Appendix B.pdf
PDF 3 MB Posted
- Attached to
- J059--UPS Equipment Maintenance
- Solicitation number
- 36C25025Q0420
About this file
This document is a detailed technical manual for Powervar Security Plus Uninterruptible Power Supply (UPS) systems. The manual covers a comprehensive range of UPS models from 2kVA to 15kVA, providing detailed specifications, installation instructions, operational guidelines, maintenance procedures, and warranty information. Key technical features include true online double-conversion topology, high input power factor, wide input voltage window, intelligent RS232 communication, and multiple communication interface options (RS232, USB, DB-9 dry contacts, optional SNMP adapter).
The manual outlines critical operational parameters such as input voltage ranges (100-240VAC), frequency tolerance (50/60 Hz), and efficiency ratings over 85% for AC-AC conversion. Installation requirements specify environmental conditions of 0-40°C operating temperature, 5-90% non-condensing humidity, and proper ventilation. Safety features include output over-voltage protection, battery low voltage protection, and self-protection functions. The warranty provides three years coverage on chassis and electronic components, with two years for batteries, and includes depot and potentially on-site service options for products 3kVA and above in specific regions.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| UPS Inventory for Contract.xlsx | XLSX spreadsheet | |
| UPS Device 11 Tag.jpg | JPG image | |
| 36C25025Q0420_2.docx | DOCX document | |
| Appendix D.pdf | ||
| Appendix C.pdf | ||
| 36C25025Q0420_1.docx | DOCX document | |
| Appendix E.pdf | ||
| Appendix A.pdf | ||
| 36C25025Q0420.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Security Plus
Online Uninterruptible Power Supply
GENERAL SAFETY INSTRUCTIONS
Warnings in this manual appear in any of four ways:
Danger- The danger symbol is a lightning bolt mark enclosed in a triangle which precedes the 3/16-inch high letters spelling the word “DANGER”. The danger symbol is used to indicate imminently hazardous situations, locations, and conditions which, if not avoided, WILL result in death, serious injury, and/or severe property damage.
DANGERDANGERDANGERDANGER
Caution- The caution symbol is an exclamation mark enclosed in a triangle which precedes the 3/16-inch high letters spelling the word “CAUTION”. The caution symbol is used to indicate potentially hazardous situations and conditions which, if not avoided may result in injury. Equipment damage may also occur.
CAUTIONCAUTIONCAUTIONCAUTION
Warning- The warning symbol is an exclamation mark in a triangle which precedes the 3/16-inch high letters spelling the word “WARNING”. The warning symbol is used to indicate potentially hazardous situations and conditions which, if not avoided COULD result in serious injury or death.
Severe property damage COULD also occur.
WARNINGWARNINGWARNINGWARNING
Attention warnings- The attention warning symbol is an exclamation mark enclosed in a triangle which precedes the 3/16-inch high letters spelling the word “ATTENTION”. The Attention warning symbol is used to indicate situations and conditions that can cause operator injury and/or equipment damage.
ATTENTIONATTENTIONATTENTIONATTENTION
Other warning symbols may appear along with the Danger and
Caution symbol and are used to specify special hazards. These warnings describe particular areas where special care and/or procedures are required in order to prevent serious injury and possible death:
Electrical warnings- The electrical warning symbol is a lightning bolt mark enclosed in a triangle. The Electrical warning symbol is used to indicate high voltage locations and conditions may cause serious injury or death if the proper p
Explosion warnings- The explosion warning symbol is an explosion mark enclosed in a triangle. The Explosion warning symbol is used to indicate locations and conditions where molten, exploding parts may cause serious injury or death if the proper precautions are not observed
N
Protective earth (Ground)
Connection point for the neutral conductor on PERMANENTLY INSTALLED
EQUIPMENT
Earth Ground
NNOOTTEE TTOO UUSSEERRSS
To ensure correct operation of the UPS, please read this instruction manual carefully. Please keep this manual handy for future reference.
IIMMPPOORRTTAANNTT IINNFFOORRMMAATTIIOONN FFOORR UUSSEERRSS OOFF
TTHHIISS UUNNIINNTTEERRRRUUPPTTIIBBLLEE PPOOWWEERR SSUUPPPPLLYY
1. Before operating the UPS or connecting any load equipment, please ensure the UPS is connected to a properly grounded electrical supply.
2. This UPS has dangerously high voltages on both its input and output connections.
Contact with these voltages may be life threatening.
3. Please do not disassemble the covers. There is a risk of electric shock.
4. In an emergency, immediately turn off the circuit breaker for the circuit supplying power to the UPS. Also immediately turn off the battery circuit breaker.
5. This UPS has two power sources. One is the circuit supplying the UPS with input power. The other is the UPS battery. Prior to any maintenance, both of these power sources must be disconnected to ensure that the UPS is de-energized. If only the input power is disconnected, the UPS can still operate from the battery, and hazardous voltages may still exist.
6. To prevent damage or a safety hazard, keep the UPS away from open flame and any other devices that may cause sparks.
7. Do not open or damage individual battery cases as spillage of caustic electrolyte may occur resulting in danger to life, safety, and the environment.
8. The charging characteristics of UPS batteries vary by both brand and type. For this reason, replacement batteries should be of the same brand and type as those specified by the manufacturer. Using batteries other than the brand and type specified by the manufacturer may affect the performance of the UPS. Before installing batteries of different brand or type, please consult with the manufacturer.
9. The UPS has an internal EMI filter for purposes of enhancing electromagnetic compatibility with the input mains supply. This filter produces leakage current to earth on the input mains. When selecting a circuit breaker for the branch circuit supplying power to the UPS, ensure that the breaker selected is not an ELCB type circuit breaker that detects earth leakage current.
10. Please contact the manufacturer or an authorized distributor for any assistance with troubleshooting.
This UPS has dangerously high voltages on both its Input and output connections. Contact with these voltages may be life threatening. Please follow the operating instructions carefully. Please give close attention to the warnings in this manual and those posted on the UPS. There are no user serviceable parts inside the UPS. Disassembly and/or maintenance should only be done by an authorized professional service technician.
11. The UPS should only be serviced or maintained by a factory authorized service technician.
12. This UPS meets FCC Class A electromagnetic compatibility requirements.
13. Depleted batteries must be disposed of in a proper manner. Contact your local recycling or hazardous waste center or the UPS manufacturer for instructions concerning proper disposal.
CCOONNTTEENNTTSS
1.0 Overview
1.1 Primary Functions and Operating Characteristics
1.2 Precautions
1.3 Performance Specifications
2.0 Structure and Basic Principles
2.1 General Structure
2.1.1 Security Plus Front Panel and Rear Panel Structure
2.1.2 Security Plus Display/Controls Operation
2.1.3 Security Plus Terminal Connection Block Illustration (2-6kVA)
2.1.4 Security Plus Terminal Connection Block Illustration (8-15kVA) ... 40
2.1.5 RS232 Communications
2.1.6 Communication Port Maintenance
2.2 Basic Principles
3.0 Equipment Installation
3.1 Site and Environment Requirements
3.1.1 Site Requirements
3.1.2 Environment Requirements
3.2 Procedures of Dismantling Containers
3.3 Installation of UPS
4.0 Equipment Use and Maintenance
4.1 Preparations for Start-up
4.2 Routine UPS Start-up Sequence
4.3 Routine UPS Shutdown
4.4 Important Battery Issues
4.5 Frequent Trouble Causes
4.6 Troubleshooting
4.6.1 Overview
4.6.2 Troubleshooting Steps
5.0 Battery Tray Replacement
5.1 Precautions
5.1.1 Battery Tray Replacement (2-6kVA)
5.1.2 Battery Tray Replacement (2-6kVA)
5.1.3 Battery Tray Replacement (8-15kVA)
6.0 Packing, Transportation and Storage
6.1 Packing
6.2 Transportation
6.3 Storage
6.4 Fuse Replacements
7.0 Mechanical Characteristics
7.1 Unit Dimensions/Weights
7.2 Shipping Dimensions/Weights
8.0 Warranty
8.1 Basic Warranty
8.2 Limitations
11..00 OOvveerrvviieeww
The Security Plus UPS is a high frequency, double conversion (true online) intelligent UPS for use with file servers, enterprise servers, microcomputers, telecommunication systems, data centers, laboratory instrumentation, and other microprocessor-based equipment that requires high quality, conditioned uninterruptible power. It is designed for use in telecom, IT, LAN, banking and financial, or almost any application where the performance of computer systems is mission critical. The Security Plus UPS is designed for connection to a single-phase alternating current input and provides power output loads requiring single-phase alternating current power.
1.1 Primary Functions and Operating Characteristics
1. Intelligent RS232 communication - Using the available RS232 standard data interface or
USB port and UPS power management software, you take advantage of three communications functions: (1) The connected host computer can supervise UPS operation and control electric parameters, (2) Remote control of power ON and OFF functions can be accomplished, (3) with an available internal SNMP network adapter inserted in the internal card SNMP option card slot, the UPS is discoverable by a network.
2. High input power factor and low input THDI – This UPS uses an advanced active power factor correction (PFC) technology, which improves the input power factor and makes the UPS friendlier to the input mains supply.
3. High performance to price ratio – This UPS uses high frequency pulse width modulation
(PWM) technology to ensure high efficiency, reduced size and weight, and improved operational reliability.
4. Dependable self-protection functions – This UPS provides dependable self-protection functions such as output over-voltage protection, battery low voltage protection, and input over-voltage protection. These self-protection features improve reliability and adaptability to a variety of electronic applications and installation environments.
5. Wide input voltage window – This UPS has a wide input voltage operating window, which ensures that even in the presence of unusually low or high input voltage, the UPS will continue to supply high quality dependable power to the connected load without discharging its battery. This reduces battery discharge cycles and results in increased battery life.
1.2 Precautions
1. There are no user serviceable parts inside this UPS. Please don't remove the covers. This system can only be maintained or repaired by trained authorized service technicians.
2. To improve electromagnetic compatibility (EMC), this UPS has an input EMI filter, which produces potentially dangerous leakage current to ground. Ensure the UPS is connected to a properly grounded input electrical source.
Please be careful to observe the following general safety precautions during operation or maintenance
3. Install this UPS indoors in an environment that is temperature and humidity controlled.
4. Install this UPS in a dust-free environment.
5. This UPS has two sources of power. Before maintenance is performed, turn off the branch circuit breaker powering the UPS and turn off all battery switches.
6. Even with the AC input power supply turned off, the UPS’s internal battery still represents a potentially dangerous source of high voltage electrical power.
7. If the battery circuit has not been disconnected from the AC input, dangerous voltage potential still exists between the battery terminal and the ground terminal.
8. UPS batteries represent a high voltage source and a potential hazard to personal safety.
Please pay attention to proper safety precautions and use insulated tools during installation.
9. UPS batteries contain corrosive and caustic chemicals. Improper handling of batteries may lead to the unintended release or leakage of these substances. Please handle batteries carefully.
10. Condensation may occur when the UPS is moved from a low temperature, low humidity environment to a warm humid environment. Condensation may cause UPS damage or hazardous electrical shock. To ensure the safety of both the UPS and the personnel around it, make sure that the UPS is installed only after it has fully acclimated to its installation environment. This UPS is not intended to be operated in an environment of either low temperature or high humidity.
11. DC voltage is still present on the battery fuses even with the UPS turned off. The battery trays must be removed before servicing UPS.
1.3 Performance Specifications
The major specifications of the Security Plus UPS are shown in the individual specification sheets on the following pages.
Note: Specifications are subject to change without notice.
FRONT SIDE REAR
Model ABCDEF2000-11 ABCDEF2000-22
Topology True On line, Double-Conversion, IGBT Design, Internal Isolation Transformer
IN
P
U T
Voltage (VAC) 100 115 120 200 208 220 230 240
Voltage Range (VAC) 70-115 81-132 84-138 140-230 146-239 154-253 161-264 168-276
Voltage Tolerance + 15% ~ -30% before switching to batteries
Frequency (Hz) 50/60
Frequency Tolerance 42 Hz to 69 Hz before switching to batteries
Input PF > 0.95 Input Current THD < 5.0%
Input Connection Hardwired Standard; Line Cord Optional (Consult factory)
Input Capacity 2160 VA 2160 VA
O
T P
Capacity 2000VA/ 1800W
Voltage (VAC) 100 115 120 200 120
220 230 120
Voltage Regulation ± 3.0% Max, ± 1.0% Normal Output Voltage THD < 3.0%
Power Factor 0.9
Step Load Response ± 4.0% for 50% step load change ± 6.0% for 100% step load change Return to ± 3.0% of nominal within 3 cycles
Crest Factor 3:1
Frequency (Hz) 50/60
Frequency Regulation ± 0.1Hz
Overload 125% for 2 minutes 150% for 30 seconds 300% for 500ms
Efficiency AC-AC >85.0%
DC-AC >71.0%
AC-AC >85.0%
DC-AC >70.0%
Common Mode Noise < 0.5 VRMS
Output Connection Hardwired Standard; Output Receptacles Optional (Consult factory)
B Y
P A
S
Input Voltage (VAC) 100 115 120 200 208 220 230 240
Output Voltage (VAC) 100 115 120 200 120
220 230 120
Transformer Voltage Regulation
± 3.0%
Overload 125% for 10 minutes 150% for 500ms 1000% for 1 cycle
Efficiency > 95.0%
11.80 (299.72)
32.65 (829.4)
28.70 (729.0)
A
T T
E R
Voltage (VDC) 96.0, nominal 109.2, float
Battery 12V, 34W flame retardant High Rate, Sealed Lead-Acid
Quantity 8
Charge Current (ADC) 2.0
Backup Time (min) > 7.0
Recharge Time 8 hours to 90%
E
V
IR
O N
M E
N T
Temperature (°C) 0 to 40, operating -20 to 60, transit
Altitude (m) 2,000, operating 12,000, transit
Humidity 5.0% to 90.0%, non condensing Audible (dBA) 50-55 @ 1m from front of unit
Heat Dissipation (BTU/hr) 1084
G
E N
C
IE
EMC FCC Part 15J Class A EN 55022 Class A/ CISPR 22
EN 50091-2
IEC 61000-3-2
Safety Agencies UL1778 4th Ed.
cUL to CSA22.2 No.107.1 CE (-22 only):
IEC62040, w/CB report and cert IEC62040, w/CB report and cert IEC61000-4-2, Electrostatic Discharge IEC61000-4-3, Radiated Electromagnetic Field Immunity IEC61000-4-4, Electrical Fast Transient/ Burst Immunity IEC61000-4-5, Surge Immunity IEC61000-4-6, Immunity to Conducted Radio Frequency Disturbances IEC61000-4-8, Power Frequency Magnetic Field Immunity IEC61000-4-11, Voltage Dips, Short Interruptions, and Voltage Variations
RoHS All units are RoHS compliant
H
Communication RS-232
USB
DB-9 Dry Contacts Internal SNMP Adapter (option)
Unit Weight -11 Models 215 lbs. / 97 kg.
-22 Models 221 lbs. / 100 kg.
Shipping Weight -11 Models 310 lbs. / 139 kg.
-22 Models 316 lbs. / 142 kg.
Plug & Receptacle* L5-30P (2)5-20R (1)L5-30R 208 VAC Input L6-30P (2)5-20R (1)L6-30R 240 VAC Input L6-20P (2)5-20R (1)L6-20R
*Hardwired unit is standard. Plug & Receptacle is optional. Contact factory for part numbers.
NOISE REJECTION-ISOLATION: With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode at the input, the noise output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-NM, CM-CM, NM-CM).
SURGE VOLTAGE WITHSTAND CAPABILITY: Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A - 6000V @ 200 amps, 0.5 usec risetime, 100 kHZ decay, Cat. B - 6000V @ 500 amps, 0.5 usec risetime, 100 kHZ decay.
ABCDEF2000-11 Compatible External (Extended Run) Battery Cabinets:
Model: D9632-11 Description: 4 Pack (32 Batt) Extended Run Battery Cabinet Model: D9648-11 Description: 6 Pack (48 Batt) Extended Run Battery Cabinet
ABCDEF2000-11 TYPICAL RUN-TIMES (MINs)
25% (450 W) 50% (900 W) 75% (1350 W) 100% (1800 W)
Internal Batteries Only 20 13 10 7
Internal + 1) D9632-11 170 110 80 65
Internal + 2) D9632-11 375 250 190 140
Internal + 3) D9632-11 625 400 300 225
Internal + 4) D9632-11 >12 Hrs 575 400 300
Internal + 5) D9632-11 >12 Hrs >12 Hrs 575 450
Internal + 1) D9648-11 250 180 130 100
Internal + 2) D9648-11 625 400 300 230
Internal + 3) D9648-11 >12 Hrs 700 500 375
Internal + 4) D9648-11 >12 Hrs >12 Hrs >12 Hrs 575
Internal + 5) D9648-11 >12 Hrs >12 Hrs >12 Hrs >12 Hrs
Note: Run-Times are based on new fully charged batteries at 25 deg C ambient.
ABCDEF2000-22 Compatible External (Extended Run) Battery Cabinets:
Model: D9632-22 Description: 4 Pack (32 Batt) Extended Run Battery Cabinet Model: D9648-22 Description: 6 Pack (48 Batt) Extended Run Battery Cabinet
ABCDEF2000-22 TYPICAL RUN-TIMES (MINs)
25% (450 W) 50% (900 W) 75% (1350 W) 100% (1800 W)
Internal Batteries Only 18 12 9 7
Internal + 1) D9632-22 160 110 80 65
Internal + 2) D9632-22 325 230 180 140
Internal + 3) D9632-22 575 375 275 225
Internal + 4) D9632-22 >12 Hrs 575 425 325
Internal + 5) D9632-22 >12 Hrs >12 Hrs 550 425
Internal + 1) D9648-22 240 170 130 100
Internal + 2) D9648-22 575 375 275 225
Internal + 3) D9648-22 >12 Hrs 650 475 375
Internal + 4) D9648-22 >12 Hrs >12 Hrs >12 Hrs 550
Internal + 5) D9648-22 >12 Hrs >12 Hrs >12 Hrs >12 Hrs
Note: Run-Times are based on new fully charged batteries at 25 deg C ambient.
Battery Life Disclaimer: Powervar’s standard battery warranty applies only to UPS and UPM products which are continuously connected to AC mains power, except during utility power outages. Products which are regularly and intentionally disconnected from AC mains power will experience battery discharge/charge cycles potentially far more numerous than those for which the battery was designed. As a result, products used in such applications will experience substantially reduced battery life. For that reason, Powervar’s standard battery warranty does not apply for applications in which the UPS or UPM product is regularly and intentionally disconnected from AC mains power. Powervar UPS and UPM products used in such applications shall receive a 90 day warranty on batteries.
Warranty/Support: Powervar warrants the electronics and transformers used in its uninterruptible power supplies to be free from defects in materials and workmanship for a period of three years from the date of shipment. Batteries are warranted for a period of two years from the date of shipment for standby use; 90 days for cyclic use. For North American service or support on any Powervar product, please contact Powervar Technical Support at (800) 369-7179 (in Illinois call (847-596-7000). For service and support in EMEA, contact Powervar, Ltd. in the United Kingdom at +44 (0) 1793 553980. Or visit the Powervar website at www.Powervar.com.
Powervar, Inc. - 1450 Lakeside Drive, Waukegan, IL 60085
FRONT SIDE REAR
\ Model ABCDEF3000-11 ABCDEF3000-22
Topology True On-line, Double-Conversion, IGBT Design, Internal Isolation Transformer
Voltage (VAC) 100 115 120 200 208 220 230 240
Voltage Range (VAC) 70-115 81-132 84-138 140-230 146-239 154-253 161-264 168-276
Voltage Tolerance + 15% ~ -30% before switching to batteries
Frequency (Hz) 50/60 Frequency Tolerance 42 Hz to 69 Hz before switching to batteries
Input PF > 0.95
Input Current THD < 5.0%
Input Capacity 3240 VA 3240 VA
T P
Capacity 3000VA/ 2700W
Voltage (VAC) 100 115 120 200 120
220 230 120
Voltage Regulation ± 3.0% Max, ± 1.0% Normal
Output Voltage THD < 3.0%
Power Factor 0.9
Step Load Response ± 4.0% for 50% step load change ± 6.0% for 100% step load change Return to ±3.0% of nominal within 3 cycles
Crest Factor 3:1
Frequency (Hz) 50/60
Frequency Regulation ± 0.1Hz
Overload 125% for 2 minutes 150% for 30 seconds 300% for 500ms
Efficiency AC-AC >85.0%
DC-AC >77.0%
AC-AC >85.0%
DC-AC >76.0%
P A
Input Voltage (VAC) 100 115 120 200 208 220 230 240 Output Voltage (VAC) 100 115 120 200 120
220 230 120
Transformer Voltage Regulation
± 3.0%
Overload 125% for 10 minutes 150% for 500ms 1000% for 1 cycle
Efficiency > 95.0%
11.80 (299.72)
32.65 (829.4)
T T
E
Battery 12V, 34W flame retardant High Rate, Sealed Lead-Acid
Quantity 16
Charge Current (ADC) 3.0
Backup Time (min) > 12.0
Recharge Time 8 Hours to 90%
V
IR
O N
M E
N T
Temperature (°C) 0 to 40, operating -20 to 60, transit
Altitude (m) 2,000, operating 12,000, transit
Humidity 5.0% to 90.0%, non condensing
Heat Dissipation (BTU/hr) 1626
E N
C
EN 50091-2
IEC 61000-3-2
Safety Agencies UL1778 4th Ed.
cUL to CSA22.2 No.107.1 CE (-22 only):
IEC62040, w/CB report and cert IEC61000-4-2, Electrostatic Discharge IEC61000-4-3, Radiated Electromagnetic Field Immunity IEC61000-4-4, Electrical Fast Transient/ Burst Immunity IEC61000-4-5, Surge Immunity IEC61000-4-6, Immunity to Conducted Radio Frequency Disturbances IEC61000-4-8, Power Frequency Magnetic Field Immunity
H
DB-9 Dry Contacts Internal SNMP Adapter (option)
Unit Weight -11 Models 294 lbs. / 132 kg.
-22 Models 300 lbs. / 135 kg.
Shipping Weight -11 Models 389 lbs. / 175 kg.
-22 Models 395 lbs. / 178 kg.
Plug & Receptacle* L5-30P (2)5-20R (1)L5-30R 208 VAC Input L6-30P (2)5-20R (1)L6-30R
240 VAC Input L6-20P (2)5-20R (1)L6-20R
*Hardwired unit is standard. Plug & Receptacle is optional. Contact factory for part numbers.
NOISE REJECTION-ISOLATION: With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode at the input, the noise output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-NM, CM-CM, NM-CM).
SURGE VOLTAGE WITHSTAND CAPABILITY: Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A - 6000V @ 200
ABCDEF3000-11 Compatible External (Extended Run) Battery Cabinets:
Model: D9632-11 Description: 4 Pack (32 Batt) Extended Run Battery Cabinet Model: D9648-11 Description: 6 Pack (48 Batt) Extended Run Battery Cabinet
ABCDEF3000-11 TYPICAL RUN-TIMES (MINs)
25% (675 W) 50% (1350 W) 75% (2025 W) 100% (2700 W)
Internal Batteries Only 40 24 17 12
Internal + 1) D9632-11 170 100 70 55
Internal + 2) D9632-11 325 200 140 110
Internal + 3) D9632-11 550 325 225 170
Internal + 4) D9632-11 >12 Hrs 450 310 230
Internal + 5) D9632-11 >12 Hrs 600 400 300
Internal + 1) D9648-11 250 150 100 80
Internal + 2) D9648-11 550 325 220 160
Internal + 3) D9648-11 >12 Hrs 525 350 250
Internal + 4) D9648-11 >12 Hrs >12 Hrs 525 375
Internal + 5) D9648-11 >12 Hrs >12 Hrs 700 525
Notes: Run-Times are based on new fully charged batteries at 25 deg C ambient.
ABCDEF3000-22 Compatible External (Extended Run) Battery Cabinets:
ABCDEF3000-22 TYPICAL RUN-TIMES (MINs)
25% (675 W) 50% (1350 W) 75% (2025 W) 100% (2700 W)
Internal Batteries Only 35 23 15 12
Internal + 1) D9632-22 160 100 70 55
Internal + 2) D9632-22 325 200 140 110
Internal + 3) D9632-22 500 300 210 165
Internal + 4) D9632-22 >12 Hrs 425 300 230
Internal + 5) D9632-22 >12 Hrs 575 400 300
Internal + 1) D9648-22 230 150 100 80
Internal + 2) D9648-22 500 300 210 160
Internal + 3) D9648-22 >12 Hrs 500 350 270
Internal + 4) D9648-22 >12 Hrs >12 Hrs 525 375
Internal + 5) D9648-22 >12 Hrs >12 Hrs 675 500
Battery Life Disclaimer: Powervar’s standard battery warranty applies only to UPS and UPM products which are continuously connected to AC mains power, except during utility power outages. Products which are regularly and intentionally disconnected from AC mains power will experience battery discharge/charge cycles potentially far more numerous than those for which the battery was designed. As a result, products used in such applications will experience substantially reduced battery life. For that reason, Powervar’s standard battery warranty does not apply for applications in which the UPS or UPM product is regularly and intentionally disconnected from AC mains power. Powervar UPS and UPM products used in such applications shall receive a 90 day warranty on batteries.
Warranty/Support: Powervar warrants the electronics and transformers used in its uninterruptible power supplies to be free from defects in materials and workmanship for a period of three years from the date of shipment. Batteries are warranted for a period of two years from the date of shipment for standby use; 90 days for cyclic use. For North American service or support on any Powervar product, please contact Powervar Technical Support at (800) 369-7179 (in Illinois call (847-596-7000). For service and support in EMEA, contact Powervar, Ltd. in the United Kingdom at +44 (0) 1793 553980. Or visit the Powervar website at www.Powervar.com.
FRONT SIDE REAR
Model ABCDEF4000-22
Topology True On-Line, Double-Conversation, IGBT Design, Internal Isolation Transformer
Voltage (VAC) 200 208 220 230 240 Voltage Range (VAC) 140-230 146-239 154-253 161-264 168-276
Voltage Tolerance + 15% ~ -30% before switching to batteries
Frequency (Hz) 50/60
Frequency Tolerance 42 Hz to 69 Hz before switching to batteries
Input PF > 0.95
Input Current THD < 5.0%
Input Capacity 4320 VA
T P
Capacity 4000VA/ 3600W
Voltage (VAC) 200 120/208/240 220 230 120/208/240
Voltage Regulation ± 3.0% Max, ± 1.0% Normal Output Voltage THD < 3.0%
Power Factor 0.9
Step Load Response ± 4.0% for 50% step load change ± 6.0% for 100% step load change Return to ±3.0% of nominal within 3 cycles
Crest Factor 3:1
Frequency (Hz) 50/60
Frequency Regulation ± 0.1Hz
Overload 125% for 2 minutes 150% for 30 seconds 300% for 500ms
Efficiency AC-AC >85.0%
DC-AC >78.0%
P A
Input Voltage (VAC) 200 208 220 230 240
Output Voltage (VAC) 200 120/208/240 220 230 120/208/240 Transformer Voltage Regulation
± 3.0%
Overload 125% for 10 minutes 150% for 500ms 1000% for 1 cycle
Efficiency > 95.0%
11.80 (299.7
32.65 (829.4)
T T
E
Battery 12V, 34W flame retardant High Rate, Sealed Lead-Acid
Quantity 16
Charge Current (ADC) 3.0
Backup Time (min) > 8.0
V
IR
O N
M E
N T
Temperature (°C) 0 to 40, operating -20 to 60, transit
Altitude (m) 2,000, operating 12,000, transit
Humidity 5.0% to 90.0%, non condensing
Heat Dissipation (BTU/hr) 3252
E N
C
EN 50091-2
IEC 61000-3-2
Safety Agencies UL1778 4th Ed.
cUL to CSA22.2 No.107.1
CE:
IEC62040, w/CB report and certificate IEC61000-4-2, Electrostatic Discharge IEC61000-4-3, Radiated Electromagnetic Field Immunity IEC61000-4-4, Electrical Fast Transient/ Burst Immunity IEC61000-4-5, Surge Immunity IEC61000-4-6, Immunity to Conducted Radio Frequency Disturbances IEC61000-4-8, Power Frequency Magnetic Field Immunity
H
DB-9 Dry Contacts Internal SNMP Adapter (option)
Unit Weight 317 lbs. / 143 kg.
Shipping Weight 412 lbs. / 185 kg.
Plug & Receptacle* L6-30P (2)5-20R (1)L6-30R
*Hardwire unit is standard. Plug & Receptacle is optional. Contact factory for part numbers.
NOISE REJECTION-ISOLATION: With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode at the input, the noise output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-NM, CM-CM, NM-CM).
SURGE VOLTAGE WITHSTAND CAPABILITY: Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A - 6000V @ 200
Compatible External (Extended Run) Battery Cabinets:
ABCDEF4000-22 TYPICAL RUN-TIMES (MINs)
25% (900 W) 50% (1800 W) 75% (2700 W) 100% (3600 W)
Internal Batteries Only 25 17 11 8
Internal + 1) D9632-22 120 75 50 35
Internal + 2) D9632-22 250 150 100 75
Internal + 3) D9632-22 375 220 150 110
Internal + 4) D9632-22 550 325 210 160
Internal + 5) D9632-22 >12 Hrs 425 275 210
Internal + 1) D9648-22 170 110 75 55
Internal + 2) D9648-22 375 220 150 120
Internal + 3) D9648-22 625 375 250 185
Internal + 4) D9648-22 >12 Hrs 525 350 275
Internal + 5) D9648-22 >12 Hrs >12 Hrs 475 350
Battery Life Disclaimer: Powervar’s standard battery warranty applies only to UPS and UPM products which are continuously connected to AC mains power, except during utility power outages. Products which are regularly and intentionally disconnected from AC mains power will experience battery discharge/charge cycles potentially far more numerous than those for which the battery was designed. As a result, products used in such applications will experience substantially reduced battery life. For that reason, Powervar’s standard battery warranty does not apply for applications in which the UPS or UPM product is regularly and intentionally disconnected from AC mains power. Powervar UPS and UPM products used in such applications shall receive a 90 day warranty on batteries.
Warranty/Support: Powervar warrants the electronics and transformers used in its uninterruptible power supplies to be free from defects in materials and workmanship for a period of three years from the date of shipment. Batteries are warranted for a period of two years from the date of shipment for standby use; 90 days for cyclic use. For North American service or support on any Powervar product, please contact Powervar Technical Support at (800) 369-7179 (in Illinois call (847-596-7000). For service and support in EMEA, contact Powervar, Ltd. in the United Kingdom at +44 (0) 1793 553980. Or visit the Powervar website at www.Powervar.com.
FRONT SIDE REAR
Model ABCDEF5200-22
Topology True On-Line, Double-Conversion, IGBT Design, Internal Isolation Transformer
Voltage Tolerance + 15% ~ -30% before switching to batteries
Frequency (Hz) 50/60
Frequency Tolerance 42 Hz to 69 Hz before switching to batteries
Input PF > 0.95
Input Current THD < 5.0%
Input Connection Hardwired Standard: Line cord Optional (Consult factory) Input Capacity 5616 VA
T P
Capacity 5200VA/ 4680W
Voltage Regulation ± 3.0% Max, ± 1.0% Normal
Output Voltage THD < 3.0% Power Factor 0.9
Step Load Response ± 4.0% for 50% step load change ± 6.0% for 100% step load change Return to ±3.0% of nominal within 3 cycles
Crest Factor 3:1
Frequency (Hz) 50/60
Frequency Regulation ± 0.1Hz
Overload 125% for 2 minutes 150% for 30 seconds 300% for 500ms
Efficiency AC-AC >85.0%
DC-AC >76.0%
P A
Transformer Voltage Regulation
± 3.0%
Overload 125% for 10 minutes 150% for 500ms 1000% for 1 cycle
Efficiency > 95.0%
11.80 (299.72)
32.65 (829.4)
T T
E
Battery 12V, 34W flame retardant High Rate, Sealed Lead-Acid
Quantity 16
Charge Current (ADC) 3.0
Backup Time (min) > 6.0
V
IR
O N
M E
N T
Temperature (°C) 0 to 40, operating -20 to 60, transit
Altitude (m) 2,000, operating 12,000, transit
Humidity 5.0% to 90.0%, non condensing
Heat Dissipation (BTU/hr) 2819.56
E N
C
EN 50091-2
IEC 61000-3-2
Safety Agencies UL1778 4th Ed.
cUL to CSA22.2 No.107.1
CE:
IEC62040, w/CB report and certificate IEC61000-4-2, Electrostatic Discharge IEC61000-4-3, Radiated Electromagnetic Field Immunity IEC61000-4-4, Electrical Fast Transient/ Burst Immunity IEC61000-4-5, Surge Immunity IEC61000-4-6, Immunity to Conducted Radio Frequency Disturbances IEC61000-4-8, Power Frequency Magnetic Field Immunity
H
DB-9 Dry Contacts Internal SNMP Adapter (option)
Unit Weight 348 lbs. / 157 kg.
Shipping Weight 443 lbs. / 200 kg.
Plug & Receptacle* L6-30P (2)5-20R (1)L6-30R (Standard)
* Hardwire unit is optional. Alternative Plug & Receptacle available - Contact factory for part numbers.
NOISE REJECTION-ISOLATION: With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode at the input, the noise output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-NM, CM-CM, NM-CM).
SURGE VOLTAGE WITHSTAND CAPABILITY: Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A - 6000V @ 200
ABCDEF5200-22 TYPICAL RUN-TIMES (MINs)
25% (1170 W) 50% (2340 W) 75% (3510 W) 100% (4680 W)
Internal Batteries Only 20 11 8 6
Internal + 1) D9632-22 90 50 35 25
Internal + 2) D9632-22 170 100 70 50
Internal + 3) D9632-22 275 160 110 80
Internal + 4) D9632-22 375 220 150 110
Internal + 5) D9632-22 500 300 200 150
Internal + 1) D9648-22 130 75 50 35
Internal + 2) D9648-22 275 160 110 80
Internal + 3) D9648-22 425 250 170 130
Internal + 4) D9648-22 625 350 240 180
Internal + 5) D9648-22 >12 Hrs 475 325 240
Battery Life Disclaimer: Powervar’s standard battery warranty applies only to UPS and UPM products which are continuously connected to AC mains power, except during utility power outages. Products which are regularly and intentionally disconnected from AC mains power will experience battery discharge/charge cycles potentially far more numerous than those for which the battery was designed. As a result, products used in such applications will experience substantially reduced battery life. For that reason, Powervar’s standard battery warranty does not apply for applications in which the UPS or UPM product is regularly and intentionally disconnected from AC mains power. Powervar UPS and UPM products used in such applications shall receive a 90 day warranty on batteries.
Warranty/Support: Powervar warrants the electronics and transformers used in its uninterruptible power supplies to be free from defects in materials and workmanship for a period of three years from the date of shipment. Batteries are warranted for a period of two years from the date of shipment for standby use; 90 days for cyclic use. For North American service or support on any Powervar product, please contact Powervar Technical Support at (800) 369-7179 (in Illinois call (847-596-7000). For service and support in EMEA, contact Powervar, Ltd. in the United Kingdom at +44 (0) 1793 553980. Or visit the Powervar website at www.Powervar.com.
FRONT SIDE REAR
Model ABCDEF6000-22
Topology True On-Line, Double-Conversion, IGBT Design, Internal Isolation Transformer
Voltage Tolerance + 15% ~ -30% before switching to batteries
Frequency (Hz) 50/60
Frequency Tolerance 42 Hz to 69 Hz before switching to batteries
Input PF > 0.95 Input Current THD < 5.0%
Input Capacity 6480 VA
T P
Capacity 6000VA/ 5400W
Voltage Regulation ± 3.0% Max, ± 1.0% Normal
Output Voltage THD < 3.0%
Power Factor 0.9
Step Load Response ± 4.0% for 50% step load change ± 6.0% for 100% step load change Return to ±3.0% of nominal within 3 cycles
Crest Factor 3:1
Frequency (Hz) 50/60
Frequency Regulation ± 0.1Hz
Overload 125% for 2 minutes 150% for 30 seconds 300% for 500ms
Efficiency AC-AC >85.0%
DC-AC >78.0%
P A
Transformer Voltage Regulation
± 3.0%
Overload 125% for 10 minutes 150% for 500ms 1000% for 1 cycle
Efficiency > 95.0%
11.80 (299.72)
32.65 (829.4)
T T
E
Battery 12V, 34W flame retardant High Rate, Sealed Lead-Acid
Quantity 16
Charge Current (ADC) 3.0
Backup Time (min) > 5.0
V
IR
O N
M E
N T
Temperature (°C) 0 to 40, operating -20 to 60, transit
Altitude (m) 2,000, operating 12,000, transit
Humidity 5.0% to 90.0%, non condensing
Heat Dissipation (BTU/hr) 3252
E N
C
EN 50091-2
IEC 61000-3-2
Safety Agencies UL1778 4th Ed.
cUL to CSA22.2 No.107.1
CE:
IEC62040, w/CB report and certificate IEC61000-4-2, Electrostatic Discharge IEC61000-4-3, Radiated Electromagnetic Field Immunity IEC61000-4-4, Electrical Fast Transient/ Burst Immunity IEC61000-4-5, Surge Immunity IEC61000-4-6, Immunity to Conducted Radio Frequency Disturbances IEC61000-4-8, Power Frequency Magnetic Field Immunity
H
DB-9 Dry Contacts Internal SNMP Adapter (option)
Unit Weight 348 lbs. / 157 kg.
Shipping Weight 443 lbs. / 200 kg.
Plug & Receptacle* *Hardwired unit is standard. Plug & Receptacle is optional. Contact factory for part numbers.
NOISE REJECTION-ISOLATION: With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode at the input, the noise output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-NM, CM-CM, NM-CM).
SURGE VOLTAGE WITHSTAND CAPABILITY: Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A - 6000V @ 200
ABCDEF6000-22 TYPICAL RUN-TIMES (MIN)
25% (1350 W) 50% (2700 W) 75% (4050 W) 100% (5400 W)
Internal Batteries Only 18 10 7 5
Internal + 1) D9632-22 80 45 30 22
Internal + 2) D9632-22 160 90 60 45
Internal + 3) D9632-22 240 140 95 70
Internal + 4) D9632-22 325 190 120 90
Internal + 5) D9632-22 450 250 160 130
Internal + 1) D9648-22 120 65 45 30
Internal + 2) D9648-22 225 140 95 70
Internal + 3) D9648-22 400 220 150 110
Internal + 4) D9648-22 550 325 210 150
Internal + 5) D9648-22 > 12 Hrs 425 275 200
Battery Life Disclaimer: Powervar’s standard battery warranty applies only to UPS and UPM products which are continuously connected to AC mains power, except during utility power outages. Products which are regularly and intentionally disconnected from AC mains power will experience battery discharge/charge cycles potentially far more numerous than those for which the battery was designed. As a result, products used in such applications will experience substantially reduced battery life. For that reason, Powervar’s standard battery warranty does not apply for applications in which the UPS or UPM product is regularly and intentionally disconnected from AC mains power. Powervar UPS and UPM products used in such applications shall receive a 90 day warranty on batteries.
Warranty/Support: Powervar warrants the electronics and transformers used in its uninterruptible power supplies to be free from defects in materials and workmanship for a period of three years from the date of shipment. Batteries are warranted for a period of two years from the date of shipment for standby use; 90 days for cyclic use. For North American service or support on any Powervar product, please contact Powervar Technical Support at (800) 369-7179 (in Illinois call (847-596-7000). For service and support in EMEA, contact Powervar, Ltd. in the United Kingdom at +44 (0) 1793 553980. Or visit the Powervar website at www.Powervar.com.
FRONT SIDE REAR
Model ABCDEF8000-22 ABCDEF10.0-22
Voltage Tolerance + 15% ~ -30% before switching to batteries
Frequency (Hz) 50/60
Frequency Tolerance 42 Hz to 69 Hz before switching to batteries
Input PF > 0.95
Input Current THD < 5.0%
Input Capacity 9195W 11494W
T P
Capacity 8000 VA / 7200W 10000 VA / 9000W
Voltage (VAC) 200
220 230
Voltage Regulation ± 3.0% Max, ± 1.0% Normal
Output Voltage THD < 3.0%
Power Factor 0.9
Step Load Response ± 4.0% for 50% step load change ± 6.0% for 100% step load change Return to ± 3.0% of nominal within 3 cycles
Crest Factor 3:1
Frequency (Hz) 50 or 60 Frequency Regulation ± 0.1Hz
Overload 125% for 2 minutes 150% for 30 seconds 300% for 500ms
Efficiency
AC-AC >87.0%
DC-AC >85.0%
13.77 (349.76)
38.61 (980.61)
33.46 (850.00)
P A
Output Voltage (VAC) 200
220 230
Transformer Voltage Regulation
± 3.0%
Overload 125% for 10 minutes 150% for 500ms 1000% for 1 cycle
Efficiency > 95.0%
T T
E
Voltage (VDC) 288.0, nominal 327.6, float
Battery 12V, 34W flame retardant High Rate, Sealed Lead-Acid
Quantity 24
Charge Current (ADC) 2.5
V
IR
O N
M E
N T
Temperature (°C) 0 to 40, operating -20 to 60, transit
Altitude (m) 2,000, operating 12,000, transit
Humidity 5.0% to 90.0%, non condensing
Audible (dBA) 55-60 @ 1m from front of unit
Heat Dissipation (BTU/hr) 4239
E N
C
EN 50091-2
IEC 61000-3-2
Safety Agencies UL1778 4th Ed.
cUL to CSA22.2 No.107.1 IEC62040, w/CB report and certificate IEC61000-4-2, Electrostatic Discharge IEC61000-4-3, Radiated Electromagnetic Field Immunity IEC61000-4-4, Electrical Fast Transient/ Burst Immunity IEC61000-4-5, Surge Immunity IEC61000-4-6, Immunity to Conducted Radio Frequency Disturbances IEC61000-4-8, Power Frequency Magnetic Field Immunity
H
DB-9 Dry Contacts Internal SNMP Adapter (optional)
Unit Weight 449.0 lbs. / 203.7 kg
Shipping Weight 641.5 lbs. / 291.0 kg
Plug & Receptacle* *Hardwire unit is standard. Plug & receptacle is optional. Contact factory for part numbers.
NOISE REJECTION-ISOLATION: With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode at the input, the noise output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-NM, CM-CM, NM-CM).
SURGE VOLTAGE WITHSTAND CAPABILITY: Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A - 6000V @ 200
Model: D28848-22 Description: 2 String x 24 (48 Batt) Extended Run Battery Cabinet
ABCDEF8000-22 TYPICAL RUN-TIMES (MINs)
25% (1800 W) 50% (3600 W) 75% (5400 W) 100% (7200 W)
Internal Batteries Only 65 25 15 10
Internal + 1) D28848-22 275 120 70 50
Internal + 2) D28848-22 525 220 140 95
Internal + 3) D28848-22 >12 Hrs 350 210 140
Internal + 4) D28848-22 >12 Hrs 500 275 200
Internal + 5) D28848-22 >12 Hrs 650 375 250
ABCDEF10.0-22 TYPICAL RUN-TIMES (MINs)
25% (2250 W) 50% (4500 W) 75% (6750 W) 100% (9000 W)
Internal Batteries Only 50 21 13 9
Internal + 1) D28848-22 200 90 55 35
Internal + 2) D28848-22 400 170 95 70
Internal + 3) D28848-22 650 275 150 100
Internal + 4) D28848-22 >12 Hrs 375 220 150
Internal + 5) D28848-22 >12 Hrs 500 275 200
Battery Life Disclaimer: Powervar’s standard battery warranty applies only to UPS and UPM products which are continuously connected to AC mains power, except during utility power outages. Products which are regularly and intentionally disconnected from AC mains power will experience battery discharge/charge cycles potentially far more numerous than those for which the battery was designed. As a result, products used in such applications will experience substantially reduced battery life. For that reason, Powervar’s standard battery warranty does not apply for applications in which the UPS or UPM product is regularly and intentionally disconnected from AC mains power. Powervar UPS and UPM products used in such applications shall receive a 90 day warranty on batteries.
Warranty/Support: Powervar warrants the electronics and transformers used in its uninterruptible power supplies to be free from defects in materials and workmanship for a period of three years from the date of shipment. Batteries are warranted for a period of two years from the date of shipment for standby use; 90 days for cyclic use. For North American service or support on any Powervar product, please contact Powervar Technical Support at (800) 369-7179 (in Illinois call (847-596-7000). For service and support in EMEA, contact Powervar, Ltd. in the United Kingdom at +44 (0) 1793 553980. Or visit the Powervar website at www.Powervar.com.
FRONT SIDE REAR
Model ABCDEF12.0-22 ABCDEF15.0-22
Voltage Tolerance + 15% ~ -30% before switching to batteries
Frequency (Hz) 50/60
Frequency Tolerance 42 Hz to 69 Hz before switching to batteries
Input PF > 0.95 Input Current THD < 5.0%
Input Capacity 13793W 17241W
T P
Capacity 12000 VA / 10800W 15000 VA / 13500W
Voltage (VAC) 200
220 230
Voltage Regulation ± 3.0% Max, ± 1.0% Normal
Output Voltage THD < 3.0% Power Factor 0.9
Step Load Response ± 4.0% for 50% step load change ± 6.0% for 100% step load change Return to ± 3.0% of nominal within 3 cycles
Crest Factor 3:1
Frequency (Hz) 50 or 60
Frequency Regulation ± 0.1Hz
Overload 125% for 2 minutes 150% for 30 seconds 300% for 500ms
Efficiency
AC-AC >87.0%
DC-AC >85.0%
15.75 (400.0)
44.39 (1127.54)
42.53 (1080.2)
P A
Output Voltage (VAC) 200
220 230
Transformer Voltage Regulation
± 3.0%
Overload 125% for 10 minutes 150% for 500ms 1000% for 1 cycle
Efficiency > 95.0%
T T
E
Voltage (VDC) 288.0, nominal 327.6, float
Battery 12V, 34W flame retardant High Rate, Sealed Lead-Acid
Quantity 24
Charge Current (ADC) 2.5
V
IR
O N
M E
N T
Temperature (°C) 0 to 40, operating -20 to 60, transit
Altitude (m) 2,000, operating 12,000, transit
Humidity 5.0% to 90.0%, non condensing
Audible (dBA) 55-60 @ 1m from front of unit
Heat Dissipation (BTU/hr) 4239
E N
C
EN 50091-2
IEC 61000-3-2
Safety Agencies UL1778 4th Ed.
cUL to CSA22.2 No.107.1 IEC62040, w/CB report and certificate IEC61000-4-2, Electrostatic Discharge IEC61000-4-3, Radiated Electromagnetic Field Immunity IEC61000-4-4, Electrical Fast Transient/ Burst Immunity IEC61000-4-5, Surge Immunity IEC61000-4-6, Immunity to Conducted Radio Frequency Disturbances IEC61000-4-8, Power Frequency Magnetic Field Immunity
H
DB-9 Dry Contacts Internal SNMP Adapter (optional)
Unit Weight 719.0lbs/ 326.1kg (12kVA) 739.0lbs/335.2kg (15kVA)
Shipping Weight 807.0lbs. / 366.0 kg (12kVA) 827.0lbs/ 375.1kg (15kVA)
Plug & Receptacle* *Hardwire unit is standard. Plug & receptacle is optional. Contact factory for part numbers.
NOISE REJECTION-ISOLATION: With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode at the input, the noise output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-NM, CM-CM, NM-CM).
SURGE VOLTAGE WITHSTAND CAPABILITY: Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A - 6000V @ 200
ABCDEF12.0-22 TYPICAL RUN-TIMES (MINs)
25% (2700 W) 50% (5400 W) 75% (8100 W) 100% (10800 W)
Internal Batteries Only 35 17 10 7
Internal + 1) D28848-22 160 70 40 25
Internal + 2) D28848-22 300 130 80 55
Internal + 3) D28848-22 475 210 120 85
Internal + 4) D28848-22 675 275 170 110
Internal + 5) D28848-22 >12 Hrs 375 230 150
ABCDEF15.0-22 TYPICAL RUN-TIMES (MINs)
25% (3375 W) 50% ( 6750 W) 75% (10125 W) 100% (13500 W)
Internal Batteries Only 25 13 7 5
Internal + 1) D28848-22 120 50 30 22
Internal + 2) D28848-22 230 100 60 45
Internal + 3) D28848-22 350 150 100 70
Internal + 4) D28848-22 500 220 130 90
Internal + 5) D28848-22 650 275 170 110
Battery Life Disclaimer: Powervar’s standard battery warranty applies only to UPS and UPM products which are continuously connected to AC mains power, except during utility power outages. Products which are regularly and intentionally disconnected from AC mains power will experience battery discharge/charge cycles potentially far more numerous than those for which the battery was designed. As a result, products used in such applications will experience substantially reduced battery life. For that reason, Powervar’s standard battery warranty does not apply for applications in which the UPS or UPM product is regularly and intentionally disconnected from AC mains power. Powervar UPS and UPM products used in such applications shall receive a 90 day warranty on batteries.
Warranty/Support: Powervar warrants the electronics and transformers used in its uninterruptible power supplies to be free from defects in materials and workmanship for a period of three years from the date of shipment. Batteries are warranted for a period of two years from the date of shipment for standby use; 90 days for cyclic use. For North American service or support on any Powervar product, please contact Powervar Technical Support at (800) 369-7179 (in Illinois call (847-596-7000). For service and support in EMEA, contact Powervar, Ltd. in the United Kingdom at +44 (0) 1793 553980. Or visit the Powervar website at www.Powervar.com.
Both the input and output connections of this UPS exhibit dangerous high voltage, which represents a hazard to personal life or safety. Please read this manual carefully prior to installation, operation, and use. Please pay close attention to any caution labels and statements. Only trained, authorized service personnel should be allowed to remove UPS covers or perform maintenance tasks.
22..00 SSttrruuccttuurree aanndd BBaassiicc PPrriinncciipplleess
2.1 General Structure
2.1.1 Security Plus Front Panel and Rear Panel Structure
The operator panel layout of the Security Plus UPS is illustrated in Fig. 2-1 and Table 2-1.
Item Function
LCD Display Window Displays status/programming information about UPS
Normal/Bypass Button Turns UPS inverter on and off (when off UPS is in bypass)
OK Button Press to confirm selection of a function
Select Button Used to select or navigate through the UPS menu
Line LED Indicator ON - main supply normal; OFF—no main supply;
Inverter LED Indicator ON - Inverter On; OFF—Inverter Off
Bypass LED Indicator ON - Indicates UPS is in bypass mode BLINKING - Bypass voltage is out of range. Bypass transfer is prohibited.
Fault LED Indicator ON - UPS is in fault mode; OFF- UPS normal or turned off
Table 2-1
Figure 2-1
2.1.2 Security Plus Display/Controls Operation
The menu visible in the LCD display of the Security Plus UPS is illustrated in Fig. 2-2 and 2-3.
The various LCD displays are accessed using the front panel controls of the UPS as follows:
Function Button Explanation
The NORMAL/BYPASS button is used to start and stop the inverter. When the inverter is stopped, the UPS will be in bypass.
The SELECT button is used to scroll through various display screens and must be pressed for 3 seconds to change UPS programming modes.
The OK button is only functional when in the programming mode (Settings Menu)
Display Content and Corresponding Operation
Default Mode
After startup, the LCD displays a message showing the UPS name and model number.
This message will display for 8 seconds unless the SELECT button is pushed. After either 8 seconds or if the SELECT button is pushed, the UPS display changes to either the “OPERATION
MODE” display (i.e. NORM, BYP, BATT) or the “FAULT” display (if the UPS has detected a fault condition). In the absence of a UPS fault condition, the “OPERATION MODE” display is the default display.
UPS Parameters Mode
When the UPS is operating normally, pressing the “SELECT” button will allow switching to the
UPS parameter displays.
The parameter displays are as follows:
1. Operation Mode
2. Output voltage display
3. Input voltage display
4. Input frequency display
5. Output frequency display
6. Output load percentage display
7. Battery voltage display
8. Battery percentage charge display
9. UPS state one display
10. UPS state two display
While in the Parameters mode, pressing the “SELECT” button for 3 seconds will cause the UPS to enter the UPS Settings Mode. Refer to Figure 2.3 for the Parameter Setting Menu in the UPS
Settings Mode.
When in the UPS Parameters mode, if no operation is performed for 30 seconds, the Parameters mode will be cancelled and the UPS display will return to the default “OPERATION MODE” display.
34 Figure 2.2 – Display Verbiage
Figure 2.2 – Display Verbiage
(8-15kVA)
BYP:XXX INV:XXX
ALARM:XXX
BATTERY VOLTAGE
XXX.XV
OUTPUT VOLTAGE
X2-X4:XXX.XV
OPERATION
BATTERY MODE
% LOAD
XXX%
OUTPUT FREQUENCY
XX.XHz
OUTPUT VOLTAGE
X1-X4:XXX.XV
INPUT VOLTAGE
XXX.XV
OPERATION
ONLINE MODE
OPERATON
BATTERY MODE
OPERATION
BYPASS MODE
BATTERY CHARGE
XXX%
INPUT FREQUENCY
XX.XHz
OPERATION
UPS START UP
OPERATION
O/P SHUTDOWN
AC:XXX BAT:XXX
INVERTER:XXX
If the NORMAL/BYPASS button is pushed and the AC input is out of range, the system will start up in battery operation mode and continue until AC returns to normal range or batteries become depleted.
OPERATION
BATTERY MODE
Press
‘NORMAL/BYPASS’
If the AC input condition is out of range, then the system will display
‘UPS Start Up’. There is no output in this condition
The system will automatically switch to ONLINE mode If the
AC input condition is in range.
SECURITY PLUS
MODEL NUMBER
Press
Press
Press
Press
Press
Press
Press
Press
Press
Press
Press
‘NORMAL/BYPASS’
Press
‘NORMAL/BYPASS’
If the ‘NORMAL/BYPASS’ key is pressed while the inverter is on and the input AC is normal, the system will switch to BYPASS mode. In this condition, the inverter is off and the battery charger is on.
If the input AC goes out of range while the system is in BYPASS mode, the output will shut down. It will stay in this mode until the input AC returns to normal
If the NORMAL/BYPASS button is pushed and the
AC input is out of range, the system will start up in battery operation mode and continue until AC returns to normal range or batteries become depleted.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .