Appendix_H-7_IFT_DI_Points_List_and_Wiring_Check-off_Worksheet_(03122019).xls

XLS spreadsheet 50 KB Posted

Attached to
Pump Station Control and SCADA Communication Panels
Solicitation number
Y25-184
Issued by
Orange County, Orlando City, Florida

About this file

The file is an Appendix H-7 Digital Input (DI) Points List and Wiring Check-off Worksheet from Orange County, Florida, related to a Pump Station Control and SCADA Communication Panels solicitation (Bid Y25-184). The county is accepting sealed electronic offers until 4:00 pm EST on Thursday, May 29, 2025, for a comprehensive digital input monitoring system that tracks various operational statuses including intrusion alarms, power systems, pump controls, float levels, generator performance, and equipment operational states. Respondents must submit proposals exclusively through the OpenGov e-Procurement Platform, with a questions submission deadline of Thursday, May 8, 2025 at 5:00 pm EST.

The solicitation requires electronic submission through a free OpenGov account, with technical support available via chat, email, and phone. Potential vendors are instructed to submit all inquiries through the platform's question and answer module, with any modifications or clarifications to be issued as written addenda. The document provides detailed technical specifications for a digital input monitoring system, including 22 specific input points covering various pump station and equipment operational parameters, which suggests a complex infrastructure monitoring requirement for county water or wastewater facilities.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DI List

APPENDIX H-7
ItemTypeReference #DescriptionFunctional StatusAddressCheckedDateOCUContractor
(DWG Line #)Active (1)Inactive (0)P
1DI181Intrusion AlarmAlarmNormalI2.0
2DI183Station PowerPower OnPower OffI2.1
3DI186SCADA Panel Power AlarmNormalAlarmI2.2
4DI189Pump Panel Control Power AlarmNormalAlarmI2.3
5DI193Off FloatLow Level OnOffI2.4
6DI195Lead FloatLead Level OnOffI2.5
7DI197Lag FloatLag Level OnOffI2.6
8DI199High FloatHigh Level OnOffI2.7
9DI257High High FloatHH Level OnOffI0.0
10DI259Pump 1 HOAIn RemoteIn LocalI0.1
11DI263Pump 1 RunRunningOffI0.2
12DI265Pump 1 FailFailureNormalI0.3
13DI269Pump 2 HOAIn RemoteIn LocalI0.4
14DI271Pump 2 RunRunningOffI0.5
15DI275Pump 2 FailFailureNormalI0.6
16DI277Main BreakerBreaker OnOffI0.7
17DI297Emergency BreakerBreaker OnOffI1.0
18DI299Generator RunRunningOffI1.1
19DI301Generator FailFailureNormalI1.2
20DI303Odor Run / Not RunRunningOffI1.3
21DI307Rain GaugeRainedDryI1.4
22DI310Battery <85%AlarmNormalI1.5
23DI312Battery AlarmAlarmNormalI1.6
24DI315Pump Panel Local / SCADA SwitchSCADA CntrlLocal CntrlI1.7
25DI302Backup Pump RunRunningOffI3.0
26DI279Pump 3 HOAIn RemoteIn LocalI3.1
27DI281Pump 3 RunRunningOffI3.2
28DI285Pump 3 FailFailureNormalI3.3
29DI198Lag 2 FloatLag 2 Level OnOffI3.4
30DI305Backup Pump FailFailureNormalI3.5
31DI300Fuel Tank AlarmFailureNormalI3.6
32DI343Mixer RunRunningOffI3.7
33DI401Mixer Switch StatusOnOffI4.0
34DI403Fuse 5 FailNormalFailureI4.1
35DI405Fuse 6 FailNormalFailureI4.2
36DI407Backup Pump Check Valve failNormalFailureI4.3
37DI409Spare DITBDTBDI4.4
38DI411Spare DITBDTBDI4.5
39DI413Spare DITBDTBDI4.6
40DI415Spare DITBDTBDI4.7
Comments:

&C&"Arial,Bold"&12OCU TWO PUMPS PS IO LIST and Wiring Interconnect Check-off Sheet &L&F&C&A, Page &P of &N&R&D