Western Upper Peninsula Shooting Facility - Addendum No. 3

This is a Construction Bid Addendum issued by the Michigan Department of Technology, Management and Budget (DTMB), State Facilities Administration Design and Construction Division for the Western Upper Peninsula Shooting Facility project (File Number 751/17172.JBB). The addendum modifies bidding documents for a shooting range facility and was issued on March 26, 2021, with a revised bid opening date of April 28, 2021 at 2:00 PM. The professional is NFE Engineers, with Jeff Barsch serving as Project Director. Key modifications include an extension of the bid due date to accommodate supplier and sub-contractor pricing delays, the addition of Specification Section 017900 Demonstration and Training, revisions to Section 116723 Shooting Range Equipment (including modified specifications for the Pilot target retriever system manufactured by Action Target Inc., with specifications for ballistic stalls, bullet traps, range control systems, safety baffles, and related equipment), structural clarifications to foundation requirements eliminating certain reinforcing steel from multiple footing locations, and approval of a metal panel substitution (Petersen Aluminum Tite-Loc Plus Standing Seam Panel replacing the specified ATAS 2" Field-Lok aluminum panel). The demonstration and training requirements mandate contractor-provided instruction for Owner personnel covering system operation, maintenance procedures, and equipment-specific training delivered on-site using actual equipment, with submission of training video recordings and comprehensive operation and maintenance manuals.

The shooting range equipment specifications establish strict ballistic performance requirements based on Action Target Inc. standards (ATI Class 2 for rifle ammunition), with the Pilot target retriever system featuring wireless capabilities, integrated cameras, strike watch shot detection technology, and integration with the SmartRange Axis Range Control System for centralized management of multiple lanes. Equipment suppliers must demonstrate minimum ten years of documented experience in manufacturing specified products, with equipment installers required to possess minimum five years of documented experience on similar projects. A three-year manufacturer's warranty covers the rubber berm trap, ballistic stalls, target system, retriever, and baffles/deflectors. The metal roof panel substitution request from Petersen Aluminum Corporation offers a .042-inch thick aluminum panel (18 inches wide with 1-3/4 inch high seams) with equivalent or superior performance ratings including UL classifications (UL-1887 wind uplift, UL-580 Class 90, UL-790 Class A, UL-2218 Impact Resistant) and a 20-year manufacturer's finish warranty, meeting or exceeding the original specification requirements.

View the file

Other files

File Type Posted
Range Equipment - 2.pdf PDF
Addendum No. 1.pdf PDF
Civil Plans.pdf PDF
Range Equipment - 1.pdf PDF
Architectural Plans.pdf PDF
Addendum No. 4.pdf PDF
Addendum No. 2.pdf PDF
Civil Updates.pdf PDF
Advertisement.pdf PDF
J942 Photos with Captions.pdf PDF
Specifications.pdf PDF
Addendum 5 17172.pdf PDF
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DTMB-0414 (Rev 12/17)

DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET

State Facilities Administration Design and Construction Division

CONSTRUCTION BID ADDENDUM NO. 3

This form identifies an Addendum to Bidding Documents, and incorporates interpretations or clarifications, modifications, acceptance of proposed “or equal” materials, and other information into the Bidding Documents. Addenda will be numbered by the Professional and distributed through www.michigan.gov/SIGMAVSS as an attachment.

TO:

ALL BIDDERS

DATE ISSUED

3/26/2021

PROJECT NAME

Western Upper Peninsula Shooting Facility

FILE NUMBER

751/17172.JBB

PROFESSIONAL

NFE Engineers

PROJECT DIRECTOR

Jeff Barsch

BID OPENING DATE:

4/28/2021

ADDENDUM ITEMS: (attach additional sheets and drawings if required)

1. Due to issues brought forward by bidders relative to delays in receiving supplier / sub-contractor pricing, the bid due date is being extended to April 28th at 2:00pm.

2. Added specification Section 017900 Demonstration and Training.

3. Revised Section 116723 Shooting Range Equipment – Refer to attached specification for items in BOLD added or crossed out removed.

4. Drawing SB101 – footing schedule – Row labeled “Steel Top”; top layer of reinforcing is not required in any footings. Remove #5 from all columns.

5. Drawing S-003 Detail #1 and Drawing SB101 Foundation schedule clarification: Foundation walls only require one layer of reinforcement centered within the wall per schedule on SB101.

6. Substitution Requests during Bidding Phase: Substitution Request 1 – Metal Panels – Approved, see attached.

ACKNOWLEDGEMENT: This Addendum must be acknowledged by the Bidder in the space provided in the Bid Summary and Bid Form. Failing to acknowledge Addenda may be cause for the Bid to be rejected. Addenda will become part of the Contract Documents.

Steve Sutton

PROFESSIONAL: DATE: 3/31/2021

APPROVED BY:

PROJECT DIRECTOR: Jeff Barsch DATE: 3/31/2021

OHM Advisors - 2021 Western Peninsula Shooting Fa-cility

751_17172.JBB

01 79 00 - 1

SECTION 01 79 00 - DEMONSTRATION AND TRAINING

PART 1 - GENERAL

1.1 SUMMARY

A. Section includes administrative and procedural requirements for instructing Owner's personnel, including the following:

1. Demonstration of operation of systems, subsystems, and equipment.

2. Training in operation and maintenance of systems, subsystems, and equipment.

3. Demonstration and training video recordings.

1.2 INFORMATIONAL SUBMITTALS

A. Instruction Program: Submit outline of instructional program for demonstration and training, including a list of training modules and a schedule of proposed dates, times, length of instruction time, and instructors' names for each training module. Include learning objective and outline for each training module.

1. Indicate proposed training modules using manufacturer-produced demonstration and training video recordings for systems, equipment, and products in lieu of video recording of live instructional module.

1.3 CLOSEOUT SUBMITTALS

A. Demonstration and Training Video Recordings: Submit two copies on flash drives within seven days of end of each training module.

B. At completion of training, submit complete training manual(s) for Owner's use prepared and bound in format matching operation and maintenance manuals and in PDF electronic file format on compact disc.

1.4 QUALITY ASSURANCE

A. Facilitator Qualifications: A firm or individual experienced in training or educating maintenance personnel in a training program similar in content and extent to that indicated for this Project, and whose work has resulted in training or education with a record of successful learning performance.

B. Instructor Qualifications: A factory-authorized service representative, complying with requirements in Section 01 40 00 "Quality Requirements," experienced in operation and maintenance procedures and training.

C. Preinstruction Conference: Conduct conference at Project site to comply with requirements in Section 01 31 00 "Project Management and Coordination." Review methods and procedures related to demonstration and training.

1.5 COORDINATION

A. Coordinate instruction schedule with Owner's operations. Adjust schedule as required to minimize disrupting Owner's operations and to ensure availability of Owner's personnel.

B. Coordinate content of training modules with content of approved emergency, operation, and maintenance manuals. Do not submit instruction program until operation and maintenance data has been reviewed and approved by Engineer.

01 79 00 - 2

PART 2 - PRODUCTS

2.1 INSTRUCTION PROGRAM

A. Program Structure: Develop an instruction program that includes individual training modules for each system and for equipment not part of a system, as required by individual Specification Sections.

B. Training Modules: Develop a learning objective and teaching outline for each module. Include a description of specific skills and knowledge that participant is expected to master. For each module, include instruction for the following as applicable to the system, equipment, or component:

1. Basis of System Design, Operational Requirements, and Criteria: Include the following:

a. System, subsystem, and equipment descriptions.

b. Performance and design criteria if Contractor is delegated design responsibility.

c. Operating standards.

d. Regulatory requirements.

e. Equipment function.

f. Operating characteristics.

g. Limiting conditions.

h. Performance curves.

2. Documentation: Review the following items in detail:

a. Emergency manuals.

b. Operations manuals.

c. Maintenance manuals.

d. Project record documents.

e. Identification systems.

f. Warranties and bonds.

g. Maintenance service agreements and similar continuing commitments.

3. Emergencies: Include the following, as applicable:

a. Instructions on meaning of warnings, trouble indications, and error messages.

b. Instructions on stopping.

c. Shutdown instructions for each type of emergency.

d. Operating instructions for conditions outside of normal operating limits.

e. Sequences for electric or electronic systems.

f. Special operating instructions and procedures.

4. Operations: Include the following, as applicable:

a. Startup procedures.

b. Equipment or system break-in procedures.

c. Routine and normal operating instructions.

d. Regulation and control procedures.

e. Control sequences.

f. Safety procedures.

g. Instructions on stopping.

h. Normal shutdown instructions.

i. Operating procedures for emergencies.

j. Operating procedures for system, subsystem, or equipment failure.

k. Seasonal and weekend operating instructions.

l. Required sequences for electric or electronic systems.

m. Special operating instructions and procedures.

5. Adjustments: Include the following:

a. Alignments.

b. Checking adjustments.

c. Noise and vibration adjustments.

d. Economy and efficiency adjustments.

01 79 00 - 3

6. Troubleshooting: Include the following:

a. Diagnostic instructions.

b. Test and inspection procedures.

7. Maintenance: Include the following:

a. Inspection procedures.

b. Types of cleaning agents to be used and methods of cleaning.

c. List of cleaning agents and methods of cleaning detrimental to product.

d. Procedures for routine cleaning

e. Procedures for preventive maintenance.

f. Procedures for routine maintenance.

g. Instruction on use of special tools.

8. Repairs: Include the following:

a. Diagnosis instructions.

b. Repair instructions.

c. Disassembly; component removal, repair, and replacement; and reassembly instructions.

d. Instructions for identifying parts and components.

e. Review of spare parts needed for operation and maintenance.

PART 3 - EXECUTION

3.1 PREPARATION

A. Assemble educational materials necessary for instruction, including documentation and training module. Assemble training modules into a training manual organized in coordination with requirements in Section 01 78 23 "Operation and Maintenance Data."

3.2 INSTRUCTION

A. Facilitator: Engage a qualified facilitator to prepare instruction program and training modules, to coordinate instructors, and to coordinate between Contractor and Owner for number of participants, instruction times, and location.

B. Engage qualified instructors to instruct Owner's personnel to adjust, operate, and maintain systems, subsystems, and equipment not part of a system.

1. Engineer will furnish an instructor to describe basis of system design, operational requirements, criteria, and regulatory requirements.

2. Owner will furnish Contractor with names and positions of participants.

C. Scheduling: Provide instruction at mutually agreed on times. For equipment that requires seasonal operation, provide similar instruction at start of each season.

1. Schedule training with Owner, through Engineer, with at least seven days' advance notice.

D. Training Location and Reference Material: Conduct training on-site in the completed and fully operational facility using the actual equipment in-place. Conduct training using final operation and maintenance data submittals.

3.3 DEMONSTRATION AND TRAINING VIDEO RECORDINGS

A. General: Engage a qualified commercial videographer to record demonstration and training video recordings. Record each training module separately. Include classroom instructions and demonstrations, board diagrams, and other visual aids, but not student practice.

1. At beginning of each training module, record each chart containing learning objective and lesson outline.

01 79 00 - 4

B. Video Recording Format: Provide high-quality color video recordings with menu navigation in format acceptable to Engineer.

END OF SECTION 01 79 00

116723 - 1

SECTION 116723 - SHOOTING RANGE EQUIPMENT

PART 1 - GENERAL

1.1 SECTION INCLUDES

A. Shooting range equipment including the following:

1. Bullet traps and collection.

2. Shooting stalls.

3. Target systems.

4. Target retrievers.

5. Range Control Systems.

6. Safety baffles and ballistic barriers.

1.2 REFERENCES

A. Action Target Ballistic Rating:

1. ATI Class 1 (Handgun).

a. Ammunition with velocities up to 1,485 fps and energy up to 1,175 ft/lbs.

2. ATI Class 2 (Rifle).

a. Ammunition with velocities up to 3,388 fps and energy up to 3,600 ft/lbs.

b. No armor-piercing or enhanced penetration rounds.

B. Conveyor Equipment Manufacturers Association (CEMA).

C. European Committee for Standardization (EN):

1. EN 1063 - Ballistic Standard.

D. National Institute of Occupational Safety and Health (NIOSH):

1. NIOSH 76-130 - Lead Exposure and Design Considerations for Indoor Firing Ranges.

E. Sheet Metal and Air Conditioning Contractors' National Association (SMACNA).

F. Society for Protective Coatings (SSPC):

1. SSPC-SP6 - Commercial Blast Cleaning.

G. U.S. Environmental Protection Agency (EPA):

1. EPA 40 CFR 50.12 - National Primary and Secondary Ambient Air Quality Standards for

Lead.

H. US Department of Transportation (DOT).

116723 - 2

I. Underwriters Laboratories (UL):

1. UL 94 HB - Horizontal Burning.

2. UL 752 - Ratings of Bullet Resistant Materials.

1.3 SUBMITTALS

A. Product Data:

1. Manufacturer's data sheets on each product to be used.

2. Preparation instructions and recommendations.

3. Storage and handling requirements and recommendations.

B. Shop Drawings:

1. Include plans, elevations, sections and full size details showing connections or attachments to other work.

2. Include wire diagrames

3. Provide load diagrams and connection points to other structural elements

C. Delegated-Design Submittal: For baffle and rubber berm support systems, provide drawings indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.

1.4 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: Submit operation and maintenance manuals for items included under this Section.

B. Documentation shall be specific to the project and collated in functional sections. Each section shall combine to form a complete system manual covering all aspects of equipment supplied by manufacturer. Instructions shall include the following as a minimum:

1. Functional descriptions of each major component complete with operating and maintenance instructions.

2. Step by step instructions on setup, configuration, and updating of control systems.

C. Operations and maintenance instructions, which rely on manufacturer cut sheets, and literature, which include general configurations, or require personnel to selectively read portions of the manual, shall not be acceptable. Operation and maintenance instructions must be specific to equipment supplied in accordance with these specifications.

D. Field Installation report.

E. Software and Firmware Operational Documentation:

1. Software operating and upgrade manuals.

116723 - 3

2. Program Software Backup.

3. Wiring diagrams for control systems

4. Printout of software application and graphic screens.

1.5 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacturing products specified in this section with a minimum 10 years documented experience.

B. Equipment Installer Qualifications: Company specializing in performing Work of this section.

Minimum five years documented experience with projects of similar scope and complexity.

1. Range Ventilation Installer: Contractor experienced in design, construction, testing, commissioning, and operation of indoor shooting range ventilation systems.

C. Source Limitations: Provide each product type from single manufacturer ensuring uniformity.

1.6 SEQUENCING

A. Supply products to affected trades in time to prevent interruption of construction progress.

1.7 WARRANTY

A. Special Manufacturer's Warranty: Manufacturer warrants products to be free from manufacturing defects and shall cover parts and labor for a period of three (3) year for the following:

1. Rubber Berm Trap

2. Ballistic Stalls

3. Target System

4. Retriever

5. Baffles and deflectors

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Basis of Design (Product Standard): Contract Documents are based on products and systems specified to establish a standard of quality. Other manufacturers offering products having equivalent characteristics may be considered, provided deviations are minor and comply with requirements of Contract Documents as judged by the Architect.

1. Action Target Inc., Email:request info (salessec@actiontarget.com);

Web:http://www.actiontarget.com

116723 - 4

2.2 BULLET TRAPS AND COLLECTION

A. Basis of Design: Structural Rubber Berm Trap; as manufactured by Action Target Inc.

1. Performance Requirements:

a. Ballistic Rating: ATI Class 2 (Rifle). Shotguns using ammunition 00 Buckshot.

b. Comply with structural requirements; wind, seismic, and snow loads.

1) Deck Plate: Secure to framework with Grade 5 nuts and bolts in horizontal and vertical directions.

2) Toe of Deck Plate: Anchors to concrete floor creating a structural diaphragm.

3) Structural strap.

2. Angle: Maximum 30 degrees from horizontal.

3. Width per Foot (Meter): as indicated on Drawings.

4. Media Depth: Perpendicular deck plane, 24 inches (610 mm); horizontal shooting depth, 48 inches (1219 mm).

5. Frame: Galvanized steel with interlocking and bolted connections.

6. Retaining Base: Galvanized steel with proprietary fin system to retain rubber layer.

a. Fins eliminate need for a continuous top-fill device.

7. Height: 8 feet (2438 mm). Mining Requirements: After 80,000 rounds per lane.

8. Media: Standard chopped rubber, 0.75 in (19 mm) average size, pure SBR, 99.9 percent free of loose wire and exposed steel.

9. Deck Plate: 1/4 inch (6.4 mm) A36 steel.

10. Back Plate: 10 gauge galvanized A36 steel, 26.5 inches (673 mm) tall.

11. Configuration: Wall supported.

12. Sidewall Protection: 1/4 inch (6.4 mm) thick A36 steel.

13. Eyebrow Protection: 10 gauge (3.6 mm) galvanized steel.

a. Size: 24 inch (610 mm).

14. Fire Protection: ASTM E108, Class A.

a. Shall adhere to chopped rubber granules.

b. Fire protectant media shall not contain absorbent materials.

c. Shall not require water application to maintain fire rating.

15. Back Plate Fascia: Replaceable 1-1/2 inch (38 mm) thick SBR panel.

a. Composite recycled vulcanized rubber with a urethane binder.

2.3 SHOOTING STALLS

A. Basis of Design: Guardsman Stall; as manufactured by Action Target Inc.

1. Performance Requirements:

a. Ammunition Rating: ATI Class 2 (Rifle).

1) Complies with UL 752 standards for Levels 5, 6, 7, 8, 9, and 10.

2) Independently tested to validate ballistic standards.

2. A physical privacy barrier between shooters to protect against accidental discharge. Serves as physical mounting for target retriever controls.

3. Steel Frame: Anchors to concrete; for mounting steel ballistic panels.

4. Panels: Combination of wood, steel, and ABS, with stainless steel trim.

a. Dimensions (WxHxD): 3 x 84 x 36 inches (76 x 2134 x 914 mm).

5. Wire Channel: Wiring routed within the stall wall through an integrated wire channel.

6. Table Configurations: Pivot table.

116723 - 5

7. Table Widths: 30 to 54 inches (762 to 1372 mm) in 6 inch (152 mm) increments.

2.4 TARGET RETRIEVERS

A. Basis of Design: Pilot; as manufactured by Action Target Inc.

1. Maximum Length: 100 meters (328 feet).

2. Maximum Speed: 7 to 12 fps (7.7 to 13 kph).

3. Carrier:

a. Deflector Plate: 3/8 inch (9.5 mm) AR500 steel.

b. Side Housings: 11 gauge, 0.1196 inch (3.038 mm) thick steel.

c. Weight: 111 pounds (50.3 kg).

d. Wireless Capabilities: Dual band compliant with 802.11 a/b/g/n/ac standards.

e. Stabilizer Wheels: 6 internal stabilizing wheels.

f. Home position shall be modifiable.

g. Positioning Accuracy: Plus or minus 1 inch (25 mm).

h. Includes 1 direct drive brushless drive motor.

i. Carrier Target Lighting:

1) User dimmable white light.

2) Muzzle blast strobe simulates return gun fire.

3) 3 Strobe patterns of red, blue, and white.

4) White Lighting: 40 fc of light at the center of target.

j. Includes strike watch technology to detect if carrier is shot. If carrier is shot, the following occurs:

1) Warning Message appears on local control.

2) Targets lights strobe red, visually notifying the shooter.

3) If shot exceeds allowable limit set in master control, the target comes home, the session is terminated, and a warning message appears on SmartRange

Axis Control System.

4) Detect shots from .22LR calibers and up.

5) Does not detect false positives from muzzle concussion.

k. Integrated Camera: Views and displays target in real time from anywhere on track on local control screen.

l. Clamp: Recessed into housing and hidden from shooter's view.

1) No leading edges or exposed hardware that could be shot.

2) Operable with one hand.

3) Designed to hold cardboard or plastic backers.

4. Track End Cap: Steel with powder coating. Includes lane numbers on rear of housing.

5. Track:

a. Material: 11-gauge (0.1196 inch, 3.038 mm thick) steel.

b. Weight: 11.66 pounds per foot (5.29 kg per 304.8 mm).

c. Standard Track Section Length: 6 feet (1829 mm).

d. Down range portion of track shall be free of bus bars, cables, and tensioners.

e. Dead stops on both ends contain gas/oil dampers housed in steel structure and capable of stopping a 111 lbs (50.3 kg) carrier traveling 20 fps (6.1 m per sec).

f. Earth-grounded.

g. Requires removing a maximum 12 bolts to replace a track section.

1) Does not require removing or adjusting adjacent track sections to remove a track section.

116723 - 6

h. Track has a flat base that directs all rounds down range towards the bullet trap.

i. Track shall be supported by zinc-coated steel hanger brackets.

6. Local Control Screen User Interface:

a. Size: 10 inch (254 mm), 1280 x 800 resolution.

b. Abrasive resistant glass touch screen.

c. Power over Ethernet (PoE) powered.

d. Displays remaining lane time via SmartRange Axis Lane Management.

e. Three levels of screen brightness to allow for low-light training.

f. Integrated help button interfaces with SmartRange Axis control screen. When pressed:

1) Target lights on carrier will strobe blue.

2) Range staff are notified of required assistance via range's SmartRange Axis control screen.

g. Displays and requires acknowledgement of range rules before a session starts.

7. SmartRange Axis Range Control System Integration: Integrates with SmartRange Axis

Control system.

8. No cables or wires to be exposed to direct or indirect projectile hits.

9. Target Rotator

2.5 RANGE CONTROL SYSTEMS

A. SmartRange Axis Range Control System:

1. Basis of Design: Range Control System as designed by Action Target Inc.

2. Description: Centralized control of Pilot Target Retrievers.

3. Connects with Action Target's cloud network for software and content updates, remote troubleshooting, and technical assistance.

4. Admin Management: Allowing unlimited users with unique logins.

5. Allows customized range rules, range name, bay and lane numbering.

6. Allows custom user groups to be defined that control the following features (if enabled) during a lane session:

a. Available programs.

b. Lighting control access.

c. Access to turning features of equipment (e.g. programs and time drills).

7. Allows custom programs to be created and organized among custom folders in a program management directory.

8. System Components consists of:

a. Centralized server.

1) Ethernet Communication; TCP/IP.

2) 128GB SSD Hard Drive Minimum.

3) 8GB Ram Minimum.

4) Fanless.

5) Intel X86 Processor.

6) 187mm Long x 155mm Wide x 52mm Tall.

7) Able to Communicate to Action Target Cloud Services for Remote Updates and Diagnostics.

b. Power over ethernet (PoE) Switch.

1) 48 port minimum. 500 W PoE sourcing capacity minimum.

2) Serve up to 15 Lanes per switch.

116723 - 7

3) Switch Size: 1U. 2 switches per 8U rack; 30 lanes per 8U rack.

c. Patch Panel: 2U panel size. 48 port Minimum. Cat6 certified.

d. Server Rack: 8U. 30 lanes per 8U rack. Add additional 8U rack per 30 lanes.

1) Integrated shelf for server.

2) Power supply unit for powering rack.

e. Power Requirements: Isolated ground 120V 20A dedicated receptacle.

f. User Interface Configuration: 15 inch (381 mm) multi-touch display. 1920 x 1080 resolution.

1) Dimensions: 15.2 x 9.8 x 1.5 inches (387 x 249 x 39 mm).

2) Ram: 2GB minimum.

3) Processor: N3160 quad-core.

4) PoE Powered (no internal battery).

5) Storage: 128 GB minimum.

6) Up to 3 per range max.

g. Display Mounting Configuration: Wall.

h. User Interface Configuration: Portable tablet. 10.5 in (267 mm) multi-touch display with 1920 x 1200 WUXGA resolution.

1) Dimensions: 10.25 x 6.34 x 0.31 inches (260 x 161 x 8 mm)

2) Ram 3 GB Minimum.

3) Battery: 7,300 mAh Minimum.

4) Storage 32 GB Minimum.

5) Processor 1.8 GHz Minimum.

6) Unlimited quantity per range.

9. Pilot Control System Integration:

a. Includes lane management for assigning lane time.

1) Ability to enter customers name and display it on the local control screen.

2) Set time-out limits for lane use; carriers return home and session ends.

3) Assign unique permissions to shooter's equipment.

b. Allows a cease fire causing targets to edge and screens to display cease fire message.

c. Offers full functionality of retrievers, including lighting and distance selection.

d. Displays all connected retrievers.

e. Allows full control of one or many lanes, including:

1) Synchronized program execution across one or multiple lanes

2) Target Lighting control across one or multiple lanes.

2.6 SAFETY BAFFLES AND BALLISTIC BARRIERS

A. Basis of Design: Modular Ceiling Baffles; as manufactured by Action Target Inc. Interconnected baffles attached to building structure.

1. Metal Z-purlin for splatter protection attachment provides air gap to increase splatter protection material life.

2. Depth: 48 inch (1219 mm) minimum to 144 inch (3658 mm) maximum.

3. Configuration: Fixed firing position.

4. Ballistic Rating: ATI Class 2 (Rifle). 3/8 inch (9.5 mm) thick AR500 steel panels.

5. Connection type: Flexible cable hangers.

6. Wall Attachment: Concrete or filled CMU block wall.

7. Splatter Protection: CDX plywood - unpainted.

8. Acoustic Tile: 1 inch (25 mm) White PEPP.

116723 - 8

a. Performance requirements:

1) Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency. Flame-Spread Index: Class A according to

ASTM E1264.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Do not begin installation until substrates have been properly constructed and prepared.

B. If substrate preparation is the responsibility of another installer, notify Architect in writing of unsatisfactory preparation before proceeding.

C. Install equipment as indicated, in accordance with manufacturer's written instruction, and in compliance with recognized industry practices to ensure that products fulfill requirements.

3.2 INSTALLATION

A. Install in accordance with manufacturer's instructions, approved submittals and in proper relationship with adjacent construction.

3.3 FIELD QUALITY CONTROL

A. Field Inspection: Coordinate field inspection in accordance with appropriate sections in Division

01.

B. Manufacturer's Services: Coordinate manufacturer's services in accordance with appropriate sections in Division 01.

C. Field Inspections

1. An experienced, competent, and authorized representative of the manufacturer shall visit the site once after equipment installation and prior to start-up to inspect, check, adjust if necessary, and approve the equipment’s installation. The equipment supplier’s representative shall revisit the jobsite as often as necessary until all issues have been corrected and the equipment installation and operation is satisfactory to

Architect.

2. Manufacturer shall furnish a written report certifying that the equipment:

a. has been properly installed;

b. that Owner’s representative has been instructed in the proper maintenance and operation of the equipment;

116723 - 9

3. Equipment supplier shall provide an experienced, factory-trained, competent, and authorized service representative for a minimum of 3 times at Site, including once during installation and systems setup and once during acceptance to inspect and confirm all parts of the equipment.

3.4 DEMONSTRATION AND TRAINING

A. The program for employee training shall educate all employees who will be required to operate and maintain the system. The objective of the training will be to provide a common working knowledge concerning all significant aspects of the equipment being supplied.

B. The training program shall consist of one (1) day on-site working with OWNER’S staff.

The training course outline shall be submitted to the Architect at least two weeks prior to the requested start of the training program.

C. The supplier shall provide all materials and manuals to conduct the training program.

D. CONTRACTOR shall record training per requirements in section 01 79 00 - demonstration and training

3.5 CLEANING AND PROTECTION

A. Clean products in accordance with the manufacturer's recommendations.

B. Touch-up, repair or replace damaged products before Substantial Completion.

END OF SECTION 116723

3/31/2021

074113.6

STANDING SEAM METAL ROOF

SEE ATTACHED

TONY SAUVE

PETERSEN ALUMINUM CORPORATION

WESTERN UPPER PENINSULA SHOOTING

FACILITY

TONY SAUVE

MARCH 30, 2021STEVE SUTTON

Michigan Office: 1421 East Shaffer Road Hope, Michigan 48628

Phone: 989-205-3531 Email: tsauve@petersenmail.com

Tuesday March 30. 2021

Attn: Steven Sutton Nowak & Fraus Engineering 46777 Woodward Ave Pontiac, MI 48342

Request for Specification Modification

Project: Western Upper Peninsula Shooting Facility Location: Ontonagon, MI Bid Date: April 14, 2021

We ask for the following product to be approved as equal and/or superior to the products listed in the project specifications:

Section 074113.6 Standing Seam Metal Roof Panels Specified: ATAS 2” Field-Lok .040 Aluminum, 19-1/2” wide panel, Oxide Series Color “Copper Brown” Requested: Petersen Aluminum Tite-Loc Plus Standing Seam Panel

• .042 thick Aluminum

• 18” wide panel X 1-3/4” high seam

• UL-1887 wind uplift

• UL-580 Class 90

• UL-790 Class A

• UL-2218 Impact Resistant Rated

• ASTM E1592, E331/1646, E283/1680 & ASTM E2140

• Manufacturers Color “Weathered Steel”

• 20 year Manufactures Finish Warranty

If you have any questions regarding the requested product(s) please feel free to visit the Petersen Aluminum Web Site www.pac-clad.com or call our office at 989-205-3531.

Approved By:

Date:

Rejected By:

Date:

http://www.pac-clad.com/

800 PAC CLAD | PAC-CLAD.COM ©2020 Petersen Aluminum

TITE-LOC PLUS PANEL

PRODUCT FEATURES

` Herr-Voss corrective leveled

` Pencil ribs and striations are only available by request

` 30-year non-prorated finish warranty

` Maximum factory-produced panel length is 64’ (check w/factory for longer lengths)

` Weathertightness warranty available

MATERIAL

` 43 stocked colors (24 gauge steel)

` 16 Stocked colors (22 gauge steel)

` 36 stocked colors (.032 aluminum)

` 22 stocked colors (.040 aluminum)

` Galvalume Plus available

UL CLASSIFICATION

` UL-580 Class 90 rated up to 18” O.C.

` UL-1897 wind uplift

` UL-790 Class A fire rated

` UL-263 fire resistance rated

` UL-2218 impact resistance rated

TESTS (TITE-LOC PLUS ONLY)

` 24 Gauge steel SSTD Missile Impact Tested - Passed

` .032 aluminum SSTD Missile Impact Tested - Passed

ASTM TESTS

` ASTM E1592 tested

` ASTM E331/1646 tested

` ASTM E283/1680 tested

` ASTM E2140 (Tite-Loc Plus only)

FLORIDA BUILDING & MIAMI-DADE PRODUCT

APPROVALS

Please refer to pac-clad.com or your local factory for specific product approval numbers for Tite-Loc Plus.

*24 gauge and 22 gauge steel and .032 and .040 aluminum panels are UL-90 classified over solid substrate. See roof deck construction in Underwriters Laboratories roofing materials and systems directory. 24 gauge and 22 gauge Tite-Loc Plus panels are FM Approved in 12" and 16" widths over 16 gauge open purlins only.

** Not available in all locations. Consult PAC rep for availability.

Not all panel conditions are available in each Petersen branch; additional freight charges might apply if specific panel condition is required. Tite-Loc and Tite-Loc Plus panels are supplied "smooth" as standard. Customer must advise if additional panel conditions are required.

SPECS

12”, 16” or 18” O.C. 2” High

MATERIALS

.032 aluminum* .040 aluminum*

24 gauge steel* 22 gauge steel*

UL-90

STRIATIONS W/ PENCIL RIBS**

(OPTIONAL)

12", 16" or 18" O.C.

2"

PENCIL RIBS

(OPTIONAL)

12", 16" or 18" O.C.

2"

WITH STRIATIONS

(OPTIONAL)

12", 16" or 18" O.C.

2"

SMOOTH PANEL

(STANDARD)

12", 16" or 18" O.C.

2"

Standard Colors

$ HEMLOCK GREEN

$ ARCADIA GREEN

$ INTERSTATE BLUE

$ BURNISHED SLATE

$ TERRA COTTA

$ SIERRA TAN

$ GRANITE

$ TEAL

$ HUNTER GREEN

$ CHARCOAL

$ DARK BRONZE

$ BURGUNDY

$ MUSKET GRAY

$ CITYSCAPE

$ PATINA GREEN

$ EVERGREEN

$ GRAPHITE

$ MATTE BLACK

$ MANSARD BROWN

$ MIDNIGHT BRONZE

$ SLATE GRAY

PAC-CLAD.COM

FOREST GREEN

MILITARY BLUE

SLATE BLUE

AGED BRONZE

CARDINAL RED

SANDSTONE

STONE WHITE

HARTFORD GREEN

BERKSHIRE BLUE

AWARD BLUE

MEDIUM BRONZE

COLONIAL RED

ALMOND

BONE WHITE

Color Guide

Premium Colors

$$ ANODIC CLEAR

$ SILVER

$ COPPER PENNY

$$ WEATHERED STEEL

$$ SILVERSMITH

$ CHAMPAGNE

$ AGED COPPER

$$ WEATHERED COPPER

Standard Colors

FOREST GREEN

MILITARY BLUE

SLATE BLUE

AGED BRONZE

CARDINAL RED

SANDSTONE

STONE WHITE

HEMLOCK GREEN

ARCADIA GREEN

INTERSTATE BLUE

BURNISHED SLATE

TERRA COTTA

SIERRA TAN

GRANITE

TEAL

HUNTER GREEN

CHARCOAL

DARK BRONZE

BURGUNDY

MUSKET GRAY

CITYSCAPE

PATINA GREEN

EVERGREEN

GRAPHITE

BLACK

ALUMINUM

MATTE

BLACK STEEL

MANSARD BROWN

MIDNIGHT BRONZE

SLATE GRAY

HARTFORD GREEN

BERKSHIRE BLUE

AWARD BLUE

MEDIUM BRONZE

COLONIAL RED

ALMOND

BONE WHITE

IL: 800 PAC CLAD TX: 800 441 8661MD: 800 344 1400
AZ: 833 750 1935 GA: 800 272 4482MN: 877 571 2025

$ ZINC $ WEATHERED ZINC

PAC-CLAD.COM

Kynar 500® or Hylar 5000® pre-finished steel and aluminum for roofing, curtainwall and storefront applications.

See back for color availability chart.

Metallic Colors $ PricingENERGY STAR® Colors

Premium ColorsCool Colors

PAC-CLAD® Color Availability

PAC-CLAD Premium finishes are available from stock at a moderate extra cost. PAC-CLAD Copper Penny is a Non-Weathering finish. Solar Reflectance Index calculated according to ASTM E-1980.

*Low Gloss/Low Sheen, 70% PVDF finish ** Appearance differs for Black Aluminum and Matte Black Steel *** 10-year finish warranty

PAC-CLAD is a registered trademark of Petersen Aluminum Corp. Kynar 500 is a registered trademark of Arkema Inc. Hylar 5000 is a registered trademark of Solvay Solexis. 2/21

ENERGY STAR PERFORMANCE CRITERIA:

Emissivity uses ASTM C1371 Reflectivity uses ASTM C1549.

TECHNICAL DATA FOR KYNAR 500/HYLAR 5000 COATING:

` South Florida Exposure: Color (ASTM D 2244) - No more than 5ΔE Hunter units at 20 years; Chalk (ASTM D 4214) – Rating no less than 8 at 20 years; Film integrity – 20 years.

` Accelerated Weathering (ASTM D 4587, ASTM G 154): 5000 Hours;

Chalk, per ASTM D 4214, rating of 6 or better; Color, per ASTM D 2244, < 5ΔE (Hunter Units) color change.

` Humidity Resistance (ASTM D 2247): Galvalume or HDG, 100% RH, 2000 hours – No field blisters; Aluminum, 100% RH, 3000 hours – No field blisters

` Salt Spray Resistance (ASTM B 117): Aluminum, 3000 hours, Galvalume or HDG, 1000 hours – Creep from scribe no more than 1/16”, no field blisters

` Chemical/Acid Pollution Resistance (ASTM D 1308): Pass
` T-Bend (ASTM D 4145): 1T – 3T with no loss of adhesion
` Pencil hardness (ASTM D 3363): HB – 2H
` Specular Gloss (ASTM D 523) @ 60 degrees: Typical – 20 – 35
` Abrasion Resistance (ASTM D 968): 67 +/- 10 liters
` Cross Hatch Adhesion (ASTM D 3359): No loss of adhesion
` Reverse Impact (ASTM D 2794): Galvalume or HDG, 2x

metal thickness inch-pounds, no loss of adhesion; Aluminum, 1.5x metal thickness inch-pounds, no loss of adhesion

` Flame Test (ASTM E 84): Class A Coating

PAC-CLAD

STANDARD COLORS REFLECTIVITY EMISSIVITY 3 YEAR

EXPOSURE SRI

STEEL ALUMINUM 20-IN. COIL ENERGY

STAR 24 GA. 22 GA. .032 .040 .050 .063 24 GA. .032

AGED BRONZE 0.29 0.87 0.27 29

ALMOND 0.56 0.86 0.55 65

ARCADIA GREEN 0.29 0.87 0.29 29

AWARD BLUE*** 0.24 0.86 0.23 22

BERKSHIRE BLUE* 0.30 0.87 0.27 31

BLACK ALUMINUM** 0.04 0.89 0.04 -2

BONE WHITE 0.70 0.86 0.69 85

BURGUNDY 0.14 0.85 0.13 9

BURNISHED SLATE 0.32 0.87 0.31 33

CARDINAL RED*** 0.44 0.86 0.44 49

CHARCOAL 0.30 0.86 0.30 30

CITYSCAPE 0.49 0.86 0.50 56

COLONIAL RED 0.31 0.86 0.31 31

DARK BRONZE 0.29 0.86 0.29 29

EVERGREEN 0.28 0.86 0.26 27

FOREST GREEN 0.10 0.86 0.10 4

GRANITE* 0.33 0.87 0.33 34

GRAPHITE 0.29 0.87 0.28 29

HARTFORD GREEN 0.08 0.88 0.08 3

HEMLOCK GREEN 0.31 0.87 0.30 32

HUNTER GREEN 0.28 0.86 0.27 27

INTERSTATE BLUE 0.16 0.87 0.15 12

MANSARD BROWN 0.31 0.86 0.31 31

MATTE BLACK STEEL** 0.26 0.86 0.25 25

MEDIUM BRONZE 0.30 0.87 0.29 31

MIDNIGHT BRONZE 0.06 0.87 0.06 0

MILITARY BLUE 0.31 0.86 0.30 31

MUSKET GRAY 0.32 0.86 0.31 33

PATINA GREEN 0.33 0.86 0.32 34

SANDSTONE 0.48 0.86 0.48 54

SIERRA TAN 0.32 0.82 0.31 31

SLATE BLUE 0.28 0.86 0.27 27

SLATE GRAY 0.38 0.86 0.37 41

STONE WHITE 0.69 0.86 0.67 84

TEAL 0.32 0.86 0.32 33

TERRA COTTA 0.34 0.87 0.33 36

PAC-CLAD PREMIUM COLORS

AGED COPPER 0.55 0.80 0.53 62

ANODIC CLEAR 0.32 0.83 0.31 31

CHAMPAGNE 0.50 0.85 0.49 57

COPPER PENNY 0.52 0.81 0.52 58

SILVER 0.47 0.87 0.46 53

SILVERSMITH 0.32 0.88 0.32 34

WEATHERED COPPER 0.45 0.88 N/A 51

WEATHERED STEEL 0.32 0.89 N/A 34

WEATHERED ZINC 0.48 0.82 0.46 53

ZINC 0.42 0.82 0.38 45

CLEAR-COAT ACRYLIC FINISH (NON-KYNAR)

GALVALUME PLUS 0.68 0.14 0.55 57

PAC-CLAD Print Coat System 20 Year Limited Warranty

Owner:

Address:

Contractor: of Customer:

Invoice Num. & Date:

Date Warranty Begins: Date Warranty Ends:

Job Name:

PART I

PETERSEN ALUMINUM CORPORATION (hereinafter referred to as “PAC”) hereby issues the following limited warranty to the above referenced owner (hereinafter referred to as OWNER) exclusively. Subject to the terms and conditions listed below, PAC warrants that upon delivery its standard color Fluropon Print System coating (hereinafter referred to as the “COATING”) applied to aluminum, G-90 hot-dipped galvanized steel or AZ50 zinc-aluminum alloy steel sheet and coil that has been fabricated, roll-formed or otherwise manufactured, within one year from the date of shipment thereof by PAC, and sold for use as painted roofing panels, fascia, mansard, soffit or other building components, will for a period of twenty (20) years from the project completion date listed above (hereinafter referred to as the “WARRANTY PERIOD”), meet the following quality standards:

A. WILL NOT chalk in excess of ASTM D-4214 number eight (8) rating.

B. Print coat pattern WILL remain intact and distinguishable.

C. WILL NOT crack, check, peel or otherwise lose adhesion. The terms, crack, check and peel, used herein shall not include minute fracturing of the COATING incurred during proper fabrication. In addition loss of adhesion of the COATING as a result of substrate corrosion, however caused, and either from the front side or the backside of the substrate is specifically excluded from this warranty.

The following additional terms, conditions and other limitations are also included as part of this warranty:

PART II

1.) This warranty and all terms, conditions and exclusions contained herein apply to PAC’s COATING only. In regards to either the aluminum, G-90 hot-dipped galvanized steel or AZ50 zinc-aluminum alloy steel substrates to which the COATING has been applied or any solar panels/solar film applied to the COATING, PAC makes no representations or other warranties whatsoever. ALL BASE METAL SUBSTRATES AND SOLAR PANEL/FILMS ARE SOLD AS IS. In addition, PAC makes no representations or otherwise warrants the weather tightness of the roofing panels, fascia, mansard, soffit or other building components referred to in Part I. Further, PAC is expressly to be held harmless for failures, leaks or consequential damages caused by the roofing panels, fascia, mansard, soffit or other building components.

2.) This warranty applies to the COATING installed on structures within the continental United States that have been exposed to normal weather and atmospheric conditions only. Failure of the COATING caused by exposure to harmful fumes, cement dust, falling sand, animal waste or its decomposition by-products, dust particles and other foreign substances in the air, chemical fumes, chemical sprays and installations with a proximity of less than a one-half mile radius from a seacoast, saltwater or other brackish water environment are all excluded from this warranty. In addition, this warranty does not apply to failure of the COATING caused by or as a result of fire, other accident or casualty, vandalism, radiation, falling objects, explosions, riots or acts of God. Also, the warranty is void for areas where materials / items such as snow guards, solar panels or solar films are attached to the COATING. In addition, the warranty is void if the COATING is perforated. Finally, this warranty does not apply to failure of the COATING caused by the following: damage incurred during shipment, improper storage, improper fabrication or improper installation, improper seaming techniques, surface scratches or other abrasions however caused, damage caused by contact with areas subject to water run-off from lead, copper or other incompatible flashings or areas in metallic contact with lead, copper or other dissimilar metals, damage caused by failure to provide free drainage of water, including internal condensation from overlaps, and all other surfaces of the roofing panels, fascia, mansard, soffit or other building components, damage caused by failure to remove debris or other accumulations of foreign substances from the surface of the roofing panels, fascia, mansard, soffit or other building components, damage caused by contact with green or wet lumber, damage caused by contact with or close proximity to damp underlayment, insulation, soil, vegetation or other corrosive materials and/or damage caused by use of unsuitable fasteners or flashings. Selection of suitable long-lasting fasteners as well as appropriate flashings rests solely with the OWNER.

3.) This warranty does not apply to failure of the COATING in the following additional circumstances: forming where the bend is tighter than

2T, forming which involves severe reverse bending, or which subjects the COATING to alternate compression and tension, roofing applications where the slope of the roof, or sections of the roof, are flatter than ½”: 12”, applications where the COATING is sheltered from periodic washing by natural rainfall such as underside eaves and soffits, or discoloration or damage to the COATING caused by failure to remove factory applied protective strippable film (where applicable).

PART III

1.) All claims filed under the provisions of this warranty must be presented by the OWNER to PAC, in writing, during the WARRANTY

PERIOD and not more than thirty (30) days after discovery of any apparent defects, delivered by Registered or Certified mail to the following address:

Petersen Aluminum Corp.

1005 Tonne Rd.

Elk Grove Village, IL 60007 ATTN: Warranty Claims

S A M P L

E

In submitting a claim under the provisions of this warranty, it is the responsibility of the OWNER to provide adequate documentation of the COATING involved in the claim, including date of installation, name of installer and contractor (if different), PAC order number, PAC invoice number and proof of payment to PAC for all such materials included as part of the claim. In no event will any claims be honored under the provisions of this warranty if invoices from PAC have not been previously satisfied in full within PAC’s standard credit terms.

OWNER further agrees to allow PAC to inspect all such documentation.

2.) After receipt of claim from owner, PAC will be given a reasonable opportunity to examine or cause to be examined, the COATING claimed to be non-conforming. OWNER shall further use reasonable care to protect any disputed material until PAC has had time to conduct its own inspection and make disposition.

3.) If after inspection it is determined by PAC that the claim is valid under the terms of this warranty, then PAC agrees, at its option, to refinish, repair or replace the defective COATING on the following basis:

a. If the COATING is to be refinished then PAC shall bear the cost of materials and labor reasonably necessary to repaint those areas showing failure. Further, PAC shall use normal painting practices to apply a Kynar 500 or Hylar 5000 coating system or other suitable alternative. The choice of appropriate coating system to use rests exclusively with PAC.

b. In the case of repair or replacement of the defective COATING, PAC shall at its option, and F.O.B. PAC plant, furnish either replacement components or sufficient sheet to fabricate replacement components, for those areas of the building where the COATING is determined to be defective. However, in no event shall PAC be liable for the cost of labor expended by others on any nonconforming material or for any special, indirect or consequential damages to anyone by reason of the fact that such material may have been nonconforming.

This warranty shall apply to the part or parts of the COATING refinished, repaired or replaced by PAC, but only for the unexpired portion of the WARRANTY PERIOD applicable to the original COATING only. It will be at the discretion of PAC what appropriate measure shall be taken; that is whether the COATING should be refinished, repaired or replaced. However, in lieu of any of the foregoing alternatives PAC also reserves the right to refund to the OWNER a cash amount equal to PAC’s original invoiced price of the nonconforming material as satisfaction in full for all claims under this warranty. In addition, should repair or replacement of the nonconforming materials necessitate the removal of solar panels/solar films PAC assumes no responsibility for either the original, replacement or reinstallation costs of these solar panels/solar films. At no time does this warranty confer upon the OWNER the right to refinish, repair or replace those areas of COATING under dispute without written notice and agreement by a duly authorized officer of PAC. Any unauthorized refinish, repair or replacement of the COATING shall result in this warranty becoming null and void.

PART IV

1.) Except as provided herein, PAC makes no warranty or guarantee, express or implied, including without limitation, WARRANTIES OF FITNESS AND MERCHANTABILITY. Further, OWNER acknowledges that PAC shall have no other liability to any other person, firm, or corporation with respect thereto, including, without limitations, any liability for indirect, consequential or resultant damages, whether based upon breach of warranty or negligence.

2.) PAC extends this warranty solely to the OWNER listed herein. This warranty is non-transferable and non-assignable.

3.) This warranty shall be subject to and shall be enforced and construed according to the laws of the State of Illinois. Any legal action to enforce or construe any portion of this warranty shall be brought in a Court of competent jurisdiction in Cook County, Illinois.

4.) If any provision of this warranty shall be held by any Court of competent jurisdiction to be invalid or unenforceable in whole or in part, the remaining provisions of this warranty shall be effective to the same extent as if such invalid or unenforceable provision had never been contained herein.

5.) PAC reserves the right to terminate this warranty at any time upon thirty (30) day written notice. However termination shall not affect the rights accruing to the OWNER prior to such termination.

6.) Both the supplier of the PAC COATING and the applicator thereof have made certain warranties to PAC which are similar to the warranties made by PAC to the OWNER under this limited warranty. In the event that the supplier and or applicator (or its successors or assigns) of the coating can no longer perform, or is not willing to perform, its obligations to PAC, then the limited warranty contained herein shall be of no further force or effect.

7.) The terms hereof shall constitute the entire agreement and understanding of the parties hereto respecting the subject matter hereof and no provision or statement contained at any time in any other writing, including without limitation, OWNERS, customers and/or contractors purchase orders, architects specifications or PAC’s acceptance forms shall be effective to change the provisions hereof, unless contained in a subsequent agreement, in writing, signed by both the OWNER and PAC expressly stating that it is intended thereby to modify or supplement this instrument.

PETERSEN ALUMINUM CORPORATION

By: _____________________________

*** Not valid without Authorized Signature***

Date:

Fluropon is a registered trademark of The Valspar Corporation Kynar 500 is a registered trademark of Atochem N.A.

Hylar 5000 is a registered trademark of Ausimont USA, Inc. PAC-CLAD is a registered trademark of Petersen Aluminum Corporation

S A M P L

E

Certificate Number TST1657 Report Date: 5/1/2013 Completion Date: 4/12/2013 Expiration Date: 4/12/2023 File Number: 13-792 Lab Number: 7279 Project Number: 13-4494

OFFICIAL TEST REPORT

MANUFACTURER: Petersen Aluminum Corporation SPECIFICATIONS: ASTM E1592-05

ADDRESS: 102 Northpoint Parkway, Bldg. 106 PROJECT: Florida State Approval

Acworth, GA 30102

DESCRIPTION OF SAMPLE

Model Designation: Series: Tite-Loc Plus (TLP) Sample A-1 The roof deck system consisted of eight full width panels. The panels measured 18" wide by 0.040" thick by 288" long. The side of the panel at the clips utilized a 2 1/8" high upright bend. The deck system was fastened to the steel purlins using one two piece deck clip with **18 gauge base and **22 gauge top each deck clip spaced every 12" on center. Deck clips were fastened to the steel purlins using two No. 14-13 by 1 1/2" pancake head with drill point per clip. The first two outer rows of panels were fastened to the steel purlins with a single row of No. 14-13 by 1 1/2" pancake head with drill point located 48" on center.

Test Frame: The test apparatus frame utilized 3" by 12" by 24' long Douglas fir wood. The steel purlins were bolted to the inside of the test apparatus. Purlins were spaced every 12" on center and were bolted to the test apparatus.

Test Results and Observations Deflection table is included on page 2 of 15 for Sample A-1. Please reference appendix A for location of deflection measurements.

Sample A-1 ultimate test load and observations made during testing: achieved load 405.0 PSF. No failure occurred during testing. Test was stopped at 405.0 PSF at client’s request.

Test Summary:

The test specimen area measuring 18" by 288" long, was tested in accordance with ASTM E 1592-05, Standard Test Method for Structural Performance of Sheet Metal Roof and Siding Systems by Uniform Static Air Pressure Difference. The purpose of this test is to evaluate the comparative resistance of the roof deck assembly to negative pressures.

Completion Date: 4/12/2013 Expiration Date: 4/12/2023 File Number: 13-792 Lab Number: 7279 Project Number: 13-4494

Sample A-1 Temperature: 72.4 Barometric Reading: 30.24 Negative Pressure: Each load was held for sixty seconds

DEFLECTION TABLE MEASUREMENTS

Loads (PSF) D-1 D-2 D-3 D-4 D-5 D-6 D-7 D-8

1.0 PSF 0 0 0 0 0 0 0 0

67.5 PSF 0.021" 0.028" 0.020" 0.029" 0.003" 0.024" 0.004" 0.022"

1.0 PSF 0.001" 0.002" 0.001" 0.002" 0 0.002" 0 0.001"

135.0 PSF 0.238" 0.246" 0.236" 0.244" 0.208" 0.241" 0.209" 0.241"

1.0 PSF 0.022" 0.023" 0.022" 0.023 " 0.010" 0.024" 0.021" 0.023"

202.5PSF 0.381" 0.392" 0.378" 0.391" 0.321" 0.384" 0.323" 0.384"

1.0 PSF 0.041" 0.046" 0.049" 0.045" 0.044" 0.048" 0.046" 0.045"

270.0 PSF 0.411" 0.427" 0.408" 0.421" 0.356" 0.414" 0.353" 0.414"

1.0 PSF 0.079" 0.078" 0.077" 0.080" 0.069" 0.081" 0.076" 0.081"

337.5 PSF 0.446" 0.460" 0.443" 0.278" 0.387" 0.444" 0.388" 0.445 "

1.0 PSF 0.099" 0.098" 0.96" 0.101" 0.094" 0.098" 0.096" 0.095"

405.0 0.506" 0.495" 0.474" 0.305" 0.422" 0.484" 0.427" 0.485"

NOTES: The ultimate load achieved was 405.0 PSF.

1.0 PSF represents the zero load condition.

Completion Date: 4/12/2013 Expiration Date: 4/12/2023 File Number: 13-792 Lab Number: 7279 Project Number: 13-4494

Test load (PSF)

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

67.5 135 202.5 270 337.5 405

Panel Deflection and Set

Average deflection in inches

Average permanent set in inches

Completion Date: 4/12/2013 Expiration Date: 4/12/2023 File Number: 13-792 Lab Number: 7279 Project Number: 13-4494

DESCRIPTION OF SAMPLE

Model Designation: Series: Tite-Loc Plus (TLP) Sample B-1 The roof deck system consisted of eight full width panels. The panels measured 18" wide by 0.040" thick by 288" long. The side of the panel at the clips utilized a 2 1/8" high upright bend.