Appendix_H-7_IFT_DI_Points_List_and_Wiring_Check-off_Worksheet_(03122019).xls
XLS spreadsheet 50 KB Posted
- Solicitation number
- Y25-184
- Issued by
- Orange County, Orlando City, Florida
About this file
The file is an Appendix H-7 Digital Input (DI) Points List and Wiring Check-off Worksheet from Orange County, Florida, related to a Pump Station Control and SCADA Communication Panels solicitation (Bid Y25-184). The county is accepting sealed electronic offers until 4:00 pm EST on Thursday, May 29, 2025, for a comprehensive digital input monitoring system that tracks various operational statuses including intrusion alarms, power systems, pump controls, float levels, generator performance, and equipment operational states. Respondents must submit proposals exclusively through the OpenGov e-Procurement Platform, with a questions submission deadline of Thursday, May 8, 2025 at 5:00 pm EST.
The solicitation requires electronic submission through a free OpenGov account, with technical support available via chat, email, and phone. Potential vendors are instructed to submit all inquiries through the platform's question and answer module, with any modifications or clarifications to be issued as written addenda. The document provides detailed technical specifications for a digital input monitoring system, including 22 specific input points covering various pump station and equipment operational parameters, which suggests a complex infrastructure monitoring requirement for county water or wastewater facilities.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DI List
| APPENDIX H-7 | |||||||||||
| Item | Type | Reference # | Description | Functional Status | Address | Checked | Date | OCU | Contractor | ||
| (DWG Line #) | Active (1) | Inactive (0) | P | ||||||||
| 1 | DI | 181 | Intrusion Alarm | Alarm | Normal | I2.0 | |||||
| 2 | DI | 183 | Station Power | Power On | Power Off | I2.1 | |||||
| 3 | DI | 186 | SCADA Panel Power Alarm | Normal | Alarm | I2.2 | |||||
| 4 | DI | 189 | Pump Panel Control Power Alarm | Normal | Alarm | I2.3 | |||||
| 5 | DI | 193 | Off Float | Low Level On | Off | I2.4 | |||||
| 6 | DI | 195 | Lead Float | Lead Level On | Off | I2.5 | |||||
| 7 | DI | 197 | Lag Float | Lag Level On | Off | I2.6 | |||||
| 8 | DI | 199 | High Float | High Level On | Off | I2.7 | |||||
| 9 | DI | 257 | High High Float | HH Level On | Off | I0.0 | |||||
| 10 | DI | 259 | Pump 1 HOA | In Remote | In Local | I0.1 | |||||
| 11 | DI | 263 | Pump 1 Run | Running | Off | I0.2 | |||||
| 12 | DI | 265 | Pump 1 Fail | Failure | Normal | I0.3 | |||||
| 13 | DI | 269 | Pump 2 HOA | In Remote | In Local | I0.4 | |||||
| 14 | DI | 271 | Pump 2 Run | Running | Off | I0.5 | |||||
| 15 | DI | 275 | Pump 2 Fail | Failure | Normal | I0.6 | |||||
| 16 | DI | 277 | Main Breaker | Breaker On | Off | I0.7 | |||||
| 17 | DI | 297 | Emergency Breaker | Breaker On | Off | I1.0 | |||||
| 18 | DI | 299 | Generator Run | Running | Off | I1.1 | |||||
| 19 | DI | 301 | Generator Fail | Failure | Normal | I1.2 | |||||
| 20 | DI | 303 | Odor Run / Not Run | Running | Off | I1.3 | |||||
| 21 | DI | 307 | Rain Gauge | Rained | Dry | I1.4 | |||||
| 22 | DI | 310 | Battery <85% | Alarm | Normal | I1.5 | |||||
| 23 | DI | 312 | Battery Alarm | Alarm | Normal | I1.6 | |||||
| 24 | DI | 315 | Pump Panel Local / SCADA Switch | SCADA Cntrl | Local Cntrl | I1.7 | |||||
| 25 | DI | 302 | Backup Pump Run | Running | Off | I3.0 | |||||
| 26 | DI | 279 | Pump 3 HOA | In Remote | In Local | I3.1 | |||||
| 27 | DI | 281 | Pump 3 Run | Running | Off | I3.2 | |||||
| 28 | DI | 285 | Pump 3 Fail | Failure | Normal | I3.3 | |||||
| 29 | DI | 198 | Lag 2 Float | Lag 2 Level On | Off | I3.4 | |||||
| 30 | DI | 305 | Backup Pump Fail | Failure | Normal | I3.5 | |||||
| 31 | DI | 300 | Fuel Tank Alarm | Failure | Normal | I3.6 | |||||
| 32 | DI | 343 | Mixer Run | Running | Off | I3.7 | |||||
| 33 | DI | 401 | Mixer Switch Status | On | Off | I4.0 | |||||
| 34 | DI | 403 | Fuse 5 Fail | Normal | Failure | I4.1 | |||||
| 35 | DI | 405 | Fuse 6 Fail | Normal | Failure | I4.2 | |||||
| 36 | DI | 407 | Backup Pump Check Valve fail | Normal | Failure | I4.3 | |||||
| 37 | DI | 409 | Spare DI | TBD | TBD | I4.4 | |||||
| 38 | DI | 411 | Spare DI | TBD | TBD | I4.5 | |||||
| 39 | DI | 413 | Spare DI | TBD | TBD | I4.6 | |||||
| 40 | DI | 415 | Spare DI | TBD | TBD | I4.7 | |||||
| Comments: |
&C&"Arial,Bold"&12OCU TWO PUMPS PS IO LIST and Wiring Interconnect Check-off Sheet &L&F&C&A, Page &P of &N&R&D