36C25025Q0420_2.docx

DOCX document 18 KB Posted

Attached to
J059--UPS Equipment Maintenance
Solicitation number
36C25025Q0420
Issued by

About this file

This document is an Amendment to a Previous Combined Solicitation for UPS Equipment Maintenance at the Richard L. Roudebush VAMC in Indianapolis, Indiana. The Department of Veterans Affairs is seeking a contractor to provide annual preventative maintenance and load testing for Uninterruptible Power Supply (UPS) devices, with a base year period from 05/01/25-04/30/26 and four optional extension years. The solicitation (36C25025Q0420) is unrestricted and covers multiple UPS units, including a Powervar model and a Medicanix MCS4480MS, with monthly and annual testing requirements.

Key details include a response deadline of 04/18/2025 at 12pm Eastern Time, with the contract specialist being Tiera Sims from the VA Network Contracting Office in Independence, OH. The solicitation covers maintenance services previously handled internally by VA electricians or case-by-case contractors. The product service code is J059, and the NAICS code is 811210. Contractors are expected to perform preventative maintenance and load tests during normal hours, following Performance Work Statement and Original Equipment Manufacturer (OEM) specifications, with weekly testing to be conducted by facility staff.

View the file

Other files

File Type Posted
UPS Inventory for Contract.xlsx XLSX spreadsheet
UPS Device 11 Tag.jpg JPG image
36C25025Q0420_1.docx DOCX document
Appendix D.pdf PDF
Appendix C.pdf PDF
Appendix E.pdf PDF
Appendix B.pdf PDF
Appendix A.pdf PDF
36C25025Q0420.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Amendment to a Previous Combined Solicitation

Amendment to a Previous Combined Solicitation

SUBJECT*
UPS Equipment Maintenance

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE*
44131
SOLICITATION NUMBER*
36C25025Q0420
RESPONSE DATE/TIME/ZONE
04-18-2025 12pm EASTERN TIME, NEW YORK, USA
ARCHIVE
60 DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
N

SET-ASIDE

PRODUCT SERVICE CODE*
J059
NAICS CODE*
811210
CONTRACTING OFFICE ADDRESS
Department of Veterans Affairs

Network Contracting Office (NCO) 10 6150 Oak Tree Blvd., Suite 300

Independence OH 44131

POINT OF CONTACT*

Contract Specialist Tiera Sims tiera.sims@va.gov 216-447-8300

PLACE OF PERFORMANCE

ADDRESS
Richard L. Roudebush VAMC

1481 W. 10th Street

Indianapolis IN

POSTAL CODE
46202

COUNTRY

ADDITIONAL INFORMATION

AGENCY’S URL
https://va.gov
URL DESCRIPTION
Home Page
AGENCY CONTACT’S EMAIL ADDRESS
tiera.sims@va.gov
EMAIL DESCRIPTION
Contract Specialist

DESCRIPTION

Please see Q & A responses below:

1. What model/type is UPS #11? Model ACDEF40 does not tell me anything. Is this the Powervar UPS?

Yes, it is a Powervar. See attached service tag.

1. How many battery strings are there on each UPS and how many batteries per string are there?

Please see attached document labeled “UPS Inventory for Contract” for the number of batteries.

1. Will you accept qualified over certified per their requirements below (PWS section 11.0 Contractor Qualifications) due to only the OEM being certified.

Yes.

1. Who currently provides contracted maintenance services on these systems?

There is currently no contract. All maintenance and repairs are done by VA Electricians or contracted out on a case-by-case basis.

1. For the Medicanix MCS4480MS- please confirm you just want annual preventative maintenance & load testing on this contract & not the weekly or monthly testing that would correspond with the generator testing or to alleviate the noted concern about over cycling your batteries by too much testing in Appendix E. Otherwise if we are to test these on a monthly basis, then please provide anticipated runtime @ 25% for each Medicanix Unit for a monthly test.

The reference to “generator” in Appendix E is referring to the battery backup unit itself, not a traditional fuel-powered generator. Please test the referenced unit according to the specific instruction in Appendix E, excluding the Weekly Testing portion only. The anticipated runtime at 25% is not known currently.

1. Why is the opportunity unrestricted and not Small Business Set Aside?

This is a resolicitation of the previous opportunity 36C25025Q0170 that was not set aside.

1. Appendix E lists multiple load tests, can you confirm which quantity we’re required to complete?

Please complete the monthly and annual testing only for the Medicanix units. Section 2.0 in the PWS specifically excludes the weekly test, “Weekly testing will be conducted by facility or clinical staff and is excluded from the contractor's scope.” Weekly tests will be performed by facility staff.

1. For the load test, are they to be completed during normal or after hours?

Load tests shall be performed during normal hours.

1. Are to PM these units as well or only load test?

PM and loads tests shall be performed as specified by the PWS and OEM specifications.

1. Is the generator part of the project, or is that maintained in-house? I don't see a separate CLIN for it.

The generator is not a part of this contract.

See attached document: UPS Device 11 Tag.

See attached document: UPS Inventory for Contract.