Appendix I.pdf
PDF 193 KB Posted
- Attached to
- Comprehensive Mechanical Systems Maintenance and Repair Services - Bronson Animal Disease Diagnostic
- Solicitation number
- ITB-16459
- Issued by
- Leon County, Florida
About this file
This appendix details the preventative maintenance (PM) service requirements for the Florida Department of Agriculture and Consumer Services' Bronson Animal Disease Diagnostic Laboratory in Kissimmee, Florida. The maintenance program encompasses multiple HVAC systems, boilers, chillers, pumps, and building automation equipment across the facility. Specific equipment requiring PM services includes three split systems, five mini split systems, five air-cooled chillers, three boilers, two pumps, six chilled water air handling units, one walk-in cooler, seven exhaust fans, one controls system, one water heater, and one Building Automation (DISTECH) system. The service requirements are structured into two maintenance tiers: Operational Service and Comprehensive Service, with minimum visit frequencies ranging from one to six visits per year depending on equipment type and tier level.
The preventative maintenance specifications detail extensive operational and comprehensive service tasks for each equipment category. Operational maintenance tasks include routine inspections, filter cleaning and replacement, lubrication, temperature and pressure recording, electrical connection checks, and leak detection across all equipment types. Comprehensive maintenance expands these services to include coil cleaning, belt replacement, control calibration, oil sampling, megohm testing, and system updates. For building automation systems specifically, operational maintenance requires daily system monitoring and alarm investigation, while comprehensive maintenance includes software updates, battery replacement, and system audit reviews. All maintenance visits must include written reports and documentation via XOI vision share links, ensuring thorough record-keeping and accountability for the contracted maintenance services.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Addendum 1_Final.pdf | ||
| ITB DAI 26 27 17_Final.pdf | ||
| REVISED Appendix I.pdf | ||
| Appendix II.pdf | ||
| Mandatory Site Visit Short List.pdf | ||
| Appendix III - CSA.pdf | ||
| REVISED Appendix II.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BID NUMBER: ITB DAI 26 27 17
APPENDIX I
PREVENTATIVE MAINTENANCE (PM) SERVICES
PM Service Frequency Minimum Visits per Year
Equipment Number of Systems Comprehensive Service Operational Service
Package Units 3 1 3
Split Systems 5 1 3
Walk-In Cooler 1 1 3
Mini Split Systems 5 1 3
Air Cooled Chillers 5 1 3
Boilers 3 1 3
Pumps 2 1 3
Chiller Air Handling Units 6 1 3
Controls System 1 0 2
Water Heater 4 1 3
Exhaust Fans 7 1 3
Building Automation
(DISTECH)
1 1 6
Package Units, Split Systems, & Walk-in Cooler
Operational Maintenance
• Install customer-provided filters during scheduled maintenance visits.
• Clean drain lines and condensate pans.
• Clean all pressurization sensors.
• Inspect evaporator and condenser coils for obstruction and dirt.
• Test all contactors and starters.
• Confirm proper operation of condensate flow.
• Test and record all compressor and motor amperages.
• Test and record return and supply temperatures.
• Lubricate fan bearings.
• Check blower motor belts and adjust or replace as required.
• Clean condensate pumps.
• Check operation controls and safety controls.
• Check thermal expansion valve for proper superheat.
• Check electrical connections for any signs of wear or overheating.
• Tighten all electrical connections.
• Visually leak check all refrigerant piping.
• Observe overall condition and report any deficiencies that are discovered.
• Provide written report and XOI vision share links.
Comprehensive Maintenance
• Perform all items listed in Operational inspections.
• Replace all belts on the blower motor, if applicable.
• Clean all metal inlet screen filters.
• Calculate subcool/superheat refrigerant line temperatures.
• Tighten set screws on fan assembly locking collars.
• In-place cleaning of condenser coils.
• In-place cleaning of the surface of evaporator coils, if accessible.
• Check thermal expansion valve sensing bulb for proper security and insulation.
• Energy Wheel Cleaning for both RTUs on building 1000 annual cleaning. Vendor will document proper reinstallation.
Mini Splits
• Clean and wash all air filters.
• Clean drain lines and condensate pans.
• Inspect evaporator and condenser coils for obstruction and dirt.
• Test all contactors and starters.
• Confirm proper operation of condensate flow.
• Test and record all amperages.
• Test and record return and supply temperatures.
• Check operation controls and safety controls.
• Clean condensate pumps.
• Check thermal expansion valve for proper superheat.
• Check electrical connections for any signs of wear or overheating.
• Tighten all electrical connections.
• Observe overall condition and report any deficiencies that are discovered.
• Provide written report and XOI vision share links.
Comprehensive Maintenance
• Perform all items listed in Operational inspections.
• Tighten set screws on fan assembly locking collars.
• In-place cleaning of condenser coils.
• In-place cleaning of the surface of evaporator coils, if accessible.
• Check thermal expansion valve sensing bulb for proper security and insulation, if accessible.
Exhaust Fans & Supply Fans
Operational Maintenance
• Adjust or belt tension as needed.
• Lubricate bearings, if applicable.
• Test motor amperages.
• Test all starters and contactors.
• Check operation controls and safety controls.
• Inspect electrical connections for any signs of wear or overheating; tighten as needed.
• Observe overall condition and report any deficiencies that are discovered.
Comprehensive Maintenance
• Perform all items listed in Operational inspections.
• Replace belts.
Boilers
Operational Maintenance
• Check operation and calibration of gas train components.
• Check igniter and flame rod assembly.
• Check pilot and burner orifices as required.
• Check combustion blower.
• Check for water leaks.
• Check burner operation sequence.
• Check operating and safety controls.
• Check and tighten all electrical connections.
• Check starters and contactors for wear.
• Lubricate all motors and fan bearings.
• Check safety relief valve.
• Check gauges for accuracy.
• Check low water cutoff control.
• Check / adjust water feed valve.
• Check circulator pump operation.
• Check expansion tank(s).
• Observe overall condition and report any deficiencies that are discovered.
• Provide written report and XOI vision share links.
Comprehensive Maintenance
• Adjust igniter and flame rod assembly.
• Clean pilot and burner orifices as required.
• Clean combustion blower and check efficiency.
• Adjust low water cutoff control.
• Clean the heat sink with dry nitrogen.
Air Cooled Chillers
Operational Maintenance
• Check performance of compressor, condenser, and evaporator.
• Check and adjust refrigerant controls.
• Check and adjust safety controls.
• Assure that the power supply to the chiller is secured at the main disconnect.
• Check equipment for any signs of leaks.
• Check and ensure proper refrigerant charge.
• Check compressor for proper oil levels.
• Check for excess noise or vibration.
• Check operation of automatic controls.
• Check the condition of electrical controls and wiring.
• Check and record operating conditions.
• Observe overall condition and report any deficiencies that are discovered.
Comprehensive Maintenance
• Perform all tasks listed in the Operational inspections.
• Inspect and calibrate operating controls.
• Clean condenser coils.
• Inspect all safety controls.
• Torque all electrical contacts.
• Megohm chiller motor and oil pump.
• Wipe down the exterior of the chiller and remove any debris from the chiller area.
• Observe overall condition and report any deficiencies that are discovered.
• Take oil sample for analysis (performed once during operating season).
Chilled Water AHUs
• Purchase and replace all pre-filters (excludes final/HEPA filters unless stated otherwise).
• Lubricate fan bearings.
• Clean drain lines and pans.
• Insect blower wheel operation.
• Insect starter contactors and connections.
• Inspect evaporator and condenser coils for obstruction and dirt.
• Confirm proper condensate flow.
• Check blower motor belts and adjust as required.
• Tighten electrical connections.
• If unit has a VFD, inspect all connections.
• Check operation controls and safety controls.
• Verify proper system pressures and temperatures.
• Observe overall condition and report any deficiencies that are discovered.
• Provide written report and XOI vision share links.
Comprehensive Maintenance
• Perform all items listed in Operational inspections.
• Replace all belts on the blower motor, if applicable.
• Tighten set screws on fan assembly locking collars.
• In-place cleaning of the surface of evaporator coils, if accessible.
• Clean the heat sink with dry nitrogen.
• Check programming.
• Check all internal parts for wear.
• Observe overall condition and report any deficiencies that are discovered.
Pumps
Operational Maintenance
• Verify pumps are operating properly.
• Verify proper pump rotation.
• Inspect seals for any signs of leakage.
• Verify pumps are securely mounted.
• Verify there is no abnormal noise during pump operation.
• Check pump bearings and fittings for proper lubrication. Lubricate as necessary.
• Check temperature and pressures on pump gauges and record readings.
• Check expansion tank for proper operating level, verify operating pressures.
• Inspect the starter contacts and wiring for any signs of wear or overheating.
• Verify Variable Frequency Drives are operating properly and set points are set per manufacturer’s recommendations (if applicable).
• Observe overall condition and report any deficiencies that are discovered.
Comprehensive Maintenance
• All steps performed in Operational inspection.
• Test changeover operation of pump package (if applicable).
• Check for proper voltage and amperage draw on pump motors.
• Check electrical connections (tighten as necessary), contacts and fuses.
• Clean VFD interior and change filters (if necessary).
• Observe overall condition and report any deficiencies that are discovered.
Building Automation Systems (DISTECH)
• Log into systems
• Check all dashboards for alarms.
• Print alarm reports.
• Investigate and correct any alarms.
• Review automation trend reports to identify any trends indicating possible equipment failure.
• Verify all systems are automating efficiently.
• Document any adjustments made to Automation Systems.
• Make adjustments to ensure consistent temperatures, humidity, airflows, water temperatures and building pressures as required for laboratory operations.
Comprehensive Maintenance
• Perform any system and software updates as required.
• Review all graphics and setpoints are reporting correctly.
• Review any system audit trails, note adjustments corresponding to service records.
• Check electrical connections (tighten as necessary)
• Replace back up batteries for controls.
[REMAINDER OF PAGE LEFT BLANK INTENTIONALLY]