A5 - GP UTILITY IFC Drawings.pdf
PDF 18 MB Posted
- Solicitation number
- 36C25726R0016
About this file
This is a comprehensive set of construction documents for a VA North Texas Healthcare utility upgrade project located at 2737 Sherman Road in Grand Prairie, Texas. The project involves constructing a new utility yard for the PACT and Dental clinics, with major work including removing existing covered parking, concrete drives, and equipment pads, and installing new infrastructure such as an Oncor service, modified Atmos gas line, a new generator, transformers, chillers, boilers, concrete drives, structural concrete equipment pads, an 8-foot tall reinforced concrete masonry unit (RCMU) wall, sliding and egress gates, temporary asphalt paving, and two dumpster enclosures. The project is divided into three phases and will follow 2021 International Building Code standards, with special inspections required throughout construction. The estimated issue date is 10-13-2023, with contract number 549-23-723, and the project is being managed by the VA Office of Facilities Management.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RLG CIVIL / STRUCTURAL ENGINEERING
12001 N. CENTRAL EXP. STE 300
DALLAS, TX 75243
MR. JEFF BETHKE, PE
T. 214.739.8100
CAMPOS ENGINEERING
1331 RIVER BEND DR.
DALLAS, TX 75247
MR. FRED C. CRABTREE, JR., PE
T. 214.696.6291
ENAPAY, LLC
MESQUITE, TX 75149
207 WEST MAIN STREET
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
IKERD
DECATUR, TX 76234
1604 W BUSINESS 380, STE 100
MR. WILL IKERD, PE
T. 214.382.9811
VA NORTH TEXAS HEALTHCARE
ENGINEER SERVICES
BLD: 9 ROOM: 118
MR. JOSE SANCHEZ GONZALEZ
T. 214.857.4830
GNR ESTIMATING SERVICES, LLC
304 TRYALL DRIVE
RUNAWAY BAY, TX 76426
MR. THEODORE E. GARNER
T. 210.487.1127
GC STAGING AREA
PROJECT NUMBER:
ISSUE DATE:
EA #:
CLIENT #:
PROJECT DIRECTORY:
EA02.0702
10-13-2023
2737 SHERMAN ROAD / GRAND PRAIRIE, TEXAS 75051 ISSUED FOR CONSTRUCTION
A E
U P
G R
A D
E U
T
IL
IT
Y
G P
S
IT
E S
U R
V E
Y E
A .0
10-13-2023
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
AE UPGRADE UTILITY GPSITE SURVEY
A-000
549-23-723
PROJECT LIMITS
VA SIGN-OFF / COMMENTS
JOSE SANCHEZ GONZALEZ DATE
S
N E
HP
ET
SNNYL
R E
G O
R
E T
RA
C
H
I
E
S
T
I
E R
D
T
S
T E X
A6
S
O F
3 3A T
E
T
C
E R
G
REVISION 01 - REMOVE DEDUCTIVE ALTERNATES FROM THE PROJECT.
11/6/2024
REVISION 02 - ADDENDUM 01 - CLEAN UP DRAWINGS.
3/11/2025
CALLOUT HEAD
DOOR TAG
? INTERIOR ELEVATION
ROOM TAG WITH
AREA
BUILDING SECTION
SPOT ELEVATION - TARGET
? WALL TAG
? WINDOW TAG
TEMP. CONSTRUCTION PARTITION
REVISION SYMBOL
REVISION NUMBER
CABINET / CEILING SECTION
EQUIPMENT TAG EQ.000
ROOM SIGNAGE TAG
X
A1/A001
KEYNOTE LEGEND
KEY VALUE KEYNOTE TEXT
09 29 00.A1 DESCRIPTIONSPECIFICATION SECTION KEYNOTE INFORMATION
ABBREVIATIONS AND ANNOTATIONS LEGEND
ROOM NAME
ROOM SF
01 PHOTO CALLOUT
N.I.C. NOT IN CONTRACT
FIRE EXTINGUISHER - WALL MOUNTEDFE
FIRE EXTINGUISHER - CABINETFE
ADDITIONAL NOTES
PROJECT SCOPE
THE PROJECT CONSISTS OF A NEW UTILITY YARD FOR THE
GRAND PRAIRIE CAMPUS - BOTH THE PACT AND DENTAL
CLINICS. THE EXISITING COVERED PARKING, CONCRETE
DRIVES AND EQUIPMENT / CONCRETE PADS WILL BE
REMOVED. THE PROJECT WILL BE CONCTRUCTED IN 3
PHASES. THE NEW NECESSARY UTILITIES WILL INCLUDE:
• A NEW ONCOR SERVICE
• MODIFY ATMOS GAS LINE
• DEMOLITION OF EXISTING UTILITIES
• NEW GENERATOR
• NEW TRANSFORMERS
• NEW CHILLERS
• NEW BOILERS IN THE BASEMENT
• NEW CONCRETE DRIVES
• NEW STRUCTURAL CONCRETE PADS FOR THE EQUIPMENT
• NEW 8'-0" TALL RCMU WALL
• NEW SLIDING GATE AND TWO EGRESS GATES
• NEW TEMPORATY ASHPHALT PAVING
• TWO NEW DUMPSTER ENCLOSURES
COMMISSIONING AS REQUIRED BY THE VA - COORDINATE
WITH THE VA'S COR.
THE GENERAL CONTRACTOR IS TO FILL OUT AN INFECTION
CONTROL RISK ASSESSMENT GUIDELINE AND SUBMIT IT TO
THE VA'S COR BEFORE STARTING THE PROJECT.
PROJECT DATA AND BUILDING
CODE INFORMATION
PROJECT DATA
PROJECT NAME:
PROJECT ADDRESS:
OWNER:
APPLICABLE CODES
BUILDING CODE:
ACCESSIBILITY CODE: 2010 STANDARDS FOR ACCESSIBLE
DESIGN (SAD)
2021 INTERNATIONAL BUILDING CODE
TABS PROJECT NUMBER: NA
VA NORTH TEXAS
UTILITY UPGRADE FOR THE PACT AND
DENTAL CLINICS
MECHANICAL CODE:
ELECTRICAL CODE:
PLUMBING CODE:
NFPA: 2021 NFPA 101 LIFE SAFETY CODE
2021 INTERNATIONAL MECHANICAL
CODE
2021 INTERNATIONAL ELECTRICAL
CODE
2021 INTERNATIONAL PLUMBING CODE
OSBC: NFPA [10, 13, 20 (2022)], 70(2023),
72 (2022), 99 (2021)
FUEL AND GAS:
ENERGY CODE: 2018 INTERNATIONAL ENERGY
CONSERVATION CODE / 2022 ASHRAE
90.1.
ACOUSTICAL DESIGN: ASHRAE APPLICATIONS VOLUME,
CHAPTER 42 / ANSI S1.8 / ASA 84
2737 SHERMAN STREET;
GRAND PRAIRIE, TX 75051-1027
DEPARTMENT OF VETERANS AFFAIRS
VA STANDARDS:
VA PHYSICAL DESIGN MANUAL (PSDM)
VA PHYSICAL SECURITY DESIGN STANDARDS
DATA DEFINITIONS
ASCE 59-11 BLAST PROTECTION OF BLDGS
(2011)
NFPA 54, ANSI Z223.1 NATIONAL FUEL
GAS CODE, 2021 EDITION
GRAPHIC REPRESENTATION: THE CONSTRUCTION DRAWINGS ARE
A GRAPHIC REPRESENTATION OF THE SCOPE, LOCATION, AND
ARRANGEMENT OF MATERIALS AND EQUIPMENT SHOWING THE
EXECUTION OF THE WORK. THE INTENT OF THE SPECIFICATIONS IS
TO OUTLINE AND/OR FURTHER INDICATE THE TYPES AND QUALITIES
OF THE MATERIALS AND WORKMANSHIP. SHOULD THE
SPECIFICATIONS AND CONSTRUCTIONS DRAWINGS DISAGREE IN
THEMSELVES OR WITH EACH OTHER, WRITTEN CLARIFICATIONS IN
THE FORM OF A REQUEST FOR INFORMATION (RFI) SHALL BE
ISSUED TO THE ARCHITECT BY THE GENERAL CONTRACTOR. IN
ABSENSE OF THE RFI, THE GENERAL CONTRACTOR'S PROPOSAL
SHALL BE BASED UPON THE MOST EXPENSIVE COMBINATION OF
QUALITY AND QUANTITY OF WORK INDICATED.
CONFLICTS: IN CASES OF CONFLICTS, INCONSISTENCIES OR
DISCREPANCIES WITHIN THE CONSTRUCTION DRAWINGS AND
SPECIFICATIONS, THE GENERAL CONTRACTOR SHALL PROVIDE
THE BETTER QUALITY AND GREATER QUANTITY OF WORK AS
DETERMINED AND DIRECTED BY THE OWNER.
1.
2.
GENERAL PROJECT NOTES
3.
4.
5.
6.
8.
7.
9.
10.
ERRORS / OMISSIONS IN THE SCHEDULES: SUCH AS THE ROOM
FINISH SCHEDULE, DOOR SCHEDULE AND EQUIPMENT SCHEDULE
SHALL NOT RELIEVE THE GENERAL CONTRACTOR FROM THE
PERFORMANCE OF THE WORK AS SHOWN IN THE CONSTRUCTION
DRAWINGS OR SPECIFICATIONS.
NOT APPLICABLE
EQUIPMENT VERIFICATION: THE GENERAL CONTRACTOR SHALL
BE RESPONSIBLE FOR THE VERIFICATION OF THE SIZE AND
LOCATION OF ALL OPENINGS FOR THE MECHANICAL / ELECTRICAL /
PLUMBING WORK AND EQUIPMENT AND SHALL COORDINATE WITH
ALL SUB-CONTRACTORS INVOLVED.
SERVICE TO UTILITIES: THE GENERAL CONTRACTOR SHALL
MAINTAIN SERVICE TO EQUIPMENT UTILITIES AND PROTECT
AGAINST DAMAGE TO SUCH DURING CONSTRUCTION AND SHALL
NOT INTERRUPT EXISTING UTILITIES SERVING OCCUPIED /
OPERATING FACILITIES EXCEPT WHEN AUTHORIZED IN WRITING
BY THE OWNER AND AUTHORITIES HAVING JURISDICTION.
NOT ALLOWED: NO GASOLINE POWERED TOOLS OR POWER
ACTUATED FASTENING DEVICES SHALL BE ALLOWED INSIDE THE
FACILITY.
CONSTRUCTION: CONSTRUCTION SHALL COMPLY WITH THE
APPLICABLE REQUIREMENTS OF NFPA 101 AND THE
REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION. IF
THERE IS NO APPLICABLE LOCAL CODE(S), THE MOST
CURRENT RECOGNIZED MODEL BUILDING CODES SHALL BE
APPLIED.
DO NOT SCALE THE DRAWINGS: USE FIGURED DIMENSIONS ONLY.
COORDINATION: THE GENERAL CONTRACTOR IS TO FIELD
VERIFY ALL DIMENSIONS AND CONDITIONS BEFORE
PROCEEDING WITH THE SCHEDULED WORK AS WELL AS
COORDINATING THE EXISTING CONDITIONS WITH THE
SCHEDULED WORK
ALTERNATES
DEDUCTIVE ALTERNATE 01:
REDUCE GENERATOR FROM 700 KVA TO 500 KVA.
DEDUCTIVE ALTERNATE 02:
REDUCE THE NATURAL GAS LINE FROM 6" TO 3".
DEDUCTIVE ALTERNATE 03:
REDUCE GEAR SIZE, CONDUIT, WIRING AND STRUCTURAL PADS.
DEDUCTIVE ALTERNATE 04:
REMOVE THE THIRD 1500 KVA TRANSFORMER.
DEFINITIONS
OWNER: U.S. DEPARTMENT OF VETERANS AFFAIRS
REPRESENTED BY THE CONTRACTING OFFICERS
REPRESENTATIVE (COR) OR THE RESIDENT
ENGINEER.
GC: GENERAL CONTRACTOR
CONTRACTOR:GENERAL CONTRACTOR
A/E: THE ARCHITECT AND ENGINEER(S) OF RECORD.
AHJ: THE AUTHORITY HAVING JURISDICTION - WHICH
IS THE OWNER.
UTILITY NOTES
CALL BEFORE YOU DIG:
TEXAS ONE CALL PARTICIPANTS REQUEST A MINIMUM 48 HOURS
NOTICE BEFORE YOU DIG, DRILL OR BLAST - STOP AND CALL:
TEXAS ONE CALL SYSTEM / 1-800-DIG-TESS (344-8377). THE
GENERAL CONTRACTOR IS TO COORDINATE WITH THE FACILITY
OWNER.
UTILITY LOCATION NOTICE:
THE LOCATION OF EXISTING UTILITIES SHOWN IN THESE
CONSTRUCTION DOCUMENTS ARE APPROXIMATE AND BASED ON
EXISTING PLANS AND DATA FURNISHED BY THE UTILITY
COMPANIES. IT REMAINS THE RESPONSIBILITY OF THE GENERAL
CONTRACTOR AND HIS SUB-CONTRACTORS TO VERIFY THE
LOCATION AND DEPTH OF ALL EXISTING UTILITIES THAT MAY BE
IN CONFLICT WITH THE PLANNED CONSTRUCTION. ANY DAMAGE
TO THE EXISTING UTILITIES SHALL BE REPAIRED AT THE
GENERAL CONTRACTOR'S EXPENSE, AT NO ADDITIONAL COST TO
THE OWNER OR A/E TEAM.
RLG CIVIL / STRUCTURAL ENGINEERING
12001 N. CENTRAL EXP. STE 300
DALLAS, TX 75243
MR. JEFF BETHKE, PE
T. 214.739.8100
CAMPOS ENGINEERING
1331 RIVER BEND DR.
DALLAS, TX 75247
MR. FRED C. CRABTREE, JR., PE
T. 214.696.6291
ENAPAY, LLC
MESQUITE, TX 75149
207 WEST MAIN STREET
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
IKERD
DECATUR, TX 76234
1604 W BUSINESS 380, STE 100
MR. WILL IKERD, PE
T. 214.382.9811
VA NORTH TEXAS HEALTHCARE
ENGINEER SERVICES
BLD: 9 ROOM: 118
MR. JOSE SANCHEZ GONZALEZ
T. 214.857.4830
GNR ESTIMATING SERVICES, LLC
304 TRYALL DRIVE
RUNAWAY BAY, TX 76426
MR. THEODORE E. GARNER
T. 210.487.1127
IFC BID PACKAGE
THE FOLLOWING DOCUMENTS ARE REQUIRED FOR THE GC
TO SUBMIT A COMPLETE BID PACKAGE:
01 A COMPLETE SET OF CONSTRUCTION DOCUMENTS AS
LISTED ON C8/A-001.
02 PROJECT MANUAL VOLUME 1 - CIVIL / STRUCTURAL /
MECHANICAL & ELECTRICAL / GENERAL CONDITIONS
03 THE DESIGN NARRATIVE ( FOR REFERENCE ONLY)
DATED OCTOBER 13, 2023
04 GEOTECHNICAL REPORT DATED MAY 20, 2022
TERRACON PROJECT NUMBER: 94225110-R1
CONTACT THE VA'S CONTRACTING OFFICERS REPRESENTATIVE
(COR) IF ITEMS 1 THROUGH 6 ARE NOT INCLUDED IN THE BID
PACKAGE. THE VA'S COR IS MR. JOSE SANCHEZ GONZALEZ /
214-857-4830.
FORCE PROTECTION
THE PERIMETER REINFORCED 12" THICK X 8' TALL CONCRETE
MASONARY WALL AND THE STEEL FENCES AND A TRAFFIC
CONTROL GATE ARE TO COMPLY WITH THE FOLLOWING:
• VA PHYSICAL SECURITY DESIGN MANUAL (PDSM) FOR
LIFE SAFETY PROTECTED FACILITIES (JANUARY 2015)
• VA PHYSICAL SECURITY DESIGN STANDARDS DATA
DEFINITIONS (RESTRICTED)
• SINGLE DEGREE OF FREEDOM STRUCTURAL RESPONSE
LIMITS FOR ANTITERRORISM DESIGN, U.S.ARMY CORPS
OF ENGINEERS PROTECTIVE DESIGN CENTER TECHNICAL
REPORT, PDC-TR 06-08, REVISION 1 (JANUARY 2008).
THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR
COMPLYING WITH THESE REQUIREMENTS.
F3 ABBREVIATIONS AND ANNOTATIONS LEGEND F8 PROJECT SCOPE
B7 PROJECT DATA AND CODE INFO
C5 GENERAL PROJECT NOTES
F7 ALTERNATES
/2
/4
/2
/4
/8
/1
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:
/8
EA:CLIENT:
P R
O J E
C T
N U
M B
E R
1 2 3 4 5 6 7 8
A-001
INDEX AND GENERAL
INFORMATION
AE UPGRADE UTILITY
GPSITE SURVEY
10-13-2023
2737 SHERMAN ROAD / GRAND PRAIRIE, TEXAS
75051
EA02.0702
A E
U P
G R
A D
E U
T
IL
IT
Y
G P
S
IT
E S
U R
V E
Y
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
549-23-723
E A
.0
10-13-2023
A6 DEFINITIONS
B6 UTILITY NOTES
F6 IFC BID PACKAGE
C8 INDEX TO DRAWINGS
ARCHITECTURE
A-000 COVER SHEET
A-001 INDEX AND GENERAL INFORMATION
A-002A ARCHITECTURAL SITE PLAN DEMO
A-002B ARCHITECTURAL SITE PLAN NEW
CIVIL
C01.00 COVERSHEET
C01.01 PRIVATE GENERAL NOTES
C01.02 PUBLIC GENERAL NOTES
C02.00 DEMOLITION PLAN
C03.00 DIMENSIONAL CONTROL PLAN
C04.00 GRADING & DRAINAGE PLAN
C05.00 UTILITY PLAN
C06.00 EROSION CONTROL PLAN
C07.00 PRIVATE DETAIL SHEET
C07.01 PRIVATE DETAIL SHEET
C07.02 VA DETAIL SHEET
MECHANICAL
M001 MECHANICAL SYMBOL LEGEND
M002 MECHANICAL GENERAL NOTES
M100 MECHANICAL SITE PLAN
M410 MECH ENLARGED PLAN - PHASE 1
M420 MECH ENLARGED PLAN - PHASE 2
M421 MECHANICAL ENLARGED PLAN - PHASE 2
M430 MECH ENLARGED PLAN - PHASE 3
M500 MECHANICAL DETAILS
M600 MECHANICAL SCHEDULES
M701 MECHANICAL CONTROLS
ELECTRICAL
E001 ELEC SYMBOL LEGEND AND NOTES
E101 ELECTRICAL SITE PLAN - PHASE 1
E102 ELECTRICAL SITE PLAN - PHASE 2
E103 ELECTRICAL SITE PLAN - PHASE 3
E601 ELECTRICAL PANEL SCHEDULES
E702 ELECTRICAL ONE LINE DIAGRAM
F5 FORCE PROTECTION
STRUCTURAL
S0.00 STRUCTURAL ABBREVIATIONS AND LEGEND
S0.01 GENERAL NOTES
S0.02 SPECIAL INSPECTIONS
S1.00 FOUNDATION PLAN
S2.00 TYPICAL FOUNDATION DETAILS
S2.01 FOUNDATION DETAILS
S N
E
HP
ET
SNNYL
R E
G O
R
E T
RA
C
H
I
E
S
T
I
E R
D
T
S
T E X
A6
S
O F
3 3A T
E
T
C
E R
G
REVISION SCHEDULE
No. DESCRIPTION DATE
REVISION 01 - REMOVE DEDUCTIVE ALTERNATES
FROM THE PROJECT.
REMOVE DEDUCTIVE ALTERNATES 11/6/2024
M702 MECHANICAL CONTROLS
M703 MECHANICAL CONTROLS
2 ADDENDUM 01 - REV 02 3/11/2025
E801 ELECTRICAL DETAILS
FOUND
1/2" IRON ROD
0.72'N 3.14'E
FOUND 1/2"
IRON ROD
ENCOMPASS
FOUND
1/2" IRON ROD
0.38'S 0.27'W
S89°57'51"E 535.00'(R/S)
N89°57'51"W 535.00'(R/S)
N '0 "W
.0 R S
N89°57'51"W 241.16'(R/S)
S89°57'51"E 243.59'(R/S)
CONC CURBCONC CURB
T
T
B "B
AC
D
E
RLG CIVIL / STRUCTURAL ENGINEERING
12001 N. CENTRAL EXP. STE 300
DALLAS, TX 75243
MR. JEFF BETHKE, PE
T. 214.739.8100
CAMPOS ENGINEERING
1331 RIVER BEND DR.
DALLAS, TX 75247
MR. FRED C. CRABTREE, JR., PE
T. 214.696.6291
ENAPAY, LLC
MESQUITE, TX 75149
207 WEST MAIN STREET
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
IKERD
DECATUR, TX 76234
1604 W BUSINESS 380, STE 100
MR. WILL IKERD, PE
T. 214.382.9811
VA NORTH TEXAS HEALTHCARE
ENGINEER SERVICES
BLD: 9 ROOM: 118
MR. JOSE SANCHEZ GONZALEZ
T. 214.857.4830
GNR ESTIMATING SERVICES, LLC
304 TRYALL DRIVE
RUNAWAY BAY, TX 76426
MR. THEODORE E. GARNER
T. 210.487.1127
1 STORY BRICK AND CONCRETE BUILDING
DIAGIONAL HATCH INDICATES
THE APPROXIMATE LIMITATIONS
OF THE DEMOLITION PROJECT AREA.
REFER TO THE CIVIL AND MEP DRAWINGS
FOR PHASING AND EQUIPMENT
INSTALLATIONS.
31' - 11"
APPROX. 61'-0"
85' - 2 1/4"
11' - 6"
A /A
-0 A
A2/A-002A
A3/A-002A
B 1/
A -0
A
B2/A-002A
B3/A-002A
C2/A-002A
C3/A-002A
D2/A-002A
D3/A -0
02A
E2/A-002A
E3/A -0
02A
F2/A-002A
F /A
-0 A
TEMPORARY SERVICE ROAD
NEW PACT CLINIC BLDG. ADDITION
DELIVERIES
CONCRETE PAD AND CHAIN LINK FENCE
12'-0" WIDE UNDERGROUND EASEMENT /
VOL. 5498 PAGE 675 (D.R.T.C.T.)
12'-0" WIDE UNDERGROUND EASEMENT /
VOL. 5471 PAGE 636 (D.R.T.C.T.)
CONCRETE PADS
ASPHALT PAVEMENT
C O
N C
R E
T E
W A
L K
CONCRETE PAD W /
OXYGEN METER
C O
N C
R E
T E
C U
R B
A N
D G
U T
T E
R
CONCRETE PAVEMENT
METAL CARPORT
CONCRETE
PAVEMENT
C O
N C
R E
T E
C U
R B
A N
D G
U T
T E
R
C O
N C
R E
T E
C U
R B
A N
D G
U T
T E
R
CONCRETE CURB AND GUTTER
25' WIDE INGRESS / EGRESS EASEMENT
DOC # D206094589 D.R.T.C.T.
DETENTION POND DRAINAGE EASEMENT
DOC # 206094589 D.R.T.C.T.
N.I.C.
HOSPITAL BLVD. (50' W.)
CONCRETE PAVEMENT
40' - 6"
THIS PORTION OF THE EXISTING
BUILDING IS TO REMAIN
THIS PORTION OF THE EXISTING
BUILDING IS TO REMAIN
/2
/4
/2
/4
/8
/1
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:
/8
EA:CLIENT:
P R
O J E
C T
N U
M B
E R
1 2 3 4 5 6 7 8
A-002A
ARCHITECTURAL SITE PLAN
DEMO
AE UPGRADE UTILITY
GPSITE SURVEY
10-13-2023 Checker Author
2737 SHERMAN ROAD / GRAND PRAIRIE, TEXAS
75051
EA02.0702
A E
U P
G R
A D
E U
T
IL
IT
Y
G P
S
IT
E S
U R
V E
Y
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
E A
.0
10-13-2023
3/64" = 1'-0"
SITE PLAN DEMOF4
A1 PHOTO_01 A2 PHOTO_02 A3 PHOTO_03
B1 PHOTO_04 B2 PHOTO_05 B3 PHOTO_06
C2 PHOTO_07 C3 PHOTO_08
D2 PHOTO_09 D3 PHOTO_10
E2 PHOTO_11 E3 PHOTO_12
F2 PHOTO_13 F3 PHOTO_14
PLAN
NORTH
S N
E
HP
ET
SNNYL
R E
G O
R
E T
RA
C
H
I
E
S
T
I
E R
D
T
S
T E X
A6
S
O F
3 3A T
E
T
C
E R
G
REVISION SCHEDULE
No. DESCRIPTION DATE
RLG CIVIL / STRUCTURAL ENGINEERING
12001 N. CENTRAL EXP. STE 300
DALLAS, TX 75243
MR. JEFF BETHKE, PE
T. 214.739.8100
CAMPOS ENGINEERING
1331 RIVER BEND DR.
DALLAS, TX 75247
MR. FRED C. CRABTREE, JR., PE
T. 214.696.6291
ENAPAY, LLC
MESQUITE, TX 75149
207 WEST MAIN STREET
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
IKERD
DECATUR, TX 76234
1604 W BUSINESS 380, STE 100
MR. WILL IKERD, PE
T. 214.382.9811
VA NORTH TEXAS HEALTHCARE
ENGINEER SERVICES
BLD: 9 ROOM: 118
MR. JOSE SANCHEZ GONZALEZ
T. 214.857.4830
GNR ESTIMATING SERVICES, LLC
304 TRYALL DRIVE
RUNAWAY BAY, TX 76426
MR. THEODORE E. GARNER
T. 210.487.1127
1 STORY BRICK AND CONCRETE BUILDING
FUTURE DENTAL CLINIC
N.I.C.
E X
IS
T
IN
G
C O
N C
R E
T E
C U
R B
A N
D G
U T
T E
R
E X
IS
T
IN
G
A S
P H
A L T
P A
V E
M E
N T
E X
IS
T
IN
G
C O
N C
R E
T E
P A
V E
M E
N T
E X
IS
T
IN
G
C O
N C
R E
T E
C U
R B
A N
D G
U T
T E
R
DELIVERIES
NEW BUILDING EXPANSION
NEW CONCRETE PAVEMENT
FOR THE TRUCK COURTYARD
TEMPORARY ASPHALT SERVICE DRIVE
NEW CONCRETE CURB AND GUTTER
NEW CURB AND GUTTER
24' - 0"
31' - 1 1/2" 16' - 0" 35' - 11"
12' - 11 3/4"
34' - 0" 5' - 10 1/4"
19' - 9 7/8"
/2
81' - 7"
3' - 6"
REFER TO B3 & C3/A-002B. 4'-0" EGRESS GATE TO BE INCLUDED.
REFER TO B3 & C3/A-002B. 4'-0" EGRESS GATE TO BE INCLUDED.
REFER TO F3/A-002B
UNDERGROUND UTILITY BYPASS
AND UGE(N) ROUGH-IN-CONDUIT
FOR CONNECTION TO THE DENTAL
CLINIC
PACTDNTL
CONCRETE PAD IN THE BASEMENT FOR BOILERS
8' - 5 7/8"
/8
20' - 0" 16' - 2 5/8"
5' - 8 5/8"
7' - 0"
/8
/4
7' - 0"
9' - 6"
11' - 0"
11' - 0"
6' - 0"
10' - 0"
7' - 6"
10' - 6"
4' - 6"
27' - 1 1/2" 31' - 11"
STACKED BOND / BLACK MORTAR /
BURNISHED BLOCK - BASIS OF DESIGN
GRAND BLANC CEMENT PRODUCTS /
CAST STONE CAP
COORDINATE THE INSTALLATION OF GRADE BEAMS / PIERS
AND CONCRETE BLOCK WALLS WITH THE PLANNED LOCATIONS
OF THE UTILITY YARD INFRASTRUCTURE.
/2
/4
/2
/4
/8
/1
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:
/8
EA:CLIENT:
P R
O J E
C T
N U
M B
E R
1 2 3 4 5 6 7 8
A-002B
ARCHITECTURAL SITE PLAN
NEW
AE UPGRADE UTILITY
GPSITE SURVEY
10-13-2023
2737 SHERMAN ROAD / GRAND PRAIRIE, TEXAS
75051
EA02.0702
A E
U P
G R
A D
E U
T
IL
IT
Y
G P
S
IT
E S
U R
V E
Y
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
E A
.0
10-13-2023
PLAN
NORTH
3/64" = 1'-0"
SITE PLAN NEWF5
B3 PHOTO_15
BASIS OF DESIGN - IMPASSE II ANTI-SCALE FENCE / 8'-0" TALL / BLACK
C3 PHOTO_16
BASIS OF DESIGN - IMPASSE II / 4' WIDE EGRESS GATE / AUTOMATIC GATE OPENER / BLACK
F3 PHOTO_17
BASIS OF DESIGN - TRANSPORT TRAVERSE II / 8' TALL / BLACK
S N
E
HP
ET
SNNYL
R E
G O
R
E T
RA
C
H
I
E
S
T
I
E R
D
T
S
T E X
A6
S
O F
3 3A T
E
T
C
E R
G
REVISION SCHEDULE
No. DESCRIPTION DATE
C2 PHOTO_07
REFER TO C2/A-002B FOR
DUMPSTER GATES
NO BRICK / REINFORCED
CONCRETE MASONRY WALL
- REF TO STRUCT
A
B
C
C
A-002B
ALL WORK IN CLOUD HAS BEEN
REMOVED FROM THE PROJECT.
C01.00
COVER SHEET
2737 SHERMAN ST
GRAND PRAIRIE, TARRANT COUNTY, TEXAS, 75051
3" =1
1/ 2"
'-0
1"
'-0
3/ 4"
'-0
1/ 2"
'-0
1/ 4"
'-0
1/ 8"
'-0
1/
'-0
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:
03/
8"
'-0
EA:CLIENT:
PR
O
JE
C
T N
U M
BE
R
1 2 3 4 5 6 7 8
AE UPGRADE UTILITY
GP SITE SURVEY
10-13-2023
2737 SHERMAN ROAD / GRAND PRAIRIE, TEXAS
75051
EA02.0702
AE
U
PG
R
AD
E
U
TI
LI
TY
G
PS
IT
E
SU
R
VE
Y
IS
SU
ED
F
O R
C O
N
ST
R U
C
TI
O N
EA
.0
REVISION SCHEDULE
No. DESCRIPTION DATE
RLG
12001 N. CENTRAL EXP. STE 300
DALLAS, TX 75243
MR. JEFF BETHKE, PE
T. 214.739.8100
CAMPOS ENGINEERING
1331 RIVER BEND DR.
DALLAS, TX 75247
MR. FRED C. CRABTREE, JR., PE
T. 214.696.6291
ENAPAY, LLC
MESQUITE, TX 75149
207 WEST MAIN STREET
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
IKERD
DECATUR, TX 76234
1604 W BUSINESS 380, STE 100
MR. WILL IKERD, PE
T. 214.382.9811
VA
ENGINEER SERVICES
BLD: 9 ROOM: 118
MR. ALEX MULLER-POITEVIEN M.E.
T. 214.857.1005 EXT-73830
GNR ESTIMATING SERVICES, LLC
304 TRYALL DRIVE
RUNAWAY BAY, TX 76426
MR. THEODORE E. GARNER
T. 210.487.1127
TBPE FIRM REG. F-493
549-23-723
Sheet List Table
C01.00 COVER SHEET
C01.01 PRIVATE GENERAL NOTES
C01.02 PUBLIC GENERAL NOTES
C02.00 DEMOLITION PLAN
C03.00 PAVING & DIMENSIONAL CONTROL PLAN
C04.00 GRADING & DRAINAGE PLAN
C05.00 UTILITY PLAN
C06.00 EROSION CONTROL PLAN
C07.00 PRIVATE DETAIL SHEET
C07.01 PRIVATE DETAIL SHEET
C07.02 VA DETAIL SHEET
REVIEW DRAWN DATE FILE NUMBER
TARRANT COUNTY, TEXAS
CITY OF GRAND PRAIRIE
RLG CONSULTING ENGINEERS
5601 BRIDGE STREET #420 FORT WORTH, TX 76112
WWW.RLGINC.COM TBPE FIRM REG. F-493
AE UPGRADE UTILITY GP SITE SURVEY
2737 SHERMAN STREET
10/13/2023
SHEET
RLGRLG
3" =1
1/ 2"
'-0
1"
'-0
3/ 4"
'-0
1/ 2"
'-0
1/ 4"
'-0
1/ 8"
'-0
1/
'-0
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:
03/
8"
'-0
" 2
EA:CLIENT:
PR
O
JE
C
T N
U M
BE
R
1 2 3 4 5 6 7 8
AE UPGRADE UTILITY
GP SITE SURVEY
10-13-2023
2737 SHERMAN ROAD / GRAND PRAIRIE, TEXAS
75051
EA02.0702
AE
U
PG
R
AD
E
U
TI
LI
TY
G
PS
IT
E
SU
R
VE
Y
IS
SU
ED
F
O R
C O
N
ST
R U
C
TI
O N
EA
.0
REVISION SCHEDULE
No. DESCRIPTION DATE
RLG
12001 N. CENTRAL EXP. STE 300
DALLAS, TX 75243
MR. JEFF BETHKE, PE
T. 214.739.8100
CAMPOS ENGINEERING
1331 RIVER BEND DR.
DALLAS, TX 75247
MR. FRED C. CRABTREE, JR., PE
T. 214.696.6291
ENAPAY, LLC
MESQUITE, TX 75149
207 WEST MAIN STREET
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
IKERD
DECATUR, TX 76234
1604 W BUSINESS 380, STE 100
MR. WILL IKERD, PE
T. 214.382.9811
VA
ENGINEER SERVICES
BLD: 9 ROOM: 118
MR. ALEX MULLER-POITEVIEN M.E.
T. 214.857.1005 EXT-73830
GNR ESTIMATING SERVICES, LLC
304 TRYALL DRIVE
RUNAWAY BAY, TX 76426
MR. THEODORE E. GARNER
T. 210.487.1127
TBPE FIRM REG. F-493
549-23-723
C01.01
PRIVATE GENERAL NOTES
C01.01
PRIVATE GENERAL NOTES
TARRANT COUNTY, TEXAS
CITY OF GRAND PRAIRIE
RLG CONSULTING ENGINEERS
5601 BRIDGE STREET #420 FORT WORTH, TX 76112
WWW.RLGINC.COM TBPE FIRM REG. F-493
AE UPGRADE UTILITY GP SITE SURVEY
2737 SHERMAN STREET
10/13/2023
SHEET
RLGRLG
3" =1
1/ 2"
'-0
1"
'-0
3/ 4"
'-0
1/ 2"
'-0
1/ 4"
'-0
1/ 8"
'-0
1/
'-0
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:
03/
8"
'-0
" 2
EA:CLIENT:
PR
O
JE
C
T N
U M
BE
R
1 2 3 4 5 6 7 8
AE UPGRADE UTILITY
GP SITE SURVEY
10-13-2023
2737 SHERMAN ROAD / GRAND PRAIRIE, TEXAS
75051
EA02.0702
AE
U
PG
R
AD
E
U
TI
LI
TY
G
PS
IT
E
SU
R
VE
Y
IS
SU
ED
F
O R
C O
N
ST
R U
C
TI
O N
EA
.0
REVISION SCHEDULE
No. DESCRIPTION DATE
RLG
12001 N. CENTRAL EXP. STE 300
DALLAS, TX 75243
MR. JEFF BETHKE, PE
T. 214.739.8100
CAMPOS ENGINEERING
1331 RIVER BEND DR.
DALLAS, TX 75247
MR. FRED C. CRABTREE, JR., PE
T. 214.696.6291
ENAPAY, LLC
MESQUITE, TX 75149
207 WEST MAIN STREET
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
IKERD
DECATUR, TX 76234
1604 W BUSINESS 380, STE 100
MR. WILL IKERD, PE
T. 214.382.9811
VA
ENGINEER SERVICES
BLD: 9 ROOM: 118
MR. ALEX MULLER-POITEVIEN M.E.
T. 214.857.1005 EXT-73830
GNR ESTIMATING SERVICES, LLC
304 TRYALL DRIVE
RUNAWAY BAY, TX 76426
MR. THEODORE E. GARNER
T. 210.487.1127
TBPE FIRM REG. F-493
549-23-723
C01.02
PUBLIC GENERAL NOTES
C01.02
PUBLIC GENERAL NOTES
TARRANT COUNTY, TEXAS
CITY OF GRAND PRAIRIE
RLG CONSULTING ENGINEERS
5601 BRIDGE STREET #420 FORT WORTH, TX 76112
WWW.RLGINC.COM TBPE FIRM REG. F-493
AE UPGRADE UTILITY GP SITE SURVEY
2737 SHERMAN STREET
10/13/2023
SHEET
RLGRLG
3" =1
1/ 2"
'-0
1"
'-0
3/ 4"
'-0
1/ 2"
'-0
1/ 4"
'-0
1/ 8"
'-0
1/
'-0
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:
03/
8"
'-0
EA:CLIENT:
PR
O
JE
C
T N
U M
BE
R
1 2 3 4 5 6 7 8
AE UPGRADE UTILITY
GP SITE SURVEY
10-13-2023
2737 SHERMAN ROAD / GRAND PRAIRIE, TEXAS
75051
EA02.0702
AE
U
PG
R
AD
E
U
TI
LI
TY
G
PS
IT
E
SU
R
VE
Y
IS
SU
ED
F
O R
C O
N
ST
R U
C
TI
O N
EA
.0
REVISION SCHEDULE
No. DESCRIPTION DATE
RLG
12001 N. CENTRAL EXP. STE 300
DALLAS, TX 75243
MR. JEFF BETHKE, PE
T. 214.739.8100
CAMPOS ENGINEERING
1331 RIVER BEND DR.
DALLAS, TX 75247
MR. FRED C. CRABTREE, JR., PE
T. 214.696.6291
ENAPAY, LLC
MESQUITE, TX 75149
207 WEST MAIN STREET
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
IKERD
DECATUR, TX 76234
1604 W BUSINESS 380, STE 100
MR. WILL IKERD, PE
T. 214.382.9811
VA
ENGINEER SERVICES
BLD: 9 ROOM: 118
MR. ALEX MULLER-POITEVIEN M.E.
T. 214.857.1005 EXT-73830
GNR ESTIMATING SERVICES, LLC
304 TRYALL DRIVE
RUNAWAY BAY, TX 76426
MR. THEODORE E. GARNER
T. 210.487.1127
TBPE FIRM REG. F-493
549-23-723
C02.00
DEMOLITION PLAN
DEMOLITION PLAN
C02.00
TARRANT COUNTY, TEXAS
CITY OF GRAND PRAIRIE
RLG CONSULTING ENGINEERS
5601 BRIDGE STREET #420 FORT WORTH, TX 76112
WWW.RLGINC.COM TBPE FIRM REG. F-493
AE UPGRADE UTILITY GP SITE SURVEY
2737 SHERMAN STREET
10/13/2023
SHEET
RLGRLG
3" =1
1/ 2"
'-0
1"
'-0
3/ 4"
'-0
1/ 2"
'-0
1/ 4"
'-0
1/ 8"
'-0
1/
'-0
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:
03/
8"
'-0
EA:CLIENT:
PR
O
JE
C
T N
U M
BE
R
1 2 3 4 5 6 7 8
AE UPGRADE UTILITY
GP SITE SURVEY
10-13-2023
2737 SHERMAN ROAD / GRAND PRAIRIE, TEXAS
75051
EA02.0702
AE
U
PG
R
AD
E
U
TI
LI
TY
G
PS
IT
E
SU
R
VE
Y
IS
SU
ED
F
O R
C O
N
ST
R U
C
TI
O N
EA
.0
REVISION SCHEDULE
No. DESCRIPTION DATE
RLG
12001 N. CENTRAL EXP. STE 300
DALLAS, TX 75243
MR. JEFF BETHKE, PE
T. 214.739.8100
CAMPOS ENGINEERING
1331 RIVER BEND DR.
DALLAS, TX 75247
MR. FRED C. CRABTREE, JR., PE
T. 214.696.6291
ENAPAY, LLC
MESQUITE, TX 75149
207 WEST MAIN STREET
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
IKERD
DECATUR, TX 76234
1604 W BUSINESS 380, STE 100
MR. WILL IKERD, PE
T. 214.382.9811
VA
ENGINEER SERVICES
BLD: 9 ROOM: 118
MR. ALEX MULLER-POITEVIEN M.E.
T. 214.857.1005 EXT-73830
GNR ESTIMATING SERVICES, LLC
304 TRYALL DRIVE
RUNAWAY BAY, TX 76426
MR. THEODORE E. GARNER
T. 210.487.1127
TBPE FIRM REG. F-493
549-23-723
C03.00
PAVING & DIMENSIONAL CONTROL PLAN
C03.00
PAVING & DIMENSIONAL
CONTROL PLAN
TARRANT COUNTY, TEXAS
CITY OF GRAND PRAIRIE
RLG CONSULTING ENGINEERS
5601 BRIDGE STREET #420 FORT WORTH, TX 76112
WWW.RLGINC.COM TBPE FIRM REG. F-493
AE UPGRADE UTILITY GP SITE SURVEY
2737 SHERMAN STREET
10/13/2023
SHEET
RLGRLG
3" =1
1/ 2"
'-0
1"
'-0
3/ 4"
'-0
1/ 2"
'-0
1/ 4"
'-0
1/ 8"
'-0
1/
'-0
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:
03/
8"
'-0
EA:CLIENT:
PR
O
JE
C
T N
U M
BE
R
1 2 3 4 5 6 7 8
AE UPGRADE UTILITY
GP SITE SURVEY
10-13-2023
2737 SHERMAN ROAD / GRAND PRAIRIE, TEXAS
75051
EA02.0702
AE
U
PG
R
AD
E
U
TI
LI
TY
G
PS
IT
E
SU
R
VE
Y
IS
SU
ED
F
O R
C O
N
ST
R U
C
TI
O N
EA
.0
REVISION SCHEDULE
No. DESCRIPTION DATE
RLG
12001 N. CENTRAL EXP. STE 300
DALLAS, TX 75243
MR. JEFF BETHKE, PE
T. 214.739.8100
CAMPOS ENGINEERING
1331 RIVER BEND DR.
DALLAS, TX 75247
MR. FRED C. CRABTREE, JR., PE
T. 214.696.6291
ENAPAY, LLC
MESQUITE, TX 75149
207 WEST MAIN STREET
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
IKERD
DECATUR, TX 76234
1604 W BUSINESS 380, STE 100
MR. WILL IKERD, PE
T. 214.382.9811
VA
ENGINEER SERVICES
BLD: 9 ROOM: 118
MR. ALEX MULLER-POITEVIEN M.E.
T. 214.857.1005 EXT-73830
GNR ESTIMATING SERVICES, LLC
304 TRYALL DRIVE
RUNAWAY BAY, TX 76426
MR. THEODORE E. GARNER
T. 210.487.1127
TBPE FIRM REG. F-493
549-23-723
C04.00
GRADING & DRAINAGE PLAN
C04.00
GRADING & DRAINAGE PLAN
TARRANT COUNTY, TEXAS
CITY OF GRAND PRAIRIE
RLG CONSULTING ENGINEERS
5601 BRIDGE STREET #420 FORT WORTH, TX 76112
WWW.RLGINC.COM TBPE FIRM REG. F-493
AE UPGRADE UTILITY GP SITE SURVEY
2737 SHERMAN STREET
10/13/2023
SHEET
RLGRLG
3" =1
1/ 2"
'-0
1"
'-0
3/ 4"
'-0
1/ 2"
'-0
1/ 4"
'-0
1/ 8"
'-0
1/
'-0
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:
03/
8"
'-0
EA:CLIENT:
PR
O
JE
C
T N
U M
BE
R
1 2 3 4 5 6 7 8
AE UPGRADE UTILITY
GP SITE SURVEY
10-13-2023
2737 SHERMAN ROAD / GRAND PRAIRIE, TEXAS
75051
EA02.0702
AE
U
PG
R
AD
E
U
TI
LI
TY
G
PS
IT
E
SU
R
VE
Y
IS
SU
ED
F
O R
C O
N
ST
R U
C
TI
O N
EA
.0
REVISION SCHEDULE
No. DESCRIPTION DATE
RLG
12001 N. CENTRAL EXP. STE 300
DALLAS, TX 75243
MR. JEFF BETHKE, PE
T. 214.739.8100
CAMPOS ENGINEERING
1331 RIVER BEND DR.
DALLAS, TX 75247
MR. FRED C. CRABTREE, JR., PE
T. 214.696.6291
ENAPAY, LLC
MESQUITE, TX 75149
207 WEST MAIN STREET
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
IKERD
DECATUR, TX 76234
1604 W BUSINESS 380, STE 100
MR. WILL IKERD, PE
T. 214.382.9811
VA
ENGINEER SERVICES
BLD: 9 ROOM: 118
MR. ALEX MULLER-POITEVIEN M.E.
T. 214.857.1005 EXT-73830
GNR ESTIMATING SERVICES, LLC
304 TRYALL DRIVE
RUNAWAY BAY, TX 76426
MR. THEODORE E. GARNER
T. 210.487.1127
TBPE FIRM REG. F-493
549-23-723
C05.00
UTILITY PLAN
C05.00
UTILITY PLAN
TARRANT COUNTY, TEXAS
CITY OF GRAND PRAIRIE
RLG CONSULTING ENGINEERS
5601 BRIDGE STREET #420 FORT WORTH, TX 76112
WWW.RLGINC.COM TBPE FIRM REG. F-493
AE UPGRADE UTILITY GP SITE SURVEY
2737 SHERMAN STREET
10/13/2023
SHEET
RLGRLG
3" =1
1/ 2"
'-0
1"
'-0
3/ 4"
'-0
1/ 2"
'-0
1/ 4"
'-0
1/ 8"
'-0
1/
'-0
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:
03/
8"
'-0
EA:CLIENT:
PR
O
JE
C
T N
U M
BE
R
1 2 3 4 5 6 7 8
AE UPGRADE UTILITY
GP SITE SURVEY
10-13-2023
2737 SHERMAN ROAD / GRAND PRAIRIE, TEXAS
75051
EA02.0702
AE
U
PG
R
AD
E
U
TI
LI
TY
G
PS
IT
E
SU
R
VE
Y
IS
SU
ED
F
O R
C O
N
ST
R U
C
TI
O N
EA
.0
REVISION SCHEDULE
No. DESCRIPTION DATE
RLG
12001 N. CENTRAL EXP. STE 300
DALLAS, TX 75243
MR. JEFF BETHKE, PE
T. 214.739.8100
CAMPOS ENGINEERING
1331 RIVER BEND DR.
DALLAS, TX 75247
MR. FRED C. CRABTREE, JR., PE
T. 214.696.6291
ENAPAY, LLC
MESQUITE, TX 75149
207 WEST MAIN STREET
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
IKERD
DECATUR, TX 76234
1604 W BUSINESS 380, STE 100
MR. WILL IKERD, PE
T. 214.382.9811
VA
ENGINEER SERVICES
BLD: 9 ROOM: 118
MR. ALEX MULLER-POITEVIEN M.E.
T. 214.857.1005 EXT-73830
GNR ESTIMATING SERVICES, LLC
304 TRYALL DRIVE
RUNAWAY BAY, TX 76426
MR. THEODORE E. GARNER
T. 210.487.1127
TBPE FIRM REG. F-493
549-23-723
C06.00
EROSION CONTROL PLAN
C06.00
EROSION CONTROL PLAN
TARRANT COUNTY, TEXAS
CITY OF GRAND PRAIRIE
RLG CONSULTING ENGINEERS
5601 BRIDGE STREET #420 FORT WORTH, TX 76112
WWW.RLGINC.COM TBPE FIRM REG. F-493
AE UPGRADE UTILITY GP SITE SURVEY
2737 SHERMAN STREET
10/13/2023
SHEET
RLGRLG
3" =1
1/ 2"
'-0
1"
'-0
3/ 4"
'-0
1/ 2"
'-0
1/ 4"
'-0
1/ 8"
'-0
1/
'-0
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:
03/
8"
'-0
" 2
EA:CLIENT:
PR
O
JE
C
T N
U M
BE
R
1 2 3 4 5 6 7 8
AE UPGRADE UTILITY
GP SITE SURVEY
10-13-2023
2737 SHERMAN ROAD / GRAND PRAIRIE, TEXAS
75051
EA02.0702
AE
U
PG
R
AD
E
U
TI
LI
TY
G
PS
IT
E
SU
R
VE
Y
IS
SU
ED
F
O R
C O
N
ST
R U
C
TI
O N
EA
.0
REVISION SCHEDULE
No. DESCRIPTION DATE
RLG
12001 N. CENTRAL EXP. STE 300
DALLAS, TX 75243
MR. JEFF BETHKE, PE
T. 214.739.8100
CAMPOS ENGINEERING
1331 RIVER BEND DR.
DALLAS, TX 75247
MR. FRED C. CRABTREE, JR., PE
T. 214.696.6291
ENAPAY, LLC
MESQUITE, TX 75149
207 WEST MAIN STREET
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
IKERD
DECATUR, TX 76234
1604 W BUSINESS 380, STE 100
MR. WILL IKERD, PE
T. 214.382.9811
VA
ENGINEER SERVICES
BLD: 9 ROOM: 118
MR. ALEX MULLER-POITEVIEN M.E.
T. 214.857.1005 EXT-73830
GNR ESTIMATING SERVICES, LLC
304 TRYALL DRIVE
RUNAWAY BAY, TX 76426
MR. THEODORE E. GARNER
T. 210.487.1127
TBPE FIRM REG. F-493
549-23-723
C07.00
PRIVATE DETAIL SHEET
C07.00
PRIVATE DETAIL SHEET
TARRANT COUNTY, TEXAS
CITY OF GRAND PRAIRIE
RLG CONSULTING ENGINEERS
5601 BRIDGE STREET #420 FORT WORTH, TX 76112
WWW.RLGINC.COM TBPE FIRM REG. F-493
AE UPGRADE UTILITY GP SITE SURVEY
2737 SHERMAN STREET
10/13/2023
SHEET
RLGRLG
3" =1
1/ 2"
'-0
1"
'-0
3/ 4"
'-0
1/ 2"
'-0
1/ 4"
'-0
1/ 8"
'-0
1/
'-0
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:
03/
8"
'-0
" 2
EA:CLIENT:
PR
O
JE
C
T N
U M
BE
R
1 2 3 4 5 6 7 8
AE UPGRADE UTILITY
GP SITE SURVEY
10-13-2023
2737 SHERMAN ROAD / GRAND PRAIRIE, TEXAS
75051
EA02.0702
AE
U
PG
R
AD
E
U
TI
LI
TY
G
PS
IT
E
SU
R
VE
Y
IS
SU
ED
F
O R
C O
N
ST
R U
C
TI
O N
EA
.0
REVISION SCHEDULE
No. DESCRIPTION DATE
RLG
12001 N. CENTRAL EXP. STE 300
DALLAS, TX 75243
MR. JEFF BETHKE, PE
T. 214.739.8100
CAMPOS ENGINEERING
1331 RIVER BEND DR.
DALLAS, TX 75247
MR. FRED C. CRABTREE, JR., PE
T. 214.696.6291
ENAPAY, LLC
MESQUITE, TX 75149
207 WEST MAIN STREET
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
IKERD
DECATUR, TX 76234
1604 W BUSINESS 380, STE 100
MR. WILL IKERD, PE
T. 214.382.9811
VA
ENGINEER SERVICES
BLD: 9 ROOM: 118
MR. ALEX MULLER-POITEVIEN M.E.
T. 214.857.1005 EXT-73830
GNR ESTIMATING SERVICES, LLC
304 TRYALL DRIVE
RUNAWAY BAY, TX 76426
MR. THEODORE E. GARNER
T. 210.487.1127
TBPE FIRM REG. F-493
549-23-723
C07.01
PRIVATE DETAIL SHEET
C07.01
PRIVATE DETAIL SHEET
TARRANT COUNTY, TEXAS
CITY OF GRAND PRAIRIE
RLG CONSULTING ENGINEERS
5601 BRIDGE STREET #420 FORT WORTH, TX 76112
WWW.RLGINC.COM TBPE FIRM REG. F-493
AE UPGRADE UTILITY GP SITE SURVEY
2737 SHERMAN STREET
10/13/2023
SHEET
RLGRLG
3" =1
1/ 2"
'-0
1"
'-0
3/ 4"
'-0
1/ 2"
'-0
1/ 4"
'-0
1/ 8"
'-0
1/
'-0
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:
03/
8"
'-0
" 2
EA:CLIENT:
PR
O
JE
C
T N
U M
BE
R
1 2 3 4 5 6 7 8
AE UPGRADE UTILITY
GP SITE SURVEY
10-13-2023
2737 SHERMAN ROAD / GRAND PRAIRIE, TEXAS
75051
EA02.0702
AE
U
PG
R
AD
E
U
TI
LI
TY
G
PS
IT
E
SU
R
VE
Y
IS
SU
ED
F
O R
C O
N
ST
R U
C
TI
O N
EA
.0
REVISION SCHEDULE
No. DESCRIPTION DATE
RLG
12001 N. CENTRAL EXP. STE 300
DALLAS, TX 75243
MR. JEFF BETHKE, PE
T. 214.739.8100
CAMPOS ENGINEERING
1331 RIVER BEND DR.
DALLAS, TX 75247
MR. FRED C. CRABTREE, JR., PE
T. 214.696.6291
ENAPAY, LLC
MESQUITE, TX 75149
207 WEST MAIN STREET
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
IKERD
DECATUR, TX 76234
1604 W BUSINESS 380, STE 100
MR. WILL IKERD, PE
T. 214.382.9811
VA
ENGINEER SERVICES
BLD: 9 ROOM: 118
MR. ALEX MULLER-POITEVIEN M.E.
T. 214.857.1005 EXT-73830
GNR ESTIMATING SERVICES, LLC
304 TRYALL DRIVE
RUNAWAY BAY, TX 76426
MR. THEODORE E. GARNER
T. 210.487.1127
TBPE FIRM REG. F-493
549-23-723
C07.02
VA DETAIL SHEET
C07.02
VA DETAIL SHEET
N
SCALE:
COCO
S
MM
S S
M M
M M
H
T
CO2
M
R
CO
VFD
R D R D
FD
FSD
SD
FD
SD
BDD
BDD
FSD
SP
SP
S S
M M
T T
H H
CO2
CO2
B B
DP
DP
DPS
DPS
AF
AF
CRD
SHEET 1/8" = 1'-0"
TOP TITLE
BOTTOM TITLE
F&T F&T
DUCTWORK SYMBOLSVALVE SYMBOLS
GATE VALVE
PIPE & FITTING SYMBOLS
MANUAL VOLUME DAMPER
GRAPHIC SYMBOLS
CONTROL SYMBOLS
VERTICAL RUN ON PLAN
READ LEFT TO RIGHT
4" CWS
H W
R C
W R
H W
S
2" HWS
2" HWR
4" CWR
READ TOP TO BOTTOM
4" CHWS
3" PCD(F) *
2" HPS
2" LPS
4" CHWR
C W
S
3" PCD(F) *
2" HPS
2" LPS
4" CHWR
4" CHWS
L P
S C
H W
R C
H W
S P
C D
(F
CHWS
CHWR
LPS
PCD(F) *
HWS
HWR
CWR
H P
S
HPS
CWS
PIPING DESIGNATION
2" CHWS
XXX-1
SYSTEM SERVICE ABBREVIATION
NOMINAL PIPE SIZE
MISCELLANEOUS SYMBOLS
EQUIPMENT DESIGNATION
(IN INCHES)
SINGLE LINE PIPE/DUCTWORK BREAK
KEYED NOTE
POINT OF DISCONNECTION
POINT OF CONNECTION (NEW TO EXISTING)
HORIZONTAL RUN ON PLAN
MULTI-LINE KEY
4" CWR
4" CWS
2" HWS
2" HWR
(D)
(R)
(E)
(N)
LIMIT OF EXISTING ITEMS TO BE REMOVED
NEW ITEM (NOTATION SHOWN AS NECESSARY
FOR CLARIFICATION)
EXISTING ITEM TO REMAIN (NOTATION
SHOWN AS NECESSARY FOR CLARIFICATION)
EXISTING ITEM TO BE RELOCATED (NOTATION
SHOWN AS NECESSARY FOR CLARIFICATION)
EXISTING ITEM TO BE DEMOLISHED (NOTATION
SHOWN AS NECESSARY FOR CLARIFICATION)
EXISTING ITEMS TO BE DEMOLISHED
EXISTING ITEMS TO REMAIN
NEW ITEMS (PIPING/DUCTWORK/EQUIPMENT)
RECTANGULAR DUCT/STANDARD BREAK
* - (F) INDICATES FUTURE PIPING ON RACK
BOP 12'-6"
AFF
LOWER
PIPE RACK
BOP 13'-6"
AFF UPPER
PIPE RACK
BOP 12'-6"
AFF
LOWER
PIPE RACK
BOP 13'-6"
AFF UPPER
PIPE RACK
SINGLE LINEDOUBLE LINE
PIPE
WELDED JOINT
SCREWED JOINT
GROOVED END JOINT
FLANGED JOINT
GROOVED END ADAPTER FLANGE
FLANGED COUPLING ADAPTER
UNION
TEE FITTING
REDUCER - ECCENTRIC
REDUCER - CONCENTRIC
CAP
ANCHOR
BLIND FLANGE
FLOW ORIFICE PLATE
ELBOW, 90 DEGREE -
CHANGE IN
DIRECTION
TOWARD VIEWER
ELBOW, 90 DEGREE -
CHANGE IN
DIRECTION
AWAY FROM VIEWER
LATERAL
NOTE:
WELDED FITTINGS ARE SHOWN FOR DOUBLE LINE PIPING.
FITTINGS WITH OTHER END CONDITIONS ARE SIMILAR.
PRESSURE GAUGE
WITH
GAUGE COCK
STEAM TRAP, TYPE AS NOTED
IB = INVERTED BUCKET
F&T = FLOAT &
THERMOSTATIC
TH = THERMODYNAMIC
BP = BALANCED PRESSURE
AIR SEPARATOR
ELBOW, 90 DEGREE
(LONG RADIUS
UON)
ELBOW, 45 DEGREE
(LONG RADIUS
UON)
VENTURI FLOW METER
CONTROL VALVES
CLEANOUT
(F) FUTURE ITEM (NOTATION SHOWN AS
NECESSARY FOR CLARIFICATION)
2"
SECTION NO.
DIRECTION OF CUTTING PLANE
SHEET NO. ON WHICH
THE SECTION IS
DRAWN
A
M5.01
DRAWING TITLE
DETAIL NO. AND SHEET NO.
SCALE OF FLOOR PLAN,
SECTION OR DETAIL
M3.01
AREA OF ENLARGED PLAN
OR
DETAIL
SHEET NO. ON
WHICH
ENLARGED
DETAIL IS DRAWN
CHWS
DOUBLE LINE PIPE/ROUND DUCTWORK BREAK
NEW CONNECTION TO EXISTING ITEM
1 REVISION DELTA
STUB END OR FLANGE
ADAPTER W/ FLANGE RING
GENERIC FLEXIBLE
COUPLING
(REFER TO SPECIFICATIONS)
2"CHWS
- OR -
TEE FITTING,
BRANCH TOWARD VIEWER
TEE FITTING,
BRANCH AWAY FROM VIEWER
PIPING WITH INSULATION
(WHEN SHOWN FOR
CLARITY)
THERMOWELL
WITH
THERMOMETER
STRAINER - "Y"
TYPE
WITH BLOW DOWN
WATER METER
PUMP, ARROW INDICATES FLOW
SINGLE LINEDOUBLE LINEDESCRIPTION DESCRIPTION
CHECK VALVE
BUTTERFLY VALVE
BALL VALVE
DIAPHRAGM VALVE
GLOBE VALVE
PLUG VALVE
PRESSURE REDUCING VALVE
BALANCING VALVE
DIRECTION OF FLOW / SLOPE
PRESSURE RELIEF VALVE
AUTOMATIC AIR VENT
MANUAL AIR VENT
SINGLE LINEDOUBLE LINE DESCRIPTION
TWO-WAY, TWO POSITION
CONTROL VALVE W/ SOLENOID
TWO-WAY, MODULATING
CONTROL VALVE
TWO-WAY, TWO POSITION
CONTROL VALVE
THREE-WAY, TWO POSITION
CONTROL VALVE
THREE-WAY, MODULATING
CONTROL VALVE
WALL MOUNTED DEVICES
HUMIDITY SENSOR/HUMIDISTAT
TEMPERATURE SENSOR/THERMOSTAT
CARBON DIOXIDE SENSOR
MOTION SENSOR
OVERRIDE SWITCH
CARBON MONOXIDE SENSOR
VARIABLE FREQUENCY DRIVE
EQUIPMENT SYMBOLS
ROOFTOP EXHAUST FAN (ROOF PLAN VIEW)
ROOFTOP EXHAUST FAN (ROOF PLAN VIEW)
WALL LOUVER WITH POSITIVE OR NEGATIVE AIRFLOW
DOOR UNDERCUT (SPECIFY CFM IF REQUIRED)UC
DOOR LOUVER (SPECIFY CFM IF REQUIRED)
LD
AxB
RECTANGULAR OR SQUARE DUCT,
DIMENSIONS ARE IN INCHES, MIN.
INSIDE CLEAR, A = WIDTH, B= HEIGHT
AxB
A"Ø
ROUND DUCT DIMENSIONS ARE IN
INCHES, MIN. INSIDE CLEAR,
A = DIAMETER
A"Ø
AxBØ
FLAT OVAL DUCT DIMENSIONS ARE
IN INCHES, MIN. INSIDE CLEAR,
A = WIDTH, B= HEIGHT
AxBØ
DUCTWORK RISE (R) OR DROP (D)
RELATIVE TO DIRECTION OF
AIRFLOW
DIRECTION OF AIR FLOW
SUPPLY AIR OR POSITIVE
PRESSURE DUCTWORK, SECTION
TOWARDS/AWAY VIEWER
RETURN AIR OR NEGATIVE
PRESSURE DUCTWORK, AIRFLOW
TOWARDS VIEWER
EXHAUST AIR DUCTWORK,
AIRFLOW TOWARDS VIEWER
RIGID ROUND DUCTWORK,
AIRFLOW TOWARDS VIEWER
FIRE DAMPER
FIRE/SMOKE DAMPER
SMOKE DAMPER
BACKDRAFT DAMPER
SMOKE DETECTOR
STATIC PRESSURE SENSOR
MOTORIZED DAMPER
TEMPERATURE SENSOR
DESCRIPTIONSINGLE LINEDOUBLE LINE
HUMIDITY SENSOR
CARBON DIOXIDE SENSOR
BAROMETRIC DAMPER
DIFFERENTIAL PRESSURE SENSOR
DIFFERENTIAL PRESSURE
SAFETY SHUT-DOWN
RELAY
AIRFLOW PROOF SWITCH
ACCESS PANEL/CLEANOUT
SUPPLY AIR OR POSITIVE
PRESSURE DUCTWORK, AIRFLOW
AWAY FROM VIEWER
RETURN AIR OR NEGATIVE
PRESSURE DUCTWORK, AIRFLOW
AWAY FROM VIEWER
EXHAUST AIR DUCTWORK,
AIRFLOW AWAY FROM VIEWER
RIGID ROUND DUCTWORK,
AIRFLOW AWAY FROM
VIEWER
TRANSITION - ECCENTRIC REDUCER
TRANSITION - CONCENTRIC REDUCER
TRANSITION - SQUARE TO ROUND
90° ELBOW WITHOUT TURNING
VANES (RETURN OR EXHAUST
DUCTWORK ONLY)
90° ELBOW WITH TURNING VANES
(REQUIRED ON SUPPLY
DUCTWORK)
45° ELBOW WITHOUT TURNING
VANES (RETURN OR EXHAUST
DUCTWORK ONLY)
45° ELBOW WITH TURNING VANES
(REQUIRED ON SUPPLY DUCTWORK)
RADIUS 90° ELBOW (R = 1.5W)
RW
RADIUS 45° ELBOW (R = 1.5W)
RW
SPIN-IN FITTING WITH FLEXIBLE
DUCTWORK, DIMENSIONS ARE IN
INCHES, MIN. INSIDE CLEAR,
A = DIAMETER
AIR DISTRIBUTION
CEILING RADIATION DAMPER
LINEAR SLOT DIFFUSER
ROUND SUPPLY AIR DIFFUSER
SIDEWALL REGISTER
8"Ø
TYP OF 2
AIR DISTRIBUTION CALLOUT
RETURN AIR OR TRANSFER AIR GRILLE
A"ØA"Ø
INLINE EXHAUST FAN (EF), AIR HANDLING UNIT
(AHU), CONDENSING UNIT (CU)
BRANCH TAKE-OFF WITH MVD
CONICAL TAKE-OFF WITH MVD
DUCTWORK SYMBOLS
SINGLE LINEDOUBLE LINE DESCRIPTION
SUPPLY AIR DIFFUSER
EXHAUST AIR GRILLE
REFER TO SCHEDULE FOR ADDITIONAL INFORMATION
DUCT MOUNTED GRILLE
DETAIL NUMBER
MECHANICAL SYMBOL LEGEND
THIS IS A STANDARD LEGEND SHEET. SOME INFORMATION ON
THIS SHEET MAY NOT NECESSARILY APPLY TO THIS PROJECT.
S1
RLG
12001 N. CENTRAL EXP. STE 300
DALLAS, TX 75243
MR. CLAYTON E. NOLAN, PE
T. 214.739.8100
CAMPOS ENGINEERING
1331 RIVER BEND DR.
DALLAS, TX 75247
MR. FRED C. CRABTREE, JR., PE
T. 214.696.6291
ENAPAY, LLC
MESQUITE, TX 75149
207 WEST MAIN STREET
MR. ROGER L. STEPHENS, AIA
T. 214.505.0659
IKERD
DECATUR, TX 76234
1604 W BUSINESS 380, STE 100
MR. WILL IKERD, PE
T. 214.382.9811
VA
ENGINEER SERVICES
BLD: 9 ROOM: 118
MR. ALEX MULLER-POITEVIEN M.E.
T. 214.857.1005 EXT-73830
GNR ESTIMATING SERVICES, LLC
304 TRYALL DRIVE
RUNAWAY BAY, TX 76426
MR. THEODORE E. GARNER
T. 210.487.1127
FRED C. CRABTREE, JR.
109799
L IC E N S ED
P R
O
FES S IONA L ENG
IN
E E
R
STATE OF TEXASCAMPOS
ENGINEERING
1331 River Bend Drive Dallas, Texas 75247
(214) 696-6291 campos@camposengineering.com Registration No. F-001731 Project Number:
/2
/4
/2
/4
/8
/1
If this sheet is not 30" by 42", it is a reduced print; and thus, must be scaled accordingly.
A
1 2 3 4 5 6 7 8
B
C
D
E
F
A
B
C
D
E
F
OFFICE OF
FACILITIES
MANAGEMENT
PROJECT NUMBER:
BUILDING NUMBER:
VA DRAWING NUMBER:
DWG ____ OF ____
PROJECT TITLE:
LOCATION:
DATE: CHECKED: DRAWN:
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR
PROJECT DIRECTORY:
/8
EA:CLIENT:
P R
O J E
C T
N U
M B
E R
1 2 3 4 5 6 7 8
D23-3247.00 M001
MECHANICAL SYMBOL
LEGEND
AE UPGRADE UTILITY GP
SITE SURVEY
10-13-2023 FCC EAG
2737 SHERMAN ROAD / GRAND PRAIRIE, TEXAS
75051
EA02.0904
A E
U P
G R
A D
E U
T
IL
IT
Y
G P
S
IT
E S
U R
V E
Y D
E S
IG
N
D E
V E
L O
P M
E N
T
549-23-723
DESIGN DEVELOPMENT / 100%
E A
.0
10-13-2023
REVISION SCHEDULE
MECHANICAL GENERAL NOTES
1. ISOLATION VALVES SHALL BE PROVIDED IN ALL BRANCH PIPING AND AT EQUIPMENT CONNECTIONS.
2. PIPING CONNECTIONS TO ALL EQUIPMENT SHALL BE FABRICATED WITH THE ISOLATION VALVES, FLANGES AND/OR UNIONS
POSITIONED TO ALLOW REMOVAL AND SERVICE OF THE COMPONENT PARTS.
3. INSTALL MANUAL AIR VENTS AT THE HIGH POINTS OF THE PIPING SYSTEMS.
4. ROUTE PIPING IN AN ORDERLY MANNER AND MAINTAIN PROPER GRADES. INSTALL TO CONSERVE HEADROOM AND TO CREATE MINIMUM INTERFERENCE WITH USE OF SPACE. ROUTE ALL PIPING PARALLEL TO BUILDING LINES UON. GROUP PIPING AT COMMON BOP ELEVATIONS WHENEVER PRACTICAL. PIPES LOCATED IN CONCEALED SPACES SHALL BE ROUTED CLOSE TO BUILDING
STRUCTURE UON.
5. INSTALL PIPING TO ALLOW FOR EXPANSION AND CONTRACTION WITHOUT STRESSING PIPE OR EQUIPMENT CONNECTED.
6. INSTALL VALVES WITH STEMS UPRIGHT OR HORIZONTAL, NOT INVERTED.
7. INSTALL VALVES AND EQUIPMENT IN ACCESSIBLE LOCATIONS. INSTALL ACCESS DOORS IN PARTITIONS OR CEILINGS WHERE VALVES
AND EQUIPMENT WOULD OTHERWISE BE INACCESSIBLE.
8. WHEN SOCKET WELD OR SOLDER END VALVES ARE INSTALLED, SPECIAL CARE SHALL BE TAKEN TO AVOID OVERHEATING AND
DAMAGING THE VALVE BODY, TRIM OR PACKING. DAMAGED VALVES SHALL BE REPLACED AT CONTRACTOR'S EXPENSE.
9. IDENTIFY EACH PIPE WITH LABELING AS REQUIRED BY SPECIFICATIONS.
10. SLEEVE ALL PIPING THAT PENETRATES FIRE RATED WALLS, FLOORS AND PARTITIONS. PENETRATIONS SHALL BE SEALED WITH A U.L.
LISTED ASSEMBLY TO PROVIDE A RATING EQUAL TO OR GREATER THAN THAT OF THE PENETRATED WALL, FLOOR OR PARTITION.
11. SLEEVE ALL PIPING THAT PENETRATES EXTERIOR BUILDING WALLS AND GRADE BEAMS. SEAL PENETRATIONS WATERTIGHT.
12. COORDINATE WITH OTHER TRADES BEFORE FABRICATION OR INSTALLATION OF ANY SYSTEMS.
13. EXISTING DUCTWORK, PIPING AND EQUIPMENT SHOWN ON THESE DRAWINGS INDICATES THE GENERAL LOCATION AND ROUTING. THE ACTUAL LOCATION SHALL BE DETERMINED BY THE CONTRACTOR WHO SHALL COORDINATE ALL WORK WITH ALL TRADES NECESSARY
TO INSTALL NEW DUCTWORK, PIPING OR EQUIPMENT AS SHOWN ON THE DRAWING.
14. THESE DRAWINGS DO NOT NECESSARILY SHOW ALL OFFSETS OR ELEVATION DIFFERENCES WHICH MAY BE NECESSARY FOR THE
COMPLETE INSTALLATION. THESE SHALL BE PROVIDED AS REQUIRED TO PROVIDE A COMPLETE AND FUNCTIONAL SYSTEM AT NO
ADDITIONAL COST TO THE CONTRACT.
15. ALL NEW DUCTWORK SHALL BE EXTERNALLY INSULATED AS SPECIFIED.
16. WHERE REMOVAL OF EXISTING DUCTWORK OR PORTIONS OF ANY AIR SYSTEM IS NECESSARY, THE DUCT SHALL BE PATCHED AND
SEALED AIRTIGHT USING PATCH OF SAME MATERIAL AND EQUAL OR GREATER THICKNESS AS EXISTING. PATCHES SHALL BE ATTACHED WITH SHEET METAL SCREWS OR OTHER MEANS OF POSITIVE ATTACHMENT (WELDING, BONDING, ETC.) AS SPECIFIED FOR THE PARTICULAR DUCT SYSTEM. NEW INSULATION SHALL BE EQUAL TO OR BETTER THAN EXISTING AND SHALL BE PATCHED AND
SEALED TO MATCH EXISTING INSULATION AND MAINTAIN VAPOR BARRIER.
17. COORDINATE ALL REMODEL WORK WITH NEW CONSTRUCTION AND OTHER TRADES.
18. THE CONTRACTOR SHALL ADJUST AND BALANCE ALL MECHANICAL SYSTEMS TO DESIGN SETTINGS AS SHOWN AND SHALL REBALANCE TO RESTORE SETTINGS OF SYSTEMS TEMPORARILY ALTERED FOR THE PURPOSES OF COMPLETING THE WORK OF THIS
PROJECT.
19. NOTIFY AND COORDINATE WITH THE OWNER AT LEAST SEVEN DAYS PRIOR TO SHUTDOWN OF ANY BUILDING SERVICES OR
EQUIPMENT. SHUTDOWN TIME SHALL BE KEPT TO A MINIMUM.
20. ANY ITEMS DAMAGED DURING DEMOLITION SHALL BE REPLACED WITH NEW MATERIALS TO MATCH EXISTING.
21. CONTRACTOR SHALL PROVIDE TEMPORARY DUCTWORK, ELECTRICAL SERVICE, PIPING OR OTHER BUILDING SERVICES AS REQUIRED TO KEEP OTHER AREAS IN OPERATION DURING REMODELING. NOTIFY OWNER PRIOR TO SHUT-DOWN FOR ANY TEMPORARY SERVICE REQUIREMENTS. ALL TEMPORARY WORK SHALL BE COMPLETELY REMOVED ONLY AFTER NEW SERVICES ARE COMPLETELY
INSTALLED AND FUNCTIONAL.
22. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR LOCATIONS OF CEILING-MOUNTED HVAC DEVICES AND EQUIPMENT.
23. DUCT ROUTING CHANGES MADE BY THE CONTRACTOR FOR THE PURPOSE OF ACCOMMODATING FIELD CONDITIONS SHALL INCLUDE FIRE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS IN RATED PARTITIONS AS SHOWN IN ORIGINAL ROUTING ARRANGEMENTS.
24. FURNISH AND INSTALL ACCESS DOORS (AD) IN THE DUCTWORK IMMEDIATELY ADJACENT TO EACH FIRE DAMPER AND EACH FIRE/SMOKE DAMPER. PARTITIONS SHALL BE PROVIDED WITH ACCESS DOORS TO PROVIDE SERVICE AND ACCESS TO DAMPER
ACCESS DOORS.
25. PROVIDE FIRE AND COMBINATION FIRE/SMOKE DAMPERS WHERE REQUIRED BY CODE. FIRE, SMOKE, AND COMBINATION FIRE/SMOKE
DAMPERS SHALL BE UL LISTED, SHALL BEAR THE UL LABEL AND SHALL COMPLY WITH NFPA BULLETIN NO. 90A. FULLY-OPEN DAMPERS
SHALL NOT HAVE ANY PROJECTIONS INTO THE AIRSTREAM.
26. ABANDONED DUCT SHALL BE REMOVED WHERE INDICATED ON THE DRAWINGS. DUCT REMAINING IN PLACE SHALL BE CAPPED, SEALED AIR TIGHT AT POINT(S) OF DEMOLITION, AND INSULATED TO MATCH EXISTING..
27. NEW HOLES THROUGH EXISTING FLOORS SHALL BE CORE DRILLED. ALL CORES SHALL BE X-RAYED PRIOR TO CORING.
28. ALL DUCT SIZES SHOWN HEREIN REPRESENT INSIDE CLEAR DIMENSIONS. EXTERNAL SHEET METAL DIMENSIONS OF DUCTWORK THAT IS SPECIFIED TO BE INTERNALLY LINED SHALL BE ADJUSTED BY THE CONTRACTOR TO ALLOW FOR THICKNESS OF LINING.
29. THE OWNER SHALL HAVE THE OPTION TO DESIGNATE ANY MATERIALS REMOVED OR DEMOLISHED DURING THIS WORK AS "RECYCLABLE" AND SHALL HAVE FINAL DISPOSITION OVER THE DISPOSAL OF THESE MATERIALS. ALL MATERIALS
REMOVED/DEMOLISHED BY THE CONTRACTOR FOR THIS JOB AND NOT RETAINED BY THE OWNER FOR RECYCLING OR OTHER
PURPOSES SHALL BE DISPOSED OFF-SITE BY THE CONTRACTOR.
30. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL OF ANY EQUIPMENT DESIGNATED FOR REMOVAL. THE OWNER SHALL PROVIDE A LIST OF ITEMS THEY REQUIRE TO BE SALVAGED PRIOR TO THE START OF DEMOLITION. THE CONTRACTOR SHALL REMOVE THESE
ITEMS USING REASONABLE CARE TO MINIMIZE DAMAGE.
31. ANY AND ALL WATER CONNECTIONS MADE FOR THE PURPOSE OF CLEANING TOOLS OR THE WORK AREA OR FOR ANY OTHER CONSTRUCTION-RELATED PURPOSES SHALL BE MADE ONLY TO DOMESTIC WATER HOSE BIBBS OR TO CONTRACTOR-SUPPLIED
WATER SOURCES. APPROVED BACKFLOW PREVENTION DEVICES SHALL BE USED AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION. CONNECTIONS SHALL NOT BE MADE TO FIRE WATER, CHILLED WATER, CONDENSER WATER, HEATING HOT WATER, DOMESTIC HOT WATER OR ANY OTHER TREATED WATER SOURCE UNLESS REQUIRED AS PART OF WORK ON THESE SYSTEMS.
32. EXCEPT WHERE REQUIRED AT EQUIPMENT NOZZLES, FLANGES SHALL BE RAISED FACE WELD-NECK.
33. INSTALL DIELECTRIC FITTINGS AT ALL FERROUS PIPE CONNECTIONS TO NON-FERROUS METALLIC PIPE OR EQUIPMENT.
34. BULLHEAD TEES SHALL NOT BE USED TO JOIN CONVERGING (RETURN) FLOWS, REGARDLESS OF ARRANGEMENT SHOWN ON PLANS.
35. PROVIDE ESCUTCHEON PLATES WHERE PIPES EXPOSED TO VIEW PENETRATE FINISHED WALLS, FLOORS AND CEILINGS. SPLIT-RING
ESCUTCHEON PLATES SHALL NOT BE USED UON.
36. PROVIDE CAPPED DRAIN VALVES AT LOW POINTS OF PIPING SYSTEMS AND AT EQUIPMENT CONNECTIONS. PROVIDE HOSE BIBB CONNECTIONS WITH CAPS AT DRAIN VALVES WHICH DO NOT DISCHARGE DIRECTLY OVER OR ARE NOT PIPED DIRECTLY TO AN
APPROPRIATE DRAIN.
37. PIPING, DUCTWORK OR EQUIPMENT CONNECTIONS OPENED BY DEMOLITION OR RENOVATION SHALL BE TEMPORARILY SEALED TO
KEEP OUT FOREIGN MATTER UNTIL SUCH TIME AS RECONNECTIONS ARE MADE.
ABBREVIATIONS
PHASEPH
FOOT, FEET
FOOT-POUND
FT
FT LB
PREHEAT COIL
PARTS PER MILLION
PHC
PRV
PPM
PRESSURE
PRESSURE SWITCH
PRESS
PS
PSF
PLUMBINGPLBG
POUNDS PER SQUARE FOOT
PRESSURE REDUCING VALVE
PSIG
PTAC
QUART
RELIEF, THERMAL RESISTANCE
QT
R
PACKAGED TERMINAL A/C
POUNDS PER SQUARE INCH GAUGE
POUNDS PER SQUARE INCHPSI
FINS PER INCH
GALLON
GENERATOR
GAUGE, GAGE
GALVANIZEDGALV
GAL
GEN
GA
FPI
GATE VALVE
GALLONS PER HOUR
HEATING COIL
GPH
HC
GTV
GALLONS PER DAYGPD
REFRIGERATION
RAC
REFR
RETURN
REDUCER
REVOLUTIONS
RELATIVE HUMIDITY
REFERENCE
RET
REV
RED
RH
REF
ROOM AIR CONDITIONER
REHEAT COIL
REHEAT VALVE
RHC
RHG
RHV
RPM
RS
RPS
RL
ROOF TOP UNIT
RELIEF VALVE
SATURATION
SUPPLY AIR
SECOND
RTU
RV
SAT
SA
S
REFRIGERANT HOT GAS
REFRIGERANT LIQUID
REVOLUTIONS PER MINUTE
REFRIGERANT SUCTION
REVOLUTIONS PER SECOND
HEAT GAIN
HEIGHT
HEAT PUMP, HORSEPOWER
HOUR
HIGH PRESSURE STEAM (>100 PSI)
HG
HGT
HPS
HPC
HP
HR
HUMIDISTAT
HEATING WATER
HUMIDITY SENSOR
HEATING WATER RETURN
HEATING WATER PUMP
HEATING WATER CIRCULATING PUMP
HEATING WATER COIL
HEATING WATER BOILER
HSTAT
HWR
HWP
HWCP
HWC
HWB
HW
HVAC
HS
HIGH PRESSURE CONDENSATE
HEATING, VENTILATION AND A/C
SPECIFIC GRAVITY, STEAM GAUGE
SENSIBLE HEAT GAIN
SENSIBLE HEAT
SENSIBLE HEAT RATIO
SG
SHG
SH
SHR
SHUT OFF VALVE
STATIC PRESSURE, SUMP PUMP
SPECIFICATION
SUPPLY
SOV
SP
SPEC
SPLY
SQUARE
STAINLESS STEEL
SQ
SSP
SST
SPS STATIC PRESSURE SENSOR
STAINLESS STEEL PIPE
SOLV SOLENOID VALVE
INPUT/OUTPUT
HERTZ (FREQUENCY)
HEATING WATER TANK
INVERT
INSIDE DIAMETER
INCHES WATER COLUMN
ID
I/O
HZ
HWT
INV
IN WC
INFRARED
KELVIN, THERMAL CONDUCTIVITY
IRON PIPE THREADED
IRON PIPE SIZE, INCHES PER SECOND
KILOWATT
POUNDS
THOUSAND FOOT-POUNDS
LEAVING AIR TEMPERATURE
KILOWATT HOUR
THOUSAND POUNDS
IR
K
KIP
KIP FT
LB
LAT
KWh
KW
IPT
IPS
IRON PIPEIP
SF SQUARE FEET
HEATING WATER SUPPLYHWS
RETURN AIRRA
HEADHD
A (0.5)
AAV
AC
AP
AD
AFF
AHU
ACU
AMB
AMP
APD
APPROX
ASC
AHJ
AS
ALT
AVG
B/B
B&S
AWG
BAL
BFC
BFV
BBR
BLDG
BFW
BFBP
BLR
BLW
BHP
BO
BOD
BOS
BOP
BTU
BV
BTUH
°C
C/C
BYP
CAP
CD
CF
CFS
CH
CHW
CHWP
CHWPP
CFM
CELSIUS [DEGREES]
COMPRESSED AIR (WORKING PRESS.)
AUTOMATIC AIR VENT
ACCESS PANEL
ACCESS DOOR, AREA DRAIN
ABOVE FINISHED FLOOR
AIR HANDLING UNIT
AMBIENT
AIR PRESSURE DROP
AIR SEPARATOR
ABOVE SUSPENDED CEILING
AUTHORITY HAVING JURISDICTION
AVERAGE
BELL & SPIGOT
BACK TO BACK
BALANCE
AIR CONDITIONING UNIT
ALTERNATING CURRENT
ALTITUDE
AMERICAN WIRE GAUGE
AMPERE
APPROXIMATE
BELOW FINISHED CEILING
BLOWOFF
CAPACITY
COOLING COIL
BYPASS
BALL VALVE
BRITISH THERMAL UNIT PER HOUR
BRITISH THERMAL UNIT
BOTTOM OF STEEL
BOTTOM OF PIPE
BOTTOM OF DUCT
BELOW
BOILER
BUILDING
BRAKE HORSEPOWER
BOILER FEED WATER
BOILER FEED BOOSTER PUMP
BUTTERFLY VALVE
CONDENSATE DRAIN
CHEMICAL FEED
CUBIC FEET PER MINUTE
CUBIC FEET PER SECOND
CHILLER
CHILLED WATER
CHILLED WATER PUMP
CHILLED WATER PRIMARY PUMP
BASE BOARD RADIATOR
STANDARD
STRAINER
STEAM
STD
STR
STWP
STM
SUCTION
SUPPLY
SAFETY VALVE
SUCT
SUP
SV
T
T&P
STEAM WORKING PRESSURE
TEMPERATURE SENSOR
TEMPERATURE AND PRESSURE
TEMPERATURE
TCV
TEMP
TD
TEMPERATURE CONTROL VALVE
TEMPERATURE DIFFERENCE
LINEAR FEET
LENGTH
LATENT HEAT GAIN
LATENT HEAT
LEAVING DRY BULB TEMPERATURE
LOW PRESSURE
LF
LG
LPC
LP
LHG
LH
LDBT
LOW TEMPERATURE HOT…
This is the start of the file's text. The full file is on GovTribe.