60 FRS-R, 600V Class RK5 1-600A FRS-R 60 60

01-C11-EL-FDS-FU 208 BUSSMANN FRS-R, 600V Class RK5 1-600A FRS-R 60 60 FRS-R, 600V Class RK5 1-600A FRS-R 60 60

01-C11L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 100 100 A2K, 250V Class RK1 15-600A A2K 100 100

01-C11P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-C12L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 100 100 A2K, 250V Class RK1 15-600A A2K 100 100

01-C12PA-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-C12PB-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 300 300 A2K, 250V Class RK1 15-600A A2K 300 300

01-C1L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-C1P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-C2-EL-FDS-FU 208 BUSSMANN FRS-R, 600V Class RK5 1-600A FRS-R 60 60 FRS-R, 600V Class RK5 1-600A FRS-R 60 60

01-C2L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 100 100 A2K, 250V Class RK1 15-600A A2K 100 100

01-C2P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 100 100 A2K, 250V Class RK1 15-600A A2K 100 100

01-C3-EL-FDS-FU 208 BUSSMANN FRS-R, 600V Class RK5 1-600A FRS-R 60 60 FRS-R, 600V Class RK5 1-600A FRS-R 60 60

01-C3L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-C3P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-C4-E1-FDS-FU 208 BUSSMANN FRS-R, 600V Class RK5 1-600A FRS-R 60 60 FRS-R, 600V Class RK5 1-600A FRS-R 60 60

01-C4L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-C4P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-C5-EL-FDS-FU 208 BUSSMANN FRS-R, 600V Class RK5 1-600A FRS-R 60 60 FRS-R, 600V Class RK5 1-600A FRS-R 60 60

01-C5L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 100 100 A2K, 250V Class RK1 15-600A A2K 100 100

01-C5P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-C6L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 100 100 A2K, 250V Class RK1 15-600A A2K 100 100

01-C6P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-C7-E-FDS-FU 208 BUSSMANN FRS, 600V Class K5 15-600A FRS 60 60 FRS, 600V Class K5 15-600A FRS 60 60

01-C7L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 100 100 A2K, 250V Class RK1 15-600A A2K 100 100

01-C7P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 225 225 A2K, 250V Class RK1 15-600A A2K 225 225

01-C8L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 100 100 A2K, 250V Class RK1 15-600A A2K 100 100

Existing Proposed

Note: Highlighted values indicate a proposed fuse change, see Section 4.7 4.4-1

Cart.

Size Trip Type Descr. Cartridge

Cart.

Size Trip

Existing Proposed

01-C8P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-CBL-BP-FU 208 GOULD SHAWMUT A6K, 600V Class RK1 15-600A A6K 100 100 A6K, 600V Class RK1 15-600A A6K 100 100

01-CBP-BP-FU 208 GOULD SHAWMUT A6K, 600V Class RK1 15-600A A6K 200 200 A6K, 600V Class RK1 15-600A A6K 200 200

01-CELL PHONE-480-FDS-FU 480 BUSSMANN FRS-R, 600V Class RK5 1-600A FRS-R 200 200 FRS-R, 600V Class RK5 1-600A FRS-R 200 200

01-E10L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 100 100 A2K, 250V Class RK1 15-600A A2K 100 100

01-E10P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 100 100 A2K, 250V Class RK1 15-600A A2K 100 100

01-E11L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 100 100 A2K, 250V Class RK1 15-600A A2K 100 100

01-E11P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-E12P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-E1L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-E1P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-E2-EL-FDS-FU 208 GOULD SHAWMUT TRS, 600V Class RK5 15-600A TRS 60 60 TRS, 600V Class RK5 15-600A TRS 60 60

01-E2L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-E2P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-E3-EL-FDS-FU 208 GOULD SHAWMUT TRS, 600V Class RK5 15-600A TRS 60 60 TRS, 600V Class RK5 15-600A TRS 60 60

01-E3L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-E3P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-E4P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-E5P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-E6L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-E6M-BP-FU 480 GOULD SHAWMUT TRS, 600V Class RK5 0.1-600A TRS-100 100 100 TRS, 600V Class RK5 0.1-600A TRS-100 100 100

01-E6P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-E7L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 100 100 A2K, 250V Class RK1 15-600A A2K 100 100

01-E7P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 225 225 A2K, 250V Class RK1 15-600A A2K 225 225

01-E8L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-E8P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-EB-EL-FDS-FU 208 GOULD SHAWMUT TRS, 600V Class RK5 15-600A TRS 60 60 TRS, 600V Class RK5 15-600A TRS 60 60

01-EBL-BP-FU 208 GOULD SHAWMUT A6K, 600V Class RK1 15-600A A6K 200 200 A6K, 600V Class RK1 15-600A A6K 200 200

01-EBP-BP-FU 208 GOULD SHAWMUT A6K, 600V Class RK1 15-600A A6K 200 125 A6K, 600V Class RK1 15-600A A6K 200 125

01-LP8A-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-N1L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-N1P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-N2-L-BP-FU 208 GOULD SHAWMUT OT, 250V Class K-5 15-600A OT 200 200 OT, 250V Class K-5 15-600A OT 200 200

01-N2L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

Note: Highlighted values indicate a proposed fuse change, see Section 4.7 4.4-2

Cart.

Size Trip Type Descr. Cartridge

Cart.

Size Trip

Existing Proposed

01-N3L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-N3P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-N5L-BP-FU 208 GOULD SHAWMUT A6K, 600V Class RK1 15-600A A6K 100 100 A6K, 600V Class RK1 15-600A A6K 100 100

01-N5PB-BP-FU 208 GOULD SHAWMUT A6K, 600V Class RK1 15-600A A6K 200 200 A6K, 600V Class RK1 15-600A A6K 200 200

01-NBL-BP-FU 208 GOULD SHAWMUT A6K, 600V Class RK1 15-600A A6K 200 200 A6K, 600V Class RK1 15-600A A6K 200 200

01-NBP-BP-FU 208 GOULD SHAWMUT A6K, 600V Class RK1 15-600A A6K 200 200 A6K, 600V Class RK1 15-600A A6K 200 200

01-PP-1-FDS-FU 208 GOULD SHAWMUT A6K, 600V Class RK1 15-600A A6K 100 100 A6K, 600V Class RK1 15-600A A6K 100 100

01-PS-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 100 100 A2K, 250V Class RK1 15-600A A2K 100 100

01-W1-E-FDS-FU 208 GOULD SHAWMUT TRS, 600V Class RK5 0.1-600A TRS-60 60 60 TRS, 600V Class RK5 0.1-600A TRS-60 60 60

01-W1-L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-W1-P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-W10L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-W10P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-W11L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 100 100 A2K, 250V Class RK1 15-600A A2K 100 100

01-W11P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-W12P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-W1P-2-BP-FU 208 BUSSMANN FRN-R, 250V Class RK5 1-600A FRN-R 200 200 FRN-R, 250V Class RK5 1-600A FRN-R 200 200

01-W2-EL-FU 208 GOULD SHAWMUT TRS, 600V Class RK5 0.1-600A TRS-60 60 60 TRS, 600V Class RK5 0.1-600A TRS-60 60 60

01-W2-L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-W2P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-W3-L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-W3LB-BP-FU 208 GOULD SHAWMUT TRS, 600V Class RK5 0.1-600A TRS-200 200 200 TRS, 600V Class RK5 0.1-600A TRS-200 200 200

01-W4L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-W4P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-W4P2-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-W5-E1-FDS-FU 208 GOULD SHAWMUT TRS, 600V Class RK5 0.1-600A TRS-60 60 60 TRS, 600V Class RK5 0.1-600A TRS-60 60 60

01-W5L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-W5P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-W6L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-W6P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-W7-EL-FU 208 GOULD SHAWMUT TRS, 600V Class RK5 0.1-600A TRS-60 60 60 TRS, 600V Class RK5 0.1-600A TRS-60 60 60

01-W7L(A)-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-W7P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-W8-EL-FU 208 GOULD SHAWMUT TRS, 600V Class RK5 0.1-600A TRS-60 60 60 TRS, 600V Class RK5 0.1-600A TRS-60 60 60

Note: Highlighted values indicate a proposed fuse change, see Section 4.7 4.4-3

Cart.

Size Trip Type Descr. Cartridge

Cart.

Size Trip

Existing Proposed

01-W8L-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 200 200 A2K, 250V Class RK1 15-600A A2K 200 200

01-W8P-BP-FU 208 GOULD SHAWMUT A2K, 250V Class RK1 15-600A A2K 150 150 A2K, 250V Class RK1 15-600A A2K 150 150

01-XF-ATS-1B-PRI-FDS-FU 480 GOULD SHAWMUT TRS, 600V Class RK5 0.1-600A TRS-400 400 400 TRS, 600V Class RK5 0.1-600A TRS-400 400 400

01-XF-ATS-4-FDS-FU 480 GOULD SHAWMUT TRS, Class RK5 15-600A TRS 400 400 TRS, Class RK5 15-600A TRS 400 400

01-XF-ATS-6-FDS-FU 480 GOULD SHAWMUT TRS, Class RK5 15-600A TRS 200 200 TRS, Class RK5 15-600A TRS 200 200

01-XF-ATS-7-B1-FDS-FU 480 GOULD SHAWMUT TRS, Class RK5 15-600A TRS 600 450 TRS, Class RK5 15-600A TRS 600 450

01-XF-B13-480-FDS-FU 480 LITTELFUSE FLSR, 600V RK5 15-600A FLSR 100 100 FLSR, 600V RK5 15-600A FLSR 100 100

01-XF-BLDG 8-FDS-FU 208 LITTELFUSE FLSR, 600V RK5 15-600A FLSR 400 400 FLSR, 600V RK5 15-600A FLSR 400 400

01-XF-PLUMBING SHOP-480-

FDS-FU

480 GOULD SHAWMUT TRS, 600V Class RK5 15-600A TRS 100 100 TRS, 600V Class RK5 15-600A TRS 100 100

05-MFDS-FU 208 GOULD SHAWMUT TR, 250V Class RK5 15-600A TR 400 250 TR, 250V Class RK5 15-600A TR 400 250

06-MDP-SW1 208 GOULD SHAWMUT TR, 250V Class RK5 15-600A TR 200 150 TR, 250V Class RK5 15-600A TR 200 150

06-MDP-SW2 208 GOULD SHAWMUT TR, 250V Class RK5 15-600A TR 200 125 TR, 250V Class RK5 15-600A TR 200 125

06-MDP-SW3 208 GOULD SHAWMUT TR, 250V Class RK5 15-600A TR 200 125 TR, 250V Class RK5 15-600A TR 200 125

08-MAIN-FDS-FU 480 LITTELFUSE FLSR, 600V RK5 15-600A FLSR 400 400 FLSR, 600V RK5 15-600A FLSR 400 400

11-LE-1-FDS-FU 208 LITTELFUSE FLSR, 600V RK5 15-600A FLSR 100 100 FLSR, 600V RK5 15-600A FLSR 100 100

22-PICNIC-FDS-FU 240 BUSSMANN FRS, 600V Class K5 15-600A FRS 30 30 FRS, 600V Class K5 15-600A FRS 30 30

27-FIRE PIT-FDS-FU 208 BUSSMANN FRS-R, Class RK5 15-600A FRS-R 60 45 FRS-R, Class RK5 15-600A FRS-R 60 45

27-KITCHEN-FDS-FU 208 BUSSMANN FRN-R, 250V Class RK5 1-600A FRN-R 225 225 FRN-R, 250V Class RK5 1-600A FRN-R 225 225

27-XF-EC2-2-FDS-FU 480 BUSSMANN FRS-R, Class RK5 15-600A FRS-R 30 25 FRS-R, Class RK5 15-600A FRS-R 30 25

27-XF-EC4-3-FDS-FU 480 GOULD SHAWMUT TRS, 600V Class RK5 0.1-600A TRS-125 125 125 TRS, 600V Class RK5 0.1-600A TRS-125 125 125

27-XF-ELS1-1-FDS-FU 480 BUSSMANN FRS-R, Class RK5 15-600A FRS-R 60 60 FRS-R, Class RK5 15-600A FRS-R 60 60

27-XF-ELS4-2-FDS-FU 480 GOULD SHAWMUT TRS, 600V Class RK5 0.1-600A TRS-100 100 100 TRS, 600V Class RK5 0.1-600A TRS-100 100 100

28-XF-EPP1-FDS-FU 480 BUSSMANN FRS, 600V Class K5 15-600A FRS 60 40 FRS, 600V Class K5 15-600A FRS 60 40

30-SMOKE SHED-FDS-FU 240 GOULD SHAWMUT TR, 250V Class RK5 15-600A TR 100 100 TR, 250V Class RK5 15-600A TR 100 100

Note: Highlighted values indicate a proposed fuse change, see Section 4.7 4.4-4

4.5. Existing & Proposed Settings Report – LV Static Trip Breakers

DevName Volt. Manuf. Type Sens. LTPU LTD STPU STD INST GFPU GFD LTPU LTD STPU STD INST GFPU GFD

01-CHALLENGER

SWBD-1

CHALLEN

GER

CK 200 1.0 (200A) LTD 8.0 (1600A)

STD (I^s T

On)

5 x Ig

(250A)

150 ms

(I^s T Off)

1.0 (200A) LTD

8.0

(1600A)

STD (I^s T

On)

5 x Ig

(250A)

150 ms (I^s

T Off)

01-CHALLENGER

SWBD-2

WESTINGH

OUSE

ND 1,200

1.0

(1200A)

LTD 6.0 (7200A)

STD (I^s T

On)

4 x Ig

(800A)

150 ms

(I^s T Off)

1.0

(1200A)

LTD

5.0

(6000A)

STD (I^s T

Off)

4 x Ig

(800A)

150 ms (I^s

T Off)

01-CHALLENGER

SWBD-3

CHALLEN

GER

CK 200 1.0 (200A) LTD 8.0 (1600A)

STD (I^s T

On)

5 x Ig

(250A)

150 ms

(I^s T Off)

1.0 (200A) LTD

8.0

(1600A)

STD (I^s T

On)

5 x Ig

(250A)

150 ms (I^s

T Off)

01-CHALLENGER

SWBD-4

CHALLEN

GER

CK 400 1.0 (400A) LTD 5.0 (2000A)

STD (I^s T

On)

2 x Ig

(160A)

150 ms

(I^s T Off)

1.0 (400A) LTD

5.0

(2000A)

STD (I^s T

On)

2 x Ig

(160A)

150 ms (I^s

T Off)

01-CHALLENGER

SWBD-MB

208 GE TP 2,500

01-E1-1 208 SQUARE D LG 400

(400A) 0.5

1.5 (600A)

OR Fixed

(4914A)

400 (400A) 0.5

1.5 (600A)

OR Fixed

(4914A)

01-EDP-SWBD-10 480 SQUARE D LJ 400

(400A)

0.5 1.5 (600A) 400 (400A) 2 4 (1600A)

01-GE SWBD-1 208 GE TKH 800 1 (800A) 4 4 (3200A)

Max (I^s T

Off) 7 (5600A) 1 (800A) 4 4 (3200A)

Max (I^s T

Off) 7 (5600A)

01-GE SWBD-2 208 GE TKH 800 0.5 (400A) 3 7 (2800A)

Max (I^s T

Off) 7 (5600A) 0.2 (160A)

Min (I^s T

Off)

0.5 (400A) 3 7 (2800A)

Max (I^s T

Off) 7 (5600A) 0.2 (160A)

Min (I^s T

Off)

01-GE SWBD-3 208 GE TKH 800 0.5 (400A) 3 5 (2000A)

Max (I^s T

Off) 10 (8000A)

0.35

(280A)

Int (I^s T

Off)

0.5 (400A) 3 5 (2000A)

Max (I^s T

Off) 10 (8000A)

0.35

(280A)

Min (I^s T

Off)

01-GE SWBD-4 208 GE TJH 600 1 (600A) 1 7 (4200A)

Int (I^s T

Off) 7 (4200A) 0.2 (120A)

Int (I^s T

Off) 1 (600A) 1 7 (4200A)

Int (I^s T

Off) 7 (4200A) 0.2 (120A)

Min (I^s T

Off)

01-GE SWBD-MB 208 GE TP 2,500 1 (2500A) 3 8 (20000A)

Max (I^s T

Off)

(32500A)

0.29

(725A)

Max (I^s T

Off) 1 (2500A) 3 8 (20000A)

Max (I^s T

Off)

3.5

(8750A)

0.37

(925A)

Max (I^s T

Off)

01-GEN-ECB-CB 480 GE TRL 2,000 1 (2000A) 4 4 (8000A)

Int (I^s T

Off) 4 (8000A)

0.75

(1500A) 4 4 (6000A)

Int (I^s T

Off) 4 (8000A)

01-MD-KP-3 208 SQUARE D LG 600

(600A) 16 11 (6600A) 600 (600A) 16 11 (6600A)

01-MP-1-MB 208 SQUARE D PG 1,000

Fixed

(1000A) Fixed 8 (8000A)

Fixed

(1000A) Fixed 4 (4000A)

01-USS-ADD-SWBD-

480 SQUARE D LX 300 1.0 (300A) 10 2.5 (750A) 0.2 8 (2400A)

0.75

(300A)

0.1 1.0 (300A) 14 8 (2400A) 0.5 8 (2400A)

0.75

(300A) 0.1

01-USS-ADD-SWBD-

480 SQUARE D LX 400 1.0 (400A) 14 8 (3200A) 0.1 8 (3200A)

0.75

(300A)

0.1 1.0 (400A) 14 8 (3200A) 0.1 8 (3200A)

0.75

(300A) 0.1

EXISTING PROPOSED

Notes: 1. Highlighted values with red text indicate a proposed setting change. 4.5-1

EXISTING PROPOSED

01-USS-ADD-SWBD-

480 SQUARE D LX 225 1.0 (225A) 2 8 (1800A) 0.1 8 (1800A)

0.65

(162.5A)

0.1 1.0 (225A) 2 8 (1800A) 0.1 8 (1800A)

0.65

(162.5A) 0.1

01-USS-ADD-SWBD-

480 SQUARE D LX 225 1.0 (225A) 14 8 (1800A) 0.1 8 (1800A)

0.75

(187.5A)

0.1 1.0 (225A) 14 8 (1800A) 0.1 8 (1800A)

0.75

(187.5A) 0.1

01-USS-ADD-SWBD-

480 SQUARE D LX 400 1.0 (400A) 14 8 (3200A) 0.1 8 (3200A)

0.75

(300A)

0.1 1.0 (400A) 14 8 (3200A) 0.1 8 (3200A)

0.75

(300A) 0.1

01-USS-ADD-SWBD-

480 SQUARE D LX 225 1.0 (225A) 14 8 (1800A) 0.1 8 (1800A)

0.65

(162.5A)

0.1 1.0 (225A) 14 8 (1800A) 0.1 8 (1800A)

0.65

(162.5A) 0.1

01-USS-ADD-SWBD-

480 SQUARE D LX 225 1.0 (225A) 14 8 (1800A) 0.1 8 (1800A)

0.65

(162.5A)

0.1 1.0 (225A) 14 8 (1800A) 0.1 8 (1800A)

0.65

(162.5A) 0.1

01-USS-ADD-SWBD-

480 SQUARE D LX 400 1.0 (400A) 14 8 (3200A) 0.1 8 (3200A)

0.75

(300A)

0.1 1.0 (400A) 14 8 (3200A) 0.1 8 (3200A)

0.75

(300A) 0.1

01-USS-ADD-SWBD-

480 SQUARE D LJ 400

(400A)

0.5 1.5 (600A) 400 (400A) 0.5 1.5 (600A)

01-USS-ADD-SWBD-

480 SQUARE D LX 225 1.0 (225A) 14 8 (1800A) 0.2 8 (1800A)

0.61

(152.5A)

0.1 1.0 (225A) 14 8 (1800A) 0.2 8 (1800A)

0.61

(152.5A) 0.1

01-USS-ADD-SWBD-

480 SQUARE D LX 600 1.0 (600A) 12 8 (4800A) 0.1 8 (4800A)

0.67

(402A)

0.1 1.0 (600A) 12 8 (4800A) 0.1 7 (4200A)

0.67

(402A) 0.1

01-USS-ADD-SWBD-

480 SQUARE D LX 600 1.0 (600A) 14 8 (4800A) 0.2 8 (4800A)

0.75

(450A)

0.1 1.0 (600A) 14 8 (4800A) 0.2 7 (4200A)

0.75

(450A) 0.1

01-USS-ADD-SWBD-

480 SQUARE D LX 600 1.0 (600A) 14 8 (4800A) 0.1 8 (4800A)

0.75

(450A)

0.1 1.0 (600A) 14 8 (4800A) 0.1 7 (4200A)

0.75

(450A) 0.1

01-USS-ADD-SWBD-

480 SQUARE D LX 450 1.0 (450A) 6 8 (3600A) 0.1 7 (3150A)

0.75

(450A)

0.1 1.0 (450A) 6 8 (3600A) 0.1 7 (3150A)

0.75

(450A) 0.1

01-USS-ADD-SWBD-

480 SQUARE D LX 400 1.0 (400A) 2 8 (3200A) 0.1 5 (2000A)

0.75

(300A)

0.1 1.0 (400A) 2 8 (3200A) 0.1 5 (2000A)

0.75

(300A) 0.1

01-USS-ADD-SWBD-

480 SQUARE D LX 225 1.0 (225A) 14 8 (1800A) 0.1 8 (1800A)

0.75

(187.5A)

0.1 1.0 (225A) 14 8 (1800A) 0.1 8 (1800A)

0.75

(187.5A) 0.1

01-USS-ADD-SWBD-

480 SQUARE D LX 400 1.0 (400A) 14 8 (3200A) 0.1 8 (3200A)

0.75

(300A)

0.1 1.0 (400A) 14 8 (3200A) 0.1 8 (3200A)

0.75

(300A) 0.1

01-USS-ADD-SWBD-

MB

480 SQUARE D SE 3,000

0.5

(1500A) 2 2 (6000A)

0.1 (I^s T

Off)

3.0 (9000A)

(630A)

0.32 (I^s T

Off)

0.5

(1500A) 2 2 (6000A)

0.1 (I^s T

Off)

3.0

(9000A) 800 (630A)

0.32 (I^s T

Off)

01-USS-SWBD-A-1 208 GE

AKRU-

30S 400 1 (400A) 4 10 (4000A) 0.4 (320A)

Min (I^s T

Off) 1 (400A) 4 10 (4000A) 0.4 (320A)

Min (I^s T

Off)

Notes: 1. Highlighted values with red text indicate a proposed setting change. 4.5-2

EXISTING PROPOSED

01-USS-SWBD-A-10 208 GE

AKRU-

30S 150 1 (150A) 4 10 (1500A) 0.4 (60A)

Min (I^s T

Off) 1 (150A) 4 10 (1500A) 0.4 (60A)

Min (I^s T

Off)

01-USS-SWBD-A-11 208 GE

AKRU-

30S 400 1 (400A) 3 10 (4000A) 0.4 (320A)

Min (I^s T

Off) 1 (400A) 3 10 (4000A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-A-12 208 GE

AKRU-

30S 300 1.1 (330A) 4 10 (3000A) 0.4 (320A)

Min (I^s T

Off)

0.8 (240A) 4 13 (3900A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-A-13 208 GE

AKRU-

30S 400 1 (400A) 4 10 (4000A) 0.4 (320A)

Min (I^s T

Off) 1 (400A) 4 10 (4000A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-A-14 208 GE

AKRU-

30S 800 1 (800A) 4 10 (8000A) 0.4 (320A)

Min (I^s T

Off) 1 (800A) 4 10 (8000A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-A-15 208 GE

AKRU-

30S 800 0.5 (400A) 3 10 (8000A) 0.4 (320A)

Min (I^s T

Off)

0.5 (400A) 4 10 (8000A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-A-16 208 GE

AKRU-

30S 800 1.1 (880A) 4 10 (8000A) 0.4 (320A)

Min (I^s T

Off)

1.1 (880A) 4 10 (8000A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-A-17 208 GE

AKRU-

30S 800 0.5 (400A) 4 7 (5600A) 0.4 (320A)

Min (I^s T

Off)

0.5 (400A) 4 7 (5600A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-A-18 208 GE

AKRU-

30S 800 1 (800A) 4 7 (5600A) 0.4 (320A)

Min (I^s T

Off) 1 (800A) 4 7 (5600A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-A-19 208 GE

AKRU-

30S 300 0.5 (150A) 4 10 (3000A) 0.4 (320A)

Min (I^s T

Off)

0.5 (150A) 4 10 (3000A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-A-2 208 GE

AKRU-

30S 600 1 (600A) 4 1.5 (900A) 0.4 (320A)

Min (I^s T

Off) 1 (600A) 4 7 (4200A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-A-3 208

UTILITY

RELAY CO.

AC-Pro retrofit

100 %

(225A)

1200 %

(2700A)

1.28

(89.6A)

0.2 (I^s T

Off)

100 %

(225A)

1200 %

(2700A)

1.28

(89.6A)

0.2 (I^s T

Off)

01-USS-SWBD-A-4 208 GE

AKRU-

30S 600 1 (600A) 4 7 (4200A) 0.4 (320A)

Min (I^s T

Off) 1 (600A) 4 7 (4200A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-A-5 208 GE

AKRU-

30S 150 1 (150A) 4 10 (1500A) 0.4 (60A)

Min (I^s T

Off) 1 (150A) 4 10 (1500A) 0.4 (60A)

Min (I^s T

Off)

01-USS-SWBD-A-6 208 GE

AKRU-

30S 225 1 (225A) 4 10 (2250A) 0.4 (160A)

Min (I^s T

Off) 1 (225A) 4 10 (2250A) 0.4 (160A)

Min (I^s T

Off)

01-USS-SWBD-A-7 208 GE

AKRU-

30S 800 0.5 (400A) 4 10 (8000A) 0.4 (320A)

Min (I^s T

Off)

0.5 (400A) 4 10 (8000A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-A-MB 208 GE

AKR-

4,000 1 (4000A) 3 4 (16000A)

Int (I^s T

Off)

0.26

(1040A)

Max (I^s T

Off) 1 (4000A) 3 3 (12000A)

Int (I^s T

Off)

0.3

(1200A)

Max (I^s T

Off)

01-USS-SWBD-A/B-

TIE

208 GE

AKR-

4,000

0.8

(3200A) 3 4 (12800A)

Int (I^s T

Off)

0.26

(1040A)

Max (I^s T

Off)

0.75

(3000A) 3 4 (12000A)

Min (I^s T

Off)

0.2 (800A)

Min (I^s T

Off)

01-USS-SWBD-B-1 208 GE

AKRU-

30S 600 1 (600A) 4 9 (5400A) 0.4 (320A)

Min (I^s T

Off) 1 (600A) 4 9 (5400A) 0.4 (320A)

Min (I^s T

Notes: 1. Highlighted values with red text indicate a proposed setting change. 4.5-3

EXISTING PROPOSED

01-USS-SWBD-B-10 208 GE

AKRU-

30S 400 1 (400A) 4 10 (4000A) 0.4 (320A)

Min (I^s T

Off) 1 (400A) 4 10 (4000A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-B-11 208 GE

AKRU-

30S 400 1 (400A) 4 10 (4000A) 0.4 (320A)

Min (I^s T

Off) 1 (400A) 4 10 (4000A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-B-12 208 GE

AKRU-

30S 800 0.5 (400A) 4 10 (8000A) 0.4 (320A)

Min (I^s T

Off)

0.5 (400A) 4 10 (8000A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-B-13 208 GE

AKRU-

800 0.8 (640A) 4 0.4 (640A)

Min (I^s T

Off)

0.8 (640A) 4

(10400A)

0.4 (640A)

Min (I^s T

Off)

01-USS-SWBD-B-14 208 GE

AKRU-

30S 600 0.5 (300A) 4 9 (5400A) 0.4 (320A)

Min (I^s T

Off)

0.5 (300A) 4 9 (5400A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-B-16 208 GE

AKRU-

30S 225 0.6 (135A) 4 10 (2250A) 0.4 (160A)

Min (I^s T

Off)

0.6 (135A) 4 10 (2250A) 0.4 (160A)

Min (I^s T

Off)

01-USS-SWBD-B-17 208 GE

AKRU-

30S

0.7

(157.5A) 4 10 (2250A) 0.4 (160A)

Min (I^s T

Off)

0.7

(157.5A) 4 10 (2250A) 0.4 (160A)

Min (I^s T

Off)

01-USS-SWBD-B-18 208 GE

AKRU-

30S 400 0.5 (200A) 4 7 (2800A)

0.25

(100A)

Min (I^s T

Off)

0.5 (200A) 4 7 (2800A)

0.25

(100A)

Min (I^s T

Off)

01-USS-SWBD-B-19 208 GE

AKRU-

30S 800 0.5 (400A) 4 10 (8000A) 0.4 (320A)

Min (I^s T

Off)

0.5 (400A) 4 10 (8000A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-B-2 208 GE

AKRU-

30S 225 1 (225A) 4 9 (2025A) 0.4 (160A)

Min (I^s T

Off) 1 (225A) 4 9 (2025A) 0.4 (160A)

Min (I^s T

Off)

01-USS-SWBD-B-20 208 GE

AKRU-

30S 800 1 (800A) 3 7 (5600A) 0.4 (320A)

Min (I^s T

Off) 1 (800A) 4

(10400A)

0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-B-22 208 GE

AKRU-

30S 600 0.6 (360A) 4 0.4 (320A)

Min (I^s T

Off)

0.6 (360A) 4 13 (7800A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-B-4 208 GE

AKRU-

30S 225 1 (225A) 4 10 (2250A) 0.4 (160A)

Min (I^s T

Off) 1 (225A) 4 10 (2250A) 0.4 (160A)

Min (I^s T

Off)

01-USS-SWBD-B-5 208 GE

AKRU-

30S 300 0.5 (150A) 4 10 (3000A) 0.4 (160A)

Min (I^s T

Off)

0.5 (150A) 4 10 (3000A) 0.4 (160A)

Min (I^s T

Off)

01-USS-SWBD-B-6 208 GE

AKRU-

30S 150 1 (150A) 4 10 (1500A) 0.4 (60A)

Min (I^s T

Off) 1 (150A) 4 10 (1500A) 0.4 (60A)

Min (I^s T

Off)

01-USS-SWBD-B-8 208 GE

AKRU-

30S 600 1 (600A) 4 7 (4200A) 0.4 (320A)

Min (I^s T

Off) 1 (600A) 4 7 (4200A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-B-9 208 GE

AKRU-

30S 600 0.5 (300A) 4 10 (6000A) 0.4 (320A)

Min (I^s T

Off)

0.5 (300A) 4 10 (6000A) 0.4 (320A)

Min (I^s T

Off)

01-USS-SWBD-B-MB 208 GE

AKR-

4,000 1 (4000A) 3 4 (16000A)

Int (I^s T

Off)

0.26

(1040A)

Max (I^s T

Off) 1 (4000A) 3 4 (16000A)

Int (I^s T

Off)

0.3

(1200A)

Max (I^s T

Notes: 1. Highlighted values with red text indicate a proposed setting change. 4.5-4

EXISTING PROPOSED

11-EBPD-MB 480 GE 1200 1,200

1.0

(1200A) 1 1.5 (1800A)

1 (I^s T

On)

4.0 (4800A)

0.75

(900A)

GFD-02

MIN (I^s

T Off)

1.0

(1200A)

1.5

(1800A)

1 (I^s T

On)

4.0

(4800A)

0.75

(900A)

GFD-02

MIN (I^s T

Off)

11-GEN-ECB-CB 480 SQUARE D PG 1,200 1 (1200A) 0.5

(14400A)

OR Fixed

(24000A)

1 (1200A) 0.5

(14400A)

OR Fixed

(24000A)

11-MCC-CH1-MB 480 SQUARE D PX 1,200

1.0

(1200A)

7.0 4.0 (4800A)

.1 (I^s T

On)

8.0 (9600A)

0.75

(900A) 0.1

1.0

(1200A)

4.0

(4800A)

.1 (I^s T

On)

8.0

(9600A)

0.75

(900A) 0.1

11-SWBD-BP-MB 208

CUTLER-

HAMMER

RGH 2,000 A (1000A) 7 4X (4000A) 120ms

Fixed

(17500A) A (1000A) 2

3X

(3000A) Inst.

Fixed

(17500A)

11-USS-SWBD-1 480

EATON/CU

TLER-

HAMMER

MDS-

1,200

1.000

(1200A)

6.000

(7200A)

0.25 (I^s T

On)

M1(14x)

(16800A)

0.25

(300A)

.25 (I^s T

Off)

1.000

(1200A)

6.000

(7200A)

0.4 (I^s T

On)

M1(14x)

(16800A)

0.25

(300A)

.25 (I^s T

Off)

11-USS-SWBD-2 480

EATON/CU

TLER-

HAMMER

MDS-

1.000

(800A)

6.000

(4800A)

0.25 (I^s T

On)

M1(14x)

(11200A)

0.25

(200A)

.25 (I^s T

Off)

1.000

(800A)

6.000

(4800A)

0.25 (I^s T

On)

M1(14x)

(11200A)

0.25

(200A)

.25 (I^s T

Off)

11-USS-SWBD-3 480

EATON/CU

TLER-

HAMMER

MDS-

1.000

(800A)

6.000

(4800A)

0.25 (I^s T

On)

M1(14x)

(11200A)

0.25

(200A)

.25 (I^s T

Off)

1.000

(800A)

6.000

(4800A)

0.25 (I^s T

On)

M1(14x)

(11200A)

0.25

(200A)

.25 (I^s T

Off)

11-USS-SWBD-4 480

EATON/CU

TLER-

HAMMER

MDS-

1.000

(800A)

8.000

(6400A)

0.25 (I^s T

On)

M1(14x)

(11200A)

0.25

(200A)

.25 (I^s T

Off)

1.000

(800A)

8.000

(6400A)

0.25 (I^s T

On)

M1(14x)

(11200A)

0.25

(200A)

.25 (I^s T

Off)

11-USS-SWBD-5 480

EATON/CU

TLER-

HAMMER

MDS-

1.000

(400A)

8.000

(3200A)

0.1 (I^s T

Off)

8.00

(3200A)

0.35

(140A)

0.3 (I^s T

Off)

1.000

(400A) 18.5

8.000

(3200A)

0.1 (I^s T

Off)

10.00

(4000A)

0.35

(140A)

0.3 (I^s T

Off)

11-USS-SWBD-6 480

EATON/CU

TLER-

HAMMER

MDS-

0.500

(400A)

8.000

(3200A)

0.15 (I^s T

On)

M1(14x)

(11200A)

0.25

(200A)

.25 (I^s T

Off)

0.500

(400A)

8.000

(3200A)

0.15 (I^s T

On)

M1(14x)

(11200A)

0.25

(200A)

.25 (I^s T

Off)

11-USS-SWBD-MB 480

EATON/CU

TLER-

HAMMER

MDS-

3,000

1.000

(3000A)

3.000

(9000A)

0.4 (I^s T

On)

0.5

(1200A)

0.5 (I^s T

Off)

1.000

(3000A)

3.000

(9000A)

0.4 (I^s T

On)

0.5

(1200A)

0.5 (I^s T

Off)

27-USS-SWBD-12 480 GE TJ 500

1.1; 0.9

(495A) 4 6 (3000A) 0.4 (200A)

Min (I^s T

On)

1.1; 0.9

(495A) 4 6 (3000A) 0.4 (200A)

Min (I^s T

Off)

27-USS-SWBD-13 480 GE TJ 300

1.1; 1

(330A) 1 10 (3000A) 0.6 (180A)

Min (I^s T

On)

1.1; 1

(330A) 1 10 (3000A) 0.6 (180A)

Min (I^s T

Off)

27-USS-SWBD-14 480 GE TJ 200

1.1; 0.9

(198A) 1 10 (2000A) 0.6 (120A)

Min (I^s T

On)

0.9; 0.9

(162A) 1 10 (2000A) 0.6 (120A)

Min (I^s T

Notes: 1. Highlighted values with red text indicate a proposed setting change. 4.5-5

EXISTING PROPOSED

27-USS-SWBD-15 480 GE TJ 400

1.1; 0.9

(396A) 1 10 (4000A) 0.6 (120A)

Min (I^s T

On)

1.1; 0.9

(396A) 1 10 (4000A) 0.6 (120A)

Min (I^s T

Off)

27-USS-SWBD-MB 480 SQUARE D DS-416 1,200

0.9

(1080A)

20.0 4.0 (4800A)

A

(260.4A)

0.9

(1080A)

6.0

(7200A) C (480A)

28-EMDP1-MB 480 GE SS 1,600

1.00X

(1600A) C-1 6X (9600A)

ST01-Min

(I^s T Off)

0.4 (640A)

GFD01

(I^s T Off)

1.00X

(1600A) C-5

6X

(9600A)

ST01-Min

(I^s T Off)

0.4 (640A)

GFD01 (I^s

T Off)

28-GEN-ECB-CB 480 SQUARE D RG 1,600 1 (1600A) 0.5 1.5 (2400A)

0.1 (I^s T

On)

Fixed

(62000A) A (500A)

0.1 (I^s T

On) 1 (1600A) 0.5

1.5

(2400A)

0.1 (I^s T

On)

Fixed

(62000A) A (500A)

0.1 (I^s T

On)

Notes: 1. Highlighted values with red text indicate a proposed setting change. 4.5-6

4.6. Existing and Proposed Settings Report - LV Thermal Magnetic Breakers

Device

Name MFR

TYPE

MODEL

Amps

Sensor

Amps

Plug LT Setting INST Setting LT Setting INST Setting

01-13-SOUTH-MB SQUARE D QO 70 70 Fixed (730-6, 70A)

01-AA-1 EATON/CUTLER-HAMMER HFD 225 225 Fixed Fixed

01-AA-2 EATON/CUTLER-HAMMER HFD 150 150 Fixed Fixed

01-AA-3 EATON/CUTLER-HAMMER HFD 225 225 Fixed Fixed

01-ATS-1B-ECB(E)-CB GE SKHA 800 800 MAX MAX

01-ATS-4-B1-ECB-CB GE SGHA 600 600 MAX 4

01-ATS-6-B1-ECB-CB GE SGHA 400 400 MAX MAX

01-ATS-7-B1-ECB-CB GE SKHA 800 800 MAX MAX

01-B1-EP-EQP-1-1 SQUARE D ED 70 70 Fixed Fixed

01-B1-EP-EQP-1-MB SQUARE D ED 100 100 Fixed Fixed

01-B1-EP-EQP-2-1 SQUARE D QO 60 60 Fixed (730-6, 60A) Fixed (730-6, 60A)

01-B1-EP-EQP-2-MB SQUARE D QB 150 150 Fixed Fixed

01-B1N-EP-EQP-1-1 SQUARE D ED 70 70 Fixed Fixed

01-B1N-EP-EQP-1-MB SQUARE D ED 100 100 Fixed Fixed

01-B1N-EP-EQP-2-MB SQUARE D QB 150 150 Fixed Fixed

01-B1N-EP-EQP-3-MB SQUARE D HD 60 60 Fixed Fixed

01-B6-BB EATON/CUTLER-HAMMER QBHW 15 15 Fixed Fixed

01-BB-1 EATON/CUTLER-HAMMER HFD 225 225 Fixed Fixed

01-BB-2 CUTLER-HAMMER GHB 100 100 Thermal Curve INST (Fixed) Fixed Thermal Curve INST (Fixed) Fixed

01-BB-3 CUTLER-HAMMER GHB 100 100 Thermal Curve INST (Fixed) Fixed Thermal Curve INST (Fixed) Fixed

01-BB-4 CUTLER-HAMMER GHB 100 100 Thermal Curve INST (Fixed) Fixed Thermal Curve INST (Fixed) Fixed

01-C10-AC-MB SQUARE D FA 100 100 Fixed Fixed

01-C10-EL-MB SQUARE D HD 60 60 Fixed Fixed

01-C10L-MB SQUARE D QD 100 100 Fixed Fixed

01-C11-AC-MB WESTINGHOUSE BA 100 100 Fixed Fixed

01-C11-E1-MB SQUARE D HD 60 60 Fixed Fixed

01-C11-EL-MB SQUARE D HD 60 60 Fixed Fixed

01-C11L-MB SQUARE D QD 100 100 Fixed Fixed

01-C12PB-1 GE 150 70 70 Opening Clearing Curve Opening Clearing Curve

01-C1-AC-MB WESTINGHOUSE BA 100 100 Fixed Fixed

01-C1L-MB SQUARE D QD 150 150 Fixed Fixed

01-C1P-1 SQUARE D Q2H 150 150 Fixed Fixed

01-C1P-MB SQUARE D QD 200 200 Fixed Fixed

01-C2-AC-MB WESTINGHOUSE BA 100 100 Fixed Fixed

01-C2-E-ECB-CB SIEMENS BQ 100 100 Fixed Fixed

01-C2-EL-MB SQUARE D HD 60 60 Fixed Fixed

PROPOSEDEXISTING

Notes: 1. Highlighted values with red text indicate a proposed setting change. 4.6- 1

Name MFR

TYPE

MODEL

Amps

Sensor

Amps

Plug LT Setting INST Setting LT Setting INST Setting

PROPOSEDEXISTING

01-C2L-MB SQUARE D QD 100 100 Fixed Fixed

01-C3-AC-MB WESTINGHOUSE BA 100 100 Fixed Fixed

01-C3-EL-MB SQUARE D HD 60 60 Fixed Fixed

01-C4-AC-MB WESTINGHOUSE BA 100 100 Fixed Fixed

01-C4-E1-MB SQUARE D HD 60 60 Fixed Fixed

01-C5-AC-MB WESTINGHOUSE BA 100 100 Fixed Fixed

01-C5-EC-MB GE SFHA 225 225 MAX 2

01-C5-EL-MB SQUARE D HD 60 60 Fixed Fixed

01-C5P-1 GE 150 150 150 Opening Clearing Curve Opening Clearing Curve

01-C5PA-1 EATON/CUTLER-HAMMER QBHW 100 100 Fixed Fixed

01-C5PA-MB EATON/CUTLER-HAMMER HFD 150 150 Fixed Fixed

01-C6-AC-MB WESTINGHOUSE BA 100 100 Fixed Fixed

01-C6-E1-MB EATON/CUTLER-HAMMER EDB 100 100 Fixed Fixed

01-C7-AC-MB WESTINGHOUSE BA 100 100 Fixed Fixed

01-C7-E-MB SQUARE D QD 100 100 Fixed Fixed

01-C7L-MB SQUARE D QD 100 100 Fixed Fixed

01-C7P-MB SQUARE D QD 225 225 Fixed Fixed

01-C8-AC-MB WESTINGHOUSE BA 100 100 Fixed Fixed

01-C9-AC-MB WESTINGHOUSE BA 100 100 Fixed Fixed

01-CB-10-BB SQUARE D QO 15 15 Fixed Fixed

01-CB-10-MB SQUARE D QG 100 100 Fixed Fixed

01-CB-AC-MB WESTINGHOUSE BA 100 100 Fixed Fixed

01-CB-E2-1 SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

01-CB-E2-MB SQUARE D KA 125 125 Thermal Curve INST HI Thermal Curve INST HI

01-CB-EL-MB GE SFHA 225 225 MAX MIN

01-CBL-MB SQUARE D QD 100 100 Fixed Fixed

01-CBP-MB SQUARE D QD 200 200 Fixed Fixed

01-C-EP-11-MB ITE 70 70 70 LTD INST Fixed LTD INST Fixed

01-C-EP-12-MB ITE 70 70 70 LTD INST Fixed LTD INST Fixed

01-C-EP-4-MB SIEMENS BQH 70 70 Fixed Fixed

01-C-EP-B-1 ITE 300 250 250 LTD INST 7.5 LTD INST 7.5

01-C-EP-B1-MB SIEMENS BQH 70 70 Fixed Fixed

01-C-EP-B-2 ITE 300 250 250 LTD INST 7.5 LTD INST 5.00

01-C-EP-B-3 ITE 100 100 100 Opening Clearing Curve Opening Clearing Curve

01-C-EP-B-4 ITE 400 400 400 LTD INST 4.8 LTD INST 4.8

Notes: 1. Highlighted values with red text indicate a proposed setting change. 4.6- 2

Name MFR

TYPE

MODEL

Amps

Sensor

Amps

Plug LT Setting INST Setting LT Setting INST Setting

PROPOSEDEXISTING

01-C-EP-C-1 EATON/CUTLER-HAMMER KDB 200 200 Thermal Curve (Fixed) INST (5-10 x Trip) 10 Thermal Curve (Fixed) INST (5-10 x Trip) 5

01-C-EP-C-2 EATON/CUTLER-HAMMER KDB 200 200 Thermal Curve (Fixed) INST (5-10 x Trip) 10 Thermal Curve (Fixed) INST (5-10 x Trip) 10

01-CHAPEL-ECB-CB SQUARE D ML3 125 125 Thermal Curve Thermal Curve

01-DK-1 SQUARE D LA 400 400 Thermal Curve INST LO Thermal Curve INST LO

01-DK-2 SQUARE D LA 350 350 Thermal Curve INST LO Thermal Curve INST LO

01-DK-3 SQUARE D QB 225 225 Fixed Fixed

01-DK-MB SQUARE D MG 800 800 Thermal Curve INST 2 Thermal Curve INST 2

01-DP-1 SQUARE D KA 225 225 Thermal Curve INST HI Thermal Curve INST HI

01-DP-MB SQUARE D LA 400 400 Thermal Curve INST LO Thermal Curve INST LO

01-E10AC-MB SQUARE D FA 100 100 Fixed Fixed

01-E11AC-MB WESTINGHOUSE 100 100 100 Opening Clearing Curve Opening Clearing Curve

01-E1-2 SQUARE D QG 225 225 Fixed Fixed

01-E1-3 SQUARE D QG 200 200 Fixed Fixed

01-E1AC-MB WESTINGHOUSE 100 100 100 Opening Clearing Curve Opening Clearing Curve

01-E2-EL-MB SQUARE D HD 60 60 Fixed Fixed

01-E2L-SECT1-MB SQUARE D QD 200 200 Fixed Fixed

01-E3AC-MB WESTINGHOUSE 100 100 100 Opening Clearing Curve Opening Clearing Curve

01-E3-E2-MB GE THQD 225 225 Fixed Fixed

01-E3-EL-MB SQUARE D HD 60 60 Fixed Fixed

01-E3L-MB SQUARE D QD 200 200 Fixed Fixed

01-E3P-MB SQUARE D HD 150 150 Fixed Fixed

01-E4AC-MB WESTINGHOUSE 100 100 100 Opening Clearing Curve Opening Clearing Curve

01-E4-E2-MB GE THQD 225 225 Fixed Fixed

01-E5AC-MB WESTINGHOUSE 100 100 100 Opening Clearing Curve Opening Clearing Curve

01-E5-E2-MB GE THQD 225 225 Fixed Fixed

01-E6AC-MB WESTINGHOUSE 100 100 100 Opening Clearing Curve Opening Clearing Curve

01-E6-E2-MB GE THQD 225 225 Fixed Fixed

01-E6L-MB EATON/CUTLER-HAMMER EDB 150 150 Fixed Fixed

01-E6P-MB EATON/CUTLER-HAMMER EDB 225 225 Fixed Fixed

01-E7AC-MB WESTINGHOUSE 100 100 100 Opening Clearing Curve Opening Clearing Curve

01-E7-E-MB ITE 100 100 100 LTD INST Fixed LTD INST Fixed

01-E7L-BB SQUARE D QO 20 20 Fixed Fixed

01-E7L-MB SQUARE D QD 100 100 Fixed Fixed

01-E7P-MB SQUARE D QD 225 225 Fixed Fixed

01-E8AC-MB WESTINGHOUSE 100 100 100 Opening Clearing Curve Opening Clearing Curve

Notes: 1. Highlighted values with red text indicate a proposed setting change. 4.6- 3

Name MFR

TYPE

MODEL

Amps

Sensor

Amps

Plug LT Setting INST Setting LT Setting INST Setting

PROPOSEDEXISTING

01-E8-E2-MB GE THQD 225 225 Fixed Fixed

01-E9AC-MB WESTINGHOUSE 100 100 100 Opening Clearing Curve Opening Clearing Curve

01-E9-E2-MB GE THQD 225 225 Fixed Fixed

01-EB51-MB GE 150 100 100 Opening Clearing Curve Opening Clearing Curve

01-EB-EL-MB SQUARE D HD 60 60 Fixed Fixed

01-EBL-1 SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

01-EBL-MB SQUARE D QD 200 200 Fixed Fixed

01-EBP2-MB SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

01-EBP-MB SQUARE D QD 100 100 Fixed Fixed

01-EDP-1 GE SGHA 400 400 MAX MAX

01-EDP-2 GE SFHA 150 150 MAX MAX

01-EDP-3 GE SFHA 150 150 MAX MAX

01-EDP-MB GE SKHA 800 800 MAX 4

01-EDP-SWBD-1 SQUARE D LC 350 350 Thermal Curve INST LO Thermal Curve INST 7

01-EDP-SWBD-11 SQUARE D FC 100 100 Fixed Fixed

01-EDP-SWBD-2 SQUARE D 600 600 600 LTD INST 5.0 LTD INST 5.0

01-EDP-SWBD-3 SQUARE D 600 600 600 LTD INST 5.0 LTD INST 5.0

01-EDP-SWBD-4 SQUARE D LC 400 400 Thermal Curve INST LO Thermal Curve INST 5

01-EDP-SWBD-5 SQUARE D 225 225 225 LTD INST 7.00 LTD INST 10.0

01-EDP-SWBD-6 SQUARE D 225 225 225 LTD INST 7.00 LTD INST 10.0

01-EDP-SWBD-7 SQUARE D LC 400 400 Thermal Curve INST LO Thermal Curve INST 4

01-EDP-SWBD-8 SQUARE D 225 225 225 LTD INST 5.0 LTD INST 10.0

01-EDP-SWBD-9 SQUARE D 225 225 225 LTD INST 6.00 LTD INST 10.0

01-EECR1A-1 SQUARE D ED 45 45 Fixed Fixed

01-EECR1A-BP-CB SQUARE D FA 100 100 Fixed Fixed

01-EECR1B-MB SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

01-EECR2A-1 EATON/CUTLER-HAMMER HFD 30 30 Fixed Fixed

01-EECR2A-BP-CB SQUARE D FA 100 100 Fixed Fixed

01-EECR2B-MB SQUARE D QO 50 50 Fixed (730-6, 50A) Fixed (730-6, 50A)

01-EECR3A-1 SQUARE D ED 30 30 Fixed Fixed

01-EECR3A-BP-CB SQUARE D FA 100 100 Fixed Fixed

01-EECR3B-MB SQUARE D QO 50 50 Fixed (730-6, 50A) Fixed (730-6, 50A)

01-EECR4A-1 SQUARE D ED 45 45 Fixed Fixed

01-EECR4A-BP-CB SQUARE D FA 100 100 Fixed Fixed

01-EECR4B-MB SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

Notes: 1. Highlighted values with red text indicate a proposed setting change. 4.6- 4

Name MFR

TYPE

MODEL

Amps

Sensor

Amps

Plug LT Setting INST Setting LT Setting INST Setting

PROPOSEDEXISTING

01-EECR5A-1 SQUARE D ED 45 45 Fixed Fixed

01-EECR5A-BP-CB SQUARE D FA 100 100 Fixed Fixed

01-EECR5B-MB SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

01-EECR6A-1 SQUARE D ED 45 45 Fixed Fixed

01-EECR6A-BP-CB SQUARE D FA 100 100 Fixed Fixed

01-EECR6B-MB SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

01-EECR7A-1 SQUARE D ED 45 45 Fixed Fixed

01-EECR7A-BP-CB SQUARE D FA 100 100 Fixed Fixed

01-EECR7B-MB SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

01-EECR8A-1 SQUARE D ED 45 45 Fixed Fixed

01-EECR8A-BP-CB SQUARE D FA 100 100 Fixed Fixed

01-EECR8B-MB SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

01-EECR9A-1 SQUARE D ED 45 45 Fixed Fixed

01-EECR9A-BP-CB SQUARE D FA 100 100 Fixed Fixed

01-EECR9B-MB SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

01-EELS1-BP-CB SQUARE D FA 60 60 Fixed Fixed

01-EELS2-BP-CB SQUARE D FA 60 60 Fixed Fixed

01-EELS3-BP-CB SQUARE D FA 60 60 Fixed Fixed

01-EELS4-BP-CB SQUARE D FA 60 60 Fixed Fixed

01-EELS5-BP-CB SQUARE D FA 60 60 Fixed Fixed

01-EELS6-BP-CB SQUARE D FA 60 60 Fixed Fixed

01-EELS7-BP-CB SQUARE D FA 60 60 Fixed Fixed

01-EELS8-BP-CB SQUARE D FA 60 60 Fixed Fixed

01-EELS9-BP-CB SQUARE D FA 60 60 Fixed Fixed

01-EELSB-BP-CB SQUARE D FA 60 60 Fixed Fixed

01-ELP2-1 SQUARE D ED 45 45 Fixed Fixed

01-ELP3-1 SQUARE D ED 30 30 Fixed Fixed

01-ELP4-1 SQUARE D ED 125 125 Fixed Fixed

01-ELP4-BP-CB SQUARE D KA 200 200 Thermal Curve INST HI Thermal Curve INST HI

01-ELP5-1 SQUARE D ED 125 125 Fixed Fixed

01-ELP5-BP-CB SQUARE D KA 200 200 Thermal Curve INST HI Thermal Curve INST HI

01-ELP6-1 SQUARE D ED 30 30 Fixed Fixed

01-ELP6-BP-CB SQUARE D FH 100 100 Fixed Fixed

01-ELP7-1 SQUARE D ED 30 30 Fixed Fixed

01-ELP7-BP-CB SQUARE D FC 100 100 Fixed Fixed

Notes: 1. Highlighted values with red text indicate a proposed setting change. 4.6- 5

Name MFR

TYPE

MODEL

Amps

Sensor

Amps

Plug LT Setting INST Setting LT Setting INST Setting

PROPOSEDEXISTING

01-ELP8-1 SQUARE D ED 30 30 Fixed Fixed

01-ELP8-BP-CB SQUARE D FH 100 100 Fixed Fixed

01-ELP9-1 SQUARE D ED 30 30 Fixed Fixed

01-ELP9-BP-CB SQUARE D FC 100 100 Fixed Fixed

01-ELPB/1/2-BP-CB SQUARE D KA 200 200 Thermal Curve INST 5 Thermal Curve INST 5

01-ELPB-1 SQUARE D EG 70 70 Fixed Fixed

01-ELPB1-1 SQUARE D ED 45 45 Fixed Fixed

01-ELP-BP-CB SQUARE D FC 100 100 Fixed Fixed

01-ELSDP-1 GE TEY 100 100 Fixed Fixed

01-ELSDP-2 GE SFHA 200 200 MAX MAX

01-ELSDP-3 GE TEY 100 100 Fixed Fixed

01-ELSDP-4 GE TEY 100 100 Fixed Fixed

01-ELSDP-MB GE SGDA 400 400 MAX MAX

01-EMCC3-1 SQUARE D FH 100 100 Fixed Fixed

01-EMCC5-1 SQUARE D FH 100 100 Fixed Fixed

01-EMCC5-2 SQUARE D HJ 100 100 Fixed Fixed

01-EPP-1-1 SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

01-EPP-1-ECB-CB GE SFHA 225 225 MAX MAX

01-EPP1-MB SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

01-EPP-1-MB SQUARE D KA 225 225 Thermal Curve INST HI Thermal Curve INST HI

01-EPP2-MB SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

01-EPP3-MB SQUARE D QO 50 50 Fixed (730-6, 50A) Fixed (730-6, 50A)

01-EPP4(L)-MB SQUARE D 150 150 150 Opening Clearing Curve Opening Clearing Curve

01-EPP5(L)-MB SQUARE D 150 150 150 Opening Clearing Curve Opening Clearing Curve

01-EPP6-MB SQUARE D QO 50 50 Fixed (730-6, 50A) Fixed (730-6, 50A)

01-EPP7-MB SQUARE D QO 50 50 Fixed (730-6, 50A) Fixed (730-6, 50A)

01-EPP8-MB SQUARE D QO 50 50 Fixed (730-6, 50A) Fixed (730-6, 50A)

01-EPP9-MB SQUARE D QO 50 50 Fixed (730-6, 50A) Fixed (730-6, 50A)

01-EPPB-1-MB SQUARE D QO-VH 150 150 Fixed (730-10, 150A) Fixed (730-10, 150A)

01-EQ-BB GE THHQB 15 15 Fixed Fixed

01-EQ-MB GE SGHA 400 400 MAX MAX

01-KLE1-MB SQUARE D LA 400 400 Thermal Curve INST LO Thermal Curve INST LO

01-L1D1-MB EATON/CUTLER-HAMMER EDB 150 150 Fixed Fixed

01-L1D2-ECB-CB SQUARE D QB 150 150 Fixed Fixed

01-L1D-MB EATON/CUTLER-HAMMER EDB 150 150 Fixed Fixed

Notes: 1. Highlighted values with red text indicate a proposed setting change. 4.6- 6

Name MFR

TYPE

MODEL

Amps

Sensor

Amps

Plug LT Setting INST Setting LT Setting INST Setting

PROPOSEDEXISTING

01-LIBERTY HALL-MB GE THQD 200 200 Fixed Fixed

01-LP-1-MB SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

01-LP8A-MB GE TED 150 150 Fixed Fixed

01-MCB-1 GE THQD 200 200 Fixed Fixed

01-MCB-2 GE THQD 100 100 Fixed Fixed

01-MCB-MB GE SGHA 225 225 MAX MAX

01-MCC-3-MB SQUARE D LA 250 250 Thermal Curve INST HI Thermal Curve INST 3

01-MCC-5-MB SQUARE D KA 225 225 Thermal Curve INST HI Thermal Curve INST HI

01-MD-KP-1 SQUARE D QG 225 225 Fixed Fixed

01-MD-KP-2 SQUARE D QG 225 225 Fixed Fixed

01-MD-KP-4 SQUARE D QG 225 225 Fixed Fixed

01-MD-KP-5 SQUARE D BG 100 100 Fixed Fixed

01-MD-KP-6 SQUARE D BG 100 100 Fixed Fixed

01-MDS-1-MB SQUARE D MG 700 700 Thermal Curve INST 2 Thermal Curve INST 2

01-METER PACK-MB SQUARE D LH 400 400 Thermal Curve INST HI Thermal Curve INST HI

01-MP-1-1 SQUARE D LA 400 400 Thermal Curve INST 4 Thermal Curve INST LO

01-MP-1-BP-CB SQUARE D 225 225 225 LTD INST 10.0 LTD INST 10.0

01-MP-CB1 SQUARE D FH 100 100 Fixed Fixed

01-MP-CB2 SQUARE D FH 100 100 Fixed Fixed

01-MP-MB SQUARE D MA 500 500 Thermal Curve INST LO Thermal Curve INST LO

01-N. PWR-BUSWAY-ECB-CB SQUARE D MA 600 600 Thermal Curve INST HI Thermal Curve INST LO

01-N1-E-1 EATON/CUTLER-HAMMER QBHW 100 100 Fixed Fixed

01-N1-E-MB EATON/CUTLER-HAMMER EDB 225 225 Fixed Fixed

01-N1L-MB EATON/CUTLER-HAMMER EDB 225 225 Fixed Fixed

01-N1-MB EATON/CUTLER-HAMMER QBHW 100 100 Fixed Fixed

01-N1P-MB EATON/CUTLER-HAMMER EDB 225 225 Fixed Fixed

01-N2L-MB EATON/CUTLER-HAMMER EDB 225 225 Fixed Fixed

01-N2P-ECB-CB SQUARE D LA 300 300 Thermal Curve (Fixed) INST (5-10 x Trip) 10.0 Thermal Curve (Fixed) INST (5-10 x Trip) 10.0

01-N2P-MB EATON/CUTLER-HAMMER DK 400 400 Thermal Curve (Fixed) INST (5-10 x Trip) 10 Thermal Curve (Fixed) INST (5-10 x Trip) 10

01-N2R2-ECB-CB EATON/CUTLER-HAMMER DK 400 400 Thermal Curve (Fixed) INST (5-10 x Trip) 10 Thermal Curve (Fixed) INST (5-10 x Trip) 6.00

01-N2R-MB EATON/CUTLER-HAMMER DK 400 400 Thermal Curve (Fixed) INST (5-10 x Trip) 10 Thermal Curve (Fixed) INST (5-10 x Trip) 6.00

01-N2X-MB CUTLER-HAMMER LGE 630 630 Thermal Curve INST, (5-10X) 5X Thermal Curve INST, (5-10X) 5X

01-N3-E1-MB GE 150 100 100 Opening Clearing Curve Opening Clearing Curve

01-N3-E-MB GE THQB 100 100 Fixed Fixed

01-N3P-MB SQUARE D Q2M 200 200 Fixed Fixed

Notes: 1. Highlighted values with red text indicate a proposed setting change. 4.6- 7

Name MFR

TYPE

MODEL

Amps

Sensor

Amps

Plug LT Setting INST Setting LT Setting INST Setting

PROPOSEDEXISTING

01-N4E-1 EATON/CUTLER-HAMMER EHB 100 100 Fixed Fixed

01-N4E-2 CUTLER-HAMMER EB 100 100 Fixed Fixed

01-N5MCC-MB SQUARE D MA 400 400 Thermal Curve INST LO Thermal Curve INST LO

01-N5PA1-1 SQUARE D KA 225 225 Thermal Curve INST HI Thermal Curve INST HI

01-N5PD-MB EATON/CUTLER-HAMMER DK 400 400 Thermal Curve (Fixed) INST (5-10 x Trip) 10 Thermal Curve (Fixed) INST (5-10 x Trip) 10

01-NBAC-MB EATON/CUTLER-HAMMER QBHW 100 100 Fixed Fixed

01-NB-E1-MB EATON/CUTLER-HAMMER EDB 100 100 Fixed Fixed

01-NB-E2-MB EATON/CUTLER-HAMMER QBHW 50 50 Fixed Fixed

01-NB-EL-MB EATON/CUTLER-HAMMER QBHW 100 100 Fixed Fixed

01-NBL-MB EATON/CUTLER-HAMMER EDB 225 225 Fixed Fixed

01-NBPA-1 EATON/CUTLER-HAMMER QBHW 100 100 Fixed Fixed

01-NBPA-MB EATON/CUTLER-HAMMER EDB 225 225 Fixed Fixed

01-NBPB-BP-CB SQUARE D KA 250 250 Thermal Curve INST HI Thermal Curve INST LO

01-NECR1A-1 EATON/CUTLER-HAMMER HFD 30 30 Fixed Fixed

01-NECR1A-BP-CB SQUARE D FA 100 100 Fixed Fixed

01-NECR1B-MB SQUARE D QO 50 50 Fixed (730-6, 50A) Fixed (730-6, 50A)

01-NECR2A-1 EATON/CUTLER-HAMMER HFD 30 30 Fixed Fixed

01-NECR2A-BP-CB SQUARE D FA 100 100 Fixed Fixed

01-NECR2B-MB SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

01-NECR3A-1 EATON/CUTLER-HAMMER HFD 45 45 Fixed Fixed

01-NECR3A-2 EATON/CUTLER-HAMMER HFD 45 45 Fixed Fixed

01-NECR3A-BP-CB SQUARE D FA 100 100 Fixed Fixed

01-NECR3B-MB SQUARE D QO 50 50 Fixed (730-6, 50A) Fixed (730-6, 50A)

01-NECR3D-SECT1-MB EATON/CUTLER-HAMMER EDB 225 225 Fixed Fixed

01-NECR4A-1 EATON/CUTLER-HAMMER HFD 45 45 Fixed Fixed

01-NECR4A-2 EATON/CUTLER-HAMMER HFD 45 45 Fixed Fixed

01-NECR4A-BP-CB SQUARE D FA 100 100 Fixed Fixed

01-NECR4B-1 SQUARE D QO 45 45 Fixed (730-6, 45A) Fixed (730-6, 45A)

01-NECR4B1-1 SQUARE D QO 45 45 Fixed (730-6, 45A) Fixed (730-6, 45A)

01-NECR4B1-2 SQUARE D QO 45 45 Fixed (730-6, 45A) Fixed (730-6, 45A)

01-NECR4B1-3 SQUARE D QO 40 40 Fixed (730-5, 40A) Fixed (730-5, 40A)

01-NECR4B1-4 SQUARE D QO 40 40 Fixed (730-5, 40A) Fixed (730-5, 40A)

01-NECR4B1-5 SQUARE D QO 40 40 Fixed (730-5, 40A) Fixed (730-5, 40A)

01-NECR4B1-6 SQUARE D QO 40 40 Fixed (730-5, 40A) Fixed (730-5, 40A)

01-NECR4B1-7 SQUARE D QO 40 40 Fixed (730-5, 40A) Fixed (730-5, 40A)

Notes: 1. Highlighted values with red text indicate a proposed setting change. 4.6- 8

Name MFR

TYPE

MODEL

Amps

Sensor

Amps

Plug LT Setting INST Setting LT Setting INST Setting

PROPOSEDEXISTING

01-NECR4B1-8 SQUARE D QO 40 40 Fixed (730-5, 40A) Fixed (730-5, 40A)

01-NECR4B1-9 SQUARE D QO 40 40 Fixed (730-5, 40A) Fixed (730-5, 40A)

01-NECR4B1-MB SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

01-NECR4B-2 SQUARE D QO 45 45 Fixed (730-6, 45A) Fixed (730-6, 45A)

01-NECR4B-3 SQUARE D QO 30 30 Fixed (730-5, 30A) Fixed (730-5, 30A)

01-NECR4B-MB SQUARE D QO 100 100 Fixed (730-7, 100A) Fixed (730-7, 100A)

01-NECRBA-1 EATON/CUTLER-HAMMER HFD 30 30 Fixed Fixed

01-NECRBA-BP-CB SQUARE D FA 100 100 Fixed Fixed

01-NECRBB-MB SQUARE D QO 50 50 Fixed (730-6, 50A) Fixed (730-6, 50A)

01-NECRE-A-MB EATON/CUTLER-HAMMER DK 250 250 Thermal Curve (Fixed) INST (5-10 x Trip) 10 Thermal Curve (Fixed) INST (5-10 x Trip) 10

01-NELS1-BP-CB SQUARE D FA 60 60 Fixed Fixed

01-NELS2-BP-CB SQUARE D FA 60 60 Fixed Fixed

01-NELS3-BP-CB SQUARE D FA 60 60 Fixed Fixed

01-NELS4-BP-CB SQUARE D FA 60 60 Fixed Fixed

01-NELS5-BP-CB SQUARE D FA 60 60 Fixed Fixed