MSB Partial Original Drawings.pdf

PDF 4 MB Posted

Attached to
RFI for MAGIS-100 Access Platforms
Solicitation number
AD_MAGIS-100_DA
Issued by

About this file

These are architectural construction drawings for the NuMI Service Buildings located in Aurora, Illinois. The document set includes detailed floor plans, building sections, wall sections, foundation plans, and structural framing plans dated January 16, 2002, prepared by Crawford, Murphy & Tilly, Inc. consulting engineers.

The project encompasses multiple building levels with spaces including a fire command center (Room 101), entry vestibule (102), staging area (103), mechanical/electrical rooms (103, 106, 107), and mechanical shafts. Construction specifications include reinforced concrete masonry unit (CMU) walls in varying thicknesses (6", 8", 10", and 12"), aluminum curtain wall systems with 1-inch insulating glass or spandrel panels, metal wall panels with rigid insulation, 4-ply built-up roofing systems, and structural steel framing at multiple elevations. Key elevation references include finish floor at EL. 748'-6", various steel tops ranging from EL. 766'-6" to EL. 782'-6", parapet walls at EL. 784'-6", and final wall heights at EL. 797'-6". The foundation design incorporates reinforced concrete footings with compacted CA-6 base, vapor barriers, rigid insulation, and continuous reinforcing steel. Interior finishes specified include ceramic tile bases and floors, painted CMU walls, and various mechanical/plumbing fixtures. The drawings reference coordination requirements with electrical, plumbing, fire protection, and mechanical trade drawings, with specific notes regarding elevator enclosure bracing and temporary support during construction.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

V A

R

STEEL COL. & COMPONENTS -

SEE STRUCT.

STEEL COLUMN &

COMPONENTS - SEE

STRUCT.

B/COL COVER

EL. 748'-8" T/CONC PIER

EL. 748'-6"

OPEN AT TOP

ALUM. COLUMN COVER

AND BOT.

TOP OF COLUMN

SCALE: 1-1/2"=1'-0" -

COLUMN-PLAN

SCALE: 1-1/2"=1'-0" -

2 BOT. OF COLUMN

SCALE: 1-1/2"=1'-0" -

LIGHT FIXTURE -

SEE ELEC.

JUNCTION BOX -

SEE ELEC.

ALUM. COLUMN

COVER - OPEN AT

TOP & BOT.

9" 9"

COL. CL

V A

R

9" 9"

9" 9"

TOP/CONC

A

WALL TYPES

SCALE: NTS

12" REINFORCED CMU (PAINT)

B

FACE BRICK - 8" x 8" x 4"3

10" REINFORCED CMU6

AIR SPACE7

RIGID INSULATION - 1 1/2"

1'-6"

C

8" NOM.

8" REINFORCED CMU1

@ 16" O.C. VERTICALLY

2" INTERIOR INSULATED

METAL LINER PANEL

9 GALVANIZED 1/2" SUBGIRT

10 1-1/2" FLUSH EXTERIOR

INSULATED METAL WALL PANEL

E

10"4" 4"

(PAINT EXPOSED FACES)

HORIZONTAL JOINT REINF.

4"

12" NOM. 2" 4"

NOM. NOM. NOMINAL NOM.

D

8"

NOM.

1 1/2" 5 1/2"

11 Z - ANGLE CLIPS

F

1'-8"

8"6"

NOM.

NOM.NOM.

6"

12 6" CMU (PAINT EXPOSED FACES)

13 5 1/2" BATT INSULATION

WITH VAPOR BARRIER

NOM.

A

1"

D1

8"

NOM.

1 1/2"

A

3"

5 1/2"

33'-10"

59'-10"

139'-2"

STEEL PIPE

BOLLARD (TYP)

SEE C-12

FIRE

COMMAND

ENTRY

VESTIBULE

STAGING

AREA

MECHANICAL /

ELECTRICAL

7' -1

8" 8"

1' -8

6' -8

6'

-4

2' -8

B

1'-8"

9' -3

6'

-4

B

B

B

B

B

B

B

CC C

C

C

C

C C C D D

A

A

A

A

SHAFT

MECHANICAL

MECHANICAL

B

B

11"

1'-6"

E

6' -0

O

P E

N

IN

G

6' -0

O P

E N

IN

G

C E

N T

E R

D O

O R

IN

T

H

IS

A R

E A

'-6

'-2

8"9"

4'-1"

'-5

9"

'-1

1' -4

'-7

11"11"

EXIST.

ELEVATOR

6'-4"

1'-6"

'-0

O

P E

N

IN

G

7"

15'-51 2"

'-5

8"

A-19 A

A-19

C

A-19

B

EXIST.

ELEV.

6' -1

03 4" 2"

2"

'-4

2"

2" 6'

-4 1 2"

2" 6'

-1 03 4"

STEEL PIPE

BOLLARD (TYP)

SEE C-12

F

ALUMINUM WINDOW

FRAMING WITH 1"

INSULATING GLASS

OR 1" SPANDREL GLASS

(SPANDREL PANELS) WHERE

ALUMINUM WINDOW

FRAMING WITH 1"

INSULATING GLASS

OR 1" SPANDREL GLASS

(SPANDREL PANELS) WHERE

SEE A-13 FOR CONTINUATION

OF CONC. APRON IN THIS AREA

DOORS INCLUDE SIDE FRAMES.

NOTE: DIMENSIONS AT PEDESTRIAN

HB

HB

FD

FD

HOSE BIBB

SEE PLBG.

HOSE BIBB

SEE PLBG.

9"

A-18

'-1

1"

2' -7

1' -6

"1 '-6

3' -0

2'

-7 3 4"

SHOWN ON ELEVATIONS

SHOWN ON ELEVATIONS

14'-0" 6'-4" 5'-8"

1'-8"

10"

21'-31 2" 3'-4"

5' -1

1"

2" O

F F

S E

T

COL CL

9'-10"SHAFTCL

EQ. EQ.

'-8

1'-0" TO FACE

OF CONC. FND.

12'-10 1/2" 6'-4"

AURORA, ILLINOIS

60504

SUITE 107

(630) 820-0350 FAX

(630) 820-1022

CRAWFORD, MURPHY & TILLY, INC.

CONSULTING ENGINEERS

600 NORTH COMMONS DRIVE

SCALE: 1/4" = 1'-0"

FLOOR PLAN

1/4"=1'-0" 4 0 4 8

SCALE FEET

1 1/2"=1'-0"

SCALE FEET

1 0 1

SCALE:

1-16-02

1-16-02

1-16-02

J. SIMS

E. CRUMPLEY

D. NEVIN

1-16-02R. PLUNKETT, D. BOGERT1-16-02B. HELD

1-16-02M. WAGNER

1-16-02R. MURPHY

1-16-02P. O'SHEA

A U

G

MSB FLOOR PLAN

A-126-7-5

NuMI SERVICE BUILDINGS

2. FIELD VERIFY ELEVATOR ENCLOSURES AND OPENINGS

1. TEMPORARY BRACING OF EXISTING ELEVATORS SHALL

AND PERMANENTLY RESUPPORTED AT NEW MASONRY

BE TEMPORARILY RESUPPORTED DURING CONSTRUCTION

WALLS - SEE STRUCTURAL.

ELEVATOR NOTES:

WITH ELEVATOR SHOP DRAWINGS, ELEVATOR

MANUFACTURER AND EXISTING CONDITIONS.

CONT. 3/16"x12"x4 1/2" BENT PLATE

CLOSURE. TYP. AT PERIMETER OF BUILDING

AT COLUMN LINES 1, 5, A AND B. WELD TO

TOP OF BEAM FLANGE. PAINT.

2x6 TREATED WOOD NAILERS & BLOCKING, FASTEN TO BENT PLATE

20 GA. CAP FLASHING. WRAP OVER

TOP / FASCIA COPING

EL. 784'-6"

4-PLY BUILT-UP ROOFING SYSTEM OVER

1/2" FIBERBOARD OVER TAPERED ROOF

INSULATION AND 1-1/2" METAL ROOF

DECK

TOP OF PARAPET WALL

4" NOM. CANT

WALL GIRT

METAL PANEL

1-1/2" FLUSH EXTERIOR INSULATED

GALV. 1/2" SUBGIRT

METAL LINER PANEL

2" INTERIOR INSULATED

NOM.

2"4"1'-0" A

A-23

1' -0

9" 51 2" 11

2"

7"9"

4"1'-0"

1'-4"

8"1"

2"51

2"8"1"

7"9"

1'-4"

10"1"

SCALE: 1-1/2" =1'-0" A-12

C

2"41

2"1"

BEAM COPE - SEE STRUCTURAL

3 1/2" TO 6" INSULATION AT PARAPET-

INCREASE WOOD BLOCKING TO

MATCH INSULATION THICKNESS.

EL. 748'-6"

FINISH FLOOR

EL. 784'-6"

TOP / PARAPET

EL. 797'-6"

TOP / WALL

EL. 748'-6"

FINISH FLOOR

EL. 784'-6"

TOP / PARAPET

EL. 797'-6"

TOP / WALL

EL. 778'-0"

TOP / STEEL

SHAFT C

EL. 770'-9"

TOP / CRANE RAIL

39'-0"1'-4" 1'-4"

41'-8"

1'-4" 39'-0" 1'-4"

41'-8"

L

A-18 A

A-18 A

SCALE: 3/16"=1'-0" A-12

A

A-18

SCALE: 3/16"=1'-0" A-12

B

A-18

NOTE: NO PORTION OF THE ROOF STRUCTURE

OR PLUMBING, HVAC, FIRE PROTECTION

EQUIPMENT SHALL EXTEND BELOW

EL. 779'-5"

EL. 765'-2"

TOP / CONCRETE

A-14

EL. 779'-5"

BOT. ALL INTERFERENCES

107A 107B

A-14

EL. 779'-5"

BOTT. ALL INTERFERENCES

NOTE: NO PORTION OF THE ROOF STRUCTURE

OR PLUMBING, HVAC, FIRE PROTECTION

EQUIPMENT SHALL EXTEND BELOW

EL. 779'-5"

AURORA, ILLINOIS

60504

SUITE 107

(630) 820-0350 FAX

(630) 820-1022

CRAWFORD, MURPHY & TILLY, INC.

CONSULTING ENGINEERS

600 NORTH COMMONS DRIVE

3/16"=1'-0" 2 0 10 146

SCALE FEET

2 4 8 12

1 1/2"=1'-0"

SCALE FEET

1 0 1

SCALE:

1-16-02

1-16-02

1-16-02

J. SIMS

E. CRUMPLEY

D. NEVIN

1-16-02R. PLUNKETT, D. BOGERT1-16-02B. HELD

1-16-02M. WAGNER

1-16-02R. MURPHY

1-16-02P. O'SHEA

MSB BUILDING SECTIONS, SHEET 1

A-176-7-5

NuMI SERVICE BUILDINGS

SOAP DISPENSOR - SD (FERMILAB FURNISHED -

SUBCONTRACTOR INSTALL)

TOILET PAPER DISPENSER - TPD (FERMILAB FURNISHED -

SUBCONTRACTOR INSTALL)

TOILET SEAT COVER DISPENSER - TSCD (FERMILAB

FURNISHED - SUBCONTRACTOR INSTALL)

PAPER TOWEL DISPENSER/WASTE RECEPTACLE -

PTD/WR (FURNISHED AND INSTALLED BY SUBCONTRACTOR)

MIRROR - M (SUBTRACTOR FURNISH AND INSTALL)

GRAB BAR - GB-30 (FURNISHED AND INSTALLED BY

SUBCONTRACTOR)

GRAB BAR - GB-42 (FURNISHED AND INSTALLED BY

SUBCONTRACTOR)

UTILITY SHELF - US (SUBCONTRACTOR FURNISH AND INSTALL)

CLOTHES HOOK - CH (SUBCONTRACTOR FURNISH AND INSTALL)

CMU - PAINT

CERAMIC TILE BASE (& FLOOR TILE)

LIGHT FIXTURE - SEE ELECTRICAL DRAWINGS

NOTES

3 2

3' -0

1'-0"3'-6"

2' -1

0"

3' -4

ELEVATION

SCALE:3/8"=1'-0" -

C ELEVATION

SCALE:3/8"=1'-0" -

D ELEVATION

SCALE:3/8"=1'-0" -

E

1' -6

4' -0

4" 2'-6"

9 7

3 2

5' -9

8'-4"

SCALE: 3/8"=1'-0"

PARTIAL FLOOR PLAN

A-12

1' -6

2'

-9

1' -6

BOT. OF MET. DECK

(2) 3"x3"x1/4" CONT ANGLES

ANCHORED TO DECK ONLY

ROD & SEALANT - BOTH

SIDES (FIRE SEAL AT

FIRE WALLS - FILL

CMU WALL

1-1/2" = 1'-0"

CMU WALL AT METAL DECK

1" w/ 1/2" S.S BOLTS AT 2'-0" CTS.

DECK VOIDS)

6"

EXISTING NEW

2TYPE 1 RAIL/FLOOR CONNECTION

1 1/2" = 1'-0"

1. (6) CURVED SECTIONS OF RAILING - RADIUS FROM CENTER OF SHAFT.

ELEVATION - RAILINGS-TYPE A-(REMOVABLE) - TYP.

SCALE: 1/2" = 1'-0"

NOTES:

A-17 B

3' -6

3 4" 5"

2" 41

2"8'-0"

5" 3'

-0 1 4"

EL. 748'-6"

FINISH FLOOR

EL. 784'-6"

TOP / PARAPET

EL. 764'-6"

ROLL-UP DOOR HEAD

EL. 770'-9"

TOP / CRANE RAIL

E

A

B

D1

106'-8"

1'-4"26'-0"1'-4"

BUILDING SECTION

SCALE: 3/16"=1'-0" A-12

A A-17

NOTE: NO PORTION OF THE BUILDING

OR PLUMBING, HVAC, FIRE PROTECTION

EQUIPMENT SHALL EXTEND BELOW

EL. 779'-5"

EL. 779'-5"

BOT / INTERFERENCES

A-14 A-15

A-22

3/16"=1'-0" 2 0 10 146

SCALE FEET

2 4 8 12

600 NORTH COMMONS DRIVE

CONSULTING ENGINEERS

CRAWFORD, MURPHY & TILLY, INC.

(630) 820-1022

(630) 820-0350 FAX

SUITE 107

60504

AURORA, ILLINOIS

SCALE:

1-16-02

1-16-02

1-16-02

J. SIMS

E. CRUMPLEY

D. NEVIN

1-16-02R. PLUNKETT, D. BOGERT1-16-02B. HELD

1-16-02M. WAGNER

1-16-02R. MURPHY

1-16-02P. O'SHEA

A U

G

MSB BUILDING SECTIONS, SHEET 2

A-186-7-5

NuMI SERVICE BUILDINGS6421

FEETSCALE

3 7501 3/8"=1'-0"

1/2"=1'-0" 5432101

SCALE FEET

1 1/2"=1'-0"

SCALE FEET

1 0 1

SCALE: 3"=1'-0" -

D

COPING FLASHING

TYPE "A"

CMU - FILL

WITH GROUT

SET IN

SEALANT

LIMESTONE

COPING

ROD AND SEALANT

TOP AND SIDES

SST SPLIT-TAIL ANCHOR

AT EA. HEAD JOINT -

SECURE TO CMU - (FILL

WITH GROUT)

PROVIDE SLOTS AT ENDS

OF EA. COPING PIECE TO

RECEIVE SPLIT-TAIL ANCHOR

BOND BEAM (H-TYPE)

EL. 765'-2", 771'-2"

T/BOND BEAM

AND EL. 776'-8"

#7 @ 32"

(FULL HEIGHT)

W/ 2-#7 CONT.

2" RIGID INSULATION

#7 @ 32"

(FULL HEIGHT)

12" CMU4" FACE BRICK

ROOF BEAMS

(BEYOND)

1'-0"

1'-6"

SCALE: 1-1/2"=1'-0" A-12

C

EL. 766'-6", 772'-6"

TOP /STEEL

AND EL. 778'-0"

NOM.

NOM.NOM. NOM.

EL. 748'-6"

FINISH FLOOR

FACE BRICK

FLASHING

EVERY SECOND BLOCK

HORIZONTAL JOINT REINF.

COURSE AND AS NOTED

2" RIGID INSUL.

FACE BRICK

EL. VARIES

TOP OF MASONRY

SLOPE

SLOPE

LIMESTONE COPING

GROUT CORES SOLID AT PARAPET

COUNTER FLASHING/FLASHING

4" CANT

1/2 " FIBERBOARD INSUL.

1 1/2" MET.DECK

12" CMU

4 PLY BUR W/GRAVEL

TAPERED INSUL. SLOPES

SEE ROOF PLAN FOR

2" RIGID INSULATION

24" X 24" CONT.

SCALE: 1-1/2"=1'-0" A-12

B

8"

4" 10" 4"

4"

4" 2" 12" NOM.

1'-6"

TREATED 2"x8" WOOD BLOCKING

91 2"

2"

71 2"

DRIP

1 2"

ROD & SEALANT

CONT. - BOTH SIDES

COPING FLASHING

TYPE "A"

SST SPLIT-TAIL ANCHOR

AT EA. HEAD JOINT - SEE

SECTION D, THIS SHEET

WEEPS @ 24" O.C.

STEEL ANGLE -

SEE STRUCTURAL

EL. VARIES

TOP / STEEL

MASONRY

4-PLY BUILT-UP ROOFING SYSTEM OVER 1/2"

FIBERBOARD OVER TAPERED INSULATION

AND 1-1/2" METAL ROOF DECK

SEE MECHANICAL, PLUMBING AND

FIRE PROTECTION DRAWINGS

METAL PANEL

1-1/2" FLUSH EXTERIOR INSULATED

GALV. 1/2" SUBGIRT

METAL LINER PANEL

2" INTERIOR INSULATED

ONLY ABOVE

ROOF LINE

AT EL. 772'-6"

A A-23

A-23

SCALE: 3/4"=1'-0" A-12

A

A-17, A-18

WALL GIRTS (TYP.)

SEE STRUCT.

COPED BEAM -

SEE STRUCTURAL

AURORA, ILLINOIS

60504

SUITE 107

(630) 820-0350 FAX

(630) 820-1022

CRAWFORD, MURPHY & TILLY, INC.

CONSULTING ENGINEERS

600 NORTH COMMONS DRIVE

3/4"=1'-0" 1 0 2 31

SCALE FEET

1 1/2"=1'-0"

SCALE FEET

1 0 1

SCALE:

1-16-02

1-16-02

1-16-02

J. SIMS

E. CRUMPLEY

D. NEVIN

1-16-02R. PLUNKETT, D. BOGERT1-16-02B. HELD

1-16-02M. WAGNER

1-16-02R. MURPHY

1-16-02P. O'SHEA

MSB WALL SECTIONS

A-196-7-5

NuMI SERVICE BUILDINGS

3"=1'-0"

CONT. 16 GA. GALV. CLEAT PAINTED

TO MATCH EXT. WALL PANELS

PRE-FINISHED 18 GA. GALV. FASCIA

COPING. COLOR TO MATCH WALL

PANELS

CONT. 3/16"x12"x4 1/2" BENT PLATE

CLOSURE. TYP. AT PERIMETER OF BUILDING

AT COLUMN LINES 1, 5, A AND B. WELD TO

TOP OF BEAM FLANGE. PAINT.

2x6 TREATED WOOD NAILERS & BLOCKING, FASTEN TO BENT PLATE

TYP.

20 GA. CAP

FLASHING. WRAP

OVER TOP OF

PARAPET WALL

20 GA. CAP FLASHING. WRAP OVER

EL. 784'-6"

TOP / FASCIA COPING

TOP / FASCIA COPING

EL. 784'-6"

4-PLY BUILT-UP ROOFING SYSTEM OVER

1/2" FIBERBOARD OVER TAPERED ROOF

INSULATION AND 1-1/2" METAL ROOF

DECK

TOP OF PARAPET WALL

4" NOM. CANT

WALL GIRT

METAL PANEL

1-1/2" FLUSH EXTERIOR INSULATED

GALV. 1/2" SUBGIRT

METAL LINER PANEL

2" INTERIOR INSULATED

JOINT & SEALANT

CONC. SLAB

REINFORCED

2" x 24" EA. WAY

FDN. INSUL.

EXTRUDED POLYSTYRENE

LEDGE ANGLE

1/2" ISOLATION21 4"

6"

1"

1" 4"

10"

7"

11 2"

4 PLY BUILT-UP ROOFING SYSTEM OVER

1/2" FIBERBOARD OVER TAPERED

ROOF INSULATION AND 1-1/2" METAL

ROOF DECK

3-1/2"x3-1/2"x3/8"x4" CLIP

ANGLE CONNECTOR - ANCHOR

TO EACH VERTICAL MULLION

CLEAR ANODIZED ALUM.

FACIA, GRAVEL STOP

TO MATCH CURTAIN WALL

WOOD BLOCKING

ANCHOR SECURELY

8"x5"x3/8" CONT.

WELD TO BEAM

SEALANT

ALUM. CURTAIN

WALL FRAMING

SYSTEM w/ 1" INSUL.

SPANDREL GLASS

VERTICAL MULLION

21 4"

6"

1"

1" 4"

VERTICAL MULLION

1" INSUL. SPANDREL GLASS

21 4"

6"

1"

1"

4"

VERTICAL MULLION

1" INSUL. SPANDREL GLASS

8" 4"

1'-0"

FIN. FLOOR

EL. 748'-6"

SEALANT

BOTH SIDES

EXTERIOR CONC. SLAB

CONC. FOUNDATION WALL

INTERIOR CONC. SLAB

ALUM. CURTAIN

WALL FRAMING

SYSTEM w/ 1" INSUL.

SPANDREL GLASS

P.J.F.

4"6"2"

ALUM. CURTAIN

WALL FRAMING

SYSTEM w/ 1" INSUL.

SPANDREL GLASS

CURVED MASONRY WALL

ALUM. SILL BELOW

6" 4"

10"

ALUM. CURTAIN

WALL FRAMING

SYSTEM w/ 1" INSUL.

SPANDREL GLASS

11"11"

8" 51 2"

9" 7"

1" 11 2"

N O

M

C M

U

1' -4

ALUM. SILL BELOW

FACE OF CONC.

FOUNDATION BELOW

EXTERIOR INSUL.

METAL PANEL

8" CMU

CONTROL JOINT

8" 1"

N O

M

C M

U

2"

1'-0"

6" 1"

1' -4

1" WOOD BLOCKING

6"

21 4" 21 2"

D O

O R

O P

E N

IN

G

D O

O R

O P

E N

IN

G

STEEL REINFORCEMENT

AT VERTICAL MULLIONS

ADJACENT TO DOORS

11"11"

8"

N O

M

C M

U

8" CMU

STEEL COLUMN

1'-10"

2" 41

2"

4" 7"11

1' -5

1 4"

3' -0

4" CMU

CONTROL JOINT

STEEL COLUMN

CONTROL JOINT

ALUM. CURTAIN

WALL FRAMING

SYSTEM w/ 1" INSUL.

SPANDREL GLASS

FLUSH ALUM. DOOR

ALUM. CURTAIN

WALL FRAMING

SYSTEM w/ 1" INSUL.

SPANDREL GLASS

8"

N O

M

C M

U

STEEL COLUMN

1' -5

1 4"

2' -4

1 4"

A

ALUMINUM CURTAIN WALL 1-1/2"=1'-0"

HEAD/ROOF FASCIA

A-20

ALUMINUM CURTAIN WALL 1-1/2"=1'-0"

(HORIZONATL SIMILAR)

A-20

10"2"

ALUMINUM CURTAIN WALL 1-1/2"=1'-0"

SILL DETAIL

A-20

ALUMINUM CURTAIN WALL 1-1/2"=1'-0"

DOOR TRANSOM

A-20

ALUMINUM CURTAIN WALL 1-1/2"=1'-0"

DOOR JAMB

A-20

A

B

ALUMINUM CURTAIN WALL 1-1/2"=1'-0"

METAL WALL PANELS

A-12

SIDE JAMB AT

ALUMINUM CURTAIN WALL 1-1/2"=1'-0"

SIDE JAMB @ MASONRY WALL

A-20

TYP. AT FOUR LOCATIONS 1-1/2"=1'-0"

MASONRY AT STEEL COLUMN

A-12

B

1-1/2"=1'-0"

METAL WALL PANELS

A-12

MASONRY EXPANSION JT. AT

A 1 B 5

1'-0" 4" 2"

1' -0

SECTION

PARAPET 1-1/2"=1'-0" A-19

A

A 1 B

4"1'-0" 1"

11"

DETAIL

WALL SILL 1-1/2"=1'-0" A-20

TYP.11

DETAIL

WALL SILL 3"=1'-0" -

4" 2"

3"

1' -0

DETAIL

COPING 3"=1'-0" -

SECTION

OVERFLOW OPENING 1-1/2"=1'-0" A-14

C

GALVANIZED 18 GA.

GRAVEL STOP 3" HIGH

4-PLY BUILT-UP ROOFING

SYSTEM OVER 1/2"

FIBERBOARD OVER

TAPERED INSULATION AND

1-1/2" METAL ROOF DECK

2' -0

CANT

GRAVEL

6"

TRIM FASTEN TO WALL

18 GA. GALV. & PAINTED STL.

STL. PLATE

SEALANT

3"x12" WIDE

PRE-FINISHED 18 GA.

GALV. FASCIA COPING.

COLOR TO MATCH WALL

PANELS

4" 2"1'-0"

WALL GIRT

EL. 782'-6"

TOP / STEEL

EL. 784'-6"

TOP / FASCIA COPING

EL. 783'-6"

BOT / FASCIA COPING

20 GA. CAP FLASHING B

OVERFLOW OPENING

3" 3"

& A-20

18 GA. GALV. &

PAINTED TRIM EJ

MASONRY TIES -

HECKMAN #325 & #326

GROUT

WOOD BLOCKING

NOTE: SECTION B ON THIS

SHEET DELETED.

MASONRY TIES - COL. 5

ONLY - HECKMAN #325 & #326

VARIES

8" TO 12"

SEE STRUCT.

A-19

STEEL FRAMING -

SEE STRUCT.

A-18 A-14

STEEL BEAMS -

SEE STRUCTURAL

8" 1'

-3

1' -1

1"

N O

M

C M

U

3 1/2" BATT INSUL.

18 GA. ALUM. INTERIOR

FACE SHEET TO MATCH

CURTAIN WALL

1" INSUL. PANEL FITTED INTO

CURTAIN WALL WITH 18 GA.

ALUM. EXTERIOR FACE SHEET

TO MATCH CURTAIN WALL

2"X4" WOOD STUDS CONT. VERTICALLY

W/ 2"X4" WOOD BLOCKING @ 16" O.C.

HORIZONTALLY - SECURE TO MASONRY

AND CURTAIN WALL.

3"x2" ALUM. CLOSURE ANGLE.

MATCH FRAME- W/ SEALANT

3 1/2 "x2" ALUM. CLOSURE

ANGLE. MATCH FRAME-

W/ SEALANT

5 8"

2"x2" ALUM.

CLOSURE ANGLE

2"x2" ALUM.

CLOSURE ANGLE

5 1/2" BATT INSUL.

S

P A

C E

S

'-1

'-5

/4

S

P A

C E

S

'-1

'-5

/4

5 8"

CL MULLION

CL MULLION

END OF CMU

@ COL. 4

1" 4"

EXTERIOR INSULATED

METAL WALL PANEL

METAL LINER PANEL

INTERIOR INSULATED

CONTINUOUS L5"x3"x1/4"

EXP.

ANCHOR

1"

2" INSIDE NEOPRENE CLOSURE

APPROX. GRADE

1"

SEALANT

SET IN CONT. BEAD

OF SEALANT

NOTE: DETAILS OF LOUVERS IN

CURTAIN WALL SIM. TO DETAILS

ON SHEET A-16

PLAN AT VERT. MULLION

CMU

CMU

FACE BRICK

NOTE:

FILLER PANEL MATERIALS IN

THIS AREA SAME AS FILLER

PANEL IN DETAIL 7 BELOW.

1' -0

CONT. 4"x3"x1

4" LLH

GALV. STEEL ANGLE

GROUT

SEALANT AND

BACKER ROD

2" Ø x 3 12"

MIN. EMB.

@ 18" O.C.

8" 1 - 18

AURORA, ILLINOIS

60504

SUITE 107

(630) 820-0350 FAX

(630) 820-1022

CRAWFORD, MURPHY & TILLY, INC.

CONSULTING ENGINEERS

600 NORTH COMMONS DRIVE

1 1/2"=1'-0"

SCALE FEET

1 0 1

3"=1'-0"

SCALE FEET

SCALE:

1-16-02

1-16-02

1-16-02

J. SIMS

E. CRUMPLEY

D. NEVIN

1-16-02R. PLUNKETT, D. BOGERT 1-16-02B. HELD

1-16-02M. WAGNER

1-16-02R. MURPHY

1-16-02P. O'SHEA

A

U G

, 2

MSB DETAILS, SHEET 1

A-236-7-5

NuMI SERVICE BUILDINGS

PROVIDE DIELECTRIC SEPARATION AT DISSIMILAR MATERIALS.NOTE:

B

A

T.O.C.

748'-6" OR

747'-10"

3/16"=1'-0" 2 0 10 146

SCALE FEET

2 4 8 12

FLOOR SLAB PLAN

FOUNDATION AND

3/16" = 1'-0"

B

SC-8

C

SC-10

E

SC-7

A

SC-8

J

SC

-9

1"=1'-0"

SCALE FEET

SC-8

F

SCALE:

1-16-02

1-16-02

1-16-02

J. SIMS

E. CRUMPLEY

D. NEVIN

1-16-02R. PLUNKETT, D. BOGERT1-16-02B. HELD

1-16-02M. WAGNER

1-16-02K. McCOY

1-16-02J. FICKBOHM

A U

G

MSB FOUNDATION PLAN AND SCHEDULE

SC-66-7-5

NuMI SERVICE BUILDINGS

G

SC-8

SC-7

H

SC-8

C

600 NORTH COMMONS DRIVE

CONSULTING ENGINEERS

CRAWFORD, MURPHY & TILLY, INC.

(630) 820-1022

(630) 820-0350 FAX

SUITE 107

60504

AURORA, ILLINOIS

SECTION

3/4" = 1'-0" -

D

D

C

DETAIL

3/8" = 1'-0" -

TYPICAL SUBGRADE DETAIL

1" = 1'-0"

8"

748'-6" T.O.C.

1 1/2" CL.

B11"

2' -0

T.O.C.

747'-11 1/2"

SEALANT

1/2" PJF &

MIN.

2'-0"

1" 8"

3' -2

/2

(SEE SLAB PLAN ON SHT. SC-6)

4'-0"

6"

6" COMPACTED CA-6 98%

STD. PROCTOR DENSITY

ON TOP OF CRUSHED

ROCK SITE FILL.

VAPOR BARRIER

6 MIL POLYETHYLENE

2" RIGID

INSULATION

#5 BENT @ 12"

(2'-0" X 3'-0")

(TYP. 3 SIDES)

6" FROST WALL

#5 BENT

@ 12"

#5 @ 12"

CONT.

3"CL.

#5 @ 12"

CONT.

#5 @ 12" W/STD.

90° HOOK

(ALT. HOOKS)

LOW POINT

EL. 747'-10 1/2"

1/2"

6X6-W6XW6

(FLAT SHEETS ONLY)

WELDED WIRE FABRIC

8" 6"6"

1'-8"

2-#5@12"

(2 FROST WALLS THUS)

WALL W/STD. 90° HOOK

INTO FOUNDATION

3-#5 DOWELS

5"

2" CL.

1'-4"

SECTION

3/4" = 1'-0" -

A

PLAN - TYPE I FOOTING

3/4" = 1'-0"

A

B

PLAN - TYPE II FOOTING

3/4" = 1'-0"

SECTION

3/4" = 1'-0" -

B

SECTION

3/4" = 1'-0" -

C

PLAN - TYPE III FOOTING

3/4" = 1'-0"

C

3/4"=1'-0" 1 0 2 31

SCALE FEET

SECTION

3/4" = 1'-0" SC-6

E

SECTION

1" = 1'-0" SC-6

H

SCALE:

600 NORTH COMMONS DRIVE

CONSULTING ENGINEERS

CRAWFORD, MURPHY & TILLY, INC.

(630) 820-1022

(630) 820-0350 FAX

SUITE 107

60504

AURORA, ILLINOIS

1-16-02

1-16-02

1-16-02

J. SIMS

E. CRUMPLEY

D. NEVIN

1-16-02R. PLUNKETT, D. BOGERT 1-16-02B. HELD

1-16-02M. WAGNER

1-16-02K. McCOY

1-16-02J. FICKBOHM

A U

G

MSB FOUNDATION DETAILS, SHEET 1

SC-76-7-5

NuMI SERVICE BUILDINGS1"=1'-0"

SECTION

1"=1'-0" -

B

B

B

G

DETAIL

1"=1'-0" -

SECTION

1"=1'-0" -

G

B

A

B

2 3 4 5

A

LOCATION

FRAMING PLAN AT EL. 782'-6"

3/16" = 1'-0"

3/16"=1'-0" 2 0 10 146

SCALE FEET

2 4 8 12

FRAMING PLAN AT EL. 766'-6"

3/16" = 1'-0"

FRAMING PLAN AT EL. 772'-6"

3/16" = 1'-0"

J

SS-11

D

SS-9

SS-7

E

SS-9

B

C

SS-9

LOCATION 2

LOCATION 3

KEY PLAN

N.T.S.

1"=1'-0"

SCALE FEET

B

A

SS-11

SS-11

C

SS-9

SS-9

A

F

SS-7

SCALE:

1-16-02

1-16-02

1-16-02

J. SIMS

E. CRUMPLEY

D. NEVIN

1-16-02R. PLUNKETT, D. BOGART1-16-02B. HELD

1-16-02M. WAGNER

1-16-02K. McCOY

1-16-02J. FICKBOHM

A U

G

MSB ROOF FRAMING PLANS

SS-86-7-5

NuMI SERVICE BUILDINGS

600 NORTH COMMONS DRIVE

CONSULTING ENGINEERS

CRAWFORD, MURPHY & TILLY, INC.

(630) 820-1022

(630) 820-0350 FAX

SUITE 107

60504

AURORA, ILLINOIS

1/4"=1'-0" 4 0 4 8

SCALE FEET

FRAMING PLAN AT EL. 778'-0"

3/16" = 1'-0"

CURVED WALL AT ROOF

STUD LAYOUT PLAN

3/16" = 1'-0"

LOCATION

5LOCATION

B

B

SS-10

SS-10

SS-10

SS-10

G

SS-7

1/8"=1'-0" 8 0 8 16

SCALE FEET

FRAMING ELEVATION ALONG COLUMN LINE

1/8" = 1'-0"

B

FRAMING ELEVATION ALONG COLUMN LINE

1/8" = 1'-0"

FRAMING ELEVATION ALONG COLUMN LINE

1/8" = 1'-0"

SS-11

SS-11

SS-11

SS-11

SS-11

FRAMING ELEVATION ALONG COLUMN LINE

1/8" = 1'-0"

A

SECTION

1" = 1'-0" SS-8

D SECTION

1" = 1'-0" SS-8

A SECTION

1" = 1'-0" SS-8

B

SS-11

SS-11

SS-11

SECTION

1" = 1'-0" SS-8

C

SCALE:

1-16-02

1-16-02

1-16-02

J. SIMS

E. CRUMPLEY

D. NEVIN

1-16-02R. PLUNKETT, D. BOGERT1-16-02B. HELD

1-16-02M. WAGNER

1-16-02K. McCOY

1-16-02J. FICKBOHM

A U

G

MSB FRAMING ELEVATIONS

SS-96-7-5

NuMI SERVICE BUILDINGS

600 NORTH COMMONS DRIVE

CONSULTING ENGINEERS

CRAWFORD, MURPHY & TILLY, INC.

(630) 820-1022

(630) 820-0350 FAX

SUITE 107

60504

AURORA, ILLINOIS

1/4"=1'-0" 4 0 4 8

SCALE FEET

SS-11

F

SS-11

A12-6-7-5 Layout1 (1)
A17-6-7-5 Layout1 (1)
A18-6-7-5 Layout1 (1)
A19-6-7-5 Layout1 (1)
A23-6-7-5 Layout1 (1)
SC06-6-7-5 Layout1 (1)
SC07-6-7-5 Layout1 (1)
SS08-6-7-5 Layout1 (1)
SS09-6-7-5 Layout1 (1)

File details come from the government source that posted it. Updated .