A06_-_Drawings.pdf
PDF 6 MB Posted
- Attached to
- JELA - INSTALL AIR COOLED CHILLER - PACC
- Solicitation number
- 140P5221R0051
About this file
This set of construction drawings and specifications is for installing a new air-cooled chiller system at the Prairie Acadian Cultural Center (PACC) within Jean Lafitte National Historical Park and Preserve. The project involves demolishing the existing water-cooled chiller, boiler, pumps and associated piping and controls, and installing a new air-cooled chiller, boiler, pumps, and controls integrated with the building automation system. Mechanical plans show the demolition and new work, including locations for the new chiller, boiler, pumps, tanks and associated piping and electrical connections. Details provide requirements for equipment pads, pipe supports, and controls integration. Diagrams show chilled water, hot water, and condenser water piping and instrumentation.
The related federal contract opportunity is to install the new air-cooled chiller system at PACC as designed in the construction documents, with responses due under Solicitation 140P5221R0051 for the National Park Service Southeast Region and Department of the Interior. The incumbent will demolish existing equipment and install a new air-cooled chiller, boiler, and associated HVAC components at the Prairie Acadian Cultural Center located in Jean Lafitte National Historical Park and Preserve in Louisiana.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PRAIRIE
ACADIAN
CULTURAL
CENTER (PACC)
LIBERTY
THEATER
COOLING TOWER
PARK AVENUE
S O
U T
H
N D
S T
R E
E T
S O
U T
H E
R
R D
S T
R E
E T
EXISTING GAS, CHILLED, HOT AND
CONDENSER WATER AND FIRE
PROTECTION WATER GAS METER
Project Manager Date
QUALITY DESIGN CERTIFICATION
OR
OR
Development (Title I)
Prepared in Accordance with Design by Design Development (Title I)
Construction Drawing Not Preceded
Approved by Superintendent on
Variance from Design Development (Title I)
Drawing No.
Date
STATEREGION COUNTY
NAME OF PARK
TITLE OF PROJECTCROFT & ASSOCIATES - P15PC00467
PRIME / ARCH / MEP:
CROFT & ASSOCIATES
KENNESAW, GEORGIA
SheetMark REVISION Date Initial
LOCATION WITHIN PARK
NATIONAL PARK SERVICE
DENVER SERVICE CENTER
UNITED STATES
DEPARTMENT OF THE INTERIOR
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
CONSTRUCTION DOCUMENTS
/1
/2
:1
:2
P M
INSTALL NEW AIR-COOLED CHILLER
SYSTEM IN PACC
PRAIRIE ACADIAN CULTURAL BUILDING
JEAN LAFITTE NATIONAL HISTORIC PARK
SOUTHEAST ST. LANDRY LOUISIANA
1 9
XX
XXXXXX
303852B
JEAN LAFITTE NATIONAL PARK AND PRESERVE
INDEX OF DRAWINGS
SHEET
SUB
SHEET TITLE OF SHEET
GENERAL
1 G001 COVER SHEET (IF NEEDED)
MECHANICAL DEMOLITION
2 MD101 MECHANICAL PLAN - DEMOLITION
MECHANICAL
3 M001 NOTES AND CALCULATIONS
4 M101 MECHANICAL PLAN - NEW WORK
5 M501 DETAILS
6 M502 DETAILS
7 M503 DETAILS
8 M504 DETAILS
9 M601 DIAGRAMS
Grand total: 9
SITE
250 PARK AVE
EUNICE, LA 70535
NOT TO SCALEG001
1 SITE PLAN
S
T
A
T
E
O
F LO
U
I S
I A
N
A
P
R
O
F
E
S
S
I O
N A
L E
N
G
I N
E
E
R
AMY E. HADLOW
License No.31314
02/12/2021
AHU-1
(EXISTING)
3"
GAS
LINE
6" F BELOW GRADE
3" CWR BELOW GRADE
3" CWS BELOW GRADE
3" HWS BELOW GRADE
3" CHWS BELOW GRADE
3" CHWR BELOW GRADE
1" CW BELOW GRADE
3" HWR BELOW GRADE
3" GAS BELOW GRADE
MD101
HP-1
D2
D1
D3
D4
D5
D6
D7
D8
D9
D10
FC-1
FC-2
D11
D13
D14
D15
D16
D17
D18
D20
D21
D16
D15
D17
D4
D14
TU-2
(EXISTING)
TU-3
(EXISTING)
TU-4
(EXISTING)
TU-5
(EXISTING)
TU-6
(EXISTING)
TU-7
(EXISTING)
TU-8
(EXISTING)
TU-1
(EXISTING)
PANEL A
PANEL A-1
PANEL MD
PANEL MS
HVAC
CONTROL
PANELS
M504
M503
M504
M503
CRAFTS
EXHIBITS
RECEPTION
PORCH
ENTRY
LOBBY
PRESENTATIONS
OFFICE MEN
WOMEN
KITCHEN
MULTI-PURPOSE
INFORMATION
REFRIGERANT LINES
D12
D12
CONTRACTOR
EQUIPMENT AND SUPPLY
LAY-DOWN AREA.
CONTRACTOR
FIELD OFFICE
SETUP LOCATION,
IF REQUIRED.
D22
CH-1
B-1
M504
M504
M503
M504
M504
M504
M503
3" GAS
(EXISTING)
3" DCW
D22
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
LOCATION WITHIN PARK
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
/1
/2
:1
:0
P M
MECHANICAL PLAN -
DEMOLITIONMD101
P. GORDY
P. GORDY
M. JOHNSON
2 9
PRAIRIE ACADIAN CULTURAL BUILDING XX
XXXXXX
303852B
JEAN LAFITTE NATIONAL HISTORIC PARK2021/02/12
SCALE
8 0 8 16
SCALE OF FEET
A
B L D
G
SCALE AMD101
1 MECHANICAL PLAN - DEMOLITION
SCALE BMD101
2 MECHANICAL PLAN - DEMOLITION - MECHANICAL ROOM
SCALE
SCALE OF FEET
2 0 2 4 B
DEMOLITION PLAN KEYNOTES
D1 CAP CHILLED WATER, HOT WATER, AND CONDENSER WATER SUPPLY AND RETURN PIPING AT WALL.
D2 DEMOLISH ALL DOMESTIC WATER PIPING DOWNSTEAM OF RPZA. EXISTING RPZA AND ALL UPSTREAM LINES AND RUNOUTS TO REMAIN
D3 EXISTING GAS LINE TO REMAIN, DEMOLISH APPROXIMATLEY 6'-0" OF DAMAGED/RUSTED GAS PIPE, DIRT LEG, AND UNIT CONNECTION AT BOILER
D4 EXISTING 6" FIRE WATER LINE TO REMAIN. (SHOWN FOR COORDINATION ONLY.)
D5 EXISTING GAS METER, SPLIT TO LIBERTY THEATER AND PACC. UTILITY COMPANY TO DEMOLISH AND REPLACE REGULATOR AT BUILDING WITH NEW GAS METER
TO SERVE PACC ONLY.
D6 PIPING THROUGH EXISTING UNDERGROUND TRENCH TO/FROM LIBERTY THEATER, COOLING TOWER AND EXISTING GAS METER
D7 EXISTING SERVICE/PIPING UNDERGROUND TRENCH
D8 EXISTING GAS PRESSURE GREGULATOR. UTILITY COMPANY TO DEMOLISH AND REPLACE WITH NEW GAS METER
D9 EXISTING COOLING TOWER TO BE ABANDONED IN PLACE.
D10 EXISTING HOT WATER SUPPLY AND RETURN TO VAV UNITS TO REMAIN.
D11 EXISTING PIPING. CAP AND ABANDON IN PLACE.
D12 EXISTING WATER SUPPLY PUMP TO REMAIN FOR REUSE. ASSOCIATED PIPING, VALVES, AND ACCESSORIES TO BE DEMOLISHED..
D13 DEMOLISH ALL EXISTING PIPING AND VALVE SERVING EXISTING AIR HANDLING UNIT.
D14 DEMOLISH EXISTING CONCRETE PAD.
D15 DEMOLISH EXISTING WATER COOLED CHILLER, EXPANSION TANKS, AIR SEPARATOR, AND ALL ASSOCIATED PIPING. DEMOLISH ELECTRICAL FEEDERS BACK TO
PANEL, AND DEMOLISH DISCONNECT. BREAKER TO REMAIN FOR REUSE.
D16 DEMOLISH ALL CHILLED WATER TANKS, AIR SEPARATORS, AND ALL ASSSOCIATED PIPING AS INDICATED.
D17 DEMOLISH EXISTING BOILER, VENT THROUGH ROOF, EXPANSION TANKS, AIR SEPARATOR, AND ASSOCIATED PIPING AS INDICATED. EXISTING ELECTRICAL TO
REMAIN FOR REUSE.
D18 DEMOLISH EXISTING CHILLED WATER PUMP AND ASSOCIATED PIPING, VALVES, AND ACCESSORIES.
D20 EXISTING WATER METER SERVING PACC AND LIBERTY THEATER. DISCONNECT LIBERTY THEATER DOMESTIC WATER SUPPLY BRANCH AND CAP STUB SO THAT EXISTING METER WILL SERVE ONLY SEALE BUILDING. CAP LIBERTY THEATER PIPING STUB AND ABANDON IN PLACE.
D21 EXISTING MULTI-SPLIT UNIT SERVING EXHIBIT AREA TO REMAIN AS BACKUP CONDITIONING AT THE REQUEST OF THE PARK. FOLLOW MANUFACTURER'S INSTRUCTIONS TO POWER DOWN UNIT AND TURN OFF THE UNIT AT THE DISCONNECT AT PROJECT CLOSEOUT, ONCE MAIN HVAC SYSTEM IS FULLY
OPERATIONAL. COORDINATE UNIT SHUTDOWN WITH CONTRACTING OFFICER.
D22 EXISTING CHILLED WATER SUPPLY AND RETURN TO BE DEMOLISHED
X
S
T
A
T
E
O
F LO
U
I S
I A
N
A
P
R
O
F
E
S
S
I O
N A
L E
N
G
I N
E
E
R
AMY E. HADLOW
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
LOCATION WITHIN PARK
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
/1
/2
:4
:1
P M
NOTES AND CALCULATIONSM001
P. GORDY
P. GORDY
M. JOHNSON
3 9
PRAIRIE ACADIAN CULTURAL BUILDING XX
XXXXXX
303852B
JEAN LAFITTE NATIONAL HISTORIC PARK2021/02/12
MODIFICATIONS TO THE CHILLED AND HOT WATER PUMP SEQUENCE OF OPERATION:
1. PUMPS SHALL OPERATE ON A LEAD-LAG ARRANGEMENT.
2. EACH PUMP SHALL ALTERNATE TIMES OF OPERATION AS INDICATED BY THE PARK
PERSONNEL.
3. WHEN PUMP IS SCHEDULED TO RUN BY THE EXISTING BUILDING AUTOMATION SYSTEM, THE
LEAD PUMP SHALL START AND THE PRESSURE SWITCH SHALL PROVE FLOW BY SENDING A
SIGNAL TO THE BUILDING AUTOMATION SYSTEM. IF LEAD PUMP FAILS TO START, THE
PRESSURE SWITCH SHALL NOT BE ACTIVATED, AN ALARM SHALL BE SENT TO THE BUILDING
AUTOMATION SYSTEM, AND THE LAG PUMP SHALL BE COMMANDED TO START, FOLLOWING
THE SAME SEQUENCE AS THE LEAD PUMP.
4. CHILLED WATER PUMPS SHALL OPERATE ON A 3-WAY CONSTANT SPEED PRIMARY CONTROL
WITH BYPASS FOR MINIMUM CHILLER FLOW.
5. AHU-1 HOT WATER VALVES SHALL OPERATE ON A 2-WAY VALVE CONTROL
6. CONDENSER WATER CONTROL WILL BE REMOVED FROM THE SYSTEM
GENERAL NOTES
1. THESE DRAWINGS ARE SCHEMATIC, AND ARE NOT REPRESENTATIVE OF ALL POTENTIAL CONDITIONS. CONTRACTOR IS
RESPONSIBLE FOR COORDINATION WITH ALL OTHER DISCIPLINES TO ENSURE PROPER INSTALLATION OF ALL SYSTEMS AND
EQUIPMENT.
2. WHEN EQUIPMENT OR PIPING IS SPECIFIED TO BE REMOVED, REMOVED ALL ASSOCIATED EQUIPMENT, PIPING, WIRING AND
HANGERS.
3. ONCE PIPING HAS BEEN EMOVED, PATCH ALL WALLS AND ROOF AS REQUIRED TO MAINTAIN INTEGRITY OF THE STRUCTURE.
2) INCLUDE FACTORY-FURNISHED NETWORK CARD COMPATIBLE WITH BOTH BACNET AND LONWORKS TO PROVIDE DIRECT INTEGRATION OF ALL
SENSORS, CONTROLS, SETPOINTS, AND ALARMS WITH EXISTING BAS SYSTEM
1) TURN DOWN RATIO: MINIMUM 8:1
NOTES:
B-1 AERCO AM399 399 395 40.0 30 160 180 120 1 60 300 87% 1
INPUT OUTPUT VOLTS PHASE FREQ (HZ)
OPER. WT.
(LBS)MARK
MFGR MODEL
CAPACITY (MBH)
FLOW
(GPM)
RELIEF
PRESS
(PSI)
EWT
(°F)
LWT (°F)
ELECTRICAL
THERMAL
EFFICIENCY
NOTES
BOILER SCHEDULE
2) CONTRACTOR TO FURNISH AND INSTALL NEW VFD FOR EXISTING PUMP TO BE REUSED. COORDINATE WITH...
1) CONTRACTOR TO FURNISH AND INSTALL NEW FACTORY-PROVIDED SUCTION DIFFUSER.
NOTES:
HWP-2 BELL & GOSSETT E-15101.25AD-ES END SUCT. 40 45 208 3 1.5 1,2
HWP-1 BELL & GOSSETT E-15101.25AD-ES END SUCT. 40 45 208 3 1.5 1,2
CHP-2 BELL & GOSSETT E-15101.25AD END SUCT. 100 60 208 3 5 1,2
CHP-1 BELL & GOSSETT E-15101.25AD END SUCT. 100 60 208 3 5 1,2
VOLTS PHASE HPMARK MFGR MODEL TYPE GPM
TOTAL HEAD
(FT)
ELECTRICAL
NOTES
PUMP SCHEDULE - EXISTING TO BE REUSED
2) INCLUDE FACTORY-FURNISHED NETWORK CARD COMPATIBLE WITH BOTH BACNET AND LONWORKS TO PROVIDE DIRECT INTEGRATION OF
ALL SENSORS, CONTROLS, SETPOINTS, AND ALARMS WITH EXISTING BAS SYSTEM
1) FURNISH AND INSTALL FACTORY-PROVIDED HURRICANE-RATED HAIL GUARDS TO PROTECT ALL COILS AND EQUIPMENT.
NOTES:
CH-1 CARRIER 30RAP040 40 92 52 42 6 95 86.4 100 208/3/60 - - 1
GPM °F IN °F OUT
MAX PD
(FT H2O)
CONDENSER
AIR °F MCA MOCP V/Ø/Hz
EER
(FULL LOAD)
NPLV
(BTU/Wh)MARK MFGR MODEL TONS
CHILLED WATER ELECTRICAL
NOTES
AIR COOLED CHILLER SCHEDULE
AS-2 ROLAIRTROL R-3F 40
AS-1 ROLAIRTROL R-3FB 92
MARK
MFGR MODEL
FLOW
(GPM)
AIR SEPARATOR SCHEDULE
ET-2 BELL & GOSSETT B-130LA 35
ET-1 BELL & GOSSETT B-130LA 34
BT-1 NILES CBT-24-072 210
MARK
MFGR MODEL
CAPACITY
(GAL)
TANK SCHEDULE
C) Upon completion of Testing and Balancing operations, controls contractor shall set system low and high point lockouts for
Pump Speed. Lockouts shall be password protected. Provide COR with passwords and a list of lockout high and low speeds, along with a written description of observed system behavior when these limits are exceeded.
B) Graphic user interface page shall include a display of all available monitored or controlled points on the boiler network card, including output and input values.
A) Controls contractor shall obtain all available points listed above from boiler network card. Supply additional sensors required to meet the control point requirements listed above only if the points are unavailable from the boiler.
GENERAL NOTES:
OUTDOOR AIR TEMP ENABLE SETPOINT
OAT ENA SP
X X
HOT WATER DISTRIBUTION SUPPLY TEMP
SETPOINT
HWS T SP
X X
HOT WATER RESET LOW LIMIT
HW RES LL
X X
HOT WATER RESET HIGH LIMIT
HW RES HL
X X
HOT WATER PUMP LEAD
HWP LEAD
X X
BAS COMMUNICATION STATE
BAS COM
X
OUTDOOR AIR TEMPERATURE LOCAL
OAT
X X X
HOT WATER TEMPERATURE CONTROL VALVE
HW T VLV
X X
HOT WATER SUPPLY TEMPERATURE LOCAL
HWS T
X X X X
HOT WATER RETURN TEMPERATURE LOCAL
HWR T
X X X X
HOT WATER DIFFERENTIAL PRESSURE
HW DP
X X X
HOT WATER BYPASS BALBE COMMAND
HW BYPV
X X
FLOW METER
FLW MTR
X X X
CARBON MONOXIDE SENSOR
CO SNSR
X X X X
BOILER PUMP 1 STATUS
BP1
X X
BOILER PUMP 1 START STOP OUTPUT
BP1
X X
BOILER PUMP 1 SPEED OUTPUT
BP1
X X
BOILER 1 STATUS
B1 STS
X X
BOILER 1 ENABLE COMMAND
B1 X X
BOILER 1 ALARM
B1 ALM
X X X
BOILER EMERGENCY SHUTDOWN SWITCH
BLR ESTOP
X X X
DESCRIPTION G
R
A H
P
IC
A N
A
LO
G H
A R
D W
A R
E I
N P
U T
A
I)
B
IN
A R
Y H
A R
D W
A R
E I
N P
U T
B
I)
A N
A
LO
G H
A R
D W
A R
E O
U T
P U
T
A O
B
IN
A R
Y H
A R
D W
A R
E O
U T
P U
T
B O
S O
F T
W A
R E
P O
IN
T
S
F T
H A
R D
W A
R E
I N
T E
R
LO
C K
H
D W
W
IR
E
LE
S S
W
LS
N E
T W
O R
K
N E
T
H
IG
H A
N A
LO
G
L
IM
IT
LO
W
A N
A
LO
G L
IM
IT
B
IN
A R
Y
LA
T
C H
D
IA
G N
O S
T
IC
S E
N S
O R
F A
IL
C O
M M
U N
IC
A
T
IO
N F
A
IL
POINTS ALARMS
POINTS LIST : HEATING PLANT SYSTEM
C) Upon completion of Testing and Balancing operations, controls contractor shall set system low and high point lockouts for Pump Speed. Lockouts shall be password protected. Provide COR with passwords and a list of lockout high and low speeds, along with a written description of observed system behavior when these limits are exceeded.
B) Graphic user interface page shall include a display of all available monitored or controlled points on the chiller network card, including output and input values.
A) Controls contractor shall obtain all available points listed above from chiller network card. Supply additional sensors required to meet the control point requirements listed above only if the points are...
GENERAL NOTES:
OUTDOOR AIR TEMP ENABLE SETPOINT
OAT ENA SP
X X
CHILLER 1 CHILLED WATER PUMP FAILURE
CH1 CHWP FAIL
X X X
CHILLED WATER SUPPLY TEMPERATURE
SETPOINT
CHW SUP TMP SP
X X
CHILLER PLANT ENABLE
SYS EN
X X
BAS COMMUNICATION STATE
BAS COM
X X X
OUTDOOR AIR TEMPERATURE LOCAL
OAT
X X X
OUTDOOR AIR RELATIVE HUMIDITY LOCAL
OAH
X X X
CHILLER 1 CHILLED WATER PUMP SPEED
CH1 CHWP
X X
CHILLER 1 CHILLED WATER PUMP STATUS
CH1 CHWP
X X
CHILLER 1 CHILLED WATER PUMP START STOP
CH1 CHWP
X X
CHILLER 1 CHILLED WATER PUMP REQUEST
FROM CHILLER
CH1 CHWP R
X X
CHILLER 1 CHILLED WATER FLOW STATUS
CH1 CHW FLW
X X
CHILLER 1 CHILLED WATER FLOW DIFFERENTIAL
PRESSURE
CH1 CHW DP
X X X X
CHILLED WATER SUPPLY DIFFERENTIAL
PRESSURE
CHW SYS DP
X X X X
CHILLED WATER SUPPLY TEMPERATURE
CHWS T
X X X X X
CHILLED WATER RETURN TEMPERATURE
CHWR T
X X X X X
CHILLED WATER BYPASS VALVE OUTPUT
CHW BYPV
X X
CHILLED WATER FLOW METER
CHW F
X X X X X
DESCRIPTION G
R
A P
H
IC
A N
A
LO
G H
A R
D W
A R
E I
N P
U T
A
I)
B
IN
A R
Y H
A R
D W
A R
E I
N P
U T
B
I)
A N
A
LO
G H
A R
D W
A R
E O
U T
P U
T
A O
B
IN
A R
Y H
A R
D W
A R
E O
U T
P U
T
B O
S O
F T
W A
R E
P O
IN
T
S
F T
H A
R D
W A
R E
I N
T E
R
LO
C K
H
D W
W
IR
E
LE
S S
W
LS
N E
T W
O R
K
N E
T
H
IG
H A
N A
LO
G
L
IM
IT
LO
W
A N
A
LO
G L
IM
IT
B
IN
A R
Y
LA
T
C H
D
IA
G N
O S
T
IC
S E
N S
O R
F A
IL
C O
M M
U N
IC
A
T
IO
N F
A
IL
POINTS ALARMS
POINTS LIST : COOLING PLANT SYSTEM
CF-1,2 WESSELS CPFTA-5 5 1
NOTESMARK MFGR MODEL TANK VOLUME...
SHOT FEEDER SCHEDULE
S
T
A
T
E
O
F LO
U
I S
I A
N
A
P
R
O
F
E
S
S
I O
N A
L E
N
G
I N
E
E
R
AMY E. HADLOW
AHU-1
(EXISTING)
3"
GAS
LINE
M101
CH-1
TU-2
(EXISTING)
TU-3
(EXISTING)
TU-4
(EXISTING)
TU-5
(EXISTING)
TU-6
(EXISTING)
TU-7
(EXISTING)
TU-8
(EXISTING)
TU-1
(EXISTING)
3" GAS
(EXISTING)
3" H W
R
(E
XIS
TIN
G
3" H W
S
(E
XIS
TIN
G
H W
S (E
X
IS
T
IN
G
H W
R (E
X
IS
T
IN
G
3" GAS
(EXISTING)
3" CWR 3" CWS
/1 M503
/5 M503
/1 M501
/5 M501
M504
M503
PANEL A
PANEL A-1
PANEL MD
PANEL MS
HVAC
CONTROL
PANELS
120 GPM CHW
12.2 GPM HW
2.5 GPM
2.5 GPM
2.5 GPM
5 GPM
5 GPM
5 GPM
1 GPM
2.5 GPM
CRAFTS
EXHIBITS
RECEPTION
PORCH
ENTRY
LOBBY
PRESENTATIONS
OFFICE MEN
WOMEN
KITCHEN
MULTI-PURPOSE
INFORMATION
15 15
/3 M501
/2 M501 /6 M501
/1 M502
M504
M501
M503
/1 M502
/7 M501
/7 M501
/4 M501
/4 M501
BT-1
ET-2
B-1
ET-1
HWP-1
HWP-2
3" CWR
3" CWS
2" HWR
2" HWS
AS-2
AS-1
3" GAS
(EXISTING)
3" DCW
1"
3" CWS
H W
S
3" FP
C W
R
C W
S
/1 M503
M504
M503
M504
M504
CF-2
CF-1
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
LOCATION WITHIN PARK
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
/1
/2
:1
:4
P M
MECHANICAL PLAN - NEW
WORKM101
P. GORDY
P. GORDY
M. JOHNSON
4 9
PRAIRIE ACADIAN CULTURAL BUILDING XX
XXXXXX
303852B
JEAN LAFITTE NATIONAL HISTORIC PARK2021/02/12
SCALE
8 0 8 16
SCALE OF FEET
A
B L D
G
SCALE AM101
1 MECHANICAL PLAN - NEW WORK
SCALE
SCALE OF FEET
2 0 2 4 B
SCALE BM101
2 MECHANICAL PLAN - NEW WORK - ENLARGED VIEW
FLOOR PLAN KEYNOTES
1 CONNECT EXISTING GAS LINE TO NEW BOILER.
2 EXISTING RPZA. SEE DETAIL FOR EXISTING RPZA LOCATION
3 NEW AIR COOLED CHILLER. CONTRACTOR TO FILL HOLE FROM TREE
REMOVAL AND COMPACT BEFORE INSTALLATION OF PAD. SEE DETAIL
4 NEW GAS METER. UTILITY COMPANY TO FURNISH AND INSTALL.
5 RECONNECT TO EXISTING WATER SUPPLY PUMPS. SEE DETAIL
FOR INSTALLATION. REUSE EXISTING CONCRETE PAD.
6 EXISTING 6" FIRE WATER RISER. SHOWN FOR COORDINATION PURPOSES
ONLY.
9 NEW 6" CONCRETE PAD FOR CHILLER. SEE DETAIL
11 POUR NEW 6" CONCRETE PAD FOR NEW BUFFER TANK, 6" LARGER THAN
TANK
12 INSTALL NEW BOILER ON EXISTING CONCRETE PAD. ROUTE NEW LISTED
AND RATED 4" COMBUSTION AIR AND EXHAUST PENETRATIONS THROUGH
ROOF. SEE WRITTEN SPECIFICATIONS FOR ADDITIONAL VENT AND INTAKE
DETAILS AND MATERIALS. FLASH, COUNTERFLASH, AND SEAL
WATERTIGHT ACCORDING TO VENT MANUFACTURER'S INSTRUCTIONS
AND WRITTEN SPECIFICATIONS.
13 NEW PUMP VFD MOUNTED ABOVE EXISTING DISCONNECT.
14 CUT NEW OPENINGS IN SIDE OF EXISTING SHEET METAL LEAN-TO
SERVICE HOUSING TO ACCOMMODATE NEW CHILLED WATER PIPING AND
INSULATION. HOLES SHALL BE CUT TO ALLOW NOT MORE THAN 1/2" GAP
AROUND FINISHED INSULATION. ROUTE INSULATION CONTINUOUSLY
THROUGH PENETRATION. PROVIDE ESCUTCHEON PLATES TO COVER
PENETRATIONS, AND SEAL WATERTIGHT WITH EXTERIOR-GRADE
UV-RESISTANT CAULK.
15 NEW CHILLED WATER SUPPLY AND RETURN. REUSE EXISTING PIPE
HANGERS.
X
ELECTRICAL FLOOR PLAN KEYNOTES
E1 AIR COOLED CHILLER TO REUSE EXISTING 225-AMP BREAKER IN EXISTING
PANEL MP. BRANCH CIRCUIT: (3) #4/0, (1) #4GND IN 2-1/2" EMT CONDUIT.
E2 NEW 400A/3P DISCONNECT WITH 225A FUSES, NEMA 4X RATED HOUSING
MOUNTED TO EXTERIOR OF CHILLER UNIT AS DIRECTED BY
MANUFACTURER. DO NOT COVER UNIT TAGS OR ACCESS PANELS WITH
DISCONNECT HOUSING.
E3 NEW BREAKER AND POWER FEEDER TO NEW 120V SERVICE RECEPTACLE
AT NEW AIR-COOLED CHILLER. BRANCH CIRCUIT: (2) #12, (1) #12 GND IN
1/2" EMT CONDUIT.
E4 NEW 120V/1P SERVICE RECEPTACLE MOUNTED ON UNISTRUT OR TO
EXTERIOR OF CHILLER UNIT AS DIRECTED BY MANUFACTURER. DO NOT
COVER UNIT TAGS OR ACCESS PANELS WITH DISCONNECT HOUSING.
E5 ROUTE NEW CONDUIT DOWN THROUGH EXISTING CHASE AND
PENETRATE THROUGH EXTERIOR WALL NOT MORE THAN 36" A.F.G. AND
NOT LESS THAN 24" A.F.G. INSIDE EXISTING LEAN-TO SERVICE HOUSING.
SEAL EXTERIOR PENETRATIONS WATERTIGHT WITH UV-RESISTANT
EXTERIOR-GRADE CAULK.
E6 CUT NEW OPENINGS IN SIDE OF EXISTING SHEET METAL LEAN-TO
SERVICE HOUSING TO ACCOMMODATE NEW CONDUIT. HOLES SHALL BE
CUT TO ALLOW NOT MORE THAN 1/2" GAP AROUND CONDUIT. PROVIDE
ESCUTCHEON PLATES TO COVER CONDUIT PENETRATIONS.
E1
E2
E3
E4
E5
E6
X
S
T
A
T
E
O
F LO
U
I S
I A
N
A
P
R
O
F
E
S
S
I O
N A
L E
N
G
I N
E
E
R
AMY E. HADLOW
SUCTION AND DISCHARGE
PIPING, FULL SIZE OF
CONNECTING PIPING
TRIPLE DUTY VALVE
PRESSURE
GAUGE, SIPHONS
AND COCKS
OSHA-
APPROVED
COUPLING
GUARD
STRUCTURAL STEEL OR CAST
IRON BASE, GROUTED TO
CONCRETE PAD
CONCRETE PAD.
FLEXIBLE PIPE
CONNECTOR -
TYPICAL
SUCTION DIFFUSER
USE REDUCERS AS
REQUIRED AT PUMP
CONNECTIONS.
TERMINATE
SLEEVE FLUSH
WITH FINISHED
WALL SURFACES.
SEAL OR CAULK
SLEEVES THRU
FIRE WALLS IN A
SMOKE TIGHT
MANNER.
PIPE AND
INSULATION TO BE
CENTERED IN
SLEEVE - DO NOT
SUPPORT PIPE
FROM SLEEVE
CONCEALED
PIPING
PIPING
EXPOSED TO
VIEW
FINISHED WALL SURFACE
FINISHED
ESCUTCHEON PLATE
FLUSH AGAINST
WALL AND OF SIZE
TO COMPLETELY
COVER OPENING.
PIPE SLEEVE OF
SIZE TO PASS PIPE
AND INSULATION.
SEE SPECIFICATION
FOR MATERIALS
INTERIOR WALLS
PIPING FROM
STREET MAIN. SEE
CIVIL DRAWINGS
FOR DETAILS
LOW-PRESSURE
SUPPLY TO BUILDING.
SEE NATURAL GAS
PLAN FOR
CONTINUATION.
NOTICE:
THE GAS SERVICE ASSEMBLY SHOWN IS FOR
PLANNING AND COORDINATION PURPOSES ONLY.
FINAL NATURAL GAS SERVICE ASSEMBLY DESIGN TO
BE COMPLETED BY UTILITY SERVICE PROVIDER.
GAS
SERVICE
METER
FURNISH AND
INSTALL NEW
CONCRETE
METER BASE.
MIN. 4,000 PSI
CONCRETE.
3/4" FULL FLOW
ISOLATION VALVE
3/4" BYPASS
LINE
3/4" LIQUID-FILLED
PRESSURE
GAUGES
3/4" FULL FLOW
ISOLATION VALVE NEW 3/4" STRAINER
NEW 3/4" FULL FLOW
ISOLATION VALVE
3/4" PRV WITH BUILT IN THERMAL
EXPANSION BYPASS. MODEL: WATTS
LF25AUB-Z3 LEAD-FREE
SET ALL PRVS TO NO
MORE THAN 10 PSI.
EQUIPMENT. COORDINATE
DIMENSIONS WITH MFGR.
TYP. ALL SIDES
6" MIN TO NEAREST
EDGE OF EQUIPMENT
#5 REBAR @ 12"
O.C. EACH WAY
(TYP.)
CHAMFER EDGES
3/4". TYP.
4000 PSI CONCRETE
AT 28 DAYS
COMPACTED
EARTH
FINISHED GRADE
M
IN
W.W.F. 6x6- W4xW4
MIN. 1" CLEAR OVER
WELDED WIRE FABRIC
APPLICATION NOTES:
1. Concrete pad reinforcing shall meet all applicable ACI standards for minimum area and concrete coverage.
2. High concentrated loads or point-supported equipment require special considerations not provided by this detail.
EQUIPMENT RAIL WITH
ANTI-VIBRATION
SUPPORTS (SEE DETAIL)
STONE BASE: MIN.
4" OF #57 GRAVEL
MIN.18"
8" THK.
1'-0"
MIN.
1/4" COPPER TO FLOOR
DRAIN
AUTOMATIC AIR VENT
1/2" GATE VALVE
CONCENTRIC REDUCER
DIRECTION OF FLOW
MAINS
SERVICE TEE
OR WELDOLET
1/2" CLOSE
NIPPLE
1/8" MPT X 1/4" FLARE ELL
MAINTAIN MINIMUM 4" SEPARATION
FROM OUTSIDE OF PIPE INSULATION
SPECIFIED PIPE INSULATION. CONTINUE
INSULATION OVER SUPPORT SADDLES
CHILLED WATER PIPING
HEIGHT AS
REQUIRED
SUPPORT SADDLES FABRICATED FROM 1/4" THICK
STEEL PLATES, WELDED TO PIPE COLUMNS
MINIMUM 2" DIA PIPE
COLUMNS
SECURE BOTTOM OF PIPE COLUMNS TO
CONCRETE PAD USING EXPANSION ANCHORS
6" HIGH
CONCRETE PAD.
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
LOCATION WITHIN PARK
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
/1
/2
:3
:3
P M
DETAILSM501
P. GORDY
P. GORDY
M. JOHNSON
5 9
PRAIRIE ACADIAN CULTURAL BUILDING XX
XXXXXX
303852B
JEAN LAFITTE NATIONAL HISTORIC PARK2021/02/12
NOT TO SCALEM501
1 BASE-MOUNTED PUMP DETAIL
NOT TO SCALEM501
2 PIPE SLEEVE THRU WALL
NOT TO SCALEM501
3 GAS SERVICE MAIN EXAMPLE DETAIL
NOT TO SCALEM501
4 NEW CHILLER AND BOILER PRV WITH BYPASS
NOT TO SCALEM501
5 EQUIPMENT PAD DETAIL
NOT TO SCALEM501
7 AUTOMATIC AIR VENT DETAIL
NOT TO SCALEM501
6 PIPE SUPPORT DETAIL
S
T
A
T
E
O
F LO
U
I S
I A
N
A
P
R
O
F
E
S
S
I O
N A
L E
N
G
I N
E
E
R
AMY E. HADLOW
FUNNEL FOR ADDING CHEMICALS
FROM PUMP SUCTION
FROM PUMP DISCHARGE5-GALLON CHEMICAL POT FEEDER
SUPPORT STAND
4" HIGH
CONCRETE PAD
TO FLOOR DRAIN
1"
1"
1"
MANUAL AIR VENT
AUTOMATIC AIR VENT
CWR
CWS
BALL VALVE - TYPICAL
3 WAY CONTROL VALVE
PIPE UNION - TYPICAL
3/4" DRAIN VALVE WITH HOSE CONNECTION
PRESSURE/TEMPERATURE TEST PLUG TYPICAL
AIR HANDLING UNIT
CHILLED WATER COIL
AAV
STRAINER INSTALLED WITHIN
5 FEET OF COIL INLET
BALANCING VALVE
AI - DISCHARGE AIR TEMP.
T
DASA
AO - ZONE DAMPER
M
AI - AIRFLOW
BI - ZONE OVERRIDE
AI - ZONE TEMP.
AI - ZONE SETPOINT ADJUST
T
AO - REHEAT VALVE
M
3-WAY MODULATION VALVE
EXISTING TERMINAL UNIT COILS AND CONTROLS:
SHOWN FOR REFERENCE, AND FOR T&B SERVICES ONLY
MANUAL AIR VENT
AUTOMATIC AIR VENT
HWR
HWS
BALL VALVE - TYPICAL
TWO-WAY, MODULATING CONTROL
VALVE WITH ELECTRONIC
ACTUATOR
PIPE UNION - TYPICAL
3/4" DRAIN VALVE WITH HOSE CONNECTION
PRESSURE/TEMPERATURE TEST PLUG TYPICAL
AIR HANDLING UNIT
HOT WATER COIL
AAV
STRAINER INSTALLED WITHIN
5 FEET OF COIL INLET
T FS
BI - CHILLED WATER FLOW SWITCH
T
A1 - CHILLED WATER RETURN TEMP.
VFD
VFD
BI - CHP 1 STATUS
BO - CHP 1 START / STOP
CT
AO - CHP 1 VFD SPEED
BI - CHP 1 VFD FAULT
M
BI - CHP 2 STATUS
BO - CHP 2 START / STOP
AO - CHP 2 VFD SPEED
BI - CHP 2 VFD FAULT
CT
M
CWR
CHILLER
AO - CHILLED WATER SUPPLY TEMP. SETPOINT RESET
BO - CHILLER ENABLE
BI - CHILLER STATUS
AI - CHILLED WATER SUPPLY TEMP.
CWS
CHP 1
CHP 2
AI - PRIMARY HHWS TEMP.
T
AI - PRIMARY HHWR TEMP.
T
BO - BOILER ENABLE
BO - BOILER STATUS
BO - BOILER ALARM STATUS
BO - LOW WATER LEVEL
CT
BI - HWP 2 STATS
BI - HWP 1 STATS
CT
M
M
HWS
HWR
BOILER
AI
PUMP DIFF.
PRESS.
AI
AI AI
PUMP DIFF.
PRESS.
HWP 2
HWP 1
VFD
BO - HWP 1 START / STOP
AO - HWP 1 VFD SPEED
BI - HWP 1 VFD FAULT
VFD
BO - HWP 2 START / STOP
AO - HWP 2 VFD SPEED
BI - HWP 2 VFD FAULT
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
LOCATION WITHIN PARK
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
/1
/2
:3
:3
P M
DETAILSM502
P. GORDY
P. GORDY
M. JOHNSON
6 9
PRAIRIE ACADIAN CULTURAL BUILDING XX
XXXXXX
303852B
JEAN LAFITTE NATIONAL HISTORIC PARK2021/02/12
NOT TO SCALEM502
1 CHEMICAL POT FEEDER DETAIL
NOT TO SCALEM502
2 CHILLED WATER COIL PIPING - AHU-1
NOT TO SCALEM502
4 EXISTING TERMINAL UNIT CONTROLS
NOT TO SCALEM502
3 HOT WATER COIL PIPING - AHU-1
NOT TO SCALEM502
5 AIR COOLED CHILLER AND PUMPS CONTROL DIAGRAM
NOT TO SCALEM502
6 BOILER AND PUMPS CONTROL DIAGRAM
S
T
A
T
E
O
F LO
U
I S
I A
N
A
P
R
O
F
E
S
S
I O
N A
L E
N
G
I N
E
E
R
AMY E. HADLOW
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
LOCATION WITHIN PARK
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
/1
/2
:1
:2
P M
DETAILSM503
P. GORDY
P. GORDY
M. JOHNSON
7 9
PRAIRIE ACADIAN CULTURAL BUILDING XX
XXXXXX
303852B
JEAN LAFITTE NATIONAL HISTORIC PARK2021/02/12
M503
1 RPZA EXISTING CONDITION
M503
2 CONTROLS/ BMS PANEL
M503
3 EXISTING DCW METER
M503
4 EXISTING PIPING EXTERIOR
M503
5 EXISTING TREE
EXTERIOR
CHASE
EXISTING WATER METER WITHIN
VAULT SHOWN TO LEFT
EXISTING TREE IN PROPOSED
CHILLER LOCATION
EXISTING PIPING WITHIN
EXTERIOR CHASE
EXISTING RPZA TO REMAIN
S
T
A
T
E
O
F LO
U
I S
I A
N
A
P
R
O
F
E
S
S
I O
N A
L E
N
G
I N
E
E
R
AMY E. HADLOW
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
LOCATION WITHIN PARK
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
/1
/2
:1
:3
P M
DETAILSM504
P. GORDY
P. GORDY
M. JOHNSON
8 9
PRAIRIE ACADIAN CULTURAL BUILDING XX
XXXXXX
303852B
JEAN LAFITTE NATIONAL HISTORIC PARK2021/02/12
M504
1 EXISTING VRF HEAT PUMP
M504
2 IRON PIPE SUPPORT
M504
3 PANEL A1
M504
4 PUMP DISCONNECT CHW
M504
5 PUMP DISCONNECT HHW
M504
6 PUMP PANEL
M504
7 SWITCHGEAR
REUSE EXISTING ANGLE
IRON PIPING SUPPORTS
FOR NEW PIPING
HHW PUMP DISCONNECTS
(2) BEHIND PIPING
SWITCHGEAR
S
T
A
T
E
O
F LO
U
I S
I A
N
A
P
R
O
F
E
S
S
I O
N A
L E
N
G
I N
E
E
R
AMY E. HADLOW
AS-2
B-1
ET-1
AS-1
DP
HWS
HWR
CWR
CWS
ET-2
CH-1
CHP-1 CHP-2
BT-1
HWP-1
HWP-2
DP DP DP
DP
DP
DP DP
M
HWR
HWR
HWS
HWS
DCW
D C
W
M
CF-1
DCW FROM
MAIN
AHU-1 (EXISTING)
HWS
HWR
CWS
CWR
/1 M503
/4 M501
CF-2
LEGEND: FLOW DIAGRAM
SYMBOL
DESCRIPTION
Anchor, main
Butterfly Valve
Pressure gauge and cock
PS Pressure switch
Thermometer
Control Valve, 3-Way
Union
Reducer
Flexible Connection
Thermometer well, only
Flow Meter
Check Valve
Triple Duty Valve
DP
DP Differential Pressure Switch
Pressure Reducing Valve
M Motorized Two-Way Valve
Strainer
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
LOCATION WITHIN PARK
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
/1
/2
:1
:4
P M
DIAGRAMSM601
P. GORDY
P. GORDY
M. JOHNSON
9 9
PRAIRIE ACADIAN CULTURAL BUILDING XX
XXXXXX
303852B
JEAN LAFITTE NATIONAL HISTORIC PARK2021/02/12
M601
1 WATER PIPING FLOW DIAGRAM
PIPING PLAN KEYNOTES
2 EXISTING RPZA. SEE DETAIL FOR EXISTING RPZA
LOCATION
7 ROUTE AIR SEPARATOR DRAIN TO NEAREST FLOOR
DRAIN AS SHOWN ON DRAWINGS
10 HEATING HOT WATER SUPPLY AND RETURN TO EXISTING
VAV BOXES. HOT WATER CONTROLLED WITH 3-WAY
VALVE.
15 NEW CHILLED WATER SUPPLY AND RETURN. REUSE
EXISTING PIPE HANGERS.
X
S
T
A
T
E
O
F LO
U
I S
I A
N
A
P
R
O
F
E
S
S
I O
N A
L E
N
G
I N
E
E
R
AMY E. HADLOW
| G001 - COVER SHEET (IF NEEDED) |
| MD101 - MECHANICAL PLAN - DEMOLITION |
| M101 - MECHANICAL PLAN - NEW WORK |
| M503 - DETAILS |
| M504 - DETAILS |
| M601 - DIAGRAMS |
File details come from the government source that posted it. Updated .